HomeMy WebLinkAboutPP - 973 SOUTHCENTER MALL - TMOBILE - PERMITS AND PLANS973 SOUTHCENTER MALL ASSOCIATED PERMITS 09-F-115 FILE CY -MOBLE FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUM3E� SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING A\D MOUNTING FA -03 FRE ALARM SYSTEM FLOO PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLA .15: Without Comments O As Nui ed in Red Attached • Pci- ,�: ��'; �� =_ tfaCheLetter 'ese plans hay t: tic ri reviewed by The Tukwila Flre vention Bureau for conformance with current City ndards. Acceptance is subject to errors and • i'nissions which do not authorize violations of adopted .standards and ordinances. The responsibility for the adequa y of design rests <c t}liy with the designer. .A& tions, deletions or ;cvis;ails to these drawings after this dt-k- will void this acceptance and will require a resubmittal of r vised drawl ins fol subsequent approval. Final acceptance is subject to field test and Inspection by 'fhe Tukwila Fire Prevention Bureau. By: .!i\‘ mate: o -9 -061 TUKWILA FIRE DEPARTS Please call: 575-4407 and give this job rro. 4614- 1t5 and exact address for shuts a„wr► or rest,;ration approvni NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and tr.srmination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72,, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 3 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD HT< LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD ® HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING lJC FIRE ALARM HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING a C FIRE ALARM HORN STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B13 WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD O MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTION BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright 2006 by Guardian PAID C UG -a 2009 Tukwila Fire z(a3 A/50 Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 7/01/09 1 SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/01 /09 BACKROUND PLAN PROVIDED BY: ,OB NUMBER: } SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING T❑ NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE "ROM XLS CONTROL PANEL OR DREVIOUS ADDRESSABLE DEVIC O DUCT DETECTOR LOCATI❑N 1 =ND OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 GROUND 0 ro O HTRI-R OSTATUS LED 00 0 N.O. 0 COM (fl 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL O LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE{ DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1; VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING O TO NEXT ADDRESSABLE DEVICE(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR .1(+) PREVIOUS ADDRESSABLE DEVICE IN END OF LINE DEVICE (3.6K 1/4W) SUPERVISED_/ SWITCH RELAY CONTACTS (4.OA @ 125VAC) GROUND (4.OA @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. 10 el TB1 ssoeeo 123456 HCP TB2 e0 6 5 kl 4321 D 7 / A 0 0 m © © HTRI-D bTATUS LED 0 co n /NOT USED O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL wa SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 000 U a 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+1-12+2-2 NC C NO + -+ -+ -+ -+ - $ 0 LJ CEJ $ $ 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) \`-'SUPERVISED NAC -4 2 NAC -3 NAC -2 2 NAC -1 WITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP �+,. NOT USED REMOTE DEVICE LOOP!, FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 10 0 0 470 OHMS EOL WITC INPU 9 9 TS M-1 O 161400 RP80i6 I- Cr) 'OOO • SMC 0 EARTH GROUND --)(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE p TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE Nora HORN STROBE / STROBE WIRING DIAGRAM LABEL SCALE SPEAKER STROBE OR STROBE ONLY-- 80" NLY 80" A.F.F. HORN/STROBE 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS EEIL SCALE:NONE NOTE FOR ADDI110NAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTITEMPERA RE: +32' F 0' C TO 100' F (38' C) HUMIDITY: 9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR rFROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE ! DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE TO NEXT DEVICE REAR VIEW >() DATA OUT � HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCANT: > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N HORN MOUNTED SPEAKER/STROBE CEILING MOUNTED HORNISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON \ CEILINGI FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT / / / / / / / / 0 0 O 0B IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR ------- SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE rn O (-; , 1z Q«C«C Z O D EEZ C� Z J U Ff. (S.-CALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/01 /09 BACKROUND PLAN PROVIDED BY: \OB NUMBER: r SHEET FA -02 EOL—S1 19.30V -11 0 2 EX 2 15 b `STOCK ROOM i 5 2S 2S 2S SALES FLOOR; 75 C5 L: NORTH AFF 10'-6" FLAG i OTE41,S: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACT❑R, WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (REV. BY: I z Q DESCRIPTION SHOP DRAWINGS DATE 0) O T O N co co T O) wiz W �o f� "�' z z O cc F— w O U� co N.1— �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/01/09 BACKROUND PLAN PROVIDED BY: �OB NUMBER: r SHEET FA -03 l LI macys 4 LEVELS 3 '' NORDSTROM 9 3 LEVELS f , 7,,275sf 250,407sf mervyrrs 2 LEVELS 65,2370 NORTH 3 LEVELS 275,46?sf 2S 2S 2S 2S 2S 2S 75 C 15 C 15 C 30 C 15 EOL -S1 FA -BOX EX 0 BE D,I D 2I SYSTEM CALCULATIONS T MOBLE T -MOBLE FACP ADD ONS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION i Tiu DATE 0, 0 0 x 99 NORTH 3 LEVELS 275,46?sf 2S 2S 2S 2S 2S 2S 75 C 15 C 15 C 30 C 15 EOL -S1 FA -BOX EX 0 BE D,I D 2I SYSTEM CALCULATIONS BATTERY SIZING CALCULATION PROJECT: T -MOBLE Panel: XLS-V Date: July 7, 2009 CIRCUIT:S1 QTY Device Type 1 1ZH-MC-C @15CD 1 ZH-MC-C @30CD 1 0 0 ZH-MC-C @75CD f ZH-MC-C @95CD IZH-HMC-C @115CD 3 ZR -MC @15CD 0 !ZR -MC @30CD 0 ZR -MC @75CD 0 ZR-MC@110CD Notification Appliance Circuit Detail --r Wire Resistance 1.62 CURRENT TOTAL -I632.5 Alarm Current! Alarm Total i Wire Size ! Wire Length 87.50 87.5i 131.00 1 1311 222.00 , 222. 292.00 i 01 371.00 I 0 64.00 i 192 98.00 175.00 Voltage at EOL Circuit Total 0 oI 233.00 0 TOTAL mA= I 632.51 12 ; 536 Total Wire Resistance (R) (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) 1.74' 0.63; 1.10. EOL Voltage 1a30; (20.4 - E) 19.3015752 632.5 RISER DIAGRAM VOLTAGE DROP CALCULATION 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: T MOBLE T -MOBLE FACP ADD ONS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION i DATE 0, 0 0 N z Current Load: Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 IZH-MC-C @15CD 1 0.0875 0.088 HTRI-D ICP -B6 0.001600 0.0035 ZH-MC-C @30CD 1 0.098 0.098 0.005 ZH-MC-C @75CD 1 0.175 0.175 ZH-MC-C @95CD 0.233 ZH-HMC-C @115CD 0.318 ZR -MC @15CD 3 0.064 0.192 0.0731 Amps 0.106 Amps ZR -MC @30CD0.098 __.__�__..______� _.._._ ZR -MC @75CD Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @110CD HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.5825 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.5825 Amps For 5 Minutes= 0.049 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.961 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.961 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION PROJECT: T -MOBLE Panel: XLS-V Date: July 7, 2009 CIRCUIT:S1 QTY Device Type 1 1ZH-MC-C @15CD 1 ZH-MC-C @30CD 1 0 0 ZH-MC-C @75CD f ZH-MC-C @95CD IZH-HMC-C @115CD 3 ZR -MC @15CD 0 !ZR -MC @30CD 0 ZR -MC @75CD 0 ZR-MC@110CD Notification Appliance Circuit Detail --r Wire Resistance 1.62 CURRENT TOTAL -I632.5 Alarm Current! Alarm Total i Wire Size ! Wire Length 87.50 87.5i 131.00 1 1311 222.00 , 222. 292.00 i 01 371.00 I 0 64.00 i 192 98.00 175.00 Voltage at EOL Circuit Total 0 oI 233.00 0 TOTAL mA= I 632.51 12 ; 536 Total Wire Resistance (R) (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) 1.74' 0.63; 1.10. EOL Voltage 1a30; (20.4 - E) 19.3015752 632.5 RISER DIAGRAM VOLTAGE DROP CALCULATION 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 0, 0 0 N z CCCaC CO CO JCO ..I W :Lu w�WWO Ow 0 T i< s C/) I-1-1-1 0 z cc co r. T- 1 0 ©C 0 M W 1- a) >- (1) SCALE: 1 /8"=1 ' cc DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/01 /09 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: SHEET FA -04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved \ 973 SOUTHCENTER MALL ASSOCIATED PERMITS 09-F-115 FILE CY -MOBLE FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUM3E� SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING A\D MOUNTING FA -03 FRE ALARM SYSTEM FLOO PLAN FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLA .15: Without Comments O As Nui ed in Red Attached • Pci- ,�: ��'; �� =_ tfaCheLetter 'ese plans hay t: tic ri reviewed by The Tukwila Flre vention Bureau for conformance with current City ndards. Acceptance is subject to errors and • i'nissions which do not authorize violations of adopted .standards and ordinances. The responsibility for the adequa y of design rests <c t}liy with the designer. .A& tions, deletions or ;cvis;ails to these drawings after this dt-k- will void this acceptance and will require a resubmittal of r vised drawl ins fol subsequent approval. Final acceptance is subject to field test and Inspection by 'fhe Tukwila Fire Prevention Bureau. By: .!i\‘ mate: o -9 -061 TUKWILA FIRE DEPARTS Please call: 575-4407 and give this job rro. 4614- 1t5 and exact address for shuts a„wr► or rest,;ration approvni NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and tr.srmination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72,, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 3 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD HT< LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD ® HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING lJC FIRE ALARM HORN STROBE (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING a C FIRE ALARM HORN STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING B13 WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD O MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTION BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright 2006 by Guardian PAID C UG -a 2009 Tukwila Fire z(a3 A/50 Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 7/01/09 1 SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/01 /09 BACKROUND PLAN PROVIDED BY: ,OB NUMBER: } SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING T❑ NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE "ROM XLS CONTROL PANEL OR DREVIOUS ADDRESSABLE DEVIC O DUCT DETECTOR LOCATI❑N 1 =ND OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 GROUND 0 ro O HTRI-R OSTATUS LED 00 0 N.O. 0 COM (fl 0 N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL O LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE{ DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1; VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING O TO NEXT ADDRESSABLE DEVICE(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR .1(+) PREVIOUS ADDRESSABLE DEVICE IN END OF LINE DEVICE (3.6K 1/4W) SUPERVISED_/ SWITCH RELAY CONTACTS (4.OA @ 125VAC) GROUND (4.OA @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. 10 el TB1 ssoeeo 123456 HCP TB2 e0 6 5 kl 4321 D 7 / A 0 0 m © © HTRI-D bTATUS LED 0 co n /NOT USED O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL wa SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 000 U a 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+1-12+2-2 NC C NO + -+ -+ -+ -+ - $ 0 LJ CEJ $ $ 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) \`-'SUPERVISED NAC -4 2 NAC -3 NAC -2 2 NAC -1 WITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP �+,. NOT USED REMOTE DEVICE LOOP!, FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 10 0 0 470 OHMS EOL WITC INPU 9 9 TS M-1 O 161400 RP80i6 I- Cr) 'OOO • SMC 0 EARTH GROUND --)(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE p TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE Nora HORN STROBE / STROBE WIRING DIAGRAM LABEL SCALE SPEAKER STROBE OR STROBE ONLY-- 80" NLY 80" A.F.F. HORN/STROBE 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS EEIL SCALE:NONE NOTE FOR ADDI110NAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERTITEMPERA RE: +32' F 0' C TO 100' F (38' C) HUMIDITY: 9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR rFROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE ! DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE TO NEXT DEVICE REAR VIEW >() DATA OUT � HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCANT: > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION N HORN MOUNTED SPEAKER/STROBE CEILING MOUNTED HORNISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX MOUNTED ON \ CEILINGI FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT / / / / / / / / 0 0 O 0B IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR ------- SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE rn O (-; , 1z Q«C«C Z O D EEZ C� Z J U Ff. (S.-CALE: 1 /8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/01 /09 BACKROUND PLAN PROVIDED BY: \OB NUMBER: r SHEET FA -02 EOL—S1 19.30V -11 0 2 EX 2 15 b `STOCK ROOM i 5 2S 2S 2S SALES FLOOR; 75 C5 L: NORTH AFF 10'-6" FLAG i OTE41,S: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACT❑R, WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (REV. BY: I z Q DESCRIPTION SHOP DRAWINGS DATE 0) O T O N co co T O) wiz W �o f� "�' z z O cc F— w O U� co N.1— �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/01/09 BACKROUND PLAN PROVIDED BY: �OB NUMBER: r SHEET FA -03 l LI macys 4 LEVELS 3 '' NORDSTROM 9 3 LEVELS f , 7,,275sf 250,407sf mervyrrs 2 LEVELS 65,2370 NORTH 3 LEVELS 275,46?sf 2S 2S 2S 2S 2S 2S 75 C 15 C 15 C 30 C 15 EOL -S1 FA -BOX EX 0 BE D,I D 2I SYSTEM CALCULATIONS T MOBLE T -MOBLE FACP ADD ONS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION i Tiu DATE 0, 0 0 x 99 NORTH 3 LEVELS 275,46?sf 2S 2S 2S 2S 2S 2S 75 C 15 C 15 C 30 C 15 EOL -S1 FA -BOX EX 0 BE D,I D 2I SYSTEM CALCULATIONS BATTERY SIZING CALCULATION PROJECT: T -MOBLE Panel: XLS-V Date: July 7, 2009 CIRCUIT:S1 QTY Device Type 1 1ZH-MC-C @15CD 1 ZH-MC-C @30CD 1 0 0 ZH-MC-C @75CD f ZH-MC-C @95CD IZH-HMC-C @115CD 3 ZR -MC @15CD 0 !ZR -MC @30CD 0 ZR -MC @75CD 0 ZR-MC@110CD Notification Appliance Circuit Detail --r Wire Resistance 1.62 CURRENT TOTAL -I632.5 Alarm Current! Alarm Total i Wire Size ! Wire Length 87.50 87.5i 131.00 1 1311 222.00 , 222. 292.00 i 01 371.00 I 0 64.00 i 192 98.00 175.00 Voltage at EOL Circuit Total 0 oI 233.00 0 TOTAL mA= I 632.51 12 ; 536 Total Wire Resistance (R) (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) 1.74' 0.63; 1.10. EOL Voltage 1a30; (20.4 - E) 19.3015752 632.5 RISER DIAGRAM VOLTAGE DROP CALCULATION 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: T MOBLE T -MOBLE FACP ADD ONS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION i DATE 0, 0 0 N z Current Load: Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 IZH-MC-C @15CD 1 0.0875 0.088 HTRI-D ICP -B6 0.001600 0.0035 ZH-MC-C @30CD 1 0.098 0.098 0.005 ZH-MC-C @75CD 1 0.175 0.175 ZH-MC-C @95CD 0.233 ZH-HMC-C @115CD 0.318 ZR -MC @15CD 3 0.064 0.192 0.0731 Amps 0.106 Amps ZR -MC @30CD0.098 __.__�__..______� _.._._ ZR -MC @75CD Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @110CD HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.5825 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.5825 Amps For 5 Minutes= 0.049 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.961 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.961 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION PROJECT: T -MOBLE Panel: XLS-V Date: July 7, 2009 CIRCUIT:S1 QTY Device Type 1 1ZH-MC-C @15CD 1 ZH-MC-C @30CD 1 0 0 ZH-MC-C @75CD f ZH-MC-C @95CD IZH-HMC-C @115CD 3 ZR -MC @15CD 0 !ZR -MC @30CD 0 ZR -MC @75CD 0 ZR-MC@110CD Notification Appliance Circuit Detail --r Wire Resistance 1.62 CURRENT TOTAL -I632.5 Alarm Current! Alarm Total i Wire Size ! Wire Length 87.50 87.5i 131.00 1 1311 222.00 , 222. 292.00 i 01 371.00 I 0 64.00 i 192 98.00 175.00 Voltage at EOL Circuit Total 0 oI 233.00 0 TOTAL mA= I 632.51 12 ; 536 Total Wire Resistance (R) (WL*2)*(R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) 1.74' 0.63; 1.10. EOL Voltage 1a30; (20.4 - E) 19.3015752 632.5 RISER DIAGRAM VOLTAGE DROP CALCULATION 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 0, 0 0 N z CCCaC CO CO JCO ..I W :Lu w�WWO Ow 0 T i< s C/) I-1-1-1 0 z cc co r. T- 1 0 ©C 0 M W 1- a) >- (1) SCALE: 1 /8"=1 ' cc DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/01 /09 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: SHEET FA -04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved \