PP - 856 SOUTHCENTER MALL - TEAVANA - PERMITS AND PLANS
856 SOUTHCENTER MALL ASSOCIATED PERMITS 15-F-153 08-F-286 15-S-152 08-S-347 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Teavana 856 Southcenter Mall Permit No.: 15-S-152 Date: September 28, 2015 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. f • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. 4 ittN/ SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: e.5in S hce 1 /er malt Suite Number: 11537 Floor: Tenant Name: -•ea V J'l Ol. New Tenant? ❑ - Yes ❑ - No Property Owner's Name: w?Sk leka. % r1(190101+ 6P -cup Mailing Address: CONTACT PERSON -if there are questions about the submittal. Name: Company Name: Mailing' Address: E-mail Address: City State Zip Day Telephone: Lies' y g 1-74069 C-stmoY t-ek-\t 1, Inc. 'PO x 1211 Greek, lAak '8o g2. City 1 StaZip Fax Number: � ' j/'.4149c- Total number of new/relocated devices or sprinkler heads: `7 Valuation of Project (contractor's bid price): $ 9X. CC) PVIA Ci) / R&/ a+e\ C73, Scope of Work (please provide detailed information): ?to#L))_?-.46161 PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. , I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Print Name: Plan Permit App.doc 611/.0-"/". dats/LRObmcso9 1/2/13 Day Telephone: Date: 93/S TFD FP Form 8 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: 856 Southcenter Mall, Tukwila, WA 98188 Suite Number: 920247-0010 Floor: Tenant Name: Teavana New Tenant? 0 - Yes ❑ - No Property Owner's Name: Westfield Property Tax Dept. Mailing Address: same as site address City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 Company Name: Guardian Security Systems Mailing Address:1743 First Ave South, Seattle, WA 98134 E-mail Address: kveliz@guardiansecurity.com Total number of new/relocated devices or sprinkler heads: 6 City State Zip Fax Number: 206.374.2852 Valuation of Project (contractor's bid price): $ 3,800. Scope of Work (please provide detailed information): Add 6 devices to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 NER OR AUTHORIZE AGENT: ii r Signature: ` Date: 1 t Print Name: Karina Veliz �-� Day Telephone: 206.349.5889 Plan Permit App doe 1/2/13 TFD FP Form 8 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Teavana 856 Southcenter Mall Permit No.: 08-S-347 Date: June 20, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. GUARDIAN SECURITY Customer LIFE AND Teavana 856 SOUTHCENTER MALL IKWILA, WA 98188 Project Teavana Project # PROPERTY PROTECTION List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: June 5, 2008 �y. Item Qty. Manuf. 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) , 18) ,19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) - •48) 49) i 50) Model Description Unit Pri Total Price Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard • rif8'49""A!F STOCKROOM ®12'-O" AFF RETAIL • t41 REFLECTED CEILING PLAN Scale: 3/8" = ID/ STOREFRONT. 5IGNA6E. gII•-o-Per - 61b17 -67r -AFF O Without Comments O _As Noted in Rei 12; Per The Attached Letter - -,Ticse plans have been reviewed by The Tukwila Fire cvention Bureau for conformance with current City- ndards. Acceptance is :subject to errors and nissions whlch.do no .3uihorize violations of adopted . n-1{.lards and ordinances: The responsibilliy' for the .� d quacy of design rest -tetany' with the designer. Additions, deletions or revisions tothese drawing's after this date Mil void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: - 1 'S By: sI.1 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/8' ALL THREAD. ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS . Design per NFPA 13, Ordinary Hazard Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 1— Add Reliable Model G56 Standard Response 165° Concealed White Pendent 1/2 x 1/2 o 7 Relocate Reliable Model G56 Standard Response 165° Concealed White Pendents 1/2 x 1/2 o 1 — Plug existing • FlexHeadSprinkler Drop . TKWIL; FIRE DEPARTME,N T ''• sssa call 2G5-.5754;107 arid dive thin Fire Perini No. /S: sa- E;nd exact t z .: es ibr shut- down hutdown or 11.1f -fo- approval. y� Cotrugated stainless s . , , , , feel hose with stainless steel brai ;� : • available In 2', 3',4',5' & 6' Iegnths . • • Multi -Port Bracket • I 11, next/EAD - INOU51RIE5 • Adjustable Hub • • • • Flexheadomme'rcial Ceiling Unit T -Bar Ceiling Installation Model #2024,036,2048,060,2072 VICINITY MAP its CERTIFICATE OMP STATE FIRE PROTECTION SPRINKLER S John J. Abel 9760.0591 -CQ Level ro Flre Protection, Inc. N ,..LL TEAVA"A SPACE 61155 SO9 SO. FT CROWN FIRE: PROTECTION - INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 856 Southcenter Mall. Space #1155 Tukwila, WA 98188 DATE: q .21.15 DRAWN: 66- SCALE: • 3' 5 a Pp SEP "TUKWIL 1. 0 -f 2015 A FIRE SHEET NUMBER FA -01 SHEET TITLE SYSTEM INFORMATION FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON FA -02 TYPICAL WIRING AND MOUNTING DETAILS FA -03 SYSTEM FA -04 CALCULATIONS AND SINGLE LINE DIAGRAM FRE ALARM SYSTEM PLA\ SHEET INDEX `ice Without Comments O As Noted in Regis O Per The Attached Letter Thee plans have been reviewed by The Tukwila Fire revel tion Bureau for conformance with current City .. _.nt aids. Acceptance is subject to errors and r�isslons which do not authorize violations of adopted EilOards and ordinances. The responsibility for the quacy or design rests totally with the desl jne.r. .;dditionS, deletions or revisions to these drawinci s after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: /— $' „1I T =6 vIL FIRE D'EPAR`T )-Tar I- LcY2: "', call 2005-575-4407 End eivQ this Fire Permit Noe :Ind exact zzdcbess for shut- down or r;sorLan approval. NOTICE .A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and O: rection :cyst -.ms. Failure of test will result in a Re -inspection Fee and termination of the testing D U LE AND CO \ D U IT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LiNE-ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART • NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1 3. 4. 5. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7 WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CA-ALOG CUT . SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10 THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALAFM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICA-ED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11 ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN—UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16 WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN FULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17 ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 181 ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19 20 21 22 23 .j THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT -T+W OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI—CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX 1 1 1 3 SYMBOL DESCRIPTION BPS ®D REMOTE BOOSTER POWER SUPPLY (EXISTING) DUCT DETECTOR MODEL PAD -3 FDBZ492—HR W/ HFP-11 DET. MANUFACTURER BACKBOX SIEMENS SIEMENS MOUNTING HEIGHT PAD-3—ENCL 66" A.F.F. TO TOP DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1—GANG BOX VERIFY IN FIELD HT -R INTERFACE MODULE HTRI—R WITH RELAY SIEMENS 4S BOX VERIFY IN FIELD FIRE ALARM STROBE ZR—MC—CW SIEMENS 4S BOX CEILING Di FIRE ALARM SPEAKER STROBE SET—MC—CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXTN END—OF—LINE RESISTOR A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND \y NORDSTROM 3 LEVELS 171.275sf LESPRESSO !'#t„�T QIX TEAVANA #856 / SPACE #1155 H AVW macys 4 LE•.'ELS 253.407s€ �E 38 PRC&ALA EL 1 9)099 ilh09A_ i -c Ni SOP S£+R TO 00 0001) 2. _ sx a crw v,ms DATEx JO a Ix A� R EMI MISER PATO PETAL .ar—SiNMNIT PAM RET/L FL FETAL ROE.' PESTNLIAAT ATM Pfl MOClFIlHAS RESTNPNRA TPECEALAMA L_ EXIST II, JCPenney 3 LRS 3 LEVELS 27 O,4SBsf PAID SEP 21 2015 TUKWILA FIRE 075 0' RELEASE/REVISIONS REV. BY: 0 0 DESCRIPTION SHOP DRAWINGS DATE co Z 0) 0 Lc) T z o L0 w;‘,--0- o �z • Q -o Z 2 Jo WQz > ?�_ Q to W %C ) W cc z's w-1co U) co 1.1.1 0 0 z N } N �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN ce 0'20.0. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved .0B NUMBER:13781-1} SHEET FA-Ol J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60HZ DEDICATED EMERGENCY ll FROM EXISTING MAIN FACP C CABLE C' CABLE 0 r LL 0000 U II 0 PAD -3 00 NPUT INPUT TROUBLE NAC, NAC2 NAC3 NAC4 AUX 1+1- 1 2+2- 2 NC C NO + - + - + - + - + - O .54 3.6k EOL 0 0 (-) (+) (-) (+) NAC S4 NAC S3 , j NAC S2 j NAC S1 EXISTING POWER SUPPLY WIRING DETAIL COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR I PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 M 0 GROUND - LCA O 0 HARD LID CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE & STROBE CEILING MOUNTING DETAIL FROM REMO E POWER SUPLY FEED FROM EXISTING VOICE CIRCUIT (V CABLE) RETURN TO EXISTING VOICE CIRCUIT (V' CABLE) (�1 ) (-) \ STROBE SPEAKER (+) (-) n (+) \ ) STROBE 4) (- STROBE SPEAKER (+) MUSIC 4 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) HTRI-R RELAY MODULE BACKGROUND MUSIC SHUTDOWN WIRING DETAIL SPEAKER STROBES & STROBES ONLY WIRING DETAIL NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODU:T DOCUMENTATION. OPER 11N TEMPERA RE: +32' F (0' C) TO 100' F 35 C) HUMIDITY: 0-93333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --) FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )>— DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCAT1ONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR f DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL TO NEXT DEVICE OR END OF LINE > TO NEXT ADDRESSABLE DEVICE TYPICAL WIRING AND MOUNTING DETAILS FROM PREVIOUS ADDRESSABLE 2 DEVICE TBI ®00 NO COM NC TO FAN SHUTDOWN EOLR 470 SWITCH +0 INPUT LED TSM -1 0 + TO NEXT ADDRESSABLE DEVICE 0 00 HTRI-R NO ® COM ® NC ® 0 TYPICAL DUCT DETECTOR/HTRI-R MODULE/TSM-1 SWITCH WIRING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 I t TO NEXT DEVICE rg O O CADDY BAR \c SMOKE DETECTOR -----..- SUSPENDED ILLUMINATED CEILING SMOKE DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: g 0 DESCRIPTION SHOP DRAWINGS DATE 09/18/15 12 ««< (4 Z CID OWr CD Q (oZ e�<LJ4 Z w QCD z ;Li cc zs' r-- - o a= W DD LL OI -- CID OD z 0 0 zcC 3: c� z Q U _2 'GALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: \OB NUMBER:13781-I) SHEET '' FA -02 I A B C D E F G H 1 J K FIRE ALARM BOOSTER Project: TEAVANA Panel: EXISTING BPS PAD -3 Date: September 21, 2015 Module/Device POWER BOOSTER Qty SUPPLY BATTERY CALCULATION Alarm (mA) i ,":.yY44g r� .vr, e,,,,,a :"„, '.,r,; zG', ",,'. YG ,w�,:,1:,, w'rx�t4 POWER Standby (mA) SUPPLY Total Alarm (mA) #"�r,.i°• , iYm�N.M.r� ',kz� ,,nY '�:^r'mT�"i '....�W' ^. h". ,:� ':�.;�,, pf,Y.r,,,,";, v. ' ,1:1r .AI �, � :,"i"i.':mY� � '', y ; ���`d,{'•: ! r Y�,!e A' �'�'^ ° Lk'e; ' .e.,, lx�v k, G„ .�, k ', ".e ? m ;' @ is x Total Standby (mA) Power Module 1 30 30 0 30 30 0 TOTAL FIRE ALARM POWER SUPPLY 30 30 Auxiliary Device Current 0 0 Notification Appliance Load (Max. Total / mA) 0 4813 Standby: Total A = CALCULATION , 30 Total B = 4843 Total current ratings of all devices in system (line A + line B + line C) 30 4843 Total current ratings converted to amperes (line D x .001) 0.03 4.843 Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5). 24 Qty Multiply lines E and F Total Standby AH 0.72 Total Alarm sounding period in hours (5 mins+ .0833 hours) Total 0.0833 Multiply lines E and H Total Alarm AH 0.4034219 Add lines G and I Total Standby and Alarm AH 1.1234219 0.0022 Multiply line J by 1.2 (20% extra insurance to meet desired performance) 1.34810628 12-V DC BATTERY SIZE RECOMMENDED (AMPERE -HOUR) 7 Notification Appliance Circuit Detail PROJEC : TEAVANA Panel:EXISTING BPS PAD -3 POWER SUPPLY Date: September 21, 2015 Wire Resistance 2.58 CURRENT TOTAL= 4813.00 2SET-M_C-CW@l5cd ^ ET -M1 +SC -CW @30cd SET-MC-,CW@75cd ; SET -MC -CW @95cd ;SET -MC -W @15cd ZR -MC -CW @30cd 111 TOTAL mA= DEVICES 69 3131 14 283 23.54 Total Wire Resistance (R ) Total Device. Load, Amps (1) Voltage prop ( E ) TM EOL` Voltage (WL * 2) * (R/ft) (Total Cct Load) _'* R) 313 1.46 0.31 0.46 ;SET -MC -CW @15cd C -CW @30cd SET -MC -CW @75cd 200 C -CW 95cd 264 ZR -MC -CW @15cd 69 C -CW @30cd 111 TOTAL mA=: DEVICES 1500; 14 Total Wire Resistance (R) Total Device Load, Amps (1) e Drop(E) 24.00; (WL*2)*Oft); (Total. "Cct Load) (E=1*R) 1500 0.00 1.50 0.00 24.00 SET -MC -CW @15cd ; 691 0 SET -MC -CW @30cd 111 0 SET -MC -CW @75cd_; 200 0 ET=iv'{C-CW @95cci 264 0 S_ET-MWC-@110cd 233: ZR -MC -CW_ ©30cd DEVICES ..0 TOTAL mA= 15001 14 24.001 Total WireResistance (R ) Total =Device Laad, Amps (1) 'Voltage Drop ( E) EOL Voltage *2)*(Rift) 1 Cct Load) (E=1*R) E) 1500 0.00 1.50 0.00 4.00 SET -MC -CW @15cd SET -MC -CW @30cd :SET -MC -CW @75cd SET -MC -CW @95cd :SET -MC -W @110cd ZR-MC-C'W @30cd 0 DEVICES :0 2001, 264 0 0 TOTAL mA=; 1500 14 Total Wire Resistance (R ) Total Device Load, Amps (1)ry~tt Voltage Drop ( E ) EOL Voltage 24.00 L*2)*(R/ft); (Total Cct Load) (E=1*R) 24 - E) 1 1500 0.00 1.50 0.00 24.00 CALCULATIONS i,, •, ��,,, C �„ r, ,' ., ., , n>Sr r(,: "C', rA r ,� ,,,, r, d, ... „,r ., ,,,. C ., .,�`4,k.'1'„4 „,.+,n e"t'„, !, 'i,,,,, .,,,„,',� �, .„,� , � �a l,,.. ., i..l,R..t,.,, 1 Ji , '"} i�,{`.:.„,l!;, �,." !, SfxrlYK ,�l1 ,t , :rrt r; fi�' '',A..,' :. .p�gg, r .,,,,f� �.i ,,' "� "r'. ."o :,,, 5, , ', :,, � .,, '.t'.. i.. 4f. '! .»:M, :,n A, B.w, a., .'�.m � � ,,9.ra. tr, , W.N.,, �.:'. Ct ra''Un:. . .r;,°. '✓.x:,Yr " k V � w.m�. a..!S �.: "�.'.„,, Vl;n�.dxR,„,i�.. °.' ° +9 �& "; :: ' '�� 5'•D"', f 3 ',! ,�' M, K. r M Yi t r �(i ,,, m� � �a• a"k, ^k !,', ,,�„� +d r °,d'P m q xrr,k dg >£ . ,�»' Is. .,. 'x: ..xR�,n .e. 1 ,Y ,rYl a '��l,„'} 'y�R`. '"'tl,: e, k , u7 h »Y:�• �. !� � „.�f?a, '� Vdr✓, »d,l..o, ,,,. � h" � , +Y �,y J„I� ,7�.�r: �,.Y,,S,,,".r, �J�' E.}',�y,im,kM..tlr,r' r� ;hk4 irmk.w„f?'",,;k ,. „x,yy4k.� �,,0,<�„I.., ''x. ,�� ' Y„ifiS > Fr . �PA Vn.r'k,'{.M., ^w, �� 0 0'},',w' Y, V' r ��a'w' „k „���'� ,k, v ':" ,., �� � "r5ti.4p'�¢F rna.. . (."r, >�r9kI.w��S„9„, i n. Yd�m:i,g�, r � i ,":.yY44g r� .vr, e,,,,,a :"„, '.,r,; zG', ",,'. YG ,w�,:,1:,, w'rx�t4 h3.,n„'',„, rv� �.,� , ,.. ,r »: a„S�.",,, „„, '1�,v.�x,h 'io,'ip;v.,W, :9. : .',c � b� 6. � :(J .' C ��' #"�r,.i°• , iYm�N.M.r� ',kz� ,,nY '�:^r'mT�"i '....�W' ^. h". ,:� ':�.;�,, pf,Y.r,,,,";, v. ' ,1:1r .AI �, � :,"i"i.':mY� � '', y ; ���`d,{'•: ! r Y�,!e A' �'�'^ ° Lk'e; ' .e.,, lx�v k, G„ .�, k ', ".e ? m ;' @ is x Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 FDBZ492-HR 1 0.0635 0.0635 0.064 0.064 HTRI MODULE 1 0.009600 0.0096 0.021 0.021 0.0731 Amps 0.085 Amps PROJECT: Panel: Date: Notification Appliance Circuit TEAVANA EXISTING SPEAKER CIRCUIT ;September 21, 2015 Detail - VOICE Wire Resistance 2:58 CURRENT TOTAL= 899.16 SET -MC @1/4 WATT 127 SET -MC @1/2 -WATT :SET @I/it-WATT SET @1/2 -WATT. DEVICES 127 3.54; 7.08 14.141 28.29 . TOTAL mA=I 0 99.16 :! 0 1228 18.30 899.16 Total Wire Resistance (RR Total Device Load, Amps (1) IVoltage Drop (E ) EOL Voltage J(WL*2)*(R/ft) otal Cct Load) 0:90 E=1*R) 6.34 5.70 TO NEAREST EXISTING SPEAKER CIRCUIT ( TO NEAREST EXISTING POWER SUPPLY TO NEAREST EXISTING DATA LOOP ( • (EXISTING BACK -OF - THE -HOUSE J -BOX) SINGLE LINE DIAGRAM S1-2 V-2 214 TSM V-3 EOL FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTE: DUCT DETECTOR, RELAY MODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved itt 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS CC 0 Lil tri z co 111 02 0 Vc) cr D0 co >- DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: SHEET FA -03 i TO EXISTING BACK -OF -THE HOUSE JUNCTION BOX n., D -<D S,V-0 o -V L — 7 0 r0 f IJ S1-1 15cd V-1 STJCKROdOM S. •• R: TAIL S1-2 30cd N 4 V-2 r I I( I.si 15cdM 711114 V-3 EOL,1i 14i (4) ((3 /I I 1 J 1 FIRE ALARM SYSTEM PLAN FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTE: DUCT DETECTOR, RELAY MODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. 1743 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 0' 0 DESCRIPTION SHOP DRAWINGS DATE 0 co o) 0 2 «aa< T Z Co LO W Co CDZ << o Z w <Z QCf) wt Lil zI— ill 's <_ W t. u- °i– v) LO co CALE: 1/4''=1'0” DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: 13781—L) Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved \ SHEET FA -04 J 'le/x(3.100e lo ow. ,±z) sso)ppe 1.3exa pug C-LS.)-SQ‘°11 ticf onp pug Latr19-9L9 :lie° °seek' 11413;ALINVcI3C1 JJId t1ttiA)M1 'W, • - ,..1,,,VsKat...4.1,14.folk•-•,,,,,,K nsrt c ) fr 'neninq uoot2nAoid art.:1 nmni oqi - - • ! Ar. uoi.,)x1,..til 1^,1.1 41,;;I pizilj a; 1.;:porAnc .s!1'30u-.71(1%-noc ieulj • . • 41 N i JJ Lfl. :AG . 80_ ot,_.) - 0 •GEIL111-Co1 A.F.E 17 -Ca 130E) *leAatdde sa opersapAti o 100 ou!did uidTO11/Ri tunq adtd wapq palmdsui eq MIA sduitals PPM *?. j'tidd;1.1;)11bw;cing;J0 sbuiwiip pot;!pai ;o telliwqnsai i;rhjIvtA OU pt0A 111N\ ;:5ep J.:vg? sf.:0..1!Kc0.Ip osoLn (4 SiJa!SiAi JO StiOnOpp 'suopppv ..p3u64p ,,411 i1}1.f\ Ailr,401 J ti6r,lep la 104-3111?epe Fy:4 ...:04AirocpstJaciF.;@; pue s)leDuels. pidope 1,0 st,JogcnA -.-D7pr,)qine wi_t 00 t43I.I.IN\ SUOISSII110 • pue SJOJJ9o V.:::,7-,!•,1?1".sippues AVOlu;).nr);) t.wm 3U1W0OOO Jo E1112 tiOgtJeAald eiLd 0.1.4 I *Aq paNn.c3vv;_41 ueeq IAEq sued SG I • Jawri -pew) CALL Jed pJ UI P-aioN 175V swoultiloolnqqw• ==c! r.:.13 •=1"' a 1 31-4" r.104 Or& 4.4 1.0.1,10 .4 lir oif 121-721,1 .121_92111 SPACE #1155 REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND: REUABLE MOD G4A CONCEALED SSP REUABLE MOD G4A CONCEALED SSP RELIABLE MOD F1FR REC SSP APPROVALS BY: SYMBOL S/N ORIFICE 1/2' 1/2' .1/2' NPT K -MCT. 1/2' 5.6 1/T 5.6 1/T 5.6 THICKNESS OF CONCRETE VARIES A 1. A 3/8.X 2-3/4' KWIK BOLI, • DA 3/8ROD CPLG. LAS RECCOMENDED BY MFG. CUT3/8' A.T.R. (PER PLAN) RING HANGER TYPICAL ARMOVER TO NEW SPRINKLER HEAD ARGCO #38 OFFSET WHERE LENGTH OF ALL THREAD ROD. EXCEEDS V-10" ADD SECOND RESTRAINT HIAD FINISH BRASS BRASS CHR 3/8 X 3-1/2 LAG SCREW FOR WOOD 3/8" KWIK BOLT FOR CONCRETE 1/4X 1 TK FOR BARIOIST OR STEEL BEAM 3/8"x1-10 ALL THREAD ROD. MAX PER SINGLE RESTRAINT HANGER RING LINE RESTRAINT DETAIL (UP TO 2" PIPE) PLATE FINISH WHT BLACK CHR TOTAL SPRINKLERS THIS SHEET NOTE: 1) SPACE WITH IN 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(2007 ed.) SECTIONS 9.3.5.8.8, • TABLE 9.3.5.8.8(c) AND 9.3.6-RESTAINT OF BRANCH LINES FOR 1* TO 4" PIPE AU. LOCATIONS (U.N.0.) (1) 318' x 2-3/4" HILTI QWIK BOLT (1) 3/8' A.T.R. x (SEE PLAN) (1) 3/8. ROD C'LG. • (1) PIPE HANGER RING #13 HANGER DETAIL • FIG.. 65 BEAM CLAMP FIG. 69 RETAINING STRAP JA LOCK NUT REQ'D VIEW A -A FIG. 100 ALL THREAD ROD FIG. 200 AD1USTABLE RING HANGER • BOTTOM BEAM CLAMP, ROD, AND RING ('E3 #92 HANGER DETAIL N.T\, • FILE COPY • GENER NOTES* I . RETAIL AREAS ARE DESIGNED IN. ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13 ORDINARY HAZARD GROUP 2 MAX SPACING 130 5Q. T. 2. COSCO POINT OF CONNECTION 15 AT EXIST BUILDING SHELL SYSTEM 4" MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS 4. ALL WIRING BY OTHER. 5. ALL MATERIAL15 NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE FIRE DEPT. G. OWNERIS RESPONSIBLE TO ASSURE THAT STRUCTURE A5 IT: 15 SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIR E SPRINKLER PIPING LOADS. 7. OWNERI5 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER Of TILE" HEAD PLACEMENT. 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO. 10. OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS Of N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD11AS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED T1-115 SYSTEM 15 BEST QUALIFIED TO PROVID• E THE ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF T1115 SYSTEM(S). ****** FIELD NOTES ****** 1) THREADED PIPE FROM I " THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO BE 5C1-1.10 (IMPORT). 3) ALL GROOVED COUPLING ARE TO 13E "RIGID" TYPE U.N.O. (IMPORT). • 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES EXISTING PIPE 5 NEW PIPE EXISTING HEAD NEWHEAD Wm?. 165 165 155 a •.o000.. COSCO • *0 00 0* • ' • 0 0 0 0 • ' Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE• 15000 Woodinville -Redmond Rd NELiCenSe No: . Woodinville, Washington 98072 COSCOFP1 IONM call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscofire.com PROEM PERMIT # D08-031 TEAVANA 856 SOUTHCENTER MALL SPACE # 1155 TUKWILA, WA 98188 iD JUN 20 2008 SCALE:1/4=1?-0 Tukwila Fire .1(2-ozc 47 .5i' DMIRACT Nit MAZ BUILDERS 1146 E. HOME ROAD • SPRINGFIELD, OH 45503 BILL 760-646-3717 DIMING TITLE • FIRE SPRINKLER TENANT IMPROVEMENT IMTE : 06/18/08 SCALE: 114=1-0" DRAM Br: • BRIAN SCHULZE 53S-7963 MEET RO. 1 OF 1 FILE COPY TEAVANA FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UVI3ER SHEET TITLE FA -01 SYSTEM I \FORVV ATI O \ FA -02 TYPICAL DETAILS - WIRI\G A\D N OU\TI\G FA -03 FRE ALARM SYSTEIV FLOOR PLA\ FA -04 SYSTEM CALCULATIONS GE\EAL), RISER, SITE PLA\ 0 , ',thota't i_.:.ro ,:'.'� 1 nese pl;".ric,;;t;,b:. `.i7.:}i..•..,•. .;t:. ,;:2. h) ..',.,. Fire Prevei:,t;cy;l !a ..21.. .:;r . .:,'.d,•.: .k:. i. ci`.d s:L_'nd:?:1d::.. . . r.._.. ,c,t. l: , .,.,, ., ,. ., ORSi>., ,_r.i:i'.i:tr'1: 1,.U:) ;1;,1 .. .,•.'4,: , 1,. ....SiC,cAC(1 F 7tart,i_.4'.:', S4S".',1 :'r :,.,.':•.1,. 1'co il'::;.',%;,'.,,� ..>.�,. 9'). tl;',', adeq{u,<"':7 r.,t ,::;..,,: THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIL 0 DUCT DETECTOR L❑CATION 0 END OF LINE DEVICE(3.6K 1/4W) m SUPERVISED SWITCH GROUND r) 0 HTRI—R STATUS LED CO 0 N.O. 0 COM 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 11 VOLTAGE MAX. - CURRENT MAX, - CONT, RES. MAX. - MAX. CABLE LENGTH - C CLINE TO LINE) - C CLINE TO SHIELD) - MAX, LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING—\ TUBE \ AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 1L) -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE {(+j FROM XLS CONTROL PANEL OR �(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS <4.OA @ 125VAC) <4.OA @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. + TB 1 5 5 0 0 0 0 123456 HCP TB2 +� m��_ m 654321 0 END OF LINE DEVICE (3.6K 1/4W) o v� 37) ; SUPERVISED ; SWITCH GROUND CV O O HTRI—D OSTATUS LED Do 0 0 NOT USED 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL yea SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 1310 _L� �� T T T 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 0 $ 31 33• 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3,6K 1/4W) 2 NAC -4 NAC -3 NAC -2 NAC -1 SUPERVISED SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP.! 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS IW EOL T M-1 Q r z LJ1 gc0 Fs. MO 0 S 0 GC >I TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP <V❑ICE CIRCUIT) ('V' CABLE) SCALE: NONE Y EARTH GROUND ..(+)TO NEXT DEVICE OR } STOP IF LAST DEVICE () TROBE) SPEAKER 0 CD ( STROBE-) (S ) STROBE SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R E 80" A.F.F. ti 4S DEEP BOX W/ 1-1/2" ING (PTEAKERNSTROBE) 14S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER�11N TEMPERATU +32' F (0' C TO 100' F (3E: 38' C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -)► FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN (-) > it DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW > (-) DATA OUT (+) DATA OUT TO NEXT DEVICE HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKEWSTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON \ CEILING FLEX \ 0 0 ; I TO NEXT DEVICE / / / / JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 r� CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO \OT I\ST _L ADDRESSABLE IN DEVICES vNTI- RRERROGRAV DEVICES ADD T AT MED W RESS. T \G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved cm 6'3 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 o <<<<< OD OD --1;40 (cc z 111 C) Wtr C Zi CCVG0 W oic op co OD I - SCALE: NOT TO SCALE DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: SHEET FA -022 EOL—S1 20.30V NORTH TEAVANA WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO INSTALL. ADDRESSABLE IN T DEVICES J\TIL PREPROGRAMMED W DEVICES ADDS=SS. I N G H Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved riZ ILI 112 ItZ c70- 0' Z O (f) LLT J F— F— W U) O U) W F— U) iv") FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: Z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 <«« co co J r J 0 2 Z <Wo �Z it;Cg=Q WQco �� I- N uJ SCALE: 1 /8" = 1'0" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:06/04/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: ( FA -O3 l LL LIT H A \ty A I I .r-.. LE R5 ; / R BASK 11"i C)313 I N P SUNGLASS U „AP .ATE K I TS 0A\/1 ER A M TH ER [-I 00E1 /1A TE PIERCING PAGODA LIDS 31.1/EC". IN TRASH II C I\ L 1150 1115`:-• rr 1440 NORTH KIDS 700TI OC;KFR 11430 1200 Li 12;._ 12101 114.251 L Li. LU rs, SPR L_Tt Lti cri L d 230 TEAVANA WESTFIELD SOUTHCENTER MALL SCALE 113214 r • ) 0 LL 12351 CI) IDOSTINC FOOTLOCKER F;bANCY .... EX D,I 21 OtEINIff BATTERY SIZING CALCULATION SYSTEM CALCULATIONS Notification Appliance Circuit Detail DESCRIPTION WESTFIELD SOUTHCENTER MALL TEAVANA TEAVANA F -DATE . FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Wire Resistance 1.62, 2 Panel: June 4 2008 CURRENT TOTAL= 162 Date: CIRCUIT: S1 Current Load: Standby: Alarm: Current Load: Alarm Current Alarm Total Wire Size Standby: Alarm: Circuit Total QTY SET -MC @15CD 64 64 Total Wire Resistance ( R ) 0.62 1 1 Device Type 98 Qty Amps Total Amps Total Device Type ( WL * 2) * (R/ft) Qty Amps SET -MC @75CD Total Amps Total HFP-11 0.0022 0.0022 0.0023 SET -MC @110CD 233 - 0 (Total Cct Load) 0 AD2-P 318 1 0.0635 0.0635 0.064 0.064 Main System Board 0.10 1 0.03 445 0.03 0.030 0.030 HTR -R I 2 0.009600 0.0096 0.021 0.042 - SET -MC @15CD 1 EOL Voltage 0.064 0.064 SET -HMC @185CD HTRI-D t 0.001600 0.0035 (20.4 - E) SET -MC @30CD 0 1 64 0 0.098 0.098 ICP -B6 0.005 Z-MC@30CD 98 0 SET -MC @75CD 0.175 SET-MC-CW@110CD 233 0 _ SET -MC @110CD 2 TOTAL m A= 162 12 191 0.233 SET-HMC-C@115CD Notification Appliance Circuit Detail 0.318 WESTFIELD SOUTHCENTER MALL 0.0731 Amps 0.106 Amps SET-HMC-C@135CD June 4, 2008 CURRENT TOTAL= 3.6 0.318 Date: SET-HMC-C@185CD SPEAKER CIRCUIT 0.445 QTY Device Type ZR -MC @15CD Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0.064 Standby Current Load: Alarm Current Load: 70.7V1/8 0.0731 0.106 Amps Amps For 24 Hours = For 5 Minutes= 1.754 0.009 Amp -hours Amp -hours ZR -MC ©30CD Total Wire Resistance ( R ) 0.99 0 0.098 0 0 HCP ( WL* 2 )*(R/ft) 0.0015 00 0Total 0.03 Amps 0.192 Amps 0 0 0 (Total Cct Load) 0 25% Derating= 2.204 Amp -hours Standby Current Load: - 0.03 Amps Voltage Drop For 24 Hours = 0.720 Amp -hours 0 0 ---- (E= 1* R) 0 0 ,,- u- -- EOL Voltage 20.40 0 Alarm Current Load: 0.192 Amps (20.4 - E) For 5 Minutes= 0.016 Amp -hours Total System Current Load: 2.204 Amp -hours 0 0 0 DEVICES 2 TOTAL m A= 3.6 14 191 25% Derating= 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH OtEINIff BATTERY SIZING CALCULATION RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved P00' co 0\ O• c0 C\J 0 ‘0 (\.1 < < Lid _J F -- 1 -- LU (I) ui P0 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a Notification Appliance Circuit Detail DESCRIPTION WESTFIELD SOUTHCENTER MALL F -DATE PROJECT: TEAVANA Wire Resistance 1.62, 2 Panel: June 4 2008 CURRENT TOTAL= 162 Date: CIRCUIT: S1 Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage_at EOL Circuit Total QTY SET -MC @15CD 64 64 Total Wire Resistance ( R ) 0.62 1 1 SET -MC @30CD 98 98 ( WL * 2) * (R/ft) 0 SET -MC @75CD 175, ATotal Device Load, AmpsQ) 0.16 0 SET -MC @110CD 233 - 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.10 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.30 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL m A= 162 12 191 20.299747921 162 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL PROJECT: Panel: TEAVANA Wire Resistance 2.58 June 4, 2008 CURRENT TOTAL= 3.6 Date: CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6___ Total Wire Resistance ( R ) 0.99 0 0 0 ( WL* 2 )*(R/ft) 00 0Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 -7-- 0 - - Voltage Drop ( E) 0.00 0 0 0 ---- (E= 1* R) 0 0 ,,- u- -- EOL Voltage 20.40 0 (20.4 - E) 0 0 0 0 DEVICES 2 TOTAL m A= 3.6 14 191 20.396451981 3.6 RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved P00' co 0\ O• c0 C\J 0 ‘0 (\.1 < < Lid _J F -- 1 -- LU (I) ui P0 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS F -DATE co 0 ...., 0 ..., co 0 2 <1<<<< 0 SCALE: AS NOTED DRAWN BY: I. AN DERSON DESIGNED BY: R.VEZZANI DATE:06/04/08 BACKROUND PLAN PROVIDED BY: :.10B NUMBER: C SHEET FA -04 856 SOUTHCENTER MALL ASSOCIATED PERMITS 15-F-153 08-F-286 15-S-152 08-S-347 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Teavana 856 Southcenter Mall Permit No.: 15-S-152 Date: September 28, 2015 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ` of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. f • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Flexible sprinkler hose bends shall not exceed the maximum radius permitted by the listing. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • All valves controlling the water supply for automatic sprinkler systems and waterflow switches on all sprinkler systems shall be electrically supervised. • All interior control valves shall be readily accessible, labeled and located not more than 6 ft. above the floor. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2013 Edition. 4 ittN/ SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: e.5in S hce 1 /er malt Suite Number: 11537 Floor: Tenant Name: -•ea V J'l Ol. New Tenant? ❑ - Yes ❑ - No Property Owner's Name: w?Sk leka. % r1(190101+ 6P -cup Mailing Address: CONTACT PERSON -if there are questions about the submittal. Name: Company Name: Mailing' Address: E-mail Address: City State Zip Day Telephone: Lies' y g 1-74069 C-stmoY t-ek-\t 1, Inc. 'PO x 1211 Greek, lAak '8o g2. City 1 StaZip Fax Number: � ' j/'.4149c- Total number of new/relocated devices or sprinkler heads: `7 Valuation of Project (contractor's bid price): $ 9X. CC) PVIA Ci) / R&/ a+e\ C73, Scope of Work (please provide detailed information): ?to#L))_?-.46161 PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. , I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: Print Name: Plan Permit App.doc 611/.0-"/". dats/LRObmcso9 1/2/13 Day Telephone: Date: 93/S TFD FP Form 8 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: Site Address: 856 Southcenter Mall, Tukwila, WA 98188 Suite Number: 920247-0010 Floor: Tenant Name: Teavana New Tenant? 0 - Yes ❑ - No Property Owner's Name: Westfield Property Tax Dept. Mailing Address: same as site address City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Karina Veliz Day Telephone: 206.349.5889 Company Name: Guardian Security Systems Mailing Address:1743 First Ave South, Seattle, WA 98134 E-mail Address: kveliz@guardiansecurity.com Total number of new/relocated devices or sprinkler heads: 6 City State Zip Fax Number: 206.374.2852 Valuation of Project (contractor's bid price): $ 3,800. Scope of Work (please provide detailed information): Add 6 devices to existing FACP. PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 NER OR AUTHORIZE AGENT: ii r Signature: ` Date: 1 t Print Name: Karina Veliz �-� Day Telephone: 206.349.5889 Plan Permit App doe 1/2/13 TFD FP Form 8 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Teavana 856 Southcenter Mall Permit No.: 08-S-347 Date: June 20, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. GUARDIAN SECURITY Customer LIFE AND Teavana 856 SOUTHCENTER MALL IKWILA, WA 98188 Project Teavana Project # PROPERTY PROTECTION List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: June 5, 2008 �y. Item Qty. Manuf. 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) , 18) ,19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) - •48) 49) i 50) Model Description Unit Pri Total Price Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard • rif8'49""A!F STOCKROOM ®12'-O" AFF RETAIL • t41 REFLECTED CEILING PLAN Scale: 3/8" = ID/ STOREFRONT. 5IGNA6E. gII•-o-Per - 61b17 -67r -AFF O Without Comments O _As Noted in Rei 12; Per The Attached Letter - -,Ticse plans have been reviewed by The Tukwila Fire cvention Bureau for conformance with current City- ndards. Acceptance is :subject to errors and nissions whlch.do no .3uihorize violations of adopted . n-1{.lards and ordinances: The responsibilliy' for the .� d quacy of design rest -tetany' with the designer. Additions, deletions or revisions tothese drawing's after this date Mil void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: - 1 'S By: sI.1 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/8' ALL THREAD. ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS . Design per NFPA 13, Ordinary Hazard Group 2 All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 1— Add Reliable Model G56 Standard Response 165° Concealed White Pendent 1/2 x 1/2 o 7 Relocate Reliable Model G56 Standard Response 165° Concealed White Pendents 1/2 x 1/2 o 1 — Plug existing • FlexHeadSprinkler Drop . TKWIL; FIRE DEPARTME,N T ''• sssa call 2G5-.5754;107 arid dive thin Fire Perini No. /S: sa- E;nd exact t z .: es ibr shut- down hutdown or 11.1f -fo- approval. y� Cotrugated stainless s . , , , , feel hose with stainless steel brai ;� : • available In 2', 3',4',5' & 6' Iegnths . • • Multi -Port Bracket • I 11, next/EAD - INOU51RIE5 • Adjustable Hub • • • • Flexheadomme'rcial Ceiling Unit T -Bar Ceiling Installation Model #2024,036,2048,060,2072 VICINITY MAP its CERTIFICATE OMP STATE FIRE PROTECTION SPRINKLER S John J. Abel 9760.0591 -CQ Level ro Flre Protection, Inc. N ,..LL TEAVA"A SPACE 61155 SO9 SO. FT CROWN FIRE: PROTECTION - INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 856 Southcenter Mall. Space #1155 Tukwila, WA 98188 DATE: q .21.15 DRAWN: 66- SCALE: • 3' 5 a Pp SEP "TUKWIL 1. 0 -f 2015 A FIRE SHEET NUMBER FA -01 SHEET TITLE SYSTEM INFORMATION FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON FA -02 TYPICAL WIRING AND MOUNTING DETAILS FA -03 SYSTEM FA -04 CALCULATIONS AND SINGLE LINE DIAGRAM FRE ALARM SYSTEM PLA\ SHEET INDEX `ice Without Comments O As Noted in Regis O Per The Attached Letter Thee plans have been reviewed by The Tukwila Fire revel tion Bureau for conformance with current City .. _.nt aids. Acceptance is subject to errors and r�isslons which do not authorize violations of adopted EilOards and ordinances. The responsibility for the quacy or design rests totally with the desl jne.r. .;dditionS, deletions or revisions to these drawinci s after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: /— $' „1I T =6 vIL FIRE D'EPAR`T )-Tar I- LcY2: "', call 2005-575-4407 End eivQ this Fire Permit Noe :Ind exact zzdcbess for shut- down or r;sorLan approval. NOTICE .A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and O: rection :cyst -.ms. Failure of test will result in a Re -inspection Fee and termination of the testing D U LE AND CO \ D U IT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LiNE-ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART • NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1 3. 4. 5. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7 WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CA-ALOG CUT . SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10 THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALAFM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICA-ED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11 ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN—UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN—UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16 WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN FULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17 ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 181 ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19 20 21 22 23 .j THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT -T+W OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI—CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX 1 1 1 3 SYMBOL DESCRIPTION BPS ®D REMOTE BOOSTER POWER SUPPLY (EXISTING) DUCT DETECTOR MODEL PAD -3 FDBZ492—HR W/ HFP-11 DET. MANUFACTURER BACKBOX SIEMENS SIEMENS MOUNTING HEIGHT PAD-3—ENCL 66" A.F.F. TO TOP DUCT HOUSING VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1—GANG BOX VERIFY IN FIELD HT -R INTERFACE MODULE HTRI—R WITH RELAY SIEMENS 4S BOX VERIFY IN FIELD FIRE ALARM STROBE ZR—MC—CW SIEMENS 4S BOX CEILING Di FIRE ALARM SPEAKER STROBE SET—MC—CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXTN END—OF—LINE RESISTOR A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND \y NORDSTROM 3 LEVELS 171.275sf LESPRESSO !'