HomeMy WebLinkAboutPP - 611 SOUTHCENTER MALL - THINGS REMEMBERED - PERMITS AND PLANS611 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-213 10-S-204 10-S-203 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Francesca's Collection 611 Southcenter Mall Permit No.: 10-S-204 Date: September 20, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. GYP: BD. CLG 10=0" A.F.F. .$GYP. BD. CLG. 141-8 314" A.F.F. MECHANICAL -T ASSEMBLY Style 920 Mechanical -T and Style 929 FIT Outlet/Mechanical-T' AppfO.1 D LISTED pages 107-11 1.as d in listings THE SERV CE INTENDED. REFESUPPLR TO PAGES 8D TO BE RAND 9 IS SUITED FOR ALWAYS LUBRICATE GASKET FOR PROPER COUPLING ASSEMBLY - REFER TO PAGE 8. PIPE MUST LWAYRBEPREFER EPAREG IS ACCO DANCEWITHVICTAULIC0 1. PREPARETO ASSEMBLE: To prepare or assembly, remove one nut and bot rem housing. Loosen the other nut anti t,is Rush with the end of the not remove. Remove the tape and lift the gasket from Mechanical T. 2. CHECK GASKET AND LUBRICATE. Apply a thin coat of.Vlctaullce Lubri- • cant or silicone lubricant to all surfaces of the,gasket This is essential ttiinsure proper sealing. Other compatible lubri- cants may be used, however do not use a petroleum base lubricant Reposition gasket Into housing using alignment tabs on sides for properPosl Honing. 3. POSmON MECHANICALT: To as- semble the couprmg on the pie first rotate the lower housing approximately 90 degrees away from the upper hous- ing. Place the upper, or outlet, section on to the face of the pipe In llnewith the outlet hole. Rotate the lower section around the pipe and close the two halves. *See pages 72 & 73 for FIT outlet pipe acsemhly. IttH 4. INSERT BOLT: Insert bolt In Rs hole and finger tighten both nut certain in oval -neck of bolt engagess housing. Make sure that the locating collar Is in the outlet hole. This may be checked by rocking the upper housing In the hole. Also make sure that the positioning lugs are properly aligned. MECHANICAL -T "CROSS" 5. TIGHTEN NUTS: Tighten bolt nuts uniformly until the upper housing is in complete surface contact in the gasket pocket area and the assembly is rigid. Nuts must be tightened to 50lb-ft with even gaps between the bolt pads for Styles 920 and 929. Torque in excess of 50 lb. ft. is not desirable. NOTE: Increased bolt torque will not improve sealing. RIM STYLE 920 - . MECHANICAL -To PERFORMANCE DATA Cross connections can be achieved with Style 920 or 929 Mechanica/TQniy_ by utilizing two Upper Housings of the same size, with the same or differing branch size connections. Assemble as .above, being certain that Locating Col- lar on each side is securely positioned inside the hole. Nuts must be tightened to 50 lb -ft with even gaps between the bolt pads. NOTE Alternate length bolts may be required for certain cross -type combi- nations. Contact Victaulic for details. IMPORTANT: If branch connection has been made to upper housing prior to Mechanical -T assembly, make certain this connection Is at 90' to n.e prior Io final tightening of Style 920 cc 929 Mechanical -T. When Mechanical -Ts are used as transition pieces between two runs, they must be assembled onto the runs before the branch connections are made. 69 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS STYLE 929 - FIT OUTLET/ MECHANICALT . PERFORMANCE DATA _ Warta` Presod 'SIB nIQ stamina/ See Deegan Tweet she net roe larded Stye Ina 1 Rona Tad Runlet, IL ft Wawa 3s1 ,r1X. a2 SBO so .ria. alit 11 500 50 1255.13 500 50 5.1Y, a. an.. 500 50 ri Re 50 BdX.'.ask Ste 50 13, si SBo 50 11511..5 a AO 50 Cross connections can be achieved with Style 920 or 929 Mechanica/TQniy_ by utilizing two Upper Housings of the same size, with the same or differing branch size connections. Assemble as .above, being certain that Locating Col- lar on each side is securely positioned inside the hole. Nuts must be tightened to 50 lb -ft with even gaps between the bolt pads. NOTE Alternate length bolts may be required for certain cross -type combi- nations. Contact Victaulic for details. IMPORTANT: If branch connection has been made to upper housing prior to Mechanical -T assembly, make certain this connection Is at 90' to n.e prior Io final tightening of Style 920 cc 929 Mechanical -T. When Mechanical -Ts are used as transition pieces between two runs, they must be assembled onto the runs before the branch connections are made. 69 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS STYLE 929 - FIT OUTLET/ MECHANICALT . PERFORMANCE DATA _ Worthrl Pressen Mei Standard/ ear Tee. s. Pipe braked for she Assent!? Res 1 Brand Oetea. MIL 3rltt,ntlk12 175 50 4,115, silk a2 175 50 •eof torque epprc a4 I. bdurnets bene at -T I. m, recesses* al brand to Mkt ate to pees eo s SI- Was! L@ids! belodins gairaiarl esre.d Iwai Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 4 Add Reliable Model Fl Standard Response 155° Pendants IA x 1/2 ', 3 Add Reliable Model G4 Consealed Standard Response 155 pendant 1/2 x 1/2 7 — Total 0. Without Comments Q As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rets totally with the designer. Additions, deletions or revisions to these drawings4kafter. this date will void this acceptance and wiU require a resubmittal of revised drawings for subsequent approval. Final acceptance Is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: O By: IiigliALA FIRE DEPART Please call: 576 - arid give this job No. / `S?e0`i and exact address for shi* down or restoration aooro #e R4' '5 raer CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 P11. (425) 481-7669 PROJECT ADDRESS; 611 SOUTHCENTER MALL TUKWILA, -INA 98188 CLIENT NAME: FRANCESCA'S COLLECTIONS DATE•5 tIG DRAWN: 3 f c, SCALE: at -) . PAID SEP 2 0 2010 TUKWILA FIRE n 14.thOLLA FIRE DEPARTLY i' Please call: 575-446Z sand give this job tta. 3 ar1J exact address for Shut or restoration approxi NCESCA'S COLLECTIONS FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3E SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL WI RING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIO\ S AN D SINGLE LIN E DIAG RAM FA -04 FIRE ALA RN SYSTEM PLA\ SHEET INDEX TE O Without Comments Vii'' As Noted in. Red ❑ Per "alt. Attached Letter These plans have ry.iiievred by The Tukwila Fire Prevention Bureau for co orrnance with current City standards. Accepta{m:. i w inject to errors and omissions which co not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. =Additions, deletions or revisions to these drawingst:after this date will void this acceptance and will require resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau.Al/t1 Date: y � -7 -/ O By: 31% _ IZ L • e --o. rt c�;�' ' - C60Jc- t c i (: Wi-OttA et/6". NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be present to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection. Systems. Failure of test will result in a Re -inspection Fee and termination of the tes,rg. WIRE SCHEDULE A\D CONDUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR - RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE IT IS LOCATED. AND JUNCTION BOXES ENVIRONMENT IN WHICH 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 2 3 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-1 1 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE 4S DEEP W/ 1G RING CEILING ®D DUCT DETECTOR AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING J BOX CTION N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 SYMBOLS LEGEND 1,1 NORDSTROM 3 LEVELS 1 171,275s1 macys 425o 40 sf )1 «A , r = RA, RCS Si C. RAR s.�&EGO VATTIT S LJ IMO CA: �T!vJ 6 CALLA THUIROOS UAR_m RA,AMA UPS ti ThE fJ i Y �. FRANCESCA'S COLLECTION (611 - SPACE #572) iIXYC TOKYO 19110.1. RSC P eniw mist_ G:OGE toss-si KING CffifTY UPS+ Y RFC UEYET! ./EATEERS EXISTING JCPenney J LE'+ELS 276,468sf PAID SEP 3 0 2010 TUKWILA FIRE ..-7b? 7/ 05-0 - 9 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 0 c co (.1 0, 0 I2 «<« 1/ 1 Z 0 0 z Z N O I-Zwooe o ";"0" JEg c„z J Q O 2 "v Q� w �_ cc w� VJ w < w U SI v C� < = W F- CCo ' C`I T W LL (/)H �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved .JOB NUMBER: 55089 } r SHEET k FA -01 , le25II,' 120VAC-60R1 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. PUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR A00111CNAL S'EC61CA110NS SEE PRODUCT DOQNFNTADON. 'CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC illEVE TO NEXT ADDRESSABLE (+ DEVICE STIP IF LAST DEVICE s - FROM Xl D CONTROL PANEL Ct I62 PREVIOUS ADDRESSABLE DEVICE 0 a 0 O —) 44 Ie; I HTRI—R NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE i 6 N L 'XI X a 0 PAD -3 oo LI INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - a a 3.6k EOL (-) (+) SPARE SPARE SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. rn s m s 0 m 0 Fl (=)(-) (+)(+) • (+) Q WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TIPS COLOR CODE TWISTED PAIR WITH SHIELD #18 FPLFPI.R RED(JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30NDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 F L 0 HTRI—R I DRY CONTACTS TO VAV �. FAN SHUTDOWN PROVIDED BY MECH/ELEC. GROUND C\ O 0❑ ❑L 0 _ IPM 0 — v _ 111,11 DESCRIPTION SHOP DRAWINGS Q o 0 oG\ SA Tli o i T F1 t 10 1 6 x •- ..u.ip usurp. " - in ,r1 ,d \+_ ..., . 1: :1:1:111.1.1' CI0 4,711M- to ,v X 7 C LI❑I (-) II (+) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (-) (+)> TO NEXT DEVICE OR (-) STOP IF LAST DEVICE DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER 1 ❑O 0 ❑ v _ 0 — DESCRIPTION SHOP DRAWINGS 0 DATE 0 yy .. xi ��C sua1 o i F1 1 6 x •- ..u.ip I °I! 1:I:l:I:1 I1:I:I. ,r1 ,d o . 0 CI0 4,711M- 1 o��,,,,�❑ STROBE ❑EJDJ CIRCUIT STROBE SPEAKERISTROBE r11:1:1 [1:1:I. STROBE CIRCUIT STROBE CIRCUIT S TO NEXT APPLIANCE OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) (-) SPEAKER CIRCUIT SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. +32' FF (o' C) TO 1W F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HP -11 SMOKE DETECTOR — — FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE tDATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR f--- DB -11 SSMTANDARDOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID --\ CEILING > TO NEXT ADDRESSABLE DEVICE HARD LID ---\\ SPEAKER SUPPORT TILE BRIDGE �— 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N �,-- CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT cip 0 0 ; TO NEXT DEVICE 0 0 CADDY BAR SMOKE/HEAT DETECTOR \\- SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved W y 2 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 09/28/10 o <a«< T 0.. �CALE: NOT TO SCALE - DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55089 i SHEET FA -02 ACIP; AD Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042. HFPT-11 0 0.002200 0 0.0023 0.000 0.0731 Amps 0.106 Amps Curren ' 'oat! Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C (a 15CD 0.0875 SET -MC -C @30CD 3 0.131 SET -MC -C @75CD 0.222 (SET -MC -C @95CD 0.292 SET -MC -C @110CD 0.259 ZR -MC @15CD 1 0.064 0.064 ZR -MC (c 30CD 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.094 Amps Standby Current Load: 0.03 Amps For 24 Hours - 0.720 Amp -hours Alarm Current Load: 0.094 Amps For 5.Minutes= 0,008 Amp -hours 25% Derating= 0.910 Amp -hours Total System Current Load: 0.910 Amp -hours 12VDC. Notification Appliance Circuit Detail PROJECT: FRANCESCA'S COLLECTIONS Panel: PAD -3 POWER SUPPLY Date: September 29, 2010 !Wire Resistance 2.58 CURRENT TOTAL=;2502.00 0 SET -MC -C @15CD SET -MC -C @30CD 0 SET -MC -C @75CD 0 SET -MC -C ©95CD 0 ZR -MC @110CD ZR -MC @15CD _ ZR -MC @30CD ZR -MC 675CD 4 0 DEVIC 87.51 131 222; 292 2591 64 98 175 TOTAL mA=i ;Total Wire Resistance (R ) Total Device Load, Amps (I) Voltage Drop (E) EOL Voltage 9 0 0 64 0 0 457 12 189 23.55 4571 ( WL* 2 )*(R/ft) (Total Cct Load) (E=I*R) 24-E) 0.981 0.46 0.451 23.55 Notification Appliance Circuit Detail PROJECT: FRANCESCA'S COLLECTION Panel: XLS-V Date: September 29, 2010 ;Wire Resistance 2.58 CURRENT TOTAL=1#REF! 18 70.7V.1/8_ 14 70.7V1/4 0 170.7V112 0 70.7V1 DEVICES= 32 32.4 0 . 0 0I 0` 0 TOTAL mA= ITotal Wire Resistance (R ) Total Device Load, Amps (I) (Voltage Drop ( E) EOLVoltage 0 32.4; 14 727 20.27845723 ( WL *. 2_.,), * (R/ft) (Total Cc# Load 1(E=1*R) (20.4-E) 32.4 3.751 0.03' 0.121 20.28 SYSTEM CALCULATIONS TO NEAREST EXISTING DATA LOOP CIRCUIT, VOICE CIRCUIT& POWER SUPPLY SYNC CIRCUIT D,V,V',2C b R S1-1 30cd V-1 1/4-W AHU-1 o-- S,2C BPS 120VAC, DEDICATED , ) (BY OTHERS) S1-2 S1-3 15cd 30cd V-2 1 /4-W S1-4 30cd V-3 1 /4-W EOL S1 c0 ON 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-654.5 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 Z co N C) 0 z a\\\\ 0 W Cl) Z Z cv -J O W FZWc J - U 00ES W < °' Z z J Q J Q CI) O 2 JCD 0 Q Z W( Q - <Cn 'Q oc (II U d6.11g O W w O Cr Li�i e U t° J 0 F- >- 1 \ - omJ\ �CALE: NOT TO SCALE" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \OB NUMBER: 55089 SHEET \ FA -03 TO NEAREST EXISTING DATA LOOP CIRCUIT, VQIbE,CIRCUIT& POWER SC):LY- SG1-'- G YN GI 1.4Fr J• ,2c,V,v:--o EX. 2x4 ACT CLG. 11,-6" V.I.F. PT -2 24' - 0" LEASE LINE .i X•. i.c .;♦ ' atSS,•• X52? ti:.,s':;r t:,'�z.r ,.`,.i ?:�Z�:r` .::a��k'Si •+\=<:t ^Sa: • :s`�.i<. ., y•a;*"." ..aia.::..x�.5c:w.aaw.,.:.+.,:a„•..:,.,�;,:..\�•�,: 'f" L D \. / AHU-1 EX. GYP. f3D. CEILItvG>i 7'-6" PT -2 S` -2 1Scd lbw :�xiJhw�.r;lx,ti..a,, :s.<>`c;.: ic�.sr •.,ra+. U} - 2 '\ Chi NVAl DRESS ROOMS 0 f • S1-8 30cd V1-2 O 1.• 8':O B' - 0". w z w Q w • NV • ....t,.3 GYP. BD. CLG. 12'-0" A.F.F. PT -1 i c:• if. tr-1- 1;"41 b EOL. S r`j 0 a " NEW STRUCTURE GYP. BD, CLG. 14'-3 3/4" A.F.F. PT -1 1 REFLECTED CEILING PLAN 1/4 = 0 0 0 0 GYP: BD. CLG. [T-2 10`-0" A.F.F. GYP. BD. CLG. 14'-S 314" A.F.F. FIRE ALARM SYSTEM PLAN 3. SCHEDULELig-MN (NOT ALL FIXTURES SHOWN) MARK DESCRIPTION LOCATION COMMENTS MARK DESCRIPTION LOCATION COMMENTS Q c7 n TRACK LIGHTING SALES AREA SURFACE MOUNT @ 10'-8„ A.F.F. REFER TO SHEET E2 FOR SPECIFICATIONS. 0 - RESTROOM FAN & LIGHT TOILET ROOMEXISTING TO REMAIN � 6"0 RECESSED CAN LIGHTEXISTING. ENTRY REFER TO SHEET E2 FOR SPECIFICATIONS. 2x2 SUPPLY AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. CE:1) CHANDELIER SALES -CENTER OVER CASH WRAP 90" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. 2x2 RETURN AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. (F) SCONCE SALES- ABOVE DRESSING 84" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. le EXIT LIGHT THROUGHOUT CEILING MOUNTED. REFER TO SHEET E2 FOR SPECIFICATIONS. EMERGENCY LIGHTING STOCKROOM, SALES REFER TO SHEET E2 FOR SPECIFICATIONS. CEILI 1 EYNOT S CENTER CHANDELIER EQUALLY OVER CASH COUNTER. TRACK LIGHTING TYP. SEE E2 FOR DETAILS. RECESSED CAN LIGHTS TYP. SEE E2 FOR DETAILS. NEW 1x4 LIGHT RECESSED. SEE E2 FOR DETAILS. NEW 2x2 ACT CEILING THROUGHOUT SALES AREA. PAINT CEILING, WALLS. GRIDWORK & DIFFUSERS PT -1. NEW SOFFIT. PAINT PT -1. NEW SOFFIT VERTICAL WALL. PAINT PT -1. 