FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Auntie Anne's Pretzels
1120 Southcenter Mall
Permit No.: 08-S-283
Date: June 5, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ` of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 1/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to any sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
AUNTIE ANNE'S 1315 119-(2°"
FIRE ALARM SYSTEM
TUKWILA, WASHINGTON
SHEET INDEX
GENERAL NOTES
SYMBOLS LEGEND
SHEET \UM3ESHEET TITLE
FA -01
SYSTEM I\ FO MATT O \
FA -02
TYPICAL DETAILS - WRI\G A\D VOU
\TI \ G
FA -03
FRE ALARM SYSTEV FLOO PLA
FA -04
SYSTEfi CALCULATIO\S
GE\EAL), �ISE�, SITE PLA\
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHAT
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL'
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
1
2
EX
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS 45 DEEP
VERIFY
IN FIELD
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS 4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS 4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS 4S DEEP
VERIFY
IN FIELD
B
LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
AD
DUCT SMOKE
DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
SET -MC -W SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -HMC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
L
C
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
CEILING
Q
c
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
FIRE ALARM
SPEAKER
(CEILING MOUNT)
SET -CW
SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
B
WP
MR
FIRE ALARM
SPEAKER
(WALL MOUNT)
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -W
SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
❑M
MAGNETIC
DOOR HOLDER
F.B.O.
LQ
- VERIEY
IN FIELD
FA JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
JUNCTI❑N BOX
F.B.❑,
F.B.❑.
CCEPTE
N/A
VERT
IN FI D
VERIF1
WIRE DESIGNATI❑N
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
D
H
P
S
A
V
I
X
UD
UI
M
B
DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET)
DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET)
DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET)
STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
ANNUNCIAT❑R TWISTED PAIR W/ SHIELD 4#16 FPL/FPLR RED (JACKET)
SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET)
REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET)
LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 . FPL/FPLR RED (JACKET)
UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET)
UNDERGROUND INITIATION TWISTED PAIR RATED 4#18 FPL/FPLR RED (JACKET)
DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET)
BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET)
ABOVE FINISHED
FLOOR
CONDUIT FILL CHART
kVA
0
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL'
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
1
2
EX
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS 45 DEEP
VERIFY
IN FIELD
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS 4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS 4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS 4S DEEP
VERIFY
IN FIELD
B
LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
AD
DUCT SMOKE
DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
SET -MC -W SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -HMC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
L
C
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
CEILING
Q
c
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
FIRE ALARM
SPEAKER
(CEILING MOUNT)
SET -CW
SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
B
WP
MR
FIRE ALARM
SPEAKER
(WALL MOUNT)
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -W
SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
❑M
MAGNETIC
DOOR HOLDER
F.B.O.
LQ
- VERIEY
IN FIELD
FA JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
JUNCTI❑N BOX
F.B.❑,
F.B.❑.
CCEPTE
N/A
VERT
IN FI D
VERIF1
REMOVE
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
OTICE
ed, signed, TukV'4\i
artment Pre-test
must be presented
nspector prior to
commencement of Acceptance
rca
z
z
c
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
TUKWILA FIRE DEPAR Iavrc.a ll a
Please call: 575-440Z
and give this job
No. 05 - r ba-
and exact address for shut*
down or restoration approval
Copyright 2006 b
Guardian Securit S stems,
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing..
L
2.008
Tukwila Fire
26t. 5/
Inc. All Ri • hts Reserved
REV. BY:
z
Q
Without Comments v
A.F.F.
ABOVE FINISHED
FLOOR
N/A
kVA
0
As Noted�yRed N/A
Per The Attached Letter
F.B.❑.
FURNISHED BY
OTHERS
N/A
We4e plans have been rd4 fired by The Tukwila P'11 -4A
Prevention Bureau for conformance with current city
N/A
NOT
APPLICABLE
N/A
ssa// r�dards. Acceptance is sub'ect to errors and
6`fltgsions which do not aufif%�irze violations of ado �d
stanaaras and oralnances. The responsibility for the
U.O.N.
UNLESS OTHERWISE
NOTED
N/A
adequacy of design rests totally with the designer.
Nations, deletions or reNcihs to these drawings► tf r
this date will void this acceptance and will require a
WP
WEATHERPROOF
DEVICEn
N/A
fmbmittal of revised dral'As for subsequent apjo' al.
Final acceptance is subject to field test and inspection by
AS BUILT
ADD OR CHANGE
N/A
IT�hrATukwila Fire PreventiQRureau. N/A
f
Date. (D o 0 By: Gd
A complet€
Fire Dep
r_o��ni
AS BUILT
N/A
Cet Lificate
to the I
REMOVE
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
OTICE
ed, signed, TukV'4\i
artment Pre-test
must be presented
nspector prior to
commencement of Acceptance
rca
z
z
c
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
TUKWILA FIRE DEPAR Iavrc.a ll a
Please call: 575-440Z
and give this job
No. 05 - r ba-
and exact address for shut*
down or restoration approval
Copyright 2006 b
Guardian Securit S stems,
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing..
L
2.008
Tukwila Fire
26t. 5/
Inc. All Ri • hts Reserved
REV. BY:
z
Q
DESCRIPTION
SHOP DRAWINGS
DATE
co
0
0
co
CO
CO
Cf)
2�Z
U)Wo�O
z ZZ
Z cr ow
W wog
� N
Z
f�
4-CALE: 1/8" =1 '
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
JOB NUMBER:
SHEET
FA -01
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
BEND OR OTHER
OBSTRUCTION
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST Go THRU THE DUCT AND BE CAPPED.
6-10 DUCT
EQUIVALENT
DIAMETERS
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
LABEL SCALE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE
STOP IF LAST DEVICE
l+
Batom
0
DUCT DETECTOR
LOCATI❑N
FROM XLS CONTROL PANEL OR +-'"—
PREVIOUS ADDRESSABLE DEVIC v
END OF LINE DEVICE(3.6K 1/4W)
SUPERVISED SWITCH
1
GROUND
0
V)
0
O
HTRI—R
OSTATUS LED
00
0- COM
co
0
N.0
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
0
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
SCALE (BACKGOUND MUSIC SHUTDOWN)
PREVI❑US ADDRESSABLE[
DEVICE
TO NEXT ADDRESSABLE
DEVICE
+
NOTE 11
VOLTAGE MAX. -
CURRENT MAX. -
CONT. RES. MAX, -
MAX, CABLE LENGTH -
C (LINE TO LINE) -
C (LINE TO SHIELD) -
MAX. LINE SIZE -
MIN. LINE SIZE -
MUSIC
OUTLET SAMPLING---•\
TUBE
INLET SAMPLING— \
TUBE
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
SCALE=NONE
'}-AC POWER SOURCE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE (+)
STOP IF LAST DEVICE+�
FROM XLS CONTROL PANEL OR
PREVI❑US ADDRESSABLE DEVICE ()
RELAY CONTACTS
(4.0A @ 125VAC)
(4.0A @ 30VDC)
27 VDC
3,5 riA DURING POLLING
10 OHMS
200 FT, (18 AWG)
0,02uF
0,04uF
14 AWG
18 AWG
NOTE 2;
ALL SUPERVISED SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE
DETECTION.
O o v
TB1
5 5 o a
123456
HCP
TB2
0 0?
65/443
O
+
21
J
0
END OF LINE 1 0
DEVICE 0
(3.6K 1/4W)
7
SUPERVISER___i i
SWITCH
GROUND
NOTE:
0
HTRI—D
OSTATUS LED
CO
0
NOT USED
END OF
LINE DEVICE
3,6K 1/4W)
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE)
0
GND N AC
0
0
0
T
01
0
PAD -3
0
00
O
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1+1— 1 2+2— 2 NC C NO + — + — + — + — + —
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
TIE
NAC -4
NAC -3
2 NAC -2
( NAC -1
UPERVISED
WITCH
(
FRONT VIEW
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
NOT USED
REMOTE
DEVICE LOOP
NOT USED
REMOTE
DEVICE LOOP
0
0
0T
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (-)>
470
OHMS
IM
EOL
TEM -1
0
0
INC
0
C
9
e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
SCALE NOW
FROM REMOTE
POWER SUPPLY
C'S' CABLE)
FROM FACP
(VOICE CIRCUIT)
('V' CABLE)
v
(-Y0
STR❑BE)
SPEAKER
(+) (,)
EARTH
GROUND
-3►(+)TO NEXT DEVICE OR
-->-(-) STOP IF LAST DEVICE
(—)
STROBE
()
STROBE
SPEAKER
(+) (—)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
SPEAKER STROBE
OR STROBE ONLY_
80" A.F.F.
