Loading...
HomeMy WebLinkAboutPP - 992 SOUTHCENTER MALL - TMOBILE SOLUTIONS - PERMITS AND PLANS992 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-108 11-S-099 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Rialto Jewelers 992 Southcenter Mall Permit No.: 11-S-099 Date: May 11, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)971-8718 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. WAIA, ..-.._v....._ 30 _are ACL ALTO TC1,/L E RS SPKINKLEk: PLAY VIEW SCALE 5- 1 10 r ❑ Without Comments ❑ As Noted in Red g Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted andards and ordinances. The responsibility for the ;adequacy of design rests totally with the designer. Additions, deletions or revisions to these.drawings after this date will void this acceptance and will require a • resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 5" I 1" 1 ( By: HEN) LEDGEN D NEW TYCO . TY 32 31- '1? k ;-'. 6 PEIVQE,YT - MIR/156 E.EX 15T1//6 TY 3.2 3.1 h k'c, 6 PEND T .ak 8R455.. yESIGNEP TO 0RD//fAM. Y f-1-AA/z19 NFA -I3C7O/a) AND THE C 17'Y OF P./f/ILA CROW/t/ FIRE 15 A -0/M- C ) NEW hf&A-P5 11SI/I6- EXIT17'o 1''- D4oP5, NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. TUKWILA FIRE DEPARTMENT Please ca!! 205-575-4407 and gi-, this Fire Permit No. //-S-o99 and exact address for shut- down hutdown or restoration approval. KEY PLAN 5OUTHCElVTfR NIA LL IVO SC AY. .. • T D CROWN FIRE PROTECTION INCORPORATED. P.O. BOX 12113. MIU. CREEK, WASHINGTON 98082-0113 PH. (425) 481-7869 `RCIA"k0 c\)-)6-e-fS qq2 he-2vA-\-er Yna\\;=AW/-1.2' 7-dkvao cA818(S DATE i -5 mot, DRAWN! rnr PAID MAY -62011 TUKWILA FIRE SCALE: ' r:� �a`�� %Z I-. 3 II fr VI V � r EX I T 1116- 5 PR I!Y L R UW AN r I AD5 E i I CROWN r OR. FEiVOF/�'' ®GING 2 NEW . cEIL,IN -S �. - EXITING- T-13At, /71 I'�wa q l 'rte ' -r l i i t 7 • i -t ..v_a.r...wyea+aeweos.+ _ .. • �+-+�m�c:.. - .. .. _. -. .. ..-.._v....._ 30 _are ACL ALTO TC1,/L E RS SPKINKLEk: PLAY VIEW SCALE 5- 1 10 r ❑ Without Comments ❑ As Noted in Red g Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted andards and ordinances. The responsibility for the ;adequacy of design rests totally with the designer. Additions, deletions or revisions to these.drawings after this date will void this acceptance and will require a • resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 5" I 1" 1 ( By: HEN) LEDGEN D NEW TYCO . TY 32 31- '1? k ;-'. 6 PEIVQE,YT - MIR/156 E.EX 15T1//6 TY 3.2 3.1 h k'c, 6 PEND T .ak 8R455.. yESIGNEP TO 0RD//fAM. Y f-1-AA/z19 NFA -I3C7O/a) AND THE C 17'Y OF P./f/ILA CROW/t/ FIRE 15 A -0/M- C ) NEW hf&A-P5 11SI/I6- EXIT17'o 1''- D4oP5, NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. TUKWILA FIRE DEPARTMENT Please ca!! 205-575-4407 and gi-, this Fire Permit No. //-S-o99 and exact address for shut- down hutdown or restoration approval. KEY PLAN 5OUTHCElVTfR NIA LL IVO SC AY. .. • T D CROWN FIRE PROTECTION INCORPORATED. P.O. BOX 12113. MIU. CREEK, WASHINGTON 98082-0113 PH. (425) 481-7869 `RCIA"k0 c\)-)6-e-fS qq2 he-2vA-\-er Yna\\;=AW/-1.2' 7-dkvao cA818(S DATE i -5 mot, DRAWN! rnr PAID MAY -62011 TUKWILA FIRE SCALE: ' r:� �a`�� %Z FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3E SHEET TITLE FA -01 SYSTEIV I\ FOR V1ATIO FA -02 TYPICAL WI RING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX 12( Without Comments o As Noted in Red o Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City �ndards. Acceptance is subject to errors and r..rtissions which do not authorize violations of adopted :..undards and ordinances. The responsibility for the r1 quaiy of design riz tr totally vlit cite designer. dations, deletior+ : r .: i i:; s tP these drawings after ()is date will void thL .'copi ice and will require a ?submittal of revised Oi tv ngs for subsequent approval. - nal acceptance is subject to field test and inspection by 1�e Tukwila Fire Prevention Bureau. )ate: 5-),0-11 By: 5'I NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing, TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and !'ii'M't No. and exact address for shut- down hutdown or restoration approval. EDULE AND CONDUIT FILL CHAT - WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN • TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1.- NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD "DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED )N ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 1 1 2 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT DETECTOR D AD2-P W/ SIEMENS HFP-1 1 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD HTR R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD 8 FIRE ALARM HORN STROBE ZH-MC-CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A - N/A N/A BLUE AS BUILT NOTES TO CAD N/A - N/A N/A N/A SYMBOLS LEGEND maty 4 LEVELS G 3 LEVELS 171.275sf 5 Ni s I f urzm.sr vD EkISING JCPenney 3 LEWIS 276,468sf PAID MAY 18 2011 TUKWILA FIRE _IKy70.20 ?o'T RELEASE/REVISIONS REV. BY: DMG DESCRIPTION I SHOP DRAWINGS DATE ''- -Z- '8 0 (f)ZZ ccs) T-- T p: <z -� 0 W 1w� WWW= v cn Er LL M IZ I- Z 0 0 Z W ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 05/10/1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FA -01J 12010.0-60H2 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. PUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NO1E FOR AD DONAI. SPECIFICATIONS SEE PRODUCT DO0AENTA110N. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC ifteltE FRDN TO NEXT ADDRESSABLE M (+ DEVICE STIP IF LAST DEVICE FRD 4 XLS CIROL PAWL (µ DR PREVIOUS ADDRESSABLE DEVICE Q 0 HTRI—R I ®' 1 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C—CABLE C—CABLE 111 E=r PAD -3 oo° INPUT INPUT TROUBLE MCI NAC2 NAC3 NAC4 AUX +1— 1 2+2— 2 NC C NO + — + — + — + — + — 00 3.6k EOL (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (—) 0❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WWf iH SHELD #18 FPIJFPIR RED {JACKED *CONTACT RATING& 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 0 L' J HTRI—R 114 E -I GROUND O o (+)) TO NEXT DEVICE OR ❑= ❑ I Li o/----- ❑ I , VI it 0 O 0 v �i'' C�' Vi 7 A ! n 7 8/114i .- ACCOEf$X .1 - \ +- . n'n AtCCE►CM r ..bel � v CCU .),j Lo/' C 0❑ (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV .�. FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL SPEAKER J 0 0 c STROBE Q DEDDJ CIRCUIT Q�p SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER IC OR FIRE ALARM CONTROL PANEL < (+) (+) 0 o 0 +aErE- I 1 (-) STROBE CIRCUIT STROBE 0❑ 1 ❑IJ CSI ICJ ° =I IDC V 0 ,�I ❑ 1 — O I , 0 O 0 v �i'' iE vur WEM Fai 25x Vi 7 A ! n 7 8/114i .- ACCOEf$X .1 - hIICCIII:I:I' j +— ARCCEtItiy�1N ..bel tins v CCU .),j Lo/' (-) (-) (+) (+) ❑EJ STROBE SPEAKERISTROBE O❑ ❑0 1 I vI — 1 I 1 O 0 iE vur WEM Fai 25x Vi 7 8/114i j +— ARCCEtItiy�1N ..bel tins v C (-) STROBE ❑c i) CIRCUIT (-) SPEAR CIRCUIT CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (+) v (+) S TO NEXT SPEAKER n OR END OR LINE RESISTOR S 24K (EOLR) 5 TO NEXT APPLIANCE S OR 24K (EOLR) (-) (-) Y (-) SPEAKER CIRCUIT NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TING TEPERATURE: +32' FF (0' C) TOM 00 F (36 C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —\ FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (—) >- r.)... DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN MEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR SMOKDB -11E STANDARD DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —� CEILING SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT f _H0 O O 0 1 TO NEXT DEVICE CADDY BAR of SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL CO 0' 0 C.� z_ (I) LU J UJ (1) 6 w LTJ C/) Ir) CT 0' CO (V 0 CV x Q TEL. (206) 622-6545 RELEASE/REVISIONS (.6 J 0 O —J U �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:05/10/1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA- (�02 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ k'd l 14" t?I!N `fi gyro -}y v M1',,;„dJ YI r ffi M "M� ° r'I•,+,,,w slbi Ym h .d"':p,h! ) ,tl 4 'tp")'� £ .fF�rr tY�li Y. l.n,¢ %.5 ,MF F+ PI�F4,h ,,,rw,M:'»:' p q, dd 44'�, i'if YA �1„JSFu i`;,,.d;dv'N ffiW,9 '�A Y'4i P u V �� � f €, I� "r ",# ^' ffi�'#1','!�4 �'CI'°..:y y�a�lj. �"�,� N 4V �': .�, 'x �,tw ,, 'k,.' t a• . r, roy ��i, w"`94' „: 1NM '"�gVL✓rl 'W „1 ';" .£,t1 s: W ,Myr / yyI y, � d"*WM F N}ti.. 40 0 Wire Resistance Date: May 10, 2011 0 0 #� ', ,r '' ^„ k{, ", .', ;ffi,: "S .t •� +. „, Current Load: 'x.t.i..r, p' ,,.,':r+'' "' 'I,,!�Y..,I,,r; i, k,, r,'"..•„x y „3' %�?.', � Standby: Alarm: „ ' � 7 yr„ ar,.,.,:J�.. lk ,i, ��� a'rt E, 'x°", '.$,,> w' l6 ,;,� e. .b,., - 1'qa � � � � Y1,k e t n, ^F I �i ryh ,F j, : },,�' y, �. ,b i, �+ 3 jj,i % d�pyr:3�,. r iQyL i V� �^' �� . �,; �, i u°4a! Ln.. e a�,��,.Y;t::c;aw' �..4rr rcta'�ue:�4•e '�`r''r... : a., ., er:..,r M' r a �;a i t ., ^'"" M � �x,� �4, �, Q°Y, ;,4: 7 t° - + �,_.. rr,�..., . ., .,� ,. "J, J• . ,_,tl r,{r.,, � 87 131 222 292 Device Type e Qty Qty Amps Total Amps Total ZH-MC W @110CD ZR -MC ©15CD ZR -MC @30CD 75i -MC ©75CD- HFP-11 . ._ .�_..o, 0 __....,..__.. a 1 0.0022: , . 0.0022 .: 0.0023 0.002 AD2-P 0 a DEVICES= 1 1 0.0635 0.0635 0.064 0.064 14 HTR -R 213 1. 0.009600 .. ' :' : 0.0096 0.021 0.021 ZH-MC-C @30CD (Rift) ft) ` o CcLoad 2 . 0.2G 0.131 0.262 ZH-MC-C @75CD 24 - E) 0.222 23.71 ZH-MC-C @95CD r 0.0731 Amps 0.085 Amps J ffiW t C C .,I, T. . I rMam,", ,. , ? ,...,,, M, 7 t ! iYY r d S FIA J f „9 N wt F 7 x -m .AW':.IX £ F i t J C ? 1 P $ m .ru .. ,.,, d o .\tl ., V^: •, n 4 , ^' 'Y ° y' '•r RIALTO JEWELERS 2.5.8 � i X p PAD -3 POWER SUPPLY DATE 0 Wire Resistance Date: May 10, 2011 0 0 #� ', ,r '' ^„ k{, ", .', ;ffi,: "S .t •� +. „, f ., '4 'b, \, `' 'x.t.i..r, p' ,,.,':r+'' "' 'I,,!�Y..,I,,r; i, k,, r,'"..•„x y „3' %�?.', � .. „ ' � 7 yr„ ar,.,.,:J�.. lk ,i, ��� a'rt E, 'x°", '.$,,> w' l6 ,;,� e. .b,., - 1'qa � � � � Y1,k e t n, ^F I �i ryh ,F j, : },,�' y, �. ,b i, �+ 3 jj,i % d�pyr:3�,. r iQyL i V� �^' �� . �,; �, i u°4a! Ln.. e a�,��,.Y;t::c;aw' �..4rr rcta'�ue:�4•e '�`r''r... : a., ., er:..,r M' r a �;a i t ., ^'"" M � �x,� �4, �, Q°Y, ;,4: 7 t° - + �,_.. rr,�..., . ., .,� ,. "J, J• . ,_,tl r,{r.,, � 87 131 222 292 Device Type Qty Amps Total Amps Total ZH-MC W @110CD ZR -MC ©15CD ZR -MC @30CD 75i -MC ©75CD- 259 ._ .�_..o, 0 __....,..__.. a _ Main System Board 0 a DEVICES= 1 0.03 0.03 0.030 0.030 2 2 6 14 71H -MC -C a©15CD 213 23.71 _:.0.087.. 262 R l) ZH-MC-C @30CD (Rift) ft) ` o CcLoad 2 . 0.2G 0.131 0.262 ZH-MC-C @75CD 24 - E) 0.222 23.71 ZH-MC-C @95CD 0.292 ZH-MC-W ©110CD 0.259 ZR -MC @15CD 0.064 ZR -MC ©30CD = 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.292 Amps Standby Current Load: 0.03 Amps^ For 24 Hours-” 0.720 Amp -hours Alarm Current Load: 0:292 Amps For 5 Minute s-= ° 0.025 Amp -hours 25% Derating= 0.931 Amp -hours Total System Current Load: 0.931 Amp -hours e r,!k ! & �a ', ':"{t y!C'rp, 5, r! # M .vv4www #..-. aj1aM& '4' //F��► 5514;999 � p -h iiYll�r4W`!'I"�6 'SYI H SYSTEM CALCULATIONS TIE TO NEAREST EXISTING STROBE CIRCUIT TIE TO NEAREST EXISTING DATA LOOP 2C b c — 2C,S BPS 120VAC, DEDICATED ) (BY OTHERS) 2C,S EOL S1 S1-1 S1-2 30cd 30cd FLAG NOTES: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Notification Appliance Circuit Detail PROJECT: RIALTO JEWELERS 2.5.8 SHOP DRAWINGS Panel: PAD -3 POWER SUPPLY DATE 0 Wire Resistance Date: May 10, 2011 0 0 w. av, iT���l.�v� ,i'.,4'a yy JI „., �, ry»e „r y 2 0 0 ,�,'„V,v.M e mf b 'i l,. :G ,"n.:!$� w':",:,.�. " , ,�. : :, J I” p N 4 r.✓', i.' r r f r u, @ .� �L... Z -I -MC -C @15CD ZH-MC-C @3QCD ZH-MC-C @75CD ZH-MC-C ©95CD F�r�� "1, �v ,,, ,,,. .v,�l . :. .,,:. x, �YF,�r 3 ,, Y P Y ', ■ SL ! �, u�S :. ,., 'n�t� r # r, .,' �'; ; 1 y p4^ eF,,,. .,r .r, tt" %. �Y� to � p F � 262 0._ 0 p ffi � { v� � V _„w u � 7 yr„ ar,.,.,:J�.. lk ,i, ��� a'rt E, 'x°", '.$,,> w' l6 ,;,� e. .b,., - 1'qa � � � � Y1,k e t n, ^F I �i ryh ,F j, : },,�' y, �. ,b i, �+ 3 jj,i % d�pyr:3�,. r iQyL i V� �^' �� . �,; �, i u°4a! Ln.. e a�,��,.Y;t::c;aw' �..4rr rcta'�ue:�4•e '�`r''r... : a., ., er:..,r M' r a �;a i t ., ^'"" M � �x,� �4, �, Q°Y, ;,4: 7 t° - + �,_.. rr,�..., . ., .,� ,. "J, J• . ,_,tl r,{r.,, � 87 131 222 292 ZH-MC W @110CD ZR -MC ©15CD ZR -MC @30CD 75i -MC ©75CD- 259 ._ .�_..o, 0 __....,..__.. a _ 0 a DEVICES= � 1?5 12 Total Wire Resistance Total Devic Load,Amps TOTAL mA= A 2 2 6 14 213 23.71 262 R l) (Rift) ft) ` o CcLoad . 0.2G Voltage Drop (E)(E=I*R)0.29 EOL Voltage 24 - E) 23.71 SYSTEM CALCULATIONS TIE TO NEAREST EXISTING STROBE CIRCUIT TIE TO NEAREST EXISTING DATA LOOP 2C b c — 2C,S BPS 120VAC, DEDICATED ) (BY OTHERS) 2C,S EOL S1 S1-1 S1-2 30cd 30cd FLAG NOTES: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 0 0 0 2CCCCC C 0 w z W �z co J WCC oz d - J o�0 .U) W <w° z W< Ws < co (..),,c) 0 W �= Ira CC D W C!) "GALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 05/1 0/ 1 1 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved .OB NUMBER: 1- SHEET '' FA -03 } 4i� f jRJALTO JEwELEP$ SPACE 432 1 1 1 t 11 1 f 1 !1 f �G � ; ' r(''` 1 1 !LLa�E 1 1 1 E G DESCRIPTION ,l1'' ,,. J+ft ; ' 51 9" i ( 1 ! 1 61 t Vin, ' DATE • a ♦ w ♦ > ,• a♦ r ♦ a f •• as a♦• r•+aa,= a a ••ra• aaa•a•.••_a>•••ar>•.•••sa--a••r i •r}{•Y«• :.•tt00th• • •ii♦ rt a+,..a♦l •ii •••a•• • a • is •tas•a.i•.i •• a,t•af a••••♦a at•Y•♦ i•.••,:•♦♦••at •.•a••a•• ••••••••a••••• .•..a1.... .. ♦. aa•..a.• ha ♦ nF•a , a ' ar' `.• r> :' • a, **VS. a1. ,l, • a V ~ •••_ .•♦»« a'� ' . 1.a '• ' ia•t♦+ ♦.k}•aw:• •t a,•aa, 1 •••'• • #�,.Xit,kRa .4+a aslaafara }t } . • w • • a i , • » 11444411, • • a X • ♦ i i.• •.• !ia, .....4 a1. a 1 aa ,• _ :• •X1 as .a •�0•14.0410.4.41,04,444, a, Y • « r t ♦ i ♦ •• a a ; r 1 a := a.a, 'f411 � �`:'ww aaa y.. ••••MllIllIll •t•,•:•a•' ♦2a: •": 4•! •4.••• • ta}#f • r 1 . • • ! + • i f t a t ♦ • t a a a, `1•t 1 = 1 1 II. AREST •s*�. '- �1/ ' T TO EXISTI � E CIRCUIT 0 EST EXISTING LOOP _ : 992 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-108 11-S-099 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Rialto Jewelers 992 Southcenter Mall Permit No.: 11-S-099 Date: May 11, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)971-8718 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. WAIA, ..-.._v....._ 30 _are ACL ALTO TC1,/L E RS SPKINKLEk: PLAY VIEW SCALE 5- 1 10 r ❑ Without Comments ❑ As Noted in Red g Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted andards and ordinances. The responsibility for the ;adequacy of design rests totally with the designer. Additions, deletions or revisions to these.drawings after this date will void this acceptance and will require a • resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 5" I 1" 1 ( By: HEN) LEDGEN D NEW TYCO . TY 32 31- '1? k ;-'. 6 PEIVQE,YT - MIR/156 E.EX 15T1//6 TY 3.2 3.1 h k'c, 6 PEND T .ak 8R455.. yESIGNEP TO 0RD//fAM. Y f-1-AA/z19 NFA -I3C7O/a) AND THE C 17'Y OF P./f/ILA CROW/t/ FIRE 15 A -0/M- C ) NEW hf&A-P5 11SI/I6- EXIT17'o 1''- D4oP5, NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. TUKWILA FIRE DEPARTMENT Please ca!! 205-575-4407 and gi-, this Fire Permit No. //-S-o99 and exact address for shut- down hutdown or restoration approval. KEY PLAN 5OUTHCElVTfR NIA LL IVO SC AY. .. • T D CROWN FIRE PROTECTION INCORPORATED. P.O. BOX 12113. MIU. CREEK, WASHINGTON 98082-0113 PH. (425) 481-7869 `RCIA"k0 c\)-)6-e-fS qq2 he-2vA-\-er Yna\\;=AW/-1.2' 7-dkvao cA818(S DATE i -5 mot, DRAWN! rnr PAID MAY -62011 TUKWILA FIRE SCALE: ' r:� �a`�� %Z I-. 3 II fr VI V � r EX I T 1116- 5 PR I!Y L R UW AN r I AD5 E i I CROWN r OR. FEiVOF/�'' ®GING 2 NEW . cEIL,IN -S �. - EXITING- T-13At, /71 I'�wa q l 'rte ' -r l i i t 7 • i -t ..v_a.r...wyea+aeweos.+ _ .. • �+-+�m�c:.. - .. .. _. -. .. ..-.._v....._ 30 _are ACL ALTO TC1,/L E RS SPKINKLEk: PLAY VIEW SCALE 5- 1 10 r ❑ Without Comments ❑ As Noted in Red g Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted andards and ordinances. The responsibility for the ;adequacy of design rests totally with the designer. Additions, deletions or revisions to these.drawings after this date will void this acceptance and will require a • resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 5" I 1" 1 ( By: HEN) LEDGEN D NEW TYCO . TY 32 31- '1? k ;-'. 6 PEIVQE,YT - MIR/156 E.EX 15T1//6 TY 3.2 3.1 h k'c, 6 PEND T .ak 8R455.. yESIGNEP TO 0RD//fAM. Y f-1-AA/z19 NFA -I3C7O/a) AND THE C 17'Y OF P./f/ILA CROW/t/ FIRE 15 A -0/M- C ) NEW hf&A-P5 11SI/I6- EXIT17'o 1''- D4oP5, NOTICE Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. TUKWILA FIRE DEPARTMENT Please ca!! 205-575-4407 and gi-, this Fire Permit No. //-S-o99 and exact address for shut- down hutdown or restoration approval. KEY PLAN 5OUTHCElVTfR NIA LL IVO SC AY. .. • T D CROWN FIRE PROTECTION INCORPORATED. P.O. BOX 12113. MIU. CREEK, WASHINGTON 98082-0113 PH. (425) 481-7869 `RCIA"k0 c\)-)6-e-fS qq2 he-2vA-\-er Yna\\;=AW/-1.2' 7-dkvao cA818(S DATE i -5 mot, DRAWN! rnr PAID MAY -62011 TUKWILA FIRE SCALE: ' r:� �a`�� %Z FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3E SHEET TITLE FA -01 SYSTEIV I\ FOR V1ATIO FA -02 TYPICAL WI RING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX 12( Without Comments o As Noted in Red o Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City �ndards. Acceptance is subject to errors and r..rtissions which do not authorize violations of adopted :..undards and ordinances. The responsibility for the r1 quaiy of design riz tr totally vlit cite designer. dations, deletior+ : r .: i i:; s tP these drawings after ()is date will void thL .'copi ice and will require a ?submittal of revised Oi tv ngs for subsequent approval. - nal acceptance is subject to field test and inspection by 1�e Tukwila Fire Prevention Bureau. )ate: 5-),0-11 By: 5'I NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing, TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and !'ii'M't No. and exact address for shut- down hutdown or restoration approval. EDULE AND CONDUIT FILL CHAT - WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN • TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1.- NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD "DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED )N ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 1 1 2 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT DETECTOR D AD2-P W/ SIEMENS HFP-1 1 DET. DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD HTR R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD 8 FIRE ALARM HORN STROBE ZH-MC-CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A - N/A N/A BLUE AS BUILT NOTES TO CAD N/A - N/A N/A N/A SYMBOLS LEGEND maty 4 LEVELS G 3 LEVELS 171.275sf 5 Ni s I f urzm.sr vD EkISING JCPenney 3 LEWIS 276,468sf PAID MAY 18 2011 TUKWILA FIRE _IKy70.20 ?o'T RELEASE/REVISIONS REV. BY: DMG DESCRIPTION I SHOP DRAWINGS DATE ''- -Z- '8 0 (f)ZZ ccs) T-- T p: <z -� 0 W 1w� WWW= v cn Er LL M IZ I- Z 0 0 Z W ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 05/10/1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FA -01J 12010.0-60H2 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. PUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NO1E FOR AD DONAI. SPECIFICATIONS SEE PRODUCT DO0AENTA110N. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC ifteltE FRDN TO NEXT ADDRESSABLE M (+ DEVICE STIP IF LAST DEVICE FRD 4 XLS CIROL PAWL (µ DR PREVIOUS ADDRESSABLE DEVICE Q 0 HTRI—R I ®' 1 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C—CABLE C—CABLE 111 E=r PAD -3 oo° INPUT INPUT TROUBLE MCI NAC2 NAC3 NAC4 AUX +1— 1 2+2— 2 NC C NO + — + — + — + — + — 00 3.6k EOL (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (—) 0❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WWf iH SHELD #18 FPIJFPIR RED {JACKED *CONTACT RATING& 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 0 L' J HTRI—R 114 E -I GROUND O o (+)) TO NEXT DEVICE OR ❑= ❑ I Li o/----- ❑ I , VI it 0 O 0 v �i'' C�' Vi 7 A ! n 7 8/114i .- ACCOEf$X .1 - \ +- . n'n AtCCE►CM r ..bel � v CCU .),j Lo/' C 0❑ (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV .�. FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL SPEAKER J 0 0 c STROBE Q DEDDJ CIRCUIT Q�p SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER IC OR FIRE ALARM CONTROL PANEL < (+) (+) 0 o 0 +aErE- I 1 (-) STROBE CIRCUIT STROBE 0❑ 1 ❑IJ CSI ICJ ° =I IDC V 0 ,�I ❑ 1 — O I , 0 O 0 v �i'' iE vur WEM Fai 25x Vi 7 A ! n 7 8/114i .- ACCOEf$X .1 - hIICCIII:I:I' j +— ARCCEtItiy�1N ..bel tins v CCU .),j Lo/' (-) (-) (+) (+) ❑EJ STROBE SPEAKERISTROBE O❑ ❑0 1 I vI — 1 I 1 O 0 iE vur WEM Fai 25x Vi 7 8/114i j +— ARCCEtItiy�1N ..bel tins v C (-) STROBE ❑c i) CIRCUIT (-) SPEAR CIRCUIT CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (+) v (+) S TO NEXT SPEAKER n OR END OR LINE RESISTOR S 24K (EOLR) 5 TO NEXT APPLIANCE S OR 24K (EOLR) (-) (-) Y (-) SPEAKER CIRCUIT NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TING TEPERATURE: +32' FF (0' C) TOM 00 F (36 C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECTOR —\ FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (—) >- r.)... DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN MEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR SMOKDB -11E STANDARD DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —� CEILING SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT f _H0 O O 0 1 TO NEXT DEVICE CADDY BAR of SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL CO 0' 0 C.� z_ (I) LU J UJ (1) 6 w LTJ C/) Ir) CT 0' CO (V 0 CV x Q TEL. (206) 622-6545 RELEASE/REVISIONS (.6 J 0 O —J U �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:05/10/1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA- (�02 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \ k'd l 14" t?I!N `fi gyro -}y v M1',,;„dJ YI r ffi M "M� ° r'I•,+,,,w slbi Ym h .d"':p,h! ) ,tl 4 'tp")'� £ .fF�rr tY�li Y. l.n,¢ %.5 ,MF F+ PI�F4,h ,,,rw,M:'»:' p q, dd 44'�, i'if YA �1„JSFu i`;,,.d;dv'N ffiW,9 '�A Y'4i P u V �� � f €, I� "r ",# ^' ffi�'#1','!�4 �'CI'°..:y y�a�lj. �"�,� N 4V �': .�, 'x �,tw ,, 'k,.' t a• . r, roy ��i, w"`94' „: 1NM '"�gVL✓rl 'W „1 ';" .£,t1 s: W ,Myr / yyI y, � d"*WM F N}ti.. 40 0 Wire Resistance Date: May 10, 2011 0 0 #� ', ,r '' ^„ k{, ", .', ;ffi,: "S .t •� +. „, Current Load: 'x.t.i..r, p' ,,.,':r+'' "' 'I,,!�Y..,I,,r; i, k,, r,'"..•„x y „3' %�?.', � Standby: Alarm: „ ' � 7 yr„ ar,.,.,:J�.. lk ,i, ��� a'rt E, 'x°", '.$,,> w' l6 ,;,� e. .b,., - 1'qa � � � � Y1,k e t n, ^F I �i ryh ,F j, : },,�' y, �. ,b i, �+ 3 jj,i % d�pyr:3�,. r iQyL i V� �^' �� . �,; �, i u°4a! Ln.. e a�,��,.Y;t::c;aw' �..4rr rcta'�ue:�4•e '�`r''r... : a., ., er:..,r M' r a �;a i t ., ^'"" M � �x,� �4, �, Q°Y, ;,4: 7 t° - + �,_.. rr,�..., . ., .,� ,. "J, J• . ,_,tl r,{r.,, � 87 131 222 292 Device Type e Qty Qty Amps Total Amps Total ZH-MC W @110CD ZR -MC ©15CD ZR -MC @30CD 75i -MC ©75CD- HFP-11 . ._ .�_..o, 0 __....,..__.. a 1 0.0022: , . 0.0022 .: 0.0023 0.002 AD2-P 0 a DEVICES= 1 1 0.0635 0.0635 0.064 0.064 14 HTR -R 213 1. 0.009600 .. ' :' : 0.0096 0.021 0.021 ZH-MC-C @30CD (Rift) ft) ` o CcLoad 2 . 0.2G 0.131 0.262 ZH-MC-C @75CD 24 - E) 0.222 23.71 ZH-MC-C @95CD r 0.0731 Amps 0.085 Amps J ffiW t C C .,I, T. . I rMam,", ,. , ? ,...,,, M, 7 t ! iYY r d S FIA J f „9 N wt F 7 x -m .AW':.IX £ F i t J C ? 1 P $ m .ru .. ,.,, d o .\tl ., V^: •, n 4 , ^' 'Y ° y' '•r RIALTO JEWELERS 2.5.8 � i X p PAD -3 POWER SUPPLY DATE 0 Wire Resistance Date: May 10, 2011 0 0 #� ', ,r '' ^„ k{, ", .', ;ffi,: "S .t •� +. „, f ., '4 'b, \, `' 'x.t.i..r, p' ,,.,':r+'' "' 'I,,!�Y..,I,,r; i, k,, r,'"..•„x y „3' %�?.', � .. „ ' � 7 yr„ ar,.,.,:J�.. lk ,i, ��� a'rt E, 'x°", '.$,,> w' l6 ,;,� e. .b,., - 1'qa � � � � Y1,k e t n, ^F I �i ryh ,F j, : },,�' y, �. ,b i, �+ 3 jj,i % d�pyr:3�,. r iQyL i V� �^' �� . �,; �, i u°4a! Ln.. e a�,��,.Y;t::c;aw' �..4rr rcta'�ue:�4•e '�`r''r... : a., ., er:..,r M' r a �;a i t ., ^'"" M � �x,� �4, �, Q°Y, ;,4: 7 t° - + �,_.. rr,�..., . ., .,� ,. "J, J• . ,_,tl r,{r.,, � 87 131 222 292 Device Type Qty Amps Total Amps Total ZH-MC W @110CD ZR -MC ©15CD ZR -MC @30CD 75i -MC ©75CD- 259 ._ .�_..o, 0 __....,..__.. a _ Main System Board 0 a DEVICES= 1 0.03 0.03 0.030 0.030 2 2 6 14 71H -MC -C a©15CD 213 23.71 _:.0.087.. 262 R l) ZH-MC-C @30CD (Rift) ft) ` o CcLoad 2 . 0.2G 0.131 0.262 ZH-MC-C @75CD 24 - E) 0.222 23.71 ZH-MC-C @95CD 0.292 ZH-MC-W ©110CD 0.259 ZR -MC @15CD 0.064 ZR -MC ©30CD = 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.292 Amps Standby Current Load: 0.03 Amps^ For 24 Hours-” 0.720 Amp -hours Alarm Current Load: 0:292 Amps For 5 Minute s-= ° 0.025 Amp -hours 25% Derating= 0.931 Amp -hours Total System Current Load: 0.931 Amp -hours e r,!k ! & �a ', ':"{t y!C'rp, 5, r! # M .vv4www #..-. aj1aM& '4' //F��► 5514;999 � p -h iiYll�r4W`!'I"�6 'SYI H SYSTEM CALCULATIONS TIE TO NEAREST EXISTING STROBE CIRCUIT TIE TO NEAREST EXISTING DATA LOOP 2C b c — 2C,S BPS 120VAC, DEDICATED ) (BY OTHERS) 2C,S EOL S1 S1-1 S1-2 30cd 30cd FLAG NOTES: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Notification Appliance Circuit Detail PROJECT: RIALTO JEWELERS 2.5.8 SHOP DRAWINGS Panel: PAD -3 POWER SUPPLY DATE 0 Wire Resistance Date: May 10, 2011 0 0 w. av, iT���l.�v� ,i'.,4'a yy JI „., �, ry»e „r y 2 0 0 ,�,'„V,v.M e mf b 'i l,. :G ,"n.:!$� w':",:,.�. " , ,�. : :, J I” p N 4 r.✓', i.' r r f r u, @ .� �L... Z -I -MC -C @15CD ZH-MC-C @3QCD ZH-MC-C @75CD ZH-MC-C ©95CD F�r�� "1, �v ,,, ,,,. .v,�l . :. .,,:. x, �YF,�r 3 ,, Y P Y ', ■ SL ! �, u�S :. ,., 'n�t� r # r, .,' �'; ; 1 y p4^ eF,,,. .,r .r, tt" %. �Y� to � p F � 262 0._ 0 p ffi � { v� � V _„w u � 7 yr„ ar,.,.,:J�.. lk ,i, ��� a'rt E, 'x°", '.$,,> w' l6 ,;,� e. .b,., - 1'qa � � � � Y1,k e t n, ^F I �i ryh ,F j, : },,�' y, �. ,b i, �+ 3 jj,i % d�pyr:3�,. r iQyL i V� �^' �� . �,; �, i u°4a! Ln.. e a�,��,.Y;t::c;aw' �..4rr rcta'�ue:�4•e '�`r''r... : a., ., er:..,r M' r a �;a i t ., ^'"" M � �x,� �4, �, Q°Y, ;,4: 7 t° - + �,_.. rr,�..., . ., .,� ,. "J, J• . ,_,tl r,{r.,, � 87 131 222 292 ZH-MC W @110CD ZR -MC ©15CD ZR -MC @30CD 75i -MC ©75CD- 259 ._ .�_..o, 0 __....,..__.. a _ 0 a DEVICES= � 1?5 12 Total Wire Resistance Total Devic Load,Amps TOTAL mA= A 2 2 6 14 213 23.71 262 R l) (Rift) ft) ` o CcLoad . 0.2G Voltage Drop (E)(E=I*R)0.29 EOL Voltage 24 - E) 23.71 SYSTEM CALCULATIONS TIE TO NEAREST EXISTING STROBE CIRCUIT TIE TO NEAREST EXISTING DATA LOOP 2C b c — 2C,S BPS 120VAC, DEDICATED ) (BY OTHERS) 2C,S EOL S1 S1-1 S1-2 30cd 30cd FLAG NOTES: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR, RELAY MODULE FOR FAN SHUTDOWN & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 0 0 0 2CCCCC C 0 w z W �z co J WCC oz d - J o�0 .U) W <w° z W< Ws < co (..),,c) 0 W �= Ira CC D W C!) "GALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 05/1 0/ 1 1 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved .OB NUMBER: 1- SHEET '' FA -03 } 4i� f jRJALTO JEwELEP$ SPACE 432 1 1 1 t 11 1 f 1 !1 f �G � ; ' r(''` 1 1 !LLa�E 1 1 1 E G DESCRIPTION ,l1'' ,,. J+ft ; ' 51 9" i ( 1 ! 1 61 t Vin, ' DATE • a ♦ w ♦ > ,• a♦ r ♦ a f •• as a♦• r•+aa,= a a ••ra• aaa•a•.••_a>•••ar>•.•••sa--a••r i •r}{•Y«• :.•tt00th• • •ii♦ rt a+,..a♦l •ii •••a•• • a • is •tas•a.i•.i •• a,t•af a••••♦a at•Y•♦ i•.••,:•♦♦••at •.•a••a•• ••••••••a••••• .•..a1.... .. ♦. aa•..a.• ha ♦ nF•a , a ' ar' `.• r> :' • a, **VS. a1. ,l, • a V ~ •••_ .•♦»« a'� ' . 1.a '• ' ia•t♦+ ♦.k}•aw:• •t a,•aa, 1 •••'• • #�,.Xit,kRa .4+a aslaafara }t } . • w • • a i , • » 11444411, • • a X • ♦ i i.• •.• !ia, .....4 a1. a 1 aa ,• _ :• •X1 as .a •�0•14.0410.4.41,04,444, a, Y • « r t ♦ i ♦ •• a a ; r 1 a := a.a, 'f411 � �`:'ww aaa y.. ••••MllIllIll •t•,•:•a•' ♦2a: •": 4•! •4.••• • ta}#f • r 1 . • • ! + • i f t a t ♦ • t a a a, `1•t 1 = 1 1 II. AREST •s*�. '- �1/ ' T TO EXISTI � E CIRCUIT 0 EST EXISTING LOOP _ :