FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: T Mobile
975 Southcenter Mall
Permit No.: 09-S-110
Date: July 21, 2009
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 1/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 30 or more heads require hydrostatic test and system
isolation if necessary.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2007 Edition.
l
10'-e" A.F.F.
COORDINATE WITH
CASEWORK VENDOR FOR
CASEWORK MOUNTED Li6HT
FIXTURES REQUIREMENTS.
ADJACENT
TENANT
INVENTORY
I
II I Qs
I I RAMI
TELECOM
ROOM
13'-0" AF.F.
RECESSED DISPLAY
WINDOW GA5L1
SYSTEM, FOIG.
PRCYIDE ELOGKIN6
PER MANUFACTURER':
RECOMMENDATIONS
13'-0" AFF.
CORRIDOR
MALL
•TOILET
ROOM
13-0"
HALLWAY
ADJACENT
TENANT
COORDINATE WITH
CASEWORK VENDOR FOR
CASEWORK MOUNTED LIGHT
FIXTURES REQUIREMENTS.
i
Design per NFPA 13 -130 sq ft per sprinkler
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any means
• 20 - Add Reliable Model FI 155°Standard Response Chrome Pendent Sprinkler Heads 1/2 x %2
• 3 - Add Reliable Model G4A 165° Standard Response Sprinkler Heads 1/2 x %2 in the store front
23 - Total
START AGF -I LAYOUT -
COORDINATE EXACT
LOCATION TO •
ACCOMMODATE LIGHT
FIXTURES
I. B.Q. E.Q. E.Q. 1 E.
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C—CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
PIPE SWIVEL RING
STEEL JOIST/TRUSS
HANGER DETAIL
NTS
❑ Without -Comments
❑ As Nit d in Red
pr Per he Attached Letter
These plans 11:3Y? :_::_::;cawed by The Tukwila Fire
' revention Bur^ :I .-;,torrnance with current City
,:t3ridards. Acc ubject to errors and
omissions which ;_r,U,1ze violations of adopted
standards and ord nat ces. The responsibility for the
adequacy of design rest:, totally with the designer.
Additions, defehors or revisions to these drawings after
this date will void this acceptance and -will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and Inspection by
The Tukwila Fire Prevention Bureau.
Date: 7 ( 0 1 Sy;Aitv-‘s
rv(*it.A FIRE EiEPARI3
Please call: 575.4402
and give this job
No.c ?- J IIo
and exact address for shuti
down or restoration avormual.
NOTICE
Weld stamps must be
inspected before pipe is
hung. Do not paint piping
prior to hydrostatic test
approval.
FILE COPY
CO R O VV\.
FIRE PROTECTION
1NCORF'ORATGD
P.O. BOX 12113 .
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
1
Westfield Southcenter Mall
633 Southcenter Mall Blvd 77 s
Space244&248
DATE:74?
'D DRAWN: 0 f y I _ SCALE: f�r{
975 SOUTHCENTER MALL
ASSOCIATED PERMITS
09-S-110
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: T Mobile
975 Southcenter Mall
Permit No.: 09-S-110
Date: July 21, 2009
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 1/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 30 or more heads require hydrostatic test and system
isolation if necessary.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2007 Edition.
l
10'-e" A.F.F.
COORDINATE WITH
CASEWORK VENDOR FOR
CASEWORK MOUNTED Li6HT
FIXTURES REQUIREMENTS.
ADJACENT
TENANT
INVENTORY
I
II I Qs
I I RAMI
TELECOM
ROOM
13'-0" AF.F.
RECESSED DISPLAY
WINDOW GA5L1
SYSTEM, FOIG.
PRCYIDE ELOGKIN6
PER MANUFACTURER':
RECOMMENDATIONS
13'-0" AFF.
CORRIDOR
MALL
•TOILET
ROOM
13-0"
HALLWAY
ADJACENT
TENANT
COORDINATE WITH
CASEWORK VENDOR FOR
CASEWORK MOUNTED LIGHT
FIXTURES REQUIREMENTS.
i
Design per NFPA 13 -130 sq ft per sprinkler
All materials to be new, U.L. listed, and F.M. approved
All heads to be a minimum of 6' apart and to be unobstructed by any means
• 20 - Add Reliable Model FI 155°Standard Response Chrome Pendent Sprinkler Heads 1/2 x %2
• 3 - Add Reliable Model G4A 165° Standard Response Sprinkler Heads 1/2 x %2 in the store front
23 - Total
START AGF -I LAYOUT -
COORDINATE EXACT
LOCATION TO •
ACCOMMODATE LIGHT
FIXTURES
I. B.Q. E.Q. E.Q. 1 E.
RETAINER STRAP WHERE REQUIRED
IN SEISMIC AREAS
TOP BEAM/ C—CLAMP
WITH SET SCREW
3/8' ALL THREAD ROD
PIPE SWIVEL RING
STEEL JOIST/TRUSS
HANGER DETAIL
NTS
❑ Without -Comments
❑ As Nit d in Red
pr Per he Attached Letter
These plans 11:3Y? :_::_::;cawed by The Tukwila Fire
' revention Bur^ :I .-;,torrnance with current City
,:t3ridards. Acc ubject to errors and
omissions which ;_r,U,1ze violations of adopted
standards and ord nat ces. The responsibility for the
adequacy of design rest:, totally with the designer.
Additions, defehors or revisions to these drawings after
this date will void this acceptance and -will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and Inspection by
The Tukwila Fire Prevention Bureau.
Date: 7 ( 0 1 Sy;Aitv-‘s
rv(*it.A FIRE EiEPARI3
Please call: 575.4402
and give this job
No.c ?- J IIo
and exact address for shuti
down or restoration avormual.
NOTICE
Weld stamps must be
inspected before pipe is
hung. Do not paint piping
prior to hydrostatic test
approval.
FILE COPY
CO R O VV\.
FIRE PROTECTION
1NCORF'ORATGD
P.O. BOX 12113 .
MILL CREEK, WASHINGTON 98082-0113
PH. (425) 481-7669
1
Westfield Southcenter Mall
633 Southcenter Mall Blvd 77 s
Space244&248
DATE:74?
'D DRAWN: 0 f y I _ SCALE: f�r{