PP - 1057 SOUTHCENTER MALL - SEATTLE TEAM SHOP KIDS - PERMITS AND PLANS
1057 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-010 08-F-260 10-S-017 08-S-315 08-S-310 0 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vanilla Shell 1 & Southcenter Mall 1 t31 Permit No.: 08-S310 Date: June 11, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe directuon per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Motherhood Maternity 1057 Southcenter Mall Permit No.: 10-S-017 Date: January 28, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. IIHydraulic Summary Job Number: KS0407 Report Description: Ordinary Group II . Job Job Number Design Engineer KS0407 Adam Kanter Job Name State Cerbficabon/License Number Vanilla Shells 1057 WESTESF136QF Address 1 AHJ Southcenter Mall City of Tukwila Address 2 - Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1-1057.cad SysteriiRemote Area(s) Most Demanding Sprinkler Data Occupancy 5.6 K-Factor 20.00 at 12.755 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 • 945.00ft2 (Actual 948.39ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(gm) 14 100.00ft2 AutoPeak Results Pressure For Remote Area(s) Adjacent To Most Remote Area Right: 72.639 Total Hose Streams 250.00_ System Flow Demand Total Water Required (Including Hose Allowance) 1 306.51 556.51 41 Maximum Pressure Unbalance In Loops All. &Irk 0.000'I.."'" .000rk Maximum Velocity Above Ground 11`t��:'. I -t;�./'. 24between 34 64 `� nodes and lir Maximumum Velocity Under Ground 1.16 between nodes 1 and 401 y, Volume capacity o1 Wet Pipes Volume capacity of Dry Pipes �,/t� 2423.43ga1 6.54ft3%om" D Supplies ' Hose Flow , Static Residual @ Flow Available @ Total Demand I Required i Safety Margin Node ' (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.511 556.51 74.798 64.714 Contractor Contractor Number Contact Name Contact Title KS0407 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web-Site Redmond WA 98052 6A ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/04/2008 4:35:46PM Page 1 Summary Of Outflowing Devices Job Number: KS0407 Report Description: Ordinary Group II © M.E.P.CAD, Inc. nAutoSPRINK® VR5 v5.2.6 06/04/2008 4:35:53PM Page 2 Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 116 25.77 20.00 5.6 21.182 Sprinkler 115 25.36 20.00 5.6 20.512 Sprinkler 114 23.52 20.00 5.6 17.639 Sprinkler 112 22.89 20.00 5.6 16.704 Sprinkler 111 22.64 20.00 5.6 16.344 Sprinkler 106 21.06 20.00 5.6 14.142 Sprinkler 107 21.13 20.00 5.6 14.243 Sprinkler 105 20.90 20.00 5.6 13.931 c Sprinkler 101 20.00 20.00 5.6 12.755 Sprinkler 103 20.09 20.00 5.6 12.869 Sprinkler 108 21.24 20.00 5.6 14.388 Sprinkler 104 20.43 20.00 5.6 13.308 Sprinkler 102 20.08 21.40 20.00 5.6 12.853 Sprinkler 110 20.00 5.6 14.598 c Most Demanding Sprinkler Data © M.E.P.CAD, Inc. nAutoSPRINK® VR5 v5.2.6 06/04/2008 4:35:53PM Page 2 111 Node Analysis Job Number: KS0407 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 33 14-6 2P0(8-0) 43.172 34 14-6 1 2P0(8-0) 43.122 60 14-6 PO(5-0) 28.216 64 14-6 2P0(5-0) 27.309 23.410 75 14-6 PO(5-0) 79 14-6 2P0(5-0) 22.140 94 13-6 PO(5-0) 18.938 98 13-6 2P0(5-0) 19.075 109 13-6 2P0(5-0) 17.394 113 13-6 P0(5-0) 18.474 123 13-6 P0(5-0) 17.000 125 13-6 E(2-0) 16.980 129 13-6 E(2-0) 18.328 163 13-2 fE(6-9'/2) 56.311 231 13-6 fE(6-91/2) _ 58.419 359 1-11 P0(26-4) 67.634 401 3-101/2 BFP(-4.500) 71.343 440 1-11 LtE(16-0) 67.654 21.182 20.512 25.77 25.36 116 12-0 Spr(-21.182) 115 12-0 Spr(-20.512) 114 12-0 SprE17.639) 17.639 23.52 112. 12-0 Spr(-16.704) 16.704 22.89 111 12-0 Spr(-16.344) 16.344 ; 22.64 106 12-0 Spr(-14.142) 14.142 21.06 107 ; 12-0 Spr(-14.243) 14.243 21.13 105 12-0 Spr(-13.931) _ 13.931 20.90 101 12-0 Spr(-12.755) 12.755 20.00 103 12-0 Spr(-12.869) 12.869 20.09 108 8-0 Sir( -14.388) 14.388 13.308 21.24 ' 104 8-0 Spr(-13.308) 20.43 102 12-0 Spr(-12.853) 12.853 20.08 110 8-0 Spr(-14.598) 14.598 21.40 1 -4-0 1 S 74.798 1 306.51 A(y ©M.E.P.CAD, Inc. 11 AutoSPRINK® VR5 v5.2.6 06/04/2008 4:35:57PM Page 3 1 Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group 11 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Length Summary Length Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Total Route 1 DR 1.049 Q=20.00 7.42 C=120 0.130131 29-7 Pf 5.280 101 12-0 q=20.00 K=5.6 12.755 Spr(-12.755) 11-0 Pe -0.641 109 13-6 17.394 3E(2-0), PO(5-0) 40-7 Pv BL 1.610 0=80.59 12.70 C=120 0.212853 7-3 Pf 1.544 109 13-6 17.394 Pe 94 13-6 18.938 7-3 Pv BL 1.610 Q=101.65 16.02 C=120 0.327034 11-0 Pf 4.906 94 13-6 18.9384-0; Pe -0.434 75 14-6 23.410 2LtE(2-0) 15-0 Pv BL 1.610 0=125.17 19.73 C=120 0.480627 10-0 Pf 4.806 75 14-6 23.410 Pe 60 14-6 28.216 10-0 Pv BL 1.610 Q=150.95 23.79 C=120 0.679571 14-0 Pf 14.956 60 14-6 28.216 8-0 Pe 33 14-6 43.172 P0(8-0) 22-0 Pv CM 4.260 0=306.51 6.90 C=120 0.022047 333-4% Pf 12.560 33 14-6 43.172 100-3 Pe 0.578 163 13-2 56.311 2P0(26-4), 7fE(6-9%), 433-7% Pv 2cplg(-1.500) CM 4.026 0=306.51 7.72 C=120 0.029029 58-10 Pf 2.253 163 13-2 56.311 18-9'% Pe -0.145 231 13-6 58.419 2EE(4-0), Eel (4-0), fE(6-9%) 77-7Y Pv CM 4.260 0=306.51 6.90 C=120 0.022047 112-0% Pf 4.197 231 13-6 58.419 78-4 Pe 5.018 359 1-11 67.634 3fE(6-91/2), CV(28-11 /2), GV(2-7%), 190-4% Pv PO(26-4) FM 8.329 0=306.51 1.80 C=120 0.000842 7-7 Pf 0.020 359 1-11 67.634 16-0, Pe -0.000 440 1-11 67.654 LtE(16-0) 23-7 Pv FM 10.420 0=306.51 1.15 C=120 0.000283 26-5'/ Pf 4.531 440 1-11 67.654 83-0 Pe -0.842 401 3-10'/2 71.343 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5%Pv UG 10.400 0=306.51 1.16 C=140 0.000215 109-2, Pf 0.047 401 3-10% 71.343 111-7 Pe 3.407 1 -4-0 74.798 E(35-1), 3LtE(25-6), S 220-9% Pv v Route 2 DR 1.049 0=20.08 7.45 C=120 0.131059 28-4% Pf 4.768 102 12-0 q=20.08 K=5.6 12.853 Spr(-12.853) 8-0 Pe -0.641 125 13-6 16.980 4E(2-0) 36-4% Pv BL 1.610 0=20.08 3.16 C=120 0.016271 1-2% Pf 0.020 125 13-6 16.980 Pe -0.000 123 13-6 17.000 1-21/2 Pv BL 1.610 Q=40.51 6.38_ C=120 0.059611 6-7% Pf 0.394 123 13-6 _ _ 17.000 Pe 0.000 109 13-6 17.394 6-7% Pv Q. Route 3 DR 1.049 0=20.09 7.46 C=120 0.131202 28-4% Pf 5.167 103 12-0 q=20.09 K=5.6 12.869 Spr(-12.869) 11-0'1 Pe -0.641 109 13-6 17.394 3E(2-0), PO(5-0) 39-4% Pv Route 4 DR 1.049 0=20.43 7.58 C=120 0.135344 33-10 Pf 6.067 104 8-0 q=20.43 K=5.6 13.308 Spr(-13.308) 11-0 Pe -2.375 123 13-6 17.000 3E(2-0), PO(5-0) 44-10 Pv Route 5 DR 1.049 0=20.90 7.76 C=120 0.141187 29-11% Pf 5.786 105 12-0 q=20.90 K=5.6 13.931 Spr(-13.931) 11-0 Pe -0.641 98 13-6 19.075 3E(2-0), PO(5-0) 40-11% Pv BL 1.610 0=84.67 13.34 C=120 0.233206 11-0 Pf 3.498 98 13-6 19.075 4-0 Pe -0.434 79 14-6 22.140 2LtE(2-0) 15-0 Pv BL 1.610 Q=130.20 20.52 C=120 0.516941 10-0 Pf 5.169 79 14-6 22.140Pe 64 14-6 27.309 10-0 Pv BL 1.610 0=155.56 24.52 C=120 0.718514 14-0 Pf 15.813 64 14-6 27.309 8-0 Pe 34 14-6 43.122 P0(8-0) 22-0 Pv CM 4.260 Q=155.56 3.50 C=120 0.006287 8-0 Pf 0.050 34 14-6 43.122 Pe 33 14-6 43.172 8-0 Pv Route 6 ©M.E.P.CAD, Inc. rj AutoSPRINK® VR5 v5.2.6 06/04/2008 4:36:01 PM Page 4 ii f Hydraulic, Analysis 1JoNumber: KS407 Report Description: Ordinary Group I Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length DR 1.049 Q=21.06 7.82 C=120 0.143168 26-11'/z Pf 5.437 106 12-0 q=21.06 K=5.6 14.142 Spr(-14.142) 11-0 Pe -0.641 94 13-6 18.938 3E(2-0), PO(5-0) 37-111/2 Pv •m Route 7 DR 1.049 Q=21.13 7.85 C=120 0.144113 26-11% Pf 5.473 107 12-0 q=21.13 K=5.6 14.243 Spr(-14.243) 11-0 Pe -0.641 98 13-6 19.075 3E(2-0), PO(5-0) 37-11% Pv v Route 8 DR 1.049 Q=21.24 7.89 C=120 0.145469 33-5 Pf 6.461 108 8-0 q=21.24 K=5.6 14.388 Spr(-14.388) 11-0 Pe -2.375 113 13-6 18.474 3E(2-0), PO(5-0) 44-5 Pv BL 1.610 Q=42.64 6.72 C=120 0.065543 9-2 Pf 0.601 113 13-6 18.474 , Pe 98 13-6 19.075 9-2 Pv v Route 9 DR 1.049 Q=21.40 7.94 C=120 0.147431 33-5 Pf 6.106 110 8-0 q=21.40 K=5.6 14.598 Spr(-14.598) 8-0 Pe -2.375 129 13-6 18.328 4E(2-0) 41-5 Pv BL 1.610 Q=21.40 3.37 C=120 0.018303 7-11% Pf 0.145 129 13-6 18.328 Pe 113 13-6 18.474 7-11 % Pv Route 10 DR 1.049 Q=22.64 8.40 C=120 0.163671 30-11% Pf 6.871 111 12-0 q=22.64 K=5.6 16.344 Spr(-16.344) 11-0 Pe -1.075 79 14-6 22.140 3E(2-0), PO(5-0) 41-11 % Pv Route 11 DR 1.049 Q=22.89 8.50 C=120 0.167010 27-11i/2Pf 6.510 112 12-0 q=22.89 K=5.6 16.704 Spr(-16.704) 11-0 Pe -1.075 79 14-6 22.140 3E(2-0), PO(5-0) 38-11% Pv .= Route 12 DR 1.049 Q=23.52 8.73 C=120 0.175634 27-111,4 Pf 6.846 114 12-0 q=23.52 K=5.6 17.639 Spr(-17.639) 11-0 Pe -1.075 75 14-6 23.410 3E(2-0), PO(5-0) 38-11 % Pv GO Route 13 DR 1.049 Q=25.36 9.42 C=120 0.201945 27-11% Pf 7.872 115 12-0 q=25.36 K=5.6 20.512 Spr(-20.512) 11-0 Pe -1.075 64 14-6 27.309 3E(2-0), PO(5-0) 38-11% Pv Route 14 DR 1.049 Q=25.77 9.57 C=120 0.208038 27-11Y Pf 8.109 116 12-0 q=25.77 K=5.6 21.182 Spr(-21.182) 11-0. Pe -1.075 60 14-6 28.216 3E(2-0), PO(5-0) 38-11'% Pv Equivalent, Pipe Lengths of Valves and Fittings (C=120 only) C Value Multiplier Actual Inside Diameter 4'87 ( ) Value Of C Multiplying Factor 100 130 140 150 0.713 1.16 1.33 1.51 = Factor Schedule 40 Steel Pipe Inside Diameter ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/04/2008 4:36:01 PM Page 5 Hydraulic Analysis Job Number: KS0407 Report Description: Ordinary Group II Pipe Type Downstream Upstream Diameter Elevation ;:Pipe Type Legend Flow Velocity HWC Friction Loss Discharge K -Factor Pt Pn Fittings Length Pressure Eq. Length Summary Total Length Units Legend Fittings Legend AO Arm -Over BL Branch Line CM Cross Main DN DR DY FM FR MS OR RN SP ST UG Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psiFoot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve De1V Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%° Elbow Ee2 22'/z Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD, Inc. yAutoSPRINK® VR5 v5.2.6 06/04/2008 4:36:01 PM Page 6 Hydraulic Graph Job Number: KS0407 Report Description: Ordinary Group II Supply at Node 1 150 Static Pressure 140.000 135 120 105 90 'Vl a Eu 1,556.51 with hose streams 75 va to I' a` —306.51 @ 74.798 60 45 System demand curve 30 10900.00 @ 20.000, 15 3 -1111J11111I I 111 1 11 1 1 II 1 1 1 1 1 1 1 1 1 1 1I 1 1 1 1 1 1 _ 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 1 1 I I I I I I I I I 1 1 1 1 1 1 1 I I I I I I I I I I 1 0 910022M 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.511 @ 556.51 System Demand 306.51 @ 74.798 System Demand (Including Hose Allowance) 556.51 @ 74.798 (A ©M.E.P.CAD,Inc. AutoSPRINK® VR5 v5.2.6 06/04/2008 4:36:11 PM Page 7 loin_iagram (Top View)' Job Number: KS0407 Report Description: Ordinary Group II "ago'fi n' r.,t,. i -f © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 06/04/2008 4:36:15PM Page 8 MOTHERHOOD MATERNITY FIRE ALARM SYSTEM TUKWILLA WA, 98188 SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 SYSTEM CALCULATIONS (GENERAL), RISER FA -04 FIRE ALARM SYSTEM FLOOR PLAN O Without Comments g As Noted in Red O Per The Attached Letter These plans have ben reviewed by The Tukwila Fire r,r evention Bureau irr t :,nfarmance with current City scandards. A; - :" : i • hject to errors and omissions which -.uthorIZe violations of adopted standards and or6-,?nceS. The responsibility for the adequacy of design r z. ;>s totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require,;a resubmittal of revised drawings for subsequent approval. Final acceptance -is subject to field test and inspection by. The Tukwila Fire Prevention Bureau. Date: f-2, ' I ° By: _ /41^'1 Si 1 1 tittWILA FIRE DEPARflI1L 11 , Please call: 575.440? and give this job /0-x-010 and exact address for shut. town or restoration approval NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1 ‘2" .82 SQUARE INCH 2 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 . 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX EX EX EX 1 RELOCATE EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FATP FIRE ALARM CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ECM INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD TRI -D DUAL INPUT INTERFACE MODULE HTR( -D SIEMENS 4S DEEP BOX VERIFY IN FIELD DUCT SMOKE D ETECTO R AD2-XHR W/ SIEMENS HFP-11 DET DUCT HOUSING VERIFY IN FIELD SMOKE DETECTOR (PHOTOELECTRIC) HFP-1 1 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1 G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1 /2" EXT. TO BOTTOM 15 STROBE (WALL MOUNT) MC -W SIEMENS 4S BOX 80" A.F.F. TO BOTTOM PAM MULTI -VOLTAGE RELAY MODULE PAM -1 AIR PRODUCTS 4S BOX VERIFY IN FIELD FIRE SMOKE DAMPER F.B,❑, F.B.❑, N/A VERIFY IN FIELD FA-BLXI JUNCTI❑N BOX X F.B.❑. F.B.❑. N/A VERIFY IN FIELD Fs WATERFLOW SWITCH F.B. F.B.O. N/A VERIFY IN FIELD TS TAMPER SWITCH F.B.D. F.B.D. VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD DR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAID JAN 2'' 2010 Tukwila Fire Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved rn c0 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE o 0 0 N .- 2 <<a< SCALE: 1'=1 /8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:10/ 14/09 BACKROUND PLAN PROVIDED BY: 10B NUMBER: C SHEET R FA -01 i 0 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. BEND OR OTHER OBSTRUCTION BEND OR OTHER OBSTRUCTION THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. DUCT DETECTOR-/ L❑CATION TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE SPEAKESTROBE SPEAKER I II II IDI 1 v 0 0 2 TUBE OUTLET - SAMPLING TUBE INLET, SAMPLING TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR AT LEAST SIX DUCT WIDTHS FROM BEND FA -02 STROBE SCALE=NONE MI ED o =I I❑o[ Z d _ IF - Fyob -0BLK PAM -1 SHOP DRAWINGS 0 O RED 11 0 OR 0 b IMMIX II J2 E« ,,,,, ,-: LI 1:1:1 11:I:I= O:, t_;- (ill SPEAKERISTROBE / ID NEXT DEVICE GENERAL NOTES 1. FRONT VIEW \ / NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DATA OUT (+) DATA OUT (-) NOT USED REMOTE DEVICE LOOP NOT USED REMOTE I DEVICE LOOP SPEAKERS ARE TAPPED AT 70.71/4 WATT. 2. STROBES CANDELAS ARE ON THE FIELD DRAWINGS. 3, CHECK CUT SHEETS SUPPLIED WITH PARTS BEFORE HOOKING -UP. 4. ALL ALD LOOP WIRES MUST BE IN METAL RACEWAY. (-) RATA CALE ILD 0 470 OHMS EOL MINNS TSM -1 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE MISTED PAIR WITHSHIELD #18 FPLIFPLR RED(JACKET} ooS J PF-IZ ou=io CO 1/40 000 • • • TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE 5. ANY ALD LOOP WIRE THAT GOES TO FANS / DAMPERS THAT ARE PART OF PRESSURIZING OR VENTING SMOKE CONTROL, NEED TO BE IN STROBE METAL RACEWAY AND 2 -HOUR PROTECTED (CI CABLE OR ENCLOSED IRCUIT IN 2 -HOUR CONCRETE OR SHEETROCK. FROM PRECEDING STROBE (-) APPLIANCE OR SYNC MODULE TO NEXT APPLIANCE OR 24K EOLR TO NEXT SPEAKER (<) END OR LINE RESISTOR 24K (EOLR) (-) SPEAKER CIRCUIT SPEAKERISTROBE AND STROBE WIRING SCALE:112'=1' 120VAC HOT NEUTRAL 0 0 TYPICAL FOR DAMPERS DAMPER — HOT O NEUTRAL 0 120VAC WHT Z d BLU -0 -0BLK PAM -1 SHOP DRAWINGS 0 O RED DATE 11/20/09 OR C NC NO DATA CABLE 0 SPEAKER CIRCUIT FAN TYPICAL FAN CONTACTOR POWER DATA CABLE 0 0 u7 HTRI—R STATUS LID 0 1///1 GROUND NOT SHIELD HTRI-R WITH PAM -1 INSIDE 4S DEEP BOX WITH EXTENSION RING TYPICAL WIRING FOR DAMPERS & FAN CONTACTOR POWER SCALE=NONE (STATUS & CONFIRMATION) CLOSED DAMPER CONTACTS NO C NC OQ OPEN DAMPER CONTACTS NO C NC O C DATA CABLE n IH 0 @ O HTRI—D ®STATUS LED IItlT USED CAM co 0 0 J LUL 0 // GROUND NOT SHIELD HTRI-D INSIDE 4S DEEP BOX SPEAKER CIRCUIT FROM PRECEDING SPEAKER OR FIRE ALARM CONTROL PANEL (FACP) (+)TO NEXT DEVICE OR 1 -) STOP IF LAST DEVICE TO NEXT (.}), ADDRESSABLE(_ DEVICE L=J ° 00 0 PAD -3 a a 00 00 AUX NAC4 W43 NAC2 NAC1 TROUBLE INPUT INPUT + - + - + - + - + NO C NC 2 2- 2+ 1 1- 1+ •J Ca NAC -4 DAMPER CONTACTS NO C NC O t/ly NAC -3 NAC -2 NAC -1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL WIRING FOR HTRI-R MODULE (PAD -3 TRIP) SCALE NONE DATA CABLE //ill GROUND NOT SHIELD DAVPER STATUS CONFIRMATION & ACTIVATION DAMPER HOOT 0 NEUTRAL 3.8k z [ I eJ I I I I • II 0 AC N CND I= IL EARTH GROUND -54-1-)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE HIRER 0 OD STATUS IID m h TO NEXT ADDRESSABLE DEVICE NEUTRAL °0 120VAC HOT FA -C2) SCALE:NONE 10 O IL, ,,,, ,,,,____,..---_,,,:,(,,.._ _____._f:)__._.i.......,________\(, 0 _v__:_____:____ COMBINE ALL SHIELDS AND ISOLATE FRIM GROUNDING TD NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL. PANEL. LR PREVWUS ADDRESSABLE DEVICE JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT J SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TING TEMPERATURE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: 93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR ,t DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > TO NEXT DEVICE< - REAR VIEW > (-) DATA OUT > (+) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —, CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \ \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE=NONE TO NEXT DEVICE CADDY BAR SUSPENDED ILLUMINATED CEILING STUD SHEET ROCK SPEAKER STROBE OR STROBE ONLY 80" A.F.F. - 4S DEEP BOX W/ 1-1/2' EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Z d DESCRIPTION SHOP DRAWINGS DATE 11/20/09 J2 E« 0 co T Wo WcLccoo cn (3) CD .teW Z W� U-1 WCC co ‘ALE: 1'=1 /8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZAN I DATE: 10/1 4/09 BACKROUND PLAN PROVIDED BY: 11 WALL MOUNTED SPEAKER STROBE FIRE MOUNTING ELEVATIONS 0B NUMBER: SCALE:NONE /r SHEET Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved J FA -02 SYSTEM CALCULATIONS Panel: XLS-V 'Wire Resistance 2.58 1 0 SET -MC ©15CD 64 0 I 2 SET -MC ©30CD 98 196 I 0 1SET-MC ©75CD 175 01 . : 1 Z-MC©15CD 64 64 i 0 iZ-MC©30CD 98 0 1 , iigii6ii= 3 TOTAL mA= - 260 14 I TotalWireResistance(R) !Total Device Load, Amps (1) 1 , Voltage Drop ( E) !EOL Voltage 197 20.141 260 (WL* 2 )*(R/ft) 1.02 1(Tota I Cct Load) 0.261 (E= I* R) 0.26 120.4 - E) 20.141 ica PROJECT: MOTHERHOOD Panel: XLS-V Wire Resistance 2.58 •,' Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 HTRI-D 0 0.001600 0 0.0035 0.000 0.0731 Amps 0.106 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Alarm Current Load: 0.106 Amps For 15 Minutes 0.027 Amp -hours 25% Derating= 2.226 Amp -hours Total System Current Load: 2.226 Amp -hours Battery Pair to be Used 12VDC Amp -hours 7AH ...., MOTHERHOOD , MATERNITY • , t , .., .. ..,.......,.. , December 2 _ . o ... . - . . , 1.8 . , .... ,... 