PP - 1011 SOUTHCENTER MALL - WATCH WORLD / THINGS REMEMBERED / VALLEY PUBLISHING - PERMITS AND PLANS
1011 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-080 10-S-068 85-176 85-039 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Things Remembered 1011 Southcenter Mall Permit No.: 11-S-068 Date: April 4, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. VALLEY PUBLISHING REC PAY:9BER. CONTROL NUMBER ,S--D J 14198 iTRAL PERMIT SYSTEM - ROUTING FO BY : ❑ BLDG. 0 DJECT /1 w DRESS l O I -/1/1- TE iTE TRANSMITTED o9 " / 3,,, PL NG KWILA ID PRKJTIONpI 11 FIRE ' .❑ POLICE ❑ CF RESPONSE REQUESTED BY P.S. STAFF COORDINATOR RESPONSE RECEIVED EASE REVIEW THE ATTACHED PROJECT PLANS NND CNECKINGDTHETH BOXPNEXTR70TE TNE LIt EiS)TS- lONTHE 1 HICH 'ACE BELOW. INDICATE CRUCIAL CONCERNS BY IAT CONCERN IS NOTED: 1 %W1if t 44 4'/ •21017,ti' 5c.s Coy'€ I 1kk vlal, p_144, 7a J J_ J 7 .. 1 6( Iled 7t% 7s? SWol oww%e D.R.C. REVIEW REQUESTED 0 PLAN SUBMITTAL REQUESTED ❑ PLAN APPROVED [, 4 Ajeli0 PLAN CHECK DATE ` 't 0- COMMENTS PREPARED BY C.P.S. FORM 2 APPLICATION .'� FOR ,�.;:�" rix, , OF �' BUILDING PERMIT T����;:; - _ _ ......IUKWILA qJ- V3 9 JOB ADDRESS ' : ; ; r•,y; • ;-;+rr':<,'s;us.:.. /do / i f -O C -t 7! toII,; , i. E '".4.,) f l'; ' ► A /! I 'v l G( ( E , ( OCC. DATE OF APPL. , 0/ ~/j —!J 5-.. DESCRIPTION OF USE„; ;; r y i ;. LEGAL DESCRIPTION ATTACHED : O ;, PROPERTY OWNER ,''; `' G(ci 44- Ce e."�tl ADDRESS J C. ...�t PHONE C 7 ENGINEER/ARCHITECT ADDRESS - PHONE .` 6 • 74011 CONTRACTOR ,:.. ' , . '.,. .'` . ,f9w /•) i". ADDRESS /I PHONE „4rlG • 74 co. AUTHORIZED AGENT ' •.:. >„ :1.• e A 1.454dk' is , . LICENSE NO. VALUE OF WORK r'Od t _.. . FIRE PROTECTION SYS M, j„. SPRINKLER gh DETECTOR USE ZONE TYPE OF CONST Ai f / l/ V ADJUSTED VALUE SENT GRADING CUBIC YARDS CUT FILL SIZE OF BUILDING / PLANNING SIZE OF UNIT WORK TO BE DONE. 'rs= : us, rrt Lt,J i �t Ct' ('et f�4. / Ail F Lc) d'/tr C• ✓ 18T FL. HEALTH %D� 2ND FL. , 144 �f'it (- D r t y ,?''S 1 *Eek t” / i'% (, I .l '•i t: /I , .(: I ,�1 { ',. A/C y. . /+' 7 ' TOTAL 1 HEREBY CERTIFY (IAT I HAVE READ AND EXAMINED THIS APPLICA- TION AND KNOWTHE SAME + E TRUE AND, CORRECT. .i'',"r' FEES AMT. DATE REC. NO BY P.C. /0 r a� /�� 4" ADJ. , SIGNATUR ,) r�� `�%� C� , / • L�'CrA!"'P/l ts''.._ 51/s/Vtfr" irel•fIle' B.P. DEMO. COMPANY - !.{., DATE 'J - / 3 - 51"-) PHONE -$7 (IA .- 74/0° TOTAL CITY USE ONLY USES SO. FT. OCC. OCC. LOAD #4...ez /'4a i . TOTALS - ICY DEPT. APPROVALS — SENT CORR. APPR. PLANNING y4 HEALTH • PUBLIC WORKS 144 �f'it FIRE /I ' i SPECIAL CONDITIONS PLAN CHECKED BY DATE a-0 APPROVED FOR PERMIT BY • DATE, a J1 9 1)4 r— 0 w -0 00 0 cm 00 0 r- 0 3 z 5 a- 0 -r) • r r • I) -Pi I A e f z ...- 1 c, -ti .i r* I - 0 I_ --i 1-• • 1 - . ‘ \ I) -Pi I A e f z ...- 1 c, -ti .i A- J 9`) t` . C• iM wr. . - - - vetvG- t otw. 6Es-r. w - -$ -• -4 i pLVdCVC t • • • • t. L 1.1L4111411=141 111' Q�_ —. r?ST¢�r# BEST� - - i ' AVI. ' e Ai .- — - ,_. _•,.: ,__„.,,, ,.....,i.: A,` A,1 - S i 4 �? ; . . .ls. stea ar ter 1. _ � s •:ter SPR ih4K LC4 VALV1 K2 a -. 4 �?% vas 3: KI; K2 ' MAQCHE•: j' MALE. -; IAt...v a 02 0 • • .11.IIETt 4t3 MA( Or Nis /.max JS 4144 t NASIMK wt 4 t ts • •..v • %.c. r;cr t$-• . r , }• • r. -.L 4 T L.* .•Y.L.*OiR Jr MU M uy MOO JOS ..•o r ALVf Pi v.4 • ♦ .4 • • i _ f--T- • , _ 1%:4--.1 ----4-:',.,::.,,v•r:_r_.-.. , ____ ,, _r_ 1 • , • 4 • - amu -I,' X . n ® © �� 4 4 PIZOiJECT PLAN • is soon r •s•. WIC IC LL Yo�vC: Gt1 C,2 .gest®EA,G'1..G3.t,4 .