Loading...
HomeMy WebLinkAboutPP - 821 SOUTHCENTER MALL - TORRID - PERMITS AND PLANS821 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-391 08-S-442 FILE COPY FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Torrid 821 Southcenter Mall Permit No.: 08-S-442 Date: September 3, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. TORRID FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUM3ER SHEET TITLE FA -01 SYSTEM INFORVIATIO\ FA -02 TYPICAL DETAILS - WIRING A\D MOU\TI \G FA -03 FIRE ALARIv SYSTEV FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (0 E\EAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL ' NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 2. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES. SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND,. 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:34:56 AM, Oce 9400 -II EPC-M1_1.x.pc3 QUANTITY 2 1 4 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 45 DEEP VERIFY IN FIELD El DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD -B"-1 LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS ® (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE L C (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) ZH-MC-W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING CoWP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) 1 MR 1 MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.❑, F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A z Ci z cc 44xz z • 1743 IST AVE. SO., SEATTLE, WASHINGTON 98131+ FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: El Aq Noted In Red DESCRIPTION SHOP DRAWINGS N/A N/A N/A E/A PerTheAttached DATE 7/22/08 N/A N/A N/A 1 nese plans have been reviewed Prevention' j3preaufor conforrnan standards. Acceptance is tkubiect F_<-<<<< AS BUILT REMOVE N/A N/A N/A omiSsiolfs wilit. h do Ho autiloi;Le stanctarad\t-r(i oroinances. The re adequacy of design rests totally w N/A N/A NOT APPLICABLE N/A N/A N/A TED U.❑.N, UNLESS OTHERWISE NOTED N/A N/A N/A Without Comments' NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to Commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and terr„inattion of the testing. Date: 7�/� B Letter by The Tukwila Fire ce with current city to errors and violations of adopted sponsibility for the ith the designer. @v these drawings atter and will require a subsequent approval test and inspection b u.. 0200 V.v8 frt 7/6-5/ 5 IUKWILA FIRE DEPARTI4s::JtL Please call: 575-4407 and give this job No. oe and exact address for shut. clown or restoration approval, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO co J 00 _.10) W �z EEG Z Q �'S Iw 0 (/) IJL T C t CV Ci co CALE: 1/8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: / SHEET FA -01 El Aq Noted In Red WP WEATHERPROOF DEVICE N/A N/A N/A E/A PerTheAttached RED AS ADD ORLT CHANGE N/A N/A N/A 1 nese plans have been reviewed Prevention' j3preaufor conforrnan standards. Acceptance is tkubiect GREEN AS BUILT REMOVE N/A N/A N/A omiSsiolfs wilit. h do Ho autiloi;Le stanctarad\t-r(i oroinances. The re adequacy of design rests totally w BLUE AS BUILT NOTES TO CAD N/A N/A N/A Additions, du.etions or revisions this date MgOoid this.acceptance resubmittal of revised drawings for Final acceptance is subject to fielc The Tukwila Fire, Prevention Bure NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to Commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and terr„inattion of the testing. Date: 7�/� B Letter by The Tukwila Fire ce with current city to errors and violations of adopted sponsibility for the ith the designer. @v these drawings atter and will require a subsequent approval test and inspection b u.. 0200 V.v8 frt 7/6-5/ 5 IUKWILA FIRE DEPARTI4s::JtL Please call: 575-4407 and give this job No. oe and exact address for shut. clown or restoration approval, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO co J 00 _.10) W �z EEG Z Q �'S Iw 0 (/) IJL T C t CV Ci co CALE: 1/8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: / SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LIBEL SCPLE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE PREVIOUS ADDRESSABLE DEVIC-� FROM XLS CONTROL PANEL OR O DUCT DETECTOR LOCATION 1 END OF LINE DEVICE(3.6K 1/4W) 5 1 - SUPERVISED SWITCH GROUND Lr) HTRI-R OSTATUS LED co 0 N.O. 0 COM CO 0 N,C NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL L'L'LE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLEf DEVICE NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - OUTLET SAMPLING-----\ TUBE INLET SAMPLING '\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE ( ) FROM XLS CONTROL PANEL OR ,{(+) PREVIOUS ADDRESSABLE DEVICE (")—p RELAY CONTACTS (4.OA @ 125VAC) (4.°A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. + TB1 123456 HCP TB2 6543'21 0 END OF LINE DEVICE (3,6K 1/4W) 0 CV 0 SUPERVISED SWITCH GROUND 0 Lf') © © HTRI-D OSTATUS LED CO 0 NOT USED END OF LINE DEVICE 3,6K 1/4W) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL ` EL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC TM ro min 1-y T 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 24K ,m TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ?NAC -4 NAC -3 2 NAC -2 NAC -1 UPERVISED 1 SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 0 0 0 0— 470 OHMS EOL TSM -1 Q 0 i__±:3cs - 0 91. TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NUE V EARTH GROUND -,1.(+)TO NEXT DEVICE OR -->(-) STOP IF LAST DEVICE HORN STROBE I STROBE WIRING DIAGRAM LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 0 0 EDL HORN/STROBE 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DEVICE IS LISTED Fr AIR VOL CITY APPLICATIONS OF "-4000 FT IN WHEN USED I ON,AINCTION WITH DUCT HOUSINr: AD -11P OR AD-11XPR HFP-11 SMOKE DETECTOR — DB -11 STANDARD SMOKE DETECTOR BASE ADDRESSABLE DEVICE FROM PREVIOUS OR POWER SOURCE DATA IN DAT N EW TO NEXT DEVICES-- (-) DATA OUT +) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX N WITH 1-1/2" EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX , MOUNTED ON CEILINGI FLEX \` / / JUNCTI❑N BOX / MOUNTED AGAINST / CEILING SUPPORT / il T o 0 O 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR —� SMOKE DETECTOR MOUNTING SCALE:NONE M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:35:01 AM, Oce 9400 -II EPC-M1_1.x.pc3 of \•--- SUSPENDED ILLUMINATED CEILING DO NO INSTA_L ADDRESSABLE INITBATD\G DEVICES L \TIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z z CO O' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4.990 TEL. (206) 622-654.5 RELEASE/REVISIONS z 4 DESCRIPTION SHOP DRAWINGS w c0 0 CV c•I r. 0 z C T T 0 CSI coco 00 J O) Q EFj WTO z_ - � in C� Q Q=� W lY (5))s a)D 1— CL SCALE: 1/8"=1' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: FA -029 SHEET EOL—S1 19.96V EX FACP NORTH TORRID WESTFIELD SOUTHCENTER MALL SCALE 118'=1' FLAG NO FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM " DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. MADrawings\Westfield Southcenter Mall\TENANT IMPROVEMENTWORRID-Fire Alarm - #\FA Dwgs`TORRID.dwg, 7/28/2008 11:35:06 AM, Oce 9400 -II EPC-M1_1.x.pc3 SLA\S \OT ADDROV DO NOT INS AL_ ADDRESSABLE IN T ATI DEVICES UNTIL PREPROGRAMMED WeTI— DEVICES ADDRESS. NG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ro 1 CY‘z 0 Rd Z 11111 < y W J W"7 -C W NOW LjQ mil CET) I FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS w 1- 00 0 N N O z C C C CO CO J T J DO 2 �z W Q Wz w 1- w= oC=¢ � O Q Wo CC co T�co H SCALE: 1/8"=1' LL DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET FA -03) 7 FAMILY A, EEs I -r f i 1\, ,��'YI , a, I CO 0 CORDON'S JEWELERS L1J L. CLQ E' JOURNEYS BASKI N ROBBINS I,!E N 1.;' 1 r, C-4.0 NORTH 1_) J J `I SU N GLASS H T '. - H1J1 C1-1 0 r.r, LATE R i f `> C A. IL-1 F R A fry RAOTH ::RHOOD mATER PIERCING LIDS 1:3Al�lf� =j'j 1E CI ,11` 11601 TR ASH c.) 14 t3 0J 20C•1, 0 `a- C_D [1210, 1 [0]I rl H (1) L.J TORRID WESTFIELD SOUTHCENTER MAIL 14201 -7 "12201 r, r./_'ter 11 [12.3u1 _.�. C .i w 1 C_) C) ,.. <1; 11235 l i is EXISTING FOOTLOCKER Tr`t;ANCY ...... ..... 12^F0 IJ 1q SCALE 1132'=1' 2S 2S 2S 2S 75 C 75 C 30 C 15 2S 15 C 15 EOL -S1 2S FA -BOX EX FACP 0 D,I D 2I Mg IT SYSTEM CALCULATIONS BATTERY SIZING CALCULATION TORRID Notification Appliance TORRID Detail FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: WESTFIELD SOUTHCENTER MALL Panel: TORRID Wire Resistance Date: July 28, 2008 CURRENT TOTAL= CIRCUIT: Current Load: Standby: Alarm: Current Load: Standby: Alarm: Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 69 138 Device Type 0.62 Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total 400 HFP-11 0.0022 0.0022 0.0023 0.71 0 SET -MC @11 OCD 233 0 (Total Cct Load) AD2-P 0 1 0.0635 0.0635 0.064 0.064_ Main System Board 1 0.03 0 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 SET -HMC @135CD ZH-MC-CW @15CD • 0 2 0.069 0.138 19.96 HTRI-D SET -HMC @185CD 445 0.001600 0.0035 ZH-MC-CW @30CD (20.4 - E) 1 1 - Z-MC@15CD 64 0.111 0.111 ICP -B6 0.005 0 Z-MC@30CD 98 ZH-MC-CW @75CD2 0.2 0.400 0 SET-MC-CW@110CD 233 0 SET -MC @110CD DEVICES= 6 TOTAL mA= • 713 0.233 191 19.958767081 713 SET HMC-C@115CD 0.318 SET-HMC-C@135CD 0.318 0.0731 Amps 0.106 Amps SETHMC-C@185CD 0.445 ZR -MC @ 15 C D 1 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD 0.098 HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.743 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours [ Alarm Current Load: 0.743 Amps For 5 Minutes= 0.062 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.978 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.978 Amp -hours i Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION z c ca z 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 W CC w LU J W c z DESCRIPTION W 00 N <I< C C< J 0 W Cr) O w cr) co cc ao ., w0 CC cn °C w Z � CC W OCD ¢ (1) W�_ 0 CO CV -- W I-- (1) ��>- VJ SCALE: 1/8"=1' DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION �OB NUMBER: SHEET \ M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:35:12 AM, Oce 9400 -II EPC-M1_1.x.pc3 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04 Notification Appliance Circuit Detail 1.62 713 PROJECT: WESTFIELD SOUTHCENTER MALL Panel: TORRID Wire Resistance Date: July 28, 2008 CURRENT TOTAL= CIRCUIT: S1 - QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 69 138 Total Wire Resistance (R) 0.62 1 SET -MC @30CD_ 111 111 (WL * 2) * (R/ft) 2 SET -MC @75CD 200 400 Total Device Load, Amps (1) 0.71 0 SET -MC @11 OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.44 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 • 0 EOL Voltage 19.96 0 SET -HMC @185CD 445 0 (20.4 - E) 1 - Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 6 TOTAL mA= • 713 12 191 19.958767081 713 z c ca z 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 W CC w LU J W c z DESCRIPTION W 00 N <I< C C< J 0 W Cr) O w cr) co cc ao ., w0 CC cn °C w Z � CC W OCD ¢ (1) W�_ 0 CO CV -- W I-- (1) ��>- VJ SCALE: 1/8"=1' DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION �OB NUMBER: SHEET \ M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:35:12 AM, Oce 9400 -II EPC-M1_1.x.pc3 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04 TOILET 3RM CL5' TOILET�P-) CL4 10'-6" A.F.F: ALCOVE 1 CL4 10'-0" A.F.F. MIRROR (P_, SOFFIT 11JJ CL4 9'-0" FTG. RM. TYPICAL 9'-6" A.F.F. {cL2 12'-6" A.F.F. CEILING TILE TRACK LIGHTS MOUN-ED TO UNDESSID OF T-5AR CEILING GRI 1 (TYP.) I" WATER LINE 6" CRON MOLDING. 6" SPKLR MAIN PAINTED P-3 (F.G.I.G.) CL2 12'-6" A.F.F. CEILING TILE 1x'+TLS t eT'1 T rI .:a 'i d8 n L' Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 13 hours in advance of the date you want an inspection. CL4 MIRROR P 1 SOFFIT \\\\\\\\\\\\\\\\\\\\\\\\\lion\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\`\\\\\\\\O\\\\\ca \ \\ \ \. . `\ \\\��\\\\\\\\\\\t\\\, \\o\\\\o\\\t\\\\\\\\\\\ \\\\\\ �\�p����ti�\\oo�u���\\\\\\\\\\\\\\\\\ t\\\\ .. !:' �v, ` i 0 f� _ � - - \ off �;=:••`.�' � �\ VP �. % � , l , ` ` �� � • %/:. ;: :%jam\tib Yi \\-•• � 'UM MIMI MN' o.si uu an sa �aa�aao_[saeiwri�r �� �sae� - 'r' ..�._ �eaca�taea \��,:���\�� F':.:,�!::'i O, � /, \ �•�, ' G \ •:off. • r E TAIL 1- ON ON =ORM MINL iimain ittim 1 no --m"'%"K: . 1210 .- lip, I mall manl 11 I II Int MI .. i■lni -' l '.i118ii■ MI if i :�nFa AM Int Mg 1IIMI IFIMIMBEIV 12'-0" A.F.F. SOFFIT P-4 'Y old stamps must be i; ;spe: ted before pipe is lung. Do not paint piping prior tC) hydrostatic t ostati C approval. SII 14Il -SPENDED METAL GRID FOR 1II \ 777777GRAPHIGS, ETC. G.G. TO TRIM 1 \�\` AT LIGHTS ON SITE. F.O.I.G. )•4" D1=EP TRACK LIGHT TROUGH. SEE STOREFRONT SECTIONS. STOREFRONT S16N ATTACHED TO SOFFIT. SEE STOREFRONT ELEVATION 4 SECTION n —mac I/2" CLEAR TEMPERED -1 6LAS5 TRANSOM WINDOW IN PAINTED WOOD STOPS • 13 ILI CL1 1T-0" A.F.F. SOFFIT P 4 t' 12'-0" A.F.F. .. SOFFIT W 1 f. !hese p'::::,-)7, .v TU a�rla l=ire Preve:•St-:i: a :, eur�ent city k C'tanciar ..; �.• t , ( is <,nd _ ? cr; iiS.:,1 �, ix. ,» .: _ riadopted 1 sty lic c a s r<<. - .. , ........;:.-:!:/,'; y for the .' adcgiu: i j r, ,:. ,.i , ��, Jnef. Aa1;l=.te{, ,, , .,. - - . ,.. r� 4sings atter i this G.`;:`� 3 . ..: .i.:: -ii i"€- ;wire a resubr;itat .a ; _ .,_.;;- _. _ wa=nt approval. a Fine! ;:CG' __ . - _ i`!';;ect to fled test and Inspection b% The Tuk r.k' i Prevcriiion Bureau. Date: By: D :14 ik Without Comments /? N:..> 1 111 Red 1.:r rrs ;A.'':. i.cCC! Letter —... �� � e"s��ffi� ei!— - oma-- �lauras®mE� feex es�seesa sieic® e e� �� �\ ®� •---_..._...._.�asr��ra � s s ES:=15 ssa®nsts sss��sa a s�®gy m =.1:11 :31aMt:1 12 es 1== = mm� Ess saw:ate `�\\ 4\`\\ \ �.\ \ gip\\ � CL6 8'-0" A.F.F. -HR. RATED PONYWALL ON HAL=L4e4A r PLATFORM CL4 81-0" A.F.F. 6" GROWN MOLDING. 5/8" TYPE 'X' GYP. BD. HALLWAYFAIN'FED • _.._.....--- i✓EAxl1RB- 55E•-DSTAIL...._. REFLECTED CEILING PLAN ON THIS SHEET. 12'-6" A.F.F. CEILING TILE TRAC< LIGHTS MOUNTED TO UNDERSIDE OF T -BAR CEILING GRID. (TYP.) I" WATER LINE MALL DUCT @ 3" SPKLR 13'-3" 14'-4" A.F.F. MAIN 0 12'-8" 2-O" 2'-l0" i 4'-I0" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 38 - Add Reliable Model G4A Quick Response Concealed Sprinkler Heads 155°1/2 x Y2 Total: 38 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD RDD PIPE SWIVEL RING STEEL JOIST/TRUSS A ..amommmisasamm.ae Israoalr Z tat •=mita,s=, Avanabie in a. I c I I Szes ; ;- 4• 1".- - i= - ( •;4:c __ ,. . x I x '� • :C .l= ,f :4 1 New -Tee -Loaf ala-'hPaicai Branch Connector From. WR D • rri-=.-sem r= rn _inv+•+*r SCALE: 1/4" = 1'-O" NoTE: FULLY RECESSED SPRINKLERS WITH WHITE BLOW -OFF GAPS AT ALL GYP. 4 T -BAR CEILINGS. r ruKwfu4 FIRE DEPART/4EW Please call: 575-4402 and give this job • No. On and exact address for Shut+ Town or restoration approvor CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 10 Torrid 821 Southcenter Mall Tukwila, WA DATE: fid) p2) DRAWN: 0 SCALE: Iy -- /V / 821 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-391 08-S-442 FILE COPY FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Torrid 821 Southcenter Mall Permit No.: 08-S-442 Date: September 3, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. TORRID FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUM3ER SHEET TITLE FA -01 SYSTEM INFORVIATIO\ FA -02 TYPICAL DETAILS - WIRING A\D MOU\TI \G FA -03 FIRE ALARIv SYSTEV FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (0 E\EAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL ' NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 2. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES. SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND,. 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:34:56 AM, Oce 9400 -II EPC-M1_1.x.pc3 QUANTITY 2 1 4 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 45 DEEP VERIFY IN FIELD El DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD -B"-1 LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS ® (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE L C (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) ZH-MC-W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING CoWP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) 1 MR 1 MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD JUNCTI❑N BOX F.B.❑, F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A z Ci z cc 44xz z • 1743 IST AVE. SO., SEATTLE, WASHINGTON 98131+ FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: El Aq Noted In Red DESCRIPTION SHOP DRAWINGS N/A N/A N/A E/A PerTheAttached DATE 7/22/08 N/A N/A N/A 1 nese plans have been reviewed Prevention' j3preaufor conforrnan standards. Acceptance is tkubiect F_<-<<<< AS BUILT REMOVE N/A N/A N/A omiSsiolfs wilit. h do Ho autiloi;Le stanctarad\t-r(i oroinances. The re adequacy of design rests totally w N/A N/A NOT APPLICABLE N/A N/A N/A TED U.❑.N, UNLESS OTHERWISE NOTED N/A N/A N/A Without Comments' NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to Commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and terr„inattion of the testing. Date: 7�/� B Letter by The Tukwila Fire ce with current city to errors and violations of adopted sponsibility for the ith the designer. @v these drawings atter and will require a subsequent approval test and inspection b u.. 0200 V.v8 frt 7/6-5/ 5 IUKWILA FIRE DEPARTI4s::JtL Please call: 575-4407 and give this job No. oe and exact address for shut. clown or restoration approval, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO co J 00 _.10) W �z EEG Z Q �'S Iw 0 (/) IJL T C t CV Ci co CALE: 1/8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: / SHEET FA -01 El Aq Noted In Red WP WEATHERPROOF DEVICE N/A N/A N/A E/A PerTheAttached RED AS ADD ORLT CHANGE N/A N/A N/A 1 nese plans have been reviewed Prevention' j3preaufor conforrnan standards. Acceptance is tkubiect GREEN AS BUILT REMOVE N/A N/A N/A omiSsiolfs wilit. h do Ho autiloi;Le stanctarad\t-r(i oroinances. The re adequacy of design rests totally w BLUE AS BUILT NOTES TO CAD N/A N/A N/A Additions, du.etions or revisions this date MgOoid this.acceptance resubmittal of revised drawings for Final acceptance is subject to fielc The Tukwila Fire, Prevention Bure NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to Commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and terr„inattion of the testing. Date: 7�/� B Letter by The Tukwila Fire ce with current city to errors and violations of adopted sponsibility for the ith the designer. @v these drawings atter and will require a subsequent approval test and inspection b u.. 0200 V.v8 frt 7/6-5/ 5 IUKWILA FIRE DEPARTI4s::JtL Please call: 575-4407 and give this job No. oe and exact address for shut. clown or restoration approval, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO co J 00 _.10) W �z EEG