HomeMy WebLinkAboutPP - 111 SOUTHCENTER MALL - FYE / PEOPLE PICTURE - PERMITS AND PLANS111 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-042 11-S-019 11-S-007 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Picture People 111 Southcenter Mall Permit No.: 11-S-019 Date: January 25, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piFiing exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vacant Space 111 Southcenter Mall Permit No.: 11-S-007 Date: January 7, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'h inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. EXISTING ADJACENT TENANT SPACE (E) GWB SOFFIT HEADER PATCH Gu. - PAINT LEVEL 4 FINISH �— EXISTING ADJACENT TENANT SPACE 2 X 2 LAY IN LIGHT FIXTURE RE; ELECTRICAL - TYPICAL MECHANICAL DIFFUSER RE: MECHANICAL TYPICAL EXISTING BACK OF HOUSE - CORRIDOR --�` REF4ECTED CEILING PLAN 1/4" = 1'-0" Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 15— Add Reliable Model Fl Standard Response 155° Pendants I/2 x I/2 & 6- Add Reliabel Model G4 Standard Response 155 pendant Concealed 1/2 x 1/2 Add Reliable Model F1 Standard Response 155 Upright 1/2x1/2 24 — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TAP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD RCD PIPE SWIVEL RING STEEL JUIST/TRUSS HANGER DETAIL NTS GWS SOFFIT AT 14'-0" AFF GM SOFFIT AT 10'-2" AFF GM SOFFIT AT I4'-0" AFF (E) FINS TO BE DEMOLISHED AT BULKHEAD - ABOVE TENANT SPACE, NEUTRAL PIER AND DOOR Q V./itho it Comments As Noted in Red Per The Attached Letter hese plans have been reviewed by The Tukwila Fire 'evention Bureau for conformance t.v!th current City 'ndards. Acceptance is subject to errors and ,lissions which do not authorize v dations of adopted 3ndards and ordinances. The ft:sponsibiiity for the -equacy of design rests totally with the'designer. ditions, deletions or ro:,/is ons to th s c drawings after is date will void this acceptance and will require a ',submlttai of revised drawings for subsequent approval. nal acceptance is subject to field test and Inspection by le Tukwila Fire Prevention Bureau. _;ate: 1^ % i ! By: I.UKWILA FIRE DEPAK 1 dta,tit Please call: 575.4407 and give this job No. /I-S-oO2 and exact address for shut. or rustaratIon aoorevnt, L CROWf\ FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 AT TENANT SPACE 728 111 SOUTHCENTER TUKWILA, WA 98188 DATE:Jo,, '%Jolt PAID JAN-- 6 2011 TUI<WILA FIRE -./7„e9( 7//7/ DRAWN: J /L I SCALE: f5/ = 1 I ,,,,I, • .':-- , , . . . 5 z .). / .., - , . •.. ... • . ... : ..... . • . •.. ... i - .. r @ IstRooM. . . . X / ACTKTX X/ .. ✓/��9�79, �:. `r skim \ 0 1 CAL '.. •,.0 ;: Y . .� -MEGHAN YET D R • TENANT SPA. i@0 Th MECHANICALII EICAL .'. m :.. : �. 1II .. X X . i ! \ , _ 1�� 1 I 1 EXISTING BACK OF HOUSE - CORRIDOR --�` REF4ECTED CEILING PLAN 1/4" = 1'-0" Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 15— Add Reliable Model Fl Standard Response 155° Pendants I/2 x I/2 & 6- Add Reliabel Model G4 Standard Response 155 pendant Concealed 1/2 x 1/2 Add Reliable Model F1 Standard Response 155 Upright 1/2x1/2 24 — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TAP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD RCD PIPE SWIVEL RING STEEL JUIST/TRUSS HANGER DETAIL NTS GWS SOFFIT AT 14'-0" AFF GM SOFFIT AT 10'-2" AFF GM SOFFIT AT I4'-0" AFF (E) FINS TO BE DEMOLISHED AT BULKHEAD - ABOVE TENANT SPACE, NEUTRAL PIER AND DOOR Q V./itho it Comments As Noted in Red Per The Attached Letter hese plans have been reviewed by The Tukwila Fire 'evention Bureau for conformance t.v!th current City 'ndards. Acceptance is subject to errors and ,lissions which do not authorize v dations of adopted 3ndards and ordinances. The ft:sponsibiiity for the -equacy of design rests totally with the'designer. ditions, deletions or ro:,/is ons to th s c drawings after is date will void this acceptance and will require a ',submlttai of revised drawings for subsequent approval. nal acceptance is subject to field test and Inspection by le Tukwila Fire Prevention Bureau. _;ate: 1^ % i ! By: I.UKWILA FIRE DEPAK 1 dta,tit Please call: 575.4407 and give this job No. /I-S-oO2 and exact address for shut. or rustaratIon aoorevnt, L CROWf\ FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 AT TENANT SPACE 728 111 SOUTHCENTER TUKWILA, WA 98188 DATE:Jo,, '%Jolt PAID JAN-- 6 2011 TUI<WILA FIRE -./7„e9( 7//7/ DRAWN: J /L I SCALE: f5/ = 1 I °k�".'tiP �4 .rvrk$�:��a s,,.Y3�4�.?� r?"Fi�w �,;�W .i,ra »,;:�.L ,�.A"F A,�'`.•:;a �.°. •{.:v:aa 't��, x* GENERAL NOTES LIGHTING. PLAN SCALE: 1/4"=1'-0" SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE ORDINARY HAZARD — 130 S.F. MAX PER SPRINKLER 23 — Add Reliable Model 04A Standard Response 165 ° Pendents V2 x %z 23 -- Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8` ALL THREAD ROD STEEL JOIST/TRUSS HANGER DETAIL NTS TEELOX MECHANICAL BRANCH CONNECTOR SQE A B C 1-1/4 x 1/2 2 1-1/2 1-3/16 1-1/4 x 3/4 2-1/16 1-1/2 1-3/16 1-1/4 x 1 2-1/8 1-1/2 1-3/16. 1-112 x 1/2 2 1-1/2 1-3/16 1-1/2 x 3/4 2-1/16 1-1/2 1-3/16 1-1/2 x 1 2-1/8 1-1/2 1-3/16 2 x 1/2 2-5/16 1-13/16 1-3/16 2 x 314 2-3/8 1-13/16 1-3/16 2 x 1 2-7/16 1-13/16 1-3/16 2-1/2x1/2 2-9/16 2-1/16 1-3/16 2-112x314 2-11/16 2-1/8 1-3/16- 2-1/2 x 1 2-3/4 2-1/8 1-3/16 Vicinity Map Site Plan NORDSTROM 3 LEVELS 1 NIP —111 [ff-3 T AG. n:». 1! r 0 0 macy LEVELS d[1 —1— ❑ ❑ 0 C I\. MS v >rn 4 1 1 c 0 Without Comments o AS Noted in Red IX Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design reSt7 ;totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. • Date: /, ) i I By: -/1 1 UKN:!LA FIRE DEPARTI~d•NN Please call: 575-440Z and give this job No. 1i -s-01 and exact address for shots sown or rest3ration app -o 1. ORQ.\A/N FIRE PROTECTION INCORPORATED P.D. BOX 1211.3.' MILL CREEK, WASHINGTON -18082-0113 PH. (425) 481-7669 ?NcVlSofl Ian 2'J,2011 picture people l I . SOUTHCENTER MALL TUKWILA; WASHINGTON • DATE: ( ysz�p DRAWN: ...� i�I. SCALE: SHEET NUM 3E� SHEET TITLE TENANT SPACE # 728 FIRE ALARM SYSTEM DDITION UKWILA, WASHINGTON FA -01 SYSTEM \FORMATION FA -02 TYPICAL WH I \G AND MOU\TING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LI\E DIAGRAM FA -04 FRE ALARM SYSTEM PLA\ SHEET INDEX COrnM rias i\i j€t, in iced E1 P ur The Attached Letter Those plans have been reviewed by The Tukwila Fire Fir- :,1t10n Burcau for conformance with current City .:tanda.; ds. Acceptance is subject to errors and omissions which on riot _authorize violations of adopted ; z ; .dards ano ordinances The responsibility for the r1 of design r : -:. totally witli the designer. ::\4iditions, deletions or revisions to these drawings after this unite ,ti'iil void tnis 3cceptanc and will require a feSubmittTal of revised drawings for subsequent approval. Final acceptance IF.: subject to field test and Inspection by re Tukwila Fire ''revention Bureau Cate: - J �' J i ( By: NOTICE A completed, signed. Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testino. 1 UKWILA FIRE DEPARTMEN'. Pls-ase call: 575-440Z and give ibis job xact address for shut. ioubl or restJration aoor'1VI RULE AND CO\DUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPUFPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED GENERAL NOTES QUANTITY 1 2 1 4 2 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT ®D DUCT DETECTOR AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP BOX VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM STROBE ZR -MC -W SIEMENS 4S DEEP BOX +80" A.F.F. TO BOTTOM JUNCTION O BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND macys LEVELS NORDSTROM 3 I_E_ VH S 171,275st rano TOKYO 1 aeras Kai 71!4 RARE ROSE C.:iEaR LJ SL*T h tt.D AY?H Jr �Au.x nrkiAs OE<Gr bAY S GA?Er t „u:o 0 O ?,):E WA;�E.v3'xMS K.FhZO'1 W'ELRS STAPROC[S SA'T_ iEAV 3v' ISPE'.OR ARERC-..U77£ VCT✓ Au .:.DRKs m SPACE #728 (111) RED �R�ar _owes DRau CASJA_ OLE Er;.1.- E BE uEr<R I RS tW NFD A lye E%STR:G JCPenney 275.468sf SEARS 265Y re. 8 PAID FEB 16 2011 TUKWILA FIRE SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE co 0 2 CCCaa Z ccoo 1-- <rn CO o ccO QILO� wZZ W 0(T., C te �O cn Q (I) W CC r J Z 0 0 W Cf) >i(f) 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: JOB NUMBER: J SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60HZ DEDICATED EMERGENCY NOTE FOR ADd1IONAL SPECEICATOIS SEE PRODUCT DO MN1ATI0N. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VOC "l TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE - FRON XLS CONTROL PANEL (+ OR PREVIOUS ADDRESSABLE DEVICE O r + 0 0 HTRI-R I 1 ° NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE X00 0 0 PAD -3 00 NPUT INPUT TROUBLE MCI NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 - - e 0 0 3.6k EOL (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) 0❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 m C-1 O v o In o F rn (-)(-) (+)(+) P1 m 0 0 (+) 0 WIRE DESIGNATION: NUMBER OFCONDUCTORS SE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 PURR RED (JACKET) *CONTACT RA1lNGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 fl® 00 i +I HTRI-R 0 0 GROUND(cN O (+)) TO NEXT DEVICE OR ❑0l 1 1 1J� — 1 1 4 DESCRIPTION + crui o 0 o ,✓I \ a. �7 , 'E ( 7 0 r eg I FIA' ;„ hill 1:1.1:1:111:1:1• +— . "? Aoerr[roo " I 0 o Lg� 11 I:I:I 111:1. rv, - so + `S?l 19 X 4 J %IN00 ePQ2/ D❑ DEDU SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < (+) (+) (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV —..>. FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER 0 ❑ ❑� off' — _ 1 1J� I _ 1 — 4 DESCRIPTION fr 0 0C 74, q'm 'E ( 7 0 r eg I FIA' ;„ hill 1:1.1:1:111:1:1• / ' -e, I 0 o Lg� , �,s - so + CIRCUIT O❑ (-) ❑=D STROBE CIRCUIT Q ❑ Er/ STROBE 0 0 i 11 I:I:I 11:1:1.• OR FIRE ALARM CONTROL PANEL < (-) SPEAKER CIRCUIT (+) (+) STROBE CIRCUIT El/ SPEAKERISTROBE 0 0 'm,115.11� PA AStOEr OM w 'a IICGIII:I:1 (-) ;J J ❑oa STROBE CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE 5 OR 24K (EOLR) TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERATIN TEMPERATU E: +32' F (0.0 TO 100' F (338 C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR � DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE FROM PREVIOUS ADDRESSABLE DEVICE r• OR POWER SOURCE DATA IN (-) > DATA IN (+) > REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ CEILING >. TO NEXT ADDRESSABLE DEVICE HARD LID —\ SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE 000 o ° o o 0 o°° SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 1 N TO NEXT DEVICE 0 0 CADDY BAR aJ SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL rr) 00 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE co 0 z «<aaa CO Z co CO o z ti `,TWO * w z Z W LSI I CL °C O W Lt� T EE F— J a w 0 t� z 0 0 cr z c� z J U -CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: I SHEET FA -02 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved A PAD ONS Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 0.0731 Amps 0.106 Amps Current Load: ndby ;Ala Device Type Qty Amps Total Amps Total Main System Board SET -MC -C @15CD 1 0.03 0.03 0.030 0.030 2 0.069 1 0.111 SET -MC -C @75CD 2 0.2 0.264 0.069 0.138 ZR -MC -W @15CD 2 0.064 0.128 0.03 0.175 Amps 0.296 Amps Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.296 Amps For 5 Minutes= 0.025 Amp -hours 25% Derating= 0.931 Amp -hours Total System Current Load: 0.931 Amp -hours Bettery air to be:Used 12VDC Amp -hours 7.2AH:;; Notification Appliance Circuit Detail __ PROJECT: SPACE #728 Panel: PAD -3 POWER SUPPLY Date: February 15, 2011 ;Wire Resistance 2.58 CURRENT TOTAL= 2760.00 SET -MC -C @15CD SET -MC -C @30CD SET -MC -C @75CD 0 SET -MC -C @95CD 0 ZR -MC -C @110CD 2 ZR -MC -C @15CD 2 ZR -MC -W @15CD 0 ZR -MC -C @75CD DEVICES=,8 691_ 138; 111 111 2001 200; 264 2591 69 64 175 TOTAL mA=? 715; 14 282 0 0 138 1281 0 ;Total Wire Resistance (R ) Total Device Load, Amps (1) Voltage Drop ( E ) EOL Voltage 19.36j....._.... (WL * 2) * (R/ft) (Total Cct Load) 0.72 1(E= 1.04! 20.4-E) 19.36' 7151 1.46! Notification Appliance Circuit Detail PROJECT: SPACE #728 Panel: XLS V Date: February 15, 2011 i Wire Resistance 2.58 CURRENT TOTAL #REF! 32 170.7V !70.7V1/8 24 70.7V 114 0 70.7V1/2 0 70.7V1 DEVICES= 56 1.81 .54 0} 0 TOTAL mA= ;Total Wire Resistance (R ) Total Device Load, Amps (1) 'Voltage Drop ( E ) EOL Voltage 57.61 84.96 0 0 142.56! 14 1,302 19.4422363 ( WL * 2 )* (R/ft) (Total Cct Load) (E= I * R) (20.4 - E) 142.561 6.72 0.14 0.96 19.44 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS SYSTEM CALCULATIONS S EX EX (HALLWAY) S1-1 S1-2 15cd 30cd V1-1 1/4-W S1-3 S1-4 15cd 15cd V1-2 1 /4-W BPS EX � (CORRIDOR) S1-5 S1-6 S1-7 15cd 15cd 15cd V1-3 1 /4-W S1-8 95cd V1-4 1 /4-W EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. !REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 Z co T COCD2Z N9.w� wzz W -O cc CL 0 T W I H oC 0 1-5 0 w z J w -J z_ E5 0 z (1) z 0 0 J 0 w F- 6ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved ( SHEET FA -03 NEW SIGNALING CIRCUIT. TO EXISTING POWER SUPPLY 2 ALONG THE CORRIDOR IQ '=.,r�-J=-.CENT TENANT EX(ST NG :SPACEALDJACF:NT TENANT s b \ 1 — (E) ELECTRIC " r. F4NEL -. ELEGT. /-�v IL 1 TEN FN s,v,v';=5 S1-1 ;, - - -- 15cd iL S1-2 30cd V1--1 GW .-.;•.OFF. EO:"/E slyly S1-3 15cd CE; QCF TO FEMLEN S1-4 15cd V1-2 l S1-5 15cd it S,V,V b VAC4" T TENANT SFAr S,V,v S1-8 95cd V1-4 FUTUIRE . EN,- RETA L .