PP - 837 SOUTHCENTER MALL - MARC ECKO CUT & SEW - PERMITS AND PLANS
837 SOUTHCENTER MALL ASSOCIATED PERMITS 15-F-076 08-F-449 15-S-098 08-S-425 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lego 837 Southcenter Mall Permit No.: 15-S-098 Date: June 3, 2015 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. Hydraulic Calculations Sheet 1 for Project Name: LEGO STORE - WESTFIELD MALL Location: TUKWILA, WA Design: Occupancy classification: Density: Coverage per sprinkler: EXTRA HAZARD GP 1 0.30 gpm/sq.ft. 100 SF MAX Type of sprinklers calculated: K=8.0 No. of sprinklers calculated: 12 heads Hose streams: 500.0 gpm Outside Hose Total water required: Including hose streams Date 05/31/15 Job: LEGO 68.22 psi @ 895.2 gpm @ Supply 118.26 psi available @ 895.2 gpm Below curve by 50.04 psi Type of System: Wet Water Supply Information: 120.00 psi Static, 20.00 psi Residual @ 8000.0 gpm Phone Number: Notes: GROUP A PLASTICS NON EXPANDED IN CARTONS ON RACKS TO 10' MAX 12' MAX CEILING HT Program: 'HydroCalc' by Micro Space Systems www.MicroSpaceSystems.com p CERTWICATEE OF NCOMPE ETENCY FIRE PROTECTION SPRINKLER SYSTEP95 John J. Abel 9760401 -CA Level 3 Moe ;,.- .n,,•. Inc. Pressure (PSI) 3 ■ Sy►stem demand = 68.22 psi with 895.2 gpm flowing. a 0 0 01 D 0 OD 0 0 Ci LEGO STORE - WESTFIELD MALL Sheet 3 Description of Fitting abbreviations Code Description T Tee E Ninety degree elbow VE Victaulic ninety degree elbow B26 Wilkens Model 350A Double Check Valve Assy. FH4 FLEX HEAD - 4' Description of Other abbreviations Code Description DR Drop BL Branch Line CM Cross Main PT Total pressure PE Pressure loss due to elevation changes PF Pressure loss due to friction ^.5 Raised to the power of .5 (Square Root) L Actual pipe length F Fitting equivalent pipe length T Total pipe length Sheet 4 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Raw data previous to any calculations No. Code Diam Length Kfacl Kfac2 Press Elev Hose HW Vel Fittings 1 DR1 1.049 3.00 8 12.000 -3.000 0.0 120 32 2E,1T,1FH4 2 DR2 1.049 1.50 8 12.000 -3.000 0.0 120 32 1T,1E,1FH4 3 DR3 1.049 1.50 8 14.060 -3.000 0.0 120 32 1T,1E,1FH4 10 BL1 1.682 1.00 DR1 0.000 0.000 0.0 120 32 11 BL1 1.682 10.00 DR2 0.000 0.000 0.0 120 32 12 BL1 1.682 10.00 DR3 0.000 0.000 0.0 120 32 13 BL1 1.682 8.00 DR3 0.000 0.000 0.0 120 32 14 BL1 1.682 16.00 DR3 0.000 0.000 0.0 120 32 1T 16 BL2 1.682 7.50 DR3 0.000 0.000 0.0 120 32 17 BL2 1.682 8.50 DR3 0.000 0.000 0.0 120 32 18 BL2 1.682 7.00 DR3 0.000 0.000 0.0 120 32 19 BL2 1.682 18.00 DR3 0.000 0.000 0.0 120 32 IT 21 BL3 1.682 5.00 DR3 0.000 0.000 0.0 120 32 22 BL3 1.682 10.00 DR3 0.000 0.000 0.0 120 32 23 BL3 1.682 18.00 DR3 0.000 0.000 0.0 120 32 IT 25 CM1 4.260 10.00 BL1 0.000 0.000 0.0 120 32 26 CM1 4.260 7.50 BL2 0.000 0.000 0.0 120 32 27 CM1 4.260 290.00 BL3 0.000 0.000 0.0 120 32 8VE 28 RI 4.260 22.00 CM1 0.000 15.000 0.0 120 32 1T,1B26,5VE 29 UG 6.160 250.00 RI 0.000 0.000 0.0 140 32 30 UG 6.160 0.00 0.000 0.000 500.0 140 32 Sheet 5 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes Drop 1 C = 120 L 3.0 PT 12.00 1 27.7=8.00(12.00)^.5 F 33.0 PE -1.30 (EL= -3.0 ft) 1 27.7 1.049 2E 1T T 36.0 0.23792 PF 8.57 10.3 1FH4 PT 19.27 10 131 Jct K -factor for drop 1 = 27.7/(19.27)^.5 = 6.31 Drop 2 L 1.5 PT 12.00 2 27.7=8.00(12.00)^.5 F 31.0 PE -1.30 2 27.7 1.049 1T 1E T 32.5 0.23792 PF 7.73 1FH4 PT 18.43 11 K -factor for drop 2 = 27.7/(18.43)^.5 = 6.45 Drop 3 L 1.5 PT 14.06 3 30.0=8.00(14.06)^.5 F 31.0 PE -1.30 3 30.0 1.049 1T 1E T 32.5 0.27547 PF 8.95 1FH4 PT 21.71 12 K -factor for drop 3 = 30.0/(21.71)".5 = 6.44 at Hyd Ref Pts 12 13 14 16 17 18 19 21 22 23 10.3 11.1 C = 120 (EL= -3.0 ft) B1 Jct C = 120 (EL= -3.0 ft) B1 Jct Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Sheet 6 Notes Branchline No. 1 (Beginning pressure increased due to Hyd Ref Pt 12) C = 120 L 1.0 PT 20.75 10 DR1 28.8=6.31(20.75)^.5 F 0.0 PE 0.00 10 28.8 1.682 T 1.0 0.02554 PF 0.03 4.2 L 10.0 PT 20.78 11 DR2 29.4=6.45(20.78)^.5 F 0.0 PE 0.00 11 58.2 1.682 T 10.0 0.09405 PF 0.94 8.4 L 10.0 PT 21.72 12 DR3 30.0=6.44(21.72)^.5 F 0.0 PE 0.00 12 88.2 1.682 T 10.0 0.20305 PF 2.03 12.7 L 8.0 PT 23.75 13 DR3 31.4=6.44(23.75)^.5 F 0.0 PE 0.00 13 119.5 1.682 T 8.0 0.35662 PF 2.85 17.3 L 16.0 PT 26.60 14 DR3 33.2=6.44(26.60)^.5 F 9.9 PE 0.00 14 152.7 1.682 1T T 25.9 0.56125 PF 14.54 22.1 PT 41.14 25 Cross main Jct K -factor for branchline no. 1 = 152.7/(41.14)^.5 = 23.81 Branchline No. 2 C = 120 L 7.5 PT 21.71 16 DR3 30.0=6.44(21.71)^.5 F 0.0 PE 0.00 16 30.0 1.682 T 7.5 0.02764 PF 0.21 4.3 L 8.5 PT 21.92 17 DR3 30.2=6.44(21.92)^.5 F 0.0 PE 0.00 17 60.1 1.682 T 8.5 0.10007 PF 0.85 8.7 L 7.0 PT 22.77 18 DR3 30.7=6.44(22.77)^.5 F 0.0 PE 0.00 18 90.9 1.682 T 7.0 0.21470 PF 1.50 13.1 L 18.0 PT 24.27 19 DR3 31.7=6.44(24.27)^.5 F 9.9 PE 0.00 19 122.6 1.682 iT T 27.9 0.37361 PF 10.42 17.7 PT 34.69 26 Cross main Jct K -factor for branchline no. 2 = 122.6/(34.69)^.5 = 20.81 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Sheet 7 Notes Branchline No. 3 C = 120 L 5.0 PT 21.71 21 DR3 30.0=6.44(21.71)^.5 F 0.0 PE 0.00 21 30.0 1.682 T 5.0 0.02764 PF 0.14 4.3 L 10.0 PT 21.85 22 DR3 30.1=6.44(21.85)^.5 F 0.0 PE 0.00 22 60.1 1.682 T 10.0 0.09992 PF 1.00 8.7 L 18.0 PT 22.85 23 DR3 30.8=6.44(22.85)^.5 F 9.9 PE 0.00 23 90.9 1.682 1T T 27.9 0.21473 PF 5.99 13.1 PT 28.84 27 Cross main Jct K -factor for branchline no. 3 = 90.9/(28.84)^.5 = 16.93 Cross main 1 C = 120 L 10.0 PT 41.14 25 BL1 152.7=23.81(41.14)^.5 F 0.0 PE 0.00 25 152.7 4.260 T 10.0 0.00608 PF 0.06 3.4 L 7.5 PT 41.20 26 BL2 133.6=20.81(41.20)^.5 F 0.0 PE 0.00 26 286.3 4.260 T 7.5 0.01943 PF 0.15 6.4 L 290.0 PT 41.35 27 BL3 108.9=16.93(41.35)^.5 F 71.6 PE 0.00 27 395.2 4.260 8VE T 361.6 0.03527 PF 12.75 8.9 PT 54.10 28 Top of Riser K -factor for Cross main 1 = 395.2/(54.10)^.5 = 53.73 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Sheet 8 Notes Riser C = 120 L 22.0 PT 54.10 28 CM 1 F 71.1 PE 6.50 (EL= 15.0 ft) 28 395.2 4.260 1T 1B26 T 93.1 0.03528 PF 6.53 8.9 1B26 = 3.24# 5VE PT 67.12 29 B.O.R. Under ground 29 395.2 6.160 500.0 gpm = Hose 30 895.2 6.160 C = 140 L 250.0 PT 67.12 29 B.O.R. F 0.0 PE 0.00 T 250.0 0.00440 PF 1.10 4.3 L 0.0 PT 68.22 30 F 0.0 PE 0.00 T 0.0 0.00000 PF 0.00 9.6 PT 68.22 31 Supply Jct Available flow at 68.22 psi is 5605.1 gpm which is 4709.9 gpm from curve. Supply pressure available with 895.2 gpm flowing is 118.26 psi, thus system requirement is 50.04 psi below supply curve. (42.3%) LEGO STORE - WESTFIELD MALL Sheet 9 Supply Analysis Node at Static Residual Available Total Required Source Pressure Pressure Flow Pressure Demand Pressure 31 120.00 20.00 8000.0 118.26 895.2 68.22 Node Analysis Elevation Node Type Pressure Discharge Node (ft) K -Value Source (psi) (gpm) Notes 1 12.00 Orif= 8.00 2 12.00 Orif= 8.00 3 12.00 Orif= 8.00 10 15.00 11 15.00 12 15.00 13 15.00 14 15.00 16 15.00 17 15.00 18 15.00 19 15.00 21 15.00 22 15.00 23 15.00 25 15.00 26 15.00 27 15.00 28 15.00 29 0.00 30 0.00 Hose 31 0.00 Supply 12.00 27.7 12.00 27.7 14.06 30.0 20.75 - 20.78 21.72 23.75 26.60 21.71 21.92 22.77 24.27 21.71 21.85 22.85 41.14 41.20 41.35 54.10 67.12 - 68.22 500.0 68.22 - LEGO STORE - WESTFIELD MALL Sheet 10 Pipe Pipe Information Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt (ft) Hose ID F (ft) Vel Elev Pe Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes 1 12.00 8.00 27.7 1" 2E 1T L 3.0 120 Pt 12.00 1 1FH4 F 33.0 10.3 Pe -1.30 10 15.00 27.7 1.049 33.0 T 36.0 0.2379 Pf 8.57 DR1:K=6.31 2 12.00 8.00 27.7 1" 1T lE L 1.5 120 Pt 12.00 2 1FH4 F 31.0 10.3 Pe -1.30 11 15.00 27.7 1.049 31.0 T 32.5 0.2379 Pf 7.73 DR2:K=6.45 3 3 12.00 8.00 12 15.00 30.0 1" 1T lE L 1.5 120 Pt 14.06 1FH4 F 31.0 11.1 Pe -1.30 30.0 1.049 31.0 T 32.5 0.2755 Pf 8.95 DR3:K=6.44 10 10 15.00 6.31 [28.7] 1 1/2" 11 15.00 28.8 1.682 L 1.0 120 Pt 20.75 DR1 F 0.0 4.2 Pe 0.00 T 1.0 0.0255 Pf 0.03 11 11 15.00 6.45 [29.4] 1 1/2" 12 15.00 58.2 1.682 L 10.0 120 Pt 20.78 DR2 F 0.0 8.4 Pe 0.00 T 10.0 0.0941 Pf 0.94 12 12 15.00 6.44 [30.0] 1 1/2" 13 15.00 88.2 1.682 L 10.0 120 Pt 21.72 DR3 F 0.0 12.7 Pe 0.00 T 10.0 0.2030 Pf 2.03 13 13 15.00 6.44 [31.4] 1 1/2" 14 15.00 119.5 1.682 L 8.0 120 Pt 23.75 DR3 F 0.0 17.3 Pe 0.00 T 8.0 0.3566 Pf 2.85 14 14 15.00 6.44 [33.2] 1 1/2" 1T 25 15.00 152.7 1.682 L 16.0 120 Pt 26.60 DR3 F 9.9 22.1 Pe 0.00 9.9 T 25.9 0.5613 Pf 14.54 BL1:K=23.81 16 16 15.00 6.44 [30.0] 1 1/2" 17 15.00 30.0 1.682 L 7.5 120 Pt 21.71 DR3 F 0.0 4.3 Pe 0.00 T 7.5 0.0276 Pf 0.21 17 17 15.00 6.44 [30.1] 1 1/2" 18 15.00 60.1 1.682 L 8.5 120 Pt 21.92 DR3 F 0.0 8.7 Pe 0.00 T 8.5 0.1001 Pf 0.85 18 18 15.00 6.44 [30.7] 1 1/2" 19 15.00 90.9 1.682 L 7.0 120 Pt 22.77 DR3 F 0.0 13.1 Pe 0.00 T 7.0 0.2147 Pf 1.50 LEGO STORE - WESTFIELD MALL Sheet 11 Pipe Information Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt Pipe (ft) Hose ID F (ft) Vel Elev Pe Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes 19 19 15.00 6.44 [31.7] 1 1/2" 1T 26 15.00 122.6 1.682 L 18.0 120 Pt 24.27 DR3 F 9.9 17.7 Pe 0.00 9.9 T 27.9 0.3736 Pf 10.42 BL2:K=20.81 21 21 15.00 6.44 [30.0] 1 1/2" 22 15.00 30.0 1.682 L 5.0 120 Pt 21.71 DR3 F 0.0 4.3 Pe 0.00 T 5.0 0.0276 Pf 0.14 22 22 15.00 6.44 [30.1] 1 1/2" 23 15.00 60.1 1.682 L 10.0 120 Pt 21.85 DR3 F 0.0 8.7 Pe 0.00 T 10.0 0.0999 Pf 1.00 23 15.00 6.44 [30.8] 1 1/2" 1T L 18.0 120 Pt 22.85 DR3 23 F 9.9 13.1 Pe 0.00 27 15.00 90.9 1.682 9.9 T 27.9 0.2147 Pf 5.99 BL3:K=16.93 25 25 15.00 23.81 [152.7] 4" 26 15.00 152.7 4.260 L 10.0 120 Pt 41.14 BL1 F 0.0 3.4 Pe 0.00 T 10.0 0.0061 Pf 0.06 26 26 15.00 20.81 [133.6] 4" 27 15.00 286.3 4.260 L 7.5 120 Pt 41.20 BL2 F 0.0 6.4 Pe 0.00 T 7.5 0.0194 Pf 0.15 27 15.00 16.93 [108.8] 4" 8VE L 290.0 120 Pt 41.35 BL3 27 F 71.6 8.9 Pe 0.00 28 15.00 395.2 4.260 71.6 T 361.6 0.0353 Pf 12.75 28 28 15.00 29 0.00 4" 1T 1B26 L 22.0 120 Pt 54.10 Top of Riser 5VE F 71.1 8.9 Pe 6.50 1B26 = 3.24# 395.2 4.260 71.1 T 93.1 0.0353 Pf 6.53 29 0.00 6" L 250.0 140 Pt 67.12 29 F 0.0 4.3 Pe 0.00 30 0.00 395.2 6.160 T 250.0 0.0044 Pf 1.10 30 0.00 6" L 0.0 140 Pt 68.22 30 500.0 F 0.0 9.6 Pe 0.00 31 0.00 895.2 6.160 T 0.0 0.0200 Pf 0.00 Supply Customer MARK ECHO 837 SOUTHCENTER MALL TUKWILA, WA 98188 GUARDIAN SECURITY LIFE AN ....Act MARK ECHO Project # 0 PROPERTY PROTECTION List of Materials Vendor Guardrail Security Systems +uc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: SEPT.,9,08 Item 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) '22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Qty. Manuf. Siemens Siemens Siemens Siemens Siemens Siemens Siemens PAD -3 AD2-P HTRI-D HTRI-R SET CW,W SET W ZR-MC-W,W Model Description Unit Pri Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Total Price Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Starica,a • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Marc Ecko 837 Southcenter Mall Permit No.: 08-S-425 Date: August 19, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. ST FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3ER SHEET TITLE FA -01 SYSTEM I N FO R MATT O N FA -02 TYPICAL WIRING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLA\ SHEET INDEX WIRE SCHEDULE AND CO\DUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHCRITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FRCM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONCUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) V/HERE THE CABLE IS INSTALLED GENERAL NOTES QUANTITY EX 2 2 2 1 1 SYMBOL DESCRIPTION MODEL W ithou {:Comments Q As Note Noteci Re4 © Per r€: i-.0:tacheJ Letter plans have be<? : ; The Tukwila Fire =ration Bureau foc with current City girds. Accept=^c : j , „ errors and ::::!ons which do not , i.or-, ,;solations of adopted -...,ndards and ordinance:-. Ti-, .-L:ronsibility for the 1uacy of desinrl lesigner. i;tions, deletions o: revision= nc drawings after ,Ls date will void this acceptant ..'1: wtii require a submittai of revised drawings r:. • quent approval. ;"final acceptance Is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: S-"1 By: 5i l MANUFACTURER BACKBOX P„a; c ti 2.f.,'6 -,11:73-1-1D7 d IS - F -Q76 ' :end exact af. i's .. b r shut- down or rc to. jon approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must he presented to:;i e ctor prior to of Acceptance Fire Alarm and L. _. _ _ on Svstcros. Failure of test will result in a Re -inspection Fee and `..rmination of the tPctinel MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY (EXISTING) PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP DUCT DETECTOR FDBZ492-HR W/ HFP-11 DET. SIEMENS DUCT HOUSING TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIEIA/ VERIFY " e.' (10 IN FIELD d HT -M SINGLE INPUT INTERFACE MINIMODULE HTRI-M SIEMENS 4S BOX VERIFY IN FIELD HT -R INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S BOX VERIFY IN FIELD FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S BOX CEILING 10 Di FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXTN END -OF -LINE RESISTOR A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A RED NOT APPLICABLE AS BUILT ADD OR CHANGE N/A N/A N/A N/A N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND -\\ NORDSTROM j 3 LEVELS 171,275sf PcnN..,C COWL 1 macys 4 LEVELS 250,407sf LEGO STORE #837 / SPACE #1450 k' GATE Lru.o . LOC'ER ROCU KIO'S 7 - PAM 1 NvCgY.YKK F_AP, C DCC CASUAL Kiss Ef.: Tf LORASY S.D WEYER ,EACLERS •. e y : 3 LEVELS' 276,468sf PAID APR 27 2015 TUKWILA FIRE cc z2 S SITE PLAN Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I DMG I DESCRIPTION SHOP DRAWINGS DATE LO M N 0 0 Z Y 00 owT Er O �Z Q o -10 C/)w¢z O wQ (,Dcrzs W -J o W CC DD V- OI-- co 111 (1) L (I)} 'CALE: NOT TO SCALE 0 0 z DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/ 15 BACKROUND PLAN PROVIDED BY: I0B NUMBER:12077-1/ U FA-Ol SHEET SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 9202470010 Site Address: 837 Southcenter Mall, Space 1450 Suite Number: Floor: Tenant Name: Lego Store New Tenant? E- Yes ❑ - No Property Owner's Name: Westfield Shopping Center Mailing Address: POB 130940, Carlsbad, CA 92013 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 Company Name: Guardian Security Systems Mailing Address: 1743 First Ave South, Seattle, WA 98134 E-mail Address: kveliz@guardiansecurity.com Total number of new/relocated devices or sprinkler heads: 1 Valuation of Project (contractor's bid price): $ 6600. City State Zip Fax Number: 206.628.4990 Scope of Work (please provide detailed information): Add 18 device to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Date: 1 2 Print Name: Karina Veliz Day Telephone: 206.349.5889 Plan Permit App.doc 1/2/13 TFD FP Form 8 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TUBE OUTLET SAMPLING TUBE INLET SAMPLING DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 12OVAC-60a —{ DEDICATED OE ONCY FROM EXISTING MAIN FACP C CABLE C' CABLE Q6 N L IX 00 0 0 PAD -3 oo° INPUT INPUT TROUBLE NCI NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - S S 3.6k EOL R Mit 0 0 (-) (+) (-) (+) ZNAC S4 , NAc S3 NAC S2 NAC S1 EXISTING POWER SUPPLY WIRING DETAIL COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIL 0 HARD LID CEILING END OF LINE DEVICE(3,6K 1/4W) SUPERVISED SWITCH GROUND 0 HTRI-R STATUS LED co O N.O. 0 COM cc HARD LID SPEAKER SUPPORT TILE BRIDGE 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE '2)c) o, 000 000 \\\\\\,,iL,„ SPEAKER STROBE & STROBE CEILING MOUNTING DETAIL FROM REMOTE POWER SUPPLY FEED FROM EXISTING VOICE CIRCUIT (V CABLE) RETURN TO EXISTING VOICE CIRCUIT (V' CABLE) O N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 MUSIC () () STROBE SPEAKER (+) (-) STROBE (+) ( ) STROBE SPEAKER (+) (-) T T 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING RELAY CONTACTS (4.OA @ 125VAC) (4.0A @ 30VDC) HTRI-R RELAY MODULE BACKGROUND MUSIC SHUTDOWN WIRING DETAIL SPEAKER STROBES & STROBES ONLY WIRING DETAIL FROM PREVIOUS ADDRESSABLE 2 DEVICE TO NEXT DEVICE OR END OF LINE TYPICAL WIRING AND MOUNTING DETAILS TBI ®®®®®©® 00110 NO COM NC 2 TO FAN SHUTDOWN EOLR 470 0 SWITCH + - INPUT LED TSM -1 HTRI-M RED BLK 00 + TO NEXT ADDRESSABLE DEVICE ORG ORG GRN NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL DUCT DETECTOR/HTRI-M MODULE/TSM-1 SWITCH WIRING DETAIL NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F 0' C TO 100' F 31T C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> E. DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCAIIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT > TO NEXT ADDRESSABLE DEVICE 0 0 TO NEXT DEVICE 0 0 CADDY BAR — EDI SMOKE DETECTOR TSUSPENDED ILLUMINATED CEILING SMOKE DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION [HOP DRAWINGS DATE 04/23/15 R CCaaa L) CO cc 3: J U SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/15 BACKROUND PLAN PROVIDED BY: \OB NUMBER:12077-1} I. SHEET FA -02 FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION Project: LEGO STORE Panel: EXISTING BPS PAD -3 BOOSTER POWER SUPPLY Date: April 23, 2015 Module/Device Qty Standby Total Standby Alarm Total Alarm (mA) (mA) (mA) (mA) Power Module 1 30 30 0 30 30 0 A TOTAL FIRE ALARM POWER SUPPLY 30 30 B Auxiliary Device Current 0 0 C Notification Appliance Load (Max. Total / mA) 0 D E F G H J K 5254 Total(A)= CALCULATION 30 : Total(B)= 5284 Total current ratings of all devices in system (line A + line B + line C) 30 5284 Total current ratings converted to amperes (line D x .001) 0.03 5.284 Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5). 24 Multiply lines E and F Total Standby AH 0.72 Alan -n sounding period in hours (5 mins+ .0833 hours) 0.0833 Multiply lines E and H Total Alarm AH 0.4401572 Add lines G and I Total Standby and Alarm AH 1.1601572 Multiply line J by 1.2 (20% extra insurance to meet desired performance) 1.39218864 12-V DC BATTERY SIZE RECOMMENDED (AMPERE -HOUR) 7 CALCULATIONS .,'r � ",;.,, ..*w ,,, � w• Notification Appliance Circuit Detail PROJECT: Panel: Date: , LEGO STORE -POWER 2.58 5254.00 EXISTING BPS PAD -3 SUPPLY Wire Resistance April 23, 2015 CURRENT TOTAL= F' 1vY 'd �s�w; f t v <^ RG I &F M M', �* } A, 1„\„ ( h "+ b i ,). y 1 „ :y. d f d 4 I f r a' a f I 1 ''Y t !R N 9 + 3f wl oY h r, { { �� i i F - i $fii i 1 F #' •P' y ; -, _ .�.-..,� y # �" Y ky(9 A'ry", %� W1, �' i JJ j, ;fN 10 SET -MC -CW ©15cd,.§ 69 ` 690 1 T .M _ _n __ __ . _- n _._ SET-MC-CW@30cd 111 ci :SET -MC -CW @75cd 200- 01 SET -MC -CW @95cd 264 SET -MC -CW ©15cd 64 641 as<aK DEVICES ZR -MC -CW 30 cd 111 0 .. 11., TOTAL mA= 754 14 325 22.74 754 ; _1.68 0.75 1.26 , - _ : ^ pTv p �µy wR� T _ Total Wire Resistance (R) (WL * 2) * (R/ft) r„ �r� T Total Device Load, Amps (I) Cct Load) Voltage Drop (E) (E= I * R) 14 EOL Voltage 24 E) I 22.74 Total Wire Resistance (R) ,» rr:i+''' a 5, °P¢;�lF 1, } : +� '4' y'I'If X �,e'I5'.� r { i t 9 , }h;o, '„ ! ( ! t Y f uN''^I � \ i ! ;SET -MC -CW @l5cd 69 0 Standby: 6.34 SET -MC -CW @30cd 111.:.. S . 'SET -MC -CW @75cd . 200_ 0 . Total Device vi a Load Amps l Load, P {) Voltage Drop (E) SET -MC -CW @95cd : 264 0 ZR -MC -CW @15cd 69' 01 of tai Cct Load _ (T} ;(E=i*R) DEVICES ZR -MC -CW @3Ocd .. 111 0 TOTAL mA=3 1500 j 14 24.00; 1500 ' 0.00 :Total Wire Resistance (R) ; (WL 2) (R/ft) Total Device Load, Amps (I) (Total Cct Load) 1.50 Voltage Drop (E) F (E= I * R) _ 0.00 a■� . .,, aS'� , "t ,, Nr. x }, �, V „t,C\„+°�� §.#�,5 .., to EOL Voltage 24 E) �1N 24.00 .v.,,,.., S.P, .. ,S •, :¢' N �Yvi M \ Palm , ,�'� .:',, ,,;, „ ., ¢, I.p - ., :, r r u. ,e, 7• ,,, $ ,'4. e". y,,;;,. ! 1 ,, f4, ,. � '�� � a: .; 1 rc„ a, 1 '"d i � 'Y�i p ,*5,�,\. � �,� ^'� $ ^+ � ,y .�, ,.v', F',+, 1,7 au�;f ,ti'�� C . 4 ", w ,� ,, .",t �„V�,;:�Mr�Po �,� of l!'fi S l� ,. :\:i �eu,i "V\ r��F 4 M,:'r, F;,�, *1, ,'j '� �,, mp' �' ������i �,k. Y�. :� s r _ �.__,......,.....�_.�. Y» ,'..�„S`k ..'.":, »,� V,k Y:�, u5!1 W �,r'! &rM.' ,y �Ar,u R' _ D r ',:' R:t � SET-MC-CW__i@1 5cd 69 0 �`",.. �.,_.., ,.� ..�.. _...�_,_ _ Amps Total -MC-CW 30cd, SET 0x @ SET -MC -CW @75cd 200. 0 SET -MC -CW @95cd 264 0 . .SET-MC-W@110cd 233 0 DEVICES ZR -MC -CW .30cd 111 0 0 TOTAL mA=' 15001 14 24.00 1500 0.00 1.50 0.00 2 Total Wire Resistance (R) j (WL 2) (Rift) 0.0022 0.0023 Total Device Load, Amps (I) otal Cct Load Voltage Drop ( E) j `(E= I * R) f �4µ } 'n EOL Voltage:' d4 '..nE 24.00 Y rn d 1d i , , \ f �� , ,, ,t"i ��!',b I • /y�� flp \ ? � 5: ,,/ i, r, „ „ i, 'FFjN �1$"}Ir r�Y � , J ',,.,r � f u„� ,y y:.." { . Vg, N � r h„ , w, gym,', , r,,,J, 1, r. 1',,,; ,,,e:''S'�Mi r, r>w , •<.,;: r3 i "'4..,.\» }�,1 ,, �,, ,a„ ,n. ,n.'. ,�,, ,, a ^,,..,� .. a '.,:•,-,..if r. rY :,�� Cr" `.�:�„� t (5 "�= Via. M:rm yy r `� , » n¢, f * y, � •�i."'. N 4e; �'' , x,a,,,t Z. '.'n" 2 :SET -MC -CW @15cd : 69 0' 0.0635 -r., CW SET-MC-30cd 111 0. SET -MC -CW @75cd 1 200' 01 SET -MC -CW' @95cd: 264 0 SET -MC -W @110cd :.... 233: 0 DEVICES ____ ZR -MC -CW 30cd 111 0 0 TOTAL mA= 1500 14 24.00' 1500 3 : - Total Wire Resistance ( R) (WL *2 ) * (R/ft) 0.00 1.50 0.00 0.021 Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage 24 E) 24.00 CALCULATIONS .,'r � ",;.,, ..*w ,,, � w• "I h, ,I h , r,, ii i, � e, �, �, l�,�r A. dr,lt M .,r�.;, Id5 °"y:,^' rv, ,'i� ,a r4 i �;b Sj: p"'�5%40v, F ',hr 1,'.S PY „v ,,., V �,,,, ,,.r. jf •.y N b;,, ��1Jj \ � 4J"W ,1 k A\4,,, � d},u, ky(9 A'ry", %� W1, �' i JJ j, ;fN Sot, �aC M� S j4 k{ v 132©.1/2-WATT SET -MC 1/2 WATT 7.08 - - --, SET @1/4 -WATT 14.14; 934.56 as<aK I .--.�-,,.,.,.. ' DEVICES SET1/2 WATT 28.29 132 TOTAL mA=I 0 934.56 14 1228 18.08; Current Load: Total Wire Resistance (R) Standby: 6.34 Alarm: Total Device vi a Load Amps l Load, P {) Voltage Drop (E) 1 of tai Cct Load _ (T} ;(E=i*R) c�.93 5.92 ,. EOL Voltage �" 24 - E 180 Device Type Qty Amps Total Amps Total HFP-11 2 0.0022. 0.0022 0.0023 0.005- FDBZ492-HR 2 0.0635 0.0635 0.064 0.128 HTRI MODULE 3 : - 0:009600 0.0096 0.021 0.063 0.0731 Amps 0.191 Amps TO NEAREST EXISTING v"p � b SPEAKER CIRCUIT TO NEAREST EXISTING POWER SUPPLY r V Sby TO NEAREST EXISTING DATA LOOP (EXISTING BACK-OF- THE-HOUSE ACKOF- THE-HOUSE J -BOX) SV S,V S,V SV S,V SV S,V S,V SV S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8 S1-9 S1-10 S1-11 15cd 15cd 15cd 1 5c 15cd 15cd 15cd 15cd 15cd 15cd 15cd (HT -R SINGLE LINE DIAGRAM EOL S1 FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC SHUTDOWN. DUCT DETECTOR, MONITOR MINIMODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Notification Appliance Circuit Detail - VOICE ' 'Wire Resistance 2.58 CURRENT TOTAL= 934.56 PROJECT: Panel: Date: ,, ^, ' LEGO STORE EXISTING SPEAKER CIRCUIT April 23, 2015 ��►►„ //ms�sa ry 1 ,.r'p,�,. 4 �.Y r d\' I ' � f �,`' �a im>: Y L4pF 1br�Yrr mwi'�' "� X �g r irbMu�d�,I Mr�f�� ri,:, R :Y ,a T f Aa„ fa .\ h :, ,,,. ,, w. i R•MI,:x, ,'„ ,,, , �'. .,, : -�, � "'; 4. p Y 1 h"i'.,, A 1, M r n ,. �,,.. .,H ..e� r'. w Md. � r , wr � ., � a i,5 �,, ,. v, G ,. �% .3nv „,,a.,. C .A' yM ��„ � a ,�:..:.. G n r .. ., a ti y '} v g 1 VYc'� Wt� ry Fi , ,�,. r ,'I� ry ., .�. � , ! t t '4, j'�} ai, .it ..w K,,,, o 0u �yr f � � n.:. 7 k {;R,V,� 6 f'V dt „� ;,,C , .w M .MY �"r „ r "w�;tw �j,. Y r• r i �bb �J . F, 5 tl d r r �� r T, t 3 rryy i D ■/#�� a C e 0 't ti�+, �" a ,,,�B.y,l '',VI .-.e,.� Ya ,i'", i � g, '1. \ d v i ,,: ,.u, ,'' a �,'. � 7 \ y n �y ! h4 _Y .., „ g �0 /S $ 4 {t v4 DATE SET -MC @1/4 WATT 3.54; 132©.1/2-WATT SET -MC 1/2 WATT 7.08 - - --, SET @1/4 -WATT 14.14; 934.56 as<aK I .--.�-,,.,.,.. ' DEVICES SET1/2 WATT 28.29 132 TOTAL mA=I 0 934.56 14 1228 18.08; 934.56 Total Wire Resistance (R) (WL * 2 )"(Rift) ._ .___ 6.34 Total Device vi a Load Amps l Load, P {) Voltage Drop (E) 1 of tai Cct Load _ (T} ;(E=i*R) c�.93 5.92 ,. EOL Voltage �" 24 - E 180 TO NEAREST EXISTING v"p � b SPEAKER CIRCUIT TO NEAREST EXISTING POWER SUPPLY r V Sby TO NEAREST EXISTING DATA LOOP (EXISTING BACK-OF- THE-HOUSE ACKOF- THE-HOUSE J -BOX) SV S,V S,V SV S,V SV S,V S,V SV S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8 S1-9 S1-10 S1-11 15cd 15cd 15cd 1 5c 15cd 15cd 15cd 15cd 15cd 15cd 15cd (HT -R SINGLE LINE DIAGRAM EOL S1 FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC SHUTDOWN. DUCT DETECTOR, MONITOR MINIMODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 04/23/15 z as<aK MQM 0 w Z co J oW) 0 U� woa.z z Cr a 0CO CCU)(/) O 2�< z w QCC DD o - CC u- OI - N M GO U w C±) >- C,) 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/15 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 12077-11 1 SHEET FA -03 D FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC SHUTDOWN. DUCT DETECTOR, MONITOR MINIMODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. S Si -3 1 5cd �+ TO EXISTING BACK -OF -THE HOUSE JUNCTION BOX s.v VIC -TI ^IC CORRIDOR 1 TOILET ROOM STOCK ROOM S S1-1 15cd S1-2 1 5cd s,v S1-4 �15cd S S1-7 Di 1 5cd s,v s,v S1-6 1 5cd iv'//./ ��////. i'//.//// J ---1,1S1-8 1—r%4 15cd SALES FLOOR Si -9 nom/ 1 5cd L1V S S S1-11 1 5cd S1-11 15cd s,v- FIRE ALARM SYSTEM PLAN ,/ / / i ./,/'/ / / ii'/:/'/ S1-10 15cd /f / i i'/'/ / / / r mi SI:OPKIT TRACK RECESSED IN CEILING, %; ��, SEE A4.1 FOR INFO \11 ci\ SIGNAGE, PROVIDED BYOWNER `1 C� 1 � 1j • ENTRY Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: CD g 0 DESCRIPTION SHOP DRAWINGS DATE 04/23/15 2<aaaa 1/4''=1'0” DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/15 BACKROUND PLAN PROVIDED BY: \0B NUMBER:12077-1/ C SHEET FA -04 FlexHead Sprinkler Drop Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' legnths Multi -Port Bracke_t_ \ Adjustable Hub FLEXHEAD I N0USt RI0 Flexhead`tommercial Ceiling Unit T -Bar Ceiling Installation Model #2024,2036,2048,2060,2072 STOCK ROOM G-3 NO. OF SPRINKELRS DENSITY DESIGN AREA WATER FLOW RATE RESIDUAL PRESSURE Co BASE OF RISER OCCUPANCY CLASSIFICATION FLOW TEST INFO: 120 PSI STATIC 120 PSI RESIDUAL FLOWING 8000 GPM REMOTE AREA 12 .30 GPM/SF ENTIRE STOCK AREA 395.2 GPM 67.12 EXTRA HAZ GP 1 SALES FLOOR 00.2 INSTALL ALL PENDANT LIGHTS SO SEAMS IN SHADES FACE TOWARDS BACK OF SALES FLOOR EXISTING' CORRIDOR C) G-1 I I.2' -O" GENERAL LEGEND —o 0 BOD BOB BOJ FOS FOW EARTHQUAKE BRACING PIPE HANGER GROOVED CAP RIGID COUPLING . ( UNLESS NOTED ) CAP PLUG CENTERLINE HYDRAULIC REFERENCE POINT CENTERLINE. PIPE TO BOTTOM OF' DECK CENTERLINE PIPE TO BOTTOM OF BEAM CENTERLINE PIPE TO BOTTOM OF JOIST FACE OF STUD FACE OF WALL FOC AFF CH R.C. 4 E/C C/C C/E GG TG TxF ATR FACE OF CONCRETE ABOVE FINISHED FLOOR CEILING HEIGHT REDUCING COUPLING OUTLET COUPLING WELDED OUTLET "FIT" FITTING. END TO CENTER CENTER TO CENTER CENTER TO END GROOVE/GROOVE THREAD/GROOVE (ALSO "Cr) THREAD/"FIT" (ALSO "FxT") ALL -THREAD ROD TOILET ROOM 04 K!b FLAN J NORDSTROM macyy 111` TT, P4 • 0 0 o a I o MI I APPROX 290' OF 4" TO TOP OF RISER TENANT SPRINKLER PIPING PLAN SCALE: 1/4" = 1'-0" 0 2' 4' 8' Group A Plastic Storage 12' Solid -piled, palletized, bin box, shelf, rack, and back-to=back shelf storage: Uriexpanded and expanded NFP A ##13 >5 to s10 >5 to s10 s1.5 >1.5: to. s3.0 >1.5 to - s3.0 15 20 4.6 6.1 01-12 - EMI EI -12 0.50, 100 0, 50, 100.. 0, 50: 100 0, 189, 379 0. 189,: 379 0. 189, 379 250 . 500 500 916--. 90 1893 120 1893 120 >10. to s12 >3.0 to.. s3.7: 17 5.2 EH2 0, 50. :100 0, 189, 379 500 :1893 120 solid piled: palletizeci,_ bin box, shelf, and back-to-back . shelf storage >10 to s12 >3.0 to S3.7 32 9.8 EH2 0, 50, :100 0. 189; 379 500.-. 1893 120 >10 to ` s12 TABLE 3: >3.0 t6 s3.7 32 9.8 OH2 +1 level of in -rack 0, 50, -100 0, 189; 379 250 916 90. SPRINKLERS SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. RELIABLE MODEL G5-56 QUICK RESP CONCELAED PENDENT 0 R3415 1/2" 1/2" 5.6 CHR CHR 155' 20 RELIABLE MODEL G5-80 QUICK RESP CONCEALED PENDENT R3412 17/32" 3/4" 8.0 CHR CHR 155' 12 TOTAL SPRINKLERS . = 32 THIS PROJECT GENERAL NOTES SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 - 2010 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS ORIGINAL SYSTEM CALCULATED FOR ORDINARY HAZARD GP 2 BACK OF HOUSE STORAGE AREA: STORAGE OF GROUP A PLASTICS NON EXPANDED IN CARDBOARD STORAGE TO A MAXIMUM OF 10' IN RACKS 12' CEILING HT IN STORAGE AREA EXTRA HAZARD GP 1 PER NFPA #13 TABLE 13.2.1 (@ LEFT) .30 GPM/SF OVER ENTIRE AREA 100 SF PER SPRINKLER MAXIMUM 500 GPM HOSE DEMAND CARTONS. TUKWILA FIRE DEPARTMENT Petr call 20€-575-4107 and give this Fire Permit No. ;Ind exact address for shut - 'town or r . o etion approval. 0 Without Comments O As Noted in Rei+ Per The Attached Letter These plans have been reviewed by The Tukwila Fire ,-evention Bureau for conformance with current City ndards. Acceptance is subject to errors and omissions which do not authorize violations of adopted :;andards and ordinances. The responsibility for the ;idequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: Ce -3 -is By: WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 LEGO 837 SOUTHCENTER MALL PAID TUKWILA, WA 98188 �U�I 2 Zo1 TUKi�VILA FIRE DATE: 5/15 DRAWN: C.O. SCALE: AS NOTED 1 OF 1 FILE COPY SHEET NUMBER SHEET TITLE SHEET INDEX MARK ECHO FIRE ALARM SYSTEM TUKWILA, WASHINGTON FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FRE ALARM SYSTEM FLOOR PLA FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN { J= Infi-z-3w r .:a•v!:....._'i.i _..•... , _ !..)lest'-: Fire P'=v..... 'si_;r,3u .:r : (. .,. ..::r, s.;t citY '„i1Ga;'c::::. r-..:fc: ` ..-:::i ::. ,S , %t'.. . r'..(i Orni:r._ii):;s 'A.:;`•••4':i j'.: 1 .........: ,. _ .,.:;,iF,"OptCd stall(:;..a ...-.... J:r4,.,.. .. . .. f:_1" the ar?::-_,,,i-...?.-,; o; •... .. 1; ^nt;r.r. t',0thik,:i= _. _ . . ;,s atter ink (i t? -,.'i?, '1)r.. J? ..,'i..:(::. •:ii.:....'i f=.;:u re a resublm ai of revia.:c,•r i ;gs ter •:;uub;,equent approval. Final acceptance is subject to field test and inspection b\ The Tukwila Fire Prevention Bureau. IDate: 9=i).-03 By: ,�->,,,,$1 FUKW1LA FIRE DEPARTMEi it Please call: 575.4402 and give this job No.0Llys. and exact address for shuti - aown or restoration approval: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. TA I? Harrri Because of Increased demand our ins rs' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES .AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 2 1 4 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP El INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD 0 DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD F< LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD I ® SMOKE DETECTOR HFP-11 W/ SIEMENS lel (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING n Q c FIRE ALARM STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B p STROBE WP (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD a MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright 2006 by Guardian PAID SEP - 8 2008 Tukwila Ft_e Ztz Security Systems, Inc. All Rights Res 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z d I- DESCRIPTION SHOP DRAWINGS DATE to 0 0 0 2 CCCaC CO co J C° O wiz E5F2 C.)(I)Z z W 2w W 0 _cog C I- 0 0 u. z 1.1.1 (1) �CALE: 1/8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 8/20/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC O DUCT DETECTOR LOCATI❑N END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 0 0 GROUND IC) © HTRI-R *STA11JS LED CO 0 N.O. r` 0 COM co 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL O LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE + + NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING \ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC }-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE 0.) O STOP IF LAST DEVICE () FROM XLS CONTROL PANEL OR - PREVIOUS ADDRESSABLE DEVICE{N END OF LINE DEVICE (3.6K 1/4W) RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 + Ie 01 TB1 S15 0000 123456 HCP TB2 0 0 + 654321 0 0 SUPERVISED_ /' SWITCH / GROUND / NOTE: 1) © © HTRI-D OSTATUS LED CO /NOT USED 0 0 0 O 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL BCAE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 0 GND N AC 013.111 El II PAD -3 0 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 24K uu 1*. + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) -SUPERVISED 1 SWITCH NAC -4 NAC -3 NAC -2 ________qNAC-1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE E DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0- 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSNBLE DEVICE (-)> 470 OHMS �IM EOL O TC INPU (+) S1 0 TS M-1 O o¢ zoo -8 O�o ' N-� X000 0 • • 12-3 Cc Ankh TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) 10 (-) STROBE SPEAKER 0 O EARTH GROUND ->(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE STROBE (+) ( ) STROBE SPEAKER (-) SPEAKERISTROBE AND STROBE LABEL SCALE SPEAKER STROBE OR STROBE ONLY R IRING O 14S DEEP BOX I WI 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX ((STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERrN TEMPERA RE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: U-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR r— DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX i WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX -\ MOUNTED ON CEILING. FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 1 /f�11 0 0 / / / 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved o 0' Ch CD (\.1 O `0 q) C.; o Z N � X La LU J F- F - W U) C5 LLI Q F- C/) K7 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z L DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 CaaCa 0 z p z 0 0 z 0 z E r1 V , 1 ..W (S.-CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:8/20/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -02 } Nre,";J 2, NORTH MARK ECHO WESTFIELD SOUTHCENTER MALL SCALE 10=1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED ❑UT 20A, 110 VAC BRANCH CIRCUIT, DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. MI Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 a<aa< Co co J� C$3 Q W2(3)z _ o czz W2 E. � ac=tn CC Q� <wo C co H .CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 8/20/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: j SHEET FA -03 j 8091 I NORDSTROM 3 LEVELS 171,275sf mervyrrs 2 LEVELS 65,237sf Macy' 4 LEVELS 253,407sf L sx a0; C Ci PRY CNtr3 CASJit 1.4 CMtt JEPA.1 KT- 'Ili E .EPE1Ers $ aa5i M:!1., NCr1tF CA ;A1EPA EYJSr3:�c WW1,. M.ELESS Y!.^.€ 5 •.51e.+.Ty1 �EASP 51s JW?A :caIE VAI SIZ<O, V> REPS PA«0, SG'1_ 'APE'S w •NT PAS.: I.ETPJ1NxE NORTH z C.1.1.5,1,5 C UEMCU1 �.EP- rzu a�a1u1 CHEE.0 CE FA^i1 rr MARK ECHO WESTFIELD SOUTHCENTER MALL 3 LEVELS 276,466sf J SCALE N.T.S 15 C 110 C 75 C 15 C EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION _ ____.___Notification Appliance Circuit Detail PROJECT:1 WESTFIELD SOUTHCENTER MALL Panel: i MARK ECHO Date: August 21, 2008 CIRCUIT:! S1 QTY Device Type 1...._ € SET -MC @15CD E ...- 64 i. 1 (SET -MC @30CD 1 981 2 ; SET MC @75CD 1751_._.350 1 !SET -MC @110CD 2331 233 0 ;SET-HMC-C@115CD € 318 0 0 I SET HMC-C@177CD 445' 0 0 1SET-HMC @135CD 318' 0 SET -HMC @185CD ; 4451 1 Z-MC@15CD i 64 0 !Z-MC@30CD 981 0 I SET-MC-CW@110CD DEVICES=16 Wire Resistance 1.62 CURRENT TOTAL= 809 !Alarm Current! Alarm Total Wre Size i Wire Length 1 Voltage at EOL Circuit Total 64 98 233 0 0. 64 0 01 TOTAL mA=! 8091 12 220 Total Wire Resistance (R) ( WL * 2)* (R/ft) 0.71 ___.___.....___._ Total Device Load, Amps {I) 0.81 (Total Cct Load) Voltage Drop ( E) 0.58 (E= I * R) EOL Voltage ` 19.82 (20.4 - E) 19.8233448 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: MARK ECHO Date: !August 21, 2008 CIRCUIT: SPEAKER CIRCUIT Device Type 70.7V1/8 0 !Wire Resistance 2.58 CURRENT TOTAL=!9 'Alarm Current; Alarm Total Wire Size Wire Length 1.81 9 01 0 0 Voltage at EOL ! Circuit Total Total Wire Resistance R (WL*2)*(R/ft) 1.05 0, 0 0 TOTAL mA=1 0 -4----___ _------ -- Total Device Load,_ Amps (I) (Total Cct Load) Loadl_Amps (Total Voltage Drop (E ) EOL Voltage (20.4-E) 0.01 20.39057268 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: MARK ECHO FRCP ADD ONS DESCRIPTION SHOP DRAWINGS 1 Current Load: 5/15/08 Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R HTRI-D ICP -B6 2 0.009600 0.0096 0.021 0.042 0.001600 0.0035 0.005 0.0731 Amps 0.106 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 25% Derating= 2.204 Amp -hours Total System Current Load: 2.204 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION _ ____.___Notification Appliance Circuit Detail PROJECT:1 WESTFIELD SOUTHCENTER MALL Panel: i MARK ECHO Date: August 21, 2008 CIRCUIT:! S1 QTY Device Type 1...._ € SET -MC @15CD E ...- 64 i. 1 (SET -MC @30CD 1 981 2 ; SET MC @75CD 1751_._.350 1 !SET -MC @110CD 2331 233 0 ;SET-HMC-C@115CD € 318 0 0 I SET HMC-C@177CD 445' 0 0 1SET-HMC @135CD 318' 0 SET -HMC @185CD ; 4451 1 Z-MC@15CD i 64 0 !Z-MC@30CD 981 0 I SET-MC-CW@110CD DEVICES=16 Wire Resistance 1.62 CURRENT TOTAL= 809 !Alarm Current! Alarm Total Wre Size i Wire Length 1 Voltage at EOL Circuit Total 64 98 233 0 0. 64 0 01 TOTAL mA=! 8091 12 220 Total Wire Resistance (R) ( WL * 2)* (R/ft) 0.71 ___.___.....___._ Total Device Load, Amps {I) 0.81 (Total Cct Load) Voltage Drop ( E) 0.58 (E= I * R) EOL Voltage ` 19.82 (20.4 - E) 19.8233448 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: MARK ECHO Date: !August 21, 2008 CIRCUIT: SPEAKER CIRCUIT Device Type 70.7V1/8 0 !Wire Resistance 2.58 CURRENT TOTAL=!9 'Alarm Current; Alarm Total Wire Size Wire Length 1.81 9 01 0 0 Voltage at EOL ! Circuit Total Total Wire Resistance R (WL*2)*(R/ft) 1.05 0, 0 0 TOTAL mA=1 0 -4----___ _------ -- Total Device Load,_ Amps (I) (Total Cct Load) Loadl_Amps (Total Voltage Drop (E ) EOL Voltage (20.4-E) 0.01 20.39057268 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS 1 DATE 5/15/08 co J'- J c0 O 2 2z _ Wo U �zz W 2w CCQ1 < 5 wO ��� N. co F- J W z 0 z 0 V W co >— (S-CALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:8/20/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1..1013 NUMBER: SHEET \ FA -04 4. OF FIABERDASHERY 1 FIXTURE &TRACK UGI-ITING ©A 0A 0A °A 0A 0A •'r, ri ORTANT Because of interred demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4107 to schedule your inspections a minirnui-li of 48 hours in adv„-.r;rl of he dale you want an inspection. 1 tj Without Co:nm3ftts As Noted in Red Per The Attached Leiter !nese plans have becIn revic•„ ,_:d by The Tukwila Fire Prevention Bu .? 2!.; ;or c.0 ::r',';.::,:.. - with current city,/ standards. A+:. c1.._,,,.a. arrcrs and OmiSsionu •t'+1 r l;i c c- ' 2doptt�c, d t stemarcis o.. ri,.:?; :' or U e l adequacy ci t Additions. ; j this date star resubmittal of r ,_ • Final accepi�•nce .. r. ; t ,d inspection The Tukwila Fire Provoniion r.turt;r�u, /Date: O -/q By: b4 c 17 TUKWILA FIRE DEPARTM' Please call: 575.4407 and give this job and exact addrecs for shuir -morn or restoration 3PDiG'val OT CE Weld stamps must be inspected before pipe is hung. not paint piping: cicir to hydrostatic test Design per NFPA 13 — Ordinary Hazard Occupancy —130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 18 — Add Reliable G4A Quick Response Concealed Sprinkler Heads 155° %Z x %Z 9 — Add Reliable FIFR Quick Response Chrome Pendent Sprinkler Heads 155° 1/2 x %z Total: 27 No. 12 Concrete Hangers ® Hanger Rings / Anchors: UL Listed & FM Approved ® Hanger Rods: Comply with NFPA 13 O All Thread Rods 0 Machine Thread Rods • Finishes: O Standard Components 0 All Galvanized Components 1” = 25.4 mm Components 1. Drop-in Anchor 2. Spring Clip Ceiling Plate (optional} 3. Hanger Rod . 4. Adjustable Hanger Ring Application / Description No. 12 Hangers are designed to support piping under smooth or flat concrete slab construction. They utilize an anchor that is set flush in a -hole predrilled in the concrete, then expanded against the sides of the hole with an internal plug. NFPA 13 terms this type of fastener an "expansion shield". In "Automatic's" data, however, the manufac- turer's nomenclature is used. It is called a drop-in anchor. There are 3 components in a basic No. 12 Hanger: The drop-in anchor, a threaded rod and an adjustable hanger ring. The rod may be either all thread .rod (ATR) or ma- chine thread rod (MTR). All thread rod is considered to be standard, however. As a rule, machine thread rod is pro- vided only when it is a specific -requirement of the job specifications. As an option, the hanger may be furnished with a spring clip ceiling plate when a more finished appearance is needed in an area. NFPA Requirements / Limitations NFPA 13 has specific requirements and/or limitations Ail aim .sarssmear s hem sr tam frhal :-.II /Sart aerre for the use' of expansion shields (drop-in anchors) when they are installed in the vertical position. The standard reads: . . . In concrete having gravel or crushed stone aggregate, expansion shields may be used in the vertical position to support pipe 4" or less in dia- meter. For the support of pipes 5" and larger, expansion shields if used in the vertical position shall alternate with hangers connected directly to the structural members such as trusses and girders, orto the sides of concrete beams. In the absence of convenient structural members, pipes 5" and larger may be sup- ported entirely by expansion shie/ds in the vertical position, but spaced not more than 10 ft (3 m) apart. Expansion shields shall not be used in ceilings of gypsum or similar soft material. In cinder concrete, expansion shields shall not be used except on branch lines where they shall alternate with through bolts or hangers attached to beams. =t --w ea Man 23=Zarcoon*.ett =me 31a Calin.ner.a Available in I Cc • i - Run- s� I • _--X X x . I x x • x L,� 1; U14- Ne:1-Tee Lo Ito-, iii -moi Branch Connector from WARD ItPai rre CROWN FiRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 r��'LECOPY l MARC EcKc5 Cul & cSew SOUTHCENTER MALL 3 7 SOUTHCENTER PARKWAY r - - TUKWILA, WA 98188 AUG 18 2008 Tukwila Fire z zb/F7 ,775-3% DATE: 8 -15 1 DRAWN: J /< I SCALE: '% r5- 1 1 837 SOUTHCENTER MALL ASSOCIATED PERMITS 15-F-076 08-F-449 15-S-098 08-S-425 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lego 837 Southcenter Mall Permit No.: 15-S-098 Date: June 3, 2015 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. Hydraulic Calculations Sheet 1 for Project Name: LEGO STORE - WESTFIELD MALL Location: TUKWILA, WA Design: Occupancy classification: Density: Coverage per sprinkler: EXTRA HAZARD GP 1 0.30 gpm/sq.ft. 100 SF MAX Type of sprinklers calculated: K=8.0 No. of sprinklers calculated: 12 heads Hose streams: 500.0 gpm Outside Hose Total water required: Including hose streams Date 05/31/15 Job: LEGO 68.22 psi @ 895.2 gpm @ Supply 118.26 psi available @ 895.2 gpm Below curve by 50.04 psi Type of System: Wet Water Supply Information: 120.00 psi Static, 20.00 psi Residual @ 8000.0 gpm Phone Number: Notes: GROUP A PLASTICS NON EXPANDED IN CARTONS ON RACKS TO 10' MAX 12' MAX CEILING HT Program: 'HydroCalc' by Micro Space Systems www.MicroSpaceSystems.com p CERTWICATEE OF NCOMPE ETENCY FIRE PROTECTION SPRINKLER SYSTEP95 John J. Abel 9760401 -CA Level 3 Moe ;,.