HomeMy WebLinkAboutPP - 1129 SOUTHCENTER MALL - FAST FIX JEWELRY REPAIR - PERMITS AND PLANS1129 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-309 08-S-317 08-S-310 0 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vanilla Shell 1129 Southcenter Mall Permit No.: 08-S310 Date: June 11, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. Hydraulic Summary 1 Job Number: KS0407 Report Description: Ordinary Group II ;gib .. Job Number KS0407 Design Engineer Adam Kanter Job Name Vanilla Shells 1129 State Certification/License Number WESTESF136QF Address 1 Southcenter Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila State Zip Code Wa 98188 Drawing Name FP-1-1129.cad System Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 579.63ft2 (Actual 579.63ft2) Additional Hose Supplies Node Flow(gpm) Number Of Sprinklers Calculated 8 Coverage Per Sprinkler 100.00ft2 op Certitic44 Oe (t C .o, r. '' t�\\ \ A o Total Hose Streams 250.00 System Flow Demand 165.74 Total Water Required (Including Hose Allowance) 415.74• •� 1V,',"S "t �- :bl Iiii, jV Maximum Pressure Unbalance In Loos 0.000 p Maximum Velocity Above Ground 13.29 between nodes 32 and 30 Maximum Velocity Under Ground 0.63 between nodes 1 and 370 0.6 Volume capacity of Wet Pipes 2394.24ga1 Volume capacity of Dry Pipes 1.22ft3 Supplies _ Hose Flow , Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available Total Demand , (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.715 415.74 41.390 98.325 Contractor Contractor Number KS0407 Contact Name Adam Kantner Contact Trtle Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 E-mail City Redmond State Zip Code WA 98052 Web -Site ©M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 06/03/2008 4:31:36PM Page 1 Summary Of Outflowing Devices Job Number: KS0407 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 106 20.95 20.00 5.6 13.995 Sprinkler 103 20.53 20.00 5.6 13.436 cii> Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 108 21.30 20.00 5.6 ' 14.470 Sprinkler 105 20.92 20.00 5.6 13.960 Sprinkler 107 21.14 20.00 5.6 14.252 Sprinkler 104 20.71 20.00 5.6 13.683 Sprinkler 102 20.19 20.00 5.6 12.992 U Most Demanding Sprinkler Data k, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/03/2008 4:31:40PM Page 2 _Node Analysis Job Number: KS0407 Report Description: Ordinary Group II Node Elevation(Foot) ' Fittings Pressure(psi) Discharge(gpm) 29 14-6 2P0(5-0) 18.405 30 14-6 2P0(5-0) 19.026 32 14-6 2P0(8-0) 21.708 34 14-6 2P0(5-0) 18.241 35 14-6 2P0(5-0) 17.830 362 1-11 PO(5-0), PO(26-4) 34.294 370 3-10'% BFP(-4.500) 37.967 406 1-11 LtE(16-0) 34.300 106 12-0 Spr(-13.995) 13.995 20.95 103 12-0 Spr(-13.436) 13.436 20.53 101 13-7 Spr(-12.755) 12.755. 20.00 108 8-0 Spr(-14.470) 14.470 21.30 105 12-0 Spr(-13.960) 13.960 20.92 107 12-0 Spr(-14.252) 14.252 21.14 104 12-0 Spr(-13.683) 13.683 20.71 102 13-7 Spr(-12.992) 12.992 20.19 1 -4-0 S 41.390 165.74 �y © M.E.P.CAD, Inc. $ AutoSPRINK® VR5 v5.2.6 06/03/2008 4:31:43PM Page 3 di Hydraulic Analysis 1 Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Length Summary Length Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Total Q. Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 31-0 Pf 5.463 11-0 Pe -0.388 42-0 Pv 101 35 13-7 q=20.00 K=5.6 14-6 12.755 17.830 Spr(-12.755) 3E(2-0), PO(5-0) BL 1.610 Q=40.19 6.33 C=120 0.058740 7-0 Pf 0.411 Pe 7-0 Pv 35 34 14-6 14-6 17.830 18.241 BL 1.610 Q=81.43 12.83 C=120 0.216935 8-0 Pf 3.467 8-0 Pe 16-0 Pv 34 32 14-6 14-6 18.241 21.708 P0(8-0) CM 4.260 Q=165.74 3.73 C=120 0.007069 394-3'h Pf 7.134 190-5'% Pe 5.452 584-9% Pv 32 362 14-6 1-11 21.708 34.294 T(26-4), 2cplg(-1.500), 4P0(26-4), 4fE(6-9%2), CV(28-11 %), GV(2-7Y2) FM 8.329 Q=165.74 0.98 C=120 0.000270 5-7 Pf 0.006 