PP - 576 SOUTHCENTER MALL - SUNGLASS HUT - PERMITS AND PLANS
576 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-333 08-S-263 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sunglass Hut 576 Southcenter Mall Permit No.: 08-S-263 Date: June 4, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. SiCo SG t 1, SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 WATER SUPPLY DATA SOURCE NODE TAG SRC STATIC PRESS. (PSI) 140.0 RESID. PRESS. (PSI) FLOW AVAIL. TOTAL @ PRESS. @ DEMAND (GPM) (PSI) (GPM) REQ'D PRESS. (PSI) 20.0 10900.0 138.8 900.9 89.5 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 S14 M1 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 10.0 10.0 10.0 11.0 11.0 11.0 11.0 11.0 11.0 8.0 10.0 11.0 11.0 11.0 14.9 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 HOSE STREAM 900.9 GPM 250.0 GPM 262.1 GPM 388.8 GPM PRESSURE (PSI) 22.8 23.0 23.9 24.7 28.0 24.8 25.1 26.1 28.2 24.4 24.7 25.3 28.0 27.8 21.6 22.1 23.0 23.6 27.3 24.3 24.0 24.9 27.5 24.0 23.3 24.8 27.3 27.0 28.4 DISCHARGE (GPM) 26.0 26.3 26.8 27.2 29.3 27.6 27.4 28.0 29.4 27.5 27.0 27.9 29.3 29.1 262.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) M2 14.9 - 28.6 M3 14.9 - 29.0 CAP 14.9 - - 29.4 TIE 14.9 - 34.8 6067 1.9 86.5 5696 1.9 86.5 6021 1.9 86.6 6176 5.7 - - - - 85.1 - - - SRC -4.0 SOURCE 89.5 650.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALL'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -26.0 1.049 PL 9.00 PF 3.4 S1 10.0 5.6 21.6 26.0 9.7 120 FTG ET PE -2.1 1 14.9 0.0 22.8 0.0 0.211 TL 16.00 PV Pipe: 2 -26.3 1.049 PL 7.00 PF 3.0 S2 10.0 5.6 22.1 26.3 9.8 120 FTG ET PE -2.1 2 14.9 0.0 23.0 0.0 0.216 TL 14.00 PV Pipe: 3 -26.8 1.049 PL 6.50 PF 3.0 S3 10.0 5.6 23.0 26.8 10.0 120 FTG ET PE -2.1 3 14.9 0.0 23.9 0.0 0.224 TL 13.50 PV Pipe: 4 -27.2 1.049 PL 4.88 PF 2.7 S4 11.0 5.6 23.6 27.2 10.1 120 FTG ET PE -1.7 4 14.9 0.0 24.7 0.0 0.230 TL 11.88 PV Pipe: 5 -29.3 1.049 PL 3.88 PF 2.3 S5 11.0 5.6 27.3 29.3 10.9 120 FTG T PE -1.7 5 14.9 0.0 28.0 0.0 0.263 TL 8.88 PV Pipe: 6 -27.6 1.049 PL 4.88 PF 2.1 S6 11.0 5.6 24.3 27.6 10.3 120 FTG 2E PE -1.7 6 14.9 0.0 24.8 0.0 0.237 TL 8.88 PV Pipe: 7 -27.4 1.049 PL 4.88 PF 2.8 S7 11.0 5.6 24.0 27.4 10.2 120 FTG ET PE -1.7 7 14.9 0.0 25.1 0.0 0.233 TL 11.88 PV Pipe: 8 -28.0 1.049 PL 4.88 PF 2.9 S8 11.0 5.6 24.9 28.0 10.4 120 FTG ET PE -1.7 8 14.9 0.0 26.1 0.0 0.242 TL 11.88 PV Pipe: 9 -29.4 1.049 PL 4.88 PF 2.3 S9 11.0 5.6 27.5 29.4 10.9 120 FTG 2E PE -1.7 9 14.9 0.0 28.2 0.0 0.265 TL 8.88 PV Pipe: 10 -27.5 1.049 PL 10.38 PF 3.4 S10 8.0 5.6 24.0 27.5 10.2 120 FTG 2E PE -3.0 10 14.9 0.0 24.4 0.0 0.234 TL 14.38 PV S11 11 Pipe: 11 -27.0 1.049 PL 8.38 PF 3.5 10.0 5.6 23.3 27.0 10.0 120 FTG ET PE -2.1 14.9 0.0 24.7 0.0 0.227 TL 15.38 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -27.9 1.049 PL 3.88 PF 2.1 S12 11.0 5.6 24.8 27.9 10.4 120 FTG T PE -1.7 12 14.9 0.0 25.3 0.0 0.241 TL 8.88 PV Pipe: 13 -29.3 1.049 PL 3.88 PF 2.3 S13 11.0 5.6 27.3 29.3 10.9 120 FTG T PE -1.7 13 14.9 0.0 28.0 0.0 0.263 TL 8.88 PV Pipe: 14 -29.1 1.049 PL 5.88 PF 2.6 S14 11.0 5.6 27.0 29.1 10.8 120 FTG 2E PE -1.7 14 14.9 0.0 27.8 0.0 0.260 TL 9.88 PV Pipe: 15 -26.0 1.610 PL 8.00 PF 0.2 1 14.9 0.0 22.8 0.0 4.1 120 FTG ---- PE 0.0 2 14.9 0.0 23.0 0.0 0.026 TL 8.00 PV Pipe: 16 -52.3 1.610 PL 8.79 PF 0.8 2 14.9 0.0 23.0 0.0 8.2 120 FTG ---- PE 0.0 3 14.9 0.0 23.9 0.0 0.096 TL 8.79 PV Pipe: 17 -79.2 1.610 PL 3.88 PF 0.8 3 14.9 0.0 23.9 0.0 12.5 120 FTG ---- PE 0.0 4 14.9 0.0 24.7 0.0 0.206 TL 3.88 PV Pipe: 18 -106.4 1.610 PL 2.38 PF 3.7 4 14.9 0.0 24.7 0.0 16.8 120 FTG T PE 0.0 M1 14.9 H.S. 28.4 262.1 0.356 TL 10.38 PV Pipe: 19 -29.3 1.610 PL 3.96 PF 0.4 5 14.9 0.0 28.0 0.0 4.6 120 FTG T PE 0.0 M1 14.9 H.S. 28.4 262.1 0.033 TL 11.96 PV Pipe: 20 -27.6 1.610 PL 10.00 PF 0.3 6 14.9 0.0 24.8 0.0 4.4 120 FTG ---- PE 0.0 7 14.9 0.0 25.1 0.0 0.029 TL 10.00 PV Pipe: 21 -55.0 1.610 PL 10.00 PF 1.1 7 14.9 0.0 25.1 0.0 8.7 120 FTG ---- PE 0.0 8 14.9 0.0 26.1 0.0 0.105 TL 10.00 PV Pipe: 22 -83.0 1.610 PL 3.00 PF 2.5 8 14.9 0.0 26.1 0.0 13.1 120 FTG T PE 0.0 M2 14.9 0.0 28.6 0.0 0.225 TL 11.00 PV Pipe: 23 -29.4 1.610 PL 5.00 PF 0.4 9 14.9 0.0 28.2 0.0 4.6 120 FTG T PE 0.0 M2 14.9 0.0 28.6 0.0 0.033 TL 13.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 24 -27.5 1.610 PL 9.67 PF 0.3 10 14.9 0.0 24.4 0.0 4.3 120 FTG ---- PE 0.0 11 14.9 0.0 24.7 0.0 0.029 TL 9.67 PV Pipe: 25 -54.5 1.610 PL 5.33 PF 0.6 11 14.9 0.0 24.7 0.0 8.6 120 FTG ---- PE 0.0 12 14.9 0.0 25.3 0.0 0.103 TL 5.33 PV Pipe: 26 -82.4 1.610 PL 9.00 PF 3.8 12 14.9 0.0 25.3 0.0 13.0 120 FTG T PE 0.0 M3 14.9 0.0 29.0 0.0 0.222 TL 17.00 PV Pipe: 27 -29.1 1.610 PL 4.00 PF 0.1 14 14.9 0.0 27.8 0.0 4.6 120 FTG ---- PE 0.0 13 14.9 0.0 28.0 0.0 0.032 TL 4.00 PV Pipe: 28 -58.3 1.610 PL 1.00 PF 1.1 13 14.9 0.0 28.0 0.0 9.2 120 FTG T PE 0.0 M3 14.9 0.0 29.0 0.0 0.117 TL 9.00 PV Pipe: 29 -397.8 4.260 PL 5.88 PF 0.2 Ml 14.9 H.S. 28.4 262.1 9.0 120 FTG ---- PE 0.0 M2 14.9 0.0 28.6 0.0 0.036 TL 5.88 PV Pipe: 30 -510.1 4.260 PL 8.00 PF 0.5 M2 14.9 0.0 28.6 0.0 11.5 120 FTG ---- PE 0.0 M3 14.9 0.0 29.0 0.0 0.057 TL 8.00 PV Pipe: 31 -650.9 4.260 PL 4.42 PF 0.4 M3 14.9 0.0 29.0 0.0 14.7 120 FTG ---- PE 0.0 CAP 14.9 0.0 29.4 0.0 0.089 TL 4.42 PV Pipe: 32 -650.9 4.260 PL 34.75 PF 5.4 CAP 14.9 0.0 29.4 0.0 14.7 120 FTG T PE 0.0 TIE 14.9 0.0 34.8 0.0 0.089 TL 61.05 PV Pipe: 33 -650.9 4.260 PL 346.01 PF 46.0 TIE 14.9 0.0 34.8 0.0 14.7 120 FTG 172.2 PE 5.6 6067 1.9 0.0 86.5 0.0 0.089 TL 518.21 PV Pipe: 34 -650.9 8.329 PL 1.50 PF 0.0 6067 1.9 0.0 86.5 0.0 3.8 120 FTG ---- PE 0.0 5696 1.9 0.0 86.5 0.0 0.003 TL 1.50 PV Pipe: 35 -650.9 8.329 PL 19.40 PF 0.2 5696 1.9 0.0 86.5 0.0 3.8 120 FTG 32.0 PE 0.0 6021 1.9 0.0 86.6 0.0 0.003 TL 51.40 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 36 -650.9 10.020 PL 20.17 PF 0.1 6021 1.9 0.0 86.6 0.0 2.6 120 FTG 67.0 PE -1.6 6176 5.7 0.0 85.1 0.0 0.001 TL 87.17 PV Pipe: 37 -650.9 10.400 PL 113.08 PF 0.2 6176 5.7 0.0 85.1 0.0 2.5 140 FTG 137.1 PE 4.2 SRC -4.0 SRCE 89.5 (N/A) 0.001 TL 250.18 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.105 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 16.8 ft/sec at pipe 18. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 8.329 22.16 43.09 16.00 55.40 14.77 4.92 38.16 38.16 43.09 10.020 22.00 50.00 16.00 55.00 19.00 5.00 37.00 37.00 50.00 10.400 26.37 59.94 19.18 65.93 22.78 5.99 44.35 44.35 59.94 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C • B G A D F Ell Tee LngEll ChkVly BfyVly GatVly A1mChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 4.260 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 E ai a) 1 tr)i rn a H CT I0 m U U o rn • o o r C o W m u) o R, as oU N ch 04 N gW A • o ami Q, i 4 i_wH• op ,-1�c0ncn a.-1 rt o b' • Y m a1 m • -H < Ham 4 co tat I o %/ %/ o o ,--i (N N U) O O o 0 rl a 'R w m m R w ¢, U] -H O O d' N N O 0 0 0 O CO 10cri 0 0 0 H 0 0 rn o 0 co ao O _ o N N O 0 In 0 0 .44.44 0 0 M 0 _0 N N O 0 N PO O O -41 O a TOLCO Pio. LNIVJSRSAL &JAY DRAG! PITTIN4 TOLCO Plb. ta0 tNIVEIRSA1. SHAY DR4CL! PITTNER " • •' •• •,sal.•' TOLCO PiPU CLAMP PIe3L 48. 0214' PIPE AND LAMER) PIl6. 4 CP PiPS AND 01A4.1xv LONGITUDINAL E3RACE MT8 ' ICWOC DOLT ORM MiN. 6' 1' ) LATERAL BRACE (2" PIPE 4 SMALLER) N1 MALL CONCOU1�(y Toixo LANNUR8r8t. SWAY DRACl! PITTINS •• 41. i; ►•' •,•,• TOI.CO PIER. 1001 PAST CLAMP • ° KWBC DOLT ativ LATERAL !RACE (21/2" PIPE 4 LARGER) MT9 I AAmoco .3e �3/a X U2 L.4 SCRD J POR WOOD 9- 1/4" =DC COLT POR C WCRETU i/4 X I TOM POR BARJOIST OR 8T1eE1. SRAM 9/8'x4-40 ALL T.RRAD ROD MAIC FSR &WHIR IRDEMTRAINT WHERE LENSTH OP ALL. THREAD IIXOSHOs P-10" ADD MONO =STRAIN? 14ANS1213 RIMS (UP TO 2" PIPIT) LiNE RESTRAINT DETAIL NOTE: 1) SPACE WiTH 1N 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NPPA-13(21 1 ed.) :SECTIONS 9.3.6.8.8, TABLE 3.3.5.8.8(c) AND .93.6-RESTA(NT OF BRANCH LiNES SYMBOL =X 331_0II 151_311 101 -,/hll 2 I vwZ ADJ TE i'-1 ' I 1112 CENT 2 -1Z 5I_/ryxll 41_311 31_0" 41 Ell�I'f% %ii77 ;fay rire DIRE SPRINlit.ER PIPING PIAN SCALE: 1/4"=1'-0II PIPE ROD SIZE DIA I' 3/8' I U4' 3/8' I I/2' 3/8' 2' 3/8• 2 I/2' 3/8' 3' 3/8' 4' 3/8' b' U2' 8' 1/2' HILTI FIG LH OR TOLCO FIG 200 HANGER RING 0 04/2001 COSCO STANDARD HANGER 2 ADJACENT TENANT TYPI AL H MM 11141314: I' MD ISI' PP114•1' CAT W-3' ALP IIt1VATiON) II!' PP321'-6It' GU FAUN FCU ALL OMR 1U3I1H6 UL HILTI KWIK BOLT TZ ANCHOR ICC REPORT #ESR -1917 MIN OF 3.000 PSI CONCRETE MIN 3 U4' CONCRETE OVER MAX 3' METAL DECK 3/8' ANCHOR w/20# TORQUE: TENSION395#. SHEAR.750# U2' ANCHOR w/40# TORQUE: TENSION'.440#.SHEAR=750# I/2' MIN N ROD COUPLING THREADED ROD PIPE ROD SiZE DIA I' 3/8' 1.25' 3/8' 1.5' 3/8' 2' 3/8' 2.5' 3/8' 3' 3/8' 4' 3/8' b' 1/2' 8' 1/2' BOLT LGTH 7' 7' r 7' 7' 7' 7' 7' IMBED DEPTH 2 I/4' 2 1/4' 2 1/4' 2 1/4' 2 1/4' 2U4' 2 1/4' 2 1/4' 2 1/4' • HILTI FIG LH OR TOLCO FIG 200 HANGER RING 0 04/2007 I COSCO STANDARD HANGER I 13 MDLH HYDRAULIC DESIGN—REMOTE AREA SUNGLASS HUT 4422 - ENTIRE TENANT SPACE ORDINARY HAZARD GROUP 2 .20 GPM/1500 S.F. K=5.6. 130 S.F. MAX. PER HEAD 14 SPRINKLERS DISCHARGING iN REMOTE AREA SYSTEM DEMAND: 900.9 GPM C 89.5 PSI Tot. TOLCO FlG. 25 SURGE RESTRAINER TYPE 1 - FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 - FOR 1-1/2" AND 2" PIPE AND HANGER TOLCO FiG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO. RESTRAIN THE UPWARD MOVEMENT OF PIPE AS iT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACT ITY FiGURE 2a SURGE RESTRAINER FOR STEEL OR CPVC PLASTIC PIPE FI E SPRINKLER SYME5OL. Leamt\ID C. LONGITUDINAL SWAY BRACE LATERAL. SWAY BRACE BRANCHLINE RESTRAINT PIPE HANGER PIPE ELEVATION AFTER FLOOR CEILING ELEVATION AFTER FLOOR HYDRAULIC NODE . PENDENT/CONCEALED SPRINKLER TYPICAL DROP TO SPRINKLER HEAD GENERA.. NOTBS 1 1/2" BRANCHLINE �11-/}SII "FLEXHEAD" FLEXABLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE ADJUSTABLE HUB MOUNTING BRACKET TYPICAL DROP TO SPRINKLER HEAD IN AC TILE CEILINGS 2. 3. 4. s. 6. '1. a 10. Ii. 10. DESIGN AND INSTALLATION SHALL CONFORM TO NFPA PAMPHLET 13 AND CITY OF TUKWiLA FiRE DEPT. REQUIREMENTS ALL MATERIALS SHALL BE NEW AND U.L. APPROVED. PIPE: ALL PIPE 2" AND LARGER TO BE SCHEDULE 40 BLACK STEEL. ALL PiPE 21" AND LARGER TO BE SCHEDULE 10 BLACK STEEL. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE STAR BRAND DUCTILE IRON. PAINTING OF PiPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. ALL ELECTRICAL WIRING AND CONDIUT iS BY OTHERS. - ALL WELDING TO CONFORM WITH AWS 010.41 AND WILL BE PERFORMED N COSCO'S SHOP. IT IS THE BUILDING OWNERS RESPONSIBILITY TO KEEP ALL AREAS WITH WET SPRINKLER SYSTEMS HEATED TO A MINIMUM 40 DEGREES FAHRENHEIT TO PREVENT FREEZING OF PIPES. OWNER iS RESPONSIBLE TO ASSURE THAT STRUCTURE AS iT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PiPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PiPING LOADS. COSCO ASSUMES NO RESPONSIBILITY, EiTHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FiRE PROTECTION. UNDERGROUND CONTRACTOR SHALL FLUSH THE UNDERGROUND AND PROVIDE C0500 WITH THE PROPER CERTIFICATE OF DOING. SO BEFORE COSCO WILL CONNECT TO THE UNDERGROUND PIPE. SPRINKLER HEADS ARE DESIGNED TO BE IN CENTERLINE OF CEILING TILE (+/- 1"). ALL DIMENSIONS ARE TO CENTERLINE OF PiPE. 0 Wiitlthout Cor MM ntt As acted In Red Per The Attached Letts, i nese plans have been r evi, t.!ved by The Tul- ,,: i Fire Prevention Bureau ' lr corif irmance wi ll current city standards. AcCi:;. .nc;, is !,..Lit:;ect to errors cod omissions wnich do i'ot authorize vioit9t ons of opted 4 standards and orinncances. i he respc.in.t t1'Qy for the adaqua-cy ot.'Jorh,n re;is tot; liy with tree designer. -Addition.S, r3, -,;;,+ions, or rivi$ioliri tht. c clrawirigs atter ;this d%3C' will vov t -3 11,:o.`j,t_i00r; SI rid will rt +.hire a x resubmittal of rW;/Is' Ur.),:/winos for uubr.K.,t.{tur rrt approval. 0 Y I, Final acceptdnee is outlject to field teat Yid Inspection by 1 The Tukwila Fire Prevention Bureau. A Date: (0' 7\ - Oi By' L WEST RISER ROOM -PLAN ViEW RLE COPY TENANT SPACE TUKWiLA FIRE DEPARTIVLENI Please call: 575-4407 and give this job No. 0S -S e1) ani exact address for shuts -Lown or restoration approval. KAY PLAN NO SCALE CEIUNG -— Awiti WnatR,I/.�LLC West REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAIV. RELIABLE MODEL G4A OR CONCEALED PENDENT • R5415 1/2' 1/2'. 5.6 BR WH 165° 14 APPROVALS BY: CITY OF TUKWiiA I TOTAL SPRINKLERS THIS SHEET 14 ••0 G 0 *•• ••® 0010•• Fire Protection COSCO FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE www.coscofire.com 15000 Woodinville -Redmond Rd NE . License No: Woodinville, Washington 98072 COSCOFP1IONM call (425) 686-8300 • fax (425) 827-4784 SAN DiEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE PRO C *: SUNGLASS. HUT #4422 633 SOUTHCENTER MALL STE 576 SEATTLE, WA. 98188 CONTRACT Nth TURNER BUSCH CONSTRUCTION 214 STATE ST HACKENSACK, NJ. 07601 2003 IUi�L�/i13 Fire DRAWING TITLE FIRE SPRINKLER TENANT IMPROVEMENT #/5-.3°° DIATE : 05-29-08 SCALE : 1/4" = l'-Ot' DRAWN BY : T.N.RHODES JOB' 5 KS 7945 SHEET NO. 1 of 1 SUNGLASS HUT 1115 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \Ulv 3ER SHEET TITLE FA -01 SYSTEM I N FO R VIATI O FA -02 TYPICAL DETAILS - WIRI\G AND MOUNT! \G FA -03 FIRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (GE\ ERAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, 8c OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SMALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES, IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) ..WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Q C ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FETID WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. A.F.F. ABOVE FINISHED FLOOR N/A :N/A c N/A VERIFY IN FIELD N/A C FURNISHED BY N/A N/A Without Coglnents N/A r 'Diu. OTHERS WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP DOOR HOLDER POWER - 24VDC DEVICE POWER - 24VDC STROBE CIRCUIT - FEED ANNUNCIATOR SPEAKER CIRCUIT - FEED REMOTE INDICATION LIGHT LOW LEVEL AUDI❑ UNDERGROUND DATA UNDERGROUND INITIATION DOOR HOLDER POWER BEAM DETECTOR POWER TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) TWO #14 ' FPL/FPLR RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWO #18 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWO #14 FPL/FPLR RED (JACKET) N/A a Per The Atned Letter N/A CONDUIT FILL CHART U.O.N. NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-12" .82 SQUARE INCH 2' 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, 8c OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SMALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES, IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) ..WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Q C ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FETID WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. A.F.F. ABOVE FINISHED FLOOR N/A :N/A c N/A VERIFY IN FIELD N/A C FURNISHED BY N/A N/A Without Coglnents N/A r 'Diu. OTHERS I' -171i As Noted In Red N/A NOT APPLICABLE N/A N/A a Per The Atned Letter N/A i nese plans have been reviewed by The Tukwila Fire U.O.N. UNLESS OTHERWISE NOTED N/A Prey ntion Bureau for conformance with current city stgileards. Acceptance is'.r6 ct to errors and ' N/A nmissinns which do not authorize violations of adopted WP WEATHERPROOF DEVICE N/A sismaras and orainances.NT,h responsibility for thit adequacy of design rests totally with the designer. Additions, dpiptinns or revisions to these drawings after RED AS BUILT ADD OR CHANGE N/A VAate will void this.accepr�ce and will require a resubmittal�t� of revised drawings for subsequent app its. GREEN AS BUILT REMOVE N/A FjRi,aAacceptance is subjecNtNietd test and inspect* Of The Tukwila Fire, Prevention Bureau. BLUE AS BUILT NOTES TO CAD N/A /7 00 Efy • 00 , ID? TUKWILA FIRE DEPARTMw.1J,, Please call: 575-440Z and give this job No.O and exact address for shut* iown or restoration approval. AID JUN 12 200 Tukwila rC�i6 1vj6 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved rS z z cc 14cz 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE CO w z DESCRIPTION SHOP DRAWINGS w 0 co 0 Ln N 0 C J c T c0 T Q I -D EL98 w o Z zz 2 w= Cn _ ©C W 0 tx z Ci SCALE: 1/8" =1 ' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: SOB NUMBER: C AE FO1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE FROM XLS CONTROL PANEL OR i+ PREVIOUS ADDRESSABLE DEVIL STOP IF LAST DEVICE END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 DUCT DETECTOR L❑CATION LID GROUND___() © © HTRI—R OSTATUS LED 00 0 N.O. N 0 CO 0 J_ COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING- \ TUBE \ AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE {(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE () RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE. DETECTION, 0 It QI TB1 5 5 0 0 0 0 123456 HCP TB2 o 654321 J END OF LINE DEVICE 0 0 (3.6K 1/4W) SUPERVISED , SWITCH / GROUND ' NOTE: © © HTRI—D 1110 STATUS LED CO 0 0 0 NOT USED END OF LINE DEVICE 3.6K 1/4W) 0 UPERVISED 1 SWITCH FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC cilop PAD-3 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - I— uuu m m o e a o am 24K (1 TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 f FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 0 el— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS IW EOL II • INPU , + 9 9 TEM -1 0 J MO1 q400 F '.O =000 0 IMC 0 COI TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL FROM REMOTE r POWER SUPPLY L ('S' CABLE) FROM FACP <V❑ICE CIRCUIT) ('V' CABLE) SCALE NM EARTH GROUND --)•(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE +) ) STROBE SPEAKER (+) (-) ( STROBE-) (STROBE) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4SDEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER61JN TEMPERAIU +32' F (0 C) TO 100' F 38' C) HUMIDITY: 0-9333333 E % RELATIVE HUMIDITY, NON -CONDENSING HFI' -11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE• DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR MR VOLOCITY APPUCATIONS OF 300-4000 FT,4AIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F ( ) DATA OUT 1 (+) DATA OUT Jj CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID ----\ HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE / 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX-- MOUNTED