Loading...
HomeMy WebLinkAboutPP - 555 SOUTHCENTER MALL - GODIVA CHOCOLATIER - PERMITS AND PLANS555 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-199 08-S-157 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Godiva 555 Southcenter Mall Permit No.: 08-S-157 Date: May 2, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'h inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a ' suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. cagy Ili C3 U 0-7 L O L O 1 O' -O" 0-7 A! Lin 5 -r. t 1_ p L) 0 U J\CEJ 0 rJ 1' `• F 0-7 L 1I C> 41 n J L. — 1'l 10 82 CEI -1 Lr.) 82 1-43 4" @ 14'-6" AFF Ir, SA SA '0 Hod B2A 15'-5; 11 .rm 1/\ TUKWILA FIRE DEPARTMEN1 Please call: 575.4402 and give this job and exact address for shut., -Jown or rostorati approval. No. I � i, I r Nfl 0-10 32 32 '1 11 BlA, } (J J A 1 I/1 f r 11 111,i 11 / 1 I1 11 11 i 11 / / n r� r 27'-O" v J i r i (GODIVA ChOCOLAT(R (scare: /2" = 1 '-o") SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K•FACT. HEAD FINISH ir11f ! 11 1 11 11 1 CONSTRUCTION NOTES: "GENERAL NOTES: ) I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "P', WHICH ARE TO 13E STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL HANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD LIST OF ELEVATIONS:; EXISTING SPRINKLER PIPE 4. @ 14'-6" ' ACT CEILING HEIGHT = AS NOTED GWS CEILING HEIGHT = 121-0" (U.N.O.) SYMBOL LEGEND:) = NEW RECESSED PENDANT ON DROP = NEW CONCEALED PENDANT ON DROP $- --S = EXISTING SPRINKLER PIPE TO REMAIN `S --i = NEW SPRINKLER PIPING 41.7 b CI Pr? e !'.<!"'i±? Fire (city! :a(opted for the per. d . avrings atter require a for I ecuant approval. sinal acc�pt�rlce is sub sot to field test and inspection by Tht Tukwila Fire Prevention Bureau. Date: PLATE FINISH TC Weld temps Dust be ins ed before pipe is hung.n t paint piping prior to hydrostatic test approval. TEMP. QUAN. Reliable Model FI FR Recessed Pendant 0 1/2' 1/2' 5.6 Chrome Chrome 155° 3 Reliable Model G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 7 APPROVALS BY: I TOTAL SPRINKLERS THIS SHEET 10 1 I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP(.( 2) 3) 4) 5) 6) 7) 8) ORDINARY HAZARD GROUP I SPRINKLER SPACING: 130 ft2 MAX. COSCO'S POINT OF CONNECTION 15 AT EXISTING SYSTEM AS SHOWN. ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY OTHER. ALL WIRING OF SYSTEM DEVICES IS BY OTHER. OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTAI 1 FD THE SYSTEMS) 1S BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. ANY RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3' METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750# * 1/2" ANCHOR w/40# TORQUE: TENSION=440#,SHEAR=750#* 'SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR TIM THREADS 1/4' MIN ROD COUPLING THREADED ROD PIPE SIZE ROD DIA. BOLT LGTH IMBED DEPTH I" 3/8" 3 3/4" 2 1/4" 1 1/4" 3/8" 3 3/4" 2 1/4" 1 I/2" 3/8" 3 3/4" 2 1/4" 2" 3/8" 3 3/4" 2 1/4" 2 1/2" 3/8' 3 3/4" 2 1/4" 3" 3/8" 3 3/4" 2 1/4' 4" 3/8" 3 3/4" 2 1/4" 6" 1/2" 3 3/4' 2 1/4" 8" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 I COSCO STANDARD HANGER 1 13 MDL N "0000" "000 . "00004" •0000 00• I cosco Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 10910 117TH Place N.E. Kirkland, Washington 98033 call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscofire.com License No: COSCOFP110NM PROJECT Godiva Chocolatier 309 Southcenter Mall, Level 1, Suite: 1020 Tukwila, Wa. 98188 CONTRACT vim The Stone Company General Contractors, Inc. 2019 Galisteo Street, Building N-10, Suite: C Santa Fe, Nm. 87505 Eric Lyons (505) 955-9960 DRAWING TUE Godiva Chocolatier: Sprinkler Piping Plan DATE : May 2008 SCALE : As Noted DRAWN BY : Justin Johnson SKS - 7930 SHEET 1413p FILE FIRS; ALA TUKWILA, IATA M SYSTEM ASHINGTON r• NERAL NOTES SHEET \U \/3E: SHEET TITLE • V C 0 0 • r., X 0 N '0 -o "a CL 0 1.4N CO N •Ln ii • a ii FA -0 1 SYSTEM I\FO.MATIO\ FA -02 TYPICAL DETAILS - I\C:AND MOU \TI \G FA -03 FRE ALAN SYSTE v FLOO: PLA\ FA -04 SYSTEV CALCULATIO\S (CEEAL), DISE SITE PLA\ 1 0 0 *cc Vvithout Comments As Noted In Red Per The Attached Letter !nese plans hays '?ren rev'itnied by The Tule: Bila Fire Prevention Burst.; `:.1 C(:!'!ti1:;i ;.. ' l'.'iirt current city standards. t,..• cuors and omissions \r..h:l.:; • (1- tit a acpted standar. LI; .. . :i. •.. f -: > ci ti::ii;GJ for the adequacy 01 t"..ii•,, ii, , ''!tji tnf.. UcSijyn r. Additions, ,}.! . t., th se cri`!iIgs atter 1 tills date will ',fold end will require a resubmittal of revts d dr e•..4 11 igs for subsequent approval. jj Final acceptance is Gut.ject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: By: II°UKWIL.A FIRE DEPARTMENT Please call: 575.4407, and give this job No.o()) F-(°\ • .10 and exact address for shut. Down or restoration approval: NOTTCE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and, termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE' WRAPPED WITH TAPE AND TAPED: AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSA, DEVICES ADDRESS. NUMBERS: ADJACENT TO DEV DEVICE 011-1-02 WOULD B 2. DETECTOR! AND AUDIBLE CIR 3. AUDIBLE/VISUAL CIRCUIT WIRI BRANCHING IS PERMISSIBL,, 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, L 5. INSTALLATION MATERIALS (I,:E STANDARD BOXES, FIBER OK ARE NOT SUPPLIED BY SIEMEN 6. DETECTORS SHALL NOT BE AIR STREAM OF AIR SUPPLY.,:, ?'3r 7. WIRING SHALL BE PER PLAN;;; TYPE, QUANTITY AND COLOR(; AND UNIQUELY MARKED FOR' 8. INSTALLING CONTRACTOR SH. DRAWINGS FOR "AS BUILT" g, FOR ADDITIONAL INSTALLATIO SHEETS AND/OR INSTALLATIQ 10. THE 120vac POWER ELECTRI MUST COMPLY WITH ARTICLE, SPECIFICALLY SECTION 1-5.211 SOURCES.. 