HomeMy WebLinkAboutPP - 827 SOUTHCENTER MALL - BARE ESSENTIALS - PERMITS AND PLANS827 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-233 08-S-159 s FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Bare Escentuals 827 Southcenter Mall Permit No.: 08-S-159 Date: May 2, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. in (Hydraulic Summary, - 1 Job Number: KS0377 Report Description: Ordinary Group II Job Job Number KS0377 Design Engineer ' Adam Kanter Job Name Bare Escentuals State Certification/License Number WESTESF136QF Address 1 827 Southcentner Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Tukwila Wa 98188 Drawing Name FP-1.cad System -. - I Remote Areas) Most Demanding Sprinkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy - Ordinary Group II _ Hose Allowance At Source 250.00 Density 0.200gpm/ft2 Area of Application 955.84ft2 (Actual 955.84ft2) Additional Hose Supplies Node Flow(qpm) Number Of Sprinklers Calculated 12 Coverage Per Sprinkler 130.00ft2 01.(4.11144 1 ,il 1 ��� ". TT � �� y ' ., Total Hose Streams 250.00, Allowance) System Flow Demand Total Water Required (Including Hose 333.43 583.43• Maximum Pressure Unbalance In Loops 0.000 1 /� Nroka 464/10 Maximum Velocity Above Ground 16.89 between nodes 39 and 33 Maximum Velocity Under Ground 1.26 between nodes 1 and 271 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2168.37gal 9.11 gal Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand Required Safety Margin (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.467 583.43 57.074 82.392 Contractor I Contractor Number KS0377 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection 1 Phone 1 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 E-mail City State Zip Code Redmond ' WA 98052 Web -Site d�l, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:28PM Page 1 II Summary Of Outflowing .Devices . . Job Number: KS0377 Report Description: Ordinary Group H Actual Flow Minimum Flow K-Factor Pressure Device (gpm) (gpm) (K) (psi) Sprinkler 106 27.67 26.00 5.6 24.422 Sprinkler 104 27.32 26.00 5.6 23.802 c> Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 105 27.61 26.00 5.6 24.308 Sprinkler 102 26.27 26.00 5.6 22.011 Sprinkler 107 28.05 26.00 5.6 25.097 Sprinkler 103 27.20 26.00 5.6 23.598 Sprinkler 110 28.67 26.00 5.6 26.203 Sprinkler 112 29.23 26.00 5.6 27.254 Sprinkler 109 28.21 26.00 5.6 25.376 Sprinkler 111 29.10 26.00 5.6 27.008 Sprinkler 108 28.08 26.00 5.6 25.148 r' Most Demanding Sprinkler Data LAy © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:32PM Page 2 111 Node Analysis Job Number: KS0377 Report Description: Ordinary Group 11 Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 16 14'-6 E(2'-0) 27.772 19 14'-6 PO(5'-0) 27.799 21 14'-6 E(2'-0) 31.484 25 14'-6 PO(5_0) 31.609 27 14'-6 P0(5-0) 28.401 31 14'-6 PO_(5'-0) 32.656 33 14'-6 PO(5'-0) 30.498 38 14'-6 2P0(8'-0) 36.357 39 14'-6 2P0(8'-0) 36.437 46 14'-6 PO(5'-0) 34.122 48 14'-6 PO(5'-0) 35.322 52 14'-6 P0(5'.±:)) 33.026 54 14'-6 PO(5'-0) 34.998 58 14'-6 P0(5'-01 32.723 263 1'-11 PO(5'-0), PO(26'-4) 49.896 271 3'-10'/4 BFP(-4.500) 53.612 307 1-11 . LtE(16'-0) 49.918 _ 106 15'-0 • Spi(-24.422) 24.422 27.67 104 11'-0'/4 Spr(-23.802) 23.802 27.32 101 11'-6'/4 Spj 21.5 21.556 26.00 105 11'-6 Spr(_24.308) 24.308 27.61 102 11'-6'% Spr(-22.01j) 22.011 , 26.27 ' 107 11'-6 Spr(-25.097) 25.097 ____ 28.05 103 11'-6'/4 Spr 23_598) 23.598 27.20 • 110 11'-6iSpr(-26.203) 26.203 28.67 112 11'-6'/, Spr(-27.254) I 27.254 29.23 LL 109 _ 11'-6 Spre_25.376) 25.376 _ 28.21 111 11'-61,4 Spr(-27.008) 27.008 29.10 108 11'-6Spr(-25.148) _ 25.148 28.08 1 -4'-0TS 57.074 333.43 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:36PM Page 3 NI Hydraulic Analysis 1 Job Number: KS0377 Report Description: Ordinary Group 11 Pipe Type Diameter Flow Velocy HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length v Route 1 DR 1.0490 Q=26.00 9.65 C=120 0.211435 26'-71/2 Pf 7.532 101 11'-6'% q=26.00 K=5.6 21.556 Spr(-21.556) 9'-0 Pe -1.289 19 14'-6 27.799 2E(2'-0), PO(5'-0) 35'-7% Pv BL 1.6100 Q=53.67 8.46 C=120 0.100341 6'-0 Pf 0.602 19 14'-6 27.799 Pe 27 14'-6 28.401 6'-0 Pv BL 1.6100 0=79.95 12.60 C=120 0.209700 10'-0 Pf 2.097 - 27 14'-6 28.401 Pe 33 14'-6 30.498 10'-0 Pv BL 1.6100 Q=107.15 16.89 C=120 0.360497 8'-5% Pf 5.939 33 14'-6 30.498 8'-0 Pe 39 14'-6 36.437 P0(8'-0) 16'-5%' Pv CM 4.2600 Q=333.43 7.51 C=120 0.025763 226'-11/2 Pf 8.008 _ 39 14'-6 36.437 84'-8'% Pe 5.452 263 1'-11 49.896 E(13'-2), 2fE(6'-9%), CV(28'-11'A), 310'-10 Pv GV(2'-7'h), PO(26'-4) FM 8.3290 Q=333.43 1.96 C=120 0.000984 5-7 Pf 0.021 _ 263 1'-11 49.896 16'-0 Pe -0.000 307 1'-11 49.918 LtE(16'-0) 21'-7% Pv FM 10.4200 0=333.43 1.25 C=120 0.000331 26'-53h Pf 4.536 307 1'-11 49.918 83'-0 Pe -0.842 271 3'-10'34 53.612 4LtE(16'-0), BV(19'-0), BFP(-4.500) 109'-5%Pv UG 10.4000 Q=333.43 1.26 C=140 0.000251 109'-2 Pf 0.055 271 3'-10% 53.612 111'-734 Pe 3.407 1 -4'-0 57.074 E(35'-1), 3LtE(25'-6), S 220'-9'/. Pv .� Route 2 DR 1.0490 Q=26.27 9.75 C=120 0.215561 26'-7% Pf 7.679 102 11'-6% q=26.27 K=5.6 22.011 Spr(-22.011) 9'-0' Pe -1.289 27 14'-6 28.401 2E(2'-0), P0(5'-0) 35-7% Pv GO Route 3 DR 1.0490 Q=27.20 10.10 C=120 0.229894 26'-7'/z Pf 8.190 103 11'-634 q=27.20 K=5.6 23.598 Spr(-23.598) 9'-0 Pe -1.289 33 14'-6 30.498 2E(2'-0), PO(5'-0) 35'-71/2 Pv Route 4 DR 1.0490 0=27.32 10.14 C=120 0.231734 33'-73,4 Pf 9.188 104 11'-034 q=27.32 K=5.6 23.802 Spr(-23.802) 6'-0 Pe -1.506 21 14'-6 31.484 3E(2'-0) 39'-7% Pv BL 1.6100 Q=27.32 4.31 C=120 0.028769 4'-434 Pf 0.125 21 14'-6 31.484 , Pe 25 14'-6 31.609 4'-4'% Pv BL 1.6100 0=54.93 8.66 C=120 0.104729 10'-0 Pf 1.047 25 14'-6 31.609 Pe 31 14'-6 32.656 10'-0 Pv BL 1.6100 Q=82.98 13.08 C=120 0.224677 8'-5% Pf 3.701 31 14'-6 32.656 8'-0' Pe 38 14'-6 36.357 PO(8'-0) 16'-5% Pv CM 4.2600_ Q=167.94 3.78 C=120 0.007244 11'-0 Pf 0.080 38 14'-6 36.357 Pe 39 14'-6 36.437 11-0 Pv Route 5 DR 1.0490 0=27.61 10.25 C=120 0.236287 27'-434 Pf 8.596 105 11'-6 q=27.61 K=5.6 24.308 Spr(-24.308) 9'-0 Pe -1.295 25 14'-6 31.609 2E(2'-0), PO(5.-0) 36'-4% Pv. v Route 6 SP 1.0490 0=27.67 10.27 C=120 0.237312 5'-234 Pf 3.131 106 15'-0 q=27.67 K=5.6 24.422 Spr(-24.422) 8'-0 Pe 0.219 16 14'-6 27.772 4E(2'-0) 13'-2% Pv BL 1.6100 Q=27.67 4.36 C=120 0.029461 0'-11 Pf 0.027 16 14'-6 27.772 Pe 19 14'-6 27.799 0'-11' Pv Route 7 DR 1.0490 0=28.05 10.41 C=120 0.243376 27-434 Pf 8.853 107 11'-6 q=28.05 K=5.6 25.097 Spr(-25.097) 9'-0 Pe -1.295 31 14'-6 32.656 2E(2'-0), PO(5'-0) 36'-4% Pv Route 8 DR 1.0490 0=28.08 10.43 C=120 _0.243831 27'-4'/z' Pf 8.870 108 11'-6 q=28.08 K=5.6 25.148 Spr(-25.148) 9'-0 Pe -1.295 58 14'-6 32.723 2E(2'-0), P0(5'-0) 36'-4'h Pv BL 1.6100 0=28.08 4.43 C=120 0.030271 10'-0 Pf 0.303 58 14'-6 32.723 ' Pe 52 14'-6 33.026 10'-0 Pv [, © M.E.P.CAD, Inc. ;in AutoSPRINKO VR5 v5.2.6 05/01/2008 5:16:40PM Page 4 1 Hydraulic Analysis Job Number: KS0377 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length BL 1.6100 Q=56.29 8.87 C=120 0.109584 10'-0 Pf 1.096 52 14'-6 33.026 Pe 46 14'-6 34.122 10'-0 Pv BL 1.6100 Q=84.96 13.39 C=120 0.234661 1'-61/4 Pf 2.235 46 14'-6 34.122 8'-0 Pe 38 14'-6 36.357 PO(8'-0) 9'-6'/4 Pv GO Route 9 DR 1.0490 10.47 C=120 0.245877 27'-41/2 Pf 8.944 _Q=28.21 109 11'-6 q=28.21 K=5.6 25.376 Spr(-25.376) 9'-0 Pe -1.295 52 14'-6 33.026 2E(2'-0), PO(5'-0) 36'-4% Pv v Route 10 DR 1.0490 Q=28.67 10.64 C=120 0.253277 27'-4Y2 Pf 9.214 110 11'-6 q=28.67 K=5.6 26.203 Spr(-26.203) 9'-0 Pe -1.295 46 14'-6 34.122 2E(2'-0), PO(5'-0) 36'-4'/2 Pv wo Route 11 DR _ 1.0490 Q=29.10 10.80 C=120 0.260472 26'-7Y2 Pf 9.279 _ _ 111 11-6% q=29.10 K=5.6 27.008 Spr(-27.008) 9'-0 Pe -1.289 54 14'-6 34.998 2E(2'-0), PO(5'-0) 35'-7% Pv BL 1.6100 Q=29.10 4.59 C=120 0.032337 10'-0 Pf 0.323 54 14'-6 34.998 Pe 48 14'-6 35.322 10'-0 Pv 1.6100 Q=58.34 9.19 C=120 0.117063 1'-61hPf 1.115 _BL _ 48 14'-6 35.322 8'-0 Pe 39 14'-6 36.437 PO(8'-0) 9'-6'/4 Pv v Route 12 DR 1.0490 Q=29.23 10.85 C=120 0.262660 26'-7'/2 Pf 9.357 _ 112 11'-6% q=29.23 