OX•----MOUNTED ON \ CEILINGI FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE "---- SUSPENDED ILLUMINATED CEILING DO NOT IN ADDRESSA' DEVICES U PREPROGRAV STALL LE I\ \TIL MED WIT TOATING DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS CO Lu z DESCRIPTION SHOP DRAWINGS L I- < 0 Co 0 0 z C C z z 0 II O 0 co 00 t 0) I— w zo 0 [fir, z L,11= oc =Q -. wcr z ; J �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: (SHEET FA -029 NORTH EOL—S1 18.84V 0 L. 1 10'-0" AFF SUNGLASS HUT 1115 WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FLAG 1\0 ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED' BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO INSAL ADDRESSABLE I\ T DEVICES U\TIL PREPROGRAMMED WI DEVICES ADDRESS. ATI\G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS w aF- 5/15/08 2 CCCC< LC) co co TJ pcp T Q co I— w o I coFz � W Cn CC Uj Cr)Q �w o5 Z �CALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: 1.0B NUMBER: SHEET FA -031J '41% 17 -14., -- ----------- UI IT: F - Cr.". [1 000 ABERCROMBIE „rvi - .11 4-, Co Z GALLEHE wE ST ELM "I 570 I 55C NORTH 1020 MARINER S -FE A M SH OP \AI PACIFIC SUNWEAR 1-1 ^-7 14j- ----- 1545] [al El P THE 'y'VALKING CO. 11001 Bebe 1110' COACH 111151 cr, 11"1535 CO rl- a. ELECTRICAL ROOM RAm BF:E \A; Z -.ECA MEXICAN.] NA AC GRI I.. L.. C A ,Jr:0 RNIA 0177 /\ R1 1 RECYCLING STORAGE KITCHEN 0 limi 1111:11 I iii Mil LOAD:NC DOCK r • ------ 15701 SUNGLASS HUT 1115 WESTFIELD SOUTHCENTER MALL 1125 17.,,T) L. SYSTEM CALCULATIONS 11 F CI --1 A "_; 2 1 vi UI 1135 [1140 Lu < C) LC n, "R33 SCALE 1132':V EX RISER DIAGRAM nz, F F BATTERY SIZING CALCULATION GUESS Notification Appliance Circuit MALL GUESS , FACP ADD ONS DESCRIPTION SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: Panel: GUESS Wire Resistance 1.62 5/15/08 Date: May 14, 2008 CURRENT TOTAL= 901 CIRCUIT: S1 Current Load: Standby: Alarm: Current Load: Device Type Alarm Current Alarm Total Standby: Alarm: Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.62 2 SET -MC @30CD 98 Device Type Qty Amps Total Amps Total 1 Device Type I Qty Amps Total Amps Total Total Device Load, Amps (1) HFP-11 2 SET -MC @110CD 0.0022 0.0022 0.0023 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 AD2-P 2 0.0635 0.0635 0.064 0.128 445 0 Main System Board 1 0.03 0.03 0.030 0.030 SET -HMC @135CD HTR -R 0 3 0.009600 _ 0.0096 0.021 0.063 EOL Voltage 19.84 SET -MC @15CD , i 445 0 0.064 HTRI-D 1 0.001600 64 0.0035 SET -MC @30CD 2 0 Z-MC@30CD 0.098 0.196 ICP -B6 0.005 0 SET-MC-CM110CD 233 'SET -MC @75CD 1 19.842425161 901 0.175 0.175 6 TOTAL m A= 901 12 191 SET -MC @110CD 2 0.233 0.466 PROJECT: WESTFIELD SOUTHCENTER MALL SET-HMC-C@115CD Panel: GUESS Wire Resistance 2.58 0.318 Date: May 14, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT SET -HMC C@135CD 0.318 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length 0.0731 Amps 0.191 Amps ' SET-HMC-C@185CD 70.7V 1/8 1.8 9 0.445 Total Wire Resistance (R)0.99 0 0 0 ZR -MC @15CD 1 0 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @30CD 0.098 0 Alarm Current Load: 0 0.191 Amps For 5 Minutes= 0.016 Amp -hours Voltage Drop HCP 0.01 0 0 0 0.0015 (E= 1* R) 0 0.03 Amps 0.931 Amps EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 25% Derating= 2.213 Amp -hours Current Load: 0 0.03 Amps 0 For 24 Hours = 0.720 Amp -hours DE\ACES= 5 TOTAL mPt= 9 14 ..,Standby 20.39112996 Total System Current Load: 2.213 Amp -hours Alarm Current Load: 0.931 Amps For 5 Minutes= 0.078 Amp -hours 25% Derating= 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail , DESCRIPTION SHOP DRAWINGS PROJECT: Panel: GUESS Wire Resistance 1.62 5/15/08 Date: May 14, 2008 CURRENT TOTAL= 901 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wre Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.62 2 SET -MC @30CD 98 196 ( WL * 2 )* (R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (1) 0.90 2 SET -MC @110CD 233 466 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.56 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.84 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CM110CD 233 0 19.842425161 901 DEVICES= 6 TOTAL m A= 901 12 191 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: GUESS Wire Resistance 2.58 Date: May 14, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 5 70.7V 1/8 1.8 9 Total Wire Resistance (R)0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load Amps (1) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.01 0 0 0 (E= 1* R) 0 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 0 0 0 DE\ACES= 5 TOTAL mPt= 9 14 191 20.39112996 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 ‘CALE: 1 /8" = 1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: \....,JOB NUMBER: SHEET FA -04 .1 576 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-333 08-S-263 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Sunglass Hut 576 Southcenter Mall Permit No.: 08-S-263 Date: June 4, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/z inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. SiCo SG t 1, SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 WATER SUPPLY DATA SOURCE NODE TAG SRC STATIC PRESS. (PSI) 140.0 RESID. PRESS. (PSI) FLOW AVAIL. TOTAL @ PRESS. @ DEMAND (GPM) (PSI) (GPM) REQ'D PRESS. (PSI) 20.0 10900.0 138.8 900.9 89.5 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE TOTAL HOSE STREAM ALLOWANCE AT SOURCE OTHER HOSE STREAM ALLOWANCES TOTAL DISCHARGE FROM ACTIVE SPRINKLERS NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE (FT) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 S14 M1 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 10.0 10.0 10.0 11.0 11.0 11.0 11.0 11.0 11.0 8.0 10.0 11.0 11.0 11.0 14.9 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 K= 5.60 HOSE STREAM 900.9 GPM 250.0 GPM 262.1 GPM 388.8 GPM PRESSURE (PSI) 22.8 23.0 23.9 24.7 28.0 24.8 25.1 26.1 28.2 24.4 24.7 25.3 28.0 27.8 21.6 22.1 23.0 23.6 27.3 24.3 24.0 24.9 27.5 24.0 23.3 24.8 27.3 27.0 28.4 DISCHARGE (GPM) 26.0 26.3 26.8 27.2 29.3 27.6 27.4 28.0 29.4 27.5 27.0 27.9 29.3 29.1 262.