R
0
4S DEEP BOX
W/ 1-1/2".
EXTENSION RING
(SPEAKER STROBE)
4S BOX
(STROBE ONLY)
SPEAKER/STROBE
WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
TO NEXT
DEVICE OR
END OF LINE
JTO NEXT
DEVICE OR
END OF LINE
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OPERATIN TEMPERATU E:
+32' F 0- C) TO 100' F 311• C)
HUMIDITY: b- 9 $$3% RELATIVE HUMIDITY,
NON -CONDENSING
HFP-11 SMOKE
DETECTOR
-�► FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
DATA IN ( )
DATA IN (+) >
DEVICE IS LISTED FOR MR VOLOCITY
APPLICATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
DB -11
STANDARD
SMOKE
DETECTOR
BASE
REAR VIEW
TO NEXT DEVICE-<-
> ( ) DATA OUT
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
LABEL SCALE
> (+) DATA OUT
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
HARD LID
CEILING
HARD LID
---SPEAKER SUPPORT Ti _-- -
BRIDGE
4' SQUARE DEEP BOX
WITH 1-1/2' EXTENSION N
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTINGjDROP CEILING)
SCALE=NONE
JUNCTION BOX
\
MOUNTED ON \
CEILING FLEX \
iii:
/
/
/
/
JUNCTI❑N BOX
MOUNTED AGAINST
CEILING SUPPORT
0 0
0 0
IL
TO NEXT DEVICE
CADDY BAR
SMOKE DETECTOR-----
SMOKE
ETECT❑R—
SMOKE DETECTOR MOUNTING
SCALE=NONE
\--- SUSPENDED
ILLUMINATED CEILING
DO \OT
ADDRESS
DEVICES
PREPROG
D
I\ST
BLE \ TOAT NC
.,INTI_
RAMMED WITH
KESS.
;VICES ADD
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
FAX (206) 628-4990
TEL. (206) 622-6545
z
0
w
w
V)
w
w
REV. BY:
NVI
DESCRIPTION
SHOP DRAWINGS
w
I-
<
0
60
Lc)
0
to
5'
as<aa
0
Z
0
1.0 oo
Tc
Cr) Jap
2Z r�
[!J if2 (� z
Z w=
Z cc ow
Q
W W pg
N
D T D
0
6ALE: 1/8" =1 '
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
\OB NUMBER:
SHEET
FA -02
EOL—S1
20.40V
FA—BOX
l
2S,2V
30
2I /
2S,2V
L_J
AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL
SCALE 10=1'
LAG
OT
S.
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS,(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
L❑CATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACT❑R,
WIRED BY ELECTRICAL
CONTRACT❑R,
SIEMENS HTRI-D ADDRESSABLE
INPUT WITH HOOD VENILLAT❑R
FIRE SUPPRESI❑N SYSTEM. FIELD
LOCATE WITHIN 3 FEET OF
C❑NTRL PANEL,
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER, AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT,
DO N0 INSTAL
ADDRESSABLE I N H
DEVICES UNTIL
'DREP OGRAvMED W
DEVICES ADDRESS.
A
I\
TH
G
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
Cs/
gib Se
ral4IX
0
z
0
c9
z_
w
UJ
Cf) Lo
`"
(N.1
Ili N
Q
CW O
tr)
W
FAX (206) 628-1+990
RELEASE/REVISIONS
[REV. BY:
z
DESCRIPTION
SHOP DRAWINGS
DATE
6/05/08 1
2<<aaa
1
1 � �
L ♦ co
L"J Jco
T < d)
(/) w cc 0
[u [Li (15-
z w zz
Z a 00)
Q
Q a=�
w wo-
Z alr
D rD
N
CC
uJ
CC
SCALE: 1/8"=1'
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
% OB NUMBER:
SHEET
FA -03)
f-'; ' S
JOURN E -111S
E3 .
SK
R CB BIN
I
I! r
11 55
C r , '.[!ER:1'
k'i C, T F --i F HI 0 f, D N,1 A -.-.:_
,PIEFRCI \ _;
A
LIDS
1
13I\jC BAN K,
cad
11 60
ELECTRICAL
RM
RECYCLING
S'ORAGE
TRASH
THI CITY
KID S FOoTL0Ch F
1430]
:L
a.
C,5
>--
C1'
LJ
c)
c3
r_
1'
SPR
'[7-`il 4-7-1
-------------------------------------
J
--------------
1
Cr)
AUNTIE ANNE'S 115
FOOTLOCKER
T1A,NCY
0
C
--,
?.I
r
0 0 0 0
r_; r: 0 0
0
r
L
0 n
0
0
7 0
ELECTRICAL
RM
--
C;F L -_ ESE -ICA i•::F: .= ,(' :;E;:
NORTH
7
CALIFORNIA PIZZA KITCHEN •
M AC GRILL
j
RI I--
_l
AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL
SYSTEM CA
z
Q
Notification Appliance Circuit Detail
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
I
AUNTIE ANNE'S 1100
AUNTIE ANNE'S 1100
FACP ADD ONS
SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations
AUNTIE ANNE'S 1100
Wire Resistance 1.62
Lno
Date:
June 5, 2008
CURRENT TOTAL=
260
CIRCUIT:
SI
Current Load:
Standby:
Alarm:
Current Load:
Standby:
Alarm:
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
0
SET -MC @15CD
64
0
Deuce Type
Qty
Amps
Total
Amps
Total
0.62
Device Type
Qty
Amps
Total
Amps
Total
HFP-11
0.0022
0.0022
0.0023
SET -MC @75CD
175
0
Total Device Load, Amps (1)
AD2-P
1
0.0635
0.0635
0.064
0.064
Main System Board
1
0.03
0.03
0.030
0.030
SET-HMC-C@115CD
HTR -R
2
0.009600
0.0096
0.021
0.042
SET -MC @15CD
0.16
0
SET-HMC-C@177CD
0.064
0
HTRI-D
0.001600
0.0035
0
SET -MC @30CD
2
0
0.098
0.196
ICP -B6
EOL Voltage
0.005
0
SET -HMC @185CD
445
0
SET -MC @75CD
0.175
(20.4 - E)
1
Z-MC@15CD
64
64
SET -MC @110CD
0.233
Z-MC@30CD
98
0
SET HMC-C@115CD
0
SET-MC-CW@110CD
233
0.318
DEVICES=
3
SET HMC-C@135CD
260
12
191
0.318
260
0.0731
Amps
0.106
Amps
SET HMC-C@185CD
ZR -MC @15CD
1
0.445
0.064
0.064
Notification Appliance Circuit Detail
Standby Current Load:
0.0731
Amps
For 24 Hours =
1.754
Amp -hours
ZR -MC @30CD
Panel:
AUNTIE ANNE'S 1100
0.098
Wire Resistance 2.58
Date:
June 5, 2008
CURRENT TOTAL=
3.6
HCP
CIRCUIT:
SPEAKER CIRCUIT
0.0015
Alarm Current Load:
0.106
Amps
For 5 Minutes=
0.009
Amp -hours
QTY
Device Type
Alarm Current
Alarm Total
0.03
Amps
0.29
Amps
2
70.7V1/8
1.8
3.6
Total Wire Resistance (R)
0.99
0
0
25% Derating=
2.204
Amp -hours
Standby Current Load:
0.03
Amps
For 24 Hours =
0.720
Amp -hours
Total Device Load, Amps (I)
0.00
0
0
0
1 (Total Cct Load)
0
0
0
•Voltage Drop
( E)
0.00
Alarm Current Load:
0.29
Amps
For 5 Minutes=
0.024
Amp -hours
Total System Current Load:
(E=I*R)
2.204
Amp -hours
0
0
EOL Voltage
20.40
0
0
(20.4 - E)
0
25% Derating=
0.930
Amp -hours
Battery Pair to be Used:
12VDC
Amp -hours
7AH
0
1
0
DEVICES=
2
TOTAL mA=
3.6
14
Total System Current Load:
20.396451981 3.6
0.930
Amp -hours
Battery Pair to be Used:
12VDC
Amp -hours
7AH
BATTERY SIZING CALCULATION
1;�.iJ -I!\
SCALE 1/32":1'
EX
RISER DIAGRAM
VOLTAGE DROP CALCULATION
0'
co
N
'D
N
X
TEL. (206) 622-6545
(�)
z
O
(1)
w
CC
C/)
)
w
J
w
CC
REV. BY:
z
Q
Notification Appliance Circuit Detail
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
DATE
o
0
Panel:
AUNTIE ANNE'S 1100
Wire Resistance 1.62
Lno
Date:
June 5, 2008
CURRENT TOTAL=
260
CIRCUIT:
SI
a«aa
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
0
SET -MC @15CD
64
0
Total Wire Resistance (R)
0.62
2
SET -MC @30CD
98
196
(WL * 2) * (R/ft)
0
SET -MC @75CD
175
0
Total Device Load, Amps (1)
0.26
0
SET -MC @11 OCD
233
0
(Total Cct Load)
0
SET-HMC-C@115CD
318
0
Voltage Drop ( E)
0.16
0
SET-HMC-C@177CD
445
0
(E= I * R)
0
SET -HMC @135CD
318
0
EOL Voltage
20.24
0
SET -HMC @185CD
445
0
(20.4 - E)
1
Z-MC@15CD
64
64
0
Z-MC@30CD
98
0
0
SET-MC-CW@110CD
233
0
DEVICES=
3
TOTAL mA=
260
12
191
20.2391016
260
Notification Appliance Circuit Detail
PROJECT:
WESTFIELD SOUTHCENTER MALL
Panel:
AUNTIE ANNE'S 1100
Wire Resistance 2.58
Date:
June 5, 2008
CURRENT TOTAL=
3.6
CIRCUIT:
SPEAKER CIRCUIT
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
2
70.7V1/8
1.8
3.6
Total Wire Resistance (R)
0.99
0
0
0
(WL*2)*(R/ft)
0
0
0
Total Device Load, Amps (I)
0.00
0
0
0
1 (Total Cct Load)
0
0
0
•Voltage Drop
( E)
0.00
0
0
0
(E=I*R)
0
0
0
0
EOL Voltage
20.40
0
0
(20.4 - E)
0
0
0
0
1
0
DEVICES=
2
TOTAL mA=
3.6
14
191
20.396451981 3.6
VOLTAGE DROP CALCULATION
0'
co
N
'D
N
X
TEL. (206) 622-6545
(�)
z
O
(1)
w
CC
C/)
)
w
J
w
CC
REV. BY:
z
Q
DESCRIPTION
SHOP DRAWINGS
DATE
o
0
Lno
CD
9
a«aa
U)
LLI
L
T CO
C� -1 rv,as ,J
(an W cc
[uw� W
ZZZ
w= w
Z cg
0
Q
<<
W
��CJ.
� Z
Z
D -D 1-
0
J
0
LU
CD I --
CD
C!)
(SCALE: 1/8"=1 '
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
\,..1.9B NUMBER:
SHEET
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
FA -04
i Without Gornmehts
0 As Noted In Red
lyr Per The Attachcd Letter
1 nese plans have tar-rmn reviewed by The Tukwila Fire
Prevention Bureau for cor:forn 2nre with current city
standards. Accopl nci:,I.iL, ,e: t to errors and
omissions which ao not auth(.,rizC: violations of adopted
opted
istanaaras and c)K.IIn.inc,:::.s. The. renorlalbilit)r for the
1 adequacy of d:...:in r .lc t,)t3i' ' vy.W-1 Me designer.
Additions, dcii€ oils or rii,vi .i:7n`z $J these drawings atter
this date will void tll'r.; <ic,c' pT:=1ncr rid will require a
resubmittal of revised di L-:win,J > for subFA.quent approval.
li Final acceptance is subject to field test and inspection by
11 The Tukwila Fire Preveniion Bureau.
Date: C —5--03 .By: / 31 '
31-311
2-5
r
"%J
�9J
4'-0"
8'-0"
5-9
—ly2'x I"
4e/ ADA CAP
12'-0'
4,
10
2-5
13"
\\5-2
/21x I11\
ADA CAP
I '-5
r),
9J
(-0
9J
0
y
(Auntie Anne's Pretzels:)
SCALE: /2" = 11-0"
ILA FIRE DEPARTMENT.
lase call: 575.4407,
-,rid givethis job
s
•
.,, Id exact address for shut*
.4:iwn or restoration aDorova1;
NOTICE
Vi eld stamps must be
inspected before pipe is
hung. fro nat paint piping
prior to hydrostatic
approval"
t. = NEW RECESSED PENDANT ON DROP
® = NEW CONCEALED PENDANT ON DROP
$---5= EXISTING SPRINKLER PIPE TO REMAIN
S ---S = NEW SPRINKLER PIPING
(.CONSTRUCTION NOTES: c GENERAL NOTES: )
I) PIPE:
THREADED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) FITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
FINISH
THREADED: STAR D.I.
3) GROOVED COUPLINGS:
STAR RIGID C-4 UNLESS MARKED WITH AN "F",
WHICH ARE TO BE STAR FLEXIBLE C-3 LW -
ORANGE PAINT FINISH
4) HANGER MATERIAL:
ALL HANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
SYMBOL LEGEND:)
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3" METAL DECK
3/8" ANCHOR w/20# TORQUE:
TENSION=395#, SHEAR=750#*
1/2" ANCHOR W/40# TORQUE:
TENSION=440#, SHEAR=750#*
•SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR THRU THREADS
1/4" MIN
op ap
11111, 0141.1/"Allk
14,4111fril,
41IPA riff, AP
ROD COUPLING
THREADED ROD
PIPE
SIZE
I"
1 1/4"
1 I/2"
2"
2 1/2"
3"
4"
6"
8"
ROD BOLT IMBED
DIA. LGTH DEPTH
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 21/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007
COSCO STANDARD HANGER
13MDL
1"
I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP II.
ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX.
2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN.
3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY
OTHER.
4) ALL WIRING OF SYSTEM DEVICES 15 BY OTHER.
5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
G) OWNER 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
7) OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) 15 BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE
CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING
SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM
ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE
PROTECTION.
SEE PLAN
FOR LENGTH
NEW BRANCH LINE
"FLEXHEAD" FLEXIBLE
DROP CORRUGATED
STAINLESS STEEL
BRAIDED HOSE
CEILING
ADJUSTABLE HUB
MOUNTING BRACKET
TYPICAL ARMOVER TO NEW . SPRINKLER HEAD
--� N.T.S.
TOLCO FIG. 25 SURGE RESTRAINER
TYPE I - FOR I " AND I/4" PIPE AND HANGER
TYPE 2 - FOR I/2" AND 2" PIPE AND HANGER
TOLCO FIG. 25 15 DESIGNED TO BE USED ONLY
WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS
IT OCCURS DURING SPRINKLER HEAD ACTIVATION
OR SEISMIC ACTIVITY
SYMBOL =
FIGURE 25 SURGE RESTRAINER
7 sOFOR STEEL OR CPVC PLASTIC PIPE
3/8' x V2' LAG SCREW FOR WOOD
3/8' x 2" KWIK BOLT FOR CONCRETE
I " x y4' TEK FOR BARJOIST OR STEEL BEAM
45° MIN.