=,R= S1-6 15cd S1-7 15cd V1-3 _EQL 51 S,v,v V'V EXISTING 3.c:CK OF SOUSE - CORRIDOR (E) DOOR TO REMAIN FIRE ALARM SYSTEM PLAN (Z) FINS, AT E.LK EID TO r : � r.'',:i , ^ - L�I N_ul €.Nu STOREFRONT GL4ZIN�JITI C — MALL COM 1C AREA R/ —, (E) `NS AT BULKCLEAD OVER DOOR TO 5E DEMO' IS" -I=D FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved Yq•Y ccT' v w y :4 z 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I DMG I DESCRIPTION SHOP DRAWINGS DATE 0 2 aaaaa 0 ao W Z «, O Q00 CO o z N < wH 1---O wZZ >m W L4-±". (/) U (j)i< w dog CC TTh F- W SCALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: I SHEET FA -04 111 SOUTHCENTER MALL ASSOCIATED PERMITS 11-F-042 11-S-019 11-S-007 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Picture People 111 Southcenter Mall Permit No.: 11-S-019 Date: January 25, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piFiing exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Vacant Space 111 Southcenter Mall Permit No.: 11-S-007 Date: January 7, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206)575-4407 • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2'h inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-05, section 13.5.6.2.2. • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 30 or more heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems, in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to all sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. EXISTING ADJACENT TENANT SPACE (E) GWB SOFFIT HEADER PATCH Gu. - PAINT LEVEL 4 FINISH �— EXISTING ADJACENT TENANT SPACE 2 X 2 LAY IN LIGHT FIXTURE RE; ELECTRICAL - TYPICAL MECHANICAL DIFFUSER RE: MECHANICAL TYPICAL EXISTING BACK OF HOUSE - CORRIDOR --�` REF4ECTED CEILING PLAN 1/4" = 1'-0" Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 15— Add Reliable Model Fl Standard Response 155° Pendants I/2 x I/2 & 6- Add Reliabel Model G4 Standard Response 155 pendant Concealed 1/2 x 1/2 Add Reliable Model F1 Standard Response 155 Upright 1/2x1/2 24 — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TAP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD RCD PIPE SWIVEL RING STEEL JUIST/TRUSS HANGER DETAIL NTS GWS SOFFIT AT 14'-0" AFF GM SOFFIT AT 10'-2" AFF GM SOFFIT AT I4'-0" AFF (E) FINS TO BE DEMOLISHED AT BULKHEAD - ABOVE TENANT SPACE, NEUTRAL PIER AND DOOR Q V./itho it Comments As Noted in Red Per The Attached Letter hese plans have been reviewed by The Tukwila Fire 'evention Bureau for conformance t.v!th current City 'ndards. Acceptance is subject to errors and ,lissions which do not authorize v dations of adopted 3ndards and ordinances. The ft:sponsibiiity for the -equacy of design rests totally with the'designer. ditions, deletions or ro:,/is ons to th s c drawings after is date will void this acceptance and will require a ',submlttai of revised drawings for subsequent approval. nal acceptance is subject to field test and Inspection by le Tukwila Fire Prevention Bureau. _;ate: 1^ % i ! By: I.UKWILA FIRE DEPAK 1 dta,tit Please call: 575.4407 and give this job No. /I-S-oO2 and exact address for shut. or rustaratIon aoorevnt, L CROWf\ FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 AT TENANT SPACE 728 111 SOUTHCENTER TUKWILA, WA 98188 DATE:Jo,, '%Jolt PAID JAN-- 6 2011 TUI<WILA FIRE -./7„e9( 7//7/ DRAWN: J /L I SCALE: f5/ = 1 I ,,,,I, • .':-- , , . . . 5 z .). / .., - , . •.. ... • . ... : ..... . • . •.. ... i - .. r @ IstRooM. . . . X / ACTKTX X/ .. ✓/��9�79, �:. `r skim \ 0 1 CAL '.. •,.0 ;: Y . .� -MEGHAN YET D R • TENANT SPA. i@0 Th MECHANICALII EICAL .'. m :.. : �. 1II .. X X . i ! \ , _ 1�� 1 I 1 EXISTING BACK OF HOUSE - CORRIDOR --�` REF4ECTED CEILING PLAN 1/4" = 1'-0" Design per NFPA 13, Ordinary Hazard 130 sq ft All materials to be new, U.L. listed, and F.M. approved All fire sprinkler heads to remain unobstructed by lightings, ceilings, or any other means All heads to be at least 6' apart o 15— Add Reliable Model Fl Standard Response 155° Pendants I/2 x I/2 & 6- Add Reliabel Model G4 Standard Response 155 pendant Concealed 1/2 x 1/2 Add Reliable Model F1 Standard Response 155 Upright 1/2x1/2 24 — Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TAP BEAM/ C -CLAMP WITH SET SCREW 3/8' ALL THREAD RCD PIPE SWIVEL RING STEEL JUIST/TRUSS HANGER DETAIL NTS GWS SOFFIT AT 14'-0" AFF GM SOFFIT AT 10'-2" AFF GM SOFFIT AT I4'-0" AFF (E) FINS TO BE DEMOLISHED AT BULKHEAD - ABOVE TENANT SPACE, NEUTRAL PIER AND DOOR Q V./itho it Comments As Noted in Red Per The Attached Letter hese plans have been reviewed by The Tukwila Fire 'evention Bureau for conformance t.v!th current City 'ndards. Acceptance is subject to errors and ,lissions which do not authorize v dations of adopted 3ndards and ordinances. The ft:sponsibiiity for the -equacy of design rests totally with the'designer. ditions, deletions or ro:,/is ons to th s c drawings after is date will void this acceptance and will require a ',submlttai of revised drawings for subsequent approval. nal acceptance is subject to field test and Inspection by le Tukwila Fire Prevention Bureau. _;ate: 1^ % i ! By: I.UKWILA FIRE DEPAK 1 dta,tit Please call: 575.4407 and give this job No. /I-S-oO2 and exact address for shut. or rustaratIon aoorevnt, L CROWf\ FIRE PROTECTION INCORPORATED P.O. BOX 12113 MILL CREEK, WASHINGTON 98082-0113 PH. (425) 481-7669 AT TENANT SPACE 728 111 SOUTHCENTER TUKWILA, WA 98188 DATE:Jo,, '%Jolt PAID JAN-- 6 2011 TUI<WILA FIRE -./7„e9( 7//7/ DRAWN: J /L I SCALE: f5/ = 1 I °k�".'tiP �4 .rvrk$�:��a s,,.Y3�4�.?� r?"Fi�w �,;�W .i,ra »,;:�.L ,�.A"F A,�'`.•:;a �.°. •{.:v:aa 't��, x* GENERAL NOTES LIGHTING. PLAN SCALE: 1/4"=1'-0" SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS SPRINKLER HEADS ARE NOT NECESSARILY LOCATED IN CENTER POINT OR QUARTER POINT OF CEILING TILE ORDINARY HAZARD — 130 S.F. MAX PER SPRINKLER 23 — Add Reliable Model 04A Standard Response 165 ° Pendents V2 x %z 23 -- Total RETAINER STRAP WHERE REQUIRED IN SEISMIC AREAS TOP BEAM/ C -CLAMP WITH SET SCREW 3/8` ALL THREAD ROD STEEL JOIST/TRUSS HANGER DETAIL NTS TEELOX MECHANICAL BRANCH CONNECTOR SQE A B C 1-1/4 x 1/2 2 1-1/2 1-3/16 1-1/4 x 3/4 2-1/16 1-1/2 1-3/16 1-1/4 x 1 2-1/8 1-1/2 1-3/16. 1-112 x 1/2 2 1-1/2 1-3/16 1-1/2 x 3/4 2-1/16 1-1/2 1-3/16 1-1/2 x 1 2-1/8 1-1/2 1-3/16 2 x 1/2 2-5/16 1-13/16 1-3/16 2 x 314 2-3/8 1-13/16 1-3/16 2 x 1 2-7/16 1-13/16 1-3/16 2-1/2x1/2 2-9/16 2-1/16 1-3/16 2-112x314 2-11/16 2-1/8 1-3/16- 2-1/2 x 1 2-3/4 2-1/8 1-3/16 Vicinity Map Site Plan NORDSTROM 3 LEVELS 1 NIP —111 [ff-3 T AG. n:». 1! r 0 0 macy LEVELS d[1 —1— ❑ ❑ 0 C I\. MS v >rn 4 1 1 c 0 Without Comments o AS Noted in Red IX Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design reSt7 ;totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. • Date: /, ) i I By: -/1 1 UKN:!LA FIRE DEPARTI~d•NN Please call: 575-440Z and give this job No. 1i -s-01 and exact address for shots sown or rest3ration app -o 1. ORQ.\A/N FIRE PROTECTION INCORPORATED P.D. BOX 1211.3.' MILL CREEK, WASHINGTON -18082-0113 PH. (425) 481-7669 ?NcVlSofl Ian 2'J,2011 picture people l I . SOUTHCENTER MALL TUKWILA; WASHINGTON • DATE: ( ysz�p DRAWN: ...� i�I. SCALE: SHEET NUM 3E� SHEET TITLE TENANT SPACE # 728 FIRE ALARM SYSTEM DDITION UKWILA, WASHINGTON FA -01 SYSTEM \FORMATION FA -02 TYPICAL WH I \G AND MOU\TING DETAILS FA -03 SYSTEM CALCULATIONS AND SINGLE LI\E DIAGRAM FA -04 FRE ALARM SYSTEM PLA\ SHEET INDEX COrnM rias i\i j€t, in iced E1 P ur The Attached Letter Those plans have been reviewed by The Tukwila Fire Fir- :,1t10n Burcau for conformance with current City .:tanda.; ds. Acceptance is subject to errors and omissions which on riot _authorize violations of adopted ; z ; .dards ano ordinances The responsibility for the r1 of design r : -:. totally witli the designer. ::\4iditions, deletions or revisions to these drawings after this unite ,ti'iil void tnis 3cceptanc and will require a feSubmittTal of revised drawings for subsequent approval. Final acceptance IF.: subject to field test and Inspection by re Tukwila Fire ''revention Bureau Cate: - J �' J i ( By: NOTICE A completed, signed. Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testino. 1 UKWILA FIRE DEPARTMEN'. Pls-ase call: 575-440Z and give ibis job xact address for shut. ioubl or restJration aoor'1VI RULE AND CO\DUIT FILL CHAT WIRE DESIGNATION SYMBOL DESCRIPTI❑N NUMBER OF CONDUCTORS SIZE TYPE COLOR CODE C STROBE SYNC TWISTED PAIR WITH SHIELD #14 FPL/FPLR RED (JACKET) D DATA LINE -ADDRESSABLE LOOP TWISTED PAIR WITH SHIELD #16 FPL/FPLR RED (JACKET) P DEVICE POWER - 24VDC TWO #16 FPL/FPLR RED (JACKET) S STROBE CIRCUIT - FEED TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) S' STROBE CIRCUIT - RETURN TWISTED PAIR W/ SHIELD #14 FPL/FPLR RED (JACKET) V SPEAKER CIRCUIT - FEED TWISTED PAIR #14 FPL/FPLR RED (JACKET) V' SPEAKER CIRCUIT - RETURN TWISTED PAIR #14 FPL/FPLR RED (JACKET) I REMOTE INDICATION LIGHT TWO #18 FPUFPLR RED (JACKET) CONDUIT FILL CHART NO. OF CONDUCTORS VOLTS WIRE SIZE TYPE DIMENSIONS AREA TWO 600V #12 AWG THHN/THWN .244 O.D. .0467 TWO 600V #14 AWG THHN/THWN TWISTED .210 0.D. .0346 TWO CONDUCTOR 300V #18 AWG FPL TW CABLE .156 O.D. .0191 CONDUIT FILL CALCULATE THE TOTAL AREA OF THE WIRE BEING RUN IN THE CONDUIT FROM THE TABLE ABOVE. CHOOSE THE SIZE OF CONDUIT BASED ON THE MAXIMUM FILL DIMENSION FROM THE TABLE BELOW THAT DOES NOT EXCEED THE TOTAL AREA OF THE WIRE. CONDUIT SIZE MAXIMUM FILL 1/2" .12 SQUARE INCH 3/4" .21 SQUARE INCH 1" .34 SQUARE INCH 1-1/8" .60 SQUARE INCH 1-1/2" .82 SQUARE INCH 2" 1.34 SQUARE INCH FIGURES ARE BASED ON 40% CONDUIT FILL AND ARE TAKEN FROM N.E.C., CHP. 9, TABLE 4. SHIELDED WIRE TO BE GROUNDED AT POINT OF ORIGIN PUNCHED THROUGH EACH DEVICE WRAPPED WITH TAPE AND TAPED AT END WIRE DESIGNATION FOR SIEMENS SYSTEM: DO NOT INSTALL ADDRESSABLE INITIATING DEVICES UNTIL PREPROGRAMMED WITH DEVICES ADDRESS. 1. NUMBERS ADJACENT TO DEVICE SYMBOL DENOTE DEVICE CIRCUIT/ADDRESS DEVICE 01-1-02 WOULD BE THE SECOND DEVICE ON ADDRESSABLE LOOP 1. 2. DETECTOR AND AUDIBLE CIRCUIT POLARITY SHALL BE OBSERVED. 3. AUDIBLE/VISUAL CIRCUIT WIRING IS SUPERVISED. NO PARALLEL BRANCHING IS PERMISSIBLE 4. INSTALLATION SHALL BE IN STRICT CONFORMANCE WITH THE NATIONAL ELECTRIC CODE, NFPA 72, LOCAL CODE(S), AND/OR AUTHORITY HAVING JURISDICTION. 5. INSTALLATION MATERIALS (I.E. CONDUIT, WIRE, FITTINGS, HANGERS, STANDARD BOXES, FIBER OPTICS CABLE, FITTINGS, AND ASSOCIATED EQUIPMENT) ARE NOT SUPPLIED BY SIEMENS CERBERUS DIVISION. 6. DETECTORS SHALL NOT BE MOUNTED IN DIRECT AIR STREAM OF AIR SUPPLY OUTLETS. PER NFPA 72 2-3.5.1 7. WIRING SHALL BE PER PLAN WITH RESPECT TO CONDUCTOR SIZE, & OR CABLE TRAY, TYPE, QUANTITY AND COLOR CODE. CONDUCTORS SHALL BE PERMANENTLY, AND UNIQUELY MARKED FOR FUTURE IDENTIFICATION. 8. INSTALLING CONTRACTOR SHALL RETURN ONE SET OF ACCURATELY MARKED DRAWINGS FOR "AS BUILT" PURPOSES. g. FOR ADDITIONAL INSTALLATION INSTRUCTIONS, REFER TO CATALOG CUT SHEETS AND/OR INSTALLATION INSTRUCTIONS. 10. THE 120vac POWER ELECTRICAL WORK SUPPLYING FIRE ALARM SYSTEM PANELS MUST COMPLY WITH ARTICLE 725 AND 760 OF NFPA 70, N.E.C. AND NFPA 72, SPECIFICALLY SECTION 1-5.2.5.2: IN REFERENCE TO DEDICATED BRANCH POWER SOURCES. 120vac POWER SHALL NOT BE APPLIED TO FIRE ALARM PANEL WITHOUT DIRECT SUPERVISION OF FIRE ALARM TECHNICIAN. 11. ALL HORN/STROBE AND STROBE DEVICES SHALL BE MOUNTED AT A HEIGHT OF 80" A.F.F. OR 6" BELOW DROPPED CEILING, WHICHEVER IS LESS. 12. ALL MANUAL PULL STATIONS SHALL BE MOUNTED AT 48" A.F.F. TO THE ACTIVATION DEVICE. 13. ALL PANEL NUMBERS AND CIRCUITS WILL BE ON THE RECORD DRAWINGS SET. 14. ALL 120VAC CIRCUITS ARE FROM DEDICATED CIRCUITS FROM THE EMERGENCY GENERATOR. 15. PER NFPA 72 SECTION 5-3.6.1.3 DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEAN-UP OF ALL TRADES IS COMPLETE AND FINAL. EXCEPTION: WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION FOR PROTECTION DURING CONSTRUCTION. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO FINAL CLEAN-UP BY ALL TRADES SHALL BE CLEANED OR REPLACED IN ACCORDANCE WITH NFPA 72 CHAPTER 7. 16. WIRING SHALL RUN CONTINUOUS FROM FACP TO FIRST DEVICE ON A CIRCUIT AND THEN FROM DEVICE TO DEVICE WITHOUT SPLICING IN PULL BOXES OR OTHER BACK BOXES OF DIFFERENT CIRCUITS. 17. ALL WIRING SHALL BE METERED, VERIFIED TO BE CONTINUOUS, FREE OF GROUND AND FREE OF SHORTS BETWEEN CONDUCTORS AND OTHER CIRCUITS PRIOR TO FINAL EQUIPMENT TRIM. 18. ALL CABLES SHALL BE MARKED AS INDICATED ON FIRE ALARM RISER WITH A PERMANENT LABEL AT ALL DEVICES, JUNCTION BOXES AND FACP. 19. THE ELECTRICAL CONTRACTOR SHALL CLEAN ALL DIRT AND DEBRIS FROM THE OUTSIDE AND INSIDE OF THE FIRE ALARM BACK BOXES AND JUNCTION BOXES AFTER COMPLETION OF THEIR INSTALLATION. 20. DETECTORS MUST BE RATED FOR TEMPERATURE IN THE ENVIRONMENT IN WHICH IT IS LOCATED. 21. ALL WIRING BETWEEN FLOORS SHALL BE LOCATED IN CONDUIT. 22. 23. NFPA 72 2007 6.4.2.2.2 ALL STYLES OF CLASS A CIRCUITS USING PHYSICAL CONDUCTORS (E.G., METALLIC, OPTICAL FIBER) SHALL BE INSTALLED SUCH THAT THE OUTGOING AND RETURN CONDUCTORS, EXITING FROM AND RETURNING TO THE CONTROL UNIT, RESPECTIVELY, ARE ROUTED SEPARATELY. THE OUTGOING AND RETURN (REDUNDANT) CIRCUIT CONDUCTORS SHALL NOT BE RUN IN THE SAME CABLE ASSEMBLY (I.E., MULTI -CONDUCTOR CABLE), ENCLOSURE, OR RACEWAY. NFPA 72 2007 A.6.4.2.2.2 A GOAL OF 6.4.2.2.2 IS TO PROVIDE ADEQUATE SEPARATION BETWEEN THE OUTGOING AND RETURN CABLES. THIS SEPARATION IS REQUIRED TO HELP ENSURE PROTECTION OF THE CABLES FROM PHYSICAL DAMAGE. THE RECOMMENDED MINIMUM SEPARATION TO PREVENT PHYSICAL DAMAGE IS 305 MM (1 FT) WHERE THE CABLE IS INSTALLED VERTICALLY AND 1.22 M (4 FT) WHERE THE CABLE IS INSTALLED GENERAL NOTES QUANTITY 1 2 1 4 2 2 EX SYMBOL DESCRIPTION MODEL MANUFACTURER BACKBOX MOUNTING HEIGHT ®D DUCT DETECTOR AD2-P W/ SIEMENS HFP-11 DET. DUCT HOUSING VERIFY IN FIELD HTR -R INTERFACE MODULE WITH RELAY HTRI-R SIEMENS 4S DEEP BOX VERIFY IN FIELD TSM DUCT DETECTOR TEST SWITCH TSM -1 SIEMENS 1 -GANG BOX VERIFY IN FIELD S FIRE ALARM SPEAKER STROBE SET -MC -CW SIEMENS 4S DEEP BOX CEILING W/ 1-1/2 EXTN FIRE ALARM STROBE ZR -MC -CW SIEMENS 4S DEEP BOX CEILING FIRE ALARM STROBE ZR -MC -W SIEMENS 4S DEEP BOX +80" A.F.F. TO BOTTOM JUNCTION O BOX N/A N/A N/A VERIFY IN FIELD A.F.F. ABOVE FINISHED FLOOR N/A N/A N/A N/A EX EXISTING DEVICE N/A N/A N/A N/A F.B.O. FURNISHED BY OTHERS N/A N/A N/A N/A N/A NOT APPLICABLE N/A N/A N/A N/A RED AS BUILT ADD OR CHANGE N/A N/A N/A N/A GREEN AS BUILT REMOVE N/A N/A N/A N/A BLUE AS BUILT NOTES TO CAD N/A N/A N/A N/A SYMBOLS LEGEND macys LEVELS NORDSTROM 3 I_E_ VH S 171,275st rano TOKYO 1 aeras Kai 71!4 RARE ROSE C.:iEaR LJ SL*T h tt.D AY?H Jr �Au.x nrkiAs OE<Gr bAY S GA?Er t „u:o 0 O ?,):E WA;�E.v3'xMS K.FhZO'1 W'ELRS STAPROC[S SA'T_ iEAV 3v' ISPE'.OR ARERC-..U77£ VCT✓ Au .:.DRKs m SPACE #728 (111) RED �R�ar _owes DRau CASJA_ OLE Er;.1.- E BE uEr<R I RS tW NFD A lye E%STR:G JCPenney 275.468sf SEARS 265Y re. 8 PAID FEB 16 2011 TUKWILA FIRE SITE PLAN Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I 0 m 0 DESCRIPTION SHOP DRAWINGS DATE co 0 2 CCCaa Z ccoo 1-- <rn CO o ccO QILO� wZZ W 0(T., C te �O cn Q (I) W CC r J Z 0 0 W Cf) >i(f) 4-CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: JOB NUMBER: J SHEET FA -01 THE DUCT SMOKE DETECTOR ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE WITH NFPA 72. THE PREFERRED INSTALL LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT WIDTHS FROM ANY BEND OR OTHER OBSTRUCTIONS AS INDICATED. NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. DUCK OVER 3' WIDE; SAMPLE TUBE MUST GO THRU THE DUCT AND BE CAPPED. TUBE OUTLET SAMPLING TUBE INLET SAMPLING AT LEAST SIX DUCT WIDTHS FROM BEND DUCT DETECTOR MOUNTING DETAIL 120VAC-60HZ DEDICATED EMERGENCY NOTE FOR ADd1IONAL SPECEICATOIS SEE PRODUCT DO MN1ATI0N. *CONTACT RATINGS 4.0A 0 125VAC 4.0A 0 30VOC "l TO NEXT ADDRESSABLE (+ DEVICE STOP IF LAST DEVICE - FRON XLS CONTROL PANEL (+ OR PREVIOUS ADDRESSABLE DEVICE O r + 0 0 HTRI-R I 1 ° NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. C -CABLE C -CABLE X00 0 0 PAD -3 00 NPUT INPUT TROUBLE MCI NAC2 NAC3 NAC4 AUX 1+ 1- 1 2+ 2- 2 NC C NO + - + - + - + - + - 0 - - e 0 0 3.6k EOL (-) (+) SPARE FROM PREVIOUS > (+) ADDRESSABLE > DEVICE (-) 0❑ NOTE: FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. 0 m C-1 O v o In o F rn (-)(-) (+)(+) P1 m 0 0 (+) 0 WIRE DESIGNATION: NUMBER OFCONDUCTORS SE TYPE COLOR CODE TWISTED PAIR WITH SHIELD #18 PURR RED (JACKET) *CONTACT RA1lNGS 4.0A 0 125VAC 4.0A 0 30VDC FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. O 0 fl® 00 i +I HTRI-R 0 0 GROUND(cN O (+)) TO NEXT DEVICE OR ❑0l 1 1 1J� — 1 1 4 DESCRIPTION + crui o 0 o ,✓I \ a. �7 , 'E ( 7 0 r eg I FIA' ;„ hill 1:1.1:1:111:1:1• +— . "? Aoerr[roo " I 0 o Lg� 11 I:I:I 111:1. rv, - so + `S?l 19 X 4 J %IN00 ePQ2/ D❑ DEDU SPARE SPARE (-) POWER SUPPLY & RELAY MODULE WIRING DETAIL FROM PRECEDING SPEAKER < (+) (+) (-) STOP IF LAST DEVICE DRY CONTACTS TO VAV —..>. FAN SHUTDOWN PROVIDED BY MECH/ELEC. DUCT DETECTOR, TEST SWITCH & RELAY MODULE WIRING DETAIL STROBE SPEAKER 0 ❑ ❑� off' — _ 1 1J� I _ 1 — 4 DESCRIPTION fr 0 0C 74, q'm 'E ( 7 0 r eg I FIA' ;„ hill 1:1.1:1:111:1:1• / ' -e, I 0 o Lg� , �,s - so + CIRCUIT O❑ (-) ❑=D STROBE CIRCUIT Q ❑ Er/ STROBE 0 0 i 11 I:I:I 11:1:1.• OR FIRE ALARM CONTROL PANEL < (-) SPEAKER CIRCUIT (+) (+) STROBE CIRCUIT El/ SPEAKERISTROBE 0 0 'm,115.11� PA AStOEr OM w 'a IICGIII:I:1 (-) ;J J ❑oa STROBE CIRCUIT (-) SPEAKER CIRCUIT SPEAKER STROBES & STROBES ONLY WIRING DETAIL TYPICAL WIRING AND MOUNTING DETAILS (+) (-) SPEAKER CIRCUIT S TO NEXT APPLIANCE 5 OR 24K (EOLR) TO NEXT SPEAKER OR END OR LINE RESISTOR 24K (EOLR) NOTE FOR ADDITIONAL SPECIFICATIONS SEE PRODUCT DOCUMENTATION. OPERATIN TEMPERATU E: +32' F (0.0 TO 100' F (338 C) HUMIDITY: 0-9 % RELATIVE HUMIDITY, NON -CONDENSING HFP-11 SMOKE DETECTOR � DEVICE IS LISTED FOR AIR VOLOCITY APPLICATIONS OF 300-4000 FT/MIN WHEN USED IN CONJUNCTION WITH DUCT HOUSINGS AD -11P OR AD-11XPR DB -11 STANDARD SMOKE DETECTOR BASE FROM PREVIOUS ADDRESSABLE DEVICE r• OR POWER SOURCE DATA IN (-) > DATA IN (+) > REAR VIEW (-) (+) SMOKE DETECTOR WIRING DETAIL HARD LID —\ CEILING >. TO NEXT ADDRESSABLE DEVICE HARD LID —\ SPEAKER SUPPORT TILE BRIDGE 4' SQUARE DEEP BOX WITH 1-1/2' EXTENSION CEILING MOUNTED SPEAKER/STROBE 000 o ° o o 0 o°° SPEAKER STROBE MOUNTING DETAIL JUNCTI❑N BOX MOUNTED ON CEILING FLEX JUNCTION BOX MOUNTED AGAINST CEILING SUPPORT 0 0 1 N TO NEXT DEVICE 0 0 CADDY BAR aJ SMOKE/HEAT DETECTOR SUSPENDED ILLUMINATED CEILING SMOKE/HEAT DETECTOR MOUNTING DETAIL rr) 00 0' 1743 IST AVE. SO., SEATTLE, WASHINGTON FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS REV. BY: 0 m 0 DESCRIPTION SHOP DRAWINGS DATE co 0 z «<aaa CO Z co CO o z ti `,TWO * w z Z W LSI I CL °C O W Lt� T EE F— J a w 0 t� z 0 0 cr z c� z J U -CALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: \OB NUMBER: I SHEET FA -02 Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved A PAD ONS Current Load: Standby: Alarm: Device Type Qty Amps Total Amps Total HFP-11 0.0022 0.0022 0.0023 0.000 AD2-P 1 0.0635 0.0635 0.064 0.064 HTR -R 2 0.009600 0.0096 0.021 0.042 0.0731 Amps 0.106 Amps Current Load: ndby ;Ala Device Type Qty Amps Total Amps Total Main System Board SET -MC -C @15CD 1 0.03 0.03 0.030 0.030 2 0.069 1 0.111 SET -MC -C @75CD 2 0.2 0.264 0.069 0.138 ZR -MC -W @15CD 2 0.064 0.128 0.03 0.175 Amps 0.296 Amps Standby Current Load: 0.03 Amps For 24 Hours = 0.720 Amp -hours Alarm Current Load: 0.296 Amps For 5 Minutes= 0.025 Amp -hours 25% Derating= 0.931 Amp -hours Total System Current Load: 0.931 Amp -hours Bettery air to be:Used 12VDC Amp -hours 7.2AH:;; Notification Appliance Circuit Detail __ PROJECT: SPACE #728 Panel: PAD -3 POWER SUPPLY Date: February 15, 2011 ;Wire Resistance 2.58 CURRENT TOTAL= 2760.00 SET -MC -C @15CD SET -MC -C @30CD SET -MC -C @75CD 0 SET -MC -C @95CD 0 ZR -MC -C @110CD 2 ZR -MC -C @15CD 2 ZR -MC -W @15CD 0 ZR -MC -C @75CD DEVICES=,8 691_ 138; 111 111 2001 200; 264 2591 69 64 175 TOTAL mA=? 715; 14 282 0 0 138 1281 0 ;Total Wire Resistance (R ) Total Device Load, Amps (1) Voltage Drop ( E ) EOL Voltage 19.36j....._.... (WL * 2) * (R/ft) (Total Cct Load) 0.72 1(E= 1.04! 20.4-E) 19.36' 7151 1.46! Notification Appliance Circuit Detail PROJECT: SPACE #728 Panel: XLS V Date: February 15, 2011 i Wire Resistance 2.58 CURRENT TOTAL #REF! 32 170.7V !70.7V1/8 24 70.7V 114 0 70.7V1/2 0 70.7V1 DEVICES= 56 1.81 .54 0} 0 TOTAL mA= ;Total Wire Resistance (R ) Total Device Load, Amps (1) 'Voltage Drop ( E ) EOL Voltage 57.61 84.96 0 0 142.56! 14 1,302 19.4422363 ( WL * 2 )* (R/ft) (Total Cct Load) (E= I * R) (20.4 - E) 142.561 6.72 0.14 0.96 19.44 1743 IST AVE. SO., SEATTLE, WASHINGTON 98134 FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS SYSTEM CALCULATIONS S EX EX (HALLWAY) S1-1 S1-2 15cd 30cd V1-1 1/4-W S1-3 S1-4 15cd 15cd V1-2 1 /4-W BPS EX � (CORRIDOR) S1-5 S1-6 S1-7 15cd 15cd 15cd V1-3 1 /4-W S1-8 95cd V1-4 1 /4-W EOL S1 FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. !REV. BY: DMG DESCRIPTION SHOP DRAWINGS DATE 0 Z co T COCD2Z N9.w� wzz W -O cc CL 0 T W I H oC 0 1-5 0 w z J w -J z_ E5 0 z (1) z 0 0 J 0 w F- 6ALE: NOT TO SCALE DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: JOB NUMBER: SINGLE LINE DIAGRAM Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved ( SHEET FA -03 NEW SIGNALING CIRCUIT. TO EXISTING POWER SUPPLY 2 ALONG THE CORRIDOR IQ '=.,r�-J=-.CENT TENANT EX(ST NG :SPACEALDJACF:NT TENANT s b \ 1 — (E) ELECTRIC " r. F4NEL -. ELEGT. /-�v IL 1 TEN FN s,v,v';=5 S1-1 ;, - - -- 15cd iL S1-2 30cd V1--1 GW .-.;•.OFF. EO:"/E slyly S1-3 15cd CE; QCF TO FEMLEN S1-4 15cd V1-2 l S1-5 15cd it S,V,V b VAC4" T TENANT SFAr S,V,v S1-8 95cd V1-4 FUTUIRE . EN,- RETA L .=,R= S1-6 15cd S1-7 15cd V1-3 _EQL 51 S,v,v V'V EXISTING 3.c:CK OF SOUSE - CORRIDOR (E) DOOR TO REMAIN FIRE ALARM SYSTEM PLAN (Z) FINS, AT E.LK EID TO r : � r.'',:i , ^ - L�I N_ul €.Nu STOREFRONT GL4ZIN�JITI C — MALL COM 1C AREA R/ —, (E) `NS AT BULKCLEAD OVER DOOR TO 5E DEMO' IS" -I=D FLAG NOTES: FIELD LOCATE RELAY MODULE FOR BACKGROUND MUSIC INTERFACE. DUCT DETECTOR & RELAY MODULE FOR FAN SHUTDOWN LOCATION TO BE FIELD VERIFIED BY MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS. Proprietary and Confidential, Copyright 2010 by Guardian Security Systems, Inc. All Rights Reserved Yq•Y ccT' v w y :4 z 1743 IST FAX (206) 628-4990 TEL. (206) 622-6545 RELEASE/REVISIONS IREV. BY: I DMG I DESCRIPTION SHOP DRAWINGS DATE 0 2 aaaaa 0 ao W Z «, O Q00 CO o z N < wH 1---O wZZ >m W L4-±". (/) U (j)i< w dog CC TTh F- W SCALE: 1/4"=1'0" DRAWN BY: D. GARCIA DESIGNED BY: R. VEZZANI DATE: 01 / 18/ 1 1 BACKROUND PLAN PROVIDED BY: .JOB NUMBER: I SHEET FA -04