HomeMy WebLinkAboutPP - 846 SOUTHCENTER MALL - FOSSIL INC - PERMITS AND PLANS846 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-306 08-S-164 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Fossil 846 Southcenter Mall Permit No.: 08-S-164 Date: May 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'h inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). I • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. 1 111,1-1ydraulic Summary Job Number: KS0354 Report Description: Ordinary Group II Job Job Number Design Engineer KS0354 Adam Kanter Job Name State Certification/License Number Fossil WESTESF136QF Address 1 Al-IJ 846 Southcentner Mall City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy 5.6 K-Factor 24.00 at 18.367 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 969.00ft2 (Actual 969.99ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(qpm) 13 120.00ft2 etovgd" C°40 Cergg& �°_�n Total Hose Streams , ( O 250.00 k . , 41 Ts System Flow Demand Total Water Required (Including Hose Allowance) iDavid A"'9 325.13 575.13 �1 `��_.����. Maximum Pressure Unbalance In Loops �y • ,1II� 0.000 S' J Maximum Velocity Above Ground �, )i, 15.78 between nodes 40 and 53 , int 'Gd pba <rrbs Maximum Velocity Under Ground D.•.''41Mme` ` 1.23 between nodes 1 and 206 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 1752.86gal 1.22ft3 Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.481 575.13 51.886 87.594 Contractor Contractor Number Contact Name Contact Title KS0358 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web-Site Redmond WA 98052 k, ©M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 05/01/2008 9:11:36AM Page 1 X99 Summary Of Outflowing Devices Job Number: KS0354 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor Pressure (K) (psi) Sprinkler Sprinkler 113 26.95 111 25.67 24.00 5.6 23.161 24.00 5.6 21.016 Sprinkler Sprinkler 110 25.36 24.00 5.6 20.503 112 25.70 24.00 Sprinkler 108 25.00 24.00 5.6 5.6 21.061 19.937 Sprinkler 104 24.52 24.00 5.6 Sprinkler 105 24.65 24.00 5.6 19.180 19.368 Sprinkler 102 24.26 24.00 5.6 c Sprinkler 101 24.00 24.00 5.6 Sprinkler 109 25.15 24.00 5.6 18.765 18.367 20.174 Sprinkler 103 24.32 24.00 5.6 Sprinkler 106 24.68 24.00 5.6 18.857 Sprinkler 19.416 107 24.87 24.00 5.6 19.727 c Most Demanding Sprinkler Data © M.E.P.CAD, Inc. 1J AutoSPRINK® VR5 v5.2.6 05/01/2008 9:11:40AM Page 2 I Node Analysis Job Number: KS0354 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 26 15-0 P0(5-0) 29.755 38 15-0 2P0(8-0) 39 15-0 2P0(8-0) 30.245 30.116 40 15-0 2P0(8-0) 30.100 47 15-0 P0(5-0) 26.933 50 15-0 P0(5-0) 26.862 53 15-0 P0(5-0) 26.750 56 15-0 P0(5-0) 25.281 59 15-0 P0(5 -0J__ 25.081 62 15-0 P0(5-0) 24.760 63 15-0 P0(5-0) 24.920 68 15-0 P0(5-0) 24.612 71 74 15-0 E(2-0) 24.773 15-0 P0(5-0)• 24.166 77 15-0 E(2-0) 24.509 80 15-0 E(2-0) 24.057 83 14-0 fE(6-9%) 33.697 84 16-1 fE(6-9'%) 32.409 206 3-10% BFP(-4.500) 48.426 231 1-11 P0(37 -8'/2I 44.715 235 14-0 fEj10-0) 39.155 246 1-11 LtE(16-0) 44.734 113 12-0 Spr( 23.161) 23.161 26.95 111 12-0 Spr(21.016) 21.016 25.67 110 12-0 Spr(-20.503) 20.503 25.36 112 12-0 Spr(-21.061) 21.061 25.70 108 12-0 Spr(-19.937) 19.937 25.00 104 12-0 Sp_4719.180) 19.180 24.52 105 12-0 Spr1-19.368) _ 19.368 24.65 102 12-0 Spr(-18.765) 18.765 24.26 101 12-0 Spr(-18.367] 18.367 24.00 109 10-9 Spr(-20.174) 20.17425.15 103 12-0 Spr(18.857)_ 18.857 24.32 106 10-9 Spr(-19.416) 19.416 24.68 107 i 10-9 SEM 9.727) 19.727 24.87 1 ' -4-0 S 51.886 325.13 �( © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 9:11:42AM Page 3 I II Hydraulic Analysis Job Number: KS0354 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Pt Friction Loss Length Pressure Length Summary Length Downstream Upstream Elevation Discharge K -Factor _ Pn Fittings Eq. Total ea Route 1 DR 1.049 Q=24.00 8.91 C=120 0.182334 30-4 Pf 7.534 101 12-0 q=24.00 K=5.6 18.367 Spr(-18.367) 11-0 Pe -1.289 68 15-0 24.612 3E(2-0), P0(5-0) 41-4 Pv BL 1.610 0=48.68 7.67 C=120 0.083741 5-7 Pf 0.469 68 15-0 24.612 Pe 59 15-0 25.081 5-7 Pv BL 1.610 0=73.20 11.54 C=120 0.178141 10-0 Pf 1.781 59 15-0 25.081 Pe 50 15-0 26.862 10-0 Pv BL 1.610 Q=98.56 15.53 C=120 0.308843 2-6% Pf 3.254 50 15-0 26.862 8-0 Pe 39 15-0 30.116 P0(8-0) 10-6% Pv CM 4.260 0=198.67 4.47 C=120 0.009885 13-0 Pf 0.129 39 15-0 30.116 .Pe 38 15-0 30.245 13-0 Pv CM 4.260 Q=325.13 7.32 C=120 0.024589 73-11 Pf 2.633 38 15-0 30.245 33-2 Pe -0.470 84 16-1 32.409 T(26-4), 2fEE(3-5) 107-1 Pv RN 4.260 Q=325.13 7.32 C=120 0.024589 2-1 Pf 0.386 84 16-1 32.409 fE(6-9%) 13-7 Pe 0.903 83 14-0 33.697 fE(6-9%) 15-8 Pv CM 4.260 0=325.13 7.32 C=120 0.024589 205-2 Pf 5.458 83 14-0 33.697 16-91/2 Pe 0.000 235 14-0 39.155 fE(6-9%), fE(10-0) 221-11%Pv FM 6.357 Q=325.13 3.29 C=120 0.0.0350.0 11-1% Pf 0.325 235 14-0 39.155 _ 81-8% Pe 5.235 231 1-11 44.715 CV(40-3), GV(3-9%), P0(37-8%) 92-10 Pv FM 8.329 0=325.13 1.91 C=120 0.000939 3-7 Pf 0.018 231 1-11 44.715 16-0 Pe -0.000 246 1-11 44.734 LtE(16-0) 19-7 Pv FM 10.420 Q=325.13 1.22 C=120 0.000315 26-5% Pf 4.535 246 1-11 _ 44.734 83-0 Pe -0.842 206 3-10% 48.426 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5% Pv UG 10.400 Q=325.13_ 1.23 C=140 0.000239 109-2 Pf 0.053 206 3-10'/z 48.426 _ 111-7 Pe 3.407 1 -4-0 51.886 E(35-1), 3LtE(25-6), S 220-9% Pv ill Route 2 DR 1.049 Q=24.26 9.01 C=120 0.185979 29-0'% Pf 7.445 102 12-0 q=24.26 K=5.6 18.765 Spr(-18.765) 11-0 Pe -1.289 63 15-0 24.920 3E(2-0), P0(5-0) 40-0% Pv BL 1.610 Q=49.41 7.79 C=120 0.086095 4-2% Pf 0.361 63 15-0 _ 24.920 Pe 56 15-0 25.281 4-2'% Pv BL 1.610 Q=74.42 11.73 C=120 0.183647 8-0 Pf 1.469 56 15-0 25.281 Pe 53 15-0 26.750 8-0 Pv BL 1.610 Q=100.11 15.78 C=120 0.317930 2-6% Pf 3.350 53 15-0 26.750 8-0 Pe 40 15-0 30.100 P0(8-0) 10-6% Pv CM 4.260 0=100.11 2.25 C=120 0.00.2782 5-10 Pf 0.016 40 15-0 30.100 Pe 39 15-0 30.116 5-10 Pv Route 3 DR 1.049 Q=24.32 9.03 C=120 0.186825 28-4 Pf 6.599 103 12-0 q=24.32 K=5.6 18.857 Spr(-18.857) 7-0 Pe -1.289 74 15-0 24.166 E(2-0), P0(5-0) 35-4 Pv BL 1.610 0=49.19 7.75 C=120 0.085385 6-11% Pf 0.594 74 15-0 24.166 Pe 62 15-0 24.760 6-11% Pv BL 1.610 0=73.84 11.64 C=120 0.181009 12-0 Pf 2.172 62 15-0 24.760 Pe 47 15-0 26.933 12-0 Pv BL 1.610 0=99.51 15.68 C=120 0.314373 2-6% Pf 3.312 47 15-0 26.933 8-0 Pe 38 15-0 30.245 P0(8-0) 10-6% Pv so Route 4 DR 1.049 Q=24.52 9.10 C=120 0.189780 30-10% Pf 7.190 104 12-0 q=24.52 K=5.6 19.180 Spr(-19.180) 7-0 Pe -1.289 59 15-0 25.081 E(2-0), P0(5-0) 37-10% Pv ai Route 5 (, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 9:11:45AM Page 4 ii Hydraulic Analysis I Job Number: KS0354 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length DR 1.049 Q=24.65 9.15 C=120 0.191506 27-10% Pf 6.681 105 12-0 q=24.65 K=5.6 19.368 Spr(-19.368) 7-0 Pe -1.289 62 15-0 24.760 E(2-0), P0(5-0) 34-101/2 Pv Route 6 DR 1.049 Q=24.68 9.16 C=120 0.191944 32-1 Pf 6.924 106 10-9 q=24.68 K=5.6 19.416 Spr(-19.416) 4-0 Pe -1.831 77 15-0 24.509 2E(2-0) 36-1 Pv BL 1.610 Q=24.68 3.89 C=120 0.023829 4-4 Pf 0.103 77 15-0 24.509 Pe 68 15-0 24.612 4-4 Pv Gil Route 7 DR 1.049 Q=24.87 9.23 C=120 0.194783 27-71/2 Pf 6.161 107 10-9 q=24.87 K=5.6 19.727 Spr(-19.727) 4-0 Pe -1.831 80 15-0 24.057 2E(2-0) 31-7% Pv BL 1.610 Q=24.87 3.92 C=120 0.024182 4-6% Pf 0.110 80 15-0 24.057 Pe 74 15-0 24.166 4-6% Pv o Route 8 DR 1.049 Q=25.00 9.28 C=120 0.196701 26-8% Pf 6.633 108 12-0 q=25.00 K=5.6 19.937 Spr(-19.937) 7-0 Pe -1.289 56 15-0 25.281 E(2-0), P0(5-0) 33-81/2 Pv wo Route 9 DR 1.049 0=25.15 9.34 C=120 0.198863 28-4 Pf 6.430 109 10-9 q=25.15 K=5.6 20.174 Spr(-20.174) 4-0 Pe -1.831 71 15-0 24.773 2E(2-0) 32-4 Pv BL 1.610 Q=25.15 3.96 C=120 0.024688 5-11% Pf 0.147 71 15-0 24.773 Pe 63 15-0 24.920 5-11% Pv ap Route 10 DR 1.049 Q=25.36 9.41 C=120 0.201864 30-10% Pf 7.648 _ 110 12-0 q=25.36 K=5.6 20.503 Spr(-20.503) 7-0 Pe -1.289 50 15-0 26.862 E(2-0), P0(5-0) 37-10% Pv ai Route 11 DR 1.049 0=25.67 9.53 C=120 0.20653.1 27-10% Pf 7.206 111 12-0 q=25.67 K=5.6 21.016 Spr(-21.016) 7-0 Pe -1.289 47 15-0 26.933 E(2-0), P0(5-0) 34-10% Pv iiii Route 12 DR 1.049 Q=25.70 9.54 C=120 0.206937 26-8% Pf 6.979 112 12-0 q=25.70 K=5.6 21.061 Spr(-21.061) 7-0 Pe -1.289 53 15-0 26.750 E(2-0), P0(5-0) 33-8% Pv so Route 13 DR 1.049 Q=26.95 10.00 C=120 0.225955 27-10% Pf 7.883 113 12-0 q=26.95 K=5.6 23.161 Spr(-23.161) 7-0 Pe -1.289 26 15-0 29.755 E(2-0), P0(5-0) 34-10% Pv BL 1.610 Q=26.95 4.25 C=120 0.028052 9-5% Pf 0.490 _ 26 15-0 29.755 8-0 Pe 38 15-0 30.245 P0(8-0) 17-5'% Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) C Value Multiplier II Actual Inside Diameter 4'87 ( ) Value Of C 100 130 140 150 =Factor Schedule 40 Steel Pipe Inside Diameter Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD, Inc. AutoSPRINK© VR5 v5.2.6 05/01/2008 9:11:45AM Page 5 1111 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0354 Report Description: Ordinary Group II Velocity HWC K -Factor Pt Pn Fittings Friction Loss Pipe Type Legend Units Legend Length Pressure Eq. Length Summary Total Length Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger pt RN Riser Nipple Pn SP Sprig Pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 111/4° Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (d� ©M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 05/01/2008 9:11:45AM Page 6 ii. ' Hydraulic GraphIIJob Number: KS035 Report Description: Ordinary Group Supply at Node 1 150 -Static 135 Pressure 140.000 120 105 90 'N 0 75 D N co N a` 60 y575.13 X25.13 45 with hose @ 51.886 streams 30 15 -System demand curve 10900.00 @ 20.000_ -1E11111111 0 11111111111111 1 1111 111111111 1111111/1 111111111 111111111 111 1 1 1 1 1 1 111111111 O 71002200 3300 4400 5500 . 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.481 @ 575.13 System Demand 325.13 @ 51.886 System Demand (Including Hose Allowance) 575.13 @ 51.886 ©M.E.P.CAD, Inc. 8 AutoSPRINKO VR5 v5.2.6 05/01/2008 9:11:51AM I I Page 7 11 Flow Diagram (Top View) r Job Number: KS0354 Report Description: Ordinary Group II (t, ©M.E.P.CAD, Inc. di AutoSPRINK© VR5 v5.2.6 05/01/2008 9:11:54AM Page 8 GUARDIAN SECURITY Customer LIFE AND PROPERTY PROTECTION Vendor FOSSIL Guardian Security Systems Inc 8411 SOUTHCENTER MALL 1743 1st Ave. South KWILA, WA 98188 Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Project Project # FOSSIL List of Materials Date: June 10, 2008 Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard VICINITY MAP (Suite# 846) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. Zone T-3 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE CLG 10'-0" Existing 4" Main Ordinary Group 11.0.20gpm/ft= for 969t00ft2 Tolit!?,1 t ,1:71t:i`iiia o -91 CLG 12'-0" a�• 4 f CLG 9'-0" CLG 12'-0" 4 Existing 4" Main CLG 12'-0" CLG 10'-9" CLG 10'-9" CLG 10'-9" FIRE SPRINKLER SYETEM 118"=1'-0" 2c) 3 5 7 9 11 TYPICAL FLEXABLE SPRINKLER CONNECTION.. FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING <, SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE 9/B' KWIK BOLT (21W EMBED LENGTH) FIG. 909 SWIVEL SWAY BRACE FITTING F4r:BRACE PIPE FIGAs. 11000cump. 470 SWAY BRACE ATTACHMENT UNE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT 9!9" KWIK BOLT (21/4_ EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT BRACE PIPE SZ�..,fil NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE 12'-0" CLG =37.0% AREA REDUCTION Hanger No. 07C HILTI Kwik Bolt III -� 11 _ / HILTIKwA Bot II Drilled Anchor i Cut Rod Lgth Rounded to Nearest Inch Rod Coupling Q All Thread Rod / 5 / •� ` 1 / — 1 { Concrete f Construction Swivel Ring Pipe Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plane Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE dflr S /� 9 .FT) N 0 LL w z 0 Adam Kantner Royal Seal Construction CONTRACTOR: SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT NO. DESCRIPTION DATE Sprinkler Legend SIN R5415 QTY. 20 Total = 20 K 5.6 SPRAY Pendent ORIF. FIN. White TEMP. 155°F MFR./MODEL G4A Concealed APPROVAL: City of Tukwila CONT. NO.: KS0354 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/19/08 t Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN / DALLAS / DECATUR / DENVER !DULUTH/HOUSTON/IWISAS CITY LAS VEGAS /MRIEAPOUS /PHOENIX/PORTLAND/ RAPIC CITY/ST. PAUL/ SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Fossil 846 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYETEM SHEET FP -1 OF 1 SHEET INDEX SHEET \UM3ER SHEET TITLE FOSSIL FIRE ALARM SYSTEM TUKWILA, WASHINGTON FA -01 SYSTEM I N FO R v1ATI O N FA -02 TYPICAL DETAILS - WIRI\ G A\D NOUNTI\G FA -03 FIRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (CE\ERAL), MISER, SITE PLA WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2' 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL. PREPROGRAMMED WITH DEVICES ADDRESS. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL DE MOUNTED AT 48" A,F.r. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ,ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM. (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. QUANTITY 2 1 1 1 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT • MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD -Sq LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP IN/ 1G RING CEILING DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING 111C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT YC B AWP MR ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD a MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. e r• F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX A.F.F. ABOVE FINISHED FLOOR F.B.O. N/A F.B.❑.� _;: N/A VERIFY' IN FIELD :,N/A N/A F.B.❑, FURNISHED BY OTHERS N/A N/A NOT APPLICABLE N/A U.O.N. UNLESS OTHERWISE NOTED N/A WP WEATHERPROOF DEVICE N/A RED AS BUILT ADD OR CHANGE N/A Without OPmments As Noted In Red Per I he Att hed Letter N/A N/A _ N/A i nese plans have been reviewed by The Tukwila Fire Prevention bureau for conformance with current citm/A dards. Acceptance is�,!i act to errors and omissions which do not authorize violations, of adopted standards and oralnancesNRae responsibility for tfte/A at2:iacy of design rests tofay ly with the designer. Additions, deletions or revisions 1n these drawings atter Ids date will void this.acceR�tace and will require aN/A &i r mittal of revised dravYitf s for subsequent approval. GREEN BLUE AS BUILT REMOVE AS BUILT NOTES TO CAD N/A N/A i -mal acceptance is subjec pljetd test and inspectit ' y TiV�ukwila Fire Prevention Bureau. r o od N/A TUKWILA FIRE DEPART;i:..41 Please call: 575-4407 and give this job 62 and exact address for shuts down or restoration approval, NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to.the Inspector prior to tO 0' 0' 0' co N .0 c CV X RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE to 0 0 0 12 (CCC« co co J' - J 0) wFE la z �o CPet w O S E< L1.. Q W CC U(?)LL 07, CO F- commencement of Acceptanze Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re inspection Fee and termination of the testing. PAID JUN 1'02008 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Z 0 F 0 z /SCALE: 1 /8"=1 ' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 j THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR !STRIATION REQUIREMENT LABEL SC LE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL ❑R+ PREVIOUS ADDRESSABLE DEVIL DUCT DETECTOR LOCATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 rr) O -2 �r- HTRI—R OSTATUS LED 0 N.O. O COM O N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING \ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR MUSIC 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.OA @ 125VAC) (4.OA e 3OVDC) 27 VDC 3.5 PIA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. 0 TB1 006)6)6)0 123456 HCP TB2 � m� 6 54 3 2 1 END OF LINE DEVICE (3.6K 1/4W) O SUPERVISED / SWITCH GROUND NOTE: 0 HTRI—D OSTATUS LED co 0 CD 0 r NOT USED 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC maim T T T O PAD -3 0 oo� INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 2 NAC -3 NAC -2 2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED SWITCH ( NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) FROM-FACP (VOICE CIRCUIT) ('V' CABLE) 470 OHMS EOL TEM -1 0 dch� 0:0 0 O :1:-2:2-:4:1 IINC TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL NUE () H STROBE SPEAKER (STROBE) EARTH GROUND 0 ->.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE (S ) STROBE SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 80" A.F.F. 0 0 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERtTEMPER/OWE: +32"F ' TO 100' F IT HUMIDITY: C) % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --,, �► FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) >-- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE-(— > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT T BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX • MOUNTED ON \ CEILING FLEX \ JUNCTION BOX MOUNTED AGAINST CEILING SUI'PUR I 0 0 ; TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO \OT INSTA_L ADDRESSABLE N DEVICES UNTI_ PREPROGRAMVED W DEVICES ADDRESS. OTDATNG TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved -U. rr) 00 O` O O' CD N \O L_ Ln LC) N N 'O CD • J UJ F— RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 6/05/08 o <CC« 0 z_ z 3 0 0 c OTO W�0 z Z .. EE co cc ie..q) O S'< W o CC w LL CO s (f) co I --- SCALE: 1/8" = 1 ' W. a -J 0 0 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -02 EOL—S1 20.19V ca of- Fit /1 FACP EX FA—BOX hN�1+HR�NM Xk(i h'jh1{d1;�X li„ NORTH. FOSSIL WESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG \ OTIES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VCNILLAT❑R FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO- INSTALL ADDRESSABLE 1NIT DEVICES JTIL PREPROGRAMN-D W DEVICES ADDRESS. ATI\G TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved r 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE co 0 0 to 19 «a« CO CO J '- J 00 W �o UJ 0 C oc • w 0 S'< ▪ Q W a- F - con SCALE : 1/8"=1' DRAWN BY: I -ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: `20B NUMBER: r SHEET FA -03 J.L.I Lu 1 5 1 5 0,1 11 0 LiJ :5 5 1 470 NORTH !11FAMILY MEN VI/1,1 CORDON'S E. WE 1.1: S 3 ,t -\`..3K I IN R 0 E3 BINS P11 0 FOSSIL WESTFIELD SOUTHCENTER MALL SCALE 1/374 I I 0 a: < . 1 K I TS C, AMER 510 IF -1 ERH COD MA TERN PIERCING PAGODA 1,.1 [)3 SP S I N Tr-AS1-1 0 BANK TH E KIDS FOOT.L.00KE:R LU.. E 1'14501 )CL- 1 'I 2101 I1.1;') -1" LiJ C) 4. LL SYSTEM CALCULATIONS SPR L.L.1 a. K1: 0 0.„ [12.30 I 2151 112:20j ........ 4201 1 1410 r: EX L. BATTERY SIZING CALCULATION FOSSIL FOSSIL FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: WESTFIELD SOUTHCENTER MALL Panel: FOSSIL Wire Resistance 1.62' Date: June 6,2008 CURRENT TOTAL= 337 Current Load: Standby: Alarm: Current Load: Standby: Alarm: QTY Device Type Alarm Current ._. Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC ©15CD 64 0 Device Type Qty Amps Total Amps Total SET -MC @30CD Device Type 98 Qty Amps Total Amps Total HFP-11 SET -MC @75CD 175 0.0022 0.0022 0.0023 Total Device Load, Amps (1) 0.34 o SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 318 Main System Board 1 0.03 0.03 0.030 0.030 0 HTR -R 445 2 0.009600 0.0096 0.021 0.042 SET -MC ©15CD 0 SET -HMC @135CD 318 0 0.064 HTRI-D EOL Voltage 0.001600 0 0.0035 445 0 SET -MC @30CD 1 (20.4 - E) 0.098 0.098 64 ICP -B6 0.005 0 SET -MC @75CD 98 1 0.175 0.175 0 SET-MC-CW©110CD 233 0 337 12 191 20.19145092L 337 SET -MC @110CD DEVICES= 3 TOTAL m A= 0.233 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL SET-HMC-C@115CD Panel: FOSSIL 0.318 Date: June 6, 2008 CURRENT TOTAL= 3.6 SET-HMC-C©135CD CIRCUIT: SPEAKER CIRCUIT 0.318 QTY 0.0731 Amps 0.106 Amps SET-HMC-C@185CD Voltage at EOL Circuit Total 0.445 70.7V1/8 1.8 3.6 Total Wire Resistance ( R ZR -MC ©15CD 0 0 0 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Total Device Load Amps (I) 0.00 0.098 0 0 (Total Cct Load) HCP 0 0 0.0015 Alarm Current Load: ( E 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0 0.03 Amps 0.303 Amps 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 DEVICES= 2 TOTAL m A= 3.6 14 191 20.39645198 3.6 Alarm Current Load: 0.303 Amps For 5 Minutes= 0.025 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.932 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.932 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION TEL. (206) 622-654.5 Cf) z 0 (1) w LU LU LLJ z DESCRIPTION SHOP DRAWINGS ILI 0 co 0 If) 0 (.0 << CO CO 0 CO cf) E Eft ---1 1-0 ev, 0 frE- w (7) 1) w (f) M 0 0 mg LL< (r) [kJ (90) z co- coD 0 _J citC 0 1.1.1 (f) ›- C/) 'ALE: 1/8"=1' "*.\ DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION ,J.OB NUMBER: F SHEETA-04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: FOSSIL Wire Resistance 1.62' Date: June 6,2008 CURRENT TOTAL= 337 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC ©15CD 64 0 Total Wire Resistance ( R ) 0.62 1 SET -MC @30CD 98 98 ( WL * 2 ) * (R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (1) 0.34 o SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.21 0 SET-HMC-C@177CD 445 o (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.19 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW©110CD 233 0 337 12 191 20.19145092L 337 DEVICES= 3 TOTAL m A= Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: FOSSIL Wire Resistance 2 11 Date: June 6, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance ( R 0.99 0 0 0 0 0 0 Total Device Load Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E ) 0.00 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL m A= 3.6 14 191 20.39645198 3.6 TEL. (206) 622-654.5 Cf) z 0 (1) w LU LU LLJ z DESCRIPTION SHOP DRAWINGS ILI 0 co 0 If) 0 (.0 << CO CO 0 CO cf) E Eft ---1 1-0 ev, 0 frE- w (7) 1) w (f) M 0 0 mg LL< (r) [kJ (90) z co- coD 0 _J citC 0 1.1.1 (f) ›- C/) 'ALE: 1/8"=1' "*.\ DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION ,J.OB NUMBER: F SHEETA-04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Fossil General Notes VICINITY MAP (Suite# 846) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not des)finned for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. Zone T-3 WEST RISER DETAIL, HYDRAULIC REFERENCE ONLY NOT TO SCALE Ordinary Group II.0.20g,pm/ft2 for 969,00it2 Existing 4" Main--- 4 --•—Existing 4" Main • ❑ Without Comments ❑ As Noted in Red Per The. tVoh=d 1 { t:er Inesepkn hV :1, I Prevention -:,,,,...;-=_ '-.; ._. standard_;.... omissions v ,FI dequacy ddit.l!ion:i. tip= da`2 ,uhrIt: tl Cit,' S., r:er. -Lt n i SCC CI I C i`. : ; ;' :>t c✓ ICS inspection by lip Tukwila Fire P;;:•.-=:;rl,;ci; :urcau. Date: S– � By: FIRE SPRINKLER SYETEM 11811=1-0" 1 3 5 7 9 11 ----TUKWILA FIRE DEPARTM .N1 Please call: 575.4407 and give this job No. 08s 7(9`1 and exact address for shut- down or reyt;,ration approval. N SCE TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE LEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE /////////////,IV/ FIG.909 SWIVEL SWAY BRACE FITTING BRACE PIPE 918' KWIK BOLT (2 IW EMBED LENGTH) F)G.100) �'- "FAST CAMP' SWAY BRACE ATTACHMENT LINE PIPE LATERAL LiNE RESTRAINTS NON -THREADED BRACE PIPE FIG -4A PIPE CLAMP FOR SWAY BRACE 6 LATERAL BRANCHLINE RESTRAINT 918' KWIK BOLT (2 114" EMBED LENGTH) 1 1 NON -THREADED BRACE PIPE LATER A T , BRANCHLINE J E RESTRAINT NOT TO SCALE Fossil Remote Area: Retail # 846 Weld stamps must b inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD 11 MAX. COVERAGE per HEAD 130 DENsrn' .20 GPM i Ft for 969.99 SPRINKLER Reliable Model G4A FP Ft ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 RESIDUAL 20 FLOW 10900 PSi PS! GPM AT BASE OF RISER. SYSTEM REQUIRES: 289.39 GPM @ 32.10 PSI • At time of Design 12'-0" CLG :37.0%AREA REDUCTION Hanger No. 07C HILTI Kwik Bolt III HILTIKwY Bolt II Dn7ted Anchor / i Rod Coupling —� Ag Thread Rod _~= Cut Rod Lgth Rounded to Nearest Inch q. Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plart Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE PA 2008 %10 Dosto Tukwila Fire rC77/.s"--- t/3 0 LL w z 0 Adam Kantner 0_ 0 Royal Seal Construction CONTRACTOR SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT DESCRIPTION SYM. SIN QTY. R5415 R3615 Sprinkler Legend APPROVAL City of Tukwila SPRAY ORIF. FIN. TEMP. Pendent 155°F 5.6 Upright Brass 155°F MFR./MODEL G4A Concealed Western States Fire F1 FR Brass Upright Total = 20 CONT. NO.: KS0354 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE 05/01/08 Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. # WESTESF1cSQF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIRI/DALLAS / DECATUR /DENVER /DULUTH/HOUSrON/KANSAS CITY LAS VEGAS /1.1I1e APOUS/PHOENUVPORTLANDIRAPID CITY/ST. PALL/SALT IA10=CITY/SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Fossil 846 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYETEM SHEET FP -1 OF 1 846 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-306 08-S-164 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Fossil 846 Southcenter Mall Permit No.: 08-S-164 Date: May 5, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'h inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). I • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. 