FireComNW,LLC
Battery Calculation Work Sheet
Project: Gene Juarez Salon TI
Southcenter Mall
Tukwila WA 98188
This project consists of a new fire alarm system for a tenant improvement for a `M' occupancy
space that is fully sprinklered. This scope of work will include installing a new fire alarm control
panel, initiating and signaling devices. This work sheet is for the fire alarm panel and the
connected devices.
Qty Part # and description
Supervised Current mA Alarm Current mA
1 D7024 Radionics FACP 269 380
1 D282 Smoke detector 0.0036 0.0036
5 GCC Horn strobe — ceiling mount 0 1915
2 GCS Strobe — ceiling mount 0 720
19 GES3 Horn strobe — wall mount 0 1045
Subtotal 269 4060
Total battery power hours x24 x.083
Subtotal 6456 337
Safety factor - 10% +646 + 34
Total 7102 ma 371 ma
Total Current Required 7473 ma or 7.5 amps
Battery size used: 2ea - 12volt, 12amp
NOV 1 C 2006
Tukwila Fire
NOTICE
A completed, signed, Tuk
Fire Department Pre-test
ettificate must be present
to the Inspector prior to.
coJnmencement of Acceptan
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
rr_a Re -inspection Fee an
termination of the testing
ACCEPTS
1'I
�] Without Comments
As Noted In Red
Per The Attached Lett-
.r.
ett-
0 r
WAKING
1021
IJ
These plans have been revevded by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do riot authorize violations of adopted
sta nl:taras and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings atter
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Firatacceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Lte-:i — °C' By:
B
COATS
JJ
B
RECEPTION
HALLWAY
1 04 1
u)Rs%/ILA FIRE DEPARTMENZ
Pie...se call: 575.441 ,"
_snd give this job
-F- ay;
140.0
a -.Acct address for shut.
,own or restoration approval
11 EOL
1
SHAMPOO
1141
DESIGN
SALON EASE
DD
MAIN
HALLWAY
10211
00
DESIGN
SALON WEST
1,31
12 1
ai 14
yi *
�1
MASSAGE
1231
SPA
HALLWAY
-_- -r. 24 1
SKIN CARE
414400
B
B
MGR OFFICE
130,11
SAFE
MULTIPURPOSE
1 22 1
LINEN
CLOSET
11931
• 1 SPA
SAANN11Y
1 "_1
OFFICE
1301
REF' 51AFF
BREAK RM
_J 1 29 1
EOL
SERVICE
ISI
C
A
A
00
c
-7(
WASHER
L DRYER
DISPENSARY
1271
SHAMPOO
11-1-71-11
'0 FACP B 1110
00209
1 25 1
tr DRYING
.-1
0�FIRE ALARM PLAN
SCALE: 3/32"-1'-0"
FIRE COM NW.
ezzzil
P0Box MI Owls WA 9812439 //04944700
DATE: 11/08/06
DRAWN:
CMEOCEO:
CEA
JD
APPROVED BY:
JD
PROJECT WE:
GENE JUAREZ SALON T.I.
SOLMC.Mar Mall
Tukwila. WA 98188
SCALE:
3/32•-1.-0.
NO
DATE
REVISION
BY
SHEET TITLE:
FIRE ALARM PLAN
JOB NUMBER: 06-195 FA -1
Vie,3414142:). d4f 4;)-eg Art:A•Va itta ttetmlta," .
FIRST FLOOR
TO 120 VAC UNSWITCHEO
DEDICATED CIRCUIT
TO TELCO ROOM
FIRE ALARM RISER DIAGRAM
SCALE: NONE
GENERAL NOTES:
1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS.
2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN
FEET - THEN IT IS TO BE IN CONDUIT.
3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED.
4. ALL INDOOR HORNS, STROBES, HORN STROBES, AND MINI HORN STROBES ARE TO BE
MOUNTED 80" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER.
6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER
B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES
7. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH
WILL PREVENT PASSAGE OF FLAME AND HOT GASES.
EQUIPMENT LEGEND
DEVICE
SYMBOL
QUANTITY
PART NUNMBER
DESCRIPTION
BACKBOX
14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
1
7024
FIRE ALARM CONTROL PANEL
INCLUDED
Et.
®
1
2WB
SMOKE DETECTOR
4 SQUARE X 1-7/8" DEEP
54C
5
GCC
HORN STROBE - CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
2
GCS
STROBE - CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
1;1
19
GES3
STROBE
4 SQUARE X 1-7/8" DEEP
ISI
4
--
DUCT DETECTOR (PROVIDED BY
OTHERS)
4 SQUARE X 1-7/8" DEEP
CI]
WIRE LEGEND
TYPE
DESCRIPTION
A
18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
B
14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
C
18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE
FIRE COM NW.
P0 kx $SU SWIM WA 7Mf47777 7084384/80
PROJECT NNE:
DRANN: GENE JUAREZ SALON T.I.
gcEO; thca
Souncr Mall
Tukwila, WA 98188
DATE:
11/08/08
APPROVED BY
CEA
JD
JD
SCALE
NONE
NO.
DATE
REVISION
BY
SHEET TITLE:
RISER DIAGRAM AND
EOUIPMENT LEGEND
J0B NUMBER: 06-195
FA -2
GENERAL LEGEND
—rt---
-4
Ir---4 -
0
BOD
BOB
BOJ
FOS
F0W
EARTHQUAKE BRACING
PIPE HANGER - -
GROOVED CAP -
RIGID COUPUNG ( UNLESS NOTED )
CAP
PLUG
CENTERLINE -
HYDRAUUC REFERENCE POINT
CENTERLINE PIPE TO BOTTOM OF DECK
CENTERLINE PIPE TO BOTTOM OF BEAM
CENTERLINE PIPE TO BOTTOLM OF JOIST
FACE OF STUD
FACE OF WALL
FOC FACE OF CONCRETE -
AFF ABOVE RNISHED FLOOR
CH C>G HEIGHT
R C REDUCING COUPUNG
c. OUTLET COUPUNG - -
at► WELDED OUTLET
F 'nr FITTING -
E/C END TO CENTER
C/C CENTER TO CENTER
C/E CENTER TO ENO
GG -GROOVE/GROOVE
TG THREAD/GROOVE (ALSO "Gr) -
TxF THREADrFir (ALSO -Fxr) -
ATR ALL -THREAD R00 -
PIPING LEGEND
EXISTING PIPING
NEW PIPING
1
24'-0'
24'-0"
24'-0'
1
48'-6'
- UNEAR HVAC DIFFUSER ABOVE CEILING
CLOUD; 1W R1 SPA TREATMENT ROOMS
4,
WAITING
02
Y)CH:: 13.1'
=___ ___=_
5 - 3 CH: 12'-0'
V u2
j -OPEN TO
TO STOREFRONT
PENDENT SPRINKLERS
RELOCATE AS REQUIRED
FOR NEW - c0 NSTRUCTION
1 i
CH: 8'-6
3112
VANITY
19
CH:9'-6'
(4)F27-0
1
Id
1
A
CH: 11'-5';-
R=20'
-
1R
- LIGHT COLE ---/
" CIS 12'–O'
�1, w
0
li
11
11
0
1J
11
7- COVE W/ CO LED
UGHT STRIP
TO STOREFRONT
PENDENT SPRINKLERS
RELOCATE AS REQUIRED
FOR NEW CONSTRUCTIO
LEASE UNE -N
•
0
t
1
1
1
1
Y2
Y.