K=5.6 27.254 Spr(-27.254) 9'-0 Pe -1.289 48 14'-6 35.322 2E(2'-0), PO(5'-0) 35'-7V2 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only)II C Value Multiplier Actual Inside Diameter 4.87 ( Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 (sU, ©M.E.P.CAD, Inc. 41AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:40PM Page 5 lig Hydraulic Analysis Job Number: KS0377 Report Description: Ordinary Group II Pipe TypLe Flow VelocityHWC Friction Loss Length Pressure Eq. Length Summary Total Length _Diameter Downstream Elevation Discharge K -Factor Pt Pn Fittings Upstream Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv - Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaiV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11%° Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap . • ©M.E.P.CAD, Inc.AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:40PM Page 6 Hydraulic ,Graph Job Number: KS0377 Report Description: Ordinary Group II 150 Supply at Node 1 135 :Static Pressure 140.000 120 105 90 .N a 75 g to N N a` 60 —333.43 583.43 with hose @ 57.074 streams 45 30 —System 15 demand curve 10900.00 @ 20.000 W I II I I I 111 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 111111111 111111111 J 1 I I I I I I I 0 OW 11002200 3300 4400 5500 6600 7700 8800 9900 Water flow, gpm 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.467 @ 583.43 System Demand 333.43 @ 57.074 System Demand (Including Hose Allowance) 583.43 @ 57.074 (, ©M.E.P.CAD, Inc. lEy� AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:50PM Page 7 Flow Diagram (Top View). Job Number: KS0377 Report Description: Ordinary Group II &.. ©M.E.P.CAD, Inc. iliAutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:54PM Page 8 Customer BARE ESCENTUALS 827 SOUTHCENTER MALL —"KWILA, WA 98188 Project BARE ESCENTUALS Project # LIFE AND AN SECURITY PROPERTY P ROTECTION List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: MAY,23,08 Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) '18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard • GUARDIAN SECURITY LIFE AND PROPERTY PROTECTION Seattle • Tacoma • Poulsbo • Bellingham 1743 First Avenue South Seattle, WA 98134 Tel: 206.622.6545 Fax: 206.341.9928 Letter to Tukwila Fire Dept Attn: To whom it may concern For the tenant space Torrid at Westfield Mall, we originally submitted drawings (which have been approved) that had speaker/strobes when it should have been horn/strobes instead. I have included here in the revision the 3 new sets of drawings, and submittals with the correct parts. I also included a copy of the original approved drawing. Please call me at (206) 359 12 68 with any questions Thanks Raedeit Kifle PM — Guardian Security Customer T,,ORft1D OUTHCENTER VV1LA, WA f31i38 GUARDIAN SECURITY" T f t) N LIPE .A N b PROPERTY PROTEC Project TORRID Project # Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM 'List of Materials Date: 7/22108 Item Qty. Manuf. Model Description Unit Pri Total Pricel 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens HFP-11 HFP-11-relay AD2-P PBA -1191 PBR-1191 PBR-1192 PBR-1193 HTRI-D HTRI-R HCP Siemens ZR-MC-CW,W Siemens ZR-MC-W,W Siemens SET-MC-CW,W Photoelectric Smoke Detector w/DB-11 Base Photoelectric Smoke Detector w/HR relay base Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Linear Beam Smoke Detector w/Backbox Prism Reflector for PBA -1191 w/Backbox 20x20 Reflector Package 10x10 Reflector Package Supervised Addressable Input Module Supervised Addressable Output Relay Module Supervised Addressable Module for Strobes Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator 1' Interior Visual Strobe Annunciator Combination Speaker/Strobe lS ** PAD -3 with BT -33 Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard , FILE COPY • I SHEET INDEX BARE ES TU FIREAL YSTE Ai. TUKWILA,HWASHINGTON GENERAL NOTES SYMBOLS LEGEND SHEET \ U V SH•RIFT- TITLE FA -01 SYS' I \ F ICH vl ATIO\ FA -02 TYP:cAL DETAILS - WHI\G:A\D MOU\TI\C FA -03 PRt ALAV SYSTE FLOCH PLA\ FA -04 SYSTEIv CALCULATIO\S (GE\EAL), SITE PLA CCP!'. vvithoutdoipments• 0 • As Noted'In!Red 0 Per The Attached'Letter • . , !nese plans have been reviewed by The Tuk•Wite. Fire Prevention Bureau for conformance with current cit, standards. Acceptance IS' subject to errors and omissions which do not aUthariz violations Of adopted stanaaras and ordinatteS. The respOnsibility for the adequacy of design restsi totally with the designer. Additions, d& ton or reViSiOns to those drawing' kaltor this date will void this acceptance and will require a' resubmittal or revised draivings.fOr subsequent approval. Final acceptance is subjeet.tOield test and inspection by The Tukwila Fire Prevention', Bureau. Date: • 4 . • • TUKWILA FIRE DEPARTMEittli Please call: 5754404 and give this job .1 and exact address for shuts rk)wn or restoration apiorOVel NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DES GNATION SCHEDULE i„1 WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END : ( h.11 !I: FOR SIEMENS •. DO NOT INSTALL ADDRESSABLE 11\11TIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. • `. .• , 1. NUMBERS ADJACENT TO DEICE 1 SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE!THE, SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT SHALL BE OBSERVED. I . 3. AUDIBLE/VISUAL CIRCUIT WIR,INQ LSUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE Ill 4, INSTALLATION SHALL BE IN ; STFICT ;CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, Lt?CAL ODE(S), AND/OR AUTHORITY 'HAVING JURISDICTION. 5. INSTALLATION MATERIALS (It po UIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS 'a BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIE . I\O$' [ • 6. DETECTORS SHALL NOT BE .1kUN ED IN DIRECT AIR STREAM OF AIR SUPPLYAOTL TS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN W1THH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE ,CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. i :, • 8. INSTALLING CONTRACTOR SHALL. .RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOES. g. FOR ADDITIONAL INSTALLATIO INST1RUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATPN I0UCTIONS. 10. THE 120vac POWER ELECTRIQAL FL< SUPPLYING ,FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE, 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5f2:i,I1N REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED •TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. , 11. ALL HORN/STROBE AND S -I -OBE 'DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPHED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIOW.H. ALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND ,OIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS AREFROM: DEDICATED' CIRCUITS FROM THE 'EMERGENCY GENERATOR., • :1 ! 11 • 15. PER NFPA 72 SECTION 5-.6.1.3 DETECTORS SHALL, NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF:ALL TRADES IS COMPLETE AND , FINAL. . .'. EXCEPTION: WHERE REQUIRED BY THE AUTHORIPC HAVING JURISDICTION. FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEb\l: INSTALLED PRIOR TO FINAL CLEAN-UP BY, ALL TRADES SHALL BE CLEANED OR ,REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7.. . , 16. WIRING SHALL RUN CONTINUOUS YROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO iDEV,ICE WITHOUT SPLICING IN PULL BOXES OR ., OTHER BACK BOXES OF DIFFERENT CIRCUITS. ,, 17. ALL WIRING SHALL BE METEREVVERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEENI CONDUCTORS AND OTHER CIRCUITS PRIOR TO L FINAL EQUIPMENT TRIM. i 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM .RISER WITH A PERMANENT LABEL AT ALL1DEVICES, JUNCTION BOXES AND FACP. . AH' 19. THE ELECTRICAL CONTRACTOR :;;SHALL CLEAN ALL DIRT AND DEBRIS .FROM THE . OUTSIDE AND INSIDE OF TI-i.1,111...ALARM BACK BOXES AND JUNCTION '..BOXE.S." AFTER COMPLETION OF TH ' 1\ .TALLATION. , 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 1A1 GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BEl,WEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. QUANTITY 3 2 2 2 2 EX I SY 0 DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT CP FIRE ALARM F'CONTROL PANEL X LS -V SIEMENS PROVIDED 66" A.F.F. TO TOP A 'FIRE ALARM SDD-C REMOTE ANNUNCIATOR II I •: ' I ,,:, PAD -3 SIEMENS PROVIDED ' .11 REMOTE BOOSTER • ill EX .p.OWER SUPPLY ' I 11-nall .. WITH RELAY HTRI-R SIEMENS 4S DEEP V E R IF Y .' NTERFACE MODULE ' DM ' ',INTERFACE INPUT HTRI-D SIEMENS a INTERFACE MODULE SIEMENS PROVIDED 66" A.F.F. TO TOP 66" A.F.F. TO TOP H CONTROL POINT PODULE 4S DEEP VERIFY IN FIELD HCP SIEMENS 4S DEEP VERIFY IN FIELD REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD }LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS KADDRESSABLE-PHOTO) DB -11 BASE 4S DEEP VV/ 1G RING CEILING DUCT SMOKE DETECTOR . AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD !HEAT DETECTOR s°11771''! KADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S. DEEP W/ 10 RING CEILING El • FIRE ALARM SPEAKER STROBE MOUNT' SET -MC -CW SIEMENS 4S DEEP BOX CEILING VV/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE SET -MC --W SIEMENS 4S DEEP BOX 80" A.F.F. ' (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM WIRE DESIGNATION .SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S 2S ' A V 2V HI .'HX UD • UI M B DATA:LINE-ADDRESSABLE LOOP DOOR.HOLDER POWER - 24VDC DEVICE POWER - 24VDC STROBE CIRCUIT - FEED STROBE CIRCUIT - RETURN ANNUNCIATOR SPEAKER CIRCUIT - FEED SPEAKER CIRCUIT - RETURN REMOTE INDICATION LIGHT. LOW LEVEL AUDIO UNDERGROUND DATA UNDERGROUND INITIATION DOOR HOLDER POWER BEAM DETECTOR POWER TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) TWD #14 FPL/FPLR RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)• TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWO #18 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) TWISTED PAIR RATED, #18 FPL/FPLR RED (JACKET) TWIST.ED,P4IR-RATED #18 FPL/FPLR RED (JACKET) TWD #16 FPL/FPLR RED (JACKET) TWO #14 FPL/FPLR RED (JACKET) FIRE ALARM STROBE ZR -MC -W SIEMENS As BOX 80" A.F.F. • ' (WALL MOUNT) W/ 10 RING TO BOTTOM U.O.N. " , CONDUIT FILL CHART ' '• .., ' ' NO. OF CONDUCTORS VOLTS WIRE SIZE ,TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. • .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END : ( h.11 !I: FOR SIEMENS •. DO NOT INSTALL ADDRESSABLE 11\11TIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. • `. .• , 1. NUMBERS ADJACENT TO DEICE 1 SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE!THE, SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT SHALL BE OBSERVED. I . 3. AUDIBLE/VISUAL CIRCUIT WIR,INQ LSUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE Ill 4, INSTALLATION SHALL BE IN ; STFICT ;CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, Lt?CAL ODE(S), AND/OR AUTHORITY 'HAVING JURISDICTION. 5. INSTALLATION MATERIALS (It po UIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS 'a BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIE . I\O$' [ • 6. DETECTORS SHALL NOT BE .1kUN ED IN DIRECT AIR STREAM OF AIR SUPPLYAOTL TS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN W1THH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE ,CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. i :, • 8. INSTALLING CONTRACTOR SHALL. .RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOES. g. FOR ADDITIONAL INSTALLATIO INST1RUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATPN I0UCTIONS. 10. THE 120vac POWER ELECTRIQAL FL< SUPPLYING ,FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE, 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5f2:i,I1N REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED •TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. , 11. ALL HORN/STROBE AND S -I -OBE 'DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPHED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIOW.H. ALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND ,OIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS AREFROM: DEDICATED' CIRCUITS FROM THE 'EMERGENCY GENERATOR., • :1 ! 11 • 15. PER NFPA 72 SECTION 5-.6.1.3 DETECTORS SHALL, NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF:ALL TRADES IS COMPLETE AND , FINAL. . .'. EXCEPTION: WHERE REQUIRED BY THE AUTHORIPC HAVING JURISDICTION. FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEb\l: INSTALLED PRIOR TO FINAL CLEAN-UP BY, ALL TRADES SHALL BE CLEANED OR ,REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7.. . , 16. WIRING SHALL RUN CONTINUOUS YROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO iDEV,ICE WITHOUT SPLICING IN PULL BOXES OR ., OTHER BACK BOXES OF DIFFERENT CIRCUITS. ,, 17. ALL WIRING SHALL BE METEREVVERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEENI CONDUCTORS AND OTHER CIRCUITS PRIOR TO L FINAL EQUIPMENT TRIM. i 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM .RISER WITH A PERMANENT LABEL AT ALL1DEVICES, JUNCTION BOXES AND FACP. . AH' 19. THE ELECTRICAL CONTRACTOR :;;SHALL CLEAN ALL DIRT AND DEBRIS .FROM THE . OUTSIDE AND INSIDE OF TI-i.1,111...ALARM BACK BOXES AND JUNCTION '..BOXE.S." AFTER COMPLETION OF TH ' 1\ .TALLATION. , 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 1A1 GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BEl,WEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. QUANTITY 3 2 2 2 2 EX I SY 0 DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT CP FIRE ALARM F'CONTROL PANEL X LS -V SIEMENS PROVIDED 66" A.F.F. TO TOP A 'FIRE ALARM SDD-C REMOTE ANNUNCIATOR II I •: ' I ,,:, PAD -3 SIEMENS PROVIDED ' .11 REMOTE BOOSTER • ill EX .p.OWER SUPPLY ' I 11-nall .. WITH RELAY HTRI-R SIEMENS 4S DEEP V E R IF Y .' NTERFACE MODULE ' DM ' ',INTERFACE INPUT HTRI-D SIEMENS a INTERFACE MODULE SIEMENS PROVIDED 66" A.F.F. TO TOP 66" A.F.F. TO TOP H CONTROL POINT PODULE 4S DEEP VERIFY IN FIELD HCP SIEMENS 4S DEEP VERIFY IN FIELD REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD }LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS KADDRESSABLE-PHOTO) DB -11 BASE 4S DEEP VV/ 1G RING CEILING DUCT SMOKE DETECTOR . AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD !HEAT DETECTOR s°11771''! KADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S. DEEP W/ 10 RING CEILING El • FIRE ALARM SPEAKER STROBE MOUNT' SET -MC -CW SIEMENS 4S DEEP BOX CEILING VV/ 1-1/2" EXT. MR' MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD • MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBDXI FIRE ALARM F.B.O. F.B.O. F.B.O. VERIFY FIRE ALARM SPEAKER STROBE SET -MC --W SIEMENS 4S DEEP BOX 80" A.F.F. ' (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM 0 d Eli " : FIRE ALARM ' SPEAKER STROBE SET -HMC -CW SIEMENS 4S DEEP BOX CEILING ' (WALL MOUNT) W/ 1-1/2" EXT. i ' 'I u FIRE ALARM STROBE ZR -MC -CW ' SIEMENS 4S BOX CEILING (CEILING MOUNT) W/ 1G RING IItl , FIRE ALARM STROBE ZR -MC -W SIEMENS As BOX 80" A.F.F. • ' (WALL MOUNT) W/ 10 RING TO BOTTOM U.O.N. " , FIRE ALARM SPEAKER SET -CW SIEMENS 4S DEEP BOX CEILING (CEILING MOUNT) W/ 1-1/2" EXT. N/A FIRE ALARM SPEAKER SET -W SIEMENS 4S DEEP BOX 80" A.F.F. (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM to 't ' 'ABOVE FINISHED .11A1F :FLOOR FIRE ALARM STROBE SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY .• vvP. (WEATHERPROOF) 1/2" PIPE . IN FIELD MR' MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD • MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBDXI FIRE ALARM F.B.O. F.B.O. F.B.O. VERIFY BLUE ,AS BUILT NOTES TO CAD N/A N/A N/A N/A It t:;:( 2e:), 2008 Tukwila Fire "177, ri ht 2006 b Guardian Securit S stems, Inc. AH R. hts Reserved �D I i REV. BY: -E' 'Ef CRWMNML UFADHNE.1 DESCRIPTION SHOP DRAWINGS ::JUN C T I 0 N BOX F,B.O. F.B.O. ' N/A . VERIFY IN FIELD to 't ' 'ABOVE FINISHED .11A1F :FLOOR N/A N/A N/A N/A tl ' FURNISHED BY OTHERS N/A N/A N/A N/A N44 "C" :i i NOT ' : , APPLICABLE It N/A N/A N/A N/A ' 11' ... ,UNLESS ,N... • 'NOTED 4 OTHERWISE N/A N/A . N/A N/A \.1,1q • '1 fyEATHERPROCIF "fr Lli DEVICE N/A . . , . . . . N/A . . . . . . .. . . . . . . . N/A N/A , AS BUILT RED . ADD OR CHANGE N/A N/A N/A N/A GRFEN 2&V/ILT N/A N/A N/A N/A BLUE ,AS BUILT NOTES TO CAD N/A N/A N/A N/A It t:;:( 2e:), 2008 Tukwila Fire "177, ri ht 2006 b Guardian Securit S stems, Inc. AH R. hts Reserved �D REV. BY: z < DESCRIPTION SHOP DRAWINGS DATE 5/22/08 co 1-5 < a) D Z (I) W 2 Ei 0 CC m.