1 111,1-1ydraulic Summary Job Number: KS0354 Report Description: Ordinary Group II Job Job Number Design Engineer KS0354 Adam Kanter Job Name State Certification/License Number Fossil WESTESF136QF Address 1 Al-IJ 846 Southcentner Mall City of Tukwila Address 2 Job Site Southcenter Mall City State Zip Code Drawing Name Tukwila Wa 98188 FP-1.cad System Remote Area(s) Most Demanding Sprinkler Data Occupancy 5.6 K-Factor 24.00 at 18.367 Ordinary Group II Hose Allowance At Source Density Area of Application 250.00 0.20gpm/ft2 969.00ft2 (Actual 969.99ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(qpm) 13 120.00ft2 etovgd" C°40 Cergg& �°_�n Total Hose Streams , ( O 250.00 k . , 41 Ts System Flow Demand Total Water Required (Including Hose Allowance) iDavid A"'9 325.13 575.13 �1 `��_.����. Maximum Pressure Unbalance In Loops �y • ,1II� 0.000 S' J Maximum Velocity Above Ground �, )i, 15.78 between nodes 40 and 53 , int 'Gd pba <rrbs Maximum Velocity Under Ground D.•.''41Mme` ` 1.23 between nodes 1 and 206 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 1752.86gal 1.22ft3 Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node (gpm) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.481 575.13 51.886 87.594 Contractor Contractor Number Contact Name Contact Title KS0358 Adam Kantner Project Manager Contractor Name Phone Extension Western States Fire Protection 425.881.0100 Address 1 FAX 7102 180th Ave Ne, Suite A-105 485.736.9032 Address 2 E-mail City State Zip Code Web-Site Redmond WA 98052 k, ©M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 05/01/2008 9:11:36AM Page 1 X99 Summary Of Outflowing Devices Job Number: KS0354 Report Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor Pressure (K) (psi) Sprinkler Sprinkler 113 26.95 111 25.67 24.00 5.6 23.161 24.00 5.6 21.016 Sprinkler Sprinkler 110 25.36 24.00 5.6 20.503 112 25.70 24.00 Sprinkler 108 25.00 24.00 5.6 5.6 21.061 19.937 Sprinkler 104 24.52 24.00 5.6 Sprinkler 105 24.65 24.00 5.6 19.180 19.368 Sprinkler 102 24.26 24.00 5.6 c Sprinkler 101 24.00 24.00 5.6 Sprinkler 109 25.15 24.00 5.6 18.765 18.367 20.174 Sprinkler 103 24.32 24.00 5.6 Sprinkler 106 24.68 24.00 5.6 18.857 Sprinkler 19.416 107 24.87 24.00 5.6 19.727 c Most Demanding Sprinkler Data © M.E.P.CAD, Inc. 1J AutoSPRINK® VR5 v5.2.6 05/01/2008 9:11:40AM Page 2 I Node Analysis Job Number: KS0354 Report Description: Ordinary Group II Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 26 15-0 P0(5-0) 29.755 38 15-0 2P0(8-0) 39 15-0 2P0(8-0) 30.245 30.116 40 15-0 2P0(8-0) 30.100 47 15-0 P0(5-0) 26.933 50 15-0 P0(5-0) 26.862 53 15-0 P0(5-0) 26.750 56 15-0 P0(5-0) 25.281 59 15-0 P0(5 -0J__ 25.081 62 15-0 P0(5-0) 24.760 63 15-0 P0(5-0) 24.920 68 15-0 P0(5-0) 24.612 71 74 15-0 E(2-0) 24.773 15-0 P0(5-0)• 24.166 77 15-0 E(2-0) 24.509 80 15-0 E(2-0) 24.057 83 14-0 fE(6-9%) 33.697 84 16-1 fE(6-9'%) 32.409 206 3-10% BFP(-4.500) 48.426 231 1-11 P0(37 -8'/2I 44.715 235 14-0 fEj10-0) 39.155 246 1-11 LtE(16-0) 44.734 113 12-0 Spr( 23.161) 23.161 26.95 111 12-0 Spr(21.016) 21.016 25.67 110 12-0 Spr(-20.503) 20.503 25.36 112 12-0 Spr(-21.061) 21.061 25.70 108 12-0 Spr(-19.937) 19.937 25.00 104 12-0 Sp_4719.180) 19.180 24.52 105 12-0 Spr1-19.368) _ 19.368 24.65 102 12-0 Spr(-18.765) 18.765 24.26 101 12-0 Spr(-18.367] 18.367 24.00 109 10-9 Spr(-20.174) 20.17425.15 103 12-0 Spr(18.857)_ 18.857 24.32 106 10-9 Spr(-19.416) 19.416 24.68 107 i 10-9 SEM 9.727) 19.727 24.87 1 ' -4-0 S 51.886 325.13 �( © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 9:11:42AM Page 3 I II Hydraulic Analysis Job Number: KS0354 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Pt Friction Loss Length Pressure Length Summary Length Downstream Upstream Elevation Discharge K -Factor _ Pn Fittings Eq. Total ea Route 1 DR 1.049 Q=24.00 8.91 C=120 0.182334 30-4 Pf 7.534 101 12-0 q=24.00 K=5.6 18.367 Spr(-18.367) 11-0 Pe -1.289 68 15-0 24.612 3E(2-0), P0(5-0) 41-4 Pv BL 1.610 0=48.68 7.67 C=120 0.083741 5-7 Pf 0.469 68 15-0 24.612 Pe 59 15-0 25.081 5-7 Pv BL 1.610 0=73.20 11.54 C=120 0.178141 10-0 Pf 1.781 59 15-0 25.081 Pe 50 15-0 26.862 10-0 Pv BL 1.610 Q=98.56 15.53 C=120 0.308843 2-6% Pf 3.254 50 15-0 26.862 8-0 Pe 39 15-0 30.116 P0(8-0) 10-6% Pv CM 4.260 0=198.67 4.47 C=120 0.009885 13-0 Pf 0.129 39 15-0 30.116 .Pe 38 15-0 30.245 13-0 Pv CM 4.260 Q=325.13 7.32 C=120 0.024589 73-11 Pf 2.633 38 15-0 30.245 33-2 Pe -0.470 84 16-1 32.409 T(26-4), 2fEE(3-5) 107-1 Pv RN 4.260 Q=325.13 7.32 C=120 0.024589 2-1 Pf 0.386 84 16-1 32.409 fE(6-9%) 13-7 Pe 0.903 83 14-0 33.697 fE(6-9%) 15-8 Pv CM 4.260 0=325.13 7.32 C=120 0.024589 205-2 Pf 5.458 83 14-0 33.697 16-91/2 Pe 0.000 235 14-0 39.155 fE(6-9%), fE(10-0) 221-11%Pv FM 6.357 Q=325.13 3.29 C=120 0.0.0350.0 11-1% Pf 0.325 235 14-0 39.155 _ 81-8% Pe 5.235 231 1-11 44.715 CV(40-3), GV(3-9%), P0(37-8%) 92-10 Pv FM 8.329 0=325.13 1.91 C=120 0.000939 3-7 Pf 0.018 231 1-11 44.715 16-0 Pe -0.000 246 1-11 44.734 LtE(16-0) 19-7 Pv FM 10.420 Q=325.13 1.22 C=120 0.000315 26-5% Pf 4.535 246 1-11 _ 44.734 83-0 Pe -0.842 206 3-10% 48.426 4LtE(16-0), BV(19-0), BFP(-4.500) 109-5% Pv UG 10.400 Q=325.13_ 1.23 C=140 0.000239 109-2 Pf 0.053 206 3-10'/z 48.426 _ 111-7 Pe 3.407 1 -4-0 51.886 E(35-1), 3LtE(25-6), S 220-9% Pv ill Route 2 DR 1.049 Q=24.26 9.01 C=120 0.185979 29-0'% Pf 7.445 102 12-0 q=24.26 K=5.6 18.765 Spr(-18.765) 11-0 Pe -1.289 63 15-0 24.920 3E(2-0), P0(5-0) 40-0% Pv BL 1.610 Q=49.41 7.79 C=120 0.086095 4-2% Pf 0.361 63 15-0 _ 24.920 Pe 56 15-0 25.281 4-2'% Pv BL 1.610 Q=74.42 11.73 C=120 0.183647 8-0 Pf 1.469 56 15-0 25.281 Pe 53 15-0 26.750 8-0 Pv BL 1.610 Q=100.11 15.78 C=120 0.317930 2-6% Pf 3.350 53 15-0 26.750 8-0 Pe 40 15-0 30.100 P0(8-0) 10-6% Pv CM 4.260 0=100.11 2.25 C=120 0.00.2782 5-10 Pf 0.016 40 15-0 30.100 Pe 39 15-0 30.116 5-10 Pv Route 3 DR 1.049 Q=24.32 9.03 C=120 0.186825 28-4 Pf 6.599 103 12-0 q=24.32 K=5.6 18.857 Spr(-18.857) 7-0 Pe -1.289 74 15-0 24.166 E(2-0), P0(5-0) 35-4 Pv BL 1.610 0=49.19 7.75 C=120 0.085385 6-11% Pf 0.594 74 15-0 24.166 Pe 62 15-0 24.760 6-11% Pv BL 1.610 0=73.84 11.64 C=120 0.181009 12-0 Pf 2.172 62 15-0 24.760 Pe 47 15-0 26.933 12-0 Pv BL 1.610 0=99.51 15.68 C=120 0.314373 2-6% Pf 3.312 47 15-0 26.933 8-0 Pe 38 15-0 30.245 P0(8-0) 10-6% Pv so Route 4 DR 1.049 Q=24.52 9.10 C=120 0.189780 30-10% Pf 7.190 104 12-0 q=24.52 K=5.6 19.180 Spr(-19.180) 7-0 Pe -1.289 59 15-0 25.081 E(2-0), P0(5-0) 37-10% Pv ai Route 5 (, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.2.6 05/01/2008 9:11:45AM Page 4 ii Hydraulic Analysis I Job Number: KS0354 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K -Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length DR 1.049 Q=24.65 9.15 C=120 0.191506 27-10% Pf 6.681 105 12-0 q=24.65 K=5.6 19.368 Spr(-19.368) 7-0 Pe -1.289 62 15-0 24.760 E(2-0), P0(5-0) 34-101/2 Pv Route 6 DR 1.049 Q=24.68 9.16 C=120 0.191944 32-1 Pf 6.924 106 10-9 q=24.68 K=5.6 19.416 Spr(-19.416) 4-0 Pe -1.831 77 15-0 24.509 2E(2-0) 36-1 Pv BL 1.610 Q=24.68 3.89 C=120 0.023829 4-4 Pf 0.103 77 15-0 24.509 Pe 68 15-0 24.612 4-4 Pv Gil Route 7 DR 1.049 Q=24.87 9.23 C=120 0.194783 27-71/2 Pf 6.161 107 10-9 q=24.87 K=5.6 19.727 Spr(-19.727) 4-0 Pe -1.831 80 15-0 24.057 2E(2-0) 31-7% Pv BL 1.610 Q=24.87 3.92 C=120 0.024182 4-6% Pf 0.110 80 15-0 24.057 Pe 74 15-0 24.166 4-6% Pv o Route 8 DR 1.049 Q=25.00 9.28 C=120 0.196701 26-8% Pf 6.633 108 12-0 q=25.00 K=5.6 19.937 Spr(-19.937) 7-0 Pe -1.289 56 15-0 25.281 E(2-0), P0(5-0) 33-81/2 Pv wo Route 9 DR 1.049 0=25.15 9.34 C=120 0.198863 28-4 Pf 6.430 109 10-9 q=25.15 K=5.6 20.174 Spr(-20.174) 4-0 Pe -1.831 71 15-0 24.773 2E(2-0) 32-4 Pv BL 1.610 Q=25.15 3.96 C=120 0.024688 5-11% Pf 0.147 71 15-0 24.773 Pe 63 15-0 24.920 5-11% Pv ap Route 10 DR 1.049 Q=25.36 9.41 C=120 0.201864 30-10% Pf 7.648 _ 110 12-0 q=25.36 K=5.6 20.503 Spr(-20.503) 7-0 Pe -1.289 50 15-0 26.862 E(2-0), P0(5-0) 37-10% Pv ai Route 11 DR 1.049 0=25.67 9.53 C=120 0.20653.1 27-10% Pf 7.206 111 12-0 q=25.67 K=5.6 21.016 Spr(-21.016) 7-0 Pe -1.289 47 15-0 26.933 E(2-0), P0(5-0) 34-10% Pv iiii Route 12 DR 1.049 Q=25.70 9.54 C=120 0.206937 26-8% Pf 6.979 112 12-0 q=25.70 K=5.6 21.061 Spr(-21.061) 7-0 Pe -1.289 53 15-0 26.750 E(2-0), P0(5-0) 33-8% Pv so Route 13 DR 1.049 Q=26.95 10.00 C=120 0.225955 27-10% Pf 7.883 113 12-0 q=26.95 K=5.6 23.161 Spr(-23.161) 7-0 Pe -1.289 26 15-0 29.755 E(2-0), P0(5-0) 34-10% Pv BL 1.610 Q=26.95 4.25 C=120 0.028052 9-5% Pf 0.490 _ 26 15-0 29.755 8-0 Pe 38 15-0 30.245 P0(8-0) 17-5'% Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only) C Value Multiplier II Actual Inside Diameter 4'87 ( ) Value Of C 100 130 140 150 =Factor Schedule 40 Steel Pipe Inside Diameter Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD, Inc. AutoSPRINK© VR5 v5.2.6 05/01/2008 9:11:45AM Page 5 1111 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0354 Report Description: Ordinary Group II Velocity HWC K -Factor Pt Pn Fittings Friction Loss Pipe Type Legend Units Legend Length Pressure Eq. Length Summary Total Length Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger pt RN Riser Nipple Pn SP Sprig Pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Eel 111/4° Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap (d� ©M.E.P.CAD, Inc. AutoSPRINKO VR5 v5.2.6 05/01/2008 9:11:45AM Page 6 ii. ' Hydraulic GraphIIJob Number: KS035 Report Description: Ordinary Group Supply at Node 1 150 -Static 135 Pressure 140.000 120 105 90 'N 0 75 D N co N a` 60 y575.13 X25.13 45 with hose @ 51.886 streams 30 15 -System demand curve 10900.00 @ 20.000_ -1E11111111 0 11111111111111 1 1111 111111111 1111111/1 111111111 111111111 111 1 1 1 1 1 1 111111111 O 71002200 3300 4400 5500 . 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.481 @ 575.13 System Demand 325.13 @ 51.886 System Demand (Including Hose Allowance) 575.13 @ 51.886 ©M.E.P.CAD, Inc. 8 AutoSPRINKO VR5 v5.2.6 05/01/2008 9:11:51AM I I Page 7 11 Flow Diagram (Top View) r Job Number: KS0354 Report Description: Ordinary Group II (t, ©M.E.P.CAD, Inc. di AutoSPRINK© VR5 v5.2.6 05/01/2008 9:11:54AM Page 8 GUARDIAN SECURITY Customer LIFE AND PROPERTY PROTECTION Vendor FOSSIL Guardian Security Systems Inc 8411 SOUTHCENTER MALL 1743 1st Ave. South KWILA, WA 98188 Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Project Project # FOSSIL List of Materials Date: June 10, 2008 Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) 18) 19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) 48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard VICINITY MAP (Suite# 846) SCALE: NTS General Notes 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. Zone T-3 WEST RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE CLG 10'-0" Existing 4" Main Ordinary Group 11.0.20gpm/ft= for 969t00ft2 Tolit!?,1 t ,1:71t:i`iiia o -91 CLG 12'-0" a�• 4 f CLG 9'-0" CLG 12'-0" 4 Existing 4" Main CLG 12'-0" CLG 10'-9" CLG 10'-9" CLG 10'-9" FIRE SPRINKLER SYETEM 118"=1'-0" 2c) 3 5 7 9 11 TYPICAL FLEXABLE SPRINKLER CONNECTION.. FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING <, SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE 9/B' KWIK BOLT (21W EMBED LENGTH) FIG. 909 SWIVEL SWAY BRACE FITTING F4r:BRACE PIPE FIGAs. 11000cump. 470 SWAY BRACE ATTACHMENT UNE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE FIG. 4A PIPE CLAMP FOR SWAY BRACE LATERAL BRANCHLINE RESTRAINT 9!9" KWIK BOLT (21/4_ EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT BRACE PIPE SZ�..,fil NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE 12'-0" CLG =37.0% AREA REDUCTION Hanger No. 07C HILTI Kwik Bolt III -� 11 _ / HILTIKwA Bot II Drilled Anchor i Cut Rod Lgth Rounded to Nearest Inch Rod Coupling Q All Thread Rod / 5 / •� ` 1 / — 1 { Concrete f Construction Swivel Ring Pipe Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plane Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE dflr S /� 9 .FT) N 0 LL w z 0 Adam Kantner Royal Seal Construction CONTRACTOR: SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT NO. DESCRIPTION DATE Sprinkler Legend SIN R5415 QTY. 20 Total = 20 K 5.6 SPRAY Pendent ORIF. FIN. White TEMP. 155°F MFR./MODEL G4A Concealed APPROVAL: City of Tukwila CONT. NO.: KS0354 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE: 06/19/08 t Western States Fire Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN / DALLAS / DECATUR / DENVER !DULUTH/HOUSTON/IWISAS CITY LAS VEGAS /MRIEAPOUS /PHOENIX/PORTLAND/ RAPIC CITY/ST. PAUL/ SALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Fossil 846 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYETEM SHEET FP -1 OF 1 SHEET INDEX SHEET \UM3ER SHEET TITLE FOSSIL FIRE ALARM SYSTEM TUKWILA, WASHINGTON FA -01 SYSTEM I N FO R v1ATI O N FA -02 TYPICAL DETAILS - WIRI\ G A\D NOUNTI\G FA -03 FIRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (CE\ERAL), MISER, SITE PLA WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2' 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL. PREPROGRAMMED WITH DEVICES ADDRESS. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL DE MOUNTED AT 48" A,F.r. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ,ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM. (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED 23. QUANTITY 2 1 1 1 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT • MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD -Sq LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP IN/ 1G RING CEILING DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING 111C FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT YC B AWP MR ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD a MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. e r• F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX A.F.F. ABOVE FINISHED FLOOR F.B.O. N/A F.B.❑.� _;: N/A VERIFY' IN FIELD :,N/A N/A F.B.❑, FURNISHED BY OTHERS N/A N/A NOT APPLICABLE N/A U.O.N. UNLESS OTHERWISE NOTED N/A WP WEATHERPROOF DEVICE N/A RED AS BUILT ADD OR CHANGE N/A Without OPmments As Noted In Red Per I he Att hed Letter N/A N/A _ N/A i nese plans have been reviewed by The Tukwila Fire Prevention bureau for conformance with current citm/A dards. Acceptance is�,!i act to errors and omissions which do not authorize violations, of adopted standards and oralnancesNRae responsibility for tfte/A at2:iacy of design rests tofay ly with the designer. Additions, deletions or revisions 1n these drawings atter Ids date will void this.acceR�tace and will require aN/A &i r mittal of revised dravYitf s for subsequent approval. GREEN BLUE AS BUILT REMOVE AS BUILT NOTES TO CAD N/A N/A i -mal acceptance is subjec pljetd test and inspectit ' y TiV�ukwila Fire Prevention Bureau. r o od N/A TUKWILA FIRE DEPART;i:..41 Please call: 575-4407 and give this job 62 and exact address for shuts down or restoration approval, NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to.the Inspector prior to tO 0' 0' 0' co N .0 c CV X RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE to 0 0 0 12 (CCC« co co J' - J 0) wFE la z �o CPet w O S E< L1.. Q W CC U(?)LL 07, CO F- commencement of Acceptanze Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re inspection Fee and termination of the testing. PAID JUN 1'02008 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Z 0 F 0 z /SCALE: 1 /8"=1 ' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -01 j THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR !STRIATION REQUIREMENT LABEL SC LE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL ❑R+ PREVIOUS ADDRESSABLE DEVIL DUCT DETECTOR LOCATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 rr) O -2 �r- HTRI—R OSTATUS LED 0 N.O. O COM O N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L NOTE 11 VOLTAGE MAX, - CURRENT MAX, - CONT, RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING \ TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR MUSIC 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE 1(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS (4.OA @ 125VAC) (4.OA e 3OVDC) 27 VDC 3.5 PIA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. 0 TB1 006)6)6)0 123456 HCP TB2 � m� 6 54 3 2 1 END OF LINE DEVICE (3.6K 1/4W) O SUPERVISED / SWITCH GROUND NOTE: 0 HTRI—D OSTATUS LED co 0 CD 0 r NOT USED 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC maim T T T O PAD -3 0 oo� INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 2 NAC -3 NAC -2 2 NAC -1 END OF LINE DEVICE 3.6K 1/4W) UPERVISED SWITCH ( NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) FROM-FACP (VOICE CIRCUIT) ('V' CABLE) 470 OHMS EOL TEM -1 0 dch� 0:0 0 O :1:-2:2-:4:1 IINC TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL NUE () H STROBE SPEAKER (STROBE) EARTH GROUND 0 ->.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE (S ) STROBE SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 80" A.F.F. 0 0 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERtTEMPER/OWE: +32"F ' TO 100' F IT HUMIDITY: C) % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --,, �► FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) >-- DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE-(— > (-) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT T BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX • MOUNTED ON \ CEILING FLEX \ JUNCTION BOX MOUNTED AGAINST CEILING SUI'PUR I 0 0 ; TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO \OT INSTA_L ADDRESSABLE N DEVICES UNTI_ PREPROGRAMVED W DEVICES ADDRESS. OTDATNG TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved -U. rr) 00 O` O O' CD N \O L_ Ln LC) N N 'O CD • J UJ F— RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE 6/05/08 o <CC« 0 z_ z 3 0 0 c OTO W�0 z Z .. EE co cc ie..q) O S'< W o CC w LL CO s (f) co I --- SCALE: 1/8" = 1 ' W. a -J 0 0 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: SHEET FA -02 EOL—S1 20.19V ca of- Fit /1 FACP EX FA—BOX hN�1+HR�NM Xk(i h'jh1{d1;�X li„ NORTH. FOSSIL WESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG \ OTIES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VCNILLAT❑R FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO- INSTALL ADDRESSABLE 1NIT DEVICES JTIL PREPROGRAMN-D W DEVICES ADDRESS. ATI\G TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved r 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE co 0 0 to 19 «a« CO CO J '- J 00 W �o UJ 0 C oc • w 0 S'< ▪ Q W a- F - con SCALE : 1/8"=1' DRAWN BY: I -ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: `20B NUMBER: r SHEET FA -03 J.L.I Lu 1 5 1 5 0,1 11 0 LiJ :5 5 1 470 NORTH !11FAMILY MEN VI/1,1 CORDON'S E. WE 1.1: S 3 ,t -\`..3K I IN R 0 E3 BINS P11 0 FOSSIL WESTFIELD SOUTHCENTER MALL SCALE 1/374 I I 0 a: < . 1 K I TS C, AMER 510 IF -1 ERH COD MA TERN PIERCING PAGODA 1,.1 [)3 SP S I N Tr-AS1-1 0 BANK TH E KIDS FOOT.L.00KE:R LU.. E 1'14501 )CL- 1 'I 2101 I1.1;') -1" LiJ C) 4. LL SYSTEM CALCULATIONS SPR L.L.1 a. K1: 0 0.„ [12.30 I 2151 112:20j ........ 4201 1 1410 r: EX L. BATTERY SIZING CALCULATION FOSSIL FOSSIL FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: WESTFIELD SOUTHCENTER MALL Panel: FOSSIL Wire Resistance 1.62' Date: June 6,2008 CURRENT TOTAL= 337 Current Load: Standby: Alarm: Current Load: Standby: Alarm: QTY Device Type Alarm Current ._. Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC ©15CD 64 0 Device Type Qty Amps Total Amps Total SET -MC @30CD Device Type 98 Qty Amps Total Amps Total HFP-11 SET -MC @75CD 175 0.0022 0.0022 0.0023 Total Device Load, Amps (1) 0.34 o SET -MC @110CD 233 0 AD2-P 1 0.0635 0.0635 0.064 0.064 318 Main System Board 1 0.03 0.03 0.030 0.030 0 HTR -R 445 2 0.009600 0.0096 0.021 0.042 SET -MC ©15CD 0 SET -HMC @135CD 318 0 0.064 HTRI-D EOL Voltage 0.001600 0 0.0035 445 0 SET -MC @30CD 1 (20.4 - E) 0.098 0.098 64 ICP -B6 0.005 0 SET -MC @75CD 98 1 0.175 0.175 0 SET-MC-CW©110CD 233 0 337 12 191 20.19145092L 337 SET -MC @110CD DEVICES= 3 TOTAL m A= 0.233 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL SET-HMC-C@115CD Panel: FOSSIL 0.318 Date: June 6, 2008 CURRENT TOTAL= 3.6 SET-HMC-C©135CD CIRCUIT: SPEAKER CIRCUIT 0.318 QTY 0.0731 Amps 0.106 Amps SET-HMC-C@185CD Voltage at EOL Circuit Total 0.445 70.7V1/8 1.8 3.6 Total Wire Resistance ( R ZR -MC ©15CD 0 0 0 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Total Device Load Amps (I) 0.00 0.098 0 0 (Total Cct Load) HCP 0 0 0.0015 Alarm Current Load: ( E 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0 0.03 Amps 0.303 Amps 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 DEVICES= 2 TOTAL m A= 3.6 14 191 20.39645198 3.6 Alarm Current Load: 0.303 Amps For 5 Minutes= 0.025 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 0.932 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.932 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION TEL. (206) 622-654.5 Cf) z 0 (1) w LU LU LLJ z DESCRIPTION SHOP DRAWINGS ILI 0 co 0 If) 0 (.0 << CO CO 0 CO cf) E Eft ---1 1-0 ev, 0 frE- w (7) 1) w (f) M 0 0 mg LL< (r) [kJ (90) z co- coD 0 _J citC 0 1.1.1 (f) ›- C/) 'ALE: 1/8"=1' "*.\ DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION ,J.OB NUMBER: F SHEETA-04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: FOSSIL Wire Resistance 1.62' Date: June 6,2008 CURRENT TOTAL= 337 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0 SET -MC ©15CD 64 0 Total Wire Resistance ( R ) 0.62 1 SET -MC @30CD 98 98 ( WL * 2 ) * (R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (1) 0.34 o SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.21 0 SET-HMC-C@177CD 445 o (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.19 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CW©110CD 233 0 337 12 191 20.19145092L 337 DEVICES= 3 TOTAL m A= Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: FOSSIL Wire Resistance 2 11 Date: June 6, 2008 CURRENT TOTAL= 3.6 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6 Total Wire Resistance ( R 0.99 0 0 0 0 0 0 Total Device Load Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E ) 0.00 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.40 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 2 TOTAL m A= 3.6 14 191 20.39645198 3.6 TEL. (206) 622-654.5 Cf) z 0 (1) w LU LU LLJ z DESCRIPTION SHOP DRAWINGS ILI 0 co 0 If) 0 (.0 << CO CO 0 CO cf) E Eft ---1 1-0 ev, 0 frE- w (7) 1) w (f) M 0 0 mg LL< (r) [kJ (90) z co- coD 0 _J citC 0 1.1.1 (f) ›- C/) 'ALE: 1/8"=1' "*.\ DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VOLTAGE DROP CALCULATION ,J.OB NUMBER: F SHEETA-04 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Fossil General Notes VICINITY MAP (Suite# 846) SCALE: NTS 1. Western States Fire Protection to add new pendent heads new upright heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not des)finned for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. Zone T-3 WEST RISER DETAIL, HYDRAULIC REFERENCE ONLY NOT TO SCALE Ordinary Group II.0.20g,pm/ft2 for 969,00it2 Existing 4" Main--- 4 --•—Existing 4" Main • ❑ Without Comments ❑ As Noted in Red Per The. tVoh=d 1 { t:er Inesepkn hV :1, I Prevention -:,,,,...;-=_ '-.; ._. standard_;.... omissions v ,FI dequacy ddit.l!ion:i. tip= da`2 ,uhrIt: tl Cit,' S., r:er. -Lt n i SCC CI I C i`. : ; ;' :>t c✓ ICS inspection by lip Tukwila Fire P;;:•.-=:;rl,;ci; :urcau. Date: S– � By: FIRE SPRINKLER SYETEM 11811=1-0" 1 3 5 7 9 11 ----TUKWILA FIRE DEPARTM .N1 Please call: 575.4407 and give this job No. 08s 7(9`1 and exact address for shut- down or reyt;,ration approval. N SCE TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE LEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE /////////////,IV/ FIG.909 SWIVEL SWAY BRACE FITTING BRACE PIPE 918' KWIK BOLT (2 IW EMBED LENGTH) F)G.100) �'- "FAST CAMP' SWAY BRACE ATTACHMENT LINE PIPE LATERAL LiNE RESTRAINTS NON -THREADED BRACE PIPE FIG -4A PIPE CLAMP FOR SWAY BRACE 6 LATERAL BRANCHLINE RESTRAINT 918' KWIK BOLT (2 114" EMBED LENGTH) 1 1 NON -THREADED BRACE PIPE LATER A T , BRANCHLINE J E RESTRAINT NOT TO SCALE Fossil Remote Area: Retail # 846 Weld stamps must b inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. CALCULATION DESIGN CRITERIA STANDARD NFPA #13-2007 OCCUPANCY cLAss ORD HAZARD 11 MAX. COVERAGE per HEAD 130 DENsrn' .20 GPM i Ft for 969.99 SPRINKLER Reliable Model G4A FP Ft ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 RESIDUAL 20 FLOW 10900 PSi PS! GPM AT BASE OF RISER. SYSTEM REQUIRES: 289.39 GPM @ 32.10 PSI • At time of Design 12'-0" CLG :37.0%AREA REDUCTION Hanger No. 07C HILTI Kwik Bolt III HILTIKwY Bolt II Dn7ted Anchor / i Rod Coupling —� Ag Thread Rod _~= Cut Rod Lgth Rounded to Nearest Inch q. Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plart Hanger Number and 'A' Dimension HANGER DETAIL NOT TO SCALE VICINITY MAP DETAIL NOT TO SCALE PA 2008 %10 Dosto Tukwila Fire rC77/.s"--- t/3 0 LL w z 0 Adam Kantner 0_ 0 Royal Seal Construction CONTRACTOR SYMBOL LEGEND REVISIONS 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT DESCRIPTION SYM. SIN QTY. R5415 R3615 Sprinkler Legend APPROVAL City of Tukwila SPRAY ORIF. FIN. TEMP. Pendent 155°F 5.6 Upright Brass 155°F MFR./MODEL G4A Concealed Western States Fire F1 FR Brass Upright Total = 20 CONT. NO.: KS0354 DRAWN BY: Adam Kantner SPRK ON SHEET: SEE LEGEND SPRK ON JOB: DATE 05/01/08 Protection Company 7102 180th AVE NE, STE A-105 - REDMOND, WA - 98052 Lic. # WESTESF1cSQF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIRI/DALLAS / DECATUR /DENVER /DULUTH/HOUSrON/KANSAS CITY LAS VEGAS /1.1I1e APOUS/PHOENUVPORTLANDIRAPID CITY/ST. PALL/SALT IA10=CITY/SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Fossil 846 Southcentner Mall Tukwila ,Wa 98188 FIRE SPRINKLER SYETEM SHEET FP -1 OF 1