HomeMy WebLinkAboutPP - 1159 SOUTHCENTER MALL - BJ'S RESTAURANT & BREWHOUSE - PERMITS AND PLANS1159 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-121 08-S-149 08-H-323 Re FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: BJ's Restaurant And Brew House 1159 Southcenter Mall Permit No.: 08-S-149 Date: May 1, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. .: A FIRE DEPARTMENT HOOD SUPPRESSION PLAN REVIEW COMMENTS Project Name: BJ's Restaurant 1159 Southcenter Mall Permit No.: 08-H-323 Date: June 12, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 FILE COPY • Nozzle heights above appliances to be per manufacturers installation guidelines. • Install splash guards between fryers and ranges/charbroilers. • Upon activation of the suppression system, the make-up air supply will shut off and the exhaust will keep running. • Type 1 hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or by means of other approved methods. • Activation of the suppression system shall shunt all electrical power under the hood as well as the gas supply. • Install a "K" rated portable fire extinguisher within 30 ft. of the cooking equipment. • The hood suppression system shall be monitored by a U.L. Central Monitoring Station. J/ 2 545/./ c Hydraulic Overview I Job Number: KC0015 Report Description: Ordinary Group II Job Job Number Design Engineer KC0015 Chris J Isaac Job Name Phone FAX B.J'S Restaurant & Brewhouse 206-491-6679 425-811-3030 Address 1 State Cerbficatron/license Number 1159 South Center Mall WESTESF136QF Address 2 AHJ City of Tukwilla Coy State Zip Code Job Site Tukwila WA 98188 South Center Mall System Density Area of Application 0.20gpm/ft2 861.00ft2 (Actual 860.59ft2) Most Demanding Sprinkler Data Hose Streams 5.6 K -Factor 26.00 at 21.556 250.00 Coverage Per Sprinkler Number Of Sprinklers Calculated 130.00ft2 7 System Pressure Demand. System Flow Demand 114.997 208.29 Total Demand Pressure Result 458.29 @ 114.997 +24.662 (17.7%) Supplies Check Point Gauges Node Flow(apm) Hose Flow(qpm) Static(psi) Residual(psi) Identifier Pressure(psi) K-Factor(K) Flow(gpm) 1 10900.00 250.00 140.000 20.000 Zone T5-BJRESTAURANT.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) 150 135 tatic Pressure 140.000 120 458.29 '08.29 with @ hose 114.997 streams 105 _ 90 a 75 m System demand cuIrye _ ,� rrt tt 60 45 30 10900.00 @ 20.000 15 0 ' . IMnu 11011111 111111111 111111 I l l 111111111 1111 1 1 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 1 1 1 1 1 130(0 5500 6600 7700 8800 9900 11000 Water flow, gpm [Ay ©M.E.P.CAD,Inc. AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:28PM Page 1 (V74 Hydraulic Summary r Job Number: KC0015 Report Description: Ordinary Group II Job Job Number KC0015 Job Name B.J'S Restaurant & Brewhouse Address I 1159 South Center Mall Address 2 City State Zip Code Tukwila WA 98188 Design Engineer Chris J Isaac State Certification/license Number WESTESF136QF AHJ City of Tukwilla Job Site South Center Mall Drawing Name Zone T5-BJRESTAURANT.cad System Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 26.00 at 21.556 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(opm) Occupancy Ordinary Group II Density Area of Application 0.20gpm/ft2 861.00ft2 (Actual 860.59ft2) Number Of Sprinklers Calculated Coverage Per Sprinkler 7 130.00ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Inducting Hose Allowance) 208.29 458.29 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 32.82 between nodes 785 and 1083 Maximum Velocity Under Ground 0.79 between nodes 1 and 941 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2686.87ga1 6.54ft3 loom OFFw��, �.u� �L1��'�`��%1 eb �iihe •0 De V Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand Required Safety Margin (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.659 458.29 114.997 24.662 Contractor Contractor Number KC0015 Contractor Name Western States Fire Protection (Redmond) Address I 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Contact Tide Chris J Isaac Designer Phone Extension (425)881-0100 FAX (425)881-3030 E -mad chris.isaac@wsfp.us Web -Site (y ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:29PM Page 2 Summary Of Outflowing Devices Job Number: KC0015 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow K -Factor Pressure (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 202 201 203 204 205 206 207 Most Demanding Sprinkler Data 26.18 26.00 26.65 28.00 30.23 33.45 37.77 26.00 26.00 26.00 26.00 26.00 26.00 26.00 5.6 5.6 5.6 5.6 5.6 5.6 5.6 21.858 21.556 22.652 25.003 29.131 35.681 45.499 i(� © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:30PM Page 3 Node Analysis Job Number: KC0015 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 91 92 187 558 797 889 868 633 969 941 1016 983 744 745 748 1032 1072 782 1083 785 202 201 203 204 205 206 207 1 13-2 E(10-0) 14-6 E(13-2) 13-2 fE(6-9%) 13-6 fE(6-9'/) 12-2 E(1-5) 12-2 P0(3-7) 1-11 P0(26-4) 13-6 fE(8-11%) 12-2 P0(3-7) 3-10% BFP(-4.500) 12-2 P0(3-7) 1-11 LtE(16-0) 14-6 P0(8-6%) 3-0 LtE(2-10) 4-0 DPV(8-0) 12-2 P0(3-7) 12-2 P0(3-7) 13-2 fE(4-31/2) 12-2 P0(3-7) 12-2 LtE(1-5) 12-11% Spr(-21.858) 12-11'/ Spr(-21.556) 13-0 Spr(-22.652) 12-11% Spr(-25.003) 12-11% Spr(-29.131) 12-11% Spr(-35.681) 13-0 Spr(-45.499) -4-0 S 98.831 98.092 99.799 100.757 22.882 23.205 107.875 102.115 24.362 111.558 26.843 107.885 96.752 87.806 89.490 31.197 38.100 62.962 48.439 55.830 21.858 21.556 22.652 25.003 29.131 35.681 45.499 114.997 26.18 26.00 26.65 28.00 30.23 33.45 37.77 208.29 k, © M.E.P.CAD, Inc. } AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:30PM Page 4 Hydraulic Analysis Job Number: KC0015 Report Description: Ordinary Group II Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Velocity K -Factor HWC Pt Friction Loss Length Pressure Pn Fittings Eq. Length Summary Total Length Route 1 SP 1.049 0=26.00 9.65 C=100 0 296253 0-10 Pf 1.297 201 12-11% q=26.00 K=5.6 21.556 Spr(-21.556) 3-7 Pe 0.352 889 12-2 23.205 P0(3-7) 4-4% Pv BL 1.610 0=52.18 8.22 C=100 0.133445 8-8 Pf 1.157 889 12-2 23.205 Pe 969 12-2 24.362 8-8 Pv BL 1.610 Q=78.83 12.42 C=100 0.286298 8-8 Pf 2.481 969 12-2 24.362 Pe 1016 12-2 26.843 8-8 Pv BL 1.610 0=106.84 16.84 C=100 0.502370 8-8 Pf 4.354 1016 12-2 26.843 Pe 1032 12-2 31.197 8-8 Pv BL 1.610 0=137.06 21.60 C=100 0.796503 8-8 Pf 6.903 1032 12-2 31.197 Pe 1072 12-2 38.100 8-8 Pv BL L 1.610 Q=170.5.1 26.87 C=100 1.193003 8-8 Pf 10.339 1072 12-2 38.100 Pe 1083 12-2 48.439 8-8 Pv 1.610 Q=208.29 32.82 C=100 1.7274.87 2-10 Pf 7.391 _BL 1083 12-2 48.439 _ 1-5 Pe 785 12-2 55.830 LtE(1-5) 4-3% Pv BL 2.067 Q=208.29 19.91 C=100 0.511621 8-4 Pf 7.566 785 12-2 55.830 6-5% Pe -0.434 782 13-2 62.962 LtE(2-1%), fE(4-3%) 14-9% Pv BL 2.469 0=208.29 13.96 C=100 0.215317 59-2% Pf 20.436 782 13-2 62.962 17-1% Pe 4.408 745 3-0 87.806 6LtE(2-10), LtE(-4.000) 76-4 Pv BL 2.067 Q=208.29 19.91 C=100 0.511621 2-0 Pf 2.118 745 3-0 87.806 2-1% Pe -0.434 748 4-0 89.490 LtE(2-1%) 4-1% Pv BL 2.469 0=208.29 13.96 C=100 0.215317 35-5% Pf 11.811 748 4-0 89.490 DPV(8-0) 19-5 Pe -4.548 744 14-6 96.752 LtE(2-10), P0(8-6%) 54-10 Pv CM 4.260 0=208.29 4.69 C=120 0.010788 111-1 Pf 1.340 744 14-6 96.752 13-2 Pe 92 14-6 98.092 E(13-2) 124-3 Pv CM 4.026 0=208.29 5.25 C=120 0.014205 1-4 Pf 0.161 92 14-6 98.092 10-0 Pe 0.578 91 13-2 98.831 E(10-0) 11-4 Pv CM 4.260 0=208.29 4.69 C=120 0.010788 42-11% Pf 0.968 91 13-2 98.831 46-9 Pe 187 13-2 99.799 P0(26-4), 3fE(6-9%) 89-8% Pv CM 4.026 0=208.29 5.25 C=120 0.014205 58-10 Pf 1.103 187 13-2 99.799 18-9% Pe -0.145 558 13-6 100.757 2EE(4-0), Eel (4-0), fE(6-9%) 77-7% Pv CM 4.260 0=208.29 4.69 C=120 0.010788 101-2 Pf 1.358 558 13-6 100.757 24-8% Pe 633 13-6 102.115 fE(6-9%), 2fE(8-11%) 125-10% Pv FM 4.260 0=208.29 4.69 C=120 0.010788 10-10% Pf 0.742 633 13-6 102.115 57-11 Pe 5.018 868 1-11 107.875 CV(28-11%), GV(2-7%), P0(26-4) 68-9% Pv FM 8.329 Q=208.29 1.23 C=120 0.000412 7-7 Pf 0.010 868 1-11 107.875 16-0 Pe 0.000 983 1-11 107.885 LtE(16-0) 23-7 Pv FM 10.420 0=208.29 0.78 C=120 0.000138 26-5% Pf 4.515 983 1-11 107.885 83-0 Pe -0.842 941 3-10% 111.558 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5% Pv UG 10.400 0=208.29 0.79 C=140 0.000105 109-2 Pf 0.032 941 3-10% 111.558 191-4 Pe 3.407 1 -4-0 114.997 E(35-1), T(79-8%), 3LtE(25-6), S 300-6 Pv c. Route 2 SP 1.049 0=26.18 9.72 C=100 0.300093 0-10 Pf 0.672 202 12-11% q=26.18 K=5.6 21.858 Spr(-21.858) 1-5 Pe 0.352 797 12-2 22.882 E(1-5) 2-3 Pv BL 1.610 0=26.18 4.13 C=100 0.037255 8-8 Pf 0.323 797 12-2 22.882 Pe 889 12-2 23.205 8-8 Pv Route 3 SP 1.049 0=26.65 9.89 C=100 0.310156 0-10 Pf 1.358 203 13-0 q=26.65 K=5.6 22.652 Spr(-22.652) 3-7 Pe 0.352 969 12-2 24.362 P0(3-7) 4-4% Pv .=. Route 4 (Iy� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:31 PM Page 5 d` Hydraulic Analysis ill Job Number: KC0015 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length SP 1.049 Q=28.00 10.39 C=100 0.339825 0-9% Pf 1.488 204 12-11% q=28.00 K=5.6 25.003 Spr(-25.003) 3-7 Pe 0.352 1016 12-2 26.843 P0(3-7) 4-4% Pv Route 5 SP 1.049 Q=30.23 11.22 C=100 0.391418 0-10 Pf 1.713 205 12-11% q=30.23 K=5.6 29.131 Spr(-29.131) 3-7 Pe 0.352 1032 12-2 31.197 P0(3-7) 4-4% Pv • Route 6 SP 1.049 0=33.45 12.42 C=100 0.472183 0-10 Pf 2.067 206 12-11% q=33.45 K=5.6 35.681 Spr(-35.681) 3-7 Pe 0.352 1072 12-2 38.100 P0(3-7) 4-4% Pv 4-• Route 7 SP 1.049 0=37.77 14.02 C=100 0.591235 0-10 Pf 2.588 207 13-0 q=37.77 K=5.6 45.499 Spr(-45.499) 3-7 Pe 0.352 1083 12-2 48.439 P0(3-7) 4-4'14 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) II C Value Multiplier I Actual Inside Diameter 4.87 ) Value Of C 100 130 140 150 = Factor ( Schedule 40 Steel Pipe Inside Diameter Multiplying Factor 0.713 1.16 1.33 1.51 Pipe Type Legend Units Legend Fittings Legend AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen -Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Pv Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11W Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Tum Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply SCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap [e� ©M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 04/29/2008 3:59:31 PM Page 6 r Hydraulic Graph J Job Number: KC0015 Rcpc:t Dcccription: Ordinary Orc.',_ 'I I Cr, Supply at Node 1 (,.) AA p� Pressure, psi p N O N O N CD O 0 i i C IIII VIII VIII II III, 11111111111111, IIIA IIII111,,11I II IIII,111111111111111111111111 IIIIIIIIIII Static Pressure 140.000 458.29 P08.29 with hose @ 114.997 streams "stem demand • curve 10900.00 © 20.000, Itl1ul➢uu 111111/11 III III III I t I I 1 I 1 I 1 I I I 1 I I I I I I I I I I I I I I I I I I I(( 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 1 1 1 1 1 91002200 3300 4400 5500 6600 7700 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 © 20.000 Available PressureTsne of Test 139.659 @ 458.29 System Demand 208.29 © 114.997 System Demand (Including Hose Allowance) 458.29 @ 114.997 (M © M.E.P.CAD, Inc. ,!6 AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:32PM Page 7 Flow Diagram Top View Job Number: KC0015 Report Dnp,-rin+inn• Ordinary Group II t• ^ a rr • a i. �1 ,a..� i I Dtip (M ©M.E.P.CAD, Inc. ? AutoSPRINK® VR5 v5.1.32 04/29/2008 3:59:33PM Page 8 •t (�k1 *: atis Hydraulic Overview , Job Number: KC0015 Report Description: Ordinary Group II Job Job Number Design Engineer KC0015 Chris J Isaac Job Name Phone FAX B.J'S Restaurant & Brewhouse TI 206-491-6679 425-811-3030 Address 1 State CenitiWtioNLicense Number 1159 South Center Mall WESTESF136QF Address 2 AHJ City of Tukwilla City State Zip Code Job Site Tukwila WA 98188 South Center Mall System Density Area of Application 0.20gpm/ft2 1069.00ft2 (Actual 1215.54ft2) Most Demanding Sprinkler Data Hose Streams 5.6 K -Factor 22.00 at 15.434 250.00 Coverage Per Sprinkler Number Of Sprinklers Calculated 110.00ft2 14 System Pressure Demand System Flow Demand 54.943 333.45 Total Demand Pressure Result 583.45 © 54.943 +84.524 (60.6%) Supplies Check Point Gauges Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psil K-Factor(K) Flow(apm) 1 10900.00 250.00 140.000 20.000 Zone T5-BJRESTAURANT.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) 150 =i Static Pressure I 140.000 135 120 105 _ 90 .N a 75 N N d d 60 X33.45 583.45 wi @ h hose 54.943 streams _ it*; t� 451 =System demand curve 30 10900.00 t 20.000 15 q=11111111111111111111LL1111111111 111111111 1111111111111111 1 1 111111111 I I I I I I 1 I I I I I I 1 1I I I 0 11002233010 5500 6600 7700 8800 9900 11000 Water flow, gpm (, ©M.E.P.CAD, Inc. } AutoSPRINK® VR5 v5.1.32 04/23/2008 7:29:57AM Page 1 r e, Hydraulic Summary I Job Number: KC0015 Report Description: Ordinary Group II Job Job Number KC0015 Job Name B.J'S Restaurant & Brewhouse TI Address 1 1159 South Center Mall Address 2 Coy State Zip Code Tukwila WA 98188 Design Engineer Chris J Isaac State Cemficationft.icense Number WESTESF136QF AHJ City of Tukwilla Job Site South Center Mall Drawing Name Zone T5-BJRESTAURANT.cad System Remote Area(s) MoM Demaning Sprinkler Data 5.6 K -Factor 22.00 at 15.434 Hose Allowance Al Source 250.00 Additional Hose Supplies Node Flow(abm) Occupancy Ordinary Group II Density Ares of Application 0.20gpm/ft2 1069.00ft2 (Actual 1215.54ft2) Number Of Sprinklers Calculated Coverage Per Sprinkler 14 110.00ft2 Total• 250 00 ms System Flow Demand Total Water Required (Inducting Hose Allowance) 333.45 583.45 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 14.32 between nodes 512 and 508 Maximum Velocity Under Ground 1.26 between nodes 1 and 941 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2599.75ga1 6.54ft3 l� Cert1fl a , 4� tool F ♦ = _ � w:I ���L�l a Y �D f*y' Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand Required Safety Margin (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.467 583.45 54.943 84.524 Contractor Contractor Number KC0015 Contractor Name Western States Fire Protection (Redmond) Address 1 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Contact Title Chris J Isaac Designer Phone Extension (425)881-0100 FAX (425)881-3030 E -mad chris.isaac@wsfp.us Web -Site (A,/, ©M.E.P.CAD, Inc. ;j AutoSPRINK® VR5 v5.1.32 04/23/2008 7:29:59AM Page 2 ♦ P 4 Summary Of Outflowing Devices r Device Actual Flow (gpm) Job Number: KC0015 Report Description: Ordinary Group II Minimum Flow K -Factor Pressure (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 103 101 105 108 114 112 104 102 106 107 110 109 111 113 E> Most Demanding Sprinkler Data 22.18 22.00 22.52 24.19 26.64 25.16 22.19 22.01 22.52 24.16 24.65 24.46 25.03 25.75 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 22.00 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 15.682 15.434 16.166 18.667 22.623 20.192 15.694 15.446 16.179 18.616 19.377 19.079 19.970 21.138 (M © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/23/2008 7:29:59AM Page 3 4,r1 Node Analysis Job Number: KC0015 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 187 13-2 fE(6-9%) 35.351 558 13-6 fE(6-9Y2) 37.840 499 16-6 E(2-0) 16.280 500 16-6 P0(5-0) 16.496 502 16-6 P0(5-0) 17.265 508 16-6 P0(5-0) 19.893 512 14-6 2P0(8-0) 25.456 516 16-6 P0(5-0) 24.033 538 16-6 E(2-0) 16.293 539 16-6 P0(5-0) 16.508 541 16-6 P0(5-0) 17.279 549 16-6 P0(5-0) 19.839 758 14-6 P0(5-0), P0(8-0) 25.340 770 14-6 P0(16-5%) 25.333 868 1-11 P0(26-4) 47.763 899 16-6 E(2-0) 20.060 902 16-6 P0(5-0) 20.323 905 16-6 P0(5-0) 21.260 907 15-2 P0(8-0) 24.129 941 3-10% BFP(-4.500) 51.480 983 1-11 LtE(16-0) 47.786 1018 15-2 P0(6-0) 24.083 1019 15-8% T(5-0) 23.495 103 16-11% Spr(-15.682) 15.682 101 16-11% Spr(-15.434) 15.434 105 16-11% Spr(-16.166) 16.166 108 16-11% Spr(-18.667) 18.667 114 16-11% Spr(-22.623) 22.623 112 16-11% Spr(-20.192) 20.192 104 16-11% Spr(-15.694) 15.694 102 16-11% Spr(-15.446) 15.446 106 16-11% Spr(-16.179) 16.179 107 16-11% Spr(-18.616) 18.616 110 16-11% Spr(-19.377) 19.377 109 16-11% Spr(-19.079) 19.079 111 16-11% Spr(-19.970) 19.970 113 17-0% Spr(-21.138) 21.138 1 -4-0 S 54.943 22.18 22.00 22.52 24.19 26.64 25.16 22.19 22.01 22.52 24.16 24.65 24.46 25.03 25.75 333.45 (M ©M.E.P.CAD, Inc. 0-4 AutoSPRINK®VR5 v5.1.32 04/23/2008 7:30:00AM Page 4 Hydraulic Analysis I Job Number: KC0015 Report Description: Ordinary Group II Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Velocity K -Factor HWC Pt Friction Loss Length Pressure Pn Fittings Eq. Length Summary Total Length Route 1 SP 1.049 Q=22.00 8.17 C=120 0.155224 0-6 Pf 0.851 101 16-111/2 q=22.00 K=5.6 15.434 Spr(-15.434) 5-0 Pe 0.210 500 16-6 16.496 P0(5-0) 5-6 Pv BL 1.610 Q=44.18 6.96 C=120 0.069986 11-0 Pf 0.770 500 16-6 16.496 Pe -0.000 502 16-6 17.265 11-0 Pv BL 1.610 Q=66.69 10.51 C=120 0.149952 9-6% Pf 2.627 502 16-6 17.265 8-0 Pe 0.000 508 16-6 19.893 4LtE(2-0) 17-6% Pv BL 1.610 Q=90.89 14.32 C=120 0.265854 5-8 Pf 4.696 508 16-6 19.893 12-0 Pe 0.867 512 14-6 25.456 2LtE(2-0), P0(8-0) 17-8 Pv CM 4.260 0=333.45 7.51 C=120 0.025765 172-1% Pf 9.318 512 14-6 25.456 73-1 Pe 0.578 187 13-2 35.351 2E(13-2), P0(26-4), 2cplg(-1.500), 245-2% Pv 3fE(6-9%) CM 4.026 Q=333.45 8.40 C=120 0.033925 58-10 Pf 2.633 187 13-2 35.351 18-9% Pe -0.145 558 13-6 37.840 2EE(4-0), Eel (4-0), fE(6-9'/z) 77-7% Pv CM M 4.260 Q=333.45 7.51 C=120 0.025765 112-0% Pf 4.905 558 13-6 37.840 78-4 Pe 5.018 868 1-11 47.763 3fE(6-9%), CV(28-11%), GV(2-7%), 190-4% Pv P0(26-4) FM 8.329 Q=333.45 1.96 C=120 0.000984 7-7 Pf 0.023 868 1-11 47.763 16-0 Pe -0.000 983 1-11 47.786 LtE(16-0) 23-7 Pv FM 10.420 0=333.45 1.25 0=120 0.000331 26-5% Pf 4.536 983 1-11 47.786 83-0 Pe -0.842 941 3-10% 51.480 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5% Pv UG 10.400 Q=333.45 1.26 C=140 0.000251 109-2 Pf 0.055 941 3-10% 51.480 111-7 Pe 3.407 1 -4-0 54.943 E(35-1), 3LtE(25-6), S 220-9% Pv a Route 2 SP 1.049 0=22.01 8.17 0=120 0.155336 0-6 Pf 0.852 102 16-11% q=22.01 K=5.6 15.446 Spr(-15.446) 5-0 Pe 0.210 539 16-6 16.508 P0(5-0) 5-6 Pv BL 1.610 Q=44.19 6.96 C=120 0.070037 11-0 Pf 0.770 539 16-6 16.508 Pe -0.000 541 16-6 17.279 11-0 Pv BL 1.610 0=66.72 10.51 C=120 0.150060 9-1 Pf 2.560 541 16-6 17.279 8-0 Pe 0.000 549 16-6 19.839 4LtE(2-0) 17-1 Pv BL 1.610 0=90.88 14.32 0=120 0.265815 5-5 Pf 4.634 549 16-6 19.839 12-0 Pe 0.867 758 14-6 25.340 2LtE(2-0), P0(8-0) 17-5 Pv CM 4.260 0=215.93 4.86 C=120 0.011532 10-0 Pf 0.115 758 14-6 25.340 Pe 512 14-6 25.45610-0 Pv c. Route 3 SP 1.049 Q=22.18 8.23 C=120 0.157534 0-5% Pf 0.391 103 16-11% q=22.18 K=5.6 15.682 Spr(-15.682) 2-0 Pe 0.208 499 16-6 16.280 E(2-0) 2-5% Pv BL 1.610 Q=22.18 3.49 C=120 0.019557 11-0 Pf 0.215 499 16-6 16.280 Pe -0.000 500 16-6 16.496 11-0 Pv ... Route 4 SP 1.049 Q=22.19 8.24 0=120 0.157648 0-5% Pf 0.391 104 16-11% q=22.19 K=5.6 15.694 Spr(-15.694) 2-0 Pe 0.208 538 16-6 16.293 E(2-0) 2-5'% Pv BL 1.610 Q=22.19 3.50 C=120 0.019571 11-0 Pf 0.215 538 16-6 16.293 Pe -0.000 539 16-6 16.508 11-0 Pv ... Route 5 SP 1.049 Q=22.52 8.36 C=120 0.162027 0-6 Pf 0.889 105 16-11% q=22.52 K=5.6 16.166 Spr(-16.166) 5-0 Pe 0.210 502 16-6 17.265 P0(5-0) 5-6 Pv Route 6 SP 1.049 Q=22.52 8.36 0=120 0.162143 0-6 Pf 0.889 106 16-11% q=22.52 K=5.6 16.179 Spr(-16.179) 5-0 Pe 0.210 541 16-6 17.279 P0(5-0) 5-6 Pv 4-4, Route 7 (M ©M.E.P.CAD, Inc. 0-4AutoSPRINK® VR5 v5.1.32 04/23/2008 7:30:00AM Page 5 din Hydraulic Analysis I Job Number: KC0015 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length SP 1.049 0=24.16 8.97 C=120 0.184615 0-6 Pf 1.013 107 16-11% q=24.16 K=5.6 18.616 Spr(-18.616) 5-0 Pe 0.210 549 16-6 19.839 P0(5-0) 5-6 Pv Route 8 SP 1.049 0=24.19 8.98 C=120 0.185084 0-6 Pf 1.015 108 16-11% q=24.19 K=5.6 18.667 Spr(-18.667) 5-0 Pe 0.210 508 16-6 19.893 P0(5-0) 5-6 Pv w Route 9 SP 1.049 0=24.46 9.08 C=120 0.188856 0-6 Pf 1.035 109 16-11% q=24.46 K=5.6 19.079 Spr(-19.079) 5-0 Pe 0.209 902 16-6 20.323 P0(5-0) 5-6 Pv BL 1.610 0=49.11 7.74 C=120 0.085133 11-0 Pf 0.936 902 16-6 20.323 Pe 0.001 905 16-6 21.260 11-0 Pv BL 1.610 0=74.14 11.68 C=120 0.182377 2-7% Pf 2.301 905 16-6 21.260 10-0 Pe 0.567 907 15-2 24.129 LtE(2-0), P0(8-0) 12-7% Pv CM 2.635 Q=99.88 5.88 C=120 0.028742 10-9% Pf 0.907 907 15-2 24.129 20-9% Pe 0.298 770 14-6 25.333 fE(4-3%), P0(16-5%) 31-6% Pv CM 4.260 0=99.88 2.25 C=120 0.002770 2-6 Pf 0.007 770 14-6 25.333 Pe 758 14-6 25.340 2-6 Pv a Route 10 SP 1.049 0=24.65 9.15 C=120 0.191589 0-5% Pf 0.475 110 16-11% q=24.65 K=5.6 19.377 Spr(-19.377) 2-0 Pe 0.208 899 16-6 20.060 E(2-0) 2-5'% Pv BL 1.610 0=24.65 3.88 C=120 0.023785 11-0 Pf 0.262 899 16-6 20.060 Pe 0.001 902 16-6 20.323 11-0 Pv a Route 11 SP 1.049 0=25.03 9.29 C=120 0.197004 0-6 Pf 1.080 111 16-11% q=25.03 K=5.6 19.970 Spr(-19.970) 5-0 Pe 0.210 905 16-6 21.260 P0(5-0) 5-6 Pv a Route 12 SP 1.049 Q=25.16 9.34 C=120 0.199026 9-5% Pf 4.074 112 16-11% q=25.16 K=5.6 20.192 Spr(-20.192) 11-0 Pe 1.075 758 14-6 25.340 3E(2-0), P0(5-0) 20-5% Pv a Route 13 BL 1.049 Q=25.75 9.56 C=120 0.207636 6-7 Pf 1.780 113 17-0% q=25.75 K=5.6 21.138 Spr(-21.138) 2-0 Pe 0.578 1019 15-8% 23.495 E(2-0) 8-7 Pv BL 1.380 0=25.75 5.52 C=120 0.054610 0-6% Pf 0.357 1019 15-8% 23.495 6-0 Pe 0.230 1018 15-2 24.083 P0(6-0) 6-6% Pv CM 2.635 0=25.75 1.51 C=120 0.002340 19-8 Pf 0.046 1018 15-2 24.083 Pe 907 15-2 24.129 19-8 Pv Route 14 SP 1.049 0=26.64 9.89 C=120 0.221096 0-5% Pf 1.208 114 16-11% q=26.64 K=5.6 22.623 Spr(-22.623) 5-0 Pe 0.202 516 16-6 24.033 P0(5-0) 5-5'% Pv BL 1.610 0=26.64 4.20 C=120 0.027448 8-0 Pf 0.549 516 16-6 24.033 12-0 Pe 0.874 512 14-6 25.456 2LtE(2-0), P0(8-0) 20-0 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier Value Of C 100 130 140 150 Multiplying Factor 0.713 1.16 1.33 1.51 Actual Inside Diameter \ 4.87 = Factor Schedule 40 Steel Pipe Inside Diameter ) (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/23/2008 7:30:00AM Page 6 Hydraulic Analysis r Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KC0015 Report Description: Ordinary Group II Velocity K -Factor HWC Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig Pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV AngV b BaIV BFP BV C cplg Cr CV DelV DPV E EE Eel Ee2 FDC fE fEE flg FN ft' g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z Alarm Valve Angle Valve Bushing Ball Valve Backflow Preventer Butterfly Valve Cross Flow Turn 90° Coupling Cross Run Check Valve Deluge Valve Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap (N ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/23/2008 7:30:00AM Page 7 Hydraulic Graph Job Number: KC0015 Report Description: Ordinary Group II Supply at Node 1 Pressure, psi av N O A pUl p p N il Uf 111111111111111111111111, I IIIIIIIIII IIII1 I II 111111111111111111111111111111111111111111111 III 11111111 Static Pressure 140.000 ,583.45 333.45 with hose @ 54.943 streams System demand curve 10900.00 @ 20.0001 I M III 111111 11111 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 111111111 11 1 I 1 1 I II 111 III III 1 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 V 1100 22°° 3300 4400 5500 6600 7700 91 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Avast* PressureTime of Test 139.467 @ 583.45 System Demand 333.45 @ 54.943 System Demand (Including Hose Allowance) 583.45 @ 54.943 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/23/2008 7:30:01 AM Page 8 Flow Diagram (Top View) I Job Number: KC0015 Report Description: Ordinary Group II (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 04/23/2008 7:30:01 AM Page 9 W Automatic gas valve To z 2 a 48'HEIGHT n4rc •1 N COtO Amerex Fire Superssion System KP 275 CJ N CO N CO nr .-1 • FUSIBLE LINKS 45ODEG N D aM to 44 - CD RD T • CM 8 0 F U z cn U cn a z z 0 >" mW W CZ Q- a ►- W 3) CC Z� aC 206 229 5245 4 Amerex Fire Superssion System KP 375 FROM HOOD if 1 1 0 Ti r° X i v �o JSIBLE LINKS 450DEG i i N 6 e'0 AMEREX KP RESTAURANT SYSTEM NOZZLE APPLICATION CHART July 2006 Section 3 Design Page 3-17 Amerex KP wet Chemical System= (EX 4658) Max. H eight 48 in. CEECCC 00 Vt CON M d' 48 in. __ 50 in. et C) r 30 in. Al C 000000 U) E U) E cf E U) C U) EE d' et 00 et i C OO M 6 CONCOVA. M C et C '3 C x= 0 18.8 in. I 55.9 in. I) Protection is not limited to the Items listed on this chart. Modullzing larger appliances Is an acceptable practice. See your Amerex KP Manual for additional information. Min. Hei ht C C-- CO CO M M C t` r C O N- C Nt C_ CO C r) 40 in. 14 in. C_ C O O C O C O C CO _C U) ' CC CJ r CO r ' CCCCC N r N r CO r CO r 0) A- Length V On += C D Unlimited Unlimited Unlimited Unlimited V On c D Length 19 in. 25 3/8 in. 25 3/8 in. C 000 r C N 24 in. C C d' NCOnf CV C C M N 4-7 depth C CON C) C Vt 48 in. C \ CO N C nr N C d'r N C M C - M . C\\ 1 N C• OO N CO N 28V2in. Length 10 ft. Diameter C CO r C N M C 00 'Tr Width • C C 'N N O O r •C N O r C CO r C ct r C N r 12 in. 14 in. 12 in. 24 in. 14-24 dia. cc 0 MM 0 30 in. C 'N M cc nt N "t N 24% in. N N C 0 r 24 in. C d' NN C d' Width y . Max. Perimeter C O U) C 0 0 150 in. Flow Points ('-4NN\ry-r.1-r-Nr rNOV r �% rr(4 N A.-1.-1.- N - N Flow Points r Flow Points rrMM-- N N Nozzle P/N 13729 13729 2-11982 11984 11982 11982 11982 17461 2 - 11984 _ 14178 11982 11982 13729 14178 2-11984 11983 11982 11982 13729 4 – 11982 11983 11983 11983 Nozzle P/N 11982 Z a O Z co r 7-71&71;1-6-. 2-11983 oa0o rnrn N el C' ) 3-11983____ v V 0 0 •p, Q 1 Deep Fat Fryer – without Drip Pan Deep Fat Fryer – with Drip Pan Deep Fat Fryer – with Drip Pan Low Proximity Range – Single Burner Range – Two Burner Range – Two Burner Range- Two Burners w/Back Shelf Low Back-Shelf/Salamander – BS Manifold Range – Three Burners Range – Four Burners Wok "Griddle Griddle Upright Broiler Charbroiler (Lava Rock) Charbroiler (Gas Radiant & Electric Radiant) II Chain Broiler – Closed Top II Chain Broiler – Open Top II Chain Broiler – Nieco Model 9025 /Catalyst (2) Natural & Mesquite Charcoal Charbroiler Mesquite Chips & Chunks Charbroiler IMesquite Log Charbroiler Plenum Single Bank/V-Bank Duct 11 Circular II Rectangular II Circular I Rectangular Circular z a. M CM z 0. Co ti P z 0. Co M ^ 1'► P3 z 0. July LUUn erection o uesign rage o — �� I Amerex KP Wet Chemical System (EX 4658) • KP DISTRIBUTION PIPING DESIGN LIMITS FOR ALL CYLINDER SIZES When designing a KP system to protect a kitchen containing a Fryer, Wok or Range, the following MINIMUM TOTAL SYSTEM PIPING must be used in accordance with the chart below: PIPING REQUIREMENTS MINIMUM MINIMUiM TOTAL APPLIANCE LINEAR FEET EQUIVALENT FEET 11=11111•1111 Wok Ranee 6.5 9 7 10 22.1 16.4 MINIMUM FLOW POINTS PER SYSTEM 2 6 4 SUPPLY LINE LIMITATIONS: All DiDe and fittings running from the distributor block or the discharge fitting to the first tee. °CYLINDER FLOW POINTS PIPE SIZE MAXIMUM LINEAR MAX. QTY. FEET OF PIPE TEES MAX. QTY. ELBOWS MAX. QTY. BUSHINGS KP275 - 8 3/8 20 1 5 0 KP375 - 11 3/8 OR 1/2 25 1 5 1 KP475 - 14 1/2 25 1 5 2 KP600 - 18 1/2 25 1 5 2 2-KP375 - 22 1/2 30 2 7 2 NOTE: 1. Use 3/8" supply line only when all piping is to be 3/8" pipe: 2. The supply line has a maximum vertical rise above the distributor of 10 feet. SUPPLY BRANCH LINE (including last nozzle branch) LIMITATIONS: All pipe and fittings leaving the first splitting tee in the system and ending with the last nozzle in the last branch line. While the last nozzle branch is included in the piping limitations for the supply branch line, the limitation (pipe size and maximum length) for nozzle branch lines apply to this portion of the supply branch line. CYLINDER FLOW POINTS PIPE SIZE MAX. FEET OF PIPE STRAIGHT MAX. FEET OF PIPE SPLIT MAX. QTY. TEES MAX. QTY. ELBOWS MAX. QTY. REDUCING BUSHINGS KP275 - 8 3/8 20 25 7 8 0 KP375 -11 3/8 OR 1/2 27 30 10 8 2 KP475 - 14 3/8 27 30 12 8 2 KP600 - 18 AS NOTED 35' OF 3/8" OR 1/2" 50' 3/8" PIPE ONLY 14 8 2 2-KP375-22 AS NOTED 40' OF 1/2" 45 OF %2" 18 8 0 *30' OF 3/8" *30' OF 3/8" NOTE: 1. In a single 3.75 Gallon Straight Pipe System, 5' of pipe may be transferred from the supply line to the supply branch line. *2. The use of 3/8" pipe with two manifold KP375s is only permitted when the supply Line length is equal to or less than 20 feet. NOZZLE BRANCH LINE LIMITATIONS: All pipe and fittings leading from the supply branch tee to a system nozzle. CYLINDER FLOW POINT S ` PIPE SIZE TOTAL LINEAR FEET. OF PIPE MAX. QTY. TEES MAX. QTY. ELBOWS MAX. QTY. BUSHINGS KP275 - 8 3/8 32 5 10 0 KP375 - 11 3/8 OR 1/2 32 8 12 11 KP475 - 14 3/8 32 10 15 0 KP600 - 18 3/8 32 11 18 15 2-KP375 - 22 3/8 32 18 18 20 MAX. PER NOZZLE BRANCH 7 3 6 4 GENERAL SYSTEM LIMITATIONS: 1. No'/z" pipe nozzle branches shorter than 12" long. 2. Nozzle types may not be mixed on any nozzle branch line and a maximum of 4 flow points. 3. The discharge fitting, distributor and distribution hose are not to be included in any calculations. 4. No mixing of pipe sizes is allowed within pipe categories. Example: if one nozzle branch is to be'/z" pipe then all must be '/2" pipe. I/2' pipe for nozzle branch lines is allowed only in an 11 flow point system. 5. Duct nozzle has a maximum vertical rise above the supply branch line of 4'0". SINGLE FLOW POINT NOZZLE (PIN 11982) One Amerex plenum node (P/N 11982) will protect a gas radiant charbroiler with a cooking surface measuring 24 inches X 24 inches (61 x 61 cm) maximum. The nozzle uses one flow point_ It must be located 18 to 48 inches (46 — 122 cm) above the cooking surface and anywhere along or within the perimeter . aimed towards the center. ELECTRIC RADIANT CHARBROILER PROTECTION SINGLE FLOW POINT N0771 F (P/N 11982) Note: Electric charbroiiiers with a non -grated surface or a solid ribbed surface may be protected using the same limitations as a griddle. Electric charbrolllers with an open grate may be protected with one Amerex appliance, plenum nozzle (P/N 11982) provided that the area is no larger than 24 inches X 24 inches (61 x 61 cm). The nozzle uses one flow point and must be located within 18 — 48 inches (46 — 122 cm) above the grate surface, anywhere along or within the perimeter of the protected area, aimed towards the center. LAVA ROCK (CERAMIC/SYNTHETIC) CHARBROILER SINGLE FLOW POINT NOZZLE (P/N 11983) A single Amerex solid fuel appliance plenum nozzle (P/N 11963) will protect a lava rock charbroiler with a maximum cooking surface of 24 inches wide (61 cm) by 24 inches deep (61 cm). The appliance nozzle uses 1 Yi flow point and for this application must be located , between 18 to 44 inches (46 to 122 cm) above the cooking surface anywhere along or within the perimeter of the appliance aimed toward the center. 1 I f F I' I 1 ' / s 0 I t p'2 ` ` . • 18' 1 ,vas iwoca . cAitebet rasesuoleittouMs 1st atuazdo tolburtspotitsocooking 3111111.10 24' I Section 3 Design Page 3-10 I Amerex KP Wet Chemical System (EX 4658) October 2003 FOUR (4) BURNER RANGE PROTECTION TWO (2) FLOW POINT NOZZLE (P/N 14178) The Amerex 4 burner range nozzle (P/N 14178) has two (2) flow points and will protect a range surface area of 24" x 24" (61 x 61 cm). The center to center distance between burners must not exceed 12 inches. The nozzle must be located 18 — 50" (46 — 127 cm) above the range surface and centered between the burners. The nozzle is aimed straight down at the center of the appliance. NOTE: Maximum and minimum heights must be measured from the tip of nozzle to the surface of the appliance. RANGE PROTECTION—MULTIPLE NOZZLES (P/N 14178) For ranges that have a surface area exceeding the capabilities of a single nozzle, multiple nozzles must be used provided that the surface area of the range is divided into equally sized modules. Each module must be equal to or less than 24" x 24" (61 x 61 cm). NOTE: When using this nozzle to protect a two (2) bumer range the aiming point is where an 8.50" radius from the center of each bumer crosses one another WOK PROTECTION SINGLE FLOW POINT N0771 E (P/N 11982) The Amerex appliance plenum nozzle (P/N 11982) has one flow point and will protect a wok with -:dimensions between a minimum diameter of 14" (36 cm) and a maximum diameter of 24" (61 cm) inclusive. The wok must have a height dimension between a minimum of 4" (10 cm) and a maximum of 7" (18 cm) inclusive. The nozzle must be centered over- the center of the wok and located at a height between 40 " (102 cm) and 50" (127 cm) from the bottom of the inside of the wok and aimed at the center of the wok. r rot' Min. Size Aim Point Max. Size Timm FRYER PROTECTION (FULL VAT) - TWO FLOW POINT NOZZLE (PIN 13729) MAXIMUM AREA: 191/2 in. (50 cm) x 25-3/8 in. (65 cm) including drainboard interface area 19'A in. (50 cm) x 19 in. (48 cm) not including drainboard interface area The Amerex fryer nozzle (PiN 13729) uses two flow points and will protect a full vat fryer. If the fryer does not include a drainboard, the maximum fryer dimensions for single nozzle coverage are 19" x 19W (48 x 50 cm) and the maximum protected area is 2.53 ft2 (2350 cm2). If the fryer does contain a drainboard the maximum fryer dimensions for single nozzle coverage are 25- 3/8" x 19W (65 x 48 cm) and the maximum protected area is 3.44 ft2 (3195 cm2). However, the maximum hazard area must not exceed 19" x 19 '/2" (48 x 50 cm). The nozzle must be located along or anywhere within the protected area. Nozzle heights must be within 36 to 48 inches (91.44 — 121.92 cm) above the appliance surface and aimed to the center of the hazard area of the appliance. Note: Maximum & minimum heights must be measured vertically from the tip of nozzle to the top of the appliance. LOW PROXIMITY APPLICATION FRYER PROTECTION (FULL VAT) TWO (2) SINGLE FLOW POINT NOZZLE (P/N 11982) MAXIMUM AREA: 191/2 in. (50 cm) X 25 3/8 in. (65 cm) (including 191A in. (50 cm) x 19 in. (48 cm) (not including A pair of Amerex single flow point nozzles (P/N 11982) will protect a full vat fryer. The nozzles must be used in pairs located on the perimeter of the appliance, 34" back from the inside edge of the appliance and within a zone extending 6" in both directions of the center of the hazard. The nozzles are to be located 180° apart (directly across from one another). They are to be aimed at a point 3" below the top of the appliance and directly below the opposing nozzle. If the fryer does not include a drainboard, the maximum fryer dimensions are 19W x 19" (50 x 48 cm) and the maximum protected area is 2.53 ft2 (2530 cm2). If the fryer does contain a drainboard, the maximum fryer dimensions are 25 3/8" x 19 'h" (65 x 50 cm) and the maximum protected area is 3.44 ft2 (3195 cm2). However, the maximum hazard area must not exceed 19 '/2 " x 19" (50 x 48 cm). The nozzle's height must be within 17W to 36" (45 - 92 cm) above the appliance surface. drainboard interface area) drainboard Interface area) FULL VAT FRYER WITH DRAINBOARD TWO NOZZLES (2 x P/N 16416) Two Amerex duct nozzles (P/N 16416) will protect ducts with a perimeter of 51 inches to 82 inches (129.5 — 208.3 cm) or a maximum diameter of 26 inches (66 cm). To correctly position the nozzles a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along a centerline into four equal distances. A nozzle should be placed at one quarter of the duct's width (or diameter) with both nozzles on the centerline, paced 2-8 inches (5.08 - 20.3 cm) into the duct opening and aimed at the center of the cross section of the duct. Each nozzle has one flow point. NOTE: In no case can the diagonal dimension of each module exceed 18.8 inches (46 cm). DUCT PROTECTION LIMITATIONS 100 IN. PERIMETER TWO — 11/2 FLOW POINT NOZZLES (P/N 11983) The Amerex solid fuel appliance/duct nozzle (P/N 11983) is listed to protect a restaurant cooking exhaust duct of unlimited length and up to 100 perimeter inches (254 cm) or 32 inch diameter (81.2 cm) using two nozzles. The nozzles total three flow points and to properly position the nozzles, a rectangular duct should be divided along its longest side into four equal distances. A circular duct should be divided along its center line into four equal distances. The nozzles are to be placed at one quarter and three quarters position of the duct width (or diameter) with both nozzles on the center line, placed 2 - 8 inches (5.08 — 20.3 cm) into the duct opening and aimed straight up in a vertically run duct. NOTE: In no case can the diagonal dimension of the duct exceed 37.2 inches (94.4 cm) without adding additional duct nozzles. NOTE: The use of one duct nozzle P/N 11983 is permitted for duct 50 perimeter inches or less in the same manner as duct nozzle 16416. M 0• AC rqk Without Comments As Noted In Red Per The Attached Letter i nese plans have been reviewed by The Tuklvti!a Fire Prevention Bureau for conf.;rn-arce wits cl rrcrt city standards. Accortance i;. -uh e:-, to erre',- -,^d omissions which on no nutn,crite vi^,a' c ,'rid stanoaros '-,d of -!,n,,),•,.•; Mr ,t 'pr,r7.+r,i ,: F:. L • adequacy o' ‘1e5 ;1 r;,•> . r-,tr, , ' . . , ,, Additions, d-. It.. ,, jr . -., r , M ,(.• , ., Ithisday^ w'il, ti r,,,1 +r „„,z .. resubrnttai or ; ev 5, d ,� a ! c• i.- ,It . , isr uw_l. i Final acceptanc; i= . r to f'rV{ t�:t and int..ir+.ctron by The Tukwila Fire Prcivenaon Bureau, Date: Co 3 By: tit•...ma..eaacw'OB1wW. staaairdrzeimr..Wa.-/+.u. IUKWILA FIRE DEPARTMEM Please call: 575.4407 and give this job No.O H- 3)-' and exact address for shut. Sown or rostjrrttion approval FIRE ALARM SYSTEM TUKWILA, WASHINGTON I''i Ill. I �I, SHEET INDEX SHEET NUM3ER SHEET TITLE FA -01 SYSTEM INFORMATION GENERAL NOTES FA -02 TYPICAL DETAILS - WRING AND MOUNTING FA -03 FIRE ALARM SYTEM, END OF LINE CALCULATIONS FA -04 SITE PLAN, SYSTEM CALCULATIONS (GENERAL), RISE DIAGRAM WIRE DESIGNATION SCHEDULE BILE OY WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE , GRUNDE,D )IAT Tblai .A❑VIRfRRFlit+Pki fED Please call: 575-440Z and give this job and exact address for shut, gown or restoration approval; 0 0 CEPTE Without Comments As Noted In Red Per The Attached Letter ;nest plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Ac<op?ince is «.-;ubicCt to errors and omissions vihii.-,11 do not authorize violations of adopted standards and or:m antes. The responsibility for the adequacy of Cie::.i.01116.sts totally with the designer. Additions, del'Ltio;; or. rc v;irions to these, drawings atter this date will void 'trri `d' t- j ftnTr e: 4Od...vill rdquire:a: resubmittal of rovisod drawings for subsequent approval. Final acccptcr''ce is subject to field test and inspection by The Tukwila Fira Prevention Bureau. Date: 14!13108 By: AVIA Si j ..�C..tS�i....2R.Gt[s.LLE.s..�a�.II::Ts.��.�.•�••mm SJJ� THROUGH NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of -Acceptance.::...: Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. EACH DEVICE WRAPPED WITH • TAPE AND TAPED .AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL ' DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. 'NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY. HAVING JURISDICTION. 5. INSTALLATION MATERIALS. (I.E. CONDUIT, . WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER; OPTICS CABLE,:. FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY: SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT ,BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA'' 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR .CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR. SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK ' SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C: AND NFPA 72, SPECIFICALLY SECTION:1-.5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ,ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL, BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE; MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS 'AND CIRCUITS WILL BE ON; . THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE. EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT 'BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR- TO. FINAL. CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. ' 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES,JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE . IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2002 6.4:2.2.2 ALL STYLES OF'.CLASS .'A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC,; OPTICAL, FIBER) `.SHALL BE INSTALLED SUCH THAT .THE OUTGOING AND RETURN. CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY.: THE OUTGOING AND RETURN '(REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2002 A.6.4.22.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING' AND RETURN CABLES. `' �: NSURE:. 'THIS SEPARATION IS`RE�QUI�RED T;O ,HELP.PROTECTION OF THE CABLES FROM PHYSICAL' DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT)'',WHERE THE CABLE IS INSTALLED VERTICALLY AND. 1.22 M (4 FT) W-IERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 2 1 11 13 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD T -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD I HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD I�,� LINEAR BEAM F N SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G, RING CEILING ®pDUCT DETECTOR SMOKE AD2-P W/ SIEMENS TSM MODULE. DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM EC (CEILING MOUNT) SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE L (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM © STROBE C (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) FIRE SPEAKER RM C (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. Y FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM BID STROBE WP (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FATC FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.❑, FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS .BUILT REMOVE N/A N/A N/A N/A BLUE AS -BUILT NOTES TO CAD N/A N/A N/A N/A ri ht Tukwila 2006 b Guardian Securit S stems, Inc. All RI . hts Reserve L;. 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 REL=EASE/REVISIONS==' Lu CE i aL V Wcp 0 1 i C t 3 rr {? isi ljI CO CO J CO < Cf) Z WO (n �ZZ s w= cc U u) w o de ;'I iib T ' + T_ It J z. H z V a z z E r 1 SCALE: j 1 /8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI. DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: 2008 \JOB NUMBER: SHEET -01 L h sok ! ( 'o & IC6 dt H -t.4. C”-• ett ie F.4- kyr ih- is) . r i I ri WIRE DESIGNATI❑N ' SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S 2S A V 2V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATION TWISTED PAIR RATED -#18 'FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE , GRUNDE,D )IAT Tblai .A❑VIRfRRFlit+Pki fED Please call: 575-440Z and give this job and exact address for shut, gown or restoration approval; 0 0 CEPTE Without Comments As Noted In Red Per The Attached Letter ;nest plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Ac<op?ince is «.-;ubicCt to errors and omissions vihii.-,11 do not authorize violations of adopted standards and or:m antes. The responsibility for the adequacy of Cie::.i.01116.sts totally with the designer. Additions, del'Ltio;; or. rc v;irions to these, drawings atter this date will void 'trri `d' t- j ftnTr e: 4Od...vill rdquire:a: resubmittal of rovisod drawings for subsequent approval. Final acccptcr''ce is subject to field test and inspection by The Tukwila Fira Prevention Bureau. Date: 14!13108 By: AVIA Si j ..�C..tS�i....2R.Gt[s.LLE.s..�a�.II::Ts.��.�.•�••mm SJJ� THROUGH NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of -Acceptance.::...: Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. EACH DEVICE WRAPPED WITH • TAPE AND TAPED .AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL ' DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. 'NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY. HAVING JURISDICTION. 5. INSTALLATION MATERIALS. (I.E. CONDUIT, . WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER; OPTICS CABLE,:. FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY: SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT ,BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA'' 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR .CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR. SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK ' SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C: AND NFPA 72, SPECIFICALLY SECTION:1-.5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ,ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL, BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE; MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS 'AND CIRCUITS WILL BE ON; . THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE. EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT 'BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR- TO. FINAL. CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. ' 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES,JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE . IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2002 6.4:2.2.2 ALL STYLES OF'.CLASS .'A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC,; OPTICAL, FIBER) `.SHALL BE INSTALLED SUCH THAT .THE OUTGOING AND RETURN. CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY.: THE OUTGOING AND RETURN '(REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2002 A.6.4.22.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING' AND RETURN CABLES. `' �: NSURE:. 'THIS SEPARATION IS`RE�QUI�RED T;O ,HELP.PROTECTION OF THE CABLES FROM PHYSICAL' DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT)'',WHERE THE CABLE IS INSTALLED VERTICALLY AND. 1.22 M (4 FT) W-IERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 2 1 11 13 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD T -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD I HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD I�,� LINEAR BEAM F N SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G, RING CEILING ®pDUCT DETECTOR SMOKE AD2-P W/ SIEMENS TSM MODULE. DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM EC (CEILING MOUNT) SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE L (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM © STROBE C (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) FIRE SPEAKER RM C (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. Y FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM BID STROBE WP (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FATC FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.❑, FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS .BUILT REMOVE N/A N/A N/A N/A BLUE AS -BUILT NOTES TO CAD N/A N/A N/A N/A ri ht Tukwila 2006 b Guardian Securit S stems, Inc. All RI . hts Reserve L;. 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 REL=EASE/REVISIONS==' Lu CE i aL V Wcp 0 1 i C t 3 rr {? isi ljI CO CO J CO < Cf) Z WO (n �ZZ s w= cc U u) w o de ;'I iib T ' + T_ It J z. H z V a z z E r 1 SCALE: j 1 /8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI. DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: 2008 \JOB NUMBER: SHEET -01 L h sok ! ( 'o & IC6 dt H -t.4. C”-• ett ie F.4- kyr ih- is) . r i I ri W1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE. SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AIR DUCT 6--10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL. OR PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 0 GROUND r 0 O O HTRI–R OSTATUS LED DUCT DETECTOR LOCATION OID 0 N.O. I` 0 COM 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE r DEVICE L NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD)- MAX. LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING TUBE `•� INLET SAMPLING• TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC 1.1 - AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE �¢� FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE t-) RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 n A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF. 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED:: AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION, 10 01 TB1 i mm0oo 123456 HCP TB2 65 i END OF LINE DEVICE 5 7" U 0 C3.6K 1/4W) .�. SUPERVISED �/ SWITCH GROUND i 0 0 0 0 HTRI–D OSTATUS LED I>\ 0 NOT USED NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 GND N AC 101 IrI 0 PAD -3 0 0 0 • INPUT INPUT: TROUBLE NAC1 NAC2 NAC3 NAC4 AUX • 1+ 1— 1 2+ 2. NC C NO +' — + 0.3 24K it TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF . ;:;' LINE DEVICE 3.6K 1/4W):'''!, NAC=4. NAC=3! N,AC--2 NAC41 UPERVISED WITCH FRONT VIEW /' NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE 11% DEVICE LOOP NOT USED REMOTE v DEVICE LOOP 0- 0 0 FROM XIS CONTROL PANEL OR (+)> PREVIOUS; ADDRESSABLE DEVICE (-)> 470 OHMS EOL 0 0 TS M-1 o< zoo • ' ORO ;* aoo � 1..0 d 0 1:2.3:4__5. TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL 0 0 EARTH GROUND -)►(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE FROM REMOTE POWER SUPPLY C'S' CABLE) rROM ;FACP (VOICE`. CIRCUIT) C'V' CABLE) SCALE: NONE (�-) ( ) STROBE SPEAKER 0-) . STROBE (+) (_) STROBE SPEAKER (+) (J) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R E: 80" A.F.F. 4S:DEEP. BOX W/.1-1/2 EXTENSION. RING (SPEAKER STROBE) 4S BOX (STROBE ONLY): SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. X0-93 TGPER X32' F D' C TOO 100' F F (3 311' G HUMIDITY: X RELATIVE HUMIDITY. NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POVIER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WIEN USED IN CONJUNCTION 1%1TH DUCT HOUSINGS AD -11P OR AD-11XPR REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE DB -11 STANDARD SMOKE DETECTOR BASE TO NEXT DEVICE > ( ) DATA OUT > (+) DATA OUT Jt CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID -- CEILING HARD LID - SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE. \. CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N BOX—, MOUNTED: ON \� CEILING, FLEX �. JUNCTION BOX MOUNTED AGAINST CEILING : SUPPORT O O TO NEXT DEVICE CADDY BAR :SMOKE DETECTOR. SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING Copyright. 2006 by Guardian Security. Systems, Inc. All Rights Reserved Ti! Y'II f`i1 • 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX . (206) 628-4990 TEL. (206) 622-6545. C C C C Co Co _j CO < o) cZ W WO E-0 Cly: zz i cc=u) 1; H <C Q I tui0 LL LO }-- I { 11 •f ''i ;1 I"I Z I CAL DETAI 4I , CAE:' 1 /8" =1 DRAWNI BY: UANIDE:RSON DESIGNED BY: R.VEZZANI DATE':2/27/08 BACKROUND PLAN PROVIDED BY: �; it Ij; �JOEI IJUMBER: SHEET -02 •s PqLL i I t k 1 I . t li ;et •Atthhtri.1.•••!...Ahrt•I ...,......1.11...1 , i I , 1 i I - - ...• r i ! } , ..... • , 'i I D , rww•tt;•••••=........2........0,4,3••••trwtj4t=wt. ?eh= • ••••••... •t .1 h.• .W.. ...., r wt .... • w.. . • V ..,....; .•.1 wr.r. r h ... .. • rcurry•re ••••••••••• ,, rr,....r. . .•••••••,,,,,,,,, .1 P. •••••••.-,,,,—, srt,....ritr,••••• Cr 4 ti •t, htt/r3.1 t•I .4.1••W ttt t ..... . ••hr•,....,•••,wwt. tt•rtt tW:,,,,,.. Wttt, h., .-W, Witt." ',tn.,. • ht......• W • h.. •• hr, •••,,•••• t.,••••••••••••••••••••• .• •••,../...• • .......h.......• M. { rh.r•ory.g.,,,h yh.t. • ,:::,,, ..„ „w .: .ITT.,:Zta..;0•. i t ; • w -; i , ! [torr 00ARD At ACARM 1.--, • ‘: : ! ul1.f::P',11.1:„..41l.C.ITC%Al-ITICIet•IPE.. E4I:..,L.C;;97..° I / I 1 I TERMINATE ALL CAT -5 1 ) TELEPHC44. T.T•RW1?.L-- \ i • It ' • .h., i , '1 ',.' Elt..WID Tar ; f!' Yc4114'1k 4fft.2111IRMIEFARROMIPELMINHAIREPASIORVE.In • , I EM g•A6 POS 1,10. r.IC. TO TERFA;MAIE .All. CAT -5 C.AtALE. r01§ POT • • g ,• f•.•:/”.• ,•••••••• •,..,•••••••••,,,,, '12 1C•'i ".41. .• ..... 4-, I `1;;•?;,' • • -t"?-"' I Ws;•••—••••; . ..... ..... I • ...... „• gq.,\-•••••!Iml";;;;!, - • ;rm. F.F.,`,11%/fF"FP ffgi -" 14" •••••••••••••vr,' tz,rrets• -1, • t . D,2V,S lit• PANEL 110 • .. .,;,_ ;i• '• 1 r '‘? • 1`-`"?;'. .• ;„„ • ; • ... , 3- '44 0, I 11 11 3 D,2V,S 1 i . 1 n-----4.-1..=. - --,,,....„......„__.„,,,,Igi-,;!;-• ,.,, • r• • . 1 I •,7•7re ,,,I, L9 i : ,, t.,,i , t 6"...' . - 1 I , •— .... ..... t 1 r-1 Ili I E -7I r,4•e•t. ATAV C; A Vi3§11,11,1,Ae.T: n§,r•i§Ar IIi.§;17•7 • ',....., • • --,--)— v -..i 1 •„, Tes ira-"‘ " 1-; ( 8 Z§"- . , : • qt; •/ • j !r,a; 15 ...... LA. -4.: . '... ...... ........, Lt...,:,.1' ... ' . ra, ' 3 F.----1 ,•,--7---., .,!•:-.- --...1 0.q., - \ i ,'.% is 1 I ti.tS I 2;A, I el , I. •••••,. --.. ..-- -.-....!---,-....'„ •. vArr,T21.-.4i-Z,--X-nyfrAi K::..0•71,;.?-,-.2-..---za',-:,-1...i. t4,44.114.11.141•41,1114141. .1.4) • .,. f 11 !!!•5 rtt h. • • • D,P1./feS!•;---tz) 4:4 .... ... — Li.... ......... 4 --• ...... 4; "1 1 I! r(1,,....,. Ti kiikVir„,.,!-,T- V.."----4- .. , • _ _. . ...`,•--11r0,4;i i / 1 i ...../4. v 4„,,i,-•• r-- l:7;41;13- ,1.:..!;" F' ,,,"". ',' -4-- i •, efi 4.4,-t-r.011,:z.,22,,t.%,g-' k,..i,a!---,------, r,,,•,::iv.r.,..,,,i.,....•,,,,,,.,,,..,,,,,,,,...........,„2-s-..,•-••-- -7-$.. 7;71 .„7.) • 11 ,.....-- : 4. -!-:.6.-;.,!--,r,,,,•.4 , d " • "0- t r--- . r ,••••••• • •••• „77 e ••°. ,/, S.,,t•f' .40J:.^..."45,r, ,sy, 1,.\.r; •:4....S.' ,_ ...„„,„.•.„ /.„„,,, „,,,,,....„.,..,,,,2 514 1 I - ..•,../..•••• ............ nr/re„,,,,,..0.,,,,........, etei.rn) ,,.--1\172.,ii., If A 7 • -.'-- Al' I ..." g k- -,...,- ek... .., „...-:\.''..0,.4-.,'.---- \ 1.,,-...,;-k• , \ ' A' ,-,,,,,,;! ...,...e> ... "..., I •••, b,W W•'.' ...,,,, .• "'. 1 li'qfle, -0''" ...1 , ,..e :.,2...: 7 :,.=.1 ,,,1 ;,..:1. ,„... , 1 . ••• :I : :: ,:'. :: .. : ,.. :::1 7 : :: ...„.. , ,. 0.,,,:” 1. .1 I, illi,•5,..i.,,,.....,:,..1:zi......!-j. 1?".'z's;'-'7..:2:-1 It I ' . i /...,....... ..... .. 1, .....,..7/,‘, /.....,A ' 2S 2V • , !;71 .," .,,, ./.$. ... . '• 1., I •:;) 2 2/2 5..1-liE.I.PE I) 10 P-IONE cqm. s ofi 14 0 H. 0 1 0 I i •,,,,.... ; , ..,,,,,. s,, ...,,,c. _ • •7" 1 cil,e ., ../ 1 ..."' ..;:•••' „ ... ,,,,••; .<,,• , ,P.::, , s ,., , .,,, /• ,,,A....' / , ' . ,,,•• ; ..•:-;,; :,:,,z‘, ,,,; ,I....:.:-., , ,,,,,,,.,,,, , .4,- .-. ,• , ..!:- `7 "'• ''-•::-......Z.:;,,,,, s 1 ;:t II ' -7:: ....... ...:-..‘.',... • .....,:. ::-.:::-..-. %-.1.-,,,-;,,,,- .... • . . -.-----..-- II II • 11 I II,' • e.P •••,!'" I 'tv•i '!'•fr •A`, Li • F ` '41 n - I( I `I it ill __„ 311 4 ,1 ...,„, 1al "y F.C. ... — .... • ...... .> 14 Ai/ CI.C.SET • tanSragriallall91.41M. KOMMINIIMiningetc ifit+tra'af.a1M-""'” 1,s II t. II ,,'.. za•.11-- '• 1, 43-...„,...,..4 --..-. 1, 1 / 1,,,,,,,,,,,, I, 4 10,,,r,-...,'. ai ri...,. ,--.-:' ',,,,,,,,' , II ii*.; lit• ; ;•,-. F.' ; if :2 . ; --0!•; IA NIi ...,'.., gi,',{ • .1 i r4.0 •,,,,,,,it, 4sly:;:-..,1;:•.••••1_ h.q fr ' 4 . II 1 VP 1>- ....'::::;.,..„!',3tt ..... ..._ i....., 1;•>'-':rbi 1 l'-';'• L: A i!ri,1,11 12r::•,),J1,;,: 1.11 ii ' 4 "'''•-•-•'" It I IP' ,,NM-1?,1413:1!:.1'7,-?:!1`• ! • "- -r.:=1-1 r4 ,i ..11•I it, 4 I; -------,-- --------A: TO---- ---------1Ii II ' dr rl • - Ill I I !!t-: ' --11 •• 1 ,,., k ! J:li r ... . . ... • ' ... A 1 -.44 ,-, „ - 1•:`,„ , • I f ••;: "A. -„,.", - il— — —!1.! f . + Id i,.t - .- .. . ..... • II , - .-- -- ----- ------- --HT !/;;.• '..-- .. • . . 11 11 ''''"'. ' ' i WI ' " ill 1••••• ••••••••• 4-''•••••""'"4"— v• I I 5'64;3 I • • If' . K•LI A Ays'' „, t 12.; \ yr. gll II 41 •t*:,,,Azy -.6 1••,. • • 11, • • ,;`• "••• •':'•••„ wIrc • '4 •••, • • `','4..‘,.. •rr: ',I,‘ ‘2, Vrt.A. ......'w;:'..Z'''....:' 1 '''‘' \ w. ...Z., S.'h., "..‘j.% , ;,..'. ''' :•:.: \ • ' '''.5-!;....:•:-.;::-..!;.. . ,'''',K' ''''`'-N, ' ''''''‘‘i;s .,,,'-'• /-/s<::-..,, ''"?•‘• <,;',-':;t4 \''''',:::;';' . • ., '',.'.. ,..../211;0 \ :;;..' 75 7' C.„:› • ',1•7 :111, 11 .. es->„,., -.:,.,,, ,$,,/ ,, 0'"'..,„. ,,.'''".';,', c, i .-.) ',-, ..../.:,,, ,,T.A.1/4„", ;, il 2...y.D '• ______ ........... ..- .,..,. .. - . ,.. - i .. ..... ..... ,..f....il ..... ....4_ ': "•-•1`•..„ .11; i'll"--71 t tg il ,..•••;,. i!. • ,. ..... ,i r [1, 1 ' -1,..-... ▪ .... g • ".? 1! s r". h .‘ • 11 \‘.1,-"'",1`• A'N • ' ' • /. •.;\ • • .•$`• ',. • , \‘‘-j • ' .0"" 407 'v L • . ! • ,• r• "s„,.•,„ , ••• „ - ” ‘0, 4 ; •M5 \ .11C; I \• rit '11PD IF ! /4\ •• It / 'li I Iril .▪ /. •, 1111•-•----::---4- •;I:...-! ., J i i 1 , I 11 1 1 II II k i Is'• 11 g i 1 paf.:.,.., .....;z:,:::-.:;=,-.•,:.-.....:,:: 11, ; i • , t 1 •• /------• . . -... i I ; 11!..,,,-..,..,,,,,,,2,19r'::::.:,:::.:-:.5.. es*, ••-• ---av;s; ----'.- --ift----1-- 'Si -4. --- III ?!I••• / " " 7 I • g I 1 •••• s ; • • • , . t % 1`"? r ) s..,\!..,„.\. ,...,.,..,,,;,:•,,,,,:.::::,:....,,,..,:r. ,..,"..A.,.., :,,...: .,.. \ ,,.4> :,,t,,,,,,,,,..r,,.. ,.., .f. ..',V, \ ' . '" ,or.,.=.1st. • 1 I, •,,,. \-\, .s••:::: ..--,,, N.,_ /, ; ..,.!::::„ ,,... ,•,.! ..., „,.‘. ZI,,,, '1k '•\ `ty,''''' II ‘ k... >'. ./•-` \ ,..gs. %, , -. "j'' ' . sf ss/rcl:,,s '..ts ''.. .\% '1:44/ \ . y`. 1.1 \ fi71.12 rAz§:” '' 4. ) . ,.. 2... N! !." ,1,.'"Ffir.;.' i s ,..„ '1(:,.ji' • sil• 1::,..r, g '-•••,,j? 111 ,,:::,.....5 '',.,S \'s.:\ •,,,,,s,. Os,,,,,,,,,, :'!A• ,.."' \\ `,.., ‘`.. ...;:Z....` . ;',,r,:, y - 1 ..! 1;•., 4' ••• ‘"2. -...,.., 0 e -1,, -,„\„ ‘,„..., , . •,•.;„..,„ - \„N :!-%7 z... ssss, Ap,..,0' ,...." .414,411,1,-/-7,1.1,4.41.,..-111 • WM-3 Ii FIRE ALAI AN APPROVED BY A LISTED ( PROPRIETARY NFPA, STD. 72 UCENSED CON' DEPARTMENT, SHEETS AND S EACH DEVICE, COMPLETED Pk! FOR REVIEW. ELECTRICAL Cr. AND OUTLET E: OWNERS FIRE SYSTEM com-ris SYSTEM SHOP PLAN CHECK PROVIDE DOM SERVICE CONTI / i I " ! -2.`A .. .... S,2VD 4.1;) ... .1 . ... VA sl.: 7,4:1C.". 1:::'' S,2V5D .",..e.,..":..,F..":o...;:?:,..ic:•:-'1-,,..`',,,, liT ..,,,Ai , ,..-- \ 11 of ,S.'''. 7, t 1,:.::1:::::::‘.411.<: m4iI• ,.t\ ,...., . "t 1' /-/ ,A.C` • f;', ',,,,,'• ..., ,...I /..-:!/ '', 30 I ' i I I 30 ,.,,,,,,,) • tf. . . i ,-c.,%•.7.-17.;117,1".1111i.171::7-7-7,111,1rq1r..7'"1"4, ' \ . I I _"' .. 4 141 2V,S5D —,==) \/1 c•ri " . e. IF V..EPFioRiii:" , ..... .........,.F.004e.,,,4.......',.. ,,,TiA.,1.2--- 2VSD ` 2V,S,D -- pos •-7„ - '`.. ii. J, 7:17 .• . . 2VSD • TE-,..FP/4011E-- r-, •--\ ; , 4 X 3 ,• . EOL—S2 • Ar q., „,...4„, J.., 4 .?` .cI:1 :>. S,'',`.:',„ ,. . • "..\, ,",,.. 'rszr-r,,••••• !s, • ••• ) ••; .,' LA Q..1../1 „eef. .1 \\ \ \„A* \• • N"`”• \ • q• -'44,::';q4. ,..,`", ‘A.,' l's :.. . ..,..-•„, .. ," 1.• ..-...V s.▪ .,";,,,,,..1•,s,,.,.., \ \ ,, „Is.," ,,,i, ,,,,,,..1::,,.--'..• ...) , „,.•••,..' :s., \`" ( ..,;...:••,' '`';N:\ ':' ,ss \').,. .....;f: -..,17-- F., t.sss..,...„..., ,. ,f,... ..F ff'' >:;;." 1 ,F"' •.,,s, \ 'rk: ‘,.;:\‘:? ".'.r.;r..C•fl> ' ...e , , ss,,,...,.,,N 'F., :i 5.\\ ,...' \ ''.„1'-...S. \ ' 1.1 • e 't , N. . 1, f.," ... , . .f.,.. ‘`. I, ,... N ., ':•,•• , ,-,;•• ,_ ' - - ' ,•••,;>g* ' 'ti,'', . . • , . • . • ;.- ' \ .:.,/\,.,,;,.,\, ..• _,...?,......,:;2,s;,••7 -.."' : • :i .,..,',..-...;-::•,;1- C:" ,,;:i''°. .‘,,,,' ,:','" ,...• ) ,t'... ''-'''.1? •-•••'',.:, ' ,-.••-',..,-.!-' / .....1 r•;) \ ,.., fp .„ 4=x.','2.i;- ...P''.;A;••,-;::::-• t. .,,, rf->''..Z_•;',;' 1E3J'S FRF ALA\V DLA\ NORTH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F— (1) uJ F— F— LU (f) F— U) FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: DESCRIPTION In 1-- 2 <<<<< ‘CALE: 1/8"=1' DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: .1.0B NUMBER: SHEET FA -03 PSI 2S,V 0:LET [1460 CL -J 4v, [D.:: ED') C.11...ri.0".] LEL; Lt CLT:t] L70 ELECTRICAL. ,. RM '• • • PLC '(C 11 STORAGE 1495] 14301 .75 C) CfI LL CD 1 11251 420 LL.1 LI • C.) -ci LI' 0_ 1T) 1 , L. Li] ----- --- 1410] L '2,5o 1.5 L.L_1 0 CI C) 0 >-- 1235 Li! 13:05 0 EEL_ ---- a 13001 0. rT.-• ' (,) '77 ------t] - fl 25 C.01,1PACTC 11 ELECTRICALPM 11 CALIFORNIA PIZZA KITCHEN 42„. MAC cRil L k 40 40 i P4 1 :,?..-.> .,,,. ,,f'<,-'-'2 -----'iP- c(:A \ ,, "5,--. -- • ---- r• BJ'S BJ'S FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Current Load: Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total. Device Type Qty Amps Total Amps Total , HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 11 0.0635 0.0635 0.064 0.704 Main System Board 1 0.03 0.03 0.030 0.030 'HTR -R , HTRI-D _.._ „ .. 2 0.009600 0.0096 0.021 0.042 'SET -MC @15CD 10.064 0.064 . 0.001600 0.0035 .._ SET -MC @30CD SET -MC @75CD 6 0.098 0.588 i 3 0.175 0.525 . SET -MC @110CD . , ZR -MC @15CD ZR -MC @30CD HCP 3 0.233 0.699 0.064 0.098 0.0731 Amps 0.746 Amps 0.0015 0.03 Amps 1.906 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.746 Amps For 5 Minutes= 0.063 Amp -hours • Alarm Current Load: 1.906 Amps For 5 Minutes= 0.160 Amp -hours 25% Derating= 2.271 Amp -hours , 25% Derating= 1.100 Amp -hours Total System Current Load: 2.271 Amp -hours Total System Current Load: 1.100 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Battery Pair to be Used: 12VDC Amp -hours 7AH H H xxxx RECOMMENDED MINIMUM BATTERY SIZE = 7, 00 AmpereKHours Eco LET] [zit ED: Ti 1.1113.7.1 t ii I 112 11E11 IT' 0.2-'7•2 6:5> 7 0.- •••,e2 ------ / \ 7\ 1 Y ./><. ----- \ \ 17i7/1 ••• _ \ !./ \,.., 1)‹.1r / \ Cs:-/ ----- (s.,(ec:-„,; • • 7 ie:••>).• \ . , \ . ...,'•.' <1;/,.0 7 ' X .5-'• \ •X".5) • 7 \ \ \ \ \ • 7 .7" 7 . .• \ \ 7 • \ \ / \ 0,7 A \ \ \ \ „.„ , 7 \ „. 7. 7 \ \ / 7' V BJ'S WESTFIELD SOUTHCENTER M SCALE 1/321' EOL -S1 S,2V S,2V S,2V S,2V 110 crS,2V 75 75 30 30 S,2V S,2V S,2V S,2V S2V S,2V 15 c3-2S,2V FA -BOX D I FACPI EX 10 30 30 30 b EOL2 STROBE 30 II fl D .7 •.. :.1. C.. N. N N N. N 9 7 < • 7•A e,-••• 77 77. --- 0 0 DD D D D RISER DIAGRAM 0 .70 7 7.7' BATTERY SIZING CALCULATION ; , , , , Notification Appliance Circuit Detail 1 ;. 1 , , i PROJECT: !WESTFIELD SOUTHCENTER MALL , I ; I 1 , ..., 1 Panel: ! BJ'S 1 , , i 1 1--- 1 . iwire Resistance 3.24 i „ 1 Date: !April 4, 2008 ; 1 , CURRENT TOTAL= 1876 i 1 . 1 I CIRCUIT 1S1 i , - I i ' -------------------------11.i € i-,-- I i:! , t '1 1 QTY 1 Device TypeAl Iarm CurrentIWire ; Alarm Total 1 Size I Wire Length Voltage at EOL I Circuit Total i .,1 0 !SET -MC ©15CD 1 1 - ' • : :.9.Eq • • 64'' •.... ,:--1,: , 315961!"' -1-- 1 .! • , . : - I • • 1 - I- I 1 • ' . 1 ( WL * 2 )* (R/ft) • 'Total Wire Resistance ( R ) -1 1941. i I 1 • Total Device Load, Amps (I): -ii .,175!, 1 1.011 2331 i 1 1 I (Total Cct Load) , i , •::. :641: 4664 , - -- _IL 1.971 01 ! • i - i . is -i 1 ---i-- 'r- IVOltage Drop ( E ) ; .• •......., •... • •r•,..._.........•... (E= I * R) 1 • 2 SET -MC @30CD 2 • SET -MC @75CD "1 2 SET MC @110CD I- 0 ]ZR -MC @15CD 0 IZR-MC @30CD 1 :: '98] 01 0 , ]ZR -MC @75CD : 175] 01 0 ZR -MC @110CD • IEOL Voltage :t. , 18.43; .2331 01 i , , I ! I - , i (20.4 7 E) •1 „ , ,. 01 . . • i :_. 0 . • 1 . 1 s • • 1 1 1012 '12: . .1 • -,00 1 • 18.432672 1012 DEVICES= 6 t TOTAL m A=1 CIRCUIT: 1S2 ; , .. i .. . . - : : { ; i . fi.- - • . I - - . . . _ crry . 1 Device Type IAlarm CUrrentLAlarni:Total i Wire Siz7ite Length j Voltage at EOL LCircuit Total 'HI 4 ]SET -MC @30CD 1 • ISETM6@15CD 1 ! SET -MC @110CD 1 . : 2331 ''' 233 1751 - 641: 98 i• 3921 ii51 641 : I ---t t . .. .. - • i . F 1 i_ 1 i ' ; . i . . : I Total Wire Resistance ( R ) .. 1 . 2.111 .1 - ;Total Device LOad, Amps (I ' - 0 iZR-MC @15CD 1 I . 641 - 0! 0 • 1ZRMC @30CD ., 01 ) 1 1- '17598i- 01 , , ! -,---- 0 I ZR -MC 5CD . 0 ']ZR -MC @110CD ; • ' 2331 • , (.. • 1 1SET-MC @75CD .... 1 Voltage Drop ( E ) 'Jr i s .I (E= I *R) . ; ; I EOL Voltage , 1 , i C. - 18.581 : ( WL * 2 y (R/ft) (Total Cct Load) 1.821 (20.4 - E) ()1, ) ol 1 t - , 1 s 1., 1 t -1:' t ' i -t- ; ' DEVICES=I7 : ' I TOTAL. m AL -1 . . 8641 . 12 325, , 1 864 , , . „...•: ...„ .,....„.,.4.. ,, ' - - •-• 18.5804161 - ---t • ' 1 - 1 ; Notification Appliance Cir tuit Dela it jj, • - • ' 1 . 1 A . I . PROJECT: i WESTFIELD SOUTHCENTER MALL- : • , -,'-'• -• I I i I 1 ; ; Panel: 1BJ'S ; iWire Resistance 5.16 ; , , , 1 Date: 'April 4, 2008-1 1 CURRENT TOTAL=1234 1 I , i i t I CIRCUIT:1SPEAKER CIRCUIT LI'', i i QTY 1 Device Type: ; iAlarrn Currenti Alarm Total 1 Wire Size I Wire Length 1 Voltage at EOL 1 Circuit Total i ' i , ,I 13 170.7V1/8 • H, 1.81 c 23.41 l I • i , i Total Wire Resistance ( R ) • i • - . 0.00 • ._ -,-, 01 0!- j - • ; i i 1.1 ( WL e` 2 )*(R/ft) ' :I • : • , , , l' I Ol - . " 0. , ••;--It''' .41T-. otal Device .Load, Amps (I):_ i. i , , - I 1- • . -I I. - • - r t . 01 0 i " , , 1 1 (Total Cct Load) 1 . i 01 01 i.-- t r , O , .• : 0.001' I i. ii • i i !Voltage Drop ( 8 ) 3 0 1 0 1 0 1 c I 1 , , (E= I *, R) . 