PP - 416 SOUTHCENTER MALL - LENSCRAFTERS - PERMITS AND PLANS
416 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-352 08-S-240 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lenscrafters 416 Southcenter Mall Permit No.: 08-S-240 Date: May 29, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/9' ALL THREAD RDD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS 1 E --ADJACENT TENANT—) 0- Area u4.30(' e t rli% �r e ,— 0 ‘V ReCe;kr1 Plar> - d- 1111'4:- Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved er 0 6 • RC -16 Re -cut existing Reliable Model F 1 Standard Response 155° Pendants 1/2 x 1/2 for new ceiling lcceecirlergicataa a rnc..nts Va;ttioUt CrG,„� �� As NotedtIn Red Per ! nc' Leter i f l es Prevention standarcb..1. Fire resu l.,i •!.� ��� (-And i��.,.t „d i 1pcdtkn by he Tukwila Fire Euicau. Date:S-01. C - -. y:_ FILE COPY Weid stamps must be inspected before pipe is h m . Do not paint piping 3. hydrostatic test EUKWttA FIRE DEPARTM:N1 Please call: 575-4407 and give this job No. OSI and exact address for shut. v_a.n or restoration approval. VICINITY MAP b -1-0b T COWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL OREMM WASHINGTON 98082-0113 PH. (425) 481-7869 Lenscrafters 416 Southcenter Ma11)I Tukwila, WA Tukwila Firo 4f2979I 4J5 e DRAWN: 021• 1 SCALE: 1 JAI_ LENS CRAFTERS FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UIV 3ER SHEET TITLE FA -01 SYSTEV \FORMATION FA -02 TYPICAL DETAILS - WIRI \G A\D MOU\TI\G FA -03 FIRE ALAR v SYSTEM FLOOR PLA\ FA -04 SYSTEM CALC U LATI O \ S GE\ERAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM FLL 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. NCH NCH NCH NCH NCH NCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED; NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED, BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR. TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM . RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT., 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS, A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL, BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS '305 MM (1 FT), WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 2 8 4 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD Ca LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD A SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING L C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. L c FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM Bp WP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1 /2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY O JUNCTION BOX A.F.F. ABOVE FINISHED FLOOR FURNISHED BY N/A VERIFY IN FIELD N/A N/A N Without QOM -tents N/A r .p.u. OTHERS• �`j -i E As Noted In Red N/A N❑TN/A APPLICABLE N/A 0 Per The Att�a�hed Letter N/A t nese plans have been reviewed by The Tukwila Fire U.O.N. UNLESS OTHERWISE,r NOTED N/A ention Bureau for conformance with current city 'andards. Acceptance isNktmect to errors and N/A omissions which do not authorize violations of adopted WP WEATHERPROOF DEVICE N/A At dargs and orainance Re responsibility for the adequacy of design rests totally with the designer. .,Additions r1 !etinns or revisions to these drawings atter i A comple Fire De ('�rtificat t0 the comment RED AS BUILT ADD ❑R CHANGE N/A date will void this ac�� pt$ nce and will require a resubmittal of revised dradA'ri�js for subsequent ap�ir hal. GREEN AS BUILT REMOVE N/A Rjrpl acceptance is subj t' field test and inspecNti9r�by The Tukwila Fire Prevention Bureau. 1 esti ng and D BLUE AS BUILT NOTES TO CAD N/A Vete AYAM� r. j7 ® �0 in a Re -i terming Copyright TUKWILA FIRE DEPART Please call: 575.4407, and give this job No. _ r-- 5 -- and exact address for shut• down or restoration approval 2006 by Guardian Security Systems, 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE co 0 2CCCCa o Ci ¢ rn W w 20 FE �z Q � w= x< vJ LL!o - z ��_ W"'co- NOTICE -J d' ted, signed, Tukwila partment Pre-test e must be presented) Inspector prior to ement of Acceptance of any Fire Alarm etectian Systems. of test will result nspection Fee and tion of the testing. Ai JUN 2 3 2008 Tukwila Fire �1ea7i2 , /V Inc. All Rights Reserved Z 0 cc 0 z tau N } N SCALE: 1/8"=1' DRAWN BY: ,1.ANDERS0N DESIGNED BY: R.VEZZANI DATE: 6/18/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: J SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC 1 END OF LINE DEVICE(3.6K 1/4W) 0 SUPERVISED SWITCH GROUND M 0 LC) 0 0 0 HTRI-R STATUS LED DUCT DETECTOR L❑CATION 00 0 N.O. 0 COM 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL `"BEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L + 1 0 0 1 TB1 NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE LI -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE �II STOP IF LAST DEVICE(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE ()� RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. S S 0 0 0 0 123456 HCP TB2 65 qI0� 4321 0 0 .0 tv END OF LINE DEVICE J_ (3.6K 1/4W) • SUPERVISED 1'/ SWITCH GROUND NOTE: i 0 HTRI-D OSTATUS LED 0 NOT USED FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0- 0 rd FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �YV EOL 0 5- TEM -1 a 0 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL EARTH GROUND -. (+)TO NEXT DEVICE OR t >(-) STOP IF LAST DEVICE FROM REMOTE POWER SUPPLY C'S' CABLE> END OF LINE DEVICE FROM FACP 3.6K 1/4W) (V❑ICE CIRCUIT) ('V' CABLE) 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC Tal OI_, Io LI 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 UPERVISED 1 SWITCH SCALE NOW (STR❑BE) SPEAKER u 1 STROBE) C 0) ) STROBE S FAKE( ) 0 SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE ❑R JJJ END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER�I11N TEMPERATUE: +32' F (0' C) TO 100' F 3g C) HUMIDITY: 0-9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS US1ED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD r SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE "E– > (-) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \. CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON \ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 11 / / 0 0 ; 1 TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO SOT INS ADDRESSABLE DEVICES .,I\ -I PREPROGRAV� DEVICES AD A _L TOATONG ED W CRESS. TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Cal LI' (i) 62,1 z tom) ao 0' 0 C7 (/) UJ F - UJ (/) C5 LL1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 6/18/08 OD OD -Ztj � 111 Z E.._ QW Or 00 z z C: CC 0 c=n 0 g = V) W =� : cc (, S W u- co J 0 SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 8/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -02 EOL—$ EOE- (,r 7 (Th 2S,2V i Pa m--2S,2V c--2S,2V FX' 15 15 2S,2V c-2S,2V °// 2S,2V—o 2S,2V u —2S,2V 15 2S,2V b l' 15 2S,2V 115 (D-2S,2V 5 ' 7:.• '_a:C7u ERV'ICE CORRIDC' —; r NORTH VN. LENS CRAFTERS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' i� FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. FIRE ALARM J—BOX (VERIFY EXACT LOCATION G C.'S FIRE ALARM CONTRACTOR TO TIE—IN ALL DEVICES TO J—BOX FINAL CONNECTION TO MALL'S FIRE ALARM SYSTEM BY L,L, APR❑VED CONTRACTOR DO \OT INSTA_L ADDRESSABLE \IT AT \G DEVICES „INTI_ PREPROGRAMMED WITH DEVICES ADDRESS. CO ON z (4Lu ti4 Ezt z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 6/18/08 ao 0o u) cc Q o) W w 20 I-' w o C7 u'zz �Q(/) wp - z cc co WT 1— SCALE: 1 /8"=1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 8/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -03 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved D LERS 40 TI ON TU RE • 1-30 DI< S R A (2,10 VERIZDN RELESS MADE IN \4/ASI--i N TC)N "11: Cr.: ljj L_LJ 02 7.17 (-2) - - 0 >-- C.7). 0 00 1.1) 1.1.1 (r) LLJ CO ELEC, c, L.; 2: u)< 'jCI h-< VLu Z .; ry LLJ I ... jAMBA JU I CF.. TI --I P I c-fLi i--"1-:: A.BERC 8 OM HE NORTH ) -7 0 0 0 r) >-- Cr. C_:21 LLJ C.) 1.1) LLJ 0 Cf.) ..... ...... 1010..... ..... ....... .... 156 ..... r 01 LENS CRAFTERS WESTFIELD SOUTHCENTER MALL 11 - . ........ - 1 1.7 Lc) Le (31.-1,a SYSTEM CALCULATIONS STAR El LI C 1.< S •-•.;E A -11.. E MARINERS TEAM SH OP PACIFIC SUN. [01 [01 101 1[1 15 I . 1540LiJ TH E WA I K. N [1100 bebe 1 110 COACH 1115 - ..... -L_ 15351 QC) (-5-1 <C SCALE 1/324 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 15 15 15 C 15 S,2 V C 15 C 115 C 75 15 15 15 C 15 C 15 C 15 15 EOL -S1 15 FA -$.31:1X FACP EX D B EOL -S2 b A D,ID • • BI 21 21 BATTERY SIZING CALCULATION LENS CRAFTERS LENS CRAFTERS Detail FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations - PROJECT: Panel: LENS CRAFTERS Wire Resistance _ Panel: Date: June 18, 2008 CURRENT TOTAL= , CIRCUIT: S1 -- Current Load: Standby: Alarm: SPEAKER CIRCUIT Current Load: QTY Standby: Alarm: Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total Alarm Current Alarm Total 0.67 8 SET -MC ©15CD 64 512 Total Wire Resistance ( R ) 0 SET -MC @30CD 98 Device Type Qty Amps Total Amps Total 0 Device Type SET -MC @75CD Qty Amps Total Amps Total (WL*2)*(R/ft) HFP-11 0.51 1 0.0022 0.0022 0.0023 0.002 Total Device Load, Amps (I) (Total Cct Load) 0 0 SET -HMC -C©1 -150D 318 0 AD2-P 2 0.0635 0.0635 0.064 0.128 0 Main System Board 445 1 0.03 0.03 0.030 0.030 (E= I * R) HTR -R 0 3 0.009600 0.0096 0.021 0.063 SET -MC @15CD (E= I* R) 11 20.06 0 SET -HMC @185CD 0.064 0.704 HTRI-D -- 0.001600 Z-MC©15CD 0.0035 0 0 SET -MC @30CD 0 0.098 98 0 ICP -B6 0 0 0.005 0 SET-MC-CW©110CD 233 SET -MC @75CD 1 0 0 0.175 0.175 DEVICES= 8 TOTAL m A= 512 12 207 20.05661184 512 23.4 SET -MC @110CD 191 20.3769379 23.4 0.233 CIRCUIT: S2 SET-HMC-C@115CD 1 0.318 0.318 Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total SET-HMC-C@135CD 3 SET -MC @15CD 64 192 0.318 Total Wire Resistance ( R ) 1.01 0 0.0731 Amps 0.191 Amps SET-HMC-C@185CD ( WL * 2 )* (R/ft) 0.445 SET -MC ©75CD 175 175 Total Device Load, Amps (1) 0.81 ZR -MC @15CD SET -MC @110CD 2 0 0.064 0.128 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Voltage Drop ( E ) 0.82 0 0.098 445 0 (E= I * R) 0 HCP 318 0 0.0015 EOL Voltage Alarm Current Load: 0 0.191 Amps For 5 Minutes= 0.016 Amp -hours 1 (20.4 - E) 2 -------7)--- 0.03 Amps 1.355 Amps - Z-MC@30CD 98 ci 0 SET-MC-CW©110CD 233 0 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps TOTAL m A= For 24 Hours = 0.720 Amp -hours 19.57815456 813 Alarm Current Load: 1.355 Amps For 5 Minutes= 0.114 Amp -hours Total System Current Load: 2.213 Amp -hours 25% Derating= 1.042 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 1.042 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH I BATTERY SIZING CALCULATION Is° co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 0 c) LU c LU Cf) LU LU Ct REV. BY: ---1 WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail 1.62 1325 - PROJECT: Panel: LENS CRAFTERS Wire Resistance _ Panel: Date: June 18, 2008 CURRENT TOTAL= , CIRCUIT: S1 -- CURRENT TOTAL= CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total Alarm Current Alarm Total 0.67 8 SET -MC ©15CD 64 512 Total Wire Resistance ( R ) 0 SET -MC @30CD 98 0 Total Wire Resistance ( R ) ( WL * 2 )* (M) 0 0 SET -MC @75CD 175 0 (WL*2)*(R/ft) Total Device Load, Amps (I) 0.51 0 SET -MC ©110CD 233 0 Total Device Load, Amps (I) (Total Cct Load) 0 0 SET -HMC -C©1 -150D 318 0 (Total Cct Load) Voltage Drop ( E ) 0.34 0 SET-HMC-C@177CD 445 0 Voltage Drop ( E) (E= I * R) 0 0 SET -HMC ©135CD 318 0 (E= I* R) EOL Voltage (20.4 - E) 20.06 0 SET -HMC @185CD 445 0 0 Z-MC©15CD 64- 0 0 0 0 Z-MC@30CD 98 0 0 0 0 SET-MC-CW©110CD 233 0 0 0 0 DEVICES= 8 TOTAL m A= 512 12 207 20.05661184 512 23.4 14 191 20.3769379 23.4 CIRCUIT: S2 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 3 SET -MC @15CD 64 192 Total Wire Resistance ( R ) 1.01 0 SET -MC @30CD 98 0 ( WL * 2 )* (R/ft) 1 SET -MC ©75CD 175 175 Total Device Load, Amps (1) 0.81 0 SET -MC @110CD 233 0 (Total Cct Load) 1 SET-HMC-C@115CD 318 318 Voltage Drop ( E ) 0.82 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.58 0 SET -HMC ©185CD 445 - --- (20.4 - E) 2 -------7)--- Z-MC©15CD 64 128 - Z-MC@30CD 98 ci 0 SET-MC-CW©110CD 233 0 DEVICES= 7 TOTAL m A= 813 12 312 19.57815456 813 Is° co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 0 c) LU c LU Cf) LU LU Ct REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL . 2.68 23.4 DATE 1 6/18/08 1 Panel: LENS CRAFTERS Wire Resistance , Date: June 18, 2008 CURRENT TOTAL= CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 13 70.7V 1/8 1.8 23.4 Total Wire Resistance ( R ) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.02 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.02 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.38 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 13 TOTAL m A= 23.4 14 191 20.3769379 23.4 Is° co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 0 c) LU c LU Cf) LU LU Ct REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 1 6/18/08 1 <-<<<< co co U) -G CE _Jo) 2 2 Z W w cc I- LLP- 0 (f) Z wI CC CC 0 cn o m< •ccis w oer z co -J w LLco w w istt cc w z w (.9 (/) z 0 _J C.) LLI F - CI) ›- C/) "ALE: 1 /8" = 1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 8/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VO TAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved NUMBER: SHEET FA -04 416 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-352 08-S-240 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lenscrafters 416 Southcenter Mall Permit No.: 08-S-240 Date: May 29, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. All references are NFPA 13, 2007 Edition. RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C—CLAMP WITH SET SCREW 3/9' ALL THREAD RDD PIPE SWIVEL RING STEEL JOIST/TRUSS HANGER DETAIL NTS 1 E --ADJACENT TENANT—) 0- Area u4.30(' e t rli% �r e ,— 0 ‘V ReCe;kr1 Plar> - d- 1111'4:- Design per NFPA 13, Ordinary Hazard All materials to be new, U.L. listed, and F.M. approved er 0 6 • RC -16 Re -cut existing Reliable Model F 1 Standard Response 155° Pendants 1/2 x 1/2 for new ceiling lcceecirlergicataa a rnc..nts Va;ttioUt CrG,„� �� As NotedtIn Red Per ! nc' Leter i f l es Prevention standarcb..1. Fire resu l.,i •!.� ��� (-And i��.,.t „d i 1pcdtkn by he Tukwila Fire Euicau. Date:S-01. C - -. y:_ FILE COPY Weid stamps must be inspected before pipe is h m . Do not paint piping 3. hydrostatic test EUKWttA FIRE DEPARTM:N1 Please call: 575-4407 and give this job No. OSI and exact address for shut. v_a.n or restoration approval. VICINITY MAP b -1-0b T COWN FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL OREMM WASHINGTON 98082-0113 PH. (425) 481-7869 Lenscrafters 416 Southcenter Ma11)I Tukwila, WA Tukwila Firo 4f2979I 4J5 e DRAWN: 021• 1 SCALE: 1 JAI_ LENS CRAFTERS FIRE ALARM SYSTEM TUKWILA, WASHINGTON SHEET INDEX GENERAL NOTES SYMBOLS LEGEND SHEET \UIV 3ER SHEET TITLE FA -01 SYSTEV \FORMATION FA -02 TYPICAL DETAILS - WIRI \G A\D MOU\TI\G FA -03 FIRE ALAR v SYSTEM FLOOR PLA\ FA -04 SYSTEM CALC U LATI O \ S GE\ERAL), RISER, SITE PLA\ WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATI❑N LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATI❑N TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE TWO 600V #12 AWG THHN/THWN TWO 600V #14 AWG THHN/THWN TWISTED TWO CONDUCTOR 300V #18 AWG FPL TW CABLE CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF CONDUIT SIZE MAXIMUM FLL 1/2" .12 SQUARE 3/4" .21 SQUARE 1" .34 SQUARE 1-1/4" .60 SQUARE 1-1/2" .82 SQUARE 2" 1.34 SQUARE FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM DIMENSIONS AREA .244 0.D. .0467 .210 0.D. .0346 .156 0.D. .0191 FROM THE TABLE FILL DIMENSION FROM THE WIRE. NCH NCH NCH NCH NCH NCH N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED; NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (LE. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED, BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR. TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM . RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT., 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS, A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL, BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS '305 MM (1 FT), WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 3 2 8 4 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD Ca LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD A SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING DUCT SMOKE ®D DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING L C FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM SPEAKER STROBE (CEILING MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -HMC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. L c FIRE ALARM STROBE (CEILING MOUNT) ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIRE ALARM SPEAKER (WALL MOUNT) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM Bp WP FIRE ALARM STROBE (WEATHERPROOF) SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1 /2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY O JUNCTION BOX A.F.F. ABOVE FINISHED FLOOR FURNISHED BY N/A VERIFY IN FIELD N/A N/A N Without QOM -tents N/A r .p.u. OTHERS• �`j -i E As Noted In Red N/A N❑TN/A APPLICABLE N/A 0 Per The Att�a�hed Letter N/A t nese plans have been reviewed by The Tukwila Fire U.O.N. UNLESS OTHERWISE,r NOTED N/A ention Bureau for conformance with current city 'andards. Acceptance isNktmect to errors and N/A omissions which do not authorize violations of adopted WP WEATHERPROOF DEVICE N/A At dargs and orainance Re responsibility for the adequacy of design rests totally with the designer. .,Additions r1 !etinns or revisions to these drawings atter i A comple Fire De ('�rtificat t0 the comment RED AS BUILT ADD ❑R CHANGE N/A date will void this ac�� pt$ nce and will require a resubmittal of revised dradA'ri�js for subsequent ap�ir hal. GREEN AS BUILT REMOVE N/A Rjrpl acceptance is subj t' field test and inspecNti9r�by The Tukwila Fire Prevention Bureau. 1 esti ng and D BLUE AS BUILT NOTES TO CAD N/A Vete AYAM� r. j7 ® �0 in a Re -i terming Copyright TUKWILA FIRE DEPART Please call: 575.4407, and give this job No. _ r-- 5 -- and exact address for shut• down or restoration approval 2006 by Guardian Security Systems, 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: NVI DESCRIPTION SHOP DRAWINGS DATE co 0 2CCCCa o Ci ¢ rn W w 20 FE �z Q � w= x< vJ LL!o - z ��_ W"'co- NOTICE -J d' ted, signed, Tukwila partment Pre-test e must be presented) Inspector prior to ement of Acceptance of any Fire Alarm etectian Systems. of test will result nspection Fee and tion of the testing. Ai JUN 2 3 2008 Tukwila Fire �1ea7i2 , /V Inc. All Rights Reserved Z 0 cc 0 z tau N } N SCALE: 1/8"=1' DRAWN BY: ,1.ANDERS0N DESIGNED BY: R.VEZZANI DATE: 6/18/08 BACKROUND PLAN PROVIDED BY: �OB NUMBER: J SHEET FA -01 J THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NEPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC 1 END OF LINE DEVICE(3.6K 1/4W) 0 SUPERVISED SWITCH GROUND M 0 LC) 0 0 0 HTRI-R STATUS LED DUCT DETECTOR L❑CATION 00 0 N.O. 0 COM 0 N.0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL `"BEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVI❑US ADDRESSABLE DEVICE TO NEXT ADDRESSABLE DEVICE L + 1 0 0 1 TB1 NOTE 11 VOLTAGE MAX. - CURRENT MAX. - CONT. RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX. LINE SIZE - MIN, LINE SIZE - MUSIC OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE=NONE LI -AC POWER SOURCE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE �II STOP IF LAST DEVICE(-) FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE ()� RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,02uF 0,04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. S S 0 0 0 0 123456 HCP TB2 65 qI0� 4321 0 0 .0 tv END OF LINE DEVICE J_ (3.6K 1/4W) • SUPERVISED 1'/ SWITCH GROUND NOTE: i 0 HTRI-D OSTATUS LED 0 NOT USED FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0- 0 rd FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �YV EOL 0 5- TEM -1 a 0 0 TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL EARTH GROUND -. (+)TO NEXT DEVICE OR t >(-) STOP IF LAST DEVICE FROM REMOTE POWER SUPPLY C'S' CABLE> END OF LINE DEVICE FROM FACP 3.6K 1/4W) (V❑ICE CIRCUIT) ('V' CABLE) 0 FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC Tal OI_, Io LI 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE NAC -4 NAC -3 NAC -2 NAC -1 UPERVISED 1 SWITCH SCALE NOW (STR❑BE) SPEAKER u 1 STROBE) C 0) ) STROBE S FAKE( ) 0 SPEAKERISTROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY 80" A.F.F. 4S DEEP BOX W/ 1-1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE TO NEXT DEVICE OR END OF LINE TO NEXT DEVICE ❑R JJJ END OF LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPER�I11N TEMPERATUE: +32' F (0' C) TO 100' F 3g C) HUMIDITY: 0-9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR --> FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) DATA IN (+) > DEVICE IS US1ED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD r SMOKE DETECTOR BASE REAR VIEW TO NEXT DEVICE "E– > (-) DATA OUT HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID —\ CEILING HARD LID SPEAKER SUPPORT BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \. CEILING MOUNTED N SPEAKER/STROBE CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE=NONE JUNCTION BOX MOUNTED ON \ CEILING FLEX \ JUNCTI❑N BOX MOUNTED AGAINST CEILING SUPPORT 11 / / 0 0 ; 1 TO NEXT DEVICE 0 0 CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE=NONE SUSPENDED ILLUMINATED CEILING DO SOT INS ADDRESSABLE DEVICES .,I\ -I PREPROGRAV� DEVICES AD A _L TOATONG ED W CRESS. TH Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved Cal LI' (i) 62,1 z tom) ao 0' 0 C7 (/) UJ F - UJ (/) C5 LL1 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 6/18/08 OD OD -Ztj � 111 Z E.._ QW Or 00 z z C: CC 0 c=n 0 g = V) W =� : cc (, S W u- co J 0 SCALE: 1 /8"=1 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 8/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -02 EOL—$ EOE- (,r 7 (Th 2S,2V i Pa m--2S,2V c--2S,2V FX' 15 15 2S,2V c-2S,2V °// 2S,2V—o 2S,2V u —2S,2V 15 2S,2V b l' 15 2S,2V 115 (D-2S,2V 5 ' 7:.• '_a:C7u ERV'ICE CORRIDC' —; r NORTH VN. LENS CRAFTERS WESTFIELD SOUTHCENTER MALL SCALE 118"=1' i� FLAG NO ES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS,(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER, AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. FIRE ALARM J—BOX (VERIFY EXACT LOCATION G C.'S FIRE ALARM CONTRACTOR TO TIE—IN ALL DEVICES TO J—BOX FINAL CONNECTION TO MALL'S FIRE ALARM SYSTEM BY L,L, APR❑VED CONTRACTOR DO \OT INSTA_L ADDRESSABLE \IT AT \G DEVICES „INTI_ PREPROGRAMMED WITH DEVICES ADDRESS. CO ON z (4Lu ti4 Ezt z FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 6/18/08 ao 0o u) cc Q o) W w 20 I-' w o C7 u'zz �Q(/) wp - z cc co WT 1— SCALE: 1 /8"=1 DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 8/08 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SHEET FA -03 Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved D LERS 40 TI ON TU RE • 1-30 DI< S R A (2,10 VERIZDN RELESS MADE IN \4/ASI--i N TC)N "11: Cr.: ljj L_LJ 02 7.17 (-2) - - 0 >-- C.7). 0 00 1.1) 1.1.1 (r) LLJ CO ELEC, c, L.; 2: u)< 'jCI h-< VLu Z .; ry LLJ I ... jAMBA JU I CF.. TI --I P I c-fLi i--"1-:: A.BERC 8 OM HE NORTH ) -7 0 0 0 r) >-- Cr. C_:21 LLJ C.) 1.1) LLJ 0 Cf.) ..... ...... 1010..... ..... ....... .... 156 ..... r 01 LENS CRAFTERS WESTFIELD SOUTHCENTER MALL 11 - . ........ - 1 1.7 Lc) Le (31.-1,a SYSTEM CALCULATIONS STAR El LI C 1.< S •-•.;E A -11.. E MARINERS TEAM SH OP PACIFIC SUN. [01 [01 101 1[1 15 I . 1540LiJ TH E WA I K. N [1100 bebe 1 110 COACH 1115 - ..... -L_ 15351 QC) (-5-1 <C SCALE 1/324 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 2S,2V 15 15 15 C 15 S,2 V C 15 C 115 C 75 15 15 15 C 15 C 15 C 15 15 EOL -S1 15 FA -$.31:1X FACP EX D B EOL -S2 b A D,ID • • BI 21 21 BATTERY SIZING CALCULATION LENS CRAFTERS LENS CRAFTERS Detail FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations - PROJECT: Panel: LENS CRAFTERS Wire Resistance _ Panel: Date: June 18, 2008 CURRENT TOTAL= , CIRCUIT: S1 -- Current Load: Standby: Alarm: SPEAKER CIRCUIT Current Load: QTY Standby: Alarm: Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total Alarm Current Alarm Total 0.67 8 SET -MC ©15CD 64 512 Total Wire Resistance ( R ) 0 SET -MC @30CD 98 Device Type Qty Amps Total Amps Total 0 Device Type SET -MC @75CD Qty Amps Total Amps Total (WL*2)*(R/ft) HFP-11 0.51 1 0.0022 0.0022 0.0023 0.002 Total Device Load, Amps (I) (Total Cct Load) 0 0 SET -HMC -C©1 -150D 318 0 AD2-P 2 0.0635 0.0635 0.064 0.128 0 Main System Board 445 1 0.03 0.03 0.030 0.030 (E= I * R) HTR -R 0 3 0.009600 0.0096 0.021 0.063 SET -MC @15CD (E= I* R) 11 20.06 0 SET -HMC @185CD 0.064 0.704 HTRI-D -- 0.001600 Z-MC©15CD 0.0035 0 0 SET -MC @30CD 0 0.098 98 0 ICP -B6 0 0 0.005 0 SET-MC-CW©110CD 233 SET -MC @75CD 1 0 0 0.175 0.175 DEVICES= 8 TOTAL m A= 512 12 207 20.05661184 512 23.4 SET -MC @110CD 191 20.3769379 23.4 0.233 CIRCUIT: S2 SET-HMC-C@115CD 1 0.318 0.318 Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total SET-HMC-C@135CD 3 SET -MC @15CD 64 192 0.318 Total Wire Resistance ( R ) 1.01 0 0.0731 Amps 0.191 Amps SET-HMC-C@185CD ( WL * 2 )* (R/ft) 0.445 SET -MC ©75CD 175 175 Total Device Load, Amps (1) 0.81 ZR -MC @15CD SET -MC @110CD 2 0 0.064 0.128 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD Voltage Drop ( E ) 0.82 0 0.098 445 0 (E= I * R) 0 HCP 318 0 0.0015 EOL Voltage Alarm Current Load: 0 0.191 Amps For 5 Minutes= 0.016 Amp -hours 1 (20.4 - E) 2 -------7)--- 0.03 Amps 1.355 Amps - Z-MC@30CD 98 ci 0 SET-MC-CW©110CD 233 0 25% Derating= 2.213 Amp -hours Standby Current Load: 0.03 Amps TOTAL m A= For 24 Hours = 0.720 Amp -hours 19.57815456 813 Alarm Current Load: 1.355 Amps For 5 Minutes= 0.114 Amp -hours Total System Current Load: 2.213 Amp -hours 25% Derating= 1.042 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 1.042 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH I BATTERY SIZING CALCULATION Is° co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 0 c) LU c LU Cf) LU LU Ct REV. BY: ---1 WESTFIELD SOUTHCENTER Notification Appliance Circuit MALL Detail 1.62 1325 - PROJECT: Panel: LENS CRAFTERS Wire Resistance _ Panel: Date: June 18, 2008 CURRENT TOTAL= , CIRCUIT: S1 -- CURRENT TOTAL= CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total Alarm Current Alarm Total 0.67 8 SET -MC ©15CD 64 512 Total Wire Resistance ( R ) 0 SET -MC @30CD 98 0 Total Wire Resistance ( R ) ( WL * 2 )* (M) 0 0 SET -MC @75CD 175 0 (WL*2)*(R/ft) Total Device Load, Amps (I) 0.51 0 SET -MC ©110CD 233 0 Total Device Load, Amps (I) (Total Cct Load) 0 0 SET -HMC -C©1 -150D 318 0 (Total Cct Load) Voltage Drop ( E ) 0.34 0 SET-HMC-C@177CD 445 0 Voltage Drop ( E) (E= I * R) 0 0 SET -HMC ©135CD 318 0 (E= I* R) EOL Voltage (20.4 - E) 20.06 0 SET -HMC @185CD 445 0 0 Z-MC©15CD 64- 0 0 0 0 Z-MC@30CD 98 0 0 0 0 SET-MC-CW©110CD 233 0 0 0 0 DEVICES= 8 TOTAL m A= 512 12 207 20.05661184 512 23.4 14 191 20.3769379 23.4 CIRCUIT: S2 QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 3 SET -MC @15CD 64 192 Total Wire Resistance ( R ) 1.01 0 SET -MC @30CD 98 0 ( WL * 2 )* (R/ft) 1 SET -MC ©75CD 175 175 Total Device Load, Amps (1) 0.81 0 SET -MC @110CD 233 0 (Total Cct Load) 1 SET-HMC-C@115CD 318 318 Voltage Drop ( E ) 0.82 0 SET-HMC-C@177CD 445 0 (E= I * R) 0 SET -HMC @135CD 318 0 EOL Voltage 19.58 0 SET -HMC ©185CD 445 - --- (20.4 - E) 2 -------7)--- Z-MC©15CD 64 128 - Z-MC@30CD 98 ci 0 SET-MC-CW©110CD 233 0 DEVICES= 7 TOTAL m A= 813 12 312 19.57815456 813 Is° co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 0 c) LU c LU Cf) LU LU Ct REV. BY: z Notification Appliance Circuit Detail DESCRIPTION PROJECT: WESTFIELD SOUTHCENTER MALL . 2.68 23.4 DATE 1 6/18/08 1 Panel: LENS CRAFTERS Wire Resistance , Date: June 18, 2008 CURRENT TOTAL= CIRCUIT: SPEAKER CIRCUIT QTY Device Type Alarm Current Alarm Total Wire Size Wire Length Voltage at EOL Circuit Total 13 70.7V 1/8 1.8 23.4 Total Wire Resistance ( R ) 0.99 0 0 0 (WL*2)*(R/ft) 0 0 0 Total Device Load, Amps (I) 0.02 0 0 0 (Total Cct Load) 0 0 0 Voltage Drop ( E) 0.02 0 0 0 (E= I* R) 0 0 0 EOL Voltage 20.38 0 0 0 (20.4 - E) 0 0 0 0 0 0 DEVICES= 13 TOTAL m A= 23.4 14 191 20.3769379 23.4 Is° co 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 0 c) LU c LU Cf) LU LU Ct REV. BY: z DESCRIPTION SHOP DRAWINGS DATE 1 6/18/08 1 <-<<<< co co U) -G CE _Jo) 2 2 Z W w cc I- LLP- 0 (f) Z wI CC CC 0 cn o m< •ccis w oer z co -J w LLco w w istt cc w z w (.9 (/) z 0 _J C.) LLI F - CI) ›- C/) "ALE: 1 /8" = 1 DRAWN BY: I.ANDERSON DESIGNED BY: R.VEZZANI DATE: 6/1 8/08 BACKROUND PLAN PROVIDED BY: RISER DIAGRAM VO TAGE DROP CALCULATION Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved NUMBER: SHEET FA -04