HomeMy WebLinkAboutPP - 757 SOUTHCENTER MALL - DUKES SOUTHCENTER CHOWDER HOUSE LLC - PERMITS AND PLANS757 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-107 08-F-016 08-S-080 FE FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Dukes Chowderhouse 757 Southcenter Mall Permit No.: 08-S-080 Date: March 19, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 20' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. All references are NFPA 13, 2007 Edition. Fi P31€PtI 12 March 2008 Advanced Fire Protection PO Box 1543 Woodinville, WA 98072 RE: Westfield Mall — Dukes Restaurant Independent Third Party Review — Fire Sprinkler System Tuazon Engineerin% PLLC 4322 NE T Street Renton, WA 98059 425.917.1683 tel 425.917.1705 fax www.tuazon.com As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. It is noted that the sprinkler system modifications shown are to Zone T1 fed from the West Riser Room. The following was reviewed: • Fire Sprinkler Drawings — Sheet 1 dated 2/5/08 • Hydraulic Calculations dated 3/9/2008 • Reference core/shell drawings FP -2, FP -4, and FP -6 • Sprinkler head product data The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Provide restraint of all branchline piping per 2007 NFPA 13 Para 9.3.6, as enforced by the City of Tukwila. 2. Provide oversized escutcheons at sprinkler ceiling penetrations per IBC/ASCE 7 if/as required by the City of Tukwila. It is noted that flexible sprinkler connections have been used in other tenant improvement projects at Westfield as an altemate means to comply with the IBC/ASCE requirement. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or ericatuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING, PLLC Eric P. Tuazon, PE Fire Protection Engineer C arpyFles\IDee 1.7*1620081eA0n.saFYI•WrMdE CUMnel1anaee usaa4lFbreaNat e SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 140.0 20.0 10900.0 139.7 458.7 45.0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 458.7 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 208.7 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) SOURCE 1.0 SOURCE 45.0 208.7 BFI 2.0 44.6 BFO 2.0 37.6 1 2.0 37.5 2 13.0 32.6 3 14.5 31.7 4 14.5 29.7 4A 15.5 26.3 5 15.5 25.8 6 15.5 25.8 7 15.5 25.7 8 13.0 16.3 9 12.0 K= 5.60 15.0 21.7 10 13.0 15.6 11 12.0 K= 5.60 14.4 21.3 12 13.0 15.4 - - - 13 10.0 K= 5.60 15.0 21.7 14 15.0 13.2 •15 12.0 K= 5.60 12.6 19.9 16 15.0 12.0 - - - 17 14.0 K= 5.60 11.2 18.7 18 15.0 11.6 19 12.0 K= 5.60 11.3 18.8 20 15.0 - - - - 11.6 - - 21 10.0 K= 5.60 12.1 19.4 22 13.0 27.1 23 15.0 17.5 24 12.0 K= 5.60 16.6 22.8 25 15.0 - - - - 16.8 - - - 26 14.0 K= 5.60 15.5 22.0 27 15.0 16.6 28 12.0 K= 5.60 15.8 22.3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 208.7 10.400 PL 2.00 PF 0.0 SOURCE 1.0 SRCE 45.0 (N/A) 0.8 140 FTG 2E PE -0.4 BFI 2.0 0.0 44.6 0.0 0.000 TL 72.00 PV Pipe: 2 FIXED PRESSURE LOSS DEVICE BFI 2.0 0.0 44.6 0.0 7.0 psi, 208.7 gpzn BFO 2.0 0.0 37.6 0.0 Pipe: 3 208.7 10.374 PL 44.50 PF 0.0 BFO 2.0 0.0 37.6 0.0 0.8 120 FTG 4ETB PE 0.0 1 2.0 0.0 37.5 0.0 0.000 TL 230.50 PV Pipe: 4 208.7 6.357 PL 12.25 PF 0.1 1 2.0 0.0 37.5 0.0 2.1 120 FTG TCG PE -4.8 2 13.0 0.0 32.6 0.0 0.002 TL 94.25 PV Pipe: 5 208.7 6.357 PL 102.50 PF 0.3 2 13.0 0.0 32.6 0.0 2.1 120 FTG 4E PE -0.6 3 14.5 0.0 31.7 0.0 0.002 TL 174.50 PV Pipe: 6 208.7 4.260 PL 174.00 PF 2.0 3 14.5 0.0 31.7 0.0 4.7 120 FTG E PE 0.0 4 14.5 0.0 29.7 0.0 0.011 TL 187.00 PV Pipe: 7 208.7 3.260 PL 44.25 PF 3.0 4 14.5 0.0 29.7 0.0 8.0 120 FTG ET PE -0.4 4A 15.5 0.0 26.3 0.0 0.040 TL 74.25 PV Pipe: 7A 141.5 3.260 PL 4.25 PF 0.5 4A 15.5 0.0 26.3 0.0 5.4 120 FTG T PE 0.0 5 15.5 0.0 25.8 0.0 0.019 TL 24.25 PV Pipe: 8 64.7 3.260 PL 10.00 PF 0.0 5 15.5 0.0 25.8 0.0 2.5 120 FTG ---- PE 0.0 6 15.5 0.0 25.8 0.0 0.005 TL 10.00 PV Pipe: 9 64.7 3.260 PL 10.00 PF 0.0 6 15.5 0.0 25.8 0.0 2.5 120 FTG ---- PE 0.0 7 15.5 0.0 25.7 0.0 0.005 TL 10.00 PV Pipe: 10 64.7 1.610 PL 46.50 PF 10.5 7 15.5 0.0 25.7 0.0 10.2 120 FTG 5ET PE 1.1 8 13.0 0.0 16.3 0.0 0.142 TL 74.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM.) FL/FT (PSI) Pipe: 11 21.7 1.049 PL 2.00 PF 1.7 8 13.0 0.0 16.3 0.0 8.1 120 FTG 2ET PE 0.4 9 12.0 5.6 15.0 21.7 0.152 TL 11.00 PV Pipe: 12 42.9 1.610 PL 10.00 PF 0.7 8 13.0 0.0 16.3 0.0 6.8 120 FTG ---- PE 0.0 10 13.0 0.0 15.6 0.0 0.066 TL 10.00 PV Pipe: 13 21.3 1.049 PL 2.00 PF 1.6 10 13.0 0.0 15.6 0.0 7.9 120 FTG 2ET PE 0.4 11 12.0 5.6 14.4 21.3 0.146 TL 11.00 PV Pipe: 14 21.7 1.610 PL 12.00 PF 0.2 10 13.0 0.0 15.6 0.0 3.4 120 FTG ---- PE 0.0 12 13.0 0.0 15.4 0.0 0.019 TL 12.00 PV Pipe: 15 21.7 1.049 PL 5.50 PF 1.7 12 13.0 0.0 15.4 0.0 8.0 120 FTG 3E PE 1.3 13 10.0 5.6 15.0 21.7 0.151 TL 11.50 PV Pipe: 16 76.9 1.610 PL 42.00 PF 12.9 5 15.5 0.0 25.8 0.0 12.1 120 FTG 4ET PE 0.2 14 15.0 0.0 13.2 0.0 0.195 TL 66.00 PV Pipe: 17 19.9 1.049 PL 5.50 PF 1.9 14 15.0 0.0 13.2 0.0 7.4 120 FTG 2ET PE 1.3 15 12.0 5.6 12.6 19.9 0.129 TL 14.50 PV Pipe: 18 57.0 1.610 PL 10.00 PF 1.1 14 15.0 0.0 13.2 0.0 9.0 120 FTG ---- PE 0.0 16 15.0 0.0 12.0 0.0 0.112 TL 10.00 PV Pipe: 19 18.7 1.049 PL 2.00 PF 1.3 16 15.0 0.0 12.0 0.0 7.0 120 FTG 2ET PE 0.4 17 14.0 5.6 11.2 18.7 0.115 TL 11.00 PV Pipe: 20 38.3 1.610 PL 8.00 PF 0.4 16 15.0 0.0 12.0 0.0 6.0 120 FTG ---- PE 0.0 18 15.0 0.0 11.6 0.0 0.054 TL 8.00 PV Pipe: 21 18.8 1.049 PL 5.00 PF 1.6 18 15.0 0.0 11.6 0.0 7.0 120 FTG 2ET PE 1.3 19 12.0 5.6 11.3 18.8 0.116 TL 14.00 PV Pipe: 22 19.4 1.610 PL 4.00 PF 0.1 18 15.0 0.0 11.6 0.0 3.1 120 FTG ---- PE 0.0 20 15.0 0.0 11.6 0.0 0.015 TL 4.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 23 19.4 1.049 PL 7.50 PF 1.7 20 15.0 0.0 11.6 0.0 7.2 120 FTG 3E PE 2.2 21 10.0 5.6 12.1 19.4 0.123 TL 13.50 PV Pipe: 24 67.2 3.260 PL 7.75 PF 0.2 4A 15.5 0.0 26.3 0.0 2.6 120 FTG 2ET PE 1.1 22 13.0 0.0 27.1 0.0 0.005 TL 47.75 PV Pipe: 26 67.2 1.610 PL 42.00 PF 8.8 22 13.0 0.0 27.1 0.0 10.6 120 FTG 2ET PE -0.9 23 15.0 0.0 17.5 0.0 0.152 TL 58.00 PV Pipe: 27 22.8 1.049 PL 4.00 PF 2.2 23 15.0 0.0 17.5 0.0 8.5 120 FTG 2ET PE 1.3 24 12.0 5.6 16.6 22.8 0.166 TL 13.00 PV Pipe: 28 44.3 1.610 PL 10.00 PF 0.7 23 15.0 0.0 17.5 0.0 7.0 120 FTG ---- PE 0.0 25 15.0 0.0 16.8 0.0 0.070 TL 10.00 PV Pipe: 29 22.0 1.049 PL 2.00 PF 1.7 25 15.0 0.0 16.8 0.0 8.2 120 FTG 2ET PE 0.4 26 14.0 5.6 15.5 22.0 0.156 TL 11.00 PV Pipe: 30 22.3 1.610 PL 8.00 PF 0.2 25 15.0 0.0 16.8 0.0 3.5 120 FTG ---- PE 0.0 27 15.0 0.0 16.6 0.0 0.020 TL 8.00 PV Pipe: 31 22.3 1.049 PL 4.00 PF 2.1 27 15.0 0.0 16.6 0.0 8.3 120 FTG 2ET PE 1.3 28 12.0 5.6 15.8 22.3 0.159 TL 13.00 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 49040769 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.100 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 12.1 ft/sec at pipe 16. DATE: 3/9/2008 C:\HASS78\DUKES.SDF SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 JOB TITLE: DUKES (4) PIPE FITTINGS TABLE Pipe Table PAGE: A Diameter (in) 1.049 1.610 PAGE: B Diameter (in) 3.260 4.260 6.357 10.374 PAGE: D Diameter (in) 10.400 Name: STANDARD.PIP MATERIAL: S40 HWC: 120 Equivalent Fitting Lengths in Feet E T L C B G A D Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 4.00 8.00 2.00 9.00 6.00 1.00 10.00 10.00 MATERIAL: THNWL HWC: 120 Equivalent Fitting Lengths in Feet E T L C B G A Ell Tee LngEll ChkVly BfyVly GatVly AlmChk 10.00 20.00 7.00 22.00 14.00 1.00 18.00 13.00 26.00 8.00 29.00 16.00 3.00 26.00 18.00 38.00 11.00 40.00 13.00 4.00 35.00 26.00 59.00 19.00 65.00 23.00 6.00 44.00 MATERIAL: DIRON HWC: 140 Equivalent Fitting Lengths in Feet E T L C B G Ell Tee LngEll ChkVly BfyVly GatV1v 35.00 80.00 26.00 88.00 30.00 8.00 NOTES (USER): N NPTee 80.00 N NPTee 5.00 8.00 D N DPV1v NPTee 18.00 20.00 26.00 26.00 35.00 38.00 44.00 59.00 DATE: 3/9/2008 JOB TITLE: DUKES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 C:\HASS78\DUKES.SDF E 04 to E E Di G. L L o 0 W N �V U 0 3OO L • >on M Q IAN = CO r >` o Z IA It V1 UN G.r1:1 Ur • LI,N�=W Wa a0 to ci a •r NIA •r NE r—Q.•>71AU W .C1 N G. L {•i rd 1.0 L = Vf r1.O.rN 0 >> 1 O V) N > rn w it Q 1-1 ce er Q oo 20.00 psi Flow: 1 O 0 0 0 m V' v -I r1 N o O 0 0 oo 0 0 0 N 0 o to cr H H 01.4tp 0 43 w a W Mcrl 0 W 41 CO 0 0 0 0 0 0 0 H 0 0 0 0 Co co O 0 r N 0 0 0 0 0 0 0 r H 1 FLOW (GPM) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES WATER SUPPLY CURVE 144+ 0 \ 132+ \ I \ 1 \ 1 \ 120+ \ 1 I \ 1 108+ \ I \ I \ I \ P 96+ R I \ E 1 \ S 1 \ S 84+ \ U I \ R I \ E 1 \ 72+ \ ( 1 \ P I \ S 1 \ I 60+ \ 1 \ 1 I \ 48+ \ X 1 1 36+ I \ 1 1 24+ LEGEND 1 "* <-20.0 psi @ 10900 gpm 1 X = Required Water Supply Flow Test Point 1 45.02 psi @ 458.7 gpm " 12+ 0 = Available Water Supply 1 139.66 psi @ 458.7 gpm " 0++-+---+----+ + + + + + + 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) 1. *[SCO / Fire & Security R-102 RESTAURANT SYSTEM NOZZLE COVERAGE SUMMARY SHEET •, ANSIJLI Appliance Nozzle Type Flow Points Width (In) Max. Side Length • (In) Max. Side Multiple Nozzle wo/Drip Board Area Sq. In. Multiple Nozzle w/Drip Board Area Sq. In. Min. Nozzle Ht. (in) Max. Nozzle Ht. (In) Fryers without drip boards Split or No Split Vat 230 2 14 15 — — 27 - 47 245 2 14 15 — — 20 27 Fryers without drip boards 4 Non -Split Vat jONLY) 290 2 19.5 19 — — 13 d ' 16 , 3N 3 19.5. 19 — — 21 34 , 3N 3 18 18 — — 25 35 Fryers with drip boards Split or No Split Vat' 230. 2 14 21 210 _ 294 27 47 245 2 14 21 210 294 2Q 27 Fryers with drip boards' Non -Split Vat (ONLY) 290 2 19.5 25 3/8 370.5 495 13 , 16 3N 3 19.5 25 3/8 370.5 495 21 34 3N 3 18 , 27 3/4 ' 324. 497 25 35 Tilt Skiilet/Braising Pan 2 Coverage Exception limitation are based on fryer sizes including the drip boards. Tilt Skillets and Braising may exceed the maximum of 6 sq. ft. ' Range Without back shelf With back shelf Without back shelf With back shelf - . 1N 1 12 32 — — 30 40 1F 1 12 28 — — 30 50 1F . 1 12 28 — — 40 48 245 2 24 28 — — 40 • 50 260 2 24 32 — — 30 40 260 . 2 12 32 — — 30 40 2 x 290 4 36 28 - — 15 20 Griddle : . • 1 W1 NSS 1 36 30 — — 35 40 290 2 30 24 — — 30 50 260 2 48 30 — — 30 50 290 2 48 30 — — 20 .30 2120 2 48 30 — — 10 20 Chain Broiler' (Overhead Protection) 2 x 1W 2 34 30 — — 10 26 Chain Broiler (Horizonte) Protection) 2 x 1N 2. 31 43 • -- — Front edge; above the chain 1 in. - 3 In. Char Broiler. Gas -Radiant Electric 1 W1 NSS 1 • 24 36 — — 15 %.. 40 1 N/1 NSS 1 20 34 .. — — 20 50 Lava -Rock 1 N/1 NSS 1 13 24 — — 18 35 Natural Charcoal' 1 W1 NSS 1 12 24 — — 18 40 Lava -Rock or Natural Charcoal' 3N 3 24 30 — — 14 40 Wood Fueled' 3N 3 24 30 — — 14 40 Upright Broiler 2 x 1/2N 1 30 32.5 Front bdge; above the grate Salamander Broiler 2 x 1/2N 1 30 32.5 — 1N 1 16 29 — _ — — 1 N nozzle location to be on the vertical edge 6 to 12 in. in front and 0 to 12 in. above the top of broiler Internal Chamber 1N 1 16 29 — — 6-12 in. above either end Wok 3.75 to 8 inches deep 260 2 14 in. to 30 in. diameter — — 35 45 3 to 6 inches deep • 1 N/1 NSS 1 11 In. to 24 in. diameter — — 30 40 For multiple nozzle protection of single fryers, see' detailed Information on pages 4-10 to 4-11 of manual. 2 See Figure 1 for nozzle location. ' Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm); and not less than 60% of intemal broiler size. ' 4 in. (102 mm) maximum fuel depth. 6 In. (15 cm) maximum fuel depth. FILE 4 4 ` 'IMOI Fire & Security' R -102 -RESTAURANT SYSTEM NOZZLE COVERAGE. SUMMARY SHEET • Duct Plenum -64n w Nozzle TypeMax.ax.Side Flow Width (In) Length (In) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height (In) Max. Height (In) loft •.tot .-: i e`$an'.'` ..., .-. -._ ..:-- � : w 1 ,:-.;...... See Manual for more detail 1267 - 0 iii. - 6in. from end of plenum • 2 - 41; Perpendicular Protection Single Bank 1W/1100 1 48 48 See Manual for more detail 1 20 Horizontal Protection V Bank 2 x 1N 2 48 120 0 in. - 6 in. from end of plenum 2 4 . Horizontal Protection V Bank 1W/1100 1 48 72 0`in. - 6 in. from end of plenum 1/3 the height of filter Perpendicular Protection V Bank 1W/1100 1 48 48 See Manual for more detail 1 20 • Duct Nozzle Type Flow Points Perimeter (In) Diameter (In) Nozzle Placement (See Manual • for More Detail) Duct Length (in) Single Nozzle 1 flow nozzle 1100 1 50 16 See Manual for more detail Unlimited ..:. I0 l9; hiozzIe.2 H441- _ le. .. . 