� 65',66;61, K4 . • SP21MKLEIL VALVE G4;GS.Ca(o. ' . • GYP. BD. CEILING AT 8'-0" . kler SQitn ,red' XtS rr."5- 3k /05 (,J1 d.'-t3�' Ab0Je' Q, b — (ACT1) CEILING AT 10'-6 416 t. r, . ,.. • iN'. r,.:• v DASHED LINES INDICATE (ACT2) ABOVE TOILET DECK (ACT2) AT 12'-0" A.F.F. BULKHEAD AT 8'-0" A.F.F: 111 GYP. BD. SOFFIT AT 9'-6" A.F.F. - Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart • 2 — Add Reliable Model F1 Standard Response 155 ° Pendents 1/2 x 1/2 • 16 — Relocate Reliable Model F1 Standard Response 155 ° Pendents 1/2 x % • E — Existing 18 --- Total Nem REFLECTED CEILING PLAN SCALE: 1/4" = 1'-0 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL ,RING STEEL. JOIST/TRUSS HANGER DETAIL NTS Without Com m ent<s As Mote{ in Red Per The Attached ► etter These plans have been reviewed -by The Tukwila Fire rrcvention Bureau for conformance v'ith current City • -71-dards. Acceptance is subject to errors and nissicns which do not authoize "ioations of adopted andards and ordinances. The responsibility for the JequacV of design rests totally with the designer. -.editions, deletions or revisions to these drawings after this date will void this acceptance and will require a iesubmittal of revised drawings for subsequent approval. Final acceptance is subject to held test and inspection by The Tukwila Fire Prevention Bureau. Date: Site Plan fLK'ILA FIRE DEPART:MlEi1IT f'.klase call: 575.4407 and give this job No. i f - S- O CE. Ind exact address for shut, iti.t.io or rti:-a:JrvElOn dour )i/RI NOFDOMROM CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113. MILL CREEK, • WASHINGTON 88082-0113 PH. (425) 481-7669 DATE:, 3 .2.5:,11 Lill lin:�A j!11101'r'NIP* it-if.W S REMEMBERED� 1 O1I Sb.JA- -en}-Cr . M A .5 Pate. 1-1 T-UtX k'3. DRAWN: SCALE: PAID MAR 28 2011 0 TUKWILA FIRE •z -V77f5 FILE GOPY FIRE ALARM SYSTEM WASHINGTON TUKWILA, SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 SYSTEM CALCULATIONS (GENERAL) FA -04 FIRE ALARM SYTEM FA -05 WESTFIELD SOUTHCENTER MALL SITE PLAN I 0 g 0 I CC' PTED Without Comments As Noted In Red Per The Attached Letter I nese plans have been reviewed by The Tukwila Fire Prevention Bureau for coritorm mce with current city standards. Acceptance to errors and omissions which oo not uui 't ., i.`_ violations of adopted { stanoarc:s and _,:?; ;:-. c. _.. Ti := r:: ponsibi:iiy for the adequacy of cic ::_ w)tr the debi.gner. Additions, et . _ ;; t o -_.o drawings atter 1 this date require a ' resubmittal of r : i:::, c� ..r `ar subsequent approval. a Final acceptance i ::;ul. pct to field test and inspection by Thc.- Tukwila F"u�� Prevention Bureau. I Date: L')/2 -)-)A) By: AIM51 I ii Shylalt 160,0A S vccQ of► dcd:ckw syste .. Cs) • NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. TUKWILA FIRE DEPARTMENT Please call: 575.4402 and give thts job and exact address for shut+ duan or restoration approval) WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT - FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS .(I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE, SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, 'REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED, BRANCH POWER. SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE 'ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION _FOR PROTECTION DURING CONSTRUCTION. . DETECTORS THAT HAVE BEEN INSTALLED PRIOR T0. FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. - 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOLS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. . 21 . ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CON 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF. CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME. CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. QUANTITY 3 2 3 1 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD 1 T -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD 1 HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ®SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. L FIRE ALARM STROBE C (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. c FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM B1DWP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD El MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.13.0. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.❑. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A L�� 2 2008" Tukwila Fire R.s55 150 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ww^ 1_ JJ co 0' TEL. (206) 622-6545 z ELEASE/REVI DESCRIPTION 1 - T C z NG AND MO H. W SCALE: 1/811=1' DRAWN BY: I:ANDERSON DESIGNED BY: R:VEZZANI DATE: 4/07/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S 2S A V 2V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO 4416 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 ._FPL/FPLR RED (JACKET) ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) . SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED ##18 FPL/FPLR RED (JACKET) UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL- CHART ,•..::.:. .. NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N-E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS .(I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE, SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, 'REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED, BRANCH POWER. SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE 'ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION _FOR PROTECTION DURING CONSTRUCTION. . DETECTORS THAT HAVE BEEN INSTALLED PRIOR T0. FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. - 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOLS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. . 21 . ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CON 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF. CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME. CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. QUANTITY 3 2 3 1 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD 1 T -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD 1 HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ®SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM 4S DEEP BOX CEILING W/ 1-1/2" EXT. L FIRE ALARM STROBE C (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. c FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM B1DWP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD El MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.13.0. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.❑. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A L�� 2 2008" Tukwila Fire R.s55 150 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ww^ 1_ JJ co 0' TEL. (206) 622-6545 z ELEASE/REVI DESCRIPTION 1 - T C z NG AND MO H. W SCALE: 1/811=1' DRAWN BY: I:ANDERSON DESIGNED BY: R:VEZZANI DATE: 4/07/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT !MOTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT SEL SELF COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE 1 14 DUCT DETECTOR LOCATION PREVIOUS ADDRESSABLE DiLy FROM XLS CONTROL PANEL^OR^ END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 0 GROUND --O 0 O 0 e HTRI—R STATUS LED 0 0-C 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L (BACKGOUND MUSIC SHUTDOWN) NOTE 1: VOLTAGE MAX.— CURRENT MAX.— CONT. RES. MAX.— MAX. CABLE LENGTH— C CLINE TO LINE)— C CLINE TO SHIELD)- MAX. LINE SIZE— MIN. LINE SIZE— MUSIC OUTLET SAMPLING---\, TUBE • INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE 14 -Ac POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(¢) STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE U-) END OF LINE DEVICE 51 U 0 C3.6K 1/4W) SUPERVISED ;' SWITCH RELAY CONTACTS (4.OA e 125VAC) GROUND --- (4.OA 2 30VDC) 27 VDC 3.5 rnA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. 0 le mI S146 0 5- 1 2 .34..5 .6 HCP TB2 6 5"4 3'2 1 0 0 ; d - 0 0 HTRI—D OSTATUS LED CC) 0 N 0 NOT USED 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LIBEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 CND N AC u 0 PAD -3 0 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1-- 2+ 2- 2 . NC C NO + - + - + - + - + - Cl MAMA lrollmI* 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 2 NAC -4 NAC -3 NAC -2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) SUPERVISED 'WITCH FRONT VIEW NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP -72 NOT USED REMOTE DEVICE LOOP j., 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S'. CABLE) FROM\FACP (VOICE CIRCUIT) C'V' CABLE) 470 OHMS iW EOL 0 INPU ( P PHP T —1 0 N C TYPICAL AD2-P DUCT SMOKE DETECTOR- WIRING DETAIL SCALE 404E C . , u (STR❑BE SPEAKER ( t ) � u () STROBE EARTH GROUND 3(+)TO NEXT DEVICE OR STOP IF LAST DEVICE ( ) STROBE SPEAKER (+) ( ) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80- A.F.F. 4S DEEP. BOX.. IN/ 1-1/2- EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERATURE: +32' F 0' C TO 1W F (319 C) HUMIDITY; X RELATIVE HUMIDITY. NON—CONDENSING HFP-11 SMOKE DETECTOR —� FROM PREVIOUS ADDRESSABLE DEVICE OR P01MER SOURCE DATA IN (-) >-- DATA IN (+) > DEVICE IS LISTED FOR ADR VOLOC TTY APPLICATIONS OF 300-4000 HAIN WEN USED IN CON.RJNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR 08-11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT ONCE -kr -- ( NCE- - ( ) DATA OUT 1 > (+) DATA OUT J} CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID - CEILING HARD LID ----\ SPEAKER SUPPORT TILE -� BRIDGE ---- 4' SQUARE DEEP B❑X WITH 1-1/2' EXTENSION N. --- CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION •B❑X —, MOUNTED ON \ CEILINGI FLEX \. JUNCTION BOX -------\ MOUNTED AGAINST CEILING SUPPORT T O O I TO NEXT DEVICE 0 0 • ----CADDY BAR SMOKE DETECTOR --- SMOKE DETECTOR MOUNTING SCALE=NONE -SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 LC) LC) N 0 N J W RELEASE/REVISION DESCRIPTION <<<<< _z. z 0 co z co < i CT) {Yt J) W W z I� 0 V ��` cc a ..J W z �— _ t= U) g La WAS LT ITo_LT co_ 1 W SCALE: 1/8"= DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 4/07/08 BACKROUND PLAN PROVIDED BY: `10B NUMBER: SHEET FA -02 J 0'-0" NO CEILING OPEN TO STRUCTURE 2S,2V b 