Loading...
HomeMy WebLinkAboutPP - 1119 SOUTHCENTER MALL - VITAMIN WORLD - PERMITS AND PLANS1119 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-295 08-S-290 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vitamin World 1119 Southcenter Mall Permit No.: 08-S-290 Date: June 10, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). M, • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. VITAMIN WORLD FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UVEB SHEET TITLE FA -01 SYSTEV I \ FO \4ATI O N FA -02 TYPICAL DETAILS - A\3 IOU\TI\C FA -03 FI RE ALARM SYSTEM FLOO PLA\ FA -04 SYSTEM CALCULATIO\S (CENEAL), RISE, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWD #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM FLL 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. NCH NCH - NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED._ 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL -BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT., 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING. PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL. OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 2 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD ❑° DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN HELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD Ca LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR (ADDRESSABLE -PHOTO) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Fic FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. [LID FIRE ALARM STROBE (CEILING MOUNT) ZR -MC ICW SIEMENS 4S BOX W/ 1G RING CEILING ILI 9c FIRE ALARM STROBE (WALL MOUNT) ZR -MC -I4 SIEMENS 4S BOX W/ 1G RING 80" A.F.F. 1 O UUU I FOM U.U.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. I o oWP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX IN/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.D. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR F.B.O. FURNISHED BY OTHERS N/A N/A ,t N/A Y N/A CCEPIED N/A II N/A ithout Comments N/A 1 `� N/A NOT APPLICABLE N/A 's to e• Nn _e• N/A per TheA"ttacAhedLetter N/A mi ,D.N. UNLESS OTHERWISE NOTED N/A fl'Re plans have been reed by The Tukwila Fire A w�����v� prevention Bureau for corff 'rMance with current citVA _ . ± -. . - ' . 1 'PP. . errors and WP WEATHERPROOF DEVICE N/A c ipsions which do not alit oAize violations of adol e9 standards and ordinances. The responsibility for the A comply RED AS BUILT ADD ❑R CHANGE N/A /}ions, disletions or rev�1s o these drawings tt this date wil void this acceptance and will required" ire I' Certifica GREEN AS BUILT REMOVE N/A N/A N/A N/p, Final acceptance is subject to field test and inspection by ` comment Testinc BLUE AS BUILT NOTES TO CAD N/A N/A " �v ° N/A i DCS N/A Date: Sy F Id D use . �;+� Copyright 'TUKWILA FIRE 575EPARTt i'� please call: end give this job do Nnd Xor restoration aat address oapPr r tvati 2006 by Guardian Security Systems, NOTICE FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m LU z DESCRIPTION SHOP DRAWINGS W 0 CC 1 ted, signed, Tukteria apartment Pre-test to must be presented Inspector prior to gement of Acceptance of any Fire Alarm Detection Systems. of test will result inspection Fee and ation of the testing. dI �N-08 �oo05g rukwila Fire CSC' Inc. All Rights Reserved �CALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -01 , THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE /.4_ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR 117-----1 PREVI❑US ADDRESSABLE DEVIC END OF LINE DEVICE<3.6K 1/4W) SUPERVISED SWITCH DUCT DETECTOR LOCATION LID N) 0 GROUND Lr) 0 0 HTRI-R STATUS LED 00 0 N.O. 0 COM CO 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L (BACKGOUND MUSIC SHUTDOWN) + O 10 01 TB1 NOTE 11 VOLTAGE MAX. - CURRENT MAX, - CONT. RES. MAX, - MAX, CABLE LENGTH - C CLINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING, TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE L$AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE l(+) STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL OR .{(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4,0A @ i25VAC) (4.OA @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2; ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTI❑N, 0 01:0000 123456 HCP TB2 mm + 654321 r 0 O END OF LINE DEVICE 0 (3.6K 1/4W) % SUPERVISED. 1' SWITCH / GROUND / m 0 0 HTRI-D OSTATUS LED CO 0 0 NOT USED O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL "L SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC _--n 0 0 0 i T 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C N0 + - + - + - + - + - 0000001=1=F=01s 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3,6K 1/4W) \SUPERVISED SWITCH 2 NAC -4 NAC -3 2 NAC -2 2 NAC -1 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE ..I.. DEVICE LOOP 0 0 0 0 0T FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY <'S' CABLE) 470 OHMS �IN EOL T INPU' (+9-) 9 f9 9 TSM -1 Q o¢ oo •( oRo x ce00 1.2.3.4.5, �Mo cccIco TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCAL FROM1FACP <V❑ICE CIRCUIT) C'V' CABLE) u � (STROBE) SPEAKER v () STR❑BE) EARTH GROUND 0 -3►(+)TO NEXT DEVICE OR } "(-) STOP IF LAST DEVICE (STROBE( -) SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERT1IN TEMPERATU E: +32' F (0' C) TO 100 F 3' C) HUMIDITY: O-9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CON%&JNCTION WITH DUCT HOUSINGS AD -11P OR AD -11)83R DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F— > ( ) DATA OUT 1 > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID — CEILING HARD LID SPEAKER SUPPORT TIL- BRIDGE /- 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \, CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING. FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT Ii1 / C,11 TO NEXT DEVICE 0 0 -------CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE --- SUSPENDED ILLUMINATED CEILING DO \O O INSTA ADDRESSABLE H \ DEVICES \TI_ PREPROG AM h/ E DEVICES ADDRE _L AT \C D WITH SS. Pr) 0' tti cc z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS co co Qa �W 2z CE 0 zz 2 w= Z 517C (Pp< Qo'- � D F - (.9 z z 3 0 0 z 0 z E U SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .OB NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reservedk FA -02 EOL—S1 20.21V NORTH VITAMIN WORLD WESTFIELDSOUTHCENTER MALL SCALE 118"=1' FLAG 0 ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT O N STA LL ADDRESSABLE IN T JFVICES UNTIL DEPROGRAMMED W DEVICES ADDRESS. AH\G TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z ti) z 615, gg z OD 0' z 0 z_ LI" J F- W O w F - (I) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION (SHOP DRAWINGS DATE 5/15/08 J co co Q T Q w z O Wo > wi =Q co Q dog D I- fSCALE:1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: V.0B NUMBER: SHEET FA -03} LL Cr: A A A Li• ---------- CN LJJ LLJ I 11 ___- • . 0 E3I ()I:: HAWAII C�RLON'S JE WE LE R S M P S. FIELDS CLAIRE'S JOURNEYS BASKIN ROBBINS SUN C1. ASS H U T CH000-- LATE 3 AR a_ KITS CAMERA M 0 TH ERHOOD MA. TER I\ 1 [iFF:::iG PAGODA LIDS I - Y .0 - S P EC'S: I N C BANI• I Ty TR A sH ,• SP R 1155 -------- (-1 • i• c • KIDS c:0 0 -1-1 OCKER r 1440 NORTH 1200 >- c:21 cri 0_ 1210] cj- r-- ----- VITAMIN WORLD WESTFIELD SOUTHCENTER MALL 0 Cr) a. J 1 2_ 30 1235 Cr(_). LiJ (.1) LJ 0 EXISTING FOOTLOCKER. TFJ;;; A N --L 11300 0 11 SCALE 11324 EX RISER DIAGRAM 1 SYSTEM CALCULATIONS BATTERY SIZING CALCULATION I NVI Notification Appliance Circuit Detail ) VITAMIN WORLD VITAMIN WORLD PROJECT: FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DATE CO 0 ",..... Ln in VITAMIN WORLD Wire Resistance 1.62 19 Panel: June 3,2008 CURRENT TOTAL 303 Date: CIRCUIT: Current Load: Standby: Alarm: Current Load: Standby: Alarm: Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Deice Type 0.62 Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total 175 HFP-11 0.0022 0.0022 0.0023 (I) 0.30 0 SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.19 0.03 0.030 0.030 0 HTR -R 2 0.009600 0.0096 0.021 0.042 0 SET -MC @15CD 318 1 0.064 0.064 EOL Voltage HTRI-D 0 SET -HMC @185CD 0.001600 0 0.0035 SET -MC @30CD (20.4 - E) 1 Z-MC@15CD 0.098 64 ICP -B6 0.005 0 Z-MC@30CD SET -MC @75CD 0 1 0.175 0.175 0 SET-MC-CW@110CD 233 0 SET -MC ©110CD DEVICES= 3 TOTAL m A= 0.233 12 191 SET-HMC-C@115CD 303 0.318 SET-HMC-C@135CD Notification Appliance Circuit Detail 0.318 WESTFIELD SOUTHCENTER MALL VITAMIN WORLD 0.0731 Amps 0.106 Amps SET-HMC-C@185CD CURRENT TOTAL= 3.6 0.445 CIRCUIT: SPEAKER CIRCUIT ZR -MC ©15CD ZR -MC @30CD QTY 1 Alarm Current Alarm Total Wire Size 0.064 0.064 Circuit Total Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0.098 ( R ) 0.99 HCP 1 0 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours Total Device Load Amps (1) 0.00 0.03 Amps 0.333 Amps 25% Derating= 2.204 Amp -hours 0 0 0 Voltage Drop Standby Current Load: 0.00 0.03 Amps 0 For 24 Hours = 0.720 Amp -hours (E= I* R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) Alarm Current Load: 0 0.333 Amps 0 For 5 Minutes= 0.028 Amp -hours Total System Current Load: 2.204 Amp -hours 0 TOTAL m A= 0 3.6 14 191 20.396451981 3.6 DE\iICES= 25% Derating= 0.935 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.935 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH _ BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Ri hts Reserved 14-) co 0' 4X I74 3 IST AVE RELEASE/REVISIONS REV. BY: I NVI Notification Appliance Circuit Detail ) DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE CO 0 ",..... Ln in VITAMIN WORLD Wire Resistance 1.62 19 Panel: June 3,2008 CURRENT TOTAL 303 Date: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Total Wire Resistance ( R ) 0.62 0 SET -MC @30CD 98 0 ( WL * 2) *(R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (I) 0.30 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.19 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.21 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL m A= 303 12 191 20.21249148 303 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL VITAMIN WORLD Wire Resistance 2.58 Panel: June 3, 2008 CURRENT TOTAL= 3.6 Date: CIRCUIT: SPEAKER CIRCUIT QTY Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 1 3.6 Total Wire Resistance ( R ) 0.99 0 1 0 (WL*2)*(R/ft) 0 0 0 Total Device Load Amps (1) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 0 2 0 TOTAL m A= 0 3.6 14 191 20.396451981 3.6 DE\iICES= VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Ri hts Reserved 14-) co 0' 4X I74 3 IST AVE RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION I SHOP DRAWINGS DATE CO 0 ",..... Ln in 19 <<<<l‹ 1 cr etz cc w z w z 0 > _J 0 w(1) >- (1) >- I 'CALE: 1 /8"= 1 DRAWN BY: 'ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: NUMBER: SHEET FA -04 3 -8" 3'-8" (G,) 12 Lf) co '• Wthout Cort : • As Noted In led [ Per The ,attached l.:lttr 1 nese plans have bean reviewed by Then/hub Then/hubFite t it Prevention Bureau conformance currs�r,L city standards. Acc:.: pi::,nce i fubiect to errors �rnd omissions which do not authorize viatatiao . of aucpted standards and ordinances. The ru `7)Gtlslhifity for the adequacy of desi )n rests totally tih'1tll the designer. Additions, deletions or rr;:visio11s to these drawings after this date will void th :s acceptance end will require a resubmittal of revised drawings for subsequent approval. 3 8„ I /2" x I ' ADA CAP 7-4 3'-5'' [=_1 L ),(N.(1) -- Back to Back 4"x I %2" M.T. 1// 5-11 8'6" 6-3 8'-0" 5-11 Back to Backii 4"x I%2" M.T. 11=1 ii 1i 11/11 2-6 7y2' 1 0 7/2" r ,L\2-6 0 1� L ..-11.10=,. 4'-8" 2'-8" Final acceptance is subject to fietd test and inspection by The Tukwila Fire Prevention Bureau. Date: 6 -to -0_ TUKWILA FIRE DEPARTMENT, Please call: 575.4402 and give this job No. and exact address for shut' or restoration approval: 6'-0" II 1, II - 1 -i: 1 II 5-10 1-9 1-8 ,iii (Vitamin World: SCALE: /2" = I '-O CONSTRUCTION NOTES: I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "F", WHICH ARE TO BE STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL HANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD SYMBOL LEGEND:) = NEW RECESSED PENDANT ON DROP ® = NEW CONCEALED PENDANT ON DROP S ---S = EXISTING SPRINKLER PIPE TO REMAIN I-5= NEW SPRINKLER PIPING HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3" METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750#* 1/2" ANCHOR w/40# TORQUE: TENSION=440#, SHEAR=750#* 'SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR THRU THREADS 1/4" MIN ROD COUPLING THREADED ROD PIPE SIZE I" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 6" 8" ROD BOLT IMBED DIA. LGTH DEPTH 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 1" GENERAL NOTES: ) I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP 11. ORDINARY HAZARD GROUP 11 SPRINKLER SPACING: 130 ftz. MAX. 2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN. 3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY OTHER. 4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER. 5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. G) OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. 7) NER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, T INC, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACC RDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) IS BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. 8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. SEE PLAN FOR LENGTH NEW BRANCH LINE "FLEXHEAD" FLEXIBLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE CEILING 2 z 6- z W W O No 2 El FILE COPY ii—ADJUSTABLE HUB OUNTING BRACKET iB COSCO STANDARD HANGER LIUIDL A TYPICAL ARMOVER TO NEW SPRINKLER HEAD --- N.T.S. TOLCO FIG. 25 SURGE RESTRAINER TYPE I - FOR I" AND 14' PIPE AND HANGER TYPE 2 - FOR 172" AND 2" PIPE AND HANGER TOLCO MG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY SYMBOL = FIGURE 25 SURGE RESTRAINER bisOFOR STEEL OR CPVC PLASTIC PIPE 3/8' x 3,Y2' LAG SCREW FOR WOOD V x 24' KWIK BOLT FOR CONCRETE --\ I " x /" TEK FOR BARJOIST OR STEEL BEAM r45° MIN. ARGCO OFFSET EYESOCKET BRKT. WHERE LENGTH 1 EXCEEDS I'- 1 0" SYMBOL = 6 LINE RESTRAINT DETAIL NALL THREAD ROD I - I O MAX. PER SINGLE. OTHERWISE ASSEMBLY REQD. BOTH SIDES ' - hANGER RING (UP TO2"PIPE) SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. Reliable G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 9 Reliable Model Fl FR Recessed Pendant 1/2' 1/2' 5.6 Chrome Chrome 155° 3 APPROVALS BY: I TOTAL SPRINKLERS THIS SHEET 12 .00000o. • 00 00 00. • ®® 00O0- • "0000°1' ICosmo Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE www.coscofire.com 10910 117TH Place N.E. Kirkland, Washington 98033 call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE License No: COSCOFP 11 ONM PROJECT: Vitamin World 1119 Southcenter Mall, Suite #1417 Tukwila, Wa. 98188-2823it--9 2118N CONTRACT WITH: Unique Structures LLC 7 Pine Grove Lane Rexford, Ny.12148 PAID dlo �r1 ' *wile Fire D(J�:— DRAWN' TIRE Vitamin World: Sprinkler Piping Plan DATE : June, 2008 SCALE : As Noted DRAWN BY : Justin Johnson MKS — 7957 SHEET NO. FP S' 6/1/ 1119 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-295 