PP - 1149 SOUTHCENTER MALL - SPEC SPACE - PERMITS AND PLANS
1149 SOUTHCENTER MALL ASSOCIATED PERMITS 09-F-170 09-S-165 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Spec Space 1149 Southcenter Mall Permit No.: 09-S-165 Date: October 23, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. FIT RIGHT ALTERATIONS FIRE ALARM SYSTEM TUKWILLA, WA 98188 SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 SYSTEM CALCULATIONS (GENERAL), RISER FA -04 FIRE ALARM SYSTEM FLOOR PLAN WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2 1.34 SQUARE riri {Rm Ar,r nACrn nm Lnw rn►Jnu uT rn 1 Atkin Ant-- "-A.ir.. 1 -gnu DIMENSIONS AREA .244 0.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH \I r r n. Ir. ei T*r.. r A SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. os -col NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY SYMBOL 3 DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FATP FIRE ALARM XLS-V CONTROL PANEL SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER PAD -3 POWER SUPPLY SIEMENS PROVIDED 66" A.F.F. TO TOP 1 2 EX TRI -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD TRI -D DUAL INPUT HTRI-D INTERFACE MODULE SIEMENS 4S DEEP BOX VERIFY IN FIELD ® DUCT SMOKE AD2-XHR W/ SIEMENS D DETECTOR HFP-11 DET DUCT HOUSING VERIFY IN FIELD O(PHOTOELECTRIC)DDBP 111 BASE SIEMENS 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM STROBE (WALL MOUNT) ST -MC -W SIEMENS 4S BOX 80" A.F.F. TO BOTTOM PAM MULTI -VOLTAGE PAM -1 RELAY MODULE AIR PRODUCTS 4S BOX VERIFY IN FIELD FIRE SMOKE DAMPER F.B.O. F.B.❑. N/A VERIFY IN FIELD FATC EX JUNCTION BOX F.B.❑, N/A VERIFY IN FIELD Fs WATER FLOW F,.B,❑, SWITCH F.B.❑, N/A VERIFY IN FIELD TS TAMPER F.D.O, SWITCH F.B.❑, VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.❑. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT N/A APPLICABLE N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PTE D Without Comments a As Noted in Red o Per The Attached Letter These plans have been reviewed by The. Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted - standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require,'a resubmittal of revised drawings for subsequent ajiproval. Final acceptance Is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 10 -30 -0°1 / y�By: S-1 �.i-ns } �► (I brrak t r hwtidl< �Igwl' o 1'•S• t;Y�,„. i- rrw ruf(WiLA FIRE DEPARTMEN1 Please call: 575.4407 .aloe this Job N0. 0.9 r' 17 ° and exact address for shut. i wn or, restoration aborhui:1 NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing, PA I . OCT 2 L 2009 Tukwila Fire Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS _l DATE 0) 0 N ,i- 2 <-<CCC U) z w°3 CC W _ CCWz00 a� ig <.r S QCO OJ _ cc 1.1_ Z 0 F cc 0 us. 1-1 W N } /SCALE: NOT TO SCALE DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 4/21/09 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. BEND OR OTHER OBSTRUCTION BEND OR OTHER OBSTRUCTION DUCT DETECTOR--" L❑CATION TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE STROBE .+ 24K STROBE CIRCUIT SPEAKER + -- 24K STROBE CIRCUIT STROBE SPEAKER - + 9 9 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. STROBE CIRCUIT TUBE OUTLET SAMPLING TUBE INLET SAMPLING TYPICAL VOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE STROBE + 0 SPEAKER CIRCUIT SPEAKER/STROBE AND STROBE V (RING STROBE CIRCUIT SPEAKER + 0 AT LEAST SIX DUCT WIDTHS FROM BEND STROBE CIRCUIT SPEAKER CIRCUIT FA -02 LABEL SCALE 120VAC HOT NEUTRAL 0 0 TYPICAL FOR DAMPERS DAMPER — HOT O NEUTRAL 0 120VAC WHT Z BLU -0 -0BLK PAM -1 SHOP DRAWINGS L0 O RED DATE 4/21/09 OR C NC NO DATA CABLE 0 0 -0 0 HTRI—R STATUS LED ILO. co 0 DOA 0 KC. to FAN TYPICAL FAN CONTACTOR POWER CLOSED DAMPER CONTACTS NO C NC O _p DATA CABLE ///// GROUND NOT SHIELD HTRI-R WITH PAM -1 INSIDE 4S DEEP BOX WITH EXTENSION RING TYPICAL WIRING FOR DAMPERS & FAN CONTACTOR POWER SCAIE:NONE (STATUS & CONFIRMATION) + OPEN DAMPER CONTACTS NO C NC o DATA CABLE 1 0 0 0 0 N @ C�7 HTRI—D STATUS LED NOT USED re 0 n0 NO. co 0 ///// GROUND NOT SHIELD HTRI-D INSIDE 4S DEEP BOX SPEAKER CIRCUIT 12X12 JBOX GENERAL NOTES 1. SPEAKERS ARE TAPPED AT 70.71/4 WATT. 2. STROBES CANDELAS ARE ON THE FIELD DRAWINGS. 3. CHECK CUT SHEETS SUPPLIED WITH PARTS BEFORE HOOKING -UP. 4. ALL ALD LOOP WIRES MUST BE IN METAL RACEWAY. / TO NEXT 0t'1C < FRONT VIEW l NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. r DATA OUT (+) 1. DATA OUT ( ) DB -11 STANDARD SMOKE DETECTOR , BASE - NOT USED REMOTE DEVICE LOOP NOT USED REMOTE ,.. DEVICE LOOP BEALIIEW DATA C� CABLE ALD N 470 OHMS EOL T M-1 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPUFPLR RED (JACKET) W � Z oho co 10 000 A • • • TYPICAL AD2-P DUCT SMOKE DETECTOR = WIRING DETAIL SCALE; NONE JUNCTI❑N BOX MOUNTED ON CEILING. FLEX JUNCTIIJN BOX MOUNTED AGAINST CEILING SUPPORT / / / / / / // o 0 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECT❑R....- SMOKE DETECTOR N'OUNTING SCALE:NONE 5. ANY ALD LOOP WIRE THAT GOES TO FANS / DAMPERS THAT ARE PART OF PRESSURIZING OR VENTING SMOKE CONTROL, NEED TO BE IN METAL RACEWAY AND 2 -HOUR PROTECTED (CI CABLE OR ENCLOSED IN 2 -HOUR CONCRETE OR SHEETROCK. —�(+)TO NEXT DEVICE OR �(-) STOP IF LAST DEVICE} TO NEXT ADDRESSABLE DE _ + DAMPER CONTACTS NO C NC O _qm/S) DATA CABLE ///7/ GROUND NOT SHIELD DAMPER STATUS CONFIRMATION & ACTIVATION SCALE:NONE DAMPER HOOT NEUTRAL + SUSPENDED ILLUMINATED CEILING TO NEXT ADDRESSABLE DEVICE NEUTRAL 0 120VAC HOT COMBINE AU. SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE_ FROM XLS CONTROL PANEL DR .(`f— pj" PREVIOUS ADDRESSABLE DE GROUND -0 EARTH GROUND -4.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER,5TING RE: +32' F (0' CC) TOMPERA 100' F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --• • DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR ,.....--- DB -11 / STANDARD P SMOKE DETECTOR BASE -*PROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) )' - DATA IN (+) > REAR VIEW i (-) DATA OUT > (+) DATA OUT TO NEXT DEVICE< - HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID - - CEILING HARD LID ---SPEAKER SUPPORT TILE-- - BRIDGE ,--- 4" SQUARE DEEP BOX / WITH 1-1/2' EXTENSION '\\ CEILING MOUNTED ----- SPEAKER/STROBE CEILING MOUNTED_ SPEAKERISTROBE UIOUNTING (DROP CEILING) SCALE:NONE 0 ONO N AC d 1:4 00 El 0 LJ fel PAD -3 0 n oo� INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX - + - 1+1- 1 2+2- 2 NC C NO + - + - + - C]IL] C] C` 3.6k EOL 61 CACI CI CI CIIC]IC] 11 1I LI O 0 0 HTR( -R STATUS LED cO 0 K0. r 0 - COM to 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL WIRING FOR HTRI-R MODULE (PAD -3 TRIP) SCALE: NONE STUD SHEET ROCK SPEAKER STROBE OR STROBE ONLY NAC -4 NAC -3 NAC -2 NAC -1 'ALL IVOUNTED SPEAKER STROBE FIRE IV SCALE:NONE 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) OUNTING ELEVATIONS FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Z DESCRIPTION SHOP DRAWINGS DATE 4/21/09 2 CCCCC LL z 0 (SCALE: NOT TO SCALE DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 4/21/09 BACKROUND PLAN PROVIDED BY: \0B NUMBER: i SHEET FA -02 JCoPYri ht 2006 by Guardian Security Systems, Inc. All Rights Reserved SYSTEM CALCULATIONS 7:..f."...'"' :tttr•-::"7"....A ... .,.. " ""•. '0 ; ....• . 0 p 1 P.A. ...0` '0 • a. . ° „" A. ''':: „ „ . •:" ''' '," ' . 40, ,,,.. 0 :le NW Panel: XLS-V r „ 6 a Wire Resistance 2.58 Ut LW' ir,nt,0 ViaVitg.ro# SET -MC ©1 5CD 64 64 981 0 0 1SEF-MC @30CD 1 SEF -mc @75CD 175 175 0 :SET -MC @110CD 233, 0 DB/ICES= 2 TOTAL mA=1 239 14 335 19.99 Total Wire Resistance ( R ) 1( WL * 2 ) * (R/ft) 1.73 Total''DeViCey;i0,..Aii)0 ,(1): :: - -,..- -''' : ' ::y::--,.::,,.:‘- ' • i: . . ..(Totali,.cot Load)- -, - .":-, r 0:.24 1Voltage Drop ( E ) ,....... 1 I(E= I * R) i 1 0.41 thi..,Viia6e..::--::.:--:_...i;.:-7:',Y - -. - . - ,- , .-- -20.4-- E),,-.,. ‘...i r' ' '' . ' :' ' : ' ' : :i 9'it 00 1 f ' *Au „ A 0 A. "•* t f'rp Panel: XLS-V Wire Resistance 2.58 losr.„*" t" Aat'AVA'Pqr. ' PP..; 50.5000.4:4 kl0-.0 0/40: 0.0 70.7V 1/8 2 70.7V 1/4 0 70.7V 1/2 0 70.7V 1 DEVICES 2 Total Wire Resistance ( R ) ( WL* 2 )* (R/ft) . iTotal Device Load, Amps (I) (Total Cct Load) 0.01 Voltage Drop (E) (E= 1* R) 0.01 EOL Voltage (20.4 - E) 20.39 0 7.2 0 TOTAL rnA= 7.2 14 389 20.38564787 Current Load: Standby: Alarm: , • Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 0 0 600 0.0096 0.021 0.063 HTRI-D 0 0.001600 0 0.0035 0.000 0.0753 Amps 0.127 Amps Standby Current Load: 0.0753 Amps For 24 Hours = 1.807 Amp -hours Alarm Current Load: 0.127 Amps For 15 Minutes= 0.032 Amp -hours 25% Derating= 2.299 Amp -hours Total System Current Load: 2.299 Amp -hours Battery Pair to be Used: II2VDC Amp -hours 8AH 1.4g041.14M.P A mq " . t 444 Device Type Qty Amps Total Amps Total Main System Board sEraivic@ SET -MC @3000 1 0.03 0.03 0.030 0.030 0.064 0.064 0.098 SET-IVIC ©75CD ZR-MCgISCD 0.17 0.175 0.064 Z1171VIP:©3OcD 0.098 • .; 0.03 Amps 0.269 Amps Standby Current Load: Alarm Current Load: 0.03 0.269 , • .... 0._ • Amps Amps For 24 Hours For 5 Minutes 25% Derating= 0.720 Amp -hours 0.023 Amp -hours 0.928 Amp -hours Total System Current Load: 0.928 Amp -hours VOLTAGE DROP CALCULATION BATTERY SIZING CALCULATION EOL -S1 3 2S,2V 0 D D B EX 1FACP EOL -V1 21 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE a) 0 z:1 .., .4, 2 < <<<< cc z LL 0 >- ‘CALE: NOT TO SCALE DRAWN BY: 'ANDERSON DESIGNED BY: R.VEZZAN I DATE: 4/21/09 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ..JOB NUMBER: SHEET FA -03 EOL -S1 EOL -V1 FACP EX 2S.2V D,I B S 21 2S.2V NORTH RETAIL AREA OU FIT RIGHT ALTERATIONS 8CALE FLAG NOTES: FIELD LOCATE RELAY MODULE FDR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR DN RETURN SIDE OF ALL VAV UNITSXSEE SIEMENS INSTALL ATION SUBMITTAL FDR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESIDN SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. ALARM SIGNAL TO ALARM SYSTEM WILL BE SUPERVIZ❑RY, SUPER VIZED CARBON M❑N❑XIDE S ENS❑R AND SHUTDOWN THE OVEN E>. TO OVEN FAN CONTROL TERMINALS STROBE SYNCE MODULE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 0 N 2 <CCCQ LL �CALE: 1 /4" =1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 4/21 /09 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -04} (E) BACK OF HOUSE CORRIDOR 41-011 STRIP LIGHT - FIX11JRES RE: ELECTRICAL (E) METAL STUD AND Glia TENANT DEMISING WALL ADJACENT TENANT SPACE REFLECTED CEILING PLAN 1 /4" = 1'-0" (E) METAL sirup AND GWB TENANT DEt 1!SING WALL Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means • - Add Reliable Model G4A 165° Concealed Sprinkler Heads, White Cover Plate 1/2 x 1/2 7 -Total 1 MALL COMMON AREA ,ea RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ta) = uuCple Iron Modal MT -3 & MT -9 Mechanical tee serves the same function as MT -1 & MT -8 but uses a steel electro plated u -bot to save space and for easier installation In tight places. It is ideal•for direct connections with sprinkler hoads•and drop nipples. HOUSING: Ductile iron ASTM A536 grade 85-45-12. COATING: Zinc electroplated U - BOLT: Carbon steel SAB grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET EPOM (-303F to + 230'F) THREADS: MT -3 NPT per ANSI/ASME 511.20.1 MT -9 British standard parallel (BSP) per ESTI T"r iUF NOMIN.% 4929 M. 1 - Mq:. 5049994 r.a.r.r C 11.1•e•• ilia IN .t4L 7>.. . aim • x 115lOW Inen non .. 19 A�?ROK. C 0 of wt-anl 6:1AGH 1/4 = 1.2 300 1.19 2.14 4 1.61.21 0.30 3123 . x • . 0.23 1174x14 703 • 1.19 2.14 1414 350 1.37 ^-.�.5 0.87 1 1 471 1 390 1,19 2.27 1.61 3.30 1,31 9.27. 1.00 1 1/291/9 300 T.99 2.34 1.74 3.59LT3 1.33 2,2.5 2.25 - 3.87 11/292/4 200 1.19 2.35 1.75 350 0.97 1 1/3 x 1 300 1,19 2.30 1.703,30 . 1.33 I :.Is 1,00 2V1/3 2 :100 1.111 2.51 2.01 3.77 1 „/i 2.26 � O.R7 93/4 200 7.19 2.51 f 2.01 3.22 1.59 1 1.5n 1 7..25 2.55-- 0.99 1.00 0.09 2111 300 1.19 9.5.1 1.5x 3.75 21/211/1 300 • 1.19 3.71 2.37 4.29 1.37 212.2/. 300 1.11 r 2.76 2.25 .9.30 1.1r 2.21 0.04 2 12 9 1 300 9.19 -2.81 2 83 2.22 ,......2 ....---._.... 3.•7 4,39 .r9.29•nn • 1 111 i '1.2s - 1.13 9 0.0.11/2_-� 3W 1.19 �- Y..75 O.Rv-- I .13.I311 - - -7 i1- NO - - ---- ... 200- 1,19 1 1.17 3 R2 2.;12 1.29 1.911 2.L 9.97 2.99 1 229 "r 4.26'. .......ST. • I -_.]d2--.__ 177d ACCE Q Without Comments pr.Q Asper in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not aumnorize violations of adopted tandards and ordinances. The responsibility for the adequacy of design rests totally with ale designer. Additions, deletions or revisions to t``rese drawingsafter this date will void this acceptance &d ��vili require;:a a resubmittal of revised drawings for stiosequent approvals. • Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau.re Date:_ /0/ 2.1(0 61 By: ./. ` % r TUKWILA FIRE . DEPARTM J 1. Please call: 575.4407 and give this job No.0`l-S-fte5 and exact address for shut flown or restoration approvel. V ILS: CROW\ FIRE PROTECTION IN CORPORA TED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 TENANANT IMPROVEMENT 1149 SOUTHCENTER TUKWILA, WA 98188P _ A! OCT 2 2009 TO W/O Firs! DATE:04t ? -o1I DRAWN: