FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Godiva
555 Southcenter Mall
Permit No.: 08-S-157
Date: May 2, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'h inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a '
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
All references are NFPA 13, 2007 Edition.
cagy
Ili
C3
U
0-7
L
O
L
O
1 O' -O"
0-7
A!
Lin
5 -r. t
1_
p
L)
0
U
J\CEJ
0
rJ
1' `•
F 0-7 L 1I
C>
41
n
J L.
—
1'l
10
82
CEI -1
Lr.)
82
1-43
4"
@ 14'-6" AFF
Ir,
SA
SA
'0
Hod
B2A
15'-5;
11 .rm
1/\
TUKWILA FIRE DEPARTMEN1
Please call: 575.4402
and give this job
and exact address for shut.,
-Jown or rostorati approval.
No.
I � i, I r Nfl 0-10
32 32
'1
11
BlA,
}
(J
J
A
1
I/1
f
r 11
111,i
11
/
1
I1
11
11
i
11
/
/
n
r� r
27'-O"
v
J i
r
i
(GODIVA ChOCOLAT(R
(scare: /2" = 1 '-o")
SPRINKLER HEAD LEGEND :
SYMBOL
S/N
ORIFICE
NPT
K•FACT.
HEAD
FINISH
ir11f
!
11
1
11
11
1
CONSTRUCTION NOTES: "GENERAL NOTES: )
I) PIPE:
THREADED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) FITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
FINISH
THREADED: STAR D.I.
3) GROOVED COUPLINGS:
STAR RIGID C-4 UNLESS MARKED WITH AN "P',
WHICH ARE TO 13E STAR FLEXIBLE C-3 LW -
ORANGE PAINT FINISH
4) HANGER MATERIAL:
ALL HANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
LIST OF ELEVATIONS:;
EXISTING SPRINKLER PIPE 4. @ 14'-6" '
ACT CEILING HEIGHT = AS NOTED
GWS CEILING HEIGHT = 121-0" (U.N.O.)
SYMBOL LEGEND:)
= NEW RECESSED PENDANT ON DROP
= NEW CONCEALED PENDANT ON DROP
$- --S = EXISTING SPRINKLER PIPE TO REMAIN
`S --i = NEW SPRINKLER PIPING
41.7
b
CI Pr? e
!'.<!"'i±? Fire
(city!
:a(opted
for the
per.
d . avrings atter
require a
for I ecuant approval.
sinal acc�pt�rlce is sub sot to field test and inspection by
Tht Tukwila Fire Prevention Bureau.
Date:
PLATE
FINISH
TC
Weld temps Dust be
ins ed before pipe is
hung.n t paint piping
prior to hydrostatic test
approval.
TEMP.
QUAN.
Reliable Model FI FR Recessed Pendant
0
1/2'
1/2'
5.6
Chrome
Chrome
155°
3
Reliable Model G4A Concealed Pendant
1/2'
1/2'
5.6
Brass
White
165°
7
APPROVALS BY:
I TOTAL SPRINKLERS
THIS SHEET
10
1
I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP(.(
2)
3)
4)
5)
6)
7)
8)
ORDINARY HAZARD GROUP I SPRINKLER SPACING: 130 ft2 MAX.
COSCO'S POINT OF CONNECTION 15 AT EXISTING SYSTEM AS SHOWN.
ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY
OTHER.
ALL WIRING OF SYSTEM DEVICES IS BY OTHER.
OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTAI 1 FD THE SYSTEMS) 1S BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
ANY RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION,
PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO
BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE
EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION.
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3' METAL DECK
3/8" ANCHOR w/20# TORQUE:
TENSION=395#, SHEAR=750# *
1/2" ANCHOR w/40# TORQUE:
TENSION=440#,SHEAR=750#*
'SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR TIM THREADS
1/4' MIN
ROD COUPLING
THREADED ROD
PIPE
SIZE
ROD
DIA.
BOLT
LGTH
IMBED
DEPTH
I"
3/8"
3 3/4"
2 1/4"
1 1/4"
3/8"
3 3/4"
2 1/4"
1 I/2"
3/8"
3 3/4"
2 1/4"
2"
3/8"
3 3/4"
2 1/4"
2 1/2"
3/8'
3 3/4"
2 1/4"
3"
3/8"
3 3/4"
2 1/4'
4"
3/8"
3 3/4"
2 1/4"
6"
1/2"
3 3/4'
2 1/4"
8"
1/2"
3 3/4"
2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007 I COSCO STANDARD HANGER 1 13 MDL
N
"0000"
"000 .
"00004"
•0000
00•
I
cosco
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
10910 117TH Place N.E.
Kirkland, Washington 98033
call (425) 827-9654 • fax (425) 827-7474
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
www.coscofire.com
License No:
COSCOFP110NM
PROJECT
Godiva Chocolatier
309 Southcenter Mall, Level 1, Suite: 1020
Tukwila, Wa. 98188
CONTRACT vim
The Stone Company General Contractors, Inc.
2019 Galisteo Street, Building N-10, Suite: C
Santa Fe, Nm. 87505 Eric Lyons (505) 955-9960
DRAWING TUE
Godiva Chocolatier: Sprinkler Piping Plan
DATE : May 2008
SCALE : As Noted
DRAWN BY : Justin Johnson
SKS - 7930
SHEET 1413p
FILE
FIRS; ALA
TUKWILA,
IATA
M SYSTEM
ASHINGTON
r•
NERAL NOTES
SHEET \U
\/3E: SHEET TITLE
•
V
C
0
0
• r.,
X
0
N
'0
-o
"a
CL
0
1.4N
CO
N
•Ln
ii
• a
ii
FA -0 1
SYSTEM
I\FO.MATIO\
FA -02
TYPICAL
DETAILS - I\C:AND MOU
\TI \G
FA -03
FRE ALAN
SYSTE
v
FLOO: PLA\
FA -04
SYSTEV
CALCULATIO\S (CEEAL),
DISE
SITE PLA\
1
0
0
*cc
Vvithout Comments
As Noted In Red
Per The Attached Letter
!nese plans hays '?ren rev'itnied by The Tule: Bila Fire
Prevention Burst.; `:.1 C(:!'!ti1:;i ;.. ' l'.'iirt current city
standards. t,..• cuors and
omissions \r..h:l.:; • (1- tit a acpted
standar. LI; .. . :i. •.. f -: > ci ti::ii;GJ for the
adequacy 01 t"..ii•,, ii, , ''!tji tnf.. UcSijyn r.
Additions, ,}.! . t., th se cri`!iIgs atter
1 tills date will ',fold end will require
a
resubmittal of revts d dr e•..4 11 igs for subsequent approval.
jj Final acceptance is Gut.ject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date:
By:
II°UKWIL.A FIRE DEPARTMENT
Please call: 575.4407,
and give this job
No.o()) F-(°\
•
.10
and exact address for shut.
Down or restoration approval:
NOTTCE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and,
termination of the testing.
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHART
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE' WRAPPED WITH TAPE AND TAPED: AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSA,
DEVICES ADDRESS.
NUMBERS: ADJACENT TO DEV
DEVICE 011-1-02 WOULD B
2. DETECTOR! AND AUDIBLE CIR
3. AUDIBLE/VISUAL CIRCUIT WIRI
BRANCHING IS PERMISSIBL,,
4. INSTALLATION SHALL BE IN
ELECTRIC CODE, NFPA 72, L
5. INSTALLATION MATERIALS (I,:E
STANDARD BOXES, FIBER OK
ARE NOT SUPPLIED BY SIEMEN
6. DETECTORS SHALL NOT BE
AIR STREAM OF AIR SUPPLY.,:,
?'3r
7. WIRING SHALL BE PER PLAN;;;
TYPE, QUANTITY AND COLOR(;
AND UNIQUELY MARKED FOR'
8. INSTALLING CONTRACTOR SH.
DRAWINGS FOR "AS BUILT"
g, FOR ADDITIONAL INSTALLATIO
SHEETS AND/OR INSTALLATIQ
10. THE 120vac POWER ELECTRI
MUST COMPLY WITH ARTICLE,
SPECIFICALLY SECTION 1-5.211
SOURCES.. 120vac POWER SH:`
DIRECT SUPERVISION OF FIR
11. ALL HORN/STROBE AND ST
OF 80" A.F.F. OR 6" BELOW;
12. ALL MANUAL PULL STATION
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND
14. ALL 120VAC CIRCUITS ARE FOM 'DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3: :1 i3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN -Up 'OFT, ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED; B,Y ,THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7. 'I 'I III
16. WIRING SHALL RUN CONTINU tt1
AND 'THEN FROM DEVICE TOIiDEVI
OTHER BACK: BOXES OF DIF
NITIATING DEVICES UNTIL PREPROGRAMMED WITH
V1BOL DENOTE DEVICE CIRCUIT/ADDRESS
:GOND DEVICE ON ADDRESSABLE LOOP 1.
LARITY SHALL BE OBSERVED.
I'i'SUPERVISED. NO PARALLEL
RICTiCONFORMANCE WITH THE NATIONAL
AL :ODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
0 UIT, WIRE, FITTINGS, HANGERS,
BLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
E'RBERUS DIVISION.
UNT
U TLE
1 TH
E
TU
"D IN DIRECT
ITS. PER NFPA 72 2-3.5.1
RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
CONDUCTORS SHALL BE PERMANENTLY,
E IDENTIFICATION.
L. ,RTURN ONE SET OF ACCURATELY MARKED
PO ES.
INSTRUCTIONS, REFER TO CATALOG CUT
INSTRUCTIONS.
RK SUPPLYING FIRE ALARM SYSTEM PANELS
ND 760 OF NEPA 70, N.E.C. AND NFPA 72,
IIN REFERENCE TO DEDICATED BRANCH POWER
NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
M TECHNICIAN.
:EVICES SHALL BE MOUNTED AT A HEIGHT
?ED CEILING, WHICHEVER IS LESS.
RA1 BE MOUNTED AT 48" A.F.F. TO THE
r
JIT$ WILL BE ON THE RECORD DRAWINGS SET.
17. ALL WIRING SHALL BE METE
AND FREE OF SHORTS BET
FINAL EQUIPMENT TRIM.
OM FACP TO FIRST DEVICE ON A CIRCUIT
E WITHOUT SPLICING IN PULL BOXES OR
CIRCUITS.
,,,ERIFIED TO BE CONTINUOU.S, FREE OF GROUND
::CONDUCTORS AND: OTHER CIRCUITS PRIOR TO
18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.'
I,i '111•
t
19. THE ELECTRICAL CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE
OUTSIDE , AND INSIDE OF1 TH;E (,FIRE,. ALARM BACK BOXES AND JUNCTION :BOXES
AFTER COMPLETION OF THE( I' INS',ALLATION:
20. DETECTORS MUST .BE RATEDFjCR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS: LOCATED.
21. ALL WIRING BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT.
22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLE:S OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., iMETALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE ,Q ITGQING AND RETURN 'CONDUCTORS, EXITING
FROM AND RETURNING TO THE'.COt' TROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OlTGOII,G AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE „t UN jj� THE SAME CABLE ASSEMBLY (I.E.,
tl it
MULTI -CONDUCTOR CABLE), '::E'NlCLO URE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 6,1:GOA OF 6.4.2.2.2 IS TO PROVIDE
EN THE OUTGOING AND RETURN CABLES.
TO HELP ENSURE, PROTECTION .OF THE
HE RECOMMENDED MINIMUM
DAMAGE IS 305 ; VM (1 FT) WHERE
Y AND 1.22 M (4 FT) WHERE THE
ADEQUATE SEPARATION BETW
THIS SEPARATION IS REQUIRE;
CABLES FROM PHYSICAL DAIS;
SEPARATION T0 PREVENT. PH
THE CABLE IS INSTALLED VE
CABLE IS ;INSTALLED:
QUANTITY
2
EX
SYMBOL ! '.IDESCRIPTION
SYMBOLS LEGEND
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
' •; FIRE ALARM
EX?,CONTROL PANEL
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
FARA
�I,FIRE ALARM
:;`:REMOTE ANNUNCIATOR
SDD-C
SIEMENS
PROVIDED
66" A.F.F.
TO TOP.
BPSll
•
,L?
•
11;13EMOTE BOOSTER PAD -3 ' SIEMENS
X,HIIPOWER SUPPLY
TERFACE MODULEHTRI-R' SIEMENS
+;WITH RELAY
PROVIDED
66" A.F.F.
TO TOP'
4S DEEP
VERIFY
IN FIELD
'`DUAL INPUT
I:INTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCRI
iCONTROL POINT
'I::MODULE
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
Il' REMOTE CONVENTIONAL HZM
I'ZONE MODULE
SIEMENS
4S DEEP
VERIFY •
IN FIELD
B
1i; LINEAR BEAM
II (;,SMOKE DETECTOR
PBA -1191 SIEMENS
PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -1 1 BASE
4S DEEP
IN/ 1G RING
CEILING
,!:(:DUCT SMOKE
:(;DETECTOR
•,;
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING
VERIFY
IN FIELD
HEAT DETECTOR
• (ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
4F FIRE ALARM
SPEAKER STROBE
l„'(CEILING MOUNT)
(.'FIRE ALARM
1('iSPEAKER STROBE
,!;(WALL MOUNT)
IiitFIRE ALARM
••'('SPEAKER STROBE
(CEILING MOUNT)
SET -MC -CW SIEMENS
SET -MC -W SIEMENS
SET -HMC -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING; •
80" A.F.F.
TO BOTTOM
CEILING
IRE ALARM
'1`HSTROBE
4(CEILING MOUNT)
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
lliIFIRE ALARM
II STROBE
:(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
it FIRE ALARM
i! SPEAKER
'i (CEILING MOUNT)
SET -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
' FIRE ALARM
SPEAKER
(WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
' FIRE ALARM
C) STROBE
WP (WEATHERPROOF)
MR
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX
1/2" PIPE
VERIFY
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA 'JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
`JUNCTI❑N BOX
F.B.D.
F.B.O.
N/A
VERIFY
IN FIELD
ABOVE FINISHED
:FLOOR
N/A
N/A
N/A
N/A
FURNISHED BY
!-:OTHERS
N/A
N/A
N/A
N/A
N%()
i:;N❑T
APPLICABLE
N/A
N/A
N/A
N/A
;.UNLTEESSD OTHERWISE
N❑
N/A
N/A
N/A
N/A
WEATHERPROOF
DEVICE
N/A
N/A
N/A
N/A
RED'
''AS BUILT •
';,ADD OR CHANGE
N/A
N/A
N/A
N/A
GREEN • AS BUVEILT
REM❑
N/A
N/A
N/A
N/A
BLUE AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
I;
•
Tu I. FIr,e
n i .•a
Copyright 2006 by Guardian Security, Systems, Inc.. All Rights.' R;eerw'e'dl;`f
l 1,
z
ci)
cc
'ccz
o'.
OD
N
X
LL
RELEASE/REVISIONS
REV. BY:
WIRE DESIGNATION
SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR C❑DE
D
H
P '
S .
2S
A
V
2V
I
X
UD
UI
M
B
DATA LINE -ADDRESSABLE LOOP TWISTED PAIR',WITH SHIELD 416 FPL/FPLR ' RED (JACKET)
DOOR HOLDER POWER - 24VDC TWO . 414 FPL/FPLR 'RED (JACKET)
DEVICE POWER - 24VDC TWO , 416 FPL/FPLR .' RED (JACKET)
STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) .
STROBE CIRCUIT - RETURN TWISTED PAIR 'W/ SHIELD 412 FPL/FPLR ,RED (JACKET)
ANNUNCIATOR TWISTED PAIR 'W/ SHIELD #16, FPL/FPLR .' RED (JACKET)
SPEAKER CIRCUIT - FEED TWISTED PAIR . 414 FPL/FPLR RED (JACKET)
SPEAKER CIRCUIT - RETURN TWISTED PAIR. 414 .FPL/FPLR ' RED (JACKET)
REMOTE INDICATI❑N LIGHT TWO 2 418 FPL/FPLR • RED (JACKET)
LOW LEVEL AUDI❑ TWISTED PAIRW/'SHIELD 416 FPL/FPLR ' RED (JACKET)
UNDERGROUND DATA TWISTED PAIR RATED '. 418 ' FPL/FPLR .RED (JACKET) ,
UNDERGROUND INITIATION ',TWISTED PAIR RATED #18 FPL/FPLR , RED .(JACKET)
DOOR HOLDER POWER TWO 416 FPL/FPLR • RED .(JACKET)
BEAM DETECTOR POWER TWO • • 414 FPL/FPLR RED (JACKET)
CONDUIT FILL CHART
SHOP DRAWINGS
NO. OF CONDUCTORS VOLTS • WIRE SIZE' TYPE :... • • DIMENSIONS AREA '
TWO 600V #12 AWG THHN/THWN .244 0.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191
CONDUIT FILL •
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON' THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" • .12 SQUARE INCH
3/4" .21 SQUARE INCH
1" ' .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4..
SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE' WRAPPED WITH TAPE AND TAPED: AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSA,
DEVICES ADDRESS.
NUMBERS: ADJACENT TO DEV
DEVICE 011-1-02 WOULD B
2. DETECTOR! AND AUDIBLE CIR
3. AUDIBLE/VISUAL CIRCUIT WIRI
BRANCHING IS PERMISSIBL,,
4. INSTALLATION SHALL BE IN
ELECTRIC CODE, NFPA 72, L
5. INSTALLATION MATERIALS (I,:E
STANDARD BOXES, FIBER OK
ARE NOT SUPPLIED BY SIEMEN
6. DETECTORS SHALL NOT BE
AIR STREAM OF AIR SUPPLY.,:,
?'3r
7. WIRING SHALL BE PER PLAN;;;
TYPE, QUANTITY AND COLOR(;
AND UNIQUELY MARKED FOR'
8. INSTALLING CONTRACTOR SH.
DRAWINGS FOR "AS BUILT"
g, FOR ADDITIONAL INSTALLATIO
SHEETS AND/OR INSTALLATIQ
10. THE 120vac POWER ELECTRI
MUST COMPLY WITH ARTICLE,
SPECIFICALLY SECTION 1-5.211
SOURCES.. 120vac POWER SH:`
DIRECT SUPERVISION OF FIR
11. ALL HORN/STROBE AND ST
OF 80" A.F.F. OR 6" BELOW;
12. ALL MANUAL PULL STATION
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND
14. ALL 120VAC CIRCUITS ARE FOM 'DEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3: :1 i3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN -Up 'OFT, ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED; B,Y ,THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7. 'I 'I III
16. WIRING SHALL RUN CONTINU tt1
AND 'THEN FROM DEVICE TOIiDEVI
OTHER BACK: BOXES OF DIF
NITIATING DEVICES UNTIL PREPROGRAMMED WITH
V1BOL DENOTE DEVICE CIRCUIT/ADDRESS
:GOND DEVICE ON ADDRESSABLE LOOP 1.
LARITY SHALL BE OBSERVED.
I'i'SUPERVISED. NO PARALLEL
RICTiCONFORMANCE WITH THE NATIONAL
AL :ODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
0 UIT, WIRE, FITTINGS, HANGERS,
BLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
E'RBERUS DIVISION.
UNT
U TLE
1 TH
E
TU
"D IN DIRECT
ITS. PER NFPA 72 2-3.5.1
RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
CONDUCTORS SHALL BE PERMANENTLY,
E IDENTIFICATION.
L. ,RTURN ONE SET OF ACCURATELY MARKED
PO ES.
INSTRUCTIONS, REFER TO CATALOG CUT
INSTRUCTIONS.
RK SUPPLYING FIRE ALARM SYSTEM PANELS
ND 760 OF NEPA 70, N.E.C. AND NFPA 72,
IIN REFERENCE TO DEDICATED BRANCH POWER
NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT
M TECHNICIAN.
:EVICES SHALL BE MOUNTED AT A HEIGHT
?ED CEILING, WHICHEVER IS LESS.
RA1 BE MOUNTED AT 48" A.F.F. TO THE
r
JIT$ WILL BE ON THE RECORD DRAWINGS SET.
17. ALL WIRING SHALL BE METE
AND FREE OF SHORTS BET
FINAL EQUIPMENT TRIM.
OM FACP TO FIRST DEVICE ON A CIRCUIT
E WITHOUT SPLICING IN PULL BOXES OR
CIRCUITS.
,,,ERIFIED TO BE CONTINUOU.S, FREE OF GROUND
::CONDUCTORS AND: OTHER CIRCUITS PRIOR TO
18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.'
I,i '111•
t
19. THE ELECTRICAL CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE
OUTSIDE , AND INSIDE OF1 TH;E (,FIRE,. ALARM BACK BOXES AND JUNCTION :BOXES
AFTER COMPLETION OF THE( I' INS',ALLATION:
20. DETECTORS MUST .BE RATEDFjCR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS: LOCATED.
21. ALL WIRING BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT.
22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLE:S OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G., iMETALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE ,Q ITGQING AND RETURN 'CONDUCTORS, EXITING
FROM AND RETURNING TO THE'.COt' TROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE OlTGOII,G AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BE „t UN jj� THE SAME CABLE ASSEMBLY (I.E.,
tl it
MULTI -CONDUCTOR CABLE), '::E'NlCLO URE, OR RACEWAY.
23.
NFPA 72 2007 A.6.4.2.2.2 6,1:GOA OF 6.4.2.2.2 IS TO PROVIDE
EN THE OUTGOING AND RETURN CABLES.
TO HELP ENSURE, PROTECTION .OF THE
HE RECOMMENDED MINIMUM
DAMAGE IS 305 ; VM (1 FT) WHERE
Y AND 1.22 M (4 FT) WHERE THE
ADEQUATE SEPARATION BETW
THIS SEPARATION IS REQUIRE;
CABLES FROM PHYSICAL DAIS;
SEPARATION T0 PREVENT. PH
THE CABLE IS INSTALLED VE
CABLE IS ;INSTALLED:
QUANTITY
2
EX
SYMBOL ! '.IDESCRIPTION
SYMBOLS LEGEND
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
' •; FIRE ALARM
EX?,CONTROL PANEL
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
FARA
�I,FIRE ALARM
:;`:REMOTE ANNUNCIATOR
SDD-C
SIEMENS
PROVIDED
66" A.F.F.
TO TOP.
BPSll
•
,L?
•
11;13EMOTE BOOSTER PAD -3 ' SIEMENS
X,HIIPOWER SUPPLY
TERFACE MODULEHTRI-R' SIEMENS
+;WITH RELAY
PROVIDED
66" A.F.F.
TO TOP'
4S DEEP
VERIFY
IN FIELD
'`DUAL INPUT
I:INTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCRI
iCONTROL POINT
'I::MODULE
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
Il' REMOTE CONVENTIONAL HZM
I'ZONE MODULE
SIEMENS
4S DEEP
VERIFY •
IN FIELD
B
1i; LINEAR BEAM
II (;,SMOKE DETECTOR
PBA -1191 SIEMENS
PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -1 1 BASE
4S DEEP
IN/ 1G RING
CEILING
,!:(:DUCT SMOKE
:(;DETECTOR
•,;
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING
VERIFY
IN FIELD
HEAT DETECTOR
• (ADDRESSABLE)
HFPT-11 W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
4F FIRE ALARM
SPEAKER STROBE
l„'(CEILING MOUNT)
(.'FIRE ALARM
1('iSPEAKER STROBE
,!;(WALL MOUNT)
IiitFIRE ALARM
••'('SPEAKER STROBE
(CEILING MOUNT)
SET -MC -CW SIEMENS
SET -MC -W SIEMENS
SET -HMC -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING; •
80" A.F.F.
TO BOTTOM
CEILING
IRE ALARM
'1`HSTROBE
4(CEILING MOUNT)
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
lliIFIRE ALARM
II STROBE
:(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
it FIRE ALARM
i! SPEAKER
'i (CEILING MOUNT)
SET -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
' FIRE ALARM
SPEAKER
(WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
' FIRE ALARM
C) STROBE
WP (WEATHERPROOF)
MR
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX
1/2" PIPE
VERIFY
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA 'JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
`JUNCTI❑N BOX
F.B.D.
F.B.O.
N/A
VERIFY
IN FIELD
ABOVE FINISHED
:FLOOR
N/A
N/A
N/A
N/A
FURNISHED BY
!-:OTHERS
N/A
N/A
N/A
N/A
N%()
i:;N❑T
APPLICABLE
N/A
N/A
N/A
N/A
;.UNLTEESSD OTHERWISE
N❑
N/A
N/A
N/A
N/A
WEATHERPROOF
DEVICE
N/A
N/A
N/A
N/A
RED'
''AS BUILT •
';,ADD OR CHANGE
N/A
N/A
N/A
N/A
GREEN • AS BUVEILT
REM❑
N/A
N/A
N/A
N/A
BLUE AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
I;
•
Tu I. FIr,e
n i .•a
Copyright 2006 by Guardian Security, Systems, Inc.. All Rights.' R;eerw'e'dl;`f
l 1,
z
ci)
cc
'ccz
o'.
OD
N
X
LL
RELEASE/REVISIONS
REV. BY:
z
a
DESCRIPTION
SHOP DRAWINGS
DATE
M
0
0
11)
o
a««
W
}
N
SCALE: 1 /8"=1
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/05/08
BACKROUND PLAN PROVIDED BY:
NUMBER:54510
FA -01
I;
CO
7,
•
NORTH
Go DIVA WESTFIELD SOUTHCENTER MALL
SC1,41110T:
, ::11 ,i'.,•
.:g
•.f:
• 11
• ; ,
1', • 11
.1 . • ,
•
• 11
'
7I,AG NOT
,S:
I
• 1
1 I
Z...
' 1
11.1,
z
1 „,
11
1
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS.(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
LOCATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR.
WIRED BY ELECTRICAL
CONTRACTOR.
SIEMENS HTRI—D ADDRESSABLE
INPUT WITH HOOD VENILLATOR
FIRE SUPPRESION SYSTEM. FIELD
LOCATE WITHIN 3 FEET OF
CONTRL PANEL.
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER. AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
' 1
kr,
DO \OT INST
ADDRESSABLE
DEVICES ._,\TI
LL
NJT
AT
PREPROGRAMVED W
DEVICES ADDRESS.
T
Copyright 2006 by Guardian Security Systems, Inc. All Rights
CO
Cl)
u_T
F—
uJ
U)
U)
ui
U)
tr)
r---
RELEASE/REVISIONS
REV. BY:
.
4
DESCRIPTION
SHOP DRAWINGS
DATE
co
0
....,
to
......
.1
—_107)
2
w 0
< Eut
wi
1.—.J cc 0 c,
<
0
LO
0
LIJ
H
>11
6ALE: 1/8"=l'
DRAWN BY:
LANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/05/08
BACKROUND PLAN PROVIDED BY:
..JOB NUMBER:54510 j
SHEET
eperyedZ. FA -03 .1
1..044, • •
13 [I
JE
3 P. I D
J1P3
/\[ f: NA ERIE.
SUN COAST
MC..) -1-1(2)1\i
C ILlR EEl
••
1131 ACI
ml
-
11
II
VE: RTZ: (i) N \NI R E L. E:; :H;I.
'I'
II
II
1-•-• I: --- Cil K '
m IN WA 1-111 \ C
SP LIN !..:;:EIR GIFTS
NORTH
r-
/
lvi AI 1
1. OFICE OFFICE
CU
LLJ
L.)
<1.•
(I)
LU
Li
NJ
LIAMBA
JUICE:
ID
1:)(l11U
ABFRCPOMBIE
- - - -
C A TEl IL
riL[1
APIN El
TE Asjvi SI
p
I I:
SYSTEM CALCULATIONS
' GODIVA
GODIVA ; • 1
,
I SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations »FACP
ADD ONS
WESTFIELD SOUTHCENTER MALL ..
PROJECT:
GODIVA
r.,
•
Wire Resistance 1.0"1, • '
Panel:
Date:
May 13, 2008 -
CURRENT TOTAL=
350 .
Current Load:
Standby
S1
-
Alarm:
-:
Current Load:
Standby:
Alarm:
---------
,!
,1; •
____ _
Device Type
Alarm Current
Alarm Total
Wire Size
1
Device Type
Qty
Amps
Total
Amps
Total
64
Device Type
Qty
Amps
Total
Amps
Total
Total Wire Resistance ( R )
0.86
0
0
_
SET -MC @30CD
.98
0
HFP-11
0.0022
0.0022
0.0023
. 2
SET -MC @75CD
175
Maid System Board
1
0.03
. 0.03
0 030
0.030
Total Device Load, Amps (I)
AD2-P
2
0.0635
0.0635
0.064
0.128
Cct Load)
0.064
SET-HMC-C115CD
318
IHTR-R
2
0.009600
0.0096
0.021
0.042
Voltage Drop ( E)0.30
-
SET-HMC-C@177CD
445
I 0
(E=• I * R)
__._ -----
0
SET -HMC g135CD
, . 318
§E -0716d5666 1
_
'
0.098
EOL Voltage '
20.10
HTRI-D
SET -HMC g185CD .
0.001600
' 0
0.0035
•
SET-MCb75CD
2
, , .
0
0.175
0.350
0-
;ICP -B6
0 005
•
•
• :
0
SEtIVIC 6110CD
98
0
0.233
,
_
0
SET-MC-CW@110CD
'1 233
0
i
SET-HMO-C@115CD
. '
_ -----
0.318
DEVICES=
2 ,
.___
350
12
265
20.099491 350
. -
SET-HMC7C@135CD
-
Notification
0.318
••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06
-trfl•11, .4 -.........*1 I* .,.1},MAY.V....11*
Circuit
...., ny...~.1.••••mws Twom.ret taw... IT.T+01
Detail
M,I" V
_
WESTFIELD SOUTHCENTER
SETI-16,76161135
,
0.445
PROJECT
- • , • ':, . 1 .;:
Wire Resistance :i08.,I, ; • - ,.;,;-
0.0731
Amps
0.17
AmPO;;
,11____
ZR -MO @I5CD
3.6
0.064
Date:
CIRCUIT:
SPEAKER CIRCUIT
,
,
Device Type
0.098
Alarm Total
Wire Size
Standby Current Load:
0 0731
Amps
For 24 Hours =
1.754
Amp -hours !
i I I;: .
.ZR-;Woco
HCP: ''
t_,
. 1.8
- 3.6
1
0.0015
Total Wire Resistance ( R ) _ _
2.92
' 0 •
-
, ' 0
• 0,,
F . i i
- ---
7 - •-
-"------ -
( WL *2 )* (R/ft)
0.03
Amps
0.38
Amps ,
Alarm Current Load:
0.17
Amps
For 5 Minutes=
0.014
Amp -hours
'
0.00
0
,
0
0
,
._____
,. .
(Total Cct Load)
0
. ,
_
0
Standb
Current Load:
0.03
Amps
For 24 Hours =
0.720
Amp -hours
0
0
; .,
25% Derating=
2.211
Amp -hours
(E= I * R)
II,I
0
_
0
_
,.I
EOL Voltage
___
20.39
0
_
, , 0
0
_
Alarmrent Load:
0.38
Amps
For 5 Minutes=
0.032
Amp -hours
0
' 0
r,
_
0
0
Total System
Current Load:
. ,
2.211
Amp -hours I,
0
2
. TOTAL mA=
3.6
25% Derating=
0.940
Amp -hours
3.6
DEVICES=
Battery Pair to be Used:
12VDC
Amp -hours
7AH
,
Total System Current Load:
0.940
Amp -hours
,
Battery pair to be Used:
12VDC
Amp -hours
7AH
0 ,
, ;
;
. 11
P
THE L
0
reF
1 01 0
r-
•
re;
15501'
I)]
[(11
'-1-5 .1
1 1 1 (-)
; !
11(1 AC_F-
5401 '1.---
GODIVA WESTFIELD SOUTHCENTER MALL
AP
D,I
21
RISER DIAGRAM
I
;
BATTERY SIZING CALCULATION
..
_ .._
. Notification Appliance 'Circuit Detail
WESTFIELD SOUTHCENTER MALL ..
PROJECT:
GODIVA
r.,
•
Wire Resistance 1.0"1, • '
Panel:
Date:
May 13, 2008 -
CURRENT TOTAL=
350 .
CIRCUIT:
QTY .
S1
-
-, L
-:
---------
____ _
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
SET -MC @15CD
64
0
.
Total Wire Resistance ( R )
0.86
0
0
_
SET -MC @30CD
.98
0
1 ( WL* 2 )*(R/ft)
. 2
SET -MC @75CD
175
• 350
;
Total Device Load, Amps (I)
0.35
0
6 .
SET -MC @110CD
233
0(Total
Cct Load)
SET-HMC-C115CD
318
: 0
Voltage Drop ( E)0.30
-
SET-HMC-C@177CD
445
I 0
(E=• I * R)
__._ -----
0
SET -HMC g135CD
, . 318
_
0
_
'
EOL Voltage '
20.10
SET -HMC g185CD .
,
445
' 0
.I
•
: (20.4 - E) ,
, , .
0
Z-MC@15CD .
. ' 64
0-
_
_
•
•
• :
0
Z-MC@30CID
98
0
,
_
0
SET-MC-CW@110CD
'1 233
0
. '
_ -----
DEVICES=
2 ,
TOTAL mA=
.___
350
12
265
20.099491 350
. -
-
Notification
.......,......._....,.. T.INIW •`.•
.Appliance
••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06
-trfl•11, .4 -.........*1 I* .,.1},MAY.V....11*
Circuit
...., ny...~.1.••••mws Twom.ret taw... IT.T+01
Detail
M,I" V
_
WESTFIELD SOUTHCENTER
___
MALL
-----
PROJECT
.GODIVA;:;-,...:.,i.,..,..,..... ....-- -,...:- • • : - ... ...... ' - •, -
- • , • ':, . 1 .;:
Wire Resistance :i08.,I, ; • - ,.;,;-
. ....
. ... . ,
..:Panel
•
May 13, 2008 ; ,
.• CURRENT TOTAL
3.6
Date:
CIRCUIT:
SPEAKER CIRCUIT
,
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
- _
QTY
2
70.7V 1/8 ,
. 1.8
- 3.6
1
Total Wire Resistance ( R ) _ _
2.92
' 0 •
-
, ' 0
• 0,,
.
( WL *2 )* (R/ft)
0 ,
, ' •;.
. .0
Total Device Load, Amps (I)
0.00
0
0
0
,
._____
,. .
(Total Cct Load)
0
. ,
_
0
_
Voltage ( E) E )
0.01
0
0
; .,
(E= I * R)
0
_
0
_
,.I
EOL Voltage
___
20.39
0
_
, , 0
0
_
L:icl
iI,I:I,
(20.4 - E)
0
' 0
r,
_
0
0
,,
--,,- --,-
•
. ,
- -
0
2
. TOTAL mA=
3.6
14
.,.;,
565
20.389504561.
3.6
DEVICES=
VOLTAGE DROP CALCULATION
z
0
(/)
LLJ
CE
LJJ
U)
UJ
_.J
LI_J
z
DESCRIPTION
z
0
0
01
LLJ0
F-
0
CO
Lfl
<<<C1
J
03
CO
PrEs
-Jo,
Z
W 0
< CC
wo
> zz
2 w
w
0 5
o
< -
W 0
(f)
tcr3
LoD
(S.*C'ALE: 1/8''=1'
DRAWN BY:
LANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/05/08
BACKROUND PLAN PROVIDED BY:
,Copyright 2006 by Guardian Security.,.SYstems, Inc. All Rights Reserved R;'
1..0B NUMBER:54510
SHEET '\
FA -04
555 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-F-199
08-S-157
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Godiva
555 Southcenter Mall
Permit No.: 08-S-157
Date: May 2, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 % inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a '
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
All references are NFPA 13, 2007 Edition.
cagy
Ili
C3
U
0-7
L
O
L
O
1 O' -O"
0-7
A!
Lin
5 -r. t
1_
p
L)
0
U
J\CEJ
0
rJ
1' `•
F 0-7 L 1I
C>
41
n
J L.
—
1'l
10
82
CEI -1
Lr.)
82
1-43
4"
@ 14'-6" AFF
Ir,
SA
SA
'0
Hod
B2A
15'-5;
11 .rm
1/\
TUKWILA FIRE DEPARTMEN1
Please call: 575.4402
and give this job
and exact address for shut.,
-Jown or rostorati approval.
No.
I � i, I r Nfl 0-10
32 32
'1
11
BlA,
}
(J
J
A
1
I/1
f
r 11
111,i
11
/
1
I1
11
11
i
11
/
/
n
r� r
27'-O"
v
J i
r
i
(GODIVA ChOCOLAT(R
(scare: /2" = 1 '-o")
SPRINKLER HEAD LEGEND :
SYMBOL
S/N
ORIFICE
NPT
K•FACT.
HEAD
FINISH
ir11f
!
11
1
11
11
1
CONSTRUCTION NOTES: "GENERAL NOTES: )
I) PIPE:
THREADED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) FITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
FINISH
THREADED: STAR D.I.
3) GROOVED COUPLINGS:
STAR RIGID C-4 UNLESS MARKED WITH AN "P',
WHICH ARE TO 13E STAR FLEXIBLE C-3 LW -
ORANGE PAINT FINISH
4) HANGER MATERIAL:
ALL HANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
LIST OF ELEVATIONS:;
EXISTING SPRINKLER PIPE 4. @ 14'-6" '
ACT CEILING HEIGHT = AS NOTED
GWS CEILING HEIGHT = 121-0" (U.N.O.)
SYMBOL LEGEND:)
= NEW RECESSED PENDANT ON DROP
= NEW CONCEALED PENDANT ON DROP
$- --S = EXISTING SPRINKLER PIPE TO REMAIN
`S --i = NEW SPRINKLER PIPING
41.7
b
CI Pr? e
!'.<!"'i±? Fire
(city!
:a(opted
for the
per.
d . avrings atter
require a
for I ecuant approval.
sinal acc�pt�rlce is sub sot to field test and inspection by
Tht Tukwila Fire Prevention Bureau.
Date:
PLATE
FINISH
TC
Weld temps Dust be
ins ed before pipe is
hung.n t paint piping
prior to hydrostatic test
approval.
TEMP.
QUAN.
Reliable Model FI FR Recessed Pendant
0
1/2'
1/2'
5.6
Chrome
Chrome
155°
3
Reliable Model G4A Concealed Pendant
1/2'
1/2'
5.6
Brass
White
165°
7
APPROVALS BY:
I TOTAL SPRINKLERS
THIS SHEET
10
1
I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP(.(
2)
3)
4)
5)
6)
7)
8)
ORDINARY HAZARD GROUP I SPRINKLER SPACING: 130 ft2 MAX.
COSCO'S POINT OF CONNECTION 15 AT EXISTING SYSTEM AS SHOWN.
ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING ( IF REQ.. ) TO BE DONE BY
OTHER.
ALL WIRING OF SYSTEM DEVICES IS BY OTHER.
OWNER IS RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
OWNER IS RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTAI 1 FD THE SYSTEMS) 1S BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
ANY RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION,
PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO
BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE
EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE PROTECTION.
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3' METAL DECK
3/8" ANCHOR w/20# TORQUE:
TENSION=395#, SHEAR=750# *
1/2" ANCHOR w/40# TORQUE:
TENSION=440#,SHEAR=750#*
'SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR TIM THREADS
1/4' MIN
ROD COUPLING
THREADED ROD
PIPE
SIZE
ROD
DIA.
BOLT
LGTH
IMBED
DEPTH
I"
3/8"
3 3/4"
2 1/4"
1 1/4"
3/8"
3 3/4"
2 1/4"
1 I/2"
3/8"
3 3/4"
2 1/4"
2"
3/8"
3 3/4"
2 1/4"
2 1/2"
3/8'
3 3/4"
2 1/4"
3"
3/8"
3 3/4"
2 1/4'
4"
3/8"
3 3/4"
2 1/4"
6"
1/2"
3 3/4'
2 1/4"
8"
1/2"
3 3/4"
2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007 I COSCO STANDARD HANGER 1 13 MDL
N
"0000"
"000 .
"00004"
•0000
00•
I
cosco
Fire Protection
FIRE PROTECTION AND LIFE SAFETY SPECIALISTS
WASHINGTON OFFICE
10910 117TH Place N.E.
Kirkland, Washington 98033
call (425) 827-9654 • fax (425) 827-7474
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
www.coscofire.com
License No:
COSCOFP110NM
PROJECT
Godiva Chocolatier
309 Southcenter Mall, Level 1, Suite: 1020
Tukwila, Wa. 98188
CONTRACT vim
The Stone Company General Contractors, Inc.
2019 Galisteo Street, Building N-10, Suite: C
Santa Fe, Nm. 87505 Eric Lyons (505) 955-9960
DRAWING TUE
Godiva Chocolatier: Sprinkler Piping Plan
DATE : May 2008
SCALE : As Noted
DRAWN BY : Justin Johnson
SKS - 7930
SHEET 1413p
FILE
FIRS; ALA
TUKWILA,
IATA
1VI SYSTEM
ASHINGTON
r•
NERAL NOTES
SHEET \U
\/3E. SHEET TITLE
• a
FA -0 1
SYSTEM
\FOMATIO\
FA -02
TYPICAL
DETAILS - WRI\G ':AND MOU
\TI \ G
FA -03
FRE ALAN
SYSTE
V
FLOG: 'PLA\
FA -04
SYSTEV
CALCULATIO\S (CEEAL),
DISE
SITE PLA\
1
0
*cc
Vvithout Comments
As Noted In Red
Per The Attached Letter
nese plans have 'b nen revitnied by The Tule: Bila Fire
Prevention Bur?.; `:.3 C:!!til::ii'i,;., 'v'.'iir', current city
standards. rurs and
omissions wh:1:i • n ::u,..: �. ,,;'.dations of adopted
>tanciara LI; •.. re:;>wlisib:iity for the
adequacy 01 t" . .ii•,, 1.ii,, ''!U i il•if.; U,..,• Sijyner.
Additions, C% }If .,'r 1 ,}! ..'`':�',I,.i lc t., Ih se ciria`!'.�ings atter
1 tills date will v ,1 tl 1• ,.::.;: +nc:e end will require a
resubmittal of re,'i al dre: ivli igs for subsequent approval.
jj Final acceptance is Subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date:
By:
II°UKWIL.A FIRE DEPARTMENT
Please call: 575.4407,
and give this job
No. o ()) F ( °\
•
.10
and exact address for shut.
clown or restoration approval:
NOTTCE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and,
termination of the testing.
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHART
SHIELDED WIRE T❑ BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED: AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSA,
DEVICES ADDRESS.
NUMBERS :ADJACENT TO DEV
DEVICE 011-1-02 WOULD B
2. DETECTOR' AND AUDIBLE CIR
3. AUDIBLE/VISUAL CIRCUIT WIRI
BRANCHING IS PERMISSIBLE,
4. INSTALLATION SHALL BE IN
ELECTRIC CODE, NFPA 72, L
5. INSTALLATION ' MATERIALS (I. ,
STANDARD, BOXES, FIBER ORA
ARE NOT SUPPLIED BY SIEMEI
6. DETECTORS SHALL NOT BE ,M
AIR STREAM OF AIR SUPPLY.,:,
?'3r
7. WIRING SHALL BE PER PLAN;;;
TYPE, QUANTITY AND COLOR(;
AND UNIQUELY MARKED FOR;'
8. INSTALLING CONTRACTOR SH
DRAWINGS FOR "AS BUILT"
g, FOR ADDITIONAL INSTALLATIO
SHEETS AND/OR INSTALLATIO
10. THE 120vac POWER ELECTRI
MUST COMPLY WITH ARTICLE,
SPECIFICALLY SECTION 1-5.211
SOURCES.. 120vac POWER SH:`
DIRECT SUPERVISION OF FIR
11. ALL HORN/STROBE AND ST,
OF 80" A.F.F. OR 6" BELOW;
12. ALL MANUAL PULL STATION'
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND
NITIATING DEVICES UNTIL PREPROGRAMMED WITH
V1BOL DENOTE DEVICE CIRCUIT/ADDRESS
:GOND DEVICE ON ADDRESSABLE LOOP 1.
LARITY SHALL BE OBSERVED.
I'i'SUPERVISED. NO PARALLEL
RICTiCONFORMANCE WITH THE NATIONAL
ALI�:ODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
0 UIT, WIRE, FITTINGS, HANGERS,
BLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
E'RBERUS DIVISION.
'UNT
�U TLE
ITH
E
TU
'D IN DIRECT
TS. PER NFPA 72 2-3.5.1
RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
,CONDUCTORS SHALL BE PERMANENTLY,
E IDENTIFICATION.
L. ,R
TURN ONE SET OF ACCURATELY MARKED
PO ES.
INS,ItRUCTIONS, REFER TO CATALOG CUT
INSTRUCTIONS.
RK SUPPLYING FIRE ALARM SYSTEM PANELS
ND 760 OF NEPA 70, N.E.C. AND NFPA 72,
IIN REFERENCE TO DEDICATED BRANCH POWER
'N'OT BE APPLIED TO FIRE ALARM PANEL WITHOUT
M TECHNICIAN.
:EVICES SHALL BE MOUNTED AT A HEIGHT
?ED CEILING, WHICHEVER IS LESS.
RA1 BE MOUNTED AT 48" A.F.F. TO THE
r
JIT$ WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE ;ROM 'DEDICATED CIRCUITS FROM' THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3. 11:3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-7,9,p10.P ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED;; B,Y ,THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7. I'I III
16. WIRING SHALL RUN CONTINU tt1
AND 'THEN FROM DEVICE TOIiDE;VI
OTHER BACK BOXES OF DIF,
17. ALL WIRING' SHALL: BE ' METE
AND FREE OF SHORTS BET
FINAL EQUIPMENT TRIM.
OM FACP TO FIRST DEVICE ON A CIRCUIT
F WITHOUT SPLICING IN PULL BOXES OR
CIRCUITS.
,,,ERIFIED TO BE CONTINUOUS, FREE OF GROUND
,0ONDUCTORS AND. OTHER CIRCUITS PRIOR TO
18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.'
I,i '111•
t
19. THE ELECTRICAL 'CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE
OUTSIDE, AND INSIDE OF TH; ;,FIR,E;. ALARM BACK BOXES AND JUNCTION :BOXES
AFTER COMPLETION OF THEA ' INS',ALLATION:
20. DETECTORS MUST '.BE RATED F jOR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS: LOCATED.
21. ALL WIRING ' BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT.
22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G iMETALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE Q ITGOING AND RETURN 'CONDUCTORS, EXITING
FROM AND RETURNING TO TilJEil COt' TROL UNIT, RESPECTIVELY, ARE
ROUTED ' SEPARATELY. THE OltGOII,,G AND RETURN, (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BEl UN jj� THE SAME CABLE ASSEMBLY (I.E.,
tit
MULTI -CONDUCTOR CABLE), '::E'NICLO URE, OR RACEWAY.
23.
NFPA •72 2007 A.6.4.2.2.2 1:GOA OF 6.4.2.2.2 IS TO PROVIDE
EN THE OUTGOING. AND RETURN CABLES.
O HELP ENSURE, PROTECTION OF THE
HE RECOMMENDED, MINIMUM
DAMAGE IS 305 ; VM (1 FT) WHERE
Y AND 1.22 M (4 FT) WHERE THE
ADEQUATE SEPARATION BETW
THIS SEPARATION IS REQUIRE
CABLES FROM PHYSICAL DAIS;
SEPARATION TO PREVENT. PH
THE CABLE IS INSTALLED VE
CABLE IS ;INSTALLED;
QUANTITY
2
EX
SYMBOL ! '.IDESCRIPTION
SYMBOLS LEGEND
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
' ; FIRE ALARM
EX?,CONTROL PANEL
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
FARA
I�,FIRE ALARM
`:REMOTE ANNUNCIATOR
SDD-C
SIEMENS
PROVIDED
66" A.F.F.
TO TOP.
BPS:i
•
4;
,L?
•
11;13EMOTE BOOSTER PAD -3 SIEMENS
X'�`IPOWER SUPPLY
';.:INTERFACE MODULEHTRI-R' SIEMENS
IWITH RELAY
PROVIDED
66" A.F.F.
TO TOP'
4S DEEP
VERIFY
IN FIELD
'`DUAL INPUT
II;INTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCR
(CONTROL POINT
(:MODULE
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
Il' REMOTE CONVENTIONAL HZM
('ZONE MODULE
SIEMENS
4S DEEP
VERIFY
IN FIELD
B
i; LINEAR BEAM
II {;,SMOKE DETECTOR
PBA -1191 SIEMENS
PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -1 1 ' BASE
4S DEEP
W/ 1G RING
CEILING
'' ('DUCT SMOKE
1;DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING
VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11: W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
4F FIRE ALARM
'SPEAKER STROBE
„'(CEILING MOUNT)
(,'FIRE ALARM
('iSPEAKER STROBE
,!';(WALL MOUNT)
lii;FIRE ALARM
,('SPEAKER STROBE
(CEILING MOUNT)
SET -MC -CW SIEMENS
SET -MC -,W SIEMENS
SET -HMC -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING;
80" A.F.F.
TO BOTTOM
CEILING
FIRE ALARM
'1`HSTROBE
II�(CEILING MOUNT)
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
Ii [:IRE ALARM
1! STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
it FIRE ALARM
i
!'SPEAKER
'i (CEILING MOUNT)
SET -CW' SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
' FIRE ALARM
'SPEAKER
. (WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
FIRE ALARM
C) 'STROBE
WP (WEATHERPROOF)
MR
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX
1/2" PIPE
VERIFY
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA 'JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
`JUNCTI❑N BOX
F,B,❑,
F,B,❑,
N/A
VERIFY
IN ' FIELD
ABOVE FINISHED
FL❑❑R
N/A
N/A
N/A
N/A
'FURNISHED BY
!-:OTHERS
N/A
N/A
N/A
N/A
N%()
!;N❑T
APPLICABLE
N/A
N/A
N/A
N/A
;.UNLESS OTHERWISE
NOTED
N/A
N/A
N/A
N/A
•.WEATHERPR❑OF
DEVICE
N/A
N/A
N/A
N/A
RED'
''AS BUILT •
';,ADD OR CHANGE
N/A
N/A
N/A
N/A
GREEN AS BUVEILT
REMO
N/A
N/A
N/A
N/A
BLUE AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
I;
•
I. FIr,e
n i .•a
Copyright 2006 by Guardian Security, Systems, Inc.. All Rights R;eerw'e'dl;`f
l 1,
z
ci)
cc
'ccz
LC).
N
0
0
N
W
F -
RELEASE/REVISIONS
REV. BY:
WIRE DESIGNATION
SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
D
H
P '
S .
2S
A
V
2V
I
X
UD
UI
M
B
DATA LINE -ADDRESSABLE LOOP TWISTED PAIR',WITH SHIELD #16 FPL/FPLR ': RED (JACKET)
DOOR HOLDER POWER - 24VDC TWO . #14 FPL/FPLR 'RED (JACKET)
DEVICE POWER - 24VDC TWO , #16 FPL/FPLR .' RED (JACKET)
STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) .
STROBE CIRCUIT - RETURN TWISTED PAIR, 'W/ SHIELD #12 FPL/FPLR ,RED (JACKET)
ANNUNCIATOR TWISTED PAIR 'W/ SHIELD #16, FPL/FPLR .' RED (JACKET)
SPEAKER CIRCUIT - FEED TWISTED PAIR . #14 FPL/FPLR RED (JACKET)
SPEAKER CIRCUIT - RETURN TWISTED PAIR. #14 .FPL/FPLR ' RED (JACKET)
REMOTE INDICATI❑N LIGHT TWO 2 #18 FPL/FPLR • RED (JACKET)
LOW LEVEL AUDI❑ TWISTED PAIR W/',SHIELD #16 FPL/FPLR '' RED (JACKET)",
UNDERGROUND DATA TWISTED PAIR RATED '. #18 ' FPL/FPLR .RED (JACKET) ,:
UNDERGROUND INITIATION ',TWISTED PAIR RATED • #18 FPL/FPLR , RED ,(JACKET)
DOOR HOLDER POWER TWO #16 FPL/FPLR • RED .(JACKET)
BEAM DETECTOR POWER TWO • • #14 FPL/FPLR RED (JACKET)
CONDUIT FILL CHART
SHOP DRAWINGS
NO. OF CONDUCTORS VOLTS • WIRE SIZE' TYPE :... • DIMENSIONS AREA '
TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346
TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191
CONDUIT FILL •
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON' THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" • '.12 SQUARE INCH
3/4" .21 SQUARE INCH
1" ' .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND 'ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4..
SHIELDED WIRE T❑ BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED: AT END
FOR SIEMENS SYSTEM:
DO NOT INSTALL ADDRESSA,
DEVICES ADDRESS.
NUMBERS :ADJACENT TO DEV
DEVICE 011-1-02 WOULD B
2. DETECTOR' AND AUDIBLE CIR
3. AUDIBLE/VISUAL CIRCUIT WIRI
BRANCHING IS PERMISSIBLE,
4. INSTALLATION SHALL BE IN
ELECTRIC CODE, NFPA 72, L
5. INSTALLATION ' MATERIALS (I. ,
STANDARD, BOXES, FIBER ORA
ARE NOT SUPPLIED BY SIEMEI
6. DETECTORS SHALL NOT BE ,M
AIR STREAM OF AIR SUPPLY.,:,
?'3r
7. WIRING SHALL BE PER PLAN;;;
TYPE, QUANTITY AND COLOR(;
AND UNIQUELY MARKED FOR;'
8. INSTALLING CONTRACTOR SH
DRAWINGS FOR "AS BUILT"
g, FOR ADDITIONAL INSTALLATIO
SHEETS AND/OR INSTALLATIO
10. THE 120vac POWER ELECTRI
MUST COMPLY WITH ARTICLE,
SPECIFICALLY SECTION 1-5.211
SOURCES.. 120vac POWER SH:`
DIRECT SUPERVISION OF FIR
11. ALL HORN/STROBE AND ST,
OF 80" A.F.F. OR 6" BELOW;
12. ALL MANUAL PULL STATION'
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND
NITIATING DEVICES UNTIL PREPROGRAMMED WITH
V1BOL DENOTE DEVICE CIRCUIT/ADDRESS
:GOND DEVICE ON ADDRESSABLE LOOP 1.
LARITY SHALL BE OBSERVED.
I'i'SUPERVISED. NO PARALLEL
RICTiCONFORMANCE WITH THE NATIONAL
ALI�:ODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
0 UIT, WIRE, FITTINGS, HANGERS,
BLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
E'RBERUS DIVISION.
'UNT
�U TLE
ITH
E
TU
'D IN DIRECT
TS. PER NFPA 72 2-3.5.1
RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
,CONDUCTORS SHALL BE PERMANENTLY,
E IDENTIFICATION.
L. ,R
TURN ONE SET OF ACCURATELY MARKED
PO ES.
INS,ItRUCTIONS, REFER TO CATALOG CUT
INSTRUCTIONS.
RK SUPPLYING FIRE ALARM SYSTEM PANELS
ND 760 OF NEPA 70, N.E.C. AND NFPA 72,
IIN REFERENCE TO DEDICATED BRANCH POWER
'N'OT BE APPLIED TO FIRE ALARM PANEL WITHOUT
M TECHNICIAN.
:EVICES SHALL BE MOUNTED AT A HEIGHT
?ED CEILING, WHICHEVER IS LESS.
RA1 BE MOUNTED AT 48" A.F.F. TO THE
r
JIT$ WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE ;ROM 'DEDICATED CIRCUITS FROM' THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3. 11:3HDETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-7,9,p10.P ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED;; B,Y ,THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEEN,; INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED;: R REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7. I'I III
16. WIRING SHALL RUN CONTINU tt1
AND 'THEN FROM DEVICE TOIiDE;VI
OTHER BACK BOXES OF DIF,
17. ALL WIRING' SHALL: BE ' METE
AND FREE OF SHORTS BET
FINAL EQUIPMENT TRIM.
OM FACP TO FIRST DEVICE ON A CIRCUIT
F WITHOUT SPLICING IN PULL BOXES OR
CIRCUITS.
,,,ERIFIED TO BE CONTINUOUS, FREE OF GROUND
,0ONDUCTORS AND. OTHER CIRCUITS PRIOR TO
18. ALL CABLES SHALL BE. MA A INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL: EVIC°S, JUNCTION BOXES AND FACP.'
I,i '111•
t
19. THE ELECTRICAL 'CONTRACTO'RI SH LL CLEAN ALL DIRT 'AND DEBRIS FROM THE
OUTSIDE, AND INSIDE OF TH; ;,FIR,E;. ALARM BACK BOXES AND JUNCTION :BOXES
AFTER COMPLETION OF THEA ' INS',ALLATION:
20. DETECTORS MUST '.BE RATED F jOR ;TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS: LOCATED.
21. ALL WIRING ' BETWEEN FLO.ORSHALL BE LOCATED IN CONDUIT.
22. NFPA 72 '2007 6.4.2.2.2 ALL; STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G iMETALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE Q ITGOING AND RETURN 'CONDUCTORS, EXITING
FROM AND RETURNING TO TilJEil COt' TROL UNIT, RESPECTIVELY, ARE
ROUTED ' SEPARATELY. THE OltGOII,,G AND RETURN, (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BEl UN jj� THE SAME CABLE ASSEMBLY (I.E.,
tit
MULTI -CONDUCTOR CABLE), '::E'NICLO URE, OR RACEWAY.
23.
NFPA •72 2007 A.6.4.2.2.2 1:GOA OF 6.4.2.2.2 IS TO PROVIDE
EN THE OUTGOING. AND RETURN CABLES.
O HELP ENSURE, PROTECTION OF THE
HE RECOMMENDED, MINIMUM
DAMAGE IS 305 ; VM (1 FT) WHERE
Y AND 1.22 M (4 FT) WHERE THE
ADEQUATE SEPARATION BETW
THIS SEPARATION IS REQUIRE
CABLES FROM PHYSICAL DAIS;
SEPARATION TO PREVENT. PH
THE CABLE IS INSTALLED VE
CABLE IS ;INSTALLED;
QUANTITY
2
EX
SYMBOL ! '.IDESCRIPTION
SYMBOLS LEGEND
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
' ; FIRE ALARM
EX?,CONTROL PANEL
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
FARA
I�,FIRE ALARM
`:REMOTE ANNUNCIATOR
SDD-C
SIEMENS
PROVIDED
66" A.F.F.
TO TOP.
BPS:i
•
4;
,L?
•
11;13EMOTE BOOSTER PAD -3 SIEMENS
X'�`IPOWER SUPPLY
';.:INTERFACE MODULEHTRI-R' SIEMENS
IWITH RELAY
PROVIDED
66" A.F.F.
TO TOP'
4S DEEP
VERIFY
IN FIELD
'`DUAL INPUT
II;INTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCR
(CONTROL POINT
(:MODULE
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
Il' REMOTE CONVENTIONAL HZM
('ZONE MODULE
SIEMENS
4S DEEP
VERIFY
IN FIELD
B
i; LINEAR BEAM
II {;,SMOKE DETECTOR
PBA -1191 SIEMENS
PROVIDED
VERIFY
IN FIELD
SMOKE DETECTOR HFP-11 W/ SIEMENS
(ADDRESSABLE -PHOTO) DB -1 1 ' BASE
4S DEEP
W/ 1G RING
CEILING
'' ('DUCT SMOKE
1;DETECTOR
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING
VERIFY
IN FIELD
HEAT DETECTOR
(ADDRESSABLE)
HFPT-11: W/ SIEMENS
DB -11 BASE
4S DEEP
W/ 1G RING
CEILING
4F FIRE ALARM
'SPEAKER STROBE
„'(CEILING MOUNT)
(,'FIRE ALARM
('iSPEAKER STROBE
,!';(WALL MOUNT)
lii;FIRE ALARM
,('SPEAKER STROBE
(CEILING MOUNT)
SET -MC -CW SIEMENS
SET -MC -,W SIEMENS
SET -HMC -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING;
80" A.F.F.
TO BOTTOM
CEILING
FIRE ALARM
'1`HSTROBE
II�(CEILING MOUNT)
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
Ii [:IRE ALARM
1! STROBE
(WALL MOUNT)
ZR -MC -W SIEMENS
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
it FIRE ALARM
i
!'SPEAKER
'i (CEILING MOUNT)
SET -CW' SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
' FIRE ALARM
'SPEAKER
. (WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
FIRE ALARM
C) 'STROBE
WP (WEATHERPROOF)
MR
MULTI -VOLTAGE
CONTROL RELAY
SET -S17 -WP SIEMENS
MT -SUR -BOX
1/2" PIPE
VERIFY
IN FIELD
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA 'JB❑X
FIRE ALARM
TERMINAL CABINET
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
`JUNCTI❑N BOX
F,B,❑,
F,B,❑,
N/A
VERIFY
IN ' FIELD
ABOVE FINISHED
FL❑❑R
N/A
N/A
N/A
N/A
'FURNISHED BY
!-:OTHERS
N/A
N/A
N/A
N/A
N%()
!;N❑T
APPLICABLE
N/A
N/A
N/A
N/A
;.UNLESS OTHERWISE
NOTED
N/A
N/A
N/A
N/A
•.WEATHERPR❑OF
DEVICE
N/A
N/A
N/A
N/A
RED'
''AS BUILT •
';,ADD OR CHANGE
N/A
N/A
N/A
N/A
GREEN AS BUVEILT
REMO
N/A
N/A
N/A
N/A
BLUE AS BUILT
NOTES TO CAD
N/A
N/A
N/A
N/A
I;
•
I. FIr,e
n i .•a
Copyright 2006 by Guardian Security, Systems, Inc.. All Rights R;eerw'e'dl;`f
l 1,
z
ci)
cc
'ccz
LC).
N
0
0
N
W
F -
RELEASE/REVISIONS
REV. BY:
z
a
DESCRIPTION
SHOP DRAWINGS
DATE
M
0
0
in
o
a««
/
SCALE: 1 /8"=1
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/05/08
BACKROUND PLAN PROVIDED BY:
NUMBER:54510
FA -0 1
I;
CO
7,
•
NORTH
Go DIVA WESTFIELD SOUTHCENTER MALL
SC1,41110T:
, ::11 ,i'.,•
.:g
•.f:
• 11
• ; ,
1', • 11
.1 . • ,
•
• 11
'
7I,AG NOT
,S:
I
• 1
1 I
Z...
' 1
11.1,
z
1 „,
11
1
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS.(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
LOCATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR.
WIRED BY ELECTRICAL
CONTRACTOR.
SIEMENS HTRI—D ADDRESSABLE
INPUT WITH HOOD VENILLATOR
FIRE SUPPRESION SYSTEM. FIELD
LOCATE WITHIN 3 FEET OF
CONTRL PANEL.
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER. AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
' 1
kr,
DO \OT INST
ADDRESSABLE
DEVICES ._,\TI
LL
NJT
AT
PREPROGRAMVED W
DEVICES ADDRESS.
T
Copyright 2006 by Guardian Security Systems, Inc. All Rights
CO
Cl)
u_T
F—
uJ
U)
U)
ui
U)
tr)
r---
RELEASE/REVISIONS
REV. BY:
.
4
DESCRIPTION
SHOP DRAWINGS
DATE
co
0
....,
to
......
.1
—_107)
2
w 0
< Eut
wi
1.—.J cc 0 c,
<
0
LO
0
LIJ
H
>11
6ALE: 1/8"=l'
DRAWN BY:
LANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/05/08
BACKROUND PLAN PROVIDED BY:
..JOB NUMBER:54510 j
SHEET
eperyedZ. FA -03 .1
1..044, • •
13 [I
JE
3 P. I D
J1P3
/\[ f: NA ERIE.
SUN COAST
MC..) -1-1(2)1\i
C ILlR EEl
••
1131 ACI
ml
-
11
II
VE: RTZ: (i) N \NI R E L. E:; :H;I.
'I'
II
II
1-•-• I: --- Cil K '
m IN WA 1-111 \ C
SP LIN !..:;:EIR GIFTS
NORTH
r-
/
lvi AI 1
1. OFICE OFFICE
CU
LLJ
L.)
<1.•
(I)
LU
Li
NJ
LIAMBA
JUICE:
ID
1:)(l11U
ABFRCPOMBIE
- - - -
C A TEl IL
riL[1
APIN El
TE Asjvi SI
p
I I:
SYSTEM CALCULATIONS
' GODIVA
GODIVA ; • 1
,
I SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations »FACP
ADD ONS
WESTFIELD SOUTHCENTER MALL ..
PROJECT:
GODIVA
r.,
•
Wire Resistance 1.0"1, • '
Panel:
Date:
May 13, 2008 -
CURRENT TOTAL=
350 .
Current Load:
Standby
S1
-
Alarm:
-:
Current Load:
Standby:
Alarm:
---------
,!
,1; •
____ _
Device Type
Alarm Current
Alarm Total
Wire Size
1
Device Type
Qty
Amps
Total
Amps
Total
64
Device Type
Qty
Amps
Total
Amps
Total
Total Wire Resistance ( R )
0.86
0
0
_
SET -MC @30CD
.98
0
HFP-11
0.0022
0.0022
0.0023
. 2
SET -MC @75CD
175
Maid System Board
1
0.03
. 0.03
0 030
0.030
Total Device Load, Amps (I)
AD2-P
2
0.0635
0.0635
0.064
0.128
Cct Load)
0.064
SET-HMC-C115CD
318
IHTR-R
2
0.009600
0.0096
0.021
0.042
Voltage Drop ( E)0.30
-
SET-HMC-C@177CD
445
I 0
(E=• I * R)
__._ -----
0
SET -HMC g135CD
, . 318
§E -0716d5666 1
_
'
0.098
EOL Voltage '
20.10
HTRI-D
SET -HMC g185CD .
0.001600
' 0
0.0035
•
SET-MCb75CD
2
, , .
0
0.175
0.350
0-
;ICP -B6
0 005
•
•
• :
0
SEtIVIC 6110CD
98
0
0.233
,
_
0
SET-MC-CW@110CD
'1 233
0
i
SET-HMO-C@115CD
. '
_ -----
0.318
DEVICES=
2 ,
.___
350
12
265
20.099491 350
. -
SET-HMC7C@135CD
-
Notification
0.318
••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06
-trfl•11, .4 -.........*1 I* .,.1},MAY.V....11*
Circuit
...., ny...~.1.••••mws Twom.ret taw... IT.T+01
Detail
M,I" V
_
WESTFIELD SOUTHCENTER
SETI-16,76161135
,
0.445
PROJECT
- • , • ':, . 1 .;:
Wire Resistance :i08.,I, ; • - ,.;,;-
0.0731
Amps
0.17
AmPO;;
,11____
ZR -MO @I5CD
3.6
0.064
Date:
CIRCUIT:
SPEAKER CIRCUIT
,
,
Device Type
0.098
Alarm Total
Wire Size
Standby Current Load:
0 0731
Amps
For 24 Hours =
1.754
Amp -hours !
i I I;: .
.ZR-;Woco
HCP: ''
t_,
. 1.8
- 3.6
1
0.0015
Total Wire Resistance ( R ) _ _
2.92
' 0 •
-
, ' 0
• 0,,
F . i i
- ---
7 - •-
-"------ -
( WL *2 )* (R/ft)
0.03
Amps
0.38
Amps ,
Alarm Current Load:
0.17
Amps
For 5 Minutes=
0.014
Amp -hours
'
0.00
0
,
0
0
,
._____
,. .
(Total Cct Load)
0
. ,
_
0
Standb
Current Load:
0.03
Amps
For 24 Hours =
0.720
Amp -hours
0
0
; .,
25% Derating=
2.211
Amp -hours
(E= I * R)
II,I
0
_
0
_
,.I
EOL Voltage
___
20.39
0
_
, , 0
0
_
Alarmrent Load:
0.38
Amps
For 5 Minutes=
0.032
Amp -hours
0
' 0
r,
_
0
0
Total System
Current Load:
. ,
2.211
Amp -hours I,
0
2
. TOTAL mA=
3.6
25% Derating=
0.940
Amp -hours
3.6
DEVICES=
Battery Pair to be Used:
12VDC
Amp -hours
7AH
,
Total System Current Load:
0.940
Amp -hours
,
Battery pair to be Used:
12VDC
Amp -hours
7AH
0 ,
, ;
;
. 11
P
THE L
0
reF
1 01 0
r-
•
re;
15501'
I)]
[(11
'-1-5 .1
1 1 1 (-)
; !
11(1 AC_F-
5401 '1.---
GODIVA WESTFIELD SOUTHCENTER MALL
AP
D,I
21
RISER DIAGRAM
I
;
BATTERY SIZING CALCULATION
..
_ .._
. Notification Appliance 'Circuit Detail
WESTFIELD SOUTHCENTER MALL ..
PROJECT:
GODIVA
r.,
•
Wire Resistance 1.0"1, • '
Panel:
Date:
May 13, 2008 -
CURRENT TOTAL=
350 .
CIRCUIT:
QTY .
S1
-
-, L
-:
---------
____ _
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
SET -MC @15CD
64
0
.
Total Wire Resistance ( R )
0.86
0
0
_
SET -MC @30CD
.98
0
1 ( WL* 2 )*(R/ft)
. 2
SET -MC @75CD
175
• 350
;
Total Device Load, Amps (I)
0.35
0
6 .
SET -MC @110CD
233
0(Total
Cct Load)
SET-HMC-C115CD
318
: 0
Voltage Drop ( E)0.30
-
SET-HMC-C@177CD
445
I 0
(E=• I * R)
__._ -----
0
SET -HMC g135CD
, . 318
_
0
_
'
EOL Voltage '
20.10
SET -HMC g185CD .
,
445
' 0
.I
•
: (20.4 - E) ,
, , .
0
Z-MC@15CD .
. ' 64
0-
_
_
•
•
• :
0
Z-MC@30CID
98
0
,
_
0
SET-MC-CW@110CD
'1 233
0
. '
_ -----
DEVICES=
2 ,
TOTAL mA=
.___
350
12
265
20.099491 350
. -
-
Notification
.......,......._....,.. T.INIW •`.•
.Appliance
••,••1.0,..,•,.. M,N 4V, /7,10.VM,.4•06
-trfl•11, .4 -.........*1 I* .,.1},MAY.V....11*
Circuit
...., ny...~.1.••••mws Twom.ret taw... IT.T+01
Detail
M,I" V
_
WESTFIELD SOUTHCENTER
___
MALL
-----
PROJECT
.GODIVA;:;-,...:.,i.,..,..,..... ....-- -,...:- • • : - ... ...... ' - •, -
- • , • ':, . 1 .;:
Wire Resistance :i08.,I, ; • - ,.;,;-
. ....
. ... . ,
..:Panel
•
May 13, 2008 ; ,
.• CURRENT TOTAL
3.6
Date:
CIRCUIT:
SPEAKER CIRCUIT
,
Device Type
Alarm Current
Alarm Total
Wire Size
Wire Length
Voltage at EOL
Circuit Total
- _
QTY
2
70.7V 1/8 ,
. 1.8
- 3.6
1
Total Wire Resistance ( R ) _ _
2.92
' 0 •
-
, ' 0
• 0,,
.
( WL *2 )* (R/ft)
0 ,
, ' •;.
. .0
Total Device Load, Amps (I)
0.00
0
0
0
,
._____
,. .
(Total Cct Load)
0
. ,
_
0
_
Voltage ( E) E )
0.01
0
0
; .,
(E= I * R)
0
_
0
_
,.I
EOL Voltage
___
20.39
0
_
, , 0
0
_
L:icl
iI,I:I,
(20.4 - E)
0
' 0
r,
_
0
0
,,
--,,- --,-
•
. ,
- -
0
2
. TOTAL mA=
3.6
14
.,.;,
565
20.389504561.
3.6
DEVICES=
VOLTAGE DROP CALCULATION
z
0
(/)
LLJ
CE
LJJ
U)
UJ
_.J
LI_J
z
DESCRIPTION
z
0
0
01
LLJ0
F-
0
CO
Lfl
<<<C1
J
03
CO
PrEs
-Jo,
Z
W 0
< CC
wo
> zz
2 w
w
0 5
o
< -
W 0
(f)
tcr3
LoD
(S.*C'ALE: 1/8''=1'
DRAWN BY:
LANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/05/08
BACKROUND PLAN PROVIDED BY:
,Copyright 2006 by Guardian Security.,.SYstems, Inc. All Rights Reserved R;'
1..0B NUMBER:54510
SHEET '\
FA -04