Loading...
HomeMy WebLinkAboutPP - 817 SOUTHCENTER MALL - ESCAPE OUTDOORS - PERMITS AND PLANS817 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-256 08-S-028 FILE COPY FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Escape Outdoors 817 Southcenter Mall Permit No.: 08-S-028 Date: February 1, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 20' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. All references are NFPA 13, 2007 Edition. N © M.E.P.CAD, Inc. Rfi AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:38AM Page 1 Hydraulic Summary Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Job Job Number K50195 Design Engineer Martin Sokulski Job Name HH Escape Outdoors State Certification/License Number WESTESF136QF Address 1 817 Southcenter Mall AHJ City of Tukwila Address 2 Job Sde Southcenter Mall City Stale , Zip Code Tukwila WA I 98188 Drawing Name FP01.cad System Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 1500.00ft2 (Actual 1335.69ft2) Additional Hose Supplies Node Flow(qpm) Number Of Sprinklers Calculated 11 Coverage Per Spnnkler 130 AuloPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Il Total Hose Streams 250.00 / 1/ ` System Flow Demand 298.12 Total Water Required (Including Hose Allowance) 548.12 1_; ' j, Cci. n„ Maximum Pressure Unbalance In Loops 0.000 —� -� N?_/If Maximum Velocity Above Ground 12.78 between nodes 54 and 99 Maximum Velocity Under Ground 1.13 between nodes 1 and 446 Volume capacity of Wet Pipes 2965.36gal Volume capacity of Dry Pipes 2.96ft3 Supplies Node Hose Flow (gpm) Static Residual Flow (psi) (psi) (gpm) Available @ Total Demand Required (psi) (gpm) (psi) Safety Margin (psi) 1 1 250.00 140.000 20.000 10900.00 1_ 139.525 548.12 54.234 1 85.291 Contractor` . Contractor Number K50195 Contact Name Martin Sokulski Contact Title PM Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7108 180th Ave NE FAX 425.881.3030 Address 2 E-mail martin.sokulski@wsfp.us City State Redmond WA Zip Code 98052 Web -Site N © M.E.P.CAD, Inc. Rfi AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:38AM Page 1 Summary Of Outflowing Devices Job Number: K50195 Report Description: HH Escape Outdoor Actual Flow Device (gpm) Minimum Flow K -Factor Pressure (gpm) (K) (psi) c> Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 108 26.92 26.00 I 5.6 23.108 Sprinkler 115 28.32 26.00 5.6 25.568 Sprinkler 111 27.42 26.00 5.6 23.979 Sprinkler 114 28.14 26.00 5.6 25.245 Sprinkler 112 27.43 26.00 5.6 23.992 Sprinkler 110 27.12 26.00 5.6 23.461 Sprinkler 107 26.91 26.00 5.6 23.098 Sprinkler 104 26.61 26.00 5.6 22.585 Sprinkler 106 26.77 26.00 5.6 22.851 Sprinkler 102 26.47 i 26.00 5.6 22.343 c Most Demanding Sprinkler Data (1J ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:40AM Page 2 Report Description: Job Number: K50195 © M.E.P.CAD, Inc. rfg AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:40AM Page 3 Node I Elevation(Foot) 1 Fittings I Pressure(psi) I Discharge(gpm) 17 14-6 E(2-0) 28.768 19 14-6 P0(5-0) 28.8081 23 14-6 E(2-0) 31.122 25 r— 14-6 PO(5-0) 29.891 29 14-6 PO(5-0) 31.463 54 14-6 2P0(8-0) 33.953 55 ! 14-6 2P0(8-0) 34.017 99 14-6 P0(5-0) I 29.907 103 14-6 P0(5-0) 29.247 105 14-6 P0(5-0) 1 28.795 109 14-6 P0(5-0) 28.157 113 14-6 P0(5-0) 28.488 117 14-6 P0(5-0) 27.856 438 1-11 PO(5-0), PO(26-4) 47.077 446 3-10'% BFP(-4.500) 50.781 482 101 1-11 10-0% LtE(16-0) Spr(-21.556) 47.094 21.556 26.00 108 13-7% Spr(-23.108) 23.108 26.92 115 13-7% Spr(-25.568) 25.568 28.32 111 13-7'/% Spr(-23.979) 23.979 27.42 114 13-7% Spr(-25.245) 25.245 28.14 112 13-7% Spr(-23.992) 23.992 27.43 110 13-7'% Spr(-23.461) 23.461 27.12 107 13-7% Spr(-23.098) 23.098 26.91 104 13-7% Spr(-22.585) 22.585 26.61 106 13-7% Spr(-22.851) 22.851 26.77 102 13-7% Spr(-22.343) 22.343 26.47 1 -4-0 S 54.234 r298.12 © M.E.P.CAD, Inc. rfg AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:40AM Page 3 Hydraulic Analysis,. Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Pipe Type Diameter Flow Velocity HWC Friction Loss Length 1 Pressure Length !Summary Length . Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Total Qt Route 1 DR 1.049 Q=26.00 9.65 C=120 0.211434 j 35-3 Pf 9.144 101 10-0% q=26.00 K=5.6 21.556 Spr(-21.556) 8-0 Pe -1.933 17 14-6 28.768 3E(0-0), 4E(2-0) 43-3 Pv BL 1.610 Q=26.00 4.10 C=120 0.026249 1-6'% Pf 0.040 17 14-6 28.768 Pe 19 14-6 28.808 1 1-6'% Pv BL 1.610 Q=52.92 8.34 C=120 0.097746 I 11-1 Pf 1.083 19 14-6 28.808 Pe 25 14-6 29.891 I 11-1i Pv BL 1.610 Q=80.34 12.66 C=120 0.211619 7-2% Pf 4.063 25 14-6 29.891 12-0 Pe 54 14-6 33.953 2LtE(2-0), PO(8-0) 19-2% Pv CM 4.260 Q=161.45 3.63 C=120 0.006735 9-6 Pf 0.064 54 14-6 33.953 I Pe 55 14-6 34.017 9-Pv CM 4.260 Q=298.12 6.71 C=120 0.020943 260-11 Pf 7.604 55 14-6 34.017 102-2 Pe 5.455 438 1-11 47.077 2P0(26-4), 2fE(8-11'/2), 363-1 Pv CV(28-11'/2), GV(2-7%) FM 8.329 Q=298.12 1.76 C=120 0.000800 5-7 Pf 0.017 438 1-11 47.077 16-0 Pe -0.000 482 1-11 47.094 LtE(16-0) 21-7 Pv FM 10.420 Q=298.12 1.12 C=120 0.000269 26-5'/ Pf 4.529 482 1-11 47.094 83- Pe -0.842 446 3-10% 50.781 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5Y Pv UG 10.400 Q=298.12 1.13 C=140 0.000204 109-2 Pf 0.045 446 3-10'/2 50.781 111-7II Pe 3.407 1 -4-0 54.234 E(35-1), 3LtE(25-6), S 220-9'/J Pv Gib Route 2 DR 1.049 Q=26.47 9.83 C=120 0.218568 22- Pf 5.901 102 13-7%z q=26.47 K=5.6 22.343 Spr(-22.343) 5- Pe -0.388 117 14 6 27.856 2E(0-0), PO(5-0) 27- Pv BL 1.610 Q=26.47 4.17 C=120 0.027135 11-1 Pf 0.301 117 14-6 27.856 Pe 109 14-6 28.157 11-1 Pv BL 1.610 Q=53.08 8.37 C=120 0.098309 11-1 Pf 1.090 109 14-6 28.157 Pe 103 14-6 29.247 11-1 Pv BL 1.610 Q=80.21 12.64 C=120 0.210969 10-7% Pf 4.771 103 14-6 29.247 12-0 Pe 55 14-6 34.017 2LtE(2-0), PO(8-0) 22-7% Pv Route 3 DR 1.049 Q=26.61 9.88 C=120 0.220755 22-0 Pf 5.960 104 13-7'/2 q=26.61 K=5.6 22.585 Spr(-22.585) 5-0 Pe -0.388 109 14-6 28.157 2E(0-0), PO(5-0) 27-0 Pv a. Route 4 DR 1.049 Q=26.77 9.94 C=120 0.223156 22-0 Pf 6.025 106 13-7%2 q=26.77 K=5.6 22.851 Spr(-22.851) 5-0 Pe -0.388 113 14-6 28.488 2E(0-0), PO(5-0) 27-0 Pv BL 1.610 Q=26.77 4.22 C=120 0.027704 11-1 Pf 0.307 113 14-6 28.488 Pe 105 14-6 28.795 11-1 Pv BL 1.610 Q=53.68 8.46 C=120 0.100371 11-1 Pf 1.112 105 14-6 28.795 Pe 99 14-6 29.907 11-1i Pv BL 1.610 Q=81.11 12.78 C=120 0.215391 6-9% Pf 4.046 99 14-6 29.907 12-0 Pe 54 14-6 33.953 2LtE(2-0), PO(8-0) 18-9''/z! Pv Q. Route 5 DR 1.049 Q=26.91 9.99 C=120 0.225385 22-0 Pf 6.085 107 13-7% q=26.91 K=5.6 23.098 Spr(-23.098) 5-0 Pe -0.388 105 14-6 28.795 2E(0-0), PO(5-0) 27-0 Pv Gib Route 6 DR 1.049 Q=26.92 9.99 C=120 0.225478 1 22-0 Pf 6.088 108 13-7'% q=26.92 K=5.6 23.108 Spr(-23.108) 1 5-0 Pe -0.388 19 14-6 28.808 2E(0-0), PO(5-0) 1 27-0 Pv v Route 7 DR 1.049 Q=27.12 10.07 C=120 0.228664 22-0 Pf 6.174 110 13-7'/2 q=27.12 K=5.6 23.461 Spr(-23.461) 5-0 Pe -0.388 103 14-6 29.247 2E(0-0), PO(5-0) 27-0 Pv Route 8 (IM, ©M.E.P.CAD, Inc. 419 AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:41 AM Paae 4 Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Velocity K -Factor HWC Friction Loss !Length I Pressure Pt Pn Fittings 1 Eq. Length Summary j Total Length , DR 1.049 Q=27.42 10.18 C=120 111 13-7% q=27.42 K=5.6 23.979 25 14-6 29.891 GO Route 9 0.233331 Spr(-23.979) 2E(0-0), PO(5-0) 22-0 Pf 6.300 5-0 Pe -0.388 27-0 Pv DR 1.049 Q=27.43 10.18 C=120 0.233449 112 13-7% q=27.43 