FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax
Tut- w la, L'' i
Site Address: 0 o C'Lv (� j Suite Number: Floor:
Tenant Name: M' )C ; t kQ �^% -S. y� ��� �"l New Tenant? g- Yes ❑ - No
Property Owner's Name:
Mailing Address:
City State Zip
CONTACT PERSON -if there are questions about the submittal.
Name: R o e d Q �' Lick_
Company Name:
Day Telephone: C2 'yy5 12.6 3
Mailing Address: ( 3 i s - At S SQA 12 r wA '1E13 y
jrl City State Z,ip
E-mail Address: 'r �t cle 5t1 cw..c� uh5'2C....✓`t 'o^Fax Number: C-2-0 Ci y l`i (17
Valuation of Project (contractor's bid price): $ � V 0
Scope of Work (please provide detailed information): `Ti yr S S 1.13ec
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT: / /
Signature: Date: I I /09/ l
Print Name: 12 0. 2,, A- Day Telephone: C 7 L) - 5 `t a GE
Plan Permit App.doc
5/14/10 TFD FP Form 8
SITE LOCATION
CITY OF TUKWILA
FIRE DEPARTMENT
444 Andover Park East
Tukwila, WA 98188
206-575-4407
Date application
accepted:
FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.:
Site Address: \'-l- 0 Gook r Wi \\
Suite Number: Floor:
Tenant Name: YV\3x V.Aes New Tenant? - Yes ❑ - No
Property Owner's Name: \`j,k&\ \ Wk(y\rpenA-
Mailing Address: \\DC1 \I i 1 \S' VIC., WVA. / 1\k ‘72111.._n‹, AVlll ('A cl Cols
City State Zip
Name: DayTelephone: eP hone:
/-426.48Y %f'o%ct
CONTACT PERSON -if there are questions about the submittal.
Company Name: CsovDYN } \Q \OY1, v c
Mailing Address: ¶DOX \Zl 1� YY1 \\ C' Y,ee� Loi q ��2
City State Zi
E-mail Address: jQ sS\ C Qe C,`f owy-v p. con-, Fax Number: /4Z6j • ygI e(dig
Valuation of Project (contractor's bid price): $ 7(Y).
Scope of Work (please provide detailed information):
.C\ C2)-C\Ce. SVf 1✓11�-e.r \Aeocl
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
'FOR THIS PERMIT.
BUILDING 0 NER OR AUTHORIZED AGENT:
Signature:
Print Name: L Siia 11' iY1��
Plan Permit App.doc
Date: //-/L71 1/
Day Telephone: 4/2�j-4,/$J- 7 ai' 9
5/14/10 TFD FP Form 8
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Max Rider
1240 Southcenter Mall
Permit No.: 11-S-260
Date: November 21, 2011
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206) 575-4407 option # 2 (Inspection Requests)
(206) 971-8718 (Plan Review Questions)
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 20 or more heads require hydrostatic test and system
isolation if necessary.
• For dry pipe and double interlock preaction systems, in addition to the standard
hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24
hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the
24 hours shall be corrected.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2010 Edition.
SHEET NUMBED
SHEET TITLE
I
FIRE ALARM SYSTEM ADDITION
TUKWILA, WASHINGTON
FA -01
SYSTEM
INFOR
VATI O N
FA -02
TYPICAL WIRING AND
V1OUNTING DETAILS
FA -03
SYSTEM
CALCULATIONS AND SINGLE LINE DIAGRAM
FA -04
FIRE ALARM SYSTEM PLAN
SHEET INDEX
Without Comments
As Noted In Red
❑ Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
nr•evention Bureau for conformance with current city
:,-tandards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
c;andards and ordinances. The responsibility for the
:.1dequacy of design rests totally with the designer.
.editions, deletions or revisions to these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
B 1(r
)ate: i f y; /
1//11.-._1*
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any,Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
termination of the testing.
TUKWILA FIRE DEPARTMENT
Please call 206-575-4407 and
give this Fire Permit No.
/1-J, -zt�
and exact address for shut-
down
hutdown or restoration approval.
WIRE SCHEDULE AND CO\DUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET)
D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET)
P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET)
S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPUFPLR RED (JACKET)
S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET)
V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET)
V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET)
I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET)
CONDUIT FILL CHART
NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" .34 SQUARE INCH
1-1/8" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED
WITH DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL
BRANCHING IS PERMISSIBLE
4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION.
6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION INSTRUCTIONS.
10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN.
11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS.
12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM.
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP.
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT.
22.
23.
NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES.
THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE
THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE
CABLE IS INSTALLED
QUANTITY
1
1
2
5
1
SYMBOL DESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
BPS
REMOTE BOOSTER
POWER SUPPLY
PAD -3
SIEMENS
PAD-3-ENCL 66" A.F.F.
TO TOP
SMOKE DETECTOR HFP-11 W/ SIEMENS
(PHOTO -ADDRESSABLE) DB -11 BASE
4S DEEP
W/ 1 G RING
CEILING
®D DUCT DETECTOR
AD2-P W/ SIEMENS
HFP-11 DET.
DUCT HOUSING VERIFY
IN FIELD
TSM
DUCT DETECTOR
TEST SWITCH
TSM -1
SIEMENS
1 -GANG BOX VERIFY
IN FIELD
HT -R
INTERFACE MODULE
WITH RELAY
HTRI-R
SIEMENS
4S DEEP BOX VERIFY
IN FIELD
Di FIRE ALARM
HORN STROBE
ZH-MC-CW SIEMENS
4S DEEP BOX CEILING
FIRE ALARM
STROBE
ZR -MC -CW SIEMENS
4S DEEP BOX
CEILING
A.F.F.
ABOVE FINISHED
FLOOR
N/A
N/A
N/A
N/A
EX
EXISTING
DEVICE
N/A
N/A
N/A
N/A
F.B.O.
FURNISHED BY
OTHERS
N/A
N/A
N/A
N/A
N/A
NOT
APPLICABLE
N/A
N/A
N/A
N/A
RED
AS BUILT
ADD OR CHANGE
N/A
N/A
N/A
N/A
GREEN
AS BUILT
REMOVE
N/A
N/A
N/A
N/A
BLUE
AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
SYMBOLS LEGEND
NORDSTROM
3 LEVELS
171,275sf
NOM
1
macys
4 LEVELS
250,407sf
g
m
I: 15ENO 415'
SISIR7000 g�
NORIA
WOES SOX
0
004
MUD=
GAA
"RIZ gur-Assn
As 5'L L_l
G7F�Y�YSINiO
MAX RIDER
#1240
II
1
•
0)501105
IJ
JCPenney
3 LEVELS
276,468sf
PAID
NOV -42011
r
TUKWILA IRE
vim' -2 „zao
rn
0-3
WASHINGTON
FAX (206) 628-4990
RELEASE/REVISIONS
REV. BY:
0
m
0
DESCRIPTION
SHOP DRAWINGS
w
i -
a
0
11/02/11
2
««<
Z
‘CALE: NOT TO SCALE
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 11 /02/1 1
BACKROUND PLAN PROVIDED BY:
�0B NUMBER:
WIRE DESIGNATION
GENERAL NOTES
Pro
SITE PLAN
rieta and Confidential, Co • ri • ht 2010 b Guardian Securit S stems, Inc. All Ri• hts Reserved
SHEET
FA -01
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
NOTE: FOR ADDI11ONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
TUBE OUTLET
SAMPLING
TUBE INLET
SAMPLING
DUCK OVER 3' WIDE:
SAMPLE TUBE MUST GO
THRU THE DUCT AND BE
CAPPED.
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
DUCT DETECTOR MOUNTING DETAIL
120VAC-60HZ
DEDICATED EMERGENCY l
NOTE FOR ADD1710NAL SPECIRCA1IONS SEE PRODUCT DOCUMENTATION.