‹ 1- w < w 0 w cc (/)..1 CCc'I < c°D 03 0 0 z 4-CALE: 1/8"=l' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/22/08 BACKROUND PLAN PROVIDED BY: 1.0B NUMBER: 1 SHEET "\ FA -01 Iil ''I •1 1.1! ;I 'I!: i 0) I GUESS WESTF UTHCENTER MALL it i FLAG NOT • .1 FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I N STLL ADDRESSABLE N DEVICES U\TI_ RR_RROG A\AMED W DEVICES ADDRESS. TAT T Cs) W fka CZ D rn z 0 z LIT H - }— w W U) FAX (206) 628-4990 N N ., c N J W F— H RELEASE/REVISIONS REV. BY: I z Q { DESCRIPTION SHOP DRAWINGS DATE 5/22/08 ; lE19ERVU:F' CORRIDOR t. •\ `Y/L.../!G'.. .,.: .: ..: ., ^'.�,.� --"'."; •.. L�"moi. � /! �L //" O� O 44. '11:x•{5 ? it --�r SAS 2S,2V { 1 ,.-11, ••.r.--.......-. F'i ., °r l� i i 7` ‘,:_\-_,-,..,.-4A,-.\.-/",......,.\..,,,, 11 } ' II • • 25, , ` _ %, 17 11 �I ' ', i:` ----1l I` _ 11 I ..r ;1 1 r 1 II _ ....{ ,t.... —!i . ;/ `. ' ` v ,.\..'"1'. 1\ \ }0. 'h' '_ F -}.... .-' \ \ I r'+ ,2 \ i '` —yj 1 0, . I [. .n ! � ' i 1 II �tMw�.i 1 I GUESS WESTF UTHCENTER MALL it i FLAG NOT • .1 FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I N STLL ADDRESSABLE N DEVICES U\TI_ RR_RROG A\AMED W DEVICES ADDRESS. TAT T Cs) W fka CZ D rn z 0 z LIT H - }— w W U) FAX (206) 628-4990 N N ., c N J W F— H RELEASE/REVISIONS REV. BY: I z Q DESCRIPTION SHOP DRAWINGS DATE 5/22/08 o CaCCC (SCALE: 1/8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER:. SHEET Copyright 2006 by Guardian SecuritySystems, Inc. All Rights Resery FA -03 1 I • A BARE ESSENTIALS FACP ADD ONS BARE ESSENTIALS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations ROBBINS I FAMILY Li MEN Er- - Standby: Alarm: Current Load: DOviCe Te HFP-11 Amps 0.0022 0.0635 Total 0.0022 0.0635 Amps. 0.0023 Total Total 0.009600 0.001600 0.005 0.0096 0.0035 0.0731 Sthndby slirrent Load: Min System Board SET -MC @15CD SET-MC@3OCD sv-mc @75CD SET -mc (Dm T-HMC-C@115CD PT-1-IMC-C@135CD W-HMC-C@185CD gRMC @15CD 0.233 0.318 0.318 0.0731 For 24 Hours = Amp -hours 0.0015 ent Load: For 5 Minutes= Amp -hours 25% Derating= Amp -hours Standby Current Load: For 24 Hours = Amp -hours Alarm Current Load: For 5 Minutes= Amp -hours Amp -hours 25% Derating= Amp -hours Battery Pair to be Used: 12VDC Amp -hours Total System Current Load: 0.970 Amp -hours RELEASE/REVISIONS BARE ESCENTUAL Battery Pair to be Used: 12VDC Amp -hours BATTERY SIZ CALCULATION ELECTRICAL PROJECT: Panel: Date: CIRCUIT: QTY 0 CHEESECAKE. FACTORY s') 1 F LOADING DOCK [149(1)1 Notification Appliance WESTFIELD SOUTHCENTER MALL BARE ESSENTIALS May 22, 2008 S1 Device Type SET -MC @I 5CD SET -MC @30CD REV. BY: z .:t DESCRIPTION SHOP DRAWINGS DATE 5/22/08- 2 < <<<< URRENT TOTAL 512 Circuit Total Total Wire Resistance ( R ) (WL*2 )*(R/ft) 2 SET -MC @75CD 0 SET -MC @110CD 0 SET-HMC-C@115CD 0 SET-HMC-C@177CD 0 SET -HMC @135CD 0 SET -HMC @185CD 1 Z-MC@1 5CD 0 Z-MC@30CD 0 SET-MC-CW@110CD DEVICES= 175 233 318 445 318 445 Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) 0 C,) C/) CC EOL Voltage (20.4 - E) 64 98 233 BARE ESCENTUALS WESTFIELD SOUTHCENTER MALL Nieta, SCALE 1132'4 PROJECT: Panel: Date: CIRCUIT: TOTAL mA=- 19.9603968 Notification Appliance WESTFIELD SOUTHCENTER MALL BARE ESSENTIALS May 22, 2008 . SPEAKER CIRCUIT Device Type Alarm Current Alarm Total 70.7V 1/8 1.8 7.2 ircu t Detail Wire Resistance 2.58 RRENT TOTAL 7.2 Wire Size Voltage at EOL Circuit Total 2S,2V 2S,2V S,2V 2S,2V 2S,2V Total Wire Resistance ( R ) ( WL * 2 )* (R/ft) Total Device Load, Amps (I) •.q (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage (20.4 - E) 75 C 75 C 15 75 C 15 75 C 15 15 DEVICES= 0 TOTAL m A= 20.37900912 IR% w z cf) z 0 0 LLI F- 6ALE: ,1/8" =1' -\ FACP DRAWN, ;BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/22/08 BACKROUND PLAN PROVIDED BY: .,10B NUMBER: RISER DIAGRAM. VOLTAGE. DRO CALCULATION SHEET risht, 2006 b Guardian Securit S stems, Inc. All FC hts serve: 1 • Bare Escentuals 7- General Notes • VICINITY MAP (Suite# 827) SCALE: NTS Ordinary Group II 0.20Ogpm/ft2 for 955.84ft2 WOOD CLG. ©- 11'-0' A.F.F. GYP. BD. @ 10'-8' A.F.F. GYP. BD. CLG. @ i,5'-0" A.F.F 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers lin the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. ZONE T-4 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE GYP. @ 11' -+— Remote i4rea 5 c, U Existing Main nal ACT ©B' 0' A.h.F. © 9'-0" A. F F. 1ffftl a Mui sal� Existing Main (N) 9-0 .A F,.F LG, 1uKWILA FIRE DEPARTMEN1 Please call: 575.4407, and give this job og arij xact address for shut. down or r;1S( ration anDroval% FIRE SPRINKLER SYSTEM 1!8"=1'-0 1 3 5 7 9 11 Bare Escentuals Remote Area: Retail # 827 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD 11 MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / FP for 955.84 Fr SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 Psi FLOW 10900 'GPM AT BASE OF RISER. SYSTEM REQUIRES: 333.43 GPM @ 53.61 PSI ' At time of Design 11'-6"..GLiz.=37.75°!o AREA REDUCTION a f 0 ACCE .`i SPRINKLER • B• RANCHLIKE.,, FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING SUSPENDED T -BAR GRID CEILING TILE • SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE FIG.900 SWIVEL SWAY BRACE FITTING OI BRACE PIPE 9/8' KW IK BOLT (2tM' EMBED LENGTH) FIG. 1000 -FAST CLAMP" SWAY BRACEATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON THREADED BRACE PIPE HOTECEE FIO.4A PIPE CLAMP FOR SWAY BRACE 3/8' KWIK BOLT (2114" EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT IA NON -THREADED BRACE PIPE LATERAL BRANCHLIKE RESTRAINT NOT TO SCALE Weld Wimps must be inspected before pipe is hung. Q nc1t paint piping,' prior to hydrostatic test approval. TE Without Comments As Noted in Red Per The Attached Letter I hese plans hav: bi,ic•r! r/=vi:'; ,od by The Tukwila Fire Prevention Burn::<(; ,:,r. cc.:,,,:,: Ce a,/ rh current city standards. Acc,-p;::..,c,; ,, . r _ ~t,.. . r :ars and omissions wh: 1, . , 1;(:• , ...'iol:_; ions o: adopted standards and c,: :.,.... . r i.; r, r: )nr; ;l;lily for the adequacy of ci::_.•-,.r, ... ,. ; . .;;, i,;,.. (esigner. Additions, d ;kc,,_;1:_.._ _ , r . i,-., ctrewings arrer" this date w'ii; voic . i,: ;..,.,,,.:_. :,._. Ir:iii require a resubmittal of avis•..:.° ,:.1,•,,,‘.',::9:,..,1-..-:r .subsequent ap h pr•ov...l, i. Final acceptance is subject to field test arid inspection by The Tukwila Fire Prevention Bureau. Date: S/--l0b By:/�1 v"I .)1 I 4 1 1 Hanger No. 07C HILTI Kwik Bolt III / H!! TI KwBt Bot 11 N Diked Anchor —/1..="-� i 'V / 7 Cut Rod Lgth Rounded to Nearest Inch Rod Coupling AB Thread Rod 111 AO Pipe Swivel Ring .� I W/ Concrete r Construction Bottom of Concrete to Center Llne of Pipe Note on Plan Note on Plan: Hanger Number and' A' Olmenslon FANCIER DETAIL NGT TO SCALE ( - 2008 Tukwila Fire roam 1z.5 -o47 7 eT' VICINITY MAP DETAIL NOT TO SCALE Bare Escentuals cY. w • z 0 Adam Kantner tl a) co 0 Construction 0 U L c (0 SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FiN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 13 5.6 Pendent YZ` Brass 165°F Rel G4A Concealed APPROVAL City of Tukwila HYDRAULIC REFERENCE POINT R3615 5 5.6 Pendent Chrome 155°F F1 FR Semi-Rec CONT. NO.: KS0377 Total = 18 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE 05/02/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. # WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALOUOUERCUE /AUSTW /DALLAS /DECATUR/DEM ER/ WLLRH /HOUSTON/ KIWSAS CM LAS VEGAS IMI)91EAPOUs/PHoDUX1 PORTLAND / RAPIo CITY!ST. PAUL /SALT LAKE CITY/SEATTLE • Phone: 425-881-0100 Ftoc 425-881-3030 Bare Escentuals 827 Southcentner Mali Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 Bare Escentua VICINITY MAP (Suite# 827) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. SYMBOL LEGEND ZONE T-4 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE REVISIONS GYP. E © 11'-E Ordinary Group II.0.200gpmlft2 for 955.84ft2 WOOD CLG. (c� 11'-0' A.F.F. 0. CLG -.