HomeMy WebLinkAboutPP - 1060 SOUTHCENTER MALL - NEW YORK & COMPANY - PERMITS AND PLANS1060 SOUTHCENTER MALL ASSOCIATED PERMITS 06-F-164 12-S-183 06-S-132 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Papaya Clothing 1060 Southcenter Mall Permit No.: 12-S-183 Date: August 14, 2012 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and crass mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe directon per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. Silent Knight SK -5700 BATTERY CALCULATION Project: New York & Co. - Southcenter Mall Date: August 29, 2006 Standby(C) Alarm(D) Hours= 24 Minutes= Module Description Base Panel--SK-5700 SD505-APS Smoke Detector SD500-AIM Monitor Module NAC Circuit Load 5 Qty Standby Total Standby Alarm Total Alarm (mA) (mA) 1 200 3 55 1 55 1 0 Total(A)= Battery Capacity= 1.2x (AxC)+((.0167xD)xB) divided by 1000 (mA) (mA) 200 325 325 165 55 165 55 23 23 0 1301 1301 420 Total(B)= 1814 12.28 18 Amp Hour Provided Notification Appliance Circuit Detail CIRCUIT: H1 Volts @ QTY Device Type Alarm Current Alarm Total Wire Size Wire Length EOL Circuit Total 3 AS24MCC @ 95cd 269 807 2 AS24MCC @ 30cd 122 244 2 AS24MCW @ 30cd 110 220 1 RSS-24MCC @ 15cd 30 30 DEVICES= 8 TOTAL mA= 1301 14 150 22.7549431 1301] HVAC CODED NOTES: GENERAL CONTRACTOR TO UNDERCUT DOOR 1" FOR AIR FLOW. Q INSTALL DUCTWORK AS HIGH AS POSSIBLE. (TYPICAL) 0 TEMPERATURE SENSOR FURNISHED AND INSTALLED BY CARRIER CONTROLS TECHNICIAN AT 48" AFF. PLENUM RATED TEMPERATURE CONTROL WIRE SHALL BE FURNISHED BY CARRIER AND INSTALLED BY MECHANICAL CONTRACTOR (CONDUIT IN WALL BY ELECTRICAL CONTRACTOR). VARIFY EXACT LOCATION OF SENSOR WITH NY&CO'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION. 0 PROVIDE AND INSTALL NEW EXHAUST FAN AND NEW EXHAUST DUCT AS INDICATED ON PLANS. CONNECT 8"0 DUCT TO EXISTING EXHAUST DUCT. O ROOM TEMPERATURE CONTROL FURNISHED AND INSTALLED BY CARRIER CONTROLS TECHNICIAN AT 48"AFF. PLENUM RATED TEMPERATURE CONTROL WIRE SHALL BE FURNISHED BY CARRIER AND INSTALLED BY MECHANICAL CONTRACTOR (CONDUIT IN WALL BY ELECTRICAL CONTRACTOR). VERIFY EXACT LOCATION OF THERMOSTAT CONTROL WITH NY&CO'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION. gO AHU-1 AND HP -1 ARE FURNISHED BY NY&CO AND INSTALLED BY MECHANICAL CONTRACTOR. INSTALL WHERE SHOWN ON PLANS. SEE HVAC SCHEDULE ON SHEET M2.0 FOR MORE INFORMATION. AHU-1 FURNISHED NTH COMPLETE ECONOMIZER PACKAGE WITH ALL CONTROLS AND WIRING FACTORY MOUNTED. ALL ROOF WORK INVOLVED WITH SETTING OF THE ROOF CURB AND UNIT SHALL BE DONE BY THE MECHANICAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL PROVIDE ADDITIONAL STRUCTURAL STEEL REQUIRED TO SUPPORT HP -1. SEE HVAC CONTACT NOTE: ON THIS PAGE FOR CARRIER CONTACT INFORMATION. V MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A DUCT MOUNTED SMOKE DETECTOR. UPON ACTIVATION SMOKE DETECTOR SHALL SHUTDOWN ALL AIR HANDLER FANS. 0 RETURN AIR DUCT TO HAVE 1" ACOUSTICAL UNING. DUCT TO BE SAME SIZE AS RETURN OPENING EXTEND MINIMUM OF 48". O ALL DUCTWORK IN MANAGER'S OFFICE SHALL BE HARD DUCTED. NO FLEX DUCT SHALL BE ALLOWED. 0 OUTDOOR AIR DUCT EXISTING TO REMAIN. C> EXTEND REFRIGERANT PIPING TO HP -1 ON ROOF. ROUTE PIPING ACCORDING TO LANDLORD INSTRUCTIONS. USE MANUFACTURES RECOMMENDED PIPING SIZES. 0 HP -1 FIELD VERIFY LOCATION. INSTALL NEW UNIT IN EXISTING LOCATION. INSTALL APPROVED AREDAMPER. 0 FIELD INSTALLED ED MIXING BOX. CG t( Without Comma • As Noted In Red [� Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conform; nce with current city standards. Acceptance is 4ubject to errors and omissions which do not authorize violations of adopted stanoaras and ordinances. The responsibility for the_ adequacy of design rests tcially with trie designer. t Additions, deletions or:ev!sions to these drawings after t this date will void thi.s acceptance and will require a i resubmittal of revised drawings for Subsequent appra}tal: I Final acceptance it eubjcet to feld tI3st and ihs eplio �y The Tukwila Fire Prevention Burn u: Date: K-ok0 By; 4 GENERAL ME PROTECTION NOTES: THE TENANT'S FIRE PROTECTIONS SPRINKLER SYSTEM SHALL BE DESIGNED TO MEET ORDINARY HAZARD REQUIREMENTS. IF NO CEILINGS OCCUR. AS IN M:CHANICAL ROOMS, ETC.. SPRINKLER HEADS AND PIPING TD BE EXPOSED BRASS UPRIGHT TYPE. ALL OTHER AREAS OF BUILDING WHERE SUSPENDED CEILINGS OCCUR SHALL BE CONCEALED WHITE PLATE HEADS. MAKE PROVISIONS FOR DRAINING AND PROVIDE INSPECTOR TESTS AS REQUIRED. ALL DRAIN PIPING SHALL BE PIPED TO OUTSIDE OR INDIRECTLY TO SINK OR F.D. ALL PIPE AND FITTINGS SHALL MATCH LOCAL FIRE DEPARTMENT THREADS. ALL ARE SUPPRESSION WORK SHALL BE PERFORMED BY UCENSED FIRE PROTECTION CONTRACTOR N THE STATE OF WASHINGTON. ALL SPRINKLER HEADS SHALL BE LOCATED IN CENTER OF CEIUNG TILE. (WHEN APPLICABLE) WHEN MODIFYING EXISTING SPRINKLER SYSTEMS SPRINKLER CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE EXISTING SPRINKLER ZONES. COORDINATE WITH NEW FIRE RATING PLANS IF APPUCABLE. NO PVC PIPE SHALL BE PERMITTED. CURRENT SHELL SPRINKLERS ARE EXTENDED COVERAGE HEAD SPRINKLERS. RENOVATED AREAS SHALL BE 100% SPRINKLED. ALL WORK SHALL BE DONE IN ACCORDANCE W114 ALL LOCAL, STATE, AND FEDERAL CODES, LAWS, AND REGULATIONS. CONTRACTOR SHALL VISIT SITE AND BE FULLY COGNIZANT OF ALL CONDITIONS PRIOR. TO SUBMITTING PROPOSAL PROVIDE A VALVED DRAIN AT THE LOW POINT IN EACH PIPING SYSTEM. ALL VALVES AND OTHER PIPING SPECIALTIES SHALL BE FULL UNE SIZE UNLESS OTHERWISE INDICATED. SEAL AROUND ALL PIPES PENETRATING FIRE SEPARATIONS WITH APPROVED INCOMBUSTIBLE PACKING RETAINED BY METAL COLLARS. COORDINATE ALL CUTTING AND PATCHING WITH GENERAL CONTRACTOR. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING FOR HIS WORK. AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH NFPA 13 AND BUILDING CODE REQUIREMENTS. REFER TO REFLECTED CEIUNG PLANS FOR EXACT LOCATIONS OF UGHT FIXTURES AND CEIUNG TYPES. COORDINATE EXACT LOCATION OF PIPING AND HEADS WITH MECHANICAL AND ELECTRICAL DRAWINGS. ALL SPRINKLER DRAWINGS. RISERS, CODE REQUIREMENTS ETC. ARE THE RESPONSIBIUTY OF AND SHALL BE PROVIDED BY THE SPRINKLER DESIGN CONTRACTOR. THE FIRE PROTECTION CONTRACTOR SHALL VERIFY SPRINKLER PIPE LOCATIONS AND ELEVATIONS AND SHALL MODIFY PIPE ELEVATIONS, AS REQUIRED, TO ACCOMODATE ANY NEW CEIUNG ELEVATIONS. THE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL CONSTRUCTION DOCUMENTS AND HYDRAULIC CALCULATIONS. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE. BUT NOT BE UMITED TO, THE LAYOUT AND SIZES OF THE PIPE, THE LOCATION OF ALL SPRINKLER HEADS, THE LOCATION AND SPACING OF SUPPORTS. THE LOCATION OF THE SYSTEM RISER, THE LOCATION OF ANY WATER SUPPLY VALVES AND THE LOCATION OF THE WATER SUPPLY SOURCE. HYDRAUUC INFORMATION SHALL INCLUDE, BUT NOT BE LIMITED TO, THE DESIGN AREA OF OPERATION. THE DESIGN DENSITY. THE OCCUPANCY HAZARD(S), THE HOSE STREAM ALLOWANCE. THE WATER SUPPLY INFORMATION, THE TOTAL SYSTEM DEMAND AND ALL OTHER SUPPORTING CALCULATIONS. rUKWILA FIRE DEPARTMENT$ Please call: 575.4407, and give this job No. 0(0- --/( y 1112). a rid ,Kact address for shut. ;,,:.J: ,r restoration approveV NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems, :lure of test will result in a Re -inspection Fee and termination of the testing, j:aM+l SYMBOL li NOTES : 1. SYMBOL KEY - 4. VOLUME DAMPER - FIRST LErTEit; S -SUPPLY R -RETURN E -DOT T -TRANSFER - FACTORY FURNISHED. OPPOSED BLADE OR BUTTERFLY SECOND LET EFt D -DIFFUSER R -REGISTER 6 -GRILLE WHERE AVAL/J3LF- ADJUSTABLE FROM FACE. 2.PROVIDE OP110AL DIRECTIONAL BLOW FEATURE FOR 5. BORDER STYLE - OTHER THAN 4 -WAY. A- SURFACE MOUNTED -8- LAY -IN, PROVIDE YATH PLASTER FRAME 3. FINISH- FOR DRYWALL L E UNG MOUNTING. -A- WHITE 'G' LAY -IN FRAME FOR T -BAR CEIUNG. 'B' O VETTE - G.C. FID PAINT TO M6. PROVIDE BOOT FOR DUCT MOUNTING. KI CEILING CR WALL 107}1 ENAMEL Mat • SYMBOL (1)(2) MANUFACTURER/ CATALOG NUMBER NOMINAL SIZE MOUNTING MATERIAL FINISH (3) DPR. (4) BORDER (5) REMARKS MOD. NECK 916 OTHER STEEL ALUM. SD -1 TUS OMNI OMNI 24"x24" 12' 0 ®—MOD MOTOR OPERATED DAMPER 8 A - S0-2 OMNI 24"x24" 14" 0 8 A - SD -3 ROM�NI 24"x24" 10" 0 B A - SG -1 TI US 300 -RS 14'X8" 12"X6" B A - RG -1 T17US PAR 24"X12"22'X10" B A - HVAC DUCTWORIC MEM SYMBOL DESCRIPTION SD ® SUPPLY DIFFUSER RR la RETURN REGISTER E -11e EXHAUST FAN I;:1. LOW VOLTAGE SENSOR AIR FLOW DIRECTION -Iv-) 1-1 NEW DUCTWORK WITH SIZE no CFM SUPPLY DIFFUSER SYMBOL & CFM RG -1 1220 CEM RETURN REGISTER SYMBOL & CFM VAV-1 NEW VAV BOX & CFM 6700 CFM ®—MOD MOTOR OPERATED DAMPER HVAC GENERAL NOTE& MECHANICAL CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF WORK. AFTER DEMOUTION WORK IS COMPLETE, NOTIFY NY&CO PROJECT MANAGER IF EXISTING CONDITIONS ARE NOT CORRECT FOR INCOMING MECHANICAL EQUIPMENT. MECHANICAL CONTRACTOR SHALL COORDINATE DUCTWORK HEIGHTS WITH ALL OTHER DISCIPUNES AND CEIUNG HEIGHTS TO AVOID INTERFERENCES. ROMf3 CONTRACTOR: ALL ROOFING WORK MUST BE DONE BY CASCADE ROOFING AT TENANTS EXPENSE. CONTACT BOB PETERSON AT (206)464-0441 AUG 2 9 2006 Tukwila Fire z-�1�73 Jze t50 HVAC CONTACT NOTE FOR HVAC SCHEDUUNG AND DELIVERY CONTACT AMY NAZARIAN AT (800)-301-0605 WITHIN THE FIRST WEEK OF CONSTRUCTION. F PROTECTKAI NOTE ALL SPRINKLER WORK TO BE DONE BY CROWN FIRE PROTECTION CONTACT JOHN ABLE AT: (425)-481-7669. FIELD VERFY ALL COMMONS DESIGN DRAWINGS ARE SCHEMATIC.. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL. LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT CLARIFICATIONS MADE BY THE ARCHITECT. ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT. ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT. NEW YORK&COMPANY 450 West 33rd Street New York, New York 10001 763 SUSQUEHANNA AVE FRANKLIN LAKES, NJ 07417 TEL: 201-848-9060 FAX: 201-848-9881 ENGINEER: Ogtar, On Oda. M•Reta9 Engineering, Ina 750 Brookeedge Blvd. WestervV e. Oh10 43081 PHONE 614.810 9391 FAX 614.818.2337 1257 Kemper Meadow Drive Suite 800 Fa -est Pork, OH 45240 PHONE 513.825.1152 FAX 513.525.4649 SEAL REVISIONS NO A DESCRIPTION DATE DESIGN CHANGE 2/27/0E BUILDING DEPT. COMMENTS 4/3/06 A ENG. CHANGE 4/4/06 FELD COND/DESIGN CHANGE 6/14/06 DATE SCALE PROJECT # : 1-24-06 AS NOTED 0808009 z qis NV O r °-,-N.YyC V )-T ots Itt be:0 Cr W O;c4J 3a © m W I! z PROJECT TITLE WESTFIELD SHOPPINGTOWN SOUTHCENTER SPACE #326 TUKWILA, WA STORE NO. — .011111. SHEET TIRE HVAC AND SPRINKLER PLAN SHEET NO. M 1.0 SPRISCLER LEGErel SYMBOL DESCRIPTION ON NEW. CONCEALED WHITE PLATTE SPRINKLER HEAD ON NEW BRASS UPRIGHT SPRINKLER HEAD VN NEW SDEWALL SPRINKLER HEAD HVAC CONTACT NOTE FOR HVAC SCHEDUUNG AND DELIVERY CONTACT AMY NAZARIAN AT (800)-301-0605 WITHIN THE FIRST WEEK OF CONSTRUCTION. F PROTECTKAI NOTE ALL SPRINKLER WORK TO BE DONE BY CROWN FIRE PROTECTION CONTACT JOHN ABLE AT: (425)-481-7669. FIELD VERFY ALL COMMONS DESIGN DRAWINGS ARE SCHEMATIC.. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL. LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT CLARIFICATIONS MADE BY THE ARCHITECT. ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT. ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT. NEW YORK&COMPANY 450 West 33rd Street New York, New York 10001 763 SUSQUEHANNA AVE FRANKLIN LAKES, NJ 07417 TEL: 201-848-9060 FAX: 201-848-9881 ENGINEER: Ogtar, On Oda. M•Reta9 Engineering, Ina 750 Brookeedge Blvd. WestervV e. Oh10 43081 PHONE 614.810 9391 FAX 614.818.2337 1257 Kemper Meadow Drive Suite 800 Fa -est Pork, OH 45240 PHONE 513.825.1152 FAX 513.525.4649 SEAL REVISIONS NO A DESCRIPTION DATE DESIGN CHANGE 2/27/0E BUILDING DEPT. COMMENTS 4/3/06 A ENG. CHANGE 4/4/06 FELD COND/DESIGN CHANGE 6/14/06 DATE SCALE PROJECT # : 1-24-06 AS NOTED 0808009 z qis NV O r °-,-N.YyC V )-T ots Itt be:0 Cr W O;c4J 3a © m W I! z PROJECT TITLE WESTFIELD SHOPPINGTOWN SOUTHCENTER SPACE #326 TUKWILA, WA STORE NO. — .011111. SHEET TIRE HVAC AND SPRINKLER PLAN SHEET NO. M 1.0 0'-0" 2 ,ALOPEN E2 411'-2" si 1 t-9" 1 11'-2" RETAINER- STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD REID PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS CCE' Tie:0 Without. Comments As rotted in Red Per The Attached Letter 1-ese plans have been reviewed by The Tukwila Fire evention Bureau for conformance with current City -.:ndards. Acceptance is subject to errors and - missions which do not authorize violations of adopted .andards and ordinances.. The responsibility for the _dequacy of design rests totally with the designer. ,.dditions, deletions or =ovisions to these drawings after this date will void th:. jcceptance and will require a resubmittal of revised drawings for subsequent approval. 'inai acceptance is subject to field test and inspection by rhe Tukwila Fire Prevention Bureau. nate: -1 `f -/ By: w, SI i RELOCATE EXIST'G DIFFUSER AS SHOWN TUK'iVILA FIRE DEPARTMENT Please call 206-5754407 and give this Fire: Permit No. S �V and exact address Cc!. shut- down hu -down or restoration approval. EXISTING EXISTING wL E,a T1ERY &CK -UP EXISTING EXISTING OPEN CLG. 3'-6" 1'-3' '-6" 3'-9" 3 .25' CAMERA ri 13'-10 1/' EXISTING EXIST'G AUST FAN m m n P. m ' R LI S. :3 ,. b? G :• P2 IE T £3 C 13 1 :} 2'-0" 2'-8" 2 —10" �qp 6'-0 3'-6" { 6'-0v c) 0 0 O r--------o---oco2,1- -� a RELOCATE EXIST'G DIFFUSER AT Hi HNC ROOM E1 Design per NFPA 13, Ordinary Hazard, Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart ®':.16 — Add Reliable Model G5 Standard Response 165 Pendents 1/2 x 1/2 o 21 — Relocate Reliable Model G Standard Response 165° Pendents 1/2 x 1/2 o E — Existing pendent o E — Existing upright REFLECTED CEILING PLAN SCALE 3/16" = 1'-0" at, 0 4,40plik4 jick;;;:;;;;617; • CROWN FIRE PROTECTION INCORPORATED. P.B. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7689 Papaya Clothing /0 (0o Southcenter Mall Tukwila, WA 98188 .: DATE: $:1 p .1 Z DRAWN: Irr SCALE: 3/I (0 I• PAID N 40-04— L AUG 012 TUIWILAFIRE l!' i •;':'"•--tt • 1 4- ! I; • —.7 • o "Ti7— ic3,wt 0'001 1-51 • xpII S -146th -St tggr S -1520 -St „ • (518.1 S4-158tht-St-• t6Oth st 160th-St---cn.. S -162nd-St-4 • 3. 