#t„�T QIX TEAVANA #856 / SPACE #1155 H AVW macys 4 LE•.'ELS 253.407s€ �E 38 PRC&ALA EL 1 9)099 ilh09A_ i -c Ni SOP S£+R TO 00 0001) 2. _ sx a crw v,ms DATEx JO a Ix A� R EMI MISER PATO PETAL .ar—SiNMNIT PAM RET/L FL FETAL ROE.' PESTNLIAAT ATM Pfl MOClFIlHAS RESTNPNRA TPECEALAMA L_ EXIST II, JCPenney 3 LRS 3 LEVELS 27 O,4SBsf PAID SEP 21 2015 TUKWILA FIRE 075 0' RELEASE/REVISIONS REV. BY: 0 0 DESCRIPTION SHOP DRAWINGS DATE co Z 0) 0 Lc) T z o L0 w;‘,--0- o �z • Q -o Z 2 Jo WQz > ?�_ Q to W %C ) W cc z's w-1co U) co 1.1.1 0 0 z N } N �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN ce 0'20.0. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved .0B NUMBER:13781-1} SHEET FA-Ol J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60HZ DEDICATED EMERGENCY ll FROM EXISTING MAIN FACP C CABLE C' CABLE 0 r LL 0000 U II 0 PAD -3 00 NPUT INPUT TROUBLE NAC, NAC2 NAC3 NAC4 AUX 1+1- 1 2+2- 2 NC C NO + - + - + - + - + - O .54 3.6k EOL 0 0 (-) (+) (-) (+) NAC S4 NAC S3 , j NAC S2 j NAC S1 EXISTING POWER SUPPLY WIRING DETAIL COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR I PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 M 0 GROUND - LCA O 0 HARD LID CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 4" SQUARE DEEP BOX WITH 1-1/2" EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE & STROBE CEILING MOUNTING DETAIL FROM REMO E POWER SUPLY FEED FROM EXISTING VOICE CIRCUIT (V CABLE) RETURN TO EXISTING VOICE CIRCUIT (V' CABLE) (�1 ) (-) \ STROBE SPEAKER (+) (-) n (+) \ ) STROBE 4) (- STROBE SPEAKER (+) MUSIC 4 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) HTRI-R RELAY MODULE BACKGROUND MUSIC SHUTDOWN WIRING DETAIL SPEAKER STROBES & STROBES ONLY WIRING DETAIL NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODU:T DOCUMENTATION. OPER 11N TEMPERA RE: +32' F (0' C) TO 100' F 35 C) HUMIDITY: 0-93333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --) FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )>— DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPUCAT1ONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR f DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL TO NEXT DEVICE OR END OF LINE > TO NEXT ADDRESSABLE DEVICE TYPICAL WIRING AND MOUNTING DETAILS FROM PREVIOUS ADDRESSABLE 2 DEVICE TBI ®00 NO COM NC TO FAN SHUTDOWN EOLR 470 SWITCH +0 INPUT LED TSM -1 0 + TO NEXT ADDRESSABLE DEVICE 0 00 HTRI-R NO ® COM ® NC ® 0 TYPICAL DUCT DETECTOR/HTRI-R MODULE/TSM-1 SWITCH WIRING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 I t TO NEXT DEVICE rg O O CADDY BAR \c SMOKE DETECTOR -----..- SUSPENDED ILLUMINATED CEILING SMOKE DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: g 0 DESCRIPTION SHOP DRAWINGS DATE 09/18/15 12 ««< (4 Z CID OWr CD Q (oZ e�<LJ4 Z w QCD z ;Li cc zs' r-- - o a= W DD LL OI -- CID OD z 0 0 zcC 3: c� z Q U _2 'GALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: \OB NUMBER:13781-I) SHEET '' FA -02 I A B C D E F G H 1 J K FIRE ALARM BOOSTER Project: TEAVANA Panel: EXISTING BPS PAD -3 Date: September 21, 2015 Module/Device POWER BOOSTER Qty SUPPLY BATTERY CALCULATION Alarm (mA) i ,":.yY44g r� .vr, e,,,,,a :"„, '.,r,; zG', ",,'. YG ,w�,:,1:,, w'rx�t4 POWER Standby (mA) SUPPLY Total Alarm (mA) #"�r,.i°• , iYm�N.M.r� ',kz� ,,nY '�:^r'mT�"i '....�W' ^. h". ,:� ':�.;�,, pf,Y.r,,,,";, v. ' ,1:1r .AI �, � :,"i"i.':mY� � '', y ; ���`d,{'•: ! r Y�,!e A' �'�'^ ° Lk'e; ' .e.,, lx�v k, G„ .�, k ', ".e ? m ;' @ is x Total Standby (mA) Power Module 1 30 30 0 30 30 0 TOTAL FIRE ALARM POWER SUPPLY 30 30 Auxiliary Device Current 0 0 Notification Appliance Load (Max. Total / mA) 0 4813 Standby: Total A = CALCULATION , 30 Total B = 4843 Total current ratings of all devices in system (line A + line B + line C) 30 4843 Total current ratings converted to amperes (line D x .001) 0.03 4.843 Number of standby hours (24 or 60 per NFPA 72, Chapter 1, 1-5.2.5). 24 Qty Multiply lines E and F Total Standby AH 0.72 Total Alarm sounding period in hours (5 mins+ .0833 hours) Total 0.0833 Multiply lines E and H Total Alarm AH 0.4034219 Add lines G and I Total Standby and Alarm AH 1.1234219 0.0022 Multiply line J by 1.2 (20% extra insurance to meet desired performance) 1.34810628 12-V DC BATTERY SIZE RECOMMENDED (AMPERE -HOUR) 7 Notification Appliance Circuit Detail PROJEC : TEAVANA Panel:EXISTING BPS PAD -3 POWER SUPPLY Date: September 21, 2015 Wire Resistance 2.58 CURRENT TOTAL= 4813.00 2SET-M_C-CW@l5cd ^ ET -M1 +SC -CW @30cd SET-MC-,CW@75cd ; SET -MC -CW @95cd ;SET -MC -W @15cd ZR -MC -CW @30cd 111 TOTAL mA= DEVICES 69 3131 14 283 23.54 Total Wire Resistance (R ) Total Device. Load, Amps (1) Voltage prop ( E ) TM EOL` Voltage (WL * 2) * (R/ft) (Total Cct Load) _'* R) 313 1.46 0.31 0.46 ;SET -MC -CW @15cd C -CW @30cd SET -MC -CW @75cd 200 C -CW 95cd 264 ZR -MC -CW @15cd 69 C -CW @30cd 111 TOTAL mA=: DEVICES 1500; 14 Total Wire Resistance (R) Total Device Load, Amps (1) e Drop(E) 24.00; (WL*2)*Oft); (Total. "Cct Load) (E=1*R) 1500 0.00 1.50 0.00 24.00 SET -MC -CW @15cd ; 691 0 SET -MC -CW @30cd 111 0 SET -MC -CW @75cd_; 200 0 ET=iv'{C-CW @95cci 264 0 S_ET-MWC-@110cd 233: ZR -MC -CW_ ©30cd DEVICES ..0 TOTAL mA= 15001 14 24.001 Total WireResistance (R ) Total =Device Laad, Amps (1) 'Voltage Drop ( E) EOL Voltage *2)*(Rift) 1 Cct Load) (E=1*R) E) 1500 0.00 1.50 0.00 4.00 SET -MC -CW @15cd SET -MC -CW @30cd :SET -MC -CW @75cd SET -MC -CW @95cd :SET -MC -W @110cd ZR-MC-C'W @30cd 0 DEVICES :0 2001, 264 0 0 TOTAL mA=; 1500 14 Total Wire Resistance (R ) Total Device Load, Amps (1)ry~tt Voltage Drop ( E ) EOL Voltage 24.00 L*2)*(R/ft); (Total Cct Load) (E=1*R) 24 - E) 1 1500 0.00 1.50 0.00 24.00 CALCULATIONS i,, •, ��,,, C �„ r, ,' ., ., , n>Sr r(,: "C', rA r ,� ,,,, r, d, ... „,r ., ,,,. C ., .,�`4,k.'1'„4 „,.+,n e"t'„, !, 'i,,,,, .,,,„,',� �, .„,� , � �a l,,.. ., i..l,R..t,.,, 1 Ji , '"} i�,{`.:.„,l!;, �,." !, SfxrlYK ,�l1 ,t , :rrt r; fi�' '',A..,' :. .p�gg, r .,,,,f� �.i ,,' "� "r'. ."o :,,, 5, , ', :,, � .,, '.t'.. i.. 4f. '! .»:M, :,n A, B.w, a., .'�.m � � ,,9.ra. tr, , W.N.,, �.:'. Ct ra''Un:. . .r;,°. '✓.x:,Yr " k V � w.m�. a..!S �.: "�.'.„,, Vl;n�.dxR,„,i�.. °.' ° +9 �& "; :: ' '�� 5'•D"', f 3 ',! ,�' M, K. r M Yi t r �(i ,,, m� � �a• a"k, ^k !,', ,,�„� +d r °,d'P m q xrr,k dg >£ . ,�»' Is. .,. 'x: ..xR�,n .e. 1 ,Y ,rYl a '��l,„'} 'y�R`. '"'tl,: e, k , u7 h »Y:�• �. !� � „.�f?a, '� Vdr✓, »d,l..o, ,,,. � h" � , +Y �,y J„I� ,7�.�r: �,.Y,,S,,,".r, �J�' E.}',�y,im,kM..tlr,r' r� ;hk4 irmk.w„f?'",,;k ,. „x,yy4k.� �,,0,<�„I.., ''x. ,�� ' Y„ifiS > Fr . �PA Vn.r'k,'{.M., ^w, �� 0 0'},',w' Y, V' r ��a'w' „k „���'� ,k, v ':" ,., �� � "r5ti.4p'�¢F rna.. . (."r, >�r9kI.w��S„9„, i n. Yd�m:i,g�, r � i ,":.yY44g r� .vr, e,,,,,a :"„, '.,r,; zG', ",,'. YG ,w�,:,1:,, w'rx�t4 h3.,n„'',„, rv� �.,� , ,.. ,r »: a„S�.",,, „„, '1�,v.�x,h 'io,'ip;v.,W, :9. : .',c � b� 6. � :(J .' C ��' #"�r,.i°• , iYm�N.M.r� ',kz� ,,nY '�:^r'mT�"i '....�W' ^. h". ,:� ':�.;�,, pf,Y.r,,,,";, v. ' ,1:1r .AI �, � :,"i"i.':mY� � '', y ; ���`d,{'•: ! r Y�,!e A' �'�'^ ° Lk'e; ' .e.,, lx�v k, G„ .