ARGCO OFFSET
EYESOCKET BRKT.
WHERE LENGTH
EXCEEDS 1'-10"
SYMBOL = 6
LINE RESTRAINT DETAIL
NALL THREAD ROD
I'- 10" MAX. PER SINGLE.
OTHERWISE ASSEMBLY
REQD. BOTH SIDES
��HANGER RING
(UP TO2"PIPE)
SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE
FILE COPY
N
153rd
S7'
SPRINKLER HEAD LEGEND:
SYMBOL
S/N
ORIFICE
NPT
K -FACT.
HEAD
FINISH
PLATE
FINISH
TEMP.
QUAN.
Reliable Model F1 FR Recessed Pendant
1/2'
1/2'
5.6
Chrome
Chrome
155°
4
Reliable Model G4A Concealed Pendant
1/2'
1/2'
5.6
Brass
White
165°
5
APPROVALS BY:
TOTAL SPRINKLERS
THIS SHEET
9
•.0 00.
"000000'
•® O•
I
cosco
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
10910 117TH Place N.E. License No:
Kirkland, Washington 98033 COSCOFP11ONM
call (425) 827-9654 • fax (425) 827-7474
SAN DIEGO'• LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
www.coscotre.com
PROJECT:
Auntie Anne's Pretzels
1120 Southcenter Mall, Suite #1315
Tukwila, Wa. 98188-2823
CONTRACT WITH:
Retail Contractors LLC
17150 Tye Street SE, Suite A
Monroe, Wa. 98272
DRAWING TIRE
PAID
c' 'j �
Tukwila FIrec
6-11
ISO+ror
Auntie Anne's Pretzels: Sprinkler Piping Pian
MATE : June, 2008
SCALE : As Noted
DRAWN BY : Justin Johnson
MKS - 7952
SHEET NO.
FP
CO
1 1 '-O"
L
5'-GY2"
(,
CD
5'Gy2"
1
'2 u
11-0
172 //
9-03'2
ry
3,-3"
O
N
2-5
9J
4'-0"
5-9
\--1/2" X 1"
4e.i ADA CAP
4'-7"
10
CO
O
N
'-5
2-5
/
-2
— /
I/ZR X I H
/ADA CAP\
Auntie Anne's Pretzels:)
SCALE: /2" = 1 '-0"
CONSTRUCTION NOTES:
I) PIPE:
THREADED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) FITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
FINISH
THREADED: STAR D.I.
3) GROOVED COUPLINGS:
STAR RIGID C-4 UNLESS MARKED WITH AN "F",
WHICH ARE TO BE STAR FLEXIBLE C-3 LW -
ORANGE PAINT FINISH
4) HANGER MATERIAL:
ALL MANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
SYMBOL LEGEND:)
= NEW RECESSED PENDANT ON DROP_
® = NEW CONCEALED PENDANT ON DROP
S ---S= EXISTING SPRINKLER PIPE TO REMAIN
4'-4 = NEW SPRINKLER PIPING
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3" METAL DECK
3/8" ANCHOR w/20# TORQUE:
TENSION=395#, SHEAR=750#*
1/2" ANCHOR W/40# TORQUE:
TENSION=440#,SHEAR=750#*
`SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR THRU THREADS
/4" MIN
4110 AP
1111, IMP
41.01.441PA
OA! AI
41IP AP -if
ROD COUPLING
THREADED ROD
PIPE ROD BOLT IMBED
SIZE DIA. LGTH DEPTH
I" 3/8" 3 3/4" 2 1/4"
1 1/4" 3/8" 3 3/4" 2 1/4"
1 1/2" 3/8" 3 3/4" 2 1/4"
2" 3/8" 3 3/4" 2 1/4"
2 1/2" 3/8" 3 3/4" 2 1/4"
3" 3/8" 3 3/4" 2 1/4"
4" 3/8" 3 3/4" 2 1/4"
6" 1/2" 3 3/4" 2 1/4"
8" 1/2" 3 3/4" 2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007
COSCO STANDARD HANGER
13 MDL
GENERAL NOTES:)
1) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP II.
ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX.
2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN.
3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY
OTHER.
4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER.
5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
G) OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
7) OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) IS BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE
CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING
SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM
ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE
PROTECTION.
SEE PLAN
FOR LENGTH
NEW BRANCH LINE
"FLEXHEAD" FLEXIBLE
DROP CORRUGATED
STAINLESS STEEL
BRAIDED HOSE
CEILING
Z
0- w
w
h O
LL
ADJUSTABLE HUB
MOUNTING BRACKET
A TYPICAL ARMOVER TO NEW SPRINKLER HEAD
N.T.S.
TOLCO FIG. 25 SURGE RESTRAINER
TYPE 1 - FOR 1" AND 1/4' PIPE AND HANGER
TYPE 2 - FOR 1/2" AND 2" PIPE AND HANGER
TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY
WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS
IT OCCURS DURING SPRINKLER HEAD ACTIVATION
OR SEISMIC ACTIVITY
SYMBOL =
FIGURE 25 SURGE RESTRAINER
% OFOR STEEL OR CPVC PLASTIC PIPE
3/g' x'Y2' LAG SCREW FOR WOOD
3/8' x 2/4' KWIK BOLT FOR CONCRETE
I " x /4' TEK FOR BARJOIST OR STEEL BEAM
45° MIN.
ARGCO OFFSET --�
EYESOCKET BRKT.
WHERE LENGTH
EXCEEDS I'- 1 0"
SYMBOL = 6
LINE RESTRAINT DETAIL
NALL THREAD ROD
I'- 10" MAX. PER SINGLE.
OTHERWISE ASSEMBLY
REQD. BOTH SIDES
��HANGER RING
( UP TO 2" PIPE)
SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE
LE
JOB SITE
os -
REVISIONS
NO.
DESCRIPTION
DATE
BY
SPRINKLER HEAD LEGEND:
SYMBOL
S/N
ORIFICE
NPT
K -FACT.
HEAD
FINISH
PLATE
FINISH
TEMP.
QUAN.
Reliable Model F1 FR Recessed Pendant
1/7'
1/2'
5.6
Chrome
Chrome
155°
4
Reliable Model G4A Concealed Pendant
1/2'
1/2'
5.6
Brass
White
165°
5
APPROVALS BY:
l TOTAL SPRINKLERS
THIS SHEET
9
;• o0 0..
"00000'
X00 00 00
I
cosco
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
www.coscofire.com 10910 117TH Place N.E.
Kirkland, Washington 98033
call (425) 827-9654 • fax (425) 827-7474
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
License No:
COSCOFP110NM
PROJECT:
Auntie Anne's Pretzels
1120 Southcenter Mall, Suite #1315
Tukwila, Wa. 98188-2823
CONTRACT WITH:
Retail Contractors LLC
17150 Tye Street SE, Suite A
Monroe, Wa. 98272
DRAWING TITLE
Auntie Anne's Pretzels: Sprinkler Piping Pian
DATE : June, 2008
SCALE : As Noted
DRAWN BY : Justin Johnson
mKs - 7952
SHEET NO,
FP
1120 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-F-291
08-S-283
.4 •
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Auntie Anne's Pretzels
1120 Southcenter Mall
Permit No.: 08-S-283
Date: June 5, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ` of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 1/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to any sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
AUNTIE ANNE'S 1315 119-(2°"
FIRE ALARM SYSTEM
TUKWILA, WASHINGTON
SHEET INDEX
GENERAL NOTES
SYMBOLS LEGEND
SHEET \UM3ESHEET TITLE
FA -01
SYSTEM I\ FO MATT O \
FA -02
TYPICAL DETAILS - WRI\G A\D VOU
\TI \ G
FA -03
FRE ALARM SYSTEV FLOO PLA
FA -04
SYSTEfi CALCULATIO\S
GE\EAL), �ISE�, SITE PLA\
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHAT
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL'
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
1
2
EX
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS 45 DEEP
VERIFY
IN FIELD
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS 4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS 4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS 4S DEEP
VERIFY
IN FIELD
B
LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
AD
DUCT SMOKE
DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
SET -MC -W SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -HMC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
L
C
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
CEILING
Q
c
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
FIRE ALARM
SPEAKER
(CEILING MOUNT)
SET -CW
SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
B
WP
MR
FIRE ALARM
SPEAKER
(WALL MOUNT)
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -W
SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
❑M
MAGNETIC
DOOR HOLDER
F.B.O.
LQ
- VERIEY
IN FIELD
FA JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
JUNCTI❑N BOX
F.B.❑,
F.B.❑.
CCEPTE
N/A
VERT
IN FI D
VERIF1
WIRE DESIGNATI❑N
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
D
H
P
S
A
V
I
X
UD
UI
M
B
DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET)
DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET)
DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET)
STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
ANNUNCIAT❑R TWISTED PAIR W/ SHIELD 4#16 FPL/FPLR RED (JACKET)
SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET)
REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET)
LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 . FPL/FPLR RED (JACKET)
UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET)
UNDERGROUND INITIATION TWISTED PAIR RATED 4#18 FPL/FPLR RED (JACKET)
DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET)
BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET)
ABOVE FINISHED
FLOOR
CONDUIT FILL CHART
kVA
0
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL'
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. •120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED 4kT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE: ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
2
1
2
EX
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
FIRE ALARM
EX CONTROL PANEL
XLS-V
SIEMENS PROVIDED
66" A.F.F.
TO TOP
FARA
FIRE ALARM
REMOTE ANNUNCIATOR
SDD-C
SIEMENS PROVIDED
66" A.F.F.
TO TOP
BPS
REMOTE BOOSTER
EX POWER SUPPLY
PAD -3
SIEMENS PROVIDED
66" A.F.F.
TO TOP
INTERFACE MODULE HTRI-R
WITH RELAY
SIEMENS 45 DEEP
VERIFY
IN FIELD
DUAL INPUT
INTERFACE MODULE
HTRI-D
SIEMENS 4S DEEP
VERIFY
IN FIELD
HCP
CONTROL POINT
MODULE
HCP
SIEMENS 4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
ZONE MODULE
SIEMENS 4S DEEP
VERIFY
IN FIELD
B
LINEAR BEAM
SMOKE DETECTOR
PBA -1191 SIEMENS PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
AD
DUCT SMOKE
DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
FIRE ALARM
SPEAKER STROBE
(CEILING MOUNT)
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -MC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
SET -MC -W SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
FIRE ALARM
SPEAKER STROBE
(WALL MOUNT)
SET -HMC -CW SIEMENS
4S DEEP BOX CEILING
IN/ 1-1/2" EXT.
L
C
FIRE ALARM
STROBE
(CEILING MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
CEILING
Q
c
FIRE ALARM
STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
FIRE ALARM
SPEAKER
(CEILING MOUNT)
SET -CW
SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
B
WP
MR
FIRE ALARM
SPEAKER
(WALL MOUNT)
FIRE ALARM
STROBE
(WEATHERPROOF)
MULTI -VOLTAGE
CONTROL RELAY
SET -W
SIEMENS 4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
❑M
MAGNETIC
DOOR HOLDER
F.B.O.
LQ
- VERIEY
IN FIELD
FA JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
JUNCTI❑N BOX
F.B.❑,
F.B.❑.
CCEPTE
N/A
VERT
IN FI D
VERIF1
REMOVE
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
OTICE
ed, signed, TukV'4\i
artment Pre-test
must be presented
nspector prior to
commencement of Acceptance
rca
z
z
c
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
TUKWILA FIRE DEPAR Iavrc.a ll a
Please call: 575-440Z
and give this job
No. 05 - r ba-
and exact address for shut*
down or restoration approval
Copyright 2006 b
Guardian Securit S stems,
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing..
L
2.008
Tukwila Fire
26t. 5/
Inc. All Ri • hts Reserved
REV. BY:
z
Q
Without Comments v
A.F.F.
ABOVE FINISHED
FLOOR
N/A
kVA
0
As Noted�yRed N/A
Per The Attached Letter
F.B.❑.
FURNISHED BY
OTHERS
N/A
We4e plans have been rd4 fired by The Tukwila P'11 -4A
Prevention Bureau for conformance with current city
N/A
NOT
APPLICABLE
N/A
ssa// r�dards. Acceptance is sub'ect to errors and
6`fltgsions which do not aufif%�irze violations of ado �d
stanaaras and oralnances. The responsibility for the
U.O.N.
UNLESS OTHERWISE
NOTED
N/A
adequacy of design rests totally with the designer.
Nations, deletions or reNcihs to these drawings► tf r
this date will void this acceptance and will require a
WP
WEATHERPROOF
DEVICEn
N/A
fmbmittal of revised dral'As for subsequent apjo' al.
Final acceptance is subject to field test and inspection by
AS BUILT
ADD OR CHANGE
N/A
IT�hrATukwila Fire PreventiQRureau. N/A
f
Date. (D o 0 By: Gd
A complet€
Fire Dep
r_o��ni
AS BUILT
N/A
Cet Lificate
to the I
REMOVE
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
OTICE
ed, signed, TukV'4\i
artment Pre-test
must be presented
nspector prior to
commencement of Acceptance
rca
z
z
c
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
TUKWILA FIRE DEPAR Iavrc.a ll a
Please call: 575-440Z
and give this job
No. 05 - r ba-
and exact address for shut*
down or restoration approval
Copyright 2006 b
Guardian Securit S stems,
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing..
L
2.008
Tukwila Fire
26t. 5/
Inc. All Ri • hts Reserved
REV. BY:
z
Q
DESCRIPTION
SHOP DRAWINGS
DATE
co
0
0
co
CO
CO
Cf)
2�Z
U)Wo�O
z ZZ
Z cr ow
W wog
� N
Z
f�
4-CALE: 1/8" =1 '
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
JOB NUMBER:
SHEET
FA -01
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
BEND OR OTHER
OBSTRUCTION
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST Go THRU THE DUCT AND BE CAPPED.
6-10 DUCT
EQUIVALENT
DIAMETERS
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
LABEL SCALE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE
STOP IF LAST DEVICE
l+
Batom
0
DUCT DETECTOR
LOCATI❑N
FROM XLS CONTROL PANEL OR +-'"—
PREVIOUS ADDRESSABLE DEVIC v
END OF LINE DEVICE(3.6K 1/4W)
SUPERVISED SWITCH
1
GROUND
0
V)
0
O
HTRI—R
OSTATUS LED
00
0- COM
co
0
N.0
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
0
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
SCALE (BACKGOUND MUSIC SHUTDOWN)
PREVI❑US ADDRESSABLE[
DEVICE
TO NEXT ADDRESSABLE
DEVICE
+
NOTE 11
VOLTAGE MAX. -
CURRENT MAX. -
CONT. RES. MAX, -
MAX, CABLE LENGTH -
C (LINE TO LINE) -
C (LINE TO SHIELD) -
MAX. LINE SIZE -
MIN. LINE SIZE -
MUSIC
OUTLET SAMPLING---•\
TUBE
INLET SAMPLING— \
TUBE
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
SCALE=NONE
'}-AC POWER SOURCE
COMBINE ALL SHIELDS AND
IS❑LATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE (+)
STOP IF LAST DEVICE+�
FROM XLS CONTROL PANEL OR
PREVI❑US ADDRESSABLE DEVICE ()
RELAY CONTACTS
(4.0A @ 125VAC)
(4.0A @ 30VDC)
27 VDC
3,5 riA DURING POLLING
10 OHMS
200 FT, (18 AWG)
0,02uF
0,04uF
14 AWG
18 AWG
NOTE 2;
ALL SUPERVISED SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE
DETECTION.
O o v
TB1
5 5 o a
123456
HCP
TB2
0 0?
65/443
O
+
21
J
0
END OF LINE 1 0
DEVICE 0
(3.6K 1/4W)
7
SUPERVISER___i i
SWITCH
GROUND
NOTE:
0
HTRI—D
OSTATUS LED
CO
0
NOT USED
END OF
LINE DEVICE
3,6K 1/4W)
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE)
0
GND N AC
0
0
0
T
01
0
PAD -3
0
00
O
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1+1— 1 2+2— 2 NC C NO + — + — + — + — + —
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
TIE
NAC -4
NAC -3
2 NAC -2
( NAC -1
UPERVISED
WITCH
(
FRONT VIEW
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
NOT USED
REMOTE
DEVICE LOOP
NOT USED
REMOTE
DEVICE LOOP
0
0
0T
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (-)>
470
OHMS
IM
EOL
TEM -1
0
0
INC
0
C
9
e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
SCALE NOW
FROM REMOTE
POWER SUPPLY
C'S' CABLE)
FROM FACP
(VOICE CIRCUIT)
('V' CABLE)
v
(-Y0
STR❑BE)
SPEAKER
(+) (,)
EARTH
GROUND
-3►(+)TO NEXT DEVICE OR
-->-(-) STOP IF LAST DEVICE
(—)
STROBE
()
STROBE
SPEAKER
(+) (—)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
SPEAKER STROBE
OR STROBE ONLY_
80" A.F.F.
R
0
4S DEEP BOX
W/ 1-1/2".
EXTENSION RING
(SPEAKER STROBE)
4S BOX
(STROBE ONLY)
SPEAKER/STROBE
WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
TO NEXT
DEVICE OR
END OF LINE
JTO NEXT
DEVICE OR
END OF LINE
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OPERATIN TEMPERATU E:
+32' F 0- C) TO 100' F 311• C)
HUMIDITY: b- 9 $$3% RELATIVE HUMIDITY,
NON -CONDENSING
HFP-11 SMOKE
DETECTOR
-�► FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
DATA IN ( )
DATA IN (+) >
DEVICE IS LISTED FOR MR VOLOCITY
APPLICATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
DB -11
STANDARD
SMOKE
DETECTOR
BASE
REAR VIEW
TO NEXT DEVICE-<-
> ( ) DATA OUT
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
LABEL SCALE
> (+) DATA OUT
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
HARD LID
CEILING
HARD LID
---SPEAKER SUPPORT Ti _-- -
BRIDGE
4' SQUARE DEEP BOX
WITH 1-1/2' EXTENSION N
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTINGjDROP CEILING)
SCALE=NONE
JUNCTION BOX
\
MOUNTED ON \
CEILING FLEX \
iii:
/
/
/
/
JUNCTI❑N BOX
MOUNTED AGAINST
CEILING SUPPORT
0 0
0 0
IL
TO NEXT DEVICE
CADDY BAR
SMOKE DETECTOR-----
SMOKE
ETECT❑R—
SMOKE DETECTOR MOUNTING
SCALE=NONE
\--- SUSPENDED
ILLUMINATED CEILING
DO \OT
ADDRESS
DEVICES
PREPROG
D
I\ST
BLE \ TOAT NC
.,INTI_
RAMMED WITH
KESS.
;VICES ADD
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
FAX (206) 628-4990
TEL. (206) 622-6545
z
0
w
w
V)
w
w
REV. BY:
NVI
DESCRIPTION
SHOP DRAWINGS
w
I-
<
0
60
Lc)
0
to
5'
as<aa
0
Z
0
1.0 oo
Tc
Cr) Jap
2Z r�
[!J if2 (� z
Z w=
Z cc ow
Q
W W pg
N
D T D
0
6ALE: 1/8" =1 '
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
\OB NUMBER:
SHEET
FA -02
EOL—S1
20.40V
FA—BOX
l
2S,2V
30
2I /
2S,2V
L_J
AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL
SCALE 10=1'
LAG
OT
S.
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS,(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
L❑CATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACT❑R,
WIRED BY ELECTRICAL
CONTRACT❑R,
SIEMENS HTRI-D ADDRESSABLE
INPUT WITH HOOD VENILLAT❑R
FIRE SUPPRESI❑N SYSTEM. FIELD
LOCATE WITHIN 3 FEET OF
C❑NTRL PANEL,
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER, AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT,
DO N0 INSTAL
ADDRESSABLE I N H
DEVICES UNTIL
'DREP OGRAvMED W
DEVICES ADDRESS.
A
I\
TH
G
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
Cs/
gib Se
ral4IX
0
z
0
c9
z_
w
UJ
Cf) Lo
`"
(N.1
Ili N
Q
CW O
tr)
W
FAX (206) 628-1+990
RELEASE/REVISIONS
[REV. BY:
z
DESCRIPTION
SHOP DRAWINGS
DATE
6/05/08 1
2<<aaa
1
1 � �
L ♦ co
L"J Jco
T < d)
(/) w cc 0
[u [Li (15-
z w zz
Z a 00)
Q
Q a=�
w wo-
Z alr
D rD
N
CC
uJ
CC
SCALE: 1/8"=1'
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
% OB NUMBER:
SHEET
FA -03)
f-'; ' S
JOURN E -111S
E3 .
SK
R CB BIN
I
I! r
11 55
C r , '.[!ER:1'
k'i C, T F --i F HI 0 f, D N,1 A -.-.:_
,PIEFRCI \ _;
A
LIDS
1
13I\jC BAN K,
cad
11 60
ELECTRICAL
RM
RECYCLING
S'ORAGE
TRASH
THI CITY
KID S FOoTL0Ch F
1430]
:L
a.
C,5
>--
C1'
LJ
c)
c3
r_
1'
SPR
'[7-`il 4-7-1
-------------------------------------
J
--------------
1
Cr)
AUNTIE ANNE'S 115
FOOTLOCKER
T1A,NCY
0
C
--,
?.I
r
0 0 0 0
r_; r: 0 0
0
r
L
0 n
0
0
7 0
ELECTRICAL
RM
--
C;F L -_ ESE -ICA i•::F: .= ,(' :;E;:
NORTH
7
CALIFORNIA PIZZA KITCHEN •
M AC GRILL
j
RI I--
_l
AUNTIE ANNE'S 1315 WESTFIELD SOUTHCENTER MALL
SYSTEM CA
z
Q
Notification Appliance Circuit Detail
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
I
AUNTIE ANNE'S 1100
AUNTIE ANNE'S 1100
FACP ADD ONS
SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations
AUNTIE ANNE'S 1100
Wire Resistance 1.62
Lno
Date:
June 5, 2008
CURRENT TOTAL=
260
CIRCUIT:
SI
Current Load:
Standby:
Alarm:
Current Load:
Standby:
Alarm:
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
0
SET -MC @15CD
64
0
Deuce Type
Qty
Amps
Total
Amps
Total
0.62
Device Type
Qty
Amps
Total
Amps
Total
HFP-11
0.0022
0.0022
0.0023
SET -MC @75CD
175
0
Total Device Load, Amps (1)
AD2-P
1
0.0635
0.0635
0.064
0.064
Main System Board
1
0.03
0.03
0.030
0.030
SET-HMC-C@115CD
HTR -R
2
0.009600
0.0096
0.021
0.042
SET -MC @15CD
0.16
0
SET-HMC-C@177CD
0.064
0
HTRI-D
0.001600
0.0035
0
SET -MC @30CD
2
0
0.098
0.196
ICP -B6
EOL Voltage
0.005
0
SET -HMC @185CD
445
0
SET -MC @75CD
0.175
(20.4 - E)
1
Z-MC@15CD
64
64
SET -MC @110CD
0.233
Z-MC@30CD
98
0
SET HMC-C@115CD
0
SET-MC-CW@110CD
233
0.318
DEVICES=
3
SET HMC-C@135CD
260
12
191
0.318
260
0.0731
Amps
0.106
Amps
SET HMC-C@185CD
ZR -MC @15CD
1
0.445
0.064
0.064
Notification Appliance Circuit Detail
Standby Current Load:
0.0731
Amps
For 24 Hours =
1.754
Amp -hours
ZR -MC @30CD
Panel:
AUNTIE ANNE'S 1100
0.098
Wire Resistance 2.58
Date:
June 5, 2008
CURRENT TOTAL=
3.6
HCP
CIRCUIT:
SPEAKER CIRCUIT
0.0015
Alarm Current Load:
0.106
Amps
For 5 Minutes=
0.009
Amp -hours
QTY
Device Type
Alarm Current
Alarm Total
0.03
Amps
0.29
Amps
2
70.7V1/8
1.8
3.6
Total Wire Resistance (R)
0.99
0
0
25% Derating=
2.204
Amp -hours
Standby Current Load:
0.03
Amps
For 24 Hours =
0.720
Amp -hours
Total Device Load, Amps (I)
0.00
0
0
0
1 (Total Cct Load)
0
0
0
•Voltage Drop
( E)
0.00
Alarm Current Load:
0.29
Amps
For 5 Minutes=
0.024
Amp -hours
Total System Current Load:
(E=I*R)
2.204
Amp -hours
0
0
EOL Voltage
20.40
0
0
(20.4 - E)
0
25% Derating=
0.930
Amp -hours
Battery Pair to be Used:
12VDC
Amp -hours
7AH
0
1
0
DEVICES=
2
TOTAL mA=
3.6
14
Total System Current Load:
20.396451981 3.6
0.930
Amp -hours
Battery Pair to be Used:
12VDC
Amp -hours
7AH
BATTERY SIZING CALCULATION
1;�.iJ -I!\
SCALE 1/32":1'
EX
RISER DIAGRAM
VOLTAGE DROP CALCULATION
0'
co
N
'D
N
X
TEL. (206) 622-6545
(�)
z
O
(1)
w
CC
C/)
)
w
J
w
CC
REV. BY:
z
Q
Notification Appliance Circuit Detail
DESCRIPTION
PROJECT:
WESTFIELD SOUTHCENTER MALL
DATE
o
0
Panel:
AUNTIE ANNE'S 1100
Wire Resistance 1.62
Lno
Date:
June 5, 2008
CURRENT TOTAL=
260
CIRCUIT:
SI
a«aa
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
0
SET -MC @15CD
64
0
Total Wire Resistance (R)
0.62
2
SET -MC @30CD
98
196
(WL * 2) * (R/ft)
0
SET -MC @75CD
175
0
Total Device Load, Amps (1)
0.26
0
SET -MC @11 OCD
233
0
(Total Cct Load)
0
SET-HMC-C@115CD
318
0
Voltage Drop ( E)
0.16
0
SET-HMC-C@177CD
445
0
(E= I * R)
0
SET -HMC @135CD
318
0
EOL Voltage
20.24
0
SET -HMC @185CD
445
0
(20.4 - E)
1
Z-MC@15CD
64
64
0
Z-MC@30CD
98
0
0
SET-MC-CW@110CD
233
0
DEVICES=
3
TOTAL mA=
260
12
191
20.2391016
260
Notification Appliance Circuit Detail
PROJECT:
WESTFIELD SOUTHCENTER MALL
Panel:
AUNTIE ANNE'S 1100
Wire Resistance 2.58
Date:
June 5, 2008
CURRENT TOTAL=
3.6
CIRCUIT:
SPEAKER CIRCUIT
QTY
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
2
70.7V1/8
1.8
3.6
Total Wire Resistance (R)
0.99
0
0
0
(WL*2)*(R/ft)
0
0
0
Total Device Load, Amps (I)
0.00
0
0
0
1 (Total Cct Load)
0
0
0
•Voltage Drop
( E)
0.00
0
0
0
(E=I*R)
0
0
0
0
EOL Voltage
20.40
0
0
(20.4 - E)
0
0
0
0
1
0
DEVICES=
2
TOTAL mA=
3.6
14
191
20.396451981 3.6
VOLTAGE DROP CALCULATION
0'
co
N
'D
N
X
TEL. (206) 622-6545
(�)
z
O
(1)
w
CC
C/)
)
w
J
w
CC
REV. BY:
z
Q
DESCRIPTION
SHOP DRAWINGS
DATE
o
0
Lno
CD
9
a«aa
U)
LLI
L
T CO
C� -1 rv,as ,J
(an W cc
[uw� W
ZZZ
w= w
Z cg
0
Q
<<
W
��CJ.
� Z
Z
D -D 1-
0
J
0
LU
CD I --
CD
C!)
(SCALE: 1/8"=1 '
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 6/05/08
BACKROUND PLAN PROVIDED BY:
\,..1.9B NUMBER:
SHEET
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved
FA -04
i Without Gornmehts
0 As Noted In Red
lyr Per The Attachcd Letter
1 nese plans have tar-rmn reviewed by The Tukwila Fire
Prevention Bureau for cor:forn 2nre with current city
standards. Accopl nci:,I.iL, ,e: t to errors and
omissions which ao not auth(.,rizC: violations of adopted
opted
istanaaras and c)K.IIn.inc,:::.s. The. renorlalbilit)r for the
1 adequacy of d:...:in r .lc t,)t3i' ' vy.W-1 Me designer.
Additions, dcii€ oils or rii,vi .i:7n`z $J these drawings atter
this date will void tll'r.; <ic,c' pT:=1ncr rid will require a
resubmittal of revised di L-:win,J > for subFA.quent approval.
li Final acceptance is subject to field test and inspection by
11 The Tukwila Fire Preveniion Bureau.
Date: C —5--03 .By: / 31 '
31-311
2-5
r
"%J
�9J
4'-0"
8'-0"
5-9
—ly2'x I"
4e/ ADA CAP
12'-0'
4,
10
2-5
13"
\\5-2
/21x I11\
ADA CAP
I '-5
r),
9J
(-0
9J
0
y
(Auntie Anne's Pretzels:)
SCALE: /2" = 11-0"
ILA FIRE DEPARTMENT.
lase call: 575.4407,
-,rid givethis job
s
•
.,, Id exact address for shut*
.4:iwn or restoration aDorova1;
NOTICE
Vi eld stamps must be
inspected before pipe is
hung. fro nat paint piping
prior to hydrostatic
approval"
t. = NEW RECESSED PENDANT ON DROP
® = NEW CONCEALED PENDANT ON DROP
$---5= EXISTING SPRINKLER PIPE TO REMAIN
S ---S = NEW SPRINKLER PIPING
(.CONSTRUCTION NOTES: c GENERAL NOTES: )
I) PIPE:
THREADED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) FITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
FINISH
THREADED: STAR D.I.
3) GROOVED COUPLINGS:
STAR RIGID C-4 UNLESS MARKED WITH AN "F",
WHICH ARE TO BE STAR FLEXIBLE C-3 LW -
ORANGE PAINT FINISH
4) HANGER MATERIAL:
ALL HANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
SYMBOL LEGEND:)
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3" METAL DECK
3/8" ANCHOR w/20# TORQUE:
TENSION=395#, SHEAR=750#*
1/2" ANCHOR W/40# TORQUE:
TENSION=440#, SHEAR=750#*
•SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR THRU THREADS
1/4" MIN
op ap
11111, 0141.1/"Allk
14,4111fril,
41IPA riff, AP
ROD COUPLING
THREADED ROD
PIPE
SIZE
I"
1 1/4"
1 I/2"
2"
2 1/2"
3"
4"
6"
8"
ROD BOLT IMBED
DIA. LGTH DEPTH
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 21/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007
COSCO STANDARD HANGER
13MDL
1"
I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP II.
ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX.
2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN.
3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY
OTHER.
4) ALL WIRING OF SYSTEM DEVICES 15 BY OTHER.
5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
G) OWNER 15 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
7) OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) 15 BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE
CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING
SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM
ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE
PROTECTION.
SEE PLAN
FOR LENGTH
NEW BRANCH LINE
"FLEXHEAD" FLEXIBLE
DROP CORRUGATED
STAINLESS STEEL
BRAIDED HOSE
CEILING
ADJUSTABLE HUB
MOUNTING BRACKET
TYPICAL ARMOVER TO NEW . SPRINKLER HEAD
--� N.T.S.
TOLCO FIG. 25 SURGE RESTRAINER
TYPE I - FOR I " AND I/4" PIPE AND HANGER
TYPE 2 - FOR I/2" AND 2" PIPE AND HANGER
TOLCO FIG. 25 15 DESIGNED TO BE USED ONLY
WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS
IT OCCURS DURING SPRINKLER HEAD ACTIVATION
OR SEISMIC ACTIVITY
SYMBOL =
FIGURE 25 SURGE RESTRAINER
7 sOFOR STEEL OR CPVC PLASTIC PIPE
3/8' x V2' LAG SCREW FOR WOOD
3/8' x 2" KWIK BOLT FOR CONCRETE
I " x y4' TEK FOR BARJOIST OR STEEL BEAM
45° MIN.
ARGCO OFFSET
EYESOCKET BRKT.
WHERE LENGTH
EXCEEDS 1'-10"
SYMBOL = 6
LINE RESTRAINT DETAIL
NALL THREAD ROD
I'- 10" MAX. PER SINGLE.
OTHERWISE ASSEMBLY
REQD. BOTH SIDES
��HANGER RING
(UP TO2"PIPE)
SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE
FILE COPY
N
153rd
S7'
SPRINKLER HEAD LEGEND:
SYMBOL
S/N
ORIFICE
NPT
K -FACT.
HEAD
FINISH
PLATE
FINISH
TEMP.
QUAN.
Reliable Model F1 FR Recessed Pendant
1/2'
1/2'
5.6
Chrome
Chrome
155°
4
Reliable Model G4A Concealed Pendant
1/2'
1/2'
5.6
Brass
White
165°
5
APPROVALS BY:
TOTAL SPRINKLERS
THIS SHEET
9
•.0 00.
"000000'
•® O•
I
cosco
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
10910 117TH Place N.E. License No:
Kirkland, Washington 98033 COSCOFP11ONM
call (425) 827-9654 • fax (425) 827-7474
SAN DIEGO'• LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
www.coscotre.com
PROJECT:
Auntie Anne's Pretzels
1120 Southcenter Mall, Suite #1315
Tukwila, Wa. 98188-2823
CONTRACT WITH:
Retail Contractors LLC
17150 Tye Street SE, Suite A
Monroe, Wa. 98272
DRAWING TIRE
PAID
c' 'j �
Tukwila FIrec
6-11
ISO+ror
Auntie Anne's Pretzels: Sprinkler Piping Pian
MATE : June, 2008
SCALE : As Noted
DRAWN BY : Justin Johnson
MKS - 7952
SHEET NO.
FP
CO
1 1 '-O"
L
5'-GY2"
(,
CD
5'Gy2"
1
'2 u
11-0
172 //
9-03'2
ry
3,-3"
O
N
2-5
9J
4'-0"
5-9
\--1/2" X 1"
4e.i ADA CAP
4'-7"
10
CO
O
N
'-5
2-5
/
-2
— /
I/ZR X I H
/ADA CAP\
Auntie Anne's Pretzels:)
SCALE: /2" = 1 '-0"
CONSTRUCTION NOTES:
I) PIPE:
THREADED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) FITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
FINISH
THREADED: STAR D.I.
3) GROOVED COUPLINGS:
STAR RIGID C-4 UNLESS MARKED WITH AN "F",
WHICH ARE TO BE STAR FLEXIBLE C-3 LW -
ORANGE PAINT FINISH
4) HANGER MATERIAL:
ALL MANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
SYMBOL LEGEND:)
= NEW RECESSED PENDANT ON DROP_
® = NEW CONCEALED PENDANT ON DROP
S ---S= EXISTING SPRINKLER PIPE TO REMAIN
4'-4 = NEW SPRINKLER PIPING
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3" METAL DECK
3/8" ANCHOR w/20# TORQUE:
TENSION=395#, SHEAR=750#*
1/2" ANCHOR W/40# TORQUE:
TENSION=440#,SHEAR=750#*
`SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR THRU THREADS
/4" MIN
4110 AP
1111, IMP
41.01.441PA
OA! AI
41IP AP -if
ROD COUPLING
THREADED ROD
PIPE ROD BOLT IMBED
SIZE DIA. LGTH DEPTH
I" 3/8" 3 3/4" 2 1/4"
1 1/4" 3/8" 3 3/4" 2 1/4"
1 1/2" 3/8" 3 3/4" 2 1/4"
2" 3/8" 3 3/4" 2 1/4"
2 1/2" 3/8" 3 3/4" 2 1/4"
3" 3/8" 3 3/4" 2 1/4"
4" 3/8" 3 3/4" 2 1/4"
6" 1/2" 3 3/4" 2 1/4"
8" 1/2" 3 3/4" 2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007
COSCO STANDARD HANGER
13 MDL
GENERAL NOTES:)
1) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP II.
ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX.
2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN.
3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY
OTHER.
4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER.
5) OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, A5 IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
G) OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
7) OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(S) IS BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE
CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING
SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM
ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE
PROTECTION.
SEE PLAN
FOR LENGTH
NEW BRANCH LINE
"FLEXHEAD" FLEXIBLE
DROP CORRUGATED
STAINLESS STEEL
BRAIDED HOSE
CEILING
Z
0- w
w
h O
LL
ADJUSTABLE HUB
MOUNTING BRACKET
A TYPICAL ARMOVER TO NEW SPRINKLER HEAD
N.T.S.
TOLCO FIG. 25 SURGE RESTRAINER
TYPE 1 - FOR 1" AND 1/4' PIPE AND HANGER
TYPE 2 - FOR 1/2" AND 2" PIPE AND HANGER
TOLCO FIG. 25 IS DESIGNED TO BE USED ONLY
WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE AS
IT OCCURS DURING SPRINKLER HEAD ACTIVATION
OR SEISMIC ACTIVITY
SYMBOL =
FIGURE 25 SURGE RESTRAINER
% OFOR STEEL OR CPVC PLASTIC PIPE
3/g' x'Y2' LAG SCREW FOR WOOD
3/8' x 2/4' KWIK BOLT FOR CONCRETE
I " x /4' TEK FOR BARJOIST OR STEEL BEAM
45° MIN.
ARGCO OFFSET --�
EYESOCKET BRKT.
WHERE LENGTH
EXCEEDS I'- 1 0"
SYMBOL = 6
LINE RESTRAINT DETAIL
NALL THREAD ROD
I'- 10" MAX. PER SINGLE.
OTHERWISE ASSEMBLY
REQD. BOTH SIDES
��HANGER RING
( UP TO 2" PIPE)
SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE
LE
JOB SITE
os -
REVISIONS
NO.
DESCRIPTION
DATE
BY
SPRINKLER HEAD LEGEND:
SYMBOL
S/N
ORIFICE
NPT
K -FACT.
HEAD
FINISH
PLATE
FINISH
TEMP.
QUAN.
Reliable Model F1 FR Recessed Pendant
1/7'
1/2'
5.6
Chrome
Chrome
155°
4
Reliable Model G4A Concealed Pendant
1/2'
1/2'
5.6
Brass
White
165°
5
APPROVALS BY:
l TOTAL SPRINKLERS
THIS SHEET
9
;• o0 0..
"00000'
X00 00 00
I
cosco
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
www.coscofire.com 10910 117TH Place N.E.
Kirkland, Washington 98033
call (425) 827-9654 • fax (425) 827-7474
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
License No:
COSCOFP110NM
PROJECT:
Auntie Anne's Pretzels
1120 Southcenter Mall, Suite #1315
Tukwila, Wa. 98188-2823
CONTRACT WITH:
Retail Contractors LLC
17150 Tye Street SE, Suite A
Monroe, Wa. 98272
DRAWING TITLE
Auntie Anne's Pretzels: Sprinkler Piping Pian
DATE : June, 2008
SCALE : As Noted
DRAWN BY : Justin Johnson
mKs - 7952
SHEET NO,
FP