- .n,,•. Inc. Pressure (PSI) 3 ■ Sy►stem demand = 68.22 psi with 895.2 gpm flowing. a 0 0 01 D 0 OD 0 0 Ci LEGO STORE - WESTFIELD MALL Sheet 3 Description of Fitting abbreviations Code Description T Tee E Ninety degree elbow VE Victaulic ninety degree elbow B26 Wilkens Model 350A Double Check Valve Assy. FH4 FLEX HEAD - 4' Description of Other abbreviations Code Description DR Drop BL Branch Line CM Cross Main PT Total pressure PE Pressure loss due to elevation changes PF Pressure loss due to friction ^.5 Raised to the power of .5 (Square Root) L Actual pipe length F Fitting equivalent pipe length T Total pipe length Sheet 4 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Raw data previous to any calculations No. Code Diam Length Kfacl Kfac2 Press Elev Hose HW Vel Fittings 1 DR1 1.049 3.00 8 12.000 -3.000 0.0 120 32 2E,1T,1FH4 2 DR2 1.049 1.50 8 12.000 -3.000 0.0 120 32 1T,1E,1FH4 3 DR3 1.049 1.50 8 14.060 -3.000 0.0 120 32 1T,1E,1FH4 10 BL1 1.682 1.00 DR1 0.000 0.000 0.0 120 32 11 BL1 1.682 10.00 DR2 0.000 0.000 0.0 120 32 12 BL1 1.682 10.00 DR3 0.000 0.000 0.0 120 32 13 BL1 1.682 8.00 DR3 0.000 0.000 0.0 120 32 14 BL1 1.682 16.00 DR3 0.000 0.000 0.0 120 32 1T 16 BL2 1.682 7.50 DR3 0.000 0.000 0.0 120 32 17 BL2 1.682 8.50 DR3 0.000 0.000 0.0 120 32 18 BL2 1.682 7.00 DR3 0.000 0.000 0.0 120 32 19 BL2 1.682 18.00 DR3 0.000 0.000 0.0 120 32 IT 21 BL3 1.682 5.00 DR3 0.000 0.000 0.0 120 32 22 BL3 1.682 10.00 DR3 0.000 0.000 0.0 120 32 23 BL3 1.682 18.00 DR3 0.000 0.000 0.0 120 32 IT 25 CM1 4.260 10.00 BL1 0.000 0.000 0.0 120 32 26 CM1 4.260 7.50 BL2 0.000 0.000 0.0 120 32 27 CM1 4.260 290.00 BL3 0.000 0.000 0.0 120 32 8VE 28 RI 4.260 22.00 CM1 0.000 15.000 0.0 120 32 1T,1B26,5VE 29 UG 6.160 250.00 RI 0.000 0.000 0.0 140 32 30 UG 6.160 0.00 0.000 0.000 500.0 140 32 Sheet 5 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Notes Drop 1 C = 120 L 3.0 PT 12.00 1 27.7=8.00(12.00)^.5 F 33.0 PE -1.30 (EL= -3.0 ft) 1 27.7 1.049 2E 1T T 36.0 0.23792 PF 8.57 10.3 1FH4 PT 19.27 10 131 Jct K -factor for drop 1 = 27.7/(19.27)^.5 = 6.31 Drop 2 L 1.5 PT 12.00 2 27.7=8.00(12.00)^.5 F 31.0 PE -1.30 2 27.7 1.049 1T 1E T 32.5 0.23792 PF 7.73 1FH4 PT 18.43 11 K -factor for drop 2 = 27.7/(18.43)^.5 = 6.45 Drop 3 L 1.5 PT 14.06 3 30.0=8.00(14.06)^.5 F 31.0 PE -1.30 3 30.0 1.049 1T 1E T 32.5 0.27547 PF 8.95 1FH4 PT 21.71 12 K -factor for drop 3 = 30.0/(21.71)".5 = 6.44 at Hyd Ref Pts 12 13 14 16 17 18 19 21 22 23 10.3 11.1 C = 120 (EL= -3.0 ft) B1 Jct C = 120 (EL= -3.0 ft) B1 Jct Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Sheet 6 Notes Branchline No. 1 (Beginning pressure increased due to Hyd Ref Pt 12) C = 120 L 1.0 PT 20.75 10 DR1 28.8=6.31(20.75)^.5 F 0.0 PE 0.00 10 28.8 1.682 T 1.0 0.02554 PF 0.03 4.2 L 10.0 PT 20.78 11 DR2 29.4=6.45(20.78)^.5 F 0.0 PE 0.00 11 58.2 1.682 T 10.0 0.09405 PF 0.94 8.4 L 10.0 PT 21.72 12 DR3 30.0=6.44(21.72)^.5 F 0.0 PE 0.00 12 88.2 1.682 T 10.0 0.20305 PF 2.03 12.7 L 8.0 PT 23.75 13 DR3 31.4=6.44(23.75)^.5 F 0.0 PE 0.00 13 119.5 1.682 T 8.0 0.35662 PF 2.85 17.3 L 16.0 PT 26.60 14 DR3 33.2=6.44(26.60)^.5 F 9.9 PE 0.00 14 152.7 1.682 1T T 25.9 0.56125 PF 14.54 22.1 PT 41.14 25 Cross main Jct K -factor for branchline no. 1 = 152.7/(41.14)^.5 = 23.81 Branchline No. 2 C = 120 L 7.5 PT 21.71 16 DR3 30.0=6.44(21.71)^.5 F 0.0 PE 0.00 16 30.0 1.682 T 7.5 0.02764 PF 0.21 4.3 L 8.5 PT 21.92 17 DR3 30.2=6.44(21.92)^.5 F 0.0 PE 0.00 17 60.1 1.682 T 8.5 0.10007 PF 0.85 8.7 L 7.0 PT 22.77 18 DR3 30.7=6.44(22.77)^.5 F 0.0 PE 0.00 18 90.9 1.682 T 7.0 0.21470 PF 1.50 13.1 L 18.0 PT 24.27 19 DR3 31.7=6.44(24.27)^.5 F 9.9 PE 0.00 19 122.6 1.682 iT T 27.9 0.37361 PF 10.42 17.7 PT 34.69 26 Cross main Jct K -factor for branchline no. 2 = 122.6/(34.69)^.5 = 20.81 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Sheet 7 Notes Branchline No. 3 C = 120 L 5.0 PT 21.71 21 DR3 30.0=6.44(21.71)^.5 F 0.0 PE 0.00 21 30.0 1.682 T 5.0 0.02764 PF 0.14 4.3 L 10.0 PT 21.85 22 DR3 30.1=6.44(21.85)^.5 F 0.0 PE 0.00 22 60.1 1.682 T 10.0 0.09992 PF 1.00 8.7 L 18.0 PT 22.85 23 DR3 30.8=6.44(22.85)^.5 F 9.9 PE 0.00 23 90.9 1.682 1T T 27.9 0.21473 PF 5.99 13.1 PT 28.84 27 Cross main Jct K -factor for branchline no. 3 = 90.9/(28.84)^.5 = 16.93 Cross main 1 C = 120 L 10.0 PT 41.14 25 BL1 152.7=23.81(41.14)^.5 F 0.0 PE 0.00 25 152.7 4.260 T 10.0 0.00608 PF 0.06 3.4 L 7.5 PT 41.20 26 BL2 133.6=20.81(41.20)^.5 F 0.0 PE 0.00 26 286.3 4.260 T 7.5 0.01943 PF 0.15 6.4 L 290.0 PT 41.35 27 BL3 108.9=16.93(41.35)^.5 F 71.6 PE 0.00 27 395.2 4.260 8VE T 361.6 0.03527 PF 12.75 8.9 PT 54.10 28 Top of Riser K -factor for Cross main 1 = 395.2/(54.10)^.5 = 53.73 Sprinkler Systems Hydraulic Flow Calculations LEGO STORE - WESTFIELD MALL TUKWILA, WA Pipe Flow Dia Fitting Length Fr Loss Press Hyd Vel No (gpm) (inch) and Dev (ft) (psi/ft) (psi) Ref (fps) Sheet 8 Notes Riser C = 120 L 22.0 PT 54.10 28 CM 1 F 71.1 PE 6.50 (EL= 15.0 ft) 28 395.2 4.260 1T 1B26 T 93.1 0.03528 PF 6.53 8.9 1B26 = 3.24# 5VE PT 67.12 29 B.O.R. Under ground 29 395.2 6.160 500.0 gpm = Hose 30 895.2 6.160 C = 140 L 250.0 PT 67.12 29 B.O.R. F 0.0 PE 0.00 T 250.0 0.00440 PF 1.10 4.3 L 0.0 PT 68.22 30 F 0.0 PE 0.00 T 0.0 0.00000 PF 0.00 9.6 PT 68.22 31 Supply Jct Available flow at 68.22 psi is 5605.1 gpm which is 4709.9 gpm from curve. Supply pressure available with 895.2 gpm flowing is 118.26 psi, thus system requirement is 50.04 psi below supply curve. (42.3%) LEGO STORE - WESTFIELD MALL Sheet 9 Supply Analysis Node at Static Residual Available Total Required Source Pressure Pressure Flow Pressure Demand Pressure 31 120.00 20.00 8000.0 118.26 895.2 68.22 Node Analysis Elevation Node Type Pressure Discharge Node (ft) K -Value Source (psi) (gpm) Notes 1 12.00 Orif= 8.00 2 12.00 Orif= 8.00 3 12.00 Orif= 8.00 10 15.00 11 15.00 12 15.00 13 15.00 14 15.00 16 15.00 17 15.00 18 15.00 19 15.00 21 15.00 22 15.00 23 15.00 25 15.00 26 15.00 27 15.00 28 15.00 29 0.00 30 0.00 Hose 31 0.00 Supply 12.00 27.7 12.00 27.7 14.06 30.0 20.75 - 20.78 21.72 23.75 26.60 21.71 21.92 22.77 24.27 21.71 21.85 22.85 41.14 41.20 41.35 54.10 67.12 - 68.22 500.0 68.22 - LEGO STORE - WESTFIELD MALL Sheet 10 Pipe Pipe Information Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt (ft) Hose ID F (ft) Vel Elev Pe Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes 1 12.00 8.00 27.7 1" 2E 1T L 3.0 120 Pt 12.00 1 1FH4 F 33.0 10.3 Pe -1.30 10 15.00 27.7 1.049 33.0 T 36.0 0.2379 Pf 8.57 DR1:K=6.31 2 12.00 8.00 27.7 1" 1T lE L 1.5 120 Pt 12.00 2 1FH4 F 31.0 10.3 Pe -1.30 11 15.00 27.7 1.049 31.0 T 32.5 0.2379 Pf 7.73 DR2:K=6.45 3 3 12.00 8.00 12 15.00 30.0 1" 1T lE L 1.5 120 Pt 14.06 1FH4 F 31.0 11.1 Pe -1.30 30.0 1.049 31.0 T 32.5 0.2755 Pf 8.95 DR3:K=6.44 10 10 15.00 6.31 [28.7] 1 1/2" 11 15.00 28.8 1.682 L 1.0 120 Pt 20.75 DR1 F 0.0 4.2 Pe 0.00 T 1.0 0.0255 Pf 0.03 11 11 15.00 6.45 [29.4] 1 1/2" 12 15.00 58.2 1.682 L 10.0 120 Pt 20.78 DR2 F 0.0 8.4 Pe 0.00 T 10.0 0.0941 Pf 0.94 12 12 15.00 6.44 [30.0] 1 1/2" 13 15.00 88.2 1.682 L 10.0 120 Pt 21.72 DR3 F 0.0 12.7 Pe 0.00 T 10.0 0.2030 Pf 2.03 13 13 15.00 6.44 [31.4] 1 1/2" 14 15.00 119.5 1.682 L 8.0 120 Pt 23.75 DR3 F 0.0 17.3 Pe 0.00 T 8.0 0.3566 Pf 2.85 14 14 15.00 6.44 [33.2] 1 1/2" 1T 25 15.00 152.7 1.682 L 16.0 120 Pt 26.60 DR3 F 9.9 22.1 Pe 0.00 9.9 T 25.9 0.5613 Pf 14.54 BL1:K=23.81 16 16 15.00 6.44 [30.0] 1 1/2" 17 15.00 30.0 1.682 L 7.5 120 Pt 21.71 DR3 F 0.0 4.3 Pe 0.00 T 7.5 0.0276 Pf 0.21 17 17 15.00 6.44 [30.1] 1 1/2" 18 15.00 60.1 1.682 L 8.5 120 Pt 21.92 DR3 F 0.0 8.7 Pe 0.00 T 8.5 0.1001 Pf 0.85 18 18 15.00 6.44 [30.7] 1 1/2" 19 15.00 90.9 1.682 L 7.0 120 Pt 22.77 DR3 F 0.0 13.1 Pe 0.00 T 7.0 0.2147 Pf 1.50 LEGO STORE - WESTFIELD MALL Sheet 11 Pipe Information Nodel Elevl Kfactor Qadd Nominal Fittings L (ft) Cfac Total Pt Pipe (ft) Hose ID F (ft) Vel Elev Pe Node2 Elev2 Qtot Actual Length T (ft) Psi/Ft Fric Pf Notes 19 19 15.00 6.44 [31.7] 1 1/2" 1T 26 15.00 122.6 1.682 L 18.0 120 Pt 24.27 DR3 F 9.9 17.7 Pe 0.00 9.9 T 27.9 0.3736 Pf 10.42 BL2:K=20.81 21 21 15.00 6.44 [30.0] 1 1/2" 22 15.00 30.0 1.682 L 5.0 120 Pt 21.71 DR3 F 0.0 4.3 Pe 0.00 T 5.0 0.0276 Pf 0.14 22 22 15.00 6.44 [30.1] 1 1/2" 23 15.00 60.1 1.682 L 10.0 120 Pt 21.85 DR3 F 0.0 8.7 Pe 0.00 T 10.0 0.0999 Pf 1.00 23 15.00 6.44 [30.8] 1 1/2" 1T L 18.0 120 Pt 22.85 DR3 23 F 9.9 13.1 Pe 0.00 27 15.00 90.9 1.682 9.9 T 27.9 0.2147 Pf 5.99 BL3:K=16.93 25 25 15.00 23.81 [152.7] 4" 26 15.00 152.7 4.260 L 10.0 120 Pt 41.14 BL1 F 0.0 3.4 Pe 0.00 T 10.0 0.0061 Pf 0.06 26 26 15.00 20.81 [133.6] 4" 27 15.00 286.3 4.260 L 7.5 120 Pt 41.20 BL2 F 0.0 6.4 Pe 0.00 T 7.5 0.0194 Pf 0.15 27 15.00 16.93 [108.8] 4" 8VE L 290.0 120 Pt 41.35 BL3 27 F 71.6 8.9 Pe 0.00 28 15.00 395.2 4.260 71.6 T 361.6 0.0353 Pf 12.75 28 28 15.00 29 0.00 4" 1T 1B26 L 22.0 120 Pt 54.10 Top of Riser 5VE F 71.1 8.9 Pe 6.50 1B26 = 3.24# 395.2 4.260 71.1 T 93.1 0.0353 Pf 6.53 29 0.00 6" L 250.0 140 Pt 67.12 29 F 0.0 4.3 Pe 0.00 30 0.00 395.2 6.160 T 250.0 0.0044 Pf 1.10 30 0.00 6" L 0.0 140 Pt 68.22 30 500.0 F 0.0 9.6 Pe 0.00 31 0.00 895.2 6.160 T 0.0 0.0200 Pf 0.00 Supply Customer MARK ECHO 837 SOUTHCENTER MALL TUKWILA, WA 98188 GUARDIAN SECURITY LIFE AN ....Act MARK ECHO Project # 0 PROPERTY PROTECTION List of Materials Vendor Guardrail Security Systems +uc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: SEPT.,9,08 Item 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) '22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Qty. Manuf. Siemens Siemens Siemens Siemens Siemens Siemens Siemens PAD -3 AD2-P HTRI-D HTRI-R SET CW,W SET W ZR-MC-W,W Model Description Unit Pri Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Total Price Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Starica,a • FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Marc Ecko 837 Southcenter Mall Permit No.: 08-S-425 Date: August 19, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. ST FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3ER SHEET TITLE FA -01 SYSTEM I N FO R MATT O N FA -02 TYPICAL WIRING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLA\ SHEET INDEX WIRE SCHEDULE AND CO\DUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHCRITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FRCM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONCUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) V/HERE THE CABLE IS INSTALLED GENERAL NOTES QUANTITY EX 2 2 2 1 1 SYMBOL DESCRIPTION MODEL W ithou {:Comments Q As Note Noteci Re4 © Per r€: i-.0:tacheJ Letter plans have be<? : ; The Tukwila Fire =ration Bureau foc with current City girds. Accept=^c : j , „ errors and ::::!ons which do not , i.or-, ,;solations of adopted -...,ndards and ordinance:-. Ti-, .