Battery Calculation Work Sheet
Project: Game Stop TI
633 Southcenter Mall
Tukwila WA 98188
This project consists of a new fire alarm system for a tenant improvement for a `M' occupancy
space that is fully sprinklered. This scope of work will include installing a new fire alarm control
panel, initiating and signaling devices. This work sheet is for the fire alarm panel and the
connected devices.
Qty Part # and description
Supervised Current mA Alarm Current mA
1 D7024 Radionics FACP 269 380
1 D282 Smoke detector 0.0036 0.0036
1 GCC Horn strobe — ceiling mount 0 190
Subtotal 269 570
Total battery power hours x24 x.083
Subtotal 6456 47
Safety factor - 10% +646 + 5
Total 7102 ma 52 ma
Total Current Required 7154 ma or 7.2 amps
Battery size used: 2ea - 12volt, 12amp
FEB 15 2007
Fire
175
AREA OF WORK
X«
ENG
33' -It"
I N = - M Inn
EOL
A
N MN I E M N I N M N M M- V
\El.0
\4
SFAC
AC
EOL
C
1
1
1
1
1
1
111
1
11
1
1
FIRE ALARM PLAN
SCALE: 1/8"=1'-0"
EOL
FIRST FLOOR
EOL
EOL
TO 120 VAC UNSWITCHED
DEDICATED CIRCUIT
TO TELCO ROOM
FIRE ALARM RISER DIAGRAM
SCALE: NONE
EQUIPMENT LEGEND
DEVICE
SYMBOL
QUANTITY
PART NUMBER
DESCRIPTION
BACKBOX
®
1
07024
FIRE ALARM CONTROL PANEL
INCLUDED
m
1
2WB
SMOKE DETECTOR
4 SQUARE X 1-7/8" DEEP
611C4
1
GCC
HORN STROBE -CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
®
1
--
DUCT DETECTOR (")
PROVIDED BY OTHERS
(*) - PROVIDED AND INSTALLED BY OTHERS
WIRE LEGEND
TYPE
DESCRIPTION
A
18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
B
14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
C
18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE
GENERAL NOTES:
1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS.
2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN FEET - THEN IT
IS TO BE IN CONDUIT.
3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED.
4. ALL WALL MOUNT INDOOR HORNS, STROBES, HORN STROBES, AND SPEAKER STROBES ARE TO BE MOUNTED
BO" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER.
5. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER
B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES
6. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH WILL
PREVENT PASSAGE OF FLAME AND HOT GASES.
FIRE COM NW..
0
a
PO Pox 3022 NMIM WA M1314012 2040344700
ATE: PROJECT NAAE:
RAMN: GAME STOP
p1Ep<Ep; 633 Southcenter Mall
Tukwila, WA 98188
SHEET TITLE:
SCALE:
2/15/07
CEA
JD
APPROVED BY:
JD
NO.
DATE
REVISION
BY
FIRE ALARM PLAN
JOB NUMBER: 07-020
FA -1
of
1
ACCEPTED
0Without Comments
a As Noted In Red
[] Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
c `andards. Acceptance is subject to errors and
orni - i -ss vThich do not authorize violations of adopted
od �!n nces. The responsibility for the
n r _Yts totally with the designer.
or revisions to these drawings atter
_:,?.:: acceptance and will require a
esus r:;a ; ct errs&ad drawings for subsequent approval.
Final accc, t.:7 . iE subject to field test and inspection by
t The Tukwila Fire, Prevention Bureau.
By: kv-%
1
1
1
Date: ) -DJ -o 7
.13
ruKwILA FIRE DEPARI:VIEN1
Please call: 575-4402
and give this job
No. 0 7 F
and exac ddress for stmt•
down or i estoration aoorovat
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate mLst be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
r
4.1
t
cf
G
1 % r
.1 1
f .1 1
.. ar
v
l„ L, j . tit' 3� - - — -
t
1 I + t 1 I 1
1
\i
i
TENANT,REFLECTED CLO PLAN
R c 1 c ,4'Ir 1 ,�
tLa Ct-(04
C. odile
t r t L Fi 5-1-11 044.4._D 2z 5 Pa.+ve—
t 7s�
•
e05 Mr x c, 4.0tit vs-
4t.1 Pt/II-gift .ri LS
•
HANGER DETAIL —
NTS
SPACE LOCATION PLAN
vv ado -
ILIKWILA FIRE DEPARTMENT
Please call 575.4407
and give this job
No OC'S-aS)
and exact address for shut.
clown or rest)ration approval
FILE
ACCEPTED
1 ,Wthout Comments
❑ As Noted In Red
❑ Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
' 0revention Bureau for conformance with current city
}+anderds Acceptance is subject to errors and
-.'n ss+ons which do not authorize violations of adopted
-inn lards and ordinances The responsibility for the
--i icy cf design rests totally with the designer
+gins d,,+: tions or revisions to these drawings atter
- I --,Y: toil void this acceptance and will require a
'..A.,Dirt tat of revised drawings for subsequent approval
` nal acceptance is subject to field test and inspection by
i he Tukwila Fire. revention Bureau
Date J -Z/' ./o [ By / 1 S l l
PAID
DEC 2 2 2006
T±.i,i1d,,'a Fire
CRO\NN
FIRE PROTECTION
IN CORPORA TED
P0.BOX ,2113
MILL 7c -M. WASHINGTON 9808c-0113
PH. (4 5) 481;-Isoo9
,075'
GAMESTOP
TENANT IMPROVEI NT
/ "SOUTHCENTER MALL SPACE #400A
TUKVi ILL\ WASHING TON
DATE. t1.-2.5 -dfo DRAwrt J
SCALE.
10