Loading...
HomeMy WebLinkAboutPP - 1120 SOUTHCENTER MALL - AUNTIE ANNES PRETZELS - PERMITS AND PLANS1120 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-291 08-S-283 .4 • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Auntie Anne's Pretzels 1120 Southcenter Mall Permit No.: 08-S-283 Date: June 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. AUNTIE ANNE'S 1315 119-(2°" FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ESHEET TITLE FA -01 SYSTEM I\ FO MATT O \ FA -02 TYPICAL DETAILS - WRI\G A\D VOU \TI \ G FA -03 FRE ALARM SYSTEV FLOO PLA FA -04 SYSTEfi CALCULATIO\S GE\EAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHAT SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL' BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 45 DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING AD DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. L C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING CEILING Q c FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD ❑M MAGNETIC DOOR HOLDER F.B.O. LQ - VERIEY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. JUNCTI❑N BOX F.B.❑, F.B.❑. CCEPTE N/A VERT IN FI D VERIF1 WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIAT❑R TWISTED PAIR W/ SHIELD 4#16 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 . FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATION TWISTED PAIR RATED 4#18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) ABOVE FINISHED FLOOR CONDUIT FILL CHART kVA 0 NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL' BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 45 DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING AD DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. L C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING CEILING Q c FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD ❑M MAGNETIC DOOR HOLDER F.B.O. LQ - VERIEY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. JUNCTI❑N BOX F.B.❑, F.B.❑. CCEPTE N/A VERT IN FI D VERIF1 REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE ed, signed, TukV'4\i artment Pre-test must be presented nspector prior to commencement of Acceptance rca z z c FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS TUKWILA FIRE DEPAR Iavrc.a ll a Please call: 575-440Z and give this job No. 05 - r ba- and exact address for shut* down or restoration approval Copyright 2006 b Guardian Securit S stems, Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing.. L 2.008 Tukwila Fire 26t. 5/ Inc. All Ri • hts Reserved REV. BY: z Q Without Comments v A.F.F. ABOVE FINISHED FLOOR N/A kVA 0 As Noted�yRed N/A Per The Attached Letter F.B.❑. FURNISHED BY OTHERS N/A We4e plans have been rd4 fired by The Tukwila P'11 -4A Prevention Bureau for conformance with current city N/A NOT APPLICABLE N/A ssa// r�dards. Acceptance is sub'ect to errors and 6`fltgsions which do not aufif%�irze violations of ado �d stanaaras and oralnances. The responsibility for the U.O.N. UNLESS OTHERWISE NOTED N/A adequacy of design rests totally with the designer. Nations, deletions or reNcihs to these drawings► tf r this date will void this acceptance and will require a WP WEATHERPROOF DEVICEn N/A fmbmittal of revised dral'As for subsequent apjo' al. Final acceptance is subject to field test and inspection by AS BUILT ADD OR CHANGE N/A IT�hrATukwila Fire PreventiQRureau. N/A f Date. (D o 0 By: Gd A complet€ Fire Dep r_o��ni AS BUILT N/A Cet Lificate to the I REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE ed, signed, TukV'4\i artment Pre-test must be presented nspector prior to commencement of Acceptance rca z z c FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS TUKWILA FIRE DEPAR Iavrc.a ll a Please call: 575-440Z and give this job No. 05 - r ba- and exact address for shut* down or restoration approval Copyright 2006 b Guardian Securit S stems, Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing.. L 2.008 Tukwila Fire 26t. 5/ Inc. All Ri • hts Reserved REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE co 0 0 co CO CO Cf) 2�Z U)Wo�O z ZZ Z cr ow W wog � N Z f� 4-CALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST Go THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE l+ Batom 0 DUCT DETECTOR LOCATI❑N FROM XLS CONTROL PANEL OR +-'"— PREVIOUS ADDRESSABLE DEVIC v END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 GROUND 0 V) 0 O HTRI—R OSTATUS LED 00 0- COM co 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING---•\ TUBE INLET SAMPLING— \ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE '}-AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE (+) STOP IF LAST DEVICE+� FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVICE () RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2; ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. O o v TB1 5 5 o a 123456 HCP TB2 0 0? 