FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Fireworks Gallery
261 Southcenter Mall
Permit No.: 10-S-047
Date: March 22, 2010
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ` of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'h inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 30 or more heads require hydrostatic test and system
isolation if necessary.
• For dry pipe and double interlock preaction systems, in addition to the standard
hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24
hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the
24 hours shall be corrected.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2007 Edition.
v
14:42 MAR 09, 2010
5S"
FAX NO: 8961216 #30600 PAGE: 2/3
L
(253) 926-1880 ° FAX (253) 926-2350
SMITH FIRE SYSTEMS, INC. 1106 54th Avenue East • Tacoma, Washington 98424
March 9, 2010
City of Tukwila
444 Andover Park East
Tukwila, WA
Attention: City of Tukwila Fire Sprinkler Plan Review
Smith Fire Systems is requesting a shut off number to temporarily relocate two pendent
sprinklers in the new Fireworks tenant space at South Center Mall to facilitate the installation of
new mechanical equipment (see attached). The two pendent sprinklers will be permanently
relocated when the rest of the sprinkler system is updated for the new tenant If you have any
questions, please contact me.
Sincerely,
Shane M Challender
Smith Fire Systems, Inc.
(253) 248-2663 direct line
schal lender(c�smithfire.com
titAWILA FIRE DEPARTOAeKt,.
Please cell: 575.4407,
and give this job
No. /O -S-OL/
and exact address for shots
down or restoration voroveil;
14:42 MAR 09, 2010
FAX NO: 89E1216
*30600 PAGE: 3,'3
1,7
9..0.
251 THE KITCHEN SHOP
6-0'
12-0'
5'-11'
4'-6'
4'E
5'-10'
11'-8'
NEW 1' PWG
2
i y
1
o-9
CUT IN NEW I'TEE
2
�- NEW 1' PWG
S ^9" 2
- O
NEW 1' PLUG
OB
\
` NEW 1' PLUG
1.5
NEW r PLUG
m
1.25 1 '."4-f
Q-0
15-0
AFF
0
1-10
SEE DETAIL
SALES
:,1
OPEN 10 STRUCIU3E
CE:000
10-2A F.F^
NEW 1' PWG
2
S \\
`NEW 1'PWG
9
15
NEW 1' PLUG
3
CEIIJ'dG (
10-2AFF
4
iA
e1-6
2-5
PIPE / FITTING LEGEND
NEW SPRINKLER PIPE
EXISTING SPRINKLER PIPE
S NEW STRAP TEE
(6) = 2 x 1
(6)=1.5x1
WIDE FLANGE STEEL BEAM
12' RETAINER STRAP
— ANVIL FIG. 92
3/8' BEAM CLAMP
3/8' x 346 ATR CTS
HANGER RING WITH
SURGE CUP
HANGER TB1 (X2)
6' RETAINER STRAP
/ BAR JOIST STIFFENER
ANVIL FIG. 92
3/8' BEAM CLAMP
3/8' x 1-6 ATR CTS
HANGER RING
HANGER TB2 (X1)
NO NEW WORK IN HATCHED AREA
NEW 1' PWG
2
15
NEW 1' PWG
O NEW 1' PWG
1.5
-111
0-8.5
WALL LEGEND
EXISTING
BRANCH UNE
I EXISTING FULL HEIGHT WALL
INSTALL NEW
PLUG AT TEE
— EXISTING DROP TO
BE DEMOED
EXISTING- \
BRANCH UNE
7.
DETAIL A (X2)
271 NATURALIZER
SPRINKLER PLAN
0 A 8
MODEL G4A
CONCEALED
SCALE 1/4'=1',7
NEW 1' PWG
0-6
T
DETAIL B (X1)
;,!uns tT ..,en ,eviewed by The Tukwila Fire
on Bureau for conformance wtth current City
-rds. Acceptance is subje t to errors and
..:sons which cio not authorize vlt;!ations of adopted
-5ndards and ordinances. The responsiblii y for the
rdequacy of design rests totallywith the designer.
Additions, deletions or r, vi tions to these drawings after
this dzAte will void this acceptance and will require)a
resubmittal of revised drawn :::, fGt- approval.
4
BUILDING SECTION
SALES
I E9
OPEN TO STRUCTURE
Final acceptance is sub:kxt to field and inspection by
The Tukwila Fire Preven n1j; �: u.
Date: )—.)-.1 =1O y:
NTS
NOT/CE
Weld stamps must be
inspected before pipe is
hung. Do not paint piping
prior to hydrostatic yes;
approval.
• -s
S
•
(t4Kwit.A FIRE DEPARTM N t
Please call: 575-4407
and give this job
Mb. /O - �S O V 7
and exact address for shut•
-lawn or restoration aoornyril
S
SPRINKLER LEGEND
SYM
NEW
MANUFACTURER 1 S I.N. TYPE 1 MODEL
04888
e
O
O
REUABLE
REUABLE
RELIABLE
85415
R3625
R3625
;.ONCEALED
SSU
SSU
G4A
FIFR
F1 FR
BRZ
BRZ
BRZ
WHITE
5.6K
5.6K
5.6K
1/7
1/7
1/7
155°
155°
155°
6
14
3
TOTAL NEW
23
S!arie Way
a co
o 01
:A Y (•�FJ
0
EXISTING
BRANCH UNE
NEW STRAP TEE --
FITTER/LISTER NOTES
1. ALL DROPS TO HARD CEILING TO BE ADN'S
2. SEND (15) 1" PLUGS
3. EXISTING PIPING IS THREADED
4. EXISTING SYSTEM IS SCHEDULED
5. EXCLUDING WORK ON OVERTIME OR AFTER HOURS.
6. EXCLUDING RELOCATING OR MODIFYING THE EXISTING SPRINKLER
SYSTEM TO ACCOMMODATE THE WORK OF OTHER TRADES.
,(PER PLAN)
GENERAL NOTES
Les r
1 (PER PLAN)
DETAIL C (X4)
NEW STRAP TEE --
EXISTING
BRANCH UNE
,(PER PLAN)
DETAIL D (X7)
EXISTING
BRANCH UNE
NEW STRAP TEE —
sour
hcf Breit
•
— 1(3-6) TOE
LENGTH PER PLAN
— 1(1-2)
DETAIL E (X3)
CV
ADN
MODEL G4A
3uthrenter Mall
stbefd Southrnr teC
AREA MAP
Tulwea
Park
-T k Sia i'
Evans B(aok
Faker Blvd
0
Strander Blvd
NTS
1. ALL STEEL PIPE TO BE AS FOLLOWS UNLESS NOTED OTHERWISE:
STEEL PIPE ASTM A-795 OR BEI IEi1
PIPE
SIZE
SCHEDULE
WALL
THICKNESS
INTERNAL
DIAMETER
END PREP TYPES ALLOWED
PROF
WATER/PPE
ran
r. D.ROS
1
40
0.133
1.049
THREADED. GUT GROOVED. ROLL GROOVED, RAN END, POLISHED
205
0.044
" WALL THICKNESS PER NEPA 813
2. ALL GROOVED COUPLINGS TO BE RIGID TYPE UNLESS NOTED (1 11) WHICH ARE FLEXIBLE.
SCOPE OF WORK
SMITH FIRE SYSTEMS (SFS) WILL MODIFY THE EXISTING SPRINKLER SYSTEM TO
ACCOMMODATE THE NEW WALLS AND CEILINGS.
CLARIFICATIONS:
1. ALL AREAS PROTECTED BY A WET PIPE SYSTEM MUST BE MAINTAINED AT
40°F IN ORDER TO PREVENT FREEZING.
EXCLUSIONS:
1. ANY WORK OUTSIDE THIS TENANT SPACE
2. PAINTING OR LABELING OF PIPE.
3. REPLACEMENT OF PAINTED, DAMAGED, OR CORRODED SPRINKLERS.
4. ELECTRICAL OR ALARM WORK OF ANY KIND.
5. BACKFLOW INSTALLATION, MODIFICATION, OR CERTIFICATION (IF REQUIRED)
6. EXCLUDING REPAIRS OR MODIFICATIONS TO THE EXISTING SYSTEM
BEYOND THE SCOPE DESCRIBED ABOVE.
DESIGN CRITERIA:
PER NFPA 13, 2007 EDITION AND THE CITY OF TUKWILA
EXISTING CRITERIA
MERCANTILE- ORDINARY GROUP II
NEW DESIGN CRITERIA:
MERCANTILE - ORDINARY GROUP II
TENANT IMPROVEMENT:
THIS PROJECT -IS A -TENANT IMPROVEMENT..-TH)S FACILITY HAS ALREADY -BEEN PROTECTED
BY A FIRE SPRINKLER SYSTEM. SMITH FIRE SYSTEMS IS ADDING AND/OR RELOCATING
SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEIUNG, LIGHTING, AND
HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE
EXISTING SYSTEM. THERE FORE NO NEW HYDRAULIC CALCULATIONS ARE NECESSARY.
MACY'S
SEARS
(EN
SITE PLAN
5
z
U
Pi -�
i
MAR 1 2010
NTS
Tukwila Fire
ABBREVIATIONS
SYMBOL LEGEND
AFF
BOB
BOD
BOJ
BOF
BOT
20
O
ORM
R85
DRO
ABOVE ENDED ROOK
OTT04
CF 684
OTT04 OF CEO(
OTTO4 OF .OST
OTTO4 OF MEN
OTT04 OF TALES
CUT TO 51x1
ELI) ODER
RMOE FACE OF WALL
OUTSIDE FACE OF WALL
NO AUTO. 56849ERs
MESS NO EB 00088.0
BOD
0
CI
—II—
CENTERLINE OF PIPE TO REFERENCED
STRUCTURE IN INCHES
2 -WAY EARTHQUAKE SWAY BRACE
LETTER INDICATES TYPE
4 -WAY EARTHOUAKE SWAY BRACE
LETTER INDICATES TYPE
HANGER LOCATION
ELEVATION ABOVE REFERENCED
POINT IN FEET AND INCHES
HYDRAULIC CALCULATION NODE
FLEXIBLE COUPLING
RIGID COUPLING
NO
DATE
BY
BUILDING INFORMATION
MAINTENANCE CONTACT :
MAINTENANCE PHONE :
ALARM COMPANY:
ALARM PHONE :
ALARM CODE :
ALARM PASSWORD:
FIRE DEPARTMENT :
FIRE DEPT. PHONE :
CONTRACT WITH
JR ABBOT CONSTRUCTION
SEATTLE, WA
PROJECT MANAGER:
PHONE:
FAX:
SUPERINTENDENT:
PHONE:
FAX:
JENNIFER STEPHAN
206.467.6500
206.447.1885
ROB ROBERTSON
206.954.5766
1 t1
la �1
III" �
'SIN.c1
"Yl'.
010201x:A1E OF COMPETENCY STAMP
5F5
SMITH FIRE SYSTEMS, INC.
1106 54th AVE EAST
TACOMA, WA 98424
CONTR. REG. NO. SMITHFS1350T
Bus: (253) 926-1880 FAX (253) 926-2350
FIREWORKS @ SOUTH CENTER
633 SOUTH CENTER
TUKWILLA, WA 98188
SHANE C.
LANE LUVAAS
03-16-10 1 1. OF 1
.10B NO.
1110029
261 SOUTHCENTER MALL
ASSOCIATED PERMITS
10-S-047
10-S-041
FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS
Project Name: Fireworks Gallery
261 Southcenter Mall
Permit No.: 10-S-047
Date: March 22, 2010
Reviewer: Al Metzler
Fire Protection Project Coordinator
(206)575-4407
• Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross
mains, and branch lines 2.5" and larger. Bracing is provided for the last length of
pipe but within 6' of the end of a feed or cross main. Bracing is required unless
all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for
any size pipe, 9.3.5.3.
• Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4
exceptions, 9.3.4.
• Longitudinal sway bracing is a maximum of 80' for mains and cross mains and
within 40 ` of the end of the line, 9.3.5.4.
• Provide lateral and longitudinal bracing for changes in pipe direction per section
9.3.5.11.2 for pipe size 2'h inches and larger.
• Restrain branch lines at the end sprinkler of each line, restrain against vertical
and lateral movement, 9.3.6.3.
• Restraints for branch lines shall be at intervals per table 9.3.6.4 and section
9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6.
• Comply with ASCE 7-05, section 13.5.6.2.2.
• Provide sprinkler protection beneath all obstructions greater than 4 ft. in width.
• Extend sprinkler protection to all combustible concealed spaces.
• Comply with NFPA 13 obstruction tables.
• Comply with obstructed/non-obstructed construction rules for sprinkler head
placement.
• Sprinkler heads spaced closer than 6 ft. apart must be baffled.
• Modifications involving 30 or more heads require hydrostatic test and system
isolation if necessary.
• For dry pipe and double interlock preaction systems, in addition to the standard
hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24
hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the
24 hours shall be corrected.
• These conditions apply to all sprinkler piping exposed as necessary to
accomplish the permitted scope of work.
All code references are NFPA 13, 2007 Edition.
v
14:42 MAR 09, 2010
5S"
FAX NO: 8961216 #30600 PAGE: 2/3
L
(253) 926-1880 ° FAX (253) 926-2350
SMITH FIRE SYSTEMS, INC. 1106 54th Avenue East • Tacoma, Washington 98424
March 9, 2010
City of Tukwila
444 Andover Park East
Tukwila, WA
Attention: City of Tukwila Fire Sprinkler Plan Review
Smith Fire Systems is requesting a shut off number to temporarily relocate two pendent
sprinklers in the new Fireworks tenant space at South Center Mall to facilitate the installation of
new mechanical equipment (see attached). The two pendent sprinklers will be permanently
relocated when the rest of the sprinkler system is updated for the new tenant If you have any
questions, please contact me.
Sincerely,
Shane M Challender
Smith Fire Systems, Inc.
(253) 248-2663 direct line
schal lender(c�smithfire.com
titAWILA FIRE DEPARTOAeKt,.
Please cell: 575.4407,
and give this job
No. /O -S-OL/
and exact address for shots
down or restoration voroveil;
14:42 MAR 09, 2010
FAX NO: 89E1216
*30600 PAGE: 3,'3
1,7
9..0.
251 THE KITCHEN SHOP
6-0'
12-0'
5'-11'
4'-6'
4'E
5'-10'
11'-8'
NEW 1' PWG
2
i y
1
o-9
CUT IN NEW I'TEE
2
�- NEW 1' PWG
S ^9" 2
- O
NEW 1' PLUG
OB
\
` NEW 1' PLUG
1.5
NEW r PLUG
m
1.25 1 '."4-f
Q-0
15-0
AFF
0
1-10
SEE DETAIL
SALES
:,1
OPEN 10 STRUCIU3E
CE:000
10-2A F.F^
NEW 1' PWG
2
S \\
`NEW 1'PWG
9
15
NEW 1' PLUG
3
CEIIJ'dG (
10-2AFF
4
iA
e1-6
2-5
PIPE / FITTING LEGEND
NEW SPRINKLER PIPE
EXISTING SPRINKLER PIPE
S NEW STRAP TEE
(6) = 2 x 1
(6)=1.5x1
WIDE FLANGE STEEL BEAM
12' RETAINER STRAP
— ANVIL FIG. 92
3/8' BEAM CLAMP
3/8' x 346 ATR CTS
HANGER RING WITH
SURGE CUP
HANGER TB1 (X2)
6' RETAINER STRAP
/ BAR JOIST STIFFENER
ANVIL FIG. 92
3/8' BEAM CLAMP
3/8' x 1-6 ATR CTS
HANGER RING
HANGER TB2 (X1)
NO NEW WORK IN HATCHED AREA
NEW 1' PWG
2
15
NEW 1' PWG
O NEW 1' PWG
1.5
-111
0-8.5
WALL LEGEND
EXISTING
BRANCH UNE
I EXISTING FULL HEIGHT WALL
INSTALL NEW
PLUG AT TEE
— EXISTING DROP TO
BE DEMOED
EXISTING- \
BRANCH UNE
7.
DETAIL A (X2)
271 NATURALIZER
SPRINKLER PLAN
0 A 8
MODEL G4A
CONCEALED
SCALE 1/4'=1',7
NEW 1' PWG
0-6
T
DETAIL B (X1)
;,!uns tT ..,en ,eviewed by The Tukwila Fire
on Bureau for conformance wtth current City
-rds. Acceptance is subje t to errors and
..:sons which cio not authorize vlt;!ations of adopted
-5ndards and ordinances. The responsiblii y for the
rdequacy of design rests totallywith the designer.
Additions, deletions or r, vi tions to these drawings after
this dzAte will void this acceptance and will require)a
resubmittal of revised drawn :::, fGt- approval.
4
BUILDING SECTION
SALES
I E9
OPEN TO STRUCTURE
Final acceptance is sub:kxt to field and inspection by
The Tukwila Fire Preven n1j; �: u.
Date: )—.)-.1 =1O y:
NTS
NOT/CE
Weld stamps must be
inspected before pipe is
hung. Do not paint piping
prior to hydrostatic yes;
approval.
• -s
S
•
(t4Kwit.A FIRE DEPARTM N t
Please call: 575-4407
and give this job
Mb. /O - �S O V 7
and exact address for shut•
-lawn or restoration aoornyril
S
SPRINKLER LEGEND
SYM
NEW
MANUFACTURER 1 S I.N. TYPE 1 MODEL
04888
e
O
O
REUABLE
REUABLE
RELIABLE
85415
R3625
R3625
;.ONCEALED
SSU
SSU
G4A
FIFR
F1 FR
BRZ
BRZ
BRZ
WHITE
5.6K
5.6K
5.6K
1/7
1/7
1/7
155°
155°
155°
6
14
3
TOTAL NEW
23
S!arie Way
a co
o 01
:A Y (•�FJ
0
EXISTING
BRANCH UNE
NEW STRAP TEE --
FITTER/LISTER NOTES
1. ALL DROPS TO HARD CEILING TO BE ADN'S
2. SEND (15) 1" PLUGS
3. EXISTING PIPING IS THREADED
4. EXISTING SYSTEM IS SCHEDULED
5. EXCLUDING WORK ON OVERTIME OR AFTER HOURS.
6. EXCLUDING RELOCATING OR MODIFYING THE EXISTING SPRINKLER
SYSTEM TO ACCOMMODATE THE WORK OF OTHER TRADES.
,(PER PLAN)
GENERAL NOTES
Les r
1 (PER PLAN)
DETAIL C (X4)
NEW STRAP TEE --
EXISTING
BRANCH UNE
,(PER PLAN)
DETAIL D (X7)
EXISTING
BRANCH UNE
NEW STRAP TEE —
sour
hcf Breit
•
— 1(3-6) TOE
LENGTH PER PLAN
— 1(1-2)
DETAIL E (X3)
CV
ADN
MODEL G4A
3uthrenter Mall
stbefd Southrnr teC
AREA MAP
Tulwea
Park
-T k Sia i'
Evans B(aok
Faker Blvd
0
Strander Blvd
NTS
1. ALL STEEL PIPE TO BE AS FOLLOWS UNLESS NOTED OTHERWISE:
STEEL PIPE ASTM A-795 OR BEI IEi1
PIPE
SIZE
SCHEDULE
WALL
THICKNESS
INTERNAL
DIAMETER
END PREP TYPES ALLOWED
PROF
WATER/PPE
ran
r. D.ROS
1
40
0.133
1.049
THREADED. GUT GROOVED. ROLL GROOVED, RAN END, POLISHED
205
0.044
" WALL THICKNESS PER NEPA 813
2. ALL GROOVED COUPLINGS TO BE RIGID TYPE UNLESS NOTED (1 11) WHICH ARE FLEXIBLE.
SCOPE OF WORK
SMITH FIRE SYSTEMS (SFS) WILL MODIFY THE EXISTING SPRINKLER SYSTEM TO
ACCOMMODATE THE NEW WALLS AND CEILINGS.
CLARIFICATIONS:
1. ALL AREAS PROTECTED BY A WET PIPE SYSTEM MUST BE MAINTAINED AT
40°F IN ORDER TO PREVENT FREEZING.
EXCLUSIONS:
1. ANY WORK OUTSIDE THIS TENANT SPACE
2. PAINTING OR LABELING OF PIPE.
3. REPLACEMENT OF PAINTED, DAMAGED, OR CORRODED SPRINKLERS.
4. ELECTRICAL OR ALARM WORK OF ANY KIND.
5. BACKFLOW INSTALLATION, MODIFICATION, OR CERTIFICATION (IF REQUIRED)
6. EXCLUDING REPAIRS OR MODIFICATIONS TO THE EXISTING SYSTEM
BEYOND THE SCOPE DESCRIBED ABOVE.
DESIGN CRITERIA:
PER NFPA 13, 2007 EDITION AND THE CITY OF TUKWILA
EXISTING CRITERIA
MERCANTILE- ORDINARY GROUP II
NEW DESIGN CRITERIA:
MERCANTILE - ORDINARY GROUP II
TENANT IMPROVEMENT:
THIS PROJECT -IS A -TENANT IMPROVEMENT..-TH)S FACILITY HAS ALREADY -BEEN PROTECTED
BY A FIRE SPRINKLER SYSTEM. SMITH FIRE SYSTEMS IS ADDING AND/OR RELOCATING
SPRINKLER HEADS TO ACCOMMODATE THE NEW TENANT WALL, CEIUNG, LIGHTING, AND
HVAC LAYOUT. ALL WORK WILL BE DONE WITHOUT AFFECTING THE CAPABILITY OF THE
EXISTING SYSTEM. THERE FORE NO NEW HYDRAULIC CALCULATIONS ARE NECESSARY.
MACY'S
SEARS
(EN
SITE PLAN
5
z
U
Pi -�
i
MAR 1 2010
NTS
Tukwila Fire
ABBREVIATIONS
SYMBOL LEGEND
AFF
BOB
BOD
BOJ
BOF
BOT
20
O
ORM
R85
DRO
ABOVE ENDED ROOK
OTT04
CF 684
OTT04 OF CEO(
OTTO4 OF .OST
OTTO4 OF MEN
OTT04 OF TALES
CUT TO 51x1
ELI) ODER
RMOE FACE OF WALL
OUTSIDE FACE OF WALL
NO AUTO. 56849ERs
MESS NO EB 00088.0
BOD
0
CI
—II—
CENTERLINE OF PIPE TO REFERENCED
STRUCTURE IN INCHES
2 -WAY EARTHQUAKE SWAY BRACE
LETTER INDICATES TYPE
4 -WAY EARTHOUAKE SWAY BRACE
LETTER INDICATES TYPE
HANGER LOCATION
ELEVATION ABOVE REFERENCED
POINT IN FEET AND INCHES
HYDRAULIC CALCULATION NODE
FLEXIBLE COUPLING
RIGID COUPLING
NO
DATE
BY
BUILDING INFORMATION
MAINTENANCE CONTACT :
MAINTENANCE PHONE :
ALARM COMPANY:
ALARM PHONE :
ALARM CODE :
ALARM PASSWORD:
FIRE DEPARTMENT :
FIRE DEPT. PHONE :
CONTRACT WITH
JR ABBOT CONSTRUCTION
SEATTLE, WA
PROJECT MANAGER:
PHONE:
FAX:
SUPERINTENDENT:
PHONE:
FAX:
JENNIFER STEPHAN
206.467.6500
206.447.1885
ROB ROBERTSON
206.954.5766
1 t1
la �1
III" �
'SIN.c1
"Yl'.
010201x:A1E OF COMPETENCY STAMP
5F5
SMITH FIRE SYSTEMS, INC.
1106 54th AVE EAST
TACOMA, WA 98424
CONTR. REG. NO. SMITHFS1350T
Bus: (253) 926-1880 FAX (253) 926-2350
FIREWORKS @ SOUTH CENTER
633 SOUTH CENTER
TUKWILLA, WA 98188
SHANE C.
LANE LUVAAS
03-16-10 1 1. OF 1
.10B NO.
1110029