PP - 539 SOUTHCENTER MALL - POLICE SUBSTATION - PERMITS AND PLANS
539 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-308 WESTFIELD POLICE SUBSTATION FIRE ALARM SYSTEM TUKWILA, WASHINGTON Iw XL - SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING A\D MOU\TI\G FA -03 FI RE ALARIV SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (GE\ERAL), RISER, SITE PLAN WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT DF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME 'CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT), WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 5 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IF<I LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) c FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC --CW SIEMENS 4S BOX W/ 1G RING CEILING n STROBE RM (WALL MOUNT) Q C ZR -MC --.0 SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM COWP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBDX FIRE ALARM TERMINAL CABINET F.B.O. r . . . . . . vtNl X IN FIELD O JUNCTION BOX A.F.F. ABOVE FINISHED FLOOR F.B.O. E. F.B.O. N/A ' N/A N/A Without Comments N/A F.B.D. FURNISHED BY OTHERS N/A N/ As Noted Ind N/A ❑ Per The Attached Letter N/A NOT APPLICABLE N/A r Neve plans have been reVibWed by The Tukwila FIrWA Prevention Bureau for conformance with current city N U.D.N. UNLESS OTHERWISE NOTED N/A standards. Acceptance is subject to errors and opOsAions which do not auttoizi,ze violations of adoptffilA standards and ordinances. The responsibility for the ' A complete Fire Dep WP WEATHERPROOF DEVICE N/A adequacy of design jests totally with the designer. pl�diktons, deletions or revibid►ics to these drawings A this date will void this acceptance and will require a Certificate to the Ir RED AS BUILT ADD OR CHANGE N/A resubmittal of revised drawings for subsequent approved. N/A N/A N/A Final acceptance is subject to fietd test and inspection by comencer m Testingc and Det GREEN AS BUILT REMOVE N/A I The I ukwila hire Prevention bureau N/A /� N/ • N/A Date: Go it 00 By: 0 00 Failure ( in a Re -in _. , ._ AS BUILT N/A terminaU NOTES TO CAD TUKWILA FIRE DEPART it&rAL Please call: 575.4402 and give this job No. 015 d exact address for shut sin or restoration approval »PP 3T80 To Ale: 67 o4/41 OTICE d, signed, Tukwi �rtment Pre-test must be presenr2d lspector prior to it: -1 00 O‘ mink O Ci3z u W o > a u) '7) TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE 00 0 in 0 (D 2 ««< z 0 F- CO W 0 0 0 J W vent of Acceptance f any Fire Alarm W ection Systems. f test will result spection Fee and �n of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F. co T C:1) 2 �z w wO W " ~z 2 W= F - D M 1- SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: 1.9B NUMBER: SHEET SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE+ A\ STOP IF LAST DEVICE { FROM XLS CONTROL PANEL ORS" PREVI❑US ADDRESSABLE DEVIC 0 DUCT DETECTOR LOCATI❑N 1 /-0 END OF LINE DEVICEC3.6K 1/4W) SUPERVISED SWITCH N GROUND LC) O O HTRI-R OSTATUS LED CO 0 N.O. n 0 CO 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL ima SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L + NOTE 11 VOLTAGE MAX,— CURRENT MAX,— CONT, RES, MAX,— MAX. CABLE LENGTH— C (LINE TO LINE)— C (LINE TO SHIELD)— MAX. LINE SIZE— MIN, LINE SIZE— MUSIC OUTLET SAMPLING \ TUBE \ INLET SAMPLING—\\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE [_AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE () END OF LINE DEVICE RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 rnA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC, TO GUARANTEE DETECTION, + TB1 S m 0 0 0 123456 HCP G1 C12 65'4321 TB2 o__21/2 (3.6K 1/4W) 0 N SUPERVISED....1 i SWITCH GROUND 0 0 U O HTRI-D OSTATUS LED 00 0 NOT USED CO 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC ni yul-J- -r -r T -r T 1' LI 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 5- 1' 75" 75 5- 5- 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) \. UPERVISED SWITCH NAC -4 NAC -3 NAC -2 NAC -1 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP .! 