••'"e• _GYP. BD. © 104-6"A F.F. GYF. BD. CLG. 15=0"AF.F.— S -• Remote "y 0 0 0 : Existing Main —r+® ®' ®I® ACT (S 9'-0' A. FF. 9'-0' A.F.F. ea �-.— Existing Main 1 s a STOCKRC:4 0- 0' 4\s I.. \. .,. pt�RESTROC 7% e (N) GYP. BD. CLG. Q 9'-0' AF.F. FIRE SPRINKLER SYSTEM Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 13 5.6 Pendent Brass 165°F Rel G4A Concealed Bare Escentuals Remote Area: Retail # 827 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 955.84 Ft' SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION`: STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 333.43 GPM © 53.61 PSI " At time of Design 11'-6" CLG.=37.75% AREA REDUCTION 3 5 7 9 11 APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R3615 5 5.6 Pendent Chrome 155°F F1 FR Semi-Rec CONT. NO.: KS4377 Total = 18 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTING 01 Al BRACE PIPE SWAY BRACE ATTACHMENT "FAST CLAMP" 378' KWIK BOLT (21/4' ELIBED LENGTH) LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE - 0LATERAL BRANCHLINE RESTRAINT I�. ..fA NON -THREADED BRACE PIPE 3/9' KWIK BOLT (21W EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Cut Rod Lgth Rounded to Nearest Inch Hanger No. 07C HILTI Kwik Bolt III 5 \11 / i , -N ( 1 \ Concrete Construction HILTI KwBB Bot II Drilled Anchor Rod Coupling Bottom of Concrete to Certer Line of Pipe Note on Plan Note on Plan: Hanger Number and'A' Dimension HANGER DETAIL NOT TO SCALE VICIhTITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE A-105- REDMOND, WA- 98052 Lic. # WESTESF135QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /ADSTPI/DALLAS H DECATUR / DENVER /DUWTH /HOUSTON 'KANSAS CITY LAS VEGAS /MINVEAPOLIS PHOENIX CITY/ST. PAUL/SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 CO— 5 (sr/ Bare Escentuals 827 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM D_ w z 0 Adam Kantner SHEET FP -1 OF 1 Trainor Commercial Construction CONTRACTOR: 827 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-233 08-S-159 s FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Bare Escentuals 827 Southcenter Mall Permit No.: 08-S-159 Date: May 2, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. in (Hydraulic Summary, - I Job Number: KS0377 Report Description: Ordinary Group II Job Job Number KS0377 Design Engineer ' Adam Kanter Job Name Bare Escentuals State Certification/License Number WESTESF136QF Address 1 827 Southcentner Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Tukwila Wa 98188 Drawing Name FP -1 -cad System -. - I Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy - Ordinary Group II _ Hose Allowance At Source 250.00 Density 0.200gpm/ft2 Area of Application 955.84ft2 (Actual 955.84ft2) Additional Hose Supplies Node Flow(qpm) Number Of Sprinklers Calculated 12 Coverage Per Sprinkler 130.00ft2 01.(4.11144 ,il I ��� ". TT �� y ' �., - Total Hose Streams 250.00, Allowance) � System Flow Demand Total Water Required (Including Hose 333.43 583.43• Maximum Pressure Unbalance In Loops 0.000 1 /� Nroka 464/10 Maximum Velocity Above Ground 16.89 between nodes 39 and 33 Maximum Velocity Under Ground 1.26 between nodes 1 and 271 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2168.37gal 9.11 gal Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.467 583.43 57.074 82.392 Contractor I Contractor Number KS0377 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection I Phone 1 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 E-mail City State Zip Code Redmond ' WA 98052 Web -Site d�l, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:28PM Page 1 II Summary Of Outf owing .Devices Job Number: KS0377 Report Description: Ordinary Group II Actual Flow Minimum Flow K-Factor Pressure Device (gpm) (gpm) (K) (psi) Sprinkler 106 27.67 26.00 5.6 24.422 Sprinkler 104 27.32 26.00 5.6 23.802 c> Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 105 27.61 26.00 5.6 24.308 Sprinkler 102 26.27 26.00 5.6 22.011 Sprinkler 107 28.05 26.00 5.6 25.097 Sprinkler 103 27.20 26.00 5.6 23.598 Sprinkler 110 28.67 26.00 5.6 26.203 Sprinkler 112 29.23 26.00 5.6 27.254 Sprinkler 109 28.21 26.00 5.6 25.376 Sprinkler 111 29.10 26.00 5.6 27.008 Sprinkler 108 28.08 26.00 5.6 25.148 r' Most Demanding Sprinkler Data LAy © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:32PM Page 2 111 Node Analysis Job Number: KS0377 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 16 14'-6 E(2'-0) 27.772 19 14'-6 P0(5-0) 27.799 21 14'-6 E(2'-0) 31.484 25 14'-6 P0(5_0) 31.609 27 14'-6 P0(5-0) 28.401 31 14'-6 P0(5'-0) 32.656 33 14'-6 P0(5'-0) 30.498 38 14'-6 2P0(8'-0) 36.357 39 14'-6 2P0(8'-0) 36.437 46 14'-6 P0(5'-0) 34.122 48 14'-6 P0(5'-0) 35.322 52 14'-6 P0(5'.±:)) 33.026 54 14'-6 P0(5'-0) 34.998 58 14'-6 P0(5'-01 32.723 263 1'-11 PO(5'-0), P0(26-4) 49.896 271 3'-10'/s BFP(-4.500) 53.612 307 1-11 , LtE(16'-0) 49.918 _ 106 15'-0 • Spi(-24.422) 24.422 27.67 104 11'-0'/4 Spr(-23.802) 23.802 27.32 101 11'-6'/4 Spj 21.5 21.556 26.00 105 11'-6 Spr(_24.308) 24.308 27.61 102 11'-6'% Spr(-22.01j) 22.011 , 26.27 ' 107 11'-6 Spr(-25.097) 25.097 ____ 28.05 103 11'-6% Spr_(223_598) 23.598 27.20 • 110 11'-6iSpr(-26.203) 26.203 28.67 112 11'-6% Spr(-27.254) I 27.254 29.23 LL 109 _ 11'-6 Spre_25.376) 25.376 _ 28.21 111 11'-6'% Spr(-27.008) 27.008 29.10 108 11'-6Spr(-25.148) _ 25.148 28.08 1 -4'-0TS 57.074 333.43 ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:36PM Page 3 NI Hydraulic Analysis I Job Number: KS0377 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocy HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length v Route 1 DR 1.0490 Q=26.00 9.65 C=120 0.211435 26'-71/2 Pf 7.532 101 11'-6'% q=26.00 K=5.6 21.556 Spr(-21.556) 9'-0 Pe -1.289 19 14'-6 27.799 2E(2'-0), P0(5'-0) 35'-7% Pv BL 1.6100 Q=53.67 8.46 C=120 0.100341 6'-0 Pf 0.602 19 14'-6 27.799 Pe 27 14'-6 28.401 6'-0 Pv BL 1.6100 0=79.95 12.60 C=120 0.209700 10'-0 Pf 2.097 - 27 14'-6 28.401 Pe 33 14'-6 30.498 10'-0 Pv BL 1.6100 Q=107.15 16.89 C=120 0.360497 8'-5% Pf 5.939 33 14'-6 30.498 8'-0 Pe 39 14'-6 36.437 P0(8'-0) 16'-5'/a' Pv CM 4.2600 Q=333.43 7.51 C=120 0.025763 226'-11/2 Pf 8.008 _ 39 14'-6 36.437 84'-81/2 Pe 5.452 263 1'-11 49.896 E(13'-2), 2fE(6'-9%), CV(28'-11%), 310'-10 Pv GV(2'-7%), P0(26'-4) FM 8.3290 Q=333.43 1.96 C=120 0.000984 5-7 Pf 0.021 _ 263 1'-11 49.896 16'-0 Pe -0.000 307 1'-11 49.918 LtE(16'-0) 21'-7% Pv FM 10.4200 0=333.43 1.25 C=120 0.000331 26'-5% Pf 4.536 307 1'-11 49.918 83'-0! Pe -0.842 271 3'-10'% 53.612 4LtE(16'-0), BV(19'-0), BFP(-4.500) 109'-5%Pv UG 10.4000 Q=333.43 1.26 C=140 0.000251 109'-2 Pf 0.055 271 3'-10% 53.612 111'-7'% Pe 3.407 1 -4'-0 57.074 E(35'-1), 3LtE(25'-6), S 220'-9% Pv .� Route 2 DR 1.0490 Q=26.27 9.75 C=120 0.215561 26'-7% Pf 7.679 102 11'-6% q=26.27 K=5.6 22.011 Spr(-22.011) 9'-0' Pe -1.289 27 14'-6 28.401 2E(2'-0), P0(5'-0) 35-7% Pv GO Route 3 DR 1.0490 Q=27.20 10.10 C=120 0.229894 26'-7'/z Pf 8.190 103 11'-6% q=27.20 K=5.6 23.598 Spr(-23.598) 9'-3 Pe -1.289 33 14'-6 30.498 2E(2'-0), P0(5'-0) 35'-7% Pv Route 4 DR 1.0490 0=27.32 10.14 C=120 0.231734 33'-7% Pf 9.188 104 11'-0% q=27.32 K=5.6 23.802 Spr(-23.802) 6'-0 Pe -1.506 21 14'-6 31.484 3E(2'-0) 39'-7% Pv BL 1.6100 Q=27.32 4.31 C=120 0.028769 4'-4% Pf 0.125 21 14'-6 31.484 , Pe 25 14'-6 31.609 4'-4'% Pv BL 1.6100 0=54.93 8.66 C=120 0.104729 10'-0 Pf 1.047 25 14'-6 31.609 Pe 31 14'-6 32.656 10'-0 Pv BL 1.6100 Q=82.98 13.08 C=120 0.224677 8'-5% Pf 3.701 31 14'-6 32.656 8'-0' Pe 38 14'-6 36.357 P0(8'-0) 16'-5% Pv CM 4.2600_ Q=167.94 3.78 C=120 0.007244 11'-0 Pf 0.080 38 14'-6 36.357 Pe 39 14'-6 36.437 11-0 Pv Route 5 DR 1.0490 Q=27.61 10.25 C=120 0.236287 27'-4'% Pf 8.596 105 11'-6 q=27.61 K=5.6 24.308 Spr(-24.308) 9'-0 Pe -1.295 25 14'-6 31.609 2E(2'-0), P0(5'-0) 36'-4'/2 Pv. v Route 6 SP 1.0490 0=27.67 10.27 C=120 0.237312 5'-2'% Pf 3.131 106 15'-0 q=27.67 K=5.6 24.422 Spr(-24.422) 8'-0 Pe 0.219 16 14'-6 27.772 4E(2'-0) 13'-2%4 Pv BL 1.6100 Q=27.67 4.36 C=120 0.029461 0'-11 Pf 0.027 16 14'-6 27.772 Pe 19 14'-6 27.799 0'-11' Pv Route 7 DR 1.0490 0=28.05 10.41 C=120 0.243376 27-4% Pf 8.853 107 11'-6 q=28.05 K=5.6 25.097 Spr(-25.097) 9'-0 Pe -1.295 31 14'-6 32.656 2E(2'-0), P0(5-0) 36'-4% Pv Route 8 DR 1.0490 0=28.08 10.43 C=120 _0.243831 27'-4'/z' Pf 8.870 108 11'-6 q=28.08 K=5.6 25.148 Spr(-25.148) 9'-0 Pe -1.295 58 14'-6 32.723 2E(2'-0), P0(5'-0) 36'-4% Pv BL 1.6100 0=28.08 4.43 C=120 0.030271 10'-0 Pf 0.303 58 14'-6 32.723 ' Pe 52 14'-6 33.026 10'-0 Pv [, © M.E.P.CAD, Inc. ;in AutoSPRINKO VR5 v5.2.6 05/01/2008 5:16:40PM Page 4 I Hydraulic Analysis Job Number: KS0377 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length BL 1.6100 Q=56.29 8.87 C=120 0.109584 10'-0 Pf 1.096 52 14'-6 33.026 Pe 46 14'-6 34.122 10'-0 Pv BL 1.6100 Q=84.96 13.39 C=120 0.234661 1'-61/4 Pf 2.235 46 14'-6 34.122 8'-0 Pe 38 14'-6 36.357 P0(8'-0) 9'-6'/4 Pv GO Route 9 DR 1.0490 10.47 C=120 0.245877 27'-41/2 Pf 8.944 _Q=28.21 109 11'-6 q=28.21 K=5.6 25.376 Spr(-25.376) 9'-0 Pe -1.295 52 14'-6 33.026 2E(2'-0), P0(5'-0) 36'-4% Pv v Route 10 DR 1.0490 Q=28.67 10.64 C=120 0.253277 27'-4% Pf 9.214 110 11'-6 q=28.67 K=5.6 26.203 Spr(-26.203) 9'-0 Pe -1.295 46 14'-6 34.122 2E(2'-0), P0(5'-0) 36'-4'/2 Pv wo Route 11 DR _ 1.0490 Q=29.10 10.80 C=120 0.260472 26'-7% Pf 9.279 _ _ 111 11-6% q=29.10 K=5.6 27.008 Spr(-27.008) 9'-0 Pe -1.289 54 14'-6 34.998 2E(2'-0), P0(5'-0) 35'-7% Pv BL 1.6100 Q=29.10 4.59 C=120 0.032337 10'-0 Pf 0.323 54 14'-6 34.998 Pe 48 14'-6 35.322 10'-0 Pv 1.6100 Q=58.34 9.19 C=120 0.117063 1'-6% Pf 1.115 _BL _ 48 14'-6 35.322 8'-0 Pe 39 14'-6 36.437 P0(8'-0) 9'-6'% Pv v Route 12 DR 1.0490 Q=29.23 10.85 C=120 0.262660 26'-7% Pf 9.357 _ 112 11'-6% q=29.23 K=5.6 27.254 Spr(-27.254) 9'-0 Pe -1.289 48 14'-6 35.322 2E(2'-0), P0(5'-0) 35'-7%2 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only)II C Value Multiplier Actual Inside Diameter 4.87 ( Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 (sU, ©M.E.P.CAD, Inc. 41AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:40PM Page 5 lig Hydraulic Analysis Job Number: KS0377 Report Description: Ordinary Group II Pipe TypLe Flow VelocityHWC Friction Loss Length Pressure Eq. Length Summary Total Length _Diameter Downstream Elevation Discharge K -Factor Pt Pn Fittings Upstream Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv - Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 11W Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap . • ©M.E.P.CAD, Inc.AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:40PM Page 6 Hydraulic ,Graph Job Number: KS0377 Report Description: Ordinary Group II 150 Supply at Node 1 135 :Static Pressure 140.000 120 105 90 .N a 75 g to N N a` 60 —333.43 583.43 with hose @ 57.074 streams 45 30 —System 15 demand curve 10900.00 @ 20.000 W I II I I I 111 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111111 111111111 111111111 J 1 I I I I I I I 0 OW 11002200 3300 4400 5500 6600 7700 8800 9900 Water flow, gpm 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.467 @ 583.43 System Demand 333.43 @ 57.074 System Demand (Including Hose Allowance) 583.43 @ 57.074 (, ©M.E.P.CAD, Inc. lEy� AutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:50PM Page 7 Flow Diagram (Top View). Job Number: KS0377 Report Description: Ordinary Group II &.. ©M.E.P.CAD, Inc. iliAutoSPRINK® VR5 v5.2.6 05/01/2008 5:16:54PM Page 8 Customer BARE ESCENTUALS 827 SOUTHCENTER MALL —"KWILA, WA 98188 Project BARE ESCENTUALS Project # LIFE AND AN SECURITY PROPERTY P ROTECTION List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: MAY,23,08 Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) '18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard • GUARDIAN SECURITY LIFE AND PROPERTY PROTECTION Seattle • Tacoma • Poulsbo • Bellingham 1743 First Avenue South Seattle, WA 98134 Tel: 206.622.6545 Fax: 206.341.9928 Letter to Tukwila Fire Dept Attn: To whom it may concern For the tenant space Torrid at Westfield Mall, we originally submitted drawings (which have been approved) that had speaker/strobes when it should have been horn/strobes instead. I have included here in the revision the 3 new sets of drawings, and submittals with the correct parts. I also included a copy of the original approved drawing. Please call me at (206) 359 12 68 with any questions Thanks Raedeit Kifle PM — Guardian Security Customer T,�ORf1D OUTHCENTER VV1LA, WA f31i38 GUARDIAN SECURITY" 7 -ION LIFE .A N b PROPERTY PROTEC Project TORRID Project # Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM 'List of Materials Date: 7/22/08 Item Qty. Manuf. Model Description Unit Pri Total Pricel 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens Siemens HFP-11 HFP-11-relay AD2-P PBA -1191 PBR-1191 PBR-1192 PBR-1193 HTRI-D HTRI-R HCP Siemens ZR-MC-CW,W Siemens ZR-MC-W,W Siemens SET-MC-CW,W Photoelectric Smoke Detector w/DB-11 Base Photoelectric Smoke Detector w/HR relay base Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Linear Beam Smoke Detector w/Backbox Prism Reflector for PBA -1191 w/Backbox 20x20 Reflector Package 10x10 Reflector Package Supervised Addressable Input Module Supervised Addressable Output Relay Module Supervised Addressable Module for Strobes Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator 1' Interior Visual Strobe Annunciator Combination Speaker/Strobe lS ** PAD -3 with BT -33 Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard , FILE COPY I • • • • I SHEET INDEX BARE 'E , TU • FIREAL YSTE Ai. TUKWILA H'nWASHINGTON . GENERAL NOTES SYMBOLS LEGEND SHEET \ U V E SH•RIFT- TITLE FA -01 SYS I \ F ICH vl AT I 0 \ FA -02 TYP:cAL DETAILS - \G A\ D MOU\TI\C FA -03 ALAV SYSTE V FLOCH PLA\ FA -04 SYSTEIv CALCULATIO \ S (GE\ EAL), SITE PLA CCFD: vothoutdcoments. 0 • As Noted'In!Red 0 Per The Attached' Letter • I . , !nese plans have been reviewed by The Tukwita Fire Prevention Bureau for conformance with current cit. standards. Acceptance is subject to errors and omissions which do not aUthariz violations Of adopted stanaaras and ordinatte. The respOnsibility for the adequacy of design restsitotatly with the designer. Additions, de4F7Aions or reViSiOris #0 those drawings:alter this date will void thi's acceptance nd will require a' resubmittal or revised draWings.fOr subsequent approval. Final acceptance is subjeCtlOield test and Inspection by The Tukwila Fire Prevention', Bureau. . • , Date: .4 4 • TUKWILA FIRE DEPARTMEittli Please call: 5754400 and give this job No..0.3„d4.• and exact address for shuts rk)wn or restoration artiorOVe NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DES GNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION .SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA. LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR. HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S ' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)• A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) :21 REMOTE INDICATION LIGHT. TWO #18 FPL/FPLR RED (JACKET) .'HX LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD • UNDERGROUND DATA TWISTED PAIR RATED, #18 FPL/FPLR RED (JACKET) JH,..LJI UNDERGROUND INITIATION TWISTEb,P4IR'RATED #18 FPL/FPLR RED (JACKET) '0.. M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE ,TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. • .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH ' ' 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END : ( h.11 !I, FOR SIEMENS •. DO NOT INSTALL ADDRESSABLE HlITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. • `. .