15 CORRIDOR 18.41V ,(( ;A BOX 2s;2v '1'' i 5) COS — F j D,I STOCKROOM N,s ALES FLOOR E135 c�-2S,2V 1•. • .iK^S,2V 15 BATHROOM 1 3 1 (J 0 II 2S,2 V —a 30 Lt 15'— / \ FLAG NOTES: BACKGROUND MUSICINTERFACE FOR SHUTDOWN UPON GENERAL ALARM MOUNT SPEAKER STROBE TO BOTTOM OF STRUCTURAL SUPPORT Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved REV. BY: DESCRIPTION DATE z ««< DRAWN BY: tANDERSON DESIGNED BY: R.VEZZANI DATE: 4/07/08 BACKROUND PLAN PROVIDED BY: Q0B NUMBER: t• SHEET -o 1 L 'MB A, 0 -"" L_ rr / A 0 ,// / //// - • - :X1-2</ . - /. - / A 0 • f 0 • • . „ „ /5 N ------------------------- - ------- 1=1-- •-` 0 =11, -p 7.1 zz. c NORTH -; - /3333 333-3 - • FINISHIIlfWSTFIELDSOUTITICENTERVALL SCALE 1132'4 15 15 15 135 c 30 EOL -S1 18.41V 2S,2V-cD • FA -BOX 13-D I FACP EX PSI RISER DIAGRAM D,1 33 .333 e s s" SYSTEM CALCULATIONS FINISHLINE FINISHLINE • FACP ADD ONS . SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations • Current Load: Standby: Alarm: Current Load: Standby: Alarm: , . Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total . HFP-11 0.0022 0.0022 0.0023 ' AD2-P 2 0.0635 0.0635 0.064 0.128 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R- HTR -R3 HTRI-15- -- ---- ---- _ - , . _ . . ..,.... _ , _______ ----- .,_._ .._ ___. ... ., ____.„_,.... ____,. ____ _____ • 0.009600 0.0096 0.021 0.063 SET -MC @15CD SET -MC @30CD 2 0.064 0.128 0.001600 0.0035 0.098 SET -MC @75CD SET -MC ©110CD SET-HMC-C@115CD __ 0.175 0.233 0.048 SET-HMC-C@135CD 1 0.318 0.318 0.0731 Amps 0.191 Amps SET-HMC-C@185CD 0.445 1R7IVIC @15CD_ ZR -MC @3OCD _._ 1 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0.098 0.0015 Alarm Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 Amps 0.54 Amps 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours _ Alarm Current Load: 0.54 Amps For 5 Minutes= 0.045 Amp -hours ! , Total System Current Load: 2.213 Amp -hours 25% Derating= 0.957 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH • Total System Current Load:- 0.957 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH xxxx RECOMMENDED MINIMUM BATTERY SIZE = 7. 00 AmperexHours BATTERY SIZING CALCULATION , , 1 . - 1 NotificatiOn Appliance Circuit Detail . . : , , 1 PROJECT: !WESTFIELD SOUTHCENTER MALL - . i 1 i Panel: :FINISHLINE ;Wire Resistance 5.16 • . - CURRENT TOTAL=17.2 Date 14, 2008 CIRCUIT:iSPEAKER CIRCUIT ! 1 1 , i 1 1 i QTY ' Device Type i Alarm Current! Alarm Total i Wire Size [ VVire Length I Voltage at EOL 1 Circuit Total 1 . , ; !., ; 1.81 7.21 . i i Total Wire Resistance ( R ) ; 5.21 0 4 707V118 , , , . , oi oi i 1 , , I ( WL * 2 ) * (R/ft) 1 , , 1 0 i 01 0! 1 . i , , s 0 0t . Total Device Load, Amps (1) i 0.01 1, , , , I i 0 , ii (Total Cct Load) : 0 0! 01 Voltage Drop ( E ) i 0.04 0 1 -I- ; 01 0; i , 1 (E= I *TR) 0; o1 , 1 ' , / -7.-- 0 i 11.._ _ EOL Voltage 0 i , : 01 0 : i , i i I i (20.4 - E) I ; 20.36; , , 0 1 i 01 di . : , i I • , , , 0 i . 1 01 01 ; , ; , - ; DEVICES= i4_. TOTAL m A= 7'.2 12 605 -2-0.36247648 7.2 Notification Appliance Circuit Detail . . ., , •,_ , ,,,•_. . . .. ..... . _ PROJECT:1WESTFIELD SOUTHCENTER MALL • Panel: FINISHLINE Wire Resistance -314* Date: CIRCUIT: QTY April 14, 2008 1S1 CURRENT TOTAL=I608 Alarm Currenti Alarm Total ! VVire Size ! Wire Length I Voltage at EOL Circuit Total i , f 1 i Device Type ; ___.......... . , . ; 1 _ , ..._. • ;, 3.27i , ; . 2 SET -MC ©15CD 641 1281 Total Wire Resistance ( R ) 1 • !SET -MC ©30CD 0 SET -MC q75CD , i 98! 