*CONTACT RATINGS
4.OA 0 125VAC
4.0A 0 30VDC
ISOLATE FkIIMSGRDUNLINGD
TO NEXT ADDRESSABLE /F
DEVICE STOP IF LAST DEVICE
FROM XLS CONTROL PANEL CI-
DR
+DR PREVIOUS ADDRESSABLE DEVICE
0 FROM PREVIOUS > (+)
ADDRESSABLE
DEVICE (—)
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
m
C)
m
O
0
21
rn
0
F -1T
rn
He
(-)(-) (+)(+)
Eg
(+)
0
WIRE DESIGNATION:
NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
TWISTED PAIR WITH SHIELD #18 FPUFPLR RED (JACKET)
*CONTACT RATINGS
4.OA 0 125VAC
4.OA 0 30VDC
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
0 0
GROUND
L
®
HTRI—R I I
J
7-17
0
(+)> TO NEXT DEVICE OR
(-)
> STOP IF LAST DEVICE
DRY CONTACTS TO VAV
FAN SHUTDOWN PROVIDED
BY MECH/ELEC.
DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL
HORN STROBE
OR STROBE ONLY
80" A.F.F.
(OR UNLESS
OTHERWISE
SPEC FI ED)
R
4S DEEP BOX
HORN STROBE & STROBE WALL MOUNTING DETAIL
GROUND^
HTRI—R
L•] 1]Co] C_]C]L)L_.1
3.6k EOL
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
C—CABLE
C—CABLE
(-)
SPARE
SPARE
SPARE
(-)
HORN/STROBE
OR
STROBE ONLY
+ v
HORN/STROBE
OR
STROBE ONLY
HORN/STROBE
OR
STROBE ONLY
(+)
POWER SUPPLY & RELAY MODULE WIRING DETAIL
(+)
HONR STROBES & STROBES ONLY WIRING DETAIL
TO NEXT
DEVICE OR
END OF LINE
TYPICAL WIRING AND MOUNTING DETAILS
CEILIN
TILE
NOTE: FOR ADDI11ONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OPERATING TEMPERATURE:
+32' F (0' C) TO 100' F (38' C)
HUMIDITY: -93% RELATIVE HUMIDITY,
NON -CONDENSING
HFP-11 SMOKE
DETECTOR
FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE
DATA IN (—) >-
DATA IN (+) >
DEVICE IS LISTED FOR AIR VOLOCITY
APPUCATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
DB -11
STANDARD
SMOKE
DETECTOR
BASE
(+)
SMOKE DETECTOR WIRING DETAIL
SUPPORT
BRIDGE
4' SQUARE
DEEP BOX
CEILING
/— HORN STROBE.
/
STROBE ONLY
DROP CEILING MOUNTING
HARD LID
CEILING
TO NEXT
ADDRESSABLE
DEVICE
SUPPORT
BRIDGE
4' SQUARE
DEEP BOX
CEILING
HORN STROBE
STROBE ONLY
HARD LID MOUNTING
HORN STROBE & STROBE CEILING MOUNTING DETAIL
JUNCTI❑N BOX
MOUNTED ON
CEILING FLEX
1�f,I04., i'I�',0i418:i 4.�i�''I itM541.iM.I � iVAMIVI,.�:�i'I�: �4l riMgl,I�:�:I i�i',I� 4!..
/
/
/
/
JUNCTION BOX
MOUNTED AGAINST
CEILING SUPPORT
/ / la 0 0 TO NEXT DEVICE
00
CADDY BAR
SMOKE/HEAT DETECTOR
SUSPENDED
ILLUMINATED CEILING
SMOKE/HEAT DETECTOR MOUNTING DETAIL
Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Ri•hts Reserved
1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY:
0
m
0
DESCRIPTION
SHOP DRAWINGS
DATE
11/02/11
2CCCCC
co
O I— • co
CI) -J
W < -JO
E§(2
cc CC
W�
I-
W�i
CIS O
LI CO I-
0
V
CV
r
J
-1<"t-
W
D
C�
Z
Z
I --
O
D
Z
Q
C�
Z
J
0
iK
SCALE
: NOT TO SCALE
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 11 /02/1 1
BACKROUND PLAN PROVIDED BY:
\OB NUMBER:
C SHEET
FA -02
Current Load:
Standby:
Alarm:
Device Type
Qty
Amps
Total
Amps
Total
HFP,
1
1»0122
0.0022
0.0023
0.002
AD2-P
1
0.0635
0.0635
0.064
0.064
HTR -R
0.009 00
10!
0.021
0.042 '..;
r
0.0731 Amps
0.106
Amps
Device Type
Main System Board
ZH-MC-C15CD
ZH-MC-CW @30CD
Z1-1II-C
IZH-MC-CW @95CD
ZHHMC-C'U1:'
1
1
Amps
0.03
Total
0.03
Amps
0.030
0.0875
0.131
0.222
0.292
Total
0.030
C
0.371
`ZR -MC -CW @15CD
ZR- M - 1C, @l 5CD
1
0.069
0.069
0.064
0,03 Amps;
Q;Q99
Amps':
Standby::Current c a
Q.03
Am
Foir 24 Hours :0,72D Am:p-- horu.rs
Alarm Curren t Load
0.099
Amps
For 5 Minutes Q.00
Amp -hours
25%;iterating= Q.9.1a Amp-hc urs,
Total System Current Load:
0.910 Amp -hours
Notification Appliance Circuit Detail
PROJECT: ! MAX RIDER
Panel: i EXISTING BPS
Date: = November 3, 2011
Wire Resistance 2.58
CURRENT TOTAL= 683.00
!ZH-Mc-CW
ZH-MC-C,
IZH-MC CW @75cd
N
ZH-MC CW 5cd
ZH-MC-CW @115cd
ZR11[C-Ct' a15cd
. 1 F
87 261;
131 131
222! 222'
DEVICES
371
TOTAL mA=
!Total Wire Resistance ( R
Toth Device Load „-Amps (i
Voltage Dropj( E )
EOL VoltagQ
683; 14
186
23.341
WL*2)*(Rift)
Cct Loa)::
* R).
i; -E
683
0.96
0.66
ro
0-5rn
W
o.
1Zt
FAX (206) 628-4990
L)
N
N
0
0
N
LU
F-
RELEASE/REVISIONS
SYSTEM CALCULATIONS
TO EXISTING
POWER SUPPLY
TO NEAREST EXISTING
DATA LOOP
S1-1
15cd
S1 -2
15cd
S1-3
15cd
S1-5
15cd
S1-6
30cd
EOL
S1
FLAG NOTES:
FIELD LOCATE RELAY MODULE FOR BACKGROUND
MUSIC INTERFACE.
DUCT DETECTOR, TEST SWITCH MODULE & RELAY
MODULE FOR FAN SHUTDOWN LOCATIONS TO BE FIELD
VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE
ALARM CONTRACTORS.
REV. BY: I
C)
M
0
DESCRIPTION
SHOP DRAWINGS
DATE
N
0
2
CCCCC
oC
a
w
z
co
zo —�
O Tcc - C�
o�z —
o
W 2 Q0 0
w2z
CC W = aC
< 0
er,wD I-
CC on
�cnF-
o0�d
0
W
C/)
}-
u)
�CALE: NOT TO SCALE
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 11 /02/1 1
SINGLE LINE DIAGRAM
BACKROUND PLAN PROVIDED BY:
,JOB NUMBER:
SHEET
FA -03
Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved
TO
EXISTING POWER SUPPLY
& NEAREST DATA LOOP
E) STOREFRONT
FIRE ALARM SYSTEM PLAN
FLAG NOTES:
FIELD LOCATE RELAY MODULE FOR BACKGROUND
MUSIC INTERFACE.
DUCT DETECTOR, TEST SWITCH MODULE & RELAY
MODULE FOR FAN SHUTDOWN LOCATIONS TO BE FIELD
VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE
ALARM CONTRACTORS.
17/43 1ST
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY:
lD-4
/
5'-4"
/
►9'-11 "
DESCRIPTION
/
.
5'-2"
(E) BACKWALL
/
/
(L-=7.-----1)
I.
S1-1
N
15cd
D s
_ J
S1-2
OFFICE
j•�
(F..) RESTROOM
15cd
\
1111
\
1 -6°
/ ////.�
//O//////o///////////d/i2///
/.�///////.d/
G
(A14F
o- D,S
C'/
C)
CD
F-�ro
co
x
n
15cd
S1-3
�2s
,
=_ I RIDE ROOM
E
r
#2
i
��///
Al
�//%//////. Z
75cd
4,
o— D S
(E) DEMISING WALL
A 4 a
(E) DEMISING WALL
1E'-9"
VA
0
Is
I
G
G
D
4
a
S1-5
fit
-fZ�=°j_
i15cd
95
.
RIDE ROOM
—LA14_1a..1
/,•-•:
_, AUTOMATIC (- _,..
.. 7
5,-D„
SLIDING DOOR
(61" WIDE X 87" FIGH)
o—D,s
0
�1
In
/C5
-_t.1
HT -R
o—D
DISPLAY WALL
HT -R1
cD
34" HT COUNTER
c
TSM
—1:11-NAA-EOL
I't N S
5'-0"
REC
30cd
E) STOREFRONT
FIRE ALARM SYSTEM PLAN
FLAG NOTES:
FIELD LOCATE RELAY MODULE FOR BACKGROUND
MUSIC INTERFACE.
DUCT DETECTOR, TEST SWITCH MODULE & RELAY
MODULE FOR FAN SHUTDOWN LOCATIONS TO BE FIELD
VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE
ALARM CONTRACTORS.
17/43 1ST
FAX (206) 628-4990
TEL. (206) 622-6545
RELEASE/REVISIONS
REV. BY:
2
0
DESCRIPTION
SHOP DRAWINGS
DATE
1 11/02/11
Lo
Co
co
Z u co
0 I— c
�Z
W<JO
0 W § z_
CC W
2 z>
CC
w
CCOD
0
N
T
‘LE: 1/4"=1'0"
DRAWN BY:
D. GARCIA
DESIGNED BY:
R. VEZZANI
DATE: 1 1 /02/1 1
BACKROUND PLAN PROVIDED BY:
.,JOB NUMBER:
/ SHEET
FA -04
Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C -CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
■i
STEEL JOIST/TRUSS
HANGER DETAIL
NTS
0 0��
1-)Q"C\rn
n C e -s1/2 Qd
5
G,�Qn ,til
tL ,�t,Z � �a�cc.
REFLECTED CEILING PLAN
,L:•
�rW w.wX 6.
0 Without Comments
.0 P-cNoted inRed
ar Per The Attached Letter
hese plans have been reviewed by The Tukwila Fire.
ventiorr Bureau for c_,i,iormanCe with current City
standards. Acceot:r ( 3' ibj nt td ei-pr5 and
I , isstons which coil , �, nr s. 4 10w:i ns. of adopted
:�rdards and ordiflance. _h CCEDoOSIbbl!iey for the
:diequacy of design , totativ; t, designer.
igner.
sdditians, deietiona: OF d nwings after
this date will void. thi : require a
r
resubmittal of revised d, _.;wln s « r-, it approval.
Final acceptance is sui?if_ei; «r:o inspection by
rhe Tukwila Firs: Pteveruk r3!..2 , ii.
/
TUKWILA FIRE DEPARTMENT 3d
Please call 2O6
give this Fire Permit Na.
11-s-16
address for shut-
down or restoration app
a�;u exactrova4.
Design per NFPA 13, Ordinary Hazard
All materials to be new, UL listed, and FM approved
• 2 — Add Reliable Model G 155° pendents % x
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
DATE: ( I