0 _ SHOP DRAWINGS . - 70.7V118 ,..„,. „,..4. ' 'I'i`'.'Standby:.,''::: , „, ..... 2 70.7V114 3.6 7.2 2 Device Type 0 70.7V 1/2 7.2 0 0 70.7V1 14.4 0 1 0.03 0.03 0.030 0.030 DEVICES= 2 TOTAL mA= 7.2 14 240 20.39108352 7.21 2 0.098 0.196 S C 7 CD- - 0.175 Total Wire Resistance ( R ) ZR -MC ©16CD 1 ( WL* 2 )* (R/ft) 1.241 0.064 Total Device Load, Amps (I) ZR -MC ©30CD , (Total Cct Load) 0.01 Voltage Drop ( E ) 0.03 Amps 0.29 (E= I * R) 0.01 EOL Voltage r Standby Current Load: (204 - E) 20.39i 0.720 Amp -hours •,' Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 HTRI-D 0 0.001600 0 0.0035 0.000 0.0731 Amps 0.106 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Alarm Current Load: 0.106 Amps For 15 Minutes 0.027 Amp -hours 25% Derating= 2.226 Amp -hours Total System Current Load: 2.226 Amp -hours Battery Pair to be Used 12VDC Amp -hours 7AH ...., MOTHERHOOD , MATERNITY • , t , .., .. ..,.......,.. , . 'N .,.‘.' 1 „ Y ,,,Signal SIEMENS , ' Panel Battery Calculations DESCRIPTION SHOP DRAWINGS u e c:i ...:,-,:.,;.4:..:' .0: .. '‘' ''''.'''' : l';, ''' .''" ,..„,. „,..4. ' 'I'i`'.'Standby:.,''::: , „, ..... .., .„ 11/20/09 2 Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 S C 1 5CD - . 0.064 SET -MC @30CD 2 0.098 0.196 S C 7 CD- - 0.175 ZR -MC ©16CD 1 0.064 0.064 ZR -MC ©30CD 0.098 0.03 Amps 0.29 Amps Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.29 Amps For 5 Minutes= 0.024 Amp -hours 25% Derating= 0.930 Amp -hours Tota Syttem -CU en Oad: 0 930 Amp -hours ',' 7hours.-1.,,,,.., '.,,, ,. ',..4,,.;,,, VOLTAGE DROP CALCULATION BATTERY SIZING CALCULATION .• ._ . (..) .• 1.1., " .• .• . C.-.. _.I ..,. E:1 i Li_/ ----__ ! ____---- 1 THE W,1-1.K114G CO. . 1 . . .• .• . . . . . .• . . . . . „ . . .• . .• . . . .• E te-i_bl, . , 1 ET a .• ii:±1 , 73 Es , .• . a. a a i .-.--- 1 r r-••,,, i 171.fq .• .• .• .• fli-lA t_J 1z. < ,--I 11. 1 --.....=, . 1 Iii --101 1 - : FJ 1 I... a a •-•___ ; ---._ --0--- -c,-- --_ -.3- DE.17..,_ T - , 4.4 l, (.5 ....- ;:i:.7' ! I-) I -__._,-• 1 . ! ! liftCA . r15. _ -----.'i,,------ _ -..... i 1-..-.2_i _ ! - .71._,Ip •._. : ,4. Iftigi 1 . 1 a 0 • ,i, • I - 1 . . 1 . I 1 ,• I 14 ......1., RAM E1.7.E4 MAL. GRILL CALIFORMLA ?;Z04. KITCHEN r-0 14551 1 _r -etctit--4 a D251 i 1.t401 El :TO !II CHAN3`5 p -n DJ _U:JAM:14G 1.14751 CHEESECAkE VAC TORs' STAR B 114;301 I t1.1. YTTTITT-i1 2S,2V 2S,2V 2S,2V EX 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS 1REV. BY: I .i DESCRIPTION SHOP DRAWINGS DATE 11/20/09 2 < <<<< I 0) CC w z w 0 (I) LLJ (i) cnj ‘CALE: 1'=1/8" DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE: 10/14/09 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SITE MAP RISER DIAGRAM SHEET FA -03 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved EOL -S1 t 28; 1 D 0 EX C. PETc_r r "F.rr-.CSLZET:ETS FC.? ADJACENT TENANT F RT. e'21 nr. va. til 2S,2V bd D S1-2 v1-1 EX MOVE FROM HERE 2S,2V 1lii�3]3]i MALL COMMON AREA NORTH S1-3 Vl-2 EX C ADJACENTTEN.NT MOTHERHOOD MATERNITY SCALE 118'=1' FLAG COTES: LI> FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATI❑N GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACT❑R, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, ALARM SIGNAL TO ALARM SYSTEM WILL BE SUPERVIZORY, SUPERVIZED CARBON MONOXIDE SENSOR AND SHUTDOWN THE OVEN TO OVEN FAN CONTROL TERMINALS EXISTING DUCT DETECTOR MUST BE SIEMENS AD2-P WITH, HTRI-R, AND TSM -1 ELECTRICAUINSTALLING CONTRACTOR SHALL RETURN ONE FULL SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT' PURPOSES. d co CT 0 C9 z (1) J w Ln o L" LL1 N Q \J J FAX (206) 628-4990 RELEASE/REVISIONS IREV. BY: I z a DESCRIPTION SHOP DRAWINGS L1.1 Q o M 0 N z cr W woo 1— dC co < W a 1- VJ� co cc 0-1 0 �zs iv. CC OF - W o O 0 0 J w >- (1) cc w CC 4CALE: 1 '= 1 /8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 10/1 4/09 BACKROUND PLAN PROVIDED BY: �0B NUMBER: 1 SHEET \ IAO4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved / SHEET \UVI3E HEE TITLE SHEET INDEX FIRE ALA TUKWILA • FA -01 YST I\ FOVATIO\ FA -02 TYPICAL DETAILS - WRI \ G A\ D V OU\TI\G FA -03 •E ALAM SYSTE v FLOO PLA\ 'FA -04 YST V CALCULATIO \S (GE\ EAL), ISE, SITE PLA\ 1!,! •;,•4 WIRE DESIGNATION SCHEDULE ' I It! .11 1J VIRE SCHEDULE AND CONDUIT FILL CHART ;•.:: • i :I !• WIRE DESIGNATION 11. . . •1:1,: ;; I' . .. ,.. • SYMBOL I:DESCRIPTION ' NUMBER OF CONDUCTORS ' SIZE TYPE ! , COLOR ' CODE D ' H P S 2S A . V 2V I X , UD UI M ! 1 B ' . ! DATA LINIE-ADDRESSABLE 1 DOOR HDL 11 DEVICE ! !1STROBE ' . 11STROBE IANNUNCI . SPEAKEFI •SPEAKEI . REMOTEINDICATIONLIGHT LOW LEVEL UNDERGROUND UNDERGROUND DOOR HOLDER BEAM DETECTOR . • ' LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) DER POWER - 24 VDC TWO #14 FPL/FPLR RED (JACKET) OWER - 24 VDC TWO #16 FPL/FPLR RED (JACKET) IRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED ' (JACKET) IRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWO #18 FPL/FPLR RED (JACKET) AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) POWER TWO #16 FPL/FPLR RED (JACKET) POWER TWO #14 FPL/FPLR RED (JACKET)' . CONDUIT FILL CHART .1, . . • :I • i ‘ 1, • 1 I • I I I I, t • i • NO. OF 1 • TWO!' 11.. , CONDUIT ' ! CALCULATE ABOVE. THE • I, •I , II ti II FIGURES CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA ! , .TWO 600V #12 AWG THHN/THWN .244 0.D. ; .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. , .0346 CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. ; .0191 FILL THE TOTAL AREA , OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL .12 SQUARE INCH .II ` • 1/2" 3/4" , . .21 SQUARE INCH 1" .34 SQUARE INCH , • . . ' . 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 1.34 SQUARE INCH . .. I . . . , , .. ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., • CHP. 9, TABLE 4. SHIELDED \A/IRE TO B GRDUNDET AT POINT CIF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH JAPE ANDITIAPED AT END. SYSTEM ASHINGTON ENAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSA1 DEVICES ADDRESS. '1\11,)ATING DEVICES UNTIL PREPROGRAMMED WITH 1. NUMBERS ADJACENT TO DEVI, ; SYMB. DEVICE 01-1-02 WOULD BE T1:E SEC T POL 2. DETECTOR AND AUDIBLE CIR 3. AUDIBLE/VISUAL CIRCUIT WIRI BRANCHING IS PERMISSIBLI, 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, Lo, 5. INSTALLATION MATERIALS (I.E STANDARD BOXES, FIBER OP ARE NOT SUPPLIED BY SIEV1 6. DETECTORS SHALL NOT BE IV AIR STREAM OF AIR SUPPLY 7. WIRING SHALL BE PER PLAN , TYPE, QUANTITY AND COLOR AND UNIQUELY MARKED FOR 8. INSTALLING CONTRACTOR SH'4 DRAWINGS FOR "AS BUILT" P FOR ADDITIONAL INSTALLATIO. SHEETS AND/OR INSTALLATIQ, 10. THE 120vac POWER ELECTRIC MUST COMPLY WITH ARTICLEI: SPECIFICALLY SECTION 1-5.2 SOURCES. 120vac POWER SH DIRECT SUPERVISION OF FIRE 9. 11. ALL HORN/STROBE AND STR1 OF 80" A.F.F. OR 6" BELOV: 12. ALL MANUAL PULL STATION5' ACTIVATION DEVICE. b ICT AL C 's L DENOTE DEVICE CIRCUIT/ADDRESS \D DEVICE ON ADDRESSABLE LOOP 1. RITY SHALL BE OBSERVED. ERVISED. NO PARALLEL C FORMANCE WITH THE NATIONAL (S), AND/OR AUTHORITY HAVING JURISDICTION. ; CONDI) WIRE, FITTINGS, HANGERS, S .CAB FITTINGS, AND ASSOCIATED EQUIPMENT) CRB RUS DIVISION. UNTED.1 DIRECT IUTLEITS1.$PER NFPA 72 2-3.5.1 ITH ODE. C,' QTURE, IL POSES. INSTR INSTR I • .1' WORK 5 ANI L NOT ILARM pECT TO CONDUCTOR SIZE, & OR CABLE ,NDUCTORS SHALL BE PERMANENTLY, 'ENTIFICATION. N ONE SET OF ACCURATELY MARKED TIONS, REFER TO CATALOG CUT TIONS. TRAY, SUPPLYING FIRE ALARM SYSTEM PANELS 760 OF NFPA 70, N.E.C. AND NFPA 72, ,EFERENCE TO DEDICATED, BRANCH POWER E APPLIED TO FIRE ALARM PANEL WITHOUT ECHNICIAN. E17,EV ES SHALL BE MOUNTED AT A HEIGHT OPI'E !CEILING, WHICHEVER IS LESS. HALLE MOUNTED AT 48" A.F.F. TO THE I 11 13. ALL PANEL NUMBERS AND b CUITS 14. ALL 120VAC CIRCUITS ARE F GENERATOR. ILL BE ON THE RECORD DRAWINGS SET. M DE ,CATED CIRCUITS• FROM THE EMERGENCY 15. PER NFPA 72 SECTION 5-3..3 DEICTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-By0FTHAI±ATuRTAHD0ERSITyISHCATINPGLE JTUERIASNDDICTFIION. NAL STRUCTION. DETECTORS THAT HAVE BEEN INSTAL ,ED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED IL R REPLI CED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. EXCEPTION: WHERE REQUIRED FOR PROTECTION DURING CO 16. WIRING SHALL RUN CONTINU S FRO AND THEN FROM DEVICE T0IIEVICE OTHER BACK BOXES OF DIF RENT1 17. ALL WIRING SHALL BE METER AND FREE OF SHORTS BETW FINAL EQUIPMENT TRIM. FACP TO FIRST DEVICE ON A CIRCUIT ,ITHOUT SPLICING IN PULL BOXES OR IRCUITS.* D, VERIiilED TO BE CONTINUOUS, FREE OF GROUND • :EN co UCTORS AND OTHER CIRCUITS PRIOR TO • f 18. ALL CABLES SHALL BE MARK:D ASI PERMANENT LABEL AT ALL VICES, 19. THE ELECTRICAL CONTRACTO SHALL OUTSIDE AND INSIDE OF THE•:FIRE A AFTER COMPLETION OF THEr INAL I • 20. DETECTORS MUST BE RATED1 OR, TE PERATURE IN THE ENVIRONMENT IN 'WHICH IT IS LOCATED. $: DICATED „ON FIRE 'ALARM RISER WITH A 'OUNCTION .BOXES AND' FACP. CLEAN ALL DIRT AND: DEBRIS FROM THE .• ARM BACK BOXES AND JUNCTION BOXES: • • IrzATION. I , 21. ALL WIRING BETWEEN FLOOR,- SNAIL( 22. NFPA 72 2007 6.4.2.2.2 ALL1 TYLES PHYSICAL CONDUCTORS (E.G. EtALI INSTALLED SUCH THAT THE C),, TON' FROM AND RETURNING TO TH CONTF . ROUTED SEPARATELY. THE OU GOING CONDUCTORS SHALL NOT BE TJNIIN MULTI -CONDUCTOR CABLE), cL* 23. NFPA 72 2007 A.6.4.2.2.2 GOALI ADEQUATE, SEPARATION BETW N THI THIS • SEPARATION IS REQUIRETO ,F1, CABLES FROM PHYSICAL DAW, GE.; TH • SEPARATION TO PREVENT PH ICAL •• THE CABLE IS INSTALLED VElfICALL CABLE IS INSTALLED • •••1 '1 II ! 1. E LOCATED IN CONDUIT. F CLASS A CIRCUITS USING OPTICAL FIBER) SHALL BE :AND RETURN CONDUCTORS, EXITING L UNIT, RESPECTIVELY, ARE • ND RETURN (REDUNDANT) :CIRCUIT HE SAME CABLE ASSEMBLY (LE., , OR RACEWAY. , . 6.4.2.2.2 IS TO PROVIDE IPUTGOING AND RETURN CABLES.. ENSURE 'PROTECTION OF THE IRECOMMENDED MINIMUM MAGE 15..305 MM ,FT) WHERE ND .1.22 M (4 FT) , WHERE THE • QUANTITY 2 3 3 EX SYMBOLS LEGEND MODEL XLS-V MANUFACTURER BACKBOX MOUNTING HEIGHT SIEMENS PROVIDED 66" A.F.F. TO TOP FIR iLALARM SDD-C SIEMENS PROVIDED RE TE ANNUNCIATOR RE �TE BOOSTER PAD -3 P0 R SUPPLY 66" A.F.F. TO TOP SIEMENS PROVIDED 66" A.F.F. TO TOP FACE MODULE RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD D.DJJ INPUT INT FACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD .1 CP ,,FROL POINT j MO PLE HCP SIEMENS 4S DEEP VERIFY IN FIELD RE ,CTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD EAR BEAM E DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SmpKE DETECTOR (Ab ,RESSABLE-PHOTO) DUEF SMOKE ; pEjr1.!-:CTOR HFP-11 \V SIEMENS DB -11 BASE 4S DEEP VI// 1G RING CEILING AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEP1114 DETECTOR (Ap, ,RESSABLE) HFPT-11 VV/ SIEMENS DB -11 BASE 4S DEEP IA// 1G RING CEILING ALARM ,KER STROBE LING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING VI// 1-1/2" EXT. ALARM KER STROBE L MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM ALARM KER STROBE ING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. ALARM BE ING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING !ALARM BE L MOUNT) ZR -MC -W SIEMENS 43 BOX 1)1// 1G RING 80" A.F.E. TO BOTTOM U.O.N. ALARM KER INC MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING IA// 1-1/2" EXT. k; ALARM KER L MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM ALARM BE THERPROOF) MU po, 1-VOLTAGE SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR-201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD NETIC R HOLDER F.B.O. F.B.O. F.B.O. FIR:ALARM TE INAL CABINET F.B.O. F.B10: F.B.O. VERIFY IN FILD VERIFY IN FI LD F.B.D. VERI IN FIELD ABIE FINISHED FLIIIIR FU ISHED BY OT !RS N/A N/A `VA Without Counts As Noted In Red Per 1he At q214ed Letter N/A 1! N/A i nese plans have been reviewed by The Tukwila Fire NO APR'. ICABLE N/A SS OTHERWISE N/A WE HERPROOF DE ICE N/A ProvAntion Bureau for conflrAnce with current cityN/A stdridards. Acceptance is sublect to errors and • omissions which do not authorize violations of adopted stanaaras and ordinances. jte he responsibility for thet, acitL66'acy of design rests t with the designer. "' " Additions, deletions or revisions to these drawings atter thiiiiRte will void this, acce e and will require a N/A resubmittal of revised drawings for subsequent approval. AS 1 :UILT ADI OR CHANGE N/A Fin,ra)Rcceptance is subject4fAetd test and inspeCtiqpx The'Tblwitila Fire, Prevention'Bureau. AS UILT NO, ,S TO CAD N/A N/A DW N/A N/A fuKWILA FIRE DEPARTMM, Please call: 575-4407, and give this job No. and exact address for shut. d, min or restoration aoorovai, N/A I I • ;• I •;;!I I ; , CD (3• 0'060.; CN..1 CD CD . C\.1 < LL • RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS uJ C21 co 0 •••,,„ 0 z Non E r. A complet0, gred, Tukvvila Fire Department Pre-test Certificatemut Icie presented to the Inspector, prior t) commencement Occeptance Testing !Of arifr Fre Alarn ,ystems, 1,11 resur: Fee ard testing. and Deectipn FaiIure4fte t • 1 in a ke-Osp.e; o terminatiOn Copyright 2006, by Guardian Security Systems, Inc. All Rights 6ALE: 1 /8" = 1 ' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY NUMBER: I-1 SHEET FA - Ho II• THE DUCT SMOK4,QETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72, THE PREFERRED INSTLIILI LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT iWIDTHS FRON ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. II BEND OR OTHER OBSTRUCTION OUTLET SAMPLING \ TUBE FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AIR DUCT 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE ,} STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIL END OF LINE DEVICE(3,6K 1/4W) SUPERVISED SWITCH ;I tV CIUND O HTRI—R OSTATUS LED INLET SAMPLIN TUBE NOT USED REMOTE + DEVICE LOOP NOT USED REMOTE DEVICE LOOP 470 OHMS DUCT DETECTOR LOCATION 00 0 N.O, 0 CD m COM N.C. TAT LEAST ,I' SIX DUCT WIDTHS FROM BEND is EARTH GROUND FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> .. (+)TO NE STOP TYPICAL MOUNT NG FOR AD2-P DUCT DETECTOR O NOTE: i FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE PREVI❑US ADDRESSABLE_ DEVICE I (BACKGOUND MUSIC SHUTDOWN) TO NEXT ADDRESSABLE DEVICE _ + NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - NOTE 2' MUSIC SCALE:NONE ; I 1. TYPICAL AD2-P DUCT SMOKE DETECTOR WIRING DETAIL �11 }-AC POWER SOURCt-1. JJJJJJ ;!'' COMBINE ALL SHIELDS Al ISOLATE FROM GROUNDIN TO NEXT ADDRESSABLE DEVI STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR it PREVIOUS ADDRESSABLE DEVICE END OF LINE; FROM REMOTE POWER SUPPLY C'S' CABLE) RELAY CONTACTS CE Iu1 TO NE rT DEVIC .r: OR END d ❑ LINE DEVICE II (3.6K 1 W) 11 'I jI i itl 1' SUPERVI,SED-:iV SWITCH 111 11II ;i (+) • (-) STROBE (4.0A a 125VAC) GROUND (4.OA @ 30VDC) 27 VDC 3,5 rnA DURING POLLING 10 OHMS 200 'FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG ALL SUPERVISED SWITCHES MUST BEHELD CLOSED AND/OR OPEN FOR AT LEAST ,25 SEC, TIJ GUARANTEE DETECTI❑N, • TB1 S 6 a m o o 123456 HC TB2 D 65 43 21 O NOTE: 'i' FOR ADDITIOIAL: SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NDOFT.: INE DE CE FROM FACP 6K 'i/4W (V❑ICE CIRCUIT) '('V' CABLE) UPERVI ED WITCH TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCS (FIRE SUPPRESSION SYSTEM INTERFACE) GNDN AOIII'' MI :7- 0 0 if ill iii L 1. I' { j , 1t° I. PAD-3 !INPUT INPUT I TROUBLE 1- 1 2+ 2— 2 NC C NO NAC1 NAC2 NAC3 NAC4 'AUX + — ' + — + — + — + — is m 0 e m B m AB. 06i 0 Q .9_ Q �+ _f �' 'I' �, 24K � �— Ai + TYPICAL WIRING FO I HCP MODULE (PAD -3 TRIP) LABEL SCALE .' is ":. r ; I,I Id , Z NAC -4 NAC -3 `, NAC -2 NAC -1 SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY F 80" A.F.F./ 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX • (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE i Ij TO NE DEVIC =` OR END D LINE ti NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER 1INQ TEMPERATU E:. +32' F (0' C) TO 100' F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) 4 DEVICE IS USED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FTAAIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE*- ( ) DATA OUT }, > (+) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE HARD LID --- 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N. CEILING MOUNTED SPEAKER/STROBE N. CEILING NOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPP❑RT. 0 O ; i I TO NEXT DE 0 O CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE ---- SUSPENDED ILLUMINATED CE LIN DO NOT I \ STA_L ADDRESSABLE NIT ATI DEVICES ,RTI_ RRERROG'RAMMED. WITH DEVICES ADDRESS. YI Copyright `. 2006 by Guardian Security Systems, Inc. All Rights eserde, K") I. O? 070 g_ co O `PH „', 'z a LL _J LU V) O CV W CV .0 Q Ci L11.1 t\,.'i': RELEASE/REVISIONS >- m LU z DESCRIPTION SHOP DRAWINGS w I— Do 0 If) L() O z SCALE: 1/87=1' DRAWN BY: I.ANDERSON DESIGNED' BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: it1 CIZ v 1,0 CO 0\ 0 0` 0\ o N 0 N 1•, m w CC z Q 0 FLAG NO RELEASE/REVISIONS DESCRIPTION --- 2S,2V 2S,2V E01, --S1 19.95V FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES`; SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. SHOP DRAWINGS w Q D o ««< FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. 24, v 12S,2V /Er Er 5 00 coT Q0) Z w° tnzZ Q2 W cc U cn ,4 LCIE1oLn� o= Itut 0 1057 WESTFIELD SCALE 118".1 ENTER MALL N DO NOT I hST _L ADDRESSABLE N T AT DEVICES UNTIL PREPROGRAMMED WIT DEVICES ADDRESS. �CALE: 1/8" =1 ' DRAWN BY: (.ANDERSON DESIGNED 'BY: R.V,EZZANI DATE: 5/ 12/08 BACKROUND : PLAN PROVIDED BY: `JOB NUMBER: j SHEET FA -03 Copyright 2006, by Guardian Security Syi;tems, Inc. All Rights ,1 (r) LJ a. (Z. LLI Cf LLJ LS) (2) 2S,2V •1 ! I • , I ; I. • • 1 ; 1' 1 mervyn*L. 17) • [li. • MTR 1 05T; El (.)E 1..0(X E R. ROOM ELEC - ONICS BOUT-101JF PRE.: TZ.E: IvE • .• • 1057 WESTFIELD SOUTHCENTER MALL SCALE 1132'4 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 30 30 15 15 C 30 15 EOL -S1 15 2S,2V 0 1- 0 EX RISER DIAGRAM 3 TLE /VORK.0117. AR ! ir! I I CASUAL • KING COLJI\ITY LiBR AR)/ H • •• - • --• -- • 1---- 1, F.: WIE LE IR < I ; • 'ji 1- D.. 1. 1057 FACP ADD ONS Id SYSTEM CAL LATIONS 2877 SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Cuttent Load;:. ,•0,1L S andby: Alarm: Ciarreilt Load: Standby: Alarm: DOCe Type: Qty Amps Total Amps Total evice, Type Qty Amps Total Amps Total HFcf'11 AD2P 0.0022 0.0022 1.1 0.0635 0.0635 HTqlrR HT -D' IC • ! , 0.009600 0.0096 0.001600 0.0023 0.064 0.021 0.0035 0.064 0.042 0.005 0.0731 Amps 0.106 Main System Board SET -MC ©15CD SET -MC @30CD SET-rp @75CD SET- ' @110CD 1 0.03 0.03 0.030 0.064 0.098 0.175 0.233 0.030 0.064 0.294 SET-1,.MC-Ci15CD MC-C@135CD Amps !I SET-' MC-C@185CD 15CD 0.318 0.318 0.445 0.064 0.192 Sta;pdby Cu ent Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 41 R -M • • 30CD 0.098 0.0015 Alatm Currelt Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 1 7 0.03 Amps 0.58 Am :•• 25% Derating= 2.204 Amp -hours tandby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0.58 Amps For 5 Minutes= 0.049 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.961 Amp -hours Bactery Pairfo be Used: tt• • tk. 12VDC Amp -hours 7AH BATTERY SIZI Total System Current Load: 0.961 Amp -hours Battey Pair to be Used: 12VDC Amp -hours 7AH ',CALCULATION PROJECT: Notification Appliance C WESTFIELD SOUTHCENTER MALL cuit etail Panel: Date: 1057 re Resistance 1.62 , May 29, 2008 R NT TOTAL= 550 CIRCUIT: S1 QTY 1 3 Device Type SET -MC @15CD SET -MC @30CD Alarm Current Alarm Total 64' 64 98 ' 294 Wire Size Wire ngth Voltage at EOL Circuit Total Total Wire Resistance ( R ) 0 SET -MC @75CD 175 0 SET -MC @110CD 233 0 SET-HMC-C@115CD SET-HMC-C@177CD SET -HMC @135CD 318 0 0 0 445 318 ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage 0.86 0.55 0.47 19.93 0. SET -HMC @185CD 445 (20.4 - E) 3 Z-MC@15CD 64 192 Z-MC@30CD 98 SET-MC-CW@110CD 233 DEVICES= 7 TOTAL m A= 550 12 19.927771 550 PROJECT Panel: Date: Notification Appliance C6 WESTFIELD SOUTHCENTER MALL 1057 uitbetail May 29,2008 111 Wire Resistance 2.58 • i R NT TOTAL= 7.2 CIRCUIT: SPEAKER CIRCUIT ' . ••••• ., • . QTY 4 • Device Type 70.7V1/8 Alarm Current 1.8 Alarm Total 7.2 Wire Size Wire Le 'oltage at EOL Circuit Total Total Wire Resistance ( R ) ( WL * 2 )* (R/ft) 0 0 • 0 DEVICES= 4 TOTAL m A= 7.2 14 56 • 20.37900912 1.1 7.21 Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= 1* R) EOL Voltage (20.4 - E) VOLTAGE DROP 11h LCULATION 2.92 0.01 0.02 20.38 Copyright 2006 by Guardian Security Systems, Inc.. All Rights Reervcl' . . RELEASE/REVISIONS DESCRIPTION DRAWINGS 0 (r) co 10 10 0 0 LLI F.- › - CD 6ALE: 1/8"=1' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: NUMBER: ( SHEET "N FA -O4,. ADJACENT TENANT NOTE: REPLACE ANY/ALL BURNED OUT LAMP. HELD VER/FY. EXISTING LAMP TYPE, THERE SHOULD BE NO MIXING OF COOL AND WARMLAMPS. REPLACE WITH COOL LAMPS.AS//F REQUIRED. Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means • 2 - Add Tyco Model TY -FRB Chrome Pendents 155° 1/2 x %z • 1 - Add Tyco Model TY -FRB Brass Upright 155° 1/2 x 1/2 • 3 - Relocate Tyco TY -FRB Chrome Pendents 155° 1/2 x 1/2 6 - Total RETAINER STRAP WHERE RIcQUIRED IN SEISMIC AREAS TOP BEAN/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD STEEL JOIST/TRUSS HANGER DETAIL NTS (d) = Ductile iron Model MT -3 8 MT -9 Mechanical tea serves the same function as MT -1 & MT -8 but uses a steel electro plated u -bolt to save space and for easier installation In tight places. It is ideal for direct connections with sprinkler heads end drop nipples. HOUSING: Ductile iron ASTM A538 grade 85-45-12. COATING: Zinc electroplated U - BOLT: Carbon steel SAE grade 2, zinc plated. NUT: Carbon steel ASTM A194, zinc plated. GASKET: EPDM (-309F to + 230°F) THREADS: MT -3 NPT per ANSI/ASME B1.20.1 MT -9 British standard parallel (BSP) per SS21 e c MV -3'& MT 110/414/11 1131 IN. 9 :"M> MAX. *090140 9.11.11 GtiAPEIGAL.TEE. 9'. k 721 M.4. aWaM11016 n}}�mmm-• AFF1109. 1.11091 k11CN 4 C 0 i 1 114 a 12 300 1.19 2.19 1.04 3.20 111 7.23 . 033 11/493(4 300 1.19 2.14 1.14 350 121 225 0.07 i I 11 700 1.19 227 131 330 121 3.23. 1.04 112112 300 1.77 024 7.74 350 1.33 7.24 027 112911 3011 1.19 7.20 134 350 1.3.3 2.23 an 171371 200 1.19 239 1.73 3.50 131 3.25 1.90 2.7/2 100 7 1 1.19 3.51 2.51 201 3.73 7.54 7.74 4.41 2 014 310 201 7.09 4.91 123 225 094 1.09 201 300 1.19 254 1p 175 75; 212a1/2 300 . 1.19 275 2.20 4_25 4.01 . 7.25 3.09 21202/4 900 1.14 2.71 3.24 4.74 7 a 2 X 0.571 28201 300 1.19 2.0 3.22 4.72 7 70 7.25 614 10.0.9la 300 1.79 2k 2.32 .177 1a° 2-1a .. 10.0314 300 1.14 443 7.32 4.24 7.90 2.25 , 0.14 `220.0..I 900 9.19 .230 2.03 4.20 194 1 2.21 . I.I! -I 11 in R•�d n : - .1 -{ ci Letter - ari d b1, The Tukwila Fire current City to errors and violat'ons of adopted ;+.lard; and ot-oir..:: s. The responsibility for the ::: t, c/ of des'•gn r sts totally with the designer. .Vitfftions iS43ri 7 to these drawings after ci::i:e ;:i=; ;7.1 ; ;;:.._ �' ,: It :.: d �oliii requireja 1 cs! bri-itztai , Lai7Yc, 0. Ytv1 ngs for subsequent approval. Finat : n °t:. e !S fi`!a test and inspection by The ! :: ti'Rv k w -f3 }U. Gate: f --Z8 '(O n ' �7 ( TUKWILA FIRE DEPARTMEM Please call: 575.4407 and give this Job lob. !0 S- °( and exact address for shut. down or restoration u():)ro7; °WVe!d stamps -must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. e L CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 .m pAID. 1057- 'JAN 057'JAN 2 2010 Tukwila Fire f'lnry/, /kip DATE: J -22-w. DRAWN: 3 SCALE: Y. = 1 "4e/2 > 2 -‘a/ Shell S • ace 1057 VICINITY MAP SCALE: General Notes Suite# 1057) 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Qccupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA &. manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. ZONE T5 if --- EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE E $1- TF1 kw 3 oto 4)7.23% .3'/ J i Ff 4 1N7 2,54 24 15'-0° A.F.F AµT+ -•■—Existing Main ZONE T5 11t 4-12'-0" A.F.F 4 f 4 �'Y % �'Y'S'� ✓/���%tel; •• b? '-0" A.F.F Ordinary Group II.020giPm/ft2 for 945.00ft2 FIRE SPRINKLEftELANL 1 3__5- 7 9-1 ' SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent %Z' Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT HANGER SYMBOL R5415 6 5.6 Pendent White 155°F G4A Concealed CONT. NO.: K$0407 FLEXI EAD DETAIL NOT TO SCALE AA I LATERAL LINE RESTRAINTS NON•TlhREADED BRACE PIPE Remote Area 1 057 SHELL SPACE 918' KWIK BOLT (21/4' EMBED LENGTH) ///://///"/ /////1/. _.