65/443 O + 21 J 0 END OF LINE 1 0 DEVICE 0 (3.6K 1/4W) 7 SUPERVISER___i i SWITCH GROUND NOTE: 0 HTRI—D OSTATUS LED CO 0 NOT USED END OF LINE DEVICE 3,6K 1/4W) FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 0 0 0 T 01 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+1— 1 2+2— 2 NC C NO + — + — + — + — + — TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE TIE NAC -4 NAC -3 2 NAC -2 ( NAC -1 UPERVISED WITCH ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0T FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS IM EOL TEM -1 0 0 INC 0 C 9 e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOW FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) v (-Y0 STR❑BE) SPEAKER (+) (,) EARTH GROUND -3►(+)TO NEXT DEVICE OR -->-(-) STOP IF LAST DEVICE (—) STROBE () STROBE SPEAKER (+) (—) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY_ 80" A.F.F. R 0 4S DEEP BOX W/ 1-1/2". EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE JTO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERATIN TEMPERATU E: +32' F 0- C) TO 100' F 311• C) HUMIDITY: b- 9 $$3% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -�► FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) DATA IN (+) > DEVICE IS LISTED FOR MR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE-<- > ( ) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID ---SPEAKER SUPPORT Ti _-- - BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTINGjDROP CEILING) SCALE=NONE JUNCTION BOX \ MOUNTED ON \ CEILING FLEX \ iii: / / / / JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR----- SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE=NONE \--- SUSPENDED ILLUMINATED CEILING DO \OT ADDRESS DEVICES PREPROG D I\ST BLE \ TOAT NC .,INTI_ RAMMED WITH KESS. ;VICES ADD Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 z 0 w w V) w w REV. BY: NVI DESCRIPTION SHOP DRAWINGS w I- < 0 60 Lc) 0 to 5' as<aa 0 Z 0 1.0 oo Tc Cr) Jap 2Z r� [!J if2 (� z Z w= Z cc ow Q W W pg N D T D 0 6ALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 EOL—S1 20.40V FA—BOX l 2S,2V 30 2I / 2S,2V L_J AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL SCALE 10=1' LAG OT S. FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACT❑R, WIRED BY ELECTRICAL CONTRACT❑R, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO N0 INSTAL ADDRESSABLE I N H DEVICES UNTIL 'DREP OGRAvMED W DEVICES ADDRESS. A I\ TH G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Cs/ gib Se ral4IX 0 z 0 c9 z_ w UJ Cf) Lo `" (N.1 Ili N Q CW O tr) W FAX (206) 628-1+990 RELEASE/REVISIONS [REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 6/05/08 1 2<<aaa 1 1 � � L ♦ co L"J Jco T < d) (/) w cc 0 [u [Li (15- z w zz Z a 00) Q Q a=� w wo- Z alr D rD N CC uJ CC SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: % OB NUMBER: SHEET FA -03) f-'; ' S JOURN E -111S E3 . SK R CB BIN I I! r 11 55 C r , '.[!ER:1' k'i C, T F --i F HI 0 f, D N,1 A -.-.:_ ,PIEFRCI \ _; A LIDS 1 13I\jC BAN K, cad 11 60 ELECTRICAL RM RECYCLING S'ORAGE TRASH THI CITY KID S FOoTL0Ch F 1430] :L a. C,5 >-- C1' LJ c) c3 r_ 1' SPR '[7-`il 4-7-1 ------------------------------------- J -------------- 1 Cr) AUNTIE ANNE'S 115 FOOTLOCKER T1A,NCY 0 C --, ?.I r 0 0 0 0 r_; r: 0 0 0 r L 0 n 0 0 7 0 ELECTRICAL RM -- C;F L -_ ESE -ICA i•::F: .= ,(' :;E;: NORTH 7 CALIFORNIA PIZZA KITCHEN • M AC GRILL j RI I-- _l AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL SYSTEM CA z Q Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL I AUNTIE ANNE'S 1100 AUNTIE ANNE'S 1100 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations AUNTIE ANNE'S 1100 Wire Resistance 1.62 Lno Date: June 5, 2008 CURRENT TOTAL= 260 CIRCUIT: SI Current Load: Standby: Alarm: Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Deuce Type Qty Amps Total Amps Total 0.62 Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 SET -MC @75CD 175 0 Total Device Load, Amps (1) AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 SET-HMC-C@115CD HTR -R 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 0.16 0 SET-HMC-C@177CD 0.064 0 HTRI-D 0.001600 0.0035 0 SET -MC @30CD 2 0 0.098 0.196 ICP -B6 EOL Voltage 0.005 0 SET -HMC @185CD 445 0 SET -MC @75CD 0.175 (20.4 - E) 1 Z-MC@15CD 64 64 SET -MC @110CD 0.233 Z-MC@30CD 98 0 SET HMC-C@115CD 0 SET-MC-CW@110CD 233 0.318 DEVICES= 3 SET HMC-C@135CD 260 12 191 0.318 260 0.0731 Amps 0.106 Amps SET HMC-C@185CD ZR -MC @15CD 1 0.445 0.064 0.064 Notification Appliance Circuit Detail Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Panel: AUNTIE ANNE'S 1100 0.098 Wire Resistance 2.58 Date: June 5, 2008 CURRENT TOTAL= 3.6 HCP CIRCUIT: SPEAKER CIRCUIT 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours QTY Device Type Alarm Current Alarm Total 0.03 Amps 0.29 Amps 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Total Device Load, Amps (I) 0.00 0 0 0 1 (Total Cct Load) 0 0 0 •Voltage Drop ( E) 0.00 Alarm Current Load: 0.29 Amps For 5 Minutes= 0.024 Amp -hours Total System Current Load: (E=I*R) 2.204 Amp -hours 0 0 EOL Voltage 20.40 0 0 (20.4 - E) 0 25% Derating= 0.930 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH 0 1 0 DEVICES= 2 TOTAL mA= 3.6 14 Total System Current Load: 20.396451981 3.6 0.930 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION 1;�.iJ -I!\ SCALE 1/32":1' EX RISER DIAGRAM VOLTAGE DROP CALCULATION 0' co N 'D N X TEL. (206) 622-6545 (�) z O (1) w CC C/) ) w J w CC REV. BY: z Q Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE o 0 Panel: AUNTIE ANNE'S 1100 Wire Resistance 1.62 Lno Date: June 5, 2008 CURRENT TOTAL= 260 CIRCUIT: SI a«aa QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.62 2 SET -MC @30CD 98 196 (WL * 2) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.26 0 SET -MC @11 OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.16 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.24 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL mA= 260 12 191 20.2391016 260 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: AUNTIE ANNE'S 1100 Wire Resistance 2.58 Date: June 5, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 1 (Total Cct Load) 0 0 0 •Voltage Drop ( E) 0.00 0 0 0 (E=I*R) 0 0 0 0 EOL Voltage 20.40 0 0 (20.4 - E) 0 0 0 0 1 0 DEVICES= 2 TOTAL mA= 3.6 14 191 20.396451981 3.6 VOLTAGE DROP CALCULATION 0' co N 'D N X TEL. (206) 622-6545 (�) z O (1) w CC C/) ) w J w CC REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE o 0 Lno CD 9 a«aa U) LLI L T CO C� -1 rv,as ,J (an W cc [uw� W ZZZ w= w Z cg 0 Q << W ��CJ. � Z Z D -D 1- 0 J 0 LU CD I -- CD C!) (SCALE: 1/8"=1 ' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: \,..1.9B NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04 i Without Gornmehts 0 As Noted In Red lyr Per The Attachcd Letter 1 nese plans have tar-rmn reviewed by The Tukwila Fire Prevention Bureau for cor:forn 2nre with current city standards. Accopl nci:,I.iL, ,e: t to errors and omissions which ao not auth(.,rizC: violations of adopted opted istanaaras and c)K.IIn.inc,:::.s. The. renorlalbilit)r for the 1 adequacy of d:...:in r .lc t,)t3i' ' vy.W-1 Me designer. Additions, dcii€ oils or rii,vi .i:7n`z $J these drawings atter this date will void tll'r.; <ic,c' pT:=1ncr rid will require a resubmittal of revised di L-:win,J > for subFA.quent approval. li Final acceptance is subject to field test and inspection by 11 The Tukwila Fire Preveniion Bureau. Date: C —5--03 .By: / 31 ' 31-311 2-5 r "%J �9J 4'-0" 8'-0" 5-9 —ly2'x I" 4e/ ADA CAP 12'-0' 4, 10 2-5 13" \\5-2 /21x I11\ ADA CAP I '-5 r), 9J (-0 9J 0 y (Auntie Anne's Pretzels:) SCALE: /2" = 11-0" ILA FIRE DEPARTMENT. lase call: 575.4407, -,rid givethis job s • .,, Id exact address for shut* .4:iwn or restoration aDorova1; NOTICE Vi eld stamps must be inspected before pipe is hung. fro nat paint piping prior to hydrostatic approval" t. = NEW RECESSED PENDANT ON DROP ® = NEW CONCEALED PENDANT ON DROP $---5= EXISTING SPRINKLER PIPE TO REMAIN S ---S = NEW SPRINKLER PIPING (.CONSTRUCTION NOTES: c GENERAL NOTES: ) I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "F", WHICH ARE TO BE STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL HANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD SYMBOL LEGEND:) HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3" METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750#* 1/2" ANCHOR W/40# TORQUE: TENSION=440#, SHEAR=750#* •SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR THRU THREADS 1/4" MIN op ap 11111, 0141.1/"Allk 14,4111fril, 41IPA riff, AP ROD COUPLING THREADED ROD PIPE SIZE I" 1 1/4" 1 I/2" 2" 2 1/2" 3" 4" 6" 8" ROD BOLT IMBED DIA. LGTH DEPTH 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 21/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 13MDL 1" I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP II. ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX. 2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN. 3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY OTHER. 4) ALL WIRING OF SYSTEM DEVICES 15 BY OTHER. 5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. G) OWNER 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. 7) OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) 15 BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. 8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. SEE PLAN FOR LENGTH NEW BRANCH LINE "FLEXHEAD" FLEXIBLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE CEILING ADJUSTABLE HUB MOUNTING BRACKET TYPICAL ARMOVER TO NEW . SPRINKLER HEAD --� N.T.S. TOLCO FIG. 25 SURGE RESTRAINER TYPE I - FOR I " AND I/4" PIPE AND HANGER TYPE 2 - FOR I/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 15 DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY SYMBOL = FIGURE 25 SURGE RESTRAINER 7 sOFOR STEEL OR CPVC PLASTIC PIPE 3/8' x V2' LAG SCREW FOR WOOD 3/8' x 2" KWIK BOLT FOR CONCRETE I " x y4' TEK FOR BARJOIST OR STEEL BEAM 45° MIN. ARGCO OFFSET EYESOCKET BRKT. WHERE LENGTH EXCEEDS 1'-10" SYMBOL = 6 LINE RESTRAINT DETAIL NALL THREAD ROD I'- 10" MAX. PER SINGLE. OTHERWISE ASSEMBLY REQD. BOTH SIDES ��HANGER RING (UP TO2"PIPE) SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE FILE COPY N 153rd S7' SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. Reliable Model F1 FR Recessed Pendant 1/2' 1/2' 5.6 Chrome Chrome 155° 4 Reliable Model G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 5 APPROVALS BY: TOTAL SPRINKLERS THIS SHEET 9 •.0 00. "000000' •® O• I cosco Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 10910 117TH Place N.E. License No: Kirkland, Washington 98033 COSCOFP11ONM call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO'• LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscotre.com PROJECT: Auntie Anne's Pretzels 1120 Southcenter Mall, Suite #1315 Tukwila, Wa. 98188-2823 CONTRACT WITH: Retail Contractors LLC 17150 Tye Street SE, Suite A Monroe, Wa. 98272 DRAWING TIRE PAID c' 'j � Tukwila FIrec 6-11 ISO+ror Auntie Anne's Pretzels: Sprinkler Piping Pian MATE : June, 2008 SCALE : As Noted DRAWN BY : Justin Johnson MKS - 7952 SHEET NO. FP CO 1 1 '-O" L 5'-GY2" (, CD 5'Gy2" 1 '2 u 11-0 172 // 9-03'2 ry 3,-3" O N 2-5 9J 4'-0" 5-9 \--1/2" X 1" 4e.i ADA CAP 4'-7" 10 CO O N '-5 2-5 / -2 — / I/ZR X I H /ADA CAP\ Auntie Anne's Pretzels:) SCALE: /2" = 1 '-0" CONSTRUCTION NOTES: I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "F", WHICH ARE TO BE STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL MANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD SYMBOL LEGEND:) = NEW RECESSED PENDANT ON DROP_ ® = NEW CONCEALED PENDANT ON DROP S ---S= EXISTING SPRINKLER PIPE TO REMAIN 4'-4 = NEW SPRINKLER PIPING HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3" METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750#* 1/2" ANCHOR W/40# TORQUE: TENSION=440#,SHEAR=750#* `SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR THRU THREADS /4" MIN 4110 AP 1111, IMP 41.01.441PA OA! AI 41IP AP -if ROD COUPLING THREADED ROD PIPE ROD BOLT IMBED SIZE DIA. LGTH DEPTH I" 3/8" 3 3/4" 2 1/4" 1 1/4" 3/8" 3 3/4" 2 1/4" 1 1/2" 3/8" 3 3/4" 2 1/4" 2" 3/8" 3 3/4" 2 1/4" 2 1/2" 3/8" 3 3/4" 2 1/4" 3" 3/8" 3 3/4" 2 1/4" 4" 3/8" 3 3/4" 2 1/4" 6" 1/2" 3 3/4" 2 1/4" 8" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 13 MDL GENERAL NOTES:) 1) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP II. ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX. 2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN. 3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY OTHER. 4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER. 5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. G) OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. 7) OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) IS BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. 8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. SEE PLAN FOR LENGTH NEW BRANCH LINE "FLEXHEAD" FLEXIBLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE CEILING Z 0- w w h O LL ADJUSTABLE HUB MOUNTING BRACKET A TYPICAL ARMOVER TO NEW SPRINKLER HEAD N.T.S. TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 - FOR 1" AND 1/4' PIPE AND HANGER TYPE 2 - FOR 1/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY SYMBOL = FIGURE 25 SURGE RESTRAINER % OFOR STEEL OR CPVC PLASTIC PIPE 3/g' x'Y2' LAG SCREW FOR WOOD 3/8' x 2/4' KWIK BOLT FOR CONCRETE I " x /4' TEK FOR BARJOIST OR STEEL BEAM 45° MIN. ARGCO OFFSET --� EYESOCKET BRKT. WHERE LENGTH EXCEEDS I'- 1 0" SYMBOL = 6 LINE RESTRAINT DETAIL NALL THREAD ROD I'- 10" MAX. PER SINGLE. OTHERWISE ASSEMBLY REQD. BOTH SIDES ��HANGER RING ( UP TO 2" PIPE) SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE LE JOB SITE os - REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. Reliable Model F1 FR Recessed Pendant 1/7' 1/2' 5.6 Chrome Chrome 155° 4 Reliable Model G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 5 APPROVALS BY: l TOTAL SPRINKLERS THIS SHEET 9 ;• o0 0.. "00000' X00 00 00 I cosco Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE www.coscofire.com 10910 117TH Place N.E. Kirkland, Washington 98033 call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE License No: COSCOFP110NM PROJECT: Auntie Anne's Pretzels 1120 Southcenter Mall, Suite #1315 Tukwila, Wa. 98188-2823 CONTRACT WITH: Retail Contractors LLC 17150 Tye Street SE, Suite A Monroe, Wa. 98272 DRAWING TITLE Auntie Anne's Pretzels: Sprinkler Piping Pian DATE : June, 2008 SCALE : As Noted DRAWN BY : Justin Johnson mKs - 7952 SHEET NO, FP 1120 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-291 08-S-283 .4 • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Auntie