HomeMy WebLinkAboutPP - 304 SOUTHCENTER MALL - LADY FOOTLOCKER - PERMITS AND PLANS304 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-226 08-S-335 1 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lady Footlocker 704-( S c_ r.A& l / 1560 Southcenter Mall Permit No.: 08-S335 Date: June 17, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods Tess than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. I IHvdraulic Overview 70'4 5-r'a.t Job Number: KS0421 •117W - 41 Report Description: WET SYSTEM Job Job Number Design Engineer KS0421 CHRIS J. ISAAC Job Name Phone FAX LADY FOOTLOCKER 206-491-6679 425-881-3030 Address 1 State Cert icationA icense Number 1560 SOUTH CENTER MALL WESTESF136QF Address 2 AHJ CITY OF TUKWILA City State Zip Code Job Site TUKWILA WA 98188 SOUTH CENTER MALL System Density Area of Application 0.20gpm/ft2 1011.63ft2 (Actual 1011.63ft2) Most Demanding Sprinkler Data Hose Streams 5.6 K -Factor 23.10 at 17.016 250.00 Coverage Per Sprinkler Number Of Sprinklers Calculated 115.50ft2 13 System Pressure Demand System Flew Demand 106.667 382.30 Total Demand Pressure Result 632.30 @ 106.667 +32.714 (23.5%) Supplies Check Point Gauges Node Flowlaom) Hose Flow(oom) Static(osil Residual(psi) Identifier Pressure(Dsil K-Factor(K) Flow(dbm) 1 10900.00 250.00 140.000 20.000 0.141. 44P4e, i ki. 41 1►lar2LiV;i: 41440 ti LADY FOOTLOCKER FP-1.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) 1 me 150 Static 1 Pressure 140.000 135 120 • 32.30 with hose streams 105 82.30 @ 106.66/ .N 90 a =d 75 N N �'60 a System demand curve I IFI 45 30 10900.00 @ 20.000 15 a 1111111111111111111111111111 111111111 111111111 111111111 111111111 111111111 0 1.93010 5500 6600 7700 8800 9900 11000 Water flow, gpm [A� ©M.E.P.CAD, Inc. ;?4 AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:33PM Page 1 VIHydraulic Summary Job Number: KS0421 Report Description: WET SYSTEM Job Job Number KS0421 Job Name LADY FOOTLOCKER Address 1 1560 SOUTH CENTER MALL Address 2 City State Zip Code TUKWILA WA 98188 Design Engineer CHRIS J. ISAAC State Certification/License Number WESTESF136QF AHJ CITY OF TUKWILA Job Site SOUTH CENTER MALL Drawing Name LADY FOOTLOCKER FP-1.cad System . Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 23.10 at 17.016 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(gpm) Occupancy Ordinary Group II Density 0.20gpm/ft2 Number Of Sprinklers Calculated 13 Area of Application 1011.63ft2 (Actual 1011.63ft2) Coverage Per Sprinkler 115.50ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Including Hose Allowance) 382.30 632.30 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 27.61 between nodes 135 and 52 Witham Velocdy Under Ground 1.44 between nodes 1 and 389 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2514.63ga1 0.75ft3 Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.381 632.30 106.667 32.714 Contractor Contractor Number KS0421 Contractor Name Western States Fire Protection (Redmond) Add., 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Chris J Isaac Phone (425)881-0100 FAX (425)881-3030' E-mail chris.isaac@wsfp.us Web -Site Contact The Designer Extension © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:34PM Page 2 41 Summary Of Outflowing Devices Device Job Number: KS0421 Report Description: WET SYSTEM Actual Flow Minimum Flow K -Factor Pressure (gpm) (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 102 103 109 101 105 104 108 113 106 110 107 111 112 E.> Most Demanding Sprinkler Data 23.59 23.61 31.68 23.10 23.95 23.70 31.35 43.99 27.08 31.92 30.15 33.11 35.08 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 17.739 17.770 32.002 17.016 18.293 17.912 31.341 61.706 23.392 32.492 28.984 34.952 39.236 (A�, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:35PM Page 3 it Node Analysis Job Number: KS0421 Report Description: WET SYSTEM Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 14 15-3 E(2-0) 22.045 20 15-3 PO(5-0) 22.079 23 15-3 E(2-0) 39.384 26 15-3 PO(5-0) 22.418 31 15-3 PO(5-0) 23.492 34 15-3 PO(5-0) 23.634 39 15-3 PO(5-0) 39.799 42 15-3 E(2-0) 80.331 46 15-3 PO(5-0) 28.370 48 15-3 PO(5-0) 41.285 52 15-3 PO(5-0) 35.312 54 15-3 PO(5-0) 44.456 63 15-3 PO(5-0) 49.971 134 15-3 P0(8-0) 84.909 135 15-3 P0(8-0) 84.630 136 15-3 P0(8-0) 84.570 257 14-2 P0(26-4) 92.883 334 1-11 99.473 389 5-8 BFP(-4.500) 102.384 398 1-11 P0(37-8%) 99.402 102 11-0 Spr(-17.739) 17.739 103 11-6 SEr(-17.770) 17.770 109 11-6 Spr(-32.002) 32.002 101 12-6 Spr(-17.016) 17.016 105 11-6 Spr(-18.293) 18.293 104 12-6 Spr(-17.912) 17.912 108 12-0 Spr(-31.341) 31.341 113 12-0 Spr(-61.706) 61.706 106 12-6 Spr(-23.392) 23.392 110 12-0 Spr(-32.492) 32.492 107 12-6 Spr(-28.984) 28.984 111 12-0 Spr(-34.952) 34.952 112 12-0 Spr(-39.236) 39.236 1 -4-0 S 106.667 23.59 23.61 31.68 23.10 23.95 23.70 31.35 43.99 27.08 31.92 30.15 33.11 35.08 382.30 L, © M.E.P.CAD, Inc. 2 AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:35PM Page 4 III Hydraulic Analysis1 Job Number: KSO421 Report Description: WET SYSTEM Pipe Type Downstream Upstream Diameter Elevation Flow Velocity HWC Discharge K-Factor Pt Friction Loss Length Pressure Pn Fittings Eq. Length Summary Total Length " Route 1 BL 1.049 Q=23.10 8.58 C=120 0.169886 25-9 Pf 6.582 101 12-6 q=23.10 K=5.6 17.016 Spr(-17.016) 13-0 Pe -1.180 26 15-3 22.418 4E(2-0), PO(5-0) 38-9 Pv BL 1.610 0=70.29 11.08 C=120 0.165270 6-6 Pf 1.074 26 15-3 22.418 Pe 31 15-3 23.492 6-6 Pv BL 1.610 Q=94.24 14.85 C=120 0.284302 0-6 Pf 0.142 31 15-3 23.492 Pe 34 15-3 23.634 0-6 Pv BL 1.610 Q=117.94 18.59 C=120 0.430542 11-0 Pf 4.736 34 15-3 23.634 Pe 46 15-3 28.370 11-0 Pv BL 1.610 0=145.03 22.86 C=120 0.631110 11-0 Pf 6.942 46 15-3 28.370 Pe 52 15-3 35.312 11-0 Pv BL 1.610 0=175.18 27.61 C=120 0.895055 47-1 Pf 49.318 52 15-3 35.312 8-0 Pe 135 15-3 84.630 P0(8-0) 55-1 Pv CM M 4.260 Q=338.31 7.62 C=120 0.026465 10-6% Pf 0.279 135 15-3 84.630 Pe 134 15-3 84.909 10-6% Pv CM 4.260 Q=38.2.30 8.61 C=120 0.033181 151-8 Pf 7.504 134 15-3 84.909 74-6 Pe 0.470 257 14-2 92.883 LtE(7-11), 2P0(26-4), 2Ee1(5-3), 226-2 Pv fEE(3-5) CM 6.357 Q=382.30 3.86 C=120 0.004724 102-1 Pf 1.211 257 14-2 92.883 154-4 Pe 5.307 398 1-11 99.402 3fE(10-0), E(17-7), fT(25-0), 256-5 Pv CV(40-3), GV(3-9Y:), PO(37-8%) FM M 8.329 0=382.30 2.25 C=120 0.001267 24-8''A Pf 0.072 398 1-11 99.402 32-0 Pe 0.000 334 1-11 99.473 2fE(16-0) 56-8'% Pv MS 10.020 0=382.30 1.56 C=120 0.000515 20-2 Pf 4.545 334 1-11 99.473 67-0 Pe -1.635 389 5-8 102.384 3LtE(16-0), BV(19-0), BFP(-4.500) 87-2 Pv VG 10.400 0=382.30 1.44 C=140 0.000323 113-1 Pf 0.084 389 5-8 102.384 146-8 Pe 4.200 1 -4-0 106.667 3LtE(25-6), E(35-1), 2EE(17-6Y:), S 259-9Y2 Pv Route 2 BL 1.049 0=23.59 8.76 C=120 0.176560 26-9 Pf 6.135 102 11-0 q=23.59 K=5.6 17.739 Spr(-17.739) 8-0 Pe -1.830 14 15-3 22.045 4E(2-0) 34-9 Pv BL 1.610 0=23.59 3.72 C=120 0.021919 1-61: Pf 0.034 14 15-3 22.045 Pe 20 15-3 22.079 1-61,4Pv BL 1.610 0=47.19 7.44 C=120 0.079082 4-3Y2 Pf 0.339 20 15-3 22.079 Pe 26 15-3 22.418 4-3Y: Pv GA, Route 3 BL 1.049 0=23.61 8.76 C=120 0.176840 26-6 Pf 5.922 103 11-6 q=23.61 K=5.6 17.770 Spr(-17.770) 7-0 Pe -1.613 20 15-3 22.079 E(2-0), PO(5-0) 33-6 Pv a Route 4 BL 1.049 0=23.70 8.80 C=120 0.178148 25-9 Pf 6.902 104 12-6 q=23.70 K=5.6 17.912 Spr(-17.912) 13-0 Pe -1.180 34 15-3 23.634 4E(2-0), PO(5-0) 38-9 Pv w Route 5 BL 1.049 0=23.95 8.89 C=120 0.181652 28-6 Pf 6.812 105 11-6 q=23.95 K=5.6 18.293 Spr(-18.293) 9-0 Pe -1.613 31 15-3 23.492 2E(2-0), PO(5-0) 37-6 Pv a Route 6 BL 1.049 0=27.08 10.05 C=120 0.228045 22-0 Pf 6.157 106 12-6 q=27.08 K=5.6 23.392 Spr(-23.392) 5-0 Pe -1.180 46 15-3 28.370 P0(5-0) 27-0 Pv w Route 7 BL 1.049 0=30.15 11.19 C=120 0.278053 22-0 Pf 7.507 107 12-6 q=30.15 K=5.6 28.984 Spr(-28.984) 5-0 Pe -1.180 52 15-3 35.312 P0(5-0) 27-0 Pv 6. Route 8 BL 1.049 0=31.35 11.64 C=120 0.298901 23-11% Pf 9.855 108 12-0 q=31.35 K=5.6 31.341 Spr(-31.341) 9-0 Pe -1.396 39 15-3 39.799 2E(2-0), PO(5-0) 32-111: Pv Ga. (e) M_E_P_CAD Inc 43AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:36PM Page 5 (i Hydraulic Analysis 1 Job Number: KS0421 Report Description: WET SYSTEM Pipe Type Diameter Flow Velocity Downstream Elevation Discharge K -Factor Upstream HWC Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length BL 1.610 Q=63.03 9.93 C=120 0.135073 11-0 Pf 1.486 39 15-3 39.799 Pe 48 15-3 41.285 11-0 Pv BL 1.610 Q=94.95 14.96 C=120 0.288260 11-0 Pf 3.171 48 15-3 41.285 Pe 54' 15-3 44.456 11-0 Pv BL 1.610 Q=128.06 20.18 C=120 0.501318 11-0 Pf 5.515 54 15-3 44.456 Pe 63 15-3 49.971 11-0 Pv BL 1.610 Q=163.14 25.71 C=120 0.784560 36-1 Pf 34.599 63 15-3 49.971 8-0 Pe 136 15-3 84.570 P0(8-0) 44-1 Pv CM 4.260 Q=163.14 3.67 C=120 0.006865 8-9'% Pf 0.060 136 15-3 84.570 Pe 135 15-3 84.630 8-9% Pv w Route 9 BL L 1.049 0=31.68 11.76 C=120 0.304727 23-6 Pf 8.995 109 11-6 q=31.68 K=5.6 32.002 Spr(-32.002) 6-0 Pe -1.613 23 15-3 39.384 3E(2-0) 29-6 Pv BL 1.610 Q=31.68 4.99 C=120 0.0.3.7831 11-0 Pf 0.416 23 15-3 39.384 Pe 39 15-3 39.799 11-0 Pv Route 10 BL 1.049 Q=31.92 11.85 C=120 0.309044 23-11'/ Pf 10.189 110 12-0 q=31.92 K=5.6 32.492 Spr(-32.492) 