08-S-290 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vitamin World 1119 Southcenter Mall Permit No.: 08-S-290 Date: June 10, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). M, • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. VITAMIN WORLD FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UVEB SHEET TITLE FA -01 SYSTEV I \ FO \4ATI O N FA -02 TYPICAL DETAILS - A\3 IOU\TI\C FA -03 FI RE ALARM SYSTEM FLOO PLA\ FA -04 SYSTEM CALCULATIO\S (CENEAL), RISE, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWD #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM FLL 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. NCH NCH - NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED._ 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL -BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT., 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING. PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL. OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 2 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD ❑° DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN HELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD Ca LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR (ADDRESSABLE -PHOTO) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING Fic FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. [LID FIRE ALARM STROBE (CEILING MOUNT) ZR -MC ICW SIEMENS 4S BOX W/ 1G RING CEILING ILI 9c FIRE ALARM STROBE (WALL MOUNT) ZR -MC -I4 SIEMENS 4S BOX W/ 1G RING 80" A.F.F. 1 O UUU I FOM U.U.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. I o oWP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX IN/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.D. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR F.B.O. FURNISHED BY OTHERS N/A N/A ,t N/A Y N/A CCEPIED N/A II N/A ithout Comments N/A 1 `� N/A NOT APPLICABLE N/A 's to e• Nn _e• N/A per TheA"ttacAhedLetter N/A mi ,D.N. UNLESS OTHERWISE NOTED N/A fl'Re plans have been reed by The Tukwila Fire A w�����v� prevention Bureau for corff 'rMance with current citVA _ . ± -. . - ' . 1 'PP. . errors and WP WEATHERPROOF DEVICE N/A c ipsions which do not alit oAize violations of adol e9 standards and ordinances. The responsibility for the A comply RED AS BUILT ADD ❑R CHANGE N/A /}ions, disletions or rev�1s o these drawings tt this date wil void this acceptance and will required" ire I' Certifica GREEN AS BUILT REMOVE N/A N/A N/A N/p, Final acceptance is subject to field test and inspection by ` comment Testinc BLUE AS BUILT NOTES TO CAD N/A N/A " �v ° N/A i DCS N/A Date: Sy F Id D use . �;+� Copyright 'TUKWILA FIRE 575EPARTt i'� please call: end give this job do Nnd Xor restoration aat address oapPr r tvati 2006 by Guardian Security Systems, NOTICE FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m LU z DESCRIPTION SHOP DRAWINGS W 0 CC 1 ted, signed, Tukteria apartment Pre-test to must be presented Inspector prior to gement of Acceptance of any Fire Alarm Detection Systems. of test will result inspection Fee and ation of the testing. dI �N-08 �oo05g rukwila Fire CSC' Inc. All Rights Reserved �CALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -01 , THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE /.4_ STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR 117-----1 PREVI❑US ADDRESSABLE DEVIC END OF LINE DEVICE<3.6K 1/4W) SUPERVISED SWITCH DUCT DETECTOR LOCATION LID N) 0 GROUND Lr) 0 0 HTRI-R STATUS LED 00 0 N.O. 0 COM CO 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L (BACKGOUND MUSIC SHUTDOWN) + O 10 01 TB1 NOTE 11 VOLTAGE MAX. - CURRENT MAX, - CONT. RES. MAX, - MAX, CABLE LENGTH - C CLINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING, TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE L$AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE l(+) STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL OR .