-L:ronsibility for the 1uacy of desinrl lesigner. i;tions, deletions o: revision= nc drawings after ,Ls date will void this acceptant ..'1: wtii require a submittai of revised drawings r:. • quent approval. ;"final acceptance Is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: S-"1 By: 5i l MANUFACTURER BACKBOX P„a; c ti 2.f.,'6 -,11:73-1-1D7 d IS - F -Q76 ' :end exact af. i's .. b r shut- down or rc to. jon approval. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must he presented to:;i e ctor prior to of Acceptance Fire Alarm and L. _. _ _ on Svstcros. Failure of test will result in a Re -inspection Fee and `..rmination of the tPctinel MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY (EXISTING) PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP DUCT DETECTOR FDBZ492-HR W/ HFP-11 DET. SIEMENS DUCT HOUSING TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIEIA/ VERIFY " e.' (10 IN FIELD d HT -M SINGLE INPUT INTERFACE MINIMODULE HTRI-M SIEMENS 4S BOX VERIFY IN FIELD HT -R INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S BOX VERIFY IN FIELD FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S BOX CEILING 10 Di FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXTN END -OF -LINE RESISTOR A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A RED NOT APPLICABLE AS BUILT ADD OR CHANGE N/A N/A N/A N/A N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND -\\ NORDSTROM j 3 LEVELS 171,275sf PcnN..,C COWL 1 macys 4 LEVELS 250,407sf LEGO STORE #837 / SPACE #1450 k' GATE Lru.o . LOC'ER ROCU KIO'S 7 - PAM 1 NvCgY.YKK F_AP, C DCC CASUAL Kiss Ef.: Tf LORASY S.D WEYER ,EACLERS •. e y : 3 LEVELS' 276,468sf PAID APR 27 2015 TUKWILA FIRE cc z2 S SITE PLAN Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I DMG I DESCRIPTION SHOP DRAWINGS DATE LO M N 0 0 Z Y 00 owT Er O �Z Q o -10 C/)w¢z O wQ (,Dcrzs W -J o W CC DD V- OI-- co 111 (1) L (I)} 'CALE: NOT TO SCALE 0 0 z DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/ 15 BACKROUND PLAN PROVIDED BY: I0B NUMBER:12077-1/ U FA-Ol SHEET SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: 9202470010 Site Address: 837 Southcenter Mall, Space 1450 Suite Number: Floor: Tenant Name: Lego Store New Tenant? E- Yes ❑ - No Property Owner's Name: Westfield Shopping Center Mailing Address: POB 130940, Carlsbad, CA 92013 City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 Company Name: Guardian Security Systems Mailing Address: 1743 First Ave South, Seattle, WA 98134 E-mail Address: kveliz@guardiansecurity.com Total number of new/relocated devices or sprinkler heads: 1 Valuation of Project (contractor's bid price): $ 6600. City State Zip Fax Number: 206.628.4990 Scope of Work (please provide detailed information): Add 18 device to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Date: 1 2 Print Name: Karina Veliz Day Telephone: 206.349.5889 Plan Permit App.doc 1/2/13 TFD FP Form 8 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TUBE OUTLET SAMPLING TUBE INLET SAMPLING DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 12OVAC-60a —{ DEDICATED OE ONCY FROM EXISTING MAIN FACP C CABLE C' CABLE Q6 N L IX 00 0 0 PAD -3 oo° INPUT INPUT TROUBLE NCI NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - S S 3.6k EOL R Mit 0 0 (-) (+) (-) (+) ZNAC S4 , NAc S3 NAC S2 NAC S1 EXISTING POWER SUPPLY WIRING DETAIL COMBINE ALL SHIELDS AND IS❑LATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIL 0 HARD LID CEILING END OF LINE DEVICE(3,6K 1/4W) SUPERVISED SWITCH GROUND 0 HTRI-R STATUS LED co O N.O. 0 COM cc HARD LID SPEAKER SUPPORT TILE BRIDGE 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE '2)c) o, 000 000 \\\\\\,,iL,„ SPEAKER STROBE & STROBE CEILING MOUNTING DETAIL FROM REMOTE POWER SUPPLY FEED FROM EXISTING VOICE CIRCUIT (V CABLE) RETURN TO EXISTING VOICE CIRCUIT (V' CABLE) O N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 MUSIC () () STROBE SPEAKER (+) (-) STROBE (+) ( ) STROBE SPEAKER (+) (-) T T 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING RELAY CONTACTS (4.OA @ 125VAC) (4.0A @ 30VDC) HTRI-R RELAY MODULE BACKGROUND MUSIC SHUTDOWN WIRING DETAIL SPEAKER STROBES & STROBES ONLY WIRING DETAIL FROM PREVIOUS ADDRESSABLE 2 DEVICE TO NEXT DEVICE OR END OF LINE TYPICAL WIRING AND MOUNTING DETAILS TBI ®®®®®©® 00110 NO COM NC 2 TO FAN SHUTDOWN EOLR 470 0 SWITCH + - INPUT LED TSM -1 HTRI-M RED BLK 00 + TO NEXT ADDRESSABLE DEVICE ORG ORG GRN NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL DUCT DETECTOR/HTRI-M MODULE/TSM-1 SWITCH WIRING DETAIL NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERA RE: +32' F 0' C TO 100' F 31T C) HUMIDITY: 9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> E. DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCAIIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT > TO NEXT ADDRESSABLE DEVICE 0 0 TO NEXT DEVICE 0 0 CADDY BAR — EDI SMOKE DETECTOR TSUSPENDED ILLUMINATED CEILING SMOKE DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION [HOP DRAWINGS DATE 04/23/15 R CCaaa L) CO cc 3: J U SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/15 BACKROUND PLAN PROVIDED BY: \OB NUMBER:12077-1} I. SHEET FA -02 FIRE ALARM BOOSTER POWER SUPPLY BATTERY CALCULATION Project: LEGO STORE Panel: EXISTING BPS PAD -3 BOOSTER POWER SUPPLY Date: April 23, 2015 Module/Device Qty Standby Total Standby Alarm Total Alarm (mA) (mA) (mA) (mA) Power Module 1 30 30 0 30 30 0 A TOTAL FIRE ALARM POWER SUPPLY 30 30 B Auxiliary Device Current 0 0 C Notification Appliance Load (Max. Total / mA) 0 D E F G H J K 5254 Total(A)= CALCULATION 30 : Total(B)= 5284 Total current ratings of all devices in system (line A + line B + line C) 30 5284 Total current ratings converted to amperes (line D x .001) 0.03 5.284 Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5). 24 Multiply lines E and F Total Standby AH 0.72 Alan -n sounding period in hours (5 mins+ .0833 hours) 0.0833 Multiply lines E and H Total Alarm AH 0.4401572 Add lines G and I Total Standby and Alarm AH 1.1601572 Multiply line J by 1.2 (20% extra insurance to meet desired performance) 1.39218864 12-V DC BATTERY SIZE RECOMMENDED (AMPERE -HOUR) 7 CALCULATIONS .,'r � ",;.,, ..*w ,,, � w• Notification Appliance Circuit Detail PROJECT: Panel: Date: , LEGO STORE -POWER 2.58 5254.00 EXISTING BPS PAD -3 SUPPLY Wire Resistance April 23, 2015 CURRENT TOTAL= F' 1vY 'd �s�w; f t v <^ RG I &F M M', �* } A, 1„\„ ( h "+ b i ,). y 1 „ :y. d f d 4 I f r a' a f I 1 ''Y t !R N 9 + 3f wl oY h r, { { �� i i F - i $fii i 1 F #' •P' y ; -, _ .�.-..,� y # �" Y ky(9 A'ry", %� W1, �' i JJ j, ;fN 10 SET -MC -CW ©15cd,.§ 69 ` 690 1 T .M _ _n __ __ . _- n _._ SET-MC-CW@30cd 111 ci :SET -MC -CW @75cd 200- 01 SET -MC -CW @95cd 264 SET -MC -CW ©15cd 64 641 as<aK DEVICES ZR -MC -CW 30 cd 111 0 .. 11., TOTAL mA= 754 14 325 22.74 754 ; _1.68 0.75 1.26 , - _ : ^ pTv p �µy wR� T _ Total Wire Resistance (R) (WL * 2) * (R/ft) r„ �r� T Total Device Load, Amps (I) Cct Load) Voltage Drop (E) (E= I * R) 14 EOL Voltage 24 E) I 22.74 Total Wire Resistance (R) ,» rr:i+''' a 5, °P¢;�lF 1, } : +� '4' y'I'If X �,e'I5'.� r { i t 9 , }h;o, '„ ! ( ! t Y f uN''^I � \ i ! ;SET -MC -CW @l5cd 69 0 Standby: 6.34 SET -MC -CW @30cd 111.:.. S . 'SET -MC -CW @75cd . 200_ 0 . Total Device vi a Load Amps l Load, P {) Voltage Drop (E) SET -MC -CW @95cd : 264 0 ZR -MC -CW @15cd 69' 01 of tai Cct Load _ (T} ;(E=i*R) DEVICES ZR -MC -CW @3Ocd .. 111 0 TOTAL mA=3 1500 j 14 24.00; 1500 ' 0.00 :Total Wire Resistance (R) ; (WL 2) (R/ft) Total Device Load, Amps (I) (Total Cct Load) 1.50 Voltage Drop (E) F (E= I * R) _ 0.00 a■� . .,, aS'� , "t ,, Nr. x }, �, V „t,C\„+°�� §.#�,5 .., to EOL Voltage 24 E) �1N 24.00 .v.,,,.., S.P, .. ,S •, :¢' N �Yvi M \ Palm , ,�'� .:',, ,,;, „ ., ¢, I.p - ., :, r r u. ,e, 7• ,,, $ ,'4. e". y,,;;,. ! 1 ,, f4, ,. � '�� � a: .; 1 rc„ a, 1 '"d i � 'Y�i p ,*5,�,\. � �,� ^'� $ ^+ � ,y .�, ,.v', F',+, 1,7 au�;f ,ti'�� C . 4 ", w ,� ,, .",t �„V�,;:�Mr�Po �,� of l!'fi S l� ,. :\:i �eu,i "V\ r��F 4 M,:'r, F;,�, *1, ,'j '� �,, mp' �' ������i �,k. Y�. :� s r _ �.__,......,.....�_.�. Y» ,'..�„S`k ..'.":, »,� V,k Y:�, u5!1 W �,r'! &rM.' ,y �Ar,u R' _ D r ',:' R:t � SET-MC-CW__i@1 5cd 69 0 �`",.. �.,_.., ,.� ..�.. _...�_,_ _ Amps Total -MC-CW 30cd, SET 0x @ SET -MC -CW @75cd 200. 0 SET -MC -CW @95cd 264 0 . .SET-MC-W@110cd 233 0 DEVICES ZR -MC -CW .30cd 111 0 0 TOTAL mA=' 15001 14 24.00 1500 0.00 1.50 0.00 2 Total Wire Resistance (R) j (WL 2) (Rift) 0.0022 0.0023 Total Device Load, Amps (I) otal Cct Load Voltage Drop ( E) j `(E= I * R) f �4µ } 'n EOL Voltage:' d4 '..nE 24.00 Y rn d 1d i , , \ f �� , ,, ,t"i ��!',b I • /y�� flp \ ? � 5: ,,/ i, r, „ „ i, 'FFjN �1$"}Ir r�Y � , J ',,.,r � f u„� ,y y:.." { . Vg, N � r h„ , w, gym,', , r,,,J, 1, r. 1',,,; ,,,e:''S'�Mi r, r>w , •<.,;: r3 i "'4..,.\» }�,1 ,, �,, ,a„ ,n. ,n.'. ,�,, ,, a ^,,..,� .. a '.,:•,-,..if r. rY :,�� Cr" `.�:�„� t (5 "�= Via. M:rm yy r `� , » n¢, f * y, � •�i."'. N 4e; �'' , x,a,,,t Z. '.'n" 2 :SET -MC -CW @15cd : 69 0' 0.0635 -r., CW SET-MC-30cd 111 0. SET -MC -CW @75cd 1 200' 01 SET -MC -CW' @95cd: 264 0 SET -MC -W @110cd :.... 233: 0 DEVICES ____ ZR -MC -CW 30cd 111 0 0 TOTAL mA= 1500 14 24.00' 1500 3 : - Total Wire Resistance ( R) (WL *2 ) * (R/ft) 0.00 1.50 0.00 0.021 Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage 24 E) 24.00 CALCULATIONS .,'r � ",;.,, ..