K=5.6 23.992 Spr(-23.992) 99 14-6 29.907 2E(0-0), PO(5-0) Route 10 DR 22-0 Pf 6.303 5-0 Pe -0.388 27-Q Pv 114 29 BL 1.049 13-7% 14-6 Q=28.14 10.45 C=120 0.244698 q=28.14 K=5.6 25.245 31.463 1.61 Spr(-25.245) 2E(0-0), PO(5-0) 22-0 Pf 6.607 5-0 Pe -0.388 27-0, Pv -•-- 29 14-6 55 14-6 31.463 34.017 2LtE(2-0), PO(8-0) I I -L rr 12-0 Pee 23-2 Pv Z.004 Route 11 DR 1.049 Q=28.32 10.51 C=120 0.247600 22-0 2-d 24-0 Pf Pe Pv 5.942 -0.388 115 13-7'% q=28.32 K=5.6 23 14-6 25.568 Spr(-25.568) 31.122 2E(0-0), E(2-0) BL 1.610 Q=28.32 4.46 C=120 0.030739 11-1 11-1 Pf Pe Pv 0.341 23 14-6 29 14-6 31.122 31.463 Equivalent Pipe Lengths of Valves and Finings (C=120 only) 0 Value Multiplier (Actual Inside Diameter 4.87 Value Of C 100 Multiplying Factor 0.713 130 140 1.16 1.33 150 1.51 Schedule 40 Steel Pipe Inside Diameter ) = Factor v m.t.r.t;HU. Inc. 4IHAutoSPRINKCR) VR.ri vR 7 R Al n/flnno n.no.., w•• Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Elevation Upstream Discharge K -Factor Pt Pn Fittings ILength I Pressure Pipe Type`Legend Units Legend •=; . Eq. Length Summary Total Length Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Tum 90° cplg Coupling Cr Cross Run CV Check Valve DeiV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%* Elbow Ee2 22Y2° Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap , © M.E.P.CAD, Inc. 4,fi AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:41AM Page 6 Hydraulic Graph Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 (AA. n M_E.P.CAD_ Inc. AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:43AM Page 7 Supply at Node 1 150 Static Pressure 140.000 135 120 105 90 .N _ n _ 75 _ w _ w _ EL' 60 D.548.12 -298.12 with hose @ 54.234 streams 45 30 -System demand curve 10900.00 @ 20.000_ 15 4 kmiluunl minim 111111111 IIIIIIII 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I I t I I(( ) t I I I i I I I t 1 1 I i ( ( I i 0 71002200 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime o/ Test 139.525 @ 548.12 System Demand 298.12 @ 54.234 System Demand (Including Hose Allowance) 548.12 @ 54.234 (AA. n M_E.P.CAD_ Inc. AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:43AM Page 7 Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 !rl RA G D rAn Inr au Ai ifnAPPIKIKM\Mc vA 2 R 01 /30/2008 9-08.43AM Paae 8 GUARDIAN SECURITY Customer L 1 F E AN ESCAOE OUTDOORS *817 SOUTHCENTER MALL �'r"WWILA, WA 98188 D PROPERTY PROTECTION Project ESCAPE OUTDOORS Project # 54505 List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: JUNE,02,08 Item Qty. Manuf. Model Description Unit Pri Total Price A 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) .18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) > 47) 48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard HH Escape Outdoors Remote Area: 1st Floor #817 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS OH Group II MAX. COVERAGE per HEAD 130 Ft2 DENSITY .20 GPM / Ft2 for 1335 Ft2 SPRINKLER Reliable Model F1FR ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI • RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 298.1 GPM © 47.1 PSI At time of Design 71-0, 4 MI MO MEI LIU 1=1 EXISTING 4" TEN -4 ! ,711/2. -6 C: r` ;S.' 11 2 Co 13-7 clg. 4 14-21A EAST RISER ROOM (for hydraulic reference) General Notes 1. Western States Fire Protection to add new pendent heads and branchlines. in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations).. 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to. remain. Western States Fire Protection will modify the existing system onlyin the areas of work. All other areas. are not in contract and WSFP is not responsible for exiting conditions. Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth oundnd(0 Berea Inch Rod Coupling Ag ThrRe d et Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan 9-O cIC S Ring Note on Plan: Henget Number end' At Dimension wiTELIIIIMOno FW. co SWIVEL SWAY I0ACE FITTING FI0.1000 "FAST CLAMP SWAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON -THREADED BRACE PPE PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT big] NON.T11READEO BRACE PIPE ACCEEPTE fUKWILA FIRE DEPART En Please call: 575.4402 and give this job, No. -ii id exact address for shut', i „,,Airt or restoration approval, LATERAL BRANCHLINE RESTRAINT nese nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subect to errors and omissions which do not authorize violations of adopted standaras and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thi.,acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date:Si By: / Si I -. FIRE PROTECTION PLAN LEVEL 1 3/1011=1-0" VICINITY MAP (Suite#1460) SCALE; NTS SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE DESCRIPTION Sprinkler Legend APPROVAL: City of Tukwila SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. HYDRAULIC REFERENCE POINT HANGER SYMBOL 17 5.6 Pendent %' White 155°F 1 Total =18 5.6 Pendent Chrome 155°F MFR./MODEL Reliable F1FR SSP Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF Reliable G4QR Concealor CONT. No.: K50195 DRAWN BY: Martin Sokulski SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: 18 01 /30/08 WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH/HOUSTON/ KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX / PORTLAND / RAPID CITY /ST. PAUL /SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 HH Escape Outdoors 817 Southcenter Mall Tukwila,WR 98188 pAID FIRE PROTECTION PLAN LEVEL 1 SHEET FP -1 OF t'R, J 3 : ZU08 Tukvvila Fire ( ESCAPE OUTDOORS FIRE ALARM SYSTEM TUKWILA, WASHINGTON r SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UV3ER SHEET TITLE FA -01 SYSTEV \FOVATIO\ FA -02 TYPICAL DETAILS - WIRI\G A\D V OU \TI \G FA -03 FRE ALA V SYSTEM FLOOR PLA\ FA -04 SYSTEM CALL U LATI O \ S (c E\EAL), RISE; SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 416 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO 414 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWD 416 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD 416 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR 414 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR 414 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWD 418 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED 418 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED 418 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO 416 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO 414 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT DF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR. TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROvI AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM . SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 2 2 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B -1 LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ® SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS DUCT HOUSING TSM MODULE VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM L c FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING n FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. Q FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM B 10 WP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. IN FZELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. • F.B.O. ACC t tED VERT IN ELD JUNCTI❑N BOX F.B.D. 1 F.B.❑. / N/A VERIY `' z Q ,, / Without Comments mi r�tw A.F.F. ABOVE FINISHED FLOOR N/A N/A As Noted I Per The AttachedLetter N/A F.B.O. FURNISHED BY OTHERS N/A i nAmplans have been revi d by The Tukwila Firel/A Prevention Bureau for conformance with current city standards. Acceptance is N/A NOT APPLICABLE N/A cuhiect to errors and on ,5Pons which do not autlitig 4e violations of adopt VA standards and orainances. The responsibility for the design CCCCC U,❑.N. UNLESS OTHERWISE NOTED N/A adequacy of ests totally with the designer. AdFii i ts, deletions or revisipmo these drawings attar'A this date will void this,acceptance and will require a WP WEATHERPROOF DEVICE N/A resubmittal of revised Jrawinus for subsequent approval. N/A NN Final acceptance is subject to field test and inspection by N A RED AS BUILT ADD DR CHANGE N/A The Tukwila Fire, Prevention Bureau., N/A N/ N/A Date: D By:`0.4" " d comptete+ Fire DepE Certificate r AC RI ITI T N/A 164944 to the In M BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE , signed, Tukwila rtment Pre-test nust be presented spector prior to commencement of Acceptance Testing of any Fire Alarm TUKWILA FIRE DEPARTMEIN1 Please call: 575-440Z and give this job and exact address for shut. Gown or restoration approval Copyright 2006 by Guardian Security Systems, and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. FBE .. 2008 Tukwila Fire Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS w I- < D 5/15/08 o CCCCC SCALE: 1/8" =1' DRAWN BY: (.ANDERSON c) CA n .OB NUMBER:54505 r SHEET DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE Moo - 0 DUCT DETECTOR LOCATION FROM XLS CONTROL PANEL OR SI - PREVIOUS ADDRESSABLE DEVIL END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 GROUND m 0 m Lr) O O HTRI—R OSTATUS LED CO 0 N.O. 0 COM 0 NC NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L _ + NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING- \ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE 11}.AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE L(-) FROM XLS CONTROL PANEL OR {(4.) PREVIOUS ADDRESSABLE DEVICE (-) END OF LINE DEVICE RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N, 0 + TB1 sam 123456 TB2 C D 654321 0 0 0 0 (3.6K 1/4W) SUPERVISED SWITCH GROUND NOTE: ; ; ; Ji ; J 0 O O HTRI—D OSTATUS LED Co m 0 A �0 NOT USED O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 CND N AC `Iop 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 0 0 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3,6K 1/4W) .."SUPERVISED /Th SWITCH NAC -4 NAC -3 NAC -2 NAC -1 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP T. NOT USED REMOTE v_ DEVICE LOOP 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �IN EOL T M-1 0 • e 0 CC_ COI e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOPE FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) C'V' CABLE) (STR❑BE) SPEAKER (0 0 EARTH GROUND -.(+)TO NEXT DEVICE OR ) (-) STOP IF LAST DEVICE 66 STR❑BE—) (STROBE) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F., 4S DEEP BOX W/ 1-1/2" EXTENSION RING • (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE To NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA�I�IN TEMPERATU E: +32' F (0 C) TO 100' F (338" C) HUMIDITY: 0--9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) > DATA IN (+) DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJLINCTION WIlli DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE-r-- ( EVICEF ( ) DATA OUT 1 ) (+) DATA OUT J7 CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT T�.�..- BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N B❑X---- MOUNTED ON \\ CEILING, FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT TO NEXT DEVICE CADDY BAR SMOKE DETECTOR -- SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT I\ST ADDRESSABLE N T1,4TING DEVICES U\TIL PREPROGRAMMED WITH DEVICES ADDRESS. LL Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z w DESCRIPTION SHOP DRAWINGS w 0 1) 0 7 C co CC co JOTD 0 J 0 2zQ w �© Q I- 1 -CO z D 2 w= cc =Q W < !E : W O J 0 LI' W /SCALE: 1/8"=1' I -- Z 0 0 cc z c� z J U 0 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER:54505 SHEET FA -02} 1 ©12 '1s 2 v 1s,2v 1 3c - ,2V 2I L -- T JJ r - :o NORTH NORTH ii izt \ I'\ EOL ; Si 19.8 V • ESCAPE OUTDOORS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG NO S: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO— NSTALL ADDRESSABLE INITIATI DEVICES UNTIL PREPROGRAMMED WITI- DEVICES ADDRESS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1,0 c0 ON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 9 ««< 1 CCCO J r � O 2 2z O w�0 a u c� z Jew= O=Q W < CL w oGQ_`5 Q �h.- 0 �CALE: 1 /8"=1 DRAWN BY: I -ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: .,10B NUMBER:545O5 j SHEET FA-03� L ALL. OFF 11(.4 -•• M 1: L.) -7- 1000 • , - „ - r-. A E-3 F1' R (DEVI E3 E. 1v 1:1 \ 11i 11 W . 111,; 11 --- rm. rn 1010 _I I I 11 3GAI..L[:RIE : 1E1 _1\4 1 570 1 1ii '\i11 1 :-)5(1) Th LL LJ 10201 ,U1 1.545 1';') LiJ ECTR!AL ROOL,• R Evl BREW NORTH MEW', "Ar'• A P A RI I\11-: S "YE AH,./1 SHOP P AC I FIG: 3J N WEAR V‘i 111 116, ASq.p. E. 33 3 THE 10/4\ LK. INC; GO. 1 00 b E b e 1 0 1540 -11 REG CUM R AGE. KISER LOADING DOCK - ----- 0_ ESCAPE OUTDOORS WESTFIELD SOUTHCENTER MALL CO LLJ EY. 1 25 L_LJ 0 17, NG'S P2 [-T-71 ETT.1 LL <a: I 135 1.1401 I'LL SYSTEM CALCULATIONS 1 STARE SCALE 11374 S,2V0 S,2V02S,2V 0 2S,2V 75 C 75 C 15 15 EOL -S1 EX D,ID DI LI CI 21 • 21 E E RISER DIAGRAM BATTERY SIZING CALCULATION ESCAPE OUTDOORS ESCAPE OUTDOORS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE Panel: ESCAPE OUTDOORS Wire Resistance 162 H 11 2 < Date: May 30, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: - QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 ...... SET -MC @15CD 64 128 Device Type Qty Amps Total Amps Total 0 Device Type 98 Qty Amps Total Amps Total ( WL * 2 )* (R/ft) HFP-11 2 SET -MC @75CD 0.0022 0.0022 0.0023 ____ Total Device Load, Amps (1) 0.94 2 SET -MC @110CD 233 466 AD2-P 2 0.0635 0.0635 0.064 0.128 SET-HMC-C@115CD Main System Board 0 1 0.03 0.03 0.030 0.030 0.58 HTR -R SET-HMC-C@177CD 3 0.009600 0.0096 0.021 0.063 SET -MC @15CD (E= I * R) _ 0 SET -HMC @135CD 318 0.064 HTRI-D 0.001600 19.82 0.0035 SET -HMC @185CD 445 SET -MC @30CD --- 2 - -- -- 0.098 0.196 0 ICP -B6 64 0 0.005 SET -MC @75CD 1 Z-MC@30CD 98 0 0.175 0.175 0 SET-MC-CW@110CD 233 0 SET -MC @110CD ______ 2 0.233 0.466 mA= 944 12 191 19.81581504L 944 DEVICES= Werner* SET-HMC-C@115CD __ Notification MVP.10frl Appliance .V.WIPINIW•laiWry.-114y•IVIS....MMIONMMAIN DWVVIVM•MS.1•Wielarnef,MISOVV•••••••FTWOOMNOVYWOMI Circuit 0.318 evnm PROJECT: WESTFIELD SOUTHCENTER MALL SET-HMC-C@135CD --- _ ESCAPE OUTDOORS1....,...i, . i. Wire Resistance '2i58'.., 0.318 Date: _ ._ May 30, 2008 CURRENT TOTAL= 7.2 0.0731 Amps 0.191 Amps SET-HMC-C@185CD 0.445 _ QTY Device Type Alarm Current Alarm Total Wire Size Wre Length Voltage at EOL Circuit Total ZR -MC @15CD 1 70.7V1/8 1.8 7.2 0.064 0.064 Standby Current Load: [Total Wire Resistance 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @30CD .. ......._...m....... .._..................._ _ WL * 2 )* (Rift) 0.098 0 0 . Total Device Load, Amps (1) 0.01 0 HCP 0 0(Total ....._ _....._ 0.0015 Cct Load) Alarm Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours Voltage Drop ( E) 0.01 0 0.03 Amps 0.931 Amps (E= I* R) _ 0 0 0 _........_ , EOL Voltage 20.39 0 • 0 0(20.4 25% Derating= 2.213 Amp -hours 0 Standby Current Load: 0 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 0 DEVICES 4 TOTAL mA= 7.2 14 191 20.39290397 7.2 Alarm Current Load: 0.931 Amps For 5 Minutes= 0.078 Amp -hours Total System Current Load: 2.213 Amp -hours 25% Derating= 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION co ON (9 (f) LU LU (f) (/) u (f) r -- TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE Panel: ESCAPE OUTDOORS Wire Resistance 162 H 11 2 < Date: May 30, 2008 CURRENT TOTAL= 944 CIRCUIT: S1 - QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 ...... SET -MC @15CD 64 128 Total Wire Resistance ( R ) 0.62 0 SET -MC @30CD 98 0 ..._ ( WL * 2 )* (R/ft) 2 SET -MC @75CD 175 _ 350 ____ Total Device Load, Amps (1) 0.94 2 SET -MC @110CD 233 466 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ---. Voltage Drop ( E ) 0.58 0 SET-HMC-C@177CD 445 0 (E= I * R) _ 0 SET -HMC @135CD 318 0 ------ EOL Voltage 19.82 0 SET -HMC @185CD 445 0 --- -- - -- -- (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 - __________ ______ 6TOTAL mA= 944 12 191 19.81581504L 944 DEVICES= Werner* __ Notification MVP.10frl Appliance .V.WIPINIW•laiWry.-114y•IVIS....MMIONMMAIN DWVVIVM•MS.1•Wielarnef,MISOVV•••••••FTWOOMNOVYWOMI Circuit Detail evnm PROJECT: WESTFIELD SOUTHCENTER MALL Panel: _ ESCAPE OUTDOORS1....,...i, . i. Wire Resistance '2i58'.., Date: _ ._ May 30, 2008 CURRENT TOTAL= 7.2 CIRCUIT: SPEAKER CIRCUIT _ QTY Device Type Alarm Current Alarm Total Wire Size Wre Length Voltage at EOL Circuit Total 4 70.7V1/8 1.8 7.2 , [Total Wire Resistance ( R ) 0.99 0 0 0( .. ......._...m....... .._..................._ _ WL * 2 )* (Rift) o 0 0 . Total Device Load, Amps (1) 0.01 0 0 0(Total ....._ _....._ Cct Load) 0 0 0 -- Voltage Drop ( E) 0.01 0 0 0 (E= I* R) _ 0 0 0 _........_ , EOL Voltage 20.39 0 • 0 0(20.4 , - E) 0 0 0 0 0 0 DEVICES 4 TOTAL mA= 7.2 14 191 20.39290397 7.2 VOLTAGE DROP CALCULATION co ON (9 (f) LU LU (f) (/) u (f) r -- TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 < <<<< .11 cc (i) w z 0 ci) z0 0 0 11.1 ›- CD ‘ALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved NUMBER:54505 SHEET --"N FA -04} OWNER. HH Escape Outdoors J� i t L V. I dry. �V � i ,�+ ��� o D D o 0 00 4 Ill l� Ill' VI :� �igh _- , , , = to. -�` ; _ f; J ,.3 , . 41) - '' 5-27 341/2 41:14 gR- Fir -1-. — _— --- + I O L. �O ©„ A , i . i ON H - / - �- ',� .F E�. 7k Fv�� �Sr•6+ *1\6 ZONE T4 I ,i 1 SYSTEM RISER = r ,o, Ir °) I, .-E ,, s �� r Q Cr) il 1 li Co)= - , /----------'• P=oi CI N /0 / , , N-. r 1 se 1 1 0 v- z ( HH Escape Outdoors ,, � .J �a-9'r2�,r Remote Area: 1st Floor #817 ® -,--0 �- O 0 1— ® 'r I '-- i1.1..):) - 114 c CALCULATION DESIGN CRITERIA: #13-2007 `c 11/21 °� M .�'�.�� /t c , 1 12 co1 M iSTANDARD_NFPA ' EXISTING 4" TENANT MAIN_t�1�.D2 `� II 0..-'1rv-1 et '1.4 NSIT., 4 5-0 0)-�_OCCUPANCY 1. 4 b 41: CLAssOH Group 4 _ ARCHITECT. Rolluda Architects _ 61 h _ MAX. COVERAGE per HEAD 130 Ft2 6"4' � © + �9-6 /2 O � .I � 11/214-2 j J2 2-5l2 8-7 11-0 11-0 6-5 7 11-0 11-0 4-01 1 6-11 /2 8-8 13-0 13-0 r.1 r DENSITY_.20 GPM ! Ft2 for 1335 Ft21-d x'02 40 JP 13-7 clg. -C-2 V EAST RISER ROOM (for hydraulic reference) SPRINKLER Reliable Model F1FR M ©� o c .Z GWB 1.02 r ORIFICE 1 /2" K=5.6 V.% _,,c, , , x�� 4: c._M dD+0, vliff WATER FLOW INFORMATION . STATIC 140 PSI i- k�� -' RESIDUAL 20 PSI r M�r 10900 GPM FLOW© r:General I Notes AT 298.1 RISER, SYSTEM @ REGI I7F�: GPM � 47.1 PSI � . �-��r2/ ioJ 5-4 1. Western States Fire Protection to add new pendent Sprinklers in the new store shall be spaced in accordance heads and branchlines with NFPA in new tenants ace. #13 Ordinary hazard space. with }�`� * At time of Design 2 Group II.0.20gpm/ft2 for 1500.00ft ---I 1 O �� �_1�/ I ®/ OQ �0 109 �, 0 2. 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent The buildina is constructed with non-combustible materials and qualifies length included in calculations). as unobstructed construction. Ordinary ( t' r / �,> €c`' © �� `� 3. 4. 5. All hanger assemblies shall be spaced and installed in accordance Branchline and arm-over pipe is black Schedule 40 pipe. All new threaded fittin s are cast iron Q class 125 or ductile iron class with NFPA & manufacturer's specifications. 150. °' � __ } 6. The owner is responsible for all a❑❑ropriate maintenance of sprinkler system in accordance with �� �- 49 Cr D� o ,k'` -�° �0- Cy 4:1P ® �• .� /- 7. 8. NFPA as well as 4 ate &local codes. 111 The nwner is resnne,sihle for the freeze nrntection of all sprinkler system that are not designed for freezing conditions. 111 Existing fire sprink►w:� system to remain. Western States Fire Protection only in the arPac of All in WSFP piping and components will modify the existing system is �: ® *ND( EOE OO�• © � �4P�' \ o r, to <<\''r to) work. other areas are not existing conditions. contract and not responsible for ENGINEER. Martin Sokulski �� per, Hanger - -' ,i .�. 4 No. 07C HILTI Kwik Bott 111 / `o,a.a A -� I Q. no, ,,t / - `VO E)�N , 6--:,) ' Rod L B� r.,„„„,,,, / ConstructionuA O1 . t. -- I' 05 /Z i( Al Thom' Rod `L� -L/: r Red LM ReMan of Comm+. to \ P1 , vM.d L of Pp. Nut NI �3-x'! 1 2;Ta� fD1 (O 1 F 1 ., N< ' I r Q O �� Notion Flan: Hangar Number and 'A'Dimension 4 2-1 ... 12-0 9-0 cl 'co \ c jG4, to C II44. 1 :�l I '!i co YF R'RR BOLT R 1N•EAIBID LBlGM 1 .I R,M•El6mIBIGT , .I ®Y O ,� �� FO.BW 6� -1. •l- 9 O i \ 1 1 -- 1 .� it , ,,.[ SWNO. SIHAr -' BRACE fRTNG FG.ra -_ d� NO-Tit, : . t1NEL SY(ATe - .e A77ACi.HTI \\ 7 -1 1'- \ __ 4'-f jam® �� \ ( BRACE PIPE 1 �, .L. \ y� ��{- ��FG.1 GIPLP w BRACE PIPE -_ .� _ ti ___ . �, SlYAr BRACE A77ACN�Nf \i/ co �_ ,co -. ,cOk \ - ; { l % , 1 UNE HPE r • - FI(iM� HPE CLAMP O --- `\ i I LATERAL UNE RESTRAINTS FOR svArBRAc. -" r �`�' ® RAL BRANCCE NE RESTRAINT �����, TaoN(riTHiEADm BRACE HPE "•FtFADED BRKE HPE l LLilw LL CONTRACTOR. Rolluda Architects ` C� - • ' LATERAL BRAN HLINE it s STRAINT 1gWP-j - ' `^JWP /`�--, , i ' -. N Am .w�WWU.I 2RWJiYYIY'lH, / 1 5\�� ! t ` i , i , 3 • _.. .._, i ._ ____ .... • ;Mrsi I� 5 �: 4 I F I 0 mit MO FIREPROTECTION PLAN LEVEL 1 x. La.XJ_ 3116"= 1'-0" VICINITY MAP(Suite#817) SCALE: NTS �� SYMBOL LEGEND REVISIONS Sprinkler Legend APPROVAL: City of Tukwila " ":� ^.• : Western States hire • Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA Lic. #: WESTESF1360F - 98052 HH Escape Outdoors 817 Southcenter Mall � Q p Q � /� / /� 98188 Tukwila V V!'1 9 81 88 FIRE PROTECTION PLAN LEVEL 1 �>��� FP-1 OF 1 T SYM. SIN _� QTY.= _ K SPRAY ORIF. FIN. TEMP. MFR./MODEL - - 1 2-WAY EARTHQUAKE BRACE No. DESCRIPTION DATE 17 5.5 Pendent %:" White 155°F Reliable F1FR SSP cow. NO.: K50195 - X - 4-WAYEARTHQUAKE BRACE i 1 5.6 Pendent /i' Chrome ° 155 F Reliable G4QR Concealor DRAWN BY: Martin Sokolski HYDRAULIC REFERENCE POINT Total = 18 - --- HANGER SYMBOL SPRKONSHEET: SEE LEGEND WESTERN STATES FIRE PROTECTION COAIAANY-OFFICESLOCATED ALBUQUERQUE/At1STWfOALLASIDEGTURlDENVER/WLUfH/HOUSTON/KALS/ISCITY LAS VEGAS/MINNEAPOLIS /PHOENIX/PORTLAND/RAPID CITY/ ST. PAWL/SALT LACE CITY/SEATTLE Phone: 425-881-0100 Fax: 425.881-3030 SPRK ON JOB: 18 ` BRANCHLINE RESTRAINT DATE 07/21/08 817 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-256 08-S-028 FILE COPY FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Escape Outdoors 817 Southcenter Mall Permit No.: 08-S-028 Date: February 1, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 20' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. All references are NFPA 13, 2007 Edition. N © M.E.P.CAD, Inc. Rfi AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:38AM Page 1 Hydraulic Summary Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Job Job Number K50195 Design Engineer Martin Sokulski Job Name HH Escape Outdoors State Certification/License Number WESTESF136QF Address 1 817 Southcenter Mall AHJ City of Tukwila Address 2 Job Sde Southcenter Mall City Stale , Zip Code Tukwila WA I 98188 Drawing Name FP01.cad System Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 1500.00ft2 (Actual 1335.69ft2) Additional Hose Supplies Node Flow(qpm) Number Of Sprinklers Calculated 11 Coverage Per Spnnkler 130 AuloPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Il Total Hose Streams 250.00 / 1/ ` System Flow Demand 298.12 Total Water Required (Including Hose Allowance) 548.12 1_; ' j, Cci. n„ Maximum Pressure Unbalance In Loops 0.000 —� -� N?_/If Maximum Velocity Above Ground 12.78 between nodes 54 and 99 Maximum Velocity Under Ground 1.13 between nodes 1 and 446 Volume capacity of Wet Pipes 2965.36gal Volume capacity of Dry Pipes 2.96ft3 Supplies Node Hose Flow (gpm) Static Residual Flow (psi) (psi) (gpm) Available @ Total Demand Required (psi) (gpm) (psi) Safety Margin (psi) 1 1 250.00 140.000 20.000 10900.00 1_ 139.525 548.12 54.234 1 85.291 Contractor` . Contractor Number K50195 Contact Name Martin Sokulski Contact Title PM Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7108 180th Ave NE FAX 425.881.3030 Address 2 E-mail martin.sokulski@wsfp.us City State Redmond WA Zip Code 98052 Web -Site N © M.E.P.CAD, Inc. Rfi AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:38AM Page 1 Summary Of Outflowing Devices Job Number: K50195 Report Description: HH Escape Outdoor Actual Flow Device (gpm) Minimum Flow K -Factor Pressure (gpm) (K) (psi) c> Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 108 26.92 26.00 I 5.6 23.108 Sprinkler 115 28.32 26.00 5.6 25.568 Sprinkler 111 27.42 26.00 5.6 23.979 Sprinkler 114 28.14 26.00 5.6 25.245 Sprinkler 112 27.43 26.00 5.6 23.992 Sprinkler 110 27.12 26.00 5.6 23.461 Sprinkler 107 26.91 26.00 5.6 23.098 Sprinkler 104 26.61 26.00 5.6 22.585 Sprinkler 106 26.77 26.00 5.6 22.851 Sprinkler 102 26.47 i 26.00 5.6 22.343 c Most Demanding Sprinkler Data (1J ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:40AM Page 2 Report Description: Job Number: K50195 © M.E.P.CAD, Inc. rfg AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:40AM Page 3 Node I Elevation(Foot) 1 Fittings I Pressure(psi) I Discharge(gpm) 17 14-6 E(2-0) 28.768 19 14-6 P0(5-0) 28.8081 23 14-6 E(2-0) 31.122 25 r— 14-6 PO(5-0) 29.891 29 14-6 PO(5-0) 31.463 54 14-6 2P0(8-0) 33.953 55 ! 14-6 2P0(8-0) 34.017 99 14-6 P0(5-0) I 29.907 103 14-6 P0(5-0) 29.247 105 14-6 P0(5-0) 1 28.795 109 14-6 P0(5-0) 28.157 113 14-6 P0(5-0) 28.488 117 14-6 P0(5-0) 27.856 438 1-11 PO(5-0), PO(26-4) 47.077 446 3-10'% BFP(-4.500) 50.781 482 101 1-11 10-0% LtE(16-0) Spr(-21.556) 47.094 21.556 26.00 108 13-7% Spr(-23.108) 23.108 26.92 115 13-7% Spr(-25.568) 25.568 28.32 111 13-7'/% Spr(-23.979) 23.979 27.42 114 13-7% Spr(-25.245) 25.245 28.14 112 13-7% Spr(-23.992) 23.992 27.43 110 13-7'% Spr(-23.461) 23.461 27.12 107 13-7% Spr(-23.098) 23.098 26.91 104 13-7% Spr(-22.585) 22.585 26.61 106 13-7% Spr(-22.851) 22.851 26.77 102 13-7% Spr(-22.343) 22.343 26.47 1 -4-0 S 54.234 r298.12 © M.E.P.CAD, Inc. rfg AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:40AM Page 3 Hydraulic Analysis,. Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Pipe Type Diameter Flow Velocity HWC Friction Loss Length 1 Pressure Length !Summary Length . Downstream Upstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Total Qt Route 1 DR 1.049 Q=26.00 9.65 C=120 0.211434 j 35-3 Pf 9.144 101 10-0% q=26.00 K=5.6 21.556 Spr(-21.556) 8-0 Pe -1.933 17 14-6 28.768 3E(0-0), 4E(2-0) 43-3 Pv BL 1.610 Q=26.00 4.10 C=120 0.026249 1-6'% Pf 0.040 17 14-6 28.768 Pe 19 14-6 28.808 1 1-6'% Pv BL 1.610 Q=52.92 8.34 C=120 0.097746 I 11-1 Pf 1.083 19 14-6 28.808 Pe 25 14-6 29.891 I 11-1i Pv BL 1.610 Q=80.34 12.66 C=120 0.211619 7-2% Pf 4.063 25 14-6 29.891 12-0 Pe 54 14-6 33.953 2LtE(2-0), PO(8-0) 19-2% Pv CM 4.260 Q=161.45 3.63 C=120 0.006735 9-6 Pf 0.064 54 14-6 33.953 I Pe 55 14-6 34.017 9-Pv CM 4.260 Q=298.12 6.71 C=120 0.020943 260-11 Pf 7.604 55 14-6 34.017 102-2 Pe 5.455 438 1-11 47.077 2P0(26-4), 2fE(8-11'/2), 363-1 Pv CV(28-11'/2), GV(2-7%) FM 8.329 Q=298.12 1.76 C=120 0.000800 5-7 Pf 0.017 438 1-11 47.077 16-0 Pe -0.000 482 1-11 47.094 LtE(16-0) 21-7 Pv FM 10.420 Q=298.12 1.12 C=120 0.000269 26-5'/ Pf 4.529 482 1-11 47.094 83- Pe -0.842 446 3-10% 50.781 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5Y Pv UG 10.400 Q=298.12 1.13 C=140 0.000204 109-2 Pf 0.045 446 3-10'/2 50.781 111-7II Pe 3.407 1 -4-0 54.234 E(35-1), 3LtE(25-6), S 220-9'/J Pv Gib Route 2 DR 1.049 Q=26.47 9.83 C=120 0.218568 22- Pf 5.901 102 13-7%z q=26.47 K=5.6 22.343 Spr(-22.343) 5- Pe -0.388 117 14 6 27.856 2E(0-0), PO(5-0) 27- Pv BL 1.610 Q=26.47 4.17 C=120 0.027135 11-1 Pf 0.301 117 14-6 27.856 Pe 109 14-6 28.157 11-1 Pv BL 1.610 Q=53.08 8.37 C=120 0.098309 11-1 Pf 1.090 109 14-6 28.157 Pe 103 14-6 29.247 11-1 Pv BL 1.610 Q=80.21 12.64 C=120 0.210969 10-7% Pf 4.771 103 14-6 29.247 12-0 Pe 55 14-6 34.017 2LtE(2-0), PO(8-0) 22-7% Pv Route 3 DR 1.049 Q=26.61 9.88 C=120 0.220755 22-0 Pf 5.960 104 13-7'/2 q=26.61 K=5.6 22.585 Spr(-22.585) 5-0 Pe -0.388 109 14-6 28.157 2E(0-0), PO(5-0) 27-0 Pv a. Route 4 DR 1.049 Q=26.77 9.94 C=120 0.223156 22-0 Pf 6.025 106 13-7%2 q=26.77 K=5.6 22.851 Spr(-22.851) 5-0 Pe -0.388 113 14-6 28.488 2E(0-0), PO(5-0) 27-0 Pv BL 1.610 Q=26.77 4.22 C=120 0.027704 11-1 Pf 0.307 113 14-6 28.488 Pe 105 14-6 28.795 11-1 Pv BL 1.610 Q=53.68 8.46 C=120 0.100371 11-1 Pf 1.112 105 14-6 28.795 Pe 99 14-6 29.907 11-1i Pv BL 1.610 Q=81.11 12.78 C=120 0.215391 6-9% Pf 4.046 99 14-6 29.907 12-0 Pe 54 14-6 33.953 2LtE(2-0), PO(8-0) 18-9''/z! Pv Q. Route 5 DR 1.049 Q=26.91 9.99 C=120 0.225385 22-0 Pf 6.085 107 13-7% q=26.91 K=5.6 23.098 Spr(-23.098) 5-0 Pe -0.388 105 14-6 28.795 2E(0-0), PO(5-0) 27-0 Pv Gib Route 6 DR 1.049 Q=26.92 9.99 C=120 0.225478 1 22-0 Pf 6.088 108 13-7'% q=26.92 K=5.6 23.108 Spr(-23.108) 1 5-0 Pe -0.388 19 14-6 28.808 2E(0-0), PO(5-0) 1 27-0 Pv v Route 7 DR 1.049 Q=27.12 10.07 C=120 0.228664 22-0 Pf 6.174 110 13-7'/2 q=27.12 K=5.6 23.461 Spr(-23.461) 5-0 Pe -0.388 103 14-6 29.247 2E(0-0), PO(5-0) 27-0 Pv Route 8 (IM, ©M.E.P.CAD, Inc. 419 AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:41 AM Paae 4 Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Velocity K -Factor HWC Friction Loss !Length I Pressure Pt Pn Fittings 1 Eq. Length Summary j Total Length , DR 1.049 Q=27.42 10.18 C=120 111 13-7% q=27.42 K=5.6 23.979 25 14-6 29.891 GO Route 9 0.233331 Spr(-23.979) 2E(0-0), PO(5-0) 22-0 Pf 6.300 5-0 Pe -0.388 27-0 Pv DR 1.049 Q=27.43 10.18 C=120 0.233449 112 13-7% q=27.43 K=5.6 23.992 Spr(-23.992) 99 14-6 29.907 2E(0-0), PO(5-0) Route 10 DR 22-0 Pf 6.303 5-0 Pe -0.388 27-Q Pv 114 29 BL 1.049 13-7% 14-6 Q=28.14 10.45 C=120 0.244698 q=28.14 K=5.6 25.245 31.463 1.61 Spr(-25.245) 2E(0-0), PO(5-0) 22-0 Pf 6.607 5-0 Pe -0.388 27-0, Pv -•-- 29 14-6 55 14-6 31.463 34.017 2LtE(2-0), PO(8-0) I I -L rr 12-0 Pee 23-2 Pv Z.004 Route 11 DR 1.049 Q=28.32 10.51 C=120 0.247600 22-0 2-d 24-0 Pf Pe Pv 5.942 -0.388 115 13-7'% q=28.32 K=5.6 23 14-6 25.568 Spr(-25.568) 31.122 2E(0-0), E(2-0) BL 1.610 Q=28.32 4.46 C=120 0.030739 11-1 11-1 Pf Pe Pv 0.341 23 14-6 29 14-6 31.122 31.463 Equivalent Pipe Lengths of Valves and Finings (C=120 only) 0 Value Multiplier (Actual Inside Diameter 4.87 Value Of C 100 Multiplying Factor 0.713 130 140 1.16 1.33 150 1.51 Schedule 40 Steel Pipe Inside Diameter ) = Factor v m.t.r.t;HU. Inc. 4IHAutoSPRINKCR) VR.ri vR 7 R Al n/flnno n.no.., w•• Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Elevation Upstream Discharge K -Factor Pt Pn Fittings ILength I Pressure Pipe Type`Legend Units Legend •=; . Eq. Length Summary Total Length Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Tum 90° cplg Coupling Cr Cross Run CV Check Valve DeiV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%* Elbow Ee2 22Y2° Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap , © M.E.P.CAD, Inc. 4,fi AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:41AM Page 6 Hydraulic Graph Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 (AA. n M_E.P.CAD_ Inc. AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:43AM Page 7 Supply at Node 1 150 Static Pressure 140.000 135 120 105 90 .N _ n _ 75 _ w _ w _ EL' 60 D.548.12 -298.12 with hose @ 54.234 streams 45 30 -System demand curve 10900.00 @ 20.000_ 15 4 kmiluunl minim 111111111 IIIIIIII 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I I t I I(( ) t I I I i I I I t 1 1 I i ( ( I i 0 71002200 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime o/ Test 139.525 @ 548.12 System Demand 298.12 @ 54.234 System Demand (Including Hose Allowance) 548.12 @ 54.234 (AA. n M_E.P.CAD_ Inc. AutoSPRINK® VR5 v5.2.6 01/30/2008 9:08:43AM Page 7 Job Number: K50195 Report Description: HH Escape Outdoors Zone T4 !rl RA G D rAn Inr au Ai ifnAPPIKIKM\Mc vA 2 R 01 /30/2008 9-08.43AM Paae 8 GUARDIAN SECURITY Customer L 1 F E AN ESCAOE OUTDOORS *817 SOUTHCENTER MALL �'r"WWILA, WA 98188 D PROPERTY PROTECTION Project ESCAPE OUTDOORS Project # 54505 List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: JUNE,02,08 Item Qty. Manuf. Model Description Unit Pri Total Price A 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) .18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) > 47) 48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard HH Escape Outdoors Remote Area: 1st Floor #817 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS OH Group II MAX. COVERAGE per HEAD 130 Ft2 DENSITY .20 GPM / Ft2 for 1335 Ft2 SPRINKLER Reliable Model F1FR ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI • RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 298.1 GPM © 47.1 PSI At time of Design 71-0, 4 MI MO MEI LIU 1=1 EXISTING 4" TEN -4 ! ,711/2. -6 C: r` ;S.' 11 2 Co 13-7 clg. 4 14-21A EAST RISER ROOM (for hydraulic reference) General Notes 1. Western States Fire Protection to add new pendent heads and branchlines. in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations).. 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to. remain. Western States Fire Protection will modify the existing system onlyin the areas of work. All other areas. are not in contract and WSFP is not responsible for exiting conditions. Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth oundnd(0 Berea Inch Rod Coupling Ag ThrRe d et Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan 9-O cIC S Ring Note on Plan: Henget Number end' At Dimension wiTELIIIIMOno FW. co SWIVEL SWAY I0ACE FITTING FI0.1000 "FAST CLAMP SWAY BRACE ATTACHMENT LATERAL LINE RESTRAINTS NON -THREADED BRACE PPE PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT big] NON.T11READEO BRACE PIPE ACCEEPTE fUKWILA FIRE DEPART En Please call: 575.4402 and give this job, No. -ii id exact address for shut', i „,,Airt or restoration approval, LATERAL BRANCHLINE RESTRAINT nese nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subect to errors and omissions which do not authorize violations of adopted standaras and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void thi.,acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date:Si By: / Si I -. FIRE PROTECTION PLAN LEVEL 1 3/1011=1-0" VICINITY MAP (Suite#1460) SCALE; NTS SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE DESCRIPTION Sprinkler Legend APPROVAL: City of Tukwila SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. HYDRAULIC REFERENCE POINT HANGER SYMBOL 17 5.6 Pendent %' White 155°F 1 Total =18 5.6 Pendent Chrome 155°F MFR./MODEL Reliable F1FR SSP Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF Reliable G4QR Concealor CONT. No.: K50195 DRAWN BY: Martin Sokulski SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: 18 01 /30/08 WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/DALLAS/DECATUR/DENVER/DULUTH/HOUSTON/ KANSAS CITY LAS VEGAS /MINNEAPOLIS /PHOENIX / PORTLAND / RAPID CITY /ST. PAUL /SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 HH Escape Outdoors 817 Southcenter Mall Tukwila,WR 98188 pAID FIRE PROTECTION PLAN LEVEL 1 SHEET FP -1 OF t'R, J 3 : ZU08 Tukvvila Fire ( ESCAPE OUTDOORS FIRE ALARM SYSTEM TUKWILA, WASHINGTON r SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UV3ER SHEET TITLE FA -01 SYSTEV \FOVATIO\ FA -02 TYPICAL DETAILS - WIRI\G A\D V OU \TI \G FA -03 FRE ALA V SYSTEM FLOOR PLA\ FA -04 SYSTEM CALL U LATI O \ S (c E\EAL), RISE; SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 416 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO 414 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWD 416 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD 416 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR 414 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR 414 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWD 418 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED 418 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED 418 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO 416 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO 414 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT DF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR. TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROvI AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM . SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 2 2 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B -1 LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ® SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS DUCT HOUSING TSM MODULE VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING IN/ 1-1/2" EXT. SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM L c FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING n FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. Q FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM B 10 WP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. IN FZELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. • F.B.O. ACC t tED VERT IN ELD JUNCTI❑N BOX F.B.D. 1 F.B.❑. / N/A VERIY `' z Q ,, / Without Comments mi r�tw A.F.F. ABOVE FINISHED FLOOR N/A N/A As Noted I Per The AttachedLetter N/A F.B.O. FURNISHED BY OTHERS N/A i nAmplans have been revi d by The Tukwila Firel/A Prevention Bureau for conformance with current city standards. Acceptance is N/A NOT APPLICABLE N/A cuhiect to errors and on ,5Pons which do not autlitig 4e violations of adopt VA standards and orainances. The responsibility for the design CCCCC U,❑.N. UNLESS OTHERWISE NOTED N/A adequacy of ests totally with the designer. AdFii i ts, deletions or revisipmo these drawings attar'A this date will void this,acceptance and will require a WP WEATHERPROOF DEVICE N/A resubmittal of revised Jrawinus for subsequent approval. N/A NN Final acceptance is subject to field test and inspection by N A RED AS BUILT ADD DR CHANGE N/A The Tukwila Fire, Prevention Bureau., N/A N/ N/A Date: D By:`0.4" " d comptete+ Fire DepE Certificate r AC RI ITI T N/A 164944 to the In M BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A OTICE , signed, Tukwila rtment Pre-test nust be presented spector prior to commencement of Acceptance Testing of any Fire Alarm TUKWILA FIRE DEPARTMEIN1 Please call: 575-440Z and give this job and exact address for shut. Gown or restoration approval Copyright 2006 by Guardian Security Systems, and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. FBE .. 2008 Tukwila Fire Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS w I- < D 5/15/08 o CCCCC SCALE: 1/8" =1' DRAWN BY: (.ANDERSON c) CA n .OB NUMBER:54505 r SHEET DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE Moo - 0 DUCT DETECTOR LOCATION FROM XLS CONTROL PANEL OR SI - PREVIOUS ADDRESSABLE DEVIL END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 GROUND m 0 m Lr) O O HTRI—R OSTATUS LED CO 0 N.O. 0 COM 0 NC NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L _ + NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING- \ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE 11}.AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE L(-) FROM XLS CONTROL PANEL OR {(4.) PREVIOUS ADDRESSABLE DEVICE (-) END OF LINE DEVICE RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTI❑N, 0 + TB1 sam 123456 TB2 C D 654321 0 0 0 0 (3.6K 1/4W) SUPERVISED SWITCH GROUND NOTE: ; ; ; Ji ; J 0 O O HTRI—D OSTATUS LED Co m 0 A �0 NOT USED O FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 CND N AC `Iop 0 PAD -3 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 0 0 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3,6K 1/4W) .."SUPERVISED /Th SWITCH NAC -4 NAC -3 NAC -2 NAC -1 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE + DEVICE LOOP T. NOT USED REMOTE v_ DEVICE LOOP 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �IN EOL T M-1 0 • e 0 CC_ COI e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NOPE FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) C'V' CABLE) (STR❑BE) SPEAKER (0 0 EARTH GROUND -.(+)TO NEXT DEVICE OR ) (-) STOP IF LAST DEVICE 66 STR❑BE—) (STROBE) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F., 4S DEEP BOX W/ 1-1/2" EXTENSION RING • (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE To NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERA�I�IN TEMPERATU E: +32' F (0 C) TO 100' F (338" C) HUMIDITY: 0--9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) > DATA IN (+) DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJLINCTION WIlli DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE-r-- ( EVICEF ( ) DATA OUT 1 ) (+) DATA OUT J7 CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT T�.�..- BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTI❑N B❑X---- MOUNTED ON \\ CEILING, FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT TO NEXT DEVICE CADDY BAR SMOKE DETECTOR -- SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT I\ST ADDRESSABLE N T1,4TING DEVICES U\TIL PREPROGRAMMED WITH DEVICES ADDRESS. LL Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z w DESCRIPTION SHOP DRAWINGS w 0 1) 0 7 C co CC co JOTD 0 J 0 2zQ w �© Q I- 1 -CO z D 2 w= cc =Q W < !E : W O J 0 LI' W /SCALE: 1/8"=1' I -- Z 0 0 cc z c� z J U 0 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER:54505 SHEET FA -02} 1 ©12 '1s 2 v 1s,2v 1 3c - ,2V 2I L -- T JJ r - :o NORTH NORTH ii izt \ I'\ EOL ; Si 19.8 V • ESCAPE OUTDOORS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG NO S: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO— NSTALL ADDRESSABLE INITIATI DEVICES UNTIL PREPROGRAMMED WITI- DEVICES ADDRESS. G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1,0 c0 ON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 9 ««< 1 CCCO J r � O 2 2z O w�0 a u c� z Jew= O=Q W < CL w oGQ_`5 Q �h.- 0 �CALE: 1 /8"=1 DRAWN BY: I -ANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: .,10B NUMBER:545O5 j SHEET FA-03� L ALL. OFF 11(.4 -•• M 1: L.) -7- 1000 • , - „ - r-. A E-3 F1' R (DEVI E3 E. 1v 1:1 \ 11i 11 W . 111,; 11 --- rm. rn 1010 _I I I 11 3GAI..L[:RIE : 1E1 _1\4 1 570 1 1ii '\i11 1 :-)5(1) Th LL LJ 10201 ,U1 1.545 1';') LiJ ECTR!AL ROOL,• R Evl BREW NORTH MEW', "Ar'• A P A RI I\11-: S "YE AH,./1 SHOP P AC I FIG: 3J N WEAR V‘i 111 116, ASq.p. E. 33 3 THE 10/4\ LK. INC; GO. 1 00 b E b e 1 0 1540 -11 REG CUM R AGE. KISER LOADING DOCK - ----- 0_ ESCAPE OUTDOORS WESTFIELD SOUTHCENTER MALL CO LLJ EY. 1 25 L_LJ 0 17, NG'S P2 [-T-71 ETT.1 LL <a: I 135 1.1401 I'LL SYSTEM CALCULATIONS 1 STARE SCALE 11374 S,2V0 S,2V02S,2V 0 2S,2V 75 C 75 C 15 15 EOL -S1 EX D,ID DI LI CI 21 • 21 E E RISER DIAGRAM BATTERY SIZING CALCULATION ESCAPE OUTDOORS ESCAPE OUTDOORS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE Panel: ESCAPE OUTDOORS Wire Resistance 162 H 11 2 < Date: May 30, 2008 CURRENT TOTAL= Current Load: Standby: Alarm: S1 Current Load: Standby: Alarm: - QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 ...... SET -MC @15CD 64 128 Device Type Qty Amps Total Amps Total 0 Device Type 98 Qty Amps Total Amps Total ( WL * 2 )* (R/ft) HFP-11 2 SET -MC @75CD 0.0022 0.0022 0.0023 ____ Total Device Load, Amps (1) 0.94 2 SET -MC @110CD 233 466 AD2-P 2 0.0635 0.0635 0.064 0.128 SET-HMC-C@115CD Main System Board 0 1 0.03 0.03 0.030 0.030 0.58 HTR -R SET-HMC-C@177CD 3 0.009600 0.0096 0.021 0.063 SET -MC @15CD (E= I * R) _ 0 SET -HMC @135CD 318 0.064 HTRI-D 0.001600 19.82 0.0035 SET -HMC @185CD 445 SET -MC @30CD --- 2 - -- -- 0.098 0.196 0 ICP -B6 64 0 0.005 SET -MC @75CD 1 Z-MC@30CD 98 0 0.175 0.175 0 SET-MC-CW@110CD 233 0 SET -MC @110CD ______ 2 0.233 0.466 mA= 944 12 191 19.81581504L 944 DEVICES= Werner* SET-HMC-C@115CD __ Notification MVP.10frl Appliance .V.WIPINIW•laiWry.-114y•IVIS....MMIONMMAIN DWVVIVM•MS.1•Wielarnef,MISOVV•••••••FTWOOMNOVYWOMI Circuit 0.318 evnm PROJECT: WESTFIELD SOUTHCENTER MALL SET-HMC-C@135CD --- _ ESCAPE OUTDOORS1....,...i, . i. Wire Resistance '2i58'.., 0.318 Date: _ ._ May 30, 2008 CURRENT TOTAL= 7.2 0.0731 Amps 0.191 Amps SET-HMC-C@185CD 0.445 _ QTY Device Type Alarm Current Alarm Total Wire Size Wre Length Voltage at EOL Circuit Total ZR -MC @15CD 1 70.7V1/8 1.8 7.2 0.064 0.064 Standby Current Load: [Total Wire Resistance 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @30CD .. ......._...m....... .._..................._ _ WL * 2 )* (Rift) 0.098 0 0 . Total Device Load, Amps (1) 0.01 0 HCP 0 0(Total ....._ _....._ 0.0015 Cct Load) Alarm Current Load: 0.191 Amps For 5 Minutes= 0.016 Amp -hours Voltage Drop ( E) 0.01 0 0.03 Amps 0.931 Amps (E= I* R) _ 0 0 0 _........_ , EOL Voltage 20.39 0 • 0 0(20.4 25% Derating= 2.213 Amp -hours 0 Standby Current Load: 0 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 0 DEVICES 4 TOTAL mA= 7.2 14 191 20.39290397 7.2 Alarm Current Load: 0.931 Amps For 5 Minutes= 0.078 Amp -hours Total System Current Load: 2.213 Amp -hours 25% Derating= 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION co ON (9 (f) LU LU (f) (/) u (f) r -- TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL DATE Panel: ESCAPE OUTDOORS Wire Resistance 162 H 11 2 < Date: May 30, 2008 CURRENT TOTAL= 944 CIRCUIT: S1 - QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 ...... SET -MC @15CD 64 128 Total Wire Resistance ( R ) 0.62 0 SET -MC @30CD 98 0 ..._ ( WL * 2 )* (R/ft) 2 SET -MC @75CD 175 _ 350 ____ Total Device Load, Amps (1) 0.94 2 SET -MC @110CD 233 466 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 ---. Voltage Drop ( E ) 0.58 0 SET-HMC-C@177CD 445 0 (E= I * R) _ 0 SET -HMC @135CD 318 0 ------ EOL Voltage 19.82 0 SET -HMC @185CD 445 0 --- -- - -- -- (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 - __________ ______ 6TOTAL mA= 944 12 191 19.81581504L 944 DEVICES= Werner* __ Notification MVP.10frl Appliance .V.WIPINIW•laiWry.-114y•IVIS....MMIONMMAIN DWVVIVM•MS.1•Wielarnef,MISOVV•••••••FTWOOMNOVYWOMI Circuit Detail evnm PROJECT: WESTFIELD SOUTHCENTER MALL Panel: _ ESCAPE OUTDOORS1....,...i, . i. Wire Resistance '2i58'.., Date: _ ._ May 30, 2008 CURRENT TOTAL= 7.2 CIRCUIT: SPEAKER CIRCUIT _ QTY Device Type Alarm Current Alarm Total Wire Size Wre Length Voltage at EOL Circuit Total 4 70.7V1/8 1.8 7.2 , [Total Wire Resistance ( R ) 0.99 0 0 0( .. ......._...m....... .._..................._ _ WL * 2 )* (Rift) o 0 0 . Total Device Load, Amps (1) 0.01 0 0 0(Total ....._ _....._ Cct Load) 0 0 0 -- Voltage Drop ( E) 0.01 0 0 0 (E= I* R) _ 0 0 0 _........_ , EOL Voltage 20.39 0 • 0 0(20.4 , - E) 0 0 0 0 0 0 DEVICES 4 TOTAL mA= 7.2 14 191 20.39290397 7.2 VOLTAGE DROP CALCULATION co ON (9 (f) LU LU (f) (/) u (f) r -- TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 < <<<< .11 cc (i) w z 0 ci) z0 0 0 11.1 ›- CD ‘ALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/12/08 BACKROUND PLAN PROVIDED BY: Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved NUMBER:54505 SHEET --"N FA -04} OWNER. HH Escape Outdoors J� i t L V. I dry. �V � i ,�+ ��� o D D o 0 00 4 Ill l� Ill' VI :� �igh _- , , , = to. -�` ; _ f; J ,.3 , . 41) - '' 5-27 341/2 41:14 gR- Fir -1-. — _— --- + I O L. �O ©„ A , i . i ON H - / - �- ',� .F E�. 7k Fv�� �Sr•6+ *1\6 ZONE T4 I ,i 1 SYSTEM RISER = r ,o, Ir °) I, .-E ,, s �� r Q Cr) il 1 li Co)= - , /----------'• P=oi CI N /0 / , , N-. r 1 se 1 1 0 v- z ( HH Escape Outdoors ,, � .J �a-9'r2�,r Remote Area: 1st Floor #817 ® -,--0 �- O 0 1— ® 'r I '-- i1.1..):) - 114 c CALCULATION DESIGN CRITERIA: #13-2007 `c 11/21 °� M .�'�.�� /t c , 1 12 co1 M iSTANDARD_NFPA ' EXISTING 4" TENANT MAIN_t�1�.D2 `� II 0..-'1rv-1 et '1.4 NSIT., 4 5-0 0)-�_OCCUPANCY 1. 4 b 41: CLAssOH Group 4 _ ARCHITECT. Rolluda Architects _ 61 h _ MAX. COVERAGE per HEAD 130 Ft2 6"4' � © + �9-6 /2 O � .I � 11/214-2 j J2 2-5l2 8-7 11-0 11-0 6-5 7 11-0 11-0 4-01 1 6-11 /2 8-8 13-0 13-0 r.1 r DENSITY_.20 GPM ! Ft2 for 1335 Ft21-d x'02 40 JP 13-7 clg. -C-2 V EAST RISER ROOM (for hydraulic reference) SPRINKLER Reliable Model F1FR M ©� o c .Z GWB 1.02 r ORIFICE 1 /2" K=5.6 V.% _,,c, , , x�� 4: c._M dD+0, vliff WATER FLOW INFORMATION . STATIC 140 PSI i- k�� -' RESIDUAL 20 PSI r M�r 10900 GPM FLOW© r:General I Notes AT 298.1 RISER, SYSTEM @ REGI I7F�: GPM � 47.1 PSI � . �-��r2/ ioJ 5-4 1. Western States Fire Protection to add new pendent Sprinklers in the new store shall be spaced in accordance heads and branchlines with NFPA in new tenants ace. #13 Ordinary hazard space. with }�`� * At time of Design 2 Group II.0.20gpm/ft2 for 1500.00ft ---I 1 O �� �_1�/ I ®/ OQ �0 109 �, 0 2. 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent The buildina is constructed with non-combustible materials and qualifies length included in calculations). as unobstructed construction. Ordinary ( t' r / �,> €c`' © �� `� 3. 4. 5. All hanger assemblies shall be spaced and installed in accordance Branchline and arm-over pipe is black Schedule 40 pipe. All new threaded fittin s are cast iron Q class 125 or ductile iron class with NFPA & manufacturer's specifications. 150. °' � __ } 6. The owner is responsible for all a❑❑ropriate maintenance of sprinkler system in accordance with �� �- 49 Cr D� o ,k'` -�° �0- Cy 4:1P ® �• .� /- 7. 8. NFPA as well as 4 ate &local codes. 111 The nwner is resnne,sihle for the freeze nrntection of all sprinkler system that are not designed for freezing conditions. 111 Existing fire sprink►w:� system to remain. Western States Fire Protection only in the arPac of All in WSFP piping and components will modify the existing system is �: ® *ND( EOE OO�• © � �4P�' \ o r, to <<\''r to) work. other areas are not existing conditions. contract and not responsible for ENGINEER. Martin Sokulski �� per, Hanger - -' ,i .�. 4 No. 07C HILTI Kwik Bott 111 / `o,a.a A -� I Q. no, ,,t / - `VO E)�N , 6--:,) ' Rod L B� r.,„„„,,,, / ConstructionuA O1 . t. -- I' 05 /Z i( Al Thom' Rod `L� -L/: r Red LM ReMan of Comm+. to \ P1 , vM.d L of Pp. Nut NI �3-x'! 1 2;Ta� fD1 (O 1 F 1 ., N< ' I r Q O �� Notion Flan: Hangar Number and 'A'Dimension 4 2-1 ... 12-0 9-0 cl 'co \ c jG4, to C II44. 1 :�l I '!i co YF R'RR BOLT R 1N•EAIBID LBlGM 1 .I R,M•El6mIBIGT , .I ®Y O ,� �� FO.BW 6� -1. •l- 9 O i \ 1 1 -- 1 .� it , ,,.[ SWNO. SIHAr -' BRACE fRTNG FG.ra -_ d� NO-Tit, : . t1NEL SY(ATe - .e A77ACi.HTI \\ 7 -1 1'- \ __ 4'-f jam® �� \ ( BRACE PIPE 1 �, .L. \ y� ��{- ��FG.1 GIPLP w BRACE PIPE -_ .� _ ti ___ . �, SlYAr BRACE A77ACN�Nf \i/ co �_ ,co -. ,cOk \ - ; { l % , 1 UNE HPE r • - FI(iM� HPE CLAMP O --- `\ i I LATERAL UNE RESTRAINTS FOR svArBRAc. -" r �`�' ® RAL BRANCCE NE RESTRAINT �����, TaoN(riTHiEADm BRACE HPE "•FtFADED BRKE HPE l LLilw LL CONTRACTOR. Rolluda Architects ` C� - • ' LATERAL BRAN HLINE it s STRAINT 1gWP-j - ' `^JWP /`�--, , i ' -. N Am .w�WWU.I 2RWJiYYIY'lH, / 1 5\�� ! t ` i , i , 3 • _.. .._, i ._ ____ .... • ;Mrsi I� 5 �: 4 I F I 0 mit MO FIREPROTECTION PLAN LEVEL 1 x. La.XJ_ 3116"= 1'-0" VICINITY MAP(Suite#817) SCALE: NTS �� SYMBOL LEGEND REVISIONS Sprinkler Legend APPROVAL: City of Tukwila " ":� ^.• : Western States hire • Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA Lic. #: WESTESF1360F - 98052 HH Escape Outdoors 817 Southcenter Mall � Q p Q � /� / /� 98188 Tukwila V V!'1 9 81 88 FIRE PROTECTION PLAN LEVEL 1 �>��� FP-1 OF 1 T SYM. SIN _� QTY.= _ K SPRAY ORIF. FIN. TEMP. MFR./MODEL - - 1 2-WAY EARTHQUAKE BRACE No. DESCRIPTION DATE 17 5.5 Pendent %:" White 155°F Reliable F1FR SSP cow. NO.: K50195 - X - 4-WAYEARTHQUAKE BRACE i 1 5.6 Pendent /i' Chrome ° 155 F Reliable G4QR Concealor DRAWN BY: Martin Sokolski HYDRAULIC REFERENCE POINT Total = 18 - --- HANGER SYMBOL SPRKONSHEET: SEE LEGEND WESTERN STATES FIRE PROTECTION COAIAANY-OFFICESLOCATED ALBUQUERQUE/At1STWfOALLASIDEGTURlDENVER/WLUfH/HOUSTON/KALS/ISCITY LAS VEGAS/MINNEAPOLIS /PHOENIX/PORTLAND/RAPID CITY/ ST. PAWL/SALT LACE CITY/SEATTLE Phone: 425-881-0100 Fax: 425.881-3030 SPRK ON JOB: 18 ` BRANCHLINE RESTRAINT DATE 07/21/08