5 144th St 541EI !c't i • B` Rol sw cn S -164th -St 117- S -1 -166th -St ; ! St - • — 170th St ---- SeaTac 7--:—;;;-1-5-172nd St --• - -----i•-S-173rd St €r2006 Microsoft Corp 02004 Nill/MQ, andforGDT.Ine: ;.• (0) * i! eplot) I; . l; ! 11 1 t I t t ! 54 Fort Dent.. Park Pc' ' — \ 7: . CP ('n 633'Southcetit2.J.Mall, ISettle,-V4A,4913188 : !--1,3aker-Blud I 53 Southcenter Pkwy , • Microalitt•k Ma pPoi nr ...17th St - o 0. try * 121. Renton Boeing Longacres nclustrial Park /m 0 • I 02, 0 • i; --t I; 0 NA (44 0 (0) *%0 rA WK I ; I RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL -DIST/TRUSS HANGER DETAIL — TOP CHORD NI ACCEPTE Without Comments O As Noted In Red ID Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conicncice with current city standards. Acceptance SUL::t lo errors and omissions which do not authorizc vioiallens of adopted standards and ordinances. ;1,.=, responsibility for the adequacy of design ri:;sts t•:;Ay with ti designer. Additions, deletions or ri-.-Nctit-_, to these drawings ater this date will void th;c.acoaptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: By: 0 i; I I • 00) 1, TUKWILA FIRE DEPARTMENT. Please call: 575-440Z and give this job No. 0 J22 and exact address for shut. down or restoration approval; ; I ; . . . (0) S Design per NFPA 13, Ordinary Hazard 130 Sq. Feet Max All materials to be new, U.L. listed, and F.M. approved 55 - Relocate Reliable Model G4A Concealed head 155° '/2 x 1/2 11 - Add Reliable Model G4A Concealed head 155° '/2 x 1/2 15 - Recut existing to Reliable Model G4A Concealed heads 155° 1/2 x 1/2 15 - Plug 1 inch outlets La RETAINED FOt RECORDS ONLY REVIEWED (..rice Comm Eivr P516:6) 1:3 FURNISH AS CORRECTED ca';REVISE AND RESUBMIT ci REJECTED Corredions or comments made on the shop drawings doting this review do not ;AI eve contractor from compliance with requirements of the drawings and ,peifications. This check is only for review of the general conformance vrith the esign concept of Om OW and gerieral complifift03 Withthe information given - in the contrad documents. The contrador is responsible for: Confirming and correlating all quantities and dimensions; seleding folxication processes and lethniques of consIndait coordinating workwith ail edam hadsand performing rill work in a sofa and sallsfadory nova Ulan REM E.724424/4 FILE Et. 6/24/a 7... • - EM1 Shoppiritown CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PIL (425) 481-7669 PAID JUN 29 2006 Tukwila. Piro NEW YORK & COMPANY -21/((6P-7 WESTFIELD SHOPPING -TOWN SOUTHCENTER 9z-/435:3:3 Southcenter Mall, Space 326 Seattle, WA 98188 DATE: 6_20-06 DRAWN: triLLSCALELLy::.Lzq__