PP - 515 SOUTHCENTER MALL - PICTURE PEOPLE - PERMITS AND PLANS
515 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-057 11-F-051 11-S-044 11-S-036 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Michael Kors 515 Southcenter Mall Permit No.: 11-S-044 Date: February 22, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables' • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. 4 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Picture People 515 Southcenter Mall Permit No.: 11-S-036 Date: February 9, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. 1 • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS TEELOX MECHANICAL BRANCH CONNECTOR SIZE A B C 1-1/4 x 1/2 2 1-1/2 1-3/16 1-1/4 x 3/4 2-1/16 1-1/2 1-3/16 1-1/4 x 1 2-1/8 1-1/2 1-3/16. 1-1/2x1/2 2 1-1/2 1-3/16 1-1/2x3/4 2-1/16 1-1/2 1-3/16 1-1/2 x 1 2-1/8 1-1/2 1-3/16 2 x 1/2 2-5/16 1-13/16 1-3/16 2 x 3/4 2-3/8 1-13/16 1-3/16 2 x 1 2-7/16 1-13/16 1-3/16 2-1/2x1/2 2-9/16 2-1/16 1-3/16 2-1/2x3/4 2-11/16 2-1/8 1-3/16' 2-1/2 x 1 2-3/4 2-1/8 1-3/16 i iiii// /////.'/////////////////////i ////i//////////////////iiii///i /i////i //////////// ////// //////,/'//// 2,22,2/ /,i/,//AV /// j / /////,// //;% - // i' fi /'///////////////////////////////////////////////////////////////////////////////////////////////////////////////%/i//////ii////////i//// 2 /i/iiii/iiiii/i<1<‹?;rf<: / «iiiii//ii/iiiii//iiiii/ii/iiiiiiii/iiiii/ii/ii/i%%///////�//�%%/�/'/////////,///,//, / r////i,/ MALL CORRIDOR (NOT IN SCOPE OF WORK) /j A• BATHRM RM (millwork) (millwork) (millwork) (GC) (miliwor ti P f P p» ( illwork) (millwork) (millw. k 3X1 F4X14 (millwork ,/-/// /,-/,/ /,-/-/-/•/-//ty•/ //'/ ////-//-/" ;/,/'/- ,////_:,:////,,i////!/////::7////://////:',:,!:!::,':;;'-,'/ , //////// / :i/=//;/;"%////;// //// //%/"'/ j/i///////i//'///////////////, //i/////,'/////;,j/ .///////i://,/ ' vii 7-777777, / L// % / / ///7 // /////,/, /7 / 7 /7,/,/, ./ 7 / 7 / 7 / / / ,/,/, / / / / / / / / //,/,/,/,/,/,/, 7 / //////7,/,/,/ / / / / / / / / / / / / / / / / : / / / / / /,/ ////// 7//,//2//,'//7//,\/ , � �//,/, ti � 44'Y4, % /// ///i/////. ;'//// %/i//////'i/////i//// '//i//////iiii.'////%///i/' i//iiii///// //, A OF DOOR OPENING ECESSED LIGHT POCKET CEILING H 0X2 (millwork) B3SX6, B3FX6 Trough (GC) DISPLAY WINDOW ///2/ ////////////,// //////'///, : /////////./ //,/ '/i/ii/i////i// 6-tili ro�J�''((lrtillyvbrlF1 `II''r �mill�i�k' ///6n'(a 6r' '//; '%%% �� //i%/�/� : i I'cirk '//iii%ii/.� i%///' r //ii//� //,' - /,,, �1 J(tnJ l�Q��(. .), , ,�. 1. �. I�� � �rn1�N � ( �) /(��rllll�vgr�, ' '2222/iiii////J/////,'/iiii/2222/ //,i//// =y7,-/:2,;/////2/22/,/2////,-/2222222///,-///,-/////://,'/, //i./,i%ii%' Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 23 - Add Reliable Model G4OrStandard Response 155 ° Pendents 1/2 x 1/2 0 5 - ADD Reliable Model F1 Standard Response 155 ° Upright 1/2 x 1/2 28 - Total EAD CURTAIN POCKET CEILING Celi(N,) 1/1-1 .7- 1 ' TN 0 Thesc!;tin, i h, t:', 's n. ' U .-.v .111.; Tukwila Fire t City -rndai-Lis. :_ i. . (., "_'ri: drd .;?isslons .'c C. ii li... or adopted - nd>r•-d.; nci ;, n' c, ;or the :�=turn of _. r: ; : _....aipner. ;additions d efr:tol,., _dr iwinps after this dat -' ;!! ; ;:�° . _e . '1�� :i .... rer1Uire a resubrictai c. is -=sail_ fc•- approval, Final acceptance is suoject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: -a-1- ! ( By: A'fr+•, -)1 ( • TUKWILA FIRE. DEPARTM€.m FicAse call: 575-4407 and give this job No. //-S-O `/K and exact address for shut. lawn or restoration aoDroum1 stamps ml`I.Dc? in5pecte i bc.,.fore pipe is hung. On /i not paint i g2yul s E i.:c. test 6.; �.. i..,i l.•i c �.. i. LOCATION MAP SITE MAP - 1ST FLOOR 0 fr- • CROWN FIRE . PROTECTION INCORPORATED P.O: BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 MICHAEL KORS WESTFIELD SOUTHCENTER 515 Southcenter Mall Tukwila, WA 98188 DATE' 2•.1 DRAWN: SCALE: r.y.I.l..og PAID FEB .16.2011 UUKWILA FIRE jj77-- �1 0 0c SALES SALE co gamC OBI i L 1 0C 1 r ,i i • v SALES oc 1:i ,/ SPRINKLER PLAN 1/4"=r -o" Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinlder heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 4— Add Reliable Model F 1 Standard Response 155 ° Upright 1/2 x 1/2 Turn 4 Drops Pendent Heads To Upright Heads 4— Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS c ❑ Without Comments ❑ As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire revention Bureau for conformance with current City • indards. Acceptance is subject to errors and . nlssions which do not authorize violations of adopted ndards and ordinances. The responsibility for the equacy of design rests 'totally with the designer. -.dditions, deletions or revisions to these drawings after his date will void this acceptance and will require a esubmittai of revised drawings for subsequent approval. =ina1 acceptance is subject to .field test and inspection by 'Pie Tukwila Fire Prevention Bureau. Date: 2--I-I ( Cv: , s ( 1 Ut w:I.LA FIRE DEPARTMEM. - fease call: 575.4407 and give this job No. s- 03Sa and exact address for shut. 7r,:un or rest)r,+ion aonrf- m PILE • CROWN FIRE PROTEC110N INCORPORA TED. P.O. BOX .12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7889 1\1 eVIS 1-.'a r a. - a 0" �2( ec I -c. ( S WESTFIELD SOUTHCENTER 2800 Southcenter Mali Space #672 Tukwila, WA 98188 • DATE: a-2-2011 DRAWN: SCALE: , J PAID FEB -3 2011 'UKWILA FIRE '7 s-' +: .. . ., Y C ............. 411♦ \ ... ... L\ '1\ ;.} \ W1..1 h .. v..=, y..r ,,¢ \ ,,.....;+. ...... ......... �"' � :.. ..... t .. ..x !, l ,. .. ,. ..... ',. 4 T .r. . w,.i .-:. y.4 .4 + i :u..,, .x h... .O \. .l• 'w..y� �. . } .. °: � x .. ♦ w �. v � „� � � }k4 .... Y ,,� SPRINKLER PLAN 1/4"=r -o" Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinlder heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 4— Add Reliable Model F 1 Standard Response 155 ° Upright 1/2 x 1/2 Turn 4 Drops Pendent Heads To Upright Heads 4— Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS c ❑ Without Comments ❑ As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire revention Bureau for conformance with current City • indards. Acceptance is subject to errors and . nlssions which do not authorize violations of adopted ndards and ordinances. The responsibility for the equacy of design rests 'totally with the designer. -.dditions, deletions or revisions to these drawings after his date will void this acceptance and will require a esubmittai of revised drawings for subsequent approval. =ina1 acceptance is subject to .field test and inspection by 'Pie Tukwila Fire Prevention Bureau. Date: 2--I-I ( Cv: , s ( 1 Ut w:I.LA FIRE DEPARTMEM. - fease call: 575.4407 and give this job No. s- 03Sa and exact address for shut. 7r,:un or rest)r,+ion aonrf- m PILE • CROWN FIRE PROTEC110N INCORPORA TED. P.O. BOX .12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7889 1\1 eVIS 1-.'a r a. - a 0" �2( ec I -c. ( S WESTFIELD SOUTHCENTER 2800 Southcenter Mali Space #672 Tukwila, WA 98188 • DATE: a-2-2011 DRAWN: SCALE: , J PAID FEB -3 2011 'UKWILA FIRE '7 s-' I st 4 h; ✓k , fS i FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3ER SHEET TITLE FA -01 SYSTEIv INFOR VAATION FA -02 TYPICAL WRING AND MOUNTI\G DETAILS FA -03 SYSTEIV CALCULATIONS A \D SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX `f,rith:Y r. Comments (� As Noted in Red Letter der These plans have been reviewed by The Tukwila Fire Prevention Bureau f or cc,lforrnance with current City standards. Accepr 7,,,:-: ;._1'_rjec : { errors and emissions which (f: cr12r.: ''ici'i.ions of adopted :rdards ant. ar± ' h" + r;siy for the .,tecl Lacy of desici 1 to ail signer. Additions, del tor.