9-0 Pe -1.396 48 15-3 41.285 2E(2-0), PO(5-0) 32-11% Pv w Route 11 BL 1.049 Q=33.11 12.29 C=120 0.330623 23-11'/z Pf 10.901 111 12-0 q=33.11 K=5.6 34.952 Spr(-34.952) 9-0 Pe -1.396 54 15-3 44.456 2E(2-0), PO(5-0) 32-11% Pv Gal Route 12 BL L 1.049 Q=35.08 13.02 C=120 0.367943 23-11% Pf 12.131 112 12-0 q=35.08 K=5.6 39.236 Spr(-39.236) 9-0 Pe -1.396 63 15-3 49.971 2E(2-0), PO(5-0) 32-11% Pv Route 13 BL 1.049 Q=43.99 16.33 C=120 0.559339 25-9Yz Pf 20.022 113 12-0 q=43.99 K=5.6 61.706 Spr(-61.706) 10-0 Pe -1.396 42 15-3 80.331 5E(2-0) 35-9',4Pv BL 1.610 Q=43.99 6.93 C=120 0.069440 57-11 Pf 4.578 42 15-3 80.331 8-0 Pe 134 15-3 84.909 P0(8-0) 65-11 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only)II C Value Multiplier Actual Inside Diameter 4'87 ( ) Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter =Factor Multiplying Factor 0.713 1.16 1.33 1.51 [M, ©M.E.P.CAD, Inc. :? AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:36PM Page 6 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0421 Report Description: WET SYSTEM Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points E Velocity pressure at a point in a pipe EE Eel Ee2 FDC fE fEE flg FN fT 9 GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z ALV Alarm Valve AngV Angle Valve b Bushing BaiV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeIV Deluge Valve DPV Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Tum 90° Tee Run Union Wirsbo Water Meter Valve Cap ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:36PM Page 7 Hydraulic Graph 1 Job Number: KS0421 Resort Description: WET SYSTEM Supply at Node 1 150 -Static Pressure 140.000 135 120 105 632.30 -82.30 with hose @ 106.667 streams 90 .y 0 ill 75 co N E a` 60 System J demand curve 45 30 10900.00 @ 20.000_ 15 JO -beilium iiiiiiii iiiitiiii iiiiiiiii 11111111/ 111111_11 l_ 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 11002200 3300 4400 5500 6600 7700 Water flow, gpm 8800 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.381 @ 632.30 System Demand 382.30 @ 106.667 System Demand (Including Hose Allowance) 632.30 @ 106.667 A[^ ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:37PM Page 8 i�� Flow Diagram (Top View) 1 Job Number: KS0421 Report Description: WET SYSTEM (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:37PM Page 9 LADY FOOTLOCKER #1560 VICINITY MAP (Suite #1560) SCALE: N General Notes 1. Western States Fire Protection to add new pendenth, heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class 11 Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyIn the areas of work. All other areas are not in contract and WSFP is not responsible for exiting conditions. 10 LI U Ea Ci En EXISTING PIPE NEW PIPE ZONE T1 MAIN RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS C42 CL 2 ®11'-r AF.f. Ordinary Group II.0.20gpm/ft2 for 1011.63ft2 7 .4)17-0" AFS. CL.l Q t2 r AFF. CL -i 11'-0'A.FF. FCL -1 611'-0' f.F CT 1 @ 6'A' AFF. 44 w k uIiiIII:1IJ1IEI Nil O n CL@tY-0'AF7 CO CL.4 a 4A' AFS. 1-2 4 ,14 1 1 1 1 1 1 1 LADY FOOTLOKER LADY FOOTLOCKER Remote Area: Retail # 1560 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 FY DENSITY .20 GPM / FP for 1011.63 Ft' SPRINKLER Reliable Model G4A/ F1FR ORIFICE 1/2" x= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 382.30 GPM © 102.38 PSI At time of Design REMOTE AREA REDUCTION - 37% 945 SD/FT int a* eta m m i m lama fit— — — — ima an ra — — IT Eti or 1/8" = 1'-0 Sprinkler Legend 1 3 5 7 9 11 APPROVAL: CITY OF TUKWILA SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS FLEXHEAD DETAIL NOT TO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING OI 31B' KWIK BOLT �{21M' EMBED LENGTH) BRACE PIPE FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE DESCRIPTION K SPRAY MFR./MODEL R3615 Pendent Chrome 155°F REL F1FR SSP CONT. NO.: KS0421 R5415 Pendent 155°F REL CONCEALOR HYDRAULIC REFERENCE POINT Total = 31 HANGER SYMBOL DRAWN BY: SPRK. ON SHEET: SEE LEGEND BRANCHLINE RESTRAINT SPRK. ON JOB: DATE: 06/10/08 FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT FIG. 4A PIPE CLAMP FOR SWAY BRACE OLATERAL BRANCHLINE RESTRAINT t ' NON -THREADED BRACE PIPE 31B' KWIK BOLT (2 IW EMBED LENGTH) BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C-HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension V`J stamps must be HANGER DfisAcM,teforepipe hung. Do not paint piping prior to hydrostatic test NOT TO SCALE LADY FOOTLOCKER iC w 0 ACCEPTED Without Comments As Noted In Red Per The Attached Letter !nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is suhiect to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this_acceptanCe and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bure VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/ DALLAS l DECATUR!DENVER!DULUTH /HOUSTON/KANSAS CITY LAS VEGAS/MINNEAPOLIS I PHOENIX) PORTLAND / RAPID CITY! ST. PAIR! SALT LAKE CITY / SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 TUKWILA FIRE DEPARTM f %. Please call: 575.4407 and give this job No. 08---S-33 and exact address for shut. icwn or restoration aporov, PAID JUN 16 2008 Tukwila Fire/2404,(4,47 LADY FOOTLOCKER 1�6f)-SOUTH CENTER MALL 3°Y TUKWILA,WA 98188 LADY FOOTLOCKER Q. FP -1 OF 1 MARKET CONTRACTORS LTD CONTRACTO SHEET FiLL COPY I 1 U'V 3ER S ET TITLE SHEET INDEX LA F FIRE ALA TUKWI 1 A FA -01 SY E IV I \ FO MATI 0 FA -02 TYPICAL DETAILS - WRI \G AND VOU\TI\ FA -03 FRE ALA V SYSTEM FLOC) P LA \ FA -04 SYSTE IV I I CALCU LATI 0 \ S GE\ EAL), SITE PLA\ 11! 4„ tZ IMINNIMIldilltrillIt.EM161411110011121, • idf.tt! 11 • : \i‘4thOtA CornMentt 0 A ikted in Rd 0 Pr The Attactied • ! ' 1 nese plans h....1‘,./i);vi.:,..o,.ed by The Tvk,.qit.a.P1';;,'.: !, Prevention Burenj-orl.pon.forManc.e w".th c.urr.':•:-.4 Oily ,. . - standards. ,e8.4::.cricu iii. fi,..ibp.::: to ein..;cs 37`4,1 !. : omissions ‘A..nit".::. do...lot.autnorze violziticnii of .s(.1ptod I ...' stancaros and ol'Otnant.,:s. -111,4 re;4>oris.I.t.,/ forr...-..- adequacy of desiGii.r&Ststoti.4116, with tilf:. Additions, dionti.,.oi! 'rh•visii.3.4 hp those dr....,,,....inc•r,.:-1r this date will void thiii,nL:;cept'ace and ',,,,i'll r.t.:,quire-L. resubmittal ofrrsvined c'i.i3win•gi-", for f.;.'ut.)sequ.,:nt p.r.ovz...1. , Final accptr.3,ncci l'.,3.,;;:b)0(...;11.(o.tielci test and inspiection bv The Tukwila Fire Prow...W.-ion biireat.i. . ! ... [Date: 51)26101_ , By: L' Ars"' ) ( L 1 : . . , , . • i: , HI .i, • ,. TUKWILA FIRE DEPARTivitm Please call: 575-4407. and give this job' No. ()1 F -- and exact address for shut. ..lown or restora ion aOo.roval1; NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE !!. SHIELDED WIRE SCHEDULE AND CONDUIT FILL CHART ..„ WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE V/RAPPED WITH TAPE AND TAPED AT END EUPJ CKER STEM ASHINGTON ERAL NOTES FOR SIEMENS SYST DO NOT INSTALL ADDRESS BLE.' ITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. .!L . • •, • , 1. NUMBERS ADJACENT TO DEICE' SY' BOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE S COND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CI UIT.PiILARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WI ING IS !SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIB4 4. INSTALLATION SHALL BE IN ONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, 4; CA4 C. DE(S), AND/OR AUTHORITY HAVING JURISDICTION. . CON 1JIT, WIRE, FITTINGS, HANGERS, ICS.10 LE, FITTINGS, AND ASSOCIATED EQUIP ly ENT) NS EBERUS DIVISION. 5. INSTALLATION MATERIALS (ii STANDARD BOXES, FIBER 0F ARE NOT SUPPLIED BY SIEij 6. DETECTORS SHALL NOT BE I, AIR STREAM OF AIR SUPPLY 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLOR AND UNIQUELY MARKED FOR 8. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" g. FOR ADDITIONAL INSTALLATI SHEETS AND/OR INSTALLATI 10. THE 120vac POWER ELECTR) MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-5 SOURCES. 120vac POWER S DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND SII; OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND 14. ALL 120VAC CIRCUITS ARE GENERATOR. .1. IOUNTEJ IN DIRECT ,OUTLE, S. PER NFPA 72 2-3.5.1 WLFHiESPECT TO CONDUCTOR SIZE, (Sc OR CABLE TRAY, CODE. rCONDUCTORS SHALL BE PERMANENTLY, ]FUTUR ' IDENTIFICATION. LL R IURN ONE SET OF ACCURATELY MARKED [JRPOS N INS UCTIONS, REFER TO CATALOG CUT N INS UCTIONS. AL \A,/, .725. .5.2: "1 ALL N ALAR OBE. D DROP K SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. VICES SHALL BE MOUNTED AT A HEIGHT D CEILING, WHICHEVER IS LESS. SI 'Ali DE MOUNTED AT 48" A.F.F. TO THE WILL BE ON THE RECORD DRAWINGS SET. Roy, EDICATED' CIRCUITS FROM THE EMERGENCY 15. PER NFPA 72 SECTION 5- .6.1.3 ,ETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN UP Or1IALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIR D BY: .HE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C DETECTORS THAT HAVE BEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANE OR R tLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. . 16. WIRING SHALL RUN CONTIN OUS F, FACP TO FIRST DEVICE. ON .A CIRCUIT AND THEN FROM DEVICE T HDEVId WITHOUT . SPLICING; IN PULL BOXES OR .. OTHER BACK BOXES OF DI :ERENi CIRCUITS. 17. ALL WIRING SHALL BE MET ED, '\) RIFIED TO BE CONTINUOLiS,FREE OF .GROUND AND FREE OF SHORTS BET EENINDUCTORS AND OTHERH CIRCUITS, PRIOR TO' FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MA KED A PERMANENT LABEL AT ALL DEVIC 19. THE ELECTRICAL CONTRAC R OUTSIDE AND INSIDE OF T FIRE AFTER COMPLETION OF TH R INS 20. DETECTORS MUST BE RATE FO'R IT IS LOCATED. I H 21. ALL WIRING BETWEEN FLOC) SskA 22. NFPA 72 2007 6.4.2.2.2 ALj STYL PHYSICAL CONDUCTORS (E.G, META INSTALLED SUCH THAT THE FCC)! FROM AND RETURNING TO T E CO ROUTED SEPARATELY. THE LJTG0,1 CONDUCTORS SHALL NOT B RUI4 MULTI -CONDUCTOR CABLE), NCLO 23. nI NFPA 72 2007 A.6.4.2.2.2 ADEQUATE SEPARATION BET THIS SEPARATION IS REQUIR CABLES FROM PHYSICAL DA SEPARATION TO PREVENT P THE CABLE IS INSTALLED V CABLE IS INSTALLED INDICATED ON FIRE ALARM .RISER WITH A , JUNCTION BOXES .AND FACP. L CLEAN ALL DIRT AND DEBRIS FROM THE LARM BACK BOXES AND JUNCTION BOXES LLATION. EMPERATURE IN THE ENVIRONMENT IN WHICH BE LOCATED IN COM*: OF CLASS A CIRCUITS USING LIC, OPTICAL FIBER) :SHALL BE G AND RETURN CONDUCTORS, EXITING ROL UNIT, RESPECTIVELY, ARE AND RETURN (REbuNANTy CIRCUIT THE SAME CABLE ASSEMBLY (LE., ,RE, OR RACEWAY. GOA"' OF 6.4.2.2.2 IS TO 'PROVIDE EEN E OUTGOING AND RETURN .CABLES. D TO'ELP ENSURE PROTECTION OF THE ACP E RECOMMENDED MINIMUM '1; YSICAILI1 DAMAGE 'IS 305 MM. (1 FI) :WHERE •.. ' TIC4 AND 1.22 M (4 FT) ,WHEREI THE QUANTITY 3 2 EX SYN 00L, bESCRIPTIQN SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT 11jI FACP IFIRE ALARM EX 'CONTROL PANEL 0. FARA XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP. FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP ' 7 MR WIRE DESIGNATION .• . : : . SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE ' . COLOR CODE D H P S 2S A V 2V I X UD UI M B DATA. 'LINE -ADDRESSABLE LOOP I TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) 'DOOR 'HOLDER POWER - 24.VDC : TWO #14 FPL/FPLR RED (JACKET) DEVICE POWER - 24VDC ' TWO #16 FPL/FPLR RED (JACKET) STROBE CIRCUIT - FEED : TWISTED PAIR \AU SHIELD #12 FPL/FPLR RED (JACKET) STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) ANNUNCIATOR TWISTED PAIR \e,,// SHIELD .#16 'FPL/FPLR RED (JACKET) ! . SPEAKER CIRCUIT - FEED ' : TWISTED PAIR #14 FPL/FPLR RED (JACKET) SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED. (JACKET) REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED '(JACKET) UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLRRED (JACKET) 'DOOR HOLDER POWER TWD #16 FPL/FPLR RED (JACKET) BEAM 'DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) . , 1fl'WITH . , . , . , . CONDUIT FILL CHART • ,.. : . . ,. INTERFACE MODULE HTRI-R SIEMENS 4S DEEP VERIFY RELAY IN FIELD . . • . NO. OF CONDUCTORS VOLTS WIRE SIZE : TYPE : DIMENSIONS , AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 •' : ! t TWO 600V /114 AWG THHN/THWN TWISTED .210 0.L% ! .0346 TWO CONDUCTOR 300V #18 AWG FPL TW ,CABLE . : .156 0.D, .0191. ! - . . . . CONDUIT FILL , : : CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM , !,,..THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL • : ... 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE: 4. ..„ WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE V/RAPPED WITH TAPE AND TAPED AT END EUPJ CKER STEM ASHINGTON ERAL NOTES FOR SIEMENS SYST DO NOT INSTALL ADDRESS BLE.' ITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. .!L . • •, • , 1. NUMBERS ADJACENT TO DEICE' SY' BOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE S COND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CI UIT.PiILARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WI ING IS !SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIB4 4. INSTALLATION SHALL BE IN ONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, 4; CA4 C. DE(S), AND/OR AUTHORITY HAVING JURISDICTION. . CON 1JIT, WIRE, FITTINGS, HANGERS, ICS.10 LE, FITTINGS, AND ASSOCIATED EQUIP ly ENT) NS EBERUS DIVISION. 5. INSTALLATION MATERIALS (ii STANDARD BOXES, FIBER 0F ARE NOT SUPPLIED BY SIEij 6. DETECTORS SHALL NOT BE I, AIR STREAM OF AIR SUPPLY 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLOR AND UNIQUELY MARKED FOR 8. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" g. FOR ADDITIONAL INSTALLATI SHEETS AND/OR INSTALLATI 10. THE 120vac POWER ELECTR) MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-5 SOURCES. 120vac POWER S DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND SII; OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND 14. ALL 120VAC CIRCUITS ARE GENERATOR. .1. IOUNTEJ IN DIRECT ,OUTLE, S. PER NFPA 72 2-3.5.1 WLFHiESPECT TO CONDUCTOR SIZE, (Sc OR CABLE TRAY, CODE. rCONDUCTORS SHALL BE PERMANENTLY, ]FUTUR ' IDENTIFICATION. LL R IURN ONE SET OF ACCURATELY MARKED [JRPOS N INS UCTIONS, REFER TO CATALOG CUT N INS UCTIONS. AL \A,/, .725. .5.2: "1 ALL N ALAR OBE. D DROP K SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. VICES SHALL BE MOUNTED AT A HEIGHT D CEILING, WHICHEVER IS LESS. SI 'Ali DE MOUNTED AT 48" A.F.F. TO THE WILL BE ON THE RECORD DRAWINGS SET. Roy, EDICATED' CIRCUITS FROM THE EMERGENCY 15. PER NFPA 72 SECTION 5- .6.1.3 ,ETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN UP Or1IALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIR D BY: .HE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C DETECTORS THAT HAVE BEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANE OR R tLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. . 16. WIRING SHALL RUN CONTIN OUS F, FACP TO FIRST DEVICE. ON .A CIRCUIT AND THEN FROM DEVICE T HDEVId WITHOUT . SPLICING; IN PULL BOXES OR .. OTHER BACK BOXES OF DI :ERENi CIRCUITS. 17. ALL WIRING SHALL BE MET ED, '\) RIFIED TO BE CONTINUOLiS,FREE OF .GROUND AND FREE OF SHORTS BET EENINDUCTORS AND OTHERH CIRCUITS, PRIOR TO' FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MA KED A PERMANENT LABEL AT ALL DEVIC 19. THE ELECTRICAL CONTRAC R OUTSIDE AND INSIDE OF T FIRE AFTER COMPLETION OF TH R INS 20. DETECTORS MUST BE RATE FO'R IT IS LOCATED. I H 21. ALL WIRING BETWEEN FLOC) SskA 22. NFPA 72 2007 6.4.2.2.2 ALj STYL PHYSICAL CONDUCTORS (E.G, META INSTALLED SUCH THAT THE FCC)! FROM AND RETURNING TO T E CO ROUTED SEPARATELY. THE LJTG0,1 CONDUCTORS SHALL NOT B RUI4 MULTI -CONDUCTOR CABLE), NCLO 23. nI NFPA 72 2007 A.6.4.2.2.2 ADEQUATE SEPARATION BET THIS SEPARATION IS REQUIR CABLES FROM PHYSICAL DA SEPARATION TO PREVENT P THE CABLE IS INSTALLED V CABLE IS INSTALLED INDICATED ON FIRE ALARM .RISER WITH A , JUNCTION BOXES .AND FACP. L CLEAN ALL DIRT AND DEBRIS FROM THE LARM BACK BOXES AND JUNCTION BOXES LLATION. EMPERATURE IN THE ENVIRONMENT IN WHICH BE LOCATED IN COM*: OF CLASS A CIRCUITS USING LIC, OPTICAL FIBER) :SHALL BE G AND RETURN CONDUCTORS, EXITING ROL UNIT, RESPECTIVELY, ARE AND RETURN (REbuNANTy CIRCUIT THE SAME CABLE ASSEMBLY (LE., ,RE, OR RACEWAY. GOA"' OF 6.4.2.2.2 IS TO 'PROVIDE EEN E OUTGOING AND RETURN .CABLES. D TO'ELP ENSURE PROTECTION OF THE ACP E RECOMMENDED MINIMUM '1; YSICAILI1 DAMAGE 'IS 305 MM. (1 FI) :WHERE •.. ' TIC4 AND 1.22 M (4 FT) ,WHEREI THE QUANTITY 3 2 EX SYN 00L, bESCRIPTIQN SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT 11jI FACP IFIRE ALARM EX 'CONTROL PANEL 0. FARA XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP. FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP ' 7 MR 1 1 L -L"" i,l, VIL.IVILI IV r • ,v • .- • TO TOP r.o.u. EX POWER SUPPLY 1fl'WITH ; INTERFACE MODULE HTRI-R SIEMENS 4S DEEP VERIFY RELAY IN FIELD 'il 'INTERFACE I ' DUAL INPUT HTRI-D SIEMENS 4S DEEP VERIFY MODULE IN FIELD ; F.B4O, N/A SIEMENS 4S DEEP VERIFY A. H P ABOVE FINISHED ONTROL POINT HCP MODULE IN FIELD N/A N/A N/A '1 SIEMENS 4S DEEP VERIFY N/A N/A ' N/A N/A REMOTE CONVENTIONAL HZM ' ' IN FIELD IA • l'i\lOT II1APPLICABLE u; IZONE MODULE N/A 1-i-. • LINEAR BEAM PBA -1191 SIEMENS PROVIDED VERIFY SMOKE DETECTOR IN FIELD 'Il. DI , iIIJNLESS OTHERWISE ,,, N/A SMOKE DETECTOR HFP-11 VV/ SIEMENS 4S DEEP CEILING (ADDRESSABLE -PHOTO) DB -11 BASE , W/ 1G RING ,• . , DUCT SMOKE AD2-P W/ SIEMENS DUCT HOUSING VERIFY DETECTOR TSM MODULE . IN FIELD :ijEATHERPROOF ,;DEVICE N/A N/A , 'HEAT DETECTOR HFPT-11 W/ SIEMENS 4S DEEP CEILING (ADDRESSABLE) DB -11 BASE W/ 1G RING 0) LI .0 FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING , (CEILING MOUNT) W/ 1-1/2'' EXT. 01; Pi . ',FIRE ALARM SPEAKER STROBE SET -MC -W SIEMENS . 4S DEEP BOX 80" A.F.F. (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM (It GR FIRE ALARM SPEAKER STROBE SET -HMC -CW SIEMENS 4S DEEP BOX CEILING (CEILING MOUNT) W/ 1-1/2" EXT. J..' , FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S BOX CEILING I'(CEILING MOUNT) , W/ 1G RING ' L 4.1 .I ' FIRE ALARM STROBE ZR MC -W SIEMENS 4S BOX 80" A.F.F. (WALL MOUNT) W/ 1G RING TO BOTTOM U.O.N. CP N/A TIRE ALARM ;SPEAKER SET -CW SIEMENS 4S DEEP BOX CEILING i(CEILING MOUNT) W/ 1-1/2" EXT. N/A I ' ;FIRE ALARM ;SPEAKER SET -W SIEMENS 4S DEEP BOX 80" A.F.F. !(WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM .STROBE SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY ! WP l(WEATHERPROOF) 1/2" PIPE IN FIELD KAI 11 T1 \ II TA r•C kAD_Orli l'rs AID Dpnnt IT c A_C pinY VRPI T. ,CONTROL RELAY MAGNETIC DOOR HOLDER MI 1 \ 1 I \ I V IN IN FIELD F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX I -I. ALAKM TERMINAL CABINET r.o.u. r.175.o. r.o.u. V L.1\11 1 IN FIELD DESCRIPTION (9 'il ' I il JUNCTION BOX F.B4O. F.B4O, N/A VERIFY IN FIELD A. 1, F. 1!1 I ' o' f-LOOR ABOVE FINISHED N/A N/A N/A N/A '1 SH E D BY ,1:3linFi:_Uli HERSRN 0 N/A N/A ' N/A N/A IA • l'i\lOT II1APPLICABLE u; N/A N/A ' . N/A N/A Li, 'Il. DI , iIIJNLESS OTHERWISE ,,, N/A N/A N/A N/A , :ijEATHERPROOF ,;DEVICE N/A N/A . . N/A N/A 6 RD IIAS BUILT ,IADD OR CHANGE N/A N/A N/A N/A GR EN•IIAS BUILT REMOVE N/A N/A N/A N/A BLUE 1, IIAS BUILT NOTES TO CAD N/A N/A N/A N/A ' 1 1 , ! 1 .t ti Copyright , P4 ( Tuk t 2006 by Guardian Security Systems, ;Inc.; All Rights (/) z0 LU Ct uJ (/) _J L1J REV. BY: Ii I"' ! :"..i'l't!i'liti-; '''' 1 ' 1 '', '1'1.I11,r,,, ,:1•11 1,,,Ii 1',,P,,IIi" I' . .• 1.. .,, • ,. ",,, , DESCRIPTION SHOP --DRAWINGS - _ _ _ ;",.11I ..1•II.."11;;;" ,... l'1.1.••I,I"I.I."';'• i'II 'I, !I ,,,':',.',1.1•.,I".',..,,,i'.,,,: '11,1 1, ::'' , I •1.,-,' 'I.. ,.. 1,, ,,'""".„I'1.I''..,;II...'.;•,.: '';'11.., ."1.'"•'',. I ' '•• Is .•!!! .:I4.1',', 1,;II;H ;,I 11 ,:il, I•eI,!:•• '',',..' "I, ' 1' :' , , ..1,„' t' I'' 1 o ul , ,i, ! :', 1,1: • ' ',. I.!,/1., : ,' 1' 'I t ' •.II; !!.!,. i .1.1.1., • 11.1.! ,h'i; • i,1: "."‘!! ! I.,1, c,!,'Iti' kj'....t, ;Ilt...!.1.1. ti.'''.1 ' .• ' .1 ': ' I I Hi' lIt i a Fire Reserved .„„.„ 0 ‘CALE:" DESIGNEDkOY.v, R.VEZZANIIH' DATE: 5rni/o BACKROUNRKAN '1F?0,11DED: BY: ; 1, •i. I 01::tt I'll. I • II 'I I• • I • I • 1-4 U) aco 0G' NORTH LADY FOOTLO SCALE 118'=1' b 2S,2V r., r 1 SALE, AREA 35 Pa7R 0LCBJFE LINE L?:P- Gf rt11-u.K Tl444JBIT;1d 1 AvOVd 14 P414EL44 a 7'-0" nr• , 43 -� 43'-4REA ESTFIELD SOUTHCENTER MALL ,j' rll HI I • T,AG NOTES FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED, BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR: SIEMENS HTRI-D ADDRESSABLE INUT WIT, I 1-10013 VCNILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I\ST _L ADDR=SSABLE N DEVICES UNTIL PREPROGRAMMED W DEVICES DDHSS. OTIAT T Copyright 2006 by Guardian Security Systems, Inc. All Rights I� ,11 (.) z 0 LL�w�y W LU J W REV. BY: r I I y IIa�' .0.V.:(7.4:: ifl II'' �� .L� I' 11 a.e!3a4ae I-- DESCRIPTION SHOP --DRAWINGS _ - - - ii' II •;!'II, I.f I :I •i'' 1 , i li Ifi 4 91 i ' ' 'i Yi; DATE N,I I "i' 141 ,I,, 1i 1+ Lf)I ,1'fK �;, ,, , 1' :; 1;, — -•>-__ i .. ..-.1•.I r1 l,�L �_ - -__ _'i q , 't-+ rias-(ur"'- -- :Z I.. .- T!'_Z' I •,•r t I i F 1II-7'3'43' t ti' ' II L 15 �S..1140++•I i ,- 0" r2" F A` i ...... •4 CN1.S,2V as,2V ... . Ii' I• \ -- _ II O P21 -,._- Iunser 2S,�y_!./ rc t• ""~4,Nr: tf M. 1 �MM Q �� • FLOOR rR:31 e!&VEE r• ED .AND AP.7.:3,/cD NM �© Iia �,_: i r; - ,moi-,: T;M45 „..4104 I'I R -1A3 SAP.; T,, 3E :1=pari..it...,,r.-,Alg.)01:7..A.L. ..Ect5 .41.1 D �. INn A.'i 'ItJlitrr •U.I. N -0L' of UJr .. o. 4-11 F4l::-'. F27ER ►'" ....._I j 110"1lJ_ NORTH LADY FOOTLO SCALE 118'=1' b 2S,2V r., r 1 SALE, AREA 35 Pa7R 0LCBJFE LINE L?:P- Gf rt11-u.K Tl444JBIT;1d 1 AvOVd 14 P414EL44 a 7'-0" nr• , 43 -� 43'-4REA ESTFIELD SOUTHCENTER MALL ,j' rll HI I • T,AG NOTES FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED, BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR: SIEMENS HTRI-D ADDRESSABLE INUT WIT, I 1-10013 VCNILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I\ST _L ADDR=SSABLE N DEVICES UNTIL PREPROGRAMMED W DEVICES DDHSS. OTIAT T Copyright 2006 by Guardian Security Systems, Inc. All Rights I� ,11 (.) z 0 LL�w�y W LU J W REV. BY: ,' 7-'-r!'ii',;, ��� li I I I y IIa�' I ifl II'' �� .L� I' 11 DESCRIPTION SHOP --DRAWINGS _ - - - ii' II •;!'II, I.f I :I •i'' 1 , i li Ifi 91 i ' ' 'i Yi; DATE N,I I "i' 141 ,I,, 1i Lf)I ,1'fK �;, ,, , 1' :; 1;, — DRAWN' BY:I It,i I.ANDERSON1 DESIGNED; :BY,• R.VEZZANIII, I/ DATE: 5/2.0''.,:W BACKROUND \ 9B NUMBER ' 4!'r' , I.„ OVIDED BY: ry c: 1c•: 1 I E)E. 'IN \NA '„---.3F-1 !! (!1 c; , c I S F)E1\,1(_"„ ER ' OIF . .1, • ; ! cc.; c; c • ',it. -ITT': • till 1 RR /1 mALL OFFI CE lc ct cc , 1 t; c: 1 1-'o.. E.! et va • • .'t I' 11:A1 1.) NORTH 1 1 SJF ---- • / ;._ IMMO I IMO I \Air1„4, ABERCROMBIE LU [boo ;r7 ' •c'• 71 1-• . 111/h- • . ic; •:-. Cl 0 co 1101 0 . CALERIE WEST El..1v1 Li a: Li] L1_1 ::,-• 1 020 !--7;4NA! C".. P4 IV; F.:',.44= -•!!C; L :MASA [ :LEO 1! PA(DFIC. SUN WE R .-• ' ID] []] 1 54.5 Lt.; Cl 5 4.-C. ) 1 c' SYSTEM CALCULATIONS IC fJi THE VV,A,L1'2NIG CO. 1 1 1 Q 1 be be 11101 COACH I '1 1 5 1 ELECTRICAL ROOM jOILE.11 RECYCLING STORAGE AZ TE CA MEXICAN GRILL CA.1...IFORI\j1A PIZZA KITCHEN LADY FOOTLOCKER WESTFIELD SOUTHCENTER MALL LOAD:NG RISER ROOM LI jr1J- ....... c.) SCALE 1132"4 135 C 15 75 C 15. EX RISER DIAGRAM D,I 21 TLC •44 P F CiHAiiC 11 R2 LADY FOOT LOCKER LADY FOOT LOCKER C ,rrent L la : D vice Ty FACP ADD ONS. At2-P HR -R . ; 1-1, ..ijr21-D, L______ IO1?-66 „!:! f - i. , F! I. r • Amps 0.0022 0.0635 Standby: Total 0.009600 0.001600 0.005 0.0022 0.0635 0.0096 Amps 0.0023 0.064 Alarm: Total „I Current Load: Device Type SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Qty Amps Standby: Total Amps Alarm: Total 0.021 0.0035 0.128 0.063 Main System Board SET -MC ©15CD SET -MC ©30CD SET -MC @75CD SET -MC @110CD SET-HMa-C@115CD 0.03 0.03 0.0731 Amps 0.191 Standby , urrent Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours SET-HMC-C@135CD__ Am ps,i SET--1--1-KroZe185CD J/7 ZR -MC @15CD 3 6E6 - KID 114 Arm Cu tent Load: !! ' 0.030 0.064 0.098 0.175 0.233 0.318 0.318 0.445 0.064 0.030 0.064 0.064 ,1,' 1! !!! 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 0.098 0.0015 Amps c,c !.! 1!! 0.333 Ams Ilj I' 1 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours I. I I:1c Alarm Current Load: 0.333 Amps For 5 Minutes= 0.028 Amp -hours Total System Current Load: 2.213 Amp -hours Ba tery P ir to be Used: 12VDC 25% Derating= 0.935 Amp -hours Amp -hours 7AH BATTERY SIZ Total System Current Load: 0.935 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH NG CALCULATION I PROJECT:_ Panel: Date: Notification Appliance WESTFIELD SOUTHCENTER MALL LADY FOOTLOCKER May 22, kmii ircgit Detail -11 --- , Wire Resistance 2.58', RRENT TOTAL 5.4 CRCUIT: SPEAKER CIRCUIT QTY Device Type 3 70.7V1/8 0 0 0. 0 0 0 0 Alarm Current Alarm Total 54 0 0 Wire Size Wird; Length Voltage at EOL Circuit Total I DEVICES= 3 PROJECT. Panel: Date: CIRCUIT: wurnItm,ottrenv.,..w.error,,v,re..mtn Tmernowu MMIOWVINWIWIWIT.1•13.. .NOtifiCation_AppliincecirC-6 WESTFIELD SOUTHCENTbi. MALL .! LADY FOOTLOCKER May 22, 2008' 0 TOTAL rnA= ' 5.4 14 65 20.384256841 5.4 S1 Wire Resistance 1.62 CURRENT TOTAL= 621 Total Wire Resistance ( R ) ( WL * 2 )* (Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage - E) 2.92 0.01 0.02 20.38 QTY 1 0 0 1 0 0 DEVICES= Device Type SET -MC @15CD SET -MC @30CD SET -MC @75CD Alarm Current 64 Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 64 SET -MC @110CD SET-HMC-C@115CD SET-HMC-C@177CD SET -HMC @135CD SET -HMC @185CD Z-MC@15CD 98 175 233 318 445 318 445 0 175 0 0 0 318 Total Wire Resistance ( R ) ( WL * 2 )* (Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I* R) 0.86 0.62 0.53 EOL Voltage (20.4 - E) 19.87 64 64 Z-MC@30CD SET-MC-CVV@110C 4 98 233 TOTAL m A= 621 12 VOLTAGE DRO 19.8668094 621 CALCULATION I 11 I REV. BY: ' . Z c I • c I ccl"ct c c! ;., c 1 ' c l' I•1 . i t ' DESCRIPTION SHOP DRAWINGS ' „'l I',• • ; . , 1 • .t i'•I i . '! I•J;!' ..' . ': •I''t!'• ! ! Lt ! ! DATE ,• ti, 1. ' itb ! . t•1 ' . . '', c ' 64 '`-. c1 • cl'r!' ' 1ic • 0 • It Ui MPS DRAWN 'BY:'!'! LAN DERSON DESIGNED BY:,!,.1!!!!:"1 R.VEZZANlic DATE: BACKROUNCi,IFIAN.fPIOY,IDEbl!Br: ,op NUNAribR-;5 Copyright 2006 by Guardian Security Systems, Inc. All Rights ReSeryed • c • 1 t I 11;1'11,1 iiji; C1 C ; -. '3 I • • 304 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-226 08-S-335 a FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lady Footlocker 704-( S c_ r.A& l / 1560 Southcenter Mall Permit No.: 08-S335 Date: June 17, 2008 Reviewer: Steve Kohler Fire Inspector/Plan Review (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/ inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. I IHvdraulic Overview 70'4 5-r'a.t Job Number: KS0421 •117W - 41 Report Description: WET SYSTEM Job Job Number Design Engineer KS0421 CHRIS J. ISAAC Job Name Phone FAX LADY FOOTLOCKER 206-491-6679 425-881-3030 Address 1 State CertficatiorLicense Number 1560 SOUTH CENTER MALL WESTESF136QF Address 2 AHJ CITY OF TUKWILA City State Zip Code Job Site TUKWILA WA 98188 SOUTH CENTER MALL System Density Area of Application 0.20gpm/ft2 1011.63ft2 (Actual 1011.63ft2) Most Demanding Sprinkler Data Hose Streams 5.6 K -Factor 23.10 at 17.016 250.00 Coverage Per Sprinkler Number Of Sprinklers Calculated 115.50ft2 13 System Pressure Demand System Flow Demand 106.667 382.30 Total Demand Pressure Result 632.30 @ 106.667 +32.714 (23.5%) Supplies Check Point Gauges Node Flowlaom) Hose Flow(oom) Static(Dsil Residual(psi) Identifier Pressure(Dsil K-Factor(K) Flow(dbm) 1 10900.00 250.00 140.000 20.000 Vow. i ki. 41 1► lar _,_ 41440 LADY FOOTLOCKER FP-1.cad Supply at Node 1 (10900.00, 250.00, 140.000, 20.000) 1 me 150 Static 1 Pressure 140.000 135 120 • 32.30 with hose streams 105 82.30 @ 106.66/ .N 90 a =d 75 N N �'60 a System demand curve I IFI 45 30 10900.00 @ 20.000 15 a 1111111111111111111111111111 111111111 111111111 111111111 111111111 111111111 0 1.300 5500 6600 7700 8800 9900 11000 Water flow, gpm [A� ©M.E.P.CAD, Inc. ;?4 AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:33PM Page 1 VIHydraulic Summary Job Number: KS0421 Report Description: WET SYSTEM Job Job Number KS0421 Job Name LADY FOOTLOCKER Address 1 1560 SOUTH CENTER MALL Address 2 City State Zip Code TUKWILA WA 98188 Design Engineer CHRIS J. ISAAC State Certification/License Number WESTESF136QF AHJ CITY OF TUKWILA Job Site SOUTH CENTER MALL Drawing Name LADY FOOTLOCKER FP-1.cad System . Remote Area(s) Most Demanding Sprinkler Data 5.6 K -Factor 23.10 at 17.016 Hose Allowance At Source 250.00 Additional Hose Supplies Node Flow(gpm) Occupancy Ordinary Group II Density 0.20gpm/ft2 Number Of Sprinklers Calculated 13 Area of Application 1011.63ft2 (Actual 1011.63ft2) Coverage Per Sprinkler 115.50ft2 Total Hose Streams 250.00 System Flow Demand Total Water Required (Including Hose Allowance) 382.30 632.30 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 27.61 between nodes 135 and 52 Motown Velocdy Under Ground 1.44 between nodes 1 and 389 Volume capacity of Wet Pipes Volume capacity of Dry Pipes 2514.63ga1 0.75ft3 Supplies Hose Flow Static Residual @ Flow Node (gpm) (psi) (psi) (gpm) Available @ Total Demand (psi) (gpm) Required Safety Margin (psi) (psi) 1 250.00 140.000 20.000 10900.00 139.381 632.30 106.667 32.714 Contractor Contractor Number KS0421 Contractor Name Western States Fire Protection (Redmond) Address 1 7102 180th Ave NE, Suite A-105 Address 2 City State Zip Code Redmond WA 98052 Contact Name Chris J Isaac Phone (425)881-0100 FAX (425)881-3030' E-mail chris.isaac@wsfp.us Web -Site Contact Title Designer Extension © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:34PM Page 2 41 Summary Of Outflowing Devices Device Job Number: KS0421 Report Description: WET SYSTEM Actual Flow Minimum Flow K -Factor Pressure (gpm) (gpm) (K) (psi) Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 102 103 109 101 105 104 108 113 106 110 107 111 112 E.> Most Demanding Sprinkler Data 23.59 23.61 31.68 23.10 23.95 23.70 31.35 43.99 27.08 31.92 30.15 33.11 35.08 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 23.10 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 17.739 17.770 32.002 17.016 18.293 17.912 31.341 61.706 23.392 32.492 28.984 34.952 39.236 (A�, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:35PM Page 3 it Node Analysis Job Number: KS0421 Report Description: WET SYSTEM Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 14 15-3 E(2-0) 22.045 20 15-3 P0(5-0) 22.079 23 15-3 E(2-0) 39.384 26 15-3 P0(5-0) 22.418 31 15-3 P0(5-0) 23.492 34 15-3 P0(5-0) 23.634 39 15-3 P0(5-0) 39.799 42 15-3 E(2-0) 80.331 46 15-3 P0(5-0) 28.370 48 15-3 P0(5-0) 41.285 52 15-3 P0(5-0) 35.312 54 15-3 P0(5-0) 44.456 63 15-3 P0(5-0) 49.971 134 15-3 P0(8-0) 84.909 135 15-3 P0(8-0) 84.630 136 15-3 P0(8-0) 84.570 257 14-2 P0(26-4) 92.883 334 1-11 99.473 389 5-8 BFP(-4.500) 102.384 398 1-11 P0(37-8%) 99.402 102 11-0 Spr(-17.739) 17.739 103 11-6 SEr(-17.770) 17.770 109 11-6 Spr(-32.002) 32.002 101 12-6 Spr(-17.016) 17.016 105 11-6 Spr(-18.293) 18.293 104 12-6 Spr(-17.912) 17.912 108 12-0 Spr(-31.341) 31.341 113 12-0 Spr(-61.706) 61.706 106 12-6 Spr(-23.392) 23.392 110 12-0 Spr(-32.492) 32.492 107 12-6 Spr(-28.984) 28.984 111 12-0 Spr(-34.952) 34.952 112 12-0 Spr(-39.236) 39.236 1 -4-0 S 106.667 23.59 23.61 31.68 23.10 23.95 23.70 31.35 43.99 27.08 31.92 30.15 33.11 35.08 382.30 L, © M.E.P.CAD, Inc. 2 AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:35PM Page 4 III Hydraulic Analysis Job Number: KSO421 Report Description: WET SYSTEM Pipe Type Downstream Upstream Diameter Elevation Flow Velocity HWC Discharge K-Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length " Route 1 BL 1.049 Q=23.10 8.58 C=120 0.169886 25-9 Pf 6.582 101 12-6 q=23.10 K=5.6 17.016 Spr(-17.016) 13-0 Pe -1.180 26 15-3 22.418 4E(2-0), P0(5-0) 38-9 Pv BL 1.610 0=70.29 11.08 C=120 0.165270 6-6 Pf 1.074 26 15-3 22.418 Pe 31 15-3 23.492 6-6 Pv BL 1.610 Q=94.24 14.85 C=120 0.284302 0-6 Pf 0.142 31 15-3 23.492 Pe 34 15-3 23.634 0-6 Pv BL 1.610 Q=117.94 18.59 C=120 0.430542 11-0 Pf 4.736 34 15-3 23.634 Pe 46 15-3 28.370 11-0 Pv BL 1.610 0=145.03 22.86 C=120 0.631110 11-0 Pf 6.942 46 15-3 28.370 Pe 52 15-3 35.312 11-0 Pv BL 1.610 0=175.18 27.61 C=120 0.895055 47-1 Pf 49.318 52 15-3 35.312 8-0 Pe 135 15-3 84.630 P0(8-0) 55-1 Pv CM M 4.260 Q=338.31 7.62 C=120 0.026465 10-6% Pf 0.279 135 15-3 84.630 Pe 134 15-3 84.909 10-6% Pv CM 4.260 Q=38.2.30 8.61 C=120 0.033181 151-8 Pf 7.504 134 15-3 84.909 74-6 Pe 0.470 257 14-2 92.883 LtE(7-11), 2P0(26-4), 2Ee1(5-3), 226-2 Pv fEE(3-5) CM 6.357 Q=382.30 3.86 C=120 0.004724 102-1 Pf 1.211 257 14-2 92.883 154-4 Pe 5.307 398 1-11 99.402 3fE(10-0), E(17-7), fT(25-0), 256-5 Pv CV(40-3), GV(3-9%), P0(37-8%) FM M 8.329 0=382.30 2.25 C=120 0.001267 24-8% Pf 0.072 398 1-11 99.402 32-0 Pe 0.000 334 1-11 99.473 2fE(16-0) 56-8'% Pv MS 10.020 0=382.30 1.56 C=120 0.000515 20-2 Pf 4.545 334 1-11 99.473 67-0 Pe -1.635 389 5-8 102.384 3LtE(16-0), BV(19-0), BFP(-4.500) 87-2 Pv VG 10.400 0=382.30 1.44 0=140 0.000323 113-1 Pf 0.084 389 5-8 102.384 146-8 Pe 4.200 1 -4-0 106.667 3LtE(25-6), E(35-1), 2EE(17-6%), S 259-9% Pv Route 2 BL 1.049 0=23.59 8.76 0=120 0.176560 26-9 Pf 6.135 102 11-0 q=23.59 K=5.6 17.739 Spr(-17.739) 8-0 Pe -1.830 14 15-3 22.045 4E(2-0) 34-9 Pv BL 1.610 0=23.59 3.72 0=120 0.021919 1-6% Pf 0.034 14 15-3 22.045 Pe 20 15-3 22.079 1-6% Pv BL 1.610 0=47.19 7.44 C=120 0.079082 4-3% Pf 0.339 20 15-3 22.079 Pe 26 15-3 22.418 4-3% Pv GA, Route 3 BL 1.049 0=23.61 8.76 0=120 0.176840 26-6 Pf 5.922 103 11-6 q=23.61 K=5.6 17.770 Spr(-17.770) 7-0 Pe -1.613 20 15-3 22.079 E(2-0), P0(5-0) 33-6 Pv a Route 4 BL 1.049 0=23.70 8.80 C=120 0.178148 25-9 Pf 6.902 104 12-6 q=23.70 K=5.6 17.912 Spr(-17.912) 13-0 Pe -1.180 34 15-3 23.634 4E(2-0), P0(5-0) 38-9 Pv w Route 5 BL 1.049 0=23.95 8.89 0=120 0.181652 28-6 Pf 6.812 105 11-6 q=23.95 K=5.6 18.293 Spr(-18.293) 9-0 Pe -1.613 31 15-3 23.492 2E(2-0), P0(5-0) 37-6 Pv a Route 6 BL 1.049 0=27.08 10.05 C=120 0.228045 22-0 Pf 6.157 106 12-6 q=27.08 K=5.6 23.392 Spr(-23.392) 5-0 Pe -1.180 46 15-3 28.370 P0(5-0) 27-0 Pv w Route 7 BL 1.049 0=30.15 11.19 C=120 0.278053 22-0 Pf 7.507 107 12-6 q=30.15 K=5.6 28.984 Spr(-28.984) 5-0 Pe -1.180 52 15-3 35.312 P0(5-0) 27-0 Pv 6. Route 8 BL 1.049 0=31.35 11.64 C=120 0.298901 23-11% Pf 9.855 108 12-0 q=31.35 K=5.6 31.341 Spr(-31.341) 9-0 Pe -1.396 39 15-3 39.799 2E(2-0), P0(5-0) 32-111/2 Pv Ga. (e) M_E_P_CAD Inc 43AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:36PM Page 5 (i Hydraulic Analysis I Job Number: KS0421 Report Description: WET SYSTEM Pipe Type Diameter Flow Velocity Downstream Elevation Discharge K -Factor Upstream HWC Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length BL 1.610 Q=63.03 9.93 C=120 0.135073 11-0 Pf 1.486 39 15-3 39.799 Pe 48 15-3 41.285 11-0 Pv BL 1.610 Q=94.95 14.96 C=120 0.288260 11-0 Pf 3.171 48 15-3 41.285 Pe 54' 15-3 44.456 11-0 Pv BL 1.610 Q=128.06 20.18 C=120 0.501318 11-0 Pf 5.515 54 15-3 44.456 Pe 63 15-3 49.971 11-0 Pv BL 1.610 Q=163.14 25.71 C=120 0.784560 36-1 Pf 34.599 63 15-3 49.971 8-0 Pe 136 15-3 84.570 P0(8-0) 44-1 Pv CM 4.260 Q=163.14 3.67 C=120 0.006865 8-9% Pf 0.060 136 15-3 84.570 Pe 135 15-3 84.630 8-9% Pv w Route 9 BL L 1.049 0=31.68 11.76 C=120 0.304727 23-6 Pf 8.995 109 11-6 q=31.68 K=5.6 32.002 Spr(-32.002) 6-0 Pe -1.613 23 15-3 39.384 3E(2-0) 29-6 Pv BL 1.610 Q=31.68 4.99 C=120 0.0.3.7831 11-0 Pf 0.416 23 15-3 39.384 Pe 39 15-3 39.799 11-0 Pv Route 10 BL 1.049 Q=31.92 11.85 C=120 0.309044 23-11% Pf 10.189 110 12-0 q=31.92 K=5.6 32.492 Spr(-32.492) 9-0 Pe -1.396 48 15-3 41.285 2E(2-0), P0(5-0) 32-11% Pv w Route 11 BL 1.049 Q=33.11 12.29 C=120 0.330623 23-11% Pf 10.901 111 12-0 q=33.11 K=5.6 34.952 Spr(-34.952) 9-0 Pe -1.396 54 15-3 44.456 2E(2-0), P0(5-0) 32-11% Pv Gal Route 12 BL L 1.049 Q=35.08 13.02 C=120 0.367943 23-11% Pf 12.131 112 12-0 q=35.08 K=5.6 39.236 Spr(-39.236) 9-0 Pe -1.396 63 15-3 49.971 2E(2-0), P0(5-0) 32-11% Pv Route 13 BL 1.049 Q=43.99 16.33 C=120 0.559339 25-9% Pf 20.022 113 12-0 q=43.99 K=5.6 61.706 Spr(-61.706) 10-0 Pe -1.396 42 15-3 80.331 5E(2-0) 35-9'% Pv BL 1.610 Q=43.99 6.93 C=120 0.069440 57-11 Pf 4.578 42 15-3 80.331 8-0 Pe 134 15-3 84.909 P0(8-0) 65-11 Pv Equivalent Pipe Lengths of Valves and Fittings (C=120 only)II C Value Multiplier Actual Inside Diameter 4'87 ( ) Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter =Factor Multiplying Factor 0.713 1.16 1.33 1.51 [M, ©M.E.P.CAD, Inc. :? AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:36PM Page 6 Hydraulic Analysis Pipe Type Downstream Upstream Diameter Elevation Flow Discharge Job Number: KS0421 Report Description: WET SYSTEM Velocity HWC K -Factor Pt Friction Loss Pn Fittings Length Pressure Eq. Length Summary Total Length Pipe Type Legend Units Legend Fittings Legend AO Arm -Over Diameter BL Branch Line Elevation CM Cross Main Flow DN Drain Discharge DR Drop Velocity DY Dynamic Pressure FM Feed Main Length FR Feed Riser Friction Loss MS Miscellaneous HWC OR Outrigger Pt RN Riser Nipple Pn SP Sprig pf ST Stand Pipe Pe UG Underground Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points E Velocity pressure at a point in a pipe EE Eel Ee2 FDC fE fEE flg FN fT 9 GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22W Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:36PM Page 7 Hydraulic Graph I Job Number: KS0421 Resort Description: WET SYSTEM A[^ ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:37PM Page 8 Supply at Node 1 150 -Static Pressure 140.000 135 120 105 632.30 -82.30 with hose @ 106.667 streams 90 .y 0 ill 75 co N E a` 60 System J demand curve 45 30 10900.00 @ 20.000_ 15 JO 1e ilium 111111111 11 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 111111_111 111111111 1 1 1 1 1 1 1 1 1 I 1 1 111111 0 11002200 3300 4400 5500 6600 7700 8800 Water flow, gpm 9900 11000 Hydraulic Graph Supply at Node 1 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.381 @ 632.30 System Demand 382.30 @ 106.667 System Demand (Including Hose Allowance) 632.30 @ 106.667 A[^ ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:37PM Page 8 i�� Flow Diagram (Top View) I Job Number: KS0421 Report Description: WET SYSTEM (M ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/10/2008 5:11:37PM Page 9 LADY FOOTLOCKER #1560 VICINITY MAP (Suite #1560) SCALE: N General Notes 1. Western States Fire Protection to add new pendenth, heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary Class 11 Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculations). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 8. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system onlyIn the areas of work. All other areas are not in contract and WSFP is not responsible for exiting conditions. 10 LI U Ea Ci En EXISTING PIPE NEW PIPE ZONE T1 MAIN RISER ROOM A DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SYMBOL LEGEND REVISIONS C42 CL 2 ®11'-r AF.f. Ordinary Group II.0.20gpm/ft2 for 1011.63ft2 7 .4)17-0" AFS. CL.l Q t2 r AFF. CL -i 11'-0'A.FF. FCL -1 611'-0' f.F CT 1 @ 6'A' AFF. 44 w k uIiiIII:1IJ1IEI Nil O n CL@tY-0'AF7 CO CL.4 a 4A' AFS. 1-2 4 ,14 1 1 1 1 1 1 1 LADY FOOTLOKER LADY FOOTLOCKER Remote Area: Retail # 1560 CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 FY DENSITY .20 GPM / FP for 1011.63 Ft' SPRINKLER Reliable Model G4A/ F1FR ORIFICE 1/2" x= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER, SYSTEM REQUIRES: 382.30 GPM © 102.38 PSI At time of Design REMOTE AREA REDUCTION - 37% 945 SD/FT int a* eta m m i m lama fit— — — — ima an ra — — IT Eti or 1/8" = 1'-0 Sprinkler Legend 1 3 5 7 9 11 APPROVAL: CITY OF TUKWILA SPRINKLER BRANCHLINE FLEXABLE CONNECTING HOSE IN STANDARD LENGTHS FLEXHEAD DETAIL NOT TO SCALE FIG. 909 SWIVEL SWAY BRACE FITTING OI 31B' KWIK BOLT �{21M' EMBED LENGTH) BRACE PIPE FIG. 1000 "FAST CLAMP" SWAY BRACE ATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS NON -THREADED BRACE PIPE 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE DESCRIPTION K SPRAY MFR./MODEL R3615 Pendent Chrome 155°F REL F1FR SSP CONT. NO.: KS0421 R5415 Pendent 155°F REL CONCEALOR HYDRAULIC REFERENCE POINT Total = 31 HANGER SYMBOL DRAWN BY: SPRK. ON SHEET: SEE LEGEND BRANCHLINE RESTRAINT SPRK. ON JOB: DATE: 06/10/08 FIG. 909 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT FIG. 4A PIPE CLAMP FOR SWAY BRACE OLATERAL BRANCHLINE RESTRAINT t ' NON -THREADED BRACE PIPE 31B' KWIK BOLT (2 IW EMBED LENGTH) BRACE PIPE LATERAL BRANCHLINE RESTRAINT NOT TO SCALE Hanger No. 07C-HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch Bottom of Concrete to Center Line of Pipe Note on Plan Note on Plan: Hanger Number and 'A' Dimension V`J stamps must be HANGER DfisAcM,teforepipe hung. Do not paint piping prior to hydrostatic test NOT TO SCALE LADY FOOTLOCKER iC w 0 ACCEPTED Without Comments As Noted In Red Per The Attached Letter !nese plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is suhiect to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings atter this date will void this_acceptanCe and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bure VICINITY MAP DETAIL NOT TO SCALE Western States Fire Protection Company 7102180th AVE NE, STE A-105 - REDMOND, WA- 98052 Lic. #: WESTESF136QF WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE/AUSTIN/ DALLAS l DECATUR!DENVER!DULUTH /HOUSTON/KANSAS CITY LAS VEGAS/MINNEAPOLIS I PHOENIX) PORTLAND / RAPID CITY! ST. PAIR! SALT LAKE CITY / SEATTLE Phone: 425-881-0100 Fax: 425-881-3030 TUKWILA FIRE DEPARTM f %. Please call: 575.4407 and give this job No. 08---S-33 and exact address for shut. icwn or restoration aporov, PAID JUN 16 2008 Tukwila Fire/2404,(4,47 LADY FOOTLOCKER 1�6f)-SOUTH CENTER MALL 3°Y TUKWILA,WA 98188 LADY FOOTLOCKER Q. FP -1 OF 1 MARKET CONTRACTORS LTD CONTRACTO SHEET I 1 U:V 3ER SHEET TITLE COPY SHEET INDEX LA F FIRE ALA TUKWI I A FA- 0 1 SYTEIV I \ FOMATIO FA -02 TYP ICAL DETAILS - WRI \G AND VOU\TI\ FA -03 FRE ALAN SYSTEM FLOC) P LA \ FA -04 SYSTE IV I CALCULATIO \ S GE\ EAL), ISE, SITE PLA\ 11: tZ 11611MIMIldilliii11.11.1111014110.11121, • bet.#.1,''Vtsi#,AAA.rael • ti • • .1. \i‘4thOt!,it CornMentt, 0 11.,s lot•ed in Rd ! Per The Attached • i nese plans h2‘,./;:)--:,:„,,ii.;'wiew:ed by The Tvk,.t9itat.F1';','.: !, Prevention Borenj-or !ponforManoe w;th c.urrt':•:-,4 Oily ,. . • standards. ,e8.4::.cricuiii, tti....tbp: to ein..;cs ad omissions wnicli do: i ;o.1..author"ize violziticnii of .s.cl•pti.:4. I • .1.' standards and rol'Ot.nan.s. -11,4 re.4)oris.i.t.,/ forr.,..- adequacy of desiGii,r&Sts tot:4.116, with tilf:t 0.i•rv.;,„:.,t-ter'i Additions, d,•Ffioionti',.oi: 'rh.visii3.4 ts:-.., those dr..,inc4:.;-1,:r this date will void thiiicept'ace and ',,,,i'll r.t.:tquire-'.: resubmittal of as vinedc!i.i3win'gi-", for :-.;;ubsequ.,:rit p'rovz..11. , ' Final accptr.3•ncci o2,•,;;,:b)0(...,1 to!tielci test and inspiection by • • • , :. • : Date: .'. AirslJ/ [ . .. .!..!, • ' ... . . , . . • i. . .11 .., • ,. The Tukwila Fire Proyt•,..rition TUKWILA FIRE DE,PARTivit.nn Please call: 575-4407; and give this job! ! No. ()1 F+>" :4(-• and exact address for Shot. ..lown or restora ion aOlayoval1; NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing. WIRE DESIGNATION SCHEDULE SHIELDED WIRE SCHEDULE AND CONDUIT FILL CHART ..„ WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYST CKER STEM ASHINGTON ERAL NOTES DO NOT INSTALL ADDRESS BLE,' DEVICES ADDRESS. . • • , 1. NUMBERS ADJACENT TO DE., ICE' SY' BOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE S COND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CI U11-4) LARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WI ING IS !SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIB4 ,• 4. INSTALLATION SHALL BE IN i" TRICT, ONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, 4; CAl_ C. DE(S), AND/OR AUTHORITY HAVING JURISDICTION. •,!'' 5. INSTALLATION MATERIALS ( . CON 1JIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OE ICS'1,C LE, FITTINGS, AND ASSOCIATED EQUIPIvENT) ARE NOT SUPPLIED BY SIEMfI1INS CF: BERUS DIVISION. ITIATING DEVICES UNTIL PREPROGRAMMED WITH I; tl 6. DETECTORS SHALL NOT BEII , AIR STREAM OF AIR SUPPLY 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLOR AND UNIQUELY MARKED FOR 8. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" 9, FOR ADDITIONAL INSTALLATI SHEETS AND/OR INSTALLATI 10. THE 120vac POWER ELECTR) MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-5 SOURCES. 120vac POWER S DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND SI; OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND 14. ALL 120VAC CIRCUITS ARE GENERATOR. lOUNTE IN DIRECT ,OUTLE, S. PER NFPA 72 2-3.5.1 WITHiESPECT TO CONDUCTOR SIZE, (Sc OR CABLE TRAY, CODE. rCONDUCTORS SHALL BE PERMANENTLY, .FUTUR IDENTIFICATION. LL R 'URN ONE SET OF ACCURATELY MARKED [JRPOS N INS UCTIONS, REFER TO CATALOG CUT N INS UCTIONS. AL IA,/. .725. .5.2: HI ALL N ALAR OBE' D DROP K SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. VICES SHALL BE MOUNTED AT A HEIGHT D CEILING, WHICHEVER IS LESS. SHAIi DE MOUNTED AT 48" A.F.F. TO THE , '14 IRCUIT. In Roy, EDICATED' CIRCUITS FROM THE EMERGENCY WILL BE ON THE RECORD DRAWINGS SET. 15. PER NFPA 72 SECTION 5- .6.1.3 ,ETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN UP Or1IALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIR D BY: , HE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C. DETECTORS THAT HAVE BEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANE OR R tLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. ' 16. WIRING SHALL RUN CONTIN OUS ,FOM FACP TO FIRST DEVICE. ON .A CIRCUIT AND THEN FROM DEVICE T HDEId WITHOUT . SPLICING; IN ,PULL BOXES OR ,. OTHER BACK BOXES OF DI .ERENi CIRCUITS. 17. ALL WIRING SHALL BE MET ED, '\) RIFIED TO BE CONTINUOUS,FREE OF .GROUND AND FREE OF SHORTS BET EEN NDUCT.ORS AND OTHERH CIRCUITS, PRIOR TO' FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MA KED A PERMANENT LABEL AT ALL DEVIC 19. THE ELECTRICAL CONTRAC R H/ OUTSIDE AND INSIDE OF T, FIRE AFTER COMPLETION OF TH R INS 20. DETECTORS MUST BE RATE FO'R IT IS LOCATED. 21. ALL WIRING BETWEEN FLOC) S SHA 22. NFPA 72 2007 6.4.2.2.2 ALj STYL PHYSICAL CONDUCTORS (E.G, META INSTALLED SUCH THAT THE UTGOI FROM AND RETURNING TO TIE CO ROUTED SEPARATELY. THE OTG0,1 CONDUCTORS SHALL NOT B RUI4 MULTI -CONDUCTOR CABLE), NCL'O 23. loI NFPA 72 2007 A.6.4.2.2.2 ADEQUATE SEPARATION BET THIS SEPARATION IS REQUIRi CABLES FROM PHYSICAL DA SEPARATION TO PREVENT P THE CABLE IS INSTALLED V CABLE IS INSTALLED INDICATED ON FIRE ALARM .RISER WITH A , JUNCTION BOXES .AND FACP. L CLEAN ALL DIRT AND DEBRIS FROM THE ALARM BACK BOXES AND JUNCTION BOXES LLATION. EMPERATURE IN THE ENVIRONMENT IN WHICH. BE LOCATED IN CONbUIT.' ;$ OF CLASS A CIRCUITS USING LIC, OPTICAL FIBER) SHALL BE G AND RETURN CONDUCTORS, EXITING ROL UNIT, RESPECTIVELY ARE AND RETURN (REbUANTy CIRCUIT THE SAME CABLE 'ASSEMBLY (I.E., ,RE, OR RACEWAY. A',GOA! OF 6.4.2.2.2 IS TO 'PROVIDE EEN E OUTGOING AND RETURN .CABLES, D TO'ELP ENSURE PROTECTION OF THE AGE11 E RECOMMENDED MINIMUM' YSICALI1 DAMAGE 'IS 305 MM. (1. FT) ;WHERE TIC4 AND 1.22 M (4 FT) WHERE' THE II' QUANTITY 3 2 EX SYV Ii Ii BOL, OESCRIPTIQN SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP 'FIRE ALARM I 'EX CONTROL PANEL ;I. ' 3! FRA It,1 XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP. FIRE ALARM • REMOTE ANNUNplATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP IIL,11 1' Ill 7 L " " iiN,Ol, VIL.IVIL.I IV r • ,v • ...- ••• TO TOP WIRE DESIGNATION . .• . . SYMBOL DESCRIPTION . NUMBER OF CONDUCTORS SIZE TYPE ! . COLOR CODE D H P S 2S A V 2V I X UD UI UI M B DATA 'LINE -ADDRESSABLE LOOP ; ;DOOR .HOLDER POWER - 24VDC : DEVICE POWER - 24VDC ' STROBE CIRCUIT - FEED ; STROBE CIRCUIT - RETURN ANNUNCIATOR ; . SPEAKER CIRCUIT - FEED ' ; SPEAKER CIRCUIT - RETURN REMOTE INDICATION LIGHT LOW LEVEL AUDIO UNDERGROUND DATA UNDERGROUND INITIATION 'DOOR HOLDER POWER BEAM 'DETECTOR POWER . TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) TWO #14 FPL/FPLR RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD ;#16 'FPL/FPLR RED (JACKET) TWISTED PAIR #14 FPL/FPLR RED (JACKET) TWISTED PAIR #14 FpL/FPLR RED. (JACKET) TWO #18 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED :(JACKET) TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) TWISTED PAIR RATED #18 FPL/FPLR! RED (JACKET) TWO #16 FPL/FPLR RED (JACKET) TWO #14 FPL/FPLR RED (JACKET) , i;.....• I . ',,, „ • I . !"1.!'"!....',...;!"-•;;...!•;...."'",.' '.,,,' •';',......I.III;;" ' - :. 1,', I.', I' ''• I , . , , . . .. CONDUIT FILL CHART • ,.: IDUAL INPUT HTRI-D SIEMENS 4S DEEP VERIFY INTERFACE MODULE IN FIELD ; , . ' . NO. OF CONDUCTORS VOLTS : WIRE SIZE . TYPE , DIMENSIONS „ AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 •' : ; t TWO 600V #14 AWG THHN/THWN TWISTED .210 O.D. . .0346 TWO CONDUCTOR 300V #18 AWG FPL TW ,CABLE „ : .156 O.D, .0191. ' . ' • ' CONDUIT FILL . . . .. ' , . CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL • : , . 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH ,., 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH . . FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C.; CHP. 9, TABLE . 4. ..„ WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYST CKER STEM ASHINGTON ERAL NOTES DO NOT INSTALL ADDRESS BLE,' DEVICES ADDRESS. . • • , 1. NUMBERS ADJACENT TO DE., ICE' SY' BOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE S COND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CI U11-4) LARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WI ING IS !SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIB4 ,• 4. INSTALLATION SHALL BE IN i" TRICT, ONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, 4; CAl_ C. DE(S), AND/OR AUTHORITY HAVING JURISDICTION. •,!'' 5. INSTALLATION MATERIALS ( . CON 1JIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OE ICS'1,C LE, FITTINGS, AND ASSOCIATED EQUIPIvENT) ARE NOT SUPPLIED BY SIEMfI1INS CF: BERUS DIVISION. ITIATING DEVICES UNTIL PREPROGRAMMED WITH I; tl 6. DETECTORS SHALL NOT BEII , AIR STREAM OF AIR SUPPLY 7. WIRING SHALL BE PER PLA TYPE, QUANTITY AND COLOR AND UNIQUELY MARKED FOR 8. INSTALLING CONTRACTOR S DRAWINGS FOR "AS BUILT" 9, FOR ADDITIONAL INSTALLATI SHEETS AND/OR INSTALLATI 10. THE 120vac POWER ELECTR) MUST COMPLY WITH ARTICL SPECIFICALLY SECTION 1-5 SOURCES. 120vac POWER S DIRECT SUPERVISION OF FIR 11. ALL HORN/STROBE AND SI; OF 80" A.F.F. OR 6" BELO 12. ALL MANUAL PULL STATIO ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND 14. ALL 120VAC CIRCUITS ARE GENERATOR. lOUNTE IN DIRECT ,OUTLE, S. PER NFPA 72 2-3.5.1 WITHiESPECT TO CONDUCTOR SIZE, (Sc OR CABLE TRAY, CODE. rCONDUCTORS SHALL BE PERMANENTLY, .FUTUR IDENTIFICATION. LL R 'URN ONE SET OF ACCURATELY MARKED [JRPOS N INS UCTIONS, REFER TO CATALOG CUT N INS UCTIONS. AL IA,/. .725. .5.2: HI ALL N ALAR OBE' D DROP K SUPPLYING FIRE ALARM SYSTEM PANELS ND 760 OF NFPA 70, N.E.C. AND NFPA 72, REFERENCE TO DEDICATED BRANCH POWER T BE APPLIED TO FIRE ALARM PANEL WITHOUT TECHNICIAN. VICES SHALL BE MOUNTED AT A HEIGHT D CEILING, WHICHEVER IS LESS. SHAIi DE MOUNTED AT 48" A.F.F. TO THE , '14 IRCUIT. In Roy, EDICATED' CIRCUITS FROM THE EMERGENCY WILL BE ON THE RECORD DRAWINGS SET. 15. PER NFPA 72 SECTION 5- .6.1.3 ,ETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN UP Or1IALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIR D BY: , HE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING C. DETECTORS THAT HAVE BEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANE OR R tLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. ' 16. WIRING SHALL RUN CONTIN OUS ,FOM FACP TO FIRST DEVICE. ON .A CIRCUIT AND THEN FROM DEVICE T HDEId WITHOUT . SPLICING; IN ,PULL BOXES OR ,. OTHER BACK BOXES OF DI .ERENi CIRCUITS. 17. ALL WIRING SHALL BE MET ED, '\) RIFIED TO BE CONTINUOUS,FREE OF .GROUND AND FREE OF SHORTS BET EEN NDUCT.ORS AND OTHERH CIRCUITS, PRIOR TO' FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MA KED A PERMANENT LABEL AT ALL DEVIC 19. THE ELECTRICAL CONTRAC R H/ OUTSIDE AND INSIDE OF T, FIRE AFTER COMPLETION OF TH R INS 20. DETECTORS MUST BE RATE FO'R IT IS LOCATED. 21. ALL WIRING BETWEEN FLOC) S SHA 22. NFPA 72 2007 6.4.2.2.2 ALj STYL PHYSICAL CONDUCTORS (E.G, META INSTALLED SUCH THAT THE UTGOI FROM AND RETURNING TO TIE CO ROUTED SEPARATELY. THE OTG0,1 CONDUCTORS SHALL NOT B RUI4 MULTI -CONDUCTOR CABLE), NCL'O 23. loI NFPA 72 2007 A.6.4.2.2.2 ADEQUATE SEPARATION BET THIS SEPARATION IS REQUIRi CABLES FROM PHYSICAL DA SEPARATION TO PREVENT P THE CABLE IS INSTALLED V CABLE IS INSTALLED INDICATED ON FIRE ALARM .RISER WITH A , JUNCTION BOXES .AND FACP. L CLEAN ALL DIRT AND DEBRIS FROM THE ALARM BACK BOXES AND JUNCTION BOXES LLATION. EMPERATURE IN THE ENVIRONMENT IN WHICH. BE LOCATED IN CONbUIT.' ;$ OF CLASS A CIRCUITS USING LIC, OPTICAL FIBER) SHALL BE G AND RETURN CONDUCTORS, EXITING ROL UNIT, RESPECTIVELY ARE AND RETURN (REbUANTy CIRCUIT THE SAME CABLE 'ASSEMBLY (I.E., ,RE, OR RACEWAY. A',GOA! OF 6.4.2.2.2 IS TO 'PROVIDE EEN E OUTGOING AND RETURN .CABLES, D TO'ELP ENSURE PROTECTION OF THE AGE11 E RECOMMENDED MINIMUM' YSICALI1 DAMAGE 'IS 305 MM. (1. FT) ;WHERE TIC4 AND 1.22 M (4 FT) WHERE' THE II' QUANTITY 3 2 EX SYV Ii Ii BOL, OESCRIPTIQN SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP 'FIRE ALARM I 'EX CONTROL PANEL ;I. ' 3! FRA It,1 XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP. FIRE ALARM • REMOTE ANNUNplATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP IIL,11 1' Ill 7 L " " iiN,Ol, VIL.IVIL.I IV r • ,v • ...- ••• TO TOP r I I.< t ALAN M TERMINAL CABINET EX tiO."\iAli`6`-R SUPPLY ; r . D. l./ . vLI\Ir I IN FIELD 'INTERFACE MODULE HTRI-R SIEMENS 4S DEEP VERIFY 'WITH RELAY IN FIELD i;.....• I . ',,, „ • I . !"1.!'"!....',...;!"-•;;...!•;...."'",.' '.,,,' •';',......I.III;;" ' - :. 1,', I.', I' ''• I , ' I ' IDUAL INPUT HTRI-D SIEMENS 4S DEEP VERIFY INTERFACE MODULE IN FIELD ; F.B.O. F.B4O. SIEMENS 4S DEEP VERIFY VERIFY IN FIELD H 'P ABOVE FINISHED FLOOR ONTROL POINT HCP MODULE IN FIELD N/A N/A N/A t F, II Hi,I OTHERSUD RT NE E D BY SIEMENS 4S DEEP VERIFY N/A ' N/A N/A REMOTE CONVENTIONAL HZM ' ' IN FIELD N/A N/A ' ZONE MODULE N/A -E.--. • .; LINEAR BEAM j PBA -1191 SIEMENS PROVIDED VERIFY SMOKE DETECTOR IN FIELD N/A N/A N/A 1,SMOKE DETECTOR HFP-11 VV/ SIEMENS 4S DEEP CEILING (ADDRESSABLE -PHOTO) DB -11 BASE , W/ 1G RING ,' I'D, , • , DUCT SMOKE AD2-P W/ SIEMENS DUCT HOUSING VERIFY' pETECTOR TSM MODULE , IN FIELD N/A N/A 'HEAT DETECTOR HFPT-11 W/ SIEMENS 4S DEEP CEILING (ADDRESSABLE) DB -11 BASE W/ 1G RING 0) 101 . FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING , (CEILING MOUNT) I W/ 1 - 1 /2'' EXT. 01, pi • ',FIRE ALARM SPEAKER STROBE SET -MC -W SIEMENS . 4S DEEP BOX 80" A.F.F. (WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM (It N/A FIRE ALARM SPEAKER STROBE SET -HMC -CW SIEMENS 4S DEEP BOX CEILING (CEILING MOUNT) W/ 1-1/2" EXT. il,-' , ' ' FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S BOX CEILING I'(CEILING MOUNT) . W/ 1G RING ' L 4.1 ' FIRE ALARM STROBE ZR MC -W SIEMENS 4S BOX 80" A.F.F. (WALL MOUNT) W/ 1G RING TO BOTTOM U.O.N. CP t i TIRE ALARM ;SPEAKER SET -CW SIEMENS 4S DEEP BOX CEILING t(CEILING MOUNT) W/ 1-1/2" EXT. . 1 i ' ;FIRE ALARM ;SPEAKER SET -W SIEMENS 4S DEEP BOX 80" A.F.F. !(WALL MOUNT) W/ 1-1/2" EXT. TO BOTTOM FIRE ALARM ;STROBE SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY I WP l(WEATHERPROOF) 1/2" PIPE IN FIELD KAI II TI \ Int TA rr kelD_Ontl l'rs AID Dpnnt IT c ac PV VRPIRY MR t; „CONTROL RELAY V IN IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JBOX r I I.< t ALAN M TERMINAL CABINET r . li.U. r .n.o. r . D. l./ . vLI\Ir I IN FIELD II, i;.....• I . ',,, „ • I . !"1.!'"!....',...;!"-•;;...!•;...."'",.' '.,,,' •';',......I.III;;" ' - :. 1,', I.', I' ''• I , ';';.1.•..,,Ii"1.1 , ,•"",,,"i,1,4.,„ ; , .; ',!it.',"!," ;''• - ."Il't, :,I II. III I,''. ,,II,'.',', It HI JUNCTION BOX F.B.O. F.B4O. N/A VERIFY IN FIELD A . ;1;1 H» 'F. ' tr ! ; ABOVE FINISHED FLOOR N/A N/A N/A N/A t F, II Hi,I OTHERSUD RT NE E D BY N/A N/A ' N/A N/A IA • l'i\lOT APPLICABLE ;II N/A N/A ' . N/A N/A Li, DI '!1.I . tIUNLESS OTHERWISE , , N/A N/A N/A N/A ; EATHERPROOF ;plEVICE N/A N/A ' . N/A N/A RN l'As BUILT D ,1ADD OR CHANGE N/A N/A N/A N/A GR BUILT EN, .iREMOVE N/A N/A , N/A N/A BLUE IIAS BUILT 1, ;1\,111TES TO CAD N/A N/A N/A N/A ,1.: !; ' 1 • 1 . . ! 1 . ti 4 . 1 ! , P4 ( Tuk I Copyright 2006 by Guardian Security Systems, ; Inc.! All Rights (/) z0 (f) LU Ct LU•••••.. (/) LU _J 11.1 REV. BY: ; : I'l • I", .1 IT' 'e,I! II',,,t.„. I;;;. ;„ :: DESCRIPTION SHOP --DRAWINGS - _ _ - _ i;.....• I . ',,, „ • I . !"1.!'"!....',...;!"-•;;...!•;...."'",.' '.,,,' •';',......I.III;;" ' - :. 1,', I.', I' ''• I , ';';.1.•..,,Ii"1.1 , ,•"",,,"i,1,4.,„ ; , .; ',!it.',"!," ;''• - ."Il't, :,I II. III I,''. ,,II,'.',', ',1.,". "I',,..' 1,'1',t,I,'' .'er,'1,1' •, ... • '.',..' t' ; ; "• ,I,, DATE co 0 •••..; 'CNI (NI,Itt,'It LI), , „. I" ', l', ii I, • ' . • " 'I, '1! , '.',•"," • 1. tt;C. '''tt''t I ,,t',. j ',,itt • t. t,tt.,i±,tte ;,:htil, ^i',.t.ttt tIt,,t'•,!, ,"...': 7.1;11 t', '.'• ''. I; ' I II I1t. 2:.. ZOO i a Fire Reserved .„ U- 0 ‘CALE.; .i4 d DESIGNEDkBY:it, R.VEZZANIIH. DATE: 5/d/� BACKROUNDiTLAN 1130,11DED! BY: • tp \,9B UMBER525 J • I II It .tttce II I' II IIhi1 ii1iIhI I I II 'I I• • I • I • 1-4 U) aco 0G' NORTH LADY FOOTLO SCALE 118'=1' b 2S,2V r., r 1 SALE, AREA 35 Pa7R 0LCBJFE LINE L?:P- Gf rt11-u.K Tl444JBIT;1d 1 AvOVd 14 P414EL44 a 7'-0" nr• , 43 -� 43'-4REA ESTFIELD SOUTHCENTER MALL ,j' rll HI I • T,AG NOTES FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED, BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR: SIEMENS HTRI-D ADDRESSABLE INUT WIT, I 1-10013 VCNILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I\ST _L ADDR=SSABLE N DEVICES UNTIL PREPROGRAMMED W DEVICES DDHSS. OTIAT T Copyright 2006 by Guardian Security Systems, Inc. All Rights I� ,11 (.) z 0 LL�w�y W LU J W REV. BY: r I I y IIa�' .0.V.:(7.4:: ifl II'' �� .L� I' 11 a.e!3a4ae I-- DESCRIPTION SHOP --DRAWINGS _ - - - ii' II •;!'II, I.f I :I •i'' 1 , i li Ifi 4 91 i ' ' 'i Yi; DATE N,I I "i' 141 ,I,, 1i 1+ Lf)I ,1'fK �;, ,, , 1' :; 1;, — -•>-__ i .. ..-.1•.I r1 l,�L �_ - -__ _'i q , 't-+ rias-(ur"'- -- :Z I.. .- T!'_Z' I •,•r t I i F 1II-7'3'43' t ti' ' II L 15 �S..1140++•I i ,- 0" r2" F A` i ...... •4 CN1.S,2V as,2V ... . Ii' I• \ -- _ II O P21 -,._- Iunser 2S,�y_!./ rc t• ""~4,Nr: tf M. 1 �MM Q �� • FLOOR rR:31 e!&VEE r• ED .AND AP.7.:3,/cD NM �© Iia �,_: i r; - ,moi-,: T;M45 „..4104 I'I R -1A3 SAP.; T,, 3E :1=pari..it...,,r.-,Alg.)01:7..A.L. ..Ect5 .41.1 D �. INn A.'i 'ItJlitrr •U.I. N -0L' of UJr .. o. 4-11 F4l::-'. F27ER ►'" ....._I j 110"1lJ_ NORTH LADY FOOTLO SCALE 118'=1' b 2S,2V r., r 1 SALE, AREA 35 Pa7R 0LCBJFE LINE L?:P- Gf rt11-u.K Tl444JBIT;1d 1 AvOVd 14 P414EL44 a 7'-0" nr• , 43 -� 43'-4REA ESTFIELD SOUTHCENTER MALL ,j' rll HI I • T,AG NOTES FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE, FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITSI(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR L❑CATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED, BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR: SIEMENS HTRI-D ADDRESSABLE INUT WIT, I 1-10013 VCNILLATOR FIRE SUPPRESI❑N SYSTEM, FIELD LOCATE WITHIN 3 FEET OF C❑NTRL PANEL: FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. DO NOT I\ST _L ADDR=SSABLE N DEVICES UNTIL PREPROGRAMMED W DEVICES DDHSS. OTIAT T Copyright 2006 by Guardian Security Systems, Inc. All Rights I� ,11 (.) z 0 LL�w�y W LU J W REV. BY: ,' 7-'-r!'ii',;, ��� li I I I y IIa�' I ifl II'' �� .L� I' 11 DESCRIPTION SHOP --DRAWINGS _ - - - ii' II •;!'II, I.f I :I •i'' 1 , i li Ifi 91 i ' ' 'i Yi; DATE N,I I "i' 141 ,I,, 1i Lf)I ,1'fK �;, ,, , 1' :; 1;, — DRAWN' BY:I It,i I.ANDERSON1 DESIGNED; :BY,• R.VEZZANIII, I/ DATE: 5/2.0''.,:W BACKROUND \ 9B NUMBER ' 4!'r' , I.„ OVIDED BY: ry c: 1c•: 1 I E)E. 'IN \NA '„---.3F-1 !! (!1 c; , c I S F)E1\,1(_"„ ER ' OIF . .1, • ; ! cc.; c; c • ',it. -ITT': • till 1 RR /1 mALL OFFI CE lc ct cc , 1 t; c: 1 1-'o.. E.! et va • • .'t I' 11:A1 1.) NORTH 1 1 SJF ---- • / ;._ IMMO I IMO I \Air1„4, ABERCROMBIE LU [boo ;r7 ' •c'• 71 1-• . 111/h- • . ic; •:-. Cl 0 co 1101 0 . CALERIE WEST El..1v1 Li a: Li] L1_1 ::,-• 1 020 !--7;4NA! C".. P4 IV; F.:',.44= -•!!C; L :MASA [ :LEO 1! PA(DFIC. SUN WE R .-• ' ID] []] 1 54.5 Lt.; Cl 5 4.-C. ) 1 c' SYSTEM CALCULATIONS IC fJi THE VV,A,L1'2NIG CO. 1 1 1 Q 1 be be 11101 COACH I '1 1 5 1 ELECTRICAL ROOM jOILE.11 RECYCLING STORAGE AZ TE CA MEXICAN GRILL CA.1...IFORI\j1A PIZZA KITCHEN LADY FOOTLOCKER WESTFIELD SOUTHCENTER MALL LOAD:NG RISER ROOM LI jr1J- ....... c.) SCALE 1132"4 135 C 15 75 C 15. EX RISER DIAGRAM D,I 21 TLC •44 P F CiHAiiC 11 R2 LADY FOOT LOCKER LADY FOOT LOCKER C ,rrent L la : D vice Ty FACP ADD ONS. At2-P HR -R . ; 1-1, ..ijr21-D, L______ IO1?-66 „!:! f - i. , F! I. r • Amps 0.0022 0.0635 Standby: Total 0.009600 0.001600 0.005 0.0022 0.0635 0.0096 Amps 0.0023 0.064 Alarm: Total „I Current Load: Device Type SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations Qty Amps Standby: Total Amps Alarm: Total 0.021 0.0035 0.128 0.063 Main System Board SET -MC ©15CD SET -MC ©30CD SET -MC @75CD SET -MC @110CD SET-HMa-C@115CD 0.03 0.03 0.0731 Amps 0.191 Standby , urrent Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours SET-HMC-C@135CD__ Am ps,i SET--1--1-KroZe185CD J/7 ZR -MC @15CD 3 6E6 - KID 114 Arm Cu tent Load: !! ' 0.030 0.064 0.098 0.175 0.233 0.318 0.318 0.445 0.064 0.030 0.064 0.064 ,1,' 1! !!! 0.191 Amps For 5 Minutes= 0.016 Amp -hours 0.03 0.098 0.0015 Amps c,c !.! 1!! 0.333 Ams Ilj I' 1 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours I. I I:1c Alarm Current Load: 0.333 Amps For 5 Minutes= 0.028 Amp -hours Total System Current Load: 2.213 Amp -hours Ba tery P ir to be Used: 12VDC 25% Derating= 0.935 Amp -hours Amp -hours 7AH BATTERY SIZ Total System Current Load: 0.935 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH NG CALCULATION I PROJECT:_ Panel: Date: Notification Appliance WESTFIELD SOUTHCENTER MALL LADY FOOTLOCKER May 22, kmii ircgit Detail -11 --- , Wire Resistance 2.58', RRENT TOTAL 5.4 CRCUIT: SPEAKER CIRCUIT QTY Device Type 3 70.7V1/8 0 0 0. 0 0 0 0 Alarm Current Alarm Total 54 0 0 Wire Size Wird; Length Voltage at EOL Circuit Total I DEVICES= 3 PROJECT. Panel: Date: CIRCUIT: wurnItm,ottrenv.,..w.error,,v,re..mtn Tmernowu MMIOWVINWIWIWIT.1•13.. .NOtifiCation_AppliincecirC-6 WESTFIELD SOUTHCENTbi. MALL .! LADY FOOTLOCKER May 22, 2008' 0 TOTAL rnA= ' 5.4 14 65 20.384256841 5.4 S1 Wire Resistance 1.62 CURRENT TOTAL= 621 Total Wire Resistance ( R ) ( WL * 2 )* (Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I * R) EOL Voltage - E) 2.92 0.01 0.02 20.38 QTY 1 0 0 1 0 0 DEVICES= Device Type SET -MC @15CD SET -MC @30CD SET -MC @75CD Alarm Current 64 Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 64 SET -MC @110CD SET-HMC-C@115CD SET-HMC-C@177CD SET -HMC @135CD SET -HMC @185CD Z-MC@15CD 98 175 233 318 445 318 445 0 175 0 0 0 318 Total Wire Resistance ( R ) ( WL * 2 )* (Rift) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I* R) 0.86 0.62 0.53 EOL Voltage (20.4 - E) 19.87 64 64 Z-MC@30CD SET-MC-CVV@110C 4 98 233 TOTAL m A= 621 12 VOLTAGE DRO 19.8668094 621 CALCULATION I 11 I REV. BY: ' . Z c I • c I ccl"ct c c! ;., c 1 ' c l' I•1 . i t ' DESCRIPTION SHOP DRAWINGS ' „'l I',• • ; . , 1 • .t i'•I i . '! I•J;!' ..' . ': •I''t!'• ! ! Lt ! ! DATE ,• ti, 1. ' itb ! . t•1 ' . . '', c ' 64 '`-. c1 • cl'r!' ' 1ic • 0 • It Ui MPS DRAWN 'BY:'!'! LAN DERSON DESIGNED BY:,!,.1!!!!:"1 R.VEZZANlic DATE: BACKROUNCi,IFIAN.fPIOY,IDEbl!Br: ,op NUNAribR-;5 Copyright 2006 by Guardian Security Systems, Inc. All Rights ReSeryed • c • 1 t I 11;1'11,1 iiji; C1 C ; -. '3 I • •