FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Clarks
466 Southcenter Mall
Permit No.: 08-S-326
Date: June 13, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80'•for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 '/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to any sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
3
COSCO FIRE PROTECTION, INC.
15000 WOODINVILLE REDMOND ROAD NE #B800
WOODINVILLE,WA 98072-4502
HYDRAULIC CALCULATIONS
FOR
Clarks
466 Southcenter Mall, Suite #1010
Tukwila, Wa. 98188-2823
FILE NUMBER: 25KS - 7936
DATE: JUN 12, 2008
-DESIGN DATA -
OCCUPANCY CLASSIFICATION: Ordinary Group II
DENSITY: 0.20 gpm/1500 sq. ft.
AREA OF APPLICATION: 1545 sq. ft.
COVERAGE PER SPRINKLER: 130 sq. ft. Max.
NUMBER OF SPRINKLERS CALCULATED: 17 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 466.3 gpm
TOTAL WATER REQUIRED (including hose): 900.0 gpm
FLOW AND PRESSURE (@ BOR): 649.9 gpm @ 89.9 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: Cosco Fire Protection, Inc.
DESIGN/LAYOUT BY: Justin Johnson
AUTHORITY HAVING JURISDICTION: Tukwila Fire Department
CONTRACTOR CERTIFICATION NUMBER: COSCOFP11OMN
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830)
HRS SYSTEMS, INC.
TUCKER, GA 30084
TUCKER, GA 30084
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
WATER SUPPLY DATA
SOURCE
NODE
TAG
SOURCE
STATIC
PRESS.
(PSI)
140.0
RESID.
PRESS.
(PSI)
20.0
AGGREGATE FLOW ANALYSIS:
FLOW
(GPM)
10900.0
TOTAL FLOW AT SOURCE
TOTAL HOSE STREAM ALLOWANCE AT SOURCE
OTHER HOSE STREAM ALLOWANCES
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS
NODE ANALYSIS DATA
NODE TAG ELEVATION
(FT)
AVAIL.
PRESS.
(PSI)
138.8
TOTAL
@ DEMAND
(GPM)
900.0 GPM
250.0 GPM
183.6 GPM
466.4 GPM
REQ'D
PRESS.
(PSI)
900.0 97.6
NODE TYPE PRESSURE DISCHARGE
(PSI) (GPM)
S1 12.0 K= 5.60 26.4
1 14.5 - - - - 32.9
S2 12.0 K= 5.60 25.8
2 14.5 - - - - 33.3
S3 13.5 K= 5.60 22.4
3 14.5 - - - - 28.1
S4 13.0 K= 5.60 21.6
4 14.5 - - - - 28.2
S5 13.0 K= 5.60 22.3
5 14.5 - - - - 29.2
S6 13.0 K= 5.60 23.8
6 14.5 - - - - 31.2
S7 12.0 K= 5.60 26.9
7 14.5 - - - - 33.1
S8 12.0 K= 5.60 26.2
8 14.5 - - - - 33.6
S9 13.5 K= 5.60 22.4
9 14.5 - - - - 28.2
S10 13.0 K= 5.60 22.2
10 14.5 - - - - 28.3
Sil 13.0 K= 5.60 23.0
11 14.5 - - - - 29.3
S12 13.0 K= 5.60 24.6
12 14.5 - - - - 31.4
S13 12.0 K= 5.60 27.6
13 14.5 - - - - 35.4
S14 13.5 K= 5.60 22.4
14 14.5 - - - - 28.7
S15 13.0 K= 5.60 22.5
15 14.5 - - - - 28.8
S16 13.0 K= 5.60 23.3
16 14.5 - - - - 29.8
S17 13.0 K= 5.60 25.0
17 14.5 - - - - 31.9
28.8
28.4
26.5
26.0
26.4
27.3
29.1
28.6
26.5
26.4
26.9
27.8
29.4
26.5
26.6
27.0
28.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
M1 14.5 HOSE STREAM 35.1 183.6
M2 14.5 - - - - 35.3
M3 14.5 35.9
M4 14.0 71.5
TOR 13.7 81.3
BOR 2.0 89.9
M5 2.0 90.2
BFO 2.0 90.3
BFI 2.0 94.8
UG1 1.2 - - - - 95.1 - - -
SOURCE -4.0 SOURCE 97.6 650.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -28.8 1.049 PL 25.58 PF 7.6
S1 12.0 5.6 26.4 28.8 10.7 120 FTG 2E PE -1.1
1 14.5 0.0 32.9 0.0 0.255 TL 29.58 PV
Pipe: 2 -28.4 1.049 PL 27.58 PF 8.6
S2 12.0 5.6 25.8 28.4 10.6 120 FTG ET PE -1.1
2 14.5 0.0 33.3 0.0 0.250 TL 34.58 PV
Pipe: 3 -26.5 1.049 PL 24.00 PF 6.1
S3 13.5 5.6 22.4 26.5 9.8 120 FTG 2E PE -0.4
3 14.5 0.0 28.1 0.0 0.219 TL 28.00 PV
Pipe: 4 -26.0 1.049 PL 27.62 PF 7.3
S4 13.0 5.6 21.6 26.0 9.7 120 FTG ET PE -0.6
4 14.5 0.0 28.2 0.0 0.211 TL 34.62 PV
Pipe: 5 -26.4 1.049 PL 27.62 PF 7.5
S5 13.0 5.6 22.3 26.4 9.8 120 FTG ET PE -0.6
5 14.5 0.0 29.2 0.0 0.218 TL 34.62 PV
Pipe: 6 -27.3 1.049 PL 27.62 PF 8.0
S6 13.0 5.6 23.8 27.3 10.2 120 FTG ET PE -0.6
6 14.5 0.0 31.2 0.0 0.232 TL 34.62 PV
Pipe: 7 -29.1 1.049 PL 24.00 PF 7.3
S7 12.0 5.6 26.9 29.1 10.8 120 FTG 2E PE -1.1
7 14.5 0.0 33.1 0.0 0.260 TL 28.00 PV
Pipe: 8 -28.6 1.049 PL 26.50 PF 8.5
S8 12.0 5.6 26.2 28.6 10.6 120 FTG ET PE -1.1
8 14.5 0.0 33.6 0.0 0.253 TL 33.50 PV
Pipe: 9 -26.5 1.049 PL 24.00 PF 6.1
S9 13.5 5.6 22.4 26.5 9.8 120 FTG 2E PE -0.4
9 14.5 0.0 28.2 0.0 0.219 TL 28.00 PV
Pipe: 10 -26.4 1.049 PL 24.00 PF 6.7
S10 13.0 5.6 22.2 26.4 9.8 120 FTG ET PE -0.6
10 14.5 0.0 28.3 0.0 0.218 TL 31.00 PV
Pipe: 11 -26.9 1.049 PL 24.00 PF 7.0
S11 13.0 5.6 23.0 26.9 10.0 120 FTG ET PE -0.6
11 14.5 0.0 29.3 0.0 0.224 TL 31.00 PV
Pipe: 12 -27.8 1.049 PL 24.00 PF 7.4
S12 13.0 5.6 24.6 27.8 10.3 120 FTG ET PE -0.6
12 14.5 0.0 31.4 0.0 0.239 TL 31.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -29.4 1.049 PL 26.50 PF 8.9
S13 12.0 5.6 27.6 29.4 10.9 120 FTG ET PE -1.1
13 14.5 0.0 35.4 0.0 0.266 TL 33.50 PV
Pipe: 14 -26.5 1.049 PL 27.00 PF 6.8
S14 13.5 5.6 22.4 26.5 9.8 120 FTG 2E PE -0.4
14 14.5 0.0 28.7 0.0 0.219 TL 31.00 PV
Pipe: 15 -26.6 1.049 PL 24.50 PF 6.9
S15 13.0 5.6 22.5 26.6 9.9 120 FTG ET PE -0.6
15 14.5 0.0 28.8 0.0 0.220 TL 31.50 PV
Pipe: 16 -27.0 1.049 PL 24.50 PF 7.2
S16 13.0 5.6 23.3 27.0 10.0 120 FTG ET PE -0.6
16 14.5 0.0 29.8 0.0 0.227 TL 31.50 PV
Pipe: 17 -28.0 1.049 PL 24.50 PF 7.6
S17 13.0 5.6 25.0 28.0 10.4 120 FTG ET PE -0.6
17 14.5 0.0 31.9 0.0 0.242 TL 31.50 PV
Pipe: 18 -28.8 1.610 PL 14.00 PF 0.4
1 14.5 0.0 32.9 0.0 4.5 120 FTG ---- PE 0.0
2 14.5 0.0 33.3 0.0 0.032 TL 14.00 PV
Pipe: 19 -57.2 1.610 PL 7.58 PF 1.8
2 14.5 0.0 33.3 0.0 9.0 120 FTG T PE 0.0
M1 14.5 H.S. 35.1 183.6 0.113 TL 15.58 PV
Pipe: 20 -26.5 1.610 PL 4.35 PF 0.1
3 14.5 0.0 28.1 0.0 4.2 120 FTG ---- PE 0.0
4 14.5 0.0 28.2 0.0 0.027 TL 4.35 PV
Pipe: 21 -52.5 1.610 PL 10.00 PF 1.0
4 14.5 0.0 28.2 0.0 8.3 120 FTG ---- PE 0.0
5 14.5 0.0 29.2 0.0 0.096 TL 10.00 PV
Pipe: 22 -78.9 1.610 PL 10.00 PF 2.0
5 14.5 0.0 29.2 0.0 12.4 120 FTG ---- PE 0.0
6 14.5 0.0 31.2 0.0 0.205 TL 10.00 PV
Pipe: 23 -106.3 1.610 PL 2.88 PF 3.9
6 14.5 0.0 31.2 0.0 16.8 120 FTG T PE 0.0
M1 14.5 H.S. 35.1 183.6 0.355 TL 10.88 PV
Pipe: 24 -29.1 1.610 PL 14.00 PF 0.5
7 14.5 0.0 33.1 0.0 4.6 120 FTG ---- PE 0.0
8 14.5 0.0 33.6 0.0 0.032 TL 14.00 PV
Pipe: 25 -57.7 1.610 PL 7.58 PF 1.8
8 14.5 0.0 33.6 0.0 9.1 120 FTG T PE 0.0
M2 14.5 0.0 35.3 0.0 0.115 TL 15.58 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 26 -26.5 1.610 PL 5.73 PF 0.2
9 14.5 0.0 28.2 0.0 4.2 120 FTG ---- PE 0.0
10 14.5 0.0 28.3 0.0 0.027 TL 5.73 PV
Pipe: 27 -52.9 1.610 PL 10.00 PF 1.0
10 14.5 0.0 28.3 0.0 8.3 120 FTG ---- PE 0.0
11 14.5 0.0 29.3 0.0 0.098 TL 10.00 PV
Pipe: 28 -79.8 1.610 PL 10.00 PF 2.1
11 14.5 0.0 29.3 0.0 12.6 120 FTG ---- PE 0.0
12 14.5 0.0 31.4 0.0 0.209 TL 10.00 PV
Pipe: 29 -107.6 1.610 PL 2.88 PF 4.0
12 14.5 0.0 31.4 0.0 17.0 120 FTG T PE 0.0
M2 14.5 0.0 35.3 0.0 0.363 TL 10.88 PV
Pipe: 30 -29.4 1.610 PL 7.58 PF 0.5
13 14.5 0.0 35.4 0.0 4.6 120 FTG T PE 0.0
M3 14.5 0.0 35.9 0.0 0.033 TL 15.58 PV
Pipe: 31 -26.5 1.610 PL 4.10 PF 0.1
14 14.5 0.0 28.7 0.0 4.2 120 FTG ---- PE 0.0
15 14.5 0.0 28.8 0.0 0.027 TL 4.10 PV
Pipe: 32 -53.1 1.610 PL 10.00 PF 1.0
15 14.5 0.0 28.8 0.0 8.4 120 FTG ---- PE 0.0
16 14.5 0.0 29.8 0.0 0.098 TL 10.00 PV
Pipe: 33 -80.1 1.610 PL 10.00 PF 2.1
16 14.5 0.0 29.8 0.0 12.6 120 FTG ---- PE 0.0
17 14.5 0.0 31.9 0.0 0.211 TL 10.00 PV
Pipe: 34 -108.1 1.610 PL 2.88 PF 4.0
17 14.5 0.0 31.9 0.0 17.0 120 FTG T PE 0.0
M3 14.5 0.0 35.9 0.0 0.366 TL 10.88 PV
Pipe: 35 -347.1 4.260 PL 8.92 PF 0.2
M1 14.5 H.S. 35.1 183.6 7.8 120 FTG ---- PE 0.0
M2 14.5 0.0 35.3 0.0 0.028 TL 8.92 PV
Pipe: 36 -512.4 4.260 PL 10.00 PF 0.6
M2 14.5 0.0 35.3 0.0 11.5 120 FTG ---- PE 0.0
M3 14.5 0.0 35.9 0.0 0.057 TL 10.00 PV
Pipe: 37 -649.9 4.260 PL 267.50 PF 35.4
M3 14.5 0.0 35.9 0.0 14.6 120 FTG 8ET PE 0.2
M4 14.0 0.0 71.5 0.0 0.089 TL 399.40 PV
Pipe: 38 -649.9 4.260 PL 69.33 PF 9.6
M4 14.0 0.0 71.5 0.0 14.6 120 FTG 3E PE 0.1
TOR 13.7 0.0 81.3 0.0 0.089 TL 108.93 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 39 -649.9 4.260 PL 11.67 PF 3.6
TOR 13.7 0.0 81.3 0.0 14.6 120 FTG C PE 5.1
BOR 2.0 0.0 89.9 0.0 0.089 TL 40.67 PV
Pipe: 40 -649.9 8.249 PL 21.25 PF 0.2
BOR 2.0 0.0 89.9 0.0 3.9 120 FTG 2E PE 0.0
M5 2.0 0.0 90.2 0.0 0.004 TL 61.25 PV
Pipe: 41 -649.9 10.374 PL 14.75 PF 0.1
M5 2.0 0.0 90.2 0.0 2.5 120 FTG 3E PE 0.0
BFO 2.0 0.0 90.3 0.0 0.001 TL 88.55 PV
Pipe: 42 FIXED PRESSURE LOSS DEVICE
BFI 2.0 0.0 94.8 0.0 4.5 psi, 649.9 gpm
BFO 2.0 0.0 90.3 0.0
Pipe: 43 -649.9 10.374 PL 2.83 PF 0.0
BFI 2.0 0.0 94.8 0.0 2.5 120 FTG E PE 0.4
UG1 1.2 0.0 95.1 0.0 0.001 TL 27.43 PV
Pipe: 44 -650.0 10.275 PL 85.00 PF 0.2
UG1 1.2 0.0 95.1 0.0 2.5 140 FTG 2ETG PE 2.2
SOURCE -4.0 SRCE 97.6 (N/A) 0.001 TL 225.80 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 7.9 computer program
under license no. 4903012830 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.167 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 17.0 ft/sec at pipe 34.
(4) PIPE FITTINGS TABLE
Pipe Table Name: MOST.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PAGE: A MATERIAL: SCH.40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D F
Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11
H Q I S U V W
22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT
1.049 2.00 5.00 2.00 5.00 0.00 0.00 0.00 0.00 1.00
0.50 0.30 1.00 6.00 5.00 9.00 0.00
1.610 4.00 8.00 2.00 9.00 0.00 0.00 0.00 0.00 2.00
1.00 0.50 1.00 8.00 6.00 12.00 0.00
PAGE: B MATERIAL: SCH.10 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D F
Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11
4.260
8.249
10.374
H Q I S U V W
22/Ell 11gEll Couplg FM90E1 FM45E1 FMTee FMRunT
13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60
3.30 1.60 1.30 18.40 11.90 31.60 0.00
20.00 38.90 14.50 50.00 13.30 4.40 45.60 0.00 10.00
5.00 2.50 1.10 24.50 14.50 43.40 0.00
24.60 56.00 17.90 61.60 21.30 5.60 0.00 0.00 12.30
6.20 3.10 1.10 29.10 16.80 56.00 0.00
PAGE: D MATERIAL: DI -52 HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D F
Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11
10.275
H Q
22/Ell 11gE11
31.30 71.10 22.70 78.20 27.00 7.10 0.00 0.00 15.60
7.80 3.90
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
0
O
rn
O
1-1
0
G4
a.
0
0
0
140.00 psi Resid
E a) a)
a E > >
rn a�
a) o U U
• • a)o
• o • >. '0
m o • o
0) m m a E
C1 R,O q
a°�' co '0 -N u v
ro r ¢ W
H 'D 0 Un
•
rtl o CS •
FICcO
N
O
0 0 0 0 0 0
W d' N 0 CO 10
H r-1 H H
(..7g0w axwu)u1:4 41 --acn-.-1--
O
0
0
0
O
0
M
m
0
_ 0
N
CU
N
O O.11
r-1
O O i
N
0
a
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
WATER SUPPLY CURVE
144+
0
I\
132+ \
\
\
\
120+ \
\
\
\
108+ \
\
\
X \
P 96+ \
R I \
E I \
s I \
S 84+ \
U I \
R I \
E I \
72+ \
( I
P I \
S 1 \
I 60+
\
1 \
\
48+
i \
\
\
36+
\
\
\
24+ LEGEND
1 X = Required Water Supply
97.60 psi @ 900.0 gpm
12+
0 = Available Water Supply
138.81 psi @ 900.0 gpm
<-20.0 psi @ 10900 gpm
Flow Test Point
0++-+ -+ -+ + + + + + +
32004800 6400 8000 9600 11200 12800 14400 16000
FLOW (GPM)
GUARDIAN SECURITY
Customer LIFE AND
CLARKS
466 SOUTHCENTER MALL
'KWILA, WA 98188
Project CLARKS
Project # 54499
PROPERTY PROTECTION
List of Materials
Vendor
Guardian Security Systems Inc
1743 1st Ave. South
Seattle, WA 98134
Phone #: (206)622-6545
Fax #: (206)628-4990
Type of Equipment
FIRE ALARM
Date: MAY,28,08
Item Qty. Manuf.
Model
Description
Unit Pri Total Price'
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)
14)
15)
16)
17)
18)
19)
20)
21)
22)
23)
24)
25)
26)
27)
28)
29)
30)
31)
32)
33)
34)
35)
36)
37)
38)
39)
40)
41)
42)
43)
44)
45)
46)
47)
48)
49)
50)
Siemens PAD -3
Siemens AD2-P
Siemens HTRI-D
Siemens HTRI-R
Siemens SET CW,W
Siemens SET W
Siemens ZR-MC-W,W
Power Supply for Strobes with Standby**
Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1
Supervised Addressable Input Module
Supervised Addressable Output Relay Module
Interior Audible Speaker Annunciator
Interior Audible Speaker Annunciator
Interior Visual Strobe Annunciator
Conduit Systems: All smoke removal and detection and control devices in
an approved metallic raceway and all devices in conduit per Standard
fl�l s c dfl
LD
3'-9"
IYa'' x 1 "
1, \ADACAP
1'
4-31¢
o
2'-4/2"..
0-6
O
8- '3
1'
1'
1-7
1
O
3-
a
CO
'-C.2N
61-0"
4'-O"
I0
-0"
10
0"
x 1"
f 1' rADA CAP
b 1-5
IY2' x I'
/ADA CAP
ll
tet
ex--
I/2' x �,
rADA CAP
1�
1'
Flex
c
1
0/
CD
CL
8'
II
2'-0"
cp
I
'-" CU
10'-0"
4
-4/2"
lex
1'
3-4
3-5
-8i2
#71t
VP. F \f L
1'
3-5
0
1'
3-5
cu
1'
2-3
7f
2-3 /
1'
-9
5
-10"
1' N
2-E
�26
0
\f
Flex
i�x I"
ADA CAP
lex
4'-6"
1'
1'
P4,
4-11
`1y"x 1"
ADA CAF
D
6'- I /2"
WILKINS 10" 350 DAG
Vertical Backflow Preventer
E
(n
2x 10" Vlctaullc #750
Butterfly Valve
F/c
4" RellableModel "G"
Riser Check Valve
10" Flange AiliE
4. @ I '-2" AFF
/ \ FF c, 0'-0"
10" D.I.
\ @
-41-0"±
System T2 Riser Assembly Detail
N.T.S.
00 -
(TUIKWILLA UTILITIES:)
CONSTRUCTION NOTES
GENERAL NOTESf
I) r'iPE:
71READED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) rITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
VISH
'READED: STAR D.I.
3) ;.ROOVED COUPLINGS:
.AR RIGID C-4 UNLESS MARKED WITH AN "F",
b'11ICH ARE TO BE STAR FLEXIBLE C-3 LW -
('RANGE PAINT FINISH
4) HANGER MATERIAL:
ALL HANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
Static Pressure = 140 psi
Re=dual Pressure = 20 psi
Fire Flow = 1 0,900 gpm
Static Pressure = 140 psi
Residual Pressure = 20 psi
Fire Flow = gpm
SYMBOL LEGEND:)
= NEW RECESSED PENDANT ON DROP
®= NEW CONCEALED PENDANT ON DROP
EXISTING SPRINKLER PIPE TO REMAIN
NEW SPRINKLER PIPING
I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP II.
ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX.
2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN.
3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY
OTHER.
4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER.
5) OWNER 15 RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
7) OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(5) IS BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE
CONDITION, PERFORMANCE OR. CURRENT CODE COMPLIANCE OF THE EXISTING
SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM
ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE
PROTECTION.
G)
SEE PLAN
FOR LENGTH
NEW BRANCH LINE
"FLEXHEAD" FLEXIBLE
DROP CORRUGATED
STAINLESS STEEL
BRAIDED HOSE
CEILING
Z
'-
gz
Q W
W
Wce
"'O
LL
ADJUSTABLE HUB
MOUNTING BRACKET
(BTYPICAL
ARMOVER TO NEW SPRINKLER HEAD
�
N.T.S.
TOLCO FIG. 25 SURGE RESTRAINER
TYPE 1 - FOR I " AND IY4' PIPE AND HANGER
TYPE 2 - FOR 172" AND 2" PIPE AND HANGER
TOLCO MG. 25 IS DESIGNED TO BE USED ONLY
WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE A5
IT OCCURS DURING SPRINKLER HEAD ACTIVATION
OR SEISMIC ACTIVITY
SYMBOL =
FIGURE 25 SURGE RESTRAINER
cht OO FOR STEEL OR CPVC PLASTIC PIPE
3/8' x aY2' LAG SCREW FOR WOOD
3/8' x 24" KWIK BOLT FOR CONCRETE —\
I" x Y4' TEK FOR BARJOIST OR STEEL BEAM
45° MIN.
ur
ARGCO OFFSET
EYESOCKET BRKT.
WHERE LENGTH 1
EXCEEDS 1'-10"
SYMBOL = 6
LINE RESTRAINT DETAIL
NALL THREAD ROD
I'- 10" MAX. PER SINGLE.
OTHERWISE ASSEMBLY
REQD. BOTH SIDES
-"------...„HANGER RING
(UP TO2"PIPE)
SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE
UL
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3" METAL DECK
3/8" ANCHOR W/20# TORQUE:
TENSION=395#, SHEAR=750#*
1/2" ANCHOR W/40# TORQUE:
TENSION=440#, SHEAR=750#*
'SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR THRU THREADS
1/4" MIN
I re pa to- Roo ri is: Fro
ti°4151:1!
or
—
ROD COUPLING
THREADED ROD
PIPE
SIZE
1 I/4"
1 1/2"
2"
2 1/2"
3"
4"
6"
8"
ROD BOLT IMBED
DIA. LGTH DEPTH
3/8" 33 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007
COSCO STANDARD HANGER
13 MDL
0
VVthoi tCornn:�ntt.
As 1J0-1sci In F;•: -,,,d
Per The
e
!hese plans have bean r: ',.'I:::, , . by j 3
Prevention hire I f:.;r .:�, :...., •
standards. Aco,,, l.ar,,::. «.... . t:,Cifrais u;
omissions vin' , 3'. ,;int
t'
standards and o::..i;.:; ..,.:
adequacy of d :, ,, s, r ::: • ',;r, Irk; c>
Additions,i .
dale:bo , of ;, .... :these : ilii sr
this date will void tl iF; ;:,:c; . ,..,,;.:: .
rid will r>`:�r.,,re: r.
resubmittal of revised di ,‘,-iri-. o ;, i ub:..eKquent approval.
Final accLp .r,cc;> i, sr.::`.: ect field test and inspection by
The Tukwila Fire i i' ri;,.,...,;1 Llureau.
:Date: 60 /3-03 By:
-11r1 stamps must be
inspected before pipz1 is
hung, . -.1: paint piping
prior t0 )
approval.
TUKWILA FIRE DEPARTMENT
Pease call: 575-440Z
and give this job
140.
at „J exact address for shut
clown or restoration approval.
z
0
>-
LO
W
Q
DESCRIPTION
0
z
z
ei
'°
24
JOB NO.
25KS - 7958
SHEET NO.
FP 1
a
TOTAL SPRINKLERS = 30
THIS SHEET
d
i
i -
o
'Q
0
iL)
W,
Fy
az,:
White
Chrome
9F,,
mz
_im
2
m
2
L
U
Q
,,,
ae
-ri
ui
NPT
APPROVALS BY:
W
1
0
z
0
N
SPRINKLER HEAD LEGEND :
Reliable Model G4A Concealed Pendant
Reliable Model F1 FR Recessed Pendant
0in-
re4 J
�Q
r „IC)
(�a
isid O W
C4 L‹
all inV/(0)
v r°'i Z
Q
0
U
••• • w
•••• f-
••••
••••0-
••••
•••• i
••••
W
0
u -
LL.
0
Z
a
License No:
10910 117TH Place N.E.
COSCOFP110NM
1"1-
c0 c
N
X
0
•
c0
170 -
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
PAID ?AIC?
d JN13 2008
Tukwila Fire
70-2a°66
0
-F—
N
0
U
V)
0
E
0
r
..
g O
z
U
0
N
it
m
a
a_d
z>
m
0 00
V) a
b
N .0
N
DRAWING TITLE
Clarks: Sprinkler Piping Plan
DATE: June, 2008
SCALE : As Noted
DRAWN BY: Justin Johnson
JOB NO.
25KS - 7958
SHEET NO.
FP 1
a
I ,545ft
IlydrauliCaly Calculated
Most ReFnote Area
(.)
0
C7 til
t
C
�pp
; L
0
c
if
�r
'1
(1
•
0
l
Py
CD
5-77.1
71
0
5
4" x 61 '-0"
@ 1 4'-6" AFF
T
WILKINS 10" 350 DAG
Vertical Backflow Preventer
4" x 1 6'-3"
E
Q)
2x 1 0" Vlctaullc #750
Butterfly Valve
m
2
'O»
'QFF
4" ReliableModel "G"
Riser Check Valve
I O" Flange
4. @ 11-2" AFF
\ FF @ 0'-0"
I O" D.I.
C@ -4'-O"±
System T2 Riser Assembly Detail
N.T.S.
-00
@ 1 5'-6" AFF
4"x5"-
'. @ 131-6"
4. @ 2'-0" AFF
West Sprinkler
Riser Room ,no
10" x 8..�I
Grooved RC
10"
@ 2'-0" ALT
T
S
4 7, ---NRS GATE VALVE
z
0
ti
W
w
1-
DESCRIPTION
O
z
171mUmq
so
N
r
Sit
TOTAL SPRINKLERS
THIS SHEET
\„..
0
Lo
vO
S17
If
,
tui
Ez
White
Chrome
C1_
H_
Zz
iu:
Brass
Chrome
V
W
O
tO
`O
LO
NPT
'( 1.'1 rl
1,1
4
`WcY'•:Y 1:f
"t.0 �A�' �
4.
APPROVALS BY:
ti. W
0
N
N
47713 %Y
7
()
Y
{.—i73.
■'
�pp
; L
0
c
if
�r
'1
(1
•
0
l
Py
CD
5-77.1
71
0
5
4" x 61 '-0"
@ 1 4'-6" AFF
T
WILKINS 10" 350 DAG
Vertical Backflow Preventer
4" x 1 6'-3"
E
Q)
2x 1 0" Vlctaullc #750
Butterfly Valve
m
2
'O»
'QFF
4" ReliableModel "G"
Riser Check Valve
I O" Flange
4. @ 11-2" AFF
\ FF @ 0'-0"
I O" D.I.
C@ -4'-O"±
System T2 Riser Assembly Detail
N.T.S.
-00
@ 1 5'-6" AFF
4"x5"-
'. @ 131-6"
4. @ 2'-0" AFF
West Sprinkler
Riser Room ,no
10" x 8..�I
Grooved RC
10"
@ 2'-0" ALT
T
S
4 7, ---NRS GATE VALVE
z
0
ti
W
w
1-
DESCRIPTION
O
z
171mUmq
so
N
TOTAL SPRINKLERS
THIS SHEET
TEMP.
0
Lo
vO
1550
tui
Ez
White
Chrome
C1_
H_
Zz
iu:
Brass
Chrome
V
W
O
tO
`O
LO
NPT
NN
APPROVALS BY:
ti. W
0
N
N
z
H
Jec
SPRINKLER HEAD LEGEND :
Reliable Model G4A Concealed Pendant
Reliable Model Fl FR Recessed Pendant
rn
O1-6
•�
t <
U
4) Lod -
(1)
a
+NJ}
113
O wC4tstt)
aci
w z
A�L�
V/ o
co)o Z
e 4 z N
as
z
0
1"
(.3
••• • w
•••e
••••
•••• a
••••
•••• E
ft
••••
License No:
10910 117TH Place N.E.
COSCOFP 110NM
0, ix)
C -
COX
C°
N •
C N
d CO
�,
K2 (NI0
U
E
0
U
0
U
0
U
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
CONTRACT WITH:
DRAWING TITLE
Clarks: Hydraulic Calculation Pian
DATE: June, 2008
SCALE: As Noted
DRAWN BY: Justin Johnson
JOB NO.
25 KS - 7958
SHEET NO.
FP 2
F4L. CO
FIRE
TUKWII,A
SHINGT N
SHEET INDEX
NERAL NOTES
SYMBOLS LEGEND
SHEET \UV3ER
SHEET TITLE
W
fin
O
ON
ON
00
cV
'0'
O
(J
><
LL
SYSTEIV I \ FO. V
AT10 \
FA -02
TYPICAL DETAILS - WRI\G A\D
FA -03
FI E ALARIV
YSTEV
SYSTE V
OU\TI\G
FLOC PLA\
CALCULATIO\S (cE\EAL), -ISER, SITE PLA\
1
0
x
0
N
Without Comm?nts
As
Notact In R, tad
(nese
Prevention,:_,:
standard::.
omissions \,",'„
stanac„c: a ,rr ,•
Adrlitic.>; '
t..
resu'brt-Iltt:41 nt 'r
NO` ICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate mt.'. t be presented
to the prior to
commen� : >;" .,,_-;.ceptance
Testing
arl::i �. _.......
Faiiure of
ink-iEkR;
termination
Fir13 aCCC,"p'',''1';
Th
I UKWILA FIRE DEPARTMEil'Y
Pease call: 575-4407
:end
give this job
and exact address for shut.
.own or restoration approval;
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET)
H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET)
P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET)
S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET)
V SPEAKER CIRCUIT - FEED TWISTED PAIR 1#14 FPL/FPLR RED (JACKET)
2V SPEAKER CIRCUIT - RETURN TWISTED PAIR 4#14 FPL/FPLR RED (JACKET)
I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET)
X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD 4#16 FPL/FPLR RED (JACKET)
UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET)
UI UNDERGROUND INITIATION TWISTED PAIR RATED 1#18 FPL/FPLR RED (JACKET)
M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET)
B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET)
.!JUNCTIDN BOX
II
I CONDUIT FILL CHART
11;
NO.
OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
I; TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
I TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346
.TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191
1
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
i 3/4" SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
�
DO NOT INSTALL ADDRESS JBLE NITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEUCE $YvIBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE;,;THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT , P LARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IIS
BRANCHING IS PERMISSIBL
4. INSTALLATION SHALL BE IN . §TRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL . CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (iv, CON',UIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OP; ICS' CBLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEM NS C �BERUS DIVISION.
6. DETECTORS SHALL NOT BE OUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN ,WITH; RIESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR ;CODE.I1 CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY v1ARKED FOR: FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL 'RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
� 1I
9, FOR ADDITIONAL INSTALLATIC I IN ;.RUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION .IN TRUCTIONS.
10. THE 120vac POWER ELECTRI. AL WO,RK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE,1725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.25.2: I, REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL N T BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRM AFAR TECHNICIAN.
11. ALL HORN/STROBE AND STOBE ;DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW!DROP 'ED CEILING WHICHEVER IS LESS.
12. ALL MANUAL PULL STATION. SHALL BE MOUNTED AT 48" A.F.F. TO THE
QUANTITY
SYM
I ESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
SUPERVISED. NO PARALLEL
l TIRE ALARM
EX• NTROL PANEL
IRE ALARM
REMOTE ANNUNCIATOR
FARA
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
2
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND ;IRCUITL WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE ROMA liEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3 6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF;; ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BYI THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEE\ INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
,NTERFACE MODULE HTRI-R
PITH RELAY
SIEMENS
4S DEEP
VERIFY
IN FIELD
QUAL INPUT
NTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
,ZONE MODULE
!NEAR BEAM
SMOKE DETECTOR
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM. :
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL .DEVICES, JUNCTION BOXES AND FACP.
' I
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE: ALARM BACK BOXES 'AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
:I
21. ' ALL WIRING BETWEEN FLOOR S• SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL, STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G:,. METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE UTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TOTE. CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE 0 TGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BEI RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23. 1
NFPA 72 2007 A.6.4.2.2.2 fo\ GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND, RETURN CABLES.
THIS SEPARATION IS REQUIRb TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAI4 DAMAGE IS 305 .MM (1 FT) WHERE
THE CABLE IS INSTALLED VETICALII.Y AND 1.22 M (4. FT) WHERE THE
CABLE IS INSTALLED I
1
2
3
EX
MOKE DETECTOR
ADDRESSABLE -PHOTO)
SIEMENS
4S DEEP
VERIFY
IN FIELD
PBA -1191 SIEMENS
HFP-11 W/ SIEMENS
DB -11 BASE
PROVIDED
4S DEEP
W/ 1G RING
VERIFY
IN FIELD
CEILING
DUCT SMOKE
!' ETECTOR
EAT DETECTOR
ADDRESSABLE)
FIRE ALARM
SPEAKER STROBE
,C ; r (CEILING MOUNT)
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING
VERIFY
IN FIELD
HFPT-11 W/
DB -11 BASE
SIEMENS.
SET -MC -CW SIEMENS
4S DEEP
W/ 1G RING
CEILING
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
IRE ALARM
PEAKER STROBE
(WALL MOUNT)
SET -MC -W SIEMENS
4S DEEP BOX 80" A.F.F.
W/ 1-1/2" EXT. TO BOTTOM
IRE ALARM
'SPEAKER STROBE
(WALL MOUNT)
SET -HMC -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
FIRE ALARM
L '
C, ';(CEILING MOUNT) STROBE
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
IFIRE ALARM
.(WALL MOUNT)
LR -MC -W SIEMENS •
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
�! TIRE ALARM
,I PEAKER
;;(CEILING MOUNT)
SET -CW SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
';FIRE ALARM
.SPEAKER
•• WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
IN/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
I1FIRE ALARM
B STROBE
WP, (WEATHERPROOF)
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MRI
MULTI -VOLTAGE
:.CONTROL RELAY
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA JB❑X
FIRE ALARM
1TERMINAL CABINET
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
d
RED
'
.!JUNCTIDN BOX
II
F,B,❑,
F.B.❑,
N/A
VERIFY
FIELD
A,FF,
AB❑VE FINISHED
FL❑❑R
I
N/A
N/A
N/A
N/A
F B❑FURNISHED
.OTHERS
BY
N/A
N/A
N/A
N/A
N
A
IN❑T
APPLICABLE
N/A
N/A
N/A
N/A
U.❑
N.
UNLESS OTHERWISE
NOTED
N/A
N/A
N/A
N/A
W
'.WEATHERPR❑❑F
.;DEVICE
N/A
N/A
,
N/A
N/A
,As BUILT
ADD OR CHANGE
N/A
N/A
N/A
N/A
AS BUILT
GR EN ,I EM❑VE
N/A
N/A
N/A
N/A
BLUE
AS BUILT
:f❑TES TO CAD
N/A
N/A
N/A
N/A
Copyright 2006 by Guardian Security Systems, Inc. All Rights
tt
eserv
RELEASE/REVISIONS
LD
LLI
cr
DESCRIPTION
SHOP DRAWINGS
LLI
0
tn
LE
as
co
co
CCI -
(0
0
DRAWN BY:
LANDERSON
DESIGNED BY:
R.VEZZANI
BACKROUND PLAN PROVIDED BY:
NUMBp: 54499
SHEET
FA -01
H:
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS !FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OPERTIN TEMPERATURE:
+32' F (0' C) TO 100' F (38 C)
HUMIDITY: -9 % RELATIVE HUMIDITY,
NON -CONDENSING
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OUTLET SAMPLING-----\.
TUBE
FRONT VIEW
HFP-11 SMOKE
DETECTOR
DEVICE IS LISTED FOR AIR VOLOCITY
APPLICATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
DB -11
STANDARD
SMOKE
DETECTOR
BASE
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST GO THRU THE DUCT AND BE CAPPED.
INLET SAMPLING
TUBE
NOT USED
REMOTE
DEVICE LOOP
NOT USED
REMOTE
DEVICE LOOP
470
OHMS
�1V
EOL
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
--›-FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE .
TO NEXT DEVICE -C---!!
6-10 DUCT
EQUIVALENT
DIAMETERS
DUCT DETECTOR
LOCATI❑N
REAR VIEW
DATA IN (-) >---
DATA IN (+) >
> (-) DATA OUT
i (+) DATA OUT
"
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
LABEL SCALE ,
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (-)>
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
SCALE=NONE
MUSIC 4 -AC POWER SOURCE
--->(+)TO
>(-) ST
EXT DEVI
IF LAS
E OR
DEVICE}
I
Ica TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
SCALE NONE
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
LABEL SCALE
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE I \ l
STOP IF LAST DEVICE I�
FROM XLS CONTROL PANEL ❑R
PREVIOUS ADDRESSABLE DEVIC ---y
END OF LINE DEVICE(3.6K 1/4V))
SUPERVISED SWITCH
TO NEXT ADDRESSABLE DEVICE l(+)
STOP IF LAST DEVICE j
FROM XLS CONTROL PANEL ❑R(+)
PREVIOUS ADDRESSABLE DEVICE(-)
FROM REMOTE
POWER SUPPLY
C'S' CABLE)
TO NEXT
;ICE OR
OF LINE
HARD LID
CEILING SPEAKER SUPPORT TTI_
BRIDGE
HARD LID
( STR❑BE—)
SUPERVISED
SWITCH
RELAY CONTACTS
(4.OA 2 125VAC) GROUND
(4.0A @ 30VDC)
END O
LINE EVICE FROM FACP
3.6K 1 4W) (VOICE CIRCUIT)
C'V' CABLE)
UPER ISED
SWITCI
T
DE
E
NEXT
'ICE OR
OF LINE
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
I' •
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
4' SQUARE DEEP BOX --
WITH 1-1/2" EXTENSION
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING
SCALE=NONE
NOTE 1:
VOLTAGE MAX. -
CURRENT MAX,-
CONT. RES, MAX, -
MAX, CABLE LENGTH -
C CLINE TO LINE) -
C CLINE TO SHIELD) -
MAX, LINE SIZE -
MIN, LINE SIZE -
27 VDC
3.5 mA DURING POLLING
10 OHMS
200 FT. (18 AWG)
0,02uF
0.O4uF
14 AWG
18 AWG
0
GND N AC
NOTE 21
ALL SUPERVISED SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE
DETECTION,;
'SPEAKER STROBE
OR STROBE ONLY
4S DEEP BOX
w/ 1-1/2"
EXTENSION RING
(SPEAKER STROBE)
4S BOX
(STROBE ONLY)
m 6 B 0 o o
123456
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1+1-'1 2+2- 2 NC C NO + - + - + - + - + -
80" A.F.F.
JUNCTION BOX
MOUNTED ON
CEILING, FLEX
JUNCTION BOX
MOUNTED AGAINST
CEILING SUPPORT
4%,
/
/
/
/
r
SMOKE DETECTOR
SMOKE DETECTOR MOUNTING
SCALE=NONE
O O
TO NEXT DEVICE
CADDY BAR
SUSPENDED
ILLUMINATED
I±I
SPEAKER/STROBE
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
DO \OT I\STA_L
ADDRESSABLE SR TAT
DEVICES „STI_
PREPROGRAMMED WIT
DEVICES ADDRESS.
rn
z
0
LLJ
LU
LU
J
LU
REV. BY:
z
a
DESCRIPTION
SHOP DRAWINGS
DATE
0
N
N
Ln
o
aaaaa
CO
CO
J T
J
2 z
W Q
ZZ
CC Uu
s�¢
E illO
1.1. (O
F—
Er
KALE: 1/8"=1'
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/20/08
BACKROUND PLAN PROVIDED BY:
`JOB NUMBER:54499
SHEET
Copyri• ht
2006 b Guardian Securit S stems, Inc. All Ri. hts
I •
I
ID
:; I
D
C\2
toL
2S,2V
2S,2V
L.
TE:,.A.r1
0
-CO
L.
12'-0"
AFF
NORTH
CLARKS WESTFIELD SOUTHCENTER MALL
SCALE 118'=1'
LAG NO
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS.(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
LOCATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR,
WIRED BY ELECTRICAL
CONTRACTOR.
SIEMENS HTRI-D ADDRESSABLE
INPUT WITH HOOD VENILLAT❑R
FIRE SUPPRESI❑N SYSTEM, FIELD
LOCATE WITHIN 3 FEET OF
C❑NTRL PANEL.
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER, AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
DO NOT I\S�,LL
ADDRESSABLE D N TIS
DEVICES URI I_
PREPROGRAMMED W
DEVICES ADDRESS.
z N
o .'0
cp
z
Q Q,
v_i
F-
<
O ,p
cn
. N
W •
a
- o
U) N
N -I;.
fh
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserv;
REV. BY:
Z
4
DESCRIPTION
SHOP DRAWINGS
DATE
CO
0
N
cV
in
o
<a<aa
co
co
J'—
00
2 Z
W 0
�'-czz
CC 2 ucp
C3 Q
W
�o�
it(0
F-
V.
SCALE: 1/8" =1 '
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 5/20/08
BACKROUND PLAN PROVIDED BY:
V.013 NUMBER:54499
SHEET
FA -03
•
;
5
re:
IZCt\I 'Oil E
IN V+1ASHINGTON
N„z
IR/I,SH
rJ
wTi M
1.,
, •
t
f)
1\1 ALI_
OFFICE
0.
(-1
(1-)
w
C.)
J ,"-; M E A
JUICE
THE PICTURE
PEOPLE
A 13 R ($/11.----:: I E
I
I'
1 505
1550
if)
1
CLARKS WESTFIELD SOUTHCENTER MALL
IL]]
1;1 54-1,2,
SEA TTL E_
MARI NI ER S
TEAM 3HOP
IFI
\
.;
:11.2
-1 IR A ‘.'"..`I•i! I. r•
•• • arr
----• (13 11
P I ("LJN IEI AR
E WALK I I`•,1
r 1 00 1
r
bebe
1 11 0
1115
1 5,35 I
15!)0j
0
1 11;
;
>--
SCALE 1132"4
75 C 75 C 15
15
15
15
2S,2V
0
D
D
EX
D,I
21
1r
SYSTEM CALC LATIONS
M
HL
CLARKS
CLARKS
FACP ADD ONS
SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations
COrrent Load:
; •
Standby:
Alarm:
CU rent Load:
Standby:
Alarm:
Total
0.030
Dice Type
HF,P-11
A2 -P
'
Qty
1
2
Amps
0.0022
0.0635
0.009600
0.001600
0.005
Total
0.0022
0.0635
0.0096
0.0731
Amps
0.0023
0.064
0.021
0.0035
Amps
Total
0.064
0.042
0.106
Amps
14
I,11;
!!,
1 :1
•
Standby Current Load:
1
0.0731
Amps
For 24 Hours =
1.754
Amp -hours
Alarm Current Load:
;
0.106 Amps
Total System Current Load:
Battery Pair to be Used:
12VDC
For 5 Minutes=
25% Derating=
Amp -hours
0.009
2.204
2.204
7AH
Amp -hours
Amp -hours
Amp -hours
11
;1' , •
Deice Type
Main System Board
STMC @15CD
.SE -MC @30CD
SE -MC @75CD
SE -MC@110CD
S -HMC-C@115CD
S T-HMC-C@135CD
S ll-HMC-C@185CD
ZR MC 61ECD
ZR MC @30CD
H p
St
ndby Current Load:
Alarm Current Load:
Battery Pair to be Used:
Qty
1
3
2
1
0.03
0.636
Amps
0.03
Amps
Amps
Total System Current Load:
12VDC
Total
0.03
0.03
For 24 Hours =
For 5 Minutes=
25% Derating=
Amp -hours
Amps
0.030
0.064
0.098
0.175
0.233
0.318
0.318
0.445
0.064
0.098
0.0015
Amps
0.720
0.053
0.967
0.967
7AH
:1 11
• I
0.350
17.H..
0.064
0.636 AM
Amp -hours
Amp -hours
Amp -hours
Amp -hours
l;
!I ,
•
'4,faat&
I
• :1::
. 1 t
'
BATTERY SIZI
Notification Appliance
PROJECT: WESTFIELD SOUTHCENTER MALL
Panel: CLARKS
Date: May 22, 2008
CIRCUIT:
QTY
0
2
0
0
0
0
1
DEVICES=
S1
Device Type
SET -MC @15CD
SET -MC @30CD
SET -MC @75CD
SET -MC @110CD
SET-HMC-C@115CD
SET-HMC-C@177CD
SET -HMC @135CD
SET -HMC @185CD
Z-MC@15CD
Z-MC@30CD
Aiarm Current Alarm Total
64 192
98
175
SET-MC-CW@110CD
6
233
318
445
318
445
64
98
233
0
350
0
0
0
0
Wire Size
CALCULATION
it Detail
Wire Resistance 1.62
606
RRENT TOTAL=
VVir Lenth
Voltage at EOL
Circuit Total
Total Wire Resistance ( R )
( WL* )* (ft)
Total lDevice Load, Amps (I)
(Total Cct Load)
Voltage Drop ( E)
64
TOTAL mA=
PROJECT.
Panel:
Date:
CIRCUIT:
QTY
5
0
606
12
--m65
Notification Appliance
WESTFIELD SOUTHCENTER MALL
CLARKS
May 27, 2008
19 8796884
ircuit Detail
6061
(E= 1* R)
EOL Voltage
(20.4 - E)
0.86
0.61
0.52
19.88
Wire Resistance ,2.66
PURrZENT TOTAL= 9
1 •
VVire eirl-n•FrIgt .--VO-Itage at EOL Circuit Total
SPEAKER CIRCUIT
Device Type Alarm Current
70.7V1/8 1.8
0
0
0
0
0
0
0
0
0
0
Alarm Total
9
0
• 0
0
Wire Size
DEVICES= 5
TOTAL mA=
0
0
0
0
0
9 14
Total Wire Resistance(R) 2.92
( WL * 2 )* (Rift)
Total Device Load, Amps (I) 0.01
(Total Cct Load)
Voltage Drop ( E) 0.03
• (E= I * R)
EOL Voltage • 20.37
(20.4 - E)
20.37376141
DRAWN BY:
LANDERSON'
DESIGNED BY:
R.VEZZANI
DATE: 5/20/08
BACKROUND PLAN PROVIDED BY:
RISER DIAGRAM
r1-
1515
I
•
VOLTAGE DROFt CALCULATION
••1
Copyright 2006 by Guardian Security Systems, Inc. All Ri hts Resery
\0B NUMBER:54499
SHEET
FA -04J
466 SOUTHCENTER MALL
ASSOCIATED PERMITS
08-F-244
08-S-326
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Clarks
466 Southcenter Mall
Permit No.: 08-S-326
Date: June 13, 2008
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80'•for mains and cross mains and
within 40 ' of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2 '/2 inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-02, section 9.6.2.6.2 (e).
• Ceilings used for flex drop attachments shall comply with ASTM C 635 and
ASTM C 636 per section 9.2.1.3.3.2.
• Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a
suspended ceiling, a hanger(s) attached to the structure shall be required to
ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3).
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• These conditions apply to any sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All references are NFPA 13, 2007 Edition.
3
COSCO FIRE PROTECTION, INC.
15000 WOODINVILLE REDMOND ROAD NE #B800
WOODINVILLE,WA 98072-4502
HYDRAULIC CALCULATIONS
FOR
Clarks
466 Southcenter Mall, Suite #1010
Tukwila, Wa. 98188-2823
FILE NUMBER: 25KS - 7936
DATE: JUN 12, 2008
-DESIGN DATA -
OCCUPANCY CLASSIFICATION: Ordinary Group II
DENSITY: 0.20 gpm/1500 sq. ft.
AREA OF APPLICATION: 1545 sq. ft.
COVERAGE PER SPRINKLER: 130 sq. ft. Max.
NUMBER OF SPRINKLERS CALCULATED: 17 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 466.3 gpm
TOTAL WATER REQUIRED (including hose): 900.0 gpm
FLOW AND PRESSURE (@ BOR): 649.9 gpm @ 89.9 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: Cosco Fire Protection, Inc.
DESIGN/LAYOUT BY: Justin Johnson
AUTHORITY HAVING JURISDICTION: Tukwila Fire Department
CONTRACTOR CERTIFICATION NUMBER: COSCOFP11OMN
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 4903012830)
HRS SYSTEMS, INC.
TUCKER, GA 30084
TUCKER, GA 30084
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
WATER SUPPLY DATA
SOURCE
NODE
TAG
SOURCE
STATIC
PRESS.
(PSI)
140.0
RESID.
PRESS.
(PSI)
20.0
AGGREGATE FLOW ANALYSIS:
FLOW
(GPM)
10900.0
TOTAL FLOW AT SOURCE
TOTAL HOSE STREAM ALLOWANCE AT SOURCE
OTHER HOSE STREAM ALLOWANCES
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS
NODE ANALYSIS DATA
NODE TAG ELEVATION
(FT)
AVAIL.
PRESS.
(PSI)
138.8
TOTAL
@ DEMAND
(GPM)
900.0 GPM
250.0 GPM
183.6 GPM
466.4 GPM
REQ'D
PRESS.
(PSI)
900.0 97.6
NODE TYPE PRESSURE DISCHARGE
(PSI) (GPM)
S1 12.0 K= 5.60 26.4
1 14.5 - - - - 32.9
S2 12.0 K= 5.60 25.8
2 14.5 - - - - 33.3
S3 13.5 K= 5.60 22.4
3 14.5 - - - - 28.1
S4 13.0 K= 5.60 21.6
4 14.5 - - - - 28.2
S5 13.0 K= 5.60 22.3
5 14.5 - - - - 29.2
S6 13.0 K= 5.60 23.8
6 14.5 - - - - 31.2
S7 12.0 K= 5.60 26.9
7 14.5 - - - - 33.1
S8 12.0 K= 5.60 26.2
8 14.5 - - - - 33.6
S9 13.5 K= 5.60 22.4
9 14.5 - - - - 28.2
S10 13.0 K= 5.60 22.2
10 14.5 - - - - 28.3
Sil 13.0 K= 5.60 23.0
11 14.5 - - - - 29.3
S12 13.0 K= 5.60 24.6
12 14.5 - - - - 31.4
S13 12.0 K= 5.60 27.6
13 14.5 - - - - 35.4
S14 13.5 K= 5.60 22.4
14 14.5 - - - - 28.7
S15 13.0 K= 5.60 22.5
15 14.5 - - - - 28.8
S16 13.0 K= 5.60 23.3
16 14.5 - - - - 29.8
S17 13.0 K= 5.60 25.0
17 14.5 - - - - 31.9
28.8
28.4
26.5
26.0
26.4
27.3
29.1
28.6
26.5
26.4
26.9
27.8
29.4
26.5
26.6
27.0
28.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
M1 14.5 HOSE STREAM 35.1 183.6
M2 14.5 - - - - 35.3
M3 14.5 35.9
M4 14.0 71.5
TOR 13.7 81.3
BOR 2.0 89.9
M5 2.0 90.2
BFO 2.0 90.3
BFI 2.0 94.8
UG1 1.2 - - - - 95.1 - - -
SOURCE -4.0 SOURCE 97.6 650.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -28.8 1.049 PL 25.58 PF 7.6
S1 12.0 5.6 26.4 28.8 10.7 120 FTG 2E PE -1.1
1 14.5 0.0 32.9 0.0 0.255 TL 29.58 PV
Pipe: 2 -28.4 1.049 PL 27.58 PF 8.6
S2 12.0 5.6 25.8 28.4 10.6 120 FTG ET PE -1.1
2 14.5 0.0 33.3 0.0 0.250 TL 34.58 PV
Pipe: 3 -26.5 1.049 PL 24.00 PF 6.1
S3 13.5 5.6 22.4 26.5 9.8 120 FTG 2E PE -0.4
3 14.5 0.0 28.1 0.0 0.219 TL 28.00 PV
Pipe: 4 -26.0 1.049 PL 27.62 PF 7.3
S4 13.0 5.6 21.6 26.0 9.7 120 FTG ET PE -0.6
4 14.5 0.0 28.2 0.0 0.211 TL 34.62 PV
Pipe: 5 -26.4 1.049 PL 27.62 PF 7.5
S5 13.0 5.6 22.3 26.4 9.8 120 FTG ET PE -0.6
5 14.5 0.0 29.2 0.0 0.218 TL 34.62 PV
Pipe: 6 -27.3 1.049 PL 27.62 PF 8.0
S6 13.0 5.6 23.8 27.3 10.2 120 FTG ET PE -0.6
6 14.5 0.0 31.2 0.0 0.232 TL 34.62 PV
Pipe: 7 -29.1 1.049 PL 24.00 PF 7.3
S7 12.0 5.6 26.9 29.1 10.8 120 FTG 2E PE -1.1
7 14.5 0.0 33.1 0.0 0.260 TL 28.00 PV
Pipe: 8 -28.6 1.049 PL 26.50 PF 8.5
S8 12.0 5.6 26.2 28.6 10.6 120 FTG ET PE -1.1
8 14.5 0.0 33.6 0.0 0.253 TL 33.50 PV
Pipe: 9 -26.5 1.049 PL 24.00 PF 6.1
S9 13.5 5.6 22.4 26.5 9.8 120 FTG 2E PE -0.4
9 14.5 0.0 28.2 0.0 0.219 TL 28.00 PV
Pipe: 10 -26.4 1.049 PL 24.00 PF 6.7
S10 13.0 5.6 22.2 26.4 9.8 120 FTG ET PE -0.6
10 14.5 0.0 28.3 0.0 0.218 TL 31.00 PV
Pipe: 11 -26.9 1.049 PL 24.00 PF 7.0
S11 13.0 5.6 23.0 26.9 10.0 120 FTG ET PE -0.6
11 14.5 0.0 29.3 0.0 0.224 TL 31.00 PV
Pipe: 12 -27.8 1.049 PL 24.00 PF 7.4
S12 13.0 5.6 24.6 27.8 10.3 120 FTG ET PE -0.6
12 14.5 0.0 31.4 0.0 0.239 TL 31.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -29.4 1.049 PL 26.50 PF 8.9
S13 12.0 5.6 27.6 29.4 10.9 120 FTG ET PE -1.1
13 14.5 0.0 35.4 0.0 0.266 TL 33.50 PV
Pipe: 14 -26.5 1.049 PL 27.00 PF 6.8
S14 13.5 5.6 22.4 26.5 9.8 120 FTG 2E PE -0.4
14 14.5 0.0 28.7 0.0 0.219 TL 31.00 PV
Pipe: 15 -26.6 1.049 PL 24.50 PF 6.9
S15 13.0 5.6 22.5 26.6 9.9 120 FTG ET PE -0.6
15 14.5 0.0 28.8 0.0 0.220 TL 31.50 PV
Pipe: 16 -27.0 1.049 PL 24.50 PF 7.2
S16 13.0 5.6 23.3 27.0 10.0 120 FTG ET PE -0.6
16 14.5 0.0 29.8 0.0 0.227 TL 31.50 PV
Pipe: 17 -28.0 1.049 PL 24.50 PF 7.6
S17 13.0 5.6 25.0 28.0 10.4 120 FTG ET PE -0.6
17 14.5 0.0 31.9 0.0 0.242 TL 31.50 PV
Pipe: 18 -28.8 1.610 PL 14.00 PF 0.4
1 14.5 0.0 32.9 0.0 4.5 120 FTG ---- PE 0.0
2 14.5 0.0 33.3 0.0 0.032 TL 14.00 PV
Pipe: 19 -57.2 1.610 PL 7.58 PF 1.8
2 14.5 0.0 33.3 0.0 9.0 120 FTG T PE 0.0
M1 14.5 H.S. 35.1 183.6 0.113 TL 15.58 PV
Pipe: 20 -26.5 1.610 PL 4.35 PF 0.1
3 14.5 0.0 28.1 0.0 4.2 120 FTG ---- PE 0.0
4 14.5 0.0 28.2 0.0 0.027 TL 4.35 PV
Pipe: 21 -52.5 1.610 PL 10.00 PF 1.0
4 14.5 0.0 28.2 0.0 8.3 120 FTG ---- PE 0.0
5 14.5 0.0 29.2 0.0 0.096 TL 10.00 PV
Pipe: 22 -78.9 1.610 PL 10.00 PF 2.0
5 14.5 0.0 29.2 0.0 12.4 120 FTG ---- PE 0.0
6 14.5 0.0 31.2 0.0 0.205 TL 10.00 PV
Pipe: 23 -106.3 1.610 PL 2.88 PF 3.9
6 14.5 0.0 31.2 0.0 16.8 120 FTG T PE 0.0
M1 14.5 H.S. 35.1 183.6 0.355 TL 10.88 PV
Pipe: 24 -29.1 1.610 PL 14.00 PF 0.5
7 14.5 0.0 33.1 0.0 4.6 120 FTG ---- PE 0.0
8 14.5 0.0 33.6 0.0 0.032 TL 14.00 PV
Pipe: 25 -57.7 1.610 PL 7.58 PF 1.8
8 14.5 0.0 33.6 0.0 9.1 120 FTG T PE 0.0
M2 14.5 0.0 35.3 0.0 0.115 TL 15.58 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 26 -26.5 1.610 PL 5.73 PF 0.2
9 14.5 0.0 28.2 0.0 4.2 120 FTG ---- PE 0.0
10 14.5 0.0 28.3 0.0 0.027 TL 5.73 PV
Pipe: 27 -52.9 1.610 PL 10.00 PF 1.0
10 14.5 0.0 28.3 0.0 8.3 120 FTG ---- PE 0.0
11 14.5 0.0 29.3 0.0 0.098 TL 10.00 PV
Pipe: 28 -79.8 1.610 PL 10.00 PF 2.1
11 14.5 0.0 29.3 0.0 12.6 120 FTG ---- PE 0.0
12 14.5 0.0 31.4 0.0 0.209 TL 10.00 PV
Pipe: 29 -107.6 1.610 PL 2.88 PF 4.0
12 14.5 0.0 31.4 0.0 17.0 120 FTG T PE 0.0
M2 14.5 0.0 35.3 0.0 0.363 TL 10.88 PV
Pipe: 30 -29.4 1.610 PL 7.58 PF 0.5
13 14.5 0.0 35.4 0.0 4.6 120 FTG T PE 0.0
M3 14.5 0.0 35.9 0.0 0.033 TL 15.58 PV
Pipe: 31 -26.5 1.610 PL 4.10 PF 0.1
14 14.5 0.0 28.7 0.0 4.2 120 FTG ---- PE 0.0
15 14.5 0.0 28.8 0.0 0.027 TL 4.10 PV
Pipe: 32 -53.1 1.610 PL 10.00 PF 1.0
15 14.5 0.0 28.8 0.0 8.4 120 FTG ---- PE 0.0
16 14.5 0.0 29.8 0.0 0.098 TL 10.00 PV
Pipe: 33 -80.1 1.610 PL 10.00 PF 2.1
16 14.5 0.0 29.8 0.0 12.6 120 FTG ---- PE 0.0
17 14.5 0.0 31.9 0.0 0.211 TL 10.00 PV
Pipe: 34 -108.1 1.610 PL 2.88 PF 4.0
17 14.5 0.0 31.9 0.0 17.0 120 FTG T PE 0.0
M3 14.5 0.0 35.9 0.0 0.366 TL 10.88 PV
Pipe: 35 -347.1 4.260 PL 8.92 PF 0.2
M1 14.5 H.S. 35.1 183.6 7.8 120 FTG ---- PE 0.0
M2 14.5 0.0 35.3 0.0 0.028 TL 8.92 PV
Pipe: 36 -512.4 4.260 PL 10.00 PF 0.6
M2 14.5 0.0 35.3 0.0 11.5 120 FTG ---- PE 0.0
M3 14.5 0.0 35.9 0.0 0.057 TL 10.00 PV
Pipe: 37 -649.9 4.260 PL 267.50 PF 35.4
M3 14.5 0.0 35.9 0.0 14.6 120 FTG 8ET PE 0.2
M4 14.0 0.0 71.5 0.0 0.089 TL 399.40 PV
Pipe: 38 -649.9 4.260 PL 69.33 PF 9.6
M4 14.0 0.0 71.5 0.0 14.6 120 FTG 3E PE 0.1
TOR 13.7 0.0 81.3 0.0 0.089 TL 108.93 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 39 -649.9 4.260 PL 11.67 PF 3.6
TOR 13.7 0.0 81.3 0.0 14.6 120 FTG C PE 5.1
BOR 2.0 0.0 89.9 0.0 0.089 TL 40.67 PV
Pipe: 40 -649.9 8.249 PL 21.25 PF 0.2
BOR 2.0 0.0 89.9 0.0 3.9 120 FTG 2E PE 0.0
M5 2.0 0.0 90.2 0.0 0.004 TL 61.25 PV
Pipe: 41 -649.9 10.374 PL 14.75 PF 0.1
M5 2.0 0.0 90.2 0.0 2.5 120 FTG 3E PE 0.0
BFO 2.0 0.0 90.3 0.0 0.001 TL 88.55 PV
Pipe: 42 FIXED PRESSURE LOSS DEVICE
BFI 2.0 0.0 94.8 0.0 4.5 psi, 649.9 gpm
BFO 2.0 0.0 90.3 0.0
Pipe: 43 -649.9 10.374 PL 2.83 PF 0.0
BFI 2.0 0.0 94.8 0.0 2.5 120 FTG E PE 0.4
UG1 1.2 0.0 95.1 0.0 0.001 TL 27.43 PV
Pipe: 44 -650.0 10.275 PL 85.00 PF 0.2
UG1 1.2 0.0 95.1 0.0 2.5 140 FTG 2ETG PE 2.2
SOURCE -4.0 SRCE 97.6 (N/A) 0.001 TL 225.80 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 7.9 computer program
under license no. 4903012830 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.167 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 17.0 ft/sec at pipe 34.
(4) PIPE FITTINGS TABLE
Pipe Table Name: MOST.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
PAGE: A MATERIAL: SCH.40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D F
Ell Tee LngEll ChkVly BfyVly GatV1v AlmChk DPV1v 45E11
H Q I S U V W
22/Ell 11gE11 Couplg FM90E1 FM45E1 FMTee FMRunT
1.049 2.00 5.00 2.00 5.00 0.00 0.00 0.00 0.00 1.00
0.50 0.30 1.00 6.00 5.00 9.00 0.00
1.610 4.00 8.00 2.00 9.00 0.00 0.00 0.00 0.00 2.00
1.00 0.50 1.00 8.00 6.00 12.00 0.00
PAGE: B MATERIAL: SCH.10 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D F
Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11
4.260
8.249
10.374
H Q I S U V W
22/Ell 11gEll Couplg FM90E1 FM45E1 FMTee FMRunT
13.20 26.30 7.90 29.00 15.80 2.60 36.90 39.50 6.60
3.30 1.60 1.30 18.40 11.90 31.60 0.00
20.00 38.90 14.50 50.00 13.30 4.40 45.60 0.00 10.00
5.00 2.50 1.10 24.50 14.50 43.40 0.00
24.60 56.00 17.90 61.60 21.30 5.60 0.00 0.00 12.30
6.20 3.10 1.10 29.10 16.80 56.00 0.00
PAGE: D MATERIAL: DI -52 HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D F
Ell Tee LngEll ChkV1v BfyVly GatV1v AlmChk DPV1v 45E11
10.275
H Q
22/Ell 11gE11
31.30 71.10 22.70 78.20 27.00 7.10 0.00 0.00 15.60
7.80 3.90
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
0
O
rn
O
1-1
0
G4
a.
0
0
0
140.00 psi Resid
E a) a)
a E > >
rn a�
a) o U U
• • a)o
• o • >. '0
m o • o
0) m m a E
C1 R,O q
a°�' co '0 -N u v
ro r ¢ W
H 'D 0 Un
•
rtl o CS •
FICcO
N
O
0 0 0 0 0 0
W d' N 0 CO 10
H r-1 H H
(..7g0w axwu)u1:4 41 --acn-.-1--
O
0
0
0
O
0
M
m
0
_ 0
N
CU
N
O O.11
r-1
O O i
N
0
a
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10
DATE: 6/12/2008\KS 7958 CLARKS\CALCULATIONS\HYDRAULIC CALC'S\CLARKS 1.SDF
JOB TITLE: Limited Too
WATER SUPPLY CURVE
144+
0
I\
132+ \
\
\
\
120+ \
\
\
\
108+ \
\
\
X \
P 96+ \
R I \
E I \
s I \
S 84+ \
U I \
R I \
E I \
72+ \
( I
P I \
S 1 \
I 60+
\
1 \
\
48+
i \
\
\
36+
\
\
\
24+ LEGEND
1 X = Required Water Supply
97.60 psi @ 900.0 gpm
12+
0 = Available Water Supply
138.81 psi @ 900.0 gpm
<-20.0 psi @ 10900 gpm
Flow Test Point
0++-+ -+ -+ + + + + + +
32004800 6400 8000 9600 11200 12800 14400 16000
FLOW (GPM)
GUARDIAN SECURITY
Customer LIFE AND
CLARKS
466 SOUTHCENTER MALL
'KWILA, WA 98188
Project CLARKS
Project # 54499
PROPERTY PROTECTION
List of Materials
Vendor
Guardian Security Systems Inc
1743 1st Ave. South
Seattle, WA 98134
Phone #: (206)622-6545
Fax #: (206)628-4990
Type of Equipment
FIRE ALARM
Date: MAY,28,08
Item Qty. Manuf.
Model
Description
Unit Pri Total Price'
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)
14)
15)
16)
17)
18)
19)
20)
21)
22)
23)
24)
25)
26)
27)
28)
29)
30)
31)
32)
33)
34)
35)
36)
37)
38)
39)
40)
41)
42)
43)
44)
45)
46)
47)
48)
49)
50)
Siemens PAD -3
Siemens AD2-P
Siemens HTRI-D
Siemens HTRI-R
Siemens SET CW,W
Siemens SET W
Siemens ZR-MC-W,W
Power Supply for Strobes with Standby**
Photoelectric Duct Detector housing w/Sample Tubes, Remote TSM -1
Supervised Addressable Input Module
Supervised Addressable Output Relay Module
Interior Audible Speaker Annunciator
Interior Audible Speaker Annunciator
Interior Visual Strobe Annunciator
Conduit Systems: All smoke removal and detection and control devices in
an approved metallic raceway and all devices in conduit per Standard
fl�l s c dfl
LD
3'-9"
IYa'' x 1 "
1, \ADACAP
1'
4-31¢
o
2'-4/2"..
0-6
O
8- '3
1'
1'
1-7
1
O
3-
a
CO
'-C.2N
61-0"
4'-O"
I0
-0"
10
0"
x 1"
f 1' rADA CAP
b 1-5
IY2' x I'
/ADA CAP
ll
tet
ex--
I/2' x �,
rADA CAP
1�
1'
Flex
c
1
0/
CD
CL
8'
II
2'-0"
cp
I
'-" CU
10'-0"
4
-4/2"
lex
1'
3-4
3-5
-8i2
#71t
VP. F \f L
1'
3-5
0
1'
3-5
cu
1'
2-3
7f
2-3 /
1'
-9
5
-10"
1' N
2-E
�26
0
\f
Flex
i�x I"
ADA CAP
lex
4'-6"
1'
1'
P4,
4-11
`1y"x 1"
ADA CAF
D
6'- I /2"
WILKINS 10" 350 DAG
Vertical Backflow Preventer
E
(n
2x 10" Vlctaullc #750
Butterfly Valve
F/c
4" RellableModel "G"
Riser Check Valve
10" Flange AiliE
4. @ I '-2" AFF
/ \ FF c, 0'-0"
10" D.I.
\ @
-41-0"±
System T2 Riser Assembly Detail
N.T.S.
00 -
(TUIKWILLA UTILITIES:)
CONSTRUCTION NOTES
GENERAL NOTESf
I) r'iPE:
71READED: STEEL, SCH 40, BLACK, IMPORT.
GROOVED: STEEL, SCH 10, BLACK, IMPORT.
2) rITTINGS:
GROOVED: STAR STANDARD - ORANGE PAINT
VISH
'READED: STAR D.I.
3) ;.ROOVED COUPLINGS:
.AR RIGID C-4 UNLESS MARKED WITH AN "F",
b'11ICH ARE TO BE STAR FLEXIBLE C-3 LW -
('RANGE PAINT FINISH
4) HANGER MATERIAL:
ALL HANGER MATERIAL IS TO BE FINISHED
BLACK OR STANDARD
Static Pressure = 140 psi
Re=dual Pressure = 20 psi
Fire Flow = 1 0,900 gpm
Static Pressure = 140 psi
Residual Pressure = 20 psi
Fire Flow = gpm
SYMBOL LEGEND:)
= NEW RECESSED PENDANT ON DROP
®= NEW CONCEALED PENDANT ON DROP
EXISTING SPRINKLER PIPE TO REMAIN
NEW SPRINKLER PIPING
I) SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF
N.F.P.A. 13-2007 ED., THE CONTRACT DOCUMENTS, AND THE CITY OF
TUKWILA.
CRITERIA:
OCCUPANCY: ORDINARY HAZARD GROUP II.
ORDINARY HAZARD GROUP II SPRINKLER SPACING: 130 ft2 MAX.
2) COSCO'S POINT OF CONNECTION IS AT EXISTING SYSTEM AS SHOWN.
3) ALL PAINTING OR PREP OF FIRE SPRINKLER PIPING (IF REQ.. ) TO BE DONE BY
OTHER.
4) ALL WIRING OF SYSTEM DEVICES IS BY OTHER.
5) OWNER 15 RESPONSIBLE TO ASSURE THAT THE STRUCTURE, AS IT IS SHOWN
ON THE CONTRACT DRAWINGS, CAN ADEQUATELY SUPPORT THE FIRE
SPRINKLER PIPING. NO AUXILIARY DEVICES OR ATTACHMENTS SHALL BE
PROVIDED BY COSCO TO SUPPLEMENT THE STRUCTURE.
OWNER IS RESPONSIBLE TO PROVIDE ADEQUATE HEAT TO MAINTAIN 40° F.
MINIMUM AT ALL TIMES.
7) OWNER 15 RESPONSIBLE TO ARRANGE FOR THE PERIODIC INSPECTION,
TESTING, AND MAINTENANCE OF THESE FIRE SPRINKLER SYSTEMS IN
ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF N.F.P.A. 25-2002 ED.,
BY QUALIFIED PERSONNEL COMMENCING AFTER WARRANTY PERIOD HAS
EXPIRED. THE FIRM THAT DESIGNED AND INSTALLED THE SYSTEM(5) IS BEST
QUALIFIED TO PROVIDE THE ONGOING LONG TERM TESTING, MAINTENANCE,
AND SERVICING.
8) COSCO TAKES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE
CONDITION, PERFORMANCE OR. CURRENT CODE COMPLIANCE OF THE EXISTING
SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM
ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY COSCO FIRE
PROTECTION.
G)
SEE PLAN
FOR LENGTH
NEW BRANCH LINE
"FLEXHEAD" FLEXIBLE
DROP CORRUGATED
STAINLESS STEEL
BRAIDED HOSE
CEILING
Z
'-
gz
Q W
W
Wce
"'O
LL
ADJUSTABLE HUB
MOUNTING BRACKET
(BTYPICAL
ARMOVER TO NEW SPRINKLER HEAD
�
N.T.S.
TOLCO FIG. 25 SURGE RESTRAINER
TYPE 1 - FOR I " AND IY4' PIPE AND HANGER
TYPE 2 - FOR 172" AND 2" PIPE AND HANGER
TOLCO MG. 25 IS DESIGNED TO BE USED ONLY
WITH TOLCO BAND HANGERS FIG. 200 AND 2NFPA
TO RESTRAIN THE UPWARD MOVEMENT OF PIPE A5
IT OCCURS DURING SPRINKLER HEAD ACTIVATION
OR SEISMIC ACTIVITY
SYMBOL =
FIGURE 25 SURGE RESTRAINER
cht OO FOR STEEL OR CPVC PLASTIC PIPE
3/8' x aY2' LAG SCREW FOR WOOD
3/8' x 24" KWIK BOLT FOR CONCRETE —\
I" x Y4' TEK FOR BARJOIST OR STEEL BEAM
45° MIN.
ur
ARGCO OFFSET
EYESOCKET BRKT.
WHERE LENGTH 1
EXCEEDS 1'-10"
SYMBOL = 6
LINE RESTRAINT DETAIL
NALL THREAD ROD
I'- 10" MAX. PER SINGLE.
OTHERWISE ASSEMBLY
REQD. BOTH SIDES
-"------...„HANGER RING
(UP TO2"PIPE)
SPACE WITH IN G" OF A HANGER EVERY 30' ON A LINE
UL
HILTI KWIK BOLT 3 ANCHOR
ICC REPORT #ESR -1385
MIN. OF 3,000 PSI CONCRETE
MIN. 3 1/4" CONCRETE OVER
MAX. 3" METAL DECK
3/8" ANCHOR W/20# TORQUE:
TENSION=395#, SHEAR=750#*
1/2" ANCHOR W/40# TORQUE:
TENSION=440#, SHEAR=750#*
'SHEAR LOADS HAVE BEEN REDUCED
BY 20% FOR SHEAR THRU THREADS
1/4" MIN
I re pa to- Roo ri is: Fro
ti°4151:1!
or
—
ROD COUPLING
THREADED ROD
PIPE
SIZE
1 I/4"
1 1/2"
2"
2 1/2"
3"
4"
6"
8"
ROD BOLT IMBED
DIA. LGTH DEPTH
3/8" 33 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
3/8" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
1/2" 3 3/4" 2 1/4"
HILTI FIG. LH OR
TOLCO FIG. 200
HANGER RING UL
04/2007
COSCO STANDARD HANGER
13 MDL
0
VVthoi tCornn:�ntt.
As 1J0-1sci In F;•: -,,,d
Per The
e
!hese plans have bean r: ',.'I:::, , . by j 3
Prevention hire I f:.;r .:�, :...., •
standards. Aco,,, l.ar,,::. «.... . t:,Cifrais u;
omissions vin' , 3'. ,;int
t'
standards and o::..i;.:; ..,.:
adequacy of d :, ,, s, r ::: • ',;r, Irk; c>
Additions,i .
dale:bo , of ;, .... :these : ilii sr
this date will void tl iF; ;:,:c; . ,..,,;.:: .
rid will r>`:�r.,,re: r.
resubmittal of revised di ,‘,-iri-. o ;, i ub:..eKquent approval.
Final accLp .r,cc;> i, sr.::`.: ect field test and inspection by
The Tukwila Fire i i' ri;,.,...,;1 Llureau.
:Date: 60 /3-03 By:
-11r1 stamps must be
inspected before pipz1 is
hung, . -.1: paint piping
prior t0 )
approval.
TUKWILA FIRE DEPARTMENT
Pease call: 575-440Z
and give this job
140.
at „J exact address for shut
clown or restoration approval.
z
0
>-
LO
W
Q
DESCRIPTION
0
z
z
ei
'°
24
JOB NO.
25KS - 7958
SHEET NO.
FP 1
a
TOTAL SPRINKLERS = 30
THIS SHEET
d
i
i -
o
'Q
0
iL)
W,
Fy
az,:
White
Chrome
9F,,
mz
_im
2
m
2
L
U
Q
,,,
ae
-ri
ui
NPT
APPROVALS BY:
W
1
0
z
0
N
SPRINKLER HEAD LEGEND :
Reliable Model G4A Concealed Pendant
Reliable Model F1 FR Recessed Pendant
0in-
re4 J
�Q
r „IC)
(�a
isid O W
C4 L‹
all inV/(0)
v r°'i Z
Q
0
U
••• • w
•••• f-
••••
••••0-
••••
•••• i
••••
W
0
u -
LL.
0
Z
a
License No:
10910 117TH Place N.E.
COSCOFP110NM
1"1-
c0 c
N
X
0
•
c0
170 -
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
PAID ?AIC?
d JN13 2008
Tukwila Fire
70-2a°66
0
-F—
N
0
U
V)
0
E
0
r
..
g O
z
U
0
N
it
m
a
a_d
z>
m
0 00
V) a
b
N .0
N
DRAWING TITLE
Clarks: Sprinkler Piping Plan
DATE: June, 2008
SCALE : As Noted
DRAWN BY: Justin Johnson
JOB NO.
25KS - 7958
SHEET NO.
FP 1
a
I ,545ft
IlydrauliCaly Calculated
Most ReFnote Area
(.)
0
C7 til
t
C
�pp
; L
0
c
if
�r
'1
(1
•
0
l
Py
CD
5-77.1
71
0
5
4" x 61 '-0"
@ 1 4'-6" AFF
T
WILKINS 10" 350 DAG
Vertical Backflow Preventer
4" x 1 6'-3"
E
Q)
2x 1 0" Vlctaullc #750
Butterfly Valve
m
2
'O»
'QFF
4" ReliableModel "G"
Riser Check Valve
I O" Flange
4. @ 11-2" AFF
\ FF @ 0'-0"
I O" D.I.
C@ -4'-O"±
System T2 Riser Assembly Detail
N.T.S.
-00
@ 1 5'-6" AFF
4"x5"-
'. @ 131-6"
4. @ 2'-0" AFF
West Sprinkler
Riser Room ,no
10" x 8..�I
Grooved RC
10"
@ 2'-0" ALT
T
S
4 7, ---NRS GATE VALVE
z
0
ti
W
w
1-
DESCRIPTION
O
z
171mUmq
so
N
r
Sit
TOTAL SPRINKLERS
THIS SHEET
\„..
0
Lo
vO
S17
If
,
tui
Ez
White
Chrome
C1_
H_
Zz
iu:
Brass
Chrome
V
W
O
tO
`O
LO
NPT
'( 1.'1 rl
1,1
4
`WcY'•:Y 1:f
"t.0 �A�' �
4.
APPROVALS BY:
ti. W
0
N
N
47713 %Y
7
()
Y
{.—i73.
■'
�pp
; L
0
c
if
�r
'1
(1
•
0
l
Py
CD
5-77.1
71
0
5
4" x 61 '-0"
@ 1 4'-6" AFF
T
WILKINS 10" 350 DAG
Vertical Backflow Preventer
4" x 1 6'-3"
E
Q)
2x 1 0" Vlctaullc #750
Butterfly Valve
m
2
'O»
'QFF
4" ReliableModel "G"
Riser Check Valve
I O" Flange
4. @ 11-2" AFF
\ FF @ 0'-0"
I O" D.I.
C@ -4'-O"±
System T2 Riser Assembly Detail
N.T.S.
-00
@ 1 5'-6" AFF
4"x5"-
'. @ 131-6"
4. @ 2'-0" AFF
West Sprinkler
Riser Room ,no
10" x 8..�I
Grooved RC
10"
@ 2'-0" ALT
T
S
4 7, ---NRS GATE VALVE
z
0
ti
W
w
1-
DESCRIPTION
O
z
171mUmq
so
N
TOTAL SPRINKLERS
THIS SHEET
TEMP.
0
Lo
vO
1550
tui
Ez
White
Chrome
C1_
H_
Zz
iu:
Brass
Chrome
V
W
O
tO
`O
LO
NPT
NN
APPROVALS BY:
ti. W
0
N
N
z
H
Jec
SPRINKLER HEAD LEGEND :
Reliable Model G4A Concealed Pendant
Reliable Model Fl FR Recessed Pendant
rn
O1-6
•�
t <
U
4) Lod -
(1)
a
+NJ}
113
O wC4tstt)
aci
w z
A�L�
V/ o
co)o Z
e 4 z N
as
z
0
1"
(.3
••• • w
•••e
••••
•••• a
••••
•••• E
ft
••••
License No:
10910 117TH Place N.E.
COSCOFP 110NM
0, ix)
C -
COX
C°
N •
C N
d CO
�,
K2 (NI0
U
E
0
U
0
U
0
U
SAN DIEGO • LOS ANGELES • FRESNO • SAN FRANCISCO • SACRAMENTO • PORTLAND • SEATTLE • ANCHORAGE
CONTRACT WITH:
DRAWING TITLE
Clarks: Hydraulic Calculation Pian
DATE: June, 2008
SCALE: As Noted
DRAWN BY: Justin Johnson
JOB NO.
25 KS - 7958
SHEET NO.
FP 2
F4L. CO
FIRE
TUKWII,A
SHINGT N
SHEET INDEX
NERAL NOTES
SYMBOLS LEGEND
SHEET \UV3ER
SHEET TITLE
W
fin
O
ON
ON
00
cV
'0'
O
(J
><
LL
SYSTEIV I \ FO. V
AT10 \
FA -02
TYPICAL DETAILS - WRI\G A\D
FA -03
FI E ALARIV
YSTEV
SYSTE V
OU\TI\G
FLOC PLA\
CALCULATIO\S (cE\EAL), -ISER, SITE PLA\
1
0
x
0
N
Without Comm?nts
As
Notact In R, tad
(nese
Prevention,:_,:
standard::.
omissions \,",'„
stanac„c: a ,rr ,•
Adrlitic.>; '
t..
resu'brt-Iltt:41 nt 'r
NO` ICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate mt.'. t be presented
to the prior to
commen� : >;" .,,_-;.ceptance
Testing
arl::i �. _.......
Faiiure of
ink-iEkR;
termination
Fir13 aCCC,"p'',''1';
Th
I UKWILA FIRE DEPARTMEil'Y
Pease call: 575-4407
:end
give this job
and exact address for shut.
.own or restoration approval;
WIRE DESIGNATION SCHEDULE
WIRE SCHEDULE AND CONDUIT FILL CHART
WIRE DESIGNATION
SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE
D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET)
H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET)
P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET)
S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
2S STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET)
A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET)
V SPEAKER CIRCUIT - FEED TWISTED PAIR 1#14 FPL/FPLR RED (JACKET)
2V SPEAKER CIRCUIT - RETURN TWISTED PAIR 4#14 FPL/FPLR RED (JACKET)
I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET)
X LOW LEVEL AUDI❑ TWISTED PAIR W/ SHIELD 4#16 FPL/FPLR RED (JACKET)
UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET)
UI UNDERGROUND INITIATION TWISTED PAIR RATED 1#18 FPL/FPLR RED (JACKET)
M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET)
B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET)
.!JUNCTIDN BOX
II
I CONDUIT FILL CHART
11;
NO.
OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA
I; TWO 600V #12 AWG THHN/THWN .244 O.D. .0467
I TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346
.TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191
1
CONDUIT FILL
CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE
ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM
THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE.
CONDUIT SIZE MAXIMUM FILL
1/2" .12 SQUARE INCH
i 3/4" SQUARE INCH
1" .34 SQUARE INCH
1-1/4" .60 SQUARE INCH
1-1/2" .82 SQUARE INCH
2" 1.34 SQUARE INCH
FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4.
SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END
FOR SIEMENS SYSTEM:
�
DO NOT INSTALL ADDRESS JBLE NITIATING DEVICES UNTIL PREPROGRAMMED WITH
DEVICES ADDRESS.
1. NUMBERS ADJACENT TO DEUCE $YvIBOL DENOTE DEVICE CIRCUIT/ADDRESS
DEVICE 01-1-02 WOULD BE;,;THE SECOND DEVICE ON ADDRESSABLE LOOP 1.
2. DETECTOR AND AUDIBLE CIRCUIT , P LARITY SHALL BE OBSERVED.
3. AUDIBLE/VISUAL CIRCUIT WIRING IIS
BRANCHING IS PERMISSIBL
4. INSTALLATION SHALL BE IN . §TRICT CONFORMANCE WITH THE NATIONAL
ELECTRIC CODE, NFPA 72, LOCAL . CODE(S), AND/OR AUTHORITY HAVING JURISDICTION.
5. INSTALLATION MATERIALS (iv, CON',UIT, WIRE, FITTINGS, HANGERS,
STANDARD BOXES, FIBER OP; ICS' CBLE, FITTINGS, AND ASSOCIATED EQUIPMENT)
ARE NOT SUPPLIED BY SIEM NS C �BERUS DIVISION.
6. DETECTORS SHALL NOT BE OUNTED IN DIRECT
AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1
7. WIRING SHALL BE PER PLAN ,WITH; RIESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY,
TYPE, QUANTITY AND COLOR ;CODE.I1 CONDUCTORS SHALL BE PERMANENTLY,
AND UNIQUELY v1ARKED FOR: FUTURE IDENTIFICATION.
8. INSTALLING CONTRACTOR SHALL 'RETURN ONE SET OF ACCURATELY MARKED
DRAWINGS FOR "AS BUILT" PURPOSES.
� 1I
9, FOR ADDITIONAL INSTALLATIC I IN ;.RUCTIONS, REFER TO CATALOG CUT
SHEETS AND/OR INSTALLATION .IN TRUCTIONS.
10. THE 120vac POWER ELECTRI. AL WO,RK SUPPLYING FIRE ALARM SYSTEM PANELS
MUST COMPLY WITH ARTICLE,1725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72,
SPECIFICALLY SECTION 1-5.25.2: I, REFERENCE TO DEDICATED BRANCH POWER
SOURCES. 120vac POWER SHALL N T BE APPLIED TO FIRE ALARM PANEL WITHOUT
DIRECT SUPERVISION OF FIRM AFAR TECHNICIAN.
11. ALL HORN/STROBE AND STOBE ;DEVICES SHALL BE MOUNTED AT A HEIGHT
OF 80" A.F.F. OR 6" BELOW!DROP 'ED CEILING WHICHEVER IS LESS.
12. ALL MANUAL PULL STATION. SHALL BE MOUNTED AT 48" A.F.F. TO THE
QUANTITY
SYM
I ESCRIPTION
MODEL
MANUFACTURER BACKBOX
MOUNTING HEIGHT
FACP
SUPERVISED. NO PARALLEL
l TIRE ALARM
EX• NTROL PANEL
IRE ALARM
REMOTE ANNUNCIATOR
FARA
XLS-V
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
SIEMENS
PROVIDED
66" A.F.F.
TO TOP
2
ACTIVATION DEVICE.
13. ALL PANEL NUMBERS AND ;IRCUITL WILL BE ON THE RECORD DRAWINGS SET.
14. ALL 120VAC CIRCUITS ARE ROMA liEDICATED CIRCUITS FROM THE EMERGENCY
GENERATOR.
15. PER NFPA 72 SECTION 5-3 6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER
THE CONSTRUCTION CLEAN-UP OF;; ALL TRADES IS COMPLETE AND FINAL.
EXCEPTION: WHERE REQUIRED BYI THE AUTHORITY HAVING JURISDICTION
FOR PROTECTION DURING CONSTRUCTION.
DETECTORS THAT HAVE BEE\ INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL
TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72
CHAPTER 7.
,NTERFACE MODULE HTRI-R
PITH RELAY
SIEMENS
4S DEEP
VERIFY
IN FIELD
QUAL INPUT
NTERFACE MODULE
HTRI-D
SIEMENS
4S DEEP
VERIFY
IN FIELD
HCP
SIEMENS
4S DEEP
VERIFY
IN FIELD
HZM
REMOTE CONVENTIONAL HZM
,ZONE MODULE
!NEAR BEAM
SMOKE DETECTOR
16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT
AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR
OTHER BACK BOXES OF DIFFERENT CIRCUITS.
17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND
AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO
FINAL EQUIPMENT TRIM. :
18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A
PERMANENT LABEL AT ALL .DEVICES, JUNCTION BOXES AND FACP.
' I
19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE
OUTSIDE AND INSIDE OF THE FIRE: ALARM BACK BOXES 'AND JUNCTION BOXES
AFTER COMPLETION OF THEIR INSTALLATION.
20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH
IT IS LOCATED.
:I
21. ' ALL WIRING BETWEEN FLOOR S• SHALL BE LOCATED IN CONDUIT.
22. NFPA 72 2007 6.4.2.2.2 ALL, STYLES OF CLASS A CIRCUITS USING
PHYSICAL CONDUCTORS (E.G:,. METALLIC, OPTICAL FIBER) SHALL BE
INSTALLED SUCH THAT THE UTGOING AND RETURN CONDUCTORS, EXITING
FROM AND RETURNING TOTE. CONTROL UNIT, RESPECTIVELY, ARE
ROUTED SEPARATELY. THE 0 TGOING AND RETURN (REDUNDANT) CIRCUIT
CONDUCTORS SHALL NOT BEI RUN IN THE SAME CABLE ASSEMBLY (I.E.,
MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY.
23. 1
NFPA 72 2007 A.6.4.2.2.2 fo\ GOAL OF 6.4.2.2.2 IS TO PROVIDE
ADEQUATE SEPARATION BETWEEN THE OUTGOING AND, RETURN CABLES.
THIS SEPARATION IS REQUIRb TO HELP ENSURE PROTECTION OF THE
CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM
SEPARATION TO PREVENT PHYSICAI4 DAMAGE IS 305 .MM (1 FT) WHERE
THE CABLE IS INSTALLED VETICALII.Y AND 1.22 M (4. FT) WHERE THE
CABLE IS INSTALLED I
1
2
3
EX
MOKE DETECTOR
ADDRESSABLE -PHOTO)
SIEMENS
4S DEEP
VERIFY
IN FIELD
PBA -1191 SIEMENS
HFP-11 W/ SIEMENS
DB -11 BASE
PROVIDED
4S DEEP
W/ 1G RING
VERIFY
IN FIELD
CEILING
DUCT SMOKE
!' ETECTOR
EAT DETECTOR
ADDRESSABLE)
FIRE ALARM
SPEAKER STROBE
,C ; r (CEILING MOUNT)
AD2-P W/ SIEMENS
TSM MODULE
DUCT HOUSING
VERIFY
IN FIELD
HFPT-11 W/
DB -11 BASE
SIEMENS.
SET -MC -CW SIEMENS
4S DEEP
W/ 1G RING
CEILING
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
IRE ALARM
PEAKER STROBE
(WALL MOUNT)
SET -MC -W SIEMENS
4S DEEP BOX 80" A.F.F.
W/ 1-1/2" EXT. TO BOTTOM
IRE ALARM
'SPEAKER STROBE
(WALL MOUNT)
SET -HMC -CW SIEMENS
4S DEEP BOX
W/ 1-1/2" EXT.
CEILING
FIRE ALARM
L '
C, ';(CEILING MOUNT) STROBE
ZR -MC -CW SIEMENS
4S BOX
W/ 1G RING
CEILING
IFIRE ALARM
.(WALL MOUNT)
LR -MC -W SIEMENS •
4S BOX
W/ 1G RING
80" A.F.F.
TO BOTTOM U.O.N.
�! TIRE ALARM
,I PEAKER
;;(CEILING MOUNT)
SET -CW SIEMENS
4S DEEP BOX CEILING
W/ 1-1/2" EXT.
';FIRE ALARM
.SPEAKER
•• WALL MOUNT)
SET -W
SIEMENS
4S DEEP BOX
IN/ 1-1/2" EXT.
80" A.F.F.
TO BOTTOM
I1FIRE ALARM
B STROBE
WP, (WEATHERPROOF)
SET -S17 -WP SIEMENS
MT -SUR -BOX VERIFY
1/2" PIPE
IN FIELD
MRI
MULTI -VOLTAGE
:.CONTROL RELAY
MR -201 /C AIR PRODUCTS 4S BOX
VERIFY
IN FIELD
MAGNETIC
DOOR HOLDER
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
FA JB❑X
FIRE ALARM
1TERMINAL CABINET
F.B.O.
F.B.O.
F.B.O.
VERIFY
IN FIELD
d
RED
'
.!JUNCTIDN BOX
II
F,B,❑,
F.B.❑,
N/A
VERIFY
FIELD
A,FF,
AB❑VE FINISHED
FL❑❑R
I
N/A
N/A
N/A
N/A
F B❑FURNISHED
.OTHERS
BY
N/A
N/A
N/A
N/A
N
A
IN❑T
APPLICABLE
N/A
N/A
N/A
N/A
U.❑
N.
UNLESS OTHERWISE
NOTED
N/A
N/A
N/A
N/A
W
'.WEATHERPR❑❑F
.;DEVICE
N/A
N/A
,
N/A
N/A
,As BUILT
ADD OR CHANGE
N/A
N/A
N/A
N/A
AS BUILT
GR EN ,I EM❑VE
N/A
N/A
N/A
N/A
BLUE
AS BUILT
:f❑TES TO CAD
N/A
N/A
N/A
N/A
Copyright 2006 by Guardian Security Systems, Inc. All Rights
tt
eserv
RELEASE/REVISIONS
LD
LLI
cr
DESCRIPTION
SHOP DRAWINGS
LLI
0
tn
LE
as
co
co
CCI -
(0
0
DRAWN BY:
LANDERSON
DESIGNED BY:
R.VEZZANI
BACKROUND PLAN PROVIDED BY:
NUMBp: 54499
SHEET
FA -01
H:
THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72.
THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX
DUCT WIDTHS !FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED.
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OPERTIN TEMPERATURE:
+32' F (0' C) TO 100' F (38 C)
HUMIDITY: -9 % RELATIVE HUMIDITY,
NON -CONDENSING
NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION.
OUTLET SAMPLING-----\.
TUBE
FRONT VIEW
HFP-11 SMOKE
DETECTOR
DEVICE IS LISTED FOR AIR VOLOCITY
APPLICATIONS OF 300-4000 FT/MIN
WHEN USED IN CONJUNCTION WITH
DUCT HOUSINGS AD -11P OR AD-11XPR
DB -11
STANDARD
SMOKE
DETECTOR
BASE
ANY DUCK OVER 3' WIDE, SAMPLE TUBE
MUST GO THRU THE DUCT AND BE CAPPED.
INLET SAMPLING
TUBE
NOT USED
REMOTE
DEVICE LOOP
NOT USED
REMOTE
DEVICE LOOP
470
OHMS
�1V
EOL
AT LEAST
SIX DUCT
WIDTHS
FROM BEND
--›-FROM PREVIOUS
ADDRESSABLE DEVICE
OR POWER SOURCE .
TO NEXT DEVICE -C---!!
6-10 DUCT
EQUIVALENT
DIAMETERS
DUCT DETECTOR
LOCATI❑N
REAR VIEW
DATA IN (-) >---
DATA IN (+) >
> (-) DATA OUT
i (+) DATA OUT
"
TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT
LABEL SCALE ,
FROM XLS CONTROL PANEL OR (+)>
PREVIOUS ADDRESSABLE DEVICE (-)>
TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR
SCALE=NONE
MUSIC 4 -AC POWER SOURCE
--->(+)TO
>(-) ST
EXT DEVI
IF LAS
E OR
DEVICE}
I
Ica TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL
SCALE NONE
HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL
LABEL SCALE
CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID)
COMBINE ALL SHIELDS AND
ISOLATE FROM GROUNDING
TO NEXT ADDRESSABLE DEVICE I \ l
STOP IF LAST DEVICE I�
FROM XLS CONTROL PANEL ❑R
PREVIOUS ADDRESSABLE DEVIC ---y
END OF LINE DEVICE(3.6K 1/4V))
SUPERVISED SWITCH
TO NEXT ADDRESSABLE DEVICE l(+)
STOP IF LAST DEVICE j
FROM XLS CONTROL PANEL ❑R(+)
PREVIOUS ADDRESSABLE DEVICE(-)
FROM REMOTE
POWER SUPPLY
C'S' CABLE)
TO NEXT
;ICE OR
OF LINE
HARD LID
CEILING SPEAKER SUPPORT TTI_
BRIDGE
HARD LID
( STR❑BE—)
SUPERVISED
SWITCH
RELAY CONTACTS
(4.OA 2 125VAC) GROUND
(4.0A @ 30VDC)
END O
LINE EVICE FROM FACP
3.6K 1 4W) (VOICE CIRCUIT)
C'V' CABLE)
UPER ISED
SWITCI
T
DE
E
NEXT
'ICE OR
OF LINE
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
I' •
TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL
NOTE:
FOR ADDITIONAL SPECIFICATIONS
SEE PRODUCT DOCUMENTATION.
TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL
LABEL SCALE (FIRE SUPPRESSION SYSTEM INTERFACE)
SPEAKERISTROBE AND STROBE WIRING
LABEL SCALE
4' SQUARE DEEP BOX --
WITH 1-1/2" EXTENSION
CEILING MOUNTED
SPEAKER/STROBE
CEILING MOUNTED SPEAKERISTROBE MOUNTING (DROP CEILING
SCALE=NONE
NOTE 1:
VOLTAGE MAX. -
CURRENT MAX,-
CONT. RES, MAX, -
MAX, CABLE LENGTH -
C CLINE TO LINE) -
C CLINE TO SHIELD) -
MAX, LINE SIZE -
MIN, LINE SIZE -
27 VDC
3.5 mA DURING POLLING
10 OHMS
200 FT. (18 AWG)
0,02uF
0.O4uF
14 AWG
18 AWG
0
GND N AC
NOTE 21
ALL SUPERVISED SWITCHES MUST BE HELD CLOSED
AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE
DETECTION,;
'SPEAKER STROBE
OR STROBE ONLY
4S DEEP BOX
w/ 1-1/2"
EXTENSION RING
(SPEAKER STROBE)
4S BOX
(STROBE ONLY)
m 6 B 0 o o
123456
INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX
1+1-'1 2+2- 2 NC C NO + - + - + - + - + -
80" A.F.F.
JUNCTION BOX
MOUNTED ON
CEILING, FLEX
JUNCTION BOX
MOUNTED AGAINST
CEILING SUPPORT
4%,
/
/
/
/
r
SMOKE DETECTOR
SMOKE DETECTOR MOUNTING
SCALE=NONE
O O
TO NEXT DEVICE
CADDY BAR
SUSPENDED
ILLUMINATED
I±I
SPEAKER/STROBE
TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP)
LABEL SCALE
WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS
SCALE=NONE
DO \OT I\STA_L
ADDRESSABLE SR TAT
DEVICES „STI_
PREPROGRAMMED WIT
DEVICES ADDRESS.
rn
z
0
LLJ
LU
LU
J
LU
REV. BY:
z
a
DESCRIPTION
SHOP DRAWINGS
DATE
0
N
N
Ln
o
aaaaa
CO
CO
J T
J
2 z
W Q
ZZ
CC Uu
s�¢
E illO
1.1. (O
F—
Er
KALE: 1/8"=1'
DRAWN BY:
I.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE:5/20/08
BACKROUND PLAN PROVIDED BY:
`JOB NUMBER:54499
SHEET
Copyri• ht
2006 b Guardian Securit S stems, Inc. All Ri. hts
I •
I
ID
:; I
D
C\2
toL
2S,2V
2S,2V
L.
TE:,.A.r1
0
-CO
L.
12'-0"
AFF
NORTH
CLARKS WESTFIELD SOUTHCENTER MALL
SCALE 118'=1'
LAG NO
FIELD LOCATE RELAY MODULE FOR
BACK GROUND MUSIC INTERFACE.
FIELD LOCATE SIEMENS DUCT
DETECTOR ON RETURN SIDE OF
ALL VAV UNITS.(SEE SIEMENS
INSTALLATION SUBMITTAL FOR
LOCATION GUIDELINES AND FA -02)
DEVICES SUPPLIED BY GSS,
INSTALLED BY MECHANICAL
CONTRACTOR,
WIRED BY ELECTRICAL
CONTRACTOR.
SIEMENS HTRI-D ADDRESSABLE
INPUT WITH HOOD VENILLAT❑R
FIRE SUPPRESI❑N SYSTEM, FIELD
LOCATE WITHIN 3 FEET OF
C❑NTRL PANEL.
FIELD LOCATE SIEMENS PAD -3
BOOSTER POWER SUPPLY FOR
STROBE POWER, AC POWER BY EC
FROM DEDICATED, LOCKED OUT
20A, 110 VAC BRANCH CIRCUIT.
DO NOT I\S�,LL
ADDRESSABLE D N TIS
DEVICES URI I_
PREPROGRAMMED W
DEVICES ADDRESS.
z N
o .'0
cp
z
Q Q,
v_i
F-
<
O ,p
cn
. N
W •
a
- o
U) N
N -I;.
fh
Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserv;
REV. BY:
Z
4
DESCRIPTION
SHOP DRAWINGS
DATE
CO
0
N
cV
in
o
<a<aa
co
co
J'—
00
2 Z
W 0
�'-czz
CC 2 ucp
C3 Q
W
�o�
it(0
F-
V.
SCALE: 1/8" =1 '
DRAWN BY:
(.ANDERSON
DESIGNED BY:
R.VEZZANI
DATE: 5/20/08
BACKROUND PLAN PROVIDED BY:
V.013 NUMBER:54499
SHEET
FA -03
•
;
5
re:
IZCt\I 'Oil E
IN V+1ASHINGTON
N„z
IR/I,SH
rJ
wTi M
1.,
, •
t
f)
1\1 ALI_
OFFICE
0.
(-1
(1-)
w
C.)
J ,"-; M E A
JUICE
THE PICTURE
PEOPLE
A 13 R ($/11.----:: I E
I
I'
1 505
1550
if)
1
CLARKS WESTFIELD SOUTHCENTER MALL
IL]]
1;1 54-1,2,
SEA TTL E_
MARI NI ER S
TEAM 3HOP
IFI
\
.;
:11.2
-1 IR A ‘.'"..`I•i! I. r•
•• • arr
----• (13 11
P I ("LJN IEI AR
E WALK I I`•,1
r 1 00 1
r
bebe
1 11 0
1115
1 5,35 I
15!)0j
0
1 11;
;
>--
SCALE 1132"4
75 C 75 C 15
15
15
15
2S,2V
0
D
D
EX
D,I
21
1r
SYSTEM CALC LATIONS
M
HL
CLARKS
CLARKS
FACP ADD ONS
SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations
COrrent Load:
; •
Standby:
Alarm:
CU rent Load:
Standby:
Alarm:
Total
0.030
Dice Type
HF,P-11
A2 -P
'
Qty
1
2
Amps
0.0022
0.0635
0.009600
0.001600
0.005
Total
0.0022
0.0635
0.0096
0.0731
Amps
0.0023
0.064
0.021
0.0035
Amps
Total
0.064
0.042
0.106
Amps
14
I,11;
!!,
1 :1
•
Standby Current Load:
1
0.0731
Amps
For 24 Hours =
1.754
Amp -hours
Alarm Current Load:
;
0.106 Amps
Total System Current Load:
Battery Pair to be Used:
12VDC
For 5 Minutes=
25% Derating=
Amp -hours
0.009
2.204
2.204
7AH
Amp -hours
Amp -hours
Amp -hours
11
;1' , •
Deice Type
Main System Board
STMC @15CD
.SE -MC @30CD
SE -MC @75CD
SE -MC@110CD
S -HMC-C@115CD
S T-HMC-C@135CD
S ll-HMC-C@185CD
ZR MC 61ECD
ZR MC @30CD
H p
St
ndby Current Load:
Alarm Current Load:
Battery Pair to be Used:
Qty
1
3
2
1
0.03
0.636
Amps
0.03
Amps
Amps
Total System Current Load:
12VDC
Total
0.03
0.03
For 24 Hours =
For 5 Minutes=
25% Derating=
Amp -hours
Amps
0.030
0.064
0.098
0.175
0.233
0.318
0.318
0.445
0.064
0.098
0.0015
Amps
0.720
0.053
0.967
0.967
7AH
:1 11
• I
0.350
17.H..
0.064
0.636 AM
Amp -hours
Amp -hours
Amp -hours
Amp -hours
l;
!I ,
•
'4,faat&
I
• :1::
. 1 t
'
BATTERY SIZI
Notification Appliance
PROJECT: WESTFIELD SOUTHCENTER MALL
Panel: CLARKS
Date: May 22, 2008
CIRCUIT:
QTY
0
2
0
0
0
0
1
DEVICES=
S1
Device Type
SET -MC @15CD
SET -MC @30CD
SET -MC @75CD
SET -MC @110CD
SET-HMC-C@115CD
SET-HMC-C@177CD
SET -HMC @135CD
SET -HMC @185CD
Z-MC@15CD
Z-MC@30CD
Aiarm Current Alarm Total
64 192
98
175
SET-MC-CW@110CD
6
233
318
445
318
445
64
98
233
0
350
0
0
0
0
Wire Size
CALCULATION
it Detail
Wire Resistance 1.62
606
RRENT TOTAL=
VVir Lenth
Voltage at EOL
Circuit Total
Total Wire Resistance ( R )
( WL* )* (ft)
Total lDevice Load, Amps (I)
(Total Cct Load)
Voltage Drop ( E)
64
TOTAL mA=
PROJECT.
Panel:
Date:
CIRCUIT:
QTY
5
0
606
12
--m65
Notification Appliance
WESTFIELD SOUTHCENTER MALL
CLARKS
May 27, 2008
19 8796884
ircuit Detail
6061
(E= 1* R)
EOL Voltage
(20.4 - E)
0.86
0.61
0.52
19.88
Wire Resistance ,2.66
PURrZENT TOTAL= 9
1 •
VVire eirl-n•FrIgt .--VO-Itage at EOL Circuit Total
SPEAKER CIRCUIT
Device Type Alarm Current
70.7V1/8 1.8
0
0
0
0
0
0
0
0
0
0
Alarm Total
9
0
• 0
0
Wire Size
DEVICES= 5
TOTAL mA=
0
0
0
0
0
9 14
Total Wire Resistance(R) 2.92
( WL * 2 )* (Rift)
Total Device Load, Amps (I) 0.01
(Total Cct Load)
Voltage Drop ( E) 0.03
• (E= I * R)
EOL Voltage • 20.37
(20.4 - E)
20.37376141
DRAWN BY:
LANDERSON'
DESIGNED BY:
R.VEZZANI
DATE: 5/20/08
BACKROUND PLAN PROVIDED BY:
RISER DIAGRAM
r1-
1515
I
•
VOLTAGE DROFt CALCULATION
••1
Copyright 2006 by Guardian Security Systems, Inc. All Ri hts Resery
\0B NUMBER:54499
SHEET
FA -04J