17 BOX BEAM OF (2) 8" 18 -GA. STRUCTURAL METAL STUDS. EXISTING CEILING TO REMAIN. PATCH & REPAIR AS REQUIRED WHERE EXISTING STORAGE ROOM WALL WAS DEMOLISHED. EXISTING GYP. BD. CEILING TO REMAIN EXTEND CEILING AS REQUIRED TO MEET NEW WALL LOCATION. MATCH EXISTING STRUCTURE & FINISH. EXISTING CEILING FAN / LIGHT TO REMAIN. ADD ADDITIONAL CEILING AS REQUIRED TO MATCH EXISTING. NEW WALL TO 6" ABOVE CEILING. ATTACHED TO STRUCTURAL JOISTS & BEAMS ABOVE. SEE DETAILS 2 & 3/A1, STORE ENTRANCE AREAS. ALL SPRINKLER HEADS RECESSED WITH COVERPLATES PAINTED TO MATCH THE CEILING COLOR. FIXTURES BELOW. TS10x2x.25" TUBE STEEL BEAM. WELDED TO COLUMNS WITH CLIP ANGLES ON GRID LINE O. 8" 16 -GA. STRUCTURAL METAL JOISTS @ 16" O.C. SET ON & ATTACHED TO 8" BEAMS. THIS AREA TO BE COVERED FROM ABOVE WITH 5/8" FRT TREADED PLYWOOD. CEP4NQ NOTES CEILING SUPPORT SHALL COMPLY WITH SEISMIC BRACING REQUIREMENTS FOR THIS REGION. ALL SUPPORTS ARE ATTACHED FROM THE STRUCTURAL JOISTS & BEAMS ABOVE. DO NOT ATTACH TO DECK. FINISH LEGEND MARK 'DESCRIPTION PT -1 VALSPAR CLR: WHIPPED APRICOT #: 2007-2B INTERIOR SATIN GENERAL LOCATION SALES AREA WALLS & CEILING. PT -2 VALSPAR CLR: SAWYER WHITE #: 7002-16 INTERIOR FLAT STOCKROOM/SOFFIT CEILINGS PT -3 VALSPAR CLR: JECKYLL CLUB VERANDA IVORY 1#: 7003-2 EGGSHELL SIGN BACKGROUND B-1 , VINYL BASE CLR: BROWN 4" STOCK ROOM/SALES I 8-2 1 STOREFRONT BASE 4" CREMA EUROPA TILE BASE STOREFRONT ST -1 MINWAX CLR: EBONY #: 2718 ALL WOOD STAIN GRADE LUMBER. STAIN MINWAX EBONY AND SEAL TWO COATS CLEAR POLYURETHANE. cc 0 O w VCT -1 12"x12" VINYL FLOORING CLR: BEIGE TYPE: -- STOCKROOM TOILET ROOM WF -1 SHAW -HARDWOOD CLR: MAIZE TYPE: VICKSBURG #SW118 4 7/8" RANDOM LENGTH. 1/2" ENGINEERED FLOORING SUPPLIER: FLOOR ZONE - HOUSTON TX. CONTACT JEFF MEGOW (713) 205.6400. SALES WT -1 WALL TILE CLR: CREMA EUROPA STOREFRONT ACT -1 0 USG INTERIORS OR EQUAL TILE: 2`x2'x3/4" MARS, CLIMA PLUS 486785 SLT ("SHADOWLINE TAPERED" EDGE -WHITE GRID: DONN 15116"DX WHITE. 2x2 SALES NOTE: ALL F NISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES. SEE SEC V. ON CODE STUDY FOR MORE DETAILS. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM AS THE PAD -3. TENANT FIRE ALARM JUNCTION BOX (FIELD LOCATE). RELAY MODULE MONITORS PAD -3 POWER SUPPLY. REPLACE AND RELOCATE EXISTING DUCT DETECTOR TO NEW LOCATION. LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m a DESCRIPTION SHOP DRAWINGS DATE 0 aD N 0 W 2 CALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: 55089 SHEET FA -04 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved / 09/20/2010 12:57 4254818695 FAX TRANSMITTAL. CROWN FIRE PAGE 01/01 Fax No. CROWN FIRE PROTECTION, INC. CEE: 9.20.10 Campan'"` Subjec 17, Fire Prevention Bureau Tukwila Fire Department Demo Permit Number of Pages (Including Cover El Urgent FJ For Review Frain: Jessica Robinson 1 0 Please Comment 0 Please Reply [206.575.4439 PH:425.481.7669 FX:425.481.8695 Comment. Please provide a demo permit to remove one fire sprinkler head in the middle of the entry way that is hanging low and is in the way. The project is Francesca' s Collection located at 611 Southcenter Mall. The building permit number is D10201. Thanks :411SW1LA FIRE DEPART N Reese call: 575407 andve this job No..0-S- o3 and exact address for shin -town or restoration aoorniot P.O. BOX 12113 MILL CREEK, WA 98082 PH: 425.481,7669 FX: 425. 481.8695 NCESCA'S COLLECTIONS FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NU1V3ER SHEET TITLE FA -01 SYSTEM INFO MATIO\ FA -02 TYPICAL WRING AND MOU\TI\G DETAILS FA -03 SYSTEM CALCULATIO\S A\D SINGLE LINE DIAGA V1 FA -04 FIRE ALAR V1 SYSTEM PLA\ SHEET INDEX WIRE SCHEDULE A\D CO\DUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vaC POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FAC?. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX EX 1 2 3 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER Ex POWER SUPPLY (EXISTING) PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP ®EX SMOKE DETECTOR. (PHOTO -ADDRESSABLE) XISTING) HFP-11 W/ SIEMENS DB -1 1 BASE 4S DEEP W/ 1 G RING CEILING DUCT DETECTOR AD2-P W/ SIEMENS HFP-1 1 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING JUNCTION D BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND 1 NORDSTROM 3 LEVELS 171,275sf EMES11 CCGr:A macys 4 LEVELS 250,407sf 313 331 } COLD 1Q(Y3 TOKYO £I.5 G1tc�A5'a!D ss CMECl:. MSW CCUIIY LW"RY s.DUEWD XNELE.S El13T!•!G JCPenney 3 LEVELS 276,468sf FRANCESCA'S COLLECTION (611 - SPACE #572) 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 00 0 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 09/28/10 ...... _...... 0 7, 0 7, 0 2a<aa< Z cl O I- z w c T (j)Z J <t J O wcci `� z ci) HQ (/)QZ__ Wwcc 8D' Z cni- cc 111 u_ (.1) 0 CC 0 z ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:09/28/10 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved .10B NUMBER: 55089 J SHEET FA -0 1 120VAC-8O11Z DEDICATED DIERG?ICY'' THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. PUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT 000MNTATION. *CONTACT RATINGS: 4.0A 0125VAC 4.0A 0 30VDC TO NEXT ADDRESSABLE&F DEVICE STOP IF LAST DEVICE MON XLS CONTROL PANEL a OR PREVIOUS ADDRESSABLE DEVICE O 0 J HTRI-R I I ° J� NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE ORD NCI I. U a PAD -3 oo° INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 3.6k EOL L 111 (-) (+) (-) (+) 1 SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) CID NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. Fri r71 C, 0 O� m m o � 0 0 o F^ (2)(-) (+)(+) 0 c m (+) WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIRWITHSHIELD #18 FPLIFRR RED(JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 0 I -c ' I ° 01 I 77 -'I _ � 1 HTRI-R 1 GROUND 0 DRY CONTACTS TO VAV �. FAN SHUTDOWN PROVIDED BY MECH/ELEC. ❑ I1 --r) — 0 I4- ;'f) I / t ID 1 I .L aI I I O O §\ g� ars. .a n. n. , ' 1 1 ' I _ '€iI 4- +- AICAEFC■ " - ,A A.CO Ei011 — AECEEiS■ " ,n I 1 bm 1:1:1:1:1 11:1:1- I:1 I:I:1 I 1:1:11. 1."-- . 1.1 1:1:111:1:1* o 0 .1 11.1 / �1 � �M9■// 0 P • , M Kurc N (• ... no (-) ° (+)>TO NEXT DEVICE OR > STOP IF LAST DEVICE DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER o❑ II ► J-� �'i 0 ;)0 , 1 1 1 1 / t ID 1 iii ri1 O .E.,1 .m.. icy mm. PM a o , ' 1 r€t'/ ' I _ ! 4- +- AICAEFC■ " - ,A A.CO Ei011 — •••-• I 1 bm 1:1:1:1:1 11:1:1- I:1 I:I:1 I 1:1:11. u 1 o 0 .1 11.1 / �1 � �M9■// 0 ❑EIDJ (IHUUIT �a�❑ SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) (-) ❑ISD STROBE CIRCUIT STROBE o❑ ❑o ❑` 0 - 1 1 1 / t a ', y , III rh O .E.,1 .m.. ! �. 1 r€t'/ • I -II 4- ABM i CN " - ,/ft A.CO Ei011 •••-• 111:1:1Ila:1' I:1 I:I:1 I 1:1:11. --; \e 11:117k �$.L.A-M© w•l=::. raril ' . / C71 4 P • , M Kurc N (• ... (-) (-) SPEAKER CIRCUIT (+) (+) on STROBE SPEAKER/STROBE no ❑o 07 o o o _ , I 1 qu t y , J'4. rh O O Ie \ ..a ww ' • I -II - A.CO Ei011 \ 0."--3 I:1 I:I:1 I 1:1:11. --; \e 11:117k �$.L.A-M© w•l=::. raril ' . / 1q= (-) on STROBE (-) n SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER �T1N TEMPERA RE: +32'F (O' C) TO 100' F (35 C) HUMIDITY: 93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN( )> Sl DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID --� CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE 0° o ° °o 000 SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR 1J SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved :410- O F- c 141 g y w :1!I- F - W GO1.1% O cnW FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (4/ J cn CC!S z0 iL?) 2" Z co U o ° oT3 I-- Wt=0°' J o �o O J d _i�_ O LU 2,... o tr_ co Fw < r 1 �(✓ Q W w EC. 8 ZZ CE ,,,SIA 7- CC CC' u_ J U SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55089 C SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 HFPT-11 0 0.002200 0 0.0023 0.000 0.0731 Amps 0.106 Amps Da nc e alc+u' Currin Loan Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C @15CD 0.0875 SET -MC -C @30CD 3 0.131 SET -MC -C ()a 7 C 0.222 ;SET -MC -C @95CD 0.292 SET -MC -C ('7110CD 0.259 ZR -MC @15CD 1 0.064 0.064 ZR -MC @30CD 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.094 Amps Standby Current. Load: 0.03 Amps For 24 Hours 0.720 Amp -hours Alarm Current Load: 0.094 Amps For 5 Minutes 0.008 Amp -hours 25% Derating= 0.910 Amp -hours Total System Current Load: 0.910 Amp -hours Battery Pair to ba Used: _ __. Notification Appliance Circuit Detail PROJECT:1 FRANCESCA'S COLLECTIONS Panes: 3PAD-3 POWER SUPPLY 1 Date: September 29, 2010 Wire Resistance CURRENT TOTAL= 2.58 2502.00 SET -MC -C @15CD SET -MC -C @30CD 0 JSET-MC-C @75CD 0 SET -MC -C @95CD 0 ZR -MC @110CD 1 ZR -MC @15CD 0 ZR -MC @30CD 0 ZR -MC @75CD DEVICES= 4 87.51 131 222 292 2591 64 981_ 175 TOTAL mA= ;Total Wire Resistance (R ) Total Device Load, Amps (1) 'Voltage Drop (E) EOL Voltage 0! 393 0 0 0', 64 01 0 4571 12 189 23.551 457 (WL*2)*(R/ft) (Total Cct Load (E=I*R) 24 - E)..... 0.981 0.46 0.45 23.55 Notification Appliance Circuit Detail PR OJECT:1 FRANCESCA'S COLLECTION Panel:1 XLS-V Date: ! September 29, 2010 18 ........ 14 0 0 DEVICES= 170.7V 1/8 70.7V 1/4 70.7V1/2 70.7V 1 32 1.81 0 0 0 TOTAL mA= 1 'Total Wire Resistance (R ) Total Device Load, Amps (1) Voltage Drop (E ) EOL Voltage !Wire Resistance 2.58 CURRENT TOTAL= #REF! 32.4 0 0 20.27845723 1(WL*2)*(R/ft) (Total Cot Load) 1(E=I*R) (20.4 - E) 32.4 3.75 0.03 0.121 20.28 SYSTEM CALCULATIONS S3-1 30cd V-1 1 /4-W ® EX S BPS 120VAC, DEDICATED , ) EX (BY OTHERS) S3-2 S3-3 15cd 30cd V-2 1 /4-W BGM FAN INTERFACE SHUTDOWN 24-110 24-111 AHU-1 D 24-112 S3-4 30cd V-3 1 /4-W EOL S3 t) 0 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 09/28/10 10/15/10 (J') O U w J -J O U (1) (!) w z CC LL co zz • w co r <55 �z < JO w �z coW< w z� U� W = CC O1_ r T (0 ALE: NOT 1 cr 0 W z J W J z E5 0 z U) z O 0 J U w (i) 1- (1) TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \J0B NUMBER: 55089 J FA -03 SHEET S -WIRE TO POWER SUPPLY CIRCUIT S3. D -WIRE TO POWER SUPPLY SMOKE DETECTOR. SEE SITE BLOW-UP PLAN. 24' - 0" LEASE LINE i 24-11 EX. 2x4 ACT GLO -E; -'` 11'-6" V.I.F. IIVTERFA PT -2 EX. GYP. BD. CEILING 7'-6" A.F.F. PT -2 1kc:::ei Cy:,;]D'� iict•kGi.�,:, . cYc;cg,y�2iifF;{ti?<q>_„c �> :,3'. ��;Y<':<i5�;: 5::�a•'' j�� z�.yr�,�z,;%C;3-.�� t24leic� �.:i �t�;-. ry. �i.�,:c:..s:....a.,,%,::�w..;,-;.< :;�a,r,:.Mta:�......1,•z;«•�:,.,.,�..ry,,:..a::.�..:�.c..:...b:.:...:.;a:.:.�.:«. �:v.tiY.w,.,.::•.•.;�a•..,'�:�.:..culc-,:+.cw�;,:a �wc...�..ra{C ."_;^s��'{'..�.�k; ><`i,Y:'��'? •`�S:S2 '6^F.:J <��,�?�i.U'r`�i: ;, ;,i• i i..b-?::Z"r, ` �.. ..?.:.��>.;:t...k....,..•n.O..�i.iT,%`.:..a�;�T.:i:a.,�.-..,ti2;v��,h. v.;.in..t�;.k�. is i,•,,..^ w.v, • •..nom.. 10'-0:' `C S','V,V DRESS ROOMS FAN • SHUTDOWN 24r1'1t • HU - 24 -112 S3-3 30cd V1-2 • � U 8'-0 J 4 70' - 6" LEASE LINE GYP. BD. CLG 12'-0" A.F.F. PT -1 I 'i... ....... :,S,V,V t "I :ry V L\ a � U 8' - 0" �.t .5,.m,,, S3 30c 1 12' -1 1/2" NEW STRUCTURE FOE GYP. BD. CLG. 14'-8 3/4" A.F.F. PT -1 GYP: BD. CLG. 10'-0" A.F.F. REFLECTED CEILING PLAN 1/4 = 1 4 ,W.....,,.0 \ GYP. BD. CLG. 14'-8 3/4" A.F.F. FIRE ALARM SYSTEM PLAN r ) \ i i S a -D ED V N' r M 3' IRA t `r 11 L ii II SITE BLOW-UP PLAN SCALE: NTS F LIGHTING DESCRIPTION (NOT ALL FIXTURES SHOWN) MARK DESCRIPTION LOCATION COMMENTS Q n Q 4= TRACK LIGHTING SALES AREA SURFACE MOUNT @ 10'-6" A.F.F. REFER TO SHEET E2 FOR SPECIFICATIONS. i 2x2 SUPPLY AIR DIFFUSER. 0 REFER TO SHEET M1 FOR SPECIFICATIONS. fit= RECESSED CAN LIGHT ENTRY EXISTING. REFER TO SHEET E2 FOR SPECIFICATIONS. CH 2x2 RETURN AIR DIFFUSER. CHANDELIER SALES -CENTER OVER CASH WRAP @ 90" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. ED SCONCE SALES- ABOVE DRESSING @ 84" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. i EXIT LIGHT THROUGHOUT CEILING MOUNTED. REFER TO SHEET E2 FOR SPECIFICATIONS. EMERGENCY LIGHTING STOCKROOM, SALES REFER TO SHEET E2 FOR SPECIFICATIONS. MARK DESCRIPTION LOCATION COMMENTS DESCRIPTION RESTROOM FAN & LIGHT TOILET ROOM EXISTING TO REMAIN x DATE 09/28/10 0 2x2 SUPPLY AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. =n 2x2 RETURN AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. illik CEILING KEYNOTES 0 a • 11 m 0 CENTER CHANDELIER EQUALLY OVER CASH COUNTER. TRACK LIGHTING TY?. SEE .E2 FOR DETAILS. RECESSED CAN LIGHTS TYP. SEE E2 FOR DETAILS. NEW 1x4 LIGHT RECESSED. SEE E2 FOR DETAILS. NEW 2x2 ACT CEILING THROUGHOUT SALES AREA. PAINT CEILING, WALLS; GRIDWORK & DIFFUSERS PT -1. NEW SOFFIT. PAINT PT -1. NEW SOFFIT VERTICAL WALL. PAINT PT -1. 17 BOX BEAM OF (2) 8" 18 -GA. STRUCTURAL METAL STUDS. EXISTING CEILING TO REMAIN. PATCH & REPAIR AS REQUIRED WHERE EXISTING STORAGE ROOM WALL WAS DEMOLISHED. EXISTING GYP. BD. CEILING TO REMAIN EXTEND -CEILING AS REQUIRED TO MEET NEW WALL LOCATION. MATCH EXISTING STRUCTURE & FINISH. EXISTING CEILING FAN I LIGHT TO REMAIN. -ADD ADDITIONAL CEILING AS REQUIRED TO MATCH EXISTING.. NEW WALL TO 6" ABOVE CEILING. ATTACHED TO STRUCTURAL JOISTS & BEAMS ABOVE. SEE DETAILS 2 & 3/Al. STORE ENTRANCE AREAS, ALL SPRINKLER HEADS RECESSED WITH COVERPLATES PAINTED TO MATCH THE CEILING COLOR. FIXTURES BELOW. TS10x2x.25" TUBE STEEL BEAM. WELDED TO COLUMNS WITH CUP ANGLES ON GRID LINE O. . 8" 16 -GA. STRUCTURAL METAL JOISTS @ 16" O.C. SET ON & ATTACHED TO 8" BEAMS. THIS AREA TO BE COVERED FROM ABOVE WITH 5/8" FRT TREADED PLYWOOD. CEILING NOTES CEILING SUPPORT SHALL COMPLY WITH SEISMIC BRACING REQUIREMENTS FOR THIS REGION. ALL SUPPORTS ARE ATTACHED FROM THE STRUCTURAL JOISTS & BEAMS ABOVE. DO NOT ATTACH TO DECK. FINISH LEGEND MARK PT -1 PT -2 PT -3 B-1 B-2 ST -1 DESCRIPTION VALSPAR CLR: WHIPPED APRICOT #: 2007-28 INTERIOR SATIN VALSPAR CLR: SAWYER WHITE 4/: 7002-16 INTERIOR FLAT GENERAL LOCATION SALES AREA WALLS & CEILING. STOCKROOM/SOFFIT CEILINGS VALSPAR CLR: JECKYLL CLUB VERANDA IVORY #: 7003-2 EGGSHELL VINYL BASE CLR: BROWN 4" SIGN BACKGROUND STOCK ROOM/SALES STOREFRONT BASE 4" CREMA EUROPA TILE BASE STOREFRONT MIN WAX CLR: EBONY if: 2718 ALL WOOD STAIN GRADE LUMBER. STAIN MINWAX EBONY AND SEAL TWO COATS CLEAR POLYURETHANE. c 0 Q U - VCT -1 12°x12" VINYL FLOORING CLR: BEIGE TYPE: - STOCKROOM TOILET ROOM WF -1 SHAW -HARDWOOD CLR: MAIZE TYPE: VICKSBURG #SW118 4 7/8" RANDOM LENGTH. 1/2" ENGINEERED FLOORING SUPPLIER: FLOOR ZONE - HOUSTON TX. CONTACT JEFF MEGOW (713) 205-6400. .SALES I WT -1 I WALL TILE CLR: CREMA EUROPA STOREFRONT ACT -1 USG INTERIORS OR EQUAL TILE: 2'x2'x3/4" MARS, CLIMA PLUS #86785 SLT ("SHADOWLINE TAPERED" EDGE -WHITE GRID: DONN 15116"DX WHITE. 2x2 SALES J NOTE:_ ALL F NISHES NEED TO MEET A MIN, OF A CLASS C FINISH FOR ENCLOSED SPACES, .SEE SEC V. ON CODE STUDY FOR MORE DETAILS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4.990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 00 0 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 09/28/10 0 =n 0 cin Zco o T LU E go" Q coZ J <_F2 w `r Z Ute_ (f) Ci) !LIQ Q ogog U) <=- W ww cc E5DZ _.,/ C\1 CC W ILL (S-CALE: 1/4"=1 '0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: 1.08 NUMBER: 55089 } SHEET FA -04 611 SOUTHCENTER MALL ASSOCIATED PERMITS 10-F-213 10-S-204 10-S-203 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Francesca's Collection 611 Southcenter Mall Permit No.: 10-S-204 Date: September 20, 2010 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. GYP: BD. CLG 10=0" A.F.F. .$GYP. BD. CLG. 141-8 314" A.F.F. MECHANICAL -T ASSEMBLY Style 920 Mechanical -T and Style 929 FIT Outlet/Mechanical-T' AppfO.1 D LISTED pages 107-11 1.as d in listings THE SERV CE INTENDED. REFESUPPLR TO PAGES 8D TO BE RAND 9 IS SUITED FOR ALWAYS LUBRICATE GASKET FOR PROPER COUPLING ASSEMBLY - REFER TO PAGE 8. PIPE MUST LWAYRBEPREFER EPAREG IS ACCO DANCEWITHVICTAULIC0 1. PREPARETO ASSEMBLE: To prepare or assembly, remove one nut and bot rem housing. Loosen the other nut anti t,is Rush with the end of the not remove. Remove the tape and lift the gasket from Mechanical T. 2. CHECK GASKET AND LUBRICATE. Apply a thin coat of.Vlctaullce Lubri- • cant or silicone lubricant to all surfaces of the,gasket This is essential ttiinsure proper sealing. Other compatible lubri- cants may be used, however do not use a petroleum base lubricant Reposition gasket Into housing using alignment tabs on sides for properPosl Honing. 3. POSmON MECHANICALT: To as- semble the couprmg on the pie first rotate the lower housing approximately 90 degrees away from the upper hous- ing. Place the upper, or outlet, section on to the face of the pipe In llnewith the outlet hole. Rotate the lower section around the pipe and close the two halves. *See pages 72 & 73 for FIT outlet pipe acsemhly. IttH 4. INSERT BOLT: Insert bolt In Rs hole and finger tighten both nut certain in oval -neck of bolt engagess housing. Make sure that the locating collar Is in the outlet hole. This may be checked by rocking the upper housing In the hole. Also make sure that the positioning lugs are properly aligned. MECHANICAL -T "CROSS" 5. TIGHTEN NUTS: Tighten bolt nuts uniformly until the upper housing is in complete surface contact in the gasket pocket area and the assembly is rigid. Nuts must be tightened to 50lb-ft with even gaps between the bolt pads for Styles 920 and 929. Torque in excess of 50 lb. ft. is not desirable. NOTE: Increased bolt torque will not improve sealing. RIM STYLE 920 - . MECHANICAL -To PERFORMANCE DATA Cross connections can be achieved with Style 920 or 929 Mechanica/TQniy_ by utilizing two Upper Housings of the same size, with the same or differing branch size connections. Assemble as .above, being certain that Locating Col- lar on each side is securely positioned inside the hole. Nuts must be tightened to 50 lb -ft with even gaps between the bolt pads. NOTE Alternate length bolts may be required for certain cross -type combi- nations. Contact Victaulic for details. IMPORTANT: If branch connection has been made to upper housing prior to Mechanical -T assembly, make certain this connection Is at 90' to n.e prior Io final tightening of Style 920 cc 929 Mechanical -T. When Mechanical -Ts are used as transition pieces between two runs, they must be assembled onto the runs before the branch connections are made. 69 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS STYLE 929 - FIT OUTLET/ MECHANICALT . PERFORMANCE DATA _ Warta` Presod 'SIB nIQ stamina/ See Deegan Tweet she net roe larded Stye Ina 1 Rona Tad Runlet, IL ft Wawa 3s1 ,r1X. a2 SBO so .ria. alit 11 500 50 1255.13 500 50 5.1Y, a. an.. 500 50 ri Re 50 BdX.'.ask Ste 50 13, si SBo 50 11511..5 a AO 50 Cross connections can be achieved with Style 920 or 929 Mechanica/TQniy_ by utilizing two Upper Housings of the same size, with the same or differing branch size connections. Assemble as .above, being certain that Locating Col- lar on each side is securely positioned inside the hole. Nuts must be tightened to 50 lb -ft with even gaps between the bolt pads. NOTE Alternate length bolts may be required for certain cross -type combi- nations. Contact Victaulic for details. IMPORTANT: If branch connection has been made to upper housing prior to Mechanical -T assembly, make certain this connection Is at 90' to n.e prior Io final tightening of Style 920 cc 929 Mechanical -T. When Mechanical -Ts are used as transition pieces between two runs, they must be assembled onto the runs before the branch connections are made. 69 RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING HANGER DETAIL NTS STYLE 929 - FIT OUTLET/ MECHANICALT . PERFORMANCE DATA _ Worthrl Pressen Mei Standard/ ear Tee. s. Pipe braked for she Assent!? Res 1 Brand Oetea. MIL 3rltt,ntlk12 175 50 4,115, silk a2 175 50 •eof torque epprc a4 I. bdurnets bene at -T I. m, recesses* al brand to Mkt ate to pees eo s SI- Was! L@ids! belodins gairaiarl esre.d Iwai Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart 4 Add Reliable Model Fl Standard Response 155° Pendants IA x 1/2 ', 3 Add Reliable Model G4 Consealed Standard Response 155 pendant 1/2 x 1/2 7 — Total 0. Without Comments Q As Noted in Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rets totally with the designer. Additions, deletions or revisions to these drawings4kafter. this date will void this acceptance and wiU require a resubmittal of revised drawings for subsequent approval. Final acceptance Is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: O By: IiigliALA FIRE DEPART Please call: 576 - arid give this job No. / `S?e0`i and exact address for shi* down or restoration aooro #e R4' '5 raer CROWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 P11. (425) 481-7669 PROJECT ADDRESS; 611 SOUTHCENTER MALL TUKWILA, -INA 98188 CLIENT NAME: FRANCESCA'S COLLECTIONS DATE•5 tIG DRAWN: 3 f c, SCALE: at -) . PAID SEP 2 0 2010 TUKWILA FIRE n 14.thOLLA FIRE DEPARTLY i' Please call: 575-446Z sand give this job tta. 3 ar1J exact address for Shut or restoration approxi NCESCA'S COLLECTIONS FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NUM3E SHEET TITLE FA -01 SYSTEM INFORMATION FA -02 TYPICAL WI RING AND MOUNTING DETAILS FA -03 SYSTEM CALCULATIO\ S AN D SINGLE LIN E DIAG RAM FA -04 FIRE ALA RN SYSTEM PLA\ SHEET INDEX TE O Without Comments Vii'' As Noted in. Red ❑ Per "alt. Attached Letter These plans have ry.iiievred by The Tukwila Fire Prevention Bureau for co orrnance with current City standards. Accepta{m:. i w inject to errors and omissions which co not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. =Additions, deletions or revisions to these drawingst:after this date will void this acceptance and will require resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau.Al/t1 Date: y � -7 -/ O By: 31% _ IZ L • e --o. rt c�;�' ' - C60Jc- t c i (: Wi-OttA et/6". NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be present to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection. Systems. Failure of test will result in a Re -inspection Fee and termination of the tes,rg. WIRE SCHEDULE A\D CONDUIT FILL CHAT WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR - RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE IT IS LOCATED. AND JUNCTION BOXES ENVIRONMENT IN WHICH 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 1 1 1 2 3 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER POWER SUPPLY PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP SMOKE DETECTOR HFP-1 1 W/ SIEMENS (PHOTO -ADDRESSABLE) DB -11 BASE 4S DEEP W/ 1G RING CEILING ®D DUCT DETECTOR AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING J BOX CTION N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 SYMBOLS LEGEND 1,1 NORDSTROM 3 LEVELS 1 171,275s1 macys 425o 40 sf )1 «A , r = RA, RCS Si C. RAR s.�&EGO VATTIT S LJ IMO CA: �T!vJ 6 CALLA THUIROOS UAR_m RA,AMA UPS ti ThE fJ i Y �. FRANCESCA'S COLLECTION (611 - SPACE #572) iIXYC TOKYO 19110.1. RSC P eniw mist_ G:OGE toss-si KING CffifTY UPS+ Y RFC UEYET! ./EATEERS EXISTING JCPenney J LE'+ELS 276,468sf PAID SEP 3 0 2010 TUKWILA FIRE ..-7b? 7/ 05-0 - 9 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE 0 c co (.1 0, 0 I2 «<« 1/ 1 Z 0 0 z Z N O I-Zwooe o ";"0" JEg c„z J Q O 2 "v Q� w �_ cc w� VJ w < w U SI v C� < = W F- CCo ' C`I T W LL (/)H �CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved .JOB NUMBER: 55089 } r SHEET k FA -01 , le25II,' 120VAC-60R1 DEDICATED EMERGENCY THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. PUCK OVER 3' WIDE: SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR A00111CNAL S'EC61CA110NS SEE PRODUCT DOQNFNTADON. 'CONTACT RATINGS: 4.0A 0 125VAC 4.0A 0 30VDC illEVE TO NEXT ADDRESSABLE (+ DEVICE STIP IF LAST DEVICE s - FROM Xl D CONTROL PANEL Ct I62 PREVIOUS ADDRESSABLE DEVICE 0 a 0 O —) 44 Ie; I HTRI—R NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE i 6 N L 'XI X a 0 PAD -3 oo LI INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - a a 3.6k EOL (-) (+) SPARE SPARE SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. rn s m s 0 m 0 Fl (=)(-) (+)(+) • (+) Q WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TIPS COLOR CODE TWISTED PAIR WITH SHIELD #18 FPLFPI.R RED(JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30NDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 F L 0 HTRI—R I DRY CONTACTS TO VAV �. FAN SHUTDOWN PROVIDED BY MECH/ELEC. GROUND C\ O 0❑ ❑L 0 _ IPM 0 — v _ 111,11 DESCRIPTION SHOP DRAWINGS Q o 0 oG\ SA Tli o i T F1 t 10 1 6 x •- ..u.ip usurp. " - in ,r1 ,d \+_ ..., . 1: :1:1:111.1.1' CI0 4,711M- to ,v X 7 C LI❑I (-) II (+) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (-) (+)> TO NEXT DEVICE OR (-) STOP IF LAST DEVICE DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER 1 ❑O 0 ❑ v _ 0 — DESCRIPTION SHOP DRAWINGS 0 DATE 0 yy .. xi ��C sua1 o i F1 1 6 x •- ..u.ip I °I! 1:I:l:I:1 I1:I:I. ,r1 ,d o . 0 CI0 4,711M- 1 o��,,,,�❑ STROBE ❑EJDJ CIRCUIT STROBE SPEAKERISTROBE r11:1:1 [1:1:I. STROBE CIRCUIT STROBE CIRCUIT S TO NEXT APPLIANCE OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) (-) SPEAKER CIRCUIT SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS SPEAKER CIRCUIT NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. +32' FF (o' C) TO 1W F (38' C) HUMIDITY: 0-93% RELATIVE HUMIDITY, NON -CONDENSING HP -11 SMOKE DETECTOR — — FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE tDATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPUCATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR f--- DB -11 SSMTANDARDOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID --\ CEILING > TO NEXT ADDRESSABLE DEVICE HARD LID ---\\ SPEAKER SUPPORT TILE BRIDGE �— 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N �,-- CEILING MOUNTED SPEAKER/STROBE SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT cip 0 0 ; TO NEXT DEVICE 0 0 CADDY BAR SMOKE/HEAT DETECTOR \\- SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved W y 2 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 09/28/10 o <a«< T 0.. �CALE: NOT TO SCALE - DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55089 i SHEET FA -02 ACIP; AD Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042. HFPT-11 0 0.002200 0 0.0023 0.000 0.0731 Amps 0.106 Amps Curren ' 'oat! Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C (a 15CD 0.0875 SET -MC -C @30CD 3 0.131 SET -MC -C @75CD 0.222 (SET -MC -C @95CD 0.292 SET -MC -C @110CD 0.259 ZR -MC @15CD 1 0.064 0.064 ZR -MC (c 30CD 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.094 Amps Standby Current Load: 0.03 Amps For 24 Hours - 0.720 Amp -hours Alarm Current Load: 0.094 Amps For 5.Minutes= 0,008 Amp -hours 25% Derating= 0.910 Amp -hours Total System Current Load: 0.910 Amp -hours 12VDC. Notification Appliance Circuit Detail PROJECT: FRANCESCA'S COLLECTIONS Panel: PAD -3 POWER SUPPLY Date: September 29, 2010 !Wire Resistance 2.58 CURRENT TOTAL=;2502.00 0 SET -MC -C @15CD SET -MC -C @30CD 0 SET -MC -C @75CD 0 SET -MC -C ©95CD 0 ZR -MC @110CD ZR -MC @15CD _ ZR -MC @30CD ZR -MC 675CD 4 0 DEVIC 87.51 131 222; 292 2591 64 98 175 TOTAL mA=i ;Total Wire Resistance (R ) Total Device Load, Amps (I) Voltage Drop (E) EOL Voltage 9 0 0 64 0 0 457 12 189 23.55 4571 ( WL* 2 )*(R/ft) (Total Cct Load) (E=I*R) 24-E) 0.981 0.46 0.451 23.55 Notification Appliance Circuit Detail PROJECT: FRANCESCA'S COLLECTION Panel: XLS-V Date: September 29, 2010 ;Wire Resistance 2.58 CURRENT TOTAL=1#REF! 18 70.7V.1/8_ 14 70.7V1/4 0 170.7V112 0 70.7V1 DEVICES= 32 32.4 0 . 0 0I 0` 0 TOTAL mA= ITotal Wire Resistance (R ) Total Device Load, Amps (I) (Voltage Drop ( E) EOLVoltage 0 32.4; 14 727 20.27845723 ( WL *. 2_.,), * (R/ft) (Total Cc# Load 1(E=1*R) (20.4-E) 32.4 3.751 0.03' 0.121 20.28 SYSTEM CALCULATIONS TO NEAREST EXISTING DATA LOOP CIRCUIT, VOICE CIRCUIT& POWER SUPPLY SYNC CIRCUIT D,V,V',2C b R S1-1 30cd V-1 1/4-W AHU-1 o-- S,2C BPS 120VAC, DEDICATED , ) (BY OTHERS) S1-2 S1-3 15cd 30cd V-2 1 /4-W S1-4 30cd V-3 1 /4-W EOL S1 c0 ON 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-654.5 RELEASE/REVISIONS REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 Z co N C) 0 z a\\\\ 0 W Cl) Z Z cv -J O W FZWc J - U 00ES W < °' Z z J Q J Q CI) O 2 JCD 0 Q Z W( Q - <Cn 'Q oc (II U d6.11g O W w O Cr Li�i e U t° J 0 F- >- 1 \ - omJ\ �CALE: NOT TO SCALE" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \OB NUMBER: 55089 SHEET \ FA -03 TO NEAREST EXISTING DATA LOOP CIRCUIT, VQIbE,CIRCUIT& POWER SC):LY- SG1-'- G YN GI 1.4Fr J• ,2c,V,v:--o EX. 2x4 ACT CLG. 11,-6" V.I.F. PT -2 24' - 0" LEASE LINE .i X•. i.c .;♦ ' atSS,•• X52? ti:.,s':;r t:,'�z.r ,.`,.i ?:�Z�:r` .::a��k'Si •+\=<:t ^Sa: • :s`�.i<. ., y•a;*"." ..aia.::..x�.5c:w.aaw.,.:.+.,:a„•..:,.,�;,:..\�•�,: 'f" L D \. / AHU-1 EX. GYP. f3D. CEILItvG>i 7'-6" PT -2 S` -2 1Scd lbw :�xiJhw�.r;lx,ti..a,, :s.<>`c;.: ic�.sr •.,ra+. U} - 2 '\ Chi NVAl DRESS ROOMS 0 f • S1-8 30cd V1-2 O 1.• 8':O B' - 0". w z w Q w • NV • ....t,.3 GYP. BD. CLG. 12'-0" A.F.F. PT -1 i c:• if. tr-1- 1;"41 b EOL. S r`j 0 a " NEW STRUCTURE GYP. BD, CLG. 14'-3 3/4" A.F.F. PT -1 1 REFLECTED CEILING PLAN 1/4 = 0 0 0 0 GYP: BD. CLG. [T-2 10`-0" A.F.F. GYP. BD. CLG. 14'-S 314" A.F.F. FIRE ALARM SYSTEM PLAN 3. SCHEDULELig-MN (NOT ALL FIXTURES SHOWN) MARK DESCRIPTION LOCATION COMMENTS MARK DESCRIPTION LOCATION COMMENTS Q c7 n TRACK LIGHTING SALES AREA SURFACE MOUNT @ 10'-8„ A.F.F. REFER TO SHEET E2 FOR SPECIFICATIONS. 0 - RESTROOM FAN & LIGHT TOILET ROOMEXISTING TO REMAIN � 6"0 RECESSED CAN LIGHTEXISTING. ENTRY REFER TO SHEET E2 FOR SPECIFICATIONS. 2x2 SUPPLY AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. CE:1) CHANDELIER SALES -CENTER OVER CASH WRAP 90" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. 2x2 RETURN AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. (F) SCONCE SALES- ABOVE DRESSING 84" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. le EXIT LIGHT THROUGHOUT CEILING MOUNTED. REFER TO SHEET E2 FOR SPECIFICATIONS. EMERGENCY LIGHTING STOCKROOM, SALES REFER TO SHEET E2 FOR SPECIFICATIONS. CEILI 1 EYNOT S CENTER CHANDELIER EQUALLY OVER CASH COUNTER. TRACK LIGHTING TYP. SEE E2 FOR DETAILS. RECESSED CAN LIGHTS TYP. SEE E2 FOR DETAILS. NEW 1x4 LIGHT RECESSED. SEE E2 FOR DETAILS. NEW 2x2 ACT CEILING THROUGHOUT SALES AREA. PAINT CEILING, WALLS. GRIDWORK & DIFFUSERS PT -1. NEW SOFFIT. PAINT PT -1. NEW SOFFIT VERTICAL WALL. PAINT PT -1. 17 BOX BEAM OF (2) 8" 18 -GA. STRUCTURAL METAL STUDS. EXISTING CEILING TO REMAIN. PATCH & REPAIR AS REQUIRED WHERE EXISTING STORAGE ROOM WALL WAS DEMOLISHED. EXISTING GYP. BD. CEILING TO REMAIN EXTEND CEILING AS REQUIRED TO MEET NEW WALL LOCATION. MATCH EXISTING STRUCTURE & FINISH. EXISTING CEILING FAN / LIGHT TO REMAIN. ADD ADDITIONAL CEILING AS REQUIRED TO MATCH EXISTING. NEW WALL TO 6" ABOVE CEILING. ATTACHED TO STRUCTURAL JOISTS & BEAMS ABOVE. SEE DETAILS 2 & 3/A1, STORE ENTRANCE AREAS. ALL SPRINKLER HEADS RECESSED WITH COVERPLATES PAINTED TO MATCH THE CEILING COLOR. FIXTURES BELOW. TS10x2x.25" TUBE STEEL BEAM. WELDED TO COLUMNS WITH CLIP ANGLES ON GRID LINE O. 8" 16 -GA. STRUCTURAL METAL JOISTS @ 16" O.C. SET ON & ATTACHED TO 8" BEAMS. THIS AREA TO BE COVERED FROM ABOVE WITH 5/8" FRT TREADED PLYWOOD. CEP4NQ NOTES CEILING SUPPORT SHALL COMPLY WITH SEISMIC BRACING REQUIREMENTS FOR THIS REGION. ALL SUPPORTS ARE ATTACHED FROM THE STRUCTURAL JOISTS & BEAMS ABOVE. DO NOT ATTACH TO DECK. FINISH LEGEND MARK 'DESCRIPTION PT -1 VALSPAR CLR: WHIPPED APRICOT #: 2007-2B INTERIOR SATIN GENERAL LOCATION SALES AREA WALLS & CEILING. PT -2 VALSPAR CLR: SAWYER WHITE #: 7002-16 INTERIOR FLAT STOCKROOM/SOFFIT CEILINGS PT -3 VALSPAR CLR: JECKYLL CLUB VERANDA IVORY 1#: 7003-2 EGGSHELL SIGN BACKGROUND B-1 , VINYL BASE CLR: BROWN 4" STOCK ROOM/SALES I 8-2 1 STOREFRONT BASE 4" CREMA EUROPA TILE BASE STOREFRONT ST -1 MINWAX CLR: EBONY #: 2718 ALL WOOD STAIN GRADE LUMBER. STAIN MINWAX EBONY AND SEAL TWO COATS CLEAR POLYURETHANE. cc 0 O w VCT -1 12"x12" VINYL FLOORING CLR: BEIGE TYPE: -- STOCKROOM TOILET ROOM WF -1 SHAW -HARDWOOD CLR: MAIZE TYPE: VICKSBURG #SW118 4 7/8" RANDOM LENGTH. 1/2" ENGINEERED FLOORING SUPPLIER: FLOOR ZONE - HOUSTON TX. CONTACT JEFF MEGOW (713) 205.6400. SALES WT -1 WALL TILE CLR: CREMA EUROPA STOREFRONT ACT -1 0 USG INTERIORS OR EQUAL TILE: 2`x2'x3/4" MARS, CLIMA PLUS 486785 SLT ("SHADOWLINE TAPERED" EDGE -WHITE GRID: DONN 15116"DX WHITE. 2x2 SALES NOTE: ALL F NISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES. SEE SEC V. ON CODE STUDY FOR MORE DETAILS. FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. SMOKE DETECTOR MUST BE LOCATED IN THE SAME ROOM AS THE PAD -3. TENANT FIRE ALARM JUNCTION BOX (FIELD LOCATE). RELAY MODULE MONITORS PAD -3 POWER SUPPLY. REPLACE AND RELOCATE EXISTING DUCT DETECTOR TO NEW LOCATION. LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m a DESCRIPTION SHOP DRAWINGS DATE 0 aD N 0 W 2 CALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: 55089 SHEET FA -04 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved / 09/20/2010 12:57 4254818695 FAX TRANSMITTAL. CROWN FIRE PAGE 01/01 Fax No. CROWN FIRE PROTECTION, INC. CEE: 9.20.10 Campan'"` Subjec 17, Fire Prevention Bureau Tukwila Fire Department Demo Permit Number of Pages (Including Cover El Urgent FJ For Review Frain: Jessica Robinson 1 0 Please Comment 0 Please Reply [206.575.4439 PH:425.481.7669 FX:425.481.8695 Comment. Please provide a demo permit to remove one fire sprinkler head in the middle of the entry way that is hanging low and is in the way. The project is Francesca' s Collection located at 611 Southcenter Mall. The building permit number is D10201. Thanks :411SW1LA FIRE DEPART N Reese call: 575407 andve this job No..0-S- o3 and exact address for shin -town or restoration aoorniot P.O. BOX 12113 MILL CREEK, WA 98082 PH: 425.481,7669 FX: 425. 481.8695 NCESCA'S COLLECTIONS FIRE ALARM SYSTEM ADDITION TUKWILA, WASHINGTON SHEET NU1V3ER SHEET TITLE FA -01 SYSTEM INFO MATIO\ FA -02 TYPICAL WRING AND MOU\TI\G DETAILS FA -03 SYSTEM CALCULATIO\S A\D SINGLE LINE DIAGA V1 FA -04 FIRE ALAR V1 SYSTEM PLA\ SHEET INDEX WIRE SCHEDULE A\D CO\DUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vaC POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FAC?. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY EX EX 1 2 3 1 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT BPS REMOTE BOOSTER Ex POWER SUPPLY (EXISTING) PAD -3 SIEMENS PAD-3-ENCL 66" A.F.F. TO TOP ®EX SMOKE DETECTOR. (PHOTO -ADDRESSABLE) XISTING) HFP-11 W/ SIEMENS DB -1 1 BASE 4S DEEP W/ 1 G RING CEILING DUCT DETECTOR AD2-P W/ SIEMENS HFP-1 1 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE HTRI-R WITH RELAY SIEMENS 4S DEEP BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1 /2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING JUNCTION D BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND 1 NORDSTROM 3 LEVELS 171,275sf EMES11 CCGr:A macys 4 LEVELS 250,407sf 313 331 } COLD 1Q(Y3 TOKYO £I.5 G1tc�A5'a!D ss CMECl:. MSW CCUIIY LW"RY s.DUEWD XNELE.S El13T!•!G JCPenney 3 LEVELS 276,468sf FRANCESCA'S COLLECTION (611 - SPACE #572) 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 00 0 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 09/28/10 ...... _...... 0 7, 0 7, 0 2a<aa< Z cl O I- z w c T (j)Z J <t J O wcci `� z ci) HQ (/)QZ__ Wwcc 8D' Z cni- cc 111 u_ (.1) 0 CC 0 z ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE:09/28/10 BACKROUND PLAN PROVIDED BY: WIRE DESIGNATION GENERAL NOTES SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved .10B NUMBER: 55089 J SHEET FA -0 1 120VAC-8O11Z DEDICATED DIERG?ICY'' THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. PUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT 000MNTATION. *CONTACT RATINGS: 4.0A 0125VAC 4.0A 0 30VDC TO NEXT ADDRESSABLE&F DEVICE STOP IF LAST DEVICE MON XLS CONTROL PANEL a OR PREVIOUS ADDRESSABLE DEVICE O 0 J HTRI-R I I ° J� NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE ORD NCI I. U a PAD -3 oo° INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX + 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 3.6k EOL L 111 (-) (+) (-) (+) 1 SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) CID NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. Fri r71 C, 0 O� m m o � 0 0 o F^ (2)(-) (+)(+) 0 c m (+) WIRE DESIGNATION: NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE TWISTED PAIRWITHSHIELD #18 FPLIFRR RED(JACKET) *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 0 I -c ' I ° 01 I 77 -'I _ � 1 HTRI-R 1 GROUND 0 DRY CONTACTS TO VAV �. FAN SHUTDOWN PROVIDED BY MECH/ELEC. ❑ I1 --r) — 0 I4- ;'f) I / t ID 1 I .L aI I I O O §\ g� ars. .a n. n. , ' 1 1 ' I _ '€iI 4- +- AICAEFC■ " - ,A A.CO Ei011 — AECEEiS■ " ,n I 1 bm 1:1:1:1:1 11:1:1- I:1 I:I:1 I 1:1:11. 1."-- . 1.1 1:1:111:1:1* o 0 .1 11.1 / �1 � �M9■// 0 P • , M Kurc N (• ... no (-) ° (+)>TO NEXT DEVICE OR > STOP IF LAST DEVICE DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER o❑ II ► J-� �'i 0 ;)0 , 1 1 1 1 / t ID 1 iii ri1 O .E.,1 .m.. icy mm. PM a o , ' 1 r€t'/ ' I _ ! 4- +- AICAEFC■ " - ,A A.CO Ei011 — •••-• I 1 bm 1:1:1:1:1 11:1:1- I:1 I:I:1 I 1:1:11. u 1 o 0 .1 11.1 / �1 � �M9■// 0 ❑EIDJ (IHUUIT �a�❑ SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < OR FIRE ALARM CONTROL PANEL < (+) (+) (-) ❑ISD STROBE CIRCUIT STROBE o❑ ❑o ❑` 0 - 1 1 1 / t a ', y , III rh O .E.,1 .m.. ! �. 1 r€t'/ • I -II 4- ABM i CN " - ,/ft A.CO Ei011 •••-• 111:1:1Ila:1' I:1 I:I:1 I 1:1:11. --; \e 11:117k �$.L.A-M© w•l=::. raril ' . / C71 4 P • , M Kurc N (• ... (-) (-) SPEAKER CIRCUIT (+) (+) on STROBE SPEAKER/STROBE no ❑o 07 o o o _ , I 1 qu t y , J'4. rh O O Ie \ ..a ww ' • I -II - A.CO Ei011 \ 0."--3 I:1 I:I:1 I 1:1:11. --; \e 11:117k �$.L.A-M© w•l=::. raril ' . / 1q= (-) on STROBE (-) n SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE S OR 24K (EOLR) S TO NEXT SPEAKER OR END OR LINE RESISTOR S 24K (EOLR) NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER �T1N TEMPERA RE: +32'F (O' C) TO 100' F (35 C) HUMIDITY: 93% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR -� FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE r DATA IN( )> Sl DATA IN (+) > DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID --� CEILING HARD LID SPEAKER SUPPORT TILE BRIDGE > TO NEXT ADDRESSABLE DEVICE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSI❑N CEILING MOUNTED SPEAKER/STROBE 0° o ° °o 000 SPEAKER STROBE MOUNTING DETAIL JUNCTION BOX MOUNTED ON CEILING FLEX JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 0 0 TO NEXT DEVICE CADDY BAR 1J SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved :410- O F- c 141 g y w :1!I- F - W GO1.1% O cnW FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS (4/ J cn CC!S z0 iL?) 2" Z co U o ° oT3 I-- Wt=0°' J o �o O J d _i�_ O LU 2,... o tr_ co Fw < r 1 �(✓ Q W w EC. 8 ZZ CE ,,,SIA 7- CC CC' u_ J U SCALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: \OB NUMBER: 55089 C SHEET FA -02 Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 1 0.0022 0.0022 0.0023 0.002 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 HFPT-11 0 0.002200 0 0.0023 0.000 0.0731 Amps 0.106 Amps Da nc e alc+u' Currin Loan Device Type Qty Amps Total Amps Total Main System Board 1 0.03 0.03 0.030 0.030 SET -MC -C @15CD 0.0875 SET -MC -C @30CD 3 0.131 SET -MC -C ()a 7 C 0.222 ;SET -MC -C @95CD 0.292 SET -MC -C ('7110CD 0.259 ZR -MC @15CD 1 0.064 0.064 ZR -MC @30CD 0.098 ZR -MC @75CD 0.2 0.03 Amps 0.094 Amps Standby Current. Load: 0.03 Amps For 24 Hours 0.720 Amp -hours Alarm Current Load: 0.094 Amps For 5 Minutes 0.008 Amp -hours 25% Derating= 0.910 Amp -hours Total System Current Load: 0.910 Amp -hours Battery Pair to ba Used: _ __. Notification Appliance Circuit Detail PROJECT:1 FRANCESCA'S COLLECTIONS Panes: 3PAD-3 POWER SUPPLY 1 Date: September 29, 2010 Wire Resistance CURRENT TOTAL= 2.58 2502.00 SET -MC -C @15CD SET -MC -C @30CD 0 JSET-MC-C @75CD 0 SET -MC -C @95CD 0 ZR -MC @110CD 1 ZR -MC @15CD 0 ZR -MC @30CD 0 ZR -MC @75CD DEVICES= 4 87.51 131 222 292 2591 64 981_ 175 TOTAL mA= ;Total Wire Resistance (R ) Total Device Load, Amps (1) 'Voltage Drop (E) EOL Voltage 0! 393 0 0 0', 64 01 0 4571 12 189 23.551 457 (WL*2)*(R/ft) (Total Cct Load (E=I*R) 24 - E)..... 0.981 0.46 0.45 23.55 Notification Appliance Circuit Detail PR OJECT:1 FRANCESCA'S COLLECTION Panel:1 XLS-V Date: ! September 29, 2010 18 ........ 14 0 0 DEVICES= 170.7V 1/8 70.7V 1/4 70.7V1/2 70.7V 1 32 1.81 0 0 0 TOTAL mA= 1 'Total Wire Resistance (R ) Total Device Load, Amps (1) Voltage Drop (E ) EOL Voltage !Wire Resistance 2.58 CURRENT TOTAL= #REF! 32.4 0 0 20.27845723 1(WL*2)*(R/ft) (Total Cot Load) 1(E=I*R) (20.4 - E) 32.4 3.75 0.03 0.121 20.28 SYSTEM CALCULATIONS S3-1 30cd V-1 1 /4-W ® EX S BPS 120VAC, DEDICATED , ) EX (BY OTHERS) S3-2 S3-3 15cd 30cd V-2 1 /4-W BGM FAN INTERFACE SHUTDOWN 24-110 24-111 AHU-1 D 24-112 S3-4 30cd V-3 1 /4-W EOL S3 t) 0 1743 1ST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: DMG 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 09/28/10 10/15/10 (J') O U w J -J O U (1) (!) w z CC LL co zz • w co r <55 �z < JO w �z coW< w z� U� W = CC O1_ r T (0 ALE: NOT 1 cr 0 W z J W J z E5 0 z U) z O 0 J U w (i) 1- (1) TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved \J0B NUMBER: 55089 J FA -03 SHEET S -WIRE TO POWER SUPPLY CIRCUIT S3. D -WIRE TO POWER SUPPLY SMOKE DETECTOR. SEE SITE BLOW-UP PLAN. 24' - 0" LEASE LINE i 24-11 EX. 2x4 ACT GLO -E; -'` 11'-6" V.I.F. IIVTERFA PT -2 EX. GYP. BD. CEILING 7'-6" A.F.F. PT -2 1kc:::ei Cy:,;]D'� iict•kGi.�,:, . cYc;cg,y�2iifF;{ti?<q>_„c �> :,3'. ��;Y<':<i5�;: 5::�a•'' j�� z�.yr�,�z,;%C;3-.�� t24leic� �.:i �t�;-. ry. �i.�,:c:..s:....a.,,%,::�w..;,-;.< :;�a,r,:.Mta:�......1,•z;«•�:,.,.,�..ry,,:..a::.�..:�.c..:...b:.:...:.;a:.:.�.:«. �:v.tiY.w,.,.::•.•.;�a•..,'�:�.:..culc-,:+.cw�;,:a �wc...�..ra{C ."_;^s��'{'..�.�k; ><`i,Y:'��'? •`�S:S2 '6^F.:J <��,�?�i.U'r`�i: ;, ;,i• i i..b-?::Z"r, ` �.. ..?.:.��>.;:t...k....,..•n.O..�i.iT,%`.:..a�;�T.:i:a.,�.-..,ti2;v��,h. v.;.in..t�;.k�. is i,•,,..^ w.v, • •..nom.. 10'-0:' `C S','V,V DRESS ROOMS FAN • SHUTDOWN 24r1'1t • HU - 24 -112 S3-3 30cd V1-2 • � U 8'-0 J 4 70' - 6" LEASE LINE GYP. BD. CLG 12'-0" A.F.F. PT -1 I 'i... ....... :,S,V,V t "I :ry V L\ a � U 8' - 0" �.t .5,.m,,, S3 30c 1 12' -1 1/2" NEW STRUCTURE FOE GYP. BD. CLG. 14'-8 3/4" A.F.F. PT -1 GYP: BD. CLG. 10'-0" A.F.F. REFLECTED CEILING PLAN 1/4 = 1 4 ,W.....,,.0 \ GYP. BD. CLG. 14'-8 3/4" A.F.F. FIRE ALARM SYSTEM PLAN r ) \ i i S a -D ED V N' r M 3' IRA t `r 11 L ii II SITE BLOW-UP PLAN SCALE: NTS F LIGHTING DESCRIPTION (NOT ALL FIXTURES SHOWN) MARK DESCRIPTION LOCATION COMMENTS Q n Q 4= TRACK LIGHTING SALES AREA SURFACE MOUNT @ 10'-6" A.F.F. REFER TO SHEET E2 FOR SPECIFICATIONS. i 2x2 SUPPLY AIR DIFFUSER. 0 REFER TO SHEET M1 FOR SPECIFICATIONS. fit= RECESSED CAN LIGHT ENTRY EXISTING. REFER TO SHEET E2 FOR SPECIFICATIONS. CH 2x2 RETURN AIR DIFFUSER. CHANDELIER SALES -CENTER OVER CASH WRAP @ 90" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. ED SCONCE SALES- ABOVE DRESSING @ 84" A.F.F. PROVIDED BY TENANT, INSTALLED BY CONTRACTOR. i EXIT LIGHT THROUGHOUT CEILING MOUNTED. REFER TO SHEET E2 FOR SPECIFICATIONS. EMERGENCY LIGHTING STOCKROOM, SALES REFER TO SHEET E2 FOR SPECIFICATIONS. MARK DESCRIPTION LOCATION COMMENTS DESCRIPTION RESTROOM FAN & LIGHT TOILET ROOM EXISTING TO REMAIN x DATE 09/28/10 0 2x2 SUPPLY AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. =n 2x2 RETURN AIR DIFFUSER. THROUGHOUT REFER TO SHEET M1 FOR SPECIFICATIONS. illik CEILING KEYNOTES 0 a • 11 m 0 CENTER CHANDELIER EQUALLY OVER CASH COUNTER. TRACK LIGHTING TY?. SEE .E2 FOR DETAILS. RECESSED CAN LIGHTS TYP. SEE E2 FOR DETAILS. NEW 1x4 LIGHT RECESSED. SEE E2 FOR DETAILS. NEW 2x2 ACT CEILING THROUGHOUT SALES AREA. PAINT CEILING, WALLS; GRIDWORK & DIFFUSERS PT -1. NEW SOFFIT. PAINT PT -1. NEW SOFFIT VERTICAL WALL. PAINT PT -1. 17 BOX BEAM OF (2) 8" 18 -GA. STRUCTURAL METAL STUDS. EXISTING CEILING TO REMAIN. PATCH & REPAIR AS REQUIRED WHERE EXISTING STORAGE ROOM WALL WAS DEMOLISHED. EXISTING GYP. BD. CEILING TO REMAIN EXTEND -CEILING AS REQUIRED TO MEET NEW WALL LOCATION. MATCH EXISTING STRUCTURE & FINISH. EXISTING CEILING FAN I LIGHT TO REMAIN. -ADD ADDITIONAL CEILING AS REQUIRED TO MATCH EXISTING.. NEW WALL TO 6" ABOVE CEILING. ATTACHED TO STRUCTURAL JOISTS & BEAMS ABOVE. SEE DETAILS 2 & 3/Al. STORE ENTRANCE AREAS, ALL SPRINKLER HEADS RECESSED WITH COVERPLATES PAINTED TO MATCH THE CEILING COLOR. FIXTURES BELOW. TS10x2x.25" TUBE STEEL BEAM. WELDED TO COLUMNS WITH CUP ANGLES ON GRID LINE O. . 8" 16 -GA. STRUCTURAL METAL JOISTS @ 16" O.C. SET ON & ATTACHED TO 8" BEAMS. THIS AREA TO BE COVERED FROM ABOVE WITH 5/8" FRT TREADED PLYWOOD. CEILING NOTES CEILING SUPPORT SHALL COMPLY WITH SEISMIC BRACING REQUIREMENTS FOR THIS REGION. ALL SUPPORTS ARE ATTACHED FROM THE STRUCTURAL JOISTS & BEAMS ABOVE. DO NOT ATTACH TO DECK. FINISH LEGEND MARK PT -1 PT -2 PT -3 B-1 B-2 ST -1 DESCRIPTION VALSPAR CLR: WHIPPED APRICOT #: 2007-28 INTERIOR SATIN VALSPAR CLR: SAWYER WHITE 4/: 7002-16 INTERIOR FLAT GENERAL LOCATION SALES AREA WALLS & CEILING. STOCKROOM/SOFFIT CEILINGS VALSPAR CLR: JECKYLL CLUB VERANDA IVORY #: 7003-2 EGGSHELL VINYL BASE CLR: BROWN 4" SIGN BACKGROUND STOCK ROOM/SALES STOREFRONT BASE 4" CREMA EUROPA TILE BASE STOREFRONT MIN WAX CLR: EBONY if: 2718 ALL WOOD STAIN GRADE LUMBER. STAIN MINWAX EBONY AND SEAL TWO COATS CLEAR POLYURETHANE. c 0 Q U - VCT -1 12°x12" VINYL FLOORING CLR: BEIGE TYPE: - STOCKROOM TOILET ROOM WF -1 SHAW -HARDWOOD CLR: MAIZE TYPE: VICKSBURG #SW118 4 7/8" RANDOM LENGTH. 1/2" ENGINEERED FLOORING SUPPLIER: FLOOR ZONE - HOUSTON TX. CONTACT JEFF MEGOW (713) 205-6400. .SALES I WT -1 I WALL TILE CLR: CREMA EUROPA STOREFRONT ACT -1 USG INTERIORS OR EQUAL TILE: 2'x2'x3/4" MARS, CLIMA PLUS #86785 SLT ("SHADOWLINE TAPERED" EDGE -WHITE GRID: DONN 15116"DX WHITE. 2x2 SALES J NOTE:_ ALL F NISHES NEED TO MEET A MIN, OF A CLASS C FINISH FOR ENCLOSED SPACES, .SEE SEC V. ON CODE STUDY FOR MORE DETAILS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved 1743 1ST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4.990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 00 0 0 DESCRIPTION SHOP DRAWINGS AS BUILT DRAWINGS DATE 09/28/10 0 =n 0 cin Zco o T LU E go" Q coZ J <_F2 w `r Z Ute_ (f) Ci) !LIQ Q ogog U) <=- W ww cc E5DZ _.,/ C\1 CC W ILL (S-CALE: 1/4"=1 '0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 09/28/10 BACKROUND PLAN PROVIDED BY: 1.08 NUMBER: 55089 } SHEET FA -04