HomeMy WebLinkAboutPP - 1070 SOUTHCENTER MALL - EXPRESS - PERMITS AND PLANS1070 SOUTHCENTER MALL ASSOCIATED PERMITS 08-S-433 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Express 1070 Southcenter Mall Permit No.: 08-S-433 Date: August 26, 2008 Reviewer: AI Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods Tess than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 'A inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. • Comply with Tuazon Engineering review letter. All references are NFPA 13, 2007 Edition. �zonE�ci�E��c 19 August 2008 Mike Maguire Fire Sprinklers Inc. 1014 North Street, Suite 200 Sumner, WA 98390 Tuazon Engineering, PLLC 4322 NE r Street Renton, WA 98059 425.917.1683 tel 425.917.1705 fax www.tuazon.com RE: Westfield Mall — Express (Suite #581) Independent Third Party Review — Fire Sprinkler System Dear Mike: As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. The following was reviewed: • Fire Sprinkler Drawing — Sheet FP -1 dated 7/31/08 • Hydraulic Calculations dated 8/19/08 The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Revise sprinkler head legend to specify QR heads (TY3531) as required for the area reduction used. 2. Add a note to the plans clarifying the design area reduction used per 2007 NFPA 13 Figure 11.2.3.2.3.1. A 40% reduction (i.e. 900 SF remote area) is used which implies a 10 ft high ceiling height. 3. Hydraulic calculations do not appear to include the equivalent length of the flexible hose sprinkler fittings used. Please include the applicable equivalent length of 1" pipe at the sprinkler head nodes based on the hose length and size (refer to Vctaulic EasyFlex product data). 4. Include applicable product data with the permit submittal to the City of Tukwila. A resubmittal to Tuazon Enaineerina is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or eric at7tuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING, PLLC Eric P. Tuazon, PE Fire Protection Engineer C Carom Rs20031Nele200143 %Mold=Yc• WaelYtl Eps1681119.09 Mon ;FUN Mew trc FIRE SPRINKLERS, INC. 1014 NORTH STREET SUMNER, WA 98390 HYDRAULIC CALCULATIONS FOR EXPRESS #581 1070 SOUTHCENTER MALL #332 TUKWILA, WA. 98188 FILE NUMBER: 2046 DATE: AUG 20, 2008 sosenierated -DESIGN DATA - OCCUPANCY CLASSIFICATION: NFPA 13 OHG II DENSITY: .20 gpm/sq. ft. AREA OF APPLICATION: 900 sq/ft COVERAGE PER SPRINKLER: 120 sq. ft. NUMBER OF SPRINKLERS CALCULATED: 10 sprinklers TOTAL SPRINKLER WATER FLOW REQUIRED: 255.6 gpm TOTAL WATER REQUIRED (including hose): 505.6 gpm FLOW AND PRESSURE (@ CITY): 505.6 gpm @ 53.2 psi SPRINKLER ORIFICE SIZE: 1/2 inch NAME OF CONTRACTOR: FIRE SPRINKLERS INC. DESIGN/LAYOUT BY: MIKE AUTHORITY HAVING JURISDICTION: CITY OF TUKWILA CONTRACTOR CERTIFICATION NUMBER: FIRESI*988RJ SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CITY 140.0 20.0 8000.0 139.3 505 .,6 53.2 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 505.6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 255.6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) CITY 0.0 SOURCE 53.2 1 13.0 K= 5.60 27.2 lA 14.5 - - - - 29.2 1B 14.5 31.3 1C 14.5 31.5 2 11.0 K= 5.60 17.3 2A 14.5 18.2 3 11.0 K= 5.60 18.0 3A 14.5 - - - - 19.8 4 11.0 K= 5.60 23.3 4A 14.5 - - - - 25.5 5 11.0 K= 5.60 15.2 5A 14.5 - - - - 15.9 6 11.0 K= 5.60 17.2 6A 14.5 - - - - 17.7 7 11.0 K= 5.60 22.7 7A 14.5 24.7 8 11.0 K= 5.60 21.0 8A 14.5 22.4 9 11.0 K= 5.60 22.1 9A 14.5 24.3 9B 14.5 31.1 10 11.0 K= 5.60 25.9 10A 14.5 30.0 A 14.0 32.9 Al 14.5 31.7 B 14.0 33.0 B1 14.5 31.3 C 14.0 33.2 255.6 29.2 23.3 23.7 27.1 21.8 23.2 26.7 25.7 26.3 28.5 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) D 14.0 - - - - 34.6 D1 14.5 - - - - 33.5 F 14.0 - - - - 42.9 G 14.0 - - - - 46.4 H 14.0 - - - - 46.9 J 14.0 - - - - 47.0 TOR 14.0 - - - - 47.0 HDR 3.0 - - - - 51.9 UG 1.0 - - - - 52.8 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 29.2 1.049 PL 6.00 PF 2.6 1A 14.5 0.0 29.2 0.0 10.8 120 FTG 2E PE 0.6 1 13.0 5.6 27.2 29.2 0.262 TL 10.00 PV Pipe: 2 23.3 1.049 PL 10.00 PF 2.4 2A 14.5 0.0 18.2 0.0 8.7 120 FTG 2E PE 1.5 2 11.0 5.6 17.3 23.3 0.173 TL 14.00 PV Pipe: 3 23.7 1.049 PL 11.50 PF 3.3 3A 14.5 0.0 19.8 0.0 8.8 120 FTG ET PE 1.5 3 11.0 5.6 18.0 23.7 0.179 TL 18.50 PV Pipe: 4 27.1 1.049 PL 12.00 PF 3.6 4A 14.5 0.0 25.5 0.0 10.0 120 FTG 2E PE 1.5 4 11.0 5.6 23.3 27.1 0.228 TL 16.00 PV Pipe: 5 21.8 1.049 PL 7.50 PF 2.2 5A 14.5 0.0 15.9 0.0 8.1 120 FTG ET PE 1.5 5 11.0 5.6 15.2 21.8 0.153 TL 14.50 PV Pipe: 6 23.2 1.049 PL 8.00 PF 2.1 6A 14.5 0.0 17.7 0.0 8.6 120 FTG 2E PE 1.5 6 11.0 5.6 17.2 23.2 0.171 TL 12.00 PV Pipe: 7 26.7 1.049 PL 9.00 PF 3.5 7A 14.5 0.0 24.7 0.0 9.9 120 FTG ET PE 1.5 7 11.0 5.6 22.7 26.7 0.222 TL 16.00 PV Pipe: 8 25.7 1.049 PL 10.00 PF 2.9 8A 14.5 0.0 22.4 0.0 9.5 120 FTG 2E PE 1.5 8 11.0 5.6 21.0 25.7 0.207 TL 14.00 PV Pipe: 9 26.3 1.049 PL 10.00 PF 3.7 9A 14.5 0.0 24.3 0.0 9.8 120 FTG ET PE 1.5 9 11.0 5.6 22.1 26.3 0.216 TL 17.00 PV Pipe: 10 28.5 1.049 PL 13.00 PF 5.5 10A 14.5 0.0 30.0 0.0 10.6 120 FTG 2ET PE 1.5 10 11.0 5.6 25.9 28.5 0.251 TL 22.00 PV Pipe: 12 -29.2 1.049 PL 8.00 PF 2.1 1A 14.5 0.0 29.2 0.0 10.8 120 FTG ---- PE 0.0 1B 14.5 0.0 31.3 0.0 0.262 TL 8.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 13 -29.2 1.610 PL 8.00 PF 0.3 1B 14.5 0.0 31.3 0.0 4.6 120 FTG ---- PE 0.0 1C 14.5 0.0 31.5 0.0 0.033 TL 8.00 PV Pipe: 14 -29.2 2.067 PL 8.00 PF 0.2 1C 14.5 0.0 31.5 0.0 2.8 120 FTG T PE 0.0 Al 14.5 0.0 31.7 0.0 0.010 TL 18.00 PV Pipe: 14A -57.7 1.610 PL 0.50 PF 1.0 Al 14.5 0.0 31.7 0.0 9.1 120 FTG T PE 0.2 A 14.0 0.0 32.9 0.0 0.115 TL 8.50 PV Pipe: 15 -23.3 1.049 PL 9.00 PF 1.6 2A 14.5 0.0 18.2 0.0 8.7 120 FTG ---- PE 0.0 3A 14.5 0.0 19.8 0.0 0.173 TL 9.00 PV Pipe: 16 -47.1 1.049 PL 9.00 PF 5.7 3A 14.5 0.0 19.8 0.0 17.5 120 FTG ---- PE 0.0 4A 14.5 0.0 25.5 0.0 0.633 TL 9.00 PV Pipe: 17 -74.1 1.380 PL 9.00 PF 5.8 4A 14.5 0.0 25.5 0.0 15.9 120 FTG T PE 0.0 B1 14.5 0.0 31.3 0.0 0.386 TL 15.00 PV Pipe: 17A -74.1 1.610 PL 0.50 PF 1.5 B1 14.5 0.0 31.3 0.0 11.7 120 FTG T PE 0.2 B 14.0 0.0 33.0 0.0 0.182 TL 8.50 PV Pipe: 18 -21.8 1.049 PL 12.00 PF 1.8 5A 14.5 0.0 15.9 0.0 8.1 120 FTG ---- PE 0.0 6A 14.5 0.0 17.7 0.0 0.153 TL 12.00 PV Pipe: 19 -45.0 1.049 PL 12.00 PF 7.0 6A 14.5 0.0 17.7 0.0 16.7 120 FTG ---- PE 0.0 7A 14.5 0.0 24.7 0.0 0.584 TL 12.00 PV Pipe: 20 -71.7 1.049 PL 1.00 PF 8.3 7A 14.5 0.0 24.7 0.0 26.6 120 FTG T PE 0.2 C 14.0 0.0 33.2 0.0 1.381 TL 6.00 PV Pipe: 21 -25.7 1.049 PL 9.00 PF 1.9 8A 14.5 0.0 22.4 0.0 9.5 120 FTG ---- PE 0.0 9A 14.5 0.0 24.3 0.0 0.207 TL 9.00 PV Pipe: 22 -52.0 1.049 PL 9.00 PF 6.9 9A 14.5 0.0 24.3 0.0 19.3 120 FTG ---- PE 0.0 9B 14.5 0.0 31.1 0.0 0.762 TL 9.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 23 -52.0 1.380 PL 6.00 PF 2.4 9B 14.5 0.0 31.1 0.0 11.2 120 FTG T PE 0.0 D1 14.5 0.0 33.5 0.0 0.200 TL 12.00 PV Pipe: 22A -52.0 1.610 PL 0.50 PF 0.8 D1 14.5 0.0 33.5 0.0 8.2 120 FTG T PE 0.2 D 14.0 0.0 34.6 0.0 0.095 TL 8.50 PV Pipe: 26 -28.5 1.049 PL 2.00 PF 1.8 10A 14.5 0.0 30.0 0.0 10.6 120 FTG T PE 0.0 Al 14.5 0.0 31.7 0.0 0.251 TL 7.00 PV Pipe: 28 -57.7 2.469 PL 9.00 PF 0.1 A 14.0 0.0 32.9 0.0 3.9 120 FTG ---- PE 0.0 8 14.0 0.0 33.0 0.0 0.014 TL 9.00 PV Pipe: 29 -131.8 2.469 PL 3.00 PF 0.2 B 14.0 0.0 33.0 0.0 8.8 120 FTG ---- PE 0.0 C 14.0 0.0 33.2 0.0 0.066 TL 3.00 PV Pipe: 30 -203.6 2.469 PL 9.00 PF 1.3 C 14.0 0.0 33.2 0.0 13.6 120 FTG ---- PE 0.0 D 14.0 0.0 34.6 0.0 0.147 TL 9.00 PV Pipe: 31 -255.6 2.469 PL 25.00 PF 8.3 D 14.0 0.0 34.6 0.0 17.1 120 FTG 2E PE 0.0 F 14.0 0.0 42.9 0.0 0.224 TL 37.00 PV Pipe: 33 -255.6 3.068 PL 32.00 PF 3.6 F 14.0 0.0 42.9 0.0 11.1 120 FTG 2E PE 0.0 G 14.0 0.0 46.4 0.0 0.078 TL 46.00 PV Pipe: 34 -255.6 4.026 PL 2.00 PF 0.5 G 