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) M2 14.9 - 28.6 M3 14.9 - 29.0 CAP 14.9 - - 29.4 TIE 14.9 - 34.8 6067 1.9 86.5 5696 1.9 86.5 6021 1.9 86.6 6176 5.7 - - - - 85.1 - - - SRC -4.0 SOURCE 89.5 650.9 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALL'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -26.0 1.049 PL 9.00 PF 3.4 S1 10.0 5.6 21.6 26.0 9.7 120 FTG ET PE -2.1 1 14.9 0.0 22.8 0.0 0.211 TL 16.00 PV Pipe: 2 -26.3 1.049 PL 7.00 PF 3.0 S2 10.0 5.6 22.1 26.3 9.8 120 FTG ET PE -2.1 2 14.9 0.0 23.0 0.0 0.216 TL 14.00 PV Pipe: 3 -26.8 1.049 PL 6.50 PF 3.0 S3 10.0 5.6 23.0 26.8 10.0 120 FTG ET PE -2.1 3 14.9 0.0 23.9 0.0 0.224 TL 13.50 PV Pipe: 4 -27.2 1.049 PL 4.88 PF 2.7 S4 11.0 5.6 23.6 27.2 10.1 120 FTG ET PE -1.7 4 14.9 0.0 24.7 0.0 0.230 TL 11.88 PV Pipe: 5 -29.3 1.049 PL 3.88 PF 2.3 S5 11.0 5.6 27.3 29.3 10.9 120 FTG T PE -1.7 5 14.9 0.0 28.0 0.0 0.263 TL 8.88 PV Pipe: 6 -27.6 1.049 PL 4.88 PF 2.1 S6 11.0 5.6 24.3 27.6 10.3 120 FTG 2E PE -1.7 6 14.9 0.0 24.8 0.0 0.237 TL 8.88 PV Pipe: 7 -27.4 1.049 PL 4.88 PF 2.8 S7 11.0 5.6 24.0 27.4 10.2 120 FTG ET PE -1.7 7 14.9 0.0 25.1 0.0 0.233 TL 11.88 PV Pipe: 8 -28.0 1.049 PL 4.88 PF 2.9 S8 11.0 5.6 24.9 28.0 10.4 120 FTG ET PE -1.7 8 14.9 0.0 26.1 0.0 0.242 TL 11.88 PV Pipe: 9 -29.4 1.049 PL 4.88 PF 2.3 S9 11.0 5.6 27.5 29.4 10.9 120 FTG 2E PE -1.7 9 14.9 0.0 28.2 0.0 0.265 TL 8.88 PV Pipe: 10 -27.5 1.049 PL 10.38 PF 3.4 S10 8.0 5.6 24.0 27.5 10.2 120 FTG 2E PE -3.0 10 14.9 0.0 24.4 0.0 0.234 TL 14.38 PV S11 11 Pipe: 11 -27.0 1.049 PL 8.38 PF 3.5 10.0 5.6 23.3 27.0 10.0 120 FTG ET PE -2.1 14.9 0.0 24.7 0.0 0.227 TL 15.38 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 12 -27.9 1.049 PL 3.88 PF 2.1 S12 11.0 5.6 24.8 27.9 10.4 120 FTG T PE -1.7 12 14.9 0.0 25.3 0.0 0.241 TL 8.88 PV Pipe: 13 -29.3 1.049 PL 3.88 PF 2.3 S13 11.0 5.6 27.3 29.3 10.9 120 FTG T PE -1.7 13 14.9 0.0 28.0 0.0 0.263 TL 8.88 PV Pipe: 14 -29.1 1.049 PL 5.88 PF 2.6 S14 11.0 5.6 27.0 29.1 10.8 120 FTG 2E PE -1.7 14 14.9 0.0 27.8 0.0 0.260 TL 9.88 PV Pipe: 15 -26.0 1.610 PL 8.00 PF 0.2 1 14.9 0.0 22.8 0.0 4.1 120 FTG ---- PE 0.0 2 14.9 0.0 23.0 0.0 0.026 TL 8.00 PV Pipe: 16 -52.3 1.610 PL 8.79 PF 0.8 2 14.9 0.0 23.0 0.0 8.2 120 FTG ---- PE 0.0 3 14.9 0.0 23.9 0.0 0.096 TL 8.79 PV Pipe: 17 -79.2 1.610 PL 3.88 PF 0.8 3 14.9 0.0 23.9 0.0 12.5 120 FTG ---- PE 0.0 4 14.9 0.0 24.7 0.0 0.206 TL 3.88 PV Pipe: 18 -106.4 1.610 PL 2.38 PF 3.7 4 14.9 0.0 24.7 0.0 16.8 120 FTG T PE 0.0 M1 14.9 H.S. 28.4 262.1 0.356 TL 10.38 PV Pipe: 19 -29.3 1.610 PL 3.96 PF 0.4 5 14.9 0.0 28.0 0.0 4.6 120 FTG T PE 0.0 M1 14.9 H.S. 28.4 262.1 0.033 TL 11.96 PV Pipe: 20 -27.6 1.610 PL 10.00 PF 0.3 6 14.9 0.0 24.8 0.0 4.4 120 FTG ---- PE 0.0 7 14.9 0.0 25.1 0.0 0.029 TL 10.00 PV Pipe: 21 -55.0 1.610 PL 10.00 PF 1.1 7 14.9 0.0 25.1 0.0 8.7 120 FTG ---- PE 0.0 8 14.9 0.0 26.1 0.0 0.105 TL 10.00 PV Pipe: 22 -83.0 1.610 PL 3.00 PF 2.5 8 14.9 0.0 26.1 0.0 13.1 120 FTG T PE 0.0 M2 14.9 0.0 28.6 0.0 0.225 TL 11.00 PV Pipe: 23 -29.4 1.610 PL 5.00 PF 0.4 9 14.9 0.0 28.2 0.0 4.6 120 FTG T PE 0.0 M2 14.9 0.0 28.6 0.0 0.033 TL 13.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 24 -27.5 1.610 PL 9.67 PF 0.3 10 14.9 0.0 24.4 0.0 4.3 120 FTG ---- PE 0.0 11 14.9 0.0 24.7 0.0 0.029 TL 9.67 PV Pipe: 25 -54.5 1.610 PL 5.33 PF 0.6 11 14.9 0.0 24.7 0.0 8.6 120 FTG ---- PE 0.0 12 14.9 0.0 25.3 0.0 0.103 TL 5.33 PV Pipe: 26 -82.4 1.610 PL 9.00 PF 3.8 12 14.9 0.0 25.3 0.0 13.0 120 FTG T PE 0.0 M3 14.9 0.0 29.0 0.0 0.222 TL 17.00 PV Pipe: 27 -29.1 1.610 PL 4.00 PF 0.1 14 14.9 0.0 27.8 0.0 4.6 120 FTG ---- PE 0.0 13 14.9 0.0 28.0 0.0 0.032 TL 4.00 PV Pipe: 28 -58.3 1.610 PL 1.00 PF 1.1 13 14.9 0.0 28.0 0.0 9.2 120 FTG T PE 0.0 M3 14.9 0.0 29.0 0.0 0.117 TL 9.00 PV Pipe: 29 -397.8 4.260 PL 5.88 PF 0.2 Ml 14.9 H.S. 28.4 262.1 9.0 120 FTG ---- PE 0.0 M2 14.9 0.0 28.6 0.0 0.036 TL 5.88 PV Pipe: 30 -510.1 4.260 PL 8.00 PF 0.5 M2 14.9 0.0 28.6 0.0 11.5 120 FTG ---- PE 0.0 M3 14.9 0.0 29.0 0.0 0.057 TL 8.00 PV Pipe: 31 -650.9 4.260 PL 4.42 PF 0.4 M3 14.9 0.0 29.0 0.0 14.7 120 FTG ---- PE 0.0 CAP 14.9 0.0 29.4 0.0 0.089 TL 4.42 PV Pipe: 32 -650.9 4.260 PL 34.75 PF 5.4 CAP 14.9 0.0 29.4 0.0 14.7 120 FTG T PE 0.0 TIE 14.9 0.0 34.8 0.0 0.089 TL 61.05 PV Pipe: 33 -650.9 4.260 PL 346.01 PF 46.0 TIE 14.9 0.0 34.8 0.0 14.7 120 FTG 172.2 PE 5.6 6067 1.9 0.0 86.5 0.0 0.089 TL 518.21 PV Pipe: 34 -650.9 8.329 PL 1.50 PF 0.0 6067 1.9 0.0 86.5 0.0 3.8 120 FTG ---- PE 0.0 5696 1.9 0.0 86.5 0.0 0.003 TL 1.50 PV Pipe: 35 -650.9 8.329 PL 19.40 PF 0.2 5696 1.9 0.0 86.5 0.0 3.8 120 FTG 32.0 PE 0.0 6021 1.9 0.0 86.6 0.0 0.003 TL 51.40 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 36 -650.9 10.020 PL 20.17 PF 0.1 6021 1.9 0.0 86.6 0.0 2.6 120 FTG 67.0 PE -1.6 6176 5.7 0.0 85.1 0.0 0.001 TL 87.17 PV Pipe: 37 -650.9 10.400 PL 113.08 PF 0.2 6176 5.7 0.0 85.1 0.0 2.5 140 FTG 137.1 PE 4.2 SRC -4.0 SRCE 89.5 (N/A) 0.001 TL 250.18 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 4903012830 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.105 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 16.8 ft/sec at pipe 18. (4) PIPE FITTINGS TABLE Pipe Table Name: MOST.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v NPTee 8.329 22.16 43.09 16.00 55.40 14.77 4.92 38.16 38.16 43.09 10.020 22.00 50.00 16.00 55.00 19.00 5.00 37.00 37.00 50.00 10.400 26.37 59.94 19.18 65.93 22.78 5.99 44.35 44.35 59.94 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 PAGE: A MATERIAL: SCH.40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C • B G A D F Ell Tee LngEll ChkVly BfyVly GatVly A1mChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 1.049 2.00 5.00 2.00 5.00 6.00 1.00 17.00 23.00 1.00 0.50 0.30 1.00 6.00 5.00 9.00 0.00 1.610 4.00 8.00 2.00 9.00 6.00 1.00 17.00 23.00 2.00 1.00 0.50 1.00 8.00 6.00 12.00 0.00 PAGE: B MATERIAL: SCH.10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D F Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11 H Q I S U V W 22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT 4.260 13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60 3.30 1.60 1.30 18.40 11.90 31.60 0.00 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 5/30/2008KS 7945 SGH 4422\CALCULATIONS\HYDRAULIC CALC'S\SGH4422.SDF JOB TITLE: Sunglass Hut #4422 E ai a) 1 tr)i rn a H CT I0 m U U o rn • o o r C o W m u) o R, as oU N ch 04 N gW A • o ami Q, i 4 i_wH• op ,-1�c0ncn a.-1 rt o b' • Y m a1 m • -H < Ham 4 co tat I o %/ %/ o o ,--i (N N U) O O o 0 rl a 'R w m m R w ¢, U] -H O O d' N N O 0 0 0 O CO 10cri 0 0 0 H 0 0 rn o 0 co ao O _ o N N O 0 In 0 0 .44.44 0 0 M 0 _0 N N O 0 N PO O O -41 O a TOLCO Pio. LNIVJSRSAL &JAY DRAG! PITTIN4 TOLCO Plb. ta0 tNIVEIRSA1. SHAY DR4CL! PITTNER " • •' •• •,sal.•' TOLCO PiPU CLAMP PIe3L 48. 0214' PIPE AND LAMER) PIl6. 4 CP PiPS AND 01A4.1xv LONGITUDINAL E3RACE MT8 ' ICWOC DOLT ORM MiN. 6' 1' ) LATERAL BRACE (2" PIPE 4 SMALLER) N1 MALL CONCOU1�(y Toixo LANNUR8r8t. SWAY DRACl! PITTINS •• 41. i; ►•' •,•,• TOI.CO PIER. 1001 PAST CLAMP • ° KWBC DOLT ativ LATERAL !RACE (21/2" PIPE 4 LARGER) MT9 I AAmoco .3e �3/a X U2 L.4 SCRD J POR WOOD 9- 1/4" =DC COLT POR C WCRETU i/4 X I TOM POR BARJOIST OR 8T1eE1. SRAM 9/8'x4-40 ALL T.RRAD ROD MAIC FSR &WHIR IRDEMTRAINT WHERE LENSTH OP ALL. THREAD IIXOSHOs P-10" ADD MONO =STRAIN? 14ANS1213 RIMS (UP TO 2" PIPIT) LiNE RESTRAINT DETAIL NOTE: 1) SPACE WiTH 1N 6" OF A HANGER EVERY 42'-0". 2) BRACING PER NPPA-13(21 1 ed.) :SECTIONS 9.3.6.8.8, TABLE 3.3.5.8.8(c) AND .93.6-RESTA(NT OF BRANCH LiNES SYMBOL =X 331_0II 151_311 101 -,/hll 2 I vwZ ADJ TE i'-1 ' I 1112 CENT 2 -1Z 5I_/ryxll 41_311 31_0" 41 Ell�I'f% %ii77 ;fay rire DIRE SPRINlit.ER PIPING PIAN SCALE: 1/4"=1'-0II PIPE ROD SIZE DIA I' 3/8' I U4' 3/8' I I/2' 3/8' 2' 3/8• 2 I/2' 3/8' 3' 3/8' 4' 3/8' b' U2' 8' 1/2' HILTI FIG LH OR TOLCO FIG 200 HANGER RING 0 04/2001 COSCO STANDARD HANGER 2 ADJACENT TENANT TYPI AL H MM 11141314: I' MD ISI' PP114•1' CAT W-3' ALP IIt1VATiON) II!' PP321'-6It' GU FAUN FCU ALL OMR 1U3I1H6 UL HILTI KWIK BOLT TZ ANCHOR ICC REPORT #ESR -1917 MIN OF 3.000 PSI CONCRETE MIN 3 U4' CONCRETE OVER MAX 3' METAL DECK 3/8' ANCHOR w/20# TORQUE: TENSION395#. SHEAR.750# U2' ANCHOR w/40# TORQUE: TENSION'.440#.SHEAR=750# I/2' MIN N ROD COUPLING THREADED ROD PIPE ROD SiZE DIA I' 3/8' 1.25' 3/8' 1.5' 3/8' 2' 3/8' 2.5' 3/8' 3' 3/8' 4' 3/8' b' 1/2' 8' 1/2' BOLT LGTH 7' 7' r 7' 7' 7' 7' 7' IMBED DEPTH 2 I/4' 2 1/4' 2 1/4' 2 1/4' 2 1/4' 2U4' 2 1/4' 2 1/4' 2 1/4' • HILTI FIG LH OR TOLCO FIG 200 HANGER RING 0 04/2007 I COSCO STANDARD HANGER I 13 MDLH HYDRAULIC DESIGN—REMOTE AREA SUNGLASS HUT 4422 - ENTIRE TENANT SPACE ORDINARY HAZARD GROUP 2 .20 GPM/1500 S.F. K=5.6. 130 S.F. MAX. PER HEAD 14 SPRINKLERS DISCHARGING iN REMOTE AREA SYSTEM DEMAND: 900.9 GPM C 89.5 PSI Tot. TOLCO FlG. 25 SURGE RESTRAINER TYPE 1 - FOR 1" AND 1-1/4" PIPE AND HANGER TYPE 2 - FOR 1-1/2" AND 2" PIPE AND HANGER TOLCO FiG. 25 IS DESIGNED TO BE USED ONLY WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA TO. RESTRAIN THE UPWARD MOVEMENT OF PIPE AS iT OCCURS DURING SPRINKLER HEAD ACTIVATION OR SEISMIC ACT ITY FiGURE 2a SURGE RESTRAINER FOR STEEL OR CPVC PLASTIC PIPE FI E SPRINKLER SYME5OL. Leamt\ID C. LONGITUDINAL SWAY BRACE LATERAL. SWAY BRACE BRANCHLINE RESTRAINT PIPE HANGER PIPE ELEVATION AFTER FLOOR CEILING ELEVATION AFTER FLOOR HYDRAULIC NODE . PENDENT/CONCEALED SPRINKLER TYPICAL DROP TO SPRINKLER HEAD GENERA.. NOTBS 1 1/2" BRANCHLINE �11-/}SII "FLEXHEAD" FLEXABLE DROP CORRUGATED STAINLESS STEEL BRAIDED HOSE ADJUSTABLE HUB MOUNTING BRACKET TYPICAL DROP TO SPRINKLER HEAD IN AC TILE CEILINGS 2. 3. 4. s. 6. '1. a 10. Ii. 10. DESIGN AND INSTALLATION SHALL CONFORM TO NFPA PAMPHLET 13 AND CITY OF TUKWiLA FiRE DEPT. REQUIREMENTS ALL MATERIALS SHALL BE NEW AND U.L. APPROVED. PIPE: ALL PIPE 2" AND LARGER TO BE SCHEDULE 40 BLACK STEEL. ALL PiPE 21" AND LARGER TO BE SCHEDULE 10 BLACK STEEL. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE STAR BRAND DUCTILE IRON. PAINTING OF PiPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. ALL ELECTRICAL WIRING AND CONDIUT iS BY OTHERS. - ALL WELDING TO CONFORM WITH AWS 010.41 AND WILL BE PERFORMED N COSCO'S SHOP. IT IS THE BUILDING OWNERS RESPONSIBILITY TO KEEP ALL AREAS WITH WET SPRINKLER SYSTEMS HEATED TO A MINIMUM 40 DEGREES FAHRENHEIT TO PREVENT FREEZING OF PIPES. OWNER iS RESPONSIBLE TO ASSURE THAT STRUCTURE AS iT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PiPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PiPING LOADS. COSCO ASSUMES NO RESPONSIBILITY, EiTHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FiRE PROTECTION. UNDERGROUND CONTRACTOR SHALL FLUSH THE UNDERGROUND AND PROVIDE C0500 WITH THE PROPER CERTIFICATE OF DOING. SO BEFORE COSCO WILL CONNECT TO THE UNDERGROUND PIPE. SPRINKLER HEADS ARE DESIGNED TO BE IN CENTERLINE OF CEILING TILE (+/- 1"). ALL DIMENSIONS ARE TO CENTERLINE OF PiPE. 0 Wiitlthout Cor MM ntt As acted In Red Per The Attached Letts, i nese plans have been r evi, t.!ved by The Tul- ,,: i Fire Prevention Bureau ' lr corif irmance wi ll current city standards. AcCi:;. .nc;, is !,..Lit:;ect to errors cod omissions wnich do i'ot authorize vioit9t ons of opted 4 standards and orinncances. i he respc.in.t t1'Qy for the adaqua-cy ot.'Jorh,n re;is tot; liy with tree designer. -Addition.S, r3, -,;;,+ions, or rivi$ioliri tht. c clrawirigs atter ;this d%3C' will vov t -3 11,:o.`j,t_i00r; SI rid will rt +.hire a x resubmittal of rW;/Is' Ur.),:/winos for uubr.K.,t.{tur rrt approval. 0 Y I, Final acceptdnee is outlject to field teat Yid Inspection by 1 The Tukwila Fire Prevention Bureau. A Date: (0' 7\ - Oi By' L WEST RISER ROOM -PLAN ViEW RLE COPY TENANT SPACE TUKWiLA FIRE DEPARTIVLENI Please call: 575-4407 and give this job No. 0S -S e1) ani exact address for shuts -Lown or restoration approval. KAY PLAN NO SCALE CEIUNG -— Awiti WnatR,I/.�LLC West REVISIONS NO. DESCRIPTION DATE BY SPRINKLER HEAD LEGEND: SYMBOL S/N ORIFICE NPT K -FACT. HEAD FINISH PLATE FINISH TEMP. QUAIV. RELIABLE MODEL G4A OR CONCEALED PENDENT • R5415 1/2' 1/2'. 