FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: GNC
911 Southcenter Mall
Permit No.: 08-S-386
Date: July 18, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 '/i inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
.VICE ROOM (101)
® IO' -O" A.F.F.
SALES AREA (100)
lALT31
o 10'-1" A.F.F.
•
DRYWALL SOFFIT
I2' -O" AFF. P-2
R_I
5B
CTIDG
'ILI\
SCALE: I/4" = I' -O"
Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any means
8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area
3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front
Total: 11
22) (TYP. OF 2)
DRYWALL SOFFIT
IP -21
1'-4" A.F.F.
DRYWALL SOFFIT
12'-O" A.F.F.
IP -21
9
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C -CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
PIPE SWIVEL RING
10
STEEL JOIST/TRUSS
HANGER DETAIL - TOP CH❑RD
NTS
1`.
IF
• X
f� y3 , Q �� to ,y-�:
F ' l q8
Without Commenis
As Noted In Red
Per The Attached Let -ter
!nese plans have: ben r o visn;,ed by The Tukwila Fire
Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city
standards. Ac.. l;:.,21.- u to eircrs and
omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted
stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the
adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer.
Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter
this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a
resubmittal of revised drrarvings for subsequent approval.
Final acczaptt nce is :zut_,ject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: 19 ' QV By: ALU V` f
rrEropy
•
TUKWILA FIRE DEPARTMEIR
Please call: 575-4407
and give this job
No. OX -S-
r-raot ; djress for shut.
apurovm!
Weld stamps must be
Inspected before pipe is
hung. .?o not paint piping
pr;or to ("iyro taft test
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX 12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
SOUTH CENTER MALL
911 SOUTH CENTER MALL
TUKWILA, WA 98188
SPACE # 3 0.8
DATE: J
S
DRAWN: j
SCALE: //qrr x
o,f
JUL 1 8 2008.
Tukwila Fi e
f
le•
/MI1
--7
1.111111111:l
\ I
GX
.g.)
' •
kW(
,
®
11
%
i
m
111111
F�
•
'
t
GX
�- 2'-61
G
11_11
H
11 ❑
—
_
_
�J
_
~T
E
2
i
i
F
I Y�
1'
DX
..
EM2X
p�
1'/�
4
w
6
i
A
A
131
A
T-2
1141.14%
RUN
It -
��:
T.
;I
�G
kii
I
Z-1
G
T-4
���
I
°
A
A
A
'
.
I -bl' i=
G
l'�
I
EM.2XI
v
G
EXISTING TOILET
_DX
DX
1
�_
��
���yyy---
T -2
`1
_ _
��
_.__�
_. -
,
ROOM (102)
::`�
'.
e
o
r��I■�■
_... . _
._._._._ .
N
EXIST. GYP. SD. CEILING
Vie,.
1 1/4
-46
1'
�..
-lid
TO REMAIN
//
��
1;1-1.-6—_,:;„;116-.
....
_.__.._
'7.—..m11111111114111111111
�
..
q
CX
111111E
SPRINKLER HEAD IN GYP.
=W
®-2'49" :H:
111111
Mill
Ileo
II
BD. CEILING IN TOILET
ROOM
lb
1111
!:i..r
GO to
Illttl
T...2
- -
SPRINKLER FEAR IN ATG
1
MINN`
—,
�I
II
CEILING ABOVE TOILET
—
ROOM
R_I
5B
CTIDG
'ILI\
SCALE: I/4" = I' -O"
Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any means
8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area
3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front
Total: 11
22) (TYP. OF 2)
DRYWALL SOFFIT
IP -21
1'-4" A.F.F.
DRYWALL SOFFIT
12'-O" A.F.F.
IP -21
9
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C -CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
PIPE SWIVEL RING
10
STEEL JOIST/TRUSS
HANGER DETAIL - TOP CH❑RD
NTS
1`.
IF
• X
f� y3 , Q �� to ,y-�:
F ' l q8
Without Commenis
As Noted In Red
Per The Attached Let -ter
!nese plans have: ben r o visn;,ed by The Tukwila Fire
Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city
standards. Ac.. l;:.,21.- u to eircrs and
omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted
stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the
adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer.
Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter
this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a
resubmittal of revised drrarvings for subsequent approval.
Final acczaptt nce is :zut_,ject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: 19 ' QV By: ALU V` f
rrEropy
•
TUKWILA FIRE DEPARTMEIR
Please call: 575-4407
and give this job
No. OX -S-
r-raot ; djress for shut.
apurovm!
Weld stamps must be
Inspected before pipe is
hung. .?o not paint piping
pr;or to ("iyro taft test
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX 12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
SOUTH CENTER MALL
911 SOUTH CENTER MALL
TUKWILA, WA 98188
SPACE # 3 0.8
DATE: J
S
DRAWN: j
SCALE: //qrr x
o,f
JUL 1 8 2008.
Tukwila Fi e
911 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-S-386
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: GNC
911 Southcenter Mall
Permit No.: 08-S-386
Date: July 18, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 '/i inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
.VICE ROOM (101)
® IO' -O" A.F.F.
SALES AREA (100)
lALT31
o 10'-1" A.F.F.
•
DRYWALL SOFFIT
I2' -O" AFF. P-2
R_I
5B
CTIDG
'ILI\
SCALE: I/4" = I' -O"
Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any means
8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area
3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front
Total: 11
22) (TYP. OF 2)
DRYWALL SOFFIT
IP -21
1'-4" A.F.F.
DRYWALL SOFFIT
12'-O" A.F.F.
IP -21
9
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C -CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
PIPE SWIVEL RING
10
STEEL JOIST/TRUSS
HANGER DETAIL - TOP CH❑RD
NTS
1`.
IF
• X
f� y3 , Q �� to ,y-�:
F ' l q8
Without Commenis
As Noted In Red
Per The Attached Let -ter
!nese plans have: ben r o visn;,ed by The Tukwila Fire
Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city
standards. Ac.. l;:.,21.- u to eircrs and
omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted
stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the
adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer.
Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter
this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a
resubmittal of revised drrarvings for subsequent approval.
Final acczaptt nce is :zut_,ject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: 19 ' QV By: ALU V` f
rrEropy
•
TUKWILA FIRE DEPARTMEIR
Please call: 575-4407
and give this job
No. OX -S-
r-raot ; djress for shut.
apurovm!
Weld stamps must be
Inspected before pipe is
hung. .?o not paint piping
pr;or to ("iyro taft test
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX 12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
SOUTH CENTER MALL
911 SOUTH CENTER MALL
TUKWILA, WA 98188
SPACE # 3 0.8
DATE: J
S
DRAWN: j
SCALE: //qrr x
o,f
JUL 1 8 2008.
Tukwila Fi e
f
le•
/MI1
--7
1.111111111:l
\ I
GX
.g.)
' •
kW(
,
®
11
%
i
m
111111
F�
•
'
t
GX
�- 2'-61
G
11_11
H
11 ❑
—
_
_
�J
_
~T
E
2
i
i
F
I Y�
1'
DX
..
EM2X
p�
1'/�
4
w
6
i
A
A
131
A
T-2
1141.14%
RUN
It -
��:
T.
;I
�G
kii
I
Z-1
G
T-4
���
I
°
A
A
A
'
.
I -bl' i=
G
l'�
I
EM.2XI
v
G
EXISTING TOILET
_DX
DX
1
�_
��
���yyy---
T -2
`1
_ _
��
_.__�
_. -
,
ROOM (102)
::`�
'.
e
o
r��I■�■
_... . _
._._._._ .
N
EXIST. GYP. SD. CEILING
Vie,.
1 1/4
-46
1'
�..
-lid
TO REMAIN
//
��
1;1-1.-6—_,:;„;116-.
....
_.__.._
'7.—..m11111111114111111111
�
..
q
CX
111111E
SPRINKLER HEAD IN GYP.
=W
®-2'49" :H:
111111
Mill
Ileo
II
BD. CEILING IN TOILET
ROOM
lb
1111
!:i..r
GO to
Illttl
T...2
- -
SPRINKLER FEAR IN ATG
1
MINN`
—,
�I
II
CEILING ABOVE TOILET
—
ROOM
R_I
5B
CTIDG
'ILI\
SCALE: I/4" = I' -O"
Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any means
8 - Relocate Reliable FI 155° Standard Response Heads %Z x 1/2 in the sales area
3 - Relocate G4 165° Concealed Standard Response Heads %Z x %Z in the store front
Total: 11
22) (TYP. OF 2)
DRYWALL SOFFIT
IP -21
1'-4" A.F.F.
DRYWALL SOFFIT
12'-O" A.F.F.
IP -21
9
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C -CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
PIPE SWIVEL RING
10
STEEL JOIST/TRUSS
HANGER DETAIL - TOP CH❑RD
NTS
1`.
IF
• X
f� y3 , Q �� to ,y-�:
F ' l q8
Without Commenis
As Noted In Red
Per The Attached Let -ter
!nese plans have: ben r o visn;,ed by The Tukwila Fire
Prevention sitar cju ror c:c:;,f:.,r: le.. -;-a ..P.11 cel±gent city
standards. Ac.. l;:.,21.- u to eircrs and
omissions \.'e'iY*.:h do riV: ql ':,r:z --..ri,..)latioris of adopted
stancares and i.. ir;; rn :-:.. fi:r, re:spo lsibili y for the
adequacy o` d ;si:1p, ri ..,. -•.; :1y ,......itii Fri designer.
Additions, ciaie:tohs or 14:4:sior1S I+ tnesc drawings atter
this date will Void trik , ect:;-,r;_.11Ci7: -.rtd will require a
resubmittal of revised drrarvings for subsequent approval.
Final acczaptt nce is :zut_,ject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: 19 ' QV By: ALU V` f
rrEropy
•
TUKWILA FIRE DEPARTMEIR
Please call: 575-4407
and give this job
No. OX -S-
r-raot ; djress for shut.
apurovm!
Weld stamps must be
Inspected before pipe is
hung. .?o not paint piping
pr;or to ("iyro taft test
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX 12113
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
SOUTH CENTER MALL
911 SOUTH CENTER MALL
TUKWILA, WA 98188
SPACE # 3 0.8
DATE: J
S
DRAWN: j
SCALE: //qrr x
o,f
JUL 1 8 2008.
Tukwila Fi e