14.0 0.0 46.4 0.0 6.4 120 FTG T PE 0.0 H 14.0 0.0 46.9 0.0 0.021 TL 22.00 PV Pipe: 35 -255.6 6.065 PL 6.00 PF 0.1 H 14.0 0.0 46.9 0.0 2.8 120 FTG T PE 0.0 J 14.0 0.0 47.0 0.0 0.003 TL 36.00 PV Pipe: 36 -255.6 8.249 PL 73.00 PF 0.1 J 14.0 0.0 47.0 0.0 1.5 120 FTG L PE 0.0 TOR 14.0 0.0 47.0 0.0 0.001 TL 87.50 PV Pipe: 37 -255.6 8.249 PL 11.00 PF 0.1 TOR 14.0 0.0 47.0 0.0 1.5 120 FTG TGA PE 4.8 HDR 3.0 0.0 51.9 0.0 0.001 TL 99.90 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 38 -255.6 8.249 PL 2.00 PF 0.0 HDR 3.0 0.0 51.9 0.0 1.5 120 FTG L PE 0.9 UG 1.0 0.0 52.8 0.0 0.001 TL 16.50 PV Pipe: 39 -255.6 8.265 PL 25.00 PF 0.0 UG 1.0 0.0 52.8 0.0 1.5 140 FTG TG PE 0.4 CITY 0.0 SRCE 53.2 (N/A) 0.000 TL 83.30 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 38011601 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.105 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 26.6 ft/sec at pipe 20. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gEll Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 0.00 0.00 0.00 0.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.380 3.00 6.00 2.00 7.00 0.00 0.00 0.00 0.00 1.50 0.80 0.40 1.00 7.00 5.50 10.00 0.00 1.610 4.00 8.00 2.00 9.00 0.00 0.00 0.00 0.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 2.067 5.00 10.00 3.00 11.00 6.00 1.00 0.00 23.00 2.50 1.30 0.60 1.00 9.00 6.50 14.00 0.00 2.469 6.00 12.00 4.00 14.00 7.00 1.00 17.00 23.00 3.00 1.50 0.80 1.00 10.00 7.00 16.00 0.00 3.068 7.00 15.00 5.00 16.00 10.00 1.00 17.00 29.00 3.50 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 8/20/2008 C:\DATA\EXPRESS.SDF JOB TITLE: EXPRESS 1.80 0.90 1.00 11.00 7.50 19.00 0.00 4.026 10.00 20.00 6.00 22.00 12.00 2.00 28.00 30.00 5.00 2.50 1.30 1.00 14.00 9.00 24.00 0.00 6.065 14.00 30.00 9.00 32.00 10.00 3.00 30.00 33.00 7.00 3.50 1.80 1.00 18.00 11.00 34.00 0.00 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gEll Couplg FM90E1 FM45E1 FMTee FMRunT 8.249 20.00 38.90 14.50 50.00 13.30 4.40 45.60 0.00 10.00 5.00 2.50 1.10 24.50 14.50 43.40 0.00 PAGE: D MATERIAL: DI -52 HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v 45E11 H Q 22/Ell 11gEll 8.265 26.90 52.30 19.40 67.20 17.90 6.00 61.20 0.00 13.40 6.70 3.40 DATE: 8/20/2008 JOB TITLE: EXPRESS WATER SUPPLY ANALYSIS Avai t:+ Static: 140.00 psi Resid: 20.00 r-1 N SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 C:\DATA\EXPRESS.SDF O O O O d N 0 0 F:4 04 x w C-1) rz w - u (n �I O O CO O O N 0 0 O O N O O O O O co 0 0 N N 0 0 w O O CO 0 - O N O - O ri FLOW (GPM) RETAINER STRA OPEN WEB TRUSS TOP BEAM C CLAMP ALL THREAD ROD (LEN. PER PLAN) HANGER RING cc U w w HANGER C (NTS) C-1 5/8' CEILING FLANGE (2) TEK SCREWS 0 A. T. Rod (Length) Hanger Ring HA\CES G D 153'-8 3/8" 0/A LEASE LINE TO LEASE UNE 25'-2 3/8' 24' O" 0 G 24'-0" 24'-0' H H I P-1 10-10 GYP.02 9 1/21 1 Wn_2 A D 0. ST8211 10•_0 P-1 ADJACENT TENANT (N.LC.) 017.60. TYP. O 6A2.0E WALL 10'-0' 11 1 P-1 11 GYP BD TYP. O" GABLE WALL I lo -o -GY-. 00. 1YP. 0 Geq.E WALL HYDRAULIC REMOTE AREA d-0. 8'-6' NFP -A -1S 170/ OHG 11 AREA REDUCED PER NFPA 13 007 FIG. 11.2..2.3.1 A THIS SYSTEM DESIGNED TO ISCHARGE 0.20 G.P.N. OVER 931 SF WHEN SUPPLIED WITH WATER AT THE CITY CONN. • •� AT A RATE OF 505.6 G.P.M. AT 53.2 P.S I. Inil OUTSIDE HOSE ALLOWANCE: 250 GPM • HALLWAY "DELI M' -1°::..:..II: :.1111: Intl IIaIN """...-- 11 :t ,u..: mumw, ri T�:t1` T-101' Lip TCq C tiii 9EN / C ?- li�. I �'..i iii e:.••':-�1 EE: 12'-T 16'-6' 1 P-8 6 :. (CAE18 -<2g. 1 • FIRE SPRINKLER ROOM 0E1: ROC H H El V. 04 y 53 �'. .,L, ------,,,,_-=:: is i :: � ill lb IIII$ i A ../ P - j' 4'-4' P1 T 0 1 8'-0" I 00 P-1 111 j GYP. 60 1 1�1 .00,260060 /// ///// • /AA I/ //!/ if d////////.4061,9060616/ 12'-6" P-1 610. 80. WOMOH'S ROOM TWO -20' CROSS BAR MT -2 NE OF :TERN TO ALIGN 141H SEAN OF 8GN 800 2'-11" I 13-0" II I P-1 GYP. Bo. aL, A G 20 per/ fl. MS x LJNAA/ UNE OF SEAM TO AIGN 1MTH SEAM OE 901 BOx A ..G. r 1 1�/1.cy11 iiia/1.,, 10'-10" L1CT-1 12'-6" P-1 GYP. E0. 20' CRCSS SAN IAT -1 13'-0' b///Aa/ n //Y/AI; d/L/I//NIJY//J P iAA, 4N, /Mr 060 0 06/ ///H///////N HATCHED AREA INCICATES 3'-0" NAX. DEEP STORAGE PLATFORM 0500E, TYR, U.N.O. & REFER TO ADJACENT TENANT a 10-0' P-1 1I TYP. O G 2LE WAIL PIPING PLAN 1/8"=1'-0" 1 10'-0" 1.1 P-1 11 C1*61 TP. O GAEL WALL 64'-5 I/2' LEASED FRONTAGE (0/A LEASE LINE TO LEASE LINE) 0 0 0 SCOPE OF WORK: 1. ADD NEW PENDENT HEADS TO NEW TENENT SPACE . 2. RE -USE EXISTING LINE PIPING, USE FLEX DROPS TO NEW HEAD LOCATIONS. 3. IMPROVEMENT TO BE DESIGNED PER NFPA #13 OHG II 130 SF MAX. 4. PLAN SUBMITTAL TO AND APPROVAL BY CITY OF TUKWILA. 5. MATERIALS PER NFPA #13 STANDARDS AS SELECTED BY FSI. 6. TESTING PER NFPA #13 AND CITY OF TUKWILA. GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. 9. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. CONSTRUCTION NOTES: 1. ALL NEW PIPING TO BE DYNA FLO, SCHD 10 AND SCHD 40. 2. ALL NEW FITTINGS TO BE THREADED DUCTILE IRON AND GROOVED FITTINGS. 3. ARMOVERS LONGER THAN 2'-0" SHALL HAVE A HANGER. 4. ALL NEW LINES TO HAVE END OF LINE RESTRAINT. 5. HEADS SHOWN ARE AT CENTERLINE OF CEILING TILE. �t cr` 6: %.., NOTICU Weld stamps must be inspected before pipe is hung. Do not paint pipinc ► r�:.h prior to hydrostatic test �r Y • approval. NOTES: RE -USE EXISTING PIPING • yt' resubrrari1.T ,;',- Final test arid inspection b The Tukwila Eve Prevention Bureau. fit':t11-S.ut .. :runerrls The Tukwila Fire current city ers and :.!• tions of adopted i ii{ly for the �' siUner. drawings atter .'U rfxluire a _I L•L:`::qu°ent approval. REMOVE ALL EXISTING SPRINKLERS I Date: _g -AC" -L5-3) INSTALL NEW SPRINKLERS ON FLEX DROPS--- ALL ROPS�'�� s `7 'm� �`"� ALL NEW COVER PLATES TO BE BRUSH CHROME E3y: 'PO TA TNOT C Because of increased demand our inspectors' scho rules are booked 3-7 days ahead. Therefore, you will need to call 205-575-1407 to schedule your insp tions a minimum of 48 hours in advance of the date you Bunt an inspection. 571 PuticWtt.A FIRE DEPARTiY1FA Please call: 575-4407 and give this job No. OE S- `I33 and exac ' 'laress for shut* rIo': n er nonrovni PARCEL # - 6364200010 PERMIT#-xxxx DRAWING SYMBOLS HYDRAULIC DESIGN INFO. HANGER LEGEND HEAD LEGEND - ALARM VALVE RISER - FLOW SWTICH RISER • - . DRY PIPE RISER 0 .f1. - DELUGE/P.A. RISER FIRE DEPARTMENT CONNECTION WATER MOTOR GONG O - ELECTRIC BELL F - FLEXIBLE GROOVED COUPLING -$- RIGID GROOVED COUPLING - THREADED PIPE COUPLING - CONTROL VALVE --�- - CHECK VALVE PIPE HANGER (SEE CHART) + - PIPE HANGER (SEE CHART) ( A-1 ) - WELDED PIPE TAG 0 - BRANCHLINE NUMBER 1 9-0 PIPE SIZE & LENGTH 1 (8-10) PIPE SIZE & LENGTH(CUT) ,00 - HYDRAULIC NODE 10'-0" AFF 0'-10" BOD ELEVATION DATUM - CENTERLINE OF PIPE TO DECK ry THIS SYSTEM IS 12-1 HYDRAULICALLY DESIGNED ❑ THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED 4 U -HOOK L "L" ROD SPRINKLER TYPE MFG MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K -FAC QTY FLOW TEST STATIC RESIDUAL GPM FLOWING DATE & TIME 140 20 8000 TFD B COACH SCREW ROD N TOGGLE NUT CONCEALED RECESSED PENDENT QR TYCO RF II O 1/2" BRASS BRUSH CF 155° 5.6 100 C "C" CLAMP P HDI -P D TOP BEAM CLAMP W/ STRAP R WEDGE ANCHOR E EYE ROD S SAtAMY SIDEWINDER (SWG20). SYSTEM DESIGN F FLUSH SHELL S20 SAMMY SUPER SCREW (GST20) REMOTE AREA DENSITY MAX. AREA/HEAD K -FACTOR 900 .20 130 5.6 XX G CEILING FLANGE SX SAMMY X -PRESS H SIDE BEAM BRACKET • T TRAPEZE J "J" BOLT U UNISTRUT POST K SHORT CLIP W TOTAL THIS SHEET Fire Sprinklers Inc WA CL# FIRESI*988RJ 1014 North Street Sumner, WA 98390 (253) 826-0099 100 email:mike@firesprinklersinc.com PROJECT: Express #581 1070 Southcenter Mall #332 Tukwila, WA. 98188 CONTRACT WITH: Greenwood Const. PA1 Al Ir. 21 2008 Fire DESIGNER: Mike DATE: July 31, 2008 SCALE: As Noted HAZARD: OHS II AHJ: City of Tukwila JOB # 2046 SHEET # FP -1 /m€-'7 4 7/ t/ • •� • Inil • • •--�■ mrl. Ii■ ii. KIM ,1 I ■ I E I {� 1 • I1 l!FILI A1 ■ iUI qCj THF{E s� E \ IIUUI 11111111 11 _ 1111 `� 1 `1 �E481 1'J 1 . b rr\ ---b- __I_ 11 1K 1 I - R' li_ 1UU "v im _ r - -C8, a' ' ° a, •W • III ■ 1'■ 1131-11 . 