120vac POWER SH:` DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND ST OF 80" A.F.F. OR 6" BELOW; 12. ALL MANUAL PULL STATION ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND 14. ALL 120VAC CIRCUITS ARE FOM 'DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3: :1 i3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN -Up 'OFT, ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED; B,Y ,THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 'I 'I III 16. WIRING SHALL RUN CONTINU tt1 AND 'THEN FROM DEVICE TOIiDEVI OTHER BACK: BOXES OF DIF NITIATING DEVICES UNTIL PREPROGRAMMED WITH V1BOL DENOTE DEVICE CIRCUIT/ADDRESS :GOND DEVICE ON ADDRESSABLE LOOP 1. LARITY SHALL BE OBSERVED. I'i'SUPERVISED. NO PARALLEL RICTiCONFORMANCE WITH THE NATIONAL AL :ODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 0 UIT, WIRE, FITTINGS, HANGERS, BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) E'RBERUS DIVISION. UNT U TLE 1 TH E TU "D IN DIRECT ITS. PER NFPA 72 2-3.5.1 RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, CONDUCTORS SHALL BE PERMANENTLY, E IDENTIFICATION. L. ,RTURN ONE SET OF ACCURATELY MARKED PO ES. INSTRUCTIONS, REFER TO CATALOG CUT INSTRUCTIONS. RK SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NEPA 70, N.E.C. AND NFPA 72, IIN REFERENCE TO DEDICATED BRANCH POWER NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT M TECHNICIAN. :EVICES SHALL BE MOUNTED AT A HEIGHT ?ED CEILING, WHICHEVER IS LESS. RA1 BE MOUNTED AT 48" A.F.F. TO THE r JIT$ WILL BE ON THE RECORD DRAWINGS SET. 17. ALL WIRING SHALL BE METE AND FREE OF SHORTS BET FINAL EQUIPMENT TRIM. OM FACP TO FIRST DEVICE ON A CIRCUIT E WITHOUT SPLICING IN PULL BOXES OR CIRCUITS. ,,,ERIFIED TO BE CONTINUOU.S, FREE OF GROUND ::CONDUCTORS AND: OTHER CIRCUITS PRIOR TO 18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.' I,i '111• t 19. THE ELECTRICAL CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE OUTSIDE , AND INSIDE OF1 TH;E (,FIRE,. ALARM BACK BOXES AND JUNCTION :BOXES AFTER COMPLETION OF THE( I' INS',ALLATION: 20. DETECTORS MUST .BE RATEDFjCR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS: LOCATED. 21. ALL WIRING BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT. 22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLE:S OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., iMETALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE ,Q ITGQING AND RETURN 'CONDUCTORS, EXITING FROM AND RETURNING TO THE'.COt' TROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OlTGOII,G AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE „t UN jj� THE SAME CABLE ASSEMBLY (I.E., tl it MULTI -CONDUCTOR CABLE), '::E'NlCLO URE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 6,1:GOA OF 6.4.2.2.2 IS TO PROVIDE EN THE OUTGOING AND RETURN CABLES. TO HELP ENSURE, PROTECTION .OF THE HE RECOMMENDED MINIMUM DAMAGE IS 305 ; VM (1 FT) WHERE Y AND 1.22 M (4 FT) WHERE THE ADEQUATE SEPARATION BETW THIS SEPARATION IS REQUIRE; CABLES FROM PHYSICAL DAIS; SEPARATION T0 PREVENT. PH THE CABLE IS INSTALLED VE CABLE IS ;INSTALLED: QUANTITY 2 EX SYMBOL ! '.IDESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP ' •; FIRE ALARM EX?,CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA �I,FIRE ALARM :;`:REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP. BPSll • ,L? • 11;13EMOTE BOOSTER PAD -3 ' SIEMENS X,HIIPOWER SUPPLY TERFACE MODULEHTRI-R' SIEMENS +;WITH RELAY PROVIDED 66" A.F.F. TO TOP' 4S DEEP VERIFY IN FIELD '`DUAL INPUT I:INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCRI iCONTROL POINT 'I::MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM Il' REMOTE CONVENTIONAL HZM I'ZONE MODULE SIEMENS 4S DEEP VERIFY • IN FIELD B 1i; LINEAR BEAM II (;,SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -1 1 BASE 4S DEEP IN/ 1G RING CEILING ,!:(:DUCT SMOKE :(;DETECTOR •,; AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR • (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 4F FIRE ALARM SPEAKER STROBE l„'(CEILING MOUNT) (.'FIRE ALARM 1('iSPEAKER STROBE ,!;(WALL MOUNT) IiitFIRE ALARM ••'('SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING; • 80" A.F.F. TO BOTTOM CEILING IRE ALARM '1`HSTROBE 4(CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING lliIFIRE ALARM II STROBE :(WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. it FIRE ALARM i! SPEAKER 'i (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ' FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM ' FIRE ALARM C) STROBE WP (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA 'JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD `JUNCTI❑N BOX F.B.D. F.B.O. N/A VERIFY IN FIELD ABOVE FINISHED :FLOOR N/A N/A N/A N/A FURNISHED BY !-:OTHERS N/A N/A N/A N/A N%() i:;N❑T APPLICABLE N/A N/A N/A N/A ;.UNLTEESSD OTHERWISE N❑ N/A N/A N/A N/A WEATHERPROOF DEVICE N/A N/A N/A N/A RED' ''AS BUILT • ';,ADD OR CHANGE N/A N/A N/A N/A GREEN • AS BUVEILT REM❑ N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A I; • Tu I. FIr,e n i .•a Copyright 2006 by Guardian Security, Systems, Inc.. All Rights.' R;eerw'e'dl;`f l 1, z ci) cc 'ccz o'. OD N X LL RELEASE/REVISIONS REV. BY: WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR C❑DE D H P ' S . 2S A V 2V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR',WITH SHIELD 416 FPL/FPLR ' RED (JACKET) DOOR HOLDER POWER - 24VDC TWO . 414 FPL/FPLR 'RED (JACKET) DEVICE POWER - 24VDC TWO , 416 FPL/FPLR .' RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) . STROBE CIRCUIT - RETURN TWISTED PAIR 'W/ SHIELD 412 FPL/FPLR ,RED (JACKET) ANNUNCIATOR TWISTED PAIR 'W/ SHIELD #16, FPL/FPLR .' RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR . 414 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - RETURN TWISTED PAIR. 414 .FPL/FPLR ' RED (JACKET) REMOTE INDICATI❑N LIGHT TWO 2 418 FPL/FPLR • RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIRW/'SHIELD 416 FPL/FPLR ' RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED '. 418 ' FPL/FPLR .RED (JACKET) , UNDERGROUND INITIATION ',TWISTED PAIR RATED #18 FPL/FPLR , RED .(JACKET) DOOR HOLDER POWER TWO 416 FPL/FPLR • RED .(JACKET) BEAM DETECTOR POWER TWO • • 414 FPL/FPLR RED (JACKET) CONDUIT FILL CHART SHOP DRAWINGS NO. OF CONDUCTORS VOLTS • WIRE SIZE' TYPE :... • • DIMENSIONS AREA ' TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL • CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON' THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" • .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" ' .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE' WRAPPED WITH TAPE AND TAPED: AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSA, DEVICES ADDRESS. NUMBERS: ADJACENT TO DEV DEVICE 011-1-02 WOULD B 2. DETECTOR! AND AUDIBLE CIR 3. AUDIBLE/VISUAL CIRCUIT WIRI BRANCHING IS PERMISSIBL,, 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, L 5. INSTALLATION MATERIALS (I,:E STANDARD BOXES, FIBER OK ARE NOT SUPPLIED BY SIEMEN 6. DETECTORS SHALL NOT BE AIR STREAM OF AIR SUPPLY.,:, ?'3r 7. WIRING SHALL BE PER PLAN;;; TYPE, QUANTITY AND COLOR(; AND UNIQUELY MARKED FOR' 8. INSTALLING CONTRACTOR SH. DRAWINGS FOR "AS BUILT" g, FOR ADDITIONAL INSTALLATIO SHEETS AND/OR INSTALLATIQ 10. THE 120vac POWER ELECTRI MUST COMPLY WITH ARTICLE, SPECIFICALLY SECTION 1-5.211 SOURCES.. 120vac POWER SH:` DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND ST OF 80" A.F.F. OR 6" BELOW; 12. ALL MANUAL PULL STATION ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND 14. ALL 120VAC CIRCUITS ARE FOM 'DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3: :1 i3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN -Up 'OFT, ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED; B,Y ,THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 'I 'I III 16. WIRING SHALL RUN CONTINU tt1 AND 'THEN FROM DEVICE TOIiDEVI OTHER BACK: BOXES OF DIF NITIATING DEVICES UNTIL PREPROGRAMMED WITH V1BOL DENOTE DEVICE CIRCUIT/ADDRESS :GOND DEVICE ON ADDRESSABLE LOOP 1. LARITY SHALL BE OBSERVED. I'i'SUPERVISED. NO PARALLEL RICTiCONFORMANCE WITH THE NATIONAL AL :ODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 0 UIT, WIRE, FITTINGS, HANGERS, BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) E'RBERUS DIVISION. UNT U TLE 1 TH E TU "D IN DIRECT ITS. PER NFPA 72 2-3.5.1 RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, CONDUCTORS SHALL BE PERMANENTLY, E IDENTIFICATION. L. ,RTURN ONE SET OF ACCURATELY MARKED PO ES. INSTRUCTIONS, REFER TO CATALOG CUT INSTRUCTIONS. RK SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NEPA 70, N.E.C. AND NFPA 72, IIN REFERENCE TO DEDICATED BRANCH POWER NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT M TECHNICIAN. :EVICES SHALL BE MOUNTED AT A HEIGHT ?ED CEILING, WHICHEVER IS LESS. RA1 BE MOUNTED AT 48" A.F.F. TO THE r JIT$ WILL BE ON THE RECORD DRAWINGS SET. 17. ALL WIRING SHALL BE METE AND FREE OF SHORTS BET FINAL EQUIPMENT TRIM. OM FACP TO FIRST DEVICE ON A CIRCUIT E WITHOUT SPLICING IN PULL BOXES OR CIRCUITS. ,,,ERIFIED TO BE CONTINUOU.S, FREE OF GROUND ::CONDUCTORS AND: OTHER CIRCUITS PRIOR TO 18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.' I,i '111• t 19. THE ELECTRICAL CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE OUTSIDE , AND INSIDE OF1 TH;E (,FIRE,. ALARM BACK BOXES AND JUNCTION :BOXES AFTER COMPLETION OF THE( I' INS',ALLATION: 20. DETECTORS MUST .BE RATEDFjCR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS: LOCATED. 21. ALL WIRING BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT. 22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLE:S OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., iMETALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE ,Q ITGQING AND RETURN 'CONDUCTORS, EXITING FROM AND RETURNING TO THE'.COt' TROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OlTGOII,G AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE „t UN jj� THE SAME CABLE ASSEMBLY (I.E., tl it MULTI -CONDUCTOR CABLE), '::E'NlCLO URE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 6,1:GOA OF 6.4.2.2.2 IS TO PROVIDE EN THE OUTGOING AND RETURN CABLES. TO HELP ENSURE, PROTECTION .OF THE HE RECOMMENDED MINIMUM DAMAGE IS 305 ; VM (1 FT) WHERE Y AND 1.22 M (4 FT) WHERE THE ADEQUATE SEPARATION BETW THIS SEPARATION IS REQUIRE; CABLES FROM PHYSICAL DAIS; SEPARATION T0 PREVENT. PH THE CABLE IS INSTALLED VE CABLE IS ;INSTALLED: QUANTITY 2 EX SYMBOL ! '.IDESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP ' •; FIRE ALARM EX?,CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA �I,FIRE ALARM :;`:REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP. BPSll • ,L? • 11;13EMOTE BOOSTER PAD -3 ' SIEMENS X,HIIPOWER SUPPLY TERFACE MODULEHTRI-R' SIEMENS +;WITH RELAY PROVIDED 66" A.F.F. TO TOP' 4S DEEP VERIFY IN FIELD '`DUAL INPUT I:INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCRI iCONTROL POINT 'I::MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM Il' REMOTE CONVENTIONAL HZM I'ZONE MODULE SIEMENS 4S DEEP VERIFY • IN FIELD B 1i; LINEAR BEAM II (;,SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -1 1 BASE 4S DEEP IN/ 1G RING CEILING ,!:(:DUCT SMOKE :(;DETECTOR •,; AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR • (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 4F FIRE ALARM SPEAKER STROBE l„'(CEILING MOUNT) (.'FIRE ALARM 1('iSPEAKER STROBE ,!;(WALL MOUNT) IiitFIRE ALARM ••'('SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING; • 80" A.F.F. TO BOTTOM CEILING IRE ALARM '1`HSTROBE 4(CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING lliIFIRE ALARM II STROBE :(WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. it FIRE ALARM i! SPEAKER 'i (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ' FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM ' FIRE ALARM C) STROBE WP (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA 'JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD `JUNCTI❑N BOX F.B.D. F.B.O. N/A VERIFY IN FIELD ABOVE FINISHED :FLOOR N/A N/A N/A N/A FURNISHED BY !-:OTHERS N/A N/A N/A N/A N%() i:;N❑T APPLICABLE N/A N/A N/A N/A ;.UNLTEESSD OTHERWISE N❑ N/A N/A N/A N/A WEATHERPROOF DEVICE N/A N/A N/A N/A RED' ''AS BUILT • ';,ADD OR CHANGE N/A N/A N/A N/A GREEN • AS BUVEILT REM❑ N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A I; • Tu I. FIr,e n i .•a Copyright 2006 by Guardian Security, Systems, Inc.. All Rights.' R;eerw'e'dl;`f l 1, z ci) cc 'ccz o'. OD N X LL RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE M 0 0 11) o a«« W } N SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: NUMBER:54510 FA -01 I; CO 7, • NORTH Go DIVA WESTFIELD SOUTHCENTER MALL SC1,41110T: , ::11 ,i'.,• .:g •.f: • 11 • ; , 1', • 11 .1 . • , • • 11 ' 7I,AG NOT ,S: I • 1 1 I Z... ' 1 11.1, z 1 „, 11 1 FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. ' 1 kr, DO \OT INST ADDRESSABLE DEVICES ._,\TI LL NJT AT PREPROGRAMVED W DEVICES ADDRESS. T Copyright 2006 by Guardian Security Systems, Inc. All Rights CO Cl) u_T F— uJ U) U) ui U) tr) r--- RELEASE/REVISIONS REV. BY: . 4 DESCRIPTION SHOP DRAWINGS DATE co 0 ...., to ...... .1 —_107) 2 w 0 < Eut wi 1.—.J cc 0 c, < 0 LO 0 LIJ H >11 6ALE: 1/8"=l' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: ..JOB NUMBER:54510 j SHEET eperyedZ. FA -03 .1 1..044, • • 13 [I JE 3 P. I D J1P3 /\[ f: NA ERIE. SUN COAST MC..) -1-1(2)1\i C ILlR EEl •• 1131 ACI ml - 11 II VE: RTZ: (i) N \NI R E L. E:; :H;I. 'I' II II 1-•-• I: --- Cil K ' m IN WA 1-111 \ C SP LIN !..:;:EIR GIFTS NORTH r- / lvi AI 1 1. OFICE OFFICE CU LLJ L.) <1.• (I) LU Li NJ LIAMBA JUICE: ID 1:)(l11U ABFRCPOMBIE - - - - C A TEl IL riL[1 APIN El TE Asjvi SI p I I: SYSTEM CALCULATIONS ' GODIVA GODIVA ; • 1 , I SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations »FACP ADD ONS WESTFIELD SOUTHCENTER MALL .. PROJECT: GODIVA r., • Wire Resistance 1.0"1, • ' Panel: Date: May 13, 2008 - CURRENT TOTAL= 350 . Current Load: Standby S1 - Alarm: -: Current Load: Standby: Alarm: --------- ,! ,1; • ____ _ Device Type Alarm Current Alarm Total Wire Size 1 Device Type Qty Amps Total Amps Total 64 Device Type Qty Amps Total Amps Total Total Wire Resistance ( R ) 0.86 0 0 _ SET -MC @30CD .98 0 HFP-11 0.0022 0.0022 0.0023 . 2 SET -MC @75CD 175 Maid System Board 1 0.03 . 0.03 0 030 0.030 Total Device Load, Amps (I) AD2-P 2 0.0635 0.0635 0.064 0.128 Cct Load) 0.064 SET-HMC-C115CD 318 IHTR-R 2 0.009600 0.0096 0.021 0.042 Voltage Drop ( E)0.30 - SET-HMC-C@177CD 445 I 0 (E=• I * R) __._ ----- 0 SET -HMC g135CD , . 318 §E -0716d5666 1 _ ' 0.098 EOL Voltage ' 20.10 HTRI-D SET -HMC g185CD . 0.001600 ' 0 0.0035 • SET-MCb75CD 2 , , . 0 0.175 0.350 0- ;ICP -B6 0 005 • • • : 0 SEtIVIC 6110CD 98 0 0.233 , _ 0 SET-MC-CW@110CD '1 233 0 i SET-HMO-C@115CD . ' _ ----- 0.318 DEVICES= 2 , .___ 350 12 265 20.099491 350 . - SET-HMC7C@135CD - Notification 0.318 ••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06 -trfl•11, .4 -.........*1 I* .,.1},MAY.V....11* Circuit ...., ny...~.1.••••mws Twom.ret taw... IT.T+01 Detail M,I" V _ WESTFIELD SOUTHCENTER SETI-16,76161135 , 0.445 PROJECT - • , • ':, . 1 .;: Wire Resistance :i08.,I, ; • - ,.;,;- 0.0731 Amps 0.17 AmPO;; ,11____ ZR -MO @I5CD 3.6 0.064 Date: CIRCUIT: SPEAKER CIRCUIT , , Device Type 0.098 Alarm Total Wire Size Standby Current Load: 0 0731 Amps For 24 Hours = 1.754 Amp -hours ! i I I;: . .ZR-;Woco HCP: '' t_, . 1.8 - 3.6 1 0.0015 Total Wire Resistance ( R ) _ _ 2.92 ' 0 • - , ' 0 • 0,, F . i i - --- 7 - •- -"------ - ( WL *2 )* (R/ft) 0.03 Amps 0.38 Amps , Alarm Current Load: 0.17 Amps For 5 Minutes= 0.014 Amp -hours ' 0.00 0 , 0 0 , ._____ ,. . (Total Cct Load) 0 . , _ 0 Standb Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 ; ., 25% Derating= 2.211 Amp -hours (E= I * R) II,I 0 _ 0 _ ,.I EOL Voltage ___ 20.39 0 _ , , 0 0 _ Alarmrent Load: 0.38 Amps For 5 Minutes= 0.032 Amp -hours 0 ' 0 r, _ 0 0 Total System Current Load: . , 2.211 Amp -hours I, 0 2 . TOTAL mA= 3.6 25% Derating= 0.940 Amp -hours 3.6 DEVICES= Battery Pair to be Used: 12VDC Amp -hours 7AH , Total System Current Load: 0.940 Amp -hours , Battery pair to be Used: 12VDC Amp -hours 7AH 0 , , ; ; . 11 P THE L 0 reF 1 01 0 r- • re; 15501' I)] [(11 '-1-5 .1 1 1 1 (-) ; ! 11(1 AC_F- 5401 '1.--- GODIVA WESTFIELD SOUTHCENTER MALL AP D,I 21 RISER DIAGRAM I ; BATTERY SIZING CALCULATION .. _ .._ . Notification Appliance 'Circuit Detail WESTFIELD SOUTHCENTER MALL .. PROJECT: GODIVA r., • Wire Resistance 1.0"1, • ' Panel: Date: May 13, 2008 - CURRENT TOTAL= 350 . CIRCUIT: QTY . S1 - -, L -: --------- ____ _ Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total SET -MC @15CD 64 0 . Total Wire Resistance ( R ) 0.86 0 0 _ SET -MC @30CD .98 0 1 ( WL* 2 )*(R/ft) . 2 SET -MC @75CD 175 • 350 ; Total Device Load, Amps (I) 0.35 0 6 . SET -MC @110CD 233 0(Total Cct Load) SET-HMC-C115CD 318 : 0 Voltage Drop ( E)0.30 - SET-HMC-C@177CD 445 I 0 (E=• I * R) __._ ----- 0 SET -HMC g135CD , . 318 _ 0 _ ' EOL Voltage ' 20.10 SET -HMC g185CD . , 445 ' 0 .I • : (20.4 - E) , , , . 0 Z-MC@15CD . . ' 64 0- _ _ • • • : 0 Z-MC@30CID 98 0 , _ 0 SET-MC-CW@110CD '1 233 0 . ' _ ----- DEVICES= 2 , TOTAL mA= .___ 350 12 265 20.099491 350 . - - Notification .......,......._....,.. T.INIW •`.• .Appliance ••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06 -trfl•11, .4 -.........*1 I* .,.1},MAY.V....11* Circuit ...., ny...~.1.••••mws Twom.ret taw... IT.T+01 Detail M,I" V _ WESTFIELD SOUTHCENTER ___ MALL ----- PROJECT .GODIVA;:;-,...:.,i.,..,..,..... ....-- -,...:- • • : - ... ...... ' - •, - - • , • ':, . 1 .;: Wire Resistance :i08.,I, ; • - ,.;,;- . .... . ... . , ..:Panel • May 13, 2008 ; , .• CURRENT TOTAL 3.6 Date: CIRCUIT: SPEAKER CIRCUIT , Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total - _ QTY 2 70.7V 1/8 , . 1.8 - 3.6 1 Total Wire Resistance ( R ) _ _ 2.92 ' 0 • - , ' 0 • 0,, . ( WL *2 )* (R/ft) 0 , , ' •;. . .0 Total Device Load, Amps (I) 0.00 0 0 0 , ._____ ,. . (Total Cct Load) 0 . , _ 0 _ Voltage ( E) E ) 0.01 0 0 ; ., (E= I * R) 0 _ 0 _ ,.I EOL Voltage ___ 20.39 0 _ , , 0 0 _ L:icl iI,I:I, (20.4 - E) 0 ' 0 r, _ 0 0 ,, --,,- --,- • . , - - 0 2 . TOTAL mA= 3.6 14 .,.;, 565 20.389504561. 3.6 DEVICES= VOLTAGE DROP CALCULATION z 0 (/) LLJ CE LJJ U) UJ _.J LI_J z DESCRIPTION z 0 0 01 LLJ0 F- 0 CO Lfl <<<C1 J 03 CO PrEs -Jo, Z W 0 < CC wo > zz 2 w w 0 5 o < - W 0 (f) tcr3 LoD (S.*C'ALE: 1/8''=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: ,Copyright 2006 by Guardian Security.,.SYstems, Inc. All Rights Reserved R;' 1..0B NUMBER:54510 SHEET '\ FA -04 555 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-199 08-S-157 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Godiva 555 Southcenter Mall Permit No.: 08-S-157 Date: May 2, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 % inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a ' suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. cagy Ili C3 U 0-7 L O L O 1 O' -O" 0-7 A! Lin 5 -r. t 1_ p L) 0 U J\CEJ 0 rJ 1' `• F 0-7 L 1I C> 41 n J L. — 1'l 10 82 CEI -1 Lr.) 82 1-43 4" @ 14'-6" AFF Ir, SA SA '0 Hod B2A 15'-5; 11 .rm 1/\ TUKWILA FIRE DEPARTMEN1 Please call: 575.4402 and give this job and exact address for shut., -Jown or rostorati approval. No. I � i, I r Nfl 0-10 32 32 '1 11 BlA, } (J J A 1 I/1 f r 11 111,i 11 / 1 I1 11 11 i 11 / / n r� r 27'-O" v J i r i (GODIVA ChOCOLAT(R (scare: /2" = 1 '-o") SPRINKLER HEAD LEGEND : SYMBOL S/N ORIFICE NPT K•FACT. HEAD FINISH ir11f ! 11 1 11 11 1 CONSTRUCTION NOTES: "GENERAL NOTES: ) I) PIPE: THREADED: STEEL, SCH 40, BLACK, IMPORT. GROOVED: STEEL, SCH 10, BLACK, IMPORT. 2) FITTINGS: GROOVED: STAR STANDARD - ORANGE PAINT FINISH THREADED: STAR D.I. 3) GROOVED COUPLINGS: STAR RIGID C-4 UNLESS MARKED WITH AN "P', WHICH ARE TO 13E STAR FLEXIBLE C-3 LW - ORANGE PAINT FINISH 4) HANGER MATERIAL: ALL HANGER MATERIAL IS TO BE FINISHED BLACK OR STANDARD LIST OF ELEVATIONS:; EXISTING SPRINKLER PIPE 4. @ 14'-6" ' ACT CEILING HEIGHT = AS NOTED GWS CEILING HEIGHT = 121-0" (U.N.O.) SYMBOL LEGEND:) = NEW RECESSED PENDANT ON DROP = NEW CONCEALED PENDANT ON DROP $- --S = EXISTING SPRINKLER PIPE TO REMAIN `S --i = NEW SPRINKLER PIPING 41.7 b CI Pr? e !'.<!"'i±? Fire (city! :a(opted for the per. d . avrings atter require a for I ecuant approval. sinal acc�pt�rlce is sub sot to field test and inspection by Tht Tukwila Fire Prevention Bureau. Date: PLATE FINISH TC Weld temps Dust be ins ed before pipe is hung.n t paint piping prior to hydrostatic test approval. TEMP. QUAN. Reliable Model FI FR Recessed Pendant 0 1/2' 1/2' 5.6 Chrome Chrome 155° 3 Reliable Model G4A Concealed Pendant 1/2' 1/2' 5.6 Brass White 165° 7 APPROVALS BY: I TOTAL SPRINKLERS THIS SHEET 10 1 I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF TUKWILA. CRITERIA: OCCUPANCY: ORDINARY HAZARD GROUP(.( 2) 3) 4) 5) 6) 7) 8) ORDINARY HAZARD GROUP I SPRINKLER SPACING: 130 ft2 MAX. COSCO'S POINT OF CONNECTION 15 AT EXISTING SYSTEM AS SHOWN. ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY OTHER. ALL WIRING OF SYSTEM DEVICES IS BY OTHER. OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE. OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F. MINIMUM AT ALL TIMES. OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION, TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED., BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS EXPIRED. THE FIRM THAT DESIGNED AND INSTAI 1 FD THE SYSTEMS) 1S BEST QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE, AND SERVICING. ANY RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION. HILTI KWIK BOLT 3 ANCHOR ICC REPORT #ESR -1385 MIN. OF 3,000 PSI CONCRETE MIN. 3 1/4" CONCRETE OVER MAX. 3' METAL DECK 3/8" ANCHOR w/20# TORQUE: TENSION=395#, SHEAR=750# * 1/2" ANCHOR w/40# TORQUE: TENSION=440#,SHEAR=750#* 'SHEAR LOADS HAVE BEEN REDUCED BY 20% FOR SHEAR TIM THREADS 1/4' MIN ROD COUPLING THREADED ROD PIPE SIZE ROD DIA. BOLT LGTH IMBED DEPTH I" 3/8" 3 3/4" 2 1/4" 1 1/4" 3/8" 3 3/4" 2 1/4" 1 I/2" 3/8" 3 3/4" 2 1/4" 2" 3/8" 3 3/4" 2 1/4" 2 1/2" 3/8' 3 3/4" 2 1/4" 3" 3/8" 3 3/4" 2 1/4' 4" 3/8" 3 3/4" 2 1/4" 6" 1/2" 3 3/4' 2 1/4" 8" 1/2" 3 3/4" 2 1/4" HILTI FIG. LH OR TOLCO FIG. 200 HANGER RING UL 04/2007 I COSCO STANDARD HANGER 1 13 MDL N "0000" "000 . "00004" •0000 00• I cosco Fire Protection FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE 10910 117TH Place N.E. Kirkland, Washington 98033 call (425) 827-9654 • fax (425) 827-7474 SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE www.coscofire.com License No: COSCOFP110NM PROJECT Godiva Chocolatier 309 Southcenter Mall, Level 1, Suite: 1020 Tukwila, Wa. 98188 CONTRACT vim The Stone Company General Contractors, Inc. 2019 Galisteo Street, Building N-10, Suite: C Santa Fe, Nm. 87505 Eric Lyons (505) 955-9960 DRAWING TUE Godiva Chocolatier: Sprinkler Piping Plan DATE : May 2008 SCALE : As Noted DRAWN BY : Justin Johnson SKS - 7930 SHEET 1413p FILE FIRS; ALA TUKWILA, IATA 1VI SYSTEM ASHINGTON r• NERAL NOTES SHEET \U \/3E. SHEET TITLE • a FA -0 1 SYSTEM \FOMATIO\ FA -02 TYPICAL DETAILS - WRI\G ':AND MOU \TI \ G FA -03 FRE ALAN SYSTE V FLOG: 'PLA\ FA -04 SYSTEV CALCULATIO\S (CEEAL), DISE SITE PLA\ 1 0 *cc Vvithout Comments As Noted In Red Per The Attached Letter nese plans have 'b nen revitnied by The Tule: Bila Fire Prevention Bur?.; `:.3 C:!!til::ii'i,;., 'v'.'iir', current city standards. rurs and omissions wh:1:i • n ::u,..: �. ,,;'.dations of adopted >tanciara LI; •.. re:;>wlisib:iity for the adequacy 01 t" . .ii•,, 1.ii,, ''!U i il•if.; U,..,• Sijyner. Additions, C% }If .,'r 1 ,}! ..'`':�',I,.i lc t., Ih se ciria`!'.�ings atter 1 tills date will v ,1 tl 1• ,.::.;: +nc:e end will require a resubmittal of re,'i al dre: ivli igs for subsequent approval. jj Final acceptance is Subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: By: II°UKWIL.A FIRE DEPARTMENT Please call: 575.4407, and give this job No. o ()) F ( °\ • .10 and exact address for shut. clown or restoration approval: NOTTCE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and, termination of the testing. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE T❑ BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED: AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSA, DEVICES ADDRESS. NUMBERS :ADJACENT TO DEV DEVICE 011-1-02 WOULD B 2. DETECTOR' AND AUDIBLE CIR 3. AUDIBLE/VISUAL CIRCUIT WIRI BRANCHING IS PERMISSIBLE, 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, L 5. INSTALLATION ' MATERIALS (I. , STANDARD, BOXES, FIBER ORA ARE NOT SUPPLIED BY SIEMEI 6. DETECTORS SHALL NOT BE ,M AIR STREAM OF AIR SUPPLY.,:, ?'3r 7. WIRING SHALL BE PER PLAN;;; TYPE, QUANTITY AND COLOR(; AND UNIQUELY MARKED FOR;' 8. INSTALLING CONTRACTOR SH DRAWINGS FOR "AS BUILT" g, FOR ADDITIONAL INSTALLATIO SHEETS AND/OR INSTALLATIO 10. THE 120vac POWER ELECTRI MUST COMPLY WITH ARTICLE, SPECIFICALLY SECTION 1-5.211 SOURCES.. 120vac POWER SH:` DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND ST, OF 80" A.F.F. OR 6" BELOW; 12. ALL MANUAL PULL STATION' ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND NITIATING DEVICES UNTIL PREPROGRAMMED WITH V1BOL DENOTE DEVICE CIRCUIT/ADDRESS :GOND DEVICE ON ADDRESSABLE LOOP 1. LARITY SHALL BE OBSERVED. I'i'SUPERVISED. NO PARALLEL RICTiCONFORMANCE WITH THE NATIONAL ALI�:ODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 0 UIT, WIRE, FITTINGS, HANGERS, BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) E'RBERUS DIVISION. 'UNT �U TLE ITH E TU 'D IN DIRECT TS. PER NFPA 72 2-3.5.1 RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, ,CONDUCTORS SHALL BE PERMANENTLY, E IDENTIFICATION. L. ,R TURN ONE SET OF ACCURATELY MARKED PO ES. INS,ItRUCTIONS, REFER TO CATALOG CUT INSTRUCTIONS. RK SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NEPA 70, N.E.C. AND NFPA 72, IIN REFERENCE TO DEDICATED BRANCH POWER 'N'OT BE APPLIED TO FIRE ALARM PANEL WITHOUT M TECHNICIAN. :EVICES SHALL BE MOUNTED AT A HEIGHT ?ED CEILING, WHICHEVER IS LESS. RA1 BE MOUNTED AT 48" A.F.F. TO THE r JIT$ WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE ;ROM 'DEDICATED CIRCUITS FROM' THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3. 11:3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-7,9,p10.P ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED;; B,Y ,THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. I'I III 16. WIRING SHALL RUN CONTINU tt1 AND 'THEN FROM DEVICE TOIiDE;VI OTHER BACK BOXES OF DIF, 17. ALL WIRING' SHALL: BE ' METE AND FREE OF SHORTS BET FINAL EQUIPMENT TRIM. OM FACP TO FIRST DEVICE ON A CIRCUIT F WITHOUT SPLICING IN PULL BOXES OR CIRCUITS. ,,,ERIFIED TO BE CONTINUOUS, FREE OF GROUND ,0ONDUCTORS AND. OTHER CIRCUITS PRIOR TO 18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.' I,i '111• t 19. THE ELECTRICAL 'CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE OUTSIDE, AND INSIDE OF TH; ;,FIR,E;. ALARM BACK BOXES AND JUNCTION :BOXES AFTER COMPLETION OF THEA ' INS',ALLATION: 20. DETECTORS MUST '.BE RATED F jOR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS: LOCATED. 21. ALL WIRING ' BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT. 22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G iMETALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE Q ITGOING AND RETURN 'CONDUCTORS, EXITING FROM AND RETURNING TO TilJEil COt' TROL UNIT, RESPECTIVELY, ARE ROUTED ' SEPARATELY. THE OltGOII,,G AND RETURN, (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BEl UN jj� THE SAME CABLE ASSEMBLY (I.E., tit MULTI -CONDUCTOR CABLE), '::E'NICLO URE, OR RACEWAY. 23. NFPA •72 2007 A.6.4.2.2.2 1:GOA OF 6.4.2.2.2 IS TO PROVIDE EN THE OUTGOING. AND RETURN CABLES. O HELP ENSURE, PROTECTION OF THE HE RECOMMENDED, MINIMUM DAMAGE IS 305 ; VM (1 FT) WHERE Y AND 1.22 M (4 FT) WHERE THE ADEQUATE SEPARATION BETW THIS SEPARATION IS REQUIRE CABLES FROM PHYSICAL DAIS; SEPARATION TO PREVENT. PH THE CABLE IS INSTALLED VE CABLE IS ;INSTALLED; QUANTITY 2 EX SYMBOL ! '.IDESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP ' ; FIRE ALARM EX?,CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA I�,FIRE ALARM `:REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP. BPS:i • 4; ,L? • 11;13EMOTE BOOSTER PAD -3 SIEMENS X'�`IPOWER SUPPLY ';.:INTERFACE MODULEHTRI-R' SIEMENS IWITH RELAY PROVIDED 66" A.F.F. TO TOP' 4S DEEP VERIFY IN FIELD '`DUAL INPUT II;INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCR (CONTROL POINT (:MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM Il' REMOTE CONVENTIONAL HZM ('ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B i; LINEAR BEAM II {;,SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -1 1 ' BASE 4S DEEP W/ 1G RING CEILING '' ('DUCT SMOKE 1;DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11: W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 4F FIRE ALARM 'SPEAKER STROBE „'(CEILING MOUNT) (,'FIRE ALARM ('iSPEAKER STROBE ,!';(WALL MOUNT) lii;FIRE ALARM ,('SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -,W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING; 80" A.F.F. TO BOTTOM CEILING FIRE ALARM '1`HSTROBE II�(CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING Ii [:IRE ALARM 1! STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. it FIRE ALARM i !'SPEAKER 'i (CEILING MOUNT) SET -CW' SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ' FIRE ALARM 'SPEAKER . (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM C) 'STROBE WP (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA 'JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD `JUNCTI❑N BOX F,B,❑, F,B,❑, N/A VERIFY IN ' FIELD ABOVE FINISHED FL❑❑R N/A N/A N/A N/A 'FURNISHED BY !-:OTHERS N/A N/A N/A N/A N%() !;N❑T APPLICABLE N/A N/A N/A N/A ;.UNLESS OTHERWISE NOTED N/A N/A N/A N/A •.WEATHERPR❑OF DEVICE N/A N/A N/A N/A RED' ''AS BUILT • ';,ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUVEILT REMO N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A I; • I. FIr,e n i .•a Copyright 2006 by Guardian Security, Systems, Inc.. All Rights R;eerw'e'dl;`f l 1, z ci) cc 'ccz LC). N 0 0 N W F - RELEASE/REVISIONS REV. BY: WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P ' S . 2S A V 2V I X UD UI M B DATA LINE -ADDRESSABLE LOOP TWISTED PAIR',WITH SHIELD #16 FPL/FPLR ': RED (JACKET) DOOR HOLDER POWER - 24VDC TWO . #14 FPL/FPLR 'RED (JACKET) DEVICE POWER - 24VDC TWO , #16 FPL/FPLR .' RED (JACKET) STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) . STROBE CIRCUIT - RETURN TWISTED PAIR, 'W/ SHIELD #12 FPL/FPLR ,RED (JACKET) ANNUNCIATOR TWISTED PAIR 'W/ SHIELD #16, FPL/FPLR .' RED (JACKET) SPEAKER CIRCUIT - FEED TWISTED PAIR . #14 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - RETURN TWISTED PAIR. #14 .FPL/FPLR ' RED (JACKET) REMOTE INDICATI❑N LIGHT TWO 2 #18 FPL/FPLR • RED (JACKET) LOW LEVEL AUDI❑ TWISTED PAIR W/',SHIELD #16 FPL/FPLR '' RED (JACKET)", UNDERGROUND DATA TWISTED PAIR RATED '. #18 ' FPL/FPLR .RED (JACKET) ,: UNDERGROUND INITIATION ',TWISTED PAIR RATED • #18 FPL/FPLR , RED ,(JACKET) DOOR HOLDER POWER TWO #16 FPL/FPLR • RED .(JACKET) BEAM DETECTOR POWER TWO • • #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART SHOP DRAWINGS NO. OF CONDUCTORS VOLTS • WIRE SIZE' TYPE :... • DIMENSIONS AREA ' TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL • CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON' THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" • '.12 SQUARE INCH 3/4" .21 SQUARE INCH 1" ' .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND 'ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.. SHIELDED WIRE T❑ BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED: AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSA, DEVICES ADDRESS. NUMBERS :ADJACENT TO DEV DEVICE 011-1-02 WOULD B 2. DETECTOR' AND AUDIBLE CIR 3. AUDIBLE/VISUAL CIRCUIT WIRI BRANCHING IS PERMISSIBLE, 4. INSTALLATION SHALL BE IN ELECTRIC CODE, NFPA 72, L 5. INSTALLATION ' MATERIALS (I. , STANDARD, BOXES, FIBER ORA ARE NOT SUPPLIED BY SIEMEI 6. DETECTORS SHALL NOT BE ,M AIR STREAM OF AIR SUPPLY.,:, ?'3r 7. WIRING SHALL BE PER PLAN;;; TYPE, QUANTITY AND COLOR(; AND UNIQUELY MARKED FOR;' 8. INSTALLING CONTRACTOR SH DRAWINGS FOR "AS BUILT" g, FOR ADDITIONAL INSTALLATIO SHEETS AND/OR INSTALLATIO 10. THE 120vac POWER ELECTRI MUST COMPLY WITH ARTICLE, SPECIFICALLY SECTION 1-5.211 SOURCES.. 120vac POWER SH:` DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND ST, OF 80" A.F.F. OR 6" BELOW; 12. ALL MANUAL PULL STATION' ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND NITIATING DEVICES UNTIL PREPROGRAMMED WITH V1BOL DENOTE DEVICE CIRCUIT/ADDRESS :GOND DEVICE ON ADDRESSABLE LOOP 1. LARITY SHALL BE OBSERVED. I'i'SUPERVISED. NO PARALLEL RICTiCONFORMANCE WITH THE NATIONAL ALI�:ODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 0 UIT, WIRE, FITTINGS, HANGERS, BLE, FITTINGS, AND ASSOCIATED EQUIPMENT) E'RBERUS DIVISION. 'UNT �U TLE ITH E TU 'D IN DIRECT TS. PER NFPA 72 2-3.5.1 RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, ,CONDUCTORS SHALL BE PERMANENTLY, E IDENTIFICATION. L. ,R TURN ONE SET OF ACCURATELY MARKED PO ES. INS,ItRUCTIONS, REFER TO CATALOG CUT INSTRUCTIONS. RK SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NEPA 70, N.E.C. AND NFPA 72, IIN REFERENCE TO DEDICATED BRANCH POWER 'N'OT BE APPLIED TO FIRE ALARM PANEL WITHOUT M TECHNICIAN. :EVICES SHALL BE MOUNTED AT A HEIGHT ?ED CEILING, WHICHEVER IS LESS. RA1 BE MOUNTED AT 48" A.F.F. TO THE r JIT$ WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE ;ROM 'DEDICATED CIRCUITS FROM' THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3. 11:3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-7,9,p10.P ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED;; B,Y ,THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. I'I III 16. WIRING SHALL RUN CONTINU tt1 AND 'THEN FROM DEVICE TOIiDE;VI OTHER BACK BOXES OF DIF, 17. ALL WIRING' SHALL: BE ' METE AND FREE OF SHORTS BET FINAL EQUIPMENT TRIM. OM FACP TO FIRST DEVICE ON A CIRCUIT F WITHOUT SPLICING IN PULL BOXES OR CIRCUITS. ,,,ERIFIED TO BE CONTINUOUS, FREE OF GROUND ,0ONDUCTORS AND. OTHER CIRCUITS PRIOR TO 18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.' I,i '111• t 19. THE ELECTRICAL 'CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE OUTSIDE, AND INSIDE OF TH; ;,FIR,E;. ALARM BACK BOXES AND JUNCTION :BOXES AFTER COMPLETION OF THEA ' INS',ALLATION: 20. DETECTORS MUST '.BE RATED F jOR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS: LOCATED. 21. ALL WIRING ' BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT. 22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G iMETALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE Q ITGOING AND RETURN 'CONDUCTORS, EXITING FROM AND RETURNING TO TilJEil COt' TROL UNIT, RESPECTIVELY, ARE ROUTED ' SEPARATELY. THE OltGOII,,G AND RETURN, (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BEl UN jj� THE SAME CABLE ASSEMBLY (I.E., tit MULTI -CONDUCTOR CABLE), '::E'NICLO URE, OR RACEWAY. 23. NFPA •72 2007 A.6.4.2.2.2 1:GOA OF 6.4.2.2.2 IS TO PROVIDE EN THE OUTGOING. AND RETURN CABLES. O HELP ENSURE, PROTECTION OF THE HE RECOMMENDED, MINIMUM DAMAGE IS 305 ; VM (1 FT) WHERE Y AND 1.22 M (4 FT) WHERE THE ADEQUATE SEPARATION BETW THIS SEPARATION IS REQUIRE CABLES FROM PHYSICAL DAIS; SEPARATION TO PREVENT. PH THE CABLE IS INSTALLED VE CABLE IS ;INSTALLED; QUANTITY 2 EX SYMBOL ! '.IDESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP ' ; FIRE ALARM EX?,CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA I�,FIRE ALARM `:REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP. BPS:i • 4; ,L? • 11;13EMOTE BOOSTER PAD -3 SIEMENS X'�`IPOWER SUPPLY ';.:INTERFACE MODULEHTRI-R' SIEMENS IWITH RELAY PROVIDED 66" A.F.F. TO TOP' 4S DEEP VERIFY IN FIELD '`DUAL INPUT II;INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCR (CONTROL POINT (:MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM Il' REMOTE CONVENTIONAL HZM ('ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD B i; LINEAR BEAM II {;,SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -1 1 ' BASE 4S DEEP W/ 1G RING CEILING '' ('DUCT SMOKE 1;DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11: W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING 4F FIRE ALARM 'SPEAKER STROBE „'(CEILING MOUNT) (,'FIRE ALARM ('iSPEAKER STROBE ,!';(WALL MOUNT) lii;FIRE ALARM ,('SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS SET -MC -,W SIEMENS SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING; 80" A.F.F. TO BOTTOM CEILING FIRE ALARM '1`HSTROBE II�(CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING Ii [:IRE ALARM 1! STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. it FIRE ALARM i !'SPEAKER 'i (CEILING MOUNT) SET -CW' SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING ' FIRE ALARM 'SPEAKER . (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM FIRE ALARM C) 'STROBE WP (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -S17 -WP SIEMENS MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA 'JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD `JUNCTI❑N BOX F,B,❑, F,B,❑, N/A VERIFY IN ' FIELD ABOVE FINISHED FL❑❑R N/A N/A N/A N/A 'FURNISHED BY !-:OTHERS N/A N/A N/A N/A N%() !;N❑T APPLICABLE N/A N/A N/A N/A ;.UNLESS OTHERWISE NOTED N/A N/A N/A N/A •.WEATHERPR❑OF DEVICE N/A N/A N/A N/A RED' ''AS BUILT • ';,ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUVEILT REMO N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A I; • I. FIr,e n i .•a Copyright 2006 by Guardian Security, Systems, Inc.. All Rights R;eerw'e'dl;`f l 1, z ci) cc 'ccz LC). N 0 0 N W F - RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE M 0 0 in o a«« / SCALE: 1 /8"=1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: NUMBER:54510 FA -0 1 I; CO 7, • NORTH Go DIVA WESTFIELD SOUTHCENTER MALL SC1,41110T: , ::11 ,i'.,• .:g •.f: • 11 • ; , 1', • 11 .1 . • , • • 11 ' 7I,AG NOT ,S: I • 1 1 I Z... ' 1 11.1, z 1 „, 11 1 FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. ' 1 kr, DO \OT INST ADDRESSABLE DEVICES ._,\TI LL NJT AT PREPROGRAMVED W DEVICES ADDRESS. T Copyright 2006 by Guardian Security Systems, Inc. All Rights CO Cl) u_T F— uJ U) U) ui U) tr) r--- RELEASE/REVISIONS REV. BY: . 4 DESCRIPTION SHOP DRAWINGS DATE co 0 ...., to ...... .1 —_107) 2 w 0 < Eut wi 1.—.J cc 0 c, < 0 LO 0 LIJ H >11 6ALE: 1/8"=l' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: ..JOB NUMBER:54510 j SHEET eperyedZ. FA -03 .1 1..044, • • 13 [I JE 3 P. I D J1P3 /\[ f: NA ERIE. SUN COAST MC..) -1-1(2)1\i C ILlR EEl •• 1131 ACI ml - 11 II VE: RTZ: (i) N \NI R E L. E:; :H;I. 'I' II II 1-•-• I: --- Cil K ' m IN WA 1-111 \ C SP LIN !..:;:EIR GIFTS NORTH r- / lvi AI 1 1. OFICE OFFICE CU LLJ L.) <1.• (I) LU Li NJ LIAMBA JUICE: ID 1:)(l11U ABFRCPOMBIE - - - - C A TEl IL riL[1 APIN El TE Asjvi SI p I I: SYSTEM CALCULATIONS ' GODIVA GODIVA ; • 1 , I SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations »FACP ADD ONS WESTFIELD SOUTHCENTER MALL .. PROJECT: GODIVA r., • Wire Resistance 1.0"1, • ' Panel: Date: May 13, 2008 - CURRENT TOTAL= 350 . Current Load: Standby S1 - Alarm: -: Current Load: Standby: Alarm: --------- ,! ,1; • ____ _ Device Type Alarm Current Alarm Total Wire Size 1 Device Type Qty Amps Total Amps Total 64 Device Type Qty Amps Total Amps Total Total Wire Resistance ( R ) 0.86 0 0 _ SET -MC @30CD .98 0 HFP-11 0.0022 0.0022 0.0023 . 2 SET -MC @75CD 175 Maid System Board 1 0.03 . 0.03 0 030 0.030 Total Device Load, Amps (I) AD2-P 2 0.0635 0.0635 0.064 0.128 Cct Load) 0.064 SET-HMC-C115CD 318 IHTR-R 2 0.009600 0.0096 0.021 0.042 Voltage Drop ( E)0.30 - SET-HMC-C@177CD 445 I 0 (E=• I * R) __._ ----- 0 SET -HMC g135CD , . 318 §E -0716d5666 1 _ ' 0.098 EOL Voltage ' 20.10 HTRI-D SET -HMC g185CD . 0.001600 ' 0 0.0035 • SET-MCb75CD 2 , , . 0 0.175 0.350 0- ;ICP -B6 0 005 • • • : 0 SEtIVIC 6110CD 98 0 0.233 , _ 0 SET-MC-CW@110CD '1 233 0 i SET-HMO-C@115CD . ' _ ----- 0.318 DEVICES= 2 , .___ 350 12 265 20.099491 350 . - SET-HMC7C@135CD - Notification 0.318 ••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06 -trfl•11, .4 -.........*1 I* .,.1},MAY.V....11* Circuit ...., ny...~.1.••••mws Twom.ret taw... IT.T+01 Detail M,I" V _ WESTFIELD SOUTHCENTER SETI-16,76161135 , 0.445 PROJECT - • , • ':, . 1 .;: Wire Resistance :i08.,I, ; • - ,.;,;- 0.0731 Amps 0.17 AmPO;; ,11____ ZR -MO @I5CD 3.6 0.064 Date: CIRCUIT: SPEAKER CIRCUIT , , Device Type 0.098 Alarm Total Wire Size Standby Current Load: 0 0731 Amps For 24 Hours = 1.754 Amp -hours ! i I I;: . .ZR-;Woco HCP: '' t_, . 1.8 - 3.6 1 0.0015 Total Wire Resistance ( R ) _ _ 2.92 ' 0 • - , ' 0 • 0,, F . i i - --- 7 - •- -"------ - ( WL *2 )* (R/ft) 0.03 Amps 0.38 Amps , Alarm Current Load: 0.17 Amps For 5 Minutes= 0.014 Amp -hours ' 0.00 0 , 0 0 , ._____ ,. . (Total Cct Load) 0 . , _ 0 Standb Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours 0 0 ; ., 25% Derating= 2.211 Amp -hours (E= I * R) II,I 0 _ 0 _ ,.I EOL Voltage ___ 20.39 0 _ , , 0 0 _ Alarmrent Load: 0.38 Amps For 5 Minutes= 0.032 Amp -hours 0 ' 0 r, _ 0 0 Total System Current Load: . , 2.211 Amp -hours I, 0 2 . TOTAL mA= 3.6 25% Derating= 0.940 Amp -hours 3.6 DEVICES= Battery Pair to be Used: 12VDC Amp -hours 7AH , Total System Current Load: 0.940 Amp -hours , Battery pair to be Used: 12VDC Amp -hours 7AH 0 , , ; ; . 11 P THE L 0 reF 1 01 0 r- • re; 15501' I)] [(11 '-1-5 .1 1 1 1 (-) ; ! 11(1 AC_F- 5401 '1.--- GODIVA WESTFIELD SOUTHCENTER MALL AP D,I 21 RISER DIAGRAM I ; BATTERY SIZING CALCULATION .. _ .._ . Notification Appliance 'Circuit Detail WESTFIELD SOUTHCENTER MALL .. PROJECT: GODIVA r., • Wire Resistance 1.0"1, • ' Panel: Date: May 13, 2008 - CURRENT TOTAL= 350 . CIRCUIT: QTY . S1 - -, L -: --------- ____ _ Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total SET -MC @15CD 64 0 . Total Wire Resistance ( R ) 0.86 0 0 _ SET -MC @30CD .98 0 1 ( WL* 2 )*(R/ft) . 2 SET -MC @75CD 175 • 350 ; Total Device Load, Amps (I) 0.35 0 6 . SET -MC @110CD 233 0(Total Cct Load) SET-HMC-C115CD 318 : 0 Voltage Drop ( E)0.30 - SET-HMC-C@177CD 445 I 0 (E=• I * R) __._ ----- 0 SET -HMC g135CD , . 318 _ 0 _ ' EOL Voltage ' 20.10 SET -HMC g185CD . , 445 ' 0 .I • : (20.4 - E) , , , . 0 Z-MC@15CD . . ' 64 0- _ _ • • • : 0 Z-MC@30CID 98 0 , _ 0 SET-MC-CW@110CD '1 233 0 . ' _ ----- DEVICES= 2 , TOTAL mA= .___ 350 12 265 20.099491 350 . - - Notification .......,......._....,.. T.INIW •`.• .Appliance ••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06 -trfl•11, .4 -.........*1 I* .,.1},MAY.V....11* Circuit ...., ny...~.1.••••mws Twom.ret taw... IT.T+01 Detail M,I" V _ WESTFIELD SOUTHCENTER ___ MALL ----- PROJECT .GODIVA;:;-,...:.,i.,..,..,..... ....-- -,...:- • • : - ... ...... ' - •, - - • , • ':, . 1 .;: Wire Resistance :i08.,I, ; • - ,.;,;- . .... . ... . , ..:Panel • May 13, 2008 ; , .• CURRENT TOTAL 3.6 Date: CIRCUIT: SPEAKER CIRCUIT , Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total - _ QTY 2 70.7V 1/8 , . 1.8 - 3.6 1 Total Wire Resistance ( R ) _ _ 2.92 ' 0 • - , ' 0 • 0,, . ( WL *2 )* (R/ft) 0 , , ' •;. . .0 Total Device Load, Amps (I) 0.00 0 0 0 , ._____ ,. . (Total Cct Load) 0 . , _ 0 _ Voltage ( E) E ) 0.01 0 0 ; ., (E= I * R) 0 _ 0 _ ,.I EOL Voltage ___ 20.39 0 _ , , 0 0 _ L:icl iI,I:I, (20.4 - E) 0 ' 0 r, _ 0 0 ,, --,,- --,- • . , - - 0 2 . TOTAL mA= 3.6 14 .,.;, 565 20.389504561. 3.6 DEVICES= VOLTAGE DROP CALCULATION z 0 (/) LLJ CE LJJ U) UJ _.J LI_J z DESCRIPTION z 0 0 01 LLJ0 F- 0 CO Lfl <<<C1 J 03 CO PrEs -Jo, Z W 0 < CC wo > zz 2 w w 0 5 o < - W 0 (f) tcr3 LoD (S.*C'ALE: 1/8''=1' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/05/08 BACKROUND PLAN PROVIDED BY: ,Copyright 2006 by Guardian Security.,.SYstems, Inc. All Rights Reserved R;' 1..0B NUMBER:54510 SHEET '\ FA -04