*w ,,, � w• "I h, ,I h , r,, ii i, � e, �, �, l�,�r A. dr,lt M .,r�.;, Id5 °"y:,^' rv, ,'i� ,a r4 i �;b Sj: p"'�5%40v, F ',hr 1,'.S PY „v ,,., V �,,,, ,,.r. jf •.y N b;,, ��1Jj \ � 4J"W ,1 k A\4,,, � d},u, ky(9 A'ry", %� W1, �' i JJ j, ;fN Sot, �aC M� S j4 k{ v 132©.1/2-WATT SET -MC 1/2 WATT 7.08 - - --, SET @1/4 -WATT 14.14; 934.56 as<aK I .--.�-,,.,.,.. ' DEVICES SET1/2 WATT 28.29 132 TOTAL mA=I 0 934.56 14 1228 18.08; Current Load: Total Wire Resistance (R) Standby: 6.34 Alarm: Total Device vi a Load Amps l Load, P {) Voltage Drop (E) 1 of tai Cct Load _ (T} ;(E=i*R) c�.93 5.92 ,. EOL Voltage �" 24 - E 180 Device Type Qty Amps Total Amps Total HFP-11 2 0.0022. 0.0022 0.0023 0.005- FDBZ492-HR 2 0.0635 0.0635 0.064 0.128 HTRI MODULE 3 : - 0:009600 0.0096 0.021 0.063 0.0731 Amps 0.191 Amps TO NEAREST EXISTING v"p � b SPEAKER CIRCUIT TO NEAREST EXISTING POWER SUPPLY r V Sby TO NEAREST EXISTING DATA LOOP (EXISTING BACK-OF- THE-HOUSE ACKOF- THE-HOUSE J -BOX) SV S,V S,V SV S,V SV S,V S,V SV S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8 S1-9 S1-10 S1-11 15cd 15cd 15cd 1 5c 15cd 15cd 15cd 15cd 15cd 15cd 15cd (HT -R SINGLE LINE DIAGRAM EOL S1 FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC SHUTDOWN. DUCT DETECTOR, MONITOR MINIMODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Notification Appliance Circuit Detail - VOICE ' 'Wire Resistance 2.58 CURRENT TOTAL= 934.56 PROJECT: Panel: Date: ,, ^, ' LEGO STORE EXISTING SPEAKER CIRCUIT April 23, 2015 ��►►„ //ms�sa ry 1 ,.r'p,�,. 4 �.Y r d\' I ' � f �,`' �a im>: Y L4pF 1br�Yrr mwi'�' "� X �g r irbMu�d�,I Mr�f�� ri,:, R :Y ,a T f Aa„ fa .\ h :, ,,,. ,, w. i R•MI,:x, ,'„ ,,, , �'. .,, : -�, � "'; 4. p Y 1 h"i'.,, A 1, M r n ,. �,,.. .,H ..e� r'. w Md. � r , wr � ., � a i,5 �,, ,. v, G ,. �% .3nv „,,a.,. C .A' yM ��„ � a ,�:..:.. G n r .. ., a ti y '} v g 1 VYc'� Wt� ry Fi , ,�,. r ,'I� ry ., .�. � , ! t t '4, j'�} ai, .it ..w K,,,, o 0u �yr f � � n.:. 7 k {;R,V,� 6 f'V dt „� ;,,C , .w M .MY �"r „ r "w�;tw �j,. Y r• r i �bb �J . F, 5 tl d r r �� r T, t 3 rryy i D ■/#�� a C e 0 't ti�+, �" a ,,,�B.y,l '',VI .-.e,.� Ya ,i'", i � g, '1. \ d v i ,,: ,.u, ,'' a �,'. � 7 \ y n �y ! h4 _Y .., „ g �0 /S $ 4 {t v4 DATE SET -MC @1/4 WATT 3.54; 132©.1/2-WATT SET -MC 1/2 WATT 7.08 - - --, SET @1/4 -WATT 14.14; 934.56 as<aK I .--.�-,,.,.,.. ' DEVICES SET1/2 WATT 28.29 132 TOTAL mA=I 0 934.56 14 1228 18.08; 934.56 Total Wire Resistance (R) (WL * 2 )"(Rift) ._ .___ 6.34 Total Device vi a Load Amps l Load, P {) Voltage Drop (E) 1 of tai Cct Load _ (T} ;(E=i*R) c�.93 5.92 ,. EOL Voltage �" 24 - E 180 TO NEAREST EXISTING v"p � b SPEAKER CIRCUIT TO NEAREST EXISTING POWER SUPPLY r V Sby TO NEAREST EXISTING DATA LOOP (EXISTING BACK-OF- THE-HOUSE ACKOF- THE-HOUSE J -BOX) SV S,V S,V SV S,V SV S,V S,V SV S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8 S1-9 S1-10 S1-11 15cd 15cd 15cd 1 5c 15cd 15cd 15cd 15cd 15cd 15cd 15cd (HT -R SINGLE LINE DIAGRAM EOL S1 FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC SHUTDOWN. DUCT DETECTOR, MONITOR MINIMODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 04/23/15 z as<aK MQM 0 w Z co J oW) 0 U� woa.z z Cr a 0CO CCU)(/) O 2�< z w QCC DD o - CC u- OI - N M GO U w C±) >- C,) 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/15 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 12077-11 1 SHEET FA -03 D FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC SHUTDOWN. DUCT DETECTOR, MONITOR MINIMODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. S Si -3 1 5cd �+ TO EXISTING BACK -OF -THE HOUSE JUNCTION BOX s.v VIC -TI ^IC CORRIDOR 1 TOILET ROOM STOCK ROOM S S1-1 15cd S1-2 1 5cd s,v S1-4 �15cd S S1-7 Di 1 5cd s,v s,v S1-6 1 5cd iv'//./ ��////. i'//.//// J ---1,1S1-8 1—r%4 15cd SALES FLOOR Si -9 nom/ 1 5cd L1V S S S1-11 1 5cd S1-11 15cd s,v- FIRE ALARM SYSTEM PLAN ,/ / / i ./,/'/ / / ii'/:/'/ S1-10 15cd /f / i i'/'/ / / / r mi SI:OPKIT TRACK RECESSED IN CEILING, %; ��, SEE A4.1 FOR INFO \11 ci\ SIGNAGE, PROVIDED BYOWNER `1 C� 1 � 1j • ENTRY Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: CD g 0 DESCRIPTION SHOP DRAWINGS DATE 04/23/15 2<aaaa 1/4''=1'0” DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 04/23/15 BACKROUND PLAN PROVIDED BY: \0B NUMBER:12077-1/ C SHEET FA -04 FlexHead Sprinkler Drop Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' legnths Multi -Port Bracke_t_ \ Adjustable Hub FLEXHEAD I N0USt RI0 Flexhead`tommercial Ceiling Unit T -Bar Ceiling Installation Model #2024,2036,2048,2060,2072 STOCK ROOM G-3 NO. OF SPRINKELRS DENSITY DESIGN AREA WATER FLOW RATE RESIDUAL PRESSURE Co BASE OF RISER OCCUPANCY CLASSIFICATION FLOW TEST INFO: 120 PSI STATIC 120 PSI RESIDUAL FLOWING 8000 GPM REMOTE AREA 12 .30 GPM/SF ENTIRE STOCK AREA 395.2 GPM 67.12 EXTRA HAZ GP 1 SALES FLOOR 00.2 INSTALL ALL PENDANT LIGHTS SO SEAMS IN SHADES FACE TOWARDS BACK OF SALES FLOOR EXISTING' CORRIDOR C) G-1 I I.2' -O" GENERAL LEGEND —o 0 BOD BOB BOJ FOS FOW EARTHQUAKE BRACING PIPE HANGER GROOVED CAP RIGID COUPLING . ( UNLESS NOTED ) CAP PLUG CENTERLINE HYDRAULIC REFERENCE POINT CENTERLINE. PIPE TO BOTTOM OF' DECK CENTERLINE PIPE TO BOTTOM OF BEAM CENTERLINE PIPE TO BOTTOM OF JOIST FACE OF STUD FACE OF WALL FOC AFF CH R.C. 4 E/C C/C C/E GG TG TxF ATR FACE OF CONCRETE ABOVE FINISHED FLOOR CEILING HEIGHT REDUCING COUPLING OUTLET COUPLING WELDED OUTLET "FIT" FITTING. END TO CENTER CENTER TO CENTER CENTER TO END GROOVE/GROOVE THREAD/GROOVE (ALSO "Cr) THREAD/"FIT" (ALSO "FxT") ALL -THREAD ROD TOILET ROOM 04 K!b FLAN J NORDSTROM macyy 111` TT, P4 • 0 0 o a I o MI I APPROX 290' OF 4" TO TOP OF RISER TENANT SPRINKLER PIPING PLAN SCALE: 1/4" = 1'-0" 0 2' 4' 8' Group A Plastic Storage 12' Solid -piled, palletized, bin box, shelf, rack, and back-to=back shelf storage: Uriexpanded and expanded NFP A ##13 >5 to s10 >5 to s10 s1.5 >1.5: to. s3.0 >1.5 to - s3.0 15 20 4.6 6.1 01-12 - EMI EI -12 0.50, 100 0, 50, 100.. 0, 50: 100 0, 189, 379 0. 189,: 379 0. 189, 379 250 . 500 500 916--. 90 1893 120 1893 120 >10. to s12 >3.0 to.. s3.7: 17 5.2 EH2 0, 50. :100 0, 189, 379 500 :1893 120 solid piled: palletizeci,_ bin box, shelf, and back-to-back . shelf storage >10 to s12 >3.0 to S3.7 32 9.8 EH2 0, 50, :100 0. 189; 379 500.-. 1893 120 >10 to ` s12 TABLE 3: >3.0 t6 s3.7 32 9.8 OH2 +1 level of in -rack 0, 50, -100 0, 189; 379 250 916 90. SPRINKLERS SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAN. RELIABLE MODEL G5-56 QUICK RESP CONCELAED PENDENT 0 R3415 1/2" 1/2" 5.6 CHR CHR 155' 20 RELIABLE MODEL G5-80 QUICK RESP CONCEALED PENDENT R3412 17/32" 3/4" 8.0 CHR CHR 155' 12 TOTAL SPRINKLERS . = 32 THIS PROJECT GENERAL NOTES SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 - 2010 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS ORIGINAL SYSTEM CALCULATED FOR ORDINARY HAZARD GP 2 BACK OF HOUSE STORAGE AREA: STORAGE OF GROUP A PLASTICS NON EXPANDED IN CARDBOARD STORAGE TO A MAXIMUM OF 10' IN RACKS 12' CEILING HT IN STORAGE AREA EXTRA HAZARD GP 1 PER NFPA #13 TABLE 13.2.1 (@ LEFT) .30 GPM/SF OVER ENTIRE AREA 100 SF PER SPRINKLER MAXIMUM 500 GPM HOSE DEMAND CARTONS. TUKWILA FIRE DEPARTMENT Petr call 20€-575-4107 and give this Fire Permit No. ;Ind exact address for shut - 'town or r . o etion approval. 0 Without Comments O As Noted in Rei+ Per The Attached Letter These plans have been reviewed by The Tukwila Fire ,-evention Bureau for conformance with current City ndards. Acceptance is subject to errors and omissions which do not authorize violations of adopted :;andards and ordinances. The responsibility for the ;idequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: Ce -3 -is By: WASHINGTON STATE CERTIFICATE OF COMPETENCY FIRE PROTECTION SPRINKLER SYSTEMS CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 LEGO 837 SOUTHCENTER MALL PAID TUKWILA, WA 98188 �U�I 2 Zo1 TUKi�VILA FIRE DATE: 5/15 DRAWN: C.O. SCALE: AS NOTED 1 OF 1 FILE COPY SHEET NUMBER SHEET TITLE SHEET INDEX MARK ECHO FIRE ALARM SYSTEM TUKWILA, WASHINGTON FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FRE ALARM SYSTEM FLOOR PLA FA -04 SYSTEM CALCULATIONS (GENERAL), RISER, SITE PLAN { J= Infi-z-3w r .:a•v!:....._'i.i _..•... , _ !..)lest'-: Fire P'=v..... 'si_;r,3u .:r : (. .,. ..::r, s.;t citY '„i1Ga;'c::::. r-..:fc: ` ..-:::i ::. ,S , %t'.. . r'..(i Orni:r._ii):;s 'A.:;`•••4':i j'.: 1 .........: ,. _ .,.:;,iF,"OptCd stall(:;..a ...-.... J:r4,.,.. .. . .. f:_1" the ar?::-_,,,i-...?.-,; o; •... .. 1; ^nt;r.r. t',0thik,:i= _. _ . . ;,s atter ink (i t? -,.'i?, '1)r.. J? ..,'i..:(::. •:ii.:....'i f=.;:u re a resublm ai of revia.:c,•r i ;gs ter •:;uub;,equent approval. Final acceptance is subject to field test and inspection b\ The Tukwila Fire Prevention Bureau. IDate: 9=i).-03 By: ,�->,,,,$1 FUKW1LA FIRE DEPARTMEi it Please call: 575.4402 and give this job No.0Llys. and exact address for shuti - aown or restoration approval: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. TA I? Harrri Because of Increased demand our ins rs' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 to schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES .AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 2 1 4 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP El INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD 0 DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD F< LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD I ® SMOKE DETECTOR HFP-11 W/ SIEMENS lel (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING L FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING n Q c FIRE ALARM STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM B p STROBE WP (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD a MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright 2006 by Guardian PAID SEP - 8 2008 Tukwila Ft_e Ztz Security Systems, Inc. All Rights Res 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z d I- DESCRIPTION SHOP DRAWINGS DATE to 0 0 0 2 CCCaC CO co J C° O wiz E5F2 C.)