�, k ', ".e ? m ;' @ is x Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 FDBZ492-HR 1 0.0635 0.0635 0.064 0.064 HTRI MODULE 1 0.009600 0.0096 0.021 0.021 0.0731 Amps 0.085 Amps PROJECT: Panel: Date: Notification Appliance Circuit TEAVANA EXISTING SPEAKER CIRCUIT ;September 21, 2015 Detail - VOICE Wire Resistance 2:58 CURRENT TOTAL= 899.16 SET -MC @1/4 WATT 127 SET -MC @1/2 -WATT :SET @I/it-WATT SET @1/2 -WATT. DEVICES 127 3.54; 7.08 14.141 28.29 . TOTAL mA=I 0 99.16 :! 0 1228 18.30 899.16 Total Wire Resistance (RR Total Device Load, Amps (1) IVoltage Drop (E ) EOL Voltage J(WL*2)*(R/ft) otal Cct Load) 0:90 E=1*R) 6.34 5.70 TO NEAREST EXISTING SPEAKER CIRCUIT ( TO NEAREST EXISTING POWER SUPPLY TO NEAREST EXISTING DATA LOOP ( • (EXISTING BACK -OF - THE -HOUSE J -BOX) SINGLE LINE DIAGRAM S1-2 V-2 214 TSM V-3 EOL FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTE: DUCT DETECTOR, RELAY MODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved itt 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS CC 0 Lil tri z co 111 02 0 Vc) cr D0 co >- DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: SHEET FA -03 i TO EXISTING BACK -OF -THE HOUSE JUNCTION BOX n., D -<D S,V-0 o -V L — 7 0 r0 f IJ S1-1 15cd V-1 STJCKROdOM S. •• R: TAIL S1-2 30cd N 4 V-2 r I I( I.si 15cdM 711114 V-3 EOL,1i 14i (4) ((3 /I I 1 J 1 FIRE ALARM SYSTEM PLAN FIRE ALARM NOTE: ALL SPEAKERS TAP TO 70 -VOLTS 1/2 -WATT. FLAG NOTE: DUCT DETECTOR, RELAY MODULE & TEST SWITCH LOCATIONS TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. DUCT DETECTOR HOUSING SHALL BE INSTALLED BY MECHANICAL CONTRACTOR. 1743 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 0' 0 DESCRIPTION SHOP DRAWINGS DATE 0 co o) 0 2 «aa< T Z Co LO W Co CDZ << o Z w <Z QCf) wt Lil zI— ill 's <_ W t. u- °i– v) LO co CALE: 1/4''=1'0” DRAWN BY: D. GARCIA DESIGNED BY: T. QUAALE DATE: 09/18/15 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: 13781—L) Proprietary and Confidential, Copyright 2013 by Guardian Security Systems, Inc. All Rights Reserved \ SHEET FA -04 J 'le/x(3.100e lo ow. ,±z) sso)ppe 1.3exa pug C-LS.)-SQ‘°11 ticf onp pug Latr19-9L9 :lie° °seek' 11413;ALINVcI3C1 JJId t1ttiA)M1 'W, • - ,..1,,,VsKat...4.1,14.folk•-•,,,,,,K nsrt c ) fr 'neninq uoot2nAoid art.:1 nmni oqi - - • ! Ar. uoi.,)x1,..til 1^,1.1 41,;;I pizilj a; 1.;:porAnc .s!1'30u-.71(1%-noc ieulj • . • 41 N i JJ Lfl. :AG . 80_ ot,_.) - 0 •GEIL111-Co1 A.F.E 17 -Ca 130E) *leAatdde sa opersapAti o 100 ou!did uidTO11/Ri tunq adtd wapq palmdsui eq MIA sduitals PPM *?. j'tidd;1.1;)11bw;cing;J0 sbuiwiip pot;!pai ;o telliwqnsai i;rhjIvtA OU pt0A 111N\ ;:5ep J.:vg? sf.:0..1!Kc0.Ip osoLn (4 SiJa!SiAi JO StiOnOpp 'suopppv ..p3u64p ,,411 i1}1.f\ Ailr,401 J ti6r,lep la 104-3111?epe Fy:4 ...:04AirocpstJaciF.;@; pue s)leDuels. pidope 1,0 st,JogcnA -.-D7pr,)qine wi_t 00 t43I.I.IN\ SUOISSII110 • pue SJOJJ9o V.:::,7-,!•,1?1".sippues AVOlu;).nr);) t.wm 3U1W0OOO Jo E1112 tiOgtJeAald eiLd 0.1.4 I *Aq paNn.c3vv;_41 ueeq IAEq sued SG I • Jawri -pew) CALL Jed pJ UI P-aioN 175V swoultiloolnqqw• ==c! r.:.13 •=1"' a 1 31-4" r.104 Or& 4.4 1.0.1,10 .4 lir oif 121-721,1 .121_92111 SPACE #1155 REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND: REUABLE MOD G4A CONCEALED SSP REUABLE MOD G4A CONCEALED SSP RELIABLE MOD F1FR REC SSP APPROVALS BY: SYMBOL S/N ORIFICE 1/2' 1/2' .1/2' NPT K -MCT. 1/2' 5.6 1/T 5.6 1/T 5.6 THICKNESS OF CONCRETE VARIES A 1. A 3/8.X 2-3/4' KWIK BOLI, • DA 3/8ROD CPLG. LAS RECCOMENDED BY MFG. CUT3/8' A.T.R. (PER PLAN) RING HANGER TYPICAL ARMOVER TO NEW SPRINKLER HEAD ARGCO #38 OFFSET WHERE LENGTH OF ALL THREAD ROD. EXCEEDS V-10" ADD SECOND RESTRAINT HIAD FINISH BRASS BRASS CHR 3/8 X 3-1/2 LAG SCREW FOR WOOD 3/8" KWIK BOLT FOR CONCRETE 1/4X 1 TK FOR BARIOIST OR STEEL BEAM 3/8"x1-10 ALL THREAD ROD. MAX PER SINGLE RESTRAINT HANGER RING LINE RESTRAINT DETAIL (UP TO 2" PIPE) PLATE FINISH WHT BLACK CHR TOTAL SPRINKLERS THIS SHEET NOTE: 1) SPACE WITH IN 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NFPA-13(2007 ed.) SECTIONS 9.3.5.8.8, • TABLE 9.3.5.8.8(c) AND 9.3.6-RESTAINT OF BRANCH LINES FOR 1* TO 4" PIPE AU. LOCATIONS (U.N.0.) (1) 318' x 2-3/4" HILTI QWIK BOLT (1) 3/8' A.T.R. x (SEE PLAN) (1) 3/8. ROD C'LG. • (1) PIPE HANGER RING #13 HANGER DETAIL • FIG.. 65 BEAM CLAMP FIG. 69 RETAINING STRAP JA LOCK NUT REQ'D VIEW A -A FIG. 100 ALL THREAD ROD FIG. 200 AD1USTABLE RING HANGER • BOTTOM BEAM CLAMP, ROD, AND RING ('E3 #92 HANGER DETAIL N.T\, • FILE COPY • GENER NOTES* I . RETAIL AREAS ARE DESIGNED IN. ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13 ORDINARY HAZARD GROUP 2 MAX SPACING 130 5Q. T. 2. COSCO POINT OF CONNECTION 15 AT EXIST BUILDING SHELL SYSTEM 4" MAIN AS SHOWN ON THESE PLANS. 3. ALL PAINTING OF FIRE SPRINKLER PIPING (IF REQ) TO BE DONE BY OTHERS 4. ALL WIRING BY OTHER. 5. ALL MATERIAL15 NEW U.L. LISTED AND MEETS THE REQUIREMENTS OF THE TUKWILA FIRE FIRE DEPT. G. OWNERIS RESPONSIBLE TO ASSURE THAT STRUCTURE A5 IT: 15 SHOWN ON CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIR E SPRINKLER PIPING LOADS. 7. OWNERI5 RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40 DEG. F. MINIMUM AT ALL TIMES YEAR ROUND. SPRINKLER HEAD LOCATIONS INDICATED ON THESE DRAWINGS ARE NOT INTENDED TO BE "CENTER Of TILE" HEAD PLACEMENT. 9. COSCO ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO. 10. OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS Of N.F.P.A. 25-2002 BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD11AS EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED T1-115 SYSTEM 15 BEST QUALIFIED TO PROVID• E THE ONGOING LONG TERM TESTING, MAINTENANCE AND SERVICING OF T1115 SYSTEM(S). ****** FIELD NOTES ****** 1) THREADED PIPE FROM I " THRU 2" SIZE TO BE SCH. 40 STD. WALL PIPE (IMPORT). 2) GROOVED END PIPE FROM 2 1/2" THRU 8" TO BE 5C1-1.10 (IMPORT). 3) ALL GROOVED COUPLING ARE TO 13E "RIGID" TYPE U.N.O. (IMPORT). • 4) ALL THREADED FITTINGS ARE 300# CLASS D.I. (IMPORT). FIELD/NOTES EXISTING PIPE 5 NEW PIPE EXISTING HEAD NEWHEAD Wm?. 165 165 155 a •.o000.. COSCO • *0 00 0* • ' • 0 0 0 0 • ' Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE• 15000 Woodinville -Redmond Rd NELiCenSe No: . Woodinville, Washington 98072 COSCOFP1 IONM call (425) 686-8300 • fax (425) 827-4784 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscofire.com PROEM PERMIT # D08-031 TEAVANA 856 SOUTHCENTER MALL SPACE # 1155 TUKWILA, WA 98188 iD JUN 20 2008 SCALE:1/4=1?-0 Tukwila Fire .1(2-ozc 47 .5i' DMIRACT Nit MAZ BUILDERS 1146 E. HOME ROAD • SPRINGFIELD, OH 45503 BILL 760-646-3717 DIMING TITLE • FIRE SPRINKLER TENANT IMPROVEMENT IMTE : 06/18/08 SCALE: 114=1-0" DRAM Br: • BRIAN SCHULZE 53S-7963 MEET RO. 1 OF 1 FILE COPY TEAVANA FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UVI3ER SHEET TITLE FA -01 SYSTEM I \FORVV ATI O \ FA -02 TYPICAL DETAILS - WIRI\G A\D N OU\TI\G FA -03 FRE ALARM SYSTEIV FLOOR PLA\ FA -04 SYSTEM CALCULATIONS GE\EAL), RISER, SITE PLA\ 0 , ',thota't i_.:.ro ,:'.'� 1 nese pl;".ric,;;t;,b:. `.i7.:}i..•..,•. .;t:. ,;:2. h) ..',.,. Fire Prevei:,t;cy;l !a ..21.. .:;r . .:,'.d,•.: .k:. i. ci`.d s:L_'nd:?:1d::.. . . r.._.. ,c,t. l: , .,.,, ., ,. ., ORSi>., ,_r.i:i'.i:tr'1: 1,.U:) ;1;,1 .. .,•.'4,: , 1,. ....SiC,cAC(1 F 7tart,i_.4'.:', S4S".',1 :'r :,.,.':•.1,. 1'co il'::;.',%;,'.,,� ..>.�,. 