{(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4,0A @ i25VAC) (4.OA @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2; ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC, TO GUARANTEE DETECTI❑N, 0 01:0000 123456 HCP TB2 mm + 654321 r 0 O END OF LINE DEVICE 0 (3.6K 1/4W) % SUPERVISED. 1' SWITCH / GROUND / m 0 0 HTRI-D OSTATUS LED CO 0 0 NOT USED O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL "L SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC _--n 0 0 0 i T 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C N0 + - + - + - + - + - 0000001=1=F=01s 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3,6K 1/4W) \SUPERVISED SWITCH 2 NAC -4 NAC -3 2 NAC -2 2 NAC -1 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE ..I.. DEVICE LOOP 0 0 0 0 0T FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY <'S' CABLE) 470 OHMS �IN EOL T INPU' (+9-) 9 f9 9 TSM -1 Q o¢ oo •( oRo x ce00 1.2.3.4.5, �Mo cccIco TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCAL FROM1FACP <V❑ICE CIRCUIT) C'V' CABLE) u � (STROBE) SPEAKER v () STR❑BE) EARTH GROUND 0 -3►(+)TO NEXT DEVICE OR } "(-) STOP IF LAST DEVICE (STROBE( -) SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE ❑R END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERT1IN TEMPERATU E: +32' F (0' C) TO 100 F 3' C) HUMIDITY: O-9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CON%&JNCTION WITH DUCT HOUSINGS AD -11P OR AD -11)83R DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F— > ( ) DATA OUT 1 > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID — CEILING HARD LID SPEAKER SUPPORT TIL- BRIDGE /- 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \, CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING. FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT Ii1 / C,11 TO NEXT DEVICE 0 0 -------CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE --- SUSPENDED ILLUMINATED CEILING DO \O O INSTA ADDRESSABLE H \ DEVICES \TI_ PREPROG AM h/ E DEVICES ADDRE _L AT \C D WITH SS. Pr) 0' tti cc z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS co co Qa �W 2z CE 0 zz 2 w= Z 517C (Pp< Qo'- � D F - (.9 z z 3 0 0 z 0 z E U SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .OB NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reservedk FA -02 EOL—S1 20.21V NORTH VITAMIN WORLD WESTFIELDSOUTHCENTER MALL SCALE 118"=1' FLAG 0 ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT O N STA LL ADDRESSABLE IN T JFVICES UNTIL DEPROGRAMMED W DEVICES ADDRESS. AH\G TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z ti) z 615, gg z OD 0' z 0 z_ LI" J F- W O w F - (I) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION (SHOP DRAWINGS DATE 5/15/08 J co co Q T Q w z O Wo > wi =Q co Q dog D I- fSCALE:1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: V.0B NUMBER: SHEET FA -03} LL Cr: A A A Li• ---------- CN LJJ LLJ I 11 ___- • . 0 E3I ()I:: HAWAII C�RLON'S JE WE LE R S M P S. FIELDS CLAIRE'S JOURNEYS BASKIN ROBBINS SUN C1. ASS H U T CH000-- LATE 3 AR a_ KITS CAMERA M 0 TH ERHOOD MA. TER I\ 1 [iFF:::iG PAGODA LIDS I - Y .0 - S P EC'S: I N C BANI• I Ty TR A sH ,• SP R 1155 -------- (-1 • i• c • KIDS c:0 0 -1-1 OCKER r 1440 NORTH 1200 >- c:21 cri 0_ 1210] cj- r-- ----- VITAMIN WORLD WESTFIELD SOUTHCENTER MALL 0 Cr) a. J 1 2_ 30 1235 Cr(_). LiJ (.1) LJ 0 EXISTING FOOTLOCKER. TFJ;;; A N --L 11300 0 11 SCALE 11324 EX RISER DIAGRAM 1 SYSTEM CALCULATIONS BATTERY SIZING CALCULATION I NVI Notification Appliance Circuit Detail ) VITAMIN WORLD VITAMIN WORLD PROJECT: FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DATE CO 0 ",..... Ln in VITAMIN