(I)Z z W 2w W 0 _cog C I- 0 0 u. z 1.1.1 (1) �CALE: 1/8"= 1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 8/20/08 BACKROUND PLAN PROVIDED BY: \OB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC O DUCT DETECTOR LOCATI❑N END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 1 0 0 GROUND IC) © HTRI-R *STA11JS LED CO 0 N.O. r` 0 COM co 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL O LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE + + NOTE 1: VOLTAGE MAX, - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING \ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE MUSIC }-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE 0.) O STOP IF LAST DEVICE () FROM XLS CONTROL PANEL OR - PREVIOUS ADDRESSABLE DEVICE{N END OF LINE DEVICE (3.6K 1/4W) RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3.5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTI❑N. 0 + Ie 01 TB1 S15 0000 123456 HCP TB2 0 0 + 654321 0 0 SUPERVISED_ /' SWITCH / GROUND / NOTE: 1) © © HTRI-D OSTATUS LED CO /NOT USED 0 0 0 O 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL BCAE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 0 GND N AC 013.111 El II PAD -3 0 0 00 O INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 24K uu 1*. + TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) -SUPERVISED 1 SWITCH NAC -4 NAC -3 NAC -2 ________qNAC-1 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE E DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0- 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSNBLE DEVICE (-)> 470 OHMS �IM EOL O TC INPU (+) S1 0 TS M-1 O o¢ zoo -8 O�o ' N-� X000 0 • • 12-3 Cc Ankh TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) ('V' CABLE) 10 (-) STROBE SPEAKER 0 O EARTH GROUND ->(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE STROBE (+) ( ) STROBE SPEAKER (-) SPEAKERISTROBE AND STROBE LABEL SCALE SPEAKER STROBE OR STROBE ONLY R IRING O 14S DEEP BOX I WI 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX ((STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERrN TEMPERA RE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: U-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR r— DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX i WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTI❑N BOX -\ MOUNTED ON CEILING. FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 1 /f�11 0 0 / / / 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved o 0' Ch CD (\.1 O `0 q) C.; o Z N � X La LU J F- F - W U) C5 LLI Q F- C/) K7 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z L DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 CaaCa 0 z p z 0 0 z 0 z E r1 V , 1 ..W (S.-CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:8/20/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -02 } Nre,";J 2, NORTH MARK ECHO WESTFIELD SOUTHCENTER MALL SCALE 10=1' FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED ❑UT 20A, 110 VAC BRANCH CIRCUIT, DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. MI Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 2 a<aa< Co co J� C$3 Q W2(3)z _ o czz W2 E. � ac=tn CC Q� <wo C co H .CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 8/20/08 BACKROUND PLAN PROVIDED BY: \0B NUMBER: j SHEET FA -03 j 8091 I NORDSTROM 3 LEVELS 171,275sf mervyrrs 2 LEVELS 65,237sf Macy' 4 LEVELS 253,407sf L sx a0; C Ci PRY CNtr3 CASJit 1.4 CMtt JEPA.1 KT- 'Ili E .EPE1Ers $ aa5i M:!1., NCr1tF CA ;A1EPA EYJSr3:�c WW1,. M.ELESS Y!.^.€ 5 •.51e.+.Ty1 �EASP 51s JW?A :caIE VAI SIZ<O, V> REPS PA«0, SG'1_ 'APE'S w •NT PAS.: I.ETPJ1NxE NORTH z C.1.1.5,1,5 C UEMCU1 �.EP- rzu a�a1u1 CHEE.0 CE FA^i1 rr MARK ECHO WESTFIELD SOUTHCENTER MALL 3 LEVELS 276,466sf J SCALE N.T.S 15 C 110 C 75 C 15 C EX SYSTEM CALCULATIONS BATTERY SIZING CALCULATION _ ____.___Notification Appliance Circuit Detail PROJECT:1 WESTFIELD SOUTHCENTER MALL Panel: i MARK ECHO Date: August 21, 2008 CIRCUIT:! S1 QTY Device Type 1...._ € SET -MC @15CD E ...- 64 i. 1 (SET -MC @30CD 1 981 2 ; SET MC @75CD 1751_._.350 1 !SET -MC @110CD 2331 233 0 ;SET-HMC-C@115CD € 318 0 0 I SET HMC-C@177CD 445' 0 0 1SET-HMC @135CD 318' 0 SET -HMC @185CD ; 4451 1 Z-MC@15CD i 64 0 !Z-MC@30CD 981 0 I SET-MC-CW@110CD DEVICES=16 Wire Resistance 1.62 CURRENT TOTAL= 809 !Alarm Current! Alarm Total Wre Size i Wire Length 1 Voltage at EOL Circuit Total 64 98 233 0 0. 64 0 01 TOTAL mA=! 8091 12 220 Total Wire Resistance (R) ( WL * 2)* (R/ft) 0.71 ___.___.....___._ Total Device Load, Amps {I) 0.81 (Total Cct Load) Voltage Drop ( E) 0.58 (E= I * R) EOL Voltage ` 19.82 (20.4 - E) 19.8233448 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: MARK ECHO Date: !August 21, 2008 CIRCUIT: SPEAKER CIRCUIT Device Type 70.7V1/8 0 !Wire Resistance 2.58 CURRENT TOTAL=!9 'Alarm Current; Alarm Total Wire Size Wire Length 1.81 9 01 0 0 Voltage at EOL ! Circuit Total Total Wire Resistance R (WL*2)*(R/ft) 1.05 0, 0 0 TOTAL mA=1 0 -4----___ _------ -- Total Device Load,_ Amps (I) (Total Cct Load) Loadl_Amps (Total Voltage Drop (E ) EOL Voltage (20.4-E) 0.01 20.39057268 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: MARK ECHO FRCP ADD ONS DESCRIPTION SHOP DRAWINGS 1 Current Load: 5/15/08 Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R HTRI-D ICP -B6 2 0.009600 0.0096 0.021 0.042 0.001600 0.0035 0.005 0.0731 Amps 0.106 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 25% Derating= 2.204 Amp -hours Total System Current Load: 2.204 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION _ ____.___Notification Appliance Circuit Detail PROJECT:1 WESTFIELD SOUTHCENTER MALL Panel: i MARK ECHO Date: August 21, 2008 CIRCUIT:! S1 QTY Device Type 1...._ € SET -MC @15CD E ...- 64 i. 1 (SET -MC @30CD 1 981 2 ; SET MC @75CD 1751_._.350 1 !SET -MC @110CD 2331 233 0 ;SET-HMC-C@115CD € 318 0 0 I SET HMC-C@177CD 445' 0 0 1SET-HMC @135CD 318' 0 SET -HMC @185CD ; 4451 1 Z-MC@15CD i 64 0 !Z-MC@30CD 981 0 I SET-MC-CW@110CD DEVICES=16 Wire Resistance 1.62 CURRENT TOTAL= 809 !Alarm Current! Alarm Total Wre Size i Wire Length 1 Voltage at EOL Circuit Total 64 98 233 0 0. 64 0 01 TOTAL mA=! 8091 12 220 Total Wire Resistance (R) ( WL * 2)* (R/ft) 0.71 ___.___.....___._ Total Device Load, Amps {I) 0.81 (Total Cct Load) Voltage Drop ( E) 0.58 (E= I * R) EOL Voltage ` 19.82 (20.4 - E) 19.8233448 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: MARK ECHO Date: !August 21, 2008 CIRCUIT: SPEAKER CIRCUIT Device Type 70.7V1/8 0 !Wire Resistance 2.58 CURRENT TOTAL=!9 'Alarm Current; Alarm Total Wire Size Wire Length 1.81 9 01 0 0 Voltage at EOL ! Circuit Total Total Wire Resistance R (WL*2)*(R/ft) 1.05 0, 0 0 TOTAL mA=1 0 -4----___ _------ -- Total Device Load,_ Amps (I) (Total Cct Load) Loadl_Amps (Total Voltage Drop (E ) EOL Voltage (20.4-E) 0.01 20.39057268 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS 1 DATE 5/15/08 co J'- J c0 O 2 2z _ Wo U �zz W 2w CCQ1 < 5 wO ��� N. co F- J W z 0 z 0 V W co >— (S-CALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:8/20/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1..1013 NUMBER: SHEET \ FA -04 4. OF FIABERDASHERY 1 FIXTURE &TRACK UGI-ITING ©A 0A 0A °A 0A 0A •'r, ri ORTANT Because of interred demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4107 to schedule your inspections a minirnui-li of 48 hours in adv„-.r;rl of he dale you want an inspection. 1 tj Without Co:nm3ftts As Noted in Red Per The Attached Leiter !nese plans have becIn revic•„ ,_:d by The Tukwila Fire Prevention Bu .? 2!.; ;or c.0 ::r',';.::,:.. - with current city,/ standards. A+:. c1.._,,,.a. arrcrs and OmiSsionu •t'+1 r l;i c c- ' 2doptt�c, d t stemarcis o.. ri,.:?; :' or U e l adequacy ci t Additions. ; j this date star resubmittal of r ,_ • Final accepi�•nce .. r. ; t ,d inspection The Tukwila Fire Provoniion r.turt;r�u, /Date: O -/q By: b4 c 17 TUKWILA FIRE DEPARTM' Please call: 575.4407 and give this job and exact addrecs for shuir -morn or restoration 3PDiG'val OT CE Weld stamps must be inspected before pipe is hung. not paint piping: cicir to hydrostatic test Design per NFPA 13 — Ordinary Hazard Occupancy —130 sq ft per sprinkler All materials to be new, U.L. listed, and F.M. approved All heads to be a minimum of 6' apart and to be unobstructed by any means 18 — Add Reliable G4A Quick Response Concealed Sprinkler Heads 155° %Z x %Z 9 — Add Reliable FIFR Quick Response Chrome Pendent Sprinkler Heads 155° 1/2 x %z Total: 27 No. 12 Concrete Hangers ® Hanger Rings / Anchors: UL Listed & FM Approved ® Hanger Rods: Comply with NFPA 13 O All Thread Rods 0 Machine Thread Rods • Finishes: O Standard Components 0 All Galvanized Components 1” = 25.4 mm Components 1. Drop-in Anchor 2. Spring Clip Ceiling Plate (optional} 3. Hanger Rod . 4. Adjustable Hanger Ring Application / Description No. 12 Hangers are designed to support piping under smooth or flat concrete slab construction. They utilize an anchor that is set flush in a -hole predrilled in the concrete, then expanded against the sides of the hole with an internal plug. NFPA 13 terms this type of fastener an "expansion shield". In "Automatic's" data, however, the manufac- turer's nomenclature is used. It is called a drop-in anchor. There are 3 components in a basic No. 12 Hanger: The drop-in anchor, a threaded rod and an adjustable hanger ring. The rod may be either all thread .rod (ATR) or ma- chine thread rod (MTR). All thread rod is considered to be standard, however. As a rule, machine thread rod is pro- vided only when it is a specific -requirement of the job specifications. As an option, the hanger may be furnished with a spring clip ceiling plate when a more finished appearance is needed in an area. NFPA Requirements / Limitations NFPA 13 has specific requirements and/or limitations Ail aim .sarssmear s hem sr tam frhal :-.II /Sart aerre for the use' of expansion shields (drop-in anchors) when they are installed in the vertical position. The standard reads: . . . In concrete having gravel or crushed stone aggregate, expansion shields may be used in the vertical position to support pipe 4" or less in dia- meter. For the support of pipes 5" and larger, expansion shields if used in the vertical position shall alternate with hangers connected directly to the structural members such as trusses and girders, orto the sides of concrete beams. In the absence of convenient structural members, pipes 5" and larger may be sup- ported entirely by expansion shie/ds in the vertical position, but spaced not more than 10 ft (3 m) apart. Expansion shields shall not be used in ceilings of gypsum or similar soft material. In cinder concrete, expansion shields shall not be used except on branch lines where they shall alternate with through bolts or hangers attached to beams. =t --w ea Man 23=Zarcoon*.ett =me 31a Calin.ner.a Available in I Cc • i - Run- s� I • _--X X x . I x x • x L,� 1; U14- Ne:1-Tee Lo Ito-, iii -moi Branch Connector from WARD ItPai rre CROWN FiRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 r��'LECOPY l MARC EcKc5 Cul & cSew SOUTHCENTER MALL 3 7 SOUTHCENTER PARKWAY r - - TUKWILA, WA 98188 AUG 18 2008 Tukwila Fire z zb/F7 ,775-3% DATE: 8 -15 1 DRAWN: J /< I SCALE: '% r5- 1 1