• , 1. NUMBERS ADJACENT TO DEICE 1 SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BEI THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT DOLARITY. SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING ISLSUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE Ill 4, INSTALLATION SHALL BE IN ; STRIGT ;CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, Lt?CAL ODE(S), AND/OR AUTHORITY 'HAVING JURISDICTION. 5. INSTALLATION MATERIALS (It po UIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS 'a BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIENO. $• [ 6. DETECTORS SHALL NOT BE 'MOUN ED IN DIRECT AIR STREAM OF AIR SUPPLY:MIL IS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE :CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. i • 8. INSTALLING CONTRACTOR SHALL, RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOES. I t 9. FOR ADDITIONAL INSTALLATIO INST1RUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION I0RUCTIONS. 10. THE 120vac POWER ELECTRIQAL I'd< SUPPLYING ,FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE, 725 A.ND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5f2:i,I1N REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED • TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. , 11. ALL HORN/STROBE AND S-1()BE 'DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPHED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONAliL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. .;•t II 13. ALL PANEL NUMBERS AND ,OCU'IT WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE 'FROM' DEDICATEDCIRCUITS FROM THE 'EMERGENCY GENERATOR. • .,I ! • 15. PER NFPA 72 SECTION 5-6.1. DETECTORS SHALL, NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND , FINAL. , .'• EXCEPTION: WHERE REQUIRED BY THE AUTHORITY: HAVING JURISDICTION. FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEb\1: INSTALLED PRIOR TO FINAL CLEAN-UP BY, ALL TRADES SHALL BE CLEANED OR ,REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7.. . , 16. WIRING SHALL RUN CONTINUOUS ,;FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO iDEV,ICE WITHOUT SPLICING IN PULL- BOXES OR ., OTHER BACK BOXES OF DIFFERENT CIRCUITS. H.,1•'! ,i • ,, 17. ALL WIRING SHALL BE METEREVVERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO L • FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM .RISER WITH A PERMANENT LABEL AT ALL1DEVICES, JUNCTION BOXES AND FACP. , IH.t' 19. THE ELECTRICAL CONTRACTOR :SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF TH.1.111...ALARM BACK BOXES 'AND.. JUNCTION ''''BOXES.. AFTER COMPLETION OF T1. R 1 1\ .TALLATION. , 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NEPA 72 2007 A.6.4.2.2.2 I 1A1 GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BEEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. . QUANTITY 3 2 2 2 2 EX , SY 0 DESCRIPTION MODEL • MANUFACTURER BACKBOX MOUNTING HEIGHT iII CP FIRE ALARM F CONTROL PANEL X LS -V SIEMENS PROVIDED 66" A.F.F. TO TOP A 'FIRE ALARM SDD-C REMOTE ANNUNCIATOR fl II •SIEMENS PROVIDED ' I .::, PAD -3 : 1 REMOTE BOOSTER • ill EX POWER SUPPLY ' I 11-nall .. WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY . NTERFACE MODULE . DM ' 'INTERFACE INPUT HTRI-D SIEMENS INTERFACE MODULE H SIEMENS PROVIDED 66" AF.F. TO TOP 66" A.F.F. TO TOP H CONTROL POINT MODULE 4S DEEP VERIFY IN FIELD HCP SIEMENS 4S DEEP VERIFY IN FIELD REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE DETECTOR . AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD !HEAT DETECTOR 71'! • '(ADDRESSABLE) cv- El HFPT-11 W/ SIEMENS DB -11 BASE 4S. DEEP W/ 1G RING CEILING . • FIRE ALARM SPEAKER STROBE . • MOUNT') SET -MC -CW 'SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD • MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBDXI FIRE ALARM F.B.O. F.B.O. F.B.O. VERIFY FIRE ALARM . . SPEAKER STROBE SET -MC --W SIEMENS 4S DEEP BOX 80" A.F.F. ' (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM dI Eli FIRE ALARM ' SPEAKER STROBE SET -HMC -CW 'SIEMENS 4S DEEP BOX CEILING ' (WALL MOUNT) W/ 1-1/2" EXT. ' u FIRE ALARM STROBE ZR -MC -CW ' SIEMENS 4S BOX CEILING (CEILING MOUNT) W/ 1G RING 1k , I FIRE ALARM • , STROBE ZR -MC -W SIEMENS A S BOX 80" A.F.F. • I (WALL MOUNT) W/ 1G RING TO BOTTOM U.O.N. " , FIRE ALARM SPEAKER SET -CW SIEMENS 4S DEEP BOX CEILING (CEILING MOUNT) W/ 1-1/2" EXT. N/A FIRE ALARM SPEAKER SET -W SIEMENS 4S DEEP BOX 80" A.F.F. (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM to 'I • 'ABOVE FINISHED .11 :FLOOR FIRE ALARM STROBE SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY (WEATHERPROOF) 1/2" PIPE , IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD • MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBDXI FIRE ALARM F.B.O. F.B.O. F.B.O. VERIFY BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A t:;:( 2e:), 2008 Tukwila Fiie "177, ri Fit 2006 b Guardian Securit S stems, Inc. All R. hts Reserved 0 �D D F- uJ F- uJ LL U) r, CD C\J CD CD C\J U_ c U) z 0 U) LU LU U) •t:r LU LU fZC REV. BY: -EI ERWMNML U/1E:MN GI DESCRIPTION SHOP DRAWINGS JUNCTION BOX • , F,B4O. F.B.0, ' N/A . VERIFY IN FIELD to 'I • 'ABOVE FINISHED .11 :FLOOR N/A N/A • N/A N/A tl ' FURNISHED BY ' • OTHERS N/A N/A N/A N/A "C" it!,, , NOT • I , APPLICABLE • It N/A N/A N/A N/A , U. 11' fN..• .. :1 • . ,• 'NOTED i. UNLESS OTHERWISE N/A N/A . N/A N/A . IF ' 1 ryt EATHERPROOF v(k) '11 DEVICE N/A . . , . . . . N/A . . . . . . .. . . . . . . N/A N/A , ADD AS BUILT CHANGE RED OR N/A N/A N/A N/A GRFEN 2&111&-T N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A t:;:( 2e:), 2008 Tukwila Fiie "177, ri Fit 2006 b Guardian Securit S stems, Inc. All R. hts Reserved 0 �D D F- uJ F- uJ LL U) r, CD C\J CD CD C\J U_ U) z 0 U) LU LU U) •t:r LU LU fZC REV. BY: z 4 DESCRIPTION SHOP DRAWINGS DATE 5/22/08 • , • co 7, < 0) D Z (I) W 2 Ei 0 cc o m.‹ I - w < w 0 w cc (n..1 CC LT- < °ID 0 0 z 'ALE: 1/8"=l' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/22/08 BACKROUND PLAN PROVIDED BY: I 1.0B NUMBER: 1 SHEET "\ 1 FA -01 Iil ''I •1 1.1! ;I 'I!: i 0) I GUESS WESTF UTHCENTER MALL it i FLAG NOT • .1 FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I N STLL ADDRESSABLE N DEVICES U\TI_ RR_RROG A\AMED W DEVICES ADDRESS. TAT T Cs) W fka CZ D rn z 0 z LIT H - }— w W U) FAX (206) 628-4990 N N ., c N J W F— H RELEASE/REVISIONS REV. BY: I z Q { DESCRIPTION SHOP DRAWINGS DATE 5/22/08 ; lE19ERVU:F' CORRIDOR t. •\ `Y/L.../!G'.. .,.: .: ..: ., ^'.�,.� --"'."; •.. L�"moi. � /! �L //" O� O 44. '11:x•{5 ? it --�r SAS 2S,2V { 1 ,.-11, ••.r.--.......-. F'i ., °r l� i i 7` ‘,:_\-_,-,..,.-4A,-.\.-/",......,.\..,,,, 11 } ' II • • 25, , ` _ %, 17 11 �I ' ', i:` ----1l I` _ 11 I ..r ;1 1 r 1 II _ ....{ ,t.... —!i . ;/ `. ' ` v ,.\..'"1'. 1\ \ }0. 'h' '_ F -}.... .-' \ \ I r'+ ,2 \ i '` —yj 1 0, . I [. .n ! � ' i 1 II �tMw�.i 1 I GUESS WESTF UTHCENTER MALL it i FLAG NOT • .1 FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I N STLL ADDRESSABLE N DEVICES U\TI_ RR_RROG A\AMED W DEVICES ADDRESS. TAT T Cs) W fka CZ D rn z 0 z LIT H - }— w W U) FAX (206) 628-4990 N N ., c N J W F— H RELEASE/REVISIONS REV. BY: I z Q DESCRIPTION SHOP DRAWINGS DATE 5/22/08 o CaCCC (SCALE: 1/8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/22/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER:. SHEET Copyright 2006 by Guardian SecuritySystems, Inc. All Rights Resery FA -03 1 I • A BARE ESSENTIALS FACP ADD ONS BARE ESSENTIALS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations ROBBINS I FAMILY Li MEN Er- - Standby: Alarm: Current Load: DOviCe Te HFP-11 Amps 0.0022 0.0635 Total 0.0022 0.0635 Amps. 0.0023 Total Total 0.009600 0.001600 0.005 0.0096 0.0035 0.0731 Sthndby slirrent Load: Min System Board SET -MC @15CD SET-MC@3OCD sv-mc @75CD SET -mc (Dm T-HMC-C@115CD PT-1-IMC-C@135CD W-HMC-C@185CD gRMC @15CD 0.233 0.318 0.318 0.0731 For 24 Hours = Amp -hours 0.0015 ent Load: For 5 Minutes= Amp -hours 25% Derating= Amp -hours Standby Current Load: For 24 Hours = Amp -hours Alarm Current Load: For 5 Minutes= Amp -hours Amp -hours 25% Derating= Amp -hours Battery Pair to be Used: 12VDC