Z Q �'S Iw 0 (/) IJL T C t CV Ci co CALE: 1/8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 7/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: / SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LIBEL SCPLE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE PREVIOUS ADDRESSABLE DEVIC-� FROM XLS CONTROL PANEL OR O DUCT DETECTOR LOCATION 1 END OF LINE DEVICE(3.6K 1/4W) 5 1 - SUPERVISED SWITCH GROUND Lr) HTRI-R OSTATUS LED co 0 N.O. 0 COM CO 0 N,C NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL L'L'LE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLEf DEVICE NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES, MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - OUTLET SAMPLING-----\ TUBE INLET SAMPLING '\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE ( ) FROM XLS CONTROL PANEL OR ,{(+) PREVIOUS ADDRESSABLE DEVICE (")—p RELAY CONTACTS (4.OA @ 125VAC) (4.°A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. + TB1 123456 HCP TB2 6543'21 0 END OF LINE DEVICE (3,6K 1/4W) 0 CV 0 SUPERVISED SWITCH GROUND 0 Lf') © © HTRI-D OSTATUS LED CO 0 NOT USED END OF LINE DEVICE 3,6K 1/4W) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL ` EL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC TM ro min 1-y T 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 24K ,m TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE ?NAC -4 NAC -3 2 NAC -2 NAC -1 UPERVISED 1 SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 0 0 0 0— 470 OHMS EOL TSM -1 Q 0 i__±:3cs - 0 91. TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NUE V EARTH GROUND -,1.(+)TO NEXT DEVICE OR -->(-) STOP IF LAST DEVICE HORN STROBE I STROBE WIRING DIAGRAM LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. R 0 0 EDL HORN/STROBE 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DEVICE IS LISTED Fr AIR VOL CITY APPLICATIONS OF "-4000 FT IN WHEN USED I ON,AINCTION WITH DUCT HOUSINr: AD -11P OR AD-11XPR HFP-11 SMOKE DETECTOR — DB -11 STANDARD SMOKE DETECTOR BASE ADDRESSABLE DEVICE FROM PREVIOUS OR POWER SOURCE DATA IN DAT N EW TO NEXT DEVICES-- (-) DATA OUT +) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX N WITH 1-1/2" EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX , MOUNTED ON CEILINGI FLEX \` / / JUNCTI❑N BOX / MOUNTED AGAINST / CEILING SUPPORT / il T o 0 O 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR —� SMOKE DETECTOR MOUNTING SCALE:NONE M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:35:01 AM, Oce 9400 -II EPC-M1_1.x.pc3 of \•--- SUSPENDED ILLUMINATED CEILING DO NO INSTA_L ADDRESSABLE INITBATD\G DEVICES L \TIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved z z CO O' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4.990 TEL. (206) 622-654.5 RELEASE/REVISIONS z 4 DESCRIPTION SHOP DRAWINGS w c0 0 CV c•I r. 0 z C T T 0 CSI coco 00 J O) Q EFj WTO z_ - � in C� Q Q=� W lY (5))s a)D 1— CL SCALE: 1/8"=1' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: FA -029 SHEET EOL—S1 19.96V EX FACP NORTH TORRID WESTFIELD SOUTHCENTER MALL SCALE 118'=1' FLAG NO FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM " DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. MADrawings\Westfield Southcenter Mall\TENANT IMPROVEMENTWORRID-Fire Alarm - #\FA Dwgs`TORRID.dwg, 7/28/2008 11:35:06 AM, Oce 9400 -II EPC-M1_1.x.pc3 SLA\S \OT ADDROV DO NOT INS AL_ ADDRESSABLE IN T ATI DEVICES UNTIL PREPROGRAMMED WeTI— DEVICES ADDRESS. NG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved ro 1 CY‘z 0 Rd Z 11111 < y W J W"7 -C W NOW LjQ mil CET) I FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS w 1- 00 0 N N O z C C C CO CO J T J DO 2 �z W Q Wz w 1- w= oC=¢ � O Q Wo CC co T�co H SCALE: 1/8"=1' LL DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: SHEET FA -03) 7 FAMILY A, EEs I -r f i 1\, ,��'YI , a, I CO 0 CORDON'S JEWELERS L1J L. CLQ E' JOURNEYS BASKI N ROBBINS I,!E N 1.;' 1 r, C-4.0 NORTH 1_) J J `I SU N GLASS H T '. - H1J1 C1-1 0 r.r, LATE R i f `> C A. IL-1 F R A fry RAOTH ::RHOOD mATER PIERCING LIDS 1:3Al�lf� =j'j 1E CI ,11` 11601 TR ASH c.) 14 t3 0J 20C•1, 0 `a- C_D [1210, 1 [0]I rl H (1) L.J TORRID WESTFIELD SOUTHCENTER MAIL 14201 -7 "12201 r, r./_'ter 11 [12.3u1 _.�. C .i w 1 C_) C) ,.. <1; 11235 l i is EXISTING FOOTLOCKER Tr`t;ANCY ...... ..... 12^F0 IJ 1q SCALE 1132'=1' 2S 2S 2S 2S 75 C 75 C 30 C 15 2S 15 C 15 EOL -S1 2S FA -BOX EX FACP 0 D,I D 2I Mg IT SYSTEM CALCULATIONS BATTERY SIZING CALCULATION TORRID Notification Appliance TORRID Detail FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: WESTFIELD SOUTHCENTER MALL Panel: TORRID Wire Resistance Date: July 28, 2008 CURRENT TOTAL= CIRCUIT: Current Load: Standby: Alarm: Current Load: Standby: Alarm: Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 69 138 Device Type 0.62 Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total 400 HFP-11 0.0022 0.0022 0.0023 0.71 0 SET -MC @11 OCD 233 0 (Total Cct Load) AD2-P 0 1 0.0635 0.0635 0.064 0.064_ Main System Board 1 0.03 0 0.03 0.030 0.030 HTR -R 2 0.009600 0.0096 0.021 0.042 SET -HMC @135CD ZH-MC-CW @15CD • 0 2 0.069 0.138 19.96 HTRI-D SET -HMC @185CD 445 0.001600 0.0035 ZH-MC-CW @30CD (20.4 - E) 1 1 - Z-MC@15CD 64 0.111 0.111 ICP -B6 0.005 0 Z-MC@30CD 98 ZH-MC-CW @75CD2 0.2 0.400 0 SET-MC-CW@110CD 233 0 SET -MC @110CD DEVICES= 6 TOTAL mA= • 713 0.233 191 19.958767081 713 SET HMC-C@115CD 0.318 SET-HMC-C@135CD 0.318 0.0731 Amps 0.106 Amps SETHMC-C@185CD 0.445 ZR -MC @ 15 C D 1 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD 0.098 HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 0.743 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours [ Alarm Current Load: 0.743 Amps For 5 Minutes= 0.062 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.978 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.978 Amp -hours i Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION z c ca z 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 W CC w LU J W c z DESCRIPTION W 00 N <I< C C< J 0 W Cr) O w cr) co cc ao ., w0 CC cn °C w Z � CC W OCD ¢ (1) W�_ 0 CO CV -- W I-- (1) ��>- VJ SCALE: 1/8"=1' DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION �OB NUMBER: SHEET \ M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:35:12 AM, Oce 9400 -II EPC-M1_1.x.pc3 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04 Notification Appliance Circuit Detail 1.62 713 PROJECT: WESTFIELD SOUTHCENTER MALL Panel: TORRID Wire Resistance Date: July 28, 2008 CURRENT TOTAL= CIRCUIT: S1 - QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 69 138 Total Wire Resistance (R) 0.62 1 SET -MC @30CD_ 111 111 (WL * 2) * (R/ft) 2 SET -MC @75CD 200 400 Total Device Load, Amps (1) 0.71 0 SET -MC @11 OCD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.44 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 • 0 EOL Voltage 19.96 0 SET -HMC @185CD 445 0 (20.4 - E) 1 - Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 6 TOTAL mA= • 713 12 191 19.958767081 713 z c ca z 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 z 0 W CC w LU J W c z DESCRIPTION W 00 N <I< C C< J 0 W Cr) O w cr) co cc ao ., w0 CC cn °C w Z � CC W OCD ¢ (1) W�_ 0 CO CV -- W I-- (1) ��>- VJ SCALE: 1/8"=1' DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE:7/22/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION �OB NUMBER: SHEET \ M:\Drawings\Westfield Southcenter Mall\TENANT IMPROVEMENTS\TORRID-\Fire Alarm - #\FA Dwgs\TORRID.dwg, 7/28/2008 11:35:12 AM, Oce 9400 -II EPC-M1_1.x.pc3 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved FA -04 TOILET 3RM CL5' TOILET�P-) CL4 10'-6" A.F.F: ALCOVE 1 CL4 10'-0" A.F.F. MIRROR (P_, SOFFIT 11JJ CL4 9'-0" FTG. RM. TYPICAL 9'-6" A.F.F. {cL2 12'-6" A.F.F. CEILING TILE TRACK LIGHTS MOUN-ED TO UNDESSID OF T-5AR CEILING GRI 1 (TYP.) I" WATER LINE 6" CRON MOLDING. 6" SPKLR MAIN PAINTED P-3 (F.G.I.G.) CL2 12'-6" A.F.F. CEILING TILE 1x'+TLS t eT'1 T rI .:a 'i d8 n L' Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 13 hours in advance of the date you want an inspection. CL4 MIRROR P 1 SOFFIT \\\\\\\\\\\\\\\\\\\\\\\\\lion\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\`\\\\\\\\O\\\\\ca \ \\ \ \. . `\ \\\��\\\\\\\\\\\t\\\, \\o\\\\o\\\t\\\\\\\\\\\ \\\\\\ �\�p����ti�\\oo�u���\\\\\\\\\\\\\\\\\ t\\\\ .. !:' �v, ` i 0 f� _ � - - \ off �;=:••`.�' � �\ VP �. % � , l , ` ` �� � • %/:. ;: :%jam\tib Yi \\-•• � 'UM MIMI MN' o.si uu an sa �aa�aao_[saeiwri�r �� �sae� - 'r' ..�._ �eaca�taea \��,:���\�� F':.:,�!::'i O, � /, \ �•�, ' G \ •:off. • r E TAIL 1- ON ON =ORM MINL iimain ittim 1 no --m"'%"K: . 1210 .- lip, I mall manl 11 I II Int MI .. i■lni -' l '.i118ii■ MI if i :�nFa AM Int Mg 1IIMI IFIMIMBEIV 12'-0" A.F.F. SOFFIT P-4 'Y old stamps must be i; ;spe: ted before pipe is lung. Do not paint piping prior tC) hydrostatic t ostati C approval. SII 14Il -SPENDED METAL GRID FOR 1II \ 777777GRAPHIGS, ETC. G.G. TO TRIM 1 \�\` AT LIGHTS ON SITE. F.O.I.G. )•4" D1=EP TRACK LIGHT TROUGH. SEE STOREFRONT SECTIONS. STOREFRONT S16N ATTACHED TO SOFFIT. SEE STOREFRONT ELEVATION 4 SECTION n —mac I/2" CLEAR TEMPERED -1 6LAS5 TRANSOM WINDOW IN PAINTED WOOD STOPS • 13 ILI CL1 1T-0" A.F.F. SOFFIT P 4 t' 12'-0" A.F.F. .. SOFFIT W 1 f. !hese p'::::,-)7, .v TU a�rla l=ire Preve:•St-:i: a :, eur�ent city k C'tanciar ..; �.• t , ( is <,nd _ ? cr; iiS.:,1 �, ix. ,» .: _ riadopted 1 sty lic c a s r<<. - .. , ........;:.-:!:/,'; y for the .' adcgiu: i j r, ,:. ,.i , ��, Jnef. Aa1;l=.te{, ,, , .,. - - . ,.. r� 4sings atter i this G.`;:`� 3 . ..: .i.:: -ii i"€- ;wire a resubr;itat .a ; _ .,_.;;- _. _ wa=nt approval. a Fine! ;:CG' __ . - _ i`!';;ect to fled test and Inspection b% The Tuk r.k' i Prevcriiion Bureau. Date: By: D :14 ik Without Comments /? N:..> 1 111 Red 1.:r rrs ;A.'':. i.cCC! Letter —... �� � e"s��ffi� ei!— - oma-- �lauras®mE� feex es�seesa sieic® e e� �� �\ ®� •---_..._...._.�asr��ra � s s ES:=15 ssa®nsts sss��sa a s�®gy m =.1:11 :31aMt:1 12 es 1== = mm� Ess saw:ate `�\\ 4\`\\ \ �.\ \ gip\\ � CL6 8'-0" A.F.F. -HR. RATED PONYWALL ON HAL=L4e4A r PLATFORM CL4 81-0" A.F.F. 6" GROWN MOLDING. 5/8" TYPE 'X' GYP. BD. HALLWAYFAIN'FED • _.._.....--- i✓EAxl1RB- 55E•-DSTAIL...._. REFLECTED CEILING PLAN ON THIS SHEET. 12'-6" A.F.F. CEILING TILE TRAC< LIGHTS MOUNTED TO UNDERSIDE OF T -BAR CEILING GRID. (TYP.) I" WATER LINE MALL DUCT @ 3" SPKLR 13'-3" 14'-4" A.F.F. MAIN 0 12'-8" 2-O" 2'-l0" i 4'-I0" Design per NFPA 13 - Ordinary Hazard Occupancy - 130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 38 - Add Reliable Model G4A Quick Response Concealed Sprinkler Heads 155°1/2 x Y2 Total: 38 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD RDD PIPE SWIVEL RING STEEL JOIST/TRUSS A ..amommmisasamm.ae Israoalr Z tat •=mita,s=, Avanabie in a. I c I I Szes ; ;- 4• 1".- - i= - ( •;4:c __ ,. . x I x '� • :C .l= ,f :4 1 New -Tee -Loaf ala-'hPaicai Branch Connector From. WR D • rri-=.-sem r= rn _inv+•+*r SCALE: 1/4" = 1'-O" NoTE: FULLY RECESSED SPRINKLERS WITH WHITE BLOW -OFF GAPS AT ALL GYP. 4 T -BAR CEILINGS. r ruKwfu4 FIRE DEPART/4EW Please call: 575-4402 and give this job • No. On and exact address for Shut+ Town or restoration approvor CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 10 Torrid 821 Southcenter Mall Tukwila, WA DATE: fid) p2) DRAWN: 0 SCALE: Iy -- /V /