1 o , , , . di [ JEOL Voltage : : ' ,': 2040]. • 01 - ; 0 i i• oi OI i , ; I i I (20.4 - E) J 1 , o 1 I 6 , of , i , I i o i ol 01 , 1 , _ 1 DEVCES •, 13 f TOTAL mAt--1 23.41 12 0 1 20.4 1 ; ' 23.41 l VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO:, SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 LU << • J 6ALE: 1/8"=1' DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: .,0B NUMBER: FA -04 SHEET VICINITY MAP (Suite# 1150) SCALE: WALK IN COOLER General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only jn the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. 1;3 II»a EXISTING PIPE NEW PIPE EXISTING ZONE T5 4" MAIN VICINITY MAP DETAIL NOT TO SCALE - -- EXISTING ZONE T54".MAIN RISER ROOM "B" DETAIL HYDRAULICS REFERENCE ONLY DINING 102 EAR DINING 104 BEER COOLER 125 DINING 103 OPEN DRY PIPE LOCATION WOMEN 108 EST RM VESTIBULE 107 PATIO 127 B.J.'S RESTAURANT WET SYSTEM Remote Area: Retail # 1150 CALCULATION DESIGN CRITERIA: STAWARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. f;OVERAGE per HEAD 130 Fl" DENSITY .20 GPM / Fe fat 1069 Ft° SPRIT, KLER Reliable Model GFR ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT ;SASE OF RISER, SYSTEM REQUIRES: 333.45 GPM a© 47.79 PSI • At time of Design 17'4' CLG.=28.75% AREA REDUCTION METROFLEX SEISMIC LOOP Ordinary Group I1a0.20gpm/ft2 for 1069.00ft2 Ordinary Group II.0.20gpm/ft2 for 861.00ft2 4 TYP ROLL UP DOOR 4 SIDE WALL HEAD TO PROTECT UNDER ROLL UP DOOR WHEN OPEN. B.J.'S RESTAURANT DRY SYSTEM Remote Area: Retail # 1150 NFPA 13 8.16.2.3.1 Dry pipe Systems in Non -Refrigerated Areas. In dry pipe systems branch lines shall be pitched at least 1/tin. per . 10 ft (4mm/m) and mains shall be pitched at least %in per 10 ft (2mm/m). B.J.'S RESTAURANT & BREWHOUSE 1/8" = 1'-0 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 861 FN SPRINKLER Reliable Model Fl FR SSU ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 208.29 GPM Q 100.95 PSI • At time of Design DRY SYSTEM VOLUME = 31.15 GAL TOTAL HEADS = 11 Igyo 11# `O TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD SPRINKLER BRANCHLINE • FLEXABLE CONNECTING HOSE ..' IN STANDARD LENGTHS MOUNTING BRACKET SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE S7B•((WIIT BOLT (31A' Bt0EO LENDTH) NG.PW SWNELSWAY GRACE FTTrINC \ BRACE PIPE FIO 1006 l-FAST CLAMP- '.\\\ SWAY BRAG EATTACIeLENT LwE PIPE OI LATERAL LINE RESTRAINTS tLWPICREADED BRACE PIPE ItCre O INEII' aED IENOTHI FIQ809 NO -THREAD SW NEL WAY BRACE ATTACHMENT BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT MON11-IEACED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Weld temps must be inspected before pipe; is hung. Do not paint piping prior to hydrostatic tt, approval. Hanger No. 07C HILTI Kwik Bolt III Sam of Concrete ID Cart.. Line of Pips Note on Ren Nob on Phi: Hang..i mA,er and IN Dknonsicn HANGER DETAIL NOT TO SCALE Steel I -Beam or Bar Joist • Rounded to Newest Inch Hanger No. 01S Top Beam C -Clamp Modal 300 Michigan Top Bual°a"' C -Clamp with Lock Not Note on Plan: Manger Number and 'A' Dimension 2W VIC QUICK RISER 30.03 SERIES 756 FIRELOCK DRY VALVE: HANGER DET NOT TO SCALE FLR MOUNT T STAND TANK MOUNTED COMPRESSOR TO BE USED `" I Lei ti 0 Without Comments As Noted In Red Per The Attached Letter B.J'S Restaurant & Brewhouse fL Lu 0 I nese plans have been reviewed by The Tule.vila Fir.~ Prevention .Bureaufor conformance with currE nt city standard .1.i.' / cce p tance is L ii: , t to errors aril omissions w.hi6i do not authorize violations of adc e i stant"i roe Liri.r! ai .+lr; ii; : ;_y. t {):. s iftr Tori • l'ddt-,C7U;a;y Uf ii 'Fi,;lit rc',i i'(::I+"L:'''iii Rita ' . y cat:: .y ier.= • Additions,'•deletft :7 or ('<.;i!ifii(:?li::i. t,J thee draw ng y • this. date w" iif.!ioi t;';c; Ir:c%pionce ' nd will req( ire •l r"e5ubrnit al.a i`a'I.od drawings for subSequen: claim al. r acccprrance:.is•subject to field test and inE,per n by yTh Tultwila.Fire:Freventiori Bureau. ate:: By.1uv l. • 0) .C1)CD\ R.kassiu .. . P6 kl:•z iur.•Jf:twe-,•.yy,M1.. ...-n.. TUKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job No._0$-3-II and exact address for shuts down or restoration approval NOT TO SCALE CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend APPROVAL: City of Tukwilla 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE 4 -WAY EARTHQUAKE BRACE SYM. SIN • R3625 QTY. K 59 5.6 SPRAY ORIF. Upright FIN. TEMP. ra s 155°F B S MFR./MODEL REL F1FR SSU HYDRAULIC REFERENCE POINT HANGER SYMBOL 0 R3615 48 5.6 BRANCHLINE RESTRAINT iy) VK176 9 5.6 Pendent 12" Pendent 1z' Chrome 155°F REL F1FR SSP Chrome 286°F VIK M STD ADJ OR DRY 5 5.6 Pendent 12' Chrome 200°F REL F1FR SSP CONT. NO.: KC0015 DRAWN BY: Chris J. Isaac SPRK. ON SHEET: SEE LEGEND R3625 7 5.6 Upright 14" Chrome 200°F REL F1FR SSU R5714 4 5.6 Sidewall 1s Chrome 200°F REL Fl FR HORZ SW total = 132 SPRIG ON JOB: DATE: 0429/08 Western States Fire Protection Company 7102 180th AVE NE, STEA 105- REDMOND, WA- 98052 WESTESF136CF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIN / DALLAS / DECATUR /DENJER/DULUTH /HOUSTON / KANSAS CITY LAS VEGAS/MINNEAPOLIS / PHOENIX/ PORTLAND/ RAPITCITYI ST. PAUL /SALT LAKE CITY/SEATTLE Phone:425-881-0100 Fa)c 425-881-3030 BUSS Restaurant & Brewhouse FP -1 1159 South Center Mall ASC) OF Tukwila ,WA 98188;x; Looe • B.J.'S RESTAURANT & BREWHOUSE da 1 SHEET 333°`?.. VICINITY MAP (Suite# 1150) SCALE: NTS WALK IN COOLER 122 FREEZER 123 General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NEPA #13 Ordinary hazard Class II Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existingfire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyin the areas of work. All other areas are not in contract and WSFP is not responsible for exiting conditions. 0 ®® ®H EXISTING PIPE NEW PIPE EXISTING ZONE T5 4" MAIN VICINITY MAP DETAIL NOT TO SCALE . ---- EXISTING ZONE T5.47 MAIN SYMBOL LEGEND RISER ROOM "B" DETAIL HYDRAULICS REFERENCE ONLY BAR DINING 104 BEER COOLER 125 DINING 103 OPEN NIC DRY PIPE LOCATION DRAIN TO OUTSIDE THROUGH SOUTH EXTERIOR WALL B.J.'S RESTAURANT WET SYSTEM Remote Area: Retail # 1150 REVISIONS CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 FLP DENSITY .20 GPM / Ft' for 1069 Ft` SPRINKLER Reliable Model GFR ORIFICE 1/2" K. 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 333.45 GPM @ 47.79 PSI At time of Design 17'-6" CLG.=28.75% AREA REDUCTION WOMEN 108 REST RM VESTIBULE 107 'DINING 5 RVICE TAKE 0 128 METROFLEX SEISMIC LOOP TYP ROLL UP DOOR 4 SIDE WALL HEAD TO PROTECT UNDER ROLL UP DOOR WHEN OPEN. B.J.'S RESTAURANT DRY SYSTEM Remote Area: Retail # 1150 NFPA 13 8.16.2.3.1 Dry pipe Systems in Non -Refrigerated Areas. In dry pipe systems branch lines shall be pitched at least'/in. per 10 ft (4mm/m) and mains shall be pitched at least %in per 10 ft (2mm/m). B.J.'S RESTAURANT & BREWHOUSE 1/8" = 1'-0 Sprinkler Legend CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft` DENSITY .20 GPM /Fre for 861 Ft' SPRINKLER Reliable Model F1FR SSU ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 RESIDUAL 20 FLOW 10900 PSI PSI GPM AT BASE OF RISER, SYSTEM REQUIRES: 208.29 GRA@ 100.95 PSI .,a • a ' At time of Design DRY SYSTEM VOLUME = 31.15 GAL TOTAL HEADS = 11 TYPICAL FLEXABLE SPRINKLER CONNECTION. • PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE ' IN STANDARD LENGTHS SUSPENDED T -BAR GRID SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE FI+b INWELSWAY BRACE E FITTING BRACE PIPE G I Ei1BE0 LPNOTNI FIG.1 C "FASTCIANP' BWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NDBTHREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE AO LATERAL BRANCHLINE RESTRAINT NONTHRFADED BRACE PIPE , P10.109 N .THREAB SWWEL SWAY BRACE ATTACHMENT i 3R" LW IK BOLT U 1I4 ELIDED LENGTM BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III Cot Rod LOW Rounded to Nearest Inch Sw vel Rig Concrete Construction Bottom of Concrete to Center Lin. of Pp. Note on Plan Hole on Plan: Han gee Number end 'A' Dimension HANGER DETAIL NOT TO SCALE Steel I -Beam or Bar Joist Rounded to NaarastInch Hanger No. 01S Top Beam C -C amp Model 300 Michigan Equal Topp Beam "lamp or with Lock Nut Thread Note on Plan: Hanger Number arid 'A' Dimension HANGER DETAIL NOT TO SCALE 2W VIC QUICK RISER 30.03 SERIES 756 FIRELOCK DRY. VALVE:: : FLR MOUNT T -STAND TANK MOUNTED COMPRESSOR TO BE USED DRY VALVE DETAIL NOT TO SCALE B.J'S Restaurant & Brewhouse TI W 0 Chris J. Isaac 26 CL 0) 10 0 Shawmut Design & Construction CONTRACTOR: 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL APPROVAL: City of Tukwilla R3625 57 5.6 Upright Brass 155°F REL F1FR SSU 21 5.6 Pendent Chrome 155°F REL G4A SSP CONT. NO.: KC0015 HANGER SYMBOL BRANCHLINE RESTRAINT R3615 32 5.6 Pendent %s r Chrome 155°F REL F1FR SSP DRAWN BY: Chris J. Isaac VK176 9 5.6 Pendent Chrome 286°F VIK M STD ADJ OR DRY SPRK. ON SHEET: SEE LEGEND 5 5.6 Pendent Chrome 200°F REL F1FR SSP SPRK. ON JOB: R3625 7 5.6 Upright Chrome 200°F REL F1FR SSU Fib/ 4 b Sidewall Y2' Chrome 2U0" F REL F1FN HORL S Total = 135 DATE: 07/21/08 Western States Fire Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR /DENVER I DULUTH/HOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS / PHOENIX/ PORTLAND / RAPID CITY/ ST. PAUL 1SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax:425-881-3030 B.J'S Restaurant & Brewhouse 1159 South Center Mall Tukwila ,WA 98188 B.J.'S RESTAURANT & BREWHOUSE FP -1 OF 1