HomeMy WebLinkAboutPP - 969 SOUTHCENTER MALL - SOUTHCENTER COBBLER - PERMITS AND PLANS969 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-082 10-S-072 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Shoe Cobbler 969 Southcenter Mall Permit No.: 10-S-072 Date: May 11, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direcfion per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. TRI -R1 SOUTHCENTER SHOE REPAIR FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING CALULATION FA -03 FIRE ALARM SYSTEM FLOOR PLAN TIONS, RISER TE Without Comments ❑ As Noted in Red ❑ Per The Attached Letter These plans have been reviewed by The Tukwila fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawingsyafter this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptarice is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: S a o -) By: / S 1( rt.mwttA FIRE DEPARTII'l: Please call: 575.4+110Z end give this job No. / -F 0 2)-- prosire and exact address for shut. down or restoration ej rov l ) NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWD #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM FLL 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-112" .82 SQUARE 2 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.D. .0467 .210 0.11 .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FATP FIRE ALARM CONTROL PANEL MXL SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP 1 2 ® SMOKE DETECTOR (PHOTOELECTRIC) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 0 HEAT DETECTOR (PHOTOELECTRIC) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD TRI -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP BOX VERIFY IN FIELD FIRE ALARM HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM HORN STROBE ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM FIRE ALARM STROBE ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM 0 MANUAL PULL STATION HMS -S SIEMENS 4S BOX W/ 1G RING 48" O.C. AFF TO BOTTOM FIRE ALARM HORN STROBE wP (WEATHERPROOF) AS -75 -R -WP SIEMENS WBB-R 4S BOX VERIFY W/ 2G RING IN FIELD R VP FIRE ALARM BELL (WEATHERPROOF) MBDC-10 SIEMENS WPBBS-R VERIFY IN FIELD O WATERFL❑W SWITCH N/A N/A N/A N/A O TAMPER SWITCH N/A N/A N/A N/A A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAID MAY 1 1 TUKvir!l ._ Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS Lu a 0 5/10/10 2 CCC1CC J 1 0 W co J' - J d 0) O w �O ~Z Lccw0, w g=d Z Odd 0 (1) LL ‘CALE: 1'=1/8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/10/10 BACKROUND PLAN PROVIDED BY: SOB NUMBER: 1 FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCT OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. BEND OR OTHER OBSTRUCTION BEND OR OTHER OBSTRUCTION DUCT DETECTOR-' LOCATION TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE 48- HORNISTROBE 7o01 11 WARNING. 0 0 TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE NIS COVER. ND USER SERVICEABLE PARTS INSII 111,1111.0 We FROM PRECEDING STROBE APPLIANCE OR SYNC MODULE (-) (+) () 00 STROB ,CIRCUI STROBE THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. I.--,,-- w 1 I\ —1:1:11:1:(1:1:iu •i i_ SHOP DRAWINGS , i I JD 1 II 0 el 11 1 IT-;• ----' i ig * 7 • i IA . 2 \\,. - Ascot m ! / • I ` t,T, • ' I - i '-'-' — '',:i; . m 4 ....—,,:: 2 - ,—,,---,,—, iLJU (-) (+) SPEAKERISTROBE AND STROBE WIRING SCALE:112'4 (-) TUBE OUTLET SAMPLING TUBE INLET SAMPLING TYPICAL MOUNTING FOR AD -2P DUCT DETECTOR SCALE:NONE HORN/STROBE STROBE CIRCUIT 0 WARNING. 0 0 TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE NIS COVER. NO USER SERVICEABLE PARTS 'NU/ •11011.1111011111.1l (-) (+) () (+) STROBE CIRCUIT AT LEAST SIX DUCT WIDTHS FROM BEND (-) TO NEXT APPLIANCE Cr' OR END OR LINE RESISTOR 5 24K (EOLR) Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HTR -R 1Z.H-MC-C ©15CD ZH-MC-C ©30CD IZH-MC-C @75CD ial-MC-C @95CD 1ZH-MC-C ©110CD ZR -MC ©15CD IZR-MC ©30CD 'ZR -MC ©75CD FS-DACT COMMUNICATOR 1 0.009600 0.0096 0.021 0.021 0.0875 0.131 1 0.222 0.222 0.292 0.259 0.064 0.098 0.200 0.038 0.054 Standby Current Load: Alarm Current Load: 0.0096 0.243 Amps Amps Total System Current Load: 12V0 0.0096 For 24 Hours = 1; • For 5 Minute 25% Deratirig= hows Iv& Amps 0.230 0.020 0.314 0.314 8AH 0.243 Amp -hours Amp -hours Amp -hours Amp -hours (+) 24K 1/2W NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA -Mc TEMPERATURE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) >- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL (-) » TO NEXT >) ADDRESSABLE I 1 (+) DEVICE > (+) MEL SCALE FRONT VIEW 1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 (+) WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPLTPLR RED (JACKET) *CONTACT RATINGS 4.OA 0 125YAC 4.OA 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 (-) TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NNE JUNCTION BOX --k MOUNTED ON CEILING FLEX • • JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT s'AL ;IC GROUND 1.10DEL: IRI -R -->(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE I L. oTD CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID— CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE DRY CONTACTS TO VAV FAN SHUTDOWN — PROVIDED BY MECHIELEC. —4' SQUARE DEEP BOX X WITH 1-1/2' EXTENSION \\ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE 1-(-----11TO NEXT DEVICE 00 CADDY BAR SMOKE DETECTOR -- JUNCTION BOX--\ MOUNTED ON CEILING FLEX `— SUSPENDED ILLUMINATED CEILING JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE 00 CADDY BAR SMOKE DETECTDR-- SMOKE DETECTOR MOUNTING SCALE:NONE .1E31 Ns-- SUSPENDED ILLUMINATED CEILING STUD SHEET ROCK SPEAKER STROBE OR STROBE ONLY 80" A.F.F. (Th 4S DEEP BOX W/ 1-1/2' EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 U) 0 LU LU w LU _J uJ c REV. BY: •i DESCRIPTION SHOP DRAWINGS DATE 5/10/10 2 <<<<< cc Z.0 0 w cc 0 w cc z F- LLI 0 c0 c0 _1;3 2 2Z I -U 0 CC I— W (/)1— WI n =it( < 1-1-1 cc co 11- co CO 0 0 z z 0 ‘CALE: 1 = 1 /8" DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE:5/10/1 0 BACKROUND PLAN PROVIDED BY: ii WALL MOUNTED SPEAKER STROBE FIRE MOUNTING ELEVATIONS ..1OB NUMBER: SHEET SCALE:NONE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA 02 } JI NORDSTROM macyt n 0 ❑ 0 //i.. or le ❑ ❑ ❑ n C FUTURE REI. L 0 ❑ ❑ ❑ ❑ 0 r. 41. —_- r _ms ,li � ■ ■ IT •'o 1 :1! 1 The document is diagrammatic and is intended only to show the demised premises of the project (hatched area.) It does not purport to show exact dimensions nor the final location of any mechanical. electrical, structural or architectural element. Further, the landlord reserves the right to odd, eliminate or modify any such element, as may be required from time to time. Tenant space dimensions, unless otherwise noted ore to the centerlines of tenant partitions and column grids, face of exterior walls and to the outside face of service area partitions adjacent to the tenant space (viz. corridors, closets, and stairs.) EOL—S1 0 44" 19' 8" HOME RUN TO FRCP n NORTH SOUTHCENTER SHOE REPAIR SCALE 118"=1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE THESE DEVICES. 3> FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. TENANT FIRE ALARM JUNCTION BOX (FIELD LOCATE) EXISTING CORE AND SHELL FIRE SMOKE DAMPERS RELAY TRIPS TO ACIVATE AND MONITORS PAD 3 E> TIE TO EXISTING DEVICE TIE TO CLOSES EXISTING SPEAKER STROBE 10 RELOCATE EXISTING DEVICE TIE TO EXISTING EOL REPLACE WITH 15CD SPEAKER STROBE FIELD LOCATE HVAC UNITS SMOKE MUST BE LOCATTED IN THE SAME ROOM AS THE POWER SUPPLY. REFFER TO RISER ON PAGE FA -03 FOR VOICE/SPEAKER WIRING S1-2 S1-1 2S 2S SOUTHCENTER SHOE REPAIR RISER SCALE 1/8"=1' ELECTRICAUINSTALLING CONTRACTOR SHALL RETURN ONE FULL SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved K) CO O' W co) D FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I z a DESCRIPTION SHOP DRAWINGS DATE 0 0 in 2CCCaa CC 0 W CO C+ CO 1.1� T LU rn O w �p U) 2 z Z CC CC La Z Wok Wry cc f3 VJ Z 0 0 J LL w CC (SCALE: 1'=1/8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 10/1 0 BACKROUND PLAN PROVIDED BY: ...JOB NUMBER: C SHEET FA -03 ,, LJ EXIST. ADJACENT TENANT - NO WOW TNIS AREA —� O o 0 0 0 0 0 n U .)k� e—wV 0 0 0 CORRIDOR NO WORK THIS AREA 1 EXIST. ADJACENT TENANT - NO WORK THIS AREA N 1 EXIST. CORRIDOR NO WORK THiS AREA --N REFLECTED CEILING PLAN 1/4" = 1'-0" t Design per NFPA 13, Ordinary Hazard 130 Sq. Feet Max All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart ❑ YYithouc`,(i" �menLS 1:3 Without rr10ri.;d ..:: Fzi Per The Attaoieci Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City 3':,:ndards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally With the designer. Additions, deletions or revisions to these drawingsi after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: s -11-1°BY� 1-r� SI ( RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TIIP BEAM/ C -CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING o 4 — Relocate Reliable Model F 1 Standard Response 155 ° Pendents I/2 x 1/2 o 4 — Re -cut Reliable Model Fl Standard Response 155 ° Pendents I/2 x I/2 to new ceiling height at 10'-0 8 — Total STEEL JOIST/TRUSS HANGER DETAIL NTS ' IKWHA HRE l��.F'Aid70A+ta $ Please call: 575-4407 and give this job No; _ /0 •"\r -07 and exact address for shut' iown or restoration Dro n I NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FILE COPY CROWN FiRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 &Alb f355-1 Act se(0 51 PAID MAY 5 2010 TUKWILA FIRE Shoe Cobbler 969 Southcenter Tukwila, WA 98188 DATE: '4.10 DRAWN:to SCALE: %)Lf 1 API 969 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-082 10-S-072 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Shoe Cobbler 969 Southcenter Mall Permit No.: 10-S-072 Date: May 11, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direcfion per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. TRI -R1 SOUTHCENTER SHOE REPAIR FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING CALULATION FA -03 FIRE ALARM SYSTEM FLOOR PLAN TIONS, RISER TE Without Comments ❑ As Noted in Red ❑ Per The Attached Letter These plans have been reviewed by The Tukwila fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawingsyafter this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptarice is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: S a o -) By: / S 1( rt.mwttA FIRE DEPARTII'l: Please call: 575.4+110Z end give this job No. / -F 0 2)-- prosire and exact address for shut. down or restoration ej rov l ) NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWD #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM FLL 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-112" .82 SQUARE 2 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.D. .0467 .210 0.11 .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FATP FIRE ALARM CONTROL PANEL MXL SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP 1 2 ® SMOKE DETECTOR (PHOTOELECTRIC) HFP-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 0 HEAT DETECTOR (PHOTOELECTRIC) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD TRI -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP BOX VERIFY IN FIELD FIRE ALARM HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM HORN STROBE ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM FIRE ALARM STROBE ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM 0 MANUAL PULL STATION HMS -S SIEMENS 4S BOX W/ 1G RING 48" O.C. AFF TO BOTTOM FIRE ALARM HORN STROBE wP (WEATHERPROOF) AS -75 -R -WP SIEMENS WBB-R 4S BOX VERIFY W/ 2G RING IN FIELD R VP FIRE ALARM BELL (WEATHERPROOF) MBDC-10 SIEMENS WPBBS-R VERIFY IN FIELD O WATERFL❑W SWITCH N/A N/A N/A N/A O TAMPER SWITCH N/A N/A N/A N/A A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A PAID MAY 1 1 TUKvir!l ._ Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS Lu a 0 5/10/10 2 CCC1CC J 1 0 W co J' - J d 0) O w �O ~Z Lccw0, w g=d Z Odd 0 (1) LL ‘CALE: 1'=1/8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/10/10 BACKROUND PLAN PROVIDED BY: SOB NUMBER: 1 FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCT OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. BEND OR OTHER OBSTRUCTION BEND OR OTHER OBSTRUCTION DUCT DETECTOR-' LOCATION TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE 48- HORNISTROBE 7o01 11 WARNING. 0 0 TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE NIS COVER. ND USER SERVICEABLE PARTS INSII 111,1111.0 We FROM PRECEDING STROBE APPLIANCE OR SYNC MODULE (-) (+) () 00 STROB ,CIRCUI STROBE THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. I.--,,-- w 1 I\ —1:1:11:1:(1:1:iu •i i_ SHOP DRAWINGS , i I JD 1 II 0 el 11 1 IT-;• ----' i ig * 7 • i IA . 2 \\,. - Ascot m ! / • I ` t,T, • ' I - i '-'-' — '',:i; . m 4 ....—,,:: 2 - ,—,,---,,—, iLJU (-) (+) SPEAKERISTROBE AND STROBE WIRING SCALE:112'4 (-) TUBE OUTLET SAMPLING TUBE INLET SAMPLING TYPICAL MOUNTING FOR AD -2P DUCT DETECTOR SCALE:NONE HORN/STROBE STROBE CIRCUIT 0 WARNING. 0 0 TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE NIS COVER. NO USER SERVICEABLE PARTS 'NU/ •11011.1111011111.1l (-) (+) () (+) STROBE CIRCUIT AT LEAST SIX DUCT WIDTHS FROM BEND (-) TO NEXT APPLIANCE Cr' OR END OR LINE RESISTOR 5 24K (EOLR) Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HTR -R 1Z.H-MC-C ©15CD ZH-MC-C ©30CD IZH-MC-C @75CD ial-MC-C @95CD 1ZH-MC-C ©110CD ZR -MC ©15CD IZR-MC ©30CD 'ZR -MC ©75CD FS-DACT COMMUNICATOR 1 0.009600 0.0096 0.021 0.021 0.0875 0.131 1 0.222 0.222 0.292 0.259 0.064 0.098 0.200 0.038 0.054 Standby Current Load: Alarm Current Load: 0.0096 0.243 Amps Amps Total System Current Load: 12V0 0.0096 For 24 Hours = 1; • For 5 Minute 25% Deratirig= hows Iv& Amps 0.230 0.020 0.314 0.314 8AH 0.243 Amp -hours Amp -hours Amp -hours Amp -hours (+) 24K 1/2W NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA -Mc TEMPERATURE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) >- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL (-) » TO NEXT >) ADDRESSABLE I 1 (+) DEVICE > (+) MEL SCALE FRONT VIEW 1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 (+) WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPLTPLR RED (JACKET) *CONTACT RATINGS 4.OA 0 125YAC 4.OA 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 (-) TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NNE JUNCTION BOX --k MOUNTED ON CEILING FLEX • • JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT s'AL ;IC GROUND 1.10DEL: IRI -R -->(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE I L. oTD CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID— CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE DRY CONTACTS TO VAV FAN SHUTDOWN — PROVIDED BY MECHIELEC. —4' SQUARE DEEP BOX X WITH 1-1/2' EXTENSION \\ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE 1-(-----11TO NEXT DEVICE 00 CADDY BAR SMOKE DETECTOR -- JUNCTION BOX--\ MOUNTED ON CEILING FLEX `— SUSPENDED ILLUMINATED CEILING JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE 00 CADDY BAR SMOKE DETECTDR-- SMOKE DETECTOR MOUNTING SCALE:NONE .1E31 Ns-- SUSPENDED ILLUMINATED CEILING STUD SHEET ROCK SPEAKER STROBE OR STROBE ONLY 80" A.F.F. (Th 4S DEEP BOX W/ 1-1/2' EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 U) 0 LU LU w LU _J uJ c REV. BY: •i DESCRIPTION SHOP DRAWINGS DATE 5/10/10 2 <<<<< cc Z.0 0 w cc 0 w cc z F- LLI 0 c0 c0 _1;3 2 2Z I -U 0 CC I— W (/)1— WI n =it( < 1-1-1 cc co 11- co CO 0 0 z z 0 ‘CALE: 1 = 1 /8" DRAWN BY: !ANDERSON DESIGNED BY: R.VEZZANI DATE:5/10/1 0 BACKROUND PLAN PROVIDED BY: ii WALL MOUNTED SPEAKER STROBE FIRE MOUNTING ELEVATIONS ..1OB NUMBER: SHEET SCALE:NONE Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA 02 } JI NORDSTROM macyt n 0 ❑ 0 //i.. or le ❑ ❑ ❑ n C FUTURE REI. L 0 ❑ ❑ ❑ ❑ 0 r. 41. —_- r _ms ,li � ■ ■ IT •'o 1 :1! 1 The document is diagrammatic and is intended only to show the demised premises of the project (hatched area.) It does not purport to show exact dimensions nor the final location of any mechanical. electrical, structural or architectural element. Further, the landlord reserves the right to odd, eliminate or modify any such element, as may be required from time to time. Tenant space dimensions, unless otherwise noted ore to the centerlines of tenant partitions and column grids, face of exterior walls and to the outside face of service area partitions adjacent to the tenant space (viz. corridors, closets, and stairs.) EOL—S1 0 44" 19' 8" HOME RUN TO FRCP n NORTH SOUTHCENTER SHOE REPAIR SCALE 118"=1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE THESE DEVICES. 3> FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. TENANT FIRE ALARM JUNCTION BOX (FIELD LOCATE) EXISTING CORE AND SHELL FIRE SMOKE DAMPERS RELAY TRIPS TO ACIVATE AND MONITORS PAD 3 E> TIE TO EXISTING DEVICE TIE TO CLOSES EXISTING SPEAKER STROBE 10 RELOCATE EXISTING DEVICE TIE TO EXISTING EOL REPLACE WITH 15CD SPEAKER STROBE FIELD LOCATE HVAC UNITS SMOKE MUST BE LOCATTED IN THE SAME ROOM AS THE POWER SUPPLY. REFFER TO RISER ON PAGE FA -03 FOR VOICE/SPEAKER WIRING S1-2 S1-1 2S 2S SOUTHCENTER SHOE REPAIR RISER SCALE 1/8"=1' ELECTRICAUINSTALLING CONTRACTOR SHALL RETURN ONE FULL SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved K) CO O' W co) D FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I z a DESCRIPTION SHOP DRAWINGS DATE 0 0 in 2CCCaa CC 0 W CO C+ CO 1.1� T LU rn O w �p U) 2 z Z CC CC La Z Wok Wry cc f3 VJ Z 0 0 J LL w CC (SCALE: 1'=1/8" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 10/1 0 BACKROUND PLAN PROVIDED BY: ...JOB NUMBER: C SHEET FA -03 ,, LJ EXIST. ADJACENT TENANT - NO WOW TNIS AREA —� O o 0 0 0 0 0 n U .)k� e—wV 0 0 0 CORRIDOR NO WORK THIS AREA 1 EXIST. ADJACENT TENANT - NO WORK THIS AREA N 1 EXIST. CORRIDOR NO WORK THiS AREA --N REFLECTED CEILING PLAN 1/4" = 1'-0" t Design per NFPA 13, Ordinary Hazard 130 Sq. Feet Max All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart ❑ YYithouc`,(i" �menLS 1:3 Without rr10ri.;d ..:: Fzi Per The Attaoieci Letter These pians have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City 3':,:ndards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally With the designer. Additions, deletions or revisions to these drawingsi after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: s -11-1°BY� 1-r� SI ( RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TIIP BEAM/ C -CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING o 4 — Relocate Reliable Model F 1 Standard Response 155 ° Pendents I/2 x 1/2 o 4 — Re -cut Reliable Model Fl Standard Response 155 ° Pendents I/2 x I/2 to new ceiling height at 10'-0 8 — Total STEEL JOIST/TRUSS HANGER DETAIL NTS ' IKWHA HRE l��.F'Aid70A+ta $ Please call: 575-4407 and give this job No; _ /0 •"\r -07 and exact address for shut' iown or restoration Dro n I NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FILE COPY CROWN FiRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 &Alb f355-1 Act se(0 51 PAID MAY 5 2010 TUKWILA FIRE Shoe Cobbler 969 Southcenter Tukwila, WA 98188 DATE: '4.10 DRAWN:to SCALE: %)Lf 1 API