9'). tl;',', adeq{u,<"':7 r.,t ,::;..,,: THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIL 0 DUCT DETECTOR L❑CATION 0 END OF LINE DEVICE(3.6K 1/4W) m SUPERVISED SWITCH GROUND r) 0 HTRI—R STATUS LED CO 0 N.O. 0 COM 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 11 VOLTAGE MAX. - CURRENT MAX, - CONT, RES. MAX. - MAX. CABLE LENGTH - C CLINE TO LINE) - C CLINE TO SHIELD) - MAX, LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING—\ TUBE \ AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE 1L) -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE {(+j FROM XLS CONTROL PANEL OR �(+) PREVIOUS ADDRESSABLE DEVICE (-) RELAY CONTACTS <4.OA @ 125VAC) <4.OA @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0.02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. + TB 1 5 5 0 0 0 0 123456 HCP TB2 +� m��_ m 654321 0 END OF LINE DEVICE (3.6K 1/4W) o v� 37) ; SUPERVISED ; SWITCH GROUND CV O O HTRI—D OSTATUS LED Do 0 0 NOT USED 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL yea SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC 1310 _L� �� T T T 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 0 $ 31 33• 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3,6K 1/4W) 2 NAC -4 NAC -3 NAC -2 NAC -1 SUPERVISED SWITCH FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP.! 0 0 0 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS IW EOL T M-1 Q r z LJ1 gc0 Fs. MO 0 S 0 GC >I TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL FROM REMOTE POWER SUPPLY ('S' CABLE) FROM FACP <V❑ICE CIRCUIT) ('V' CABLE) SCALE: NONE Y EARTH GROUND ..(+)TO NEXT DEVICE OR } STOP IF LAST DEVICE () TROBE) SPEAKER 0 CD ( STROBE-) (S ) STROBE SPEAKER (+) (-) SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R E 80" A.F.F. ti 4S DEEP BOX W/ 1-1/2" ING (PTEAKERNSTROBE) 14S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER�11N TEMPERATU +32' F (0' C TO 100' F (3E: 38' C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -)► FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN (-) > it DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW > (-) DATA OUT (+) DATA OUT TO NEXT DEVICE HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKEWSTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON \ CEILING FLEX \ 0 0 ; I TO NEXT DEVICE / / / / JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 r� CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO \OT I\ST _L ADDRESSABLE IN DEVICES vNTI- RRERROGRAV DEVICES ADD T AT MED W RESS. T \G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved cm 6'3 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 o <<<<< OD OD --1;40 (cc z 111 C) Wtr C Zi CCVG0 W oic op co OD I - SCALE: NOT TO SCALE DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 06/04/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: SHEET FA -022 EOL—S1 20.30V NORTH TEAVANA WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO INSTALL. ADDRESSABLE IN T DEVICES J\TIL PREPROGRAMMED W DEVICES ADDS=SS. I N G H Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved riZ ILI 112 ItZ c70- 0' Z O (f) LLT J F— F— W U) O U) W F— U) iv") FAX (206) 628-4990 RELEASE/REVISIONS REV. BY: Z DESCRIPTION SHOP DRAWINGS DATE 06/04/08 <«« co co J r J 0 2 Z <Wo �Z it;Cg=Q WQco �� I- N uJ SCALE: 1 /8" = 1'0" DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE:06/04/08 BACKROUND PLAN PROVIDED BY: `JOB NUMBER: ( FA -O3 l LL LIT H A \ty A I I .r-.. LE R5 ; / R BASK 11"i C)313 I N P SUNGLASS U „AP .ATE K I TS 0A\/1 ER A M TH ER [-I 00E1 /1A TE PIERCING PAGODA LIDS 31.1/EC". IN TRASH II C I\ L 1150 1115`:-• rr 1440 NORTH KIDS 700TI OC;KFR 11430 1200 Li 12;._ 12101 114.251 L Li. LU rs, SPR L_Tt Lti cri L d 230 TEAVANA WESTFIELD SOUTHCENTER MALL SCALE 113214 r • ) 0 LL 12351 CI) IDOSTINC FOOTLOCKER F;bANCY .... EX D,I 21 OtEINIff BATTERY SIZING CALCULATION SYSTEM CALCULATIONS Notification Appliance Circuit Detail DESCRIPTION WESTFIELD SOUTHCENTER MALL TEAVANA TEAVANA F -DATE . FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Wire Resistance 1.62, 2 Panel: June 4 2008 CURRENT TOTAL= 162 Date: CIRCUIT: S1 Current Load: Standby: Alarm: Current Load: Alarm Current Alarm Total Wire Size Standby: Alarm: Circuit Total QTY SET -MC @15CD 64 64 Total Wire Resistance ( R ) 0.62 1 1 Device Type 98 Qty Amps Total Amps Total Device Type ( WL * 2) * (R/ft) Qty Amps SET -MC @75CD Total Amps Total HFP-11 0.0022 0.0022 0.0023 SET -MC @110CD 233 - 0 (Total Cct Load) 0 AD2-P 318 1 0.0635 0.0635 0.064 0.064 Main System Board 0.10 1 0.03 445 0.03 0.030 0.030 HTR -R I 2 0.009600 0.0096 0.021 0.042 - SET -MC @15CD 1 EOL Voltage 0.064 0.064 SET -HMC @185CD HTRI-D t 0.001600 0.0035 (20.4 - E) SET -MC @30CD 0 1 64 0 0.098 0.098 ICP -B6 0.005 Z-MC@30CD 98 0 SET -MC @75CD 0.175 SET-MC-CW@110CD 233 0 _ SET -MC @110CD 2 TOTAL m A= 162 12 191 0.233 SET-HMC-C@115CD Notification Appliance Circuit Detail 0.318 WESTFIELD SOUTHCENTER MALL 0.0731 Amps 0.106 Amps SET-HMC-C@135CD June 4, 2008 CURRENT TOTAL= 3.6 0.318 Date: SET-HMC-C@185CD SPEAKER CIRCUIT 0.445 QTY Device Type ZR -MC @15CD Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 0.064 Standby Current Load: Alarm Current Load: 70.7V1/8 0.0731 0.106 Amps Amps For 24 Hours = For 5 Minutes= 1.754 0.009 Amp -hours Amp -hours ZR -MC ©30CD Total Wire Resistance ( R ) 0.99 0 0.098 0 0 HCP ( WL* 2 )*(R/ft) 0.0015 00 0Total 0.03 Amps 0.192 Amps 0 0 0 (Total Cct Load) 0 25% Derating= 2.204 Amp -hours Standby Current Load: - 0.03 Amps Voltage Drop For 24 Hours = 0.720 Amp -hours 0 0 ---- (E= 1* R) 0 0 ,,- u- -- EOL Voltage 20.40 0 Alarm Current Load: 0.192 Amps (20.4 - E) For 5 Minutes= 0.016 Amp -hours Total System Current Load: 2.204 Amp -hours 0 0 0 DEVICES 2 TOTAL m A= 3.6 14 191 25% Derating= 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.920 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH OtEINIff BATTERY SIZING CALCULATION RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved P00' co 0\ O• c0 C\J 0 ‘0 (\.1 < < Lid _J F -- 1 -- LU (I) ui P0 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a Notification Appliance Circuit Detail DESCRIPTION WESTFIELD SOUTHCENTER MALL F -DATE PROJECT: TEAVANA Wire Resistance 1.62, 2 Panel: June 4 2008 CURRENT TOTAL= 162 Date: CIRCUIT: S1 Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage_at EOL Circuit Total QTY SET -MC @15CD 64 64 Total Wire Resistance ( R ) 0.62 1 1 SET -MC @30CD 98 98 ( WL * 2) * (R/ft) 0 SET -MC @75CD 175, ATotal Device Load, AmpsQ) 0.16 0 SET -MC @110CD 233 - 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.10 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 20.30 0 SET -HMC @185CD 445 0 (20.4 - E) 0 Z-MC@15CD 64 0 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 2 TOTAL m A= 162 12 191 20.299747921 162 Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL PROJECT: Panel: TEAVANA Wire Resistance 2.58 June 4, 2008 CURRENT TOTAL= 3.6 Date: CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 70.7V1/8 1.8 3.6___ Total Wire Resistance ( R ) 0.99 0 0 0 ( WL* 2 )*(R/ft) 00 0Total Device Load, Amps (I) 0.00 0 0 0 (Total Cct Load) 0 0 -7-- 0 - - Voltage Drop ( E) 0.00 0 0 0 ---- (E= 1* R) 0 0 ,,- u- -- EOL Voltage 20.40 0 (20.4 - E) 0 0 0 0 DEVICES 2 TOTAL m A= 3.6 14 191 20.396451981 3.6 RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved P00' co 0\ O• c0 C\J 0 ‘0 (\.1 < < Lid _J F -- 1 -- LU (I) ui P0 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS F -DATE co 0 ...., 0 ..., co 0 2 <1<<<< 0 SCALE: AS NOTED DRAWN BY: I. AN DERSON DESIGNED BY: R.VEZZANI DATE:06/04/08 BACKROUND PLAN PROVIDED BY: :.10B NUMBER: C SHEET FA -04