114 �R
1111=MMIIMI• •••••1 AMIN= 1
1
CH: (.10'-0.!_--
c=";
RECEPTION
Ot
CH: 13'-0'
1
° CH:9'-0"
2
RECEPTION
HALLWAY
e—
CH: 12`-0"
MOM
8" SYSTEM RISER
i
. GENE JUAREZ
TENANT SPRINKLERS
QTY
® RELIABLE MODEL G4A QUICK RESPONSE CONCEALED PENDENT 1/2" 155' 92
W/ WHITE COVER PLATE
RECESSED CEILING TRACK
FOR MO CURTAIN: TYP t
AT CHANGING ROOMS -
TENANT SPRINKLER PLAN
SCALE: 3/16' = 1'-0'
/
GENERAL NOTES
1" ARM -OVERS TYPICAL
HANG ALL ARM -OVERS GREATER THAN 12"
SPRINKLER SYSTEM DESIGN PER N.F.P.A 113
ALL MATERIALS SHALL BE NEW AND U.L LISTED OR F.M. APPROVED
FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13
ALL ELECTRICAL PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS
SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE
SIZING PER ORDINARY HAZARD SCHEDULE - MALL STANDARD
ORDINARY HAZARD OCCUPANCY: 130 S.F. PER SPRINKLER MAX
NEW PIPING TO BE 'DYNA-THREAD' THREADABLE THINWALL
•
•
FILE
ACCEPTED
Without Comments -
-.f] As Noted In Red
0 Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
stanaaras and oralnances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions lo these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: /0/1-/°).- • By: /Q '^^ ' / f
rUKWULA FIRE DEPARTMEtI%
Please call: 575-440Z -" -
and give this job
mom
and exact address for shdti 1
down or restoration approve
GENE JUAREZ TENANT
1
LIACY1S
SEARS
MERVYN'S
JCPENNEY
SOUTHCENTER MALL KEY PLAN
NTS
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX 12113
MILL CREEK. WASHINGTON 98082-0113
PH. (425) 481-7669
Gene Juarez
Southcenter Mall =Space A-120
Tukwila, WA PAID
SEP 2 S zw8
DATE: 9/06
DRAWN: C.A.
Tuk,:i : Fire
SCALE: NOTED 1 OF 1
280 SOUTHCENTER MALL
ASSOCIATED PERMITS
06-F-246
06-S-195
PO Box 3932
Seattle WA 981244932
206-234.6700
FireComNW,LLC
Battery Calculation Work Sheet
Project: Gene Juarez Salon TI
Southcenter Mall
Tukwila WA 98188
This project consists of a new fire alarm system for a tenant improvement for a `M' occupancy
space that is fully sprinklered. This scope of work will include installing a new fire alarm control
panel, initiating and signaling devices. This work sheet is for the fire alarm panel and the
connected devices.
Qty Part # and description
Supervised Current mA Alarm Current mA
1 D7024 Radionics FACP 269 380
1 D282 Smoke detector 0.0036 0.0036
5 GCC Horn strobe — ceiling mount 0 1915
2 GCS Strobe — ceiling mount 0 720
19 GES3 Horn strobe — wall mount 0 1045
Subtotal 269 4060
Total battery power hours x24 x.083
Subtotal 6456 337
Safety factor - 10% +646 + 34
Total 7102 ma 371 ma
Total Current Required 7473 ma or 7.5 amps
Battery size used: 2ea - 12volt, 12amp
NOV 1 C 2006
Tukwila Fire
NOTICE
A completed, signed, Tuk
Fire Department Pre-test
ettificate must be present
to the Inspector prior to.
coJnmencement of Acceptan
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
rr_a Re -inspection Fee an
termination of the testing
ACCEPTS
1'I
�] Without Comments
As Noted In Red
Per The Attached Lett-
.r.
ett-
0 r
WAKING
1021
IJ
These plans have been revevded by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do riot authorize violations of adopted
sta nl:taras and ordinances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions to these drawings atter
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Firatacceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Lte-:i — °C' By:
B
COATS
JJ
B
RECEPTION
HALLWAY
1 04 1
u)Rs%/ILA FIRE DEPARTMENZ
Pie...se call: 575.441 ,"
_snd give this job
-F- ay;
140.0
a -.Acct address for shut.
,own or restoration approval
11 EOL
1
SHAMPOO
1141
DESIGN
SALON EASE
DD
MAIN
HALLWAY
10211
00
DESIGN
SALON WEST
1,31
12 1
ai 14
yi *
�1
MASSAGE
1231
SPA
HALLWAY
-_- -r. 24 1
SKIN CARE
414400
B
B
MGR OFFICE
130,11
SAFE
MULTIPURPOSE
1 22 1
LINEN
CLOSET
11931
• 1 SPA
SAANN11Y
1 "_1
OFFICE
1301
REF' 51AFF
BREAK RM
_J 1 29 1
EOL
SERVICE
ISI
C
A
A
00
c
-7(
WASHER
L DRYER
DISPENSARY
1271
SHAMPOO
11-1-71-11
'0 FACP B 1110
00209
1 25 1
tr DRYING
.-1
0�FIRE ALARM PLAN
SCALE: 3/32"-1'-0"
FIRE COM NW.
ezzzil
P0Box MI Owls WA 9812439 //04944700
DATE: 11/08/06
DRAWN:
CMEOCEO:
CEA
JD
APPROVED BY:
JD
PROJECT WE:
GENE JUAREZ SALON T.I.
