HomeMy WebLinkAboutPP - 1030 SOUTHCENTER MALL - EXPRESS - PERMITS AND PLANS1030 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-349 09-S-028 . ,w FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Champs 1030 Southcenter Mall Permit No.: 09-S-028 Date: February 12, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. /y r l+ • Comply with obstructed/non-obstructed construction rules for sprunkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. IP 8 February 2009 JI John Abel Crown Fire Protection P.O. Box 12113 Mill Creek, WA 98082-0113 J RE: Westfield — Champs Sports (Space 324) Independent Third Party Review — Fire Sprinkler System Dear John: Tuazon Engineering, PLLC 4322 NE 7" Street Renton, WA 98059 425.917.1683 tel 425.917.1705 fax www.tuazon.com As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. The following was reviewed: • Fire Sprinkler Drawing — Sheet 1 of 1 The documents were reviewed for compliance with 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Drawings indicate new upright and pendent sprinkler heads will be installed for tenant improvement work. No new piping was indicated. If any new piping is to be installed, show all new and existing piping on the plan so that ordinary pipe schedule sizing per NFPA 13 Table 22.5.3.4 can be reviewed. 2. Indicate the drawing scale on the plan per 2007 NFPA 13 Para 22.1.3 (32). Drawing was reviewed assuming a'/4" = 1'-0" scale. 3. There appears to be (1) sprinkler missing from the plan at approximately grid 2.5 in the middle of the room. Confirm coverage and add as required. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or eric@tuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING, PLLC Eric P. Tuazon, PE Fire Protection Engineer A.2409 ... warm Asucermo erem.oeer ne•wam GUARDIAN SECURITY Customer. LIFE ARO PROPERTY PROTECTION Vendor EXI?RESS Guardian Security Systems, Inc 1030 SOUTHCENTER 17431st Ave. South 'CIWILA, WA 54478 :Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Project Project # List of .Materials Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4)... 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) :43). 44) 45): 46) 48) 49) 50) Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens HFP-11 HFP-11-relay AD2-P PBA -1191 PBR-1191 PBR-1192 PBR-1193 HTRI-D HTRI-R HCP SET CW,W ZR-MC-CW,W ZR-MC-W,W SET-MC-CW,W Photoelectric Smoke Detector w/DB-11 Base Photoelectric Smoke Detector w/HR relay base Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Linear Beam Smoke Detector w!Backbox Prism Reflector for PBA -1191 w/Backbox 20x20 Reflector Package 10x10 Reflector Package Supervised Addressable Input Module Supervised Addressable Output Relay Module Supervised Addressable Module for Strobes Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Interior Visual Strobe Annunciator Combination Speaker/Strobe PAD -3 with BT -33 Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard Design per NFPA 13 — Ordinary Hazard Occupancy -130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 25 — Add Reliable Model FI 155° Chrome Pendent Sprinkler Heads 1/2 x %z 0 21 — Add Reliable Model FI 155° Brass Upright Sprinkler Heads %z x ' 2 'W. 6 — Add Reliable Model G4A 155° Concealed Sprinkler Heads %z x ' 2 Total: 52 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING MALL KEY PLAN CHAMPS SPORTS SPACE #324 LEVEL 1 of 1 STEEL JOIST/TRUSS HANGER DETAIL NTS 1/41 11 ter Sit„, klgdp O Without Comments CAs Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire . Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the • adequacy of designrvs :s totally with the designer. Additions, deletions or revis on: to these drawings after this date will void th:3 and will requirea resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection.by The Tukwila Fire Prevention Bureau. Date: I a —131 By: S1 f TUKWILA FIRE DEPARTMENT Please call: 575.4407 and give this job No. O , S -Oa•� and exact address for shut down or restoration aporoval. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrosi:at c t(,-; st approve/. I i PORTA IT NOTICE Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48• hours in advance of the date you want an inspection. E CROW\ FIRE PROTECTION INCORPORATED • P.O. BOX 12113 MILL CREEK, WASHINGTON . 98052-0113 PH..(425) 481-7669 SOUTHCENTER MALL 633 SOUTHCENTER SPACE #324 TUKWILA, WA 98188 DATE:. - J) - DRAWN: J 1 SCALE: /3/11...7.) 1 • f EXPRESS FIRE ALARM SYSTEM TUKWILA, WASHINGTON 1 SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UvRESHEET TITLE FA -01 SYSTEM I \FORMATIO N FA -02 TYPICAL DETAILS - WIRI\G A\D V OU\TI\G FA -03 FI E ALARM SYSTEv FLOOR PLA\ FA -04 SYSTE V CALCULATIO\S (CE\ERAL), RISE, SITE FLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER DF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD *16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR *14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART N0. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72; SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT. A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SI TALL DE MOUNTED AT 48" All. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 8 3 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP El INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTR I - D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IB< LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM gL C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L C n Q C FIRE ALARM STROBE (CEILING MOUNT) FIRE ALARM STROBE (WALL MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B AWP MR FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD ❑M MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. IN FI4LD A.F.F. ABOVE FINISHED FLOOR N/A A I / Without Comments L.N. F,B,❑ f U[IV1J1'ILL D I OTHERS IV/ H E IV/ Y�" As Noted 'fTt�+ea Ivy El Per The Attached Letter N/A NOT APPLICABLE N/A 'nese plans have been rev ved by The Tufovila i 6A P Prevention Bureau fcr conformance with current at U.O.N. UNLESS OTHERWISE NOTED N/A6Thinssfons s,aPds. Acceptance iskr rutvir ttoerrorsand which donot aah&izeviolafon.oOadoR4 st-Arrtaram and c,Tirrr;?vices. Tha responsibility for the W P WEATHERPROOF DEVICE N/A ;el afde.ai��n're,- ' I withthedesigner, Additions,, d::a,efi; I� s ar remit= to thane drawirsgstff ' tt,-,it_dl�,.. ‘,iJ�n mrlia PIS • , 2rAmPt arm and %ial require a RED AS BUILT ADD OR CHANGE N / A Irrutll air regi d9 atil° for subsequentsubsequentapevAa(r ocft t© field tEstt and II-IT/aeon by al! xc t^ is st ie� GREEN AS BUILT REMOVE N/A ir IXA-11' km ilia Fire P ` t:0 p.1u N/A Qom- i C n �,.°d TI , if -.AS BUILT N/A ; : N/A N/A N/A_ NOTES TO CAD NOTICE TUKWILA FIRE DEPARTriv,Qeii Please call: 575-440Z and give this jo No.0 and exact address for shut' down or restoration approval 41 Copyright 2006 by Guardian Security Systems, A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination) esting. JUN 2 3 2008 Tukwila Fire 24 4.1s) Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 J RELEASE/REVISIONS CID uJ z Q DESCRIPTION SHOP DRAWINGS Lu co 0 < CO <a)CC2 2Z C/,�WWo W �ZZ 0 a itO= 1 >LailO .0).5 Er_ 0 - (11) H SCALE: 1/8' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/12/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: SHEET FA -01 (7 7/ THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR+ PREVIOUS ADDRESSABLE DEVIL DUCT DETECTOR LOCATION O0 END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 0 GROUND -101 1.0 O O HTRI-R OSTATUS LED co 0 0 N.O. COM (a 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 11 VOLTAGE MAX - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C CLINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE- OUTLET SAMPLING \ TUBE `•� INLET SAMPLING—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC —4 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE +) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) O END OF LINE DEVICE (3.6K 1/4W) 0 SUPERVISED RELAY CONTACTS SWITCH (4MA @ 125VAC) GROUND ' (4.0A @ 30VDC) 27 VDC 3.5 rnA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 + I 01 TB1 gmmab 123456 H�P TB2 00.?!!..\1). 654321 NOTE: 0 d - O O HTRI-D bTATUS LED 0 1` m NOT USED CO m 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 010 T T T 0 -1=1- PAD-3 c PAD-3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K 12.1.)19_131.a_62 ia.s19194.sal.62 n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) "-..-SUPERVISED 1 SWITCH NAC -4 NAC -3 NAC -2 NAC -1 1 ( NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0- 0 K7 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS EOL 0 NPU 0 9 9 TEM -1 0 Cctg TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL v EARTH GROUND 0 -).(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE SCALE: NM FROM REMOTE (� POWER SUPPLY L C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) (+) ( ) STROBE SPEAKER (STROBE (STR❑BE) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE ..• OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR J END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICA1IONS SEE PRODUCT DOCUMENTATION. 0PERA1iNG TEMPERA1U E: +32' F (0 C) TO 100' F (38' C) HUMIDITY: 0-9333332 RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -* FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FTA4IN WHEN USED IN CONXNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE DATA IN (-) DATA IN (+) > I I REAR VIEW TO NEXT DEVICE > (-) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —� CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING. FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR----- SMOKE ETECT❑R— SMOKE DETECTOR MOUNTING SCALE:NONE of \--SUSPENDED ILLUMINATED CEILING DO NOT I\STALL ADDRESSABLE IN DEVICES UNTIL PR=PROGRAMVED W DEVICES ADDRESS. STOAT NG TH r) ab CT 0 L9 z (/) LU W (/) LU I— r---- FAX (206) 628-4990 RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS LL1 co 0 Ln u7 �oC C C Car 1� \ 0 z F-' z 0 00 op J r CO < O) Z ul � W � zz LI.cc U= co �/ � < F..< cC'S >< 11.1 0 CC 00 CE 8 5E0 T �1 1- 0 z 0 z ( J CL (SCALE: 1 /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: .1..0B NUMBER: SHEET F'J\02 1 Copyright 2006' by Guardian Security Systems, Inc. All Rights Reserved i EOL—S1 19.92V WOMEN'S ROOM TWO OCES81NG AREA 2S,2V ,2V I I I I I I �•i 2S,2V 75 I "DENIM WALLI :.� " " ,a T EX ILICNUI -$ALES kREA RESTNOOh ALCOVE N 2S,2V ".T. z.7.l7ZI::G7i 1 j--'--' -9i WOMEN'S TOILET \. F - ,.fit ROOM o--2S,2V 1 EOL—S2 20.04V '1 15 2S,2V Cs,2Iw�- il'::17!•lil;' 1 4 MEN'STOILET t) ROOM M' R DM TI REE D MANAOEWS OF 5- :/C..•%a-t:ac V- 2S,2V WOMEN'S I ROOM ONE 30 i "7.Z2Z 7llrlZZ7- l Z2L.. `.7Z/1 rlf7l Y�lll/T: KllTl%%72lyl //4 .r !7!_.'Tl.-irk 2S,2V 1 30.___... MEN`S ROOM TWO CREAK I I AREA • �_ 15./ C %' :GL •a ZOrIE///// 2S,2V 2S,2V ✓ r / / / l % / Ki / i j j j G f'%c% 'IlT 2Z.:.:227Lla:jYJ• 'l<a:l,'�TL7l:lri2.7 .l:2Z l7Ll:%a:"lll1:Z 27227.7.1.7,171:•1 NORTH I E Jl ,- .T171 z. !^l7Zlarl ll lacer(C.'ZI2Z22l`Z72.74 l ll•!:T' - " ^Z.7TZ'l<a<!_.'Tl7ZZ21 �l.✓.'l_.T277.G":2l...J ll2/a✓_7.722l iz_ ADJACENT TENANT EXPRESS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' 30 MEWS ROOM ONE FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE: FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS:(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER: AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, DO N0- INSTALL ADDRESSABLE IN T ATI\G DEVICES JNTIL PREPROGRAMVED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 174.3 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 5/15/08 z a«« COCO CO 0) 2 2ZO W5 c, ) [L.! CC �U= WCCCO o� 1- ctN uJ 4. - ALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET FA -03 725( Ip M P:31:,1 C01P. macVs a L. --'-'E---`; 250,407S' IP � 1 I • 5t`U; u A A 010 CO 1 PUBLIC CORK:DOP ?nE '.l:R S;102 GH,FTZ Ti CO JANE 'YAITIC.:E W :.I 5- 'i CLAIRE'S KIT: CAME4A 1 MOTIIE.R:f0CD MATER'. STA<3071?� :1050-0.0 If./,M SHOP ;:1E00150 0000 0.0 ts 0501; 10 000WEAFJ 0 A- 0 0 O 0 J• 494 C050.1 ('15/ r16-61 w- -- 0A_KIII 0003:50 10:S 1,0011C,CE t1 `1 fi ,270 (,251 <1 ,2 --,._ [1125. ' yJ w ! r11h^ .1135] t n 0 •�,,..... [,``CI 19.61 S: • I - 11, 42Oi 1 ZelISCA SIMS CA:,r Cc•NI5 PITA K:TOH(-N:J til'` LI.4 3 f,7 29.W C -,ht roc: Elovrim II_10IA:! I51IC: IS ( CAl11RIE RAM 0110 5 501000 ME;;:0011 Ai I:RILL CAL'EOPI:A P122A 511011E,1 rR1] R20500S L STAPOJCKS 64^J1 CHEESECAKE rAC TOR, [ Rt1 11495 It I NORTH GUESS WESTFIELD SOUTHCENTER MALL MerVYWS 2LEVELS 65 PAI; E'SS HCESE,JR-"c 1.00HER 000M w,,.,.,. •0,,000 • J'«..,,.,.,, �, �,. 5>m:: 11C: