Loading...
HomeMy WebLinkAboutPP - 975 SOUTHCENTER MALL - SHIRTZ TO GO - PERMITS AND PLANS975 SOUTHCENTER MALL ASSOCIATED PERMITS 09-S-110 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: T Mobile 975 Southcenter Mall Permit No.: 09-S-110 Date: July 21, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. l 10'-e" A.F.F. COORDINATE WITH CASEWORK VENDOR FOR CASEWORK MOUNTED Li6HT FIXTURES REQUIREMENTS. ADJACENT TENANT INVENTORY I II I Qs I I RAMI TELECOM ROOM 13'-0" AF.F. RECESSED DISPLAY WINDOW GA5L1 SYSTEM, FOIG. PRCYIDE ELOGKIN6 PER MANUFACTURER': RECOMMENDATIONS 13'-0" AFF. CORRIDOR MALL •TOILET ROOM 13-0" HALLWAY ADJACENT TENANT COORDINATE WITH CASEWORK VENDOR FOR CASEWORK MOUNTED LIGHT FIXTURES REQUIREMENTS. i Design per NFPA 13 -130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means • 20 - Add Reliable Model FI 155°Standard Response Chrome Pendent Sprinkler Heads 1/2 x %2 • 3 - Add Reliable Model G4A 165° Standard Response Sprinkler Heads 1/2 x %2 in the store front 23 - Total START AGF -I LAYOUT - COORDINATE EXACT LOCATION TO • ACCOMMODATE LIGHT FIXTURES I. B.Q. E.Q. E.Q. 1 E. RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ❑ Without -Comments ❑ As Nit d in Red pr Per he Attached Letter These plans 11:3Y? :_::_::;cawed by The Tukwila Fire ' revention Bur^ :I .-;,torrnance with current City ,:t3ridards. Acc ubject to errors and omissions which ;_r,U,1ze violations of adopted standards and ord nat ces. The responsibility for the adequacy of design rest:, totally with the designer. Additions, defehors or revisions to these drawings after this date will void this acceptance and -will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 7 ( 0 1 Sy;Aitv-‘s rv(*it.A FIRE EiEPARI3 Please call: 575.4402 and give this job No.c ?- J IIo and exact address for shuti down or restoration avormual. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FILE COPY CO R O VV\. FIRE PROTECTION 1NCORF'ORATGD P.O. BOX 12113 . MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 1 Westfield Southcenter Mall 633 Southcenter Mall Blvd 77 s Space244&248 DATE:74? 'D DRAWN: 0 f y I _ SCALE: f�r{ 975 SOUTHCENTER MALL ASSOCIATED PERMITS 09-S-110 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: T Mobile 975 Southcenter Mall Permit No.: 09-S-110 Date: July 21, 2009 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2007 Edition. l 10'-e" A.F.F. COORDINATE WITH CASEWORK VENDOR FOR CASEWORK MOUNTED Li6HT FIXTURES REQUIREMENTS. ADJACENT TENANT INVENTORY I II I Qs I I RAMI TELECOM ROOM 13'-0" AF.F. RECESSED DISPLAY WINDOW GA5L1 SYSTEM, FOIG. PRCYIDE ELOGKIN6 PER MANUFACTURER': RECOMMENDATIONS 13'-0" AFF. CORRIDOR MALL •TOILET ROOM 13-0" HALLWAY ADJACENT TENANT COORDINATE WITH CASEWORK VENDOR FOR CASEWORK MOUNTED LIGHT FIXTURES REQUIREMENTS. i Design per NFPA 13 -130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means • 20 - Add Reliable Model FI 155°Standard Response Chrome Pendent Sprinkler Heads 1/2 x %2 • 3 - Add Reliable Model G4A 165° Standard Response Sprinkler Heads 1/2 x %2 in the store front 23 - Total START AGF -I LAYOUT - COORDINATE EXACT LOCATION TO • ACCOMMODATE LIGHT FIXTURES I. B.Q. E.Q. E.Q. 1 E. RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ❑ Without -Comments ❑ As Nit d in Red pr Per he Attached Letter These plans 11:3Y? :_::_::;cawed by The Tukwila Fire ' revention Bur^ :I .-;,torrnance with current City ,:t3ridards. Acc ubject to errors and omissions which ;_r,U,1ze violations of adopted standards and ord nat ces. The responsibility for the adequacy of design rest:, totally with the designer. Additions, defehors or revisions to these drawings after this date will void this acceptance and -will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 7 ( 0 1 Sy;Aitv-‘s rv(*it.A FIRE EiEPARI3 Please call: 575.4402 and give this job No.c ?- J IIo and exact address for shuti down or restoration avormual. NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FILE COPY CO R O VV\. FIRE PROTECTION 1NCORF'ORATGD P.O. BOX 12113 . MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 1 Westfield Southcenter Mall 633 Southcenter Mall Blvd 77 s Space244&248 DATE:74? 'D DRAWN: 0 f y I _ SCALE: f�r{