HomeMy WebLinkAboutPP - 231 SOUTHCENTER MALL - BATH & BODY WORKS - PERMITS AND PLANS231 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-451 08-S-443 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Bath & Body Works 231 Southcenter Mall Permit No.: 08-S-443 Date: September 3, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. 1JF _0 i n c & : r5 IIr 29 August 2008 John Abel Crown Fire Protection PO Box 12113 Mill Creek, WA 98082-0113 Tuazon Engineering, PLLC 4322 NE r Street Renton, WA 98059 425.917.1683 tel 425917.1705 fax www.tuazon.com RE: Westfield Mall — Bath & Body Words (#231) Independent Third Party Review — Fire Sprinkler System Dear John: As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. The following was reviewed: • Fire Sprinkler Drawing — Sheet 1 of 1 dated 8/26/08 The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. The system shown has been designed using the Ordinary Hazard Pipe Schedule method per 2007 NFPA 13 Para 23.5.3. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Include applicable product data (i.e. new sprinkler heads) with the permit submittal to the City of Tukwila. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or eric(tuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING, PLLC )1"tx?---- Enc P. Tuazon, PE Fire Protection Engineer Weartpsyiis. 0a Pigd62005A0 Gem R-WsY18ii.08.0231 1 nat*MY*mwAx WATCHED AREA INDICATES NON–ACCESSIBLE SPACE ABOVE TOILET ROOM AND DM OFFICE –6" 10'-2 3/4" OPEN GYP. BD. PT -5 GYP. 8D. TO DECK 16'–q" SERVICE CORRIDOR (N.LC.) ADJACENT TENANT. IN,LC.i FOCAL HALL, DONNLIGHTS, TRACK LIGHTS, * DIFFUSERS q'-7 I/4"J GYP. HD. GYP. BD. DISPLAY C#BINET TRACK LIGHTS, --- U .N. IGHTS,U...N. RETAINER STRAP WHERE REQUIREP IN SEISHIC AREAS TOP BEAR/ C-CLAHP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING 1l11l■■l z,.7 iiiiiiiiiii�iiiiiiivii�iiiiiii� � J –( ,J_i . _i ./ •7.:7Z fEs_ic.:,r17f� s:: FILE COPY SHEET INDEX SHEET NUM3ER SHEET TITLE BATH AND BODY WORKS FIRE A ARM SYS EM TUKWILA, WASHINGTON FA -01 SYSTEM I\FORMATIO\ FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FRE ALA R\A SYSTE vl FLOOR PLAN FA -04 SYSTE V CALCULATIONS (GENERAL), MISER, SITE PLAN r".'3j. .. i.. Fire .11 city cti : dopted !Cr the !r!gs alter I gauue a leSu r r.,`t: -1 t ; approval. Final acccpte-ice i^ !!t' ect to in irj test and inspection bl h:3 Tu'kvilia Fifa Prevention Bureau. t Date: 9-a-08 By: J J ( it 4 1 ruKWILA FIRE DEPARTMEI`'ft Please call: 575-440Z and give this job No. 02 - F and exact address for shut. ,„Km or rastaration approved: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and `,rninlinnof the testing. � 9 u�.-na...,� n :d a tsa 2 ecause of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-5754407 to schedule your inspections a minimum of 43 hours in advance of the date you want ari inspection. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 7 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP 111 INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IFC LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ISI SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE F C (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD E1 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTION BOX F.B.O. F.B.D. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright PAID SEP 10 2008 Tukwila Fire 2006 by Guardian Security Systems, Inc. All Rights Reserved 1.0 CO 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 9/08/08 2 CCCCa co co O §z°1 FEJ 0c"zz L) 2 WI Zoo- Q 1L co- Z N= I7 Q W (1) 0, (S.-CALE: 1/8"=1' Z 0 0 ILZ DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/08/08 BACKROUND PLAN PROVIDED BY: .0B NUMBER: SHEET k FA -01, THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIC 0 DUCT DETECTOR LOCATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH r GROUND 0 N) 0 HTRI-R OSTATUS LED co 0 N.O. 0 0 COM N.C. ' • NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABELSCALE(BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE{ DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1: VOLTAGE MAX. - CURRENT MAX, - CONT, RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING 0 TO NEXT ADDRESSABLE DEVICE f( STOP IF LAST DEVICE `(-) FROM XLS CONTROL PANEL OR 1(+) PREVIOUS ADDRESSABLE DEVICE LA RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,o2uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. 0 J La 01 TB1 5`50000 123456 HCP TB2 00 6543'2 1 0 END OF LINE DEVICE (3.6K 1/4W) SUPERVISED/ j SWITCH / GROUND 0 0 0 et - LC) © © 0 HTRI-D OSTATUS LED CO NOT USED 0 0 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL seLE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC minim T to 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE �(33.6K 1/4W) `-6UPERVISED SWITCH NAC -4 NAC -3 NAC -2 NAC -1 NOTE: FOR ADDI11ONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP T. NOT USED REMOTE DEVICE LOOP !� 0 0. 0 0 0— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �N1 EOL 0 TC INPU Q 9 9 TSM -1 O 0 • • • TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE EARTH GROUND -30.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE HORN STROBE / STROBE WIRING DIAGRAM LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 0 HORN/STROBE 14S DEEP BOX w/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE EOL NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERPTIN TEMPERA RE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: O-9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE HARD LID 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX--\ MOUNTED ON \ CEILING. FLEX / / JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0�r� 1 TO NEXT DEVICE 00 CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS CO LLJ h- 0 Q Q O rn 2 CCaaa z 1— z 0 co co z O 7.1c73 r MZ c) ,� 0 u) J =Q Q �i Z wok T � = N -� Q � CO 0 "GALE: 1/8"=1' 0 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/08/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: SHEET FA—O2,, EOL - 19.73 51' 3 F:.. TO FAC? cO �S✓' /SN -h ii TO :ACP ZONE . O FAC' 1 11 ' a r v 10 BE CONVECTED/TIED—!N TO THE =.AAL_/EUILO!NG F!RE AL4P14 SrSTEu P.ELD VER:FE AND COORDINATE ALL RELATED REOUIPEuENTS PRIOR TO DID ==yiaNJ W-311 C0 NCEMGNT R• 0 jj � a II ;J I II A r :r ir ,r 1 II " is J N t - TOar_CPa —JL— JL J JL_ _JL J' 'L J 2S n 5 •�o 1 n e f J 1. tl : I1 .i u 7l5 Lri .0 FACP LS V __TO FACP ZONE 3 � V, ..:l 'O FACP TO FACP ZONE 4 EX Cs) { A�'�J NORTH TO FACP ,u• 75 2 S ---m I r,3 TO FACP ZONE 3 BATH AND BODY WORKS VESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 1 NVI DESCRIPTION SHOP DRAWINGS DATE 00 0 co 0 \ 0, w co O --'r J 2 2z >- Wo ocnzz O 2 LT -1 CO g=Q < Z T = N� F- CO 1 11J F1i W �CALE: 1/8" =1 ' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:9/08/08 BACKROUND PLAN PROVIDED BY: J.OB NUMBER: SHEET FA—O3, LL...JYVY1YVYVY1- ESFRESSO J.C. TR A Cr) 0 M. ELEC I! ELEC �! BEN BRIDLE. JEWE_ERS PAR~UMERIE SUNC0AST MOTION PICTURE WALDENBOOKS NORTH CINGULAP (f)I 1) 01 - L;) VICTORIAS 0 W W z CO 0 CASUAL CORNER PETITE SOPHISTICATE GODIVA CODIVA AVON AVON P \i C LRANK SUN CLASS DESIGN BIAGIO VERIZON WIRELESS kt ADE IN WAST-IICTONN SPENCER GIFTS SII I,TR� Y tifk:11Tij. MALL OFFICE ETZ:s W W 0 m 0 `LEC!kiL MALL OFFICE COMPANY SYSTEM CALCULATIONS NATURALIZF_R JAMBA JUICE THE PICTURE PEOPLE ABERCROMBIE 111 IIIN a BATH AND BODY WORKS WESTFIELD SOUTHCENTER MALS PARFUMERIE 1025 BATTERY SIZING CALCULATION SCALE 1132 30 2S 75 2S 15 2S 15 2S 75 2S 75 2S 15 2S 110 EOL -S1 19.73V 2S EX D D,ID 2I RISER DIAGRAM PROJECT: Panel: Date: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL BATH AND BODY WORKS September 9, 2008 CIRCUIT:: S1 QTY Device Type 2 'ZH-MC @15CD 1 ZH-MC @30CD 3 IZH-MC @75CD 1 1ZH-MC @75CD 0 0 0 1 0 Z-MC@15CD 1Z-MC@30CD DEVICES=!8 Wire Resistance 1.62 CURRENT TOTAL=1356 ;Alarm Current Alarm Total ' Wire Sian ; Wire Length Voltage at EOL 1081 2161 142 142.. 2191 _.._.,....__._.657, 277 2771 0 641 98 I TOTAL mA=I 1356; 12 1 138 0 01 o1 64 • Circuit Total Tota lW i re Resistance (R ) (WL*2)*(R/ft) 0.45 Total Device Load, Amps (I) 1.36 (Total Cct Load) Voltage Drop (_E) 0.61 (E= I * R) EOL Voltage 19.79 (20.4 - E) 0, 19.79370528 1356 PROJECT Pane Date: CIRCUIT:iS1 QTY 1 IZH-MC @15CD 0 1ZH-MC @30CD 1ZH-MC @75CD Notification Appliance_ Circuit Detail WESTFIELD SOUTHCENTER MALL APPLE S1 September 9, 2008 Wire Resistance 1.62 CURRENT TOTAL=1893 Device Type ,Alarm Current) Alarm Total 1 Wire Size 1 Wire Length 3 10 0 0 0 2 =Z-MC@15CD 0 1Z-MC@30CD DEVICES=16 108 1421 2191 108` Voltage at EOL Circuit Total Total Wire Resistance (R ) 1.61 0 6571 i 0 0 0 01 0` 641 1281 98 01 TOTAL m A= 8931 12 I 497 1 (WL*2)*(R/ft) Total Device Load, Amps (1) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.89 1.44 18.96 18.96201996 893 _L_ VOLTAGE DROP CALCULATION rte) co 0\ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: BATH AND BODY WORKS BATH AND BODY WORKS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION SHOP DRAWINGS DATE I. 9/08/08 2 aCCCC Current Load: Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R HTRI-D 2 0.009600 0.0096 0.021 0.042 ZH-MC-CW @15CD 2 0.108 0.216 0.001600 0.0035 ZH-MC-CW @30CD 1 0.142 0.142 ICP -B6 0.005 ZH-MC-CW @75CD 3 0.219 0.657 ZH-MC-CW @110CD 1 0.277 0.277 0.0731 Amps 0.106 Amps ZR -MC @15CD 1 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD 0.098 HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 1.386 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 1.386 Amps For 5 Minutes= 0.116 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 1.046 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 1.046 Amp -hours 1 Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION SCALE 1132 30 2S 75 2S 15 2S 15 2S 75 2S 75 2S 15 2S 110 EOL -S1 19.73V 2S EX D D,ID 2I RISER DIAGRAM PROJECT: Panel: Date: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL BATH AND BODY WORKS September 9, 2008 CIRCUIT:: S1 QTY Device Type 2 'ZH-MC @15CD 1 ZH-MC @30CD 3 IZH-MC @75CD 1 1ZH-MC @75CD 0 0 0 1 0 Z-MC@15CD 1Z-MC@30CD DEVICES=!8 Wire Resistance 1.62 CURRENT TOTAL=1356 ;Alarm Current Alarm Total ' Wire Sian ; Wire Length Voltage at EOL 1081 2161 142 142.. 2191 _.._.,....__._.657, 277 2771 0 641 98 I TOTAL mA=I 1356; 12 1 138 0 01 o1 64 • Circuit Total Tota lW i re Resistance (R ) (WL*2)*(R/ft) 0.45 Total Device Load, Amps (I) 1.36 (Total Cct Load) Voltage Drop (_E) 0.61 (E= I * R) EOL Voltage 19.79 (20.4 - E) 0, 19.79370528 1356 PROJECT Pane Date: CIRCUIT:iS1 QTY 1 IZH-MC @15CD 0 1ZH-MC @30CD 1ZH-MC @75CD Notification Appliance_ Circuit Detail WESTFIELD SOUTHCENTER MALL APPLE S1 September 9, 2008 Wire Resistance 1.62 CURRENT TOTAL=1893 Device Type ,Alarm Current) Alarm Total 1 Wire Size 1 Wire Length 3 10 0 0 0 2 =Z-MC@15CD 0 1Z-MC@30CD DEVICES=16 108 1421 2191 108` Voltage at EOL Circuit Total Total Wire Resistance (R ) 1.61 0 6571 i 0 0 0 01 0` 641 1281 98 01 TOTAL m A= 8931 12 I 497 1 (WL*2)*(R/ft) Total Device Load, Amps (1) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.89 1.44 18.96 18.96201996 893 _L_ VOLTAGE DROP CALCULATION rte) co 0\ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE I. 9/08/08 2 aCCCC co co J '_ -J ay W 2z wO w� (3 Zz CC 0 co � W= <C Q CCo_j C) CCO 1 - J 0 w w CO CC CC w w z 0 E-- 0 W >- �CALE: 1/8" =1 ' Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZAN I DATE:9/08/08 BACKROUND PLAN PROVIDED BY: t0B NUMBER: ( SHEET FA -04} 231 SOUTHCENTER MALL ASSOCIATED PERMITS 08-F-451 08-S-443 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Bath & Body Works 231 Southcenter Mall Permit No.: 08-S-443 Date: September 3, 2008 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All references are NFPA 13, 2007 Edition. 1JF _0 i n c & : r5 IIr 29 August 2008 John Abel Crown Fire Protection PO Box 12113 Mill Creek, WA 98082-0113 Tuazon Engineering, PLLC 4322 NE r Street Renton, WA 98059 425.917.1683 tel 425917.1705 fax www.tuazon.com RE: Westfield Mall — Bath & Body Words (#231) Independent Third Party Review — Fire Sprinkler System Dear John: As requested, I have performed an Independent Third Party Plan Review on the fire sprinkler system for the above referenced project. The following was reviewed: • Fire Sprinkler Drawing — Sheet 1 of 1 dated 8/26/08 The documents were reviewed for compliance with the 2007 NFPA 13, Installation of Sprinkler Systems and Tukwila Municipal Code Chapter 16.42, Sprinkler Systems. The system shown has been designed using the Ordinary Hazard Pipe Schedule method per 2007 NFPA 13 Para 23.5.3. I have found the fire sprinkler design to be acceptable subject to the following comments: 1. Include applicable product data (i.e. new sprinkler heads) with the permit submittal to the City of Tukwila. A resubmittal to Tuazon Engineering is not required provided the above are resolved to the satisfaction of Tukwila Fire Department. The comments made above do not relieve the contractor from compliance with requirements of contract drawings, specifications, or codes. Tuazon Engineering has performed a detailed review of the submittal for general conformance with the standards referenced. Please contact me at 425-917-1683 or eric(tuazon.com with any questions regarding this review. Respectfully, TUAZON ENGINEERING, PLLC )1"tx?---- Enc P. Tuazon, PE Fire Protection Engineer Weartpsyiis. 0a Pigd62005A0 Gem R-WsY18ii.08.0231 1 nat*MY*mwAx WATCHED AREA INDICATES NON–ACCESSIBLE SPACE ABOVE TOILET ROOM AND DM OFFICE –6" 10'-2 3/4" OPEN GYP. BD. PT -5 GYP. 8D. TO DECK 16'–q" SERVICE CORRIDOR (N.LC.) ADJACENT TENANT. IN,LC.i FOCAL HALL, DONNLIGHTS, TRACK LIGHTS, * DIFFUSERS q'-7 I/4"J GYP. HD. GYP. BD. DISPLAY C#BINET TRACK LIGHTS, --- U .N. IGHTS,U...N. RETAINER STRAP WHERE REQUIREP IN SEISHIC AREAS TOP BEAR/ C-CLAHP WITH SET SCREW 3/8' ALL THREAD ROD PIPE SWIVEL RING 1l11l■■l z,.7 iiiiiiiiiii�iiiiiiivii�iiiiiii� � J –( ,J_i . _i ./ •7.:7Z fEs_ic.:,r17f� s:: FILE COPY SHEET INDEX SHEET NUM3ER SHEET TITLE BATH AND BODY WORKS FIRE A ARM SYS EM TUKWILA, WASHINGTON FA -01 SYSTEM I\FORMATIO\ FA -02 TYPICAL DETAILS - WIRING AND MOUNTING FA -03 FRE ALA R\A SYSTE vl FLOOR PLAN FA -04 SYSTE V CALCULATIONS (GENERAL), MISER, SITE PLAN r".'3j. .. i.. Fire .11 city cti : dopted !Cr the !r!gs alter I gauue a leSu r r.,`t: -1 t ; approval. Final acccpte-ice i^ !!t' ect to in irj test and inspection bl h:3 Tu'kvilia Fifa Prevention Bureau. t Date: 9-a-08 By: J J ( it 4 1 ruKWILA FIRE DEPARTMEI`'ft Please call: 575-440Z and give this job No. 02 - F and exact address for shut. ,„Km or rastaration approved: NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and `,rninlinnof the testing. � 9 u�.-na...,� n :d a tsa 2 ecause of increased demand our inspectors' schedules are booked 3-7 days ahead. Therefore, you will need to call 206-5754407 to schedule your inspections a minimum of 43 hours in advance of the date you want ari inspection. WIRE DESIGNATION SCHEDULE WIRE SCHEDULE AND CONDUIT FILL CHART WIRE DESIGNATI❑N SYMBOL DESCRIPTION NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) H DOOR HOLDER POWER - 24VDC TWO #14 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #12 FPL/FPLR RED (JACKET) A ANNUNCIATOR TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPL/FPLR RED (JACKET) X LOW LEVEL AUDIO TWISTED PAIR W/ SHIELD #16 FPL/FPLR RED (JACKET) UD UNDERGROUND DATA TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) UI UNDERGROUND INITIATION TWISTED PAIR RATED #18 FPL/FPLR RED (JACKET) M DOOR HOLDER POWER TWO #16 FPL/FPLR RED (JACKET) B BEAM DETECTOR POWER TWO #14 FPL/FPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 0.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 0.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/4" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT P❑INT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END GENERAL NOTES FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. 9, FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. 23. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED QUANTITY 2 1 7 1 EX SYMBOL DESCRIPTION SYMBOLS LEGEND MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT FACP FIRE ALARM EX CONTROL PANEL XLS-V SIEMENS PROVIDED 66" A.F.F. TO TOP FARA FIRE ALARM REMOTE ANNUNCIATOR SDD-C SIEMENS PROVIDED 66" A.F.F. TO TOP BPS REMOTE BOOSTER EX POWER SUPPLY PAD -3 SIEMENS PROVIDED 66" A.F.F. TO TOP 111 INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP VERIFY IN FIELD DUAL INPUT INTERFACE MODULE HTRI-D SIEMENS 4S DEEP VERIFY IN FIELD HCP CONTROL POINT MODULE HCP SIEMENS 4S DEEP VERIFY IN FIELD HZM REMOTE CONVENTIONAL HZM ZONE MODULE SIEMENS 4S DEEP VERIFY IN FIELD IFC LINEAR BEAM SMOKE DETECTOR PBA -1191 SIEMENS PROVIDED VERIFY IN FIELD ISI SMOKE DETECTOR HFP-11 W/ SIEMENS (ADDRESSABLE -PHOTO) DB -11 BASE 4S DEEP W/ 1G RING CEILING D DUCT SMOKE DETECTOR AD2-P W/ SIEMENS TSM MODULE DUCT HOUSING VERIFY IN FIELD HEAT DETECTOR (ADDRESSABLE) HFPT-11 W/ SIEMENS DB -11 BASE 4S DEEP W/ 1G RING CEILING FIRE ALARM SPEAKER STROBE F C (CEILING MOUNT) ZH-MC-CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM SPEAKER STROBE (WALL MOUNT) FIRE ALARM STROBE (CEILING MOUNT) ZH-MC-W SIEMENS 4S DEEP BOX 80" A.F.F. TO BOTTOM ZR -MC -CW SIEMENS 4S BOX W/ 1G RING CEILING L FIRE ALARM STROBE (WALL MOUNT) ZR -MC -W SIEMENS 4S BOX W/ 1G RING 80" A.F.F. TO BOTTOM U.O.N. Q C FIRE ALARM SPEAKER (CEILING MOUNT) SET -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2" EXT. B WP FIRE ALARM SPEAKER (WALL MOUNT) FIRE ALARM STROBE (WEATHERPROOF) SET -W SIEMENS 4S DEEP BOX 80" A.F.F. W/ 1-1/2" EXT. TO BOTTOM SET -S17 -WP SIEMENS MT -SUR -BOX VERIFY 1/2" PIPE IN FIELD MR MULTI -VOLTAGE CONTROL RELAY MR -201 /C AIR PRODUCTS 4S BOX VERIFY IN FIELD E1 MAGNETIC DOOR HOLDER F.B.O. F.B.O. F.B.O. VERIFY IN FIELD FA JB❑X FIRE ALARM TERMINAL CABINET F.B.O. F.B.O. F.B.O. VERIFY IN FIELD O JUNCTION BOX F.B.O. F.B.D. N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A F.B.D. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A U.O.N. UNLESS OTHERWISE NOTED N/A N/A N/A N/A WP WEATHERPROOF DEVICE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A Copyright PAID SEP 10 2008 Tukwila Fire 2006 by Guardian Security Systems, Inc. All Rights Reserved 1.0 CO 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z a DESCRIPTION SHOP DRAWINGS DATE 9/08/08 2 CCCCa co co O §z°1 FEJ 0c"zz L) 2 WI Zoo- Q 1L co- Z N= I7 Q W (1) 0, (S.-CALE: 1/8"=1' Z 0 0 ILZ DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/08/08 BACKROUND PLAN PROVIDED BY: .0B NUMBER: SHEET k FA -01, THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. BEND OR OTHER OBSTRUCTION ANY DUCK OVER 3' WIDE, SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. 6-10 DUCT EQUIVALENT DIAMETERS TYPICAL SMOKE DETECTOR ISTALATION REQUIREMENT LABEL SCALE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING TO NEXT ADDRESSABLE DEVICE STOP IF LAST DEVICE FROM XLS CONTROL PANEL OR PREVI❑US ADDRESSABLE DEVIC 0 DUCT DETECTOR LOCATION END OF LINE DEVICE(3.6K 1/4W) SUPERVISED SWITCH r GROUND 0 N) 0 HTRI-R OSTATUS LED co 0 N.O. 0 0 COM N.C. ' • NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 TYPICAL HTRI-R CONTROL RELAY MODULE -WIRING AND MOUNTING DETAIL LABELSCALE(BACKGOUND MUSIC SHUTDOWN) PREVIOUS ADDRESSABLE{ DEVICE TO NEXT ADDRESSABLE DEVICE + NOTE 1: VOLTAGE MAX. - CURRENT MAX, - CONT, RES. MAX. - MAX, CABLE LENGTH - C (LINE TO LINE) - C (LINE TO SHIELD) - MAX, LINE SIZE - MIN. LINE SIZE - OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS FROM BEND TYPICAL MOUNTING FOR AD2-P DUCT DETECTOR SCALE:NONE COMBINE ALL SHIELDS AND ISOLATE FROM GROUNDING 0 TO NEXT ADDRESSABLE DEVICE f( STOP IF LAST DEVICE `(-) FROM XLS CONTROL PANEL OR 1(+) PREVIOUS ADDRESSABLE DEVICE LA RELAY CONTACTS (4.0A @ 125VAC) (4.0A @ 30VDC) 27 VDC 3.5 mA DURING POLLING 10 OHMS 200 FT. (18 AWG) 0,o2uF 0.04uF 14 AWG 18 AWG NOTE 21 ALL SUPERVISED SWITCHES MUST BE HELD CLOSED AND/OR OPEN FOR AT LEAST 25 SEC. TO GUARANTEE DETECTION. 0 J La 01 TB1 5`50000 123456 HCP TB2 00 6543'2 1 0 END OF LINE DEVICE (3.6K 1/4W) SUPERVISED/ j SWITCH / GROUND 0 0 0 et - LC) © © 0 HTRI-D OSTATUS LED CO NOT USED 0 0 0 0 NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. TYPICAL HTRI-D ADDRESSABLE INPUT MODULE -WIRING DETAIL LABEL seLE (FIRE SUPPRESSION SYSTEM INTERFACE) 0 GND N AC minim T to 0 PAD -3 0 00 0 INPUT INPUT TROUBLE NAC1 NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 24K n TYPICAL WIRING FOR HCP MODULE (PAD -3 TRIP) LABEL SCALE END OF LINE DEVICE �(33.6K 1/4W) `-6UPERVISED SWITCH NAC -4 NAC -3 NAC -2 NAC -1 NOTE: FOR ADDI11ONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. NOT USED REMOTE DEVICE LOOP T. NOT USED REMOTE DEVICE LOOP !� 0 0. 0 0 0— FROM XLS CONTROL PANEL OR (+)> PREVIOUS ADDRESSABLE DEVICE (-)> 470 OHMS �N1 EOL 0 TC INPU Q 9 9 TSM -1 O 0 • • • TYPICAL AD2-P DUCT SMOKE DETECTOR - WIRING DETAIL SCALE NONE EARTH GROUND -30.(+)TO NEXT DEVICE OR >(-) STOP IF LAST DEVICE HORN STROBE / STROBE WIRING DIAGRAM LABEL SCALE SPEAKER STROBE OR STROBE ONLY R 0 HORN/STROBE 14S DEEP BOX w/ 1-1/2" EXTENSION RING (SPEAKER STROBE) 4S BOX (STROBE ONLY) WALL MOUNTED FIRE ALARM DEVICE MOUNTING ELEVATIONS SCALE=NONE EOL NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERPTIN TEMPERA RE: +32' F (0' C) TO 100' F (38' C) HUMIDITY: O-9333333% RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR FROM PREVIOUS ADDRESSABLE DEVICE OR POWER SOURCE DATA IN (-) > DATA IN (+) > DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT IN WHEN USED IN CONJUNCTION TH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD DETECTOR BASE REAR VIEW HFP-11 SMOKE AND DB -11 DETECTOR BASE -WIRING DETAIL LABEL SCALE TO NEXT DEVICE ( ) DATA OUT > (+) DATA OUT CEILING MOUNT SPEAKER/STROBE MOUNTING (HARD LID) HARD LID CEILING SPEAKER SUPPORT TILE BRIDGE HARD LID 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION \ CEILING MOUNTED SPEAKER/STROBE CEILING MOUNTED SPEAKER/STROBE MOUNTING (DROP CEILING) SCALE:NONE JUNCTION BOX--\ MOUNTED ON \ CEILING. FLEX / / JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0�r� 1 TO NEXT DEVICE 00 CADDY BAR SMOKE DETECTOR SMOKE DETECTOR MOUNTING SCALE:NONE SUSPENDED ILLUMINATED CEILING DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS CO LLJ h- 0 Q Q O rn 2 CCaaa z 1— z 0 co co z O 7.1c73 r MZ c) ,� 0 u) J =Q Q �i Z wok T � = N -� Q � CO 0 "GALE: 1/8"=1' 0 DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZANI DATE: 9/08/08 BACKROUND PLAN PROVIDED BY: ,JOB NUMBER: SHEET FA—O2,, EOL - 19.73 51' 3 F:.. TO FAC? cO �S✓' /SN -h ii TO :ACP ZONE . O FAC' 1 11 ' a r v 10 BE CONVECTED/TIED—!N TO THE =.AAL_/EUILO!NG F!RE AL4P14 SrSTEu P.ELD VER:FE AND COORDINATE ALL RELATED REOUIPEuENTS PRIOR TO DID ==yiaNJ W-311 C0 NCEMGNT R• 0 jj � a II ;J I II A r :r ir ,r 1 II " is J N t - TOar_CPa —JL— JL J JL_ _JL J' 'L J 2S n 5 •�o 1 n e f J 1. tl : I1 .i u 7l5 Lri .0 FACP LS V __TO FACP ZONE 3 � V, ..:l 'O FACP TO FACP ZONE 4 EX Cs) { A�'�J NORTH TO FACP ,u• 75 2 S ---m I r,3 TO FACP ZONE 3 BATH AND BODY WORKS VESTFIELD SOUTHCENTER MALL SCALE 118"=1' LAG NOTES: FIELD LOCATE RELAY MODULE FOR BACK GROUND MUSIC INTERFACE. FIELD LOCATE SIEMENS DUCT DETECTOR ON RETURN SIDE OF ALL VAV UNITS.(SEE SIEMENS INSTALLATI❑N SUBMITTAL FOR LOCATION GUIDELINES AND FA -02) DEVICES SUPPLIED BY GSS, INSTALLED BY MECHANICAL CONTRACTOR. WIRED BY ELECTRICAL CONTRACTOR. SIEMENS HTRI-D ADDRESSABLE INPUT WITH HOOD VENILLAT❑R FIRE SUPPRESI❑N SYSTEM. FIELD LOCATE WITHIN 3 FEET OF CONTRL PANEL. FIELD LOCATE SIEMENS PAD -3 BOOSTER POWER SUPPLY FOR STROBE POWER. AC POWER BY EC FROM DEDICATED, LOCKED OUT 20A, 110 VAC BRANCH CIRCUIT, Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 1 NVI DESCRIPTION SHOP DRAWINGS DATE 00 0 co 0 \ 0, w co O --'r J 2 2z >- Wo ocnzz O 2 LT -1 CO g=Q < Z T = N� F- CO 1 11J F1i W �CALE: 1/8" =1 ' DRAWN BY: LANDERSON DESIGNED BY: R.VEZZANI DATE:9/08/08 BACKROUND PLAN PROVIDED BY: J.OB NUMBER: SHEET FA—O3, LL...JYVY1YVYVY1- ESFRESSO J.C. TR A Cr) 0 M. ELEC I! ELEC �! BEN BRIDLE. JEWE_ERS PAR~UMERIE SUNC0AST MOTION PICTURE WALDENBOOKS NORTH CINGULAP (f)I 1) 01 - L;) VICTORIAS 0 W W z CO 0 CASUAL CORNER PETITE SOPHISTICATE GODIVA CODIVA AVON AVON P \i C LRANK SUN CLASS DESIGN BIAGIO VERIZON WIRELESS kt ADE IN WAST-IICTONN SPENCER GIFTS SII I,TR� Y tifk:11Tij. MALL OFFICE ETZ:s W W 0 m 0 `LEC!kiL MALL OFFICE COMPANY SYSTEM CALCULATIONS NATURALIZF_R JAMBA JUICE THE PICTURE PEOPLE ABERCROMBIE 111 IIIN a BATH AND BODY WORKS WESTFIELD SOUTHCENTER MALS PARFUMERIE 1025 BATTERY SIZING CALCULATION SCALE 1132 30 2S 75 2S 15 2S 15 2S 75 2S 75 2S 15 2S 110 EOL -S1 19.73V 2S EX D D,ID 2I RISER DIAGRAM PROJECT: Panel: Date: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL BATH AND BODY WORKS September 9, 2008 CIRCUIT:: S1 QTY Device Type 2 'ZH-MC @15CD 1 ZH-MC @30CD 3 IZH-MC @75CD 1 1ZH-MC @75CD 0 0 0 1 0 Z-MC@15CD 1Z-MC@30CD DEVICES=!8 Wire Resistance 1.62 CURRENT TOTAL=1356 ;Alarm Current Alarm Total ' Wire Sian ; Wire Length Voltage at EOL 1081 2161 142 142.. 2191 _.._.,....__._.657, 277 2771 0 641 98 I TOTAL mA=I 1356; 12 1 138 0 01 o1 64 • Circuit Total Tota lW i re Resistance (R ) (WL*2)*(R/ft) 0.45 Total Device Load, Amps (I) 1.36 (Total Cct Load) Voltage Drop (_E) 0.61 (E= I * R) EOL Voltage 19.79 (20.4 - E) 0, 19.79370528 1356 PROJECT Pane Date: CIRCUIT:iS1 QTY 1 IZH-MC @15CD 0 1ZH-MC @30CD 1ZH-MC @75CD Notification Appliance_ Circuit Detail WESTFIELD SOUTHCENTER MALL APPLE S1 September 9, 2008 Wire Resistance 1.62 CURRENT TOTAL=1893 Device Type ,Alarm Current) Alarm Total 1 Wire Size 1 Wire Length 3 10 0 0 0 2 =Z-MC@15CD 0 1Z-MC@30CD DEVICES=16 108 1421 2191 108` Voltage at EOL Circuit Total Total Wire Resistance (R ) 1.61 0 6571 i 0 0 0 01 0` 641 1281 98 01 TOTAL m A= 8931 12 I 497 1 (WL*2)*(R/ft) Total Device Load, Amps (1) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.89 1.44 18.96 18.96201996 893 _L_ VOLTAGE DROP CALCULATION rte) co 0\ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: BATH AND BODY WORKS BATH AND BODY WORKS FACP ADD ONS SIEMENS PAD -3 Signal Extender Panel Battery Load Calculations DESCRIPTION SHOP DRAWINGS DATE I. 9/08/08 2 aCCCC Current Load: Standby: Alarm: Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 AD2-P 1 0.0635 0.0635 0.064 0.064 Main System Board 1 0.03 0.03 0.030 0.030 HTR -R HTRI-D 2 0.009600 0.0096 0.021 0.042 ZH-MC-CW @15CD 2 0.108 0.216 0.001600 0.0035 ZH-MC-CW @30CD 1 0.142 0.142 ICP -B6 0.005 ZH-MC-CW @75CD 3 0.219 0.657 ZH-MC-CW @110CD 1 0.277 0.277 0.0731 Amps 0.106 Amps ZR -MC @15CD 1 0.064 0.064 Standby Current Load: 0.0731 Amps For 24 Hours = 1.754 Amp -hours ZR -MC @30CD 0.098 HCP 0.0015 Alarm Current Load: 0.106 Amps For 5 Minutes= 0.009 Amp -hours 0.03 Amps 1.386 Amps 25% Derating= 2.204 Amp -hours Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 1.386 Amps For 5 Minutes= 0.116 Amp -hours Total System Current Load: 2.204 Amp -hours 25% Derating= 1.046 Amp -hours Battery Pair to be Used: 12VDC Amp -hours 7AH Total System Current Load: 1.046 Amp -hours 1 Battery Pair to be Used: 12VDC Amp -hours 7AH BATTERY SIZING CALCULATION SCALE 1132 30 2S 75 2S 15 2S 15 2S 75 2S 75 2S 15 2S 110 EOL -S1 19.73V 2S EX D D,ID 2I RISER DIAGRAM PROJECT: Panel: Date: Notification Appliance Circuit Detail WESTFIELD SOUTHCENTER MALL BATH AND BODY WORKS September 9, 2008 CIRCUIT:: S1 QTY Device Type 2 'ZH-MC @15CD 1 ZH-MC @30CD 3 IZH-MC @75CD 1 1ZH-MC @75CD 0 0 0 1 0 Z-MC@15CD 1Z-MC@30CD DEVICES=!8 Wire Resistance 1.62 CURRENT TOTAL=1356 ;Alarm Current Alarm Total ' Wire Sian ; Wire Length Voltage at EOL 1081 2161 142 142.. 2191 _.._.,....__._.657, 277 2771 0 641 98 I TOTAL mA=I 1356; 12 1 138 0 01 o1 64 • Circuit Total Tota lW i re Resistance (R ) (WL*2)*(R/ft) 0.45 Total Device Load, Amps (I) 1.36 (Total Cct Load) Voltage Drop (_E) 0.61 (E= I * R) EOL Voltage 19.79 (20.4 - E) 0, 19.79370528 1356 PROJECT Pane Date: CIRCUIT:iS1 QTY 1 IZH-MC @15CD 0 1ZH-MC @30CD 1ZH-MC @75CD Notification Appliance_ Circuit Detail WESTFIELD SOUTHCENTER MALL APPLE S1 September 9, 2008 Wire Resistance 1.62 CURRENT TOTAL=1893 Device Type ,Alarm Current) Alarm Total 1 Wire Size 1 Wire Length 3 10 0 0 0 2 =Z-MC@15CD 0 1Z-MC@30CD DEVICES=16 108 1421 2191 108` Voltage at EOL Circuit Total Total Wire Resistance (R ) 1.61 0 6571 i 0 0 0 01 0` 641 1281 98 01 TOTAL m A= 8931 12 I 497 1 (WL*2)*(R/ft) Total Device Load, Amps (1) (Total Cct Load) Voltage Drop ( E ) (E= I * R) EOL Voltage (20.4 - E) 0.89 1.44 18.96 18.96201996 893 _L_ VOLTAGE DROP CALCULATION rte) co 0\ 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: z Q DESCRIPTION SHOP DRAWINGS DATE I. 9/08/08 2 aCCCC co co J '_ -J ay W 2z wO w� (3 Zz CC 0 co � W= <C Q CCo_j C) CCO 1 - J 0 w w CO CC CC w w z 0 E-- 0 W >- �CALE: 1/8" =1 ' Copyright 2006 by Guardian Security Systems, Inc. All Rights Reserved DRAWN BY: (.ANDERSON DESIGNED BY: R.VEZZAN I DATE:9/08/08 BACKROUND PLAN PROVIDED BY: t0B NUMBER: ( SHEET FA -04}