SOLMC.Mar Mall
Tukwila. WA 98188
SCALE:
3/32•-1.-0.
NO
DATE
REVISION
BY
SHEET TITLE:
FIRE ALARM PLAN
JOB NUMBER: 06-195 FA -1
Vie,3414142:). d4f 4;)-eg Art:A•Va itta ttetmlta," .
FIRST FLOOR
TO 120 VAC UNSWITCHEO
DEDICATED CIRCUIT
TO TELCO ROOM
FIRE ALARM RISER DIAGRAM
SCALE: NONE
GENERAL NOTES:
1. ALL WORK IS TO CONFORM TO NATIONAL ELECTRIC CODE STANDARDS.
2. WIRING METHOD IS TO BE OPEN CABLING EXCEPT WHERE IT IS EXPOSED AND BELOW SEVEN
FEET - THEN IT IS TO BE IN CONDUIT.
3. ALL JUNCTION BOXES, COVERS, AND BACK BOXES ARE TO BE PAINTED RED.
4. ALL INDOOR HORNS, STROBES, HORN STROBES, AND MINI HORN STROBES ARE TO BE
MOUNTED 80" ABOVE THE FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER.
6. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE FOLLOWING:
A) 36" INCHES AWAY FROM ANY AIR HANDLING SYSTEM DIFFUSER
B) NOT IN CLOSE PROXIMITY TO ANY FLUORESCENT LIGHT FIXTURES
7. ALL WIRING PENETRATING ANY FIRE RATED BARRIER SHALL BE SEALED WITH MATERIAL WHICH
WILL PREVENT PASSAGE OF FLAME AND HOT GASES.
EQUIPMENT LEGEND
DEVICE
SYMBOL
QUANTITY
PART NUNMBER
DESCRIPTION
BACKBOX
14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
1
7024
FIRE ALARM CONTROL PANEL
INCLUDED
Et.
®
1
2WB
SMOKE DETECTOR
4 SQUARE X 1-7/8" DEEP
54C
5
GCC
HORN STROBE - CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
2
GCS
STROBE - CEILING MOUNT
4 SQUARE X 1-7/8" DEEP
1;1
19
GES3
STROBE
4 SQUARE X 1-7/8" DEEP
ISI
4
--
DUCT DETECTOR (PROVIDED BY
OTHERS)
4 SQUARE X 1-7/8" DEEP
CI]
WIRE LEGEND
TYPE
DESCRIPTION
A
18 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
B
14 AWG, 2 CONDUCTOR 'FPLP' JACKETED CABLE
C
18 AWG, 4 CONDUCTOR 'FPLP' JACKETED CABLE
FIRE COM NW.
P0 kx $SU SWIM WA 7Mf47777 7084384/80
PROJECT NNE:
DRANN: GENE JUAREZ SALON T.I.
gcEO; thca
Souncr Mall
Tukwila, WA 98188
DATE:
11/08/08
APPROVED BY
CEA
JD
JD
SCALE
NONE
NO.
DATE
REVISION
BY
SHEET TITLE:
RISER DIAGRAM AND
EOUIPMENT LEGEND
J0B NUMBER: 06-195
FA -2
GENERAL LEGEND
—rt---
-4
Ir---4 -
0
BOD
BOB
BOJ
FOS
F0W
EARTHQUAKE BRACING
PIPE HANGER - -
GROOVED CAP -
RIGID COUPUNG ( UNLESS NOTED )
CAP
PLUG
CENTERLINE -
HYDRAUUC REFERENCE POINT
CENTERLINE PIPE TO BOTTOM OF DECK
CENTERLINE PIPE TO BOTTOM OF BEAM
CENTERLINE PIPE TO BOTTOLM OF JOIST
FACE OF STUD
FACE OF WALL
FOC FACE OF CONCRETE -
AFF ABOVE RNISHED FLOOR
CH C>G HEIGHT
R C REDUCING COUPUNG
c. OUTLET COUPUNG - -
at► WELDED OUTLET
F 'nr FITTING -
E/C END TO CENTER
C/C CENTER TO CENTER
C/E CENTER TO ENO
GG -GROOVE/GROOVE
TG THREAD/GROOVE (ALSO "Gr) -
TxF THREADrFir (ALSO -Fxr) -
ATR ALL -THREAD R00 -
PIPING LEGEND
EXISTING PIPING
NEW PIPING
1
24'-0'
24'-0"
24'-0'
1
48'-6'
- UNEAR HVAC DIFFUSER ABOVE CEILING
CLOUD; 1W R1 SPA TREATMENT ROOMS
4,
WAITING
02
Y)CH:: 13.1'
=___ ___=_
5 - 3 CH: 12'-0'
V u2
j -OPEN TO
TO STOREFRONT
PENDENT SPRINKLERS
RELOCATE AS REQUIRED
FOR NEW - c0 NSTRUCTION
1 i
CH: 8'-6
3112
VANITY
19
CH:9'-6'
(4)F27-0
1
Id
1
A
CH: 11'-5';-
R=20'
-
1R
- LIGHT COLE ---/
" CIS 12'–O'
�1, w
0
li
11
11
0
1J
11
7- COVE W/ CO LED
UGHT STRIP
TO STOREFRONT
PENDENT SPRINKLERS
RELOCATE AS REQUIRED
FOR NEW CONSTRUCTIO
LEASE UNE -N
•
0
t
1
1
1
1
Y2
Y.
114 �R
1111=MMIIMI• •••••1 AMIN= 1
1
CH: (.10'-0.!_--
c=";
RECEPTION
Ot
CH: 13'-0'
1
° CH:9'-0"
2
RECEPTION
HALLWAY
e—
CH: 12`-0"
MOM
8" SYSTEM RISER
i
. GENE JUAREZ
TENANT SPRINKLERS
QTY
® RELIABLE MODEL G4A QUICK RESPONSE CONCEALED PENDENT 1/2" 155' 92
W/ WHITE COVER PLATE
RECESSED CEILING TRACK
FOR MO CURTAIN: TYP t
AT CHANGING ROOMS -
TENANT SPRINKLER PLAN
SCALE: 3/16' = 1'-0'
/
GENERAL NOTES
1" ARM -OVERS TYPICAL
HANG ALL ARM -OVERS GREATER THAN 12"
SPRINKLER SYSTEM DESIGN PER N.F.P.A 113
ALL MATERIALS SHALL BE NEW AND U.L LISTED OR F.M. APPROVED
FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13
ALL ELECTRICAL PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS
SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE
SIZING PER ORDINARY HAZARD SCHEDULE - MALL STANDARD
ORDINARY HAZARD OCCUPANCY: 130 S.F. PER SPRINKLER MAX
NEW PIPING TO BE 'DYNA-THREAD' THREADABLE THINWALL
•
•
FILE
ACCEPTED
Without Comments -
-.f] As Noted In Red
0 Per The Attached Letter
These plans have been reviewed by The Tukwila Fire
Prevention Bureau for conformance with current city
standards. Acceptance is subject to errors and
omissions which do not authorize violations of adopted
stanaaras and oralnances. The responsibility for the
adequacy of design rests totally with the designer.
Additions, deletions or revisions lo these drawings after
this date will void this acceptance and will require a
resubmittal of revised drawings for subsequent approval.
Final acceptance is subject to field test and inspection by
The Tukwila Fire Prevention Bureau.
Date: /0/1-/°).- • By: /Q '^^ ' / f
rUKWULA FIRE DEPARTMEtI%
Please call: 575-440Z -" -
and give this job
mom
and exact address for shdti 1
down or restoration approve
GENE JUAREZ TENANT
1
LIACY1S
SEARS
MERVYN'S
JCPENNEY
SOUTHCENTER MALL KEY PLAN
NTS
CROWN
FIRE PROTECTION
INCORPORATED
P.O. BOX 12113
MILL CREEK. WASHINGTON 98082-0113
PH. (425) 481-7669
Gene Juarez
Southcenter Mall =Space A-120
Tukwila, WA PAID
SEP 2 S zw8
DATE: 9/06
DRAWN: C.A.
Tuk,:i : Fire
SCALE: NOTED 1 OF 1