PP - 446 SOUTHCENTER MALL - PARFUMERIE - PERMITS AND PLANS
446 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-261 08-S-298 08-S-297 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Parfumerie 446 Southcenter Mall Permit No.: 08-S-298 Date: June 10, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. tit f-Hydraulic Overview Job Number: KS0430 Report Description: Ordinary Group II Job Job Number KS0430 Design Engineer Andrew Chancellor Job Name Parfumerie Phone (425)881-0100 FAX (425)881-3030 Address 1 446 Southcenter Mall State Certification/License Number WESTESF136QF Address 2 AHJ City of Tukwila City Tukwila State WA Zip Code I 98188 Job Site Southcenter Mall System ' Density 0.20gpm/ft2 Area of Application 980.55ft2 (Actual 1019.44ft2) Most Demanding Sprinkler Data 5.6 K-Factor 20.00 at 12.755 Hose Streams 250.00 Coverage Per Sprinkler 100.00ft2 Number Of Sprinklers Calculated 17 System Pressure Demand 51.901 System Flow Demand 358.72 Total Demand 608.72 @ 51.901 Pressure Result +87.522 (62.8%) Supplies Check Point Gauges Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psi) K-Factor(K) Flow(gpm) 2 10900.00 250.00 140.000 20.000 rotation Co w 4 r� Q ra At .4i. v$ Parfumerie Supply at Node 2 (10900.00, 250.00, 140.000, 20.000) 150 _! =Static 1 1 1 1 Pressure 140.000 -.! 135 c 120 a. 4;105 Io` o c o 90 0 o *(7) a ai-75 • 7i Cit O ® m •II N to , 60 s cc c c _ _ _ °- X608.72 45 X58.72@51.901 wi h hose streams I` c : ___, © 30 =.--system demand o^ - 15 curve 10900.00 @ 20.000 quill II�� IIit�pIIhII111111!!ttItttII 111111111 11111111 Illllllfl 111111111 11111111! 1ry1003"3000 5500 6600 7700 8800 9900 11000 Water flow, gpm © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:40:59PM Page 1 Hydraulic Summary Job Job Number: KS0430 Report Description: Ordinary Group II Job Number KS0430 Design Engineer Andrew Chancellor Job Name Parfumerie State Certification/License Number WESTESF136QF Address 1 446 Southcenter Mall AHJ City of Tukwila Address 2 Job See Southcenter Mall City Tukwila State WA Zip Code 98188 Drawing Name Parfumerie System Remote Areas) Most Demanding Sprinkler Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 980.55ft2 (Actual 1019.44ft2) Additional Hose Supplies Node Flow(gpm) Number Of Sprinklers Calculated 17 Coverage Per Sprinkler 100.00ft2 AutoPeak Results. Pressure For Remote Area(s) Adjacent To Most Remote Area Total Hose Streams 250.00 System Flow Demand 358.72 Total Water Required (Including Hose Allowance) 608.72 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 16.42 between nodes 64 and 126 Maximum Velocity Under Ground 1.35 between nodes 2 and 288 Volume capacity of Wet Pipes 2673.91gal Volume capacity of Dry Pipes 0.75ft' Supplies Node Hose Flow (gpm) Static (psi) Residual @ Flow (psi) (gpm) Available @ Total Demand (psi) (gpm) Required (psi) Safety Margin (psi) 2 250.00 140.000 20.000 1 10900.00 139.423 1 608.72 51.901 1 87.522 Contractor".„ Contractor Number KS0430 Contact Name Andrew Chancellor Contact Title Project Manager Contractor Name Western States Fire Protection Phone (425)881-0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX (425)881-3030 Address 2 E-mail City Redmond State WA Zip Code 98052 Web -Site (� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:05PM Page 2 8Report Summary Of Outflowing Devices ` Job Number: KS0430 Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Density (gpmpft2) Sprinkler 115 21.54 20.00 5.6 14.798 0.22gpm/ft2 Sprinkler 116 21.74 20.00 5.6 15.077 0.22gpm/ft2 Sprinkler 105 20.67 20.00 5.6 13.629 0.21gpm/ft2 I Sprinkler 102 20.41 20.00 5.6 13.281 0.20gpm/ft2 Sprinkler 107 20.95 20.00 5.6 14.002 0.21 gpm/ft2 Sprinkler 109 21.02 20.00 5.6 14.091 0.21gpm/ft2 Sprinkler 114 21.51 20.00 5.6 14.755 0.22gpm/ft2 Sprinkler 112 21.47 20.00 5.6 14.696 0.21gpm/ft2 Sprinkler 111 21.42 20.00 5.6 14.632 0.21gpm/ft2 Sprinkler 117 22.03 20.00 5.6 15.482 0.22gpm/ft2 Sprinkler 113 21.47 20.00 5.6 14.705 0.21gpm/ft2 Sprinkler 106 20.92 20.00 5.6 13.958 0.21gpm/ft2 Sprinkler 110 21.23 20.00 5.6 14.370 0.21gpm/ft2 Sprinkler 104 20.67 20.00. 5.6 13.626 0.21gpm/ft2 Sprinkler 108 21.00 20.00 5.6 14.058 0.21gpm/ft2 b Sprinkler 101 20.00 20.00 5.6 12.755 0.20gpm/ft2 Sprinkler 103 20.64 20.00 5.6 13.590 0.21gpm/ft2 c Most Demanding Sprinkler Data (, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:O6PM Page 3 Hydraulic Analysis 1 Job Number: KSO430 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Summary Downstream Upstream Elevation Discharge K -Factor Pt Pn FittingsEq. Length ITotal Length Go Route 1 DR 1.049 0=20.00 7.42 C=120 0.130131 22-10% Pf 3.889 101 13-7 q=20.00 K=5.6 12.755 Spr(-12.755) 7-0 Pe -0.300 141 14-3 16.344 E(2-0), PO(5-0) 29-10% Pv BL 1.610 Q=40.64 6.41 C=120 0.059988 8-3 Pf 0.494 141 14-3 16.344 Pe 0.000 136 14-3 16.838 8-3 Pv BL 1.610 0=61.32 9.66 C=120 0.128358 11-0 Pf 1.412 136 14-3 16.838 Pe -0.000 129 14-3 18.250 11-0 Pv BL 1.610 0=82.79 13.05 C=120 0.223705 1-7 Pf 0.351 129 14-3 18.250 Pe 126 14-3 18.602 1-7 Pv BL 1.610 0=104.21 16.42 C=120 0.342415 1-9 Pf 3.336 126 14-3 18.602 8-d Pe 64 14-3 21.938 PO(8-0) 9-9 Pv CM 4.260 0=358.72 8.07 C=120 0.029493 374-6'/ Pf 17.275 64 14-3 21.938 211-2'% Pe 5.448 258 1-8% 44.660 12fE(8-11'/2), 2P0(26-4), 585-9 Pv 2fEE(4-5%), 2Ee2(5-3), CV(28-11'/2), GV(2-7%) FM 8.329 Q=358.72 2.11 C=120 0.001126 21-10 Pf 0.061 258 1-8% 44.660 32-0 Pe -0.000 248 1-8% 44.721 2fE(16-0) 53-10 Pv MS 10.020 0=358.72 1.46 C=120 0.000458 20-2 Pf 4.540 248 1-8% 44.721 67-0 Pe -1.635 288 5-5% 47.626 3LtE(16-0), BV(19-0), BFP(-4.500) 87-2 Pv UG 10.400 Q=358.72 1.35 C=140 0.000287 113-1 Pf 0.075 288 5-5'/ 47.626 146- Pe 4.200 2 -4-2% 51.901 3LtE(25-6), E(35-1), 2EE(17-6%), 259-9'/ Pv S Gib Route 2 DR 1.049 0=20.41 7.58 C=120 0.135088 28-10'/2 Pf 4.847 102 11-2 q=20.41 K=5.6 13.281 Spr(-13.281) 7-0 Pe -1.347 28 14-3 16.780 E(2-0), PO(5-0) 35-10% Pv BL 1.610 0=62.62 9.87 C=120 0.133472 11-0 Pf 1.468 28 14-3 16.780 Pe 37 14-3 18.249 11-0 Pv BL 1.610 0=84.14 13.26 C=120 0.230474 7-8 Pf 3.615 37 14-3 18.249 8-0�I Pe 63 14-3 21.864 Z, PO(8-0) 15-81 Pv CM 4.260 0=169.32 3.81 C=120 0.007354 10-0 Pf 0.074 63 14-3 21.864 Pe -0.000 64 14-3 21.938 10-0 Pv Route 3 DR 1.049 0=20.64 7.66 C=120 0.137994 29-0'/ Pf 4.557 103 10-0 q=20.64 K=5.6 13.590 Spr(-13.590) 4- Pe -1.853 163 14-3 16.294 2E(2-0) 33-0'/ Pv BL 1.610 0=20.64 3.25 C=120 0.017131 2-111/1 2-11Y Pf 0.050 Pe Pv 163 141 14-3 14-3 16.294 16.344 imo Route 4 DR 1.049 0=20.67 7.67 C=120 0.138332 25-11'/ Pf 4.560 104 11-2 q=20.67 K=5.6 13.626 Spr(-13.626) 7-01,Pe -1.347 136 14-3 16.838 E(2-0), PO(5-0) 32-11'% Pv a. Route 5 DR 1.049 Q=20.67 7.67 C=120 0.138361 25- Pf 4.499 105 11-2 q=20.67 K=5.6 13.629 Spr(-13.629) 7- Pe -1.347 28 14-3 16.780 E(2-0), PO(5-0) 32- Pv fai Route 6 DR 1.049 Q=20.92 7.77 C=120 0.141446 28-6'/ Pf 5.028 106 11-6 q=20.92 K=5.6 13.958 Spr(-13.958) 7- Pe -1.203 125 14-3 17.783 E(2-0), P0(5-0) 35-6'/ Pv BL 1.610 0=63.15 9.95 C=120 0.135536 10-5 Pf 1.414 125 14-3 17.783 Pe -0.000 131 14-3 19.197 10-5 Pv BL 1.610 0=85.18 13.42 C=120 0.235801 3-4 Pf 2.668 131 14-3 19.197 8-0 Pe 63 14-3 21.864 P0(8-0) 11-4 Pv ab Route 7 DR 1.049 0=20.95 7.78 C=120 0.141853 25-11'1 Pf 4.676 107 11-2 q=20.95 K=5.6 14.002 Spr(-14.002) 7-0 Pe -1.347 29 14-3 17.330 E(2-0), P0(5-0) 32-11% Pv (, © M.E.P.CAD, Inc. 4 AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:08PM Page 4 Hydraulic Analysis Job Number: KS0430 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Summary Downstream Elevation Discharge K -Factor Upstream Pt Pn Fittings Eq. Length Total Length BL 1.610 Q=42.70 6.73 C=120 0.065717 8-5 Pf 0.554 Pe -0.000 Pv 29 14-3 34 14-3 17.330 17.884 8-5 BL 1.610 Q=63.72 10.04 C=120 0.137823 2-7 Pf 0.354 Pe Pv 34 14-3 38 14-3 17.884 18.238 2- BL 1.610 Q=85.19 13.42 C=120 0.235834 7-8 Pf 3.700 Pe Pv 38 14-3 64 14-3 18.238 21.938 P0(8-0) 8-0' 15-8 le Route 8 DR 1.049 Q=21.00 7.79 C=120 0.142378 23- Pf 3.843 Pe -0.300 Pv 108 13-7 q=21.00 K=5.6 137 14-3 14.058 17.601 Spr(-14.058) 2E(2-0) 4- 27- BL 1.610 Q=21.00 3.31 C=120 0.017676 8-3 8-3 Pf 0.146 Pe 0.000 Pv 137 14-3 130 14-3 17.601 17.746 BL 1.610 Q=42.22 6.65 C=120 0.064373 0-7 Pf 0.037 Pe 0-7 Pv 130 14-3 125 14-3_ 17.746 17.783 Route 9 DR 1.049 Q=21.02 7.80 C=120 0.142689 28-0 7-0 35-0, Pf 4.996 Pe -1.203 Pv 109 11-6 q=21.02 K=5.6 34 14-3 14.091 17.884 Spr(-14.091) E(2-0), PO(5-0) Route 10 DR 1.049 Q=21.23 7.88 C=120 0.145298 25-6 7-0 32-6 Pf 4.724 Pe -1.347 Pv 110 11-2 q=21.23 K=5.6 130 14-3 14.370 17.746 Spr(-14.370) E(2-0), PO(5-0) Route 11 DR 1.049 Q=21.42 7.95 C=120 0.147747 28-0 7-0 35-0 Pf 5.173 Pe -1.203 Pv 111 11-6 q=21.42 K=5.6 126 14-3 14.632 18.602 Spr(-14.632) E(2-0), PO(5-0) Route 12 DR 1.049 Q=21.47 7.97 C=120 0.148346 25-11Y 7- 32-11'/ Pf 4.890 Pe -1.347 Pv 112 11-2 q=21.47 K=5.6 38 14-3 14.696 18.238 Spr(-14.696) E(2-0), PO(5-0) o Route 13 DR 1.049 Q=21.47 7.97 C=120 0.148435 25-11'/ 7- 32-11'/ Pf 4.893 Pe -1.347 Pv 113 11-2 q=21.47 K=5.6 129 14-3 14.705 18.250 Spr(-14.705) E(2-0), PO(5-0) Route 14 DR 1.049 Q=21.51 7.99 C=120 0.148899 25-6 7-0 32-6 Pf 4.841 Pe -1.347 Pv 114 11-2 q=21.51 K=5.6 37 14-3 14.755 18.249 Spr(-14.755) E(2-0), PO(5-0) iai Route 15 DR 1.049 Q=21.54 8.00 C=120 0.149303 28-3i Pf 4.818 4-0 Pe -2.937 32-31 Pv 115 7-6 q=21.54 K=5.6 20 14-3 14.798 16.679 Spr(-14.798) 2E(2-0) BL 1.610 Q=21.54 3.39 C=120 0.018535 5-5% 5-5% Pf 0.101 Pe Pv 20 14-3 28 14-3 16.679 16.780 ea Route 16 DR 1.049 Q=21.74 8.07 C=120 0.151903 29-6 4-0 33-6 Pf 5.088 Pe -2.937 Pv 116 7-6 q=21.74 K=5.6 24 14-3 15.077 17.228 Spr(-15.077) 2E(2-0) BL 1.610 Q=21.74 3.43 C=120 0.018858 5-5 5-5 Pf 0.102 Pe 0.000 Pv 24 14-3 29 14-3 17.228 17.330 Route 17 DR 1.049 Q=22.03 8.18 C=120 0.155678 25-6 Pf 5.062 7-0 Pe -1.347 32-6 Pv 117 11-2 q=22.03 K=5.6 131 14-3 15.482 19.197 Spr(-15.482) E(2-0), PO(5-0) Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier I Actual Inside Diameter 4.87 ( Value Of C 100 Multiplying Factor 0.713 130 140 150 1.16 1.33 1.51 Schedule 40 Steel Pipe Inside Diameter ) =Factor g6, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:08PM Page 5 li Hydraulic Analysis Job Number: KS0430 Report Description: Ordinary Group 11 Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Elevation Upstream Discharge K -Factor Pt Pn Fittings Length Eq. Length Total Length Pressure Summary Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points E Velocity pressure at a point in a pipe EE Eel Ee2 FDC fE fEE fig FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z ALV Alarm Valve AngV Angle Valve b Bushing BaiV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeiV Deluge Valve DPV Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22'/2° Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 06/04/2008 3:41:08PM Page 6 ge Hydraulic..Grap,h Job Number: KS0430 Report Description: Ordinary Group II Supply at Node 2 150 135 :Static Pressure 140.000 120 105 90 *(0 a 11-1 75 co N N o_ 60 45 608.72 X58.72 with hose @ 51.901 streams 30 15 System demand curve 10900.00 @ 20.000, 4 0 111111 11111 11 1 1 I I 1 1 1 1 1 1 1 11 1 1 1 1 1 I 1 111111111 1 I J L I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 1 1 I I 1 p1IILW 11002200 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 2 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.423 @ 608.72 System Demand 358.72 @ 51.901 System Demand (Including Hose Allowance) 608.72 @ 51.901 (¢, ©M.E.P.CAD, Inc. 1 AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:09PM Page 7 Customer 446 656 $OUTHCENTER MALL IPGIVILA, WA 98188 , GUARDIAN SECURITY LIFE .AND PROPERTY Project 446 Project # PROTECTION List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: MAY,30,08 Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) " 18) .19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) ..48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard PARFUMERIE VICINITY MAP (Suite# 446) SCALE: NTS General Notes TOILET ROOM STOCK ROOM WALL LIGHT / GYP BD CEILING 7-B" AFF Ordinary Group II*0.20 pm/ft2 for 980.55ft2 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculaticns). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 6. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. 0 ' Wthout Commeht ❑As Noted In Red w- Per The AttachedLettet. !nese plans have been reviewed by The Tukw l.a Fir Prevention Bureau for conformance with current 014, standards. Acceptance is suhiactto errors.and..... omissions.which do not authorize violations of r_doptei standards and ordinances. The resporlsihiliW far the adequacy of design rests totally with the designer Additions, deletions or revisions to these.dra+riinijS. dt'Gr this date.will void this acceptance i2,1111 rct.iuie.:a resubmittal of revised drawings for ::ub equcnt Final acceptance is subject to field test and inspccdon . ; The Tukwila Fire Prevention aireau. IDate: C /0 -Q1 3 By: L . -,,.31, ---. 210... I UKWILA FIRE DEPARTMEItII Please call: 575.4407 and give this job No.O�-S- and exact address for shut. town or restoration approval PICTECE \'Veld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test pprovai. RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SPRINKLER MAIN (TYPJ/ 14'-3" AFF LAY -IN CEILING WITH CLIPS FOR PLENUM APPLICATION —ELECTRICAL PANEL f--- MALL'S X BRACE ABOVE EXHAUST FAN f A�mirw N r ,M1111110111101 i:ummormis,/.0, `F 11o2I ,r 1U7i LIGHT FIXTURE LIGHT FIXTURE CEILING MOUNTED TRACK FOR MERCHANDISE DISPLAY LUMINARIES GYP BD SOFFIT 11'-2" AFF GYP BD SOFFIT 11'-6" AFF GYP BD SOFFIT 13'-7" AFF LIGHT FIXTURE /1 STOREFRONT PLANE ABOVE 10'-0" STOREFRONT PLANE / AT GROUND LEVEL FIRE SPRINKLER PLAN 114"= 1' 0' 2' 4' Scale: 114" _ 1'-0" .-TYPICAL.. FLEXABLE SPRINKLER CONNECTION FLEXHEAD PIPE NIPPLE gym. SPRINKLER BRANCHLINE LEXABLE CONNECTING HOSE.::. IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.809 • SWIVEL SWAY 'BRACE RTTING bid BRACE PIPE 32' KWIK BOLT (2 VC EMBED LENGTH) FIG. 10)0 'FAST CLAMP' SWAY BRACEATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS HON•THREADED BRACE PIPE Parfumerie Remote Area: Retail # 446 r CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 F? DENSITY .20 GPM / Fe for 980.56 F * SPRINKLER Reliable Model G4A ORIFICE 112" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 358.72 GPM( 47.63: PSI • At time of Design 13'-7" CLG.=34.63% AREA REDUCTION SYMBOL LEGEND REVISIONS Sprinkler Legend APPROVAL: City of Tukwila 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 17 5.6 Pendent %s White 155°F Reliable G4A Concealer Total = 17 CONT. NO.: KS0430 12' FILE COPY FIG.4A PIPE CLAMP FOR SWAY BRACE 39' KWIK BOLT (21H' EMBED LENGTH) FIG. 809 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT NOt4THREADED BRACE PIPE LATERAL ERANCHLINE RE S TRAIY T NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch Concrete Construction Bottom or Concrete to Center Line of Pipe Note on Plan Note on Plan: Hangar Number and'A' Dimension HANGER DETAIL NOT TO SCALE Western States Fire Protection Company DRAWN BY: Andrew Chancellor SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/04/08 7102180th AVE NE, STE A-1 C 5 - REDMOND, WA - 98052 Lic. #: WESTESF I36QF VICINITY MAP DETAIL NOT TO SCALE z WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIN / DALLAS I DECATUP /DENVER r OJUJTH /HOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS 1 PHOENIX/ PORTLAND,/ RAPID CITY/ ST. PAIL (SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Parfumerie 446 Southcenter Mall Tukwila,WA 98188 FIRE SPRINKLER PLAN 7nr i, kvilia Fire ZIpD2e Mo, 51) ir 1.4. I • . I 4. TUKWILA RIE Y id M INGTON 4. t'•.; • SHEET INDEX RAL NOTES .t, SYMBOLS LEGEND SHEET \U vi3E HET TITLE FA -01 YST6 l\FO• vATIO\ FA -02 YPIQAL DETAILS - WRI\G A\D vOU\TI\G FA -03 SYSTE V FLOO PLA\ FA -04 SY 110\A CALCULATIO\S (GE \EAL), 'ISER, SITE, PLA !,I • :14 • ; WIRE DESIGNATION. SCHEDULE WIRE SCHEDULE AND CO\DUIT FILL CHART WIRE DESIGNATION • • „I..; , - , • sYmkiL DESCRIF?TION • NUMBER OF CONDUCTORS SIZE. TYPE ' , COLOR CODE • : i:4 D H,1H H •i:.4I11 P ; S ; 2S! A.'•14i; .1!.1 V:I.,;;;, l'•11 2v, ' I• :4'1! X,; T4:4i UD$1!! Uiik • III'''.; M4,:ti i' DATA LINE DOOR HOLDER HI', DEVICE14P0WER STROBE STROBEI:•CIRCUIT ANNUNCATDR i: SPEAKE SPEAKER:: I• REMOTEL.INDICATION i 4 LOW LEVEL , UNDER9ROUND UNDERGOUND ! t DOOR HOLDER BEAM DLTECTOR .. . • -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 416 FPL/FPLR • RED (JACKET) POWER - 24VDC TWO 414 FPL/FPLR ' RED '(JACKET) - 24VDC TWO 416 FPL/FPLR RED (JACKET) , CIRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) - RETURN TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD 416 . FPL/FPLR RED (JACKET) CIRCUIT - FEED TWISTED PAIR 414 , FPL/FPLR RED (JACKET) CIRCUIT - RETURN TWISTED PAIR • 414 FPL/FPLR : RED (JACKET) LIGHT TWO ' ' 418 FPL/FPLR , RED (JACKET) AUDIO , TWISTED PAIR W/ SHIELD 416 FPL/FPLR . RED (JACKET) DATA ' TWISTED PAIR RATED ' 418 FPL/FPLR . RED (JACKET) INITIATION TWISTED PAIR RATED 418 FPL/FPLR .RED (JACKET) ' .. POWER TWO ' 416 • FPL/FPLR ' RED (JACKET) POWER TWO . ' 414 FPL/FPLR , RED (JACKET) DESCRIPTION .. CONDUIT FILL CHART . ; • . , , . ! 1H, , ' 1 •1:'' 1t1.: : .•, ! ': :! . • ', ' . . • • 1 NO. CJ,F •1! TWO I CONDUIT I; l• , l• , , I ;II ! ' . . CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED ' .210 O.D. .0346 .. • : ., CONDUCTOR 300V . #18 AWG FPL TW CABLE .156 0.D. , .0191. . FILL . , . ., . • , • ' .: CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. , , , CONDUIT SIZE MAXIMUM FILL . ,.. 1/2" .12 SQUARE INCH 3/4" : .21 SQUARE INCH , ' • 1" .34 SQUARE INCH , 1-1/4" .60 SQUARE INCH 4 1-1/2" .82 SQUARE INCH • . 2" 1.34 SQUARE INCH ' , FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4 ' ' I SHIELDED WIRE TO BE !11 GROUND/ED , I : ! AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE ANDHTAPED AT END FOR SIEMENS SYSTE • I ! , DO NOT INSTALL ADDRESSA:LE INI IATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. ,, 1. NUMBERS ADJACENT TO DEVI4 SYMBk DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE 2. DETECTOR AND AUDIBLE CIRC 3. AUDIBLE/VISUAL CIRCUIT WIRII BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN 5 ELECTRIC CODE, NFPA 72, Lq 5. INSTALLATION MATERIALS (I.Ell STANDARD BOXES, FIBER 011 ARE NOT SUPPLIED BY SIEME 6. DETECTORS SHALL NOT BE M AIR STREAM OF AIR SUPPLY 1 ; SECO;NID DEVICE ON ADDRESSABLE LOOP 1. IT P,4 Gj $ I Y SHALL BE OBSERVED. ERVISED. NO PARALLEL ,ICT FORVIANCE WITH THE NATIONAL ALC01(S), AND/OR AUTHORITY HAVING JURISDICTION. CONDUI WIRE, FITTINGS, HANGERS, S :CAIBIIE, FITTINGS, AND ASSOCIATED EQUIPMENT) CERR'RUS DIVISION. b,NITED h DIRECT UTLETS PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN ITH, RE TYPE, QUANTITY AND COLOR ODE C, AND UNIQUELY MARKED FOR TURE 8. INSTALLING CONTRACTOR SHig LI REfLi DRAWINGS FOR "AS BUILT" P ,JOSE,S 9. FOR ADDITIONAL INSTALLATIO ILINSTR SHEETS AND/OR INSTALLATIO 1\1$T13 10. THE 120vac POWER ELECTRIC WOR MUST COMPLY WITH ARTICLE 25 ;AN SPECIFICALLY SECTION 1-5.2p'.2.:1N SOURCES. 120vac POWER SH L NOT DIRECT SUPERVISION OF FIRE 'A LArN 11. ALL HORN/STROBE AND STROBE DE OF 80" A.F.F. OR 6" BELOW ROPpE 12. ALL MANUAL PULL STATIONS • ACTIVATION DEVICE. ALL 13. ALL PANEL NUMBERS AND CI CUITS 14. ALL 120VAC GENERATOR. CIRCUITS ARE FJ),M DE PECT TO CONDUCTOR SIZE, & OR CABLE TRAY, ,\IDUCTORS SHALL BE PERMANENTLY, PENTIFICATION. N ONE SET OF ACCURATELY MARKED TIONS, REFER TO CATALOG CUT TIONS. SUPPLYING FIRE ALARIv SYSTEV PANELS 760 OF NFPA 70, N.E.C. AND NFPA 72, EFERENCE TO DEDICATED BRANCH POWER ILDE APPLIED TO FIRE ALARM PANEL WITHOUT iECHNICIAN. IES SHALL BE MOUNTED AT A HEIGHT CEILING, WHICHEVER IS LESS. E MOUNTED AT 48" A.F.F. TO THE ILL BE ON THE RECORD DRAWINGS SET. ''CATED CIRCUITS FROM THE EMERGENCY 15. PER NFPA 72 SECTION 5-3 .3AE CTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN -4 OF AL TRADES IS COMPLETE AND FINAL. EXCEPTION' WHERE ' BY 'THE' AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING COSTRUCTON. DETECTORS THAT HAVE BEEN1' INSTAL:0 PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED R REPL4CED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CON TINU • AND THEN FROM DEVICE TO • OTHER BACK BOXES OF DIF 17, ALL WIRING SHALL BE METER AND FREE OF SHORTS BETW, • FINAL EQUIPMENT TRIM. ' 111 S FRO FACP TO FIRST DEVICE ON A CIRCUIT EVJCE IITH0UT SPLICING IN PULL BOXES OR RENT.1 D, VER EN • 4 2 IED TO BE CONTINUOUS, FREE OF GROUND UCTORS AND OTHER CIRCUITS PRIOR TO . 18. ALL CABLES SHALL BE MAR !-. AS J DICATED ON FIRE ALARM' RISER WITH A PERMANENT LABEL AT ALL VICES UNCTION BOXES AND FACP. ! ., . 19. THE ELECTRICAL CON TRACTO SH414• LEAN ALL DIRT. AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THirIRI RM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEP" NSTA[. ATION. 1 I •P 1 ! 11 ,, • ; 20. DETECTORS MUST BE RATED RHITE ERATURE IN THE ENVIRONMENT IN WHICH . . IT IS LOCATED. 21. ALL WIRING BETWEEN FLOOR H4L, E LOCATED •IN CONDUIT. 22. NFPA 72'2007 6.4.2.2.2 ALL Ibl-YLES F CLASS A CIRCUITS USING • PHYSICAL CONDUCTORS (E.G.,METAL, OPTICAL. FIBER) SHALL BE. • INSTALLED SUCH THAT THE 0 11GOINGIAND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO TH IbONT.R L UNIT, RESPECTIVELY, ARE ; ROUTED SEPARATELY. THE 0L0iNd ND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE ON'111\I! E SAME CABLE ASSEMBLY (LE., • MULTI -CONDUCTOR CABLE), E CL SdPDE OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 Al ADEQUATE SEPARATION) BETW THIS SEPARATION IS REQUIRE CABLES FROM PHYSICAL DAM, SEPARATION TO PREVENT PH THE CABLE IS INSTALLED VER: CABLE IS INSTALLED !!, coAL' 6.4.2.2.2 IS TO PROVIDE HE OUTGOING AND RETURN CABLES'. ;ToEp ENSURE PROTECTION OF THE GE.HTHREC0MMENIED MINIMUM I!, 14CA'L D A MAGE IS 305 MM (1 FT) WHERE CALLY, ND 1.22 M (4 FT) WHERE THE• , . !;I11, •, QUANTITY 2 3 EX SYM B DE RIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FAC FIF,"i ALARM ,6( CO TROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FAR dFIR ALARM ' SOD -C' 1 66" A.F.F. RETE ANNUNCIATOR TO TOP RE (OTE BOOSTERPAD-3 T606" TAO.PF. F. , ER SUPPLY INRFACE MODULE HTRI-R VERIFY .111: RELAY . IN FIELD T !RFACE MODULE IN FIELD VERIFY IN HTRI-D SIEMENS 4S DEEP DLPL INPUT BP ! 1EX SIEMENS PROVIDED 11-n: SIEMENS PROVIDED SIEMENS 4S DEEP HC CO MO, TIROL POINT ;ULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZ RE ZO, ,OTE CONVENTIONAL HZM MODULE AR BEAM KE DETECTOR Llir* SIEMENS 4S DEEP VERIFY IN FIELD PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD (AD KE DETECTOR HFP-11 W/ SIEMENS RESSABLE-PHOTO) DB -11 BASE 4S DEEP W/ 10 RING CEILING DO DE T SMOKE CTOR AD2-P W/ SIEMENS DUCT HOUSING VERIFY TSM MODULE IN FIELD HE 44,J DETECTOR RESSABLE) HFPT-1 1 \AV SIEMENS DB -11 BASE 4S DEEP W/ 10 RING CEILING ALARM KER STROBE LING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIR;1 ALARM SP:o KER STROBE (W LL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIR SP ALARM KER STROBE L MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. FIR. ST (C • st, ALARM BE LING MOUNT) CEILING ZR -MC -CW SIEMENS 4S BOX W/ 10 RING CEILING FIR ST OA) • ALARM BE MOUNT) ZR -MC -W SIEMN3 43 DOX W/ 10 RING 80" A.F.F. TO BOTTOM U.O.N. FIR SP' (c ! ALARM ik‘KER LING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. • FIR SR: (\f`f FIR ST A ! ALARM AKER MOUNT) SET -W SIEMENS 45 DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM MR ALARM BE ATHERPROOF) MU VI -VOLTAGE CONTROL RELAY I , SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD Li MAONETIC DO 'R HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB13X 14 FIR TE ALARM I NAL CABINET F.B.O. e!! F.B.O. 4410114041204.1.4111144Mill•411.0111411112144111114 F.B.O. VERItiY IN FIELD TION BOX FBO. FB,O, '44 • TE VERIEY IN F ELD AF. 44 14 I ,• F,B. AB FL, E FINISHED N/A N/ U,O, WP FU OT ISHED BY RS N/A AP ICABLE N/A 1 N/A 0 Per The Atkithibd Letter N/A N/A N/A N/A Without Comments As Noted In Rcd 1 !len plans have been renevAd by 1 he i Mtge Hre , A PeOdhtion Bureau for confoYfrignce with current cite/ 9 standards. Acceptance is subject to errors and UN NO; SS OTHERWISE N/A WE DE THERPROOF N/A ICE RE AS: AD UILT OR CHANGE N/A GRE AS1' RE UILT VE N/A omissions which do not authorize violations of adopted stWaras and ordinances. 11-66 responsibility for theWA adequacy of design rests totally with the designer. AMtisions, deletions or revisloh§ to these drawings atter, this date will void this.acceteae and will require a 'N'm resubmittal of revised drawings for subsequent approval. i 4. ;7! ;J. 4.4 44.4 91 uJ uJ LU LU isr) CO C3• REV. BY: EGH - DESCRIPTION SHOP DRAWINGS . t 1_11 5:1 Q 05/20/20081 2<<<<< •,1•12r..! • /A complete0 signe Tukwla Fi6Acceptance is subjectVfletd test and inspectia* Tb a Tukwila Fire Prevention Bureau Dtait0 6/3/Oe ByN:/ 700 N/A BLU AS, NO BUILT ES TO CAD N/A N/A N/A N/A Fire Depd;nent Pre-test • Certifiote ilrusib4iresent& to the Inpetorrior to Testing oft nj, frO Alarm commenceni ntIcceptan Aina and DetOctiorl *terns. • Failure ofiest resuli in a Re -inspection )ee and termination of hetesting. !I H 11 TUKWILA FIRE DEPARTMM Please call: 575-440Z and give this job No.cf3'- r-gc,o/ and exact address for shut., iown or restoration approvaL TuwiaI 1-4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Rerve rSALE: 1/8"1' ==1 F33 DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACIMUND PLAN PROVIDED BY: .J..013 NUMBER: SHEET A-01 • •;.;' 144, 11 :• II' THE DUCT SMOK6 !DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE NM NEPA 72. THE PREFERRED INSTALL LOCATION:OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT!WiDTHS FROM!iANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. •I; „ Is! BEND,OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. ; ,! I, 6-10 DUCT EQUIVALENT I, DIAMETERS ; • • . I j _ !;-11 TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING 1 4 1 , TO NEXT ADDRESSABLE DEVICE A H STOP IF LAST DEVICE 1 FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC DUCT DETECTOR LOCATION END OF LINE DEVICE (3.6K 1/4W) H11. SUPERVISED SWITCH 0 1.0 0 1, OUND •" HTRI-R STATUS LED 00 0 N.O. 0 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE • !• 'I • ' ..1,1 TO NEXT ADDRESSABLE DEVICE •I !'1 NOTE 1' VOLTAGE MAX -- CURRENT MAX.— CONT. RES. MAX -- MAX. CABLE LENGTH— C (LINE TO LINE)— C (LINE TO SHIELD)— MAX. LINE SIZE— MIN. LINE SIZE— OUTLET SAMPLING TUBE INLET SAMPLIN TUBE 1.; AT LEAST SIX DUCT WIDTHS FROM BEND (Z) I I TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR • I I SCALE=NONE !!! MUSIC ),L AC POWER SOURffe!.li , . 01; COMBINE ALL SHIELDS Afl ISOLATE FROM GROUNDIN TO NEXT ADDRESSABLE DEVICE: STOP IF LAST DEVICE FROM XLS CONTROL PANEL bI PREVIOUS ADDRESSABLE BEY: 'END OF:ii DEVICEi1 (3.6K 11'' // / SUPERISEDL.LL./ // SWITCH GROUND 1!; RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0.02uF 0,04uF 14 AWG 18 AWG NOTE 2' ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. Io I 'TB1 s 000 ,$) 1 2 3 4 5 6 TB2 C P 0 0 65 461 4 3 2 1 TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP !ABEL SCALE 0 7 0 tr) 0 tr) @ @ HTRI-D STATUS LED CO 0 0 NUT CO 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-b ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 •Ii1;iiI ,GND N. 0 PAD -3 0 00 0 , • . INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 .-AUX 14- 1- 1 2+ 2- 2 NC C NO + - + + - , + - + - 24K n NAC -4 NAC -3 NAC -2 NAC -1 I ; I I 1 : USED ND, OF; INE DE 6K1/4 1 , UPEIRVI WITCH 3' FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE -71: DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 ( FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) 'ICE FROM FACP (VOICE CIRCUIT) ('V' CABLE) 1' 470 OHMS 11/1 EOL Prn TSM -1 0 11 ] • 0 0 OC TYPICAL AD2-P DUCT SMOKE DETECTOR - WRING DETAIL SCALE NONE (+) (-) STROBE SPEAKER (+) (--) (+) STROBE EARTH GROUND 1 -->.(4-)TO NE --4*(-) STOP (+) (-) STROBE SPEAKER (r) SPEAKER/STROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 0 80" A.F.F. 4S DEEP BOX W/ 1 -1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE ' 1 ! DEVICE LAST D TO NE DEVIC ; END 111 1 TO 'NE DEVIC END! I • OR LINE OR LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERtlINI TEMPERATU,RE: +32' F 0 C TO 100' F (36 HUMIDITY: —9 % RELATIVE HUMI ITY, NON—CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (—) DATA IN (+) > •-t DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION KM DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE -1c- > (-) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID HARD LID CEILING SPEAKER SUPPORT TIL.E. BRIDGE ti • 4" SQUARE DEEP BOX • / WITH 1-1/2" EXTENSION N CEILING MOUNTED SPEAKER/STROBE N, CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING FLEX \ • JUNCTI MOUNTED A CEILING S N BOX AINST PPORT • :SMKE DETECTOR -- SMOKE DETECTOR MOUNTING SCALE:NONE 00 0 0 1 TO NEXT DEVICE' CADDY BAR SUSPENDED .';• ILLUMINATED CEILING DO \OT INSTA_L ADDRESSABLE 0\ DEVICES U\TI_ •PRPROGRAMMED W • DEVICES ADDRESS. TIAT1 ri ht .2006 b Guardian Securit S stems, Inc. All R hts Resery RELEASE/REVISIONS >- m - LU z -t< DESCRIPTION SHOP DRAWINGS lu i-- 05/20/20081 6ALE: 1/8"=l' RING AND _J DRAWN BY: • E.HAMERSKI DESIGNED I BY: R.VEZZANI DATE:05/20/2008 } BACIROUND PLAN PROVIDED BY: \.2..op NUMBER: SHEET A-0 I , 1, 1 FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED ;BY MECHANICAL CONTRACTOR, WIRED, BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. REV. BY: EGH DESCRIPTION - SHOP DRAWINGS 1. I' . . -1 - DATE - 05/20/2008 12 <- <<<< 1 . -. • :,. E1F1.hr. fr. , : 2 1.! 1 2S, Alitill, ,, .. ...... ..... . - - '1 r Adr. ---,1 , ir 0 .,1 ., , , . . . C I i • , r D,I .: ,r, 1 , • .t i 4 4.1Z, 1 : 1 1 t -, NAN — ....,... ,.. .... i , f i IP 1 .7.' I n'-- , ' , ...1 . I ' 1 .LT ... ,- . ;------ ..... I ,,.........,..-1,a Al , I /\ AI ...,• . if \ o. -I—if:ill) FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED ;BY MECHANICAL CONTRACTOR, WIRED, BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. REV. BY: EGH DESCRIPTION - SHOP DRAWINGS DATE - 05/20/2008 12 <- <<<< DO NOT NS" ---ALL ADDRESSABLE INTOA DEVICES J\TIL PREPROGRAMMED W DEVICES ADDRESS. DESIGNED BY: R.VEZZANF BACKROUND PLAN PROVIDED BY V.OB NUMBER: SHEET 1'1 111 Copyright 2006 by Guardian Security Systems, Inc. All Rights ResOrve SYSTEM CAL LATIONS PARFUMERIE SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PARFUMERIE FACP ADD ONS Current Load: Devid0 Type Standby: Alarm: Total Total Curretit Load: DeviCkType Standby: Alarm: Tc, C A M ER A 01-1-1 ER H [VI A TER N] TR ASH KOS 1700-FLOCKFR EX:ST:NG F001! COI< -f1 TANLI- MaiOYsteml,Board SE14C 150D L SET -MC 30qD SET'(' 76qD SEIMQ 17,4CD §ttILIMC-C115CD SE-0-imc,c0135CD SE*IMC-C@185CD ZR -F 15CO__ ZR- 30C 0.064 0.098 0.175 0.318 0.318 0.445 0.064 0.196 0.350 Amps 0.0022 0.0635 0.009600 0.001600 Total 0.0022 0.0635 0.0096 Amps 0.0023 0.064 0.021 0.0035 Total 0.0731 0.064 0.098 0.0015 y Current Load: .:Current Load: 0.0731 For 24 Hours = Amp -hours For 5 Minutes= Amp -hours Stan. by CurrOnt Load: AlarCurren Load: 1ir 0.03 Amps For 24 Hours = 0.720 Amp -hours 25% Derating= Amp -hours 0.704 Amps For 5 Minutes= 0.059 Amp -hours Total System Current Load: Amp -hours 25% Derating= 0.974 Amp -hours 12VDC Amp -hours 0 a. Amp -hours Batt ry. Pair to be Used: Amp -hours PROJECT: Panel: Date: ATTERY SIZ I Notification Appliance C WESTFIELD SOUTHCENTER MALL PARFUMERIE May 29, 2008 ENT TOTAL= 849 CIRCUIT: QTY 1 27 CALH- ORNIIA RiZZA KITCHEN ,4> " v, DEVICES= Device Type Alarm Current - SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET-HMC.C@115CD SET-HMC-C@177CD SET -HMC @135CD SET -HMC @185CD Z-MC@15CD Z-MC@30CD SET-MC-CW@110CD 7 64 98 175 233 Alarm Total 64 196 525 0 Wire Size Voltage at EOL Circuit Total 318 445 318 445 64 98 233 TOTAL m A= Total Wire Resistance ( R ) ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I* R) EOL Voltage (20.4 - E) 19.6710486 SUITE 446 WESTFIELD SOUTHCENTER MALL SCALE 1132'4 PROJECT: Panel: Date: CIRCUIT: QTY 3 0 0 0 Notification Appliance C cut etail WESTFIELD SOUTHCENTER MALL PARFUMERIE May 29, 2008 SPEAKER CIRCUIT Device Type 70.7V 1/8 Alarm Current Alarm Total 1.8 5.4 WireSize Wire gth ,Voltage at EOL Circuit Total 2S,2V 2S,2V 2S,2V Total Wire Resistance ( R ) 2.92 ( WL * 2 )*(R/ft) Total Device Load, Amps (I) 0.01 (Total Cct Load) Voltage Drop ( E ) 0.02 (E= I * R) EOL Voltage 20.38 (20.4 - E) FA -BOX FACP EXEX DEVICES= TOTAL m A= 5.4 RISER DIAGRAM DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACROLJND; PLAN PROVIDEDi:BY: NUMBER: VOLTAGE DROP LCULATION SHEET ri ht 2006 b Guardian Securit S stems, Inc. All R' hts Reserved 446 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-261 08-S-298 08-S-297 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Parfumerie 446 Southcenter Mall Permit No.: 08-S-298 Date: June 10, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. tit f-Hydraulic Overview Job Number: KS0430 Report Description: Ordinary Group II Job Job Number KS0430 Design Engineer Andrew Chancellor Job Name Parfumerie Phone (425)881-0100 FAX (425)881-3030 Address 1 446 Southcenter Mall State Certification/License Number WESTESF136QF Address 2 AHJ City of Tukwila City Tukwila State WA Zip Code I 98188 Job Site Southcenter Mall System ' Density 0.20gpm/ft2 Area of Application 980.55ft2 (Actual 1019.44ft2) Most Demanding Sprinkler Data 5.6 K-Factor 20.00 at 12.755 Hose Streams 250.00 Coverage Per Sprinkler 100.00ft2 Number Of Sprinklers Calculated 17 System Pressure Demand 51.901 System Flow Demand 358.72 Total Demand 608.72 @ 51.901 Pressure Result +87.522 (62.8%) Supplies Check Point Gauges Node Flow(gpm) Hose Flow(gpm) Static(psi) Residual(psi) Identifier Pressure(psi) K-Factor(K) Flow(gpm) 2 10900.00 250.00 140.000 20.000 rotation Co w 4 r� Q ra At .4i. v$ Parfumerie Supply at Node 2 (10900.00, 250.00, 140.000, 20.000) 150 _! =Static 1 1 1 1 Pressure 140.000 -.! 135 c 120 a. 4;105 Io` o c o 90 0 o *(7) a ai-75 • 7i Cit O ® m •II N to , 60 s cc c c _ _ _ °- X608.72 45 X58.72@51.901 wi h hose streams I` c : ___, © 30 =.--system demand o^ - 15 curve 10900.00 @ 20.000 quill II�� IIit�pIIhII111111!!ttItttII 111111111 11111111 Illllllfl 111111111 11111111! 1ry1003"3000 5500 6600 7700 8800 9900 11000 Water flow, gpm © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:40:59PM Page 1 Hydraulic Summary Job Job Number: KS0430 Report Description: Ordinary Group II Job Number KS0430 Design Engineer Andrew Chancellor Job Name Parfumerie State Certification/License Number WESTESF136QF Address 1 446 Southcenter Mall AHJ City of Tukwila Address 2 Job See Southcenter Mall City Tukwila State WA Zip Code 98188 Drawing Name Parfumerie System Remote Areas) Most Demanding Sprinkler Data 5.6 K -Factor 20.00 at 12.755 Occupancy Ordinary Group II Hose Allowance At Source 250.00 Density 0.20gpm/ft2 Area of Application 980.55ft2 (Actual 1019.44ft2) Additional Hose Supplies Node Flow(gpm) Number Of Sprinklers Calculated 17 Coverage Per Sprinkler 100.00ft2 AutoPeak Results. Pressure For Remote Area(s) Adjacent To Most Remote Area Total Hose Streams 250.00 System Flow Demand 358.72 Total Water Required (Including Hose Allowance) 608.72 Maximum Pressure Unbalance In Loops 0.000 Maximum Velocity Above Ground 16.42 between nodes 64 and 126 Maximum Velocity Under Ground 1.35 between nodes 2 and 288 Volume capacity of Wet Pipes 2673.91gal Volume capacity of Dry Pipes 0.75ft' Supplies Node Hose Flow (gpm) Static (psi) Residual @ Flow (psi) (gpm) Available @ Total Demand (psi) (gpm) Required (psi) Safety Margin (psi) 2 250.00 140.000 20.000 1 10900.00 139.423 1 608.72 51.901 1 87.522 Contractor".„ Contractor Number KS0430 Contact Name Andrew Chancellor Contact Title Project Manager Contractor Name Western States Fire Protection Phone (425)881-0100 Extension Address 1 7102 180th Ave Ne, Suite A-105 FAX (425)881-3030 Address 2 E-mail City Redmond State WA Zip Code 98052 Web -Site (� ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:05PM Page 2 8Report Summary Of Outflowing Devices ` Job Number: KS0430 Description: Ordinary Group II Device Actual Flow (gpm) Minimum Flow (gpm) K -Factor (K) Pressure (psi) Density (gpmpft2) Sprinkler 115 21.54 20.00 5.6 14.798 0.22gpm/ft2 Sprinkler 116 21.74 20.00 5.6 15.077 0.22gpm/ft2 Sprinkler 105 20.67 20.00 5.6 13.629 0.21gpm/ft2 I Sprinkler 102 20.41 20.00 5.6 13.281 0.20gpm/ft2 Sprinkler 107 20.95 20.00 5.6 14.002 0.21 gpm/ft2 Sprinkler 109 21.02 20.00 5.6 14.091 0.21gpm/ft2 Sprinkler 114 21.51 20.00 5.6 14.755 0.22gpm/ft2 Sprinkler 112 21.47 20.00 5.6 14.696 0.21gpm/ft2 Sprinkler 111 21.42 20.00 5.6 14.632 0.21gpm/ft2 Sprinkler 117 22.03 20.00 5.6 15.482 0.22gpm/ft2 Sprinkler 113 21.47 20.00 5.6 14.705 0.21gpm/ft2 Sprinkler 106 20.92 20.00 5.6 13.958 0.21gpm/ft2 Sprinkler 110 21.23 20.00 5.6 14.370 0.21gpm/ft2 Sprinkler 104 20.67 20.00. 5.6 13.626 0.21gpm/ft2 Sprinkler 108 21.00 20.00 5.6 14.058 0.21gpm/ft2 b Sprinkler 101 20.00 20.00 5.6 12.755 0.20gpm/ft2 Sprinkler 103 20.64 20.00 5.6 13.590 0.21gpm/ft2 c Most Demanding Sprinkler Data (, © M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:O6PM Page 3 Hydraulic Analysis 1 Job Number: KSO430 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Summary Downstream Upstream Elevation Discharge K -Factor Pt Pn FittingsEq. Length ITotal Length Go Route 1 DR 1.049 0=20.00 7.42 C=120 0.130131 22-10% Pf 3.889 101 13-7 q=20.00 K=5.6 12.755 Spr(-12.755) 7-0 Pe -0.300 141 14-3 16.344 E(2-0), PO(5-0) 29-10% Pv BL 1.610 Q=40.64 6.41 C=120 0.059988 8-3 Pf 0.494 141 14-3 16.344 Pe 0.000 136 14-3 16.838 8-3 Pv BL 1.610 0=61.32 9.66 C=120 0.128358 11-0 Pf 1.412 136 14-3 16.838 Pe -0.000 129 14-3 18.250 11-0 Pv BL 1.610 0=82.79 13.05 C=120 0.223705 1-7 Pf 0.351 129 14-3 18.250 Pe 126 14-3 18.602 1-7 Pv BL 1.610 0=104.21 16.42 C=120 0.342415 1-9 Pf 3.336 126 14-3 18.602 8-d Pe 64 14-3 21.938 PO(8-0) 9-9 Pv CM 4.260 0=358.72 8.07 C=120 0.029493 374-6'/ Pf 17.275 64 14-3 21.938 211-2'% Pe 5.448 258 1-8% 44.660 12fE(8-11'/2), 2P0(26-4), 585-9 Pv 2fEE(4-5%), 2Ee2(5-3), CV(28-11'/2), GV(2-7%) FM 8.329 Q=358.72 2.11 C=120 0.001126 21-10 Pf 0.061 258 1-8% 44.660 32-0 Pe -0.000 248 1-8% 44.721 2fE(16-0) 53-10 Pv MS 10.020 0=358.72 1.46 C=120 0.000458 20-2 Pf 4.540 248 1-8% 44.721 67-0 Pe -1.635 288 5-5% 47.626 3LtE(16-0), BV(19-0), BFP(-4.500) 87-2 Pv UG 10.400 Q=358.72 1.35 C=140 0.000287 113-1 Pf 0.075 288 5-5'/ 47.626 146- Pe 4.200 2 -4-2% 51.901 3LtE(25-6), E(35-1), 2EE(17-6%), 259-9'/ Pv S Gib Route 2 DR 1.049 0=20.41 7.58 C=120 0.135088 28-10'/2 Pf 4.847 102 11-2 q=20.41 K=5.6 13.281 Spr(-13.281) 7-0 Pe -1.347 28 14-3 16.780 E(2-0), PO(5-0) 35-10% Pv BL 1.610 0=62.62 9.87 C=120 0.133472 11-0 Pf 1.468 28 14-3 16.780 Pe 37 14-3 18.249 11-0 Pv BL 1.610 0=84.14 13.26 C=120 0.230474 7-8 Pf 3.615 37 14-3 18.249 8-0�I Pe 63 14-3 21.864 Z, PO(8-0) 15-81 Pv CM 4.260 0=169.32 3.81 C=120 0.007354 10-0 Pf 0.074 63 14-3 21.864 Pe -0.000 64 14-3 21.938 10-0 Pv Route 3 DR 1.049 0=20.64 7.66 C=120 0.137994 29-0'/ Pf 4.557 103 10-0 q=20.64 K=5.6 13.590 Spr(-13.590) 4- Pe -1.853 163 14-3 16.294 2E(2-0) 33-0'/ Pv BL 1.610 0=20.64 3.25 C=120 0.017131 2-111/1 2-11Y Pf 0.050 Pe Pv 163 141 14-3 14-3 16.294 16.344 imo Route 4 DR 1.049 0=20.67 7.67 C=120 0.138332 25-11'/ Pf 4.560 104 11-2 q=20.67 K=5.6 13.626 Spr(-13.626) 7-01,Pe -1.347 136 14-3 16.838 E(2-0), PO(5-0) 32-11'% Pv a. Route 5 DR 1.049 Q=20.67 7.67 C=120 0.138361 25- Pf 4.499 105 11-2 q=20.67 K=5.6 13.629 Spr(-13.629) 7- Pe -1.347 28 14-3 16.780 E(2-0), PO(5-0) 32- Pv fai Route 6 DR 1.049 Q=20.92 7.77 C=120 0.141446 28-6'/ Pf 5.028 106 11-6 q=20.92 K=5.6 13.958 Spr(-13.958) 7- Pe -1.203 125 14-3 17.783 E(2-0), P0(5-0) 35-6'/ Pv BL 1.610 0=63.15 9.95 C=120 0.135536 10-5 Pf 1.414 125 14-3 17.783 Pe -0.000 131 14-3 19.197 10-5 Pv BL 1.610 0=85.18 13.42 C=120 0.235801 3-4 Pf 2.668 131 14-3 19.197 8-0 Pe 63 14-3 21.864 P0(8-0) 11-4 Pv ab Route 7 DR 1.049 0=20.95 7.78 C=120 0.141853 25-11'1 Pf 4.676 107 11-2 q=20.95 K=5.6 14.002 Spr(-14.002) 7-0 Pe -1.347 29 14-3 17.330 E(2-0), P0(5-0) 32-11% Pv (, © M.E.P.CAD, Inc. 4 AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:08PM Page 4 Hydraulic Analysis Job Number: KS0430 Report Description: Ordinary Group II Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Summary Downstream Elevation Discharge K -Factor Upstream Pt Pn Fittings Eq. Length Total Length BL 1.610 Q=42.70 6.73 C=120 0.065717 8-5 Pf 0.554 Pe -0.000 Pv 29 14-3 34 14-3 17.330 17.884 8-5 BL 1.610 Q=63.72 10.04 C=120 0.137823 2-7 Pf 0.354 Pe Pv 34 14-3 38 14-3 17.884 18.238 2- BL 1.610 Q=85.19 13.42 C=120 0.235834 7-8 Pf 3.700 Pe Pv 38 14-3 64 14-3 18.238 21.938 P0(8-0) 8-0' 15-8 le Route 8 DR 1.049 Q=21.00 7.79 C=120 0.142378 23- Pf 3.843 Pe -0.300 Pv 108 13-7 q=21.00 K=5.6 137 14-3 14.058 17.601 Spr(-14.058) 2E(2-0) 4- 27- BL 1.610 Q=21.00 3.31 C=120 0.017676 8-3 8-3 Pf 0.146 Pe 0.000 Pv 137 14-3 130 14-3 17.601 17.746 BL 1.610 Q=42.22 6.65 C=120 0.064373 0-7 Pf 0.037 Pe 0-7 Pv 130 14-3 125 14-3_ 17.746 17.783 Route 9 DR 1.049 Q=21.02 7.80 C=120 0.142689 28-0 7-0 35-0, Pf 4.996 Pe -1.203 Pv 109 11-6 q=21.02 K=5.6 34 14-3 14.091 17.884 Spr(-14.091) E(2-0), PO(5-0) Route 10 DR 1.049 Q=21.23 7.88 C=120 0.145298 25-6 7-0 32-6 Pf 4.724 Pe -1.347 Pv 110 11-2 q=21.23 K=5.6 130 14-3 14.370 17.746 Spr(-14.370) E(2-0), PO(5-0) Route 11 DR 1.049 Q=21.42 7.95 C=120 0.147747 28-0 7-0 35-0 Pf 5.173 Pe -1.203 Pv 111 11-6 q=21.42 K=5.6 126 14-3 14.632 18.602 Spr(-14.632) E(2-0), PO(5-0) Route 12 DR 1.049 Q=21.47 7.97 C=120 0.148346 25-11Y 7- 32-11'/ Pf 4.890 Pe -1.347 Pv 112 11-2 q=21.47 K=5.6 38 14-3 14.696 18.238 Spr(-14.696) E(2-0), PO(5-0) o Route 13 DR 1.049 Q=21.47 7.97 C=120 0.148435 25-11'/ 7- 32-11'/ Pf 4.893 Pe -1.347 Pv 113 11-2 q=21.47 K=5.6 129 14-3 14.705 18.250 Spr(-14.705) E(2-0), PO(5-0) Route 14 DR 1.049 Q=21.51 7.99 C=120 0.148899 25-6 7-0 32-6 Pf 4.841 Pe -1.347 Pv 114 11-2 q=21.51 K=5.6 37 14-3 14.755 18.249 Spr(-14.755) E(2-0), PO(5-0) iai Route 15 DR 1.049 Q=21.54 8.00 C=120 0.149303 28-3i Pf 4.818 4-0 Pe -2.937 32-31 Pv 115 7-6 q=21.54 K=5.6 20 14-3 14.798 16.679 Spr(-14.798) 2E(2-0) BL 1.610 Q=21.54 3.39 C=120 0.018535 5-5% 5-5% Pf 0.101 Pe Pv 20 14-3 28 14-3 16.679 16.780 ea Route 16 DR 1.049 Q=21.74 8.07 C=120 0.151903 29-6 4-0 33-6 Pf 5.088 Pe -2.937 Pv 116 7-6 q=21.74 K=5.6 24 14-3 15.077 17.228 Spr(-15.077) 2E(2-0) BL 1.610 Q=21.74 3.43 C=120 0.018858 5-5 5-5 Pf 0.102 Pe 0.000 Pv 24 14-3 29 14-3 17.228 17.330 Route 17 DR 1.049 Q=22.03 8.18 C=120 0.155678 25-6 Pf 5.062 7-0 Pe -1.347 32-6 Pv 117 11-2 q=22.03 K=5.6 131 14-3 15.482 19.197 Spr(-15.482) E(2-0), PO(5-0) Equivalent Pipe Lengths of Valves and Fittings (C=120 only) ` C Value Multiplier I Actual Inside Diameter 4.87 ( Value Of C 100 Multiplying Factor 0.713 130 140 150 1.16 1.33 1.51 Schedule 40 Steel Pipe Inside Diameter ) =Factor g6, ©M.E.P.CAD, Inc. AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:08PM Page 5 li Hydraulic Analysis Job Number: KS0430 Report Description: Ordinary Group 11 Pipe Type Diameter Flow Velocity HWC Friction Loss Downstream Elevation Upstream Discharge K -Factor Pt Pn Fittings Length Eq. Length Total Length Pressure Summary Pipe Type Legend Units Legend Fittings Legend AO BL CM DN DR DY FM FR MS OR RN SP ST UG Arm -Over Branch Line Cross Main Drain Drop Dynamic Feed Main Feed Riser Miscellaneous Outrigger Riser Nipple Sprig Stand Pipe Underground Diameter Elevation Flow Discharge Velocity Pressure Length Friction Loss HWC Pt Pn Pf Pe Pv Inch Foot gpm gpm fps psi Foot psi/Foot Hazen -Williams Constant Total pressure at a point in a pipe Normal pressure at a point in a pipe Pressure loss due to friction between points Pressure due to elevation difference between indicated points E Velocity pressure at a point in a pipe EE Eel Ee2 FDC fE fEE fig FN fT g GIoV GV Hose HV Hyd LtE mecT Noz P1 P2 PIV PO PrV PRV red S sCV Spr St T Tr U WirF WMV z ALV Alarm Valve AngV Angle Valve b Bushing BaiV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DeiV Deluge Valve DPV Dry Pipe Valve 90° Elbow 45° Elbow 11W Elbow 22'/2° Elbow Flow Device Fire Department Connection 90° FireLock(TM) Elbow 45° FireLock(TM) Elbow Flange Floating Node FireLock(TM) Tee Gauge Globe Valve Gate Valve Hose Hose Valve Hydrant Long Turn Elbow Mechanical Tee Nozzle Pump In Pump Out Post Indicating Valve Pipe Outlet Pressure Relief Valve Pressure Reducing Valve Reducer/Adapter Supply Swing Check Valve Sprinkler Strainer Tee Flow Turn 90° Tee Run Union Wirsbo Water Meter Valve Cap M.E.P.CAD, Inc. AutoSPRINK®VR5 v5.1.32 06/04/2008 3:41:08PM Page 6 ge Hydraulic..Grap,h Job Number: KS0430 Report Description: Ordinary Group II Supply at Node 2 150 135 :Static Pressure 140.000 120 105 90 *(0 a 11-1 75 co N N o_ 60 45 608.72 X58.72 with hose @ 51.901 streams 30 15 System demand curve 10900.00 @ 20.000, 4 0 111111 11111 11 1 1 I I 1 1 1 1 1 1 1 11 1 1 1 1 1 I 1 111111111 1 I J L I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 1 1 1 1 1 1 1 I I 1 p1IILW 11002200 3300 4400 5500 6600 7700 8800 9900 11000 Water flow, gpm Hydraulic Graph Supply at Node 2 Static Pressure 140.000 Residual Pressure 10900.00 @ 20.000 Available PressureTime of Test 139.423 @ 608.72 System Demand 358.72 @ 51.901 System Demand (Including Hose Allowance) 608.72 @ 51.901 (¢, ©M.E.P.CAD, Inc. 1 AutoSPRINK® VR5 v5.1.32 06/04/2008 3:41:09PM Page 7 Customer 446 656 $OUTHCENTER MALL IPGIVILA, WA 98188 , GUARDIAN SECURITY LIFE .AND PROPERTY Project 446 Project # PROTECTION List of Materials Vendor Guardian Security Systems Inc 1743 1st Ave. South Seattle, WA 98134 Phone #: (206)622-6545 Fax #: (206)628-4990 Type of Equipment FIRE ALARM Date: MAY,30,08 Item Qty. Manuf. Model Description Unit Pri Total Price 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) 16) 17) " 18) .19) 20) 21) 22) 23) 24) 25) 26) 27) 28) 29) 30) 31) 32) 33) 34) 35) 36) 37) 38) 39) 40) 41) 42) 43) 44) 45) 46) 47) ..48) 49) 50) Siemens PAD -3 Siemens AD2-P Siemens HTRI-D Siemens HTRI-R Siemens SET CW,W Siemens SET W Siemens ZR-MC-W,W Power Supply for Strobes with Standby** Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1 Supervised Addressable Input Module Supervised Addressable Output Relay Module Interior Audible Speaker Annunciator Interior Audible Speaker Annunciator Interior Visual Strobe Annunciator Conduit Systems: All smoke removal and detection and control devices in an approved metallic raceway and all devices in conduit per Standard PARFUMERIE VICINITY MAP (Suite# 446) SCALE: NTS General Notes TOILET ROOM STOCK ROOM WALL LIGHT / GYP BD CEILING 7-B" AFF Ordinary Group II*0.20 pm/ft2 for 980.55ft2 1. Western States Fire Protection to add new pendent heads and branchlines in new tenant space. Sprinklers in the new store shall be spaced in accordance with NFPA #13 Ordinary hazard Occupancy with 130 ft2 maximum spacing (.20 density used in calculations) FlexHead Brand flexheads will be used to pipe heads to ceiling (equivalent length included in calculaticns). 2. The building is constructed with non-combustible materials and qualifies as unobstructed construction. 3. All hanger assemblies shall be spaced and installed in accordance with NFPA & manufacturer's specifications. 4. Branchline and arm -over pipe is black Schedule 40 pipe. 5. All new threaded fittings are cast iron class 125 or ductile iron class 150. 6. The owner is responsible for all appropriate maintenance of sprinkler system in accordance with NFPA, as well as state & local codes. 7. The owner is responsible for the freeze protection of all sprinkler system piping and components that are not designed for freezing conditions. 6. Existing fire sprinkler system to remain. Western States Fire Protection will modify the existing system only in the areas of work. All other areas are not in contract and WSFP is not responsible for existing conditions. 0 ' Wthout Commeht ❑As Noted In Red w- Per The AttachedLettet. !nese plans have been reviewed by The Tukw l.a Fir Prevention Bureau for conformance with current 014, standards. Acceptance is suhiactto errors.and..... omissions.which do not authorize violations of r_doptei standards and ordinances. The resporlsihiliW far the adequacy of design rests totally with the designer Additions, deletions or revisions to these.dra+riinijS. dt'Gr this date.will void this acceptance i2,1111 rct.iuie.:a resubmittal of revised drawings for ::ub equcnt Final acceptance is subject to field test and inspccdon . ; The Tukwila Fire Prevention aireau. IDate: C /0 -Q1 3 By: L . -,,.31, ---. 210... I UKWILA FIRE DEPARTMEItII Please call: 575.4407 and give this job No.O�-S- and exact address for shut. town or restoration approval PICTECE \'Veld stamps must be inspected before pipe is hung. Do not paint piping prior to hydrostatic test pprovai. RISER DETAIL HYDRAULIC REFERENCE ONLY NOT TO SCALE SPRINKLER MAIN (TYPJ/ 14'-3" AFF LAY -IN CEILING WITH CLIPS FOR PLENUM APPLICATION —ELECTRICAL PANEL f--- MALL'S X BRACE ABOVE EXHAUST FAN f A�mirw N r ,M1111110111101 i:ummormis,/.0, `F 11o2I ,r 1U7i LIGHT FIXTURE LIGHT FIXTURE CEILING MOUNTED TRACK FOR MERCHANDISE DISPLAY LUMINARIES GYP BD SOFFIT 11'-2" AFF GYP BD SOFFIT 11'-6" AFF GYP BD SOFFIT 13'-7" AFF LIGHT FIXTURE /1 STOREFRONT PLANE ABOVE 10'-0" STOREFRONT PLANE / AT GROUND LEVEL FIRE SPRINKLER PLAN 114"= 1' 0' 2' 4' Scale: 114" _ 1'-0" .-TYPICAL.. FLEXABLE SPRINKLER CONNECTION FLEXHEAD PIPE NIPPLE gym. SPRINKLER BRANCHLINE LEXABLE CONNECTING HOSE.::. IN STANDARD LENGTHS MOUNTING BRACKET REDUCING FITTING SUSPENDED T -BAR GRID SPRINKLER HEAD CEILING TILE FLEXHEAD DETAIL NOT TO SCALE FIG.809 • SWIVEL SWAY 'BRACE RTTING bid BRACE PIPE 32' KWIK BOLT (2 VC EMBED LENGTH) FIG. 10)0 'FAST CLAMP' SWAY BRACEATTACHMENT LINE PIPE LATERAL LINE RESTRAINTS HON•THREADED BRACE PIPE Parfumerie Remote Area: Retail # 446 r CALCULATION DESIGN CRITERIA: STANDARD NFPA #13-2007 OCCUPANCY CLASS ORD HAZARD II MAX. COVERAGE per HEAD 130 F? DENSITY .20 GPM / Fe for 980.56 F * SPRINKLER Reliable Model G4A ORIFICE 112" K= 5.6 WATER FLOW INFORMATION': STATIC 140 PSI RESIDUAL 20 PSI FLOW 10900 GPM AT BASE OF RISER. SYSTEM REQUIRES: 358.72 GPM( 47.63: PSI • At time of Design 13'-7" CLG.=34.63% AREA REDUCTION SYMBOL LEGEND REVISIONS Sprinkler Legend APPROVAL: City of Tukwila 2 -WAY EARTHQUAKE BRACE 4 -WAY EARTHQUAKE BRACE HYDRAULIC REFERENCE POINT HANGER SYMBOL BRANCHLINE RESTRAINT NO. DESCRIPTION DATE SYM. SIN QTY. K SPRAY ORIF. FIN. TEMP. MFR./MODEL 17 5.6 Pendent %s White 155°F Reliable G4A Concealer Total = 17 CONT. NO.: KS0430 12' FILE COPY FIG.4A PIPE CLAMP FOR SWAY BRACE 39' KWIK BOLT (21H' EMBED LENGTH) FIG. 809 NO -THREAD SWIVEL SWAY BRACE ATTACHMENT LATERAL BRANCHLINE RESTRAINT NOt4THREADED BRACE PIPE LATERAL ERANCHLINE RE S TRAIY T NOT TO SCALE Hanger No. 07C HILTI Kwik Bolt III Cut Rod Lgth Rounded to Nearest Inch Concrete Construction Bottom or Concrete to Center Line of Pipe Note on Plan Note on Plan: Hangar Number and'A' Dimension HANGER DETAIL NOT TO SCALE Western States Fire Protection Company DRAWN BY: Andrew Chancellor SPRK. ON SHEET: SEE LEGEND SPRK. ON JOB: DATE: 06/04/08 7102180th AVE NE, STE A-1 C 5 - REDMOND, WA - 98052 Lic. #: WESTESF I36QF VICINITY MAP DETAIL NOT TO SCALE z WESTERN STATES FIRE PROTECTION COMPANY- OFFICES LOCATED ALBUQUERQUE /AUSTIN / DALLAS I DECATUP /DENVER r OJUJTH /HOUSTON /KANSAS CITY LAS VEGAS /MINNEAPOLIS 1 PHOENIX/ PORTLAND,/ RAPID CITY/ ST. PAIL (SALT LAKE CITY /SEATTLE Phone: 425-881-0100 Fax 425-881-3030 Parfumerie 446 Southcenter Mall Tukwila,WA 98188 FIRE SPRINKLER PLAN 7nr i, kvilia Fire ZIpD2e Mo, 51) ir 1.4. I • . I 4. TUKWILA RIE Y id M INGTON 4. t'•.; • SHEET INDEX RAL NOTES .t, SYMBOLS LEGEND SHEET \U vi3E HET TITLE FA -01 YST6 l\FO• vATIO\ FA -02 YPIQAL DETAILS - WRI\G A\D vOU\TI\G FA -03 SYSTE V FLOO PLA\ FA -04 SY 110\A CALCULATIO\S (GE \EAL), 'ISER, SITE, PLA !,I • :14 • ; WIRE DESIGNATION. SCHEDULE WIRE SCHEDULE AND CO\DUIT FILL CHART WIRE DESIGNATION • • „I..; , - , • sYmkiL DESCRIF?TION • NUMBER OF CONDUCTORS SIZE. TYPE ' , COLOR CODE • : i:4 D H,1H H •i:.4I11 P ; S ; 2S! A.'•14i; .1!.1 V:I.,;;;, l'•11 2v, ' I• :4'1! X,; T4:4i UD$1!! Uiik • III'''.; M4,:ti i' DATA LINE DOOR HOLDER HI', DEVICE14P0WER STROBE STROBEI:•CIRCUIT ANNUNCATDR i: SPEAKE SPEAKER:: I• REMOTEL.INDICATION i 4 LOW LEVEL , UNDER9ROUND UNDERGOUND ! t DOOR HOLDER BEAM DLTECTOR .. . • -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD 416 FPL/FPLR • RED (JACKET) POWER - 24VDC TWO 414 FPL/FPLR ' RED '(JACKET) - 24VDC TWO 416 FPL/FPLR RED (JACKET) , CIRCUIT - FEED TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) - RETURN TWISTED PAIR W/ SHIELD 412 FPL/FPLR RED (JACKET) TWISTED PAIR W/ SHIELD 416 . FPL/FPLR RED (JACKET) CIRCUIT - FEED TWISTED PAIR 414 , FPL/FPLR RED (JACKET) CIRCUIT - RETURN TWISTED PAIR • 414 FPL/FPLR : RED (JACKET) LIGHT TWO ' ' 418 FPL/FPLR , RED (JACKET) AUDIO , TWISTED PAIR W/ SHIELD 416 FPL/FPLR . RED (JACKET) DATA ' TWISTED PAIR RATED ' 418 FPL/FPLR . RED (JACKET) INITIATION TWISTED PAIR RATED 418 FPL/FPLR .RED (JACKET) ' .. POWER TWO ' 416 • FPL/FPLR ' RED (JACKET) POWER TWO . ' 414 FPL/FPLR , RED (JACKET) DESCRIPTION .. CONDUIT FILL CHART . ; • . , , . ! 1H, , ' 1 •1:'' 1t1.: : .•, ! ': :! . • ', ' . . • • 1 NO. CJ,F •1! TWO I CONDUIT I; l• , l• , , I ;II ! ' . . CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED ' .210 O.D. .0346 .. • : ., CONDUCTOR 300V . #18 AWG FPL TW CABLE .156 0.D. , .0191. . FILL . , . ., . • , • ' .: CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. , , , CONDUIT SIZE MAXIMUM FILL . ,.. 1/2" .12 SQUARE INCH 3/4" : .21 SQUARE INCH , ' • 1" .34 SQUARE INCH , 1-1/4" .60 SQUARE INCH 4 1-1/2" .82 SQUARE INCH • . 2" 1.34 SQUARE INCH ' , FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4 ' ' I SHIELDED WIRE TO BE !11 GROUND/ED , I : ! AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE ANDHTAPED AT END FOR SIEMENS SYSTE • I ! , DO NOT INSTALL ADDRESSA:LE INI IATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. ,, 1. NUMBERS ADJACENT TO DEVI4 SYMBk DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE 2. DETECTOR AND AUDIBLE CIRC 3. AUDIBLE/VISUAL CIRCUIT WIRII BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN 5 ELECTRIC CODE, NFPA 72, Lq 5. INSTALLATION MATERIALS (I.Ell STANDARD BOXES, FIBER 011 ARE NOT SUPPLIED BY SIEME 6. DETECTORS SHALL NOT BE M AIR STREAM OF AIR SUPPLY 1 ; SECO;NID DEVICE ON ADDRESSABLE LOOP 1. IT P,4 Gj $ I Y SHALL BE OBSERVED. ERVISED. NO PARALLEL ,ICT FORVIANCE WITH THE NATIONAL ALC01(S), AND/OR AUTHORITY HAVING JURISDICTION. CONDUI WIRE, FITTINGS, HANGERS, S :CAIBIIE, FITTINGS, AND ASSOCIATED EQUIPMENT) CERR'RUS DIVISION. b,NITED h DIRECT UTLETS PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN ITH, RE TYPE, QUANTITY AND COLOR ODE C, AND UNIQUELY MARKED FOR TURE 8. INSTALLING CONTRACTOR SHig LI REfLi DRAWINGS FOR "AS BUILT" P ,JOSE,S 9. FOR ADDITIONAL INSTALLATIO ILINSTR SHEETS AND/OR INSTALLATIO 1\1$T13 10. THE 120vac POWER ELECTRIC WOR MUST COMPLY WITH ARTICLE 25 ;AN SPECIFICALLY SECTION 1-5.2p'.2.:1N SOURCES. 120vac POWER SH L NOT DIRECT SUPERVISION OF FIRE 'A LArN 11. ALL HORN/STROBE AND STROBE DE OF 80" A.F.F. OR 6" BELOW ROPpE 12. ALL MANUAL PULL STATIONS • ACTIVATION DEVICE. ALL 13. ALL PANEL NUMBERS AND CI CUITS 14. ALL 120VAC GENERATOR. CIRCUITS ARE FJ),M DE PECT TO CONDUCTOR SIZE, & OR CABLE TRAY, ,\IDUCTORS SHALL BE PERMANENTLY, PENTIFICATION. N ONE SET OF ACCURATELY MARKED TIONS, REFER TO CATALOG CUT TIONS. SUPPLYING FIRE ALARIv SYSTEV PANELS 760 OF NFPA 70, N.E.C. AND NFPA 72, EFERENCE TO DEDICATED BRANCH POWER ILDE APPLIED TO FIRE ALARM PANEL WITHOUT iECHNICIAN. IES SHALL BE MOUNTED AT A HEIGHT CEILING, WHICHEVER IS LESS. E MOUNTED AT 48" A.F.F. TO THE ILL BE ON THE RECORD DRAWINGS SET. ''CATED CIRCUITS FROM THE EMERGENCY 15. PER NFPA 72 SECTION 5-3 .3AE CTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN -4 OF AL TRADES IS COMPLETE AND FINAL. EXCEPTION' WHERE ' BY 'THE' AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING COSTRUCTON. DETECTORS THAT HAVE BEEN1' INSTAL:0 PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED R REPL4CED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CON TINU • AND THEN FROM DEVICE TO • OTHER BACK BOXES OF DIF 17, ALL WIRING SHALL BE METER AND FREE OF SHORTS BETW, • FINAL EQUIPMENT TRIM. ' 111 S FRO FACP TO FIRST DEVICE ON A CIRCUIT EVJCE IITH0UT SPLICING IN PULL BOXES OR RENT.1 D, VER EN • 4 2 IED TO BE CONTINUOUS, FREE OF GROUND UCTORS AND OTHER CIRCUITS PRIOR TO . 18. ALL CABLES SHALL BE MAR !-. AS J DICATED ON FIRE ALARM' RISER WITH A PERMANENT LABEL AT ALL VICES UNCTION BOXES AND FACP. ! ., . 19. THE ELECTRICAL CON TRACTO SH414• LEAN ALL DIRT. AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THirIRI RM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEP" NSTA[. ATION. 1 I •P 1 ! 11 ,, • ; 20. DETECTORS MUST BE RATED RHITE ERATURE IN THE ENVIRONMENT IN WHICH . . IT IS LOCATED. 21. ALL WIRING BETWEEN FLOOR H4L, E LOCATED •IN CONDUIT. 22. NFPA 72'2007 6.4.2.2.2 ALL Ibl-YLES F CLASS A CIRCUITS USING • PHYSICAL CONDUCTORS (E.G.,METAL, OPTICAL. FIBER) SHALL BE. • INSTALLED SUCH THAT THE 0 11GOINGIAND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO TH IbONT.R L UNIT, RESPECTIVELY, ARE ; ROUTED SEPARATELY. THE 0L0iNd ND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE ON'111\I! E SAME CABLE ASSEMBLY (LE., • MULTI -CONDUCTOR CABLE), E CL SdPDE OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 Al ADEQUATE SEPARATION) BETW THIS SEPARATION IS REQUIRE CABLES FROM PHYSICAL DAM, SEPARATION TO PREVENT PH THE CABLE IS INSTALLED VER: CABLE IS INSTALLED !!, coAL' 6.4.2.2.2 IS TO PROVIDE HE OUTGOING AND RETURN CABLES'. ;ToEp ENSURE PROTECTION OF THE GE.HTHREC0MMENIED MINIMUM I!, 14CA'L D A MAGE IS 305 MM (1 FT) WHERE CALLY, ND 1.22 M (4 FT) WHERE THE• , . !;I11, •, QUANTITY 2 3 EX SYM B DE RIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FAC FIF,"i ALARM ,6( CO TROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FAR dFIR ALARM ' SOD -C' 1 66" A.F.F. RETE ANNUNCIATOR TO TOP RE (OTE BOOSTERPAD-3 T606" TAO.PF. F. , ER SUPPLY INRFACE MODULE HTRI-R VERIFY .111: RELAY . IN FIELD T !RFACE MODULE IN FIELD VERIFY IN HTRI-D SIEMENS 4S DEEP DLPL INPUT BP ! 1EX SIEMENS PROVIDED 11-n: SIEMENS PROVIDED SIEMENS 4S DEEP HC CO MO, TIROL POINT ;ULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZ RE ZO, ,OTE CONVENTIONAL HZM MODULE AR BEAM KE DETECTOR Llir* SIEMENS 4S DEEP VERIFY IN FIELD PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD (AD KE DETECTOR HFP-11 W/ SIEMENS RESSABLE-PHOTO) DB -11 BASE 4S DEEP W/ 10 RING CEILING DO DE T SMOKE CTOR AD2-P W/ SIEMENS DUCT HOUSING VERIFY TSM MODULE IN FIELD HE 44,J DETECTOR RESSABLE) HFPT-1 1 \AV SIEMENS DB -11 BASE 4S DEEP W/ 10 RING CEILING ALARM KER STROBE LING MOUNT) SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. FIR;1 ALARM SP:o KER STROBE (W LL MOUNT) SET -MC -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM FIR SP ALARM KER STROBE L MOUNT) SET -HMC -CW SIEMENS 4S DEEP BOX W/ 1-1/2" EXT. FIR. ST (C • st, ALARM BE LING MOUNT) CEILING ZR -MC -CW SIEMENS 4S BOX W/ 10 RING CEILING FIR ST OA) • ALARM BE MOUNT) ZR -MC -W SIEMN3 43 DOX W/ 10 RING 80" A.F.F. TO BOTTOM U.O.N. FIR SP' (c ! ALARM ik‘KER LING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. • FIR SR: (\f`f FIR ST A ! ALARM AKER MOUNT) SET -W SIEMENS 45 DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM MR ALARM BE ATHERPROOF) MU VI -VOLTAGE CONTROL RELAY I , SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR -201/C AIR PRODUCTS 4S BOX VERIFY IN FIELD Li MAONETIC DO 'R HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB13X 14 FIR TE ALARM I NAL CABINET F.B.O. e!! F.B.O. 4410114041204.1.4111144Mill•411.0111411112144111114 F.B.O. VERItiY IN FIELD TION BOX FBO. FB,O, '44 • TE VERIEY IN F ELD AF. 44 14 I ,• F,B. AB FL, E FINISHED N/A N/ U,O, WP FU OT ISHED BY RS N/A AP ICABLE N/A 1 N/A 0 Per The Atkithibd Letter N/A N/A N/A N/A Without Comments As Noted In Rcd 1 !len plans have been renevAd by 1 he i Mtge Hre , A PeOdhtion Bureau for confoYfrignce with current cite/ 9 standards. Acceptance is subject to errors and UN NO; SS OTHERWISE N/A WE DE THERPROOF N/A ICE RE AS: AD UILT OR CHANGE N/A GRE AS1' RE UILT VE N/A omissions which do not authorize violations of adopted stWaras and ordinances. 11-66 responsibility for theWA adequacy of design rests totally with the designer. AMtisions, deletions or revisloh§ to these drawings atter, this date will void this.acceteae and will require a 'N'm resubmittal of revised drawings for subsequent approval. i 4. ;7! ;J. 4.4 44.4 91 uJ uJ LU LU isr) CO C3• REV. BY: EGH - DESCRIPTION SHOP DRAWINGS . t 1_11 5:1 Q 05/20/20081 2<<<<< •,1•12r..! • /A complete0 signe Tukwla Fi6Acceptance is subjectVfletd test and inspectia* Tb a Tukwila Fire Prevention Bureau Dtait0 6/3/Oe ByN:/ 700 N/A BLU AS, NO BUILT ES TO CAD N/A N/A N/A N/A Fire Depd;nent Pre-test • Certifiote ilrusib4iresent& to the Inpetorrior to Testing oft nj, frO Alarm commenceni ntIcceptan Aina and DetOctiorl *terns. • Failure ofiest resuli in a Re -inspection )ee and termination of hetesting. !I H 11 TUKWILA FIRE DEPARTMM Please call: 575-440Z and give this job No.cf3'- r-gc,o/ and exact address for shut., iown or restoration approvaL TuwiaI 1-4 Copyright 2006 by Guardian Security Systems, Inc. All Rights Rerve rSALE: 1/8"1' ==1 F33 DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE:05/20/2008 BACIMUND PLAN PROVIDED BY: .J..013 NUMBER: SHEET A-01 • •;.;' 144, 11 :• II' THE DUCT SMOK6 !DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE NM NEPA 72. THE PREFERRED INSTALL LOCATION:OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT!WiDTHS FROM!iANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. •I; „ Is! BEND,OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. ; ,! I, 6-10 DUCT EQUIVALENT I, DIAMETERS ; • • . I j _ !;-11 TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING 1 4 1 , TO NEXT ADDRESSABLE DEVICE A H STOP IF LAST DEVICE 1 FROM XLS CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVIC DUCT DETECTOR LOCATION END OF LINE DEVICE (3.6K 1/4W) H11. SUPERVISED SWITCH 0 1.0 0 1, OUND •" HTRI-R STATUS LED 00 0 N.O. 0 0 COM N.C. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABEL SCALE (BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE DEVICE • !• 'I • ' ..1,1 TO NEXT ADDRESSABLE DEVICE •I !'1 NOTE 1' VOLTAGE MAX -- CURRENT MAX.— CONT. RES. MAX -- MAX. CABLE LENGTH— C (LINE TO LINE)— C (LINE TO SHIELD)— MAX. LINE SIZE— MIN. LINE SIZE— OUTLET SAMPLING TUBE INLET SAMPLIN TUBE 1.; AT LEAST SIX DUCT WIDTHS FROM BEND (Z) I I TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR • I I SCALE=NONE !!! MUSIC ),L AC POWER SOURffe!.li , . 01; COMBINE ALL SHIELDS Afl ISOLATE FROM GROUNDIN TO NEXT ADDRESSABLE DEVICE: STOP IF LAST DEVICE FROM XLS CONTROL PANEL bI PREVIOUS ADDRESSABLE BEY: 'END OF:ii DEVICEi1 (3.6K 11'' // / SUPERISEDL.LL./ // SWITCH GROUND 1!; RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT, (18 AWG) 0.02uF 0,04uF 14 AWG 18 AWG NOTE 2' ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. Io I 'TB1 s 000 ,$) 1 2 3 4 5 6 TB2 C P 0 0 65 461 4 3 2 1 TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP !ABEL SCALE 0 7 0 tr) 0 tr) @ @ HTRI-D STATUS LED CO 0 0 NUT CO 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-b ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 •Ii1;iiI ,GND N. 0 PAD -3 0 00 0 , • . INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 .-AUX 14- 1- 1 2+ 2- 2 NC C NO + - + + - , + - + - 24K n NAC -4 NAC -3 NAC -2 NAC -1 I ; I I 1 : USED ND, OF; INE DE 6K1/4 1 , UPEIRVI WITCH 3' FRONT VIEW NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE -71: DEVICE LOOP NOT USED REMOTE DEVICE LOOP 0 0 0 ( FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> FROM REMOTE POWER SUPPLY ('S' CABLE) 'ICE FROM FACP (VOICE CIRCUIT) ('V' CABLE) 1' 470 OHMS 11/1 EOL Prn TSM -1 0 11 ] • 0 0 OC TYPICAL AD2-P DUCT SMOKE DETECTOR - WRING DETAIL SCALE NONE (+) (-) STROBE SPEAKER (+) (--) (+) STROBE EARTH GROUND 1 -->.(4-)TO NE --4*(-) STOP (+) (-) STROBE SPEAKER (r) SPEAKER/STROBE AND STROBE WIRING LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 0 80" A.F.F. 4S DEEP BOX W/ 1 -1 /2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) SPEAKER/STROBE WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE ' 1 ! DEVICE LAST D TO NE DEVIC ; END 111 1 TO 'NE DEVIC END! I • OR LINE OR LINE NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERtlINI TEMPERATU,RE: +32' F 0 C TO 100' F (36 HUMIDITY: —9 % RELATIVE HUMI ITY, NON—CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (—) DATA IN (+) > •-t DEVICE IS USTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION KM DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE -1c- > (-) DATA OUT (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID HARD LID CEILING SPEAKER SUPPORT TIL.E. BRIDGE ti • 4" SQUARE DEEP BOX • / WITH 1-1/2" EXTENSION N CEILING MOUNTED SPEAKER/STROBE N, CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX MOUNTED ON CEILING FLEX \ • JUNCTI MOUNTED A CEILING S N BOX AINST PPORT • :SMKE DETECTOR -- SMOKE DETECTOR MOUNTING SCALE:NONE 00 0 0 1 TO NEXT DEVICE' CADDY BAR SUSPENDED .';• ILLUMINATED CEILING DO \OT INSTA_L ADDRESSABLE 0\ DEVICES U\TI_ •PRPROGRAMMED W • DEVICES ADDRESS. TIAT1 ri ht .2006 b Guardian Securit S stems, Inc. All R hts Resery RELEASE/REVISIONS >- m - LU z -t< DESCRIPTION SHOP DRAWINGS lu i-- 05/20/20081 6ALE: 1/8"=l' RING AND _J DRAWN BY: • E.HAMERSKI DESIGNED I BY: R.VEZZANI DATE:05/20/2008 } BACIROUND PLAN PROVIDED BY: \.2..op NUMBER: SHEET A-0 I , 1, 1 FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED ;BY MECHANICAL CONTRACTOR, WIRED, BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. REV. BY: EGH DESCRIPTION - SHOP DRAWINGS 1. I' . . -1 - DATE - 05/20/2008 12 <- <<<< 1 . -. • :,. E1F1.hr. fr. , : 2 1.! 1 2S, Alitill, ,, .. ...... ..... . - - '1 r Adr. ---,1 , ir 0 .,1 ., , , . . . C I i • , r D,I .: ,r, 1 , • .t i 4 4.1Z, 1 : 1 1 t -, NAN — ....,... ,.. .... i , f i IP 1 .7.' I n'-- , ' , ...1 . I ' 1 .LT ... ,- . ;------ ..... I ,,.........,..-1,a Al , I /\ AI ...,• . if \ o. -I—if:ill) FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATION SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED ;BY MECHANICAL CONTRACTOR, WIRED, BY ELECTRICAL CONTRACTOR, SIEMENS HTRI—D ADDRESSABLE INPUT WITH HOOD VENILLATOR FIRE SUPPRESION SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT. REV. BY: EGH DESCRIPTION - SHOP DRAWINGS DATE - 05/20/2008 12 <- <<<< DO NOT NS" ---ALL ADDRESSABLE INTOA DEVICES J\TIL PREPROGRAMMED W DEVICES ADDRESS. DESIGNED BY: R.VEZZANF BACKROUND PLAN PROVIDED BY V.OB NUMBER: SHEET 1'1 111 Copyright 2006 by Guardian Security Systems, Inc. All Rights ResOrve SYSTEM CAL LATIONS PARFUMERIE SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations PARFUMERIE FACP ADD ONS Current Load: Devid0 Type Standby: Alarm: Total Total Curretit Load: DeviCkType Standby: Alarm: Tc, C A M ER A 01-1-1 ER H [VI A TER N] TR ASH KOS 1700-FLOCKFR EX:ST:NG F001! COI< -f1 TANLI- MaiOYsteml,Board SE14C 150D L SET -MC 30qD SET'(' 76qD SEIMQ 17,4CD §ttILIMC-C115CD SE-0-imc,c0135CD SE*IMC-C@185CD ZR -F 15CO__ ZR- 30C 0.064 0.098 0.175 0.318 0.318 0.445 0.064 0.196 0.350 Amps 0.0022 0.0635 0.009600 0.001600 Total 0.0022 0.0635 0.0096 Amps 0.0023 0.064 0.021 0.0035 Total 0.0731 0.064 0.098 0.0015 y Current Load: .:Current Load: 0.0731 For 24 Hours = Amp -hours For 5 Minutes= Amp -hours Stan. by CurrOnt Load: AlarCurren Load: 1ir 0.03 Amps For 24 Hours = 0.720 Amp -hours 25% Derating= Amp -hours 0.704 Amps For 5 Minutes= 0.059 Amp -hours Total System Current Load: Amp -hours 25% Derating= 0.974 Amp -hours 12VDC Amp -hours 0 a. Amp -hours Batt ry. Pair to be Used: Amp -hours PROJECT: Panel: Date: ATTERY SIZ I Notification Appliance C WESTFIELD SOUTHCENTER MALL PARFUMERIE May 29, 2008 ENT TOTAL= 849 CIRCUIT: QTY 1 27 CALH- ORNIIA RiZZA KITCHEN ,4> " v, DEVICES= Device Type Alarm Current - SET -MC @15CD SET -MC @30CD SET -MC @75CD SET -MC @110CD SET-HMC.C@115CD SET-HMC-C@177CD SET -HMC @135CD SET -HMC @185CD Z-MC@15CD Z-MC@30CD SET-MC-CW@110CD 7 64 98 175 233 Alarm Total 64 196 525 0 Wire Size Voltage at EOL Circuit Total 318 445 318 445 64 98 233 TOTAL m A= Total Wire Resistance ( R ) ( WL * 2 )* (R/ft) Total Device Load, Amps (I) (Total Cct Load) Voltage Drop ( E) (E= I* R) EOL Voltage (20.4 - E) 19.6710486 SUITE 446 WESTFIELD SOUTHCENTER MALL SCALE 1132'4 PROJECT: Panel: Date: CIRCUIT: QTY 3 0 0 0 Notification Appliance C cut etail WESTFIELD SOUTHCENTER MALL PARFUMERIE May 29, 2008 SPEAKER CIRCUIT Device Type 70.7V 1/8 Alarm Current Alarm Total 1.8 5.4 WireSize Wire gth ,Voltage at EOL Circuit Total 2S,2V 2S,2V 2S,2V Total Wire Resistance ( R ) 2.92 ( WL * 2 )*(R/ft) Total Device Load, Amps (I) 0.01 (Total Cct Load) Voltage Drop ( E ) 0.02 (E= I * R) EOL Voltage 20.38 (20.4 - E) FA -BOX FACP EXEX DEVICES= TOTAL m A= 5.4 RISER DIAGRAM DRAWN BY: E.HAMERSKI DESIGNED BY: R.VEZZANI DATE: 05/20/2008 BACROLJND; PLAN PROVIDEDi:BY: NUMBER: VOLTAGE DROP LCULATION SHEET ri ht 2006 b Guardian Securit S stems, Inc. All R' hts Reserved