2W 2 10031 7/8 See Manual—for more detail Unlimited Multiple*Nozzle 2W +1100 3 135 48 See Manual for more detail Unlimited Multiple 2W Nozzle 2W — >135 >135 See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245•nozzle, Part No. 419340, is the only approved nozzle for overlapping (zone) protection. Appliance Type Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Panfri t Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Char -Broiler Electric Char -Broiler -' See Figure 1 tor nozzle location. Maximum. Cooking Hazard 34 in. (864 mm) Deep x 5.8 sq. ft. (.54 sq. m) 30 in. (762 mm) Deep x Unlimited Length 28 in. (711 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 in. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 in. (864 mm) Deep x Unlimited Length 32 in. (813 mm) Deep x Unlimited Length 32 in. (813 mm) Deep x Unlimited Length (4 in. (102 mm) Maximum Fuel Depth) 32 in. (813 mm) Deep x Unlimited Length (12 in. (305 mm) Maximum Fuel Depth) 36 in. (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length TYCO SAFETY PRODUCTS, ONE STANTON STREET, MARINETIE. WI 54143.2542 COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-6 IN. (0-15 cm) 111 If 1I I I 1 ZONE 40-45 IN. (1-1.1 m) I ZONE CENTER LINE 006927 l=1faUFtE`1 ` 715-735-7411 Form No. F-2005010 02005 Ansul Incorporated Utho In U.S.Arf SECTION IV — SYSTEM DESIGN ► UL EX. 3470 ULC CEx747 Page 4-34 7.1-98 REV.4 KNK AND CARTRIDGE REQUIREMENTS Qnoe the hazard analysts Is completed and the total nozzle flow numbers are established, the quantity and 'size of agent tanks and cartridges needed to supply the nozzles with the proper volumes of agent at the proper flow rates can be determined, For cartridges used In the regulated release mechanism, flow capacities, tank quantities and sizes, and regulated release cartridge options are given iri the table below. Total Quantity and Regulated Release Flow Size of Cartridge Options Numbers' Tank(s) Nitrogen Carbon Dioxide 1 — 5 (1) 1.6 Gallon LT 20-R (7032) 101-10 (15850) 6 — 11 (1) 3.0 Galion LT 30-R (5373) 101-20 (17492) 11 — 16 (1) 1.5 Gallon Double (73022) 101-30 (15851) (1) 3.0 Gallon X�1,11,, 16 — 22 (2) 3.0 Gallon Double (73022) 101-30 (15851)11A When one or more regulated actuators are used, the following tank and cartridge combinations apply for each regulated actuator: Regulated Actuator Regulated Actuator Tank(s) Cartridge (1) 1.5 Gallon (1) 3.0 Gallon (1) 1.5 Gallon and (1) 3.0 Gallon (2) 3.0 Galion LT 20-R or 101-10 LT 30-R or 101-20 LT -A-101-30 or 101=30" LT -A-101-30 or 101-30** _mor exoepllons to maximum Mow numbers, esti Distribution Piping Rtiqulremenls toi 1.ti OW' and 3.0 gallon systems In Ibis Section. For higher total flow numbers (23 to 110), multiple cartridges and regulated actuators are required as shown in the System Selection Guide In Section IX — Appendix. ACTUATION GAS LINE WITH AN LT -20-11, LT -30 -FL 101.10 OR 101.20 CARTRIDGE MAXIMUM LENGTH OF 20 FT. (0 m), MAXIMUM NO. OF FITTINGS 0 'ANSULAUTOMAN' REGULATED RELEASE ASSEMBLY ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS This section contains the guidelines for Installing the actuation and expellant gas lines between the regulated release mechanism reg- ulator, each regulated aotilator regulator, and each agent tank. These limitations should be considered when selecting the com- ponent mounting Iocatione. r Actuation Gas Line — 6 to 6* Tanks Maximum 8 Tank maximum reflects the utilization of 3 tank regulated actuators. 1. Use only 1/4 in. Schedule 40 black Iron, hot -dipped galva- nized, chrome -plated, or stainless steel pipe and fittings. 2. The actuation gas line piping is Installed from the regulated release mechanism to each regulated actuator connected within the system. The total length of the actuation gas line from the regulated release assembly to the regulated actuator assembly(ies) must riot exceed 20 ft. (6 m) when using an LT -20-R (Part No. 7032), an LT 30-R nitrogen cartridge (Patt No. 6373), or a 101-10 (Part.No. 16850) or a 101-20 (Part No. ► 17492) carbon dioxide cartridge. See Figure 73. REGULATED ACTUATOR ASSEMBLY EXPELLANT GAS LINES NOT INCLUDED IN ACTUATION GAS UNE LENGTH TOTALS REGULATED ACTUATOR ASSEMBLY REGULATED ACTUATOR ASSEMBLY FIGURE 73 000775 i A LJ e Is =p3 fag U W Pigg 113 F. S d • • • • • • . • • • • •••• • • • • • • • • • • • • • • • • • • • • 8 Id LI IM W 111 W 1111 w MI 111 • • t g ffi 1 8 • j § �jj -J = O.rI- §< czo0 �4k $) u / 4 FT. HOOD 12X16" DUCT 360* FUSE LINT{ \)\ e }j\ \} M\ DUKES CHOWDER HOUSE GAS SHUTOFF \ e- :R. iAi | , k ] 0 @ = 2 0ct ■ ■ o/ / o _c en 0) 2k 030 f 03 0 7 01 03 5 - E \/\ 133 > CD § F o_ u± -R /\ S k I {§ 3 Ecs E k].0 � CI 73 C 1 20/ La.=/A < 2: II R` 0 z / ) -c E k k / • JAN -18-2008 02:48P FROM: TO:5754439 P.2 SECTION L; - APPENDIX UL EX, 3470 ULC CEx7; 17 Page 9-1 10- I -02 REV. 5 tl SYSTEM SELECTION GUIDE Note: System options do not cover all conceivable 3riations.They are listed here as a general guideline to show the mc st common type arrangement for multiple systems, Based on certair system designs utilizing manifolding, non-manifolding, 3 -tank sys ems, etc., other tank/cartridge combinations can be designed. The cc mbinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizii ig 12 flow and 6 flow systems when appropriate. *Total Flow No,* 1-5 6-11 12-16 Tank Type of Quantity System 1 Single Single Type of 11 ware 1.5 G al. Reg. Release 3.0 G al. Reg. Release 2 Double 1.5 C al. Reg. Release 3.0 C al. Additional Tank 17-22 2 Double 3.0 C al. Reg. Release 3.0 C al. Additional Tank 23-33 3 Multiple 3.0 C al. Reg. Release 3.0 C al. Reg. Actuator 3.0 C al. Additional Tank 23-27 3 Multiple 1.5 C al. Reg. Release (Optional) 3.0 C al. Reg, Actuator 3.0 C al. Additbnal Tank 28-33 3 Multiple 3.0 C al. Reg. Release (Optional) (2) 3 0 Gal. Additional Tanks 34-38 4 Multiple 1.5 C al. Reg. Release 3.0 C al. Reg. Actuator Dout le 3,0 Gal. Tank Box 1.5 C al. Reg. Release 3.0 Cal. Additional Tank 3.0 C al. Reg. Actuator 3.0 C ai. Additional Tank 34-38 4 Multiple (Optional) 39-44 4 Multiple 39-44 4 Multiple (Optional) 45-49 45-49 (Optional) 3:0 C al. Fleg. Release 3.0 c sl. Reg. Actuator Dout le 3.0 Gal. Tank Box 3.0 (Idl. Reg. Release 3.0 (gal. Additional Tank 3.0 C gal. Reg. Actuator 3.0 (gal. Additional Tank 5 Multiple 1.5 (lal. Reg. Release 3.0 (gal. Additional Tank 3.0 (lal. Reg. Actuator Doul le 3.0 Gal. Tank Box 5 Multiple 1.5 (Lal. Reg. Release ' 3.0 (lal. Reg. Actuator 3.0 (tal. Additional Tank 3.0 (ial. Reg. Actuator 3.0 (Lal. Additional Tank Carbon Dioxide Cartridge Required 101-10 (423439) 101-20 (423441) 101-30 (423443) 101-30 (423443)** 101-20 (423441) 101-30 (423443)*** 101-10 (423439) 101-30 (423443)*** N/A Nitroge n Cartrid 1e Required LT 20-F ; (423429) LT -30-f ; (423435) Double (423493) Double (423493) LT -30 -fl (423435) LT -A-1(1-30 (423491) LT 20-f I (423429) LT -A-1111-30 (423491) Double (423493) 101-10 (423439) LT -20-11 (423435) N/A LT -A-11)1-30 (423491) 101-30 (423443) 101-30(4234443)"' 101-20 (423441) N/A 101-30 (423443)** 101-30 (423443)*** 101-30 (423443) N/A 101-10 (423439) 101-30 (423443)*** '101-30 (423443)"' Based on 6 Row numbers for a 1.5 gel. system and 11 flow r umbers k r a 3.0 gal. system. " 11 tanks are manlolded, only a -double tank" nitrogen cartridge Marl N 1.423493) can be used. -'- If Lanka are manflolded. either an LT -A-101.30 nitrogen carol Sia (Part go. 423491) or s double tank cartridge (Part Na. 423493) can be used. ► Double (423493) LTA -1111.30 (423491) LT -30-11 (423435) LT -A-1 )1-30 (42349i) Doublt (423493) LT -A-1 )1-30 (423491) Doublt; (423493) LT -A-1 )1-30 (423491) LT -20- I (423429) LT -A-1 )1-30 (423491) LT -A-1 )1-30 (423491) [] Without CD., orients As.. P3 1 r nese plans hal ° Prevention Bi standards. i - omissions + .. ' stanaaras adequacy Additions, u. .. i cgs atter !, the date will quire a 1 resubmittal or . . 4 _ ,... subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: I - o O By: klfv\ 1 -I — E1ed-ri(gt .k Shvh,+ qs Wel( as cr.5 M ci ke -up A *l r -k 5i+. " U.L. G e4-60 t Into.1-Vv om . Because of increaF^ri rlemand our inspectors' schedules are boo!:aci 3-7 days ahead. Therefore, you will r: to call 206-575-4407 or em ii fireinsprequestPci.tuiv,A!i1a,wa.us fo schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. UKWILA FIRE DEPARTAi$ Please call: 575-440Z and give this job l No. 03-F °/ and exact address for shut. ,l.wn or restoration approve. D U K E' S CHO . DER HOUSE FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 SYSTEM CALCULATIONS (GENERAL) FA -04 FIRE ALARM SYTEM FA -05 CONCEPT 5 WESTFIELD SOUTHCENTER MALL SITE PLAN WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H ,D❑❑R HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P • DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD ##12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR. #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO 1414 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V 1114 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUrr FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY, HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT:. AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO'ONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING; WHICHEVER 1S LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION _ FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN . ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2002 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (11., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2002 A.6.4.2.2.2 A GOAL OF 6.4.2:2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 1 12 3 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT 1FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE WITH RELAY HTRI-R SIEMENS • 4S DEEP VERIFY IN FIELD T -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD 1 HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED • VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11. BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM -1 MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-1 1 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING gL C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT.. TO BOTTOM ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. 4 C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1 -1 /2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. • TO BOTTOM IBbwp FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY M R-201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FATC FIRE ALARM TERMINAL CABINET F.B.O. F.8.0. F.B.O. VERIFY IN FIELD FA JB❑X JUNCTI❑N BOX F.B.O. F.B.O. • N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD DR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A r> 1 ACCEPT ❑ without Comments As Noted In Red ❑ Per The Attached Letter !hese plans have been reviewed by The Tu! wita Fire Prevention Bureau for conformance with current city s >>dards. Acceptance to errors and is which do not authorize violations of adopted and cr-cJ:nances. The re ponsibi ty for the ,i _',._ ,,r; re_._ tote; y with the designer. it.. - =s, cies sio, s or revisions `;v hese drawings atter voic! accept3nce ry.nd 1"til require e r€ c'.>rviz,:-AUrawin gsforSubsequentapproval. Fir,_, z..,. =�: <ce is ub]ect to fe'S test and inspection by The Tu: if=`r :- Prevention Bureau. ' Date: 9- 7- 08 By: 1 /`'t 7 1 TUKWILA FIRE DEPARTMENT ;1 Please call: 575-440Z - _ and give this job and exact address for shut' .` Town or restoration approv 4I NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement,of Acceptance Testing of aT*ffiedAlarm and Detection Sy�ss Failure of test will f BIt in a Re -ins jpvnd termination h,ng. //7z/ r ri.ht 2006 b Guardian5ecurif Sys ems, -Inc. All R. his Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS DESCRIPTION C CCC O SCALE:;; rTh z z 3 0 0 z C z E t1 (j J DRAWN; BY:;,., (.ANDERSON DESIGNED, BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: 'JOB tyr:- UMBER: i,.SHEET - JK)4A,1 I toacov-f- de vic-c oN, FA sv4o. die) c4k los•c.4,k'ev, NrFi4 2oo.e dv;4-,,/,ti . r THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE KITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WOE. SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AIR DUCT 6-10 DUCT EQUIVALENT ______ DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC DUCT DETECTOR LOCATION 1 END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 --0 0 0 HTRI—R 010 STATUS LED 0 N.O. r- 0 COM 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 p TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING----•\ TUBE INLET SAMPLING—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE NONE )-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE .(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) END OF LINE � U_ DEVICE (3.6K 1/4W) SUPERVISED RELAY CONTACTS SWITCH (4.0A @ 125VAC) GROUND (4.0A @ 30VDC) 27 VDC 3.5 nA DURING POLLING 10 OHMS 200 FT. (18 AVG) 0.02 uF 0.04 uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. Ie I TBI 6 1.2.34 -;56 - HCP TB2 ee 6 5 4 3 2 1 i 0 0 0 0 HTRI-D OSTATUS LED CO 0 n NOT USED 0 END OF LINE DEVICE 0 i 3.6K 1/4W) O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABa SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 GND N AC O X00 El 0 0 PAD -•3 0 00 O . INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX • 1+ 1--.1 2+2— 2 NC C NO + — + .— + — + — + — . 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 UPERVISED SWITCH FRONT VIEW ./ NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE ,! DEVICE LOOP !, 0 0 [FROM XLS CONTROL PANEL OR (+), PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) C'V' CABLE> 470 OHMS EOL T M-1 O o: • Lgclgco TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE ( STROBE (-) SPEAKER (c (-) 0 0 (STROBE 0 O EARTH GROUND -2,(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE (+) (-) STROBE SPEAKER 0 SPEAKERISTROBE AND STROBE VA (RING LABEL SCALE "SPEAKER STROBE • OR STROBE ONLY 4S DEEP BOX... W/ 1-1/2". EXTENSION- RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER1 TEMPERATURE +32' F {0' C TO 100' F (30' C) HHUMIDITY; O- RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POMO SOURCE DATA IN (-) DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN MIEN USED IN CONJUNCTION YelEi IY.ICT HOUSINGS AD -11P OR AD-11XPR 03-11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL BSCALE TO NEXT DEVICE (-) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID —\ SPEAKER SUPPORT TILE— BRIDGE 7--4' SQUARE DEEP BOX -- WITH 1-1/2' EXTENSION N. /--- CEILING MOUNTED ----N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON CEILING FLEX ' JUNCTIC[IN BOX -- MOUNTED AaAINST CEILING SUPPORT / / / 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECTOR--= SMOKE DETECTOR MOUNTING SCALE=NONE of SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS DESCRIPTION 0 Z W _ c_ WVSG W aO o 65 L.1' ig '2„=, (:)!5'.6i< J.. wcc 0 EE' 1E55 3.. ~ E- :2) 0 c - : 0) U W %� CALE: /8"=1' DRAWN: BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: ..OB NUMBER: SHEET ..J FA -02 � 11 is eT 1 FA JBOXR---`' D,P 2V,S keg = 112 Freezer 70 x .33 = 93 Cooler 125 x 1.33 = 166 rgriAnt-AurTma--e-Ffsi -4100E-IYIT'D /26 ( 44 (50 r -A. I I 52 1 k108% 0.27) '1282 c129.n. v.." ,---- -, 1 / I \ I % I 1 ----- --- ------ -----21, I ; 1 \ y ------- -t—.--.:3- ---- ., ‘ • 1 1•1111...1, \ % ___ /I 1 1 \ \I„„ sf----:2------ r • -- 1 1111 ----., . I di' 1111 1 1 l\ I 1 t/ /--..''`.. I k A .. II, x -.---. / .., I 1 \ 1 / 1 \ I A ':"-. \ I \\\1 / .' . A n , , ‘ • I / ‘ 1 1, f.:3-'-"------'- 44; 14 v- 1141 'It- .,,,--- c,.... , ,, \ ,o,ti \ \-) 1 ... ‘r\v.7—'/A1-E—N-:S:E—S-11R)0, M\- .7 ... LKL,2j 1 iwz.1 I WWW4 : -T-11:11- _1=1:71 1.17111:1LJLJ - -1=111-1 2V, ffj pri.vATE DINING 013 LJLJ LITI ) 111 • /Th t ; :=R;44T1.4;,:a 2V,S 30 48V I •4::t rJNI0 012 A 1 \ / I ; \ \ Ak.AIING •-__ Pr -Z1.. DINING 93,1 1 15 L 2F f L L v,s Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F) CO 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS DESCRIPTION LiJ • w „_co c1:3 2 cc z CE w < 0 W o (1) >O CC Z (j) 5 w< o < () [LI LN60 /SCALE: 1 /8"= 1 DRAWN BY: [ANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: JC)B NUMBER: SHEET . a :.:•:.:•:.:•:•:•:•:•:•:•:•:•:410:40:•:07.0:•:•:•:•:•:•:•:•:11,:•:•:•:•:•:•:•:•:•:€11,:•:•:•:•:•:•:•:O:4:41,:1144:41:•:•:CCVAKCCO:•:•:01:10:•::•:•:10:•:•:•:11:•:11.:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:40:4,:•:•:41:•:•:•:•::•:•:•::•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:97.• 1074:14:•74:•:40:•:•:',..:•:•:* •:•:€1.7.*:•:•:•:41*,0:4:4:10:•:•:•:€•:•:•79...... 2;•••:41,11".;9;,•::4 r...............................T............................................".......T.,....."...................................."10.1, ;446.4.4eire•*or. .b"."••;%...W.i.W40••••nee*.W.V.Wini."*"•-•"46".'Nee'iriew."*"46"ele•"404.4.W•ediara*.ebW4.*dbnine46.4•4:•".Venir ;* 4.••••••• 1 ....,... ... , , .... n .... ....4 ,i.. — f% A oki 011111L111111.01011 I i;, 3 1J .41 ,4 6 —I 3_41 ... c3 !IIIININIEIWIIIiIMI ' 1 . ER WALK IN RE1 - -5-0 1-1 514 l'? -b. 7-wlia • I •6;rldli '• .. ‘13 lailiall • ,4/...• • • Mr • • • V, •41 WALK IN FREE *no •••••••••••••;teeeieea.e.W 7.9.191019...9bniitireer. 4N4.14 "AK' t"...••• ,••••• 0.4....•:•:•:•.• • .44.40:0:40:1:•.• 6,16-51,4 IQ .0 RESTROO fi V tcqe, 2435/, CA • (9118)301.5109 FIG. 68 WIDE THROAT TOP BEAM "C" CLAMP WITH LOCKNUT Size Range - 3/S thru 7/8 inch rod. Function - For attachment tC sttuctural shapes requiring wider throat especial'/ under roof with bar joist constn:ction. This clamp may be used in the set screw down pcsiticr: cMy. Approvals - Conforms :0 Manufacturers Stand. ardization Society SP•69, type 19. Finish - Plain and Electro•Galvanized. Order By - Figure number, rod size. and finish. Note - Do not overtighten se: screw. • • : 11:41:•••:•:•:•:•:40:•.•:•:•10:•1•.•.. FIG. 69 BEAM CLAMP RETAINING STRAP Size Range - 3/8 :hru 7/8 inch rod by 4 thru 14 inch length. Materia! - Carbon Steel Function - To offer more secure fastening of beam clamp to beam when denser of movement might be expected. Approvals - UnderuzitersLaboratories listed when used wit:t4Tolco U.L. Listed Fig. 65 and 66 Universal Beam Clamp, Finish - Mii. Galvanized and Stainless Steel. Order By - FiSty'e number, type, length "K, and rod size being used with beam clamp. Note - Minimutn return on Strap: r. • •••••••••4•••467. 7r••.6-4ewe4•&oeA OFFICE II•11.4 I•4 • 0 • OM .4 Nor Ell 'I: ow*11 410"0"dr4e4W410:.11,:•:**9.4,.• •••••,.4 fo, 404 to DINING ROD HOLE STOCK TYPE SIZE S SIZE A FINISH 1 3/8 7/16 16gax1 t Mil. Galv. 17g. -.911-6". 3:6244 _t - 2 5/8 11/16 14gax1•1/4 t M2. Galv. - ' -3 .16 14gax1-1/4 t - 7ffirsak,... C. 3/8 • 7/8 specify 1290x1-1/4 111=1W1111 111111111111111111111111M11111111111111111111111111111111111111111111111111111111111.: MINN Nil EIE!MIIEEIM iiiii1111.0111 04•,.,•,,)•,,„•.„•,; :$ :$ • )i 0 A x A p, ....„ A ..p. ,-, :3 ili 4,, A il • p.... 0,.4 :$ 4 P. t i3 .,_, ...P. :$ p • , .k: 11",iiiA,. A 9:4 t• .41,..•.. 10., ii,, I fr Wei I 74,....4.4 1.1.041 ,4 AAA MA 0.4 1'4•74 7411'4,741.••••••••4 11 MA re" 4.•••••"...04P•VOW4 r•VI A 4/7•70•W•••••V We; 0.4701174.174104 fill ••••••••* 'POW ••••V• 111,••••• 041 1 fGWB 44$ iii 144 A DINING A 4441 -111E1uu v 111111.4114.14M• J4•4 C.;44 rrailli, 111 . • 011 Mi - ACK BAR ENTRY FRONTBAR „roxieva..0:00t0 tile tl• 04, 0.49 (,419 .1 • • HDI Drop -In Anchor • Anchor, setting tool and HMI drill bit form a matched tolerance system to provide reliable fastening • Below Sabo° setting for easy patchwork • Allows for shallow embedment without sacrificing performance Technical Data 0050 materIW •Nom.cmckadconcroto • Ughavolght concrete • Ughmecht concrete over motel deck Anchor material • HOICarbon Stool materla moat» 1110 rociwornents of Al51111050or A1511010 for 11101/4". 3/001181/2" I -101's pr. Alst12L1 4 fix CWIEn and 3/4.1-100s, • Carbon Stew HD paned vath a aloe Men for Cortosion protection In accordance wth ASTM 8633 1.1570111 ype • HOIStalolesa Stool material 0700131110 requirement. of /101 303. Listings/Approvals UL (Underwear Luboratorleo) Coreml No. 7670 • (Fectay Mutual/ Serial No. 22765 ICC -ES (Intemadonel Code ER Report No. 2835 — Coonca) 000111101 0010 COLA (Gay of Lea Angel...) Flapco No. 23709 os.c.aeanronnvill Feoeral Speak:aeon 'Noel • • - :$4 Wee '01r...1•74.Wer re. OZ.:•:•.:411.7.1•14"Xt r.;.•:•:•:•: X.•14,1•ICACIIMICATAK XXX" :$ DAYLIG T CONTROL AR A SEE LI TING/ENERGY CALCS. Carbon Steel Muster Carton 15011 110. Cly Item No 336425 100 3001507 336428 50 3001508 336427 50 3001509 336428 25 256540 336429 25 258541 stainicess Steel Cly 1200 600 300 100 100 Description HD! 1/4" I-101 3/8" HD! 1/2' HDI 5/8' MCI 3/4" Hole 010 3/8' 1/2" 5/6" 27/32' Meetly Carton Hole earn No Oty Item No. 0115 DOSCliptiOn 010 338430 100 339617 1200 80(1/4" (55303) 3/8" 330431 50 339818 800 110( 3/8" (0S303) 1/2' 336432 50 333519 300 HDI 1/2" (55303) 5/6' 336433 25 339820 100 801 5/0" (S5303) 27/32' 336434 25 339621 100 8131 3/4" (S5303) 1" r 522 HO Product Tac Mice, 0611110 116 complete parkmane. as. Embed Anchor Length 1. 1-0/16" 2' 2-9/16" 3-3/16' 111110044. Anal. Length 1' 1-9/16' 2' 2-9/15" 3-3/18' Ufa:1bl° Thread Length 7/1V, 5/8' 11/16' 7/8' Useetle llyead Length 7/16" 5/8' 11/16' 7/8' 1-3/e' Internal 5000/11501 1,00113 Thread 4000 p010071111010' Sze 30115011 /411 51010/1411 570 - sas..„ 3/8" 1115 1250 ,ii.r. 1785 2125_ 5/6" 2920 3250 , /4! 4005 5009', Intemal Traced Soo 1/4" 3/8' 1/21 5/8" 3/4' 5006008008000 4000 psl concroco' Tonafon 611) 5110011 141) , 480 809, 1040 1230 _1540 2790.: 2630 4510 3630 5560 rr 311111; . marECE AAAANNWANAAV.W.A Wthout As Note Per The nese plans have been r Prevention Bureau for co standards. Acceptance i omissions which do not a standaras and °romance adequacy of design rests Additions, deletions or re ornments In Red ttached Letter viewed by The Tukwila Fire formance with current city ubiect to errors and thorize violations of adopted . The responsibility for the totally with the designer. ision o tc: drawings atter this date will void this acr2ptance F,rid will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: Weld stamps must inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FHLPCTHD CF \G PLA\ ' 8' 10' 12' 14' 16' 18' TUKWILA FIRE DEPARTMENT, Please call: 575-4407 and give thls job and exact address for shut. down or restoration approval. Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinsprequest(@ci.tukwilafwa,us to schedule your inspections a minimum of 48 hours in 'advance of the want an inspection. SPRINKLERS We _az, Vbe 4WD. 0 ISSD t55° kg" Vt Korn 1-16ZR, 4 4 IL FIG. 69 BEAM CLAMP RETAINING STRAP Size Range - 3/8 :hru 7/8 inch rod by 4 thru 14 inch length. Materia! - Carbon Steel Function - To offer more secure fastening of beam clamp to beam when denser of movement might be expected. Approvals - UnderuzitersLaboratories listed when used wit:t4Tolco U.L. Listed Fig. 65 and 66 Universal Beam Clamp, Finish - Mii. Galvanized and Stainless Steel. Order By - FiSty'e number, type, length "K, and rod size being used with beam clamp. Note - Minimutn return on Strap: r. • •••••••••4•••467. 7r••.6-4ewe4•&oeA OFFICE II•11.4 I•4 • 0 • OM .4 Nor Ell 'I: ow*11 410"0"dr4e4W410:.11,:•:**9.4,.• •••••,.4 fo, 404 to DINING ROD HOLE STOCK TYPE SIZE S SIZE A FINISH 1 3/8 7/16 16gax1 t Mil. Galv. 17g. -.911-6". 3:6244 _t - 2 5/8 11/16 14gax1•1/4 t M2. Galv. - ' -3 .16 14gax1-1/4 t - 7ffirsak,... C. 3/8 • 7/8 specify 1290x1-1/4 111=1W1111 111111111111111111111111M11111111111111111111111111111111111111111111111111111111111.: MINN Nil EIE!MIIEEIM iiiii1111.0111 04•,.,•,,)•,,„•.„•,; :$ :$ • )i 0 A x A p, ....„ A ..p. ,-, :3 ili 4,, A il • p.... 0,.4 :$ 4 P. t i3 .,_, ...P. :$ p • , .k: 11",iiiA,. A 9:4 t• .41,..•.. 10., ii,, I fr Wei I 74,....4.4 1.1.041 ,4 AAA MA 0.4 1'4•74 7411'4,741.••••••••4 11 MA re" 4.•••••"...04P•VOW4 r•VI A 4/7•70•W•••••V We; 0.4701174.174104 fill ••••••••* 'POW ••••V• 111,••••• 041 1 fGWB 44$ iii 144 A DINING A 4441 -111E1uu v 111111.4114.14M• J4•4 C.;44 rrailli, 111 . • 011 Mi - ACK BAR ENTRY FRONTBAR „roxieva..0:00t0 tile tl• 04, 0.49 (,419 .1 • • HDI Drop -In Anchor • Anchor, setting tool and HMI drill bit form a matched tolerance system to provide reliable fastening • Below Sabo° setting for easy patchwork • Allows for shallow embedment without sacrificing performance Technical Data 0050 materIW •Nom.cmckadconcroto • Ughavolght concrete • Ughmecht concrete over motel deck Anchor material • HOICarbon Stool materla moat» 1110 rociwornents of Al51111050or A1511010 for 11101/4". 3/001181/2" I -101's pr. Alst12L1 4 fix CWIEn and 3/4.1-100s, • Carbon Stew HD paned vath a aloe Men for Cortosion protection In accordance wth ASTM 8633 1.1570111 ype • HOIStalolesa Stool material 0700131110 requirement. of /101 303. Listings/Approvals UL (Underwear Luboratorleo) Coreml No. 7670 • (Fectay Mutual/ Serial No. 22765 ICC -ES (Intemadonel Code ER Report No. 2835 — Coonca) 000111101 0010 COLA (Gay of Lea Angel...) Flapco No. 23709 os.c.aeanronnvill Feoeral Speak:aeon 'Noel • • - :$4 Wee '01r...1•74.Wer re. OZ.:•:•.:411.7.1•14"Xt r.;.•:•:•:•: X.•14,1•ICACIIMICATAK XXX" :$ DAYLIG T CONTROL AR A SEE LI TING/ENERGY CALCS. Carbon Steel Muster Carton 15011 110. Cly Item No 336425 100 3001507 336428 50 3001508 336427 50 3001509 336428 25 256540 336429 25 258541 stainicess Steel Cly 1200 600 300 100 100 Description HD! 1/4" I-101 3/8" HD! 1/2' HDI 5/8' MCI 3/4" Hole 010 3/8' 1/2" 5/6" 27/32' Meetly Carton Hole earn No Oty Item No. 0115 DOSCliptiOn 010 338430 100 339617 1200 80(1/4" (55303) 3/8" 330431 50 339818 800 110( 3/8" (0S303) 1/2' 336432 50 333519 300 HDI 1/2" (55303) 5/6' 336433 25 339820 100 801 5/0" (S5303) 27/32' 336434 25 339621 100 8131 3/4" (S5303) 1" r 522 HO Product Tac Mice, 0611110 116 complete parkmane. as. Embed Anchor Length 1. 1-0/16" 2' 2-9/16" 3-3/16' 111110044. Anal. Length 1' 1-9/16' 2' 2-9/15" 3-3/18' Ufa:1bl° Thread Length 7/1V, 5/8' 11/16' 7/8' Useetle llyead Length 7/16" 5/8' 11/16' 7/8' 1-3/e' Internal 5000/11501 1,00113 Thread 4000 p010071111010' Sze 30115011 /411 51010/1411 570 - sas..„ 3/8" 1115 1250 ,ii.r. 1785 2125_ 5/6" 2920 3250 , /4! 4005 5009', Intemal Traced Soo 1/4" 3/8' 1/21 5/8" 3/4' 5006008008000 4000 psl concroco' Tonafon 611) 5110011 141) , 480 809, 1040 1230 _1540 2790.: 2630 4510 3630 5560 rr 311111; . marECE AAAANNWANAAV.W.A Wthout As Note Per The nese plans have been r Prevention Bureau for co standards. Acceptance i omissions which do not a standaras and °romance adequacy of design rests Additions, deletions or re ornments In Red ttached Letter viewed by The Tukwila Fire formance with current city ubiect to errors and thorize violations of adopted . The responsibility for the totally with the designer. ision o tc: drawings atter this date will void this acr2ptance F,rid will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: Weld stamps must inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FHLPCTHD CF \G PLA\ ' 8' 10' 12' 14' 16' 18' TUKWILA FIRE DEPARTMENT, Please call: 575-4407 and give thls job and exact address for shut. down or restoration approval. Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinsprequest(@ci.tukwilafwa,us to schedule your inspections a minimum of 48 hours in 'advance of the want an inspection. SPRINKLERS We _az, Vbe 4WD. • 0 ISSD t55° kg" Vt Korn 1-16ZR, 4 DATEZ.--03 SCALE atbircia PIPING PLAN & DETAILS B S W,LYITRACE SPACLNG FOR LATERALS AND LO." rVDINALS SHALL BE -Mr AND RM' R.LSPlx'TIVE x.v FOR ALL NEW MAIN PIPING. i-001 (3 3.$4 EMBED LENGTH) FIG. 910 TYPICAL 1Y7 BLACK STEEL PIPE (SO+I4D. 40) (LENGTH NOT TO EXCEED T-01 LATERAL BRACING FOR MAINS rAir FIO.i000 FAST CLAMP 1/2 -HDI (3 1,4'81113E13 LENGTH) FIG. 810__ TYPICAL 1' BLACK STEEL PI (SCHED. 40) (LEITH NOT TD EXCEED T.0") LAT ERAL BRACING FOR MAWS UP TO 4' FIG. 1000 FAST CLAMP S1' HOi (33.44' . LENGTH) FIG. 010 C- TYPICAL I Y.' BLACILSTE,EL PIPE (SCHED. 40} 212 PIPE CLAMP LONGITUDINAL BRACE FOR MAINS a• & B' F10. 010 :ry' •\ TYPICAL ,F7 HO1 (s ihr EMBED LENGTH) 1' BLACK STEEL PIPE (SCHED. 40) 717 PIPE CLAMP LONGITUDINAL BRACE FOR MAINS UP T04' LEAF SPAM CZ3:A122JRATIONANO DTIT7CTATH)■ RFVFOi NBT at>i tnartTTiEn A�2 •1A S.1020tCt S.1O t eAf sTw,Na FIAT T3 MtruAI1 PIN LAM RfOLPAL010A01/6 TIOPTTEiiHEX NUTS I.kTIL t TX I.OtlNC ' /LAX LAra ALEARTHQUAKE BRACE .57p SFOTIIO GDNf 171J KA110N T"g1107,d.,s BOTTOM BEAM CLAMP, ROD, MID ANG ?V 0 } 110. M RETAINING STRAP CY_K NUT RECTO !WAN Ai'AAICLiLIP __. FID. t CO ALL THRCAD ROD Fl0.200 NatUIrTAALE RT HKiOUt TOP BEAM CLAMP. ROD. AND RING FIG. 1000 FAST CLAMP-' 1' BLACK STEEL P' (SCHED. 4f11 12' H TYPICAL (215' FAIRED LENGTH)TYP I410 FIG. 1000 FAST CLAMP RISER BRACE (FOR ALL MAIN RISER DIAMETERS/ FIG.1000 FAST CLAMP FIG. 1000 FAST CLAMP 1' BLACK STEEL PIPE (LCHED.40) 112" HDI TYPICAL (2W 1348EP LENGTH) o*ik! 1 -TYPICAL FIG. 1000 FAST CLAMP RISER BRACE FSG. 1000 FAST CLAMP C'a LATERAL EARTHQUAKE BRACE 1u`r.( K14•11#4cAOCD ORAD P(Pt teen a, on IT LAAWERSAI. SWIVEL SWAY BRACE ATTACUMENT 1440) i+000CONSTRUCT l4v T AVOWS �` FAST CLAMP RISER BRACE T a,TOitAMy EARTHQUAKE SWAYBRACE DETAILS AND COMPONENTS SWAYBRACE LOAD CALCULATIONS PIPE SIZE BRACE SIZE BRACE SPACING LAT LONG ASSIGNED LOAD Obs.) MULTI P LYING FACTOR K .B NFPA 613 TABLE 4-6.4.3.5.3 BRACE TYPE ATTACHMENT TYPE W/ MAX LOAD VALUE (Lbs.) a 8" 4' 3. 214" SCIIA4O 151' SCN.AO I" SCH.4o r SCH.40 1' SCH.40 3Q 40' 40' 40' 40' 80' 80' 80' 80' 80' 2186 2088 1392 1304 1266 Hanger No. 02C Concrete Anchor None an Elam Hanger Number and W Dienemskin Hanger No. 03C Concrete Spike Wean Mara /ismer Miner and WM:tension Hanger No. 05C Concrete Anchor HILTI 3/9' liDt.P AI Rod Shrivel RINI q. Pico ConsInschon COrillt Una of Rpi Note on Pion: ftinger Nurntem and 'A' Dm -arnica Hanger No. 14S Inverted Top Beam C -Clamp wiTh Retaining Strap (Beam) Note ea Nom Hoot Numbortzttl 'A' OnnentIon Hanger No. 03T Pipe/Top Beam C-Clemps /*Top Belem Chimp ot Egad Hanger No. 13S Top Beam C -Clamp with Retaining Strap (Joist) Not* on Mal: Hanger IaLL-ntse and W DimessHi TYPE •B' TYPE "B" TYPE 'B' TYPE "9' TYPE "8' 6/8' BOLT = 2857 SIB" BOLT = 2857 112" BOLT = 1782 112' BOLT a 1782 1/2" BOLT - 1782 P0.010 SWIVEL 1 NAY h ACEF,TTNCI no TOOL FA3TCLAUF DRAT {RA Ci AtThOW2+1 LATERAL EARTHQUAKE BRACE M ACE PIPE 1T RFA0 CO CNt k` O Hanger No. 185 Acqustable Pipe Stand Peon SLUR* We 0-11(*9"Pl Pod bNIP7:14th.) er of Threads - C.13 Base 1.01 Sth 40 Threndon Fest* Roar to CANFmLgrel Pim Hanger No. 07C HUT! Kwik Bolt II Dried Anoka!' t Note on Ram Hanger Rumba: and 'A' Gammon Hanger No. i 5S Inverted Top Beam C -Clamp with Retaining Strap (Joist) Shad 1-Boarn or Bar Joist - Rounded to Nearest Inch Rire Tee B111111 C-Cbierp Or Eqvai Nat* on Pim: Honger-Numboir and 'A' Olmention 1-10.1100 134TAT SPATE ATTACHLiENt STEEL L SEAL SWIY21. SWAY SPACE FiTma SWAY BRACE ATTAC1.1MENT TO STEEL I•BEAAI 1 PIPS Ci.Aote root *WAY SVGA. LONGMIDINAL EARTHQUAKE BRACE 10344,4gEA.D.:12 aRAct Di Di: rval AND ALL Egariaa 2s RATIONS FLEXIBLE COUPLING 1TYP HoLe MR SLEEVE, CHROME ESCUTCHEON."' PIPE SIZE CORE DETAIL THROUGH WALLS AND FLOORS NTS HANGER NO, 175 STEEL SAMMY SCREW AND ROD NOTE PLAN; HANGER NJMIIIER AND 'A` DIMENSION Hanger No. 04T UnIstrut/Top Beam C-Clarnps Inverted or Joist Noto on Pew Hanger Wanner. Dinvansion, Hangar No. 12S Top Beam C-Ctemp with Retaining Strap (Beam) STEEL PIPE HANGER LOCATION DETAIL PIPE SIZE A CI* C STEEL PIPE I ill ' MAXIMUM STEEL HANGER SPACING FOR THREADED LIGHTWALL PIPE IS 17-0" FOR ALL PIPE SIZES HANGER NO. 18S AND ROD --Z PURUN NOTE ON PLAN: HANGet NUMBER AND "A' DIMENSION 1-ianger No. 20S Sammy Xpress f `••-- ma 70 STC33.CCJLwO 0.LAT6 ___.. FIC. IDS ALL THREAD ROD Ina. ac A0wa-r W LL RY43 P.Ati:CA CEILINGS PLATE, ROD AND RING Yk,TA1 D*CRDN w57ALLATICN all4 WAY EARTHQUAKE BRACE !AT le,AL!{.tSf1C C1 LNaPAL MATI,OiLAKA 5RAG T_6900tLd.e RISER ROOM EQUIPMENT 1. RELIABLE 6" MODEL 'G ' RISER CHECK VALVE 2. VITAULIC 6" FIRELOCK #771 GG OS&Y GATE VALVE 3. 2" MAIN DRAIN- DISCHARGE LOCATION TO BE DETERMINED. 4. GLOBE ANGLE VALVE 1" TT 5. AGF TEST AND DRAIN VALVE 2" TT, MAIN DRAIN 6. SYSTEM SENSOR 6" WFD SERIES WATER FLOW SWITCH 7. SYSTEM SENSOR 4" WFD SERIES WATER FLOW SWITCH 8. VICTAULIC FIRELOCK 6" no4 FLEXIBLE COUPLING 9. SYSTEM FDC FEEDS FOR RISER ROOM 'A' AND 'B' 10. RELIABLE MODEL 'G' CHECK VALVE GG FOR FDC 11. 6" UNDERGROUND FOR FDC'S TO FEED 10" PIPE THAT IS TO SUPPLY EXISTING MALL SYSTEMS. TO BE INSTALLED BY OTHERS. 12. UNDERGROUND FOR FDC'S TO FEED NEW SYSTEMS IN MALL EXPANSION. TO BE INSTALLED BY OTHERS. 13. DRY SYSTEM FEED RISER ROOM 'A' AND 'Er. 14. VICTAULIC FIRELOCK 10".#004 FLEXIBLE COUPLING 15. VITAULIC 10" FIRELOCK #771 GG OS&Y GATE VALVE 16. 10" RISER MANIFOLD 17. RELIABLE MODEL 'D' 4° GG DRY PIPE VALVE WiTRIM 18. WILKINS 10" 350 DAG VERTICAL BACKFLOW PREVENTER 19. 10" VICTAULIC #705 BUTTERFLY VALVE 20. 10" SYSTEM UNDERGROUND, TO BE DONE BY OTHERS. 21. 10" SCHEDULE 10 PIPE TO BE INSTALLED DURING MALL EXPANSION TO FEED EXISTING MALL SPACE. 22. VITAULIC 4" FIRELOCK #771 GG OS&Y GATE VALVE 23. RELIABLE 4" MODEL 'G ' RISER CHECK VALVE 24. VICTAULIC FIRELOCK 4" #004 FLEXIBLE COUPLING 25. GAST AIR COMPRESSOR FOR DRY PIPE SYSTEMS Lk MODEL 26. SYSTEM FDC FEEDS FOR NEW 10" IN EXISTING MALL. 27. SPARE HEAD SPRINKLER BOX FOR 24 HEADS WITH WRENCHES 28. HEADER FOR MEANS OF FORWARD TESTING BACKFLOW. INCLUDES HOSE VALVES TO RUN HOSE OUTSIDE TO EXTERIOR ON LOADING DOCK. NOTE: WEST LOADING DRY SYSTEM= 44 GALLONS EAST LOADING DRY SYSTEM= 33 GALLONS -ZONE INDICATOR 7 01.F0 MIL 25 1.1.4A;22 RESCRAINEF1 Prat 2. FOR 14/2* AN22` PIPE AlISHANOAR 011e VIEW OF soAc 'cols ALL s-inun nos /r2.1:0 P' 713 SlinCAS its trTNAvoiA, 011,11171.CO MK) WkNOVI M. 709 AIM 21,4PA TO PCS -TOM 71.6 UPWARD L+CrySitett OF PtP6 Ir OCCURS OVII MG SPRINKLE -RHEA!) FIGURE 25 SURGE RESTRAINER FOS arm Om cmia .Last la PIPE \ a i W'ertlit D 1.010N ALL nift CAD POO LATERAL BRANCFILINE RESTRAINT PIPE CLAPP MR SWAY 141.14-6 LONGITUDINAL EARTHOUAKE BRACE • • AOC SS PAtla ALiea BUTTERBALL VALVE DETAIL - NTS FOR ELEVATOR MACHINE ROOM(S) WEST RISER ROOM -SECTIONAL VIEW MANW EAST RISER ROOM -SECTIONAL VIEW LAA JO/ OA RACE AITA2riikli-e' Vit, 10 :0,4! 111111111111111111// er, .tizing:ippinFire ATTACIati mi -A FIGURE 825 USIDOTA.T WITH °THEIS 301..0.0 SEISMIC SEPARATION ASSEMBLY 1Y,'OR 1W FiRELOCK *DOS RIG) COUPLING SHURJOiNT 14.00a MI awl tiOt. Went EARS TOLICN i'‘,164i1SNSIZEEL PIPE ar ArtIVERILLMIE ITEM. SCHEXILICti ALL OPT TTATE./CALS CAST MOOR PoOTILS 15(44' THREADED RENDE =I, IS ItiftUlt [AIM. ISPACIWG Poo?! • FIG.2001 SWAY BRACE ATTACHMENT 402103 CONtcr.• RUCTION 7..7001 Avg SHURJOINT END-ALL FITTING DETAIL(TYPICAL) • ma 100 T1.111EALI R00 ALLIVST AUL R1742 KAAT.:C.Tt SELF DRILLING ANCNOR, ROO AND RING PTO, Fal SWAT SPACL At TALI4AEAT TO DRAGE, Firm) Fla AA PIPE. CLAW SWAY it R ACE AT TACHILIPNT TO STEEL 1.11Efue Note on Plan'. Henget Mlle.:rand "A' D'o..:ntion WEST RISER ROOM -PLAN VIEW EAST RISER ROOM -PLAN VIEW -414 Iowa DRAWN BY: Martin SokuIski DATE: 08/21/07 PLOT DATE 08/21/07-06:4-3:16 CONTRACT NUMBER 790228 DRAWING FILE NAME SHEET FP 2 OF AID SHEET FP -3 IZEILTJEHMIEICZE3 1:313MBEMIDIUMMUCIMEIE3C3IZID SHEET FP -4 NOT A PART OF CONTRACT/PERMIT 1:21131 CA El LE CZ 111 DEa El ,E1L1NGS -1.1\1A HINE "4011 *44 $owit lutz) tis) co) al= Cat) 41) '4=0 It* Cie ;2124 0 ••t' "S LI? 0 00 00 10 fl 0 CTRICA OM N.)1? OPY PLAN S (A8.3-7) ..;."a 0 10-0-- - 10-0 N N N? •SR \)1 N§ vcs. N 41' ‘ ,14:k$ + 44e, 0. et, - Kti VO,i WI Fal ; !AI q.-11 iskOM m iM a"; YIS 41X 5'4 7,04i ,kite% ,a.f.4 'r.in mot azi la r4.46 tw: a wi 4. ..tio J TO (ABOVE 10 10-0 —424 ALL ST RAGE Li A.F.F LJU ( 10-0 01 . 11 02N0 Et NES HV ONLY r.74 —1— air 11111111411111111111111111 4111E11 - .4 101L*."'Ill OPE(' DEC( 19'0frmmuimmr, Asigegi,=, NOT A PART OF CONTRACT/PERMIT BY TE ANT "KT 11141111111111117 111 '*• 4:11.ga EGRE. RRIDO OPEN TC e?ECK ABOVE— E.: EVATO II :WPM III I PEN TO — ECK ABOVE .12 1 POTENTIA FABRIC CANOP\ BY TENANT -re* .41111g4.1ralitazi.a4 VittAzit LEASE LINE OPEN 7 0 F1)4 Pig IRA op 4,0.01: 0 UTHCENTER EXPANSION Remote Area: 1st Floor - Loading Dock West rat* g055rt CEILINGS BY TENANT lualutropicrxjaztztizzarecrzw, CALCULATION DESIGN CRITERIA: STANDARD NFPA 1 3-2007 OCCUPANCY CLASS Uralnary Hazard II MAX. covePAoE per HEAD 130 DENSITY .20 GPM 1 Fr for 957 Ft, Fr spainKLER Reliable Model F3QR DRY ORIFICE 1/2" WATER FLOW INFORMATION': STATIC 140 NO OM NO STIB E CA REO HIED Rs6iDuAL 20 novv 10900 PSI GPM AT BASE OF RISER. SYSTEM REQUIRES: 528 GPM GT 62 PSt +16-1"A.F.F. ' AI time of Dosion . . • 'RAMP PNY AYpTE10 PR ...SUGGESTED. TO BE FE EXISTING FAIWNG ST •'.PENDING APPROVAL P .AKI; • . . • 4.. • o o o o s .44.1 • Sprinkler Legend MFR./MODEL Reliable F1FR SSU Reliable FIFR SSP r g i A TEMP. ,.... rn t° .... tel 5,2 155°F I ... g.p -.°, ,.. N T,-, 4.10 tl i'zi Er_lill I Lb -42: OR kkkkk SPRAY I tigifoi ( ccg ‘Ti :f -i fi t ..." co Total = 2932 I :.--: :PI: >-- cn >-• m I. hilbisiiimmilillimi k...):K4).k4 hill 11:114.° Pill: A k / co z o 0 rt z o ff Er" (..) fp U.1 0 City of Tukwila Review 4:C CI C) DRAWN BY: Martin Sokulski DATE: 08121/07 PLOT DATE: 08/21/07-07:4246 SCALE: 1/8"= 11-0" co ct) 4-0 anC 4rna 0 co Fire Protection Area '8' Level I CONTRA NUMBER 790228 DRAWING FILE NAME JR -Level 1.cad North SHEET FP -4 OF 21 757 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-107 08-F-016 08-S-080 FE FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Dukes Chowderhouse 757 Southcenter Mall Permit No.: 08-S-080 Date: March 19, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 20' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. All references are NFPA 13, 2007 Edition. Fi P31€PtI 12 March 2008 Advanced Fire Protection PO Box 1543 Woodinville, WA 98072 RE: Westfield Mall — Dukes Restaurant Independent Third Party Review — Fire Sprinkler System Tuazon Engineerin% PLLC 4322 NE T Street Renton, WA 98059 425.917.1683 tel 425.917.1705 fax www.tuazon.com As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. It is noted that the sprinkler system modifications shown are to Zone T1 fed from the West Riser Room. The following was reviewed: • Fire Sprinkler Drawings — Sheet 1 dated 2/5/08 • Hydraulic Calculations dated 3/9/2008 • Reference core/shell drawings FP -2, FP -4, and FP -6 • Sprinkler head product data The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Provide restraint of all branchline piping per 2007 NFPA 13 Para 9.3.6, as enforced by the City of Tukwila. 2. Provide oversized escutcheons at sprinkler ceiling penetrations per IBC/ASCE 7 if/as required by the City of Tukwila. It is noted that flexible sprinkler connections have been used in other tenant improvement projects at Westfield as an altemate means to comply with the IBC/ASCE requirement. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or ericatuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING, PLLC Eric P. Tuazon, PE Fire Protection Engineer C arpyFles\IDee 1.7*1620081eA0n.saFYI•WrMdE CUMnel1anaee usaa4lFbreaNat e SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 140.0 20.0 10900.0 139.7 458.7 45.0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 458.7 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 208.7 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) SOURCE 1.0 SOURCE 45.0 208.7 BFI 2.0 44.6 BFO 2.0 37.6 1 2.0 37.5 2 13.0 32.6 3 14.5 31.7 4 14.5 29.7 4A 15.5 26.3 5 15.5 25.8 6 15.5 25.8 7 15.5 25.7 8 13.0 16.3 9 12.0 K= 5.60 15.0 21.7 10 13.0 15.6 11 12.0 K= 5.60 14.4 21.3 12 13.0 15.4 - - - 13 10.0 K= 5.60 15.0 21.7 14 15.0 13.2 •15 12.0 K= 5.60 12.6 19.9 16 15.0 12.0 - - - 17 14.0 K= 5.60 11.2 18.7 18 15.0 11.6 19 12.0 K= 5.60 11.3 18.8 20 15.0 - - - - 11.6 - - 21 10.0 K= 5.60 12.1 19.4 22 13.0 27.1 23 15.0 17.5 24 12.0 K= 5.60 16.6 22.8 25 15.0 - - - - 16.8 - - - 26 14.0 K= 5.60 15.5 22.0 27 15.0 16.6 28 12.0 K= 5.60 15.8 22.3 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 208.7 10.400 PL 2.00 PF 0.0 SOURCE 1.0 SRCE 45.0 (N/A) 0.8 140 FTG 2E PE -0.4 BFI 2.0 0.0 44.6 0.0 0.000 TL 72.00 PV Pipe: 2 FIXED PRESSURE LOSS DEVICE BFI 2.0 0.0 44.6 0.0 7.0 psi, 208.7 gpzn BFO 2.0 0.0 37.6 0.0 Pipe: 3 208.7 10.374 PL 44.50 PF 0.0 BFO 2.0 0.0 37.6 0.0 0.8 120 FTG 4ETB PE 0.0 1 2.0 0.0 37.5 0.0 0.000 TL 230.50 PV Pipe: 4 208.7 6.357 PL 12.25 PF 0.1 1 2.0 0.0 37.5 0.0 2.1 120 FTG TCG PE -4.8 2 13.0 0.0 32.6 0.0 0.002 TL 94.25 PV Pipe: 5 208.7 6.357 PL 102.50 PF 0.3 2 13.0 0.0 32.6 0.0 2.1 120 FTG 4E PE -0.6 3 14.5 0.0 31.7 0.0 0.002 TL 174.50 PV Pipe: 6 208.7 4.260 PL 174.00 PF 2.0 3 14.5 0.0 31.7 0.0 4.7 120 FTG E PE 0.0 4 14.5 0.0 29.7 0.0 0.011 TL 187.00 PV Pipe: 7 208.7 3.260 PL 44.25 PF 3.0 4 14.5 0.0 29.7 0.0 8.0 120 FTG ET PE -0.4 4A 15.5 0.0 26.3 0.0 0.040 TL 74.25 PV Pipe: 7A 141.5 3.260 PL 4.25 PF 0.5 4A 15.5 0.0 26.3 0.0 5.4 120 FTG T PE 0.0 5 15.5 0.0 25.8 0.0 0.019 TL 24.25 PV Pipe: 8 64.7 3.260 PL 10.00 PF 0.0 5 15.5 0.0 25.8 0.0 2.5 120 FTG ---- PE 0.0 6 15.5 0.0 25.8 0.0 0.005 TL 10.00 PV Pipe: 9 64.7 3.260 PL 10.00 PF 0.0 6 15.5 0.0 25.8 0.0 2.5 120 FTG ---- PE 0.0 7 15.5 0.0 25.7 0.0 0.005 TL 10.00 PV Pipe: 10 64.7 1.610 PL 46.50 PF 10.5 7 15.5 0.0 25.7 0.0 10.2 120 FTG 5ET PE 1.1 8 13.0 0.0 16.3 0.0 0.142 TL 74.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM.) FL/FT (PSI) Pipe: 11 21.7 1.049 PL 2.00 PF 1.7 8 13.0 0.0 16.3 0.0 8.1 120 FTG 2ET PE 0.4 9 12.0 5.6 15.0 21.7 0.152 TL 11.00 PV Pipe: 12 42.9 1.610 PL 10.00 PF 0.7 8 13.0 0.0 16.3 0.0 6.8 120 FTG ---- PE 0.0 10 13.0 0.0 15.6 0.0 0.066 TL 10.00 PV Pipe: 13 21.3 1.049 PL 2.00 PF 1.6 10 13.0 0.0 15.6 0.0 7.9 120 FTG 2ET PE 0.4 11 12.0 5.6 14.4 21.3 0.146 TL 11.00 PV Pipe: 14 21.7 1.610 PL 12.00 PF 0.2 10 13.0 0.0 15.6 0.0 3.4 120 FTG ---- PE 0.0 12 13.0 0.0 15.4 0.0 0.019 TL 12.00 PV Pipe: 15 21.7 1.049 PL 5.50 PF 1.7 12 13.0 0.0 15.4 0.0 8.0 120 FTG 3E PE 1.3 13 10.0 5.6 15.0 21.7 0.151 TL 11.50 PV Pipe: 16 76.9 1.610 PL 42.00 PF 12.9 5 15.5 0.0 25.8 0.0 12.1 120 FTG 4ET PE 0.2 14 15.0 0.0 13.2 0.0 0.195 TL 66.00 PV Pipe: 17 19.9 1.049 PL 5.50 PF 1.9 14 15.0 0.0 13.2 0.0 7.4 120 FTG 2ET PE 1.3 15 12.0 5.6 12.6 19.9 0.129 TL 14.50 PV Pipe: 18 57.0 1.610 PL 10.00 PF 1.1 14 15.0 0.0 13.2 0.0 9.0 120 FTG ---- PE 0.0 16 15.0 0.0 12.0 0.0 0.112 TL 10.00 PV Pipe: 19 18.7 1.049 PL 2.00 PF 1.3 16 15.0 0.0 12.0 0.0 7.0 120 FTG 2ET PE 0.4 17 14.0 5.6 11.2 18.7 0.115 TL 11.00 PV Pipe: 20 38.3 1.610 PL 8.00 PF 0.4 16 15.0 0.0 12.0 0.0 6.0 120 FTG ---- PE 0.0 18 15.0 0.0 11.6 0.0 0.054 TL 8.00 PV Pipe: 21 18.8 1.049 PL 5.00 PF 1.6 18 15.0 0.0 11.6 0.0 7.0 120 FTG 2ET PE 1.3 19 12.0 5.6 11.3 18.8 0.116 TL 14.00 PV Pipe: 22 19.4 1.610 PL 4.00 PF 0.1 18 15.0 0.0 11.6 0.0 3.1 120 FTG ---- PE 0.0 20 15.0 0.0 11.6 0.0 0.015 TL 4.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 23 19.4 1.049 PL 7.50 PF 1.7 20 15.0 0.0 11.6 0.0 7.2 120 FTG 3E PE 2.2 21 10.0 5.6 12.1 19.4 0.123 TL 13.50 PV Pipe: 24 67.2 3.260 PL 7.75 PF 0.2 4A 15.5 0.0 26.3 0.0 2.6 120 FTG 2ET PE 1.1 22 13.0 0.0 27.1 0.0 0.005 TL 47.75 PV Pipe: 26 67.2 1.610 PL 42.00 PF 8.8 22 13.0 0.0 27.1 0.0 10.6 120 FTG 2ET PE -0.9 23 15.0 0.0 17.5 0.0 0.152 TL 58.00 PV Pipe: 27 22.8 1.049 PL 4.00 PF 2.2 23 15.0 0.0 17.5 0.0 8.5 120 FTG 2ET PE 1.3 24 12.0 5.6 16.6 22.8 0.166 TL 13.00 PV Pipe: 28 44.3 1.610 PL 10.00 PF 0.7 23 15.0 0.0 17.5 0.0 7.0 120 FTG ---- PE 0.0 25 15.0 0.0 16.8 0.0 0.070 TL 10.00 PV Pipe: 29 22.0 1.049 PL 2.00 PF 1.7 25 15.0 0.0 16.8 0.0 8.2 120 FTG 2ET PE 0.4 26 14.0 5.6 15.5 22.0 0.156 TL 11.00 PV Pipe: 30 22.3 1.610 PL 8.00 PF 0.2 25 15.0 0.0 16.8 0.0 3.5 120 FTG ---- PE 0.0 27 15.0 0.0 16.6 0.0 0.020 TL 8.00 PV Pipe: 31 22.3 1.049 PL 4.00 PF 2.1 27 15.0 0.0 16.6 0.0 8.3 120 FTG 2ET PE 1.3 28 12.0 5.6 15.8 22.3 0.159 TL 13.00 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 49040769 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.100 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 12.1 ft/sec at pipe 16. DATE: 3/9/2008 C:\HASS78\DUKES.SDF SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 JOB TITLE: DUKES (4) PIPE FITTINGS TABLE Pipe Table PAGE: A Diameter (in) 1.049 1.610 PAGE: B Diameter (in) 3.260 4.260 6.357 10.374 PAGE: D Diameter (in) 10.400 Name: STANDARD.PIP MATERIAL: S40 HWC: 120 Equivalent Fitting Lengths in Feet E T L C B G A D Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 4.00 8.00 2.00 9.00 6.00 1.00 10.00 10.00 MATERIAL: THNWL HWC: 120 Equivalent Fitting Lengths in Feet E T L C B G A Ell Tee LngEll ChkVly BfyVly GatVly AlmChk 10.00 20.00 7.00 22.00 14.00 1.00 18.00 13.00 26.00 8.00 29.00 16.00 3.00 26.00 18.00 38.00 11.00 40.00 13.00 4.00 35.00 26.00 59.00 19.00 65.00 23.00 6.00 44.00 MATERIAL: DIRON HWC: 140 Equivalent Fitting Lengths in Feet E T L C B G Ell Tee LngEll ChkVly BfyVly GatV1v 35.00 80.00 26.00 88.00 30.00 8.00 NOTES (USER): N NPTee 80.00 N NPTee 5.00 8.00 D N DPV1v NPTee 18.00 20.00 26.00 26.00 35.00 38.00 44.00 59.00 DATE: 3/9/2008 JOB TITLE: DUKES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 C:\HASS78\DUKES.SDF E 04 to E E Di G. L L o 0 W N �V U 0 3OO L • >on M Q IAN = CO r >` o Z IA It V1 UN G.r1:1 Ur • LI,N�=W Wa a0 to ci a •r NIA •r NE r—Q.•>71AU W .C1 N G. L {•i rd 1.0 L = Vf r1.O.rN 0 >> 1 O V) N > rn w it Q 1-1 ce er Q oo 20.00 psi Flow: 1 O 0 0 0 m V' v -I r1 N o O 0 0 oo 0 0 0 N 0 o to cr H H 01.4tp 0 43 w a W Mcrl 0 W 41 CO 0 0 0 0 0 0 0 H 0 0 0 0 Co co O 0 r N 0 0 0 0 0 0 0 r H 1 FLOW (GPM) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 3/9/2008 C:\HASS78\DUKES.SDF JOB TITLE: DUKES WATER SUPPLY CURVE 144+ 0 \ 132+ \ I \ 1 \ 1 \ 120+ \ 1 I \ 1 108+ \ I \ I \ I \ P 96+ R I \ E 1 \ S 1 \ S 84+ \ U I \ R I \ E 1 \ 72+ \ ( 1 \ P I \ S 1 \ I 60+ \ 1 \ 1 I \ 48+ \ X 1 1 36+ I \ 1 1 24+ LEGEND 1 "* <-20.0 psi @ 10900 gpm 1 X = Required Water Supply Flow Test Point 1 45.02 psi @ 458.7 gpm " 12+ 0 = Available Water Supply 1 139.66 psi @ 458.7 gpm " 0++-+---+----+ + + + + + + 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) 1. *[SCO / Fire & Security R-102 RESTAURANT SYSTEM NOZZLE COVERAGE SUMMARY SHEET •, ANSIJLI Appliance Nozzle Type Flow Points Width (In) Max. Side Length • (In) Max. Side Multiple Nozzle wo/Drip Board Area Sq. In. Multiple Nozzle w/Drip Board Area Sq. In. Min. Nozzle Ht. (in) Max. Nozzle Ht. (In) Fryers without drip boards Split or No Split Vat 230 2 14 15 — — 27 - 47 245 2 14 15 — — 20 27 Fryers without drip boards 4 Non -Split Vat jONLY) 290 2 19.5 19 — — 13 d ' 16 , 3N 3 19.5. 19 — — 21 34 , 3N 3 18 18 — — 25 35 Fryers with drip boards Split or No Split Vat' 230. 2 14 21 210 _ 294 27 47 245 2 14 21 210 294 2Q 27 Fryers with drip boards' Non -Split Vat (ONLY) 290 2 19.5 25 3/8 370.5 495 13 , 16 3N 3 19.5 25 3/8 370.5 495 21 34 3N 3 18 , 27 3/4 ' 324. 497 25 35 Tilt Skiilet/Braising Pan 2 Coverage Exception limitation are based on fryer sizes including the drip boards. Tilt Skillets and Braising may exceed the maximum of 6 sq. ft. ' Range Without back shelf With back shelf Without back shelf With back shelf - . 1N 1 12 32 — — 30 40 1F 1 12 28 — — 30 50 1F . 1 12 28 — — 40 48 245 2 24 28 — — 40 • 50 260 2 24 32 — — 30 40 260 . 2 12 32 — — 30 40 2 x 290 4 36 28 - — 15 20 Griddle : . • 1 W1 NSS 1 36 30 — — 35 40 290 2 30 24 — — 30 50 260 2 48 30 — — 30 50 290 2 48 30 — — 20 .30 2120 2 48 30 — — 10 20 Chain Broiler' (Overhead Protection) 2 x 1W 2 34 30 — — 10 26 Chain Broiler (Horizonte) Protection) 2 x 1N 2. 31 43 • -- — Front edge; above the chain 1 in. - 3 In. Char Broiler. Gas -Radiant Electric 1 W1 NSS 1 • 24 36 — — 15 %.. 40 1 N/1 NSS 1 20 34 .. — — 20 50 Lava -Rock 1 N/1 NSS 1 13 24 — — 18 35 Natural Charcoal' 1 W1 NSS 1 12 24 — — 18 40 Lava -Rock or Natural Charcoal' 3N 3 24 30 — — 14 40 Wood Fueled' 3N 3 24 30 — — 14 40 Upright Broiler 2 x 1/2N 1 30 32.5 Front bdge; above the grate Salamander Broiler 2 x 1/2N 1 30 32.5 — 1N 1 16 29 — _ — — 1 N nozzle location to be on the vertical edge 6 to 12 in. in front and 0 to 12 in. above the top of broiler Internal Chamber 1N 1 16 29 — — 6-12 in. above either end Wok 3.75 to 8 inches deep 260 2 14 in. to 30 in. diameter — — 35 45 3 to 6 inches deep • 1 N/1 NSS 1 11 In. to 24 in. diameter — — 30 40 For multiple nozzle protection of single fryers, see' detailed Information on pages 4-10 to 4-11 of manual. 2 See Figure 1 for nozzle location. ' Minimum chain broiler exhaust opening —12 in. x 12 in. (31 cm x 31 cm); and not less than 60% of intemal broiler size. ' 4 in. (102 mm) maximum fuel depth. 6 In. (15 cm) maximum fuel depth. FILE 4 4 ` 'IMOI Fire & Security' R -102 -RESTAURANT SYSTEM NOZZLE COVERAGE. SUMMARY SHEET • Duct Plenum -64n w Nozzle TypeMax.ax.Side Flow Width (In) Length (In) Max. Side Nozzle Placement (See Manual for More Detail) Min. Height (In) Max. Height (In) loft •.tot .-: i e`$an'.'` ..., .-. -._ ..:-- � : w 1 ,:-.;...... See Manual for more detail 1267 - 0 iii. - 6in. from end of plenum • 2 - 41; Perpendicular Protection Single Bank 1W/1100 1 48 48 See Manual for more detail 1 20 Horizontal Protection V Bank 2 x 1N 2 48 120 0 in. - 6 in. from end of plenum 2 4 . Horizontal Protection V Bank 1W/1100 1 48 72 0`in. - 6 in. from end of plenum 1/3 the height of filter Perpendicular Protection V Bank 1W/1100 1 48 48 See Manual for more detail 1 20 • Duct Nozzle Type Flow Points Perimeter (In) Diameter (In) Nozzle Placement (See Manual • for More Detail) Duct Length (in) Single Nozzle 1 flow nozzle 1100 1 50 16 See Manual for more detail Unlimited ..:. I0 l9; hiozzIe.2 H441- _ le. .. . 2W 2 10031 7/8 See Manual—for more detail Unlimited Multiple*Nozzle 2W +1100 3 135 48 See Manual for more detail Unlimited Multiple 2W Nozzle 2W — >135 >135 See Manual for more detail Unlimited R-102 OVERLAPPING PROTECTION The 245•nozzle, Part No. 419340, is the only approved nozzle for overlapping (zone) protection. Appliance Type Fryer Griddle Range Wok, Maximum Wok, Minimum Braising Panfri t Skillet' Lava Rock Char -Broiler Charcoal Broiler Mesquite Wood Broiler Gas Radiant Char -Broiler Electric Char -Broiler -' See Figure 1 tor nozzle location. Maximum. Cooking Hazard 34 in. (864 mm) Deep x 5.8 sq. ft. (.54 sq. m) 30 in. (762 mm) Deep x Unlimited Length 28 in. (711 mm) Deep x Unlimited Length 30 in. (762 mm) Diameter x 8 in. (203 mm) Deep 11 in. (279 mm) Diameter x 3 in. (76 mm) Deep 34 in. (864 mm) Deep x Unlimited Length 32 in. (813 mm) Deep x Unlimited Length 32 in. (813 mm) Deep x Unlimited Length (4 in. (102 mm) Maximum Fuel Depth) 32 in. (813 mm) Deep x Unlimited Length (12 in. (305 mm) Maximum Fuel Depth) 36 in. (914 mm) Deep x Unlimited Length 34 in. (864 mm) Deep x Unlimited Length TYCO SAFETY PRODUCTS, ONE STANTON STREET, MARINETIE. WI 54143.2542 COVER MUST NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN 0-6 IN. (0-15 cm) 111 If 1I I I 1 ZONE 40-45 IN. (1-1.1 m) I ZONE CENTER LINE 006927 l=1faUFtE`1 ` 715-735-7411 Form No. F-2005010 02005 Ansul Incorporated Utho In U.S.Arf SECTION IV — SYSTEM DESIGN ► UL EX. 3470 ULC CEx747 Page 4-34 7.1-98 REV.4 KNK AND CARTRIDGE REQUIREMENTS Qnoe the hazard analysts Is completed and the total nozzle flow numbers are established, the quantity and 'size of agent tanks and cartridges needed to supply the nozzles with the proper volumes of agent at the proper flow rates can be determined, For cartridges used In the regulated release mechanism, flow capacities, tank quantities and sizes, and regulated release cartridge options are given iri the table below. Total Quantity and Regulated Release Flow Size of Cartridge Options Numbers' Tank(s) Nitrogen Carbon Dioxide 1 — 5 (1) 1.6 Gallon LT 20-R (7032) 101-10 (15850) 6 — 11 (1) 3.0 Galion LT 30-R (5373) 101-20 (17492) 11 — 16 (1) 1.5 Gallon Double (73022) 101-30 (15851) (1) 3.0 Gallon X�1,11,, 16 — 22 (2) 3.0 Gallon Double (73022) 101-30 (15851)11A When one or more regulated actuators are used, the following tank and cartridge combinations apply for each regulated actuator: Regulated Actuator Regulated Actuator Tank(s) Cartridge (1) 1.5 Gallon (1) 3.0 Gallon (1) 1.5 Gallon and (1) 3.0 Gallon (2) 3.0 Galion LT 20-R or 101-10 LT 30-R or 101-20 LT -A-101-30 or 101=30" LT -A-101-30 or 101-30** _mor exoepllons to maximum Mow numbers, esti Distribution Piping Rtiqulremenls toi 1.ti OW' and 3.0 gallon systems In Ibis Section. For higher total flow numbers (23 to 110), multiple cartridges and regulated actuators are required as shown in the System Selection Guide In Section IX — Appendix. ACTUATION GAS LINE WITH AN LT -20-11, LT -30 -FL 101.10 OR 101.20 CARTRIDGE MAXIMUM LENGTH OF 20 FT. (0 m), MAXIMUM NO. OF FITTINGS 0 'ANSULAUTOMAN' REGULATED RELEASE ASSEMBLY ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS This section contains the guidelines for Installing the actuation and expellant gas lines between the regulated release mechanism reg- ulator, each regulated aotilator regulator, and each agent tank. These limitations should be considered when selecting the com- ponent mounting Iocatione. r Actuation Gas Line — 6 to 6* Tanks Maximum 8 Tank maximum reflects the utilization of 3 tank regulated actuators. 1. Use only 1/4 in. Schedule 40 black Iron, hot -dipped galva- nized, chrome -plated, or stainless steel pipe and fittings. 2. The actuation gas line piping is Installed from the regulated release mechanism to each regulated actuator connected within the system. The total length of the actuation gas line from the regulated release assembly to the regulated actuator assembly(ies) must riot exceed 20 ft. (6 m) when using an LT -20-R (Part No. 7032), an LT 30-R nitrogen cartridge (Patt No. 6373), or a 101-10 (Part.No. 16850) or a 101-20 (Part No. ► 17492) carbon dioxide cartridge. See Figure 73. REGULATED ACTUATOR ASSEMBLY EXPELLANT GAS LINES NOT INCLUDED IN ACTUATION GAS UNE LENGTH TOTALS REGULATED ACTUATOR ASSEMBLY REGULATED ACTUATOR ASSEMBLY FIGURE 73 000775 i A LJ e Is =p3 fag U W Pigg 113 F. S d • • • • • • . • • • • •••• • • • • • • • • • • • • • • • • • • • • 8 Id LI IM W 111 W 1111 w MI 111 • • t g ffi 1 8 • j § �jj -J = O.rI- §< czo0 �4k $) u / 4 FT. HOOD 12X16" DUCT 360* FUSE LINT{ \)\ e }j\ \} M\ DUKES CHOWDER HOUSE GAS SHUTOFF \ e- :R. iAi | , k ] 0 @ = 2 0ct ■ ■ o/ / o _c en 0) 2k 030 f 03 0 7 01 03 5 - E \/\ 133 > CD § F o_ u± -R /\ S k I {§ 3 Ecs E k].0 � CI 73 C 1 20/ La.=/A < 2: II R` 0 z / ) -c E k k / • JAN -18-2008 02:48P FROM: TO:5754439 P.2 SECTION L; - APPENDIX UL EX, 3470 ULC CEx7; 17 Page 9-1 10- I -02 REV. 5 tl SYSTEM SELECTION GUIDE Note: System options do not cover all conceivable 3riations.They are listed here as a general guideline to show the mc st common type arrangement for multiple systems, Based on certair system designs utilizing manifolding, non-manifolding, 3 -tank sys ems, etc., other tank/cartridge combinations can be designed. The cc mbinations below are based on 11 flow, 3.0 gallon tanks and 5 flow, 1.5 gallon tanks. More competitive designs may be available by utilizii ig 12 flow and 6 flow systems when appropriate. *Total Flow No,* 1-5 6-11 12-16 Tank Type of Quantity System 1 Single Single Type of 11 ware 1.5 G al. Reg. Release 3.0 G al. Reg. Release 2 Double 1.5 C al. Reg. Release 3.0 C al. Additional Tank 17-22 2 Double 3.0 C al. Reg. Release 3.0 C al. Additional Tank 23-33 3 Multiple 3.0 C al. Reg. Release 3.0 C al. Reg. Actuator 3.0 C al. Additional Tank 23-27 3 Multiple 1.5 C al. Reg. Release (Optional) 3.0 C al. Reg, Actuator 3.0 C al. Additbnal Tank 28-33 3 Multiple 3.0 C al. Reg. Release (Optional) (2) 3 0 Gal. Additional Tanks 34-38 4 Multiple 1.5 C al. Reg. Release 3.0 C al. Reg. Actuator Dout le 3,0 Gal. Tank Box 1.5 C al. Reg. Release 3.0 Cal. Additional Tank 3.0 C al. Reg. Actuator 3.0 C ai. Additional Tank 34-38 4 Multiple (Optional) 39-44 4 Multiple 39-44 4 Multiple (Optional) 45-49 45-49 (Optional) 3:0 C al. Fleg. Release 3.0 c sl. Reg. Actuator Dout le 3.0 Gal. Tank Box 3.0 (Idl. Reg. Release 3.0 (gal. Additional Tank 3.0 C gal. Reg. Actuator 3.0 (gal. Additional Tank 5 Multiple 1.5 (lal. Reg. Release 3.0 (gal. Additional Tank 3.0 (lal. Reg. Actuator Doul le 3.0 Gal. Tank Box 5 Multiple 1.5 (Lal. Reg. Release ' 3.0 (lal. Reg. Actuator 3.0 (tal. Additional Tank 3.0 (ial. Reg. Actuator 3.0 (Lal. Additional Tank Carbon Dioxide Cartridge Required 101-10 (423439) 101-20 (423441) 101-30 (423443) 101-30 (423443)** 101-20 (423441) 101-30 (423443)*** 101-10 (423439) 101-30 (423443)*** N/A Nitroge n Cartrid 1e Required LT 20-F ; (423429) LT -30-f ; (423435) Double (423493) Double (423493) LT -30 -fl (423435) LT -A-1(1-30 (423491) LT 20-f I (423429) LT -A-1111-30 (423491) Double (423493) 101-10 (423439) LT -20-11 (423435) N/A LT -A-11)1-30 (423491) 101-30 (423443) 101-30(4234443)"' 101-20 (423441) N/A 101-30 (423443)** 101-30 (423443)*** 101-30 (423443) N/A 101-10 (423439) 101-30 (423443)*** '101-30 (423443)"' Based on 6 Row numbers for a 1.5 gel. system and 11 flow r umbers k r a 3.0 gal. system. " 11 tanks are manlolded, only a -double tank" nitrogen cartridge Marl N 1.423493) can be used. -'- If Lanka are manflolded. either an LT -A-101.30 nitrogen carol Sia (Part go. 423491) or s double tank cartridge (Part Na. 423493) can be used. ► Double (423493) LTA -1111.30 (423491) LT -30-11 (423435) LT -A-1 )1-30 (42349i) Doublt (423493) LT -A-1 )1-30 (423491) Doublt; (423493) LT -A-1 )1-30 (423491) LT -20- I (423429) LT -A-1 )1-30 (423491) LT -A-1 )1-30 (423491) [] Without CD., orients As.. P3 1 r nese plans hal ° Prevention Bi standards. i - omissions + .. ' stanaaras adequacy Additions, u. .. i cgs atter !, the date will quire a 1 resubmittal or . . 4 _ ,... subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: I - o O By: klfv\ 1 -I — E1ed-ri(gt .k Shvh,+ qs Wel( as cr.5 M ci ke -up A *l r -k 5i+. " U.L. G e4-60 t Into.1-Vv om . Because of increaF^ri rlemand our inspectors' schedules are boo!:aci 3-7 days ahead. Therefore, you will r: to call 206-575-4407 or em ii fireinsprequestPci.tuiv,A!i1a,wa.us fo schedule your inspections a minimum of 48 hours in advance of the date you want an inspection. UKWILA FIRE DEPARTAi$ Please call: 575-440Z and give this job l No. 03-F °/ and exact address for shut. ,l.wn or restoration approve. D U K E' S CHO . DER HOUSE FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 SYSTEM CALCULATIONS (GENERAL) FA -04 FIRE ALARM SYTEM FA -05 CONCEPT 5 WESTFIELD SOUTHCENTER MALL SITE PLAN WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H ,D❑❑R HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P • DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) 2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD ##12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) 2V SPEAKER CIRCUIT - RETURN TWISTED PAIR. #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO 1414 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V 1114 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUrr FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY, HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT:. AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO'ONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING; WHICHEVER 1S LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION _ FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN . ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2002 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (11., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2002 A.6.4.2.2.2 A GOAL OF 6.4.2:2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED SYMBOLS LEGEND QUANTITY 1 12 3 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT 1FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE WITH RELAY HTRI-R SIEMENS • 4S DEEP VERIFY IN FIELD T -D DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD 1 HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED • VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11. BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE p DETECTOR AD2-P W/ SIEMENS TSM -1 MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-1 1 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING gL C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT.. TO BOTTOM ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. 4 C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1 -1 /2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. • TO BOTTOM IBbwp FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY M R-201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FATC FIRE ALARM TERMINAL CABINET F.B.O. F.8.0. F.B.O. VERIFY IN FIELD FA JB❑X JUNCTI❑N BOX F.B.O. F.B.O. • N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD DR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A r> 1 ACCEPT ❑ without Comments As Noted In Red ❑ Per The Attached Letter !hese plans have been reviewed by The Tu! wita Fire Prevention Bureau for conformance with current city s >>dards. Acceptance to errors and is which do not authorize violations of adopted and cr-cJ:nances. The re ponsibi ty for the ,i _',._ ,,r; re_._ tote; y with the designer. it.. - =s, cies sio, s or revisions `;v hese drawings atter voic! accept3nce ry.nd 1"til require e r€ c'.>rviz,:-AUrawin gsforSubsequentapproval. Fir,_, z..,. =�: <ce is ub]ect to fe'S test and inspection by The Tu: if=`r :- Prevention Bureau. ' Date: 9- 7- 08 By: 1 /`'t 7 1 TUKWILA FIRE DEPARTMENT ;1 Please call: 575-440Z - _ and give this job and exact address for shut' .` Town or restoration approv 4I NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement,of Acceptance Testing of aT*ffiedAlarm and Detection Sy�ss Failure of test will f BIt in a Re -ins jpvnd termination h,ng. //7z/ r ri.ht 2006 b Guardian5ecurif Sys ems, -Inc. All R. his Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS DESCRIPTION C CCC O SCALE:;; rTh z z 3 0 0 z C z E t1 (j J DRAWN; BY:;,., (.ANDERSON DESIGNED, BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: 'JOB tyr:- UMBER: i,.SHEET - JK)4A,1 I toacov-f- de vic-c oN, FA sv4o. die) c4k los•c.4,k'ev, NrFi4 2oo.e dv;4-,,/,ti . r THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE KITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WOE. SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. AIR DUCT 6-10 DUCT EQUIVALENT ______ DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC DUCT DETECTOR LOCATION 1 END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH GROUND 0 --0 0 0 HTRI—R 010 STATUS LED 0 N.O. r- 0 COM 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 p TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE - MUSIC OUTLET SAMPLING----•\ TUBE INLET SAMPLING—\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE NONE )-AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f STOP IF LAST DEVICE .(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE (-) END OF LINE � U_ DEVICE (3.6K 1/4W) SUPERVISED RELAY CONTACTS SWITCH (4.0A @ 125VAC) GROUND (4.0A @ 30VDC) 27 VDC 3.5 nA DURING POLLING 10 OHMS 200 FT. (18 AVG) 0.02 uF 0.04 uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. Ie I TBI 6 1.2.34 -;56 - HCP TB2 ee 6 5 4 3 2 1 i 0 0 0 0 HTRI-D OSTATUS LED CO 0 n NOT USED 0 END OF LINE DEVICE 0 i 3.6K 1/4W) O NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABa SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 GND N AC O X00 El 0 0 PAD -•3 0 00 O . INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX • 1+ 1--.1 2+2— 2 NC C NO + — + .— + — + — + — . 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 UPERVISED SWITCH FRONT VIEW ./ NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE ,! DEVICE LOOP !, 0 0 [FROM XLS CONTROL PANEL OR (+), PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE) FROM FACP (VOICE CIRCUIT) C'V' CABLE> 470 OHMS EOL T M-1 O o: • Lgclgco TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE ( STROBE (-) SPEAKER (c (-) 0 0 (STROBE 0 O EARTH GROUND -2,(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE (+) (-) STROBE SPEAKER 0 SPEAKERISTROBE AND STROBE VA (RING LABEL SCALE "SPEAKER STROBE • OR STROBE ONLY 4S DEEP BOX... W/ 1-1/2". EXTENSION- RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER1 TEMPERATURE +32' F {0' C TO 100' F (30' C) HHUMIDITY; O- RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POMO SOURCE DATA IN (-) DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN MIEN USED IN CONJUNCTION YelEi IY.ICT HOUSINGS AD -11P OR AD-11XPR 03-11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL BSCALE TO NEXT DEVICE (-) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING HARD LID —\ SPEAKER SUPPORT TILE— BRIDGE 7--4' SQUARE DEEP BOX -- WITH 1-1/2' EXTENSION N. /--- CEILING MOUNTED ----N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON CEILING FLEX ' JUNCTIC[IN BOX -- MOUNTED AaAINST CEILING SUPPORT / / / 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECTOR--= SMOKE DETECTOR MOUNTING SCALE=NONE of SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS DESCRIPTION 0 Z W _ c_ WVSG W aO o 65 L.1' ig '2„=, (:)!5'.6i< J.. wcc 0 EE' 1E55 3.. ~ E- :2) 0 c - : 0) U W %� CALE: /8"=1' DRAWN: BY: LAN DERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: ..OB NUMBER: SHEET ..J FA -02 � 11 is eT 1 FA JBOXR---`' D,P 2V,S keg = 112 Freezer 70 x .33 = 93 Cooler 125 x 1.33 = 166 rgriAnt-AurTma--e-Ffsi -4100E-IYIT'D /26 ( 44 (50 r -A. I I 52 1 k108% 0.27) '1282 c129.n. v.." ,---- -, 1 / I \ I % I 1 ----- --- ------ -----21, I ; 1 \ y ------- -t—.--.:3- ---- ., ‘ • 1 1•1111...1, \ % ___ /I 1 1 \ \I„„ sf----:2------ r • -- 1 1111 ----., . I di' 1111 1 1 l\ I 1 t/ /--..''`.. I k A .. II, x -.---. / .., I 1 \ 1 / 1 \ I A ':"-. \ I \\\1 / .' . A n , , ‘ • I / ‘ 1 1, f.:3-'-"------'- 44; 14 v- 1141 'It- .,,,--- c,.... , ,, \ ,o,ti \ \-) 1 ... ‘r\v.7—'/A1-E—N-:S:E—S-11R)0, M\- .7 ... LKL,2j 1 iwz.1 I WWW4 : -T-11:11- _1=1:71 1.17111:1LJLJ - -1=111-1 2V, ffj pri.vATE DINING 013 LJLJ LITI ) 111 • /Th t ; :=R;44T1.4;,:a 2V,S 30 48V I •4::t rJNI0 012 A 1 \ / I ; \ \ Ak.AIING •-__ Pr -Z1.. DINING 93,1 1 15 L 2F f L L v,s Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F) CO 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS DESCRIPTION LiJ • w „_co c1:3 2 cc z CE w < 0 W o (1) >O CC Z (j) 5 w< o < () [LI LN60 /SCALE: 1 /8"= 1 DRAWN BY: [ANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: JC)B NUMBER: SHEET . a :.:•:.:•:.:•:•:•:•:•:•:•:•:•:410:40:•:07.0:•:•:•:•:•:•:•:•:11,:•:•:•:•:•:•:•:•:•:€11,:•:•:•:•:•:•:•:O:4:41,:1144:41:•:•:CCVAKCCO:•:•:01:10:•::•:•:10:•:•:•:11:•:11.:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:40:4,:•:•:41:•:•:•:•::•:•:•::•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:•:97.• 1074:14:•74:•:40:•:•:',..:•:•:* •:•:€1.7.*:•:•:•:41*,0:4:4:10:•:•:•:€•:•:•79...... 2;•••:41,11".;9;,•::4 r...............................T............................................".......T.,....."...................................."10.1, ;446.4.4eire•*or. .b"."••;%...W.i.W40••••nee*.W.V.Wini."*"•-•"46".'Nee'iriew."*"46"ele•"404.4.W•ediara*.ebW4.*dbnine46.4•4:•".Venir ;* 4.••••••• 1 ....,... ... , , .... n .... ....4 ,i.. — f% A oki 011111L111111.01011 I i;, 3 1J .41 ,4 6 —I 3_41 ... c3 !IIIININIEIWIIIiIMI ' 1 . ER WALK IN RE1 - -5-0 1-1 514 l'? -b. 7-wlia • I •6;rldli '• .. ‘13 lailiall • ,4/...• • • Mr • • • V, •41 WALK IN FREE *no •••••••••••••;teeeieea.e.W 7.9.191019...9bniitireer. 4N4.14 "AK' t"...••• ,••••• 0.4....•:•:•:•.• • .44.40:0:40:1:•.• 6,16-51,4 IQ .0 RESTROO fi V tcqe, 2435/, CA • (9118)301.5109 FIG. 68 WIDE THROAT TOP BEAM "C" CLAMP WITH LOCKNUT Size Range - 3/S thru 7/8 inch rod. Function - For attachment tC sttuctural shapes requiring wider throat especial'/ under roof with bar joist constn:ction. This clamp may be used in the set screw down pcsiticr: cMy. Approvals - Conforms :0 Manufacturers Stand. ardization Society SP•69, type 19. Finish - Plain and Electro•Galvanized. Order By - Figure number, rod size. and finish. Note - Do not overtighten se: screw. • • : 11:41:•••:•:•:•:•:40:•.•:•:•10:•1•.•.. FIG. 69 BEAM CLAMP RETAINING STRAP Size Range - 3/8 :hru 7/8 inch rod by 4 thru 14 inch length. Materia! - Carbon Steel Function - To offer more secure fastening of beam clamp to beam when denser of movement might be expected. Approvals - UnderuzitersLaboratories listed when used wit:t4Tolco U.L. Listed Fig. 65 and 66 Universal Beam Clamp, Finish - Mii. Galvanized and Stainless Steel. Order By - FiSty'e number, type, length "K, and rod size being used with beam clamp. Note - Minimutn return on Strap: r. • •••••••••4•••467. 7r••.6-4ewe4•&oeA OFFICE II•11.4 I•4 • 0 • OM .4 Nor Ell 'I: ow*11 410"0"dr4e4W410:.11,:•:**9.4,.• •••••,.4 fo, 404 to DINING ROD HOLE STOCK TYPE SIZE S SIZE A FINISH 1 3/8 7/16 16gax1 t Mil. Galv. 17g. -.911-6". 3:6244 _t - 2 5/8 11/16 14gax1•1/4 t M2. Galv. - ' -3 .16 14gax1-1/4 t - 7ffirsak,... C. 3/8 • 7/8 specify 1290x1-1/4 111=1W1111 111111111111111111111111M11111111111111111111111111111111111111111111111111111111111.: MINN Nil EIE!MIIEEIM iiiii1111.0111 04•,.,•,,)•,,„•.„•,; :$ :$ • )i 0 A x A p, ....„ A ..p. ,-, :3 ili 4,, A il • p.... 0,.4 :$ 4 P. t i3 .,_, ...P. :$ p • , .k: 11",iiiA,. A 9:4 t• .41,..•.. 10., ii,, I fr Wei I 74,....4.4 1.1.041 ,4 AAA MA 0.4 1'4•74 7411'4,741.••••••••4 11 MA re" 4.•••••"...04P•VOW4 r•VI A 4/7•70•W•••••V We; 0.4701174.174104 fill ••••••••* 'POW ••••V• 111,••••• 041 1 fGWB 44$ iii 144 A DINING A 4441 -111E1uu v 111111.4114.14M• J4•4 C.;44 rrailli, 111 . • 011 Mi - ACK BAR ENTRY FRONTBAR „roxieva..0:00t0 tile tl• 04, 0.49 (,419 .1 • • HDI Drop -In Anchor • Anchor, setting tool and HMI drill bit form a matched tolerance system to provide reliable fastening • Below Sabo° setting for easy patchwork • Allows for shallow embedment without sacrificing performance Technical Data 0050 materIW •Nom.cmckadconcroto • Ughavolght concrete • Ughmecht concrete over motel deck Anchor material • HOICarbon Stool materla moat» 1110 rociwornents of Al51111050or A1511010 for 11101/4". 3/001181/2" I -101's pr. Alst12L1 4 fix CWIEn and 3/4.1-100s, • Carbon Stew HD paned vath a aloe Men for Cortosion protection In accordance wth ASTM 8633 1.1570111 ype • HOIStalolesa Stool material 0700131110 requirement. of /101 303. Listings/Approvals UL (Underwear Luboratorleo) Coreml No. 7670 • (Fectay Mutual/ Serial No. 22765 ICC -ES (Intemadonel Code ER Report No. 2835 — Coonca) 000111101 0010 COLA (Gay of Lea Angel...) Flapco No. 23709 os.c.aeanronnvill Feoeral Speak:aeon 'Noel • • - :$4 Wee '01r...1•74.Wer re. OZ.:•:•.:411.7.1•14"Xt r.;.•:•:•:•: X.•14,1•ICACIIMICATAK XXX" :$ DAYLIG T CONTROL AR A SEE LI TING/ENERGY CALCS. Carbon Steel Muster Carton 15011 110. Cly Item No 336425 100 3001507 336428 50 3001508 336427 50 3001509 336428 25 256540 336429 25 258541 stainicess Steel Cly 1200 600 300 100 100 Description HD! 1/4" I-101 3/8" HD! 1/2' HDI 5/8' MCI 3/4" Hole 010 3/8' 1/2" 5/6" 27/32' Meetly Carton Hole earn No Oty Item No. 0115 DOSCliptiOn 010 338430 100 339617 1200 80(1/4" (55303) 3/8" 330431 50 339818 800 110( 3/8" (0S303) 1/2' 336432 50 333519 300 HDI 1/2" (55303) 5/6' 336433 25 339820 100 801 5/0" (S5303) 27/32' 336434 25 339621 100 8131 3/4" (S5303) 1" r 522 HO Product Tac Mice, 0611110 116 complete parkmane. as. Embed Anchor Length 1. 1-0/16" 2' 2-9/16" 3-3/16' 111110044. Anal. Length 1' 1-9/16' 2' 2-9/15" 3-3/18' Ufa:1bl° Thread Length 7/1V, 5/8' 11/16' 7/8' Useetle llyead Length 7/16" 5/8' 11/16' 7/8' 1-3/e' Internal 5000/11501 1,00113 Thread 4000 p010071111010' Sze 30115011 /411 51010/1411 570 - sas..„ 3/8" 1115 1250 ,ii.r. 1785 2125_ 5/6" 2920 3250 , /4! 4005 5009', Intemal Traced Soo 1/4" 3/8' 1/21 5/8" 3/4' 5006008008000 4000 psl concroco' Tonafon 611) 5110011 141) , 480 809, 1040 1230 _1540 2790.: 2630 4510 3630 5560 rr 311111; . marECE AAAANNWANAAV.W.A Wthout As Note Per The nese plans have been r Prevention Bureau for co standards. Acceptance i omissions which do not a standaras and °romance adequacy of design rests Additions, deletions or re ornments In Red ttached Letter viewed by The Tukwila Fire formance with current city ubiect to errors and thorize violations of adopted . The responsibility for the totally with the designer. ision o tc: drawings atter this date will void this acr2ptance F,rid will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: Weld stamps must inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FHLPCTHD CF \G PLA\ ' 8' 10' 12' 14' 16' 18' TUKWILA FIRE DEPARTMENT, Please call: 575-4407 and give thls job and exact address for shut. down or restoration approval. Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinsprequest(@ci.tukwilafwa,us to schedule your inspections a minimum of 48 hours in 'advance of the want an inspection. SPRINKLERS We _az, Vbe 4WD. 0 ISSD t55° kg" Vt Korn 1-16ZR, 4 4 IL FIG. 69 BEAM CLAMP RETAINING STRAP Size Range - 3/8 :hru 7/8 inch rod by 4 thru 14 inch length. Materia! - Carbon Steel Function - To offer more secure fastening of beam clamp to beam when denser of movement might be expected. Approvals - UnderuzitersLaboratories listed when used wit:t4Tolco U.L. Listed Fig. 65 and 66 Universal Beam Clamp, Finish - Mii. Galvanized and Stainless Steel. Order By - FiSty'e number, type, length "K, and rod size being used with beam clamp. Note - Minimutn return on Strap: r. • •••••••••4•••467. 7r••.6-4ewe4•&oeA OFFICE II•11.4 I•4 • 0 • OM .4 Nor Ell 'I: ow*11 410"0"dr4e4W410:.11,:•:**9.4,.• •••••,.4 fo, 404 to DINING ROD HOLE STOCK TYPE SIZE S SIZE A FINISH 1 3/8 7/16 16gax1 t Mil. Galv. 17g. -.911-6". 3:6244 _t - 2 5/8 11/16 14gax1•1/4 t M2. Galv. - ' -3 .16 14gax1-1/4 t - 7ffirsak,... C. 3/8 • 7/8 specify 1290x1-1/4 111=1W1111 111111111111111111111111M11111111111111111111111111111111111111111111111111111111111.: MINN Nil EIE!MIIEEIM iiiii1111.0111 04•,.,•,,)•,,„•.„•,; :$ :$ • )i 0 A x A p, ....„ A ..p. ,-, :3 ili 4,, A il • p.... 0,.4 :$ 4 P. t i3 .,_, ...P. :$ p • , .k: 11",iiiA,. A 9:4 t• .41,..•.. 10., ii,, I fr Wei I 74,....4.4 1.1.041 ,4 AAA MA 0.4 1'4•74 7411'4,741.••••••••4 11 MA re" 4.•••••"...04P•VOW4 r•VI A 4/7•70•W•••••V We; 0.4701174.174104 fill ••••••••* 'POW ••••V• 111,••••• 041 1 fGWB 44$ iii 144 A DINING A 4441 -111E1uu v 111111.4114.14M• J4•4 C.;44 rrailli, 111 . • 011 Mi - ACK BAR ENTRY FRONTBAR „roxieva..0:00t0 tile tl• 04, 0.49 (,419 .1 • • HDI Drop -In Anchor • Anchor, setting tool and HMI drill bit form a matched tolerance system to provide reliable fastening • Below Sabo° setting for easy patchwork • Allows for shallow embedment without sacrificing performance Technical Data 0050 materIW •Nom.cmckadconcroto • Ughavolght concrete • Ughmecht concrete over motel deck Anchor material • HOICarbon Stool materla moat» 1110 rociwornents of Al51111050or A1511010 for 11101/4". 3/001181/2" I -101's pr. Alst12L1 4 fix CWIEn and 3/4.1-100s, • Carbon Stew HD paned vath a aloe Men for Cortosion protection In accordance wth ASTM 8633 1.1570111 ype • HOIStalolesa Stool material 0700131110 requirement. of /101 303. Listings/Approvals UL (Underwear Luboratorleo) Coreml No. 7670 • (Fectay Mutual/ Serial No. 22765 ICC -ES (Intemadonel Code ER Report No. 2835 — Coonca) 000111101 0010 COLA (Gay of Lea Angel...) Flapco No. 23709 os.c.aeanronnvill Feoeral Speak:aeon 'Noel • • - :$4 Wee '01r...1•74.Wer re. OZ.:•:•.:411.7.1•14"Xt r.;.•:•:•:•: X.•14,1•ICACIIMICATAK XXX" :$ DAYLIG T CONTROL AR A SEE LI TING/ENERGY CALCS. Carbon Steel Muster Carton 15011 110. Cly Item No 336425 100 3001507 336428 50 3001508 336427 50 3001509 336428 25 256540 336429 25 258541 stainicess Steel Cly 1200 600 300 100 100 Description HD! 1/4" I-101 3/8" HD! 1/2' HDI 5/8' MCI 3/4" Hole 010 3/8' 1/2" 5/6" 27/32' Meetly Carton Hole earn No Oty Item No. 0115 DOSCliptiOn 010 338430 100 339617 1200 80(1/4" (55303) 3/8" 330431 50 339818 800 110( 3/8" (0S303) 1/2' 336432 50 333519 300 HDI 1/2" (55303) 5/6' 336433 25 339820 100 801 5/0" (S5303) 27/32' 336434 25 339621 100 8131 3/4" (S5303) 1" r 522 HO Product Tac Mice, 0611110 116 complete parkmane. as. Embed Anchor Length 1. 1-0/16" 2' 2-9/16" 3-3/16' 111110044. Anal. Length 1' 1-9/16' 2' 2-9/15" 3-3/18' Ufa:1bl° Thread Length 7/1V, 5/8' 11/16' 7/8' Useetle llyead Length 7/16" 5/8' 11/16' 7/8' 1-3/e' Internal 5000/11501 1,00113 Thread 4000 p010071111010' Sze 30115011 /411 51010/1411 570 - sas..„ 3/8" 1115 1250 ,ii.r. 1785 2125_ 5/6" 2920 3250 , /4! 4005 5009', Intemal Traced Soo 1/4" 3/8' 1/21 5/8" 3/4' 5006008008000 4000 psl concroco' Tonafon 611) 5110011 141) , 480 809, 1040 1230 _1540 2790.: 2630 4510 3630 5560 rr 311111; . marECE AAAANNWANAAV.W.A Wthout As Note Per The nese plans have been r Prevention Bureau for co standards. Acceptance i omissions which do not a standaras and °romance adequacy of design rests Additions, deletions or re ornments In Red ttached Letter viewed by The Tukwila Fire formance with current city ubiect to errors and thorize violations of adopted . The responsibility for the totally with the designer. ision o tc: drawings atter this date will void this acr2ptance F,rid will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: Weld stamps must inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. FHLPCTHD CF \G PLA\ ' 8' 10' 12' 14' 16' 18' TUKWILA FIRE DEPARTMENT, Please call: 575-4407 and give thls job and exact address for shut. down or restoration approval. Because of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-575-4407 or email fireinsprequest(@ci.tukwilafwa,us to schedule your inspections a minimum of 48 hours in 'advance of the want an inspection. SPRINKLERS We _az, Vbe 4WD. • 0 ISSD t55° kg" Vt Korn 1-16ZR, 4 DATEZ.--03 SCALE atbircia PIPING PLAN & DETAILS B S W,LYITRACE SPACLNG FOR LATERALS AND LO." rVDINALS SHALL BE -Mr AND RM' R.LSPlx'TIVE x.v FOR ALL NEW MAIN PIPING. i-001 (3 3.$4 EMBED LENGTH) FIG. 910 TYPICAL 1Y7 BLACK STEEL PIPE (SO+I4D. 40) (LENGTH NOT TO EXCEED T-01 LATERAL BRACING FOR MAINS rAir FIO.i000 FAST CLAMP 1/2 -HDI (3 1,4'81113E13 LENGTH) FIG. 810__ TYPICAL 1' BLACK STEEL PI (SCHED. 40) (LEITH NOT TD EXCEED T.0") LAT ERAL BRACING FOR MAWS UP TO 4' FIG. 1000 FAST CLAMP S1' HOi (33.44' . LENGTH) FIG. 010 C- TYPICAL I Y.' BLACILSTE,EL PIPE (SCHED. 40} 212 PIPE CLAMP LONGITUDINAL BRACE FOR MAINS a• & B' F10. 010 :ry' •\ TYPICAL ,F7 HO1 (s ihr EMBED LENGTH) 1' BLACK STEEL PIPE (SCHED. 40) 717 PIPE CLAMP LONGITUDINAL BRACE FOR MAINS UP T04' LEAF SPAM CZ3:A122JRATIONANO DTIT7CTATH)■ RFVFOi NBT at>i tnartTTiEn A�2 •1A S.1020tCt S.1O t eAf sTw,Na FIAT T3 MtruAI1 PIN LAM RfOLPAL010A01/6 TIOPTTEiiHEX NUTS I.kTIL t TX I.OtlNC ' /LAX LAra ALEARTHQUAKE BRACE .57p SFOTIIO GDNf 171J KA110N T"g1107,d.,s BOTTOM BEAM CLAMP, ROD, MID ANG ?V 0 } 110. M RETAINING STRAP CY_K NUT RECTO !WAN Ai'AAICLiLIP __. FID. t CO ALL THRCAD ROD Fl0.200 NatUIrTAALE RT HKiOUt TOP BEAM CLAMP. ROD. AND RING FIG. 1000 FAST CLAMP-' 1' BLACK STEEL P' (SCHED. 4f11 12' H TYPICAL (215' FAIRED LENGTH)TYP I410 FIG. 1000 FAST CLAMP RISER BRACE (FOR ALL MAIN RISER DIAMETERS/ FIG.1000 FAST CLAMP FIG. 1000 FAST CLAMP 1' BLACK STEEL PIPE (LCHED.40) 112" HDI TYPICAL (2W 1348EP LENGTH) o*ik! 1 -TYPICAL FIG. 1000 FAST CLAMP RISER BRACE FSG. 1000 FAST CLAMP C'a LATERAL EARTHQUAKE BRACE 1u`r.( K14•11#4cAOCD ORAD P(Pt teen a, on IT LAAWERSAI. SWIVEL SWAY BRACE ATTACUMENT 1440) i+000CONSTRUCT l4v T AVOWS �` FAST CLAMP RISER BRACE T a,TOitAMy EARTHQUAKE SWAYBRACE DETAILS AND COMPONENTS SWAYBRACE LOAD CALCULATIONS PIPE SIZE BRACE SIZE BRACE SPACING LAT LONG ASSIGNED LOAD Obs.) MULTI P LYING FACTOR K .B NFPA 613 TABLE 4-6.4.3.5.3 BRACE TYPE ATTACHMENT TYPE W/ MAX LOAD VALUE (Lbs.) a 8" 4' 3. 214" SCIIA4O 151' SCN.AO I" SCH.4o r SCH.40 1' SCH.40 3Q 40' 40' 40' 40' 80' 80' 80' 80' 80' 2186 2088 1392 1304 1266 Hanger No. 02C Concrete Anchor None an Elam Hanger Number and W Dienemskin Hanger No. 03C Concrete Spike Wean Mara /ismer Miner and WM:tension Hanger No. 05C Concrete Anchor HILTI 3/9' liDt.P AI Rod Shrivel RINI q. Pico ConsInschon COrillt Una of Rpi Note on Pion: ftinger Nurntem and 'A' Dm -arnica Hanger No. 14S Inverted Top Beam C -Clamp wiTh Retaining Strap (Beam) Note ea Nom Hoot Numbortzttl 'A' OnnentIon Hanger No. 03T Pipe/Top Beam C-Clemps /*Top Belem Chimp ot Egad Hanger No. 13S Top Beam C -Clamp with Retaining Strap (Joist) Not* on Mal: Hanger IaLL-ntse and W DimessHi TYPE •B' TYPE "B" TYPE 'B' TYPE "9' TYPE "8' 6/8' BOLT = 2857 SIB" BOLT = 2857 112" BOLT = 1782 112' BOLT a 1782 1/2" BOLT - 1782 P0.010 SWIVEL 1 NAY h ACEF,TTNCI no TOOL FA3TCLAUF DRAT {RA Ci AtThOW2+1 LATERAL EARTHQUAKE BRACE M ACE PIPE 1T RFA0 CO CNt k` O Hanger No. 185 Acqustable Pipe Stand Peon SLUR* We 0-11(*9"Pl Pod bNIP7:14th.) er of Threads - C.13 Base 1.01 Sth 40 Threndon Fest* Roar to CANFmLgrel Pim Hanger No. 07C HUT! Kwik Bolt II Dried Anoka!' t Note on Ram Hanger Rumba: and 'A' Gammon Hanger No. i 5S Inverted Top Beam C -Clamp with Retaining Strap (Joist) Shad 1-Boarn or Bar Joist - Rounded to Nearest Inch Rire Tee B111111 C-Cbierp Or Eqvai Nat* on Pim: Honger-Numboir and 'A' Olmention 1-10.1100 134TAT SPATE ATTACHLiENt STEEL L SEAL SWIY21. SWAY SPACE FiTma SWAY BRACE ATTAC1.1MENT TO STEEL I•BEAAI 1 PIPS Ci.Aote root *WAY SVGA. LONGMIDINAL EARTHQUAKE BRACE 10344,4gEA.D.:12 aRAct Di Di: rval AND ALL Egariaa 2s RATIONS FLEXIBLE COUPLING 1TYP HoLe MR SLEEVE, CHROME ESCUTCHEON."' PIPE SIZE CORE DETAIL THROUGH WALLS AND FLOORS NTS HANGER NO, 175 STEEL SAMMY SCREW AND ROD NOTE PLAN; HANGER NJMIIIER AND 'A` DIMENSION Hanger No. 04T UnIstrut/Top Beam C-Clarnps Inverted or Joist Noto on Pew Hanger Wanner. Dinvansion, Hangar No. 12S Top Beam C-Ctemp with Retaining Strap (Beam) STEEL PIPE HANGER LOCATION DETAIL PIPE SIZE A CI* C STEEL PIPE I ill ' MAXIMUM STEEL HANGER SPACING FOR THREADED LIGHTWALL PIPE IS 17-0" FOR ALL PIPE SIZES HANGER NO. 18S AND ROD --Z PURUN NOTE ON PLAN: HANGet NUMBER AND "A' DIMENSION 1-ianger No. 20S Sammy Xpress f `••-- ma 70 STC33.CCJLwO 0.LAT6 ___.. FIC. IDS ALL THREAD ROD Ina. ac A0wa-r W LL RY43 P.Ati:CA CEILINGS PLATE, ROD AND RING Yk,TA1 D*CRDN w57ALLATICN all4 WAY EARTHQUAKE BRACE !AT le,AL!{.tSf1C C1 LNaPAL MATI,OiLAKA 5RAG T_6900tLd.e RISER ROOM EQUIPMENT 1. RELIABLE 6" MODEL 'G ' RISER CHECK VALVE 2. VITAULIC 6" FIRELOCK #771 GG OS&Y GATE VALVE 3. 2" MAIN DRAIN- DISCHARGE LOCATION TO BE DETERMINED. 4. GLOBE ANGLE VALVE 1" TT 5. AGF TEST AND DRAIN VALVE 2" TT, MAIN DRAIN 6. SYSTEM SENSOR 6" WFD SERIES WATER FLOW SWITCH 7. SYSTEM SENSOR 4" WFD SERIES WATER FLOW SWITCH 8. VICTAULIC FIRELOCK 6" no4 FLEXIBLE COUPLING 9. SYSTEM FDC FEEDS FOR RISER ROOM 'A' AND 'B' 10. RELIABLE MODEL 'G' CHECK VALVE GG FOR FDC 11. 6" UNDERGROUND FOR FDC'S TO FEED 10" PIPE THAT IS TO SUPPLY EXISTING MALL SYSTEMS. TO BE INSTALLED BY OTHERS. 12. UNDERGROUND FOR FDC'S TO FEED NEW SYSTEMS IN MALL EXPANSION. TO BE INSTALLED BY OTHERS. 13. DRY SYSTEM FEED RISER ROOM 'A' AND 'Er. 14. VICTAULIC FIRELOCK 10".#004 FLEXIBLE COUPLING 15. VITAULIC 10" FIRELOCK #771 GG OS&Y GATE VALVE 16. 10" RISER MANIFOLD 17. RELIABLE MODEL 'D' 4° GG DRY PIPE VALVE WiTRIM 18. WILKINS 10" 350 DAG VERTICAL BACKFLOW PREVENTER 19. 10" VICTAULIC #705 BUTTERFLY VALVE 20. 10" SYSTEM UNDERGROUND, TO BE DONE BY OTHERS. 21. 10" SCHEDULE 10 PIPE TO BE INSTALLED DURING MALL EXPANSION TO FEED EXISTING MALL SPACE. 22. VITAULIC 4" FIRELOCK #771 GG OS&Y GATE VALVE 23. RELIABLE 4" MODEL 'G ' RISER CHECK VALVE 24. VICTAULIC FIRELOCK 4" #004 FLEXIBLE COUPLING 25. GAST AIR COMPRESSOR FOR DRY PIPE SYSTEMS Lk MODEL 26. SYSTEM FDC FEEDS FOR NEW 10" IN EXISTING MALL. 27. SPARE HEAD SPRINKLER BOX FOR 24 HEADS WITH WRENCHES 28. HEADER FOR MEANS OF FORWARD TESTING BACKFLOW. INCLUDES HOSE VALVES TO RUN HOSE OUTSIDE TO EXTERIOR ON LOADING DOCK. NOTE: WEST LOADING DRY SYSTEM= 44 GALLONS EAST LOADING DRY SYSTEM= 33 GALLONS -ZONE INDICATOR 7 01.F0 MIL 25 1.1.4A;22 RESCRAINEF1 Prat 2. FOR 14/2* AN22` PIPE AlISHANOAR 011e VIEW OF soAc 'cols ALL s-inun nos /r2.1:0 P' 713 SlinCAS its trTNAvoiA, 011,11171.CO MK) WkNOVI M. 709 AIM 21,4PA TO PCS -TOM 71.6 UPWARD L+CrySitett OF PtP6 Ir OCCURS OVII MG SPRINKLE -RHEA!) FIGURE 25 SURGE RESTRAINER FOS arm Om cmia .Last la PIPE \ a i W'ertlit D 1.010N ALL nift CAD POO LATERAL BRANCFILINE RESTRAINT PIPE CLAPP MR SWAY 141.14-6 LONGITUDINAL EARTHOUAKE BRACE • • AOC SS PAtla ALiea BUTTERBALL VALVE DETAIL - NTS FOR ELEVATOR MACHINE ROOM(S) WEST RISER ROOM -SECTIONAL VIEW MANW EAST RISER ROOM -SECTIONAL VIEW LAA JO/ OA RACE AITA2riikli-e' Vit, 10 :0,4! 111111111111111111// er, .tizing:ippinFire ATTACIati mi -A FIGURE 825 USIDOTA.T WITH °THEIS 301..0.0 SEISMIC SEPARATION ASSEMBLY 1Y,'OR 1W FiRELOCK *DOS RIG) COUPLING SHURJOiNT 14.00a MI awl tiOt. Went EARS TOLICN i'‘,164i1SNSIZEEL PIPE ar ArtIVERILLMIE ITEM. SCHEXILICti ALL OPT TTATE./CALS CAST MOOR PoOTILS 15(44' THREADED RENDE =I, IS ItiftUlt [AIM. ISPACIWG Poo?! • FIG.2001 SWAY BRACE ATTACHMENT 402103 CONtcr.• RUCTION 7..7001 Avg SHURJOINT END-ALL FITTING DETAIL(TYPICAL) • ma 100 T1.111EALI R00 ALLIVST AUL R1742 KAAT.:C.Tt SELF DRILLING ANCNOR, ROO AND RING PTO, Fal SWAT SPACL At TALI4AEAT TO DRAGE, Firm) Fla AA PIPE. CLAW SWAY it R ACE AT TACHILIPNT TO STEEL 1.11Efue Note on Plan'. Henget Mlle.:rand "A' D'o..:ntion WEST RISER ROOM -PLAN VIEW EAST RISER ROOM -PLAN VIEW -414 Iowa DRAWN BY: Martin SokuIski DATE: 08/21/07 PLOT DATE 08/21/07-06:4-3:16 CONTRACT NUMBER 790228 DRAWING FILE NAME SHEET FP 2 OF AID SHEET FP -3 IZEILTJEHMIEICZE3 1:313MBEMIDIUMMUCIMEIE3C3IZID SHEET FP -4 NOT A PART OF CONTRACT/PERMIT 1:21131 CA El LE CZ 111 DEa El ,E1L1NGS -1.1\1A HINE "4011 *44 $owit lutz) tis) co) al= Cat) 41) '4=0 It* Cie ;2124 0 ••t' "S LI? 0 00 00 10 fl 0 CTRICA OM N.)1? OPY PLAN S (A8.3-7) ..;."a 0 10-0-- - 10-0 N N N? •SR \)1 N§ vcs. N 41' ‘ ,14:k$ + 44e, 0. et, - Kti VO,i WI Fal ; !AI q.-11 iskOM m iM a"; YIS 41X 5'4 7,04i ,kite% ,a.f.4 'r.in mot azi la r4.46 tw: a wi 4. ..tio J TO (ABOVE 10 10-0 —424 ALL ST RAGE Li A.F.F LJU ( 10-0 01 . 11 02N0 Et NES HV ONLY r.74 —1— air 11111111411111111111111111 4111E11 - .4 101L*."'Ill OPE(' DEC( 19'0frmmuimmr, Asigegi,=, NOT A PART OF CONTRACT/PERMIT BY TE ANT "KT 11141111111111117 111 '*• 4:11.ga EGRE. RRIDO OPEN TC e?ECK ABOVE— E.: EVATO II :WPM III I PEN TO — ECK ABOVE .12 1 POTENTIA FABRIC CANOP\ BY TENANT -re* .41111g4.1ralitazi.a4 VittAzit LEASE LINE OPEN 7 0 F1)4 Pig IRA op 4,0.01: 0 UTHCENTER EXPANSION Remote Area: 1st Floor - Loading Dock West rat* g055rt CEILINGS BY TENANT lualutropicrxjaztztizzarecrzw, CALCULATION DESIGN CRITERIA: STANDARD NFPA 1 3-2007 OCCUPANCY CLASS Uralnary Hazard II MAX. covePAoE per HEAD 130 DENSITY .20 GPM 1 Fr for 957 Ft, Fr spainKLER Reliable Model F3QR DRY ORIFICE 1/2" WATER FLOW INFORMATION': STATIC 140 NO OM NO STIB E CA REO HIED Rs6iDuAL 20 novv 10900 PSI GPM AT BASE OF RISER. SYSTEM REQUIRES: 528 GPM GT 62 PSt +16-1"A.F.F. ' AI time of Dosion . . • 'RAMP PNY AYpTE10 PR ...SUGGESTED. TO BE FE EXISTING FAIWNG ST •'.PENDING APPROVAL P .AKI; • . . • 4.. • o o o o s .44.1 • Sprinkler Legend MFR./MODEL Reliable F1FR SSU Reliable FIFR SSP r g i A TEMP. ,.... rn t° .... tel 5,2 155°F I ... g.p -.°, ,.. N T,-, 4.10 tl i'zi Er_lill I Lb -42: OR kkkkk SPRAY I tigifoi ( ccg ‘Ti :f -i fi t ..." co Total = 2932 I :.--: :PI: >-- cn >-• m I. hilbisiiimmilillimi k...):K4).k4 hill 11:114.° Pill: A k / co z o 0 rt z o ff Er" (..) fp U.1 0 City of Tukwila Review 4:C CI C) DRAWN BY: Martin Sokulski DATE: 08121/07 PLOT DATE: 08/21/07-07:4246 SCALE: 1/8"= 11-0" co ct) 4-0 anC 4rna 0 co Fire Protection Area '8' Level I CONTRA NUMBER 790228 DRAWING FILE NAME JR -Level 1.cad North SHEET FP -4 OF 21