16-0 Pe -0.000 21-7 Pv 362 406 1-11 1-11 34.294 34.300 LtE(16-0) FM 10.420 Q=165.74 0.62 C=120 0.000091 26-5% Pf 4.510 83-0 Pe -0.842 109-5% Pv 406 370 1-11 3-10% 34.300 37.967 4LtE(16-0), BV(19-0), BFP(-4.500) UG 10.400 Q=165.74 0.63 C=140 0.000069 109-2 Pf 0.015 111-7 Pe 3.407 220-9% Pv 370 1 3-10% -4-0 37.967 41.390 E(35-1), 3LtE(25-6), S a. Route 2 DR 1.049 Q=20.19 7.49 C=120 0.132370 28-6 Pf 5.226 11-0 Pe -0.388 39-6 Pv 102 35 13-7 q=20.19 K=5.6 14-6 12.992 17.830 Spr(-12.992) 3E(2-0), PO(5-0) v Route 3 DR 1.049 Q=20.53 7.62 C=120 0.136541 32-11 Pf 5.881 114 Pe -1.075 43-1' Pv 103 34 12-0 q=20.53 K=5.6 14-6 13.436 18.241 Spr(-13.436) 3E(2-0), PO(5-0) Route 4 DR 1.049 Q=20.71 7.69 C=120 0.138866 29-7 Pf 5.633 11-0 Pe -1.075 40-7 Pv 104 34 12-0 q=20.71 K=5.6 14-6 13.683 18.241 Spr(-13.683) 3E(2-0), PO(5-0) v Route 5 DR 1.049 Q=20.92 7.77 C=120 0.141461 28-01 Pf 5.520 11-0 Pe -1.075 39-0 Pv 105 29 12-0 q=20.92 K=5.6 14-6 13.960 18.405 Spr(-13.960) 3E(2-0), PO(5-0) BL 1.610 Q=42.23 6.65 C=120 0.064376 9-8 Pf 0.622 Pe 9-8 Pv 29 30 14-6 14-6 18.405 19.026 BL 1.610 Q=84.32 13.29 C=120 0.231388 3-7 Pf 2.682 8-0 Pe 11-7 Pv 30 32 14-6 14-6 19.026 21.708 P0(8-0) a. Route 6 DR 1.049 Q=20.95 7.78 C=120 0.141788 32-1, Pf 6.106 11-0 Pe -1.075 43-1 Pv 106 30 12-0 q=20.95 K=5.6 14-6 13.995 19.026 Spr(-13.995) 3E(2-0), PO(5-0) a. Route 7 DR 1.049 Q=21.14 7.85 C=120 0.144197 29-7 Pf 5.849 11-0 Pe -1.075 40-7 Pv 107 30 12-0 q=21.14 K=5.6 14-6 14.252 19.026 Spr(-14.252) 3E(2-0), PO(5-0) Q. Route 8 DR 1.049 Q=21.30 7.91 C=120 0.146240 35-1% Pf 6.743 11-0 Pe -2.809 46-1% Pv 108 29 8-0 q=21.30 K=5.6 14-6 14.470 18.405 Spr(-14.470) 3E(2-0), PO(5-0) Equivalent Pipe Lengths of.Valves and Fittings (C=120 only) ` C Value Multiplier Actual Inside Diameter 487 ) = Factor Value Of C 100 130 Multiplying Factor 0.713 1.16 140 150 1.33 1.51 Schedule 40 Steel Pipe Inside Diameter ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/03/2008 4:31:47PM Page 4 1 Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Elevation Upstream Discharge K -Factor Pt Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points E Velocity pressure at a point in a pipe EE Eel Ee2 FDC fE fEE flg FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22'% Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap (41, ©M.E.P.CAD, Inc. +111AutoSPRINKO VR5 v5.2.6 06/03/2008 4:31:47PM Page 5 Hydraulic Graph Job Number: KS0407 Report Description: Ordinary GrouD II Supply at Node 1 150 135 Static Pressure 140.000 120 105 90 .N a 2 75 N . 4) a` 60 45 ,415.74 =165.74 with hose @ 41.390 streams 30 =System 15 demand curve 10900.00 @ 20.00_ 1 0 inutiIIIIII 1111111 I I 1111 11 I 1 1 I t I 1 1 I 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 111111111 111111111 11002200 3300 4400 5500 6600 7700 8800 9900 , 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.715 @ 415.74 System Demand 165.74 @ 41.390 System Demand (Including Hose Allowance) 415.74 @ 41.390 ©M.E.P.CAD, Inc. 11 AutoSPRINK® VR5 v5.2.6 06/03/2008 4:31:53PM Page 6 Flow Diagram (Top View) 1 Job Number: KS0407 Report Description: Ordinary Group II Up .tlT`� Dn 'R :limit ll�r�: vitittc 14,1 ©M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 06/03/2008 4:31:57PM Page 7 WESTFIELD SUITE 1129 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND S EET \UM3ESHEET TITLE FA -01 SYSTEV I \ FO MATT O \ FA -02 TYPICAL DETAILS - WRI\G A\D MOUNTI\G FA -03 FRE ALARM SYSTEM FLOO PLA\ FA -04 SYSTEM CALCULATIO\S (GE\EAL), MISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 1#16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR 4#14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT, AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, :WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS WAND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. _. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD to Q LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING L C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A: F. F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. n C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1 G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 49 BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING Q B WP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F,B.❑, i F.B.❑. N/A VERIItY IN FELD A.F.F. ABOVE FINISHED FLOOR N/A N/A e CC [!! TE N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A NOT APPLICABLE N/A U.D.N. UNLESS OTHERWISE NOTED N/A WP WEATHERPROOF DEVICE N/A RED AS BUILT ADD OR CHANGE N/A GREEN AS BUILT REMOVE N/A BLUE AS BUILT NOTES TO CAD N/A Without Comments N/A As Noted In Red N/A 10 Per The AttUllthd Letter N/A hese plans have been reviewed by The Tukwila Fire Pretion Bureau for confd?ia'ignce with current city N/A standards. Acceptance is subject to errors and omissions which do not authorize violations of adoptgd/A hdh- st�as and ordinances. Ylihesponsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings at -ser, thiblydgte will void this accept and will require a N i dA' resubmittal of revised drawings for subsequent approval Firf1'bceptance is subject I ff eld test and Inspection A;' The Tukwila Fire Prevention Bureau. • Da2/(7/Og ByN/ ©`%DU N/A z (.3z z FAX (206) 628-4990 TEL. (206) 622-651+5 NOTICE A completed, signed, Tukwila RELEASE/REVISIONS REV. BY: EGH DESCRIPTION SHOP DRAWINGS DATE cO 0 0 N 0 N 0 9 «a<a 0) CV o0 00 T Q I-wcco 2 w= o < Dij W Q wo LL - C /) v , Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance TUKWILA FIRE DEPARTIvii v , Please call: 575-440Z and give this job and exact address for shut. down or restoration approve* Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SCALE: 1/8"=1' Z 0 0 W N } (i) DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT _________________ _ EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE��, STOP IF LAST DEVICE FROM XLS CONTROL PANEL ❑R+ PREVI❑US ADDRESSABLE DEVIL END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 331§9.— DUCT DETECTOR LOCATI❑N o0 -o GROUND LO O U HTRI—R OSTATUS LED 10 ca 0 0 0 N.O. COM N NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCA<E (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L _ + NOTE 11 VOLTAGE MAX, - CURRENT MAX,- C❑NT, RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE- MIN, LINE SIZE - MUSIC OUTLET SAMPLING --- TUBE INLET SAMPLING—\\ TUBE \ AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 4 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE 1(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 mA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC, TO GUARANTEE DETECTION, 0 + 1 0 0 1 TB1 S 61 0 0 0 0 123456 TB2 C 00iP c� m0 654321 0 END OF LINE DEVICE (3.6K 1/4W) O SUPERVISED SWITCH GROUND 0 HTRI—D OSTATUS LED NOT USED CO 0 CO (0 0 O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC �-L T T T T 0 0 PAD -3 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 0 0 0 0 0 24K n + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 2 NAC -4 NAC -3 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS EOL T M-1 Q 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL EARTH GROUND -->(+)TO NEXT DEVICE OR 1 >(-) STOP IF LAST DEVICE f FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) SCALE NONE ( STROBE SPEAKER ( ) 6) STROBE-) (+) (-) STROBE SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R O 4S DEEP BOX W/ 1-1/2 EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1IN TEMPERATU E: +32' F O- C) TO 100' F (38' C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) >- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r-- DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICEF > ( ) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\. CEILING ----SPEAKER SUPPORT TILE BRIDGE HARD LID ----\ , 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \ CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON \ CEILING, FLEX JUNCTI❑N BOX ----- MOUNTED AGAINST CEILING SUPPORT /fO 0 0 0 IL TO NEXT DEVICE --CADDY BAR SMOKE DETECTOR----- SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO IMOD I\STA_L ADDRESSABLE I N DEVICES ,NIL PREP: OGVAMMLD W DEVICES ADDRESS. -HATING I H Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved K7 co 0' FAX (206) 628-4990 RELEASE/REVISIONS z LLI DESCRIPTION SHOP DRAWINGS w a CO 0 0 N 0 N Ln 0 0 z 0) N CO T CO J<0) c0 W 2 �z I—wcEo - zz ?(f) wO� I— LL CV v , T W f— z z 3 0 0 z cc r � V , E -- W J ‘CALE: 1/8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: .OB NUMBER: SHEET FA -02 J 8 —0 ____ T,� E Tom, AFF 12'-0" AFF EOL—S1 20..11V rocwi 5 vSf "K•°OCM :2S.2; 2S _g r_9 .F -:r. 2S,2V L 115 1 C 30 C 11J NORTH VANILLA SPACE 1129 WESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG \O ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACT❑R, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO NOT D NlSTAL ADDRESSABLE IN TIATI DFVICES UNTIL 3REPROGRAMMED W0M1- DEVICES ADD ESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 0) N T LU 0 J LU LL rr� vJ LU co co J r < Q) 2 2z wW — C�3 W= 5 _< Q <C cc O.) N D SCALE: 1/8"=1' DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: ,..JOB NUMBER: SHEET � FA -03} TE L\ R ` f SITS CAMERA 0-1-1-1E::R-1001 P,' ATERN. PIER CI N PAGODA ,__.I D ._. SPECS : `J THE CI.1_Y TRASH KIDS FOOTLOCKER 4 3D L: Lt. 0 i w 21 5 1 201 ;30 1 I 1 I 11 / 1 1 I 1 I I. I I i j 1 I 1 1 0 ETJ X3051 roc rLoING cI• aR . TENANCY, 240 1_:j ELEC TRiCAL CALIFORN.I IA PI ZZ.A KITCHEN NORTH SUITE 1129 WESTFIELD SOUTHCENTER MALL EXIS NG JCPenney \! V _ ,_l SCALE 1132'=1' EX D,I 2I RISER DIAGRAM BATTERY SIZING CALCULATION EGH SYSTEM LC L TI S DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL 1129 05/20/2008 1129 SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations FACP ADD ONS May 29, 2008 CURRENT TOTAL= 480 Date: CIRCUIT: S1 Current Load: QTY Device Type Alarm Current Standby: Alarm: Wire Length Current Load: Circuit Total Standby: Alarm: 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.86 1 SET -MC @30CD 98 98 Device Type Qty Amps 0 Total Amps Total Device Type Qty Amps Total Amps Total SET -MC @11OCD 233 0 (Total Cct Load) HFP-11 SET-HMC-C@115CD 318 0.0022 0.0022 0.0023 Main System Board Voltage Drop (E) 1 0.03 SET-HMC-C@177CD 0.03 0.030 0.030 AD2-P 1 0.0635 0.0635 0.064 0.064 318 SET -MC @15CD 0.064 19.99 0 HTR -R 445 2 0.009600 0.0096 0.021 0.042 SET -MC @30CD 1 Z-MC@15CD 64 64 0.098 0.098 HTRI-D0.001600 0 0.0035 98 0 SET -MC @75CD 0.175 0 SET-MC-CW@110CD ICP -B6 0 0.005 SET -MC @110CD DEVICES= 3 TOTAL mA= 480 12 0.233 19.987872 480 .............. ...... . SET HMC-C@115CD . 1 0.318 0.318 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL SET HMC-C@135CD Panel: 1129 Wire Resistance 2,58 0.318 Date: May 29, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT SET HMC-C@185CD 0.445 QTY Device Type Alarm Current Alarm Total 0.0731 Amps 0.106 Amps ZR -MC @15C D 1 2 70.7V1/8 1.8 0.064 0.064 ' Total Wire Resistance (R) 2.92 0 0 ZR -MC @30CD 0.098 0 Standby Current Load: 0 0.0731 Amps For 24 Hours = 1.754 Amp -hours HCP 0.00 0 0 0 0.0015 (Total Cct Load) 0 0 0 0.03 Amps 0.51 Amps Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours (E=I*R) 0 0 . 0 EOL Voltage 20.39 0 0 0 Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 25% Derating= 2.204 Amp -hours 0 0 0 DEVICES= 2 TOTAL mA= 3.6 . 14 Alarm Current Load: 20.38950456` 3.6 0.51 Amps For 5 Minutes= 0.043 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.954 Amp -hours _ Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.954 Amp -hours Battery Pair to be Used: 12VDC - Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved t1,0-4 09 . co 0' ii o0 z 1. o Z ~ o CI)z�, (/) x 1141 • Q LL• w F- F-- < iii ® o cn Ca m It L.6Q Su)E_ to ...t Cr,. TEL. (206) 622-6545 z O w w C/) w J W rY REV. BY: EGH Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL 1129 05/20/2008 Wire Resistance 1.62 Panel: May 29, 2008 CURRENT TOTAL= 480 Date: CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance (R) 0.86 1 SET -MC @30CD 98 98 (WL * 2 ) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (I) 0.48 0 SET -MC @11OCD 233 0 (Total Cct Load) 1 SET-HMC-C@115CD 318 318 Voltage Drop (E) 0.41 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.99 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 3 TOTAL mA= 480 12 265 19.987872 480 .............. ...... . Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: 1129 Wire Resistance 2,58 Date: May 29, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 ' Total Wire Resistance (R) 2.92 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.01 0 (E=I*R) 0 0 . 0 EOL Voltage 20.39 0 0 0 (20.4-E) 0 0 0 0 0 0 DEVICES= 2 TOTAL mA= 3.6 . 14 565 20.38950456` 3.6 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved t1,0-4 09 . co 0' ii o0 z 1. o Z ~ o CI)z�, (/) x 1141 • Q LL• w F- F-- < iii ® o cn Ca m It L.6Q Su)E_ to ...t Cr,. TEL. (206) 622-6545 z O w w C/) w J W rY REV. BY: EGH DESCRIPTION SHOP DRAWINGS DATE 05/20/2008 2 ««< 0) N co �. 1"'"' co .. "r"' J co J W < ~ w- W 0 CC ZZ 'J wi w VP° 0 W Q � wog < IL. cc Cn T 1-- W �-- 0 J 0 W (1) V) SCALE: SEE SHEET DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACKROUND PLAN PROVIDED BY: .OB NUMBER: r SHEET FA -04 �w IJn I'Tl.1�=.4k. Shell Space 1129 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD PIPE NIPPLE SPRINKLER BRANCHLIKE FLEXABLE C iNNhC rING NOSE IN STANDARD LENGTHS • (z;4 VICINITY MAP (Suite# 1129) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system on yt ng e a eascoitioof work. All other areas are not in contract and WSFP is not responsible for —ZONE T4 Remote Area GYP. BD. CELING 8'-0" A.F.F 25\ MOUNTING BRACKET REDUCING FITTING GYP. BD. CELING 12'-0" A.F.F GYP. BD. CELING 13'-7" A.F.F ..e.. *me .b .fin. axe ,.sw . GYP. BD. CELING 12'40" A.F.F s i -E ZONE T49 Main Ordinary Group 110.20gpmi'ft2 for 579.63ft2 26 SUSPENDED T -BAR GRID CEILING TILE SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTING 9AY KWIK BOLT .-(2 U4' EMBED LENGTH) F10.1000 FAST CLAMP' SWAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT It i NON -THREADED BRACE PIPE 9f9' KWIK BOLT (2 1/4 EMBED LENGTH) FIG. 009 NO•THREAD SWIVEL SWAY BRACE ATTACHMENT BRACE PIPE LATERAL BRANCH - E RESTRAINT - NOT TO SCALE Remote Area 1129 SHELL SPACE CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 occuPANcv CLASS. ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM, re for 579.63 Ft' SPRINKLER Reliable F1 FR Semi-Rec ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 165.74 GPM © 37.96 " At time of Design PSI Hanger No. 07C HILTI Kwik Bolt III Rod Coupling —� All Thread Rad Cut Rod Lgth Rounded to Nearest Inch Swivel Ring Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and A' Dimension HANGER DETAIL NOT TO SCALE i 0 E Without Comments As Noted In Red. ' Per The Attached Letter s_ N i nese plans have been revie,+ved by The Tukwilaire Prevention Bureau for conformance with current-c1 y standards. Acceptance is ,subiect to'errors and omissions which do not authorize violations of ado+te standards and ordinances. The responsibility for tie adequacy of design rests totally with the designer. < Additions, deletions or revisions to these drawings atter this date will void thi.s acceptance and will require resubmittal of revised drawings for subsequent apkirovpl. Final acceptance is subject to field test and inspec ion v The Tukwila Fire Prevention Bureau.�u.� ' Date: ( O By e�t'�P700 rUKWILA FIRE DE.PAri, A441 Please call: 575-4407 and give this job and exact address for shut_ down or restoration approvit EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS FIRE SPRINKLER SYSTEM 1/8"=1'-0" Sprinkler Legend APPROVAL: 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT DESCRIPTION FR SEMI-REC 4 4 R3615 SPRAY Pendent Pendent Chrome 155°F MFR./MODEL R3615 City of Tukwila 155°F G4A CONCEALED Total = 8 CONT, NO.: KS0407 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK, ON JOB: VICINITY . MAP DETAIL NOT TO SCALE Western States Fire Protection Company DATE 06/03/08 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 LIc. !k WESTESF138QI2 WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/ DECATUR/DENVER/DULUTH/HOUSTON /KANSAS CITY LAS VEGAS /MINVEAPOLIS / PHOENIX/PORTLAND/ RAPID CITY/ST. PAUL/SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Vanilla Shells 1129 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM li SHEET FP -1 OF 1 900 Tukwila Fire Shell Space 1129 L.! ti I x .... VICINITY MAP (Suite# 1129) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads. to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprihkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE 24 Remote Area—u.-- GYP. BD. CELING 8.-0" A.F.F ?L' t).53 GYP. BD. CELING GYP. BD. CELING 13'-7" A.F.F GYP. BD. CELING 12-0" A.F.F 11 Existing Main ZONE T4 • Ordinary Group 11-3.20gpt0t2 for 579.63ft2 FIRE SPRINKLER SYSTEM 3 5 7 9 11 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD ! • • . ••• • •••• . MOUNTING BRACKET PIPE NIPPLE ; • . ••,...• • • . SPRINKLER BRANCHLINE, :•. FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS . , REDUCING FITTING . • . • 1,10421400,0140.4**MS4441.4.0044.411.)0.M•41.4-1-~.04.1,44,14.440)•4 SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG9°9 SWIVEL SWAY BRACE FITTING BRACE PIPE air KWIK BOLT (2 1/4" EMBED LENGTH) FIG. 1000 -FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS 'NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT Aidi.) NON -THREADED BRACE PIPE 3/8" KWIK BOLT (2 1/4" EMBED LENGTH) BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Remote Area 1129 SHELL SPACE CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / for 579.63, Ft' SPRINKLER Reliable F1FR Semi-Rec ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRE 165.74 GPM @ 37.96 PSI • At time of Design Hanger No. 07C HILTI Kwik Bolt III HILTI Kwik Bolt it Drilled Anchor Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'ADimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE .0w z ci CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT SYM.I SIN [ QTY. 4FIFR SEMI-REC 4 R3615 4 K SPRAY ORIF. FIN. TEMP. MFR./MODEL 5.6 Pendent Chrome 155°F R3615 APPROVAL: City of Tukwila 5.6 Pendent White 155°F G4A CONCEALED CONT. NO.: KS0407 Total = 8 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 11 Western States Fire Protection company 7102 180th AVE NE, STE A-105. REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY • OFFICES LOCATED ALBUOUEROUE /AUSTIN DALLAS / DECATUR 1DENVER'l DULUTH /HOUSTON /KANSAS CITY LAS VEGAS / MINNEAPOLIS / PHOENIX/ PORTLAND /RAPID CITY/ ST. PAUL /SALT LAKE CITY / SEATTLE Phone: 425-881-0100 'Fax: 425-881-3030 Vanilla Shells Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1