0 0- 0 0 0— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE> FROM FACP (VOICE CIRCUIT) ('V' CABLE) 470 OHMS EOL P N T M-1 oZ 'Pu0` r � X000 INC 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE N0 (STROBE(—) SPEAKER (+) () (+) STRDBE-) EARTH GROUND �►(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (+) (_) STROBE SPEAKER (3 () SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 80" A.F.F. } 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE 06WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS - SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE ❑R END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. ERV��N TEMPERATU E: +32 F (0' C) TO 106 F (338' C) HUMIDITY: 00--9 X RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECT)R —> FROM PREMQJS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE E-- > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX - z WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON \\ CEILING! FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 11 / / „/H0 0 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE `--- SUSPENDED ILLUMINATED CEILING D0 \OT INSTA_L ADDRESSABLE N T ATING DEVICES 1/4., \-1-11L PREPROGRA'VVED WITH DI -VICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., .SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS LU co 0 to 0 C CC C z 0 0o CO J cn � W �.- W cn z z _< 0 Q O.. w o JLL M LU 1 SCALE: 1/8" =1' DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: ..JOB NUMBER: SHEET FA -02 J ID0ST G METER CUTER 1200A, 20"/120A ER, 4W NEW SWOON TO DOSING 'mw -fl' NETER wfltR- ■ 1 1 3/4'C _ 313, Meg a CORRIE#S1n10G 1 0R 1 — 11N 0� CPTi. % E3EN HR1DGE LIF W 1_ER S PAREL IVI ER I E: S j C C) A T NA 0 11 ON WALDEN I-3 00 I \II S, NORTH BIAGIO :LLE NA ADE I N WA SF -1 I N f (DN SPEN E I f: Ts IEL.ECLL=i'i t'.. . WESTEJI AtNi Et= Al .1="111.07,a [IELEC LJ I CIF: THIE P C IL) PEOPL ABERCROMBIE >.- 1000 I ET1 11010 Li 1 56 0 • WESTFIELD POLICE SUBSTATION WESTFIELD SOUTHCENTER MALL [15501 0. 5 SCALE 11371 Ellen 15 15 30 30 30 15 15 EOL -S1 15 2S,2V (t) FA BOX EX FACP :71 5451 SYSTEM CALCULATIONS BATTERY SIZING CALCULATION WESTFIELD POLICE SUBSTATION WESTFIELD POLICE SUBSTATION FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Panel: WESTFIELD POLICE SUBSTATION Wire Resistance 1.62 Date: June 9, 2008 CURRENT TOTAL= 614 Current Load: CIRCUIT: S1 Standby: Alarm: Current Load: Standby: Alarm: Device Type Alarm Current 1 Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Deltice Type Total Wire Resistance ( R ) Qty Amps Total Amps Total Device Type Qty Amps WL * 2) * (R/ft) Total Amps Total 175 HFP-11 1 0.0022 0.0022 0.0023 0.002 0.61 0 SET -MC @110CD 233 0 AD2-P 0 0.0635 0.0635 0.064 Main System Board 1 0.03 0.38 0.03 0.030 0.030 0 HTR -R 0.009600 0.0096 0.021 0 SET -MC @15CD 318 2 0.064 0.128 Voltage HTRI-D 0 0.001600 0 0.0035 SET -MC @30CD •(20.4 3 0.098 0.294 ICP -B6 i , 0.005 3 Z-MC@15CD SET -MC @75CD 192 0.175 0 Z-MC@30CD 98 0 SET -MC @110CD 0 SET-MC-CW@110CD 233 0.233 DEVICES= 8 TOTAL m A= SET-HMC-C@115CD 191 20.02003224 614 0.318 allill , SET-HMC-C@135CD Notification Appliance Circuit Detail 0.318 PROJECT: WESTFIELD SOUTHCENTER MALL 0.0731 Amps Amps SET-HMC-C©185CD ZR -MC @15CD 1 3 Wire Resistance 2.58 0.445 0.064 0.192 CURRENT TOTAL= 9 Standby Current Load: SPEAKER CIRCUIT 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD QTY Device Type Alarm Current 0.098 Wire Size Wire Length Voltage at EOL Circuit Total 5. 70.7V1/8 1.8 HCP 0.0015 ( R ) Alarm Current Load: 0 Amps For 5 Minutes= Amp -hours (WL*2)*(R/ft) 0 0.03 Amps 0.644 Amps allrIIIIIIIIIIIIIIIIII •Total Device Load, Amps (I) 0.01 _0 0 0 (Total Cct Load) 0 0 0 25% Derating= 2.193 Amp -hours Standby Current Load: Drop 0.03 Amps 0.01 For 24 Hours = 0.720 Amp -hours 0 •(E= I * R) 0 0 0 EOL Voltage 20.39 0 0 0 Alarm Current Load: 0.644 Amps 0 For 5 Minutes= 0.054 Amp -hours Total System Current Load: 2.193 Amp -hours 0 0 DEVICES 5 TOTAL mA= 9 14 191 20.39112996 9 25% Derating= 0.968 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH , Total System Current Load: 0.968 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION FAX (206) 628-4990 (i) RELEASE/REVISI m UJ c z DESCRIPTION SHOP DRAWINGS uJ co 0 << r ‘CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F SHEE.:04 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: WESTFIELD POLICE SUBSTATION Wire Resistance 1.62 Date: June 9, 2008 CURRENT TOTAL= 614 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Total Wire Resistance ( R ) 0.62 3 SET -MC @30CD 98 294 •( WL * 2) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.61 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 •Voltage Drop ( E) 0.38 0 SET-HMC-C@177CD 445 0 • (E= I * R) 0 SET -HMC @135CD 318 0 •EOL Voltage 20.02 0 SET -HMC @185CD 445 0 •(20.4 - E) 3 Z-MC@15CD 64 192 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 8 TOTAL m A= 614IIlI 191 20.02003224 614 allill Notification Appliance Circuit Detail * PROJECT: WESTFIELD SOUTHCENTER MALL 111 Panel: WESTFIELD POLICE SUBSTATION Wire Resistance 2.58 Date: June 9, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 5. 70.7V1/8 1.8 9 Total Wire Resistance ( R ) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 allrIIIIIIIIIIIIIIIIII •Total Device Load, Amps (I) 0.01 _0 0 0 (Total Cct Load) 0 0 0 •Voltage Drop ( E ) 0.01 0, 0 0 •(E= I * R) 0 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES 5 TOTAL mA= 9 14 191 20.39112996 9 FAX (206) 628-4990 (i) RELEASE/REVISI m UJ c z DESCRIPTION SHOP DRAWINGS uJ co 0 << r ‘CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F SHEE.:04 539 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-308 WESTFIELD POLICE SUBSTATION FIRE ALARM SYSTEM TUKWILA, WASHINGTON Iw XL - SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UM3ER SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL DETAILS - WIRING A\D MOU\TI\G FA -03 FI RE ALARIV SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (GE\ERAL), RISER, SITE PLAN WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM F 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 O.D. .0467 .210 O.D. .0346 .156 O.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. LL NCH NCH NCH NCH NCH INCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT DF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO 'CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME 'CABLE ASSEMBLY (LE., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT), WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 5 3 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IF<I LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) c FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. ZR -MC --CW SIEMENS 4S BOX W/ 1G RING CEILING n STROBE RM (WALL MOUNT) Q C ZR -MC --.0 SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM COWP MR FIRE ALARM STROBE (WEATHERPROOF) MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBDX FIRE ALARM TERMINAL CABINET F.B.O. r . . . . . . vtNl X IN FIELD O JUNCTION BOX A.F.F. ABOVE FINISHED FLOOR F.B.O. E. F.B.O. N/A ' N/A N/A Without Comments N/A F.B.D. FURNISHED BY OTHERS N/A N/ As Noted Ind N/A ❑ Per The Attached Letter N/A NOT APPLICABLE N/A r Neve plans have been reVibWed by The Tukwila FIrWA Prevention Bureau for conformance with current city N U.D.N. UNLESS OTHERWISE NOTED N/A standards. Acceptance is subject to errors and opOsAions which do not auttoizi,ze violations of adoptffilA standards and ordinances. The responsibility for the ' A complete Fire Dep WP WEATHERPROOF DEVICE N/A adequacy of design jests totally with the designer. pl�diktons, deletions or revibid►ics to these drawings A this date will void this acceptance and will require a Certificate to the Ir RED AS BUILT ADD OR CHANGE N/A resubmittal of revised drawings for subsequent approved. N/A N/A N/A Final acceptance is subject to fietd test and inspection by comencer m Testingc and Det GREEN AS BUILT REMOVE N/A I The I ukwila hire Prevention bureau N/A /� N/ • N/A Date: Go it 00 By: 0 00 Failure ( in a Re -in _. , ._ AS BUILT N/A terminaU NOTES TO CAD TUKWILA FIRE DEPART it&rAL Please call: 575.4402 and give this job No. 015 d exact address for shut sin or restoration approval »PP 3T80 To Ale: 67 o4/41 OTICE d, signed, Tukwi �rtment Pre-test must be presenr2d lspector prior to it: -1 00 O‘ mink O Ci3z u W o > a u) '7) TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: I NVI DESCRIPTION SHOP DRAWINGS DATE 00 0 in 0 (D 2 ««< z 0 F- CO W 0 0 0 J W vent of Acceptance f any Fire Alarm W ection Systems. f test will result spection Fee and �n of the testing. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F. co T C:1) 2 �z w wO W " ~z 2 W= F - D M 1- SCALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: 1.9B NUMBER: SHEET SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE+ A\ STOP IF LAST DEVICE { FROM XLS CONTROL PANEL ORS" PREVI❑US ADDRESSABLE DEVIC 0 DUCT DETECTOR LOCATI❑N 1 /-0 END OF LINE DEVICEC3.6K 1/4W) SUPERVISED SWITCH N GROUND LC) O O HTRI-R OSTATUS LED CO 0 N.O. n 0 CO 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL ima SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE[ DEVICE TO NEXT ADDRESSABLE DEVICE L + NOTE 11 VOLTAGE MAX,— CURRENT MAX,— CONT, RES, MAX,— MAX. CABLE LENGTH— C (LINE TO LINE)— C (LINE TO SHIELD)— MAX. LINE SIZE— MIN, LINE SIZE— MUSIC OUTLET SAMPLING \ TUBE \ INLET SAMPLING—\\ TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE [_AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE f(+) STOP IF LAST DEVICE (-) FROM XLS CONTROL PANEL OR {(+) PREVIOUS ADDRESSABLE DEVICE () END OF LINE DEVICE RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3,5 rnA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC, TO GUARANTEE DETECTION, + TB1 S m 0 0 0 123456 HCP G1 C12 65'4321 TB2 o__21/2 (3.6K 1/4W) 0 N SUPERVISED....1 i SWITCH GROUND 0 0 U O HTRI-D OSTATUS LED 00 0 NOT USED CO 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC ni yul-J- -r -r T -r T 1' LI 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1— 1 2+ 2— 2 NC C NO + — + — + — + — + — 5- 1' 75" 75 5- 5- 24K TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE 3.6K 1/4W) \. UPERVISED SWITCH NAC -4 NAC -3 NAC -2 NAC -1 FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP .! 0 0- 0 0 0— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY C'S' CABLE> FROM FACP (VOICE CIRCUIT) ('V' CABLE) 470 OHMS EOL P N T M-1 oZ 'Pu0` r � X000 INC 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE N0 (STROBE(—) SPEAKER (+) () (+) STRDBE-) EARTH GROUND �►(+)TO NEXT DEVICE OR } >(-) STOP IF LAST DEVICE (+) (_) STROBE SPEAKER (3 () SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 80" A.F.F. } 4S DEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE 06WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS - SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE ❑R END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. ERV��N TEMPERATU E: +32 F (0' C) TO 106 F (338' C) HUMIDITY: 00--9 X RELATIVE HUMIDITY, NON—CONDENSING HFP-11 SMOKE DETECT)R —> FROM PREMQJS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN ( )> DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE E-- > ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX - z WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON \\ CEILING! FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 11 / / „/H0 0 0 0 IL TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE `--- SUSPENDED ILLUMINATED CEILING D0 \OT INSTA_L ADDRESSABLE N T ATING DEVICES 1/4., \-1-11L PREPROGRA'VVED WITH DI -VICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., .SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS z DESCRIPTION SHOP DRAWINGS LU co 0 to 0 C CC C z 0 0o CO J cn � W �.- W cn z z _< 0 Q O.. w o JLL M LU 1 SCALE: 1/8" =1' DRAWN BY: !.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: ..JOB NUMBER: SHEET FA -02 J ID0ST G METER CUTER 1200A, 20"/120A ER, 4W NEW SWOON TO DOSING 'mw -fl' NETER wfltR- ■ 1 1 3/4'C _ 313, Meg a CORRIE#S1n10G 1 0R 1 — 11N 0� CPTi. % E3EN HR1DGE LIF W 1_ER S PAREL IVI ER I E: S j C C) A T NA 0 11 ON WALDEN I-3 00 I \II S, NORTH BIAGIO :LLE NA ADE I N WA SF -1 I N f (DN SPEN E I f: Ts IEL.ECLL=i'i t'.. . WESTEJI AtNi Et= Al .1="111.07,a [IELEC LJ I CIF: THIE P C IL) PEOPL ABERCROMBIE >.- 1000 I ET1 11010 Li 1 56 0 • WESTFIELD POLICE SUBSTATION WESTFIELD SOUTHCENTER MALL [15501 0. 5 SCALE 11371 Ellen 15 15 30 30 30 15 15 EOL -S1 15 2S,2V (t) FA BOX EX FACP :71 5451 SYSTEM CALCULATIONS BATTERY SIZING CALCULATION WESTFIELD POLICE SUBSTATION WESTFIELD POLICE SUBSTATION FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Panel: WESTFIELD POLICE SUBSTATION Wire Resistance 1.62 Date: June 9, 2008 CURRENT TOTAL= 614 Current Load: CIRCUIT: S1 Standby: Alarm: Current Load: Standby: Alarm: Device Type Alarm Current 1 Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Deltice Type Total Wire Resistance ( R ) Qty Amps Total Amps Total Device Type Qty Amps WL * 2) * (R/ft) Total Amps Total 175 HFP-11 1 0.0022 0.0022 0.0023 0.002 0.61 0 SET -MC @110CD 233 0 AD2-P 0 0.0635 0.0635 0.064 Main System Board 1 0.03 0.38 0.03 0.030 0.030 0 HTR -R 0.009600 0.0096 0.021 0 SET -MC @15CD 318 2 0.064 0.128 Voltage HTRI-D 0 0.001600 0 0.0035 SET -MC @30CD •(20.4 3 0.098 0.294 ICP -B6 i , 0.005 3 Z-MC@15CD SET -MC @75CD 192 0.175 0 Z-MC@30CD 98 0 SET -MC @110CD 0 SET-MC-CW@110CD 233 0.233 DEVICES= 8 TOTAL m A= SET-HMC-C@115CD 191 20.02003224 614 0.318 allill , SET-HMC-C@135CD Notification Appliance Circuit Detail 0.318 PROJECT: WESTFIELD SOUTHCENTER MALL 0.0731 Amps Amps SET-HMC-C©185CD ZR -MC @15CD 1 3 Wire Resistance 2.58 0.445 0.064 0.192 CURRENT TOTAL= 9 Standby Current Load: SPEAKER CIRCUIT 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD QTY Device Type Alarm Current 0.098 Wire Size Wire Length Voltage at EOL Circuit Total 5. 70.7V1/8 1.8 HCP 0.0015 ( R ) Alarm Current Load: 0 Amps For 5 Minutes= Amp -hours (WL*2)*(R/ft) 0 0.03 Amps 0.644 Amps allrIIIIIIIIIIIIIIIIII •Total Device Load, Amps (I) 0.01 _0 0 0 (Total Cct Load) 0 0 0 25% Derating= 2.193 Amp -hours Standby Current Load: Drop 0.03 Amps 0.01 For 24 Hours = 0.720 Amp -hours 0 •(E= I * R) 0 0 0 EOL Voltage 20.39 0 0 0 Alarm Current Load: 0.644 Amps 0 For 5 Minutes= 0.054 Amp -hours Total System Current Load: 2.193 Amp -hours 0 0 DEVICES 5 TOTAL mA= 9 14 191 20.39112996 9 25% Derating= 0.968 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH , Total System Current Load: 0.968 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION FAX (206) 628-4990 (i) RELEASE/REVISI m UJ c z DESCRIPTION SHOP DRAWINGS uJ co 0 << r ‘CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F SHEE.:04 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: WESTFIELD POLICE SUBSTATION Wire Resistance 1.62 Date: June 9, 2008 CURRENT TOTAL= 614 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 2 SET -MC @15CD 64 128 Total Wire Resistance ( R ) 0.62 3 SET -MC @30CD 98 294 •( WL * 2) * (R/ft) 0 SET -MC @75CD 175 0 Total Device Load, Amps (1) 0.61 0 SET -MC @110CD 233 0 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 •Voltage Drop ( E) 0.38 0 SET-HMC-C@177CD 445 0 • (E= I * R) 0 SET -HMC @135CD 318 0 •EOL Voltage 20.02 0 SET -HMC @185CD 445 0 •(20.4 - E) 3 Z-MC@15CD 64 192 0 Z-MC@30CD 98 0 0 SET-MC-CW@110CD 233 0 DEVICES= 8 TOTAL m A= 614IIlI 191 20.02003224 614 allill Notification Appliance Circuit Detail * PROJECT: WESTFIELD SOUTHCENTER MALL 111 Panel: WESTFIELD POLICE SUBSTATION Wire Resistance 2.58 Date: June 9, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 5. 70.7V1/8 1.8 9 Total Wire Resistance ( R ) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 allrIIIIIIIIIIIIIIIIII •Total Device Load, Amps (I) 0.01 _0 0 0 (Total Cct Load) 0 0 0 •Voltage Drop ( E ) 0.01 0, 0 0 •(E= I * R) 0 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES 5 TOTAL mA= 9 14 191 20.39112996 9 FAX (206) 628-4990 (i) RELEASE/REVISI m UJ c z DESCRIPTION SHOP DRAWINGS uJ co 0 << r ‘CALE: 1/8"=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/05/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: RISER DIAGRAM VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved F SHEE.:04