HomeMy WebLinkAboutPP - 988 SOUTHCENTER MALL - PIERCING PAGODA - PERMITS AND PLANS988 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-260 10-S-264 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: The Cool 988 Southcenter Mall Permit No.: 10-S-264 Date: December 8, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. N • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. GUARDIAN SECURITY LIFE AND PROPERTY PROTECTION Seattle • Silverdale • Bellingham MFG. THE COOL 988 Southcenter Mall, Tukwila, Washington 98188 Fire Alarm System Submittal MODEL# DESCRIPTION 1743 First Avenue South Seattle, WA 98134 Tel: 206.6226545 Fax: 206.341.9928 [FIRE ALARM DEVICES] SIEMENS HTRI-R Intelligent Interface Module, with Relay SIEMENS SET -MC -CW Multi -Candela Speaker Strobe, Ceiling Mount December 2, 2010 Ifo 114 Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 13- Add Reliable Model F1 Stander Response 155 Upright 112x1/2 Sc 0-1 e; 13— Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ❑ NNithcut ❑ As Noted in Rec.' '' Per The Attached Letter mese plans have been reviewed by The Tukwila Fire Prevention Bureau for 7onforrrr;�-:cr ::itr current City --andards. Acceptaocc- s .suojeCt to -:-tors and nissions which do not. authorize vtoiation ; of adopted .3ndards and ordinances. The responsibility tor the iequacy of design rests totally with the designer. -dditions, deletions or revisions to these drawings after nis date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject.to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /4 1//0 By: *1J tlaiIKWILA FIRE DEPARTI Al Please call: 575-4407 and give this job No. /0 kg' and exact address for shut. lown or restoration an,, -vat. CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 The Cool NorthWest 425 Southcenter Mall Tukwila Wash DATE: Q ec_ 320 DRAWN: J )t I SCALE: .109 PAID Y' , DEC - 3 2010'x TUKWILA FIRE SHEET NUM3ER SHEET TITLE FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON FA -01 SYSTEM INFORMATION FA -02 TYPICAL WIRING AND VOUNTI \G DETAILS FA -03 SYSTEM CALCULATIONS AND SI GLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX 0 �? Ji • P 1 ,e These plans have been re -vie\ :ea :...1ne Tukwila Fire Prevention Bureau for cc.iforrn 1:s :A.iti:; current City standards. Acceptanu: i:, subjecr. errors and omissions which do nmr..non ,= r., t!ons of adopted standards and ordinTanc: Mr: . ;, -,:nslbility for the adequacy of design r€_$tt: wtai ',fs!:r•, che designer. Additions, deletions c e.V!Sio,, So itse,SC drawings after this date will void this .ccepta CQ 3i :d wri! require a resubmittal of revisal drawings for 5u).bse-quent approval. Final acceptance is subject to fiela test and inspection by The Tukwila Fire Prevention Bureau. Date:/) --3-/o By: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the tect;nq. WKWILA FIRE DEPARTMEN' Please call: 575.4402 and give this job J .,1 addre :s for shut. -, ,,r r;on arn,rouaL D U LE AND CONDUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) 1 REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT ❑F ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 7-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN JUNCTION XCTION N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND macys 4 LEVELS 250, 407s f NORDSTROM 3 LEVELS 171,275sf T.L Tu SCP Tw 2r�5 iAAT t7, 1.E R S' CGGrvA Ar_w GA ?NG ANN EXST4NG ,OLLIEEE CNGCC CASUAL 1060 CC,..+:Ty vs=4:r 0 NOVA 6(65 f6E65 JCPenney SLV_JAST CT,�E W 4Cf!.3.s l BIAGO w.Fraw wREtas 3 4E6660 276,468sf YAC IN NASNI4016,: A9EPCPGY?[ 64:64016 S&46'EA: L__ THECOOL (988) >u RS 16,06,w, 0.66*, L_ PAID DEC - 3 2010 TUKWILA F,,IRE_ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS DATE 0 0 N Z co00 T CO 2z _! ,o _ O 01--(5WZz Liu i< CC <U1 88CO cc 0 U I J Z 0 cc 0 W (I) ›- 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 \OB NUMBER: SHEET WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ °'s) BACKROUND PLAN PROVIDED BY: FA -01 l 120VAC-60H1 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE: FOR MINK& SPEW:CA710NS SLE PRODUCT DOCUIENTAMN. *CONTACT RA1IHG& 4.0A 0 125VAC 4.0A 0 30VDC WE Mx TO NEXT ADDRESSABLE (+ DEVICE SMP IF LAST DEVICE - rani xi 5 CONTRDI. PANEL OR PREVIOUS ADDRESSABLE DEVICE 0 0 0 a 0 HTRI—RI ®; I 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE MOO a 0 PAD -3 OOH INPUT INPUT TROUBLE NAC1 NAG2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - em 3.6k EOL (-) (+) SPARE a FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) I I OO 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) TSM -1 0 WIRE DESIGNATION. NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHELD #18 FPIIFPIR RED (JACKET) *CONTACT RA11NGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. GROUND (-) a I 0 0 0 (+)>TO NEXT DEVICE OR (-) > STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL Pa ar 1 *sears' " - A 111:1:111:1:1 a0❑ a a STROBE ❑0J CIRCUIT SPARE c SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) ry SPEAKER I I 0 0 AtetL/•t 1:1:1:1:1117:1 0 0 0 assst- wnsara mmm I i I), a 1 (-) STROBE CIRCUIT ao❑ a� ❑ G STROBE I I I I 1 0 0 1 I I:I:1 I I:I:I& (-) 1 (-) SPEAKER CIRCUIT (+) (+) STROBE CIRCUIT SPEAKERISTROBE 0 0 STROBE CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER,ATING TEMPERATURE: +32' F (0' C) TO 100.F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR i —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW DATA IN ( ) > DATA IN (+) > > TO NEXT (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 O O TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL CO 0 C7 Z_ (1) LL J F-- uJ () LO ' LCD CD N LLJ(V Q C_n (V zt J W FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 0 N ZCO co Z O 2"O �W WZ W 2 i< cc 28 cc a_ LL F— •7(- CD — �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01 /1 0 BACKROUND PLAN PROVIDED BY: �OB NUMBER: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ J SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 0.0635 0.0635 0.064 0.000 HTR -R 1 0.009600 0.0096 0.021 0.021 0.0731 Amps 0.021 Amps E n Cur nt'L:O ndby Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C @15CD SET -MC -C @30CD SET -MC -C @75CD SET -MC -C @95CD 15 0.0875 1.313 12 0.131 1.572 0.222 1.332 1 0.292 0.292 SET -MC -C @110CD ZR -MC @15CD ZR -MC @30CD ZR -MC @75CD 0.259 8 0.064 0.512 1 0.098 0.098 0.2 0.03 Amps 5.1485 Amps Standby Current Load: 0.03 Amps For 24 Hours 0.720 Amp -hours Alarm Current Load: 5.1485 Amps For 5 Minutes= 0.432 Amp -hours 25% Derating 1.441 Amp -hours Total System Current Load: 1.441 Amp -hours Lised. AQP" PCI Notification Appliance Circuit Detail PROJECT: I THE COOL Panel: !PAD -3 POWER SUPPLY Date: December 2, 2010 Wire Resistance 2.58 1SET-MC-C @15CD 87.5 6 SET -MC -C @30CD. 131 0 ;SET -MC -C @75CD 1 SET -MC -C @95CD 0 #ZR -MC @110CD 3 ZRMC@15CD 0 ZR -MC @30CD 0 ZR -MC @75CD DEVICES= 14 2221 292 2591 350E 786 01 292 OF 64 192 980 175 .. _ 0 TOTAL mA= i 1620E 14 !Total Wire Resistance (R ) Total Device Load, Amps (1) !Voltage Drop ( E) EOL Voltage 422 • 20.47 WL*2)*(R/ft) Total Cct Load (E=I*R) 4-E) 1620 2.18 3.53 20.47 Notification Appliance Circuit Detail PROJECT: t_THE COOL 1 Panel: XLS-V Date: December 2, 2010 Wire Resistance 2.58 170.7V 70.7V 114 70.7V 1/2 0 70.7V1 DEVICES=;55 SYSTEM CALCULATIONS 1.8 3:54 0 0 TOTAL mA= iTotal Wire Resistance (R ) Total Device Load, Amps (I) !Voltage Drop (E) 1 EOL Voltage 37.81 120.36 0 0 158.161 14 1,429 19.2337851 (WL * 2 ). *.(Rift). (Total Cct Load) I(E_ I *R), .. (20.4 - E)'.,�._.�.._- 158.16 7:37 0.'16 1.17 19.23: TIE TO SHEIKH SHOES' , b IHTR-RI EXISTING DATA LOOP ( TIE TO NEAREST EXISTING s,s1 STROBE CIRCUIT ON MALL b HALLWAY TIE TO NEAREST EXISTING SPEAKER CIRCUIT ON MALL CONCOURSE S1-2 95cd V1-1 1 /4-W S1-1 15cd V1-2 1 /4-W s,s' b FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 0 N z<aa<< Zco co T Q 0 M 0 WWz co Ow W 2 cc F-- 5 2,5 co ccco LL F- oc 0 0 W W J z E5 0 z C!) z 0 1- 0 J 0 W > (1) fcCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SINGLE LINE DIAGRAM 1 SHEET FA -03 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved / l MALL C:01-1-1Oi\1 AREA --� TIE TO NEAREST EXISTING SPEAKER CIRCUIT TIE TO SHIEKH SHOES EXISTING DATA LOOP --O ATL INE OF SOFFIT s���T %-i51!O'/Ec VAP S1-2 95cd V1-1 VACANT TENANT SPACE OSE! S,S',V,V' \--FR (E) ELECTRIC._ F4NEL S1-1 1 5cd V1-1 % iE STOCK. r ROOM % I 101 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. Sb. FIRE ALARM SYSTEM PLAN TIE TO NEAREST EXISTING STROBE CIRCUIT Prorietar and Confidential, Co. ri • ht 2010 b Guardian Securit S stems, Inc. All Ri • hts Reserved rn co 0' 0 C9 cn Lu J F- F -- W 0 U) U) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 z 0 N 0 LLI Z o0 O Q� QCZ < wp (/) ›- OwZ le. w 14 (f) 2_< I J°S eC wco CC cc0)n L W r•C111 /SCALE: 3/8"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:12/01 / 10 BACKROUND PLAN PROVIDED BY: 1,08 NUMBER: SHEET //�� FA -04 II FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL WIRING AND MOUNTI\ G DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX WIRE SCHEDULE A\D CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED E(UIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN FULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD DUCT DETECTOR AD2-P WITH SIEMENS HFP-1 1 DETECTOR DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 4S DEEP BOX CEILING FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN JUNCTION O BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND macys 4 LEVELS 25Q,'4v _. NORDSTROM I I ., 3 LEVELS 171,275sf C RESSC }I�I.TY1Y}N In �r ,Jelr COOL 1CKYU 1,19 EE L �5 SLI C,OCE CABJA_ aNG COBS1Y IJDRARY *B' SOY -BASS rfig TI£ PARE TCS L✓ A`.C? h BLVD CYAN.. PNC a'" �U•1riA5 BEM Peax SM ,'?S AT I DO ac QST BUY C lE I5 CAS TMC N7 co 0\ 0 (-9 Z_ U) Lu LU c./3 LI) 6 L N LLl N Q ., CD C/) N LJ FAX (206) 628-4990 RELEASE/REVISIONS REV. BY] 0 0 0 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 0 0 r- 0 0 N 2<aaaC Z co00 T < O) Z -apmt W O O WZZ C.3 (1) t� � 1 CCLU E- Q CC 0)n LL 1- 0 IA A:4CCAST YCMCN ❑ EX,STINC JCPenney 3 LEVELS ~O AI.'atiEtS ' C 4AII-ReTY WALCENBOCES K.FIZ^41,111:55 UA IN stka.NMON ABEPCP E e.sW:4 .xBeiS 0 276,468sf Bu THE COOL (988) MARS 21SW M4 r,. 0..V.. W �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:12/01 / 10 BACKROUND PLAN PROVIDED BY: \0B NUMBER: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved SHEET 1 FA -01 120VAC-6011Z DEDICATE)) O&ER FNCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE: FOR MOTIONAL SPECIFICATKNS SEE PRODUCT DOCUUENTA1 c I. *CONTACT RATIN' 4.0A 0 125VAC 4.0A 0 30VDC FRON TIZD TO NEXT ADDRESSABLE DEVICE STIP IF LAST DEVICEs"- FROM XLS CONTROL. PANEL OR PREVIOUS ADDRESSABLE DEVICE 0 0 � CC 0 0 If HTRI-R I I 0 J 1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C—CABLE C—CABLE T 0 0 CAD L OEIM 0 PAD -3 oo NPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — -fi- 3.6k EOL 'J I= V113 0 (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (—) o❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHELD #18 FPIJFPLR RED (JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 rg T1° ®0 41 L . J 1 el I FITRI-R t GROUND O o /J 0 (+)> ID NEXT DEVICE OR ❑o 1- o 0 1 0 rg , DESCRIPTION SHOP DRAWINGS 1, . DATE O ,-`, ru n m vm xin•1.05. rir AI 0 7 $_ f i4- N N f n'II AlGOCION CCCaa ���'� � I 11:1:111:1:1' El❑ I❑EJ SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER CI= ❑o[. 0 0 I:I I:I:I I I:I:I 0 0 o 0 C rg (-) (+) (+) (-) SPEAKER CIRCUIT STROBE CIRCUIT STROBE 1 ❑1=1- 0 0 f0 Vf STROBE ❑op CIRCUIT (+) aCO❑ SPEAKER/STROBE 0 0 i SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) or -p, STROBE CIRCUIT (-) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) S S NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERATURE: +32' F 0' C TO 100' F (3S C) HUMIDITY: 9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) ),._ DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) > TO NEXT ADDRESSABLE (+) SMOKE DETECTOR WIRING DETAIL HARD LID -\ CEILING SPEAKER SUPPORT TILE BRIDGE Nc- DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX /% < 4'; 'r ems I 't JjJ ,1W WW FIr 1St I �i'.i.4�•.f- , ,''z` is, a�S.�`a..��i�s..h JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR -� SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: l 0 M 0 DMG DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 0 0 0 0 N N o CCCaa J Z o I- P 0m Q UO O ��� Q w zz 0 LSI W 2 CC OD LU CC 0)D �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 BACKROUND PLAN PROVIDED BY: .10B NUMBER: SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 0.0635 0.0635 0.064 0.000 HTR -R 0.009600 0.0096 0.021 0.021 0.0731 Amps 0.021 Amps SignaI Extender COI tiOn'" n oad! Cu Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C ©15CD 15 0.0875 1.313. SET -MC -C ©30CD 12 0.131 1.572 SET -MCC @75CD: 6. 0.222 1.332 SET -MC -C ©95CD 1 0.292 0.292 SET -MC -C ©110CD 0.259 ZR -MC ©15CD 8 0.064 0.512 ZR -MC ©30CD 0.098 0.098 ZR -MC @75CD 0.2 0.03 Amps 5.1485 Amps Standby Curr�nt Load: 0.03 Amps For 24 Hours= 0.720 Amp -hours Alarm Current Load: 5.1485 Amps For 5Mintites. 0.432 Amp -hours 25% Derating= 1.441 Amp -hours Total System Current Load: 1.441 Amp -hours 12VDC` Amp -hours 1 Notification Appliance Circuit Detail PROJECT: THE COOL Panel: 1, PAD -3 POWER SUPPLY I Date: lDecember2, 2010 'Wire Resistance 2.58 4 , 1SET-MC-C ©15CD j 87.51 3501 6 SET -MC -C ©306D . 131 786. . . 0 iSET-MC-C @75CD 2221 01 1 SET -MC -C ©95CD - 292 ' . - 292 1 , 0 1ZR-MC ©110CD 2591 01 3 ZR -MC ©15CD ' 64 - 192 0 1ZR-MC ©30CD 981 01 0 , ZR -MC @75CD ' . 175 0 DEVICES= 14 _ TOTALniA=I 16201 14 Total Wire Resistance ( R ) 1 Total Device Load, Amps (1) 'Voltage Drop ( E ) EOL Voltage • 422 20471 1620 WL * 2 )* (R/ft) 2.18 (Total Cct Load) 1.62 24-E)20.47 PROJECT: !THE COOL Panel: ,XLS-V Date:1December 2, 2010 Notification Appliance Circuit Detail 'Wire Resistance 2.58 21 170.7V 1/8 1.8 37.81 34 70.7V 114 3.54 120.36 0 I70.7V1/2 0 01 0 70.7V 1 0 0 DEVICES=155 TOTAL mA= 158.16 14 Total Wire Resistance ( R ) 1 Total Device Load, Amps (1) VoitageDrop(E)jj ) EOL Voftage 1,429 19.23378511 158.16 ( WL * 2 )* (Rift) 7.37 Cct Loaii (E= I * R) 1.171 20-.4 - 14.23 SYSTEM CALCULATIONS TIE TO NEAREST EXISTING DATA LOOP ON MALL HALLWAY TIE TO NEAREST EXISTING STROBE CIRCUIT ON MALL HALLWAY TIE TO NEAREST EXISTING SPEAKER CIRCUIT ON MALL CONCOURSE S1-2 95cd v1-1 1/4-W S1-1 15cd V1-2 1/4-W FLAG NOTES: RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I 00 M 00 M DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 00 v- ....7..., .-- (C:* 00 "....... `..,.. N N 2 <<<<< 1- 2\ 0 z co z co o -I a) < Z o Z CT) C) < EE- Owzz wz c) (1) w < cn 2 cc nZ 5)) co CC 0) D u. 0 0 >- (1) ‘C"ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 2/01 /1 0 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \J.OB NUMBER: C SHEET \ FA -03 MALL Oh1MON AREA TIE TO NEAREST EXISTING SPEAKER CIRCUIT OUTLINE OF SOFFIT 45QVE HTR -R S1-2 95cd V1-1 VACANT TENANT SPACE 100 S,S',V,v b (E) ELECTRICAL F'.4NEL D FLAG NOTES: RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. —O HTR -R) TSMI S1-1 1 5cd V1-1 (E) STQcK ROOM 101 S, S ' FIRE ALARM SYSTEM PLAN TIE TO NEAREST EXISTING DATA LOOP TIE TO NEAREST EXISTING STROBE CIRCUIT 1743 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG 0 M 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS < o 0 o 0 co 0 N N 2 ««< z cco T Q C� 0, 2z 11.1 O Qw0 "9 ( }w z z i W 2 � = cc I— Q 2 5 co W o0 2 LL 1- W CC SCALE: 3/8"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 BACKROUND PLAN PROVIDED BY: 1.0B NUMBER: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 988 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-260 10-S-264 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: The Cool 988 Southcenter Mall Permit No.: 10-S-264 Date: December 8, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. N • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. GUARDIAN SECURITY LIFE AND PROPERTY PROTECTION Seattle • Silverdale • Bellingham MFG. THE COOL 988 Southcenter Mall, Tukwila, Washington 98188 Fire Alarm System Submittal MODEL# DESCRIPTION 1743 First Avenue South Seattle, WA 98134 Tel: 206.6226545 Fax: 206.341.9928 [FIRE ALARM DEVICES] SIEMENS HTRI-R Intelligent Interface Module, with Relay SIEMENS SET -MC -CW Multi -Candela Speaker Strobe, Ceiling Mount December 2, 2010 Ifo 114 Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 13- Add Reliable Model F1 Stander Response 155 Upright 112x1/2 Sc 0-1 e; 13— Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS ❑ NNithcut ❑ As Noted in Rec.' '' Per The Attached Letter mese plans have been reviewed by The Tukwila Fire Prevention Bureau for 7onforrrr;�-:cr ::itr current City --andards. Acceptaocc- s .suojeCt to -:-tors and nissions which do not. authorize vtoiation ; of adopted .3ndards and ordinances. The responsibility tor the iequacy of design rests totally with the designer. -dditions, deletions or revisions to these drawings after nis date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject.to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /4 1//0 By: *1J tlaiIKWILA FIRE DEPARTI Al Please call: 575-4407 and give this job No. /0 kg' and exact address for shut. lown or restoration an,, -vat. CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 The Cool NorthWest 425 Southcenter Mall Tukwila Wash DATE: Q ec_ 320 DRAWN: J )t I SCALE: .109 PAID Y' , DEC - 3 2010'x TUKWILA FIRE SHEET NUM3ER SHEET TITLE FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON FA -01 SYSTEM INFORMATION FA -02 TYPICAL WIRING AND VOUNTI \G DETAILS FA -03 SYSTEM CALCULATIONS AND SI GLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX 0 �? Ji • P 1 ,e These plans have been re -vie\ :ea :...1ne Tukwila Fire Prevention Bureau for cc.iforrn 1:s :A.iti:; current City standards. Acceptanu: i:, subjecr. errors and omissions which do nmr..non ,= r., t!ons of adopted standards and ordinTanc: Mr: . ;, -,:nslbility for the adequacy of design r€_$tt: wtai ',fs!:r•, che designer. Additions, deletions c e.V!Sio,, So itse,SC drawings after this date will void this .ccepta CQ 3i :d wri! require a resubmittal of revisal drawings for 5u).bse-quent approval. Final acceptance is subject to fiela test and inspection by The Tukwila Fire Prevention Bureau. Date:/) --3-/o By: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the tect;nq. WKWILA FIRE DEPARTMEN' Please call: 575.4402 and give this job J .,1 addre :s for shut. -, ,,r r;on arn,rouaL D U LE AND CONDUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) 1 REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT ❑F ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 7-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN JUNCTION XCTION N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND macys 4 LEVELS 250, 407s f NORDSTROM 3 LEVELS 171,275sf T.L Tu SCP Tw 2r�5 iAAT t7, 1.E R S' CGGrvA Ar_w GA ?NG ANN EXST4NG ,OLLIEEE CNGCC CASUAL 1060 CC,..+:Ty vs=4:r 0 NOVA 6(65 f6E65 JCPenney SLV_JAST CT,�E W 4Cf!.3.s l BIAGO w.Fraw wREtas 3 4E6660 276,468sf YAC IN NASNI4016,: A9EPCPGY?[ 64:64016 S&46'EA: L__ THECOOL (988) >u RS 16,06,w, 0.66*, L_ PAID DEC - 3 2010 TUKWILA F,,IRE_ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS DATE 0 0 N Z co00 T CO 2z _! ,o _ O 01--(5WZz Liu i< CC <U1 88CO cc 0 U I J Z 0 cc 0 W (I) ›- 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 \OB NUMBER: SHEET WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ °'s) BACKROUND PLAN PROVIDED BY: FA -01 l 120VAC-60H1 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE: FOR MINK& SPEW:CA710NS SLE PRODUCT DOCUIENTAMN. *CONTACT RA1IHG& 4.0A 0 125VAC 4.0A 0 30VDC WE Mx TO NEXT ADDRESSABLE (+ DEVICE SMP IF LAST DEVICE - rani xi 5 CONTRDI. PANEL OR PREVIOUS ADDRESSABLE DEVICE 0 0 0 a 0 HTRI—RI ®; I 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE MOO a 0 PAD -3 OOH INPUT INPUT TROUBLE NAC1 NAG2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - em 3.6k EOL (-) (+) SPARE a FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) I I OO 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) TSM -1 0 WIRE DESIGNATION. NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHELD #18 FPIIFPIR RED (JACKET) *CONTACT RA11NGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. GROUND (-) a I 0 0 0 (+)>TO NEXT DEVICE OR (-) > STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL Pa ar 1 *sears' " - A 111:1:111:1:1 a0❑ a a STROBE ❑0J CIRCUIT SPARE c SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) ry SPEAKER I I 0 0 AtetL/•t 1:1:1:1:1117:1 0 0 0 assst- wnsara mmm I i I), a 1 (-) STROBE CIRCUIT ao❑ a� ❑ G STROBE I I I I 1 0 0 1 I I:I:1 I I:I:I& (-) 1 (-) SPEAKER CIRCUIT (+) (+) STROBE CIRCUIT SPEAKERISTROBE 0 0 STROBE CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER,ATING TEMPERATURE: +32' F (0' C) TO 100.F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR i —> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION HATH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW DATA IN ( ) > DATA IN (+) > > TO NEXT (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 O O TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL CO 0 C7 Z_ (1) LL J F-- uJ () LO ' LCD CD N LLJ(V Q C_n (V zt J W FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 0 N ZCO co Z O 2"O �W WZ W 2 i< cc 28 cc a_ LL F— •7(- CD — �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01 /1 0 BACKROUND PLAN PROVIDED BY: �OB NUMBER: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ J SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 0.0635 0.0635 0.064 0.000 HTR -R 1 0.009600 0.0096 0.021 0.021 0.0731 Amps 0.021 Amps E n Cur nt'L:O ndby Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C @15CD SET -MC -C @30CD SET -MC -C @75CD SET -MC -C @95CD 15 0.0875 1.313 12 0.131 1.572 0.222 1.332 1 0.292 0.292 SET -MC -C @110CD ZR -MC @15CD ZR -MC @30CD ZR -MC @75CD 0.259 8 0.064 0.512 1 0.098 0.098 0.2 0.03 Amps 5.1485 Amps Standby Current Load: 0.03 Amps For 24 Hours 0.720 Amp -hours Alarm Current Load: 5.1485 Amps For 5 Minutes= 0.432 Amp -hours 25% Derating 1.441 Amp -hours Total System Current Load: 1.441 Amp -hours Lised. AQP" PCI Notification Appliance Circuit Detail PROJECT: I THE COOL Panel: !PAD -3 POWER SUPPLY Date: December 2, 2010 Wire Resistance 2.58 1SET-MC-C @15CD 87.5 6 SET -MC -C @30CD. 131 0 ;SET -MC -C @75CD 1 SET -MC -C @95CD 0 #ZR -MC @110CD 3 ZRMC@15CD 0 ZR -MC @30CD 0 ZR -MC @75CD DEVICES= 14 2221 292 2591 350E 786 01 292 OF 64 192 980 175 .. _ 0 TOTAL mA= i 1620E 14 !Total Wire Resistance (R ) Total Device Load, Amps (1) !Voltage Drop ( E) EOL Voltage 422 • 20.47 WL*2)*(R/ft) Total Cct Load (E=I*R) 4-E) 1620 2.18 3.53 20.47 Notification Appliance Circuit Detail PROJECT: t_THE COOL 1 Panel: XLS-V Date: December 2, 2010 Wire Resistance 2.58 170.7V 70.7V 114 70.7V 1/2 0 70.7V1 DEVICES=;55 SYSTEM CALCULATIONS 1.8 3:54 0 0 TOTAL mA= iTotal Wire Resistance (R ) Total Device Load, Amps (I) !Voltage Drop (E) 1 EOL Voltage 37.81 120.36 0 0 158.161 14 1,429 19.2337851 (WL * 2 ). *.(Rift). (Total Cct Load) I(E_ I *R), .. (20.4 - E)'.,�._.�.._- 158.16 7:37 0.'16 1.17 19.23: TIE TO SHEIKH SHOES' , b IHTR-RI EXISTING DATA LOOP ( TIE TO NEAREST EXISTING s,s1 STROBE CIRCUIT ON MALL b HALLWAY TIE TO NEAREST EXISTING SPEAKER CIRCUIT ON MALL CONCOURSE S1-2 95cd V1-1 1 /4-W S1-1 15cd V1-2 1 /4-W s,s' b FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 0 N z<aa<< Zco co T Q 0 M 0 WWz co Ow W 2 cc F-- 5 2,5 co ccco LL F- oc 0 0 W W J z E5 0 z C!) z 0 1- 0 J 0 W > (1) fcCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SINGLE LINE DIAGRAM 1 SHEET FA -03 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved / l MALL C:01-1-1Oi\1 AREA --� TIE TO NEAREST EXISTING SPEAKER CIRCUIT TIE TO SHIEKH SHOES EXISTING DATA LOOP --O ATL INE OF SOFFIT s���T %-i51!O'/Ec VAP S1-2 95cd V1-1 VACANT TENANT SPACE OSE! S,S',V,V' \--FR (E) ELECTRIC._ F4NEL S1-1 1 5cd V1-1 % iE STOCK. r ROOM % I 101 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. Sb. FIRE ALARM SYSTEM PLAN TIE TO NEAREST EXISTING STROBE CIRCUIT Prorietar and Confidential, Co. ri • ht 2010 b Guardian Securit S stems, Inc. All Ri • hts Reserved rn co 0' 0 C9 cn Lu J F- F -- W 0 U) U) FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 z 0 N 0 LLI Z o0 O Q� QCZ < wp (/) ›- OwZ le. w 14 (f) 2_< I J°S eC wco CC cc0)n L W r•C111 /SCALE: 3/8"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:12/01 / 10 BACKROUND PLAN PROVIDED BY: 1,08 NUMBER: SHEET //�� FA -04 II FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL WIRING AND MOUNTI\ G DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX WIRE SCHEDULE A\D CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED E(UIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN FULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD DUCT DETECTOR AD2-P WITH SIEMENS HFP-1 1 DETECTOR DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 4S DEEP BOX CEILING FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN JUNCTION O BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND macys 4 LEVELS 25Q,'4v _. NORDSTROM I I ., 3 LEVELS 171,275sf C RESSC }I�I.TY1Y}N In �r ,Jelr COOL 1CKYU 1,19 EE L �5 SLI C,OCE CABJA_ aNG COBS1Y IJDRARY *B' SOY -BASS rfig TI£ PARE TCS L✓ A`.C? h BLVD CYAN.. PNC a'" �U•1riA5 BEM Peax SM ,'?S AT I DO ac QST BUY C lE I5 CAS TMC N7 co 0\ 0 (-9 Z_ U) Lu LU c./3 LI) 6 L N LLl N Q ., CD C/) N LJ FAX (206) 628-4990 RELEASE/REVISIONS REV. BY] 0 0 0 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 0 0 r- 0 0 N 2<aaaC Z co00 T < O) Z -apmt W O O WZZ C.3 (1) t� � 1 CCLU E- Q CC 0)n LL 1- 0 IA A:4CCAST YCMCN ❑ EX,STINC JCPenney 3 LEVELS ~O AI.'atiEtS ' C 4AII-ReTY WALCENBOCES K.FIZ^41,111:55 UA IN stka.NMON ABEPCP E e.sW:4 .xBeiS 0 276,468sf Bu THE COOL (988) MARS 21SW M4 r,. 0..V.. W �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:12/01 / 10 BACKROUND PLAN PROVIDED BY: \0B NUMBER: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved SHEET 1 FA -01 120VAC-6011Z DEDICATE)) O&ER FNCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE: FOR MOTIONAL SPECIFICATKNS SEE PRODUCT DOCUUENTA1 c I. *CONTACT RATIN' 4.0A 0 125VAC 4.0A 0 30VDC FRON TIZD TO NEXT ADDRESSABLE DEVICE STIP IF LAST DEVICEs"- FROM XLS CONTROL. PANEL OR PREVIOUS ADDRESSABLE DEVICE 0 0 � CC 0 0 If HTRI-R I I 0 J 1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C—CABLE C—CABLE T 0 0 CAD L OEIM 0 PAD -3 oo NPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — -fi- 3.6k EOL 'J I= V113 0 (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (—) o❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHELD #18 FPIJFPLR RED (JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 rg T1° ®0 41 L . J 1 el I FITRI-R t GROUND O o /J 0 (+)> ID NEXT DEVICE OR ❑o 1- o 0 1 0 rg , DESCRIPTION SHOP DRAWINGS 1, . DATE O ,-`, ru n m vm xin•1.05. rir AI 0 7 $_ f i4- N N f n'II AlGOCION CCCaa ���'� � I 11:1:111:1:1' El❑ I❑EJ SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER CI= ❑o[. 0 0 I:I I:I:I I I:I:I 0 0 o 0 C rg (-) (+) (+) (-) SPEAKER CIRCUIT STROBE CIRCUIT STROBE 1 ❑1=1- 0 0 f0 Vf STROBE ❑op CIRCUIT (+) aCO❑ SPEAKER/STROBE 0 0 i SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) or -p, STROBE CIRCUIT (-) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) S S NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERATURE: +32' F 0' C TO 100' F (3S C) HUMIDITY: 9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) ),._ DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) > TO NEXT ADDRESSABLE (+) SMOKE DETECTOR WIRING DETAIL HARD LID -\ CEILING SPEAKER SUPPORT TILE BRIDGE Nc- DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX /% < 4'; 'r ems I 't JjJ ,1W WW FIr 1St I �i'.i.4�•.f- , ,''z` is, a�S.�`a..��i�s..h JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR -� SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: l 0 M 0 DMG DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 0 0 0 0 N N o CCCaa J Z o I- P 0m Q UO O ��� Q w zz 0 LSI W 2 CC OD LU CC 0)D �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 BACKROUND PLAN PROVIDED BY: .10B NUMBER: SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 0.0635 0.0635 0.064 0.000 HTR -R 0.009600 0.0096 0.021 0.021 0.0731 Amps 0.021 Amps SignaI Extender COI tiOn'" n oad! Cu Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C ©15CD 15 0.0875 1.313. SET -MC -C ©30CD 12 0.131 1.572 SET -MCC @75CD: 6. 0.222 1.332 SET -MC -C ©95CD 1 0.292 0.292 SET -MC -C ©110CD 0.259 ZR -MC ©15CD 8 0.064 0.512 ZR -MC ©30CD 0.098 0.098 ZR -MC @75CD 0.2 0.03 Amps 5.1485 Amps Standby Curr�nt Load: 0.03 Amps For 24 Hours= 0.720 Amp -hours Alarm Current Load: 5.1485 Amps For 5Mintites. 0.432 Amp -hours 25% Derating= 1.441 Amp -hours Total System Current Load: 1.441 Amp -hours 12VDC` Amp -hours 1 Notification Appliance Circuit Detail PROJECT: THE COOL Panel: 1, PAD -3 POWER SUPPLY I Date: lDecember2, 2010 'Wire Resistance 2.58 4 , 1SET-MC-C ©15CD j 87.51 3501 6 SET -MC -C ©306D . 131 786. . . 0 iSET-MC-C @75CD 2221 01 1 SET -MC -C ©95CD - 292 ' . - 292 1 , 0 1ZR-MC ©110CD 2591 01 3 ZR -MC ©15CD ' 64 - 192 0 1ZR-MC ©30CD 981 01 0 , ZR -MC @75CD ' . 175 0 DEVICES= 14 _ TOTALniA=I 16201 14 Total Wire Resistance ( R ) 1 Total Device Load, Amps (1) 'Voltage Drop ( E ) EOL Voltage • 422 20471 1620 WL * 2 )* (R/ft) 2.18 (Total Cct Load) 1.62 24-E)20.47 PROJECT: !THE COOL Panel: ,XLS-V Date:1December 2, 2010 Notification Appliance Circuit Detail 'Wire Resistance 2.58 21 170.7V 1/8 1.8 37.81 34 70.7V 114 3.54 120.36 0 I70.7V1/2 0 01 0 70.7V 1 0 0 DEVICES=155 TOTAL mA= 158.16 14 Total Wire Resistance ( R ) 1 Total Device Load, Amps (1) VoitageDrop(E)jj ) EOL Voftage 1,429 19.23378511 158.16 ( WL * 2 )* (Rift) 7.37 Cct Loaii (E= I * R) 1.171 20-.4 - 14.23 SYSTEM CALCULATIONS TIE TO NEAREST EXISTING DATA LOOP ON MALL HALLWAY TIE TO NEAREST EXISTING STROBE CIRCUIT ON MALL HALLWAY TIE TO NEAREST EXISTING SPEAKER CIRCUIT ON MALL CONCOURSE S1-2 95cd v1-1 1/4-W S1-1 15cd V1-2 1/4-W FLAG NOTES: RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I 00 M 00 M DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 00 v- ....7..., .-- (C:* 00 "....... `..,.. N N 2 <<<<< 1- 2\ 0 z co z co o -I a) < Z o Z CT) C) < EE- Owzz wz c) (1) w < cn 2 cc nZ 5)) co CC 0) D u. 0 0 >- (1) ‘C"ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 1 2/01 /1 0 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \J.OB NUMBER: C SHEET \ FA -03 MALL Oh1MON AREA TIE TO NEAREST EXISTING SPEAKER CIRCUIT OUTLINE OF SOFFIT 45QVE HTR -R S1-2 95cd V1-1 VACANT TENANT SPACE 100 S,S',V,v b (E) ELECTRICAL F'.4NEL D FLAG NOTES: RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. —O HTR -R) TSMI S1-1 1 5cd V1-1 (E) STQcK ROOM 101 S, S ' FIRE ALARM SYSTEM PLAN TIE TO NEAREST EXISTING DATA LOOP TIE TO NEAREST EXISTING STROBE CIRCUIT 1743 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG 0 M 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS < o 0 o 0 co 0 N N 2 ««< z cco T Q C� 0, 2z 11.1 O Qw0 "9 ( }w z z i W 2 � = cc I— Q 2 5 co W o0 2 LL 1- W CC SCALE: 3/8"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 12/01/10 BACKROUND PLAN PROVIDED BY: 1.0B NUMBER: Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04