98; ! i i I - ( WL * 2 ) *SR/ft) ) 1751 0 I - , ' ITotal Device Load, Amps (I) 1 0.611 1 (Total Cct Load) I , 0iSET-MC @.110CD 2331 01 - SET-MC-CW©15CD 691 0 333333 !SET-MC-CW@30CD 1111 SET-HMC-@135CD •1 318! 3181 • f 0 ISET-MC-CW@185CD 684! 01 1ZR-MC ©15CD • • • 64 64; 1 99: _ : 4 Voltage Drop ( E ) o ZR -MC 030CD 98! - 01 , (E= I * R) , i 1751 0; ; i i EOL Voltage , 1841 , .; -- .,...... :_.. , , 0 1ZR-MC ©110CD , 233! 0 ! . i 1 i 1 (20.4 - E) • • , ; I i ; , •01 . - .. .... ? i ; I ; ; , i I 0 ZR-MC@75CD 01 3 ; 1 1 . i i I DEVICES=5 i TOTAL m A= i 608i 12 1 - . 505 18.4103808 608 • VOLTAGE DROP CALCULATION cc -4 co z 0 (1) uJ _J LIJ C.) Li] CD ON ';• OD -4 C\I c • '. .0 .0. osi _J W . f RELEASE/REVISIONS DESCRIPTION uJ <<<<< cc /ALE: 1/8" =1' DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE: 4/07/08 BACKROUND PLAN PROVIDED BY: ..10B NUMBER: Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 'MINT C4- xr iz 1 1� yFIRE ALARM SYSTEM ADDITIONTUKWILA, WASHINGTON SHEET NUM3ER SHEET TITLE FA -01 SYSTEM INFO MATION FA -02 TYPICAL WI SING AND N O U NTI \G DETAILS FA -03 SYSTEM CALCULATIONS A\ D SINGLE LI \ E DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN tU'N;MLA FIRE DEPAR; inENX Please call: 575.4402 and give this job No. /I- F Og anti exact address for shuti town or restoration approval: SHEET INDEX W:thcut Comments D As Noted in Red Per The Attached Letter These plans have been reviewed by The T ui(vvila Fire Prevention Bureau fr ccrnlOrmance whit current City standards. Accep zItlre 17,7, c rc c and cnhLsions which cc not %,+ •i'r-}, I c, „ini,3>:irr;_: cIf adapted standards and orrii , t:;_..S!i*i;y for the -adequacy of di:=,r,;; r , �. ;.. ,r• i, ri: :.e goer. t:idicions, deletion i;, ,t ;a;,1?!' , c}p : . i`r<"J n(;s after this date: viii voic .� ., .._. 1 ;i. a resubrmittat of r,_"i:::.. ....., „ ;. t: n approval. Final acceptance is :tloy.c.:; t, : Heio ,_.,.:.: }u . pection by The Tukwila Fire Prevention Bureau, Date:11-d -/1 By: E SC L RULE AND CONDUIT FILL CHA SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 1 2 2 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD -3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -1 1 BASE 4S DEEP W/ 1G RING CEILING ® DUCT DETECTOR D AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN N( FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM i I j 3 LEVELS >v� 25Q,4.. _. 33 11 •v�r� ��``!! A**11vvAA i.'�'. , t`LL1.t i, RtRE ❑ El 00 EX SING JCPenney Le. 2E w *A4e13,a4 9,E. OTIS �Jurr RCW(S o -t ,s. ��CE, KriS kTERcPC.E£ 3LEELS 276,455xf THINGS REMEMBERED (1011) WIRE DESIGNATION GENERAL NOTES SITE PLAN PAID APR 11 2011 T KWILA FIRE • /7015 /50' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C D P S S' V V I STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC TWO #16 FPUFPLR RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART SHOP DRAWINGS NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 1 2 2 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD -3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -1 1 BASE 4S DEEP W/ 1G RING CEILING ® DUCT DETECTOR D AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN N( FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM i I j 3 LEVELS >v� 25Q,4.. _. 33 11 •v�r� ��``!! A**11vvAA i.'�'. , t`LL1.t i, RtRE ❑ El 00 EX SING JCPenney Le. 2E w *A4e13,a4 9,E. OTIS �Jurr RCW(S o -t ,s. ��CE, KriS kTERcPC.E£ 3LEELS 276,455xf THINGS REMEMBERED (1011) WIRE DESIGNATION GENERAL NOTES SITE PLAN PAID APR 11 2011 T KWILA FIRE • /7015 /50' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 04/08/11 2 <<aaa 0 CC 0 J '- W <cao cco <t H W LU cc (i) 453 < Log F- 111 (1)H (11) (S-CALE: NOT TO SCALE Z 0 0 Z DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 04/08/ 1 1 BACKROUND PLAN PROVIDED BY: Pro rieta and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1013 NUMBER: 55187 J SHEET � FA -01 } \A THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-6OHZ DEDICATED EMERGENCY NOTE FOR A001110NAL SPECi1CARONS SEE PRODUCT DOCUMENTATION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 304DC TO NEXT ADDRESSABLE C+ DEVICE STOP IF LAST DEVICE - FROM XLS ca1TRn. PANEL. a OR PREVIOUS ADDRESSABLE DEVICE 0 0 0 HTRI-R e; I 0 OR ADOITIONAL SPEaRCADONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE 0 PAD -3 00 ODPUT MPUF TROUBLE HClANAC2 NAC3 NAC4 AUX +1- 1 2+2- 2 NC C NO + - + - + - + - + - 0 3.6k EOL'LS $ $ B (-) (+) e SPARE SPARE SPARE FROM PREVIOUS> (+) ADDRESSABLE > DEVICE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. v v S z S o^� f.41)oor o 1—J* (2)(-) (+)(+) (+) TSM -1 O WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTEDPNRWIiHSHIEIO #18 FPUFPLR RED(JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 r - r GROUND L { 4 o @ 4 HTRI-R I a (+)> TO NEXT DEVICE OR ❑0 • ❑, 1\ 0 m 0 - 1 1 ❑ �Q � 0 G ID DESCRIPTION r +, A ,❑ Q 0 0 0 0 A :1) ) (1 7 1..Amaral a€ 1 II i - '^ II = ` -11 I'M 1:1:1.I•III•I•I'. 0 0F19 0 0 ar I4 109 ,'.a XX 'RISK!• - ��. 1 4=sa_;� � NW K_ _ 00 V /1 O❑ (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER O❑ ❑O �,41 al O 1 — CIt 1 0 m 0 1 1 — ❑ �Q � 0 G ID DESCRIPTION r +, A ,❑ a - 0 0 e mean R � (1 7 2 a€ 1 II i II = ` -11 I'M 1:1:1.I•III•I•I'. 0 0F19 0 0 It.Q 109 ,'.a - ��. 1 4=sa_;� k� :} °vi1 DEDDJ G" UII �an❑ (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER OR FIRE ALARM CONTROL PANEL .t (+) (+) (-) ❑O STROBE a0❑ STROBE 0 (-) II (-) (+) (+) 0 a 111:1:111:1:1 - ca. 4 I 1 ❑OP STROBE CIRCUIT SPEAKERISTROBE 0 0 I I I:I:111:1:I' (-) (-) STROBE CIRCUIT (+) (+) SPEAKER SPEAKER CIRCUIT CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS 5 TO NEXT APPLIANCE S OR 24K (EOLR) (+)S TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) (-) (-) `) (-) SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTIN TEMPERATU� E: +32' F 0' C) TO 100' F (30. C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —* FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE rDATA IN ( )>- DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID -� CEILING SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCION BOX MOUtED AGAINST CEILLG SUPPORT 1DKE/HEAT DETECTOR TO NEXT DEVICE CADDY BAR SUSPENDED ILLUMINATED CEILING SIOKE/HEAT DETECTOR MOUNTING DETAIL rn co CT O O C!) uJ I-- uJ C) cnO LTJ P-- (/) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: 1 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 04/08/11 2 a<aaa -J w zcc 0 1— w r=¢cs, D occo O w w zz 61-±- 0 w Cf) CC 2 �� C!a r� _J V< z wT z on z _ Li- -' J 0 /S.-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 04/08/ 1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55187 Proprietary ancConfidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0009600 0..0096 0.021 0.042 0.0731 Amps 0.106 Amps SignaI nde Current ti by: Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C ©15CD 0.0875 j SET -MC -C ©30CD 1 0.131 SET -MC -C @75CD. 0.222 SET -MC -C @95CD SET -MC -C ©110CD jZR-MC ©15CD 1 0.292 0.292 0.259 1 0.064 0.064 ZR -MC ©30CD 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.386 Amps Standby Current Load: 0.03 Amps For 24 Hou 0.720 Amp -hours Alarm Current Load: 0.386 Amps For 5 Minutes 0.032 Amp -hours 25% Derating= 0.941 Amp -hours Total System Current Load: 0.941 Amp -hours Battery Pair to b Notification Appliance Circuit Detail PROJECT: THINGS REMEMBERED Panel:IPAD-3 POWER SUPPLY !Wire Resistance 2.58 Date: April 8, 2011 CURRENT TOTAL= 487.00 ' 0 :SET -MC -C ©15CD 1 SET -MC -C ©30CD 131 131 0 ISET-MC-C @75CD 1 2221 0 1 SET -MC -C ©95CD 292 292 0 ZR -MC ©110CD 2591 01 1 ZR -MC ©15CD 64 64 0 IZR-MC ©30CD 98j 01 0 ZR -MC ©75CD 175 r0 DEVICES= 3 TOTALmAI 4871 12 133 23.671 ITotal Wire Resistance ( R ) 487 i( WL* 2 )1'(R/ft) r 0.69 Total Device Load, Amps (I) (Total Cct Load) 0.49: 1Voltage Drop ( E ) 1 i j(E= I * 0.33, EOL Voltage 24E)' 23.67 Notification Appliance Circuit Detail PROJECT: !THINGS REMEMBERED r I Panel: !XLS-V i !Wire Resistance 2.68 , Date: 1 April 8, 2011 ' CUR-FiENT TOTAL=r#REF! 16 170.7V1/8 1.81 28.8i 34 70.7V 1/4 3.54 120.36 0 I 70.7V 1/2 01 • 0 70.7V 1 0 0 DEVICES=1 50 I TOTAL mA= I 149.161 14 1 1,323 19.381732411 149.16 'Total Wire Resistance ( R ) Total Device Load, Amps (l) (Total Cct Load) ' 0.15' i , . 1Voltage Drop ( E) j : (E= 1* R) i 1.02 i i , . EOL Voltage 20.4 - E) ' ' 1938. ( WL *2 )* (R/ft) 1 6.83 SYSTEM CALCULATIONS co ON z z LU uJ ILi to FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS EXLJ (HALLWAY) TO NEAREST EXISTING DATA LOOP 2C,V,V' S1-1 S1-2 30cd 15cd V1-1 1/4-W 2C,S BPS 120VAC, DEDICATED 1 ) (BY OTHERS) D HTR -R ITSM S1-3 95cd V1-2 1/4-W EOL Si FLAG NOTES: FIELC LOCATE RELAY MODULE FOR BACIGROUND MUSIC INTERFACE. FIELE LOCATE SIEMENS PAD -3 BOOSTER POVER SUPPLY FOR STROBE POWER. AC POI/1ER BY EC FROM DEDICATED, LOCKED OUT 20A,110VAC BRANCH CIRCUIT. SMOKE DETICTOR MUST BE LOCATED IN THE SAME ROCV1/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUDOWN & TEST SWITCH LOCATIONS TO BE FIED VERIFIED BY MECHANICAL, ELECTRICAL ANEFIRE ALARM CONTRACTORS. SINGLE LINE DIAGRAM IREV. BY: I 0 M 0 DESCRIPTION SHOP DRAWINGS w ::... F- 03 <0 in \ -1. 0 2 <<<<< cc 0 w z -J w z Er) z z 0 0 LU Cf) Cl, 4CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:04/08/11 BACKROOND PLAN PROVIDED BY: \JOB NUMBER: 55187 Pro.rietar aneonfidential, Co. right 2010 b Guardian Securit S stems, Inc. All Rio hts Reserved SHEET FA -03 TO NEAREST EXISTING DATA LOOP 1 4 6 0 9 O L 0 01 O 0 0 011 0 REFLECTED CEILING PLAN HALLWAY s,s' TT TT 7 S1-1 30cd V1-1 O S1-2 1 5cd D s,vy EOL S1 S1-3 95cd V1-2 1 FIRE ALARM SYSTEM PLAN rcL) FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BYEC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOP MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOVN & TEST SWITCH LOCATIONS TO BE FIELD VEIRFIED BY MECHANICAL, ELECTRICAL AND FIRE4LARM CONTRACTORS. 1743 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE co 0 a z<aaad CC 0 W F� <O) in o CC 0 < w t -- W wwz WCO < CC 2E— cc 5:)')s <Z 1E2 Eg SCALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 04/08/11 BACKROUND PLAN PROVIDED BY: 1.0B NUMBER: 55187 SHEET FA -04 Proprietary ancConfidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \.