HomeMy WebLinkAboutPP - 681 SOUTHCENTER MALL - BUCKLE - PERMITS AND PLANS681 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-052 11-S-039 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Buckle 681 Southcenter Mall Permit No.: 11-S-039 Date: February 14, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. SHEET NU ViBER SHEET TITLE FIRE A ARM SYSTEM TUKWILA, WASHIN FA -01 SYSTE vl INFORMATION FA -02 TYPICAL WRING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LI \ E DIAGRAM FA -04 FIRE ALARM SYSTEM PLA SHEET INDEX 'a Without Comments ® As Noted in Red C3 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Preyei tion Bureau for conformance with current City anderds. Acceptant, is subject to errors and ni5sions which do e'ot authorize "iolations of adopted In:dards and ordinances. The respjonsibility for the 3equacy of design:sts totally +,,,ith the designer. iditions, deletions or revisions to these drawings after . ; is date will void this acceptance and will require a _;submittal of revised drawings for s'ubsequ'ent approval. i7inal acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 3- `f-! By: SCH t UKWILA FIRE DEPARTMENT, PLezise call: 575.4407 and give this job if -F-05-1. ,:,_i exact address for shut' •,•,L%n or r`,-?+tjr,3tion annrni_eal NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Deirection Systems. Failure of test will result in a Re -inspection Fee and terrnination of the testing. ,IDULE AND CONDUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPUFPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.=.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FiNAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED ADDITION TON QUANTITY 1 1 3 4 3 5 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE 4S DEEP BOX W/ 1G RING CEILING ®DUCT DETECTOR D AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN 14 FIRE ALARM STROBE EX ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A ( SYMBOLS LEGEND I NORDSTROM 11 3 LEVELS 171,275sf PAID MAR -12011 TUKWILA FIRE 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS L DATE N N 0 2 a<aaa Zco co T F Q O) m ci cro w 2 E -o J w zz U� cD- CC) og cccop LL l- Z 0 0 W Pd) >- (0 /SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/21/11 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved \OB NUMBER: 55171 SHEET k FA -01 123VAC-60NZ DEDICATED EMERGENCY 111 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOM FOR ADD1110NA1. SP6CF1CA110NS SFE PRODUCT DOCWENTA1ION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC TU NUT ADDRESSABLE & DEVICE STOP IF LAST DEVICE - FRaI XLs ca1TRa. PANEL OR PREVIOUS ADDRESSABLE DEVICE - 0 0 0 0 HTRI-R 114 e'_ 0 NOTE: FADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE CFD N L Oil 00 0 0 0 PAD -3 oo° INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX +1- 1 2+2- 2 NC C NO + - + - + - + - + - S 0 0 0 0 0 o a 0 3.6k EOL (-) (+) SPARE SPARE ; SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATIOtf NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPUFPLR RED (JACKET) VONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 F GROUND 0 0 0 0 HTRI-R I a ° (+)i TO NEXT DEVICE OR ❑0 !Vok - 0 �f C0 m 0 0❑I ID o OI I❑I 1 , � 4q -I -S, n � Q � 1 O O O aDg UM nn . PM WV 70V 7(e 1 T , I , e �I Y i I I +- A...EF.■ " �A 642 1:1.1:1:III:I:I` +- .'n II%. *minx " - ', -e A.e ►Ero■ ' V lil * ,.4 f 1:11:1 I I:I:I• �• bilII�v1XXt ' „L NI 111 a❑ (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) 0 (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV -. FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER ISD ❑o — O — I C0 m 0 _ , , SHOP DRAWINGS n � o O rl .an. rI T T ,€ ll i I I I +- A...EF.■ " �A 642 1:1.1:1:III:I:I` +- .'n II%. *minx " - ', V lil * " II= I I:I:Ir al ►�°10P 00 411 (-) STROBE ❑EIDJ CIRCUIT STROBE ❑ 0 0 (-) SPEAKER CIRCUIT (+) (+) /� STROBE DIl17 CIRCUIT SPEAKERISTROBE ❑a •y _ O I C0 m 0 • _ I - , SHOP DRAWINGS o o J s� rI T 2 I as +- .'n II%. *minx " - ', ,•I". " II= I I:I:Ir I ' NI 111 0 ❑o (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS STROBE (+) (+) (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERATU E: +32' F (0' C) TO 100' F (NT C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —; FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> DATA IN(+)> DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE HARD LID —\ TO NEXT ADDRESSABLE DEVICE 4" SQUARE DEEP BOX // WITH 1-1/2" EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX 0 0 JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 3 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: C0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/21/11 2 << as co Z T Co O Qco 2z CO Q =o LU F-0 �wzz Lorr-T, OD _i l"' cc co D Li 0.. �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/21/11 BACKROUND PLAN PROVIDED BY: NUMBER: 55171 J SHEET FA -02 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved Current Load: Standby: Alarm: Device Type HFP-11 Qty Amps Total Amps Total 0.0022 00022:: 00023:: 0.002IL AD2-P 3 0.0635 0.0635 0.064 0.192 HTR -R 4 0.009600 0.0096 0.021 0.084 0.0731 Amps 0.276 Amps Current Load: *Icti. a. Device Type Qty Amps Total Amps Total Main System Board SET -MC -C ©15CD 1 0.03 0.03 0.030 0.030 0.069 ISET-MC-C ©30CD S C 7 CD 2 0.111 1 0.2 SET -MC -C @95CD 2 0.264 ZR -MC -C @15CD 14 0.069 0.966 ZR -MC -W @I5CD 0.064 ZR -MC -C @75CD 0.175 0.03 Amps 0 996 Amps Standby Current Load: 0.03 Amps For 24 Hours= 0.720 Amp -hours Alarm Current Load: 0.996 Amps For 5 Minute 0.084 Amp -hours 25% Derating= 1.005 Amp -hours Total System Current Load: 1.005 Amp -hours TO NEAREST., EXISTING DATA LOOP Do 12VD rs RTU -3 RTU -2 D,21 HTR -R ITSMI RTU -1 D,21 HTR -R FTSTV11 (HALLWAY) 8 EX 2C -c, Notification Appliance Circuit Detail PROJECT: BUCKLE B Panel: PAD -3 POWER SUPPLY Wire Resistance 2.58 Date: February 28, 2011 CURRENT TOTAL 1945.00 0 SET -MC -C ©15CD 691 0 - 2 SET -MC -C ©30CD - I1IH 222 I o ._,ISET7IVIC-C©76CD 200 01 01 _ 264 • 0 0 ZR -MC -C ©1106D 1 2591 01 ' - 7 ZR -MC -C ©15CD 69 . - 483 1 'ZR -MC -C ©30CD 981 981 1 _0 -MC-C ©75CD 175 0 DEVICES=110 1 TOTAL mA=1 8031 14 221 19.481 8031 'Total Wire Resistance ( R ) 1 1 (WL* 2 )*(R/ft) 1.14 Total Device Load, Amps (I) (Total Cct Load) 0.80 1(E= I* R) 1 0.92 1Voltage Drop ( E ) EOL Voltage 20.4 - E) 19.48 0 ISET-MC-C ©16CD 1 611 01 0 SET -MC -C ©30CD 111 0 1 SET -MC -C ©75CD 1 2001 2001 2 2 SET -MC -C ©65CD ' _: „ 264 ' 528 , 01ZR-MC-C ...s,,..A110CD 1 2591 01 ,.i 6 ' ZR -MC -C ©1' 5CD 69 414 • 0 1ZR-MC-W ©15CD 1 641 01 - ' 0 ZR -MC -C ©75CD . . 176 - - , 0 DEVICES=19 TOTAL mA=1 11421 14 204 19.971 1142' . . - Total Wire Resistance ( R ) TOtaf Device Load, Amps (1) iVoltage Drop ( E) EOL Voltage ( WL * 2 )* (R/ft) , 1.05 (Total Cct Load) = 1.14 (E= I * R) 1.20' 20.4 - E) 19.20 SYSTEM CALCULATIONS Notification Appliance Circuit Detail PROJECT: BUCKLE B Panel: XLS-V Date: February 28, 2011 Wire Resistance 2.58 BPS 120VAC, DEDICATED ) (BY OTHERS) S2-1 S2-2 75cd 15cd V-3 1/4-W S2-3 S2-4 15cd 15cd S2-5 95cd V-4 1/4-W S2-6 S2-7 19 70.7V 1/8 1.8 34.2 28 :707V114 3.64 99.12 0 170.7V 1/2 01 o 0 70.7V 1 0 0 DEVICES= 47 TOTAL m A= 133.321 14 947 19.74852915: 133.321 S,V,V Total Wire Resistance ( R ) Total Device Load, Amps (I) !Voltage Drop ( E) 1 1 EOL Voltage S2-8 15cd 15cd 15cd S2-9 95cd V-5 1/4-W EOL S2 S1-1 15cd S1-2 30cd V-1 1/4-W S1-3 S1-4 S1-5 S1-6 S1-7 15cd 15cd 15cd 15cd 15cd SINGLE LINE DIAGRAM S1-8 30cd 15cd 15cd V-2 1/4-W S1-9 S 1 - 1 0 EOL Si Cct Load"013 - (E= I * R) 065j (2014 - E FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1•0 CO 0' 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 IREV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/21/11 2 <<<<< cc 0 w z w co -J z 0 < Z Z C75 Ca cc 0 < wi- W 0 w zzz < 0 CI) < CI) cc z Ca (5)) 0 cc con Er_ 1 - UJ (i) >- ci) (S--CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:02/21/11 BACKROUND PLAN PROVIDED BY: OB NUMBER: 55171 ( SHEET FA -03 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved A ) 1/4 y TO NEAREST EXISTING DATA LOOP ATCHLINE MATCHLINE S1-5 15cd Nc2f YOMRN'Q. TOILET L s,vy—C TOILET S1-4 15cd SNAP rff_ 1 I _ 1-3 5cd - -1- — s- = S1-2 , 30cd V-1 : =-- TO S1-6 ? FROM EXISTIN SPEAKER_STR BE TO HTRI-R f s,v,v TO S1-6 Slm5 30cd = = = S,V,V Si -8 3Ccd V-2 RTU -3 HTR -R TEAMMATE HO F. TTINIG CiM f2( S1-7 15cd RTU -2 R -R S OCI<RO0M TSMI H TO RI -R fEOL r TSM S1-9 I 15cd S o I IT INC I R(OM ii S1-10 EXIT CORRIDOR 15cd V,V r HOKERUN T9 BPS L FITTING I ROOM S2-2 15cd rr- 1 1 sv,v 6 FITTING . , DM FITTING ROO 1‘A S2 3 15 d FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. S2-4 15cd 75cd V-3 II 1 IIII I II I II -+- 11 PAY —17 11 II i L S,V,V S2-5 95cd V-4 TO PAD -3? POWFR SUPPLY 1 11 II 11 11 11 11 11 11 II 11 IL ii II Ii 11 II 11 s,v,v ...1 E S2-6 15cd Fl II INC,: rs, k A S, FIRE ALARM SYSTEM PLAN S2-7 15cd db. FIT INC RC DM II 11 II 11 11 11 11 Ii 1 Ash 1S2c- 51 HI HNC - ROOM S2-9 95cd V-5 EOL S2 -RTU-1- liffR-R1 TSM 1 --F 1- 1743 1ST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS . 1_ <x c. 02/21/11 2 <<<<< co Z co 0 217) < z CC) „en cc o 0 w z 1 z 16 (01< —0 Cc co o < CO W Or; CC CD ‘CALE: DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/21 /1 1 BACKROUND PLAN PROVIDED BY: 1.0E3 NUMBER: 55171 SHEET FA -04 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved GENERAL LEGEND 4EARTHQUAKE BRACING PiPE HANGER —• GROOVED CAP RIGID COUPLING ( UNLESS NOTED ) CAP -4 PLUG g CENTERLINE O HYDRAULIC REFERENCE POINT BOD CENTERLINE PIPE TO BOTTOM OF DECK BOB CENTERI JNE PiPE TO BOTTOM OF BEAM BOJ CENTERLINE PiPE TO BOTTOM OF JOIST FOS FACE OF STUD FOW FACE OF WALL —c Multi -Port Bracket FOC AFF CH R.C. 4 E/C C/C C/E GG TG TxF AIR Mud -lead Sprinkler Drop FACE OF CONCRETE ABOVE FINISHED FLOOR CEILING HEIGHT REDUCING COUPLING OUTLET COUPLING YIELDED OUTLET 'FIT' FITTING END TO CENTER CENTER TO CENTER CENTER TO END GROOVE/GROOVE THREAD/GROOVE (ALSO 'Gr) THREAD/'FH (ALSO 'Fxl') ALL -THREAD ROD ic"" GEILE'{C GYP. . hl . _c t.i1at= f.3 -1P. ,'O. (IDLINGt. ^�.:t :,'-"5 _�; ._,..._.....__ ;T r..._.....�s:172.t!'s�..�a • :3 t.-.-z.-r z^�:- •rr. K,�•:�g __n?w. ..T_-_._,._.�..a-..,. ¢f'...,.'=�:....: �y....:._,�T_>r�_.�..r..v. may._ f�._3,.,..'x- ..F:, _ u I INE Ot: -ARM HEIGHT 'V:ALLS BELOW, PEE, .`:=h iL LIE PLAN 'i - B l.; �tl _1 2 A i a— ti Ed i ;f. 1Y" -s fr GIP. 1:0 COO /2 4; 1 1 t. q ��f,�'5•� -_- z ti. BD. ' 1ILING y /K` 2-2 EXIT 0G111. ON EXIT WALL ABC's,'DOOR LIGHT 1 Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' legnths Adjustable Hub FLEXHEAD I NOU5151E5'1,44 Flexheag Commercial Ceiling Unit T -Dar Calling Installation Model #2024,2036,2048,2060,2072 I:3 Without Comments aAs Noted in Red Per The Attached Letter -!..ese plans have been reviewed by The Tukwila Fire rsvention Bureau for conformance with current City -.dards. Accepta-lcr is subject to errors and .Missions which do nor authorize violations of adopted :..dards and ordinances. The responsibility for the f,auacy of design r-,sts totally with the designer. .ddltioris, deletions or revisions to these drawings after -nis date will void this acceptance and will require a i esubrnittai of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. ') te: a— I LI - I By: I 7-10 c EXIT CORRIDOR WITH 9'-O" CEILING GW. BO. 10ELINGw,, 7' I-- PEND. © 9' LID - LINE t HEIGHT WALLS IELO's1', . REF: SATE11 L n PLAN C 2=0 311). 30. CEii. f G --G 112' �;.!'.F.i "^'F.tint ..� ..,T-zPmT-•-�-- -- h,�'`:'�-...N�...�_s ��:.:u=..�•.���»..,�-:sem a.n.4 r_».,.__,;z>;�:ri.=•_��' R (D) 1-b i• . . -- r D 1PJ 2T`YIt2' o ?/24 024.3 1/2' - GYP_ I -IL). CEILING 1/2'- A.F.F.L /-1--1 9'-6 i/ f' Ai.F.('.I{ P-1 _ j- -:), . P.t..1, `;I1F r. t; 9' A' n. 3' ` I .'`i i.i' F E ..-- 1---1- ^e•- -'g ✓+'-r> •-rT.9 .1.<..t ._� a Y -r'- ','�'� -•-4': ^*CIS 4^•r } F 3 z- .:-f- . i. '<`."`�.." s" i'. - :+i'a:?•¢ate-F• e.-�ezw »`z+•e A..?'Fifi>= 4 - _ ,s_. ._..._�zr�. ,,..;re._ _..a„._M....,:,.-,.._..:.,��..,.-e_.�.__.-r_.--._..,....1_,Y.._._....�f'..-•_::-:_. _.r..-,.4�.�, � s.e:�.{•-�,.�. - :.t...._.....__._.1.-,� POT acc TRACK 1,1 CORRUGATED MUM -M7L-7_, tAj 21 ?Jease call: 575-440Z 3 nd give this job 3nd exact address for shut. NOTICE Weld stamps must be inspected before pipe is hung, Do not paint piping prior to hydrostatic test appi l'• 17, CI La di rr 144 Y. UTE: BOTTOM OF TRACKHEAD 10. 'GYP. BD. CEILING —GYP. ED. CLING Legend NEW 1/2" PENDENT SPRINKLER 'FLEX -DROP' EXISTING 1/2" PENDENT SPRINKLER TO REMAIN EXISTING SPRINKLER PIPING NEW PIPING Sprinklers SPRINKLER HEAD LEGEND: PROJECT DIRECTORY TENANT ARCHTTECT PROECT ADDRESS THE BUCKLE, INC. 2407 WEST 24TH KEARNEY. NE 68845 TEL: (308) 235-8491 ATTN: LORI KOEPPE FAX: (308) 238-2415 MICHAEL R. MACK, AIA The Buckle #296 SPACE: E552 2800 SOUTFICENTER MAU. TUKWILA. WA 98188 THE BUCKLE, INC. 3100 E. PANDOL ATIU. AMINGTON, TEXAS 76011 LANDLORD A e 817.701.4819 1/2" 12E115 JONES IIALTSBERSER. 5.6 — SUITE 302 SAN AMMO. 1X 78247 121: (210) 545-1007 ATTN: ALBERT CARO.% Et4GINEER CONTACT: CANYULE BRAKUS 2800 SOUTHCENTER MI TEL: (206) 246-7400 AIA FAX: (210) 545-9517 B 0 TUKWILA. WA 98188 MAIL INFORMATM DR BURDING DEPARTMENT BLACK DANIEL A. REEVES, P.E. 155' SOUTHCENTER OPERATIONS TANAGER: PAT BURNS 2800 SOUTHCENTER MALL TEL: (206) 246-0423 TUKWILA. WA 98188 3100 E Road Mg ad Adtrylan.1X 76011 (617)6334200 FAX 18171633.4152 Wad**. Dana 644016 CITY OF TUKWILA CEPARTMENT Of COIMUNITY DEVELOPMENT 6300 SOUINCENTER BLVD.. #100 ATTI't ALUEN JOHANNESSEN TUKWILA. WA 98188 TIEL: (236) 431-3670 FAX: (208) 431-3885 RA1314 1/2" 1/2" 5.6 APPLICABLE CODES INCLUDE BUT ARE HOT BUCKLE Lamm TO TIM FOLLOWIN SPACE # . E552 GOWRIIING CMS ...../-."--% A. BUILDING CODE: 2009 INTERNATIONAL BUILDING CODE ATEA ' \ 5147 S.F. B. MECHANICAL CODE: 2009 INTERNATIONM. MECHMOCAL. CODE ..................ei C. PIJUMBING CODE: 2009 INTERNATIONAL PUMPING CODE OCCUPMCY 0 0 to D. FIRE & SAFETY CODE: 2009 INTERNATIONAL FIRE CODE CONSTRUCTION TYPE E. TLFPA #13 INSTALIATION OF SPRINKLER SYSTBAS 1/2" BB FULLY SPRINIDED YES 5.6 G. OS.HA H. ELECTRICAL CODE 2008 PLATEINAL ELECTR/CAL CODE CHROME I. ACCESSIBILJTY CODE: 2003 ICC/ANSI A117.1 J. ENERGY CODE: 2006 WASHINGTON STATE ENERGY CODE 7 OCCUPANCY LOAD TOTAL SPRINKLERS = 70 THIS SHEET MTN- LEASABLE SPACE 113TAL OCCUPANT LDAD .. 136 5147 ga. Fr. r Legend NEW 1/2" PENDENT SPRINKLER 'FLEX -DROP' EXISTING 1/2" PENDENT SPRINKLER TO REMAIN EXISTING SPRINKLER PIPING NEW PIPING Sprinklers SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. nE, afa TEMP. QUAN. RELIABLE G4 CONCEALED PENDENT A e R2115 1/2" 1/2" 5.6 — WHITE 155' 27 RELIABLE F1 RECESSED PENDENT B 0 RA1314 1/2" 1/2" 5.6 BLACK BLACK 155' 21 RELIABLE F1 RECESSED PENDENT C • RA1314 1/2" 1/2" 5.6 CHROME CHROME 155' 15 RELIABLE G4 CONCEALED PENDENT 0 0 R2115 1/2" 1/2" 5.6 — CHROME 1.-ij 7 APPROVALS BY: TOTAL SPRINKLERS = 70 THIS SHEET TYPE SPRINKLER SPEC DRAWING A-4 A 1) SPRINKLER PENDENTS IN STOREFRONT WHALL BE CONCEALED TYPE WITH WHITE COVER PLATE B 2) SPRINKLER PENDENTS IN SALES AREA LAY—IN TILE CEILING SHALL BE SEMI—RECESSED BLACK WITH BLACK ESCUTCHEON 3) SPRINKER PENDENTS IN SALES AREA LAY—IN TILE SHALL BE CENTERED IN CEILING TILE C 4) SPRINKLER PENDENTS IN STOCKROOM SHALL BE SEMI—RECESSED WITH CHROME ESCUTCHEON D 5) SPRINKLER PENDENTS IN CORRUGATED METAL SHALL BE CONCEALED TYPE WITH BRUSHED CHROME COVER PLATE A 6) SPRINKLER PENDENTS IN DRYWALL INSTALLATIONS IN SALES AREA SHALL BE CONCEALED TYPE WITH WHITE COVER PLATE A 7) SPRINKLER PENDENTS AT PERIMETER AND NEAR TRACK HEADS (12" OR LESS) SHALL BE CONCEALED TYPE WITH WHITE COVER PLATE 8) MAINTAIN 10" CLEAR FROM TRACK LIGHTING FIXTURES 9) SPRINKLER PENDENTS AT PERIMETER AND NEAR TRACK HEADS (12n OR LESS) SHALL BE 200' GENERAL NOTES SCOPE OF WORK: ADD NEW PENDENT FOR TENANT IMPROVEMENT WORK SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 -280-7 ED. ALL MATRIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED EXISTING SYSTEM HYDRAULICS ARE NOT EFFECTED BY ADDED SPRINKLERS ORDINARY HAZARD GROUP 2 OCCUPANCY — 130 S.F. PER SPRINKLER MAX TENANT SPRINKLER PIPING PLAN r\ 1/Li A 2/9/11 REVISE PER PD. REVIEW 24' FUT Py PAID FEB 1C 2011 TUKWILA FIRE CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 Buckle 0 U TH CEN TER Mal k Store No. 296 Space No. E552 Tukwila, Wasington DATE: 2/11 SCALE: AS NOTED 681 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-052 11-S-039 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Buckle 681 Southcenter Mall Permit No.: 11-S-039 Date: February 14, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. SHEET NU ViBER SHEET TITLE FIRE A ARM SYSTEM TUKWILA, WASHIN FA -01 SYSTE vl INFORMATION FA -02 TYPICAL WRING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LI \ E DIAGRAM FA -04 FIRE ALARM SYSTEM PLA SHEET INDEX 'a Without Comments ® As Noted in Red C3 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Preyei tion Bureau for conformance with current City anderds. Acceptant, is subject to errors and ni5sions which do e'ot authorize "iolations of adopted In:dards and ordinances. The respjonsibility for the 3equacy of design:sts totally +,,,ith the designer. iditions, deletions or revisions to these drawings after . ; is date will void this acceptance and will require a _;submittal of revised drawings for s'ubsequ'ent approval. i7inal acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: 3- `f-! By: SCH t UKWILA FIRE DEPARTMENT, PLezise call: 575.4407 and give this job if -F-05-1. ,:,_i exact address for shut' •,•,L%n or r`,-?+tjr,3tion annrni_eal NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Deirection Systems. Failure of test will result in a Re -inspection Fee and terrnination of the testing. ,IDULE AND CONDUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPUFPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.=.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FiNAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED ADDITION TON QUANTITY 1 1 3 4 3 5 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE 4S DEEP BOX W/ 1G RING CEILING ®DUCT DETECTOR D AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN 14 FIRE ALARM STROBE EX ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A ( SYMBOLS LEGEND I NORDSTROM 11 3 LEVELS 171,275sf PAID MAR -12011 TUKWILA FIRE 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS L DATE N N 0 2 a<aaa Zco co T F Q O) m ci cro w 2 E -o J w zz U� cD- CC) og cccop LL l- Z 0 0 W Pd) >- (0 /SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/21/11 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved \OB NUMBER: 55171 SHEET k FA -01 123VAC-60NZ DEDICATED EMERGENCY 111 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOM FOR ADD1110NA1. SP6CF1CA110NS SFE PRODUCT DOCWENTA1ION. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC TU NUT ADDRESSABLE & DEVICE STOP IF LAST DEVICE - FRaI XLs ca1TRa. PANEL OR PREVIOUS ADDRESSABLE DEVICE - 0 0 0 0 HTRI-R 114 e'_ 0 NOTE: FADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE CFD N L Oil 00 0 0 0 PAD -3 oo° INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX +1- 1 2+2- 2 NC C NO + - + - + - + - + - S 0 0 0 0 0 o a 0 3.6k EOL (-) (+) SPARE SPARE ; SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. (+) 0 WIRE DESIGNATIOtf NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPUFPLR RED (JACKET) VONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 F GROUND 0 0 0 0 HTRI-R I a ° (+)i TO NEXT DEVICE OR ❑0 !Vok - 0 �f C0 m 0 0❑I ID o OI I❑I 1 , � 4q -I -S, n � Q � 1 O O O aDg UM nn . PM WV 70V 7(e 1 T , I , e �I Y i I I +- A...EF.■ " �A 642 1:1.1:1:III:I:I` +- .'n II%. *minx " - ', -e A.e ►Ero■ ' V lil * ,.4 f 1:11:1 I I:I:I• �• bilII�v1XXt ' „L NI 111 a❑ (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) 0 (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV -. FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER ISD ❑o — O — I C0 m 0 _ , , SHOP DRAWINGS n � o O rl .an. rI T T ,€ ll i I I I +- A...EF.■ " �A 642 1:1.1:1:III:I:I` +- .'n II%. *minx " - ', V lil * " II= I I:I:Ir al ►�°10P 00 411 (-) STROBE ❑EIDJ CIRCUIT STROBE ❑ 0 0 (-) SPEAKER CIRCUIT (+) (+) /� STROBE DIl17 CIRCUIT SPEAKERISTROBE ❑a •y _ O I C0 m 0 • _ I - , SHOP DRAWINGS o o J s� rI T 2 I as +- .'n II%. *minx " - ', ,•I". " II= I I:I:Ir I ' NI 111 0 ❑o (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS STROBE (+) (+) (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER T1N TEMPERATU E: +32' F (0' C) TO 100' F (NT C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR —; FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> DATA IN(+)> DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE HARD LID —\ TO NEXT ADDRESSABLE DEVICE 4" SQUARE DEEP BOX // WITH 1-1/2" EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX 0 0 JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 3 0 0 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: C0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/21/11 2 << as co Z T Co O Qco 2z CO Q =o LU F-0 �wzz Lorr-T, OD _i l"' cc co D Li 0.. �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/21/11 BACKROUND PLAN PROVIDED BY: NUMBER: 55171 J SHEET FA -02 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved Current Load: Standby: Alarm: Device Type HFP-11 Qty Amps Total Amps Total 0.0022 00022:: 00023:: 0.002IL AD2-P 3 0.0635 0.0635 0.064 0.192 HTR -R 4 0.009600 0.0096 0.021 0.084 0.0731 Amps 0.276 Amps Current Load: *Icti. a. Device Type Qty Amps Total Amps Total Main System Board SET -MC -C ©15CD 1 0.03 0.03 0.030 0.030 0.069 ISET-MC-C ©30CD S C 7 CD 2 0.111 1 0.2 SET -MC -C @95CD 2 0.264 ZR -MC -C @15CD 14 0.069 0.966 ZR -MC -W @I5CD 0.064 ZR -MC -C @75CD 0.175 0.03 Amps 0 996 Amps Standby Current Load: 0.03 Amps For 24 Hours= 0.720 Amp -hours Alarm Current Load: 0.996 Amps For 5 Minute 0.084 Amp -hours 25% Derating= 1.005 Amp -hours Total System Current Load: 1.005 Amp -hours TO NEAREST., EXISTING DATA LOOP Do 12VD rs RTU -3 RTU -2 D,21 HTR -R ITSMI RTU -1 D,21 HTR -R FTSTV11 (HALLWAY) 8 EX 2C -c, Notification Appliance Circuit Detail PROJECT: BUCKLE B Panel: PAD -3 POWER SUPPLY Wire Resistance 2.58 Date: February 28, 2011 CURRENT TOTAL 1945.00 0 SET -MC -C ©15CD 691 0 - 2 SET -MC -C ©30CD - I1IH 222 I o ._,ISET7IVIC-C©76CD 200 01 01 _ 264 • 0 0 ZR -MC -C ©1106D 1 2591 01 ' - 7 ZR -MC -C ©15CD 69 . - 483 1 'ZR -MC -C ©30CD 981 981 1 _0 -MC-C ©75CD 175 0 DEVICES=110 1 TOTAL mA=1 8031 14 221 19.481 8031 'Total Wire Resistance ( R ) 1 1 (WL* 2 )*(R/ft) 1.14 Total Device Load, Amps (I) (Total Cct Load) 0.80 1(E= I* R) 1 0.92 1Voltage Drop ( E ) EOL Voltage 20.4 - E) 19.48 0 ISET-MC-C ©16CD 1 611 01 0 SET -MC -C ©30CD 111 0 1 SET -MC -C ©75CD 1 2001 2001 2 2 SET -MC -C ©65CD ' _: „ 264 ' 528 , 01ZR-MC-C ...s,,..A110CD 1 2591 01 ,.i 6 ' ZR -MC -C ©1' 5CD 69 414 • 0 1ZR-MC-W ©15CD 1 641 01 - ' 0 ZR -MC -C ©75CD . . 176 - - , 0 DEVICES=19 TOTAL mA=1 11421 14 204 19.971 1142' . . - Total Wire Resistance ( R ) TOtaf Device Load, Amps (1) iVoltage Drop ( E) EOL Voltage ( WL * 2 )* (R/ft) , 1.05 (Total Cct Load) = 1.14 (E= I * R) 1.20' 20.4 - E) 19.20 SYSTEM CALCULATIONS Notification Appliance Circuit Detail PROJECT: BUCKLE B Panel: XLS-V Date: February 28, 2011 Wire Resistance 2.58 BPS 120VAC, DEDICATED ) (BY OTHERS) S2-1 S2-2 75cd 15cd V-3 1/4-W S2-3 S2-4 15cd 15cd S2-5 95cd V-4 1/4-W S2-6 S2-7 19 70.7V 1/8 1.8 34.2 28 :707V114 3.64 99.12 0 170.7V 1/2 01 o 0 70.7V 1 0 0 DEVICES= 47 TOTAL m A= 133.321 14 947 19.74852915: 133.321 S,V,V Total Wire Resistance ( R ) Total Device Load, Amps (I) !Voltage Drop ( E) 1 1 EOL Voltage S2-8 15cd 15cd 15cd S2-9 95cd V-5 1/4-W EOL S2 S1-1 15cd S1-2 30cd V-1 1/4-W S1-3 S1-4 S1-5 S1-6 S1-7 15cd 15cd 15cd 15cd 15cd SINGLE LINE DIAGRAM S1-8 30cd 15cd 15cd V-2 1/4-W S1-9 S 1 - 1 0 EOL Si Cct Load"013 - (E= I * R) 065j (2014 - E FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1•0 CO 0' 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 IREV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/21/11 2 <<<<< cc 0 w z w co -J z 0 < Z Z C75 Ca cc 0 < wi- W 0 w zzz < 0 CI) < CI) cc z Ca (5)) 0 cc con Er_ 1 - UJ (i) >- ci) (S--CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:02/21/11 BACKROUND PLAN PROVIDED BY: OB NUMBER: 55171 ( SHEET FA -03 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved A ) 1/4 y TO NEAREST EXISTING DATA LOOP ATCHLINE MATCHLINE S1-5 15cd Nc2f YOMRN'Q. TOILET L s,vy—C TOILET S1-4 15cd SNAP rff_ 1 I _ 1-3 5cd - -1- — s- = S1-2 , 