Anne's Pretzels 1120 Southcenter Mall Permit No.: 08-S-283 Date: June 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. AUNTIE ANNE'S 1315 119-(2°" FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ESHEET TITLE FA -01 SYSTEM I\ FO MATT O \ FA -02 TYPICAL DETAILS - WRI\G A\D VOU \TI \ G FA -03 FRE ALARM SYSTEV FLOO PLA FA -04 SYSTEfi CALCULATIO\S GE\EAL), �ISE�, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHAT SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL' BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 45 DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING AD DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. L C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING CEILING Q c FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD ❑M MAGNETIC DOOR HOLDER F.B.O. LQ - VERIEY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. JUNCTI❑N BOX F.B.❑, F.B.❑. CCEPTE N/A VERT IN FI D VERIF1 WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIAT❑R TWISTED PAIR W/ SHIELD 4#16 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 . FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATION TWISTED PAIR RATED 4#18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) ABOVE FINISHED FLOOR CONDUIT FILL CHART kVA 0 NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL' BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 45 DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING AD DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. L C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING CEILING Q c FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD ❑M MAGNETIC DOOR HOLDER F.B.O. LQ - VERIEY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. JUNCTI❑N BOX F.B.❑, F.B.❑. CCEPTE N/A VERT IN FI D VERIF1 REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE ed, signed, TukV'4\i artment Pre-test must be presented nspector prior to commencement of Acceptance rca z z c FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS TUKWILA FIRE DEPAR Iavrc.a ll a Please call: 575-440Z and give this job No. 05 - r ba- and exact address for shut* down or restoration approval Copyright 2006 b Guardian Securit S stems, Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing.. L 2.008 Tukwila Fire 26t. 5/ Inc. All Ri • hts Reserved REV. BY: z Q Without Comments v A.F.F. ABOVE FINISHED FLOOR N/A kVA 0 As Noted�yRed N/A Per The Attached Letter F.B.❑. FURNISHED BY OTHERS N/A We4e plans have been rd4 fired by The Tukwila P'11 -4A Prevention Bureau for conformance with current city N/A NOT APPLICABLE N/A ssa// r�dards. Acceptance is sub'ect to errors and 6`fltgsions which do not aufif%�irze violations of ado �d stanaaras and oralnances. The responsibility for the U.O.N. UNLESS OTHERWISE NOTED N/A adequacy of design rests totally with the designer. Nations, deletions or reNcihs to these drawings► tf r this date will void this acceptance and will require a WP WEATHERPROOF DEVICEn N/A fmbmittal of revised dral'As for subsequent apjo' al. Final acceptance is subject to field test and inspection by AS BUILT ADD OR CHANGE N/A IT�hrATukwila Fire PreventiQRureau. N/A f Date. (D o 0 By: Gd A complet€ Fire Dep r_o��ni AS BUILT N/A Cet Lificate to the I REMOVE BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE ed, signed, TukV'4\i artment Pre-test must be presented nspector prior to commencement of Acceptance rca z z c FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS TUKWILA FIRE DEPAR Iavrc.a ll a Please call: 575-440Z and give this job No. 05 - r ba- and exact address for shut* down or restoration approval Copyright 2006 b Guardian Securit S stems, Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing.. L 2.008 Tukwila Fire 26t. 5/ Inc. All Ri • hts Reserved REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE co 0 0 co CO CO Cf) 2�Z U)Wo�O z ZZ Z cr ow W wog � N Z f� 4-CALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST Go THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE l+ Batom 0 DUCT DETECTOR LOCATI❑N FROM XLS CONTROL PANEL OR +-'"— PREVIOUS ADDRESSABLE DEVIC v END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 GROUND 0 V) 0 O HTRI—R OSTATUS LED 00 0- COM co 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING---•\ TUBE INLET SAMPLING— \ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE '}-AC POWER SOURCE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE (+) STOP IF LAST DEVICE+� FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVICE () RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 riA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2; ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. O o v TB1 5 5 o a 123456 HCP TB2 0 0? 