PP - 616 SOUTHCENTER MALL - SEPHORA - PERMITS AND PLANS
616 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-106 08-S-095 FILE COPY FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sephora 616 Southcenter Mall Permit No.: 08-S-095 Date: March 31, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 20' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. TUfILEIJF1 [I Fre :_ t:',:: 21 March 2008 Martin Sokolski Westem States Fire Protection 7102 180th Ave NE, Suite A-105 Redmond, WA 98052 RE: Westfield Mall — Sephora (Suite #616) Independent Third Party Review — Fire Sprinkler System Tuazon Engineering PLLC 4322 NE 7°' Street Renton, WA 98059 425.917.1683 tel 425.917.1705 fax www.tuazon.com As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. It is noted that the sprinkler system modifications shown are to Zone 12 fed from the West Riser Room. The following was reviewed: • Fire Sprinkler Drawing — Sheet FP1 dated 3/20/08 • Hydraulic Calculations dated 3/20/2008 The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Ensure storefront show window areas are provided with sprinkler coverage per NFPA 13. It appears there may be a wall or ceiling break at the east window area that may prevent sprinkler coverage. 2. The hydraulic data table on the drawing lists a maximum coverage per head of 130 SF. It should read 120 SF to match the hydraulic calculations. 3. Please include applicable product data with the permit submittal to the City of Tukwila. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or eric(&tuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING PLLC Eric P. Tuazon, PE Fire Protection Engineer CADmvaniFbd2009Piejsc1020E19WW•InE1101-116.11.118whonalrraelluesesprhlarmitwdoe m11 Hydraulic Summary Job Number: KS0287 Report Description: Sephora Zone T2 Job Job Number KS0287 Design Engineer Martin Sokulski Job Name Sephora State Certrfication/license Number WESTESF136QF Address 1 616 Southcenter Mall AHJ City of Tukwila Address 2 Job Sae Southcenter Mall City Tukwila State WA Zip Code 98188 Drawing Name FP1.cad System Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 975.00ft2 (Actual 1006.71ft2) Additional Hose Supplies Node Flow(opm) Number Of Sprinklers Calculated 9 Coverage Per Sprinkler 130.00ft2 l ' • fi l ` .L, /..•it.'t ' � lk NilVil %lei Total Hose Streams 250.00 System Flow Demand 253.73 Total Water Required (Including Hose Allowance) 503.73 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocdy Above Ground 21.22 between nodes 133 and 256 Maximum Velocity Under Ground 0.96 between nodes 1 and 439 Volume capacity of Wet Pipes 2009.32ga1 Volume capacity of Dry Pipes 0.75fts Supplies Node Hose Flow (gpm) Static (psi) Residual @ Flow (psi) (gpm) Available @ Total Demand (psi) (gpm) Required (psi) Safety Margin (psi) 1 250.00 140.000 20.000 I 10900.00 139.594 I 503.73 81.941 57.652 Contractor Contractor Number KS0287 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 E-mail City Redmond State WA Zip Code 98052 Web -Site Hydraulic Summary Job Number: KS0287 Report Description: Sephora Zone T2 Job Job Number KS0287 Design Engineer Martin Sokulski Job Name Sephora State Certification/License Number WESTESF136QF Address 1 616 Southcenter Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila State WA Zip Code 98188 Drawing Name FP1.cad System Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 975.00ft2 (Actual 1006.71ft2) Additional Hose Supplies Node Flow(qpm) Number Of Spnnklers Calculated 9 Coverage Per Sprinkler 130.00ft2 I I ' • fi i ,`/, � •��t ,/I 11)if air Lk 7 ' ] VJi % NJ� f 4111140D� Total Hose Streams 250.00 System Flow Demand 253.73 Total Water Required (Including Hose Allowance) 503.73 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 21.22 between nodes 133 and 256 Maximum Velocity Under Ground 0.96 between nodes 1 and 439 Volume capacity of Wet Pipes 2009.32gal Volume capacity of Dry Pipes 0.75ft3 Supplies Node Hose Flow (gpm) Static (psi) Residual @ Flow (psi) (gpm) Available @ Total Demand (psi) (gpm) Required (psi) Safety Margin (psi) 1 250.00 140.000 20.000 1 10900.00 139.594 1 503.73 81.941 57.652 Contractor Contractor Number KS0287 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 _ Address 2 E-mail City Redmond State WA Zip Code 98052 Web -Site 11B Summary Of Outflowing Devices Job Number: KS0287 Report Description: Sephora Zone T2 Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 105 28.80 26.00 5.6 26.440 Sprinkler 109 30.69 26.00 5.6 30.031 Sprinkler 104 27.38 26.00 5.6 23.908 Sprinkler 108 29.74 26.00 5.6 28.204 Sprinkler 103 26.45 26.00 5.6 22.302 Sprinkler 106 29.24 26.00 5.6 27.259 cJ Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 102 26.03 26.00 5.6 21.614 Sprinkler 107 29.40 26.00 5.6 27.572 Most Demanding Sprinkler Data 119 Node Analysis I Job Number: KS0287 Report Description: Sephora Zone T2 Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 133 14-10 2P0(8-0) 60.036 119 14-10 2P0(8-0) 60.001 256 14-10 P0(5-0) 35.113 263 14-10 P0(5-0) 39.639 277 14-10 P0(5-0) 31.764 266 14-10 P0(5-0) 37.241 297 14-10 P0(5-0) 29.636 287 14-10 P0(5-0) 36.000 312 14-10 P0(5-0) 28.647 322 14-10 E(2-0) 28.631 325 14-10 E(2-0) 35.604 399 1-11 T(50-0) 74.816 409 1-11 P0(26-4) 74.784 439 5-8% BFP(-4.500) 77.702 105 13-71/2 Spr(-26.440) 26.440 28.80 109 13-7% Spr(-30.031) 30.031 30.69 104 13-7% Spr(-23.908) 23.908 27.38 108 13-7% Spr(-28.204) 28.204 29.74 103 13-7% Spr(-22.302) 22.302 26.45 106 13-7% Spr(-27.259) 27.259 29.24 101 13-7% Spr(-21.556) 21.556 26.00 102 13-7% Spr(-21.614) 21.614 26.03 107 13-7% Spr(-27.572) 27.572 29.40 1 -4-0 S 81.941 253.73 ill Hydraulic Analysis I Job Number: KS0287 Report Description: Sephora Zone T2 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge K -Factor Pt Pn Fittings Upstream a Route 8 DR 1.049 0=29.74 11.04 C=120 0.271121 24-3 Pf 9.553 108 13-7% q=29.74 K=5.6 28.204 Spr(-28.204) 266 14-10 37.241 3E(2-0), P0(5-0) 11-0 Pe -0.517 35-3 Pv a Route 9 DR 1.049 0=30.69 11.39 C=120 0.287330 24-3 Pf 10.125 11-0 Pe -0.517 35-3 Pv 109 13-71/2 q=30.69 K=5.6 30.031 Spr(-30.031) 263 14-10 39.639 3E(2-0), P0(5-0) Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1 C Value Multiplier 4 Value Of C 100 130 140 150 Multiplying Factor 0.713 1.16 1.33 1.51 Actual Inside Diameter l4.87 ( Factor Schedule 40 Steel Pipe Inside Diameter / = Pipe Type Legend Units Legend Fittings Legend AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG UndergroundPv Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen -Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve Defy Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow - Eel 11W Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose I-IV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap 111 Hydraulic Analysis Job Number: KS0287 Report Description: Sephora Zone T2 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge K -Factor Pt Pn Fittings Upstream Route 1 DR 1.049 0=26.00 9.65 C=120 0.211435 25- Pf 7.608 11- Pe -0.517 36 Pv 101 13-7% q=26.00 K=5.6 21.556 Spr(-21.556) 312 14-10 28.647 3E(2-0), P0(5-0) BL 1.610 0=52.03 8.20 C=120 0.094745 10-5% Pf 0.989 I Pe 10-5'/ Pv 312 14-10 28.647 297 14-10 29.636 BL 1.610 0=78.48 12.37 C=120 0.202640 10-6 10-6 Pf 2.128 Pe Pv 297 14-10 29.636 277 14-10 31.764 BL 1.610 0=105.86 16.68 C=120 0.352521 9-6 9-6 Pf 3.349 Pe Pv 277 14-10 31.764 256 14-10 35.113 BL 1.610 0=134.66 21.22 C=120 0.550160 33-3%2 12-0 45-3'/ Pf 24.923 Pe Pv 256 14-10 35.113 133 14-10 60.036 2LtE(2-0), P0(8-0) CM 4.260 0=253.73 5.71 C=120 0.015542 397-5 Pf 9.155 133 14-10 60.036 191-7Y 409 1-11 74.784 12fE(8-11%), 2fEE(4-5%), 589-1 2Ee2(5-3), fE(6-91/2), CV(28-11'/2), GV(2-7%), P0(26-4) Pe 5.593 Pv FM 8.329 0=253.73 1.49 C=120 0.000594 21-10 Pf 0.032 409 1-11 74.784 32-0 399 1-11 74.816 2fE(16-0) 53-10 Pe -0.000 Pv MS 10.020 0=253.73 1.03 C=120 0.000241 20-2 Pf 4.521 399 1-11 74.816 67-0 439 5-8% 77.702 3LtE(16-0), BV(19-0), BFP(-4.500) 87-2 Pe -1.635 Pv UG 10.400 0=253.73 0.96 C=140 0.000151 113-1 Pf 0.039 439 5-8% 77.702 146-8 1 -4-0 81.941 3LtE(25-6), E(35-1), 2EE(17-6'r), 259-9% S Pe 4.200 Pv 0 Route 2 DR 1.049 0=26.03 9.66 C=120 0.211961 27-6% 8-0 35-6% Pf 7.533 Pe -0.517 Pv 102 13-71/2 q=26.03 K=5.6 21.614 Spr(-21.614) 322 14-10 28.631 4E(2-0) BL 1.610 0=26.03 4.10 C=120 0.026314 0-7% 0-7% Pf 0.016 Pe Pv 322 14-10 28.631 312 14-10 28.647 Route 3 DR 1.049 0=26.45 9.82 C=120 0.218194 25-0 11-0 36-0 Pf 7.851 Pe -0.517 Pv 103 13-7% q=26.45 K=5.6 22.302 Spr(-22.302) 297 14-10 29.636 3E(2-0), P0(5-0) Aw Route 4 DR 1.049 0=27.38 10.16 C=120 0.232690 25-0 11-0 36-0 Pf 8.372 Pe -0.517 Pv 104 13-7% q=27.38 K=5.6 23.908 Spr(-23.908) 277 14-10 31.764 3E(2-0), P0(5-0) 46, Route 5 DR 1.049 0=28.80 10.69 C=120 0.255398 25-0 11-0 36-0, Pf 9.189 Pe -0.517 Pv 105 13-7% q=28.80 K=5.6 26.440 Spr(-26.440) 256 14-10 35.113 3E(2-0), P0(5-0) o Route 6 DR 1.049 0=29.24 10.85 C=120 0.262710 24-3 11-0 35-3 Pf 9.257 Pe -0.517 Pv 106 13-7% q=29.24 K=5.6 27.259 Spr(-27.259) 287 14-10 36.000 3E(2-0), P0(5-0) BL 1.610 0=58.64 9.24 C=120 0.118197 10-6 10-Pv Pf 1.241 Pe 287 14-10 36.000 266 14-10 37.241 BL 1.610 0=88.38 13.93 C=120 0.252460 9-6 9-6 Pf 2.398 Pe Pv 266 14-10 37.241 263 14-10 39.639 BL 1.610 0=119.07 18.76 C=120 0.438182 34-5Y Pf 20.362 12-0 Pe 46-5% Pv 263 14-10 39.639 119 14-10 60.001 2LtE(2-0), P0(8-0) CM 4.260 0=119.07 2.68 C=120 0.003834 9-2 Pf 0.035 Pe 9-2 Pv 119 14-10 60.001 133 14-10 60.036 Ge Route 7 DR 1.049 0=29.40 10.92 C=120 0.265492 24-3 Pf 8.559 8-0 Pe -0.526 32-3 Pv 107 13-7% q=29.40 K=5.6 27.572 Spr(-27.572) 325 14-10 35.604 4E(2-0) BL 1.610 0=29.40 4.63 C=120 0.032960 12-0 12-11 Pf 0.395 Pe Pv 325 14-10 35.604 7527 , d_1 n IA nnn 111,Hydraulic Graph I Job Number: KS0287 Report Description: Sephora Zone T2 Supply at Node 1 150 J Static Pressure 140.000 135 120 H 105 90 •) a 503.73 X53.73 with hose @ 81.941 streams g 75 fn m at a 60 45-' System demand curve 30 10900.00 @ 20.000 15 a —IIm IIIIIIIII 111111111 I I I 111111 111111111 I I I I t I t( t I I t t I t I I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 t ( t I 1 1 1 0 91002200 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.594 © 503.73 System Demand 253.73 @ 81.941 System Demand (Including Hose Allowance) 503.73 @ 81.941 I 111 Flow Diagram (Top View) Job Number: KS0287 Report Description: Sephora Zone T2 11E FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYTEM FA -04 SITE PLAN, SYSTEM CALCULATIONS (GENERAL), RISER DIAGRAM WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATIDN SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWO #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWO #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TW❑ #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2' .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS. SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL -BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2002 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2002 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 4 1 3 9 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM XLS-V CONTROL PANEL SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP 1 BPS 1 REMOTE BOOSTER PAD -3 POWER SUPPLY SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD T -D DUAL INPUT HTRI-D INTERFACE MODULE SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT HCP MODULE SIEMENS 4S DEEP VERIFY IN FIELD 1 HZM 1 REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM l N SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED :VERIFY IN FIELD SMOKE DETECTOR HFP-1 1 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -1 1 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE AD2-P W/ SIEMENS p DETECTOR TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR HFPT-11 W/ SIEMENS (ADDRESSABLE) DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE ZR -MC -CW SIEMENS _ - (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. IN/ 1-1/2" EXT. TO BOTTOM 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM WP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE MR -201/C AIR PRODUCTS 4S BOX CONTROL RELAY VERIFY IN FIELD DOOR HOLDER MAGNETIC F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA -BOX FIRE ALARM F.B.O. TERMINAL CABINET F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED 13Y OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF N/A DEVICE N/A N/A N/A RED AS BUILT ADD OR CHANGE. N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A Without Comments AS Noted In Red Per The Attached Letter AS ILT N/A BLUE' , ,N❑T 6 I�PIRE DEPARTMEI end give this job end exact st Town or restorationaddressfor apphurova14 nese pl^ns have been reviewed by The, Tukwila Fire Prevention Bureau for conformance with current city standards. Ac:,eptarce is tiuhiect to errors and omissions which do not authorize violations of adopted stam:I:?ras and °roti; ?nces. The reiponsibillty for the c-{fU->_, r n f is tet n +` iih the de'.'':gner. ot .z:o tht-;3e cera,.,ings atter and ,+; require a C resubmitta: of sL. c: dra.11ings for subsequent approval. t Final ,ptmce is subject to field test and inspection by 1 T to TuWrila Fise Prevention Bureau. Gate: 1- O 3 By: S (( N/A N/A N/A NOTICE completed, signed, Tukwila Fire Department Pre-test ertificate must be presented to the Inspector prior to mmencement of Acceptanc1 Testing of any Fire Alarm and Detection Systems. Failure of test will result a Re -inspection Fee and rmination of the testing, - -i - n jb I ( 10(11 OS}- o(cvr(-e Oh FA SyGrc,c4- b.. c'ke• coal,tY. t,�:�, ,v P•4 7a- Qat . } o• ri•ht 2006 b 2008 Tukwila Fire 2sT1y14'z, Guardian Securit S stems, Inc. All Ri . has Reserved oC C. z 0 z_ cn LU J LU (/) r� Lu (1) FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE/REVISIONS w DESCRIPTION U.1 0 z t, J z z O 0 z V z E J CD J fICALE: i /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: ,1OB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT IMDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' VIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS \--DUCT DETECTOR LOCATION o TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT a LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.GK 1/4W) SUPERVISED SWITCH 0 GROUND O O d HTRI-R STATUS LED 0 N 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. © TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL W LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) - PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING - TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NQNE MUSIC 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE ,f STOP IF LAST DEVICE 1(¢j FROM XLS CONTROL PANEL OR 1t¢, PREVIOUS ADDRESSABLE DEVICE H-) END OF LINE ± 1 DEVICE 0 (3.6K 1/4W) SUPERVISED I � / RELAY CONTACTS SWITCH / (4.0A @ 125VAC) GROUND - -� ' (4.0A @ 30VDC) 27 VDC 3.5 rIA DURING POLLING 10 OHMS 200 FT. (18 AVG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. I& I TBI 550000 2 3 4:5..6. • HCP TB2 654321 r O O� HTRI-D OSTATUS LED CO 0 N. 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 GND N AC 0 0 U 0000 0 PAD -3 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX • .1+. 1-. ,1 2+ 2-. 2 NC C NO + -- + - + + + - KO*llIv I N31 111 IMI 24K NOT USED FRONT VIEW NOTE FOR ADDITIONAL SPECIRCATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP .. 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS EOL p 0 INPU P Pi7P9 T M-1 0 o�Id zL_ RK Pu ORO �.a L.- MOO e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE FROM REMOTE POWER SUPPLY ('S' CABLE) END OF LINE DEVICE FRQM;EACP .. 3.6K 1/4W) (VOICE CIRCUIT) UPERVISED WITCH ('V' CABLE) n r. t) {) STROBE SPEAKER �) (-) EARN GROUND 0 _►(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE (STR❑BE) (STROBE) SPEAKER (+) (—) SPEAKER/STROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 2 NAC -4 2 NAC -3 2 NAC -2 NAC -I 80" AF.F_ 4S DEEP BOX W/ 1 -1/2 - EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR :END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERAIIN TEMPERATURE: + 32 F 0- C) TO 100' F {3(1 C) •x RELATIVE HUMIDITY. NM-CUMMING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSAD.E DEVICE OR POKER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS LISTED FOR AIR VO.OITY APPLICATIONS OF 300-4000 HAIN MEN USED IN CON.AINCTION WTH DUCT HOUSINGS AD -11P OR M)-11XPR REAR VIEW > ( ) DATA OUT 1 (+) DATA OUT J} HFP-1 1 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID ---- HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE ------ 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION - CEILING MOUNTED --� SPEAKER/STROBE �. CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE JUNCTI❑N BOX MOUNTED ON CEILING FLEX UNCTION BOX ------- ❑UNTED AGAINST EILING SUPPORT / / / / / / / 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m Lu Ct DESCRIPTION Lu C:1 0 0 1 I TO NEXT DEVICE O O -----CADDY BAR MOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE ---SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO CO J r J a, 2 Z < w oco Cr w c� z_ w= W Q� c,cco� z z 0 z Z J (SCALE:1/8'1=1' DRAWN BY: !.ANDERSON DESIGNED : BY: R.VEZZANI DATE: 2/27/08 BACKROUND;PLAN PROVIDED BY: B ; C.3; ; D ' ADJACENT TENANT E E.7 ,.E.10; H i I RK:VsINC.: L.* • — - • EOL T S1 S,2V 11 S,2 11 177 BUILDING CORRIDOR ; II .0-er" IL:ma , :,... ../,' ,.. ,,',,..,..:I.....:,:,..:.:.:::•:.,.....,..:.::::.:.:::4::.':,..!:,:.,::..i. III ,I1. 15 1 •;,..„ D. ;......' J, u.....;A !?:. L. ..:.X.:•:.N.:...:.:.;:,,,N.:.:.:.1,!;.:.:.;.:.;•,...,...,:, ;,,.....:4.:....,:!... x...,........X. :.......X.......;.,,N.,;.:,.;;•:.;.:.',':•;,....: "t -- (4- t , I Its -------------I ADJACENT TENANT ' I , [ , [ •[ • [ FXIS 1 ! 1 I L' 2 -en? MALL COMMON 10 - NORTH • OA Fl ALAV DLA 1 . . 1 , . • , • . • , . . , • . ' , • I • ' . , I.' cO Ci• 0 Cf) La 1.1_1 (1) U) LL3 >5 F- FAX (206) 628-4.990 TEL. (206) 622-6545 7. RELEASE/REVISIONS CO lij [ • 1 I . SCALE:1Y8„ DRAWN 1 BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND.. PLAN PROVIDED BY: \LJOB NUMBER: Copyright 2006, by Guardictn;SCurity Systems, Inc. All Rights Reserved A3ERC OMBIE__ ----------------------- ------ ------------•J E'j�- ALLERIE ELM 1r _/ ,l1 1.;) F - Li c 4 =. Cr. I_L i Li 10201 j: i 1 M _. P r_ =tii=ti IL,] El] 1545 iJ 1 PACIFIC ' 1..4I\I \IF A I`4 TIE= WALKING CO. 11;0 he be COACH 77, 1125 ----------------------- 171-1 171 .1 ��rl 35 1140 r 6t) 0 ta IC'.LET SYSTEM CALCULATIONS nm luoll 11W 11111!11 1M MP. . -----------1 11-1501 ILLUMINATIONS 11475, r.ECI'CLI`r nr-F. AZ N MAC GHLL URNIA PIZZA KITCHEN R1 NORTH LOM!!!!!,,, ecce P F CHANG'S P2 BUCKS Li 480 �+ fl 5 C- SEPHORA WESTFIELD SOUTHCENTER MALL SCALE 1132'=1' S,2V A S,2V A S,2V A S,2V A S,2V A S,2V A S,2V A S,2V 30 30 75 15 15 15 110 110 110 D D D 0,I LI o= D,I FA-BDX D IFACP EX 2S,V PSI I EOL1 STROBE SEPORA SEPHORA FACP ADD ONS SIEMAENS PAD -3 Signal Extender Panel Battery Load Calculations Current Load: .- Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 3 0.0635 0.0635 0.064 0.192 Main System Board 1 0.03 0.03 0.030 0.030 1 HTR -R 4 0.009600 0.0096 0.021 0.084 S_ET-MC @15CD ST -MC @3OC D .___� _. SET -MC @75CD 3 0.064 0.192 HTR I -D, y _-_._._tt-__-...___. .____._ 0.001600 0.0035 _- 2 0.098 0.196 1 0.175 0.175 SET -MC @110CD 3 0.233 0.699 �__.-____ _.« . �. m _ �r �._ ZR -MC @15CD 0.064 __ �____.v_..-.s�-..._.__ _ v._� ..m�___Y a.y�_- ZR -MC @30CD 0.098 -- __ _____._ 0.0731 Amps 0.276 Amps HCP 0.0015 R�F_y rtT}< 0.03 Amps 1.292 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.276 Amps For 5 Minutes= 0.023 Amp -hours Alarm Current Load: 1.292 Amps For 5 Minutes= 0.109 Amp -hours 25% Derating= 2.222 Amp -hours 25% Derating= 1.036 Amp -hours Total System Current Load: 2.222 Amp -hours Total System Current Load: 1.036 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH • Battery Pair to be Used: 12VDC 1 Amp -hours 7AH MOO 31( RECOMMENDED MINIMUM BATTERY SIZE = 7.00 Aripere*Hours BATTERY SIZING CALCULATION ,__Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel:l SEPHORA Date:1 Apri14, 2008 QTY - Device Type 3 !SET -MC @15CD -, 1 - 1 1 !Wire Resistance 3.24 . CURRENT TOTAL=i 2331 ;Alarm Current) Alarm Total 1 Wire Size { Wire Length Voltage at EOLw . Circuit Total�I 641 1921 i -- ;Total Wire Resistance (R) 2.14'=: r- SET-MC @30C D 981 1961 ;SET -MC @75C D 1751 1751 +SET -MC @110CD -2331 6991 4R -MC @15CD-_-�_._.,._.�._.._.._.__.�64',._�.�...,.�.�....�._.._.Of ZR -MC @30C D i _____. _ _ 98 0 1ZR-MC @75CD i 1751 0 1Z14 -MC._. 0CD____�_.___ ..__.------- --- 2331 0 1 I 1 DEVICES=19 { g----------------Ti-i 1 TOTAL m A=1 1262 1 12 330 �� _� � _._..�. �_,�..�,-�'l. otification.Av_��lariceWCrcuit,.D .---,� ��:.M_�.._,.._��r�n._ F -.___o__ -_i_. __..----.-__.-__ _-_�.�._�__�.._.� ___._.�.___.._ _-_.-_--�_-- _--__-___pl--------------------------------T etas i ; # WESTFIELD SOUTHCENTER MALL -------<-____--_.-__..._�..�_,-._----- -_____�_.�� ;PROJECT: ] L Panel: ; SEPHORA - - Date: 'April 4, 2008 1 CIRCUIT:'SPEAKER CIRCUIT i 1 _ ; :Total Device Load, Amps (I) 1.261 (Total Cct Load) I $ IV oltage Drop (E ) (E= I * R) ] 17.7013392 • ;EOL Voltage 17.701 _ (20.4 - E) ;Wire Resistance 5.16 CURRENT TOTAL=116.2 i QTY I Device Type !Alarm Current' Alarm Total 3 Wire Size 1 Wire Length 9 170.7V1/8 1.8E 16.21 I 0 jo 1 I 0 0 0 0 0 I 0 0 DEVICES=9 0'0` ' ] i I __pi » 0 0 01 01 01 01 01 01 -- 01 TOTAL m A= E 16.21 12 1 330 4 20.34482928 4 Voltage at EOL I Circuit Total 1 I !Total Wire Resistance (R ) (WL*2)*(R/ft) !Total Device Load, Amps (I) (Total Cct Load) ;Voltage Drop ( E ) f { EOL Voltage (20.4 - E) 1 - i 3.41! 0.021 0.06i 20.34' I; FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS W DESCRIPTION 0 «a<a Y5- co T - OD Z cr fit. -u O wcc ow= W <CO LEY (95D 0: - I - SCALE: 1 /32"=1 DRAWN BY: [:ANDERSON DESIGNED DI': R.VEZZANI SYSTEM CALCULATIONS DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: RISER DIAG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved JOB NUMBER: SHEET FA -04 i; ivA N N VICINITY MAP (Suite# 616) SCALE: N General Notes 1. Western States Fire Protection to add new pendent heads new u r�igght heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyin the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. WEST RISER DETAIL TUKWILA FIRE DEPARTMEN1. Please call: 575-440Z and give this job No. 02-S,os and exact address for shut' O•-.,nlrt or restoration aporov?J r 7 I 7 I I z ACC Wthout Comments Q As Noted In Red Fr Per The Attached Letter nese plans have been reviewed by The Tukwila File Prevention Bureau for conformance with current city standards. Acceptance is Itchiest to errors and omissions which do not outooii'3 violcticns of adopted standards and 0r:11—arises. i i I'_:,,;vri'_i Wily for the oequacy of de i jfi r�.. P,,:_.:;,' .. i;I tre designer. dditions, deletions or is s'i ion .: 'tiii, i drawings atter .;3 date will Void this acceptance w ii require a ..submittal of revised cirswirigs for subsequent approval. incl acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /3 o 8 By: 7�+' ` 1 In i 1 2-51/2 10-111/2 . ... NORM to M1 JQ + M 1 1 O,k° 8-7 0 /2 Existing 4" Main Holrzcu O °'Pi\ NN,' JQ�pQ o 1 �o 1, 0-4, 8-7 tom=¢ 1/ 0-6h/2 c a® O Existing 4" Main 0.41/2 Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. 1NVN311N3JVrOV 1NVN31!NJJVf0V ID FIRE SPRINKLER PLAN 0 o, -0 V 0 Sephora Remote Area: Retail #616 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Fey for 975 F� SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI 10900 GPM FLOW AT BASE OF RISER. SYSTEM REQUIRES: 254 GPM @ 75 PSI TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING als0 BRACE PIPE 3/9' KWIK BOLT (21/4' EMBED LENGTH) FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS 14014 -THREADED BRACE PIPE . At time of Design 13'4" CLG.=35% AREA REDUCTION FIG. 4A PIPE CLAMP FOR SWAY BRACE 319' KWIK BOLT (2 1W EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT BRACE PIPE bid NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT Ordinary Group Ih2p VICINITY MAP DETAIL Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL PA ma 2 2000 1 Tukwila Fire W W 2 U Lu2 Scheiner Commercial Group Inc CONTRACTO SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL APPROVAL: City of Tukwila 4 -WAY EARTHQUAKE BRACE R5415 42 5.6 Pendent %2° Chrome 155°F ReI G4A Concealor HYDRAULIC REFERENCE POINT R3615 3 5.6 Pendent Chrome 155°F Rel F1FR SSP CONT. NO.: KS00287 HANGER SYMBOL R3625 14 5.6 Upright %i' Brass 155°F Rel F1FR SSU DRAWN BY: Adam Kantner Total = 59 SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: 59 DATE:3/20/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105- REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBIJOUEROUE/AUSTIN I DALLAS/DECATUR /DENVERI DULUTH/HOUSTON/KANSAS CITY LAS VEGAS/MINNEAPOLIS/PHOENIX/ PORTLAND I RAPID CITY/ ST. PAUL ISALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Sephora 616 Southcenter Mall Tukwila, WA 98188 Fire Sprinkler Plan SHEET FP -1 OF 1 616 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-106 08-S-095 FILE COPY FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sephora 616 Southcenter Mall Permit No.: 08-S-095 Date: March 31, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 20' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. TUfILEIJF1 [I Fre :_ t:',:: 21 March 2008 Martin Sokolski Westem States Fire Protection 7102 180th Ave NE, Suite A-105 Redmond, WA 98052 RE: Westfield Mall — Sephora (Suite #616) Independent Third Party Review — Fire Sprinkler System Tuazon Engineering PLLC 4322 NE 7°' Street Renton, WA 98059 425.917.1683 tel 425.917.1705 fax www.tuazon.com As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. It is noted that the sprinkler system modifications shown are to Zone 12 fed from the West Riser Room. The following was reviewed: • Fire Sprinkler Drawing — Sheet FP1 dated 3/20/08 • Hydraulic Calculations dated 3/20/2008 The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Ensure storefront show window areas are provided with sprinkler coverage per NFPA 13. It appears there may be a wall or ceiling break at the east window area that may prevent sprinkler coverage. 2. The hydraulic data table on the drawing lists a maximum coverage per head of 130 SF. It should read 120 SF to match the hydraulic calculations. 3. Please include applicable product data with the permit submittal to the City of Tukwila. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or eric(&tuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING PLLC Eric P. Tuazon, PE Fire Protection Engineer CADmvaniFbd2009Piejsc1020E19WW•InE1101-116.11.118whonalrraelluesesprhlarmitwdoe m11 Hydraulic Summary Job Number: KS0287 Report Description: Sephora Zone T2 Job Job Number KS0287 Design Engineer Martin Sokulski Job Name Sephora State Certrfication/license Number WESTESF136QF Address 1 616 Southcenter Mall AHJ City of Tukwila Address 2 Job Sae Southcenter Mall City Tukwila State WA Zip Code 98188 Drawing Name FP1.cad System Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 975.00ft2 (Actual 1006.71ft2) Additional Hose Supplies Node Flow(opm) Number Of Sprinklers Calculated 9 Coverage Per Sprinkler 130.00ft2 l ' • fi l ` .L, /..•it.'t ' � lk NilVil %lei Total Hose Streams 250.00 System Flow Demand 253.73 Total Water Required (Including Hose Allowance) 503.73 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocdy Above Ground 21.22 between nodes 133 and 256 Maximum Velocity Under Ground 0.96 between nodes 1 and 439 Volume capacity of Wet Pipes 2009.32ga1 Volume capacity of Dry Pipes 0.75fts Supplies Node Hose Flow (gpm) Static (psi) Residual @ Flow (psi) (gpm) Available @ Total Demand (psi) (gpm) Required (psi) Safety Margin (psi) 1 250.00 140.000 20.000 I 10900.00 139.594 I 503.73 81.941 57.652 Contractor Contractor Number KS0287 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 Address 2 E-mail City Redmond State WA Zip Code 98052 Web -Site Hydraulic Summary Job Number: KS0287 Report Description: Sephora Zone T2 Job Job Number KS0287 Design Engineer Martin Sokulski Job Name Sephora State Certification/License Number WESTESF136QF Address 1 616 Southcenter Mall AHJ City of Tukwila Address 2 Job Site Southcenter Mall City Tukwila State WA Zip Code 98188 Drawing Name FP1.cad System Remote Area(s) Most Demanding Spnnkler Data 5.6 K -Factor 26.00 at 21.556 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 975.00ft2 (Actual 1006.71ft2) Additional Hose Supplies Node Flow(qpm) Number Of Spnnklers Calculated 9 Coverage Per Sprinkler 130.00ft2 I I ' • fi i ,`/, � •��t ,/I 11)if air Lk 7 ' ] VJi % NJ� f 4111140D� Total Hose Streams 250.00 System Flow Demand 253.73 Total Water Required (Including Hose Allowance) 503.73 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 21.22 between nodes 133 and 256 Maximum Velocity Under Ground 0.96 between nodes 1 and 439 Volume capacity of Wet Pipes 2009.32gal Volume capacity of Dry Pipes 0.75ft3 Supplies Node Hose Flow (gpm) Static (psi) Residual @ Flow (psi) (gpm) Available @ Total Demand (psi) (gpm) Required (psi) Safety Margin (psi) 1 250.00 140.000 20.000 1 10900.00 139.594 1 503.73 81.941 57.652 Contractor Contractor Number KS0287 Contact Name Adam Kantner Contact Title Project Manager Contractor Name Western States Fire Protection Phone 425.881.0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX 485.736.9032 _ Address 2 E-mail City Redmond State WA Zip Code 98052 Web -Site 11B Summary Of Outflowing Devices Job Number: KS0287 Report Description: Sephora Zone T2 Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Sprinkler 105 28.80 26.00 5.6 26.440 Sprinkler 109 30.69 26.00 5.6 30.031 Sprinkler 104 27.38 26.00 5.6 23.908 Sprinkler 108 29.74 26.00 5.6 28.204 Sprinkler 103 26.45 26.00 5.6 22.302 Sprinkler 106 29.24 26.00 5.6 27.259 cJ Sprinkler 101 26.00 26.00 5.6 21.556 Sprinkler 102 26.03 26.00 5.6 21.614 Sprinkler 107 29.40 26.00 5.6 27.572 Most Demanding Sprinkler Data 119 Node Analysis I Job Number: KS0287 Report Description: Sephora Zone T2 Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 133 14-10 2P0(8-0) 60.036 119 14-10 2P0(8-0) 60.001 256 14-10 P0(5-0) 35.113 263 14-10 P0(5-0) 39.639 277 14-10 P0(5-0) 31.764 266 14-10 P0(5-0) 37.241 297 14-10 P0(5-0) 29.636 287 14-10 P0(5-0) 36.000 312 14-10 P0(5-0) 28.647 322 14-10 E(2-0) 28.631 325 14-10 E(2-0) 35.604 399 1-11 T(50-0) 74.816 409 1-11 P0(26-4) 74.784 439 5-8% BFP(-4.500) 77.702 105 13-71/2 Spr(-26.440) 26.440 28.80 109 13-7% Spr(-30.031) 30.031 30.69 104 13-7% Spr(-23.908) 23.908 27.38 108 13-7% Spr(-28.204) 28.204 29.74 103 13-7% Spr(-22.302) 22.302 26.45 106 13-7% Spr(-27.259) 27.259 29.24 101 13-7% Spr(-21.556) 21.556 26.00 102 13-7% Spr(-21.614) 21.614 26.03 107 13-7% Spr(-27.572) 27.572 29.40 1 -4-0 S 81.941 253.73 ill Hydraulic Analysis I Job Number: KS0287 Report Description: Sephora Zone T2 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge K -Factor Pt Pn Fittings Upstream a Route 8 DR 1.049 0=29.74 11.04 C=120 0.271121 24-3 Pf 9.553 108 13-7% q=29.74 K=5.6 28.204 Spr(-28.204) 266 14-10 37.241 3E(2-0), P0(5-0) 11-0 Pe -0.517 35-3 Pv a Route 9 DR 1.049 0=30.69 11.39 C=120 0.287330 24-3 Pf 10.125 11-0 Pe -0.517 35-3 Pv 109 13-71/2 q=30.69 K=5.6 30.031 Spr(-30.031) 263 14-10 39.639 3E(2-0), P0(5-0) Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1 C Value Multiplier 4 Value Of C 100 130 140 150 Multiplying Factor 0.713 1.16 1.33 1.51 Actual Inside Diameter l4.87 ( Factor Schedule 40 Steel Pipe Inside Diameter / = Pipe Type Legend Units Legend Fittings Legend AO Arm -Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG UndergroundPv Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen -Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Velocity pressure at a point in a pipe ALV Alarm Valve AngV Angle Valve b Bushing BaIV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve Defy Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow - Eel 11W Elbow Ee2 22W Elbow f Flow Device FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GIoV Globe Valve GV Gate Valve Hose Hose I-IV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap 111 Hydraulic Analysis Job Number: KS0287 Report Description: Sephora Zone T2 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Eq. Length Total Length Pressure Summary Downstream Elevation Discharge K -Factor Pt Pn Fittings Upstream Route 1 DR 1.049 0=26.00 9.65 C=120 0.211435 25- Pf 7.608 11- Pe -0.517 36 Pv 101 13-7% q=26.00 K=5.6 21.556 Spr(-21.556) 312 14-10 28.647 3E(2-0), P0(5-0) BL 1.610 0=52.03 8.20 C=120 0.094745 10-5% Pf 0.989 I Pe 10-5'/ Pv 312 14-10 28.647 297 14-10 29.636 BL 1.610 0=78.48 12.37 C=120 0.202640 10-6 10-6 Pf 2.128 Pe Pv 297 14-10 29.636 277 14-10 31.764 BL 1.610 0=105.86 16.68 C=120 0.352521 9-6 9-6 Pf 3.349 Pe Pv 277 14-10 31.764 256 14-10 35.113 BL 1.610 0=134.66 21.22 C=120 0.550160 33-3%2 12-0 45-3'/ Pf 24.923 Pe Pv 256 14-10 35.113 133 14-10 60.036 2LtE(2-0), P0(8-0) CM 4.260 0=253.73 5.71 C=120 0.015542 397-5 Pf 9.155 133 14-10 60.036 191-7Y 409 1-11 74.784 12fE(8-11%), 2fEE(4-5%), 589-1 2Ee2(5-3), fE(6-91/2), CV(28-11'/2), GV(2-7%), P0(26-4) Pe 5.593 Pv FM 8.329 0=253.73 1.49 C=120 0.000594 21-10 Pf 0.032 409 1-11 74.784 32-0 399 1-11 74.816 2fE(16-0) 53-10 Pe -0.000 Pv MS 10.020 0=253.73 1.03 C=120 0.000241 20-2 Pf 4.521 399 1-11 74.816 67-0 439 5-8% 77.702 3LtE(16-0), BV(19-0), BFP(-4.500) 87-2 Pe -1.635 Pv UG 10.400 0=253.73 0.96 C=140 0.000151 113-1 Pf 0.039 439 5-8% 77.702 146-8 1 -4-0 81.941 3LtE(25-6), E(35-1), 2EE(17-6'r), 259-9% S Pe 4.200 Pv 0 Route 2 DR 1.049 0=26.03 9.66 C=120 0.211961 27-6% 8-0 35-6% Pf 7.533 Pe -0.517 Pv 102 13-71/2 q=26.03 K=5.6 21.614 Spr(-21.614) 322 14-10 28.631 4E(2-0) BL 1.610 0=26.03 4.10 C=120 0.026314 0-7% 0-7% Pf 0.016 Pe Pv 322 14-10 28.631 312 14-10 28.647 Route 3 DR 1.049 0=26.45 9.82 C=120 0.218194 25-0 11-0 36-0 Pf 7.851 Pe -0.517 Pv 103 13-7% q=26.45 K=5.6 22.302 Spr(-22.302) 297 14-10 29.636 3E(2-0), P0(5-0) Aw Route 4 DR 1.049 0=27.38 10.16 C=120 0.232690 25-0 11-0 36-0 Pf 8.372 Pe -0.517 Pv 104 13-7% q=27.38 K=5.6 23.908 Spr(-23.908) 277 14-10 31.764 3E(2-0), P0(5-0) 46, Route 5 DR 1.049 0=28.80 10.69 C=120 0.255398 25-0 11-0 36-0, Pf 9.189 Pe -0.517 Pv 105 13-7% q=28.80 K=5.6 26.440 Spr(-26.440) 256 14-10 35.113 3E(2-0), P0(5-0) o Route 6 DR 1.049 0=29.24 10.85 C=120 0.262710 24-3 11-0 35-3 Pf 9.257 Pe -0.517 Pv 106 13-7% q=29.24 K=5.6 27.259 Spr(-27.259) 287 14-10 36.000 3E(2-0), P0(5-0) BL 1.610 0=58.64 9.24 C=120 0.118197 10-6 10-Pv Pf 1.241 Pe 287 14-10 36.000 266 14-10 37.241 BL 1.610 0=88.38 13.93 C=120 0.252460 9-6 9-6 Pf 2.398 Pe Pv 266 14-10 37.241 263 14-10 39.639 BL 1.610 0=119.07 18.76 C=120 0.438182 34-5Y Pf 20.362 12-0 Pe 46-5% Pv 263 14-10 39.639 119 14-10 60.001 2LtE(2-0), P0(8-0) CM 4.260 0=119.07 2.68 C=120 0.003834 9-2 Pf 0.035 Pe 9-2 Pv 119 14-10 60.001 133 14-10 60.036 Ge Route 7 DR 1.049 0=29.40 10.92 C=120 0.265492 24-3 Pf 8.559 8-0 Pe -0.526 32-3 Pv 107 13-7% q=29.40 K=5.6 27.572 Spr(-27.572) 325 14-10 35.604 4E(2-0) BL 1.610 0=29.40 4.63 C=120 0.032960 12-0 12-11 Pf 0.395 Pe Pv 325 14-10 35.604 7527 , d_1 n IA nnn 111,Hydraulic Graph I Job Number: KS0287 Report Description: Sephora Zone T2 Supply at Node 1 150 J Static Pressure 140.000 135 120 H 105 90 •) a 503.73 X53.73 with hose @ 81.941 streams g 75 fn m at a 60 45-' System demand curve 30 10900.00 @ 20.000 15 a —IIm IIIIIIIII 111111111 I I I 111111 111111111 I I I I t I t( t I I t t I t I I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 t ( t I 1 1 1 0 91002200 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.594 © 503.73 System Demand 253.73 @ 81.941 System Demand (Including Hose Allowance) 503.73 @ 81.941 I 111 Flow Diagram (Top View) Job Number: KS0287 Report Description: Sephora Zone T2 11E FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FIRE ALARM SYTEM FA -04 SITE PLAN, SYSTEM CALCULATIONS (GENERAL), RISER DIAGRAM WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATIDN SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWO #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWO #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TW❑ #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2' .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROPGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS. SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL -BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2002 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2002 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 4 1 3 9 1 SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM XLS-V CONTROL PANEL SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM SDD-C REMOTE ANNUNCIATOR SIEMENS PROVIDED 66" A.F.F. TO TOP 1 BPS 1 REMOTE BOOSTER PAD -3 POWER SUPPLY SIEMENS PROVIDED 66" A.F.F. TO TOP ® INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD T -D DUAL INPUT HTRI-D INTERFACE MODULE SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT HCP MODULE SIEMENS 4S DEEP VERIFY IN FIELD 1 HZM 1 REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM l N SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED :VERIFY IN FIELD SMOKE DETECTOR HFP-1 1 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -1 1 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE AD2-P W/ SIEMENS p DETECTOR TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR HFPT-11 W/ SIEMENS (ADDRESSABLE) DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE ZR -MC -CW SIEMENS _ - (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. IN/ 1-1/2" EXT. TO BOTTOM 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM WP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE MR -201/C AIR PRODUCTS 4S BOX CONTROL RELAY VERIFY IN FIELD DOOR HOLDER MAGNETIC F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA -BOX FIRE ALARM F.B.O. TERMINAL CABINET F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. F.B.O. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.O. FURNISHED 13Y OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF N/A DEVICE N/A N/A N/A RED AS BUILT ADD OR CHANGE. N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A Without Comments AS Noted In Red Per The Attached Letter AS ILT N/A BLUE' , ,N❑T 6 I�PIRE DEPARTMEI end give this job end exact st Town or restorationaddressfor apphurova14 nese pl^ns have been reviewed by The, Tukwila Fire Prevention Bureau for conformance with current city standards. Ac:,eptarce is tiuhiect to errors and omissions which do not authorize violations of adopted stam:I:?ras and °roti; ?nces. The reiponsibillty for the c-{fU->_, r n f is tet n +` iih the de'.'':gner. ot .z:o tht-;3e cera,.,ings atter and ,+; require a C resubmitta: of sL. c: dra.11ings for subsequent approval. t Final ,ptmce is subject to field test and inspection by 1 T to TuWrila Fise Prevention Bureau. Gate: 1- O 3 By: S (( N/A N/A N/A NOTICE completed, signed, Tukwila Fire Department Pre-test ertificate must be presented to the Inspector prior to mmencement of Acceptanc1 Testing of any Fire Alarm and Detection Systems. Failure of test will result a Re -inspection Fee and rmination of the testing, - -i - n jb I ( 10(11 OS}- o(cvr(-e Oh FA SyGrc,c4- b.. c'ke• coal,tY. t,�:�, ,v P•4 7a- Qat . } o• ri•ht 2006 b 2008 Tukwila Fire 2sT1y14'z, Guardian Securit S stems, Inc. All Ri . has Reserved oC C. z 0 z_ cn LU J LU (/) r� Lu (1) FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE/REVISIONS w DESCRIPTION U.1 0 z t, J z z O 0 z V z E J CD J fICALE: i /8"=1 ' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: ,1OB NUMBER: SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT IMDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' VIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS \--DUCT DETECTOR LOCATION o TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT a LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC END OF LINE DEVICE(3.GK 1/4W) SUPERVISED SWITCH 0 GROUND O O d HTRI-R STATUS LED 0 N 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. © TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL W LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) - PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE NOTE 1: VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX. CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN. LINE SIZE- OUTLET SAMPLING - TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NQNE MUSIC 1 -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE ,f STOP IF LAST DEVICE 1(¢j FROM XLS CONTROL PANEL OR 1t¢, PREVIOUS ADDRESSABLE DEVICE H-) END OF LINE ± 1 DEVICE 0 (3.6K 1/4W) SUPERVISED I � / RELAY CONTACTS SWITCH / (4.0A @ 125VAC) GROUND - -� ' (4.0A @ 30VDC) 27 VDC 3.5 rIA DURING POLLING 10 OHMS 200 FT. (18 AVG) 0.02uF 0.04uF 14 AWG 18 AWG NOTE 2: ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE DETECTION. I& I TBI 550000 2 3 4:5..6. • HCP TB2 654321 r O O� HTRI-D OSTATUS LED CO 0 N. 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) - 0 GND N AC 0 0 U 0000 0 PAD -3 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX • .1+. 1-. ,1 2+ 2-. 2 NC C NO + -- + - + + + - KO*llIv I N31 111 IMI 24K NOT USED FRONT VIEW NOTE FOR ADDITIONAL SPECIRCATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP .. 0 FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS EOL p 0 INPU P Pi7P9 T M-1 0 o�Id zL_ RK Pu ORO �.a L.- MOO e TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE: NONE FROM REMOTE POWER SUPPLY ('S' CABLE) END OF LINE DEVICE FRQM;EACP .. 3.6K 1/4W) (VOICE CIRCUIT) UPERVISED WITCH ('V' CABLE) n r. t) {) STROBE SPEAKER �) (-) EARN GROUND 0 _►(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE (STR❑BE) (STROBE) SPEAKER (+) (—) SPEAKER/STROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE 2 NAC -4 2 NAC -3 2 NAC -2 NAC -I 80" AF.F_ 4S DEEP BOX W/ 1 -1/2 - EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR :END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERAIIN TEMPERATURE: + 32 F 0- C) TO 100' F {3(1 C) •x RELATIVE HUMIDITY. NM-CUMMING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSAD.E DEVICE OR POKER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS LISTED FOR AIR VO.OITY APPLICATIONS OF 300-4000 HAIN MEN USED IN CON.AINCTION WTH DUCT HOUSINGS AD -11P OR M)-11XPR REAR VIEW > ( ) DATA OUT 1 (+) DATA OUT J} HFP-1 1 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID ---- HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE ------ 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION - CEILING MOUNTED --� SPEAKER/STROBE �. CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE JUNCTI❑N BOX MOUNTED ON CEILING FLEX UNCTION BOX ------- ❑UNTED AGAINST EILING SUPPORT / / / / / / / 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS m Lu Ct DESCRIPTION Lu C:1 0 0 1 I TO NEXT DEVICE O O -----CADDY BAR MOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE ---SUSPENDED ILLUMINATED CEILING Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved CO CO J r J a, 2 Z < w oco Cr w c� z_ w= W Q� c,cco� z z 0 z Z J (SCALE:1/8'1=1' DRAWN BY: !.ANDERSON DESIGNED : BY: R.VEZZANI DATE: 2/27/08 BACKROUND;PLAN PROVIDED BY: B ; C.3; ; D ' ADJACENT TENANT E E.7 ,.E.10; H i I RK:VsINC.: L.* • — - • EOL T S1 S,2V 11 S,2 11 177 BUILDING CORRIDOR ; II .0-er" IL:ma , :,... ../,' ,.. ,,',,..,..:I.....:,:,..:.:.:::•:.,.....,..:.::::.:.:::4::.':,..!:,:.,::..i. III ,I1. 15 1 •;,..„ D. ;......' J, u.....;A !?:. L. ..:.X.:•:.N.:...:.:.;:,,,N.:.:.:.1,!;.:.:.;.:.;•,...,...,:, ;,,.....:4.:....,:!... x...,........X. :.......X.......;.,,N.,;.:,.;;•:.;.:.',':•;,....: "t -- (4- t , I Its -------------I ADJACENT TENANT ' I , [ , [ •[ • [ FXIS 1 ! 1 I L' 2 -en? MALL COMMON 10 - NORTH • OA Fl ALAV DLA 1 . . 1 , . • , • . • , . . , • . ' , • I • ' . , I.' cO Ci• 0 Cf) La 1.1_1 (1) U) LL3 >5 F- FAX (206) 628-4.990 TEL. (206) 622-6545 7. RELEASE/REVISIONS CO lij [ • 1 I . SCALE:1Y8„ DRAWN 1 BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 2/27/08 BACKROUND.. PLAN PROVIDED BY: \LJOB NUMBER: Copyright 2006, by Guardictn;SCurity Systems, Inc. All Rights Reserved A3ERC OMBIE__ ----------------------- ------ ------------•J E'j�- ALLERIE ELM 1r _/ ,l1 1.;) F - Li c 4 =. Cr. I_L i Li 10201 j: i 1 M _. P r_ =tii=ti IL,] El] 1545 iJ 1 PACIFIC ' 1..4I\I \IF A I`4 TIE= WALKING CO. 11;0 he be COACH 77, 1125 ----------------------- 171-1 171 .1 ��rl 35 1140 r 6t) 0 ta IC'.LET SYSTEM CALCULATIONS nm luoll 11W 11111!11 1M MP. . -----------1 11-1501 ILLUMINATIONS 11475, r.ECI'CLI`r nr-F. AZ N MAC GHLL URNIA PIZZA KITCHEN R1 NORTH LOM!!!!!,,, ecce P F CHANG'S P2 BUCKS Li 480 �+ fl 5 C- SEPHORA WESTFIELD SOUTHCENTER MALL SCALE 1132'=1' S,2V A S,2V A S,2V A S,2V A S,2V A S,2V A S,2V A S,2V 30 30 75 15 15 15 110 110 110 D D D 0,I LI o= D,I FA-BDX D IFACP EX 2S,V PSI I EOL1 STROBE SEPORA SEPHORA FACP ADD ONS SIEMAENS PAD -3 Signal Extender Panel Battery Load Calculations Current Load: .- Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 3 0.0635 0.0635 0.064 0.192 Main System Board 1 0.03 0.03 0.030 0.030 1 HTR -R 4 0.009600 0.0096 0.021 0.084 S_ET-MC @15CD ST -MC @3OC D .___� _. SET -MC @75CD 3 0.064 0.192 HTR I -D, y _-_._._tt-__-...___. .____._ 0.001600 0.0035 _- 2 0.098 0.196 1 0.175 0.175 SET -MC @110CD 3 0.233 0.699 �__.-____ _.« . �. m _ �r �._ ZR -MC @15CD 0.064 __ �____.v_..-.s�-..._.__ _ v._� ..m�___Y a.y�_- ZR -MC @30CD 0.098 -- __ _____._ 0.0731 Amps 0.276 Amps HCP 0.0015 R�F_y rtT}< 0.03 Amps 1.292 Amps Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.276 Amps For 5 Minutes= 0.023 Amp -hours Alarm Current Load: 1.292 Amps For 5 Minutes= 0.109 Amp -hours 25% Derating= 2.222 Amp -hours 25% Derating= 1.036 Amp -hours Total System Current Load: 2.222 Amp -hours Total System Current Load: 1.036 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH • Battery Pair to be Used: 12VDC 1 Amp -hours 7AH MOO 31( RECOMMENDED MINIMUM BATTERY SIZE = 7.00 Aripere*Hours BATTERY SIZING CALCULATION ,__Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel:l SEPHORA Date:1 Apri14, 2008 QTY - Device Type 3 !SET -MC @15CD -, 1 - 1 1 !Wire Resistance 3.24 . CURRENT TOTAL=i 2331 ;Alarm Current) Alarm Total 1 Wire Size { Wire Length Voltage at EOLw . Circuit Total�I 641 1921 i -- ;Total Wire Resistance (R) 2.14'=: r- SET-MC @30C D 981 1961 ;SET -MC @75C D 1751 1751 +SET -MC @110CD -2331 6991 4R -MC @15CD-_-�_._.,._.�._.._.._.__.�64',._�.�...,.�.�....�._.._.Of ZR -MC @30C D i _____. _ _ 98 0 1ZR-MC @75CD i 1751 0 1Z14 -MC._. 0CD____�_.___ ..__.------- --- 2331 0 1 I 1 DEVICES=19 { g----------------Ti-i 1 TOTAL m A=1 1262 1 12 330 �� _� � _._..�. �_,�..�,-�'l. otification.Av_��lariceWCrcuit,.D .---,� ��:.M_�.._,.._��r�n._ F -.___o__ -_i_. __..----.-__.-__ _-_�.�._�__�.._.� ___._.�.___.._ _-_.-_--�_-- _--__-___pl--------------------------------T etas i ; # WESTFIELD SOUTHCENTER MALL -------<-____--_.-__..._�..�_,-._----- -_____�_.�� ;PROJECT: ] L Panel: ; SEPHORA - - Date: 'April 4, 2008 1 CIRCUIT:'SPEAKER CIRCUIT i 1 _ ; :Total Device Load, Amps (I) 1.261 (Total Cct Load) I $ IV oltage Drop (E ) (E= I * R) ] 17.7013392 • ;EOL Voltage 17.701 _ (20.4 - E) ;Wire Resistance 5.16 CURRENT TOTAL=116.2 i QTY I Device Type !Alarm Current' Alarm Total 3 Wire Size 1 Wire Length 9 170.7V1/8 1.8E 16.21 I 0 jo 1 I 0 0 0 0 0 I 0 0 DEVICES=9 0'0` ' ] i I __pi » 0 0 01 01 01 01 01 01 -- 01 TOTAL m A= E 16.21 12 1 330 4 20.34482928 4 Voltage at EOL I Circuit Total 1 I !Total Wire Resistance (R ) (WL*2)*(R/ft) !Total Device Load, Amps (I) (Total Cct Load) ;Voltage Drop ( E ) f { EOL Voltage (20.4 - E) 1 - i 3.41! 0.021 0.06i 20.34' I; FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS W DESCRIPTION 0 «a<a Y5- co T - OD Z cr fit. -u O wcc ow= W <CO LEY (95D 0: - I - SCALE: 1 /32"=1 DRAWN BY: [:ANDERSON DESIGNED DI': R.VEZZANI SYSTEM CALCULATIONS DATE: 2/27/08 BACKROUND PLAN PROVIDED BY: RISER DIAG Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved JOB NUMBER: SHEET FA -04 i; ivA N N VICINITY MAP (Suite# 616) SCALE: N General Notes 1. Western States Fire Protection to add new pendent heads new u r�igght heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyin the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. WEST RISER DETAIL TUKWILA FIRE DEPARTMEN1. Please call: 575-440Z and give this job No. 02-S,os and exact address for shut' O•-.,nlrt or restoration aporov?J r 7 I 7 I I z ACC Wthout Comments Q As Noted In Red Fr Per The Attached Letter nese plans have been reviewed by The Tukwila File Prevention Bureau for conformance with current city standards. Acceptance is Itchiest to errors and omissions which do not outooii'3 violcticns of adopted standards and 0r:11—arises. i i I'_:,,;vri'_i Wily for the oequacy of de i jfi r�.. P,,:_.:;,' .. i;I tre designer. dditions, deletions or is s'i ion .: 'tiii, i drawings atter .;3 date will Void this acceptance w ii require a ..submittal of revised cirswirigs for subsequent approval. incl acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /3 o 8 By: 7�+' ` 1 In i 1 2-51/2 10-111/2 . ... NORM to M1 JQ + M 1 1 O,k° 8-7 0 /2 Existing 4" Main Holrzcu O °'Pi\ NN,' JQ�pQ o 1 �o 1, 0-4, 8-7 tom=¢ 1/ 0-6h/2 c a® O Existing 4" Main 0.41/2 Weld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test approval. 1NVN311N3JVrOV 1NVN31!NJJVf0V ID FIRE SPRINKLER PLAN 0 o, -0 V 0 Sephora Remote Area: Retail #616 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 Ft' DENSITY .20 GPM / Fey for 975 F� SPRINKLER Reliable Model G4A ORIFICE 1/2" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI 10900 GPM FLOW AT BASE OF RISER. SYSTEM REQUIRES: 254 GPM @ 75 PSI TYPICAL FLEXABLE SPRINKLER CONNECTION: FLEXHEAD MOUNTING BRACKET PIPE NIPPLE SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS REDUCING FITTING SUSPENDED T BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING als0 BRACE PIPE 3/9' KWIK BOLT (21/4' EMBED LENGTH) FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS 14014 -THREADED BRACE PIPE . At time of Design 13'4" CLG.=35% AREA REDUCTION FIG. 4A PIPE CLAMP FOR SWAY BRACE 319' KWIK BOLT (2 1W EMBED LENGTH) FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT BRACE PIPE bid NON -THREADED BRACE PIPE LATERAL BRANCHLINE RESTRAINT Ordinary Group Ih2p VICINITY MAP DETAIL Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch Rod Coupling All Thread Rod Swivel Ring Concrete Construction Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension HANGER DETAIL PA ma 2 2000 1 Tukwila Fire W W 2 U Lu2 Scheiner Commercial Group Inc CONTRACTO SYMBOL LEGEND REVISIONS Sprinkler Legend 2 -WAY EARTHQUAKE BRACE NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL APPROVAL: City of Tukwila 4 -WAY EARTHQUAKE BRACE R5415 42 5.6 Pendent %2° Chrome 155°F ReI G4A Concealor HYDRAULIC REFERENCE POINT R3615 3 5.6 Pendent Chrome 155°F Rel F1FR SSP CONT. NO.: KS00287 HANGER SYMBOL R3625 14 5.6 Upright %i' Brass 155°F Rel F1FR SSU DRAWN BY: Adam Kantner Total = 59 SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: 59 DATE:3/20/08 Western States Fire Protection Company 7102 180th AVE NE, STE A-105- REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBIJOUEROUE/AUSTIN I DALLAS/DECATUR /DENVERI DULUTH/HOUSTON/KANSAS CITY LAS VEGAS/MINNEAPOLIS/PHOENIX/ PORTLAND I RAPID CITY/ ST. PAUL ISALT LAKE CITY/SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 Sephora 616 Southcenter Mall Tukwila, WA 98188 Fire Sprinkler Plan SHEET FP -1 OF 1