` masc.: c.rrawilgs after this date.. will vt1C ±! r:qui re a resubmittal of rri\ri, ,;J ..':equent approval. Final acceptance IF St o1 -:c:• to i1 !d ;13i. and inspection by The Tukwila Fire Prever,cicl i Lur eau. Date: 3 - IU1 WILA. FIRE DEPART -Nam s ,ease call: 575.4407 and give this job _ No. " 0.5 I and exact address for shut. ,,,wn or restoration aoornva! NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm anci Detection Systems. Failure of test will result in a Re -inspection Fee ancj termination of tej1ng f RE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.0. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 2 1 3 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -1 1 BASE 4S DEEP BOX W/ 1G RING CEILING ®D DUCT DETECTOR AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP BOX VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM fj 1 1,275sf 1• y 3 LEVELS ArDti r,c 8ux nri7es dsa' macys 4 LEVEL 251, 07s f TEL SWIM: o.7NC ?ACC OVRCOR IIY.-�` - QIR 'Ni R R RDS U BEST BUY UODILE relk c rs Sti^YCRD a3.. I I 221 tD CHOW ANC TOKYO ,pro ss MICHAEL KORS (515) EXISTING JCPenney tEvus 276,45ssf PAID MAR -1 2011 TUKWILA FIRED - 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS u.i F__ 0 02/28/11 I Z co0 o T U) opo QW� wzz W SOF OC C.� ° S 1.<iicc Lop LL 1- 4-CALE: NOT Z 0 0 u. Z (I) (I) TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/28/11 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved JOB NUMBER: 55170 N SHEET FA -01 } 120VAC-6012 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. BUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE: FOR ADd71@tAL SPECFICATXNS SEE PRODUCT DOg*IENTAT1dl *CONTACT RAMS 4.0A 0 125VAC 4.0A 0 30VDC „ 47) TO NEXT ADDRESSAELEe+ DEVICE STOP IF LAST DEVICE - FROM XLS comm. PANEL (1' DR PREVIOUS ADDRESSABLE DEVICE - 0 0 o c 0 e. I HTRI—R I J O � NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C—CABLE C—CABLE GRD N L 01 11 PAD -3 oo INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX +1- 1 2+2- 2 NC C NO + - + - + - + - + - (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (—) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. WIRE DESIGNATION. NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPUFPIR RED (JACKET) 'CONTACT RAM ` 4.0A 0 125VAC 4.0A 0 304DC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DRY CONTACTS TO VAV _► FAN SHUTDOWN PROVIDED BY MECH/ELEC. GROUND 2 SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER OR FIRE ALARM CONTROL PANEL < (+) (+) (—) (+)>TO NEXT DEVICE OR (—) STOP IF LAST DEVICE DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL all❑ o CI SPEAKER 0 0 1177 1 ^ I AOCuu,II " - +n 1:1:1:1:111:1:1■ STROBE Q CIRCUIT JE D I 1 (-) STROBE CIRCUIT STROBE 111❑ 7 0 0 (-) SPEAKER CIRCUIT (+) (+) / ` LI STROBE OODJ CIRCUIT SPEAKERISTROBE QO❑ 0 0 En 0 0 X (-) STROBE CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (-) (+) (+) (— SPEAKER CIRCUIT 5 TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERATURE: +32' F 0' C TO 100' F 31T C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR :t FROM PREVIOUS [--).- ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOaTY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 / STANDARD SMOKE DETECTOR BASE REAR VIEW (-) )1" TO NEXT 1 J ADDRESSABLE (+) SMOKE DETECTOR WIRING DETAIL HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 1 TO NEXT DEVICE CADDY BAR l SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved 178196 NOIDNIHSVM `T-111.V]S "OS ']AV ISI gi7L1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS DATE CO N N, N 0 a<aa< ZCO co J T U)I,trn O QWF_ Cs WZZ W cn CC n U Q°S w�u� LL 1-- SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:02/28/1 1 BACKROUND PLAN PROVIDED BY: .10E3 NUMBER: 55170 SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 0.0731 Amps 0.106 Amps r 5Y Cnrire Loac n Device Type Qty Amps Total Amps Total Main System Board SET -MC -C (u3.15CD 1 0.03 0.03 0.030 0.030 0.069 SET -MC -C @30CD SET -MC -C @75CD SET -MC -C @95CD 1 0.111 0.2 2 0.264 ZR -MC -C @15CD 2 0.069 0.138 ZR -MC - 15CD 0.064 jZR-MC-C @75CD 0.175 0.03 Amps 0.168 Amps Standby Current Load: 0.03 Amps. For 24 Hours. 0.720 Amp -hours Alarm Current Load: 0.168 Amps For 5 Minutes= 0.014 Amp -hours 25%.Derating= 0.918 Amp -hours Total System Current Load: 0.918 Amp -hours att+r Isirr b Amp - 7.01' Notification Appliance_Circuit Detail _ -MICHAEL MICHAEL KORS Panel: PAD -3 POWER SUPPLY Date: March 1, 2011 ;SET -MC -C @15CD SET -MC -C @30CD 0 SET -MC -C @75CD 2 - SET -MC -C @95CD 0ZR-MC-C @110CD 2 _ ZR -MC -C @15CDY 0 IZR-MC-W @15CD 0.._. ZR -MC -C @75CD DEVICES= j 5 Wire Resistance 2.58 - CURRENT TOTAL= :777.00 Notification Appliance Circuit Detail PROJECT: MICHAEL KORS Panel: XLS-V Date: March 1, 2011 Wire Resistance 2.58 CURRENT TOTAL= r#REF! 111, 264 259 69 641 175 TOTAL mA=j ;Total Wire Resistance (R Total be -vice Load, Amps (1) Voltage Drop (E) y, EOL Voltage 111 0) 528 0 138 01 0 777 127 19.89' j( WL*2)*(R/t) (Tetall Cct Load) 1(E= R) 20.4 - E) 7771 0.66 0.78? 0.511 19.89 0 70.7V 1/8 70.7V114 70.7V 1/2 70.7V 1 DEVICES=158M 1.8 37.8 3.54 130.98 0 0. TOTAL mA=j 168.781 Total Wire Resistance (R ) Total Device Load, Amps (1) ;Voltage Drop (E) EOL Voltage 1,337 19.23560028 (WL*2)*(R/ft) . (Total Cct Load) (E= I * R) (20.4-E) 168.781 _.. 6.901 0.17; 1.161 19.24 SYSTEM CALCULATIONS TO EXISTING DATA LOOP IN JAMBA JUICE TO EXISTING DATA LOOP IN JAMBA JUICE b (HALLWAY) s EX 2C -o BPS V,V b I (HALLWAY) 120VAC, DEDICATED , (BY OTHERS) ( S1-1 95cd V-1 1 /4-W S1-2 95cd 15cd V-2 1 /4-W S1-3 S1-4 15cd S1-5 30cd V-3 1 /4-W EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11 OVAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. V) 0o 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/28/11 dC CC 0 w z w z c -� PQa Z Cr 2z t� J W Wz z w U( < ©C c1) =acs- Z CLQ ° - 0 CC LOD J 0 w > C/) fs'cALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/28/ 1 1 SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55170 SHEET FA -03 / / / / / / ,/ / ,/' / / ,/ ,/ / /,/,/ , 1 /,/ / ,/ / / ,/ ,/ / ,/ / / / ,/ / / ,/ • / / ,/ ' / / ,/ /,/,2 .- /,/ / / / / / / / . • / / / - / ,/ ,/ / /,/ -- " / / , / /,/ / / ,/ / , i // ' / / / / ,/ ,/ / ,/ .-" ," ,' / , / / / ,, / / / / / / / / / // / // //1- /// /1/ „/,/ ./// 47/ /// • //,/, , - 7/'/.- ///" /7",// /'// /,//, /7,7 /// -. //,1,,- /// /1/., //// //,/, 7//,///.- -' ///, ///, 71/ - /1/ /7/ -7/////7 7 - //,/////, -///,/,////' ////i 7// '/:////// , 7,7/ /// /77 " //,/ /7,7,, ///, /1/... . ///.-' 7,1,1 ,/,/ . '/,1,/, //,/„/ /1,1, /,1,7 - ///, /// /7,7,/ 7,1/ ///./- 7,/, /// / /// - /://' /71/,/,/ -', 1/ ‘1,/,/. -'/// ,/,/,/..,,.//7 //// /I /-7 ' ///,/ //,/ /1/ 1// /,/,/ .,-//,./., //,/ • ///., //,/ /1,/,//1„/ /,/,/- //,1,, //,/ ,-- //,/,, /7,/ ,/7,7. -/7 /// 77,1/ ./7:// /1,1./ /7/ ,77-7 - //_. / /:/', - ii//,.. .,///,/,/,/,. ///-/-..y 7,7 --,/(//' /-/:/ ./ 71 /7,"/,--,/// //7" /,7/- ,/// -1/7. /7/ .,- - /7/ ///. /1/ ., /// - /,7,/ , /7,1 ./77 , 7/7 /1/. /7// /// /(/ , '7//‘ /7:7 ,.. 7/1,- //;/ ,77/ /7,/ //,, / ///',/7/ '1//,/ //'7" ///./ ///"7"/" ' / ,//) //"/ - /.// 1// • /1 ' ' /////,'7 ,-11, ' /1/ /77" /7/". //7 - --/1/ •/// '../AF),4"At7,\•(7".1-7/rAk' 1 /z//AVX/11defe- /// " '/// ''//7' /.// // ' ///',- /1/7/ // - "/"/ ' /,/ •' /7'/" /// // '/ ,- //// '// - 1 //, /// // • • • • / • • // / // -,,--,7,/ /,/,7 /,/ ,,, 7,/, !/,.... 7,/, /./-7,/. ,, /,/.. 77,/ /,/,/ /,//,,, 7,/, / / // ,;--,/(_ -,f/,7,„./„./,,/,4,-,/,,,(A ',//7,) //./ / //,' /// ' / // /7/ r /,77 - - /7/ / , , , , ,. //.• / / 7 , ,/// . ,/ 7// ,/ ,//, ///1 / '/,' // //// / / / //, / /1, - .. I /// , //. /// ',./,1,1 , /,7, / - /,-/, '7 /7, ' /1,1 / 7 ,/',1'2>?-) 1, 7 1,I4,/- az ',k,121)11,) -i/X / 7 ,//, ' //,/ -// 1,1, ,' /1,1 ' /-,1/ „ - //, / /11 7•7/ ., / /, • „/,/,,, '///1. •/,/,/ ,--1/, ///, 7-,77,-/, /A /// ' /// i // ' 7,1,, .„--77-", „r•-• 4;7_ /// ,/ 7,1 ' 7,/,/ / /"/,. - ' / /7,7 / // ,--•' /// - /// 7// ' /// / //, - / /7,- ./ / 7' /// , /,//, /1,1,._ Z// ' ///", / /71 ' 1/., ' /1,1. //,/,< ///'/ - :7,/,/ -/,/, 77 1/ -,/:/ --/:/ , 1 -• 1/ „ // / /1 / 7/ 7- .--' 7-,/ ' .//i 7 7,1/ /// , //,/ , - /77 , - -//./ //7..- - 1"/ , 7,1/ /1 / i /7/ , /// . //,/, /1/ . ///.. , /,/ / 1,/ - /,1,7 „/ /1,/ - 71,/, 7,/ "71, . ',/,7 /-7/1„ 7/7/, //- /// : ,/,/, -7-'/:7 .7, // .7//' „ // „, 71 / 1/1 1/11 / 1/ - / //,"/ /-,11 / //// /1/ 171 1///, // / /// ' /;/"7" -1// - 7;7 / - 7// ./ 1,1 ./ , /1,. //// • ' /// _ '' /// - //,/ . ,77, ///:// //- /// /,// . ' /7'7" • /// 17_ ' -t/ /// / /1"/ /// //, 7../ // / ' // .,-- V/ /7,1 71 ,/ - ////- /K. / 71, / ////' //// ./7/ 71/ ' /// „, //, // 7/, / 7- / / "/7,1 - ///,- /1/ /1/ 7 .• 7/1. "7,7, 7 7/7, //,/,77, -17 - /,/,/. / 1//' .- //7 //7//>/ //" ////, /// ../17 /// "7,i/ , /1,/ , /1/ ' - 1-/,/ / 1,/ .-/ /1/ /,/ / 71/ /1/ . /1/ 1/,/ 71/ /7/ "//,/ 7/7 77"/ 1/,/ •-• /1,/ 7/ / . - -7,7/ //// .7,/,/ / -/'//, /,/,/,, '1 //' .,TG,:/:.- ',//, /I '/ / , i ,/,/ •07 ; ,4 :._, 1 i 1 ,4 S C 0 - ,.„,; - vo,.._,,R \ I ,,, , /// //,.:/:7. .,e///i///,, /7/:///,:/,' // , //7 /// /1, '.,- 71 ,/711 /71 /71. //7 1/1 //, ,,,--. //,.,' - "7,1" /,71 /7/ ' /7,1 /,1/ /7"/"/ 7,1 . . ' /11/ 7,/,/ /X/ . -- //7 /71 -1 ,7,7/7-71 - ,/// i /7'/' -71,/., ,yo' i=,,,,,. ..,./r.,(A.r" /// ty , ,/±// i„ // zizy .,, .,.-//' ./// /// /// ,,,/-/ ,-•,,,-//_, /// -,,,-/ / /-/ is,,,,/,';‘)/,;b/,, j'/'(/,1,\‘/IniT, //'.,-/-// ., ,-//- /// , 77/ /// /77/7/ •• .- 77 //1 ,././7/' , '// )=-. i;a,"/IN,a,talf MALL , . -!--i - '-` , r", f-, E 7-` ^ HO .--) - (M.- kAinny \ IN JAMBA JUld . /7 / • /7 //e , , ,, ,- TO EXISTING DATA LOOP IN JAMBA JUICE S1-4 15cd BoH BATHR 107 D HTR -R ap-S,V,V FITT43 RM I 104 1 D , / 71 S1-3 15cd "Th v 106 S1-5 !30cd V-3 EOL S1 RTU -1 D I HTR -R I 1 TSM I 2 7 7. %1 HIDDEN LINE OF BACK WALL (BY , .. S1-2 95cd V-2 cD-V,V L EX 2C T ,Al FLOOR 103 s,v,v Sk7FIT 7. D BPS L// /.777= 1 S1-1 95cd V-1 INE OF FXISTING FASCIA OF SAWTOOCH CEILING Rt1LvL • ENTRY 101 ,,„ „, ,,r,. •, 1:, :'• '" , ,:,,,,:::",, ,,:t,:,!,!: ,,,,', : ,,, „ ,:' ::, H'-*:' • ,„ -" / 2 > / / / 2, ,-- - /// ; / ' , . ',-/ / / . / .ff , / ; // / / : .. ./- / 2"-/- ,• // , / / >' ; 7-, /- / - - , -2- / , ' / / >/ / / -/-' *''':- '-'-''''''''/ / e . / • ' o / / . • / / / • / . . / / . / / / / / • . / . / / / • / / / / / / • / ' . /7/ ' /7/ / // ' /7/ 7/7/ /7 / /7/ /// i /7/ // /./ ' //// 7/ .'"/ / 7/ / 7 /7/ /// ' /// // /7 .7 ' /7 / / /7 7/ /7 / /7/ ' /7/ ' ' .7// -• 7/ . / /// / /7 7/ 77 ././ /// .' /7/ ./ /7/7 /// •/ ' /7/ . /1 //' / // /77/ / / / / /7/ V / / i 77 ' / // /// / // / / 7/ / ' 7/, // /// / //// / ' // 7 //7/ ' / // / / // / /1/ 7,/ /// ///,.. / / // ' ///// / 7/ / 7// / / 7 / / 7 //,/, / // / / / / /./ / / /, / // / / • / ' . // /// /7/ /7/ /// /7 / . /// . /77' /7/ /77 ' /7 / . /7 / /7 // /7/ .' /// /7/ 777 ' / 7/1/ /7 / ' /7 / / 7 / / /// • /77 /77 . / /7 / /V/ /7/7 /7/ // //1 ' /// /7/ /7/ /7 >2' . / / / / /7 / / 7 / ' / 7 / 7 / V /7 /7/, '. /// / / / / / / '//. / 7 / / / / ' / / / / / 7 / -/. /7/ / / 7 / ' ' /7 / 7 '. /// /// i 7/ / 7 /// /7/, / // / 7 / /// / 7 7 ' 77 ' / /7 / . 7 / / /7/ / /7/ / /// ,/, ' 4 ' " /7 - / / / /7/ / /7/ i // /r -T4// / //7 --/// /// /7/ z // / '// / / /7 /' 777 /- 777 : /77 /7/7/7/ r If /±/ / / // / . //// ," 77/ /V/ ///. ' /7 / //// / 7 / ,' //1/ /7/ / /7/ - / / / , / /1/ - i / / /////1 / . / / . / / • / / / / / , -e/ 77 / / // ' .//7/ 7./>- //7 .1 >017: 777 /7/ 7777 / '7/ r. /7/ 777 /// . / /7/: . /7/ //7 /7/ /7/ :/ ///:.:./, 7-//,-./'../1 / /7 / :.-/,:- 7 ,-/ 7, /./' 7 ., ///', ,/:,- / 7/.,' /- /7 /:- //:- 7/ /:' 7-/ 7. 7/2//,', ,/ / 47 /// /7/ // // /72/7/'/7/ /// //7 // /7/'///7/7/7///1/ /// :7/77,/7/,/////7//7/ //7//7/ /7/ //7/7/ /// /7/ ///// r///-/7'' , 7/, <, /,, /,,//,/ /7,/,,/7,‘/,, /,,.<7///,7,//7//,,AxNAEA/,"/,I/:/7,//,, ,/,./,,.,,/ /,,/,,,,,,•/77 /7/ /7,//,,//,//,7://-./A / //, /// 7, /7, // /,/// ///, //, /,,/,././//,,,, / ,, /7/i\,///<,Az/,/, ./7/ /7, ,/,/ /7, , ///.7/ //7 ,,,•,,,77/ 77/, //.// 77,/ /7./ /K7/7,,/7, ,7/,7//7 717 /// 11/11 /117,/11//// /1k\9/)7\WI///1///;/1K /////7/'////Xi'////:/11 /// /// ////77//1/7//// 7/ '// ///// // / // ///:/// /// /// ////// 1// /// /// /7//,/ ///// //// ///// /// /77/ // ////'/71 /// /// /////7/// // //7/'// /7/ / / /7/ //7 /7/ /7 /7 i /7///7z/// //7/ /7/ /// // ///7//// /7/ /7/ // '//// 7/ ///7 /// /7/ /// // T /// 1/ z/ /7 ///X /7/ /////'/v,/.1//,// / // /// / /// ///./1 / /// // ////// /7/ // /7///// // //X/ //7////// /17/ 4/ /'// /// // /// /// /// ///1/i/// /////////// /// 1// /// // // /Z /7/ /17 /77 //r///71/i/1/ /// 7/7/ 7/7/7/ 1/ /1//'/ // '/// //// 1///1////1 /////1/ ////.717 //I/ //./// /7/// ' 111i 1 FIRE ALARM SYSTEM PLAN FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/28/11 2 < < < < < co Z co Can zicSS CC z 0Lcl cc° < 2 LEo 1LUZZ 1.1.1 Fo < < 15 (<o cn--1 Lu !,f2 ct LL 1- 'CALE: 3/8"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:02/28/1 1 BACKROUND PLAN PROVIDED BY: SOB NUMBER: 55170 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 SPACE #672 FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFO MATION FA -02 TYPICAL WRING AND MOU\TING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGWAM FA -04 FIRE ALARM SYSTE \4 PLAN SHEET INDEX 5 / I'I' :0 j ih.+, tdi r' i• iLet it rre,icow�di by.'TiheTiultwil Ire r e ,;:, rrent may/ rt„r��`i'�'1� ��"�i4' 1it1 � Ev�l'< �'(l i�r'i% Cnr.1°,' 1",tir nG' • ,f 1 :•&, sub -j v: - c e�.�:t�rs. and WF i,C."[ C l: j' n �' - 't ✓f _C ',ij;o r 3 of adopted hh p % r:; >; nS; cythe drift C7 .::. : 'jy� F_��;�. �T: r for the 3110. L...-' . .i quac/ 6f < < '� � c : _ , ;i with ti^ e designer. alciorr�, d l ilii eoi it'oliotig to these drawings after Eris diiiE ill L`61 ri1= tide@ptkk4ttce and will require a resubriilttal 6f fE Vi§ed drrntwlit for subsequent approval. Fin6i:ga0Fite it tllbjett: tO field test and inspection by The TVivA Pete tion Bureau. -- 1( NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. 1 UKWILA FIRE DEPARTMENL Ptoase call: 575.4407, and give this job No. 11-1: o51 and exact address for shuts IOwn or rest ration aoornva) WIRE SCHEDULE AND CONDUIT HILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND rv.. NORDSTROM 3 LEVELS 171,275sf ICZOIVAl macy 4 LEVELS 250,407sf 1 aVl Yll M. F. J: .YttitEL VOCE USW, CWNtY 1.1ePAAY nY�R r ;au ` "'�!:I-s I el m GiiEW\Y'GEaSE YO SPACE #672 STO RAG E (515) 0 E..ISI YC r RED ui.YER 1 .E NE�.ERS JCPenney 7 LEVELS 275,468sf 11.041 PAID MAR 15 2011 TUKWILA FIRE A-y7a-7/ 417' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 g 0 DESCRIPTION SHOP DRAWINGS w M 0 2CCaaa z 0 z °00 Qc. CC 0 2z WO Wzz 0 iej(T) =Q f2 Z 0 J_ cc Lon LL H W (1) 0) SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:03/14/1 1 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved \ 0B NUMBER: 55178 } �l\ SHEET FA -01‘-\ 12OVAC-60HZ �l DEDICATED O4ERGENCY 111 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR AMORAL SFECF1CADOIS SEE PRODUCT DOCIUEDTAIXN. "CONTACT RAI1NGS 4.0A 0 125VAC 4.0A 0 30VDC TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE - FROi XLS CONTRIL PANEL (F OR PREVIOUS ADDRESSABLE DEVICE 0 0 • O G 0 J ® HTRI—R I e, 1 0 NOTE: SSEEEE PRODUDOCUMENTATION. C -CABLE C -CABLE 2/ 2) ID N L 00 00 U 0 0 PAD -3 00 ° NPUT INPUT TROUBLE NAC) NAC2 NAC3 NAC4 AUX 1+ - 1 2+ 2- 2 NC C NO + - + - + - + - + - s Q 3.6k EOL (—) (+) (—) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) all❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. N (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SITE TYPE COLOR CODE TWISTED PAR WITH SHIELD 918 FPLIFPLR RED (JACKET) ACCNTACT RATINGS 4.0A 0 125VAC 4.0A 0 304DC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 o O GROUND 0 0 0 __l HTRI—R 0 (+)>TO NEXT DEVICE OR ❑0 O 1 Iib Z0 0 ❑ _ 1 O q\. DESCRIPTION SHOP DRAWINGS = 4 1 o DATE o 0 w a+ �a MS I. � 7 7 F l t , e I F h MGIC CY ' In r -I ASCOEFIN " - rn \ fes. - `_ II 1:1:1:1 I1:1:1y f ,0°.'-2 1.1:1:1:111:1:1• — 32 cal 4 ' %IA � ;I no! 11 (-) > STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL 0I SPEAKER I I PF0'5 / D El STROBE Q ❑flp CIRCUIT QD❑ SPARE j SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL t (+) (+) 0 I I 0 0 1:1.1:1:111:1:1 I I (-) DED) STROBE CIRCUIT STROBE SPEAKERISTROBE D�f1 4l I❑ — 1 O - Z0 0 1 0 ri DESCRIPTION SHOP DRAWINGS 1111 DATE M O MS I. � 7 , e I F h r -I ASCOEFIN " - rn f ,0°.'-2 1.1:1:1:111:1:1• — 32 cal 4 (—) (—) SPEAKER CIRCUIT (+) (+) STROBE 0=2/ CIRCUIT ❑on 0 0 144 I:1 GGl 11:1:1 an❑ (-) (+) (+) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) v�au STROBE ❑ED/ CIRCUIT (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFCAIIONS SEE PRODUCT DOCUMENTATION. OPERATIN TEMPERA RE: +32'F O- C) TO 100' F (38' C) HUMIDITY: b-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS USTED FOR AIR voLOaTY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (—) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX 11111056" -- JUNCTION JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 0 0 1 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Z0 0 DESCRIPTION SHOP DRAWINGS DATE M O �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 03/1 4/ 1 1 BACKROUND PLAN PROVIDED BY: .1.0B NUMBER: 55178 SHEET FA -02 J a r Y k 1 d J } 7Ye t P f rv' r i,i v E ' �Y 1 .um ua y� i fi `'q 9 fitl j'�' kw �u qAd I}S e , °r r'f � v i�,�� ". ' r ��.F��bTMw� IY ,d IIIm ^.I , �l� dIX a,. rw�"N k , n X:, 'S M „1: u„ t �.I�. I � Irv. o, �r �' 4 ., �. „A m w � ,.S:N y�` '.'wn ao p n „p I 'p d _, ��" �'F�. ,, al d t u „_.:w 0 m 0 e.,.:p ,d �...d' r, v':" p^� �:"," } , '���', .. M q:i IW.d,'d" ..e }.}}IX 1 }o+„ SHOP DRAWINGS •°^'.',. pB w,�{:�;�'�wl, 4 ,,,'�:,r �r,n „}, •:> ,! .�S. a;a,4v .,, ,.,q,,, DATE CLOT, ti. I r Mh h ' '. P ll b t m +, d" qq 1 A 7 �} a ,3 } i' i� 1w t „'I I * ,M (a �'�p'' �y• '•t 'r w� ? ^ 2 CCCaa Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SFT -MC -C ©15CD 12 0.069 SET -MC -C @30CD 5 0.111 SC-C©75CD 3 0.2 SET -MC -C @95CD 2 0.264 ZR -MC -C @15CD 2 0.069 0.138 ZR- dIC-W @ i 5CD 4 0.064 0.256 ZR -MC -C @75CD 0.175 0.03 Amps 0.424 Amps Standby Current Load: 0.03 Amps : ' For 24 Hours=-. 0:720 Amp -hours Alarm Current Load: 0:424 Amps . For 5 Minute 0.036 Amp -hours 25% Derating ; 0.945 Amp -hours Total System Current Load: 0.945 Amp -hours ,tl 5 _ { ' a, °;:,' lvi PI"�, ,,. rn1e'' a M d°,c 9 d,. Notification ion A liance Circuit Detail PROJECT: SPACE #672 STORAGE Panel: I PAD -3 POWER SUPPLY Date: i March 14, 2011 Notification n t Appliance CircuitDetail to PROJECT: SPACE #672 STORAGE G XLS-V Date: March 14 2011 Wire Resistance CURRENT TOTAL 2.58 629.00 Panel: Wire Resistance 2.58 #REF! CURRENT TOTAL= ET -MC -C, @15CD C -C r©i 30CD SET -MC -C @75CD SET -MC -C @95CD ZR -MC -C @110CD ZR MC -C @15CD ZR -MC -W @15CD 0 : ZR -MC -C @75CD__ DEVICES= i 6 207 ! 222 200 0 52.2 4.96 0 DEVICES= 70,7V 137.16 14 175 TOTAL mA= 4 Total Wire Resistance (R ) Total Device Load, Amps (I) Voltage Drop (E) I EOL. Voltage„ ( WL * 2 )* (R/ft) (Total Cct Load) (E= 1,* R) 20.4-E) 1.991 0.63 1.25 19.15' Total Wire Resistance ( R ) Total DeviceLoad, Amps (I) Voltage Drop (E ) EOL: Voltage 19.68730018 137.16 (171/C;-2-) 2) * (R/ft)��.. otal Cct Load, (E= I R) 20.4-E SYSTEM CALCULATIONS (HALLWAY) s EX s,s',v,v' S-1 75cd V-1 1 /4-W V) co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE i\ V M 0 2 CCCaa W z o = ¢ T C) a 2 t— < WO wzz (Ou) w (9)g Uif 2 C!) CC ac 0 W z J LU z to 0 z aC C1) z O 5 J 0 W F- C/) Cr)} /SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 03/ 14/ 1 1 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved .0B NUMBER: 55178 J % SHEET FA -03 EY: 1 ST 1 - CORRID.C.-)R EXIE')TING .A.JACENT TENANT 5F40:: EXISTING-- 5 4 CI< CF HOUE7E. - CORRIDOR • ' S,S',V,V 8-1 75cd V LANDLORD I C„,- RAGE 2.E4 101 T Ac; Lr erA*7 merzir Air 4316._ • • FIRE ALARM SYSTEM PLAN -17-1 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 (i) z0 (7) LU uJ (i) 1.1.1 LU REV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS LL1 < - 0 \ K) 0 2 <<<<< 0 z cc8 0 cc o < w (/) w z Z (NI ow' N. coco co i< -fP cc 0 w < cc Li/n 0_ 11 I— 111 CC LL ALE: 1/4" 1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:03/14/1 1 BACKROUND PLAN PROVIDED BY: JOB NUMBER: 55178 } C SHEET FA -04 515 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-057 11-F-051 11-S-044 11-S-036 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Michael Kors 515 Southcenter Mall Permit No.: 11-S-044 Date: February 22, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables' • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. 4 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Picture People 515 Southcenter Mall Permit No.: 11-S-036 Date: February 9, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. 1 • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS TEELOX MECHANICAL BRANCH CONNECTOR SIZE A B C 1-1/4 x 1/2 2 1-1/2 1-3/16 1-1/4 x 3/4 2-1/16 1-1/2 1-3/16 1-1/4 x 1 2-1/8 1-1/2 1-3/16. 1-1/2x1/2 2 1-1/2 1-3/16 1-1/2x3/4 2-1/16 1-1/2 1-3/16 1-1/2 x 1 2-1/8 1-1/2 1-3/16 2 x 1/2 2-5/16 1-13/16 1-3/16 2 x 3/4 2-3/8 1-13/16 1-3/16 2 x 1 2-7/16 1-13/16 1-3/16 2-1/2x1/2 2-9/16 2-1/16 1-3/16 2-1/2x3/4 2-11/16 2-1/8 1-3/16' 2-1/2 x 1 2-3/4 2-1/8 1-3/16 i iiii// /////.'/////////////////////i ////i//////////////////iiii///i /i////i //////////// ////// //////,/'//// 2,22,2/ /,i/,//AV /// j / /////,// //;% - // i' fi /'///////////////////////////////////////////////////////////////////////////////////////////////////////////////%/i//////ii////////i//// 2 /i/iiii/iiiii/i<1<‹?;rf<: / «iiiii//ii/iiiii//iiiii/ii/iiiiiiii/iiiii/ii/ii/i%%///////�//�%%/�/'/////////,///,//, / r////i,/ MALL CORRIDOR (NOT IN SCOPE OF WORK) /j A• BATHRM RM (millwork) (millwork) (millwork) (GC) (miliwor ti P f P p» ( illwork) (millwork) (millw. k 3X1 F4X14 (millwork ,/-/// /,-/,/ /,-/-/-/•/-//ty•/ //'/ ////-//-/" ;/,/'/- ,////_:,:////,,i////!/////::7////://////:',:,!:!::,':;;'-,'/ , //////// / :i/=//;/;"%////;// //// //%/"'/ j/i///////i//'///////////////, //i/////,'/////;,j/ .///////i://,/ ' vii 7-777777, / L// % / / ///7 // /////,/, /7 / 7 /7,/,/, ./ 7 / 7 / 7 / / / ,/,/, / / / / / / / / //,/,/,/,/,/,/, 7 / //////7,/,/,/ / / / / / / / / / / / / / / / / : / / / / / /,/ ////// 7//,//2//,'//7//,\/ , � �//,/, ti � 44'Y4, % /// ///i/////. ;'//// %/i//////'i/////i//// '//i//////iiii.'////%///i/' i//iiii///// //, A OF DOOR OPENING ECESSED LIGHT POCKET CEILING H 0X2 (millwork) B3SX6, B3FX6 Trough (GC) DISPLAY WINDOW ///2/ ////////////,// //////'///, : /////////./ //,/ '/i/ii/i////i// 6-tili ro�J�''((lrtillyvbrlF1 `II''r �mill�i�k' ///6n'(a 6r' '//; '%%% �� //i%/�/� : i I'cirk '//iii%ii/.� i%///' r //ii//� //,' - /,,, �1 J(tnJ l�Q��(. .), , ,�. 1. �. I�� � �rn1�N � ( �) /(��rllll�vgr�, ' '2222/iiii////J/////,'/iiii/2222/ //,i//// =y7,-/:2,;/////2/22/,/2////,-/2222222///,-///,-/////://,'/, //i./,i%ii%' Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 23 - Add Reliable Model G4OrStandard Response 155 ° Pendents 1/2 x 1/2 0 5 - ADD Reliable Model F1 Standard Response 155 ° Upright 1/2 x 1/2 28 - Total EAD CURTAIN POCKET CEILING Celi(N,) 1/1-1 .7- 1 ' TN 0 Thesc!;tin, i h, t:', 's n. ' U .-.v .111.; Tukwila Fire t City -rndai-Lis. :_ i. . (., "_'ri: drd .;?isslons .'c C. ii li... or adopted - nd>r•-d.; nci ;, n' c, ;or the :�=turn of _. r: ; : _....aipner. ;additions d efr:tol,., _dr iwinps after this dat -' ;!! ; ;:�° . _e . '1�� :i .... rer1Uire a resubrictai c. is -=sail_ fc•- approval, Final acceptance is suoject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: -a-1- ! ( By: A'fr+•, -)1 ( • TUKWILA FIRE. DEPARTM€.m FicAse call: 575-4407 and give this job No. //-S-O `/K and exact address for shut. lawn or restoration aoDroum1 stamps ml`I.Dc? in5pecte i bc.,.fore pipe is hung. On /i not paint i g2yul s E i.:c. test 6.; �.. i..,i l.•i c �.. i. LOCATION MAP SITE MAP - 1ST FLOOR 0 fr- • CROWN FIRE . PROTECTION INCORPORATED P.O: BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 MICHAEL KORS WESTFIELD SOUTHCENTER 515 Southcenter Mall Tukwila, WA 98188 DATE' 2•.1 DRAWN: SCALE: r.y.I.l..og PAID FEB .16.2011 UUKWILA FIRE jj77-- �1 0 0c SALES SALE co gamC OBI i L 1 0C 1 r ,i i • v SALES oc 1:i ,/ SPRINKLER PLAN 1/4"=r -o" Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinlder heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 4— Add Reliable Model F 1 Standard Response 155 ° Upright 1/2 x 1/2 Turn 4 Drops Pendent Heads To Upright Heads 4— Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS c ❑ Without Comments ❑ As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire revention Bureau for conformance with current City • indards. Acceptance is subject to errors and . nlssions which do not authorize violations of adopted ndards and ordinances. The responsibility for the equacy of design rests 'totally with the designer. -.dditions, deletions or revisions to these drawings after his date will void this acceptance and will require a esubmittai of revised drawings for subsequent approval. =ina1 acceptance is subject to .field test and inspection by 'Pie Tukwila Fire Prevention Bureau. Date: 2--I-I ( Cv: , s ( 1 Ut w:I.LA FIRE DEPARTMEM. - fease call: 575.4407 and give this job No. s- 03Sa and exact address for shut. 7r,:un or rest)r,+ion aonrf- m PILE • CROWN FIRE PROTEC110N INCORPORA TED. P.O. BOX .12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7889 1\1 eVIS 1-.'a r a. - a 0" �2( ec I -c. ( S WESTFIELD SOUTHCENTER 2800 Southcenter Mali Space #672 Tukwila, WA 98188 • DATE: a-2-2011 DRAWN: SCALE: , J PAID FEB -3 2011 'UKWILA FIRE '7 s-' +: .. . ., Y C ............. 411♦ \ ... ... L\ '1\ ;.} \ W1..1 h .. v..=, y..r ,,¢ \ ,,.....;+. ...... ......... �"' � :.. ..... t .. ..x !, l ,. .. ,. ..... ',. 4 T .r. . w,.i .-:. y.4 .4 + i :u..,, .x h... .O \. .l• 'w..y� �. . } .. °: � x .. ♦ w �. v � „� � � }k4 .... Y ,,� SPRINKLER PLAN 1/4"=r -o" Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved All fire sprinlder heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 4— Add Reliable Model F 1 Standard Response 155 ° Upright 1/2 x 1/2 Turn 4 Drops Pendent Heads To Upright Heads 4— Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/9' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS c ❑ Without Comments ❑ As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire revention Bureau for conformance with current City • indards. Acceptance is subject to errors and . nlssions which do not authorize violations of adopted ndards and ordinances. The responsibility for the equacy of design rests 'totally with the designer. -.dditions, deletions or revisions to these drawings after his date will void this acceptance and will require a esubmittai of revised drawings for subsequent approval. =ina1 acceptance is subject to .field test and inspection by 'Pie Tukwila Fire Prevention Bureau. Date: 2--I-I ( Cv: , s ( 1 Ut w:I.LA FIRE DEPARTMEM. - fease call: 575.4407 and give this job No. s- 03Sa and exact address for shut. 7r,:un or rest)r,+ion aonrf- m PILE • CROWN FIRE PROTEC110N INCORPORA TED. P.O. BOX .12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7889 1\1 eVIS 1-.'a r a. - a 0" �2( ec I -c. ( S WESTFIELD SOUTHCENTER 2800 Southcenter Mali Space #672 Tukwila, WA 98188 • DATE: a-2-2011 DRAWN: SCALE: , J PAID FEB -3 2011 'UKWILA FIRE '7 s-' I st 4 h; ✓k , fS i FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3ER SHEET TITLE FA -01 SYSTEIv INFOR VAATION FA -02 TYPICAL WRING AND MOUNTI\G DETAILS FA -03 SYSTEIV CALCULATIONS A \D SINGLE LINE DIAGRAM FA -04 FIRE ALARM SYSTEM PLAN SHEET INDEX `f,rith:Y r. Comments (� As Noted in Red Letter der These plans have been reviewed by The Tukwila Fire Prevention Bureau f or cc,lforrnance with current City standards. Accepr 7,,,:-: ;._1'_rjec : { errors and emissions which (f: cr12r.: ''ici'i.ions of adopted :rdards ant. ar± ' h" + r;siy for the .,tecl Lacy of desici 1 to ail signer. Additions, del tor.` masc.: c.rrawilgs after this date.. will vt1C ±! r:qui re a resubmittal of rri\ri, ,;J ..':equent approval. Final acceptance IF St o1 -:c:• to i1 !d ;13i. and inspection by The Tukwila Fire Prever,cicl i Lur eau. Date: 3 - IU1 WILA. FIRE DEPART -Nam s ,ease call: 575.4407 and give this job _ No. " 0.5 I and exact address for shut. ,,,wn or restoration aoornva! NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm anci Detection Systems. Failure of test will result in a Re -inspection Fee ancj termination of tej1ng f RE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.0. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 2 1 3 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-11 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -1 1 BASE 4S DEEP BOX W/ 1G RING CEILING ®D DUCT DETECTOR AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP BOX VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND NORDSTROM fj 1 1,275sf 1• y 3 LEVELS ArDti r,c 8ux nri7es dsa' macys 4 LEVEL 251, 07s f TEL SWIM: o.7NC ?ACC OVRCOR IIY.-�` - QIR 'Ni R R RDS U BEST BUY UODILE relk c rs Sti^YCRD a3.. I I 221 tD CHOW ANC TOKYO ,pro ss MICHAEL KORS (515) EXISTING JCPenney tEvus 276,45ssf PAID MAR -1 2011 TUKWILA FIRED - 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS u.i F__ 0 02/28/11 I Z co0 o T U) opo QW� wzz W SOF OC C.� ° S 1.<iicc Lop LL 1- 4-CALE: NOT Z 0 0 u. Z (I) (I) TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/28/11 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved JOB NUMBER: 55170 N SHEET FA -01 } 120VAC-6012 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. BUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE: FOR ADd71@tAL SPECFICATXNS SEE PRODUCT DOg*IENTAT1dl *CONTACT RAMS 4.0A 0 125VAC 4.0A 0 30VDC „ 47) TO NEXT ADDRESSAELEe+ DEVICE STOP IF LAST DEVICE - FROM XLS comm. PANEL (1' DR PREVIOUS ADDRESSABLE DEVICE - 0 0 o c 0 e. I HTRI—R I J O � NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C—CABLE C—CABLE GRD N L 01 11 PAD -3 oo INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX +1- 1 2+2- 2 NC C NO + - + - + - + - + - (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (—) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. WIRE DESIGNATION. NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 FPUFPIR RED (JACKET) 'CONTACT RAM ` 4.0A 0 125VAC 4.0A 0 304DC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DRY CONTACTS TO VAV _► FAN SHUTDOWN PROVIDED BY MECH/ELEC. GROUND 2 SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER OR FIRE ALARM CONTROL PANEL < (+) (+) (—) (+)>TO NEXT DEVICE OR (—) STOP IF LAST DEVICE DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL all❑ o CI SPEAKER 0 0 1177 1 ^ I AOCuu,II " - +n 1:1:1:1:111:1:1■ STROBE Q CIRCUIT JE D I 1 (-) STROBE CIRCUIT STROBE 111❑ 7 0 0 (-) SPEAKER CIRCUIT (+) (+) / ` LI STROBE OODJ CIRCUIT SPEAKERISTROBE QO❑ 0 0 En 0 0 X (-) STROBE CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (-) (+) (+) (— SPEAKER CIRCUIT 5 TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER TIN TEMPERATURE: +32' F 0' C TO 100' F 31T C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR :t FROM PREVIOUS [--).- ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( ) DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOaTY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 / STANDARD SMOKE DETECTOR BASE REAR VIEW (-) )1" TO NEXT 1 J ADDRESSABLE (+) SMOKE DETECTOR WIRING DETAIL HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 1 TO NEXT DEVICE CADDY BAR l SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved 178196 NOIDNIHSVM `T-111.V]S "OS ']AV ISI gi7L1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS DATE CO N N, N 0 a<aa< ZCO co J T U)I,trn O QWF_ Cs WZZ W cn CC n U Q°S w�u� LL 1-- SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:02/28/1 1 BACKROUND PLAN PROVIDED BY: .10E3 NUMBER: 55170 SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 0.0731 Amps 0.106 Amps r 5Y Cnrire Loac n Device Type Qty Amps Total Amps Total Main System Board SET -MC -C (u3.15CD 1 0.03 0.03 0.030 0.030 0.069 SET -MC -C @30CD SET -MC -C @75CD SET -MC -C @95CD 1 0.111 0.2 2 0.264 ZR -MC -C @15CD 2 0.069 0.138 ZR -MC - 15CD 0.064 jZR-MC-C @75CD 0.175 0.03 Amps 0.168 Amps Standby Current Load: 0.03 Amps. For 24 Hours. 0.720 Amp -hours Alarm Current Load: 0.168 Amps For 5 Minutes= 0.014 Amp -hours 25%.Derating= 0.918 Amp -hours Total System Current Load: 0.918 Amp -hours att+r Isirr b Amp - 7.01' Notification Appliance_Circuit Detail _ -MICHAEL MICHAEL KORS Panel: PAD -3 POWER SUPPLY Date: March 1, 2011 ;SET -MC -C @15CD SET -MC -C @30CD 0 SET -MC -C @75CD 2 - SET -MC -C @95CD 0ZR-MC-C @110CD 2 _ ZR -MC -C @15CDY 0 IZR-MC-W @15CD 0.._. ZR -MC -C @75CD DEVICES= j 5 Wire Resistance 2.58 - CURRENT TOTAL= :777.00 Notification Appliance Circuit Detail PROJECT: MICHAEL KORS Panel: XLS-V Date: March 1, 2011 Wire Resistance 2.58 CURRENT TOTAL= r#REF! 111, 264 259 69 641 175 TOTAL mA=j ;Total Wire Resistance (R Total be -vice Load, Amps (1) Voltage Drop (E) y, EOL Voltage 111 0) 528 0 138 01 0 777 127 19.89' j( WL*2)*(R/t) (Tetall Cct Load) 1(E= R) 20.4 - E) 7771 0.66 0.78? 0.511 19.89 0 70.7V 1/8 70.7V114 70.7V 1/2 70.7V 1 DEVICES=158M 1.8 37.8 3.54 130.98 0 0. TOTAL mA=j 168.781 Total Wire Resistance (R ) Total Device Load, Amps (1) ;Voltage Drop (E) EOL Voltage 1,337 19.23560028 (WL*2)*(R/ft) . (Total Cct Load) (E= I * R) (20.4-E) 168.781 _.. 6.901 0.17; 1.161 19.24 SYSTEM CALCULATIONS TO EXISTING DATA LOOP IN JAMBA JUICE TO EXISTING DATA LOOP IN JAMBA JUICE b (HALLWAY) s EX 2C -o BPS V,V b I (HALLWAY) 120VAC, DEDICATED , (BY OTHERS) ( S1-1 95cd V-1 1 /4-W S1-2 95cd 15cd V-2 1 /4-W S1-3 S1-4 15cd S1-5 30cd V-3 1 /4-W EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 11 OVAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. V) 0o 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/28/11 dC CC 0 w z w z c -� PQa Z Cr 2z t� J W Wz z w U( < ©C c1) =acs- Z CLQ ° - 0 CC LOD J 0 w > C/) fs'cALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 02/28/ 1 1 SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55170 SHEET FA -03 / / / / / / ,/ / ,/' / / ,/ ,/ / /,/,/ , 1 /,/ / ,/ / / ,/ ,/ / ,/ / / / ,/ / / ,/ • / / ,/ ' / / ,/ /,/,2 .- /,/ / / / / / / / . • / / / - / ,/ ,/ / /,/ -- " / / , / /,/ / / ,/ / , i // ' / / / / ,/ ,/ / ,/ .-" ," ,' / , / / / ,, / / / / / / / / / // / // //1- /// /1/ „/,/ ./// 47/ /// • //,/, , - 7/'/.- ///" /7",// /'// /,//, /7,7 /// -. //,1,,- /// /1/., //// //,/, 7//,///.- -' ///, ///, 71/ - /1/ /7/ -7/////7 7 - //,/////, -///,/,////' ////i 7// '/:////// , 7,7/ /// /77 " //,/ /7,7,, ///, /1/... . ///.-' 7,1,1 ,/,/ . '/,1,/, //,/„/ /1,1, /,1,7 - ///, /// /7,7,/ 7,1/ ///./- 7,/, /// / /// - /://' /71/,/,/ -', 1/ ‘1,/,/. -'/// ,/,/,/..,,.//7 //// /I /-7 ' ///,/ //,/ /1/ 1// /,/,/ .,-//,./., //,/ • ///., //,/ /1,/,//1„/ /,/,/- //,1,, //,/ ,-- //,/,, /7,/ ,/7,7. -/7 /// 77,1/ ./7:// /1,1./ /7/ ,77-7 - //_. / /:/', - ii//,.. .,///,/,/,/,. ///-/-..y 7,7 --,/(//' /-/:/ ./ 71 /7,"/,--,/// //7" /,7/- ,/// -1/7. /7/ .,- - /7/ ///. /1/ ., /// - /,7,/ , /7,1 ./77 , 7/7 /1/. /7// /// /(/ , '7//‘ /7:7 ,.. 7/1,- //;/ ,77/ /7,/ //,, / ///',/7/ '1//,/ //'7" ///./ ///"7"/" ' / ,//) //"/ - /.// 1// • /1 ' ' /////,'7 ,-11, ' /1/ /77" /7/". //7 - --/1/ •/// '../AF),4"At7,\•(7".1-7/rAk' 1 /z//AVX/11defe- /// " '/// ''//7' /.// // ' ///',- /1/7/ // - "/"/ ' /,/ •' /7'/" /// // '/ ,- //// '// - 1 //, /// // • • • • / • • // / // -,,--,7,/ /,/,7 /,/ ,,, 7,/, !/,.... 7,/, /./-7,/. ,, /,/.. 77,/ /,/,/ /,//,,, 7,/, / / // ,;--,/(_ -,f/,7,„./„./,,/,4,-,/,,,(A ',//7,) //./ / //,' /// ' / // /7/ r /,77 - - /7/ / , , , , ,. //.• / / 7 , ,/// . ,/ 7// ,/ ,//, ///1 / '/,' // //// / / / //, / /1, - .. I /// , //. /// ',./,1,1 , /,7, / - /,-/, '7 /7, ' /1,1 / 7 ,/',1'2>?-) 1, 7 1,I4,/- az ',k,121)11,) -i/X / 7 ,//, ' //,/ -// 1,1, ,' /1,1 ' /-,1/ „ - //, / /11 7•7/ ., / /, • „/,/,,, '///1. •/,/,/ ,--1/, ///, 7-,77,-/, /A /// ' /// i // ' 7,1,, .„--77-", „r•-• 4;7_ /// ,/ 7,1 ' 7,/,/ / /"/,. - ' / /7,7 / // ,--•' /// - /// 7// ' /// / //, - / /7,- ./ / 7' /// , /,//, /1,1,._ Z// ' ///", / /71 ' 1/., ' /1,1. //,/,< ///'/ - :7,/,/ -/,/, 77 1/ -,/:/ --/:/ , 1 -• 1/ „ // / /1 / 7/ 7- .--' 7-,/ ' .//i 7 7,1/ /// , //,/ , - /77 , - -//./ //7..- - 1"/ , 7,1/ /1 / i /7/ , /// . //,/, /1/ . ///.. , /,/ / 1,/ - /,1,7 „/ /1,/ - 71,/, 7,/ "71, . ',/,7 /-7/1„ 7/7/, //- /// : ,/,/, -7-'/:7 .7, // .7//' „ // „, 71 / 1/1 1/11 / 1/ - / //,"/ /-,11 / //// /1/ 171 1///, // / /// ' /;/"7" -1// - 7;7 / - 7// ./ 1,1 ./ , /1,. //// • ' /// _ '' /// - //,/ . ,77, ///:// //- /// /,// . ' /7'7" • /// 17_ ' -t/ /// / /1"/ /// //, 7../ // / ' // .,-- V/ /7,1 71 ,/ - ////- /K. / 71, / ////' //// ./7/ 71/ ' /// „, //, // 7/, / 7- / / "/7,1 - ///,- /1/ /1/ 7 .• 7/1. "7,7, 7 7/7, //,/,77, -17 - /,/,/. / 1//' .- //7 //7//>/ //" ////, /// ../17 /// "7,i/ , /1,/ , /1/ ' - 1-/,/ / 1,/ .-/ /1/ /,/ / 71/ /1/ . /1/ 1/,/ 71/ /7/ "//,/ 7/7 77"/ 1/,/ •-• /1,/ 7/ / . - -7,7/ //// .7,/,/ / -/'//, /,/,/,, '1 //' .,TG,:/:.- ',//, /I '/ / , i ,/,/ •07 ; ,4 :._, 1 i 1 ,4 S C 0 - ,.„,; - vo,.._,,R \ I ,,, , /// //,.:/:7. .,e///i///,, /7/:///,:/,' // , //7 /// /1, '.,- 71 ,/711 /71 /71. //7 1/1 //, ,,,--. //,.,' - "7,1" /,71 /7/ ' /7,1 /,1/ /7"/"/ 7,1 . . ' /11/ 7,/,/ /X/ . -- //7 /71 -1 ,7,7/7-71 - ,/// i /7'/' -71,/., ,yo' i=,,,,,. ..,./r.,(A.r" /// ty , ,/±// i„ // zizy .,, .,.-//' ./// /// /// ,,,/-/ ,-•,,,-//_, /// -,,,-/ / /-/ is,,,,/,';‘)/,;b/,, j'/'(/,1,\‘/IniT, //'.,-/-// ., ,-//- /// , 77/ /// /77/7/ •• .- 77 //1 ,././7/' , '// )=-. i;a,"/IN,a,talf MALL , . -!--i - '-` , r", f-, E 7-` ^ HO .--) - (M.- kAinny \ IN JAMBA JUld . /7 / • /7 //e , , ,, ,- TO EXISTING DATA LOOP IN JAMBA JUICE S1-4 15cd BoH BATHR 107 D HTR -R ap-S,V,V FITT43 RM I 104 1 D , / 71 S1-3 15cd "Th v 106 S1-5 !30cd V-3 EOL S1 RTU -1 D I HTR -R I 1 TSM I 2 7 7. %1 HIDDEN LINE OF BACK WALL (BY , .. S1-2 95cd V-2 cD-V,V L EX 2C T ,Al FLOOR 103 s,v,v Sk7FIT 7. D BPS L// /.777= 1 S1-1 95cd V-1 INE OF FXISTING FASCIA OF SAWTOOCH CEILING Rt1LvL • ENTRY 101 ,,„ „, ,,r,. •, 1:, :'• '" , ,:,,,,:::",, ,,:t,:,!,!: ,,,,', : ,,, „ ,:' ::, H'-*:' • ,„ -" / 2 > / / / 2, ,-- - /// ; / ' , . ',-/ / / . / .ff , / ; // / / : .. ./- / 2"-/- ,• // , / / >' ; 7-, /- / - - , -2- / , ' / / >/ / / -/-' *''':- '-'-''''''''/ / e . / • ' o / / . • / / / • / . . / / . / / / / / • . / . / / / • / / / / / / • / ' . /7/ ' /7/ / // ' /7/ 7/7/ /7 / /7/ /// i /7/ // /./ ' //// 7/ .'"/ / 7/ / 7 /7/ /// ' /// // /7 .7 ' /7 / / /7 7/ /7 / /7/ ' /7/ ' ' .7// -• 7/ . / /// / /7 7/ 77 ././ /// .' /7/ ./ /7/7 /// •/ ' /7/ . /1 //' / // /77/ / / / / /7/ V / / i 77 ' / // /// / // / / 7/ / ' 7/, // /// / //// / ' // 7 //7/ ' / // / / // / /1/ 7,/ /// ///,.. / / // ' ///// / 7/ / 7// / / 7 / / 7 //,/, / // / / / / /./ / / /, / // / / • / ' . // /// /7/ /7/ /// /7 / . /// . /77' /7/ /77 ' /7 / . /7 / /7 // /7/ .' /// /7/ 777 ' / 7/1/ /7 / ' /7 / / 7 / / /// • /77 /77 . / /7 / /V/ /7/7 /7/ // //1 ' /// /7/ /7/ /7 >2' . / / / / /7 / / 7 / ' / 7 / 7 / V /7 /7/, '. /// / / / / / / '//. / 7 / / / / ' / / / / / 7 / -/. /7/ / / 7 / ' ' /7 / 7 '. /// /// i 7/ / 7 /// /7/, / // / 7 / /// / 7 7 ' 77 ' / /7 / . 7 / / /7/ / /7/ / /// ,/, ' 4 ' " /7 - / / / /7/ / /7/ i // /r -T4// / //7 --/// /// /7/ z // / '// / / /7 /' 777 /- 777 : /77 /7/7/7/ r If /±/ / / // / . //// ," 77/ /V/ ///. ' /7 / //// / 7 / ,' //1/ /7/ / /7/ - / / / , / /1/ - i / / /////1 / . / / . / / • / / / / / , -e/ 77 / / // ' .//7/ 7./>- //7 .1 >017: 777 /7/ 7777 / '7/ r. /7/ 777 /// . / /7/: . /7/ //7 /7/ /7/ :/ ///:.:./, 7-//,-./'../1 / /7 / :.-/,:- 7 ,-/ 7, /./' 7 ., ///', ,/:,- / 7/.,' /- /7 /:- //:- 7/ /:' 7-/ 7. 7/2//,', ,/ / 47 /// /7/ // // /72/7/'/7/ /// //7 // /7/'///7/7/7///1/ /// :7/77,/7/,/////7//7/ //7//7/ /7/ //7/7/ /// /7/ ///// r///-/7'' , 7/, <, /,, /,,//,/ /7,/,,/7,‘/,, /,,.<7///,7,//7//,,AxNAEA/,"/,I/:/7,//,, ,/,./,,.,,/ /,,/,,,,,,•/77 /7/ /7,//,,//,//,7://-./A / //, /// 7, /7, // /,/// ///, //, /,,/,././//,,,, / ,, /7/i\,///<,Az/,/, ./7/ /7, ,/,/ /7, , ///.7/ //7 ,,,•,,,77/ 77/, //.// 77,/ /7./ /K7/7,,/7, ,7/,7//7 717 /// 11/11 /117,/11//// /1k\9/)7\WI///1///;/1K /////7/'////Xi'////:/11 /// /// ////77//1/7//// 7/ '// ///// // / // ///:/// /// /// ////// 1// /// /// /7//,/ ///// //// ///// /// /77/ // ////'/71 /// /// /////7/// // //7/'// /7/ / / /7/ //7 /7/ /7 /7 i /7///7z/// //7/ /7/ /// // ///7//// /7/ /7/ // '//// 7/ ///7 /// /7/ /// // T /// 1/ z/ /7 ///X /7/ /////'/v,/.1//,// / // /// / /// ///./1 / /// // ////// /7/ // /7///// // //X/ //7////// /17/ 4/ /'// /// // /// /// /// ///1/i/// /////////// /// 1// /// // // /Z /7/ /17 /77 //r///71/i/1/ /// 7/7/ 7/7/7/ 1/ /1//'/ // '/// //// 1///1////1 /////1/ ////.717 //I/ //./// /7/// ' 111i 1 FIRE ALARM SYSTEM PLAN FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM/AREA AS THE PAD -3. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 02/28/11 2 < < < < < co Z co Can zicSS CC z 0Lcl cc° < 2 LEo 1LUZZ 1.1.1 Fo < < 15 (<o cn--1 Lu !,f2 ct LL 1- 'CALE: 3/8"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:02/28/1 1 BACKROUND PLAN PROVIDED BY: SOB NUMBER: 55170 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved SHEET FA -04 SPACE #672 FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUMBER SHEET TITLE FA -01 SYSTEM INFO MATION FA -02 TYPICAL WRING AND MOU\TING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LINE DIAGWAM FA -04 FIRE ALARM SYSTE \4 PLAN SHEET INDEX 5 / I'I' :0 j ih.+, tdi r' i• iLet it rre,icow�di by.'TiheTiultwil Ire r e ,;:, rrent may/ rt„r��`i'�'1� ��"�i4' 1it1 � Ev�l'< �'(l i�r'i% Cnr.1°,' 1",tir nG' • ,f 1 :•&, sub -j v: - c e�.�:t�rs. and WF i,C."[ C l: j' n �' - 't ✓f _C ',ij;o r 3 of adopted hh p % r:; >; nS; cythe drift C7 .::. : 'jy� F_��;�. �T: r for the 3110. L...-' . .i quac/ 6f < < '� � c : _ , ;i with ti^ e designer. alciorr�, d l ilii eoi it'oliotig to these drawings after Eris diiiE ill L`61 ri1= tide@ptkk4ttce and will require a resubriilttal 6f fE Vi§ed drrntwlit for subsequent approval. Fin6i:ga0Fite it tllbjett: tO field test and inspection by The TVivA Pete tion Bureau. -- 1( NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. 1 UKWILA FIRE DEPARTMENL Ptoase call: 575.4407, and give this job No. 11-1: o51 and exact address for shuts IOwn or rest ration aoornva) WIRE SCHEDULE AND CONDUIT HILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.0. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND rv.. NORDSTROM 3 LEVELS 171,275sf ICZOIVAl macy 4 LEVELS 250,407sf 1 aVl Yll M. F. J: .YttitEL VOCE USW, CWNtY 1.1ePAAY nY�R r ;au ` "'�!:I-s I el m GiiEW\Y'GEaSE YO SPACE #672 STO RAG E (515) 0 E..ISI YC r RED ui.YER 1 .E NE�.ERS JCPenney 7 LEVELS 275,468sf 11.041 PAID MAR 15 2011 TUKWILA FIRE A-y7a-7/ 417' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 g 0 DESCRIPTION SHOP DRAWINGS w M 0 2CCaaa z 0 z °00 Qc. CC 0 2z WO Wzz 0 iej(T) =Q f2 Z 0 J_ cc Lon LL H W (1) 0) SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:03/14/1 1 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved \ 0B NUMBER: 55178 } �l\ SHEET FA -01‘-\ 12OVAC-60HZ �l DEDICATED O4ERGENCY 111 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR AMORAL SFECF1CADOIS SEE PRODUCT DOCIUEDTAIXN. "CONTACT RAI1NGS 4.0A 0 125VAC 4.0A 0 30VDC TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE - FROi XLS CONTRIL PANEL (F OR PREVIOUS ADDRESSABLE DEVICE 0 0 • O G 0 J ® HTRI—R I e, 1 0 NOTE: SSEEEE PRODUDOCUMENTATION. C -CABLE C -CABLE 2/ 2) ID N L 00 00 U 0 0 PAD -3 00 ° NPUT INPUT TROUBLE NAC) NAC2 NAC3 NAC4 AUX 1+ - 1 2+ 2- 2 NC C NO + - + - + - + - + - s Q 3.6k EOL (—) (+) (—) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) all❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. N (+) 0 WIRE DESIGNATION: NUMBER OF CONDUCTORS SITE TYPE COLOR CODE TWISTED PAR WITH SHIELD 918 FPLIFPLR RED (JACKET) ACCNTACT RATINGS 4.0A 0 125VAC 4.0A 0 304DC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 o O GROUND 0 0 0 __l HTRI—R 0 (+)>TO NEXT DEVICE OR ❑0 O 1 Iib Z0 0 ❑ _ 1 O q\. DESCRIPTION SHOP DRAWINGS = 4 1 o DATE o 0 w a+ �a MS I. � 7 7 F l t , e I F h MGIC CY ' In r -I ASCOEFIN " - rn \ fes. - `_ II 1:1:1:1 I1:1:1y f ,0°.'-2 1.1:1:1:111:1:1• — 32 cal 4 ' %IA � ;I no! 11 (-) > STOP IF LAST DEVICE DRY CONTACTS TO VAV FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL 0I SPEAKER I I PF0'5 / D El STROBE Q ❑flp CIRCUIT QD❑ SPARE j SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL t (+) (+) 0 I I 0 0 1:1.1:1:111:1:1 I I (-) DED) STROBE CIRCUIT STROBE SPEAKERISTROBE D�f1 4l I❑ — 1 O - Z0 0 1 0 ri DESCRIPTION SHOP DRAWINGS 1111 DATE M O MS I. � 7 , e I F h r -I ASCOEFIN " - rn f ,0°.'-2 1.1:1:1:111:1:1• — 32 cal 4 (—) (—) SPEAKER CIRCUIT (+) (+) STROBE 0=2/ CIRCUIT ❑on 0 0 144 I:1 GGl 11:1:1 an❑ (-) (+) (+) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) v�au STROBE ❑ED/ CIRCUIT (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFCAIIONS SEE PRODUCT DOCUMENTATION. OPERATIN TEMPERA RE: +32'F O- C) TO 100' F (38' C) HUMIDITY: b-93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS USTED FOR AIR voLOaTY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR r DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (—) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX 11111056" -- JUNCTION JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 0 0 1 TO NEXT DEVICE CADDY BAR SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: Z0 0 DESCRIPTION SHOP DRAWINGS DATE M O �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 03/1 4/ 1 1 BACKROUND PLAN PROVIDED BY: .1.0B NUMBER: 55178 SHEET FA -02 J a r Y k 1 d J } 7Ye t P f rv' r i,i v E ' �Y 1 .um ua y� i fi `'q 9 fitl j'�' kw �u qAd I}S e , °r r'f � v i�,�� ". ' r ��.F��bTMw� IY ,d IIIm ^.I , �l� dIX a,. rw�"N k , n X:, 'S M „1: u„ t �.I�. I � Irv. o, �r �' 4 ., �. „A m w � ,.S:N y�` '.'wn ao p n „p I 'p d _, ��" �'F�. ,, al d t u „_.:w 0 m 0 e.,.:p ,d �...d' r, v':" p^� �:"," } , '���', .. M q:i IW.d,'d" ..e }.}}IX 1 }o+„ SHOP DRAWINGS •°^'.',. pB w,�{:�;�'�wl, 4 ,,,'�:,r �r,n „}, •:> ,! .�S. a;a,4v .,, ,.,q,,, DATE CLOT, ti. I r Mh h ' '. P ll b t m +, d" qq 1 A 7 �} a ,3 } i' i� 1w t „'I I * ,M (a �'�p'' �y• '•t 'r w� ? ^ 2 CCCaa Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SFT -MC -C ©15CD 12 0.069 SET -MC -C @30CD 5 0.111 SC-C©75CD 3 0.2 SET -MC -C @95CD 2 0.264 ZR -MC -C @15CD 2 0.069 0.138 ZR- dIC-W @ i 5CD 4 0.064 0.256 ZR -MC -C @75CD 0.175 0.03 Amps 0.424 Amps Standby Current Load: 0.03 Amps : ' For 24 Hours=-. 0:720 Amp -hours Alarm Current Load: 0:424 Amps . For 5 Minute 0.036 Amp -hours 25% Derating ; 0.945 Amp -hours Total System Current Load: 0.945 Amp -hours ,tl 5 _ { ' a, °;:,' lvi PI"�, ,,. rn1e'' a M d°,c 9 d,. Notification ion A liance Circuit Detail PROJECT: SPACE #672 STORAGE Panel: I PAD -3 POWER SUPPLY Date: i March 14, 2011 Notification n t Appliance CircuitDetail to PROJECT: SPACE #672 STORAGE G XLS-V Date: March 14 2011 Wire Resistance CURRENT TOTAL 2.58 629.00 Panel: Wire Resistance 2.58 #REF! CURRENT TOTAL= ET -MC -C, @15CD C -C r©i 30CD SET -MC -C @75CD SET -MC -C @95CD ZR -MC -C @110CD ZR MC -C @15CD ZR -MC -W @15CD 0 : ZR -MC -C @75CD__ DEVICES= i 6 207 ! 222 200 0 52.2 4.96 0 DEVICES= 70,7V 137.16 14 175 TOTAL mA= 4 Total Wire Resistance (R ) Total Device Load, Amps (I) Voltage Drop (E) I EOL. Voltage„ ( WL * 2 )* (R/ft) (Total Cct Load) (E= 1,* R) 20.4-E) 1.991 0.63 1.25 19.15' Total Wire Resistance ( R ) Total DeviceLoad, Amps (I) Voltage Drop (E ) EOL: Voltage 19.68730018 137.16 (171/C;-2-) 2) * (R/ft)��.. otal Cct Load, (E= I R) 20.4-E SYSTEM CALCULATIONS (HALLWAY) s EX s,s',v,v' S-1 75cd V-1 1 /4-W V) co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE i\ V M 0 2 CCCaa W z o = ¢ T C) a 2 t— < WO wzz (Ou) w (9)g Uif 2 C!) CC ac 0 W z J LU z to 0 z aC C1) z O 5 J 0 W F- C/) Cr)} /SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 03/ 14/ 1 1 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved .0B NUMBER: 55178 J % SHEET FA -03 EY: 1 ST 1 - CORRID.C.-)R EXIE')TING .A.JACENT TENANT 5F40:: EXISTING-- 5 4 CI< CF HOUE7E. - CORRIDOR • ' S,S',V,V 8-1 75cd V LANDLORD I C„,- RAGE 2.E4 101 T Ac; Lr erA*7 merzir Air 4316._ • • FIRE ALARM SYSTEM PLAN -17-1 Proprietary and Confidential, Copyright 2011 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 (i) z0 (7) LU uJ (i) 1.1.1 LU REV. BY: 0 M 0 DESCRIPTION SHOP DRAWINGS LL1 < - 0 \ K) 0 2 <<<<< 0 z cc8 0 cc o < w (/) w z Z (NI ow' N. coco co i< -fP cc 0 w < cc Li/n 0_ 11 I— 111 CC LL ALE: 1/4" 1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:03/14/1 1 BACKROUND PLAN PROVIDED BY: JOB NUMBER: 55178 } C SHEET FA -04