5.6 BR WH 165° 14 APPROVALS BY: CITY OF TUKWiiA I TOTAL SPRINKLERS THIS SHEET 14 ••0 G 0 *•• ••® 0010•• Fire Protection COSCO FIRE PROTECTION AND LIFE SAFETY SPECIALISTS WASHINGTON OFFICE www.coscofire.com 15000 Woodinville -Redmond Rd NE . License No: Woodinville, Washington 98072 COSCOFP1IONM call (425) 686-8300 • fax (425) 827-4784 SAN DiEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE PRO C *: SUNGLASS. HUT #4422 633 SOUTHCENTER MALL STE 576 SEATTLE, WA. 98188 CONTRACT Nth TURNER BUSCH CONSTRUCTION 214 STATE ST HACKENSACK, NJ. 07601 2003 IUi�L�/i13 Fire DRAWING TITLE FIRE SPRINKLER TENANT IMPROVEMENT #/5-.3°° DIATE : 05-29-08 SCALE : 1/4" = l'-Ot' DRAWN BY : T.N.RHODES JOB' 5 KS 7945 SHEET NO. 1 of 1 SUNGLASS HUT 1115 FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \Ulv 3ER SHEET TITLE FA -01 SYSTEM I N FO R VIATI O FA -02 TYPICAL DETAILS - WIRI\G AND MOUNT! \G FA -03 FIRE ALARM SYSTEM FLOOR PLA\ FA -04 SYSTEM CALCULATIONS (GE\ ERAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, 8c OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SMALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES, IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) ..WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Q C ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FETID WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. A.F.F. ABOVE FINISHED FLOOR N/A :N/A c N/A VERIFY IN FIELD N/A C FURNISHED BY N/A N/A Without Coglnents N/A r 'Diu. OTHERS WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D H P S A V I X UD UI M B DATA LINE -ADDRESSABLE LOOP DOOR HOLDER POWER - 24VDC DEVICE POWER - 24VDC STROBE CIRCUIT - FEED ANNUNCIATOR SPEAKER CIRCUIT - FEED REMOTE INDICATION LIGHT LOW LEVEL AUDI❑ UNDERGROUND DATA UNDERGROUND INITIATION DOOR HOLDER POWER BEAM DETECTOR POWER TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) TWO #14 ' FPL/FPLR RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWO #18 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWO #14 FPL/FPLR RED (JACKET) N/A a Per The Atned Letter N/A CONDUIT FILL CHART U.O.N. NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-12" .82 SQUARE INCH 2' 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED: NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, 8c OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SMALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES, IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) ..WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 1 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING ® DUCT SMOKE D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE (CEILING MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (WALL MOUNT) SET -MC -CW SIEMENS SET -MC -W SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. 4S DEEP BOX W/ 1-1/2" EXT. CEILING 80" A.F.F. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM © STROBE (WALL MOUNT) FIRE ALARM SPEAKER (CEILING MOUNT) Q C ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. SET -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. CEILING FETID WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) MR MULTI -VOLTAGE CONTROL RELAY SET -W SIEMENS SET -S17 -WP SIEMENS MR -201 /C AIR PRODUCTS 4S DEEP BOX W/ 1-1/2" EXT. 80" A.F.F. TO BOTTOM MT -SUR -BOX 1/2" PIPE VERIFY IN FIELD 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTI❑N BOX F.B.O. A.F.F. ABOVE FINISHED FLOOR N/A :N/A c N/A VERIFY IN FIELD N/A C FURNISHED BY N/A N/A Without Coglnents N/A r 'Diu. OTHERS I' -171i As Noted In Red N/A NOT APPLICABLE N/A N/A a Per The Atned Letter N/A i nese plans have been reviewed by The Tukwila Fire U.O.N. UNLESS OTHERWISE NOTED N/A Prey ntion Bureau for conformance with current city stgileards. Acceptance is'.r6 ct to errors and ' N/A nmissinns which do not authorize violations of adopted WP WEATHERPROOF DEVICE N/A sismaras and orainances.NT,h responsibility for thit adequacy of design rests totally with the designer. Additions, dpiptinns or revisions to these drawings after RED AS BUILT ADD OR CHANGE N/A VAate will void this.accepr�ce and will require a resubmittal�t� of revised drawings for subsequent app its. GREEN AS BUILT REMOVE N/A FjRi,aAacceptance is subjecNtNietd test and inspect* Of The Tukwila Fire, Prevention Bureau. BLUE AS BUILT NOTES TO CAD N/A /7 00 Efy • 00 , ID? TUKWILA FIRE DEPARTMw.1J,, Please call: 575-440Z and give this job No.O and exact address for shut* iown or restoration approval. AID JUN 12 200 Tukwila rC�i6 1vj6 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved rS z z cc 14cz 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-1+990 TEL. (206) 622-6545 RELEASE CO w z DESCRIPTION SHOP DRAWINGS w 0 co 0 Ln N 0 C J c T c0 T Q I -D EL98 w o Z zz 2 w= Cn _ ©C W 0 tx z Ci SCALE: 1/8" =1 ' DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: SOB NUMBER: C AE FO1 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE FROM XLS CONTROL PANEL OR i+ PREVIOUS ADDRESSABLE DEVIL STOP IF LAST DEVICE END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH 0 DUCT DETECTOR L❑CATION LID GROUND___() © © HTRI—R OSTATUS LED 00 0 N.O. N 0 CO 0 J_ COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX, - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING- \ TUBE \ AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE {(+) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE () RELAY CONTACTS (4.OA @ 125VAC) (4.OA @ 30VDC) 27 VDC 3,5 r1A DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST .25 SEC. TO GUARANTEE. DETECTION, 0 It QI TB1 5 5 0 0 0 0 123456 HCP TB2 o 654321 J END OF LINE DEVICE 0 0 (3.6K 1/4W) SUPERVISED , SWITCH / GROUND ' NOTE: © © HTRI—D 1110 STATUS LED CO 0 0 0 NOT USED END OF LINE DEVICE 3.6K 1/4W) 0 UPERVISED 1 SWITCH FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC cilop PAD-3 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - I— uuu m m o e a o am 24K (1 TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 f FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 0 el— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS IW EOL II • INPU , + 9 9 TEM -1 0 J MO1 q400 F '.O =000 0 IMC 0 COI TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL FROM REMOTE r POWER SUPPLY L ('S' CABLE) FROM FACP <V❑ICE CIRCUIT) ('V' CABLE) SCALE NM EARTH GROUND --)•(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE +) ) STROBE SPEAKER (+) (-) ( STROBE-) (STROBE) SPEAKER SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4SDEEP BOX W/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE:NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE OR END OF LINE NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER61JN TEMPERAIU +32' F (0 C) TO 100' F 38' C) HUMIDITY: 0-9333333 E % RELATIVE HUMIDITY, NON -CONDENSING HFI' -11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE• DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR MR VOLOCITY APPUCATIONS OF 300-4000 FT,4AIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE F ( ) DATA OUT 1 (+) DATA OUT Jj CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID ----\ HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE / 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX-- MOUNTED OX•----MOUNTED ON \ CEILINGI FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE "---- SUSPENDED ILLUMINATED CEILING DO NOT IN ADDRESSA' DEVICES U PREPROGRAV STALL LE I\ \TIL MED WIT TOATING DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS CO Lu z DESCRIPTION SHOP DRAWINGS L I- < 0 Co 0 0 z C C z z 0 II O 0 co 00 t 0) I— w zo 0 [fir, z L,11= oc =Q -. wcr z ; J �CALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: (SHEET FA -029 NORTH EOL—S1 18.84V 0 L. 1 10'-0" AFF SUNGLASS HUT 1115 WESTFIELD SOUTHCENTER MALL SCALE 118"=1' FLAG 1\0 ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED' BY ELECTRICAL CONTRACTOR. SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL, FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NO INSAL ADDRESSABLE I\ T DEVICES U\TIL PREPROGRAMMED WI DEVICES ADDRESS. ATI\G Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS w aF- 5/15/08 2 CCCC< LC) co co TJ pcp T Q co I— w o I coFz � W Cn CC Uj Cr)Q �w o5 Z �CALE: 1/8"=1' DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 5/ 12/08 BACKROUND PLAN PROVIDED BY: 1.0B NUMBER: SHEET FA -031J '41% 17 -14., -- ----------- UI IT: F - Cr.". [1 000 ABERCROMBIE „rvi - .11 4-, Co Z GALLEHE wE ST ELM "I 570 I 55C NORTH 1020 MARINER S -FE A M SH OP \AI PACIFIC SUNWEAR 1-1 ^-7 14j- ----- 1545] [al El P THE 'y'VALKING CO. 11001 Bebe 1110' COACH 111151 cr, 11"1535 CO rl- a. ELECTRICAL ROOM RAm BF:E \A; Z -.ECA MEXICAN.] NA AC GRI I.. L.. C A ,Jr:0 RNIA 0177 /\ R1 1 RECYCLING STORAGE KITCHEN 0 limi 1111:11 I iii Mil LOAD:NC DOCK r • ------ 15701 SUNGLASS HUT 1115 WESTFIELD SOUTHCENTER MALL 1125 17.,,T) L. SYSTEM CALCULATIONS 11 F CI --1 A "_; 2 1 vi UI 1135 [1140 Lu < C) LC n, "R33 SCALE 1132':V EX RISER DIAGRAM nz, F F BATTERY SIZING CALCULATION GUESS Notification Appliance Circuit MALL GUESS , FACP ADD ONS DESCRIPTION SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PROJECT: Panel: GUESS Wire Resistance 1.62 5/15/08 Date: May 14, 2008 CURRENT TOTAL= 901 CIRCUIT: S1 Current Load: Standby: Alarm: Current Load: Device Type Alarm Current Alarm Total Standby: Alarm: Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.62 2 SET -MC @30CD 98 Device Type Qty Amps Total Amps Total 1 Device Type I Qty Amps Total Amps Total Total Device Load, Amps (1) HFP-11 2 SET -MC @110CD 0.0022 0.0022 0.0023 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 AD2-P 2 0.0635 0.0635 0.064 0.128 445 0 Main System Board 1 0.03 0.03 0.030 0.030 SET -HMC @135CD HTR -R 0 3 0.009600 _ 0.0096 0.021 0.063 EOL Voltage 19.84 SET -MC @15CD , i 445 0 0.064 HTRI-D 1 0.001600 64 0.0035 SET -MC @30CD 2 0 Z-MC@30CD 0.098 0.196 ICP -B6 0.005 0 SET-MC-CM110CD 233 'SET -MC @75CD 1 19.842425161 901 0.175 0.175 6 TOTAL m A= 901 12 191 SET -MC @110CD 2 0.233 0.466 PROJECT: WESTFIELD SOUTHCENTER MALL SET-HMC-C@115CD Panel: GUESS Wire Resistance 2.58 0.318 Date: May 14, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT SET -HMC C@135CD 0.318 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length 0.0731 Amps 0.191 Amps ' SET-HMC-C@185CD 70.7V 1/8 1.8 9 0.445 Total Wire Resistance (R)0.99 0 0 0 ZR -MC @15CD 1 0 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours 0 ZR -MC @30CD 0.098 0 Alarm Current Load: 0 0.191 Amps For 5 Minutes= 0.016 Amp -hours Voltage Drop HCP 0.01 0 0 0 0.0015 (E= 1* R) 0 0.03 Amps 0.931 Amps EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 25% Derating= 2.213 Amp -hours Current Load: 0 0.03 Amps 0 For 24 Hours = 0.720 Amp -hours DE\ACES= 5 TOTAL mPt= 9 14 ..,Standby 20.39112996 Total System Current Load: 2.213 Amp -hours Alarm Current Load: 0.931 Amps For 5 Minutes= 0.078 Amp -hours 25% Derating= 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 0.998 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail , DESCRIPTION SHOP DRAWINGS PROJECT: Panel: GUESS Wire Resistance 1.62 5/15/08 Date: May 14, 2008 CURRENT TOTAL= 901 CIRCUIT: S1 QTY Device Type Alarm Current Alarm Total Wire Size Wre Length Voltage at EOL Circuit Total 0 SET -MC @15CD 64 0 Total Wire Resistance ( R ) 0.62 2 SET -MC @30CD 98 196 ( WL * 2 )* (R/ft) 1 SET -MC @75CD 175 175 Total Device Load, Amps (1) 0.90 2 SET -MC @110CD 233 466 (Total Cct Load) 0 SET-HMC-C@115CD 318 0 Voltage Drop ( E) 0.56 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.84 0 SET -HMC @185CD 445 0 (20.4 - E) 1 Z-MC@15CD 64 64 0 Z-MC@30CD 98 0 0 SET-MC-CM110CD 233 0 19.842425161 901 DEVICES= 6 TOTAL m A= 901 12 191 Notification Appliance Circuit Detail PROJECT: WESTFIELD SOUTHCENTER MALL Panel: GUESS Wire Resistance 2.58 Date: May 14, 2008 CURRENT TOTAL= 9 CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 5 70.7V 1/8 1.8 9 Total Wire Resistance (R)0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load Amps (1) 0.01 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.01 0 0 0 (E= 1* R) 0 0 0 EOL Voltage 20.39 0 0 0 (20.4 - E) 0 0 0 0 0 DE\ACES= 5 TOTAL mPt= 9 14 191 20.39112996 VOLTAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 5/15/08 ‘CALE: 1 /8" = 1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:5/1 2/08 BACKROUND PLAN PROVIDED BY: \....,JOB NUMBER: SHEET FA -04 .1