Amp -hours Total System Current Load: 0.970 Amp -hours RELEASE/REVISIONS BARE ESCENTUAL Battery Pair to be Used: 12VDC Amp -hours BATTERY SIZ CALCULATION ELECTRICAL PROJECT: Panel: Date: CIRCUIT: QTY 0 CHEESECAKE. FACTORY s') 1 F LOADING DOCK [149(1)1 Notification Appliance WESTFIELD SOUTHCENTER MALL BARE ESSENTIALS May 22, 2008 S1 Device Type SET -MC @I 5CD SET -MC @30CD REV. BY: z .:t DESCRIPTION SHOP DRAWINGS DATE 5/22/08- 2 < <<<< URRENT TOTAL 512 Circuit Total Total Wire Resistance ( R ) (WL*2 )*(R/ft) 2 SET -MC @75CD 0 SET -MC @110CD 0 SET-HMC-C@115CD 0 SET-HMC-C@177CD 0 SET -HMC @135CD 0 SET -HMC @185CD 1 Z-MC@1 5CD 0 Z-MC@30CD 0 SET-MC-CW@110CD DEVICES= 175 233 318 445 318 445 Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E ) (E= I * R) 0 C,) C/) CC EOL Voltage (20.4 - E) 64 98 233 BARE ESCENTUALS WESTFIELD SOUTHCENTER MALL Nieta, SCALE 1132'4 PROJECT: Panel: Date: CIRCUIT: TOTAL mA=- 19.9603968 Notification Appliance WESTFIELD SOUTHCENTER MALL BARE ESSENTIALS May 22, 2008 . SPEAKER CIRCUIT Device Type Alarm Current Alarm Total 70.7V 1/8 1.8 7.2 ircu t Detail Wire Resistance 2.58 RRENT TOTAL 7.2 Wire Size Voltage at EOL Circuit Total 2S,2V 2S,2V S,2V 2S,2V 2S,2V Total Wire Resistance ( R ) ( WL * 2 )* (R/ft) Total Device Load, Amps (I) •.q (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage (20.4 - E) 75 C 75 C 15 75 C 15 75 C 15 15 DEVICES= 0 TOTAL m A= 20.37900912 IR% w z cf) z 0 0 LLI F- 6ALE: ,1/8" =1' -\ FACP DRAWN, ;BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/22/08 BACKROUND PLAN PROVIDED BY: .,10B NUMBER: RISER DIAGRAM. VOLTAGE. DRO CALCULATION SHEET risht, 2006 b Guardian Securit S stems, Inc. All FC hts serve: 1 • Bare Escentuals 7- General Notes • VICINITY MAP (Suite# 827) SCALE: NTS Ordinary Group II 0.20Ogpm/ft2 for 955.84ft2 WOOD CLG. ©- 11'-0' A.F.F. GYP. BD. @ 10'-8' A.F.F. GYP. BD. CLG. @ i,5'-0" A.F.F 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers lin the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. ZONE T-4 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE GYP. @ 11' -+— Remote i4rea 5 c, U Existing Main nal ACT ©B' 0' A.h.F. © 9'-0" A. F F. 1ffftl a Mui sal� Existing Main (N) 9-0 .A F,.F LG, 1uKWILA FIRE DEPARTMEN1 Please call: 575.4407, and give this job og arij xact address for shut. down or r;1S( ration anDroval% FIRE SPRINKLER SYSTEM 1!8"=1'-0 1 3 5 7 9 11 Bare Escentuals Remote Area: Retail # 827 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD 11 MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / FP for 955.84 Fr SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 Psi FLOW 10900 'GPM AT BASE OF RISER. SYSTEM REQUIRES: 333.43 GPM @ 53.61 PSI ' At time of Design 11'-6"..GLiz.=37.75°!o AREA REDUCTION a f 0 ACCE .`i SPRINKLER • B• RANCHLIKE.,, FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING SUSPENDED T -BAR GRID CEILING TILE • SPRINKLER HEAD FLEXHEAD DETAIL NOT TO SCALE FIG.900 SWIVEL SWAY BRACE FITTING OI BRACE PIPE 9/8' KW IK BOLT (2tM' EMBED LENGTH) FIG. 1000 -FAST CLAMP" SWAY BRACEATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON THREADED BRACE PIPE HOTECEE FIO.4A PIPE CLAMP FOR SWAY BRACE 3/8' KWIK BOLT (2114" EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT IA NON -THREADED BRACE PIPE LATERAL BRANCHLIKE RESTRAINT NOT TO SCALE Weld Wimps must be inspected before pipe is hung. Q nc1t paint piping,' prior to hydrostatic test approval. TE Without Comments As Noted in Red Per The Attached Letter I hese plans hav: bi,ic•r! r/=vi:'; ,od by The Tukwila Fire Prevention Burn::<(; ,:,r. cc.:,,,:,: Ce a,/ rh current city standards. Acc,-p;::..,c,; ,, . r _ ~t,.. . r :ars and omissions wh: 1, . , 1;(:• , ...'iol:_; ions o: adopted standards and c,: :.,.... . r i.; r, r: )nr; ;l;lily for the adequacy of ci::_.•-,.r, ... ,. ; . .;;, i,;,.. (esigner. Additions, d ;kc,,_;1:_.._ _ , r . i,-., ctrewings arrer" this date w'ii; voic . i,: ;..,.,,,.:_. :,._. Ir:iii require a resubmittal of avis•..:.° ,:.1,•,,,‘.',::9:,..,1-..-:r .subsequent ap h pr•ov...l, i. Final acceptance is subject to field test arid inspection by The Tukwila Fire Prevention Bureau. Date: S/--l0b By:/�1 v"I .)1 I 4 1 1 Hanger No. 07C HILTI Kwik Bolt III / H!! TI KwBt Bot 11 N Diked Anchor —/1..="-� i 'V / 7 Cut Rod Lgth Rounded to Nearest Inch Rod Coupling AB Thread Rod 111 AO Pipe Swivel Ring .� I W/ Concrete r Construction Bottom of Concrete to Center Llne of Pipe Note on Plan Note on Plan: Hanger Number and' A' Olmenslon FANCIER DETAIL NGT TO SCALE ( - 2008 Tukwila Fire roam 1z.5 -o47 7 eT' VICINITY MAP DETAIL NOT TO SCALE Bare Escentuals cY. w • z 0 Adam Kantner tl a) co 0 Construction 0 U L c (0 SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FiN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 13 5.6 Pendent YZ` Brass 165°F Rel G4A Concealed APPROVAL City of Tukwila HYDRAULIC REFERENCE POINT R3615 5 5.6 Pendent Chrome 155°F F1 FR Semi-Rec CONT. NO.: KS0377 Total = 18 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE 05/02/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. # WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY -OFFICES LOCATED ALOUOUERCUE /AUSTW /DALLAS /DECATUR/DEM ER/ WLLRH /HOUSTON/ KIWSAS CM LAS VEGAS IMI)91EAPOUs/PHoDUX1 PORTLAND / RAPIo CITY!ST. PAUL /SALT LAKE CITY/SEATTLE • Phone: 425-881-0100 Ftoc 425-881-3030 Bare Escentuals 827 Southcentner Mali Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM SHEET FP -1 OF 1 Bare Escentua VICINITY MAP (Suite# 827) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. SYMBOL LEGEND ZONE T-4 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE REVISIONS GYP. E © 11'-E Ordinary Group II.0.200gpmlft2 for 955.84ft2 WOOD CLG. (c� 11'-0' A.F.F. 0. CLG -.••'"e• _GYP. BD. © 104-6"A F.F. GYF. BD. CLG. 15=0"AF.F.— S -• Remote "y 0 0 0 : Existing Main —r+® ®' ®I® ACT (S 9'-0' A. FF. 9'-0' A.F.F. ea �-.— Existing Main 1 s a STOCKRC:4 0- 0' 4\s I.. \. .,. pt�RESTROC 7% e (N) GYP. BD. CLG. Q 9'-0' AF.F. FIRE SPRINKLER SYSTEM Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 4 -WAY EARTHQUAKE BRACE R5415 13 5.6 Pendent Brass 165°F Rel G4A Concealed Bare Escentuals Remote Area: Retail # 827 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Ft' for 955.84 Ft' SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION`: STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 333.43 GPM © 53.61 PSI " At time of Design 11'-6" CLG.=37.75% AREA REDUCTION 3 5 7 9 11 APPROVAL: City of Tukwila HYDRAULIC REFERENCE POINT R3615 5 5.6 Pendent Chrome 155°F F1 FR Semi-Rec CONT. NO.: KS4377 Total = 18 DRAWN BY: Adam Kantner HANGER SYMBOL BRANCHLINE RESTRAINT SPRK ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/19/08 TYPICAL FLEXABLE SPRINKLER CONNECTION FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.909 SWIVEL SWAY BRACE FITTING 01 Al BRACE PIPE SWAY BRACE ATTACHMENT "FAST CLAMP" 378' KWIK BOLT (21/4' ELIBED LENGTH) LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG.4A PIPE CLAMP FOR SWAY BRACE - 0LATERAL BRANCHLINE RESTRAINT I�. ..fA NON -THREADED BRACE PIPE 3/9' KWIK BOLT (21W EMBED LENGTH) FIG.909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Cut Rod Lgth Rounded to Nearest Inch Hanger No. 07C HILTI Kwik Bolt III 5 \11 / i , -N ( 1 \ Concrete Construction HILTI KwBB Bot II Drilled Anchor Rod Coupling Bottom of Concrete to Certer Line of Pipe Note on Plan Note on Plan: Hanger Number and'A' Dimension HANGER DETAIL NOT TO SCALE VICIhTITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102 180th AVE NE, STE A-105- REDMOND, WA- 98052 Lic. # WESTESF135QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /ADSTPI/DALLAS H DECATUR / DENVER /DUWTH /HOUSTON 'KANSAS CITY LAS VEGAS /MINVEAPOLIS PHOENIX CITY/ST. PAUL/SALT LAKE CITY/ SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 CO— 5 (sr/ Bare Escentuals 827 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYSTEM D_ w z 0 Adam Kantner SHEET FP -1 OF 1 Trainor Commercial Construction CONTRACTOR: