HomeMy WebLinkAboutPP - 911 SOUTHCENTER MALL - UNKNOWN TENANT - PERMITS AND PLANS911 SOUTHCENTER MALL ASSOCIATED PERMITS 08-S-386 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: GNC 911 Southcenter Mall Permit No.: 08-S-386 Date: July 18, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/i inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. .VICE ROOM (101) ® IO' -O" A.F.F. SALES AREA (100) lALT31 o 10'-1" A.F.F. • DRYWALL SOFFIT I2' -O" AFF. P-2 R_I 5B CTIDG 'ILI\ SCALE: I/4" = I' -O" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area 3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front Total: 11 22) (TYP. OF 2) DRYWALL SOFFIT IP -21 1'-4" A.F.F. DRYWALL SOFFIT 12'-O" A.F.F. IP -21 9 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING 10 STEEL JOIST/TRUSS HANGER DETAIL - TOP CH❑RD NTS 1`. IF • X f� y3 , Q �� to ,y-�: F ' l q8 Without Commenis As Noted In Red Per The Attached Let -ter !nese plans have: ben r o visn;,ed by The Tukwila Fire Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city standards. Ac.. l;:.,21.- u to eircrs and omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer. Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a resubmittal of revised drrarvings for subsequent approval. Final acczaptt nce is :zut_,ject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 19 ' QV By: ALU V` f rrEropy • TUKWILA FIRE DEPARTMEIR Please call: 575-4407 and give this job No. OX -S- r-raot ; djress for shut. apurovm! Weld stamps must be Inspected before pipe is hung. .?o not paint piping pr;or to ("iyro taft test CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 SOUTH CENTER MALL 911 SOUTH CENTER MALL TUKWILA, WA 98188 SPACE # 3 0.8 DATE: J S DRAWN: j SCALE: //qrr x o,f JUL 1 8 2008. Tukwila Fi e f le• /MI1 --7 1.111111111:l \ I GX .g.) ' • kW( , ® 11 % i m 111111 F� • ' t GX �- 2'-61 G 11_11 H 11 ❑ — _ _ �J _ ~T E 2 i i F I Y� 1' DX .. EM2X p� 1'/� 4 w 6 i A A 131 A T-2 1141.14% RUN It - ��: T. ;I �G kii I Z-1 G T-4 ��� I ° A A A ' . I -bl' i= G l'� I EM.2XI v G EXISTING TOILET _DX DX 1 �_ �� ���yyy--- T -2 `1 _ _ �� _.__� _. - , ROOM (102) ::`� '. e o r��I■�■ _... . _ ._._._._ . N EXIST. GYP. SD. CEILING Vie,. 1 1/4 -46 1' �.. -lid TO REMAIN // �� 1;1-1.-6—_,:;„;116-. .... _.__.._ '7.—..m11111111114111111111 � .. q CX 111111E SPRINKLER HEAD IN GYP. =W ®-2'49" :H: 111111 Mill Ileo II BD. CEILING IN TOILET ROOM lb 1111 !:i..r GO to Illttl T...2 - - SPRINKLER FEAR IN ATG 1 MINN` —, �I II CEILING ABOVE TOILET — ROOM R_I 5B CTIDG 'ILI\ SCALE: I/4" = I' -O" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area 3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front Total: 11 22) (TYP. OF 2) DRYWALL SOFFIT IP -21 1'-4" A.F.F. DRYWALL SOFFIT 12'-O" A.F.F. IP -21 9 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING 10 STEEL JOIST/TRUSS HANGER DETAIL - TOP CH❑RD NTS 1`. IF • X f� y3 , Q �� to ,y-�: F ' l q8 Without Commenis As Noted In Red Per The Attached Let -ter !nese plans have: ben r o visn;,ed by The Tukwila Fire Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city standards. Ac.. l;:.,21.- u to eircrs and omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer. Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a resubmittal of revised drrarvings for subsequent approval. Final acczaptt nce is :zut_,ject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 19 ' QV By: ALU V` f rrEropy • TUKWILA FIRE DEPARTMEIR Please call: 575-4407 and give this job No. OX -S- r-raot ; djress for shut. apurovm! Weld stamps must be Inspected before pipe is hung. .?o not paint piping pr;or to ("iyro taft test CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 SOUTH CENTER MALL 911 SOUTH CENTER MALL TUKWILA, WA 98188 SPACE # 3 0.8 DATE: J S DRAWN: j SCALE: //qrr x o,f JUL 1 8 2008. Tukwila Fi e 911 SOUTHCENTER MALL ASSOCIATED PERMITS 08-S-386 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: GNC 911 Southcenter Mall Permit No.: 08-S-386 Date: July 18, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/i inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. .VICE ROOM (101) ® IO' -O" A.F.F. SALES AREA (100) lALT31 o 10'-1" A.F.F. • DRYWALL SOFFIT I2' -O" AFF. P-2 R_I 5B CTIDG 'ILI\ SCALE: I/4" = I' -O" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area 3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front Total: 11 22) (TYP. OF 2) DRYWALL SOFFIT IP -21 1'-4" A.F.F. DRYWALL SOFFIT 12'-O" A.F.F. IP -21 9 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING 10 STEEL JOIST/TRUSS HANGER DETAIL - TOP CH❑RD NTS 1`. IF • X f� y3 , Q �� to ,y-�: F ' l q8 Without Commenis As Noted In Red Per The Attached Let -ter !nese plans have: ben r o visn;,ed by The Tukwila Fire Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city standards. Ac.. l;:.,21.- u to eircrs and omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer. Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a resubmittal of revised drrarvings for subsequent approval. Final acczaptt nce is :zut_,ject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 19 ' QV By: ALU V` f rrEropy • TUKWILA FIRE DEPARTMEIR Please call: 575-4407 and give this job No. OX -S- r-raot ; djress for shut. apurovm! Weld stamps must be Inspected before pipe is hung. .?o not paint piping pr;or to ("iyro taft test CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 SOUTH CENTER MALL 911 SOUTH CENTER MALL TUKWILA, WA 98188 SPACE # 3 0.8 DATE: J S DRAWN: j SCALE: //qrr x o,f JUL 1 8 2008. Tukwila Fi e f le• /MI1 --7 1.111111111:l \ I GX .g.) ' • kW( , ® 11 % i m 111111 F� • ' t GX �- 2'-61 G 11_11 H 11 ❑ — _ _ �J _ ~T E 2 i i F I Y� 1' DX .. EM2X p� 1'/� 4 w 6 i A A 131 A T-2 1141.14% RUN It - ��: T. ;I �G kii I Z-1 G T-4 ��� I ° A A A ' . I -bl' i= G l'� I EM.2XI v G EXISTING TOILET _DX DX 1 �_ �� ���yyy--- T -2 `1 _ _ �� _.__� _. - , ROOM (102) ::`� '. e o r��I■�■ _... . _ ._._._._ . N EXIST. GYP. SD. CEILING Vie,. 1 1/4 -46 1' �.. -lid TO REMAIN // �� 1;1-1.-6—_,:;„;116-. .... _.__.._ '7.—..m11111111114111111111 � .. q CX 111111E SPRINKLER HEAD IN GYP. =W ®-2'49" :H: 111111 Mill Ileo II BD. CEILING IN TOILET ROOM lb 1111 !:i..r GO to Illttl T...2 - - SPRINKLER FEAR IN ATG 1 MINN` —, �I II CEILING ABOVE TOILET — ROOM R_I 5B CTIDG 'ILI\ SCALE: I/4" = I' -O" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area 3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front Total: 11 22) (TYP. OF 2) DRYWALL SOFFIT IP -21 1'-4" A.F.F. DRYWALL SOFFIT 12'-O" A.F.F. IP -21 9 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING 10 STEEL JOIST/TRUSS HANGER DETAIL - TOP CH❑RD NTS 1`. IF • X f� y3 , Q �� to ,y-�: F ' l q8 Without Commenis As Noted In Red Per The Attached Let -ter !nese plans have: ben r o visn;,ed by The Tukwila Fire Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city standards. Ac.. l;:.,21.- u to eircrs and omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer. Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a resubmittal of revised drrarvings for subsequent approval. Final acczaptt nce is :zut_,ject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 19 ' QV By: ALU V` f rrEropy • TUKWILA FIRE DEPARTMEIR Please call: 575-4407 and give this job No. OX -S- r-raot ; djress for shut. apurovm! Weld stamps must be Inspected before pipe is hung. .?o not paint piping pr;or to ("iyro taft test CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 SOUTH CENTER MALL 911 SOUTH CENTER MALL TUKWILA, WA 98188 SPACE # 3 0.8 DATE: J S DRAWN: j SCALE: //qrr x o,f JUL 1 8 2008. Tukwila Fi e