65/443 O + 21 J 0 END OF LINE 1 0 DEVICE 0 (3.6K 1/4W) 7 SUPERVISER___i i SWITCH GROUND NOTE: 0 HTRI—D OSTATUS LED CO 0 NOT USED END OF LINE DEVICE 3,6K 1/4W) FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 0 0 0 T 01 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+1— 1 2+2— 2 NC C NO + — + — + — + — + — TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE TIE NAC -4 NAC -3 2 NAC -2 ( NAC -1 UPERVISED WITCH ( FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0T FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS IM EOL TEM -1 0 0 INC 0 C 9 e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOW FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) v (-Y0 STR❑BE) SPEAKER (+) (,) EARTH GROUND -3►(+)TO NEXT DEVICE OR -->-(-) STOP IF LAST DEVICE (—) STROBE () STROBE SPEAKER (+) (—) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY_ 80" A.F.F. R 0 4S DEEP BOX W/ 1-1/2". EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE JTO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERATIN TEMPERATU E: +32' F 0- C) TO 100' F 311• C) HUMIDITY: b- 9 $$3% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -�► FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) DATA IN (+) > DEVICE IS LISTED FOR MR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE-<- > ( ) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID ---SPEAKER SUPPORT Ti _-- - BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTINGjDROP CEILING) SCALE=NONE JUNCTION BOX \ MOUNTED ON \ CEILING FLEX \ iii: / / / / JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR----- SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE=NONE \--- SUSPENDED ILLUMINATED CEILING DO \OT ADDRESS DEVICES PREPROG D I\ST BLE \ TOAT NC .,INTI_ RAMMED WITH KESS. ;VICES ADD Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 z 0 w w V) w w REV. BY: NVI DESCRIPTION SHOP DRAWINGS w I- < 0 60 Lc) 0 to 5' as<aa 0 Z 0 1.0 oo Tc Cr) Jap 2Z r� [!J if2 (� z Z w= Z cc ow Q W W pg N D T D 0 6ALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -02 EOL—S1 20.40V FA—BOX l 2S,2V 30 2I / 2S,2V L_J AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL SCALE 10=1' LAG OT S. FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACT❑R, WIRED BY ELECTRICAL CONTRACT❑R, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO N0 INSTAL ADDRESSABLE I N H DEVICES UNTIL 'DREP OGRAvMED W DEVICES ADDRESS. A I\ TH G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Cs/ gib Se ral4IX 0 z 0 c9 z_ w UJ Cf) Lo `" (N.1 Ili N Q CW O tr) W FAX (206) 628-1+990 RELEASE/REVISIONS [REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 6/05/08 1 2<<aaa 1 1 � � L ♦ co L"J Jco T < d) (/) w cc 0 [u [Li (15- z w zz Z a 00) Q Q a=� w wo- Z alr D rD N CC uJ CC SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: % OB NUMBER: SHEET FA -03) f-'; ' S JOURN E -111S E3 . SK R CB BIN I I! r 11 55 C r , '.[!ER:1' k'i C, T F --i F HI 0 f, D N,1 A -.-.:_ ,PIEFRCI \ _; A LIDS 1 13I\jC BAN K, cad 11 60 ELECTRICAL RM RECYCLING S'ORAGE TRASH THI CITY KID S FOoTL0Ch F 1430] :L a. C,5 >-- C1' LJ c) c3 r_ 1' SPR '[7-`il 4-7-1 ------------------------------------- J -------------- 1 Cr) AUNTIE ANNE'S 115 FOOTLOCKER T1A,NCY 0 C --, ?.I r 0 0 0 0 r_; r: 0 0 0 r L 0 n 0 0 7 0 ELECTRICAL RM -- C;F L -_ ESE -ICA i•::F: .= ,(' :;E;: NORTH 7 CALIFORNIA PIZZA KITCHEN • M AC GRILL j RI I-- _l AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL SYSTEM CA z Q Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL I AUNTIE ANNE'S 1100 AUNTIE ANNE'S 1100 FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations AUNTIE ANNE'S 1100 Wire Resistance 1.62 Lno Date: June 5, 2008 CURRENT TOTAL= 260 CIRCUIT: SI Current Load: Standby: Alarm: Current Load: Standby: Alarm: QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Deuce Type Qty Amps Total Amps Total 0.62 Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 SET -MC @75CD 175 0 Total Device Load, Amps (1) AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 SET-HMC-C@115CD HTR -R 2 0.009600 0.0096 0.021 0.042 SET -MC @15CD 0.16 0 SET-HMC-C@177CD 0.064 0 HTRI-D 0.001600 0.0035 0 SET -MC @30CD 2 0 0.098 0.196 ICP -B6 EOL Voltage 0.005 0 SET -HMC @185CD 445 0 SET -MC @75CD 0.175 (20.4 - E) 1 Z-MC@15CD 64 64 SET -MC @110CD 0.233 Z-MC@30CD 98 0 SET HMC-C@115CD 0 SET-MC-CW@110CD 233 0.318 DEVICES= 3 SET HMC-C@135CD 260 12 191 0.318 260 0.0731 Amps 0.106 Amps SET HMC-C@185CD ZR -MC @15CD 1 0.445 0.064 0.064 Notification Appliance Circuit Detail Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Panel: AUNTIE ANNE'S 1100 0.098 Wire Resistance 2.58 Date: June 5, 2008 CURRENT TOTAL= 3.6 HCP CIRCUIT: SPEAKER CIRCUIT 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours QTY Device Type Alarm Current Alarm Total 0.03 Amps 0.29 Amps 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Total Device Load, Amps (I) 0.00 0 0 0 1 (Total Cct Load) 0 0 0 •Voltage Drop ( E) 0.00 Alarm Current Load: 0.29 Amps For 5 Minutes= 0.024 Amp -hours Total System Current Load: (E=I*R) 2.204 Amp -hours 0 0 EOL Voltage 20.40 0 0 (20.4 - E) 0 25% Derating= 0.930 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH 0 1 0 DEVICES= 2 TOTAL mA= 3.6 14 Total System Current Load: 20.396451981 3.6 0.930 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION 1;�.iJ -I!\ SCALE 1/32":1' EX RISER DIAGRAM VOLTAGE DROP CALCULATION 0' co N 'D N X TEL. (206) 622-6545 (�) z O (1) w CC C/) ) w J w CC REV. BY: z Q Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE o 0 Panel: AUNTIE ANNE'S 1100 Wire Resistance 1.62 Lno Date: June 5, 2008 CURRENT TOTAL= 260 CIRCUIT: SI a«aa QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.62 2 SET -MC @30CD 98 196 (WL * 2) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.26 0 SET -MC @11 OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.16 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.24 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL mA= 260 12 191 20.2391016 260 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: AUNTIE ANNE'S 1100 Wire Resistance 2.58 Date: June 5, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance (R) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 1 (Total Cct Load) 0 0 0 •Voltage Drop ( E) 0.00 0 0 0 (E=I*R) 0 0 0 0 EOL Voltage 20.40 0 0 (20.4 - E) 0 0 0 0 1 0 DEVICES= 2 TOTAL mA= 3.6 14 191 20.396451981 3.6 VOLTAGE DROP CALCULATION 0' co N 'D N X TEL. (206) 622-6545 (�) z O (1) w CC C/) ) w J w CC REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE o 0 Lno CD 9 a«aa U) LLI L T CO C� -1 rv,as ,J (an W cc [uw� W ZZZ w= w Z cg 0 Q << W ��CJ. � Z Z D -D 1- 0 J 0 LU CD I -- CD C!) (SCALE: 1/8"=1 ' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: \,..1.9B NUMBER: SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04 i Without Gornmehts 0 As Noted In Red lyr Per The Attachcd Letter 1 nese plans have tar-rmn reviewed by The Tukwila Fire Prevention Bureau for cor:forn 2nre with current city standards. Accopl nci:,I.iL, ,e: t to errors and omissions which ao not auth(.,rizC: violations of adopted opted istanaaras and c)K.IIn.inc,:::.s. The. renorlalbilit)r for the 1 adequacy of d:...:in r .lc t,)t3i' ' vy.W-1 Me designer. Additions, dcii€ oils or rii,vi .i:7n`z $J these drawings atter this date will void tll'r.; <ic,c' pT:=1ncr rid will require a resubmittal of revised di L-:win,J > for subFA.quent approval. li Final acceptance is subject to field test and inspection by 11 The Tukwila Fire Preveniion Bureau. Date: C —5--03 .By: / 31 ' 31-311 2-5 r "%J �9J 4'-0" 8'-0" 5-9 —ly2'x I" 4e/ ADA CAP 12'-0' 4, 10 2-5 13" \\5-2 /21x I11\ ADA CAP I '-5 r), 9J (-0 9J 0 y (Auntie Anne's Pretzels:) SCALE: /2" = 11-0" ILA FIRE DEPARTMENT. lase call: 575.4407, -,rid givethis job s • .,, Id exact address for shut* .4:iwn or restoration aDorova1; NOTICE Vi eld stamps must be inspected before pipe is hung. fro nat paint piping prior to hydrostatic approval" t. = NEW RECESSED PENDANT ON DROP ® = NEW CONCEALED PENDANT ON DROP $---5= EXISTING SPRINKLER PIPE TO REMAIN S ---S = NEW SPRINKLER PIPING (.CONSTRUCTION NOTES: c GENERAL NOTES: ) I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "F", WHICH ARE TO BE STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL HANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD SYMBOL LEGEND:) HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3" METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750#* 1/2" ANCHOR W/40# TORQUE: TENSION=440#, SHEAR=750#* •SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR THRU THREADS 1/4" MIN op ap 11111, 0141.1/"Allk 14,4111fril, 41IPA riff, AP ROD COUPLING THREADED ROD PIPE SIZE I" 1 1/4" 1 I/2" 2" 2 1/2" 3" 4" 6" 8" ROD BOLT IMBED DIA. LGTH DEPTH 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 21/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 3/8" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 13MDL 1" I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP II. ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX. 2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN. 3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY OTHER. 4) ALL WIRING OF SYSTEM DEVICES 15 BY OTHER. 5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. G) OWNER 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. 7) OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) 15 BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. 8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. SEE PLAN FOR LENGTH NEW BRANCH LINE "FLEXHEAD" FLEXIBLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE CEILING ADJUSTABLE HUB MOUNTING BRACKET TYPICAL ARMOVER TO NEW . SPRINKLER HEAD --� N.T.S. TOLCO FIG. 25 SURGE RESTRAINER TYPE I - FOR I " AND I/4" PIPE AND HANGER TYPE 2 - FOR I/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 15 DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY SYMBOL = FIGURE 25 SURGE RESTRAINER 7 sOFOR STEEL OR CPVC PLASTIC PIPE 3/8' x V2' LAG SCREW FOR WOOD 3/8' x 2" KWIK BOLT FOR CONCRETE I " x y4' TEK FOR BARJOIST OR STEEL BEAM 45° MIN. ARGCO OFFSET EYESOCKET BRKT. WHERE LENGTH EXCEEDS 1'-10" SYMBOL = 6 LINE RESTRAINT DETAIL NALL THREAD ROD I'- 10" MAX. PER SINGLE. OTHERWISE ASSEMBLY REQD. BOTH SIDES ��HANGER RING (UP TO2"PIPE) SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE FILE COPY N 153rd S7' SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. Reliable Model F1 FR Recessed Pendant 1/2' 1/2' 5.6 Chrome Chrome 155° 4 Reliable Model G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 5 APPROVALS BY: TOTAL SPRINKLERS THIS SHEET 9 •.0 00. "000000' •® O• I cosco Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 10910 117TH Place N.E. License No: Kirkland, Washington 98033 COSCOFP11ONM call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO'• LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscotre.com PROJECT: Auntie Anne's Pretzels 1120 Southcenter Mall, Suite #1315 Tukwila, Wa. 98188-2823 CONTRACT WITH: Retail Contractors LLC 17150 Tye Street SE, Suite A Monroe, Wa. 98272 DRAWING TIRE PAID c' 'j � Tukwila FIrec 6-11 ISO+ror Auntie Anne's Pretzels: Sprinkler Piping Pian MATE : June, 2008 SCALE : As Noted DRAWN BY : Justin Johnson MKS - 7952 SHEET NO. FP CO 1 1 '-O" L 5'-GY2" (, CD 5'Gy2" 1 '2 u 11-0 172 // 9-03'2 ry 3,-3" O N 2-5 9J 4'-0" 5-9 \--1/2" X 1" 4e.i ADA CAP 4'-7" 10 CO O N '-5 2-5 / -2 — / I/ZR X I H /ADA CAP\ Auntie Anne's Pretzels:) SCALE: /2" = 1 '-0" CONSTRUCTION NOTES: I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "F", WHICH ARE TO BE STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL MANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD SYMBOL LEGEND:) = NEW RECESSED PENDANT ON DROP_ ® = NEW CONCEALED PENDANT ON DROP S ---S= EXISTING SPRINKLER PIPE TO REMAIN 4'-4 = NEW SPRINKLER PIPING HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3" METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750#* 1/2" ANCHOR W/40# TORQUE: TENSION=440#,SHEAR=750#* `SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR THRU THREADS /4" MIN 4110 AP 1111, IMP 41.01.441PA OA! AI 41IP AP -if ROD COUPLING THREADED ROD PIPE ROD BOLT IMBED SIZE DIA. LGTH DEPTH I" 3/8" 3 3/4" 2 1/4" 1 1/4" 3/8" 3 3/4" 2 1/4" 1 1/2" 3/8" 3 3/4" 2 1/4" 2" 3/8" 3 3/4" 2 1/4" 2 1/2" 3/8" 3 3/4" 2 1/4" 3" 3/8" 3 3/4" 2 1/4" 4" 3/8" 3 3/4" 2 1/4" 6" 1/2" 3 3/4" 2 1/4" 8" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 COSCO STANDARD HANGER 13 MDL GENERAL NOTES:) 1) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP II. ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX. 2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN. 3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY OTHER. 4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER. 5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. G) OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. 7) OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) IS BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. 8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. SEE PLAN FOR LENGTH NEW BRANCH LINE "FLEXHEAD" FLEXIBLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE CEILING Z 0- w w h O LL ADJUSTABLE HUB MOUNTING BRACKET A TYPICAL ARMOVER TO NEW SPRINKLER HEAD N.T.S. TOLCO FIG. 25 SURGE RESTRAINER TYPE 1 - FOR 1" AND 1/4' PIPE AND HANGER TYPE 2 - FOR 1/2" AND 2" PIPE AND HANGER TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS IT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACTIVITY SYMBOL = FIGURE 25 SURGE RESTRAINER % OFOR STEEL OR CPVC PLASTIC PIPE 3/g' x'Y2' LAG SCREW FOR WOOD 3/8' x 2/4' KWIK BOLT FOR CONCRETE I " x /4' TEK FOR BARJOIST OR STEEL BEAM 45° MIN. ARGCO OFFSET --� EYESOCKET BRKT. WHERE LENGTH EXCEEDS I'- 1 0" SYMBOL = 6 LINE RESTRAINT DETAIL NALL THREAD ROD I'- 10" MAX. PER SINGLE. OTHERWISE ASSEMBLY REQD. BOTH SIDES ��HANGER RING ( UP TO 2" PIPE) SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE LE JOB SITE os - REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. Reliable Model F1 FR Recessed Pendant 1/7' 1/2' 5.6 Chrome Chrome 155° 4 Reliable Model G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 5 APPROVALS BY: l TOTAL SPRINKLERS THIS SHEET 9 ;• o0 0.. "00000' X00 00 00 I cosco Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE www.coscofire.com 10910 117TH Place N.E. Kirkland, Washington 98033 call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE License No: COSCOFP110NM PROJECT: Auntie Anne's Pretzels 1120 Southcenter Mall, Suite #1315 Tukwila, Wa. 98188-2823 CONTRACT WITH: Retail Contractors LLC 17150 Tye Street SE, Suite A Monroe, Wa. 98272 DRAWING TITLE Auntie Anne's Pretzels: Sprinkler Piping Pian DATE : June, 2008 SCALE : As Noted DRAWN BY : Justin Johnson mKs - 7952 SHEET NO, FP