WORLD Wire Resistance 1.62 19 Panel: June 3,2008 CURRENT TOTAL 303 Date: CIRCUIT: Current Load: Standby: Alarm: Current Load: Standby: Alarm: Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Deice Type 0.62 Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total 175 HFP-11 0.0022 0.0022 0.0023 (I) 0.30 0 SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.19 0.03 0.030 0.030 0 HTR -R 2 0.009600 0.0096 0.021 0.042 0 SET -MC @15CD 318 1 0.064 0.064 EOL Voltage HTRI-D 0 SET -HMC @185CD 0.001600 0 0.0035 SET -MC @30CD (20.4 - E) 1 Z-MC@15CD 0.098 64 ICP -B6 0.005 0 Z-MC@30CD SET -MC @75CD 0 1 0.175 0.175 0 SET-MC-CW@110CD 233 0 SET -MC ©110CD DEVICES= 3 TOTAL m A= 0.233 12 191 SET-HMC-C@115CD 303 0.318 SET-HMC-C@135CD Notification Appliance Circuit Detail 0.318 WESTFIELD SOUTHCENTER MALL VITAMIN WORLD 0.0731 Amps 0.106 Amps SET-HMC-C@185CD CURRENT TOTAL= 3.6 0.445 CIRCUIT: SPEAKER CIRCUIT ZR -MC ©15CD ZR -MC @30CD QTY 1 Alarm Current Alarm Total Wire Size 0.064 0.064 Circuit Total Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0.098 ( R ) 0.99 HCP 1 0 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours Total Device Load Amps (1) 0.00 0.03 Amps 0.333 Amps 25% Derating= 2.204 Amp -hours 0 0 0 Voltage Drop Standby Current Load: 0.00 0.03 Amps 0 For 24 Hours = 0.720 Amp -hours (E= I* R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) Alarm Current Load: 0 0.333 Amps 0 For 5 Minutes= 0.028 Amp -hours Total System Current Load: 2.204 Amp -hours 0 TOTAL m A= 0 3.6 14 191 20.396451981 3.6 DE\iICES= 25% Derating= 0.935 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.935 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH _ BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Ri hts Reserved 14-) co 0' 4X I74 3 IST AVE RELEASE/REVISIONS REV. BY: I NVI Notification Appliance Circuit Detail ) DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE CO 0 ",..... Ln in VITAMIN WORLD Wire Resistance 1.62 19 Panel: June 3,2008 CURRENT TOTAL 303 Date: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 1 SET -MC @15CD 64 64 Total Wire Resistance ( R ) 0.62 0 SET -MC @30CD 98 0 ( WL * 2) *(R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (I) 0.30 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.19 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.21 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL m A= 303 12 191 20.21249148 303 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL VITAMIN WORLD Wire Resistance 2.58 Panel: June 3, 2008 CURRENT TOTAL= 3.6 Date: CIRCUIT: SPEAKER CIRCUIT QTY Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 1 3.6 Total Wire Resistance ( R ) 0.99 0 1 0 (WL*2)*(R/ft) 0 0 0 Total Device Load Amps (1) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.00 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 0 2 0 TOTAL m A= 0 3.6 14 191 20.396451981 3.6 DE\iICES= VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Ri hts Reserved 14-) co 0' 4X I74 3 IST AVE RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION I SHOP DRAWINGS DATE CO 0 ",..... Ln in 19 <<<<l‹ 1 cr etz cc w z w z 0 > _J 0 w(1) >- (1) >- I 'CALE: 1 /8"= 1 DRAWN BY: 'ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: NUMBER: SHEET FA -04 3 -8" 3'-8" (G,) 12 Lf) co '• Wthout Cort : • As Noted In led [ Per The ,attached l.:lttr 1 nese plans have bean reviewed by Then/hub Then/hubFite t it Prevention Bureau conformance currs�r,L city standards. Acc:.: pi::,nce i fubiect to errors �rnd omissions which do not authorize viatatiao . of aucpted standards and ordinances. The ru `7)Gtlslhifity for the adequacy of desi )n rests totally tih'1tll the designer. Additions, deletions or rr;:visio11s to these drawings after this date will void th :s acceptance end will require a resubmittal of revised drawings for subsequent approval. 3 8„ I /2" x I ' ADA CAP 7-4 3'-5'' [=_1 L ),(N.(1) -- Back to Back 4"x I %2" M.T. 1// 5-11 8'6" 6-3 8'-0" 5-11 Back to Backii 4"x I%2" M.T. 11=1 ii 1i 11/11 2-6 7y2' 1 0 7/2" r ,L\2-6 0 1� L ..-11.10=,. 4'-8" 2'-8" Final acceptance is subject to fietd test and inspection by The Tukwila Fire Prevention Bureau. Date: 6 -to -0_ TUKWILA FIRE DEPARTMENT, Please call: 575.4402 and give this job No. s and exact address for shut' or restoration approval: 6'-0" II 1, II - 1 -i: 1 II 5-10 1-9 1-8 ,iii (Vitamin World: SCALE: /2" = I '-O CONSTRUCTION NOTES: I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "F", WHICH ARE TO BE STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL HANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD SYMBOL LEGEND:) = NEW RECESSED PENDANT ON DROP ® = NEW CONCEALED PENDANT ON DROP S ---S = EXISTING SPRINKLER PIPE TO REMAIN I-5= NEW SPRINKLER PIPING HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3" METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750#* 1/2" ANCHOR w/40# TORQUE: TENSION=440#, SHEAR=750#* 'SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR THRU THREADS 1/4" MIN ROD COUPLING THREADED ROD PIPE SIZE I" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 6" 8" ROD BOLT IMBED DIA. LGTH DEPTH 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 1" GENERAL NOTES: ) I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP 11. ORDINARY HAZARD GROUP 11 SPRINKLER SPACING: 130 ftz. MAX. 2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN. 3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY OTHER. 4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER. 5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. G) OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. 7) NER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, T INC, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACC RDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) IS BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. 8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. SEE PLAN FOR LENGTH NEW BRANCH LINE "FLEXHEAD" FLEXIBLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE CEILING 2 z 6- z W W O No 2 El FILE COPY ii—ADJUSTABLE HUB OUNTING BRACKET iB COSCO STANDARD HANGER LIUIDL A TYPICAL ARMOVER TO NEW SPRINKLER HEAD --- N.T.S. TOLCO FIG. 25 SURGE RESTRAINER TYPE I - FOR I" AND 14' PIPE AND HANGER TYPE 2 - FOR 172" AND 2" PIPE AND HANGER TOLCO MG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY SYMBOL = FIGURE 25 SURGE RESTRAINER bisOFOR STEEL OR CPVC PLASTIC PIPE 3/8' x 3,Y2' LAG SCREW FOR WOOD V x 24' KWIK BOLT FOR CONCRETE --\ I " x /" TEK FOR BARJOIST OR STEEL BEAM r45° MIN. ARGCO OFFSET EYESOCKET BRKT. WHERE LENGTH 1 EXCEEDS I'- 1 0" SYMBOL = 6 LINE RESTRAINT DETAIL NALL THREAD ROD I - I O MAX. PER SINGLE. OTHERWISE ASSEMBLY REQD. BOTH SIDES ' - hANGER RING (UP TO2"PIPE) SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. Reliable G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 9 Reliable Model Fl FR Recessed Pendant 1/2' 1/2' 5.6 Chrome Chrome 155° 3 APPROVALS BY: I TOTAL SPRINKLERS THIS SHEET 12 .00000o. • 00 00 00. • ®® 00O0- • "0000°1' ICosmo Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE www.coscofire.com 10910 117TH Place N.E. Kirkland, Washington 98033 call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE License No: COSCOFP 11 ONM PROJECT: Vitamin World 1119 Southcenter Mall, Suite #1417 Tukwila, Wa. 98188-2823it--9 2118N CONTRACT WITH: Unique Structures LLC 7 Pine Grove Lane Rexford, Ny.12148 PAID dlo �r1 ' *wile Fire D(J�:— DRAWN' TIRE Vitamin World: Sprinkler Piping Plan DATE : June, 2008 SCALE : As Noted DRAWN BY : Justin Johnson MKS — 7957 SHEET NO. FP S' 6/1/