30cd V-1 : =-- TO S1-6 ? FROM EXISTIN SPEAKER_STR BE TO HTRI-R f s,v,v TO S1-6 Slm5 30cd = = = S,V,V Si -8 3Ccd V-2 RTU -3 HTR -R TEAMMATE HO F. TTINIG CiM f2( S1-7 15cd RTU -2 R -R S OCI<RO0M TSMI H TO RI -R fEOL r TSM S1-9 I 15cd S o I IT INC I R(OM ii S1-10 EXIT CORRIDOR 15cd V,V r HOKERUN T9 BPS L FITTING I ROOM S2-2 15cd rr- 1 1 sv,v 6 FITTING . , DM FITTING ROO 1‘A S2 3 15 d FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. S2-4 15cd 75cd V-3 II 1 IIII I II I II -+- 11 PAY —17 11 II i L S,V,V S2-5 95cd V-4 TO PAD -3? POWFR SUPPLY 1 11 II 11 11 11 11 11 11 II 11 IL ii II Ii 11 II 11 s,v,v ...1 E S2-6 15cd Fl II INC,: rs, k A S, FIRE ALARM SYSTEM PLAN S2-7 15cd db. FIT INC RC DM II 11 II 11 11 11 11 Ii 1 Ash 1S2c- 51 HI HNC - ROOM S2-9 95cd V-5 EOL S2 -RTU-1- liffR-R1 TSM 1 --F 1- 1743 1ST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS . 1_ <x c. 02/21/11 2 <<<<< co Z co 0 217) < z CC) „en cc o 0 w z 1 z 16 (01< —0 Cc co o < CO W Or; CC CD ‘CALE: DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/21 /1 1 BACKROUND PLAN PROVIDED BY: 1.0E3 NUMBER: 55171 SHEET FA -04 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved GENERAL LEGEND 4EARTHQUAKE BRACING PiPE HANGER —• GROOVED CAP RIGID COUPLING ( UNLESS NOTED ) CAP -4 PLUG g CENTERLINE O HYDRAULIC REFERENCE POINT BOD CENTERLINE PIPE TO BOTTOM OF DECK BOB CENTERI JNE PiPE TO BOTTOM OF BEAM BOJ CENTERLINE PiPE TO BOTTOM OF JOIST FOS FACE OF STUD FOW FACE OF WALL —c Multi -Port Bracket FOC AFF CH R.C. 4 E/C C/C C/E GG TG TxF AIR Mud -lead Sprinkler Drop FACE OF CONCRETE ABOVE FINISHED FLOOR CEILING HEIGHT REDUCING COUPLING OUTLET COUPLING YIELDED OUTLET 'FIT' FITTING END TO CENTER CENTER TO CENTER CENTER TO END GROOVE/GROOVE THREAD/GROOVE (ALSO 'Gr) THREAD/'FH (ALSO 'Fxl') ALL -THREAD ROD ic"" GEILE'{C GYP. . hl . _c t.i1at= f.3 -1P. ,'O. (IDLINGt. ^�.:t :,'-"5 _�; ._,..._.....__ ;T r..._.....�s:172.t!'s�..�a • :3 t.-.-z.-r z^�:- •rr. K,�•:�g __n?w. ..T_-_._,._.�..a-..,. ¢f'...,.'=�:....: �y....:._,�T_>r�_.�..r..v. may._ f�._3,.,..'x- ..F:, _ u I INE Ot: -ARM HEIGHT 'V:ALLS BELOW, PEE, .`:=h iL LIE PLAN 'i - B l.; �tl _1 2 A i a— ti Ed i ;f. 1Y" -s fr GIP. 1:0 COO /2 4; 1 1 t. q ��f,�'5•� -_- z ti. BD. ' 1ILING y /K` 2-2 EXIT 0G111. ON EXIT WALL ABC's,'DOOR LIGHT 1 Corrugated stainless steel hose with stainless steel braid available in 2', 3',4',5' & 6' legnths Adjustable Hub FLEXHEAD I NOU5151E5'1,44 Flexheag Commercial Ceiling Unit T -Dar Calling Installation Model #2024,2036,2048,2060,2072 I:3 Without Comments aAs Noted in Red Per The Attached Letter -!..ese plans have been reviewed by The Tukwila Fire rsvention Bureau for conformance with current City -.dards. Accepta-lcr is subject to errors and .Missions which do nor authorize violations of adopted :..dards and ordinances. The responsibility for the f,auacy of design r-,sts totally with the designer. .ddltioris, deletions or revisions to these drawings after -nis date will void this acceptance and will require a i esubrnittai of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. ') te: a— I LI - I By: I 7-10 c EXIT CORRIDOR WITH 9'-O" CEILING GW. BO. 10ELINGw,, 7' I-- PEND. © 9' LID - LINE t HEIGHT WALLS IELO's1', . REF: SATE11 L n PLAN C 2=0 311). 30. CEii. f G --G 112' �;.!'.F.i "^'F.tint ..� ..,T-zPmT-•-�-- -- h,�'`:'�-...N�...�_s ��:.:u=..�•.���»..,�-:sem a.n.4 r_».,.__,;z>;�:ri.=•_��' R (D) 1-b i• . . -- r D 1PJ 2T`YIt2' o ?/24 024.3 1/2' - GYP_ I -IL). CEILING 1/2'- A.F.F.L /-1--1 9'-6 i/ f' Ai.F.('.I{ P-1 _ j- -:), . P.t..1, `;I1F r. t; 9' A' n. 3' ` I .'`i i.i' F E ..-- 1---1- ^e•- -'g ✓+'-r> •-rT.9 .1.<..t ._� a Y -r'- ','�'� -•-4': ^*CIS 4^•r } F 3 z- .:-f- . i. '<`."`�.." s" i'. - :+i'a:?•¢ate-F• e.-�ezw »`z+•e A..?'Fifi>= 4 - _ ,s_. ._..._�zr�. ,,..;re._ _..a„._M....,:,.-,.._..:.,��..,.-e_.�.__.-r_.--._..,....1_,Y.._._....�f'..-•_::-:_. _.r..-,.4�.�, � s.e:�.{•-�,.�. - :.t...._.....__._.1.-,� POT acc TRACK 1,1 CORRUGATED MUM -M7L-7_, tAj 21 ?Jease call: 575-440Z 3 nd give this job 3nd exact address for shut. NOTICE Weld stamps must be inspected before pipe is hung, Do not paint piping prior to hydrostatic test appi l'• 17, CI La di rr 144 Y. UTE: BOTTOM OF TRACKHEAD 10. 'GYP. BD. CEILING —GYP. ED. CLING Legend NEW 1/2" PENDENT SPRINKLER 'FLEX -DROP' EXISTING 1/2" PENDENT SPRINKLER TO REMAIN EXISTING SPRINKLER PIPING NEW PIPING Sprinklers SPRINKLER HEAD LEGEND: PROJECT DIRECTORY TENANT ARCHTTECT PROECT ADDRESS THE BUCKLE, INC. 2407 WEST 24TH KEARNEY. NE 68845 TEL: (308) 235-8491 ATTN: LORI KOEPPE FAX: (308) 238-2415 MICHAEL R. MACK, AIA The Buckle #296 SPACE: E552 2800 SOUTFICENTER MAU. TUKWILA. WA 98188 THE BUCKLE, INC. 3100 E. PANDOL ATIU. AMINGTON, TEXAS 76011 LANDLORD A e 817.701.4819 1/2" 12E115 JONES IIALTSBERSER. 5.6 — SUITE 302 SAN AMMO. 1X 78247 121: (210) 545-1007 ATTN: ALBERT CARO.% Et4GINEER CONTACT: CANYULE BRAKUS 2800 SOUTHCENTER MI TEL: (206) 246-7400 AIA FAX: (210) 545-9517 B 0 TUKWILA. WA 98188 MAIL INFORMATM DR BURDING DEPARTMENT BLACK DANIEL A. REEVES, P.E. 155' SOUTHCENTER OPERATIONS TANAGER: PAT BURNS 2800 SOUTHCENTER MALL TEL: (206) 246-0423 TUKWILA. WA 98188 3100 E Road Mg ad Adtrylan.1X 76011 (617)6334200 FAX 18171633.4152 Wad**. Dana 644016 CITY OF TUKWILA CEPARTMENT Of COIMUNITY DEVELOPMENT 6300 SOUINCENTER BLVD.. #100 ATTI't ALUEN JOHANNESSEN TUKWILA. WA 98188 TIEL: (236) 431-3670 FAX: (208) 431-3885 RA1314 1/2" 1/2" 5.6 APPLICABLE CODES INCLUDE BUT ARE HOT BUCKLE Lamm TO TIM FOLLOWIN SPACE # . E552 GOWRIIING CMS ...../-."--% A. BUILDING CODE: 2009 INTERNATIONAL BUILDING CODE ATEA ' \ 5147 S.F. B. MECHANICAL CODE: 2009 INTERNATIONM. MECHMOCAL. CODE ..................ei C. PIJUMBING CODE: 2009 INTERNATIONAL PUMPING CODE OCCUPMCY 0 0 to D. FIRE & SAFETY CODE: 2009 INTERNATIONAL FIRE CODE CONSTRUCTION TYPE E. TLFPA #13 INSTALIATION OF SPRINKLER SYSTBAS 1/2" BB FULLY SPRINIDED YES 5.6 G. OS.HA H. ELECTRICAL CODE 2008 PLATEINAL ELECTR/CAL CODE CHROME I. ACCESSIBILJTY CODE: 2003 ICC/ANSI A117.1 J. ENERGY CODE: 2006 WASHINGTON STATE ENERGY CODE 7 OCCUPANCY LOAD TOTAL SPRINKLERS = 70 THIS SHEET MTN- LEASABLE SPACE 113TAL OCCUPANT LDAD .. 136 5147 ga. Fr. r Legend NEW 1/2" PENDENT SPRINKLER 'FLEX -DROP' EXISTING 1/2" PENDENT SPRINKLER TO REMAIN EXISTING SPRINKLER PIPING NEW PIPING Sprinklers SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. nE, afa TEMP. QUAN. RELIABLE G4 CONCEALED PENDENT A e R2115 1/2" 1/2" 5.6 — WHITE 155' 27 RELIABLE F1 RECESSED PENDENT B 0 RA1314 1/2" 1/2" 5.6 BLACK BLACK 155' 21 RELIABLE F1 RECESSED PENDENT C • RA1314 1/2" 1/2" 5.6 CHROME CHROME 155' 15 RELIABLE G4 CONCEALED PENDENT 0 0 R2115 1/2" 1/2" 5.6 — CHROME 1.-ij 7 APPROVALS BY: TOTAL SPRINKLERS = 70 THIS SHEET TYPE SPRINKLER SPEC DRAWING A-4 A 1) SPRINKLER PENDENTS IN STOREFRONT WHALL BE CONCEALED TYPE WITH WHITE COVER PLATE B 2) SPRINKLER PENDENTS IN SALES AREA LAY—IN TILE CEILING SHALL BE SEMI—RECESSED BLACK WITH BLACK ESCUTCHEON 3) SPRINKER PENDENTS IN SALES AREA LAY—IN TILE SHALL BE CENTERED IN CEILING TILE C 4) SPRINKLER PENDENTS IN STOCKROOM SHALL BE SEMI—RECESSED WITH CHROME ESCUTCHEON D 5) SPRINKLER PENDENTS IN CORRUGATED METAL SHALL BE CONCEALED TYPE WITH BRUSHED CHROME COVER PLATE A 6) SPRINKLER PENDENTS IN DRYWALL INSTALLATIONS IN SALES AREA SHALL BE CONCEALED TYPE WITH WHITE COVER PLATE A 7) SPRINKLER PENDENTS AT PERIMETER AND NEAR TRACK HEADS (12" OR LESS) SHALL BE CONCEALED TYPE WITH WHITE COVER PLATE 8) MAINTAIN 10" CLEAR FROM TRACK LIGHTING FIXTURES 9) SPRINKLER PENDENTS AT PERIMETER AND NEAR TRACK HEADS (12n OR LESS) SHALL BE 200' GENERAL NOTES SCOPE OF WORK: ADD NEW PENDENT FOR TENANT IMPROVEMENT WORK SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 -280-7 ED. ALL MATRIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED EXISTING SYSTEM HYDRAULICS ARE NOT EFFECTED BY ADDED SPRINKLERS ORDINARY HAZARD GROUP 2 OCCUPANCY — 130 S.F. PER SPRINKLER MAX TENANT SPRINKLER PIPING PLAN r\ 1/Li A 2/9/11 REVISE PER PD. REVIEW 24' FUT Py PAID FEB 1C 2011 TUKWILA FIRE CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 Buckle 0 U TH CEN TER Mal k Store No. 296 Space No. E552 Tukwila, Wasington DATE: 2/11 SCALE: AS NOTED