---' / / / / // j:.N BRACE PIPE FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT y' • FIG. 4A PIPE CLAMP FOR SWAY BRACE r�� LATERAL BRANCHLINE RESTRAINT -6A1)NON•THREADED BRACE PIPE 0.A �. LATERAL BRANCHLINE RESTRAINT NOT TO SCALE CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 945.00 Fe SPRINKLER Reliable F1 FR Semi-Rec ORIFICE 1/2" K.= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 306.51 GPM O 71.34 PSI • At time of Design 12'- 0" CLC. = 37.00% AREA REDUCTION Hanger No. 07C HILTI Kwik Bolt I11 "T / ; \ r / Drilled Anchor% \ • \ HILT! Kwa Bok 0 Cut Rod Lgth Rounded to Nearest Inch imoncE Rod Coupling — r Pipe All Thread Rod Swivel Ring Concrete �v. Construction Bottom of Concrete to Center tJne of Pipe Note on Plan Note an Plan: Hanger Number and'A' Dimension Wold stamps must be inspected , ore pipe is thong. Gon©t pal pf or to hydrostatic a prova1. 'AGER DETAIL NOT TO SCALE CEP ED O Without Comments As Noted In Red Per The Attached Letter c I nese plans have been reviewed by The Tukwila rir Prevention Bureau for conformance with current ci`y� standards. Acceptance is eubie:.t to errors and omissions which do not authorize violations of adcptEE stanaaras and ordinances. The responsibility for tveL0 adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atte't this date will void thiG.acceptance and will require a resubmittal of revised drawings for subsequent apxoVel. Final acceptance is subject to field test and inspec'tioro y The Tukwila Fire, Prevention Bureau. Date: M21610 By. VICINITY MAP DETAIL NOT TO SCALE fUKWILA FIRE DEPARTME Please call: 575.4407, and give this job No. P9'--' S'3/5,, and exact address for shut. lawn or restoration approval V7 -a Swinerton Bui CONTRACTOR: BRANCHLINE RESTRAINT Total =21 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/04/08 Western States Fire Protection Company 7102180th AVE NE, STE A•105 - REDMOND, WA - 98052 Lk . # WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUOl1ERO0E /AUSTIN / DALLAS / DECATUR / DENVER / DULUTH /HOUSTON/KANSAS CITY LAS VEDAS !MI NEAPOLIS/PHOENIX!PORT1AtD/RAPID CRY/ST. PAIL/SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Vanilla Shells 1057 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER PLAN SHEET FP -1 OF X700 1 .li►lkvvilli Fh-a 124 2.2 Shell Space 10t7 IA •U VICINITY MAP (Suite# 1057) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinilder system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. ZONE T5 EAST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE 2t3 1-11 w .............................i Q ▪ 4�1 X-' :12::::0:11 4Q2:1/4:10 o --.7-15'-0" A.F.F � � i��i. � 6, • 7-9 `^ 8-0 �( 8-9 6� a m MI +—Existing Main ZONE T5 Remote Area —74 • 7:7; /0.1!1 T77 G77,'.7* .J7' 7 1 C>+0; i .-+w5 . © 3 TQJ�'r— 2 . T/777 -777r"77-777 77777 .7i7r NI' 1-1..,-....- \-1- -1.- - - 1 Ordinary Group II.0.204pm/ft2 for 945.0Of FIRE SPRINKLER PLAN 1/8"=1'-0" 8'-0" A.F.F 1 �E J 3 5 7 9 11 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE 3 SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.909 • SWIVEL SWM BRACE FITTING 3)8' KWIK BOLT —(2114' EMBED LENGTH) FIG.1000 "FAST CLAMP' SWAY BRACE ATTACFMENT LATERAL LINE RESTRAINTS 1 I NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE 3/8' KWIK BOLT (2 /N' EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT I� re LATERAL BRANCHLINE RESTRAINT WI) NON -THREADED BRACE PIPE BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III • HILTI Kw* BoR II / Drilled Anchor tJ Cut Rod Lgth Rounded to Nearest Inch Rod Coupling A9 Thread Rod Swivel Ring is + Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Vanilla Shells 1057 w z 0 Adam Kantner s v N O! 0 Swinerton Builders CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent z Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 6 5.6 Pendent %Z' White 155°F G4A Concealed CONT. NO.: KS0407 Total = 21 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIN / DALLAS /DECATUR/DENVERIDULUTH/HOUSTON/KANSAS CITY LAS VEGAS/YRPEAPOUS /PHOENIX/PORTLAND/ RAPID CITY/ST. PAUL /SALT LAKE CLTY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Vanilla Shells 1057 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER PLAN SHEE T FP - OF 1 1 , . gi? r Remote Area —74 • 7:7; /0.1!1 T77 G77,'.7* .J7' 7 1 C>+0; i .-+w5 . © 3 TQJ�'r— 2 . T/777 -777r"77-777 77777 .7i7r NI' 1-1..,-....- \-1- -1.- - - 1 Ordinary Group II.0.204pm/ft2 for 945.0Of FIRE SPRINKLER PLAN 1/8"=1'-0" 8'-0" A.F.F 1 �E J 3 5 7 9 11 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE 3 SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.909 • SWIVEL SWM BRACE FITTING 3)8' KWIK BOLT —(2114' EMBED LENGTH) FIG.1000 "FAST CLAMP' SWAY BRACE ATTACFMENT LATERAL LINE RESTRAINTS 1 I NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE 3/8' KWIK BOLT (2 /N' EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT I� re LATERAL BRANCHLINE RESTRAINT WI) NON -THREADED BRACE PIPE BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III • HILTI Kw* BoR II / Drilled Anchor tJ Cut Rod Lgth Rounded to Nearest Inch Rod Coupling A9 Thread Rod Swivel Ring is + Pipe Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE Vanilla Shells 1057 w z 0 Adam Kantner s v N O! 0 Swinerton Builders CONTRACTOR: SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R3615 15 5.6 Pendent z Chrome 155°F F1 FR Semi-Rec APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R5415 6 5.6 Pendent %Z' White 155°F G4A Concealed CONT. NO.: KS0407 Total = 21 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE 06/19/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIN / DALLAS /DECATUR/DENVERIDULUTH/HOUSTON/KANSAS CITY LAS VEGAS/YRPEAPOUS /PHOENIX/PORTLAND/ RAPID CITY/ST. PAUL /SALT LAKE CLTY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Vanilla Shells 1057 Southcenter Mall Tukwila ,Wa 98188 FIRE SPRINKLER PLAN SHEE T FP - OF 1 1