PP - 1090 SOUTHCENTER MALL - FOOTLOCKER - PERMITS AND PLANS
1090 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-105 06-F-246 06-F-234 10-S-104 06-S-201 • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Foot Locker 1090 Southcenter Mall Permit No.: 10-S-104 Date: June 7, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition 1;o the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. FELE Po Box 3932 Seattle WA 98124-3932 206-2344700 RreComNW,LLC Battery Calculation Work Sheet Project: Foot Locker Store #7010 Fire Alarm System Project Southcenter Mall Space 340 Tukwila WA 98188 This project consists of installing a new addressable fire alarm system. The building is fully sprinklered. This worksheet is for the new fire alarm control panel and the connected devices. Qty Part # and description Supervised Current mA Alarm Current mA 1 5700 Silent Knight FACP 160 330 1 SD505-APS Add smoke det 0.55 0.55 2 SD5O5-ADHR Add duct det 1.1 1.1 1 GEC3 Horn strobes - wall mount 0 164 3 GES3 Strobes — wall mount 0 165 4 GCC Horn strobes — ceiling mount 0 1532 Subtotal 162 2193 Total battery power hours x24 x.083 Subtotal 3888 182 Safety factor - 10% +389 + 18 Total 4277 ma 200 ma Total Current Required 4477 ma or 4.5 amps Battery size used: 2ea - 12volt, 7amp c � PAID NOV -8 20060U 1 Vr SHEET \UMBE SH TITL_ SHEET INDEX FA -01 SYSTEM I\FO RMATIO\ FA -02 TYDICAL =TAILS - WRING A\D MOU\TING FA -03 SYST v CALC U LATI O \ S r G _ \EAL), RIS =A-04 FIR -71 ALARM SYSTEM FLOOR D LA\ CC Without Comments 0 As Noted in Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire ^revention Bureau for conformance with current City •:.andards. Acceptance is subject to errors and i.irnissIons which do not authorize violations of adopted -andards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Ariditions, deletions or revisions to these drawings after this date will void this acceptance and wili'require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by Tne Tukwila Fire Prevention Bureau. Date:-�-�� By: S�� ft"WtLA FIRE DEPARTMilita Please call: 5754407 and give this job / az.,.i l!;act address for shut. euwo or restoration aaarove! NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing, WIRE DESIGNATION SCHEDULE WIR SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO 1416 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 1414 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 1 REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO 4416 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V X12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" - .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL • CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NEPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: W -ERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUN AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. D 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS .(E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CO\IDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEN BLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAIvAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 2 5 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL XLS SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ANN FIRE ALARM REMOTE ANNUNCIATOR SSD -C SIEMENS PROVIDED 66" A.F.F. TO TOP IA SMOKE DETECTOR (PHOTOELECTRIC) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING ®D DUCT SMOKE DETECTOR AD2-2P SIEMENS HFP-11 DET DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (PHOTOELECTRIC) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP BOX VERIFY IN FIELD [3G FIRE ALARM HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM HORN STROBE ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM FIRE ALARM STROBE ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM n MANUAL PULL STATION HMS -S SIEMENS 4S BOX W/ 1G RING 48" 0.0. AFF TO BOTTOM FIRE ALARM HORN STROBE WP (WEATHERPROOF) AS -75 -R -WP SIEMENS WBB-R 4S BOX VERIFY W/ 2G RING IN FIELD WP FIRE ALARM BELL (WEATHERPROOF) MBDC-10 SIEMENS WPBBS-R VERIFY IN FIELD 0 WATERFL❑W SWITCH N/A N/A N/A N/A O TAMPER SWITCH N/A N/A N/A N/A FATC EX JUNCTION BOX F.B,❑, F,B,❑, N/A VERIFY IN FIELD A.F,F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F,B4O, FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAID JUN - 7 2010 TUKWILA FIRE s� *so Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 6/03/10 0 0 z W Fan J(1).} (S.-CALE: 1'=1/8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/1 0 BACKROUND PLAN PROVIDED BY: sl.OB NUMBER: SHEET FA -01 } THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCT OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. BEND OR OTHER OBSTRUCTION DUCT DETECTOR LOCATION TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE 120VAC-60HZ DEDICATED EMERGENCY NOTE FOR ADDITIONAL 9'ECI 1CATIONS SEE PRODUCT DOCUMENTATION. MODULE 2RONS ® SUPERVISORY POINT ® FORM "C- RELAY CONTACTS LED *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC ISOLBATE FROMSG DING TO NEXT ADDRESSABLE DEVICE STOP IF LAST -CI' DEVICE FROM XLS CONTROL. PANEL-(+ OR PREVIOUS ADDRESSABLE DEVICE O GROUND Ir 4, MODEL: HTRI-R MOUNTING HODS FOR SNITCH PLATE MOUNTING SLOTS FOR DOUBLE GANG SNATCH BOX MOUNTING STATS (—) FOR 4 INCH SIMTCH BOX FROM EXISTING STROBE -- -- CIRCUIT OR PADS NOTE SEEPDCTADCES ADDITIONAL �Q 0 PAD -3 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — FEED TYPICAL WIRING FOR HTRI-R MODULE (PAD -3 TRIP) SCALE: NONE JUNCTION BOX MOUNTED ON CEILING FLEX .•,.rig';t�!iY�,'✓,.cr��Jy�.:ti��`�GYC'.•'l!�v:,.r.^.J�*vl: yt. ;,y.�.,�...\ ^"CZN�,a,n vXlv�:✓n; . , JUNCTION BOX MOUNTED AGAINS CEILING SUPPORT 0 0 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TO BATTERY n_ TUBE OUTLET SAMPLING TUBE INLET SAMPLING TYPICAL MOUNTING FOR AD -2P DUCT DETECTOR SCALE:NONE 48' HORNISTROBE FROM PRECEDING STROBE APPLIANCE OR SYNC MODULE tt NAC -4 NAC -3 NAC -2 ),10 0 OTO NEXT DEVICE SMOKE DETECTOR syr JUNCTION BOX MOUNTED ON CEILING FLEX �rw • rrrr SUSPENDED ILLUMINATED CEILING JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING NAC -1 11 11 0 0 WARNING. 0 0 ° TO PREVENT ELECTRIC SHOCK, DO NOT REMOVV IS COVER. NO USER SERVICEABLE PARTS INSI (+) TB UD 0 0 C3� AT LEAST SIX DUCT WIDTHS FROM BEND STROBE 0 0 __a ❑ 1;( O c DESCRIPTION n s1 I. CII O 11 b r w 4 - Ase[oaroM .. Irl.11...4;!& \ z «<<< R,- OWE 001 ♦ � ✓ STROBE CIRCUI Q (-) (+) I I SPEAKERISTROBE AND STROBE WIRING SCALE:112":1' (-) �1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA,TO 100' F (TINGG TEMPERATURE: ) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE f DATA IN ( )> /----)s- l DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE HORNISTROBE STROBE CIRCUIT 11 4,1 0 WARNINGS I 0 �✓G TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE 31IS COVER. NO USER SERVICEABLE PARTS INSIE (+) CEILING 6" IN. AS -75 WEATHERPROOF STROBE OR HORN T 90" A.F.F. WBB-R WEATHER PROOF BACKBOX 4S DEEP BOX W/ 2 GANG RING A TB UD 4 (-) STROBE 1 11' 11 (,CIRCUIT (+) WBB-R WEATHER PROOF BACKBOX ZH-MC HORN STROBE �-1 I R E 80" A.F.F. SEE NOTE #1 HMS -S MANUAL PULL c' STATION I I 048"O.C. AFFi- --_1 SII 4 i I "10 I WP -1 WEATHER PROOF BACKBOX 4" SQUARE DEEP •1 BACK BOX WITH 1G TRIM RING EXTERIOR HORNISTROBE & MANUAL STATION ELEVATION SCALE:NONE (—)TO NEXT APPLIANCE S OR END OR LINE RESISTOR i, (+) S 24K (EOLR) 24K 1/2W TO NEXT (-) ADDRESSABLE I (+) > DEVICE > (+) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. FRONT VIEW 470 OHMS EEOL (+) WITCH INPUI� (+�t t ) c DESCRIPTION n ) (.____D LTJ Q C3 O o L0 T�M-1 \ z «<<< (-) TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPLIFPLR RED (JACKET) *CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 _(+)TO NEXT DEVICE OR } (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECHIELEC. HARD LID CEILING CADDY SUPPORT BRACKET' CEILING TILE o 4" SQUARE DEEP BOX CEILING STROBE CEILING MOUNTED HORNISTROBE MOUNTING (DROP CEILING) SCALE:NONE SUPPORT BRIDGE ti c0 Cr 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Z a DESCRIPTION SHOP DRAWINGS LTJ Q C3 O o L0 z «<<< co >,OO W CC mZ w � 3F—O O ac v z = cn 1-3 pm%'' w 0 V CC (/) O� `/CALF: 1'=1 /8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/1 0 BACKROUND PLAN PROVIDED BY: \OB NUMBER: } /r SHEET 2006 byGuardian SecuritySystems, Inc. All Rights Reserved F" '-O2 ,/ Copyright Y Notification Appliance Circuit Detail PROJECT:1FOOT LOCKER , Panel:IXLS-V I ; Wire Resistance 1.62 Date: June 3, 2010 CURRENT TOTAL=13493.00 ":-;g:-e.i0OATA Ari.',14'2AAVIP • 1$4 0 1ZH-MC-C @15CD 87.5 0 i o ZH-MC-C ©30CD 131 0 2 IZI-1-MC-C @75CD 222 444 3 al -MC -C @95CD 292 876 0 I ZR -MC @110CD 259 01 -.•'''' 2 ' ..1 71:4-iyic1.5a D - :. . :: , .:: :_..:..-:,-a4 ,:,-.::,....-,::-, _, --113::-.:,-,:.-,.:_.:_,.:, .., 981 • ' I 0 IZR-MC @30CD 01 i . . . .. . . . -.. . ..„ , .. (:' : ' - ' . ''''Zf'-,N1 C@7.5CD.,•:' =':. .'''.. -. - ', . • -'-',.:17$ .. • --'..'::'-'.'E -'-:'..-1,-': --.-'0:, ,.-.:,-1' '-'' . '.'-- . • '•-'.".- .-."' . - -=1.'.' •..,, - ':- '-:-' '.- .,-. ':'. , - . '.;•-:', E. '2:1:: -:•:"': ,-f -- '.,'„ '1 E'--- - '- , - - - --•i - - - .... .... . .--.--, -... ..: ... - - :-. ....-, -..-: • .: ..-..... - ...-., • „,. : ..„. . ..-- . -.. .... .. -- ... , . .- • .....-.-.- .. .--- . . DEVICES=17 TOTAL mA= I 14481 12 1 1 14 1 , 23.47! 1448 0.37 ; Total Wire Resistance ( R ) ( WL * 2 )* (Rift) I Total Device Load, Amps (1) I ' Cct Load 1.45' 0.53 Eot. Voltage !Voltage DroP ( E ) „ „ 24 2147 (E= I * VOLTAGE DROP CALCULATION EOL—S1 SYSTEM CALCULATIONS S1-7 s S1-6 s S1-5 s S1-4 S1-3 S1-2 S1 -1s Device Type Qty Amps Total Amps Total Main System Board 0.03 0.030 ZH-MC-C ©15CD 0.0875 ZH-NIC-C @30CD 0.131 Tii-MC-C ©75CD 2 • 0.222 ZH-MC-C @95CD 3 0.292 ZWIVIC-C @1 OCD •- „ 0.269 ZR -MC @15CD 2 0.064 0.128 ZR- C ©30CD 0.098 ZR -MC @75CD 0.2 Amps 0.128 'kips StandbY:CtirrentlOad,:: Amps For24 HOurs Amp -hours AliniCurretit-load;' 0.128 Amps Fo..5 Mititites 011 Amp -hours 25% Derating: 0.013 Amp -hours DEDICATED EMERGENCY POWER 120VAC-60HZ RISER DIAGRAM Current Load: Device Type HFP 11 Qty Amps 0 0.0022 tandby: Alarm: Total Amps 0.0022 0.0023 Total 0.0,00 AD2-P HTR -R HTRI-D . - Standby Current Load: Alarm Current Load: 1 0.0635 1 0 009600 0 0.001600 0.0731 Amps 0.085 Amps Total System Current Load: Battery Pair to be Used12VDC 0.0635 0.064 0.0096 - 0 0.021 0.0035 0.0731 Amps For 24 Hours = ';• For 15 Minute 1.754 0.064 0 021 0.000 0.085 Amps Amp -hours 0.021 Amp -hours 25% Derating= 2.220 Amp -hours 2.220 Amp -hours Amp -hours BATTERY SIZING CALCULATION 7AH OD FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS 1 DATE 6/03/10 2 <<<<< 03 03 CI (70. CCO) W 2 m z 111 cc 0 W u) E"'" Z Z Li 2 w cc (/) ‹c < I— —I < LL.I 0 0 EC (1) 0 (S-CALE: 1 '= 1 /8" -*\ DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/10 BACKROUND PLAN PROVIDED BY: NUMBER: SHEET FA -03 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved HOME RUN TO— BPS ti ei x 1-13 TRI -R EX X 1-14 i S. I S1-3 HUI—FRI) 1 s1- •.•.7,n Ss4'r::c.i::'1a'�i 2'".9'ii< `i'i�Ia''i'.. "`aa'-. S•fi:Xis2'-.x41iS�Yi`::..:. Y.'Y,zc::F'::::;:i':sY'aa iSY:i:iv: ::a Yta�:. x 0 0 X x x X 0 0 X 0 0 X 0 0 x 0 X X 0 0 NORTH FOOT LOCKER SCALE 118"=1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE THESE DEVICES. Ll›- FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. TENANT FIRE ALARM JUNCTION BOX (FIELD LOCATE) EXISTING CORE AND SHELL FIRE SMOKE DAMPERS RELAY TRIPS TO ACIVATE AND MONITORS PAD 3 > TIE TO EXISTING DEVICE TIE TO CLOSES EXISTING -- SPEAKER STROBE 10 RELOCATE EXISTING DEVICE ® TIE TO EXISTING EOL V>. REPLACE WITH 15CD SPEAKER STROBE FIELD LOCATE HVAC UNITS SMOKE MUST BE LOCATTED IN THE SAME ROOM AS THE POWER SUPPLY. 1›- REFFER TO RISER ON PAGE FA -03 FOR VOICE/SPEAKER WIRING ELECTRICAL/INSTALLING CONTRACTOR SHALL RETURN ONE FULL SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. RELEASE/REVISIONS 5.1 m Lu Z DESCRIPTION SHOP DRAWINGS 0 1- < o ' M O (0 z \\<\\ r .co OG CC Of.l w z W° co 0 Coo W— cc o(f) Ca W0 CC Cr) of w(f)CC WCCEr. DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/10 BACKROUND PLAN PROVIDED BY: JOB NUMBER: ( FA -04 SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved \112206—redline\Redline Projects 2006\FCNW\Foot Locker — S. Ctr\Codd\FA-1—Foot Locker dwg FIRST FLOOR FACP TO 120 VAC UNSWITCHED ,' DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISER DIAGRAM SCALE: NONE GENERAL NOTES: 1. ALL WORK 18 TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD 18 TO BE OPEN CABLING EXCEPT WHERE IT 18 EXPOSED AND BELOW SEVEN FEET - THEN IT 18 TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED. 4. ALL INDOOR HORN$, STROBES, HORN STROBES, AND MINI HORN STROBES ARE TO BE MOUNTED 80" ABOVE THE FLOOR OR 8' BELOW THE CE1UNG, WHICHEVER 18 LOWER. 8. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING: A) 38' INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER 8) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASES. EQUIPMENT LEGEND DEVICE SYMBOL QUANTITY PART NUNNBER DESCRIPTION BACKBOX 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE FIRE ALARM CONTROL PANEL INCLUDED SMOKE DETECTOR 4 SQUARE X 1-7/8" DEEP HORN STROBE 4 SQUARE X 1-7/8" DEEP HORN STROBE - CEILING MOUNT 4 SQUARE X 1-7/8" DEEP GESS STROBE 4 SQUARE X 1-7/8" DEEP SD505ACHR DUCT DETECTOR 4 SQUARE X 1-7/8" DEEP WIRE LEGEND TYPE DESCRIPTION 13 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE B 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE C 18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE EOL ) SCALE: 3/32"-i'-0' FIRE ALARM PLAN FIRE COM NW DRAM: CHECKED: 11176 PROJECT NAME CBA FOOT LOCKER 17010 T1 FIRE ALARM PUN APPROVED BY: SCALE N0. DATE REVISOR SY JOB NUMBER: TUKWILA FIRE DEPAlifivialit Please call: 575-440Z and give this job No. 0(0- itgo and exact address for shut. down or restoration approval, A " f#‘ 4114:7 163.,,ex 441* rrlOtd, 4ka Without Comments As Noted In Red Per The Attached Letter s These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violationof adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thacceptance and will require a resubmittal of revised drawings for 5 ubsequent approval. Final acceptance is subject to field teat and inspection by The Tukwila Fire Prevention Bureau. Date: J2jajp.,',.(e_By: ttacglanametaimart......,00makenwaamempig. \Redline Projects 2006\FCNW\Foot Locker — S. Ctr\Cadd\FA-1—Foot Locker.dwg 43 AM DWG: DATE: 11/7/2006 1 OL-(EYISTIN..) I CL -1 • 1I'.O' CFP 1 CL•I a II'.O" 6fr c) -2B • • DD FIRST FLOOR EOL ♦ '• TO 120 VAC UNSWITCHED DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISER DIAGRAM SCALE: NONE GENERAL NOTES: 1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN FEET - THEN IT IS TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED. 4. ALL INDOOR HORNS, STROBES, HORN STROBES, AND MINI HORN STROBES ARE TO BE MOUNTED 80" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER. 6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING: A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASES. ll CL -I • II'.J' C CL•I ♦ p'-(' CFF EQUIPMENT LEGEND DEVICE SYMBOL QUANTITY PART NUNMBER DESCRIPTION BACKBOX 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE 1 5700 FIRE ALARM CONTROL PANEL INCLUDED EG ® 1 SD505APS SMOKE DETECTOR 4 SQUARE X 1-7/8" DEEP 24 1 GEC3 HORN STROBE 4 SQUARE X 1-7/8" DEEP ®4C 4 GCC HORN STROBE - CEILING MOUNT 4 SQUARE X 1-7/8" DEEP 3 GES3 STROBE 4 SQUARE X 1-7/8" DEEP IN 2 SD505ADHR DUCT DETECTOR 4 SQUARE X 1-7/8" DEEP CD WIRE LEGEND TYPE DESCRIPTION A 18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE 6 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE C 18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE I EOL FII E ALA FRMPLAN SCALE: 3/32".1'-0" FIRE COM NWu0 PO Bax 3022 BatW WA 241244332 DATE: 11/7/08 DRAWN: CEA CHEO<ED: JD APPROVED BY: JD 2044344700 PROJECT NAME: FOOT LOCKER #7010 11 Southcenter Mall Space 340 Tukwila, WA 98188 SCALE: 3/32"=1'-0" NO. DATE REVISION BY SHEET IDLE FIRE ALARM PLAN JOB NUMBER: 06-214 FA -1 of/ 1 CCE 7'E Without Comments 0 AsNotedlnRed 0 , Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stanaaras and or-amances. The responsibility for the a.dequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this acceptance and will require a resubmittal -of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /1-1 3 -°5- By: /V --1 % NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. I UKWILA FIRE DEPARTMENT Please call: 575-440Z and give this job No. a� - r- -,.3 `f wade and exact address for shut. down or restoration approval: Design per NFPA 13 — Ordinary Hazard Occupancy —130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means — Relocate Reliable Model G -4A Concealed Sprinkler Heads 165° 1/2 x 1/2 �$ — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ACCEPTE D Without Comments As Noted In Red 04: Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted ~tandards and ordinances. The responsibility for the adequacy of design rests totally with the designer. _ Additions, deletions or revisions to these drawings.after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: (o-7-( 6 By: /v v"''.51 1 \iL;J�17r1111ti1. ft.H(WItA FIRE DEPART Please call: 575.440Z and give this job IVo. '} ^-s- /o Tot address for shut. a0oroval, • CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 . MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 House of Hoops 1090 Southcenter Mali Tukwila, WA PAID MAY 20 2010 TUKWILA FIRE *r&5-3 DATE: /7 DRAWN: d ft, SCALE: 31/ C 44/ II'O"AFF CL L-2 a. l2'-0'J AFF "AFF I03/29/10 1 -2 -- + 4 e II' -6 1 CL -1 L-1 m 12'-0 "AFFOWE) 23'-11 3/8" � � �(6t�L "G 5/8" ID23'-II X'G' GRID EXA—.C.Try. _./., /10 GRID ID49-Id EX 'CQ AC.T. - , _ t c3 - - �iH - rI _i_((� __J f-� lmEQQ(w r FIm-EM/NL t2 I24/12 ;' (TYH P � tYP. •4._ _ E) (E)= GXE I 01(E) TtJCP / C> 1 H 101CL- Q I ,\1vZe/i0CL-I QQ1.---e 1w L1(E.CRP)0 III ..— 1 !_L P2 L P2:71.1.4-- C1w 214 1H2 ,G CRP) 03/2910I5 t CL A Il AFF ] H20i(dHLi H2 -3 -8" 1 Flo \ 3'- 8" 3' O9E)01- (E.) 14 -1(R. 4> L _ J_ _ -L — - 1 - c /I) r.- 1 1 H20) I® I®• ' e O 09/2S 1 I 1 1 VP Ilr 5._9.. / (1:J I -I ' ' (I� t>=$3 �7(R I T -1 (( 13 i P2 G7 P2 O CI P2 E2 NIF P2 Al,0 i�/2 THE.,) Q L H2 (tYP.) 2 (E) (E (E (EJ ---1 ---1--r- 71'(RJ ■■■ I I ■■■ 1 1 © 4_m� �7( li O(1� --T--- 1 T --4 - _ H H'2 ) TYP. 712 [1- - fa3/Za --+----•-+-----NI es`O HI 14 it - © w (TYP.) (T®.: ® -1--_L---- (� ® 1 CL -3 0 9'-3" AFF (TYP. EGI E0 Hr12n� �_ 0 1 ) ( I f2 / F2 -EM F2 F2 -EM — F2 F.2 t ,F2 LflL - ---\i< , -+---- --1 H H2 712 2 X �L(( O NI NI \ / ^� I ® (TYP.) 1 ll(E) 1 8 V / 1e i H �! t^ 2 .412 EZ_ F2 to / 0 -:1(RO N q F2 F2 F2 (I) 1 -1 • I _ __� I H H2 © (TYP.) H2' 2 II 67(R- © Io 7lR1- O() IPO O itak Mit �3-8' �io' 411/ ,r 3'-5. 5'-9" TF(E' (EJ la- H`n''� 2 6to -7(1Q.) �� 1 1111'Irl) •>< 0 X, X Z F2 _ CL-3 e� Il' -8" AR F2 2 -EM UFim� 04/12/10(E) (E% !Fa (E)2 H2 I 14 H2 H2 O -- 0-70Z) 2 ,,.• 2 2 fl.;�.'r Ha. H„ H H "L s03/2r J 1111 EN8 8 I G 1 G1(P) Gi(E) G7(f) Ca(P) t� o a s ' ; o s I I I 4'-e" F � (l) G1fE) TF(E) I ,QipQ Z I TYP. . ill ? r - �-- - _Ter YP. - - -14- - 1-I- -� _ W -EM .L r -1 1 I I I___-_-_-___ _ -- - - - - \ _ 4 _7. +_ _+____= C IA,4 ®4/12/1® A Design per NFPA 13 — Ordinary Hazard Occupancy —130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means — Relocate Reliable Model G -4A Concealed Sprinkler Heads 165° 1/2 x 1/2 �$ — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ACCEPTE D Without Comments As Noted In Red 04: Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted ~tandards and ordinances. The responsibility for the adequacy of design rests totally with the designer. _ Additions, deletions or revisions to these drawings.after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: (o-7-( 6 By: /v v"''.51 1 \iL;J�17r1111ti1. ft.H(WItA FIRE DEPART Please call: 575.440Z and give this job IVo. '} ^-s- /o Tot address for shut. a0oroval, • CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 . MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 House of Hoops 1090 Southcenter Mali Tukwila, WA PAID MAY 20 2010 TUKWILA FIRE *r&5-3 DATE: /7 DRAWN: d ft, SCALE: 31/ C 44/ GL-C-aXISTINr ) CL -I 9 11'-0" AA� i 23'-10" CL -1 s IP -0" Air - X • x X x i x :c x = x thCii -U e Tee -Lox Mechanical r3cal Branc?•T Connector From WARD 23'-10" 151'-2" I = ^== DIMENS ON CLC-. GRID G CLG--. GRID ICL -I o 11•-0• AFr EQ E0x EG I EQ I I ?^-3=3 M=3,07. MAX.�V'��'_�=�.: If :ss 23'-1m" CL -1 s I2'-6" A RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C-CLANP WITH SET SCREW 3/8' ALL THREAD ROD HANGER DETAIL NTS X23'-10" �I? OL trN I i ti - -1 —W — _ S�1 77 77 W - • p I; It 1l QE I !I• w — 1- • O E \ EXISTING CEILING GRID, DCT 4 LIGHT•� FIXTUii TO REMAIN -TEN NT GC TO /\A ACHIEVE AS NE' ESSARY TO ACHIEVE A "LIKE -NEW" -EARANCE tri CHAIN MOUNTED HRIXTURES MOUNTED 2'-0" 430VE TOP • SHELF (TYP.) CEILING OPEN TO DECK SPRINKLER PIPING PLAN 3/16"= 1' r e e II oq �.�I f I _ BANNER TRACK SYSTEM (SEE DETAIL BELOW) 0 nin 117-1_1 I I ©° Nu I.=.1 _n I 1 t1 O`0 I1 4 N ..1 1 3 E EO „L-iCL-1 g 11'-0' AFr CLC.GRID • N • Design per NFPA 13, Ordinary Hazard II, 130 Sq. Feet Max All materials to be new, U.L. listed, and F.M. approved Existing Storefront 6 — Relocate Reliable G4A 165° concealed pendents 1/2 x 1/2 N L 2 9 11'-11 I/4" J i Sales Floor 36 — Change from upright to Reliable Fl 155° semi -recessed pendents 1/2 x 1/2 02 — Plug existing uprights Warehouse 19 — Existing uprights no change 08 — Relocate Reliable Fl 155° Uprights 1/2 x 1/2 Warehouse — corridor/offices 10 — Add Reliable F1 155° semi -recessed pendents 1/2 x 1/2 01 — Change from upright to Reliable Fl 155° semi -recessed pendents 1/2 x 1/2 - 01 — Existing Pendent 63 — Total e II LEASE LINE O N 2 g 9'-3 I/4" AFS 1 1.1.1 c1� t CLG RID 2'-0" X 2'-0" FL. MOUNTED FIRE RATED METAL ACCESS PANEL W/ CONCEALED HINGES FOR STOREFRONT SIGNAGE AND GRILLE ACCE55. !LOCATION TO BE VERIFIED BYTENANT GC ACCE Without Comments As Noted in R:3d Per The s:.,-_,hdLetter These plans have beer, ; .y w ..., >:a L.;: - i i . T = ., ) j Prevention Bur „- .:.•,`,.::II :::..:r:' 1.1,:, '- ' eke'," standards. Ac; , ._.- .,•-:i-,-c.:1:,-._, ..... omissions which dc r o _ urP.Ori: i vr...ad c ns CI -_air':`wu ¢ ster,aards and C:.rCrir. i r..ti :r. ? i E'-r•o . -i,r fr-fe. radequacy o¢,:.,_ c;.. i= .. ..,ft ,. s .- ;Additions, cieie ;,,;,•s or= y ,;::_.,-...,, s, .-.t. this date will dL: d mf-."-._: : r.i-:,::', ,,.,,,,•••„;„ „ 1, resubmittal of r ev;s•:&' L .... ',F 7`18 'i01 Subs tient pr o :31. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /0 /v -U By: / ,51/ IiCL 2 m II' -11 1/4" ATRI li —BANNER TRACK SYSTEM (SEE DETAIL BELOW) TUKWILA FIRE DEPARTME L Please call: 575.4402 -' and give this(�job v - int address for shut. ,,r restoration approva,+l. S 144th t �, S 146t�t 4St-- �� - 99 •I S -148th --St 5 1,6Qth-St /7 S 152nd St- <'c r5 154th -St c '•5518.) S 158th St- -ribath-st- S-162nd St S -164th -St--- - , ,2 -5 -166th -St 54B 0.4 `c S 17oth-St --.1C- 41 SeaTac S -1 -72nd -PI S 173rd .St -- - cn ®2006 Microsoft Colp 02005 NOTEQ, and forGDT, Incl Fort Dent-. Park 957 tSouthcenter Mall, • rTukwila,yVU'A, 981882822 1 _ T • Boeing Renton • - 1Longacres Industrial 54 Baker -Blvd-;• Park MapPoint• SW -7th -St— 0 ` a CD p to SW 16th St Strander- Blvd 53r: 0 La a OCT 4 2.006 C WN FIRE PROTECTION FOOT LOCKER 957 SOUTHCENTER MALL, TUKWILA, WA, 98188 INCORPORATED P.o. Box.12n3 MILL CREEK, WASHING1C44 9B082-0113 PH. (425) 481-7689 1090 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-105 06-F-246 06-F-234 10-S-104 06-S-201 • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Foot Locker 1090 Southcenter Mall Permit No.: 10-S-104 Date: June 7, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition 1;o the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. FELE Po Box 3932 Seattle WA 98124-3932 206-2344700 RreComNW,LLC Battery Calculation Work Sheet Project: Foot Locker Store #7010 Fire Alarm System Project Southcenter Mall Space 340 Tukwila WA 98188 This project consists of installing a new addressable fire alarm system. The building is fully sprinklered. This worksheet is for the new fire alarm control panel and the connected devices. Qty Part # and description Supervised Current mA Alarm Current mA 1 5700 Silent Knight FACP 160 330 1 SD505-APS Add smoke det 0.55 0.55 2 SD5O5-ADHR Add duct det 1.1 1.1 1 GEC3 Horn strobes - wall mount 0 164 3 GES3 Strobes — wall mount 0 165 4 GCC Horn strobes — ceiling mount 0 1532 Subtotal 162 2193 Total battery power hours x24 x.083 Subtotal 3888 182 Safety factor - 10% +389 + 18 Total 4277 ma 200 ma Total Current Required 4477 ma or 4.5 amps Battery size used: 2ea - 12volt, 7amp c � PAID NOV -8 20060U 1 Vr SHEET \UMBE SH TITL_ SHEET INDEX FA -01 SYSTEM I\FO RMATIO\ FA -02 TYDICAL =TAILS - WRING A\D MOU\TING FA -03 SYST v CALC U LATI O \ S r G _ \EAL), RIS =A-04 FIR -71 ALARM SYSTEM FLOOR D LA\ CC Without Comments 0 As Noted in Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire ^revention Bureau for conformance with current City •:.andards. Acceptance is subject to errors and i.irnissIons which do not authorize violations of adopted -andards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Ariditions, deletions or revisions to these drawings after this date will void this acceptance and wili'require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by Tne Tukwila Fire Prevention Bureau. Date:-�-�� By: S�� ft"WtLA FIRE DEPARTMilita Please call: 5754407 and give this job / az.,.i l!;act address for shut. euwo or restoration aaarove! NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing, WIRE DESIGNATION SCHEDULE WIR SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO 1416 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 1414 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 1 REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO 4416 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V X12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" - .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL • CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NEPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: W -ERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUN AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. D 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS .(E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CO\IDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEN BLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAIvAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 2 5 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL XLS SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ANN FIRE ALARM REMOTE ANNUNCIATOR SSD -C SIEMENS PROVIDED 66" A.F.F. TO TOP IA SMOKE DETECTOR (PHOTOELECTRIC) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING ®D DUCT SMOKE DETECTOR AD2-2P SIEMENS HFP-11 DET DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (PHOTOELECTRIC) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP BOX VERIFY IN FIELD [3G FIRE ALARM HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM HORN STROBE ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM FIRE ALARM STROBE ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM n MANUAL PULL STATION HMS -S SIEMENS 4S BOX W/ 1G RING 48" 0.0. AFF TO BOTTOM FIRE ALARM HORN STROBE WP (WEATHERPROOF) AS -75 -R -WP SIEMENS WBB-R 4S BOX VERIFY W/ 2G RING IN FIELD WP FIRE ALARM BELL (WEATHERPROOF) MBDC-10 SIEMENS WPBBS-R VERIFY IN FIELD 0 WATERFL❑W SWITCH N/A N/A N/A N/A O TAMPER SWITCH N/A N/A N/A N/A FATC EX JUNCTION BOX F.B,❑, F,B,❑, N/A VERIFY IN FIELD A.F,F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F,B4O, FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAID JUN - 7 2010 TUKWILA FIRE s� *so Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 6/03/10 0 0 z W Fan J(1).} (S.-CALE: 1'=1/8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/1 0 BACKROUND PLAN PROVIDED BY: sl.OB NUMBER: SHEET FA -01 } THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCT OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. BEND OR OTHER OBSTRUCTION DUCT DETECTOR LOCATION TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE 120VAC-60HZ DEDICATED EMERGENCY NOTE FOR ADDITIONAL 9'ECI 1CATIONS SEE PRODUCT DOCUMENTATION. MODULE 2RONS ® SUPERVISORY POINT ® FORM "C- RELAY CONTACTS LED *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC ISOLBATE FROMSG DING TO NEXT ADDRESSABLE DEVICE STOP IF LAST -CI' DEVICE FROM XLS CONTROL. PANEL-(+ OR PREVIOUS ADDRESSABLE DEVICE O GROUND Ir 4, MODEL: HTRI-R MOUNTING HODS FOR SNITCH PLATE MOUNTING SLOTS FOR DOUBLE GANG SNATCH BOX MOUNTING STATS (—) FOR 4 INCH SIMTCH BOX FROM EXISTING STROBE -- -- CIRCUIT OR PADS NOTE SEEPDCTADCES ADDITIONAL �Q 0 PAD -3 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — FEED TYPICAL WIRING FOR HTRI-R MODULE (PAD -3 TRIP) SCALE: NONE JUNCTION BOX MOUNTED ON CEILING FLEX .•,.rig';t�!iY�,'✓,.cr��Jy�.:ti��`�GYC'.•'l!�v:,.r.^.J�*vl: yt. ;,y.�.,�...\ ^"CZN�,a,n vXlv�:✓n; . , JUNCTION BOX MOUNTED AGAINS CEILING SUPPORT 0 0 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TO BATTERY n_ TUBE OUTLET SAMPLING TUBE INLET SAMPLING TYPICAL MOUNTING FOR AD -2P DUCT DETECTOR SCALE:NONE 48' HORNISTROBE FROM PRECEDING STROBE APPLIANCE OR SYNC MODULE tt NAC -4 NAC -3 NAC -2 ),10 0 OTO NEXT DEVICE SMOKE DETECTOR syr JUNCTION BOX MOUNTED ON CEILING FLEX �rw • rrrr SUSPENDED ILLUMINATED CEILING JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING NAC -1 11 11 0 0 WARNING. 0 0 ° TO PREVENT ELECTRIC SHOCK, DO NOT REMOVV IS COVER. NO USER SERVICEABLE PARTS INSI (+) TB UD 0 0 C3� AT LEAST SIX DUCT WIDTHS FROM BEND STROBE 0 0 __a ❑ 1;( O c DESCRIPTION n s1 I. CII O 11 b r w 4 - Ase[oaroM .. Irl.11...4;!& \ z «<<< R,- OWE 001 ♦ � ✓ STROBE CIRCUI Q (-) (+) I I SPEAKERISTROBE AND STROBE WIRING SCALE:112":1' (-) �1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA,TO 100' F (TINGG TEMPERATURE: ) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE f DATA IN ( )> /----)s- l DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE HORNISTROBE STROBE CIRCUIT 11 4,1 0 WARNINGS I 0 �✓G TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE 31IS COVER. NO USER SERVICEABLE PARTS INSIE (+) CEILING 6" IN. AS -75 WEATHERPROOF STROBE OR HORN T 90" A.F.F. WBB-R WEATHER PROOF BACKBOX 4S DEEP BOX W/ 2 GANG RING A TB UD 4 (-) STROBE 1 11' 11 (,CIRCUIT (+) WBB-R WEATHER PROOF BACKBOX ZH-MC HORN STROBE �-1 I R E 80" A.F.F. SEE NOTE #1 HMS -S MANUAL PULL c' STATION I I 048"O.C. AFFi- --_1 SII 4 i I "10 I WP -1 WEATHER PROOF BACKBOX 4" SQUARE DEEP •1 BACK BOX WITH 1G TRIM RING EXTERIOR HORNISTROBE & MANUAL STATION ELEVATION SCALE:NONE (—)TO NEXT APPLIANCE S OR END OR LINE RESISTOR i, (+) S 24K (EOLR) 24K 1/2W TO NEXT (-) ADDRESSABLE I (+) > DEVICE > (+) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. FRONT VIEW 470 OHMS EEOL (+) WITCH INPUI� (+�t t ) c DESCRIPTION n ) (.____D LTJ Q C3 O o L0 T�M-1 \ z «<<< (-) TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPLIFPLR RED (JACKET) *CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 _(+)TO NEXT DEVICE OR } (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECHIELEC. HARD LID CEILING CADDY SUPPORT BRACKET' CEILING TILE o 4" SQUARE DEEP BOX CEILING STROBE CEILING MOUNTED HORNISTROBE MOUNTING (DROP CEILING) SCALE:NONE SUPPORT BRIDGE ti c0 Cr 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Z a DESCRIPTION SHOP DRAWINGS LTJ Q C3 O o L0 z «<<< co >,OO W CC mZ w � 3F—O O ac v z = cn 1-3 pm%'' w 0 V CC (/) O� `/CALF: 1'=1 /8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/1 0 BACKROUND PLAN PROVIDED BY: \OB NUMBER: } /r SHEET 2006 byGuardian SecuritySystems, Inc. All Rights Reserved F" '-O2 ,/ Copyright Y Notification Appliance Circuit Detail PROJECT:1FOOT LOCKER , Panel:IXLS-V I ; Wire Resistance 1.62 Date: June 3, 2010 CURRENT TOTAL=13493.00 ":-;g:-e.i0OATA Ari.',14'2AAVIP • 1$4 0 1ZH-MC-C @15CD 87.5 0 i o ZH-MC-C ©30CD 131 0 2 IZI-1-MC-C @75CD 222 444 3 al -MC -C @95CD 292 876 0 I ZR -MC @110CD 259 01 -.•'''' 2 ' ..1 71:4-iyic1.5a D - :. . :: , .:: :_..:..-:,-a4 ,:,-.::,....-,::-, _, --113::-.:,-,:.-,.:_.:_,.:, .., 981 • ' I 0 IZR-MC @30CD 01 i . . . .. . . . -.. . ..„ , .. (:' : ' - ' . ''''Zf'-,N1 C@7.5CD.,•:' =':. .'''.. -. - ', . • -'-',.:17$ .. • --'..'::'-'.'E -'-:'..-1,-': --.-'0:, ,.-.:,-1' '-'' . '.'-- . • '•-'.".- .-."' . - -=1.'.' •..,, - ':- '-:-' '.- .,-. ':'. , - . '.;•-:', E. '2:1:: -:•:"': ,-f -- '.,'„ '1 E'--- - '- , - - - --•i - - - .... .... . .--.--, -... ..: ... - - :-. ....-, -..-: • .: ..-..... - ...-., • „,. : ..„. . ..-- . -.. .... .. -- ... , . .- • .....-.-.- .. .--- . . DEVICES=17 TOTAL mA= I 14481 12 1 1 14 1 , 23.47! 1448 0.37 ; Total Wire Resistance ( R ) ( WL * 2 )* (Rift) I Total Device Load, Amps (1) I ' Cct Load 1.45' 0.53 Eot. Voltage !Voltage DroP ( E ) „ „ 24 2147 (E= I * VOLTAGE DROP CALCULATION EOL—S1 SYSTEM CALCULATIONS S1-7 s S1-6 s S1-5 s S1-4 S1-3 S1-2 S1 -1s Device Type Qty Amps Total Amps Total Main System Board 0.03 0.030 ZH-MC-C ©15CD 0.0875 ZH-NIC-C @30CD 0.131 Tii-MC-C ©75CD 2 • 0.222 ZH-MC-C @95CD 3 0.292 ZWIVIC-C @1 OCD •- „ 0.269 ZR -MC @15CD 2 0.064 0.128 ZR- C ©30CD 0.098 ZR -MC @75CD 0.2 Amps 0.128 'kips StandbY:CtirrentlOad,:: Amps For24 HOurs Amp -hours AliniCurretit-load;' 0.128 Amps Fo..5 Mititites 011 Amp -hours 25% Derating: 0.013 Amp -hours DEDICATED EMERGENCY POWER 120VAC-60HZ RISER DIAGRAM Current Load: Device Type HFP 11 Qty Amps 0 0.0022 tandby: Alarm: Total Amps 0.0022 0.0023 Total 0.0,00 AD2-P HTR -R HTRI-D . - Standby Current Load: Alarm Current Load: 1 0.0635 1 0 009600 0 0.001600 0.0731 Amps 0.085 Amps Total System Current Load: Battery Pair to be Used12VDC 0.0635 0.064 0.0096 - 0 0.021 0.0035 0.0731 Amps For 24 Hours = ';• For 15 Minute 1.754 0.064 0 021 0.000 0.085 Amps Amp -hours 0.021 Amp -hours 25% Derating= 2.220 Amp -hours 2.220 Amp -hours Amp -hours BATTERY SIZING CALCULATION 7AH OD FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS 1 DATE 6/03/10 2 <<<<< 03 03 CI (70. CCO) W 2 m z 111 cc 0 W u) E"'" Z Z Li 2 w cc (/) ‹c < I— —I < LL.I 0 0 EC (1) 0 (S-CALE: 1 '= 1 /8" -*\ DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/10 BACKROUND PLAN PROVIDED BY: NUMBER: SHEET FA -03 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved HOME RUN TO— BPS ti ei x 1-13 TRI -R EX X 1-14 i S. I S1-3 HUI—FRI) 1 s1- •.•.7,n Ss4'r::c.i::'1a'�i 2'".9'ii< `i'i�Ia''i'.. "`aa'-. S•fi:Xis2'-.x41iS�Yi`::..:. Y.'Y,zc::F'::::;:i':sY'aa iSY:i:iv: ::a Yta�:. x 0 0 X x x X 0 0 X 0 0 X 0 0 x 0 X X 0 0 NORTH FOOT LOCKER SCALE 118"=1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE THESE DEVICES. Ll›- FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. TENANT FIRE ALARM JUNCTION BOX (FIELD LOCATE) EXISTING CORE AND SHELL FIRE SMOKE DAMPERS RELAY TRIPS TO ACIVATE AND MONITORS PAD 3 > TIE TO EXISTING DEVICE TIE TO CLOSES EXISTING -- SPEAKER STROBE 10 RELOCATE EXISTING DEVICE ® TIE TO EXISTING EOL V>. REPLACE WITH 15CD SPEAKER STROBE FIELD LOCATE HVAC UNITS SMOKE MUST BE LOCATTED IN THE SAME ROOM AS THE POWER SUPPLY. 1›- REFFER TO RISER ON PAGE FA -03 FOR VOICE/SPEAKER WIRING ELECTRICAL/INSTALLING CONTRACTOR SHALL RETURN ONE FULL SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. RELEASE/REVISIONS 5.1 m Lu Z DESCRIPTION SHOP DRAWINGS 0 1- < o ' M O (0 z \\<\\ r .co OG CC Of.l w z W° co 0 Coo W— cc o(f) Ca W0 CC Cr) of w(f)CC WCCEr. DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/03/10 BACKROUND PLAN PROVIDED BY: JOB NUMBER: ( FA -04 SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved \112206—redline\Redline Projects 2006\FCNW\Foot Locker — S. Ctr\Codd\FA-1—Foot Locker dwg 0 0 0 0 N 0 N 0 0 0 N (.1.; 0 CL•/EXIOTW) a•1 . u••o• .w 10.1. IraM 1 CL.1 . ['-6' Ni 1 U A A T-2B o-8 o -B El DD c -B EOL FIRST FLOOR FACP TO 120 VAC UNSWITCHED ,' DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISER DIAGRAM SCALE: NONE GENERAL NOTES: 1. ALL WORK 18 TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD 18 TO BE OPEN CABLING EXCEPT WHERE IT 18 EXPOSED AND BELOW SEVEN FEET - THEN IT 18 TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED. 4. ALL INDOOR HORN$, STROBES, HORN STROBES, AND MINI HORN STROBES ARE TO BE MOUNTED 80" ABOVE THE FLOOR OR 8' BELOW THE CE1UNG, WHICHEVER 18 LOWER. 8. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING: A) 38' INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER 8) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASES. o-8 J 1 1 4 B A b --I CL.l . Ir -4' GfP I 111111111111111111 CL•I • t2.. 6' 4T EQUIPMENT LEGEND DEVICE SYMBOL QUANTITY PART NUNNBER DESCRIPTION BACKBOX 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE 1 5700 FIRE ALARM CONTROL PANEL INCLUDED ZS Q 3 SD505APS SMOKE DETECTOR 4 SQUARE X 1-7/8" DEEP al 1 GEC3 HORN STROBE 4 SQUARE X 1-7/8" DEEP ®4C 4 GCC HORN STROBE - CEILING MOUNT 4 SQUARE X 1-7/8" DEEP 3 GESS STROBE 4 SQUARE X 1-7/8" DEEP iN 2 SD505ACHR DUCT DETECTOR 4 SQUARE X 1-7/8" DEEP Ell WIRE LEGEND TYPE DESCRIPTION A 13 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE B 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE C 18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE EOL ) SCALE: 3/32"-i'-0' FIRE ALARM PLAN G,/iseb Ara \2i,1zooto ADD --41rez 1)&7- c7 Dv� 76 MU/u& DvL77UAJ1-5.?.3.2. (E) -ui. 012P 1-1, FIRE COM NW ►Osa�sb! II .WA I*1IU 30W$AII DATE: DRAM: CHECKED: 11176 PROJECT NAME CBA FOOT LOCKER 17010 T1 JD Tik* AW Me epos SHEET Tat FIRE ALARM PUN APPROVED BY: SCALE N0. DATE ID 819Y•i .o' REVISOR SY JOB NUMBER: 06214 FA -1 of 1 TUKWILA FIRE DEPAlifivialit Please call: 575-440Z and give this job No. 0(0- itgo and exact address for shut. down or restoration approval, A " f#‘ 4114:7 163.,,ex 441* rrlOtd, 4ka Without Comments As Noted In Red Per The Attached Letter s These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violationof adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thacceptance and will require a resubmittal of revised drawings for 5 ubsequent approval. Final acceptance is subject to field teat and inspection by The Tukwila Fire Prevention Bureau. Date: J2jajp.,',.(e_By: ttacglanametaimart......,00makenwaamempig. \Redline Projects 2006\FCNW\Foot Locker — S. Ctr\Cadd\FA-1—Foot Locker.dwg 43 AM DWG: DATE: 11/7/2006 1 OL-(EYISTIN..) I CL -1 • 1I'.O' CFP 1 CL•I a II'.O" 6fr c) -2B • • DD FIRST FLOOR EOL ♦ '• TO 120 VAC UNSWITCHED DEDICATED CIRCUIT TO TELCO ROOM FIRE ALARM RISER DIAGRAM SCALE: NONE GENERAL NOTES: 1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS. 2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN FEET - THEN IT IS TO BE IN CONDUIT. 3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED. 4. ALL INDOOR HORNS, STROBES, HORN STROBES, AND MINI HORN STROBES ARE TO BE MOUNTED 80" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER. 6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING: A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES 7. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL PREVENT PASSAGE OF FLAME AND HOT GASES. ll CL -I • II'.J' C CL•I ♦ p'-(' CFF EQUIPMENT LEGEND DEVICE SYMBOL QUANTITY PART NUNMBER DESCRIPTION BACKBOX 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE 1 5700 FIRE ALARM CONTROL PANEL INCLUDED EG ® 1 SD505APS SMOKE DETECTOR 4 SQUARE X 1-7/8" DEEP 24 1 GEC3 HORN STROBE 4 SQUARE X 1-7/8" DEEP ®4C 4 GCC HORN STROBE - CEILING MOUNT 4 SQUARE X 1-7/8" DEEP 3 GES3 STROBE 4 SQUARE X 1-7/8" DEEP IN 2 SD505ADHR DUCT DETECTOR 4 SQUARE X 1-7/8" DEEP CD WIRE LEGEND TYPE DESCRIPTION A 18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE 6 14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE C 18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE I EOL FII E ALA FRMPLAN SCALE: 3/32".1'-0" FIRE COM NWu0 PO Bax 3022 BatW WA 241244332 DATE: 11/7/08 DRAWN: CEA CHEO<ED: JD APPROVED BY: JD 2044344700 PROJECT NAME: FOOT LOCKER #7010 11 Southcenter Mall Space 340 Tukwila, WA 98188 SCALE: 3/32"=1'-0" NO. DATE REVISION BY SHEET IDLE FIRE ALARM PLAN JOB NUMBER: 06-214 FA -1 of/ 1 CCE 7'E Without Comments 0 AsNotedlnRed 0 , Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted stanaaras and or-amances. The responsibility for the a.dequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this acceptance and will require a resubmittal -of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /1-1 3 -°5- By: /V --1 % NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. I UKWILA FIRE DEPARTMENT Please call: 575-440Z and give this job No. a� - r- -,.3 `f wade and exact address for shut. down or restoration approval: Design per NFPA 13 — Ordinary Hazard Occupancy —130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means — Relocate Reliable Model G -4A Concealed Sprinkler Heads 165° 1/2 x 1/2 �$ — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ACCEPTE D Without Comments As Noted In Red 04: Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted ~tandards and ordinances. The responsibility for the adequacy of design rests totally with the designer. _ Additions, deletions or revisions to these drawings.after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: (o-7-( 6 By: /v v"''.51 1 \iL;J�17r1111ti1. ft.H(WItA FIRE DEPART Please call: 575.440Z and give this job IVo. '} ^-s- /o Tot address for shut. a0oroval, • CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 . MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 House of Hoops 1090 Southcenter Mali Tukwila, WA PAID MAY 20 2010 TUKWILA FIRE *r&5-3 DATE: /7 DRAWN: d ft, SCALE: 31/ C 44/ II'O"AFF CL L-2 a. l2'-0'J AFF "AFF I03/29/10 1 -2 -- + 4 e II' -6 1 CL -1 L-1 m 12'-0 "AFFOWE) 23'-11 3/8" � � �(6t�L "G 5/8" ID23'-II X'G' GRID EXA—.C.Try. _./., /10 GRID ID49-Id EX 'CQ AC.T. - , _ t c3 - - �iH - rI _i_((� __J f-� lmEQQ(w r FIm-EM/NL t2 I24/12 ;' (TYH P � tYP. •4._ _ E) (E)= GXE I 01(E) TtJCP / C> 1 H 101CL- Q I ,\1vZe/i0CL-I QQ1.---e 1w L1(E.CRP)0 III ..— 1 !_L P2 L P2:71.1.4-- C1w 214 1H2 ,G CRP) 03/2910I5 t CL A Il AFF ] H20i(dHLi H2 -3 -8" 1 Flo \ 3'- 8" 3' O9E)01- (E.) 14 -1(R. 4> L _ J_ _ -L — - 1 - c /I) r.- 1 1 H20) I® I®• ' e O 09/2S 1 I 1 1 VP Ilr 5._9.. / (1:J I -I ' ' (I� t>=$3 �7(R I T -1 (( 13 i P2 G7 P2 O CI P2 E2 NIF P2 Al,0 i�/2 THE.,) Q L H2 (tYP.) 2 (E) (E (E (EJ ---1 ---1--r- 71'(RJ ■■■ I I ■■■ 1 1 © 4_m� �7( li O(1� --T--- 1 T --4 - _ H H'2 ) TYP. 712 [1- - fa3/Za --+----•-+-----NI es`O HI 14 it - © w (TYP.) (T®.: ® -1--_L---- (� ® 1 CL -3 0 9'-3" AFF (TYP. EGI E0 Hr12n� �_ 0 1 ) ( I f2 / F2 -EM F2 F2 -EM — F2 F.2 t ,F2 LflL - ---\i< , -+---- --1 H H2 712 2 X �L(( O NI NI \ / ^� I ® (TYP.) 1 ll(E) 1 8 V / 1e i H �! t^ 2 .412 EZ_ F2 to / 0 -:1(RO N q F2 F2 F2 (I) 1 -1 • I _ __� I H H2 © (TYP.) H2' 2 II 67(R- © Io 7lR1- O() IPO O itak Mit �3-8' �io' 411/ ,r 3'-5. 5'-9" TF(E' (EJ la- H`n''� 2 6to -7(1Q.) �� 1 1111'Irl) •>< 0 X, X Z F2 _ CL-3 e� Il' -8" AR F2 2 -EM UFim� 04/12/10(E) (E% !Fa (E)2 H2 I 14 H2 H2 O -- 0-70Z) 2 ,,.• 2 2 fl.;�.'r Ha. H„ H H "L s03/2r J 1111 EN8 8 I G 1 G1(P) Gi(E) G7(f) Ca(P) t� o a s ' ; o s I I I 4'-e" F � (l) G1fE) TF(E) I ,QipQ Z I TYP. . ill ? r - �-- - _Ter YP. - - -14- - 1-I- -� _ W -EM .L r -1 1 I I I___-_-_-___ _ -- - - - - \ _ 4 _7. +_ _+____= C IA,4 ®4/12/1® A Design per NFPA 13 — Ordinary Hazard Occupancy —130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means — Relocate Reliable Model G -4A Concealed Sprinkler Heads 165° 1/2 x 1/2 �$ — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ACCEPTE D Without Comments As Noted In Red 04: Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted ~tandards and ordinances. The responsibility for the adequacy of design rests totally with the designer. _ Additions, deletions or revisions to these drawings.after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: (o-7-( 6 By: /v v"''.51 1 \iL;J�17r1111ti1. ft.H(WItA FIRE DEPART Please call: 575.440Z and give this job IVo. '} ^-s- /o Tot address for shut. a0oroval, • CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 . MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 House of Hoops 1090 Southcenter Mali Tukwila, WA PAID MAY 20 2010 TUKWILA FIRE *r&5-3 DATE: /7 DRAWN: d ft, SCALE: 31/ C 44/ GL-C-aXISTINr ) CL -I 9 11'-0" AA� i 23'-10" CL -1 s IP -0" Air - X • x X x i x :c x = x thCii -U e Tee -Lox Mechanical r3cal Branc?•T Connector From WARD 23'-10" 151'-2" I = ^== DIMENS ON CLC-. GRID G CLG--. GRID ICL -I o 11•-0• AFr EQ E0x EG I EQ I I ?^-3=3 M=3,07. MAX.�V'��'_�=�.: If :ss 23'-1m" CL -1 s I2'-6" A RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C-CLANP WITH SET SCREW 3/8' ALL THREAD ROD HANGER DETAIL NTS X23'-10" �I? OL trN I i ti - -1 —W — _ S�1 77 77 W - • p I; It 1l QE I !I• w — 1- • O E \ EXISTING CEILING GRID, DCT 4 LIGHT•� FIXTUii TO REMAIN -TEN NT GC TO /\A ACHIEVE AS NE' ESSARY TO ACHIEVE A "LIKE -NEW" -EARANCE tri CHAIN MOUNTED HRIXTURES MOUNTED 2'-0" 430VE TOP • SHELF (TYP.) CEILING OPEN TO DECK SPRINKLER PIPING PLAN 3/16"= 1' r e e II oq �.�I f I _ BANNER TRACK SYSTEM (SEE DETAIL BELOW) 0 nin 117-1_1 I I ©° Nu I.=.1 _n I 1 t1 O`0 I1 4 N ..1 1 3 E EO „L-iCL-1 g 11'-0' AFr CLC.GRID • N • Design per NFPA 13, Ordinary Hazard II, 130 Sq. Feet Max All materials to be new, U.L. listed, and F.M. approved Existing Storefront 6 — Relocate Reliable G4A 165° concealed pendents 1/2 x 1/2 N L 2 9 11'-11 I/4" J i Sales Floor 36 — Change from upright to Reliable Fl 155° semi -recessed pendents 1/2 x 1/2 02 — Plug existing uprights Warehouse 19 — Existing uprights no change 08 — Relocate Reliable Fl 155° Uprights 1/2 x 1/2 Warehouse — corridor/offices 10 — Add Reliable F1 155° semi -recessed pendents 1/2 x 1/2 01 — Change from upright to Reliable Fl 155° semi -recessed pendents 1/2 x 1/2 - 01 — Existing Pendent 63 — Total e II LEASE LINE O N 2 g 9'-3 I/4" AFS 1 1.1.1 c1� t CLG RID 2'-0" X 2'-0" FL. MOUNTED FIRE RATED METAL ACCESS PANEL W/ CONCEALED HINGES FOR STOREFRONT SIGNAGE AND GRILLE ACCE55. !LOCATION TO BE VERIFIED BYTENANT GC ACCE Without Comments As Noted in R:3d Per The s:.,-_,hdLetter These plans have beer, ; .y w ..., >:a L.;: - i i . T = ., ) j Prevention Bur „- .:.•,`,.::II :::..:r:' 1.1,:, '- ' eke'," standards. Ac; , ._.- .,•-:i-,-c.:1:,-._, ..... omissions which dc r o _ urP.Ori: i vr...ad c ns CI -_air':`wu ¢ ster,aards and C:.rCrir. i r..ti :r. ? i E'-r•o . -i,r fr-fe. radequacy o¢,:.,_ c;.. i= .. ..,ft ,. s .- ;Additions, cieie ;,,;,•s or= y ,;::_.,-...,, s, .-.t. this date will dL: d mf-."-._: : r.i-:,::', ,,.,,,,•••„;„ „ 1, resubmittal of r ev;s•:&' L .... ',F 7`18 'i01 Subs tient pr o :31. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /0 /v -U By: / ,51/ IiCL 2 m II' -11 1/4" ATRI li —BANNER TRACK SYSTEM (SEE DETAIL BELOW) TUKWILA FIRE DEPARTME L Please call: 575.4402 -' and give this(�job v - int address for shut. ,,r restoration approva,+l. S 144th t �, S 146t�t 4St-- �� - 99 •I S -148th --St 5 1,6Qth-St /7 S 152nd St- <'c r5 154th -St c '•5518.) S 158th St- -ribath-st- S-162nd St S -164th -St--- - , ,2 -5 -166th -St 54B 0.4 `c S 17oth-St --.1C- 41 SeaTac S -1 -72nd -PI S 173rd .St -- - cn ®2006 Microsoft Colp 02005 NOTEQ, and forGDT, Incl Fort Dent-. Park 957 tSouthcenter Mall, • rTukwila,yVU'A, 981882822 1 _ T • Boeing Renton • - 1Longacres Industrial 54 Baker -Blvd-;• Park MapPoint• SW -7th -St— 0 ` a CD p to SW 16th St Strander- Blvd 53r: 0 La a OCT 4 2.006 C WN FIRE PROTECTION FOOT LOCKER 957 SOUTHCENTER MALL, TUKWILA, WA, 98188 INCORPORATED P.o. Box.12n3 MILL CREEK, WASHING1C44 9B082-0113 PH. (425) 481-7689