1 ® 13 i- IJ R .. L ESI IPA - A -� • 12'-6" P-1 610. 80. WOMOH'S ROOM TWO -20' CROSS BAR MT -2 NE OF :TERN TO ALIGN 141H SEAN OF 8GN 800 2'-11" I 13-0" II I P-1 GYP. Bo. aL, A G 20 per/ fl. MS x LJNAA/ UNE OF SEAM TO AIGN 1MTH SEAM OE 901 BOx A ..G. r 1 1�/1.cy11 iiia/1.,, 10'-10" L1CT-1 12'-6" P-1 GYP. E0. 20' CRCSS SAN IAT -1 13'-0' b///Aa/ n //Y/AI; d/L/I//NIJY//J P iAA, 4N, /Mr 060 0 06/ ///H///////N HATCHED AREA INCICATES 3'-0" NAX. DEEP STORAGE PLATFORM 0500E, TYR, U.N.O. & REFER TO ADJACENT TENANT a 10-0' P-1 1I TYP. O G 2LE WAIL PIPING PLAN 1/8"=1'-0" 1 10'-0" 1.1 P-1 11 C1*61 TP. O GAEL WALL 64'-5 I/2' LEASED FRONTAGE (0/A LEASE LINE TO LEASE LINE) 0 0 0 SCOPE OF WORK: 1. ADD NEW PENDENT HEADS TO NEW TENENT SPACE . 2. RE -USE EXISTING LINE PIPING, USE FLEX DROPS TO NEW HEAD LOCATIONS. 3. IMPROVEMENT TO BE DESIGNED PER NFPA #13 OHG II 130 SF MAX. 4. PLAN SUBMITTAL TO AND APPROVAL BY CITY OF TUKWILA. 5. MATERIALS PER NFPA #13 STANDARDS AS SELECTED BY FSI. 6. TESTING PER NFPA #13 AND CITY OF TUKWILA. GENERAL NOTES: 1. ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM APPROVED. 2. PIPING DIMENSIONS ARE CENTER TO CENTER EXCEPT RISER & DIMENSIONS SHOWN THUSLY (1-6), WHICH IS END TO END. 3. EARTHQUAKE BRACING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA PAMPHLET #13. 4. PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 5. PIPING SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 6. JOINING OF PIPE AND FITTINGS, THREADED AND WELDED SHALL BE IN ACCORDANCE WITH NFPA PAMPHLET #13. 7. OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE SPRINKLER SYSTEM. 8. STRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. 9. ALL FIRE ALARMS, WIRING AND MONITORING ARE TO BE INSTALLED BY OTHERS. RESPONSIBILITY OF THE OWNER AND/OR HIS STRUCTURAL. CONSTRUCTION NOTES: 1. ALL NEW PIPING TO BE DYNA FLO, SCHD 10 AND SCHD 40. 2. ALL NEW FITTINGS TO BE THREADED DUCTILE IRON AND GROOVED FITTINGS. 3. ARMOVERS LONGER THAN 2'-0" SHALL HAVE A HANGER. 4. ALL NEW LINES TO HAVE END OF LINE RESTRAINT. 5. HEADS SHOWN ARE AT CENTERLINE OF CEILING TILE. �t cr` 6: %.., NOTICU Weld stamps must be inspected before pipe is hung. Do not paint pipinc ► r�:.h prior to hydrostatic test �r Y • approval. NOTES: RE -USE EXISTING PIPING • yt' resubrrari1.T ,;',- Final test arid inspection b The Tukwila Eve Prevention Bureau. fit':t11-S.ut .. :runerrls The Tukwila Fire current city ers and :.!• tions of adopted i ii{ly for the �' siUner. drawings atter .'U rfxluire a _I L•L:`::qu°ent approval. REMOVE ALL EXISTING SPRINKLERS I Date: _g -AC" -L5-3) INSTALL NEW SPRINKLERS ON FLEX DROPS--- ALL ROPS�'�� s `7 'm� �`"� ALL NEW COVER PLATES TO BE BRUSH CHROME E3y: 'PO TA TNOT C Because of increased demand our inspectors' scho rules are booked 3-7 days ahead. Therefore, you will need to call 205-575-1407 to schedule your insp tions a minimum of 48 hours in advance of the date you Bunt an inspection. 571 PuticWtt.A FIRE DEPARTiY1FA Please call: 575-4407 and give this job No. OE S- `I33 and exac ' 'laress for shut* rIo': n er nonrovni PARCEL # - 6364200010 PERMIT#-xxxx DRAWING SYMBOLS HYDRAULIC DESIGN INFO. HANGER LEGEND HEAD LEGEND - ALARM VALVE RISER - FLOW SWTICH RISER • - . DRY PIPE RISER 0 .f1. - DELUGE/P.A. RISER FIRE DEPARTMENT CONNECTION WATER MOTOR GONG O - ELECTRIC BELL F - FLEXIBLE GROOVED COUPLING -$- RIGID GROOVED COUPLING - THREADED PIPE COUPLING - CONTROL VALVE --�- - CHECK VALVE PIPE HANGER (SEE CHART) + - PIPE HANGER (SEE CHART) ( A-1 ) - WELDED PIPE TAG 0 - BRANCHLINE NUMBER 1 9-0 PIPE SIZE & LENGTH 1 (8-10) PIPE SIZE & LENGTH(CUT) ,00 - HYDRAULIC NODE 10'-0" AFF 0'-10" BOD ELEVATION DATUM - CENTERLINE OF PIPE TO DECK ry THIS SYSTEM IS 12-1 HYDRAULICALLY DESIGNED ❑ THIS SYSTEM IS NOT HYDRAULICALLY DESIGNED 4 U -HOOK L "L" ROD SPRINKLER TYPE MFG MODEL SYMBOL ORIFICE FINISH CANOPY TEMP K -FAC QTY FLOW TEST STATIC RESIDUAL GPM FLOWING DATE & TIME 140 20 8000 TFD B COACH SCREW ROD N TOGGLE NUT CONCEALED RECESSED PENDENT QR TYCO RF II O 1/2" BRASS BRUSH CF 155° 5.6 100 C "C" CLAMP P HDI -P D TOP BEAM CLAMP W/ STRAP R WEDGE ANCHOR E EYE ROD S SAtAMY SIDEWINDER (SWG20). SYSTEM DESIGN F FLUSH SHELL S20 SAMMY SUPER SCREW (GST20) REMOTE AREA DENSITY MAX. AREA/HEAD K -FACTOR 900 .20 130 5.6 XX G CEILING FLANGE SX SAMMY X -PRESS H SIDE BEAM BRACKET • T TRAPEZE J "J" BOLT U UNISTRUT POST K SHORT CLIP W TOTAL THIS SHEET Fire Sprinklers Inc WA CL# FIRESI*988RJ 1014 North Street Sumner, WA 98390 (253) 826-0099 100 email:mike@firesprinklersinc.com PROJECT: Express #581 1070 Southcenter Mall #332 Tukwila, WA. 98188 CONTRACT WITH: Greenwood Const. PA1 Al Ir. 21 2008 Fire DESIGNER: Mike DATE: July 31, 2008 SCALE: As Noted HAZARD: OHS II AHJ: City of Tukwila JOB # 2046 SHEET # FP -1 /m€-'7 4 7/ t/