10-F-001
Ansul
CO2 FLOW CALCULATION PROGRAM
Version 4.2.0
Data Input File:Data file name: C:1Program FilesIHP CO2 FLOWIQ1.hp2 with unsaved revisions.
Job: 0939
Customer: JORGENSEN FORGE
Address:
SEATTLE
REMARKS: Q6 QUENCH TANK 100# MAIN & RESERVE
System Conditions
Number of cylinders: 1 each containing 100 lbs CO2. Total agent 100 lbs
Engineering units (ft, lbs, psia) are specified
Local Application system
Flow rate is specified for each nozzle
Calculation based on 70 degree Fahrenheit pre -discharge Pipeline Temperature
Pipe Data Input
Sec Sec Nominal Length Elev 90's Side Thru Union/ Qty EqI
Start End Pipe Size (ft) (ft) Tee Tee Cplg CO2 (ft)
1 2 1/2 - 40T 0.10 0.00 0 0 0 0 0.00 38.0
2 3 1/2 - 80T 30.00 -8.00 9 0 0 0 0.00 13.0
3 501 1/2 - 40T 6.00 4.00 3 2* 0 0 11.00 0.0
3 502 1/2 - 40T 6.00 4.00 3 2* 0 0 11.00 0.0
* Section contains one or more side tees configured as dirt traps.
1 (End of Data Input File Printout)
Ansul Incorporated
HP CO2 FLOW CALCULATIONS
Version 4. 2.0
Data input file name: C:\Program Files1HP CO2 FLOWIQ1.hp2
0939
SEATTLE
REMARKS: Q6 QUENCH TANK 100# MAIN & RESERVE
Engineering units (ft, lbs, psia) are specified
Local Application system
Flow rate is specified for each nozzle
Agent Storage Conditions
Nominal Storage Pressure is 750 psi at 70 degrees Fahrenheit
100 lbs of carbon dioxide is stored in each of 1 cylinders.
Total carbon dioxide discharged is 100 lbs
Pressure Drop Results
Sec Sec Nominal Length Equiv Elev Tee/ Start Term Flow
Start End Pipe Size (ft) Length(ft) (ft) Mfld psi psi (lbs/min)
1 2 1/2 40 T 0.1 38.1 0.0 CV -98 750 748 22.0
2 3 1/2 40 T 30.0 57.0 -8.0 748 748 22.0
3 501 1/2 40 T 6.0 16.9 4.0 BHT 748 747 11.0
3 502 1/2 40 T 6.0 16.9 4.0 BHT 748 747 11.0
Calculation based on 70 degree Fahrenheit pre -discharge Pipeline Temperature
Nozzle Performance Summary
Nozzle Nominal Nozzle Weight (lbs) Initial Vapor Liquid End of Discharge
Number Pipe Size Code Discharged Time (sec) Time (sec) Time (sec)
501 1/2 40 T 1.80 50.0 3.6 193.0 196.6
502 1/2 40 T 1.80 50.0 3.6 193.0 196.6
Total carbon dioxide discharged is 100 lbs
Messages
Hydraulic calculation was successful.
Shortest liquid discharge time for Local Application Nozzle is 193. sec
Calculation performed on 12/10/2009 2:14:22 PM
Calculation by Suppression Systems, Inc.
Steven Tuck
4417 Pacific Hwy E
Tacoma WA 98424-2611 US
Telephone: 253-926-3300
Fax: 253-926-3306
12/10/2009 Time: 2:14:40 PM
1 End of Printout
Ansul
CO2 FLOW CALCULATION PROGRAM
Version 4. 2. 0
Data Input File:Data file name: C:\Program Files\HP CO2 FLOW1Q6.hp2 with unsaved revisions.
Job: 0939
Customer: JORGENSEN FORGE
Address:
SEATTLE
REMARKS: Q1 QUENCH TANK 200# MAIN & RESERVE
System Conditions
Number of cylinders: 2 each containing 100 lbs CO2. Total agent 200 lbs
Engineering units (ft, lbs, psia) are specified
Local Application system
Flow rate is specified for each nozzle
Calculation based on 70 degree Fahrenheit pre -discharge Pipeline Temperature
Pipe Data Input
Sec Sec Nominal Length Elev 90's Side Thru Union/ Qty Eql
Start End Pipe Size (ft) (ft) Tee Tee Cplg CO2 (ft)
1 2 1/2 - 40T 0.10 0.00 0 0 0 0 0.00 38.0
2 3 3/4 - 80T 1.00 0.00 0 0 1 0 0.00 24.0
3 4 3/4 - 80T 50.00 -8.00 6 0 0 0 0.00 17.0
4 5 3/4 - DFT 6.00 0.00 1 1 0 0 0.00 0.0
5 503 3/4 - DFT 1.00 0.00 0 1 0 0 23.00 0.0
5 6 3/4 - DFT 2.00 0.00 0 0 1 0 0.00 0.0
6 504 3/4 - DFT 1.00 0.00 0 1 0 0 23.00 0.0
6 505 3/4 - DFT 2.00 0.00 1 1* 1 0 23.00 0.0
4 7 3/4 - DFT 6.00 0.00 1 1 0 0 0.00 0.0
7 506 3/4 - DFT 1.00 0.00 0 1 0 0 23.00 0.0
7 8 3/4 - DFT 2.00 0.00 0 0 1 0 0.00 0.0
8 507 3/4 - DFT 1.00 0.00 0 1 0 0 23.00 0.0
8 508 3/4 - DFT 2.00 0.00 1 1* 1 0 23.00 0.0
* Section contains one or more side tees configured as dirt traps.
1 (End of Data Input File Printout)
Ansul Incorporated
HP CO2 FLOW CALCULATIONS
Version 4. 2.0
Data input file name: C:IProgram Files\HP CO2 FLOWIQ6.hp2
0939
SEATTLE
REMARKS: Q1 QUENCH TANK 200# MAIN & RESERVE
Engineering units (ft, lbs, psia) are specified
Local Application system
Flow rate is specified for each nozzle
Agent Storage Conditions
Nominal Storage Pressure is 750 psi at 70 degrees Fahrenheit
100 lbs of carbon dioxide is stored in each of 2 cylinders.
Total carbon dioxide discharged is 200 lbs
Pressure Drop Results
Sec Sec Nominal Length Equiv Elev
Start End Pipe Size (ft) Length(ft) (ft)
Tee/
Mfld
1 2 1/2 40 T 0.1 38.1 0.0 CV -98
2 3 3/4 40 T 1.0 26.4 0.0 2 cyl
3 4 3/4 40 T 50.0 79.4 -8.0
4 5 3/4 40 T 6.0 12.2 0.0 BHT
5 503 3/4 40 T 1.0 5.1 0.0 Side
5 6 3/4 40 T 2.0 3.4 0.0 Thru
6 504 3/4 40 T 1.0 5.1 0.0 Side
6 505 3/4 40 T 2.0 9.6 0.0 Thru
4 7 3/4 40 T 6.0 12.2 0.0 BHT
7 506 3/4 40 T 1.0 5.1 0.0 Side
7 8 3/4 40 T 2.0 3.4 0.0 Thru
8 507 3/4 40 T 1.0 5.1 0.0 Side
8 508 3/4 40 T 2.0 9.6 0.0 Thru
Start Term Flow
psi psi (lbs/min)
750 736 69.0
736 726 138.0
726 703 138.0
703 701 69.0
701 701 23.0
701 701 46.0
701 701 23.0
701 701 23.0
703 701 69.0
701 701 23.0
701 701 46.0
701 701 23.0
701 701 23.0
Calculation based on 70 degree Fahrenheit pre -discharge Pipeline Temperature
Nozzle
Number
503
504
505
Nominal
Pipe Size
3/4 40 T
3/4 40 T
3/4 40 T
Nozzle Performance Summary
Nozzle Weight (lbs)
Code Discharged
2.94 33.4
2.94 33.3
2.94 33.3
Initial Vapor Liquid End of Discharge
Time (sec) Time (sec) Time (sec)
1.4 61.5 62.9
1.5 61.4 62.9
1.6 61.3 62.9
1 (Continued)
Ansul Incorporated
HP CO2 FLOW CALCULATIONS
Version 4. 2. 0
Data input file name: C:\Program Files\HP CO2 FLOW\Q6.hp2
Nozzle Performance Summary (Continued)
Nozzle Nominal
Number Pipe Size
506 3/4 40 T
507 3/4 40 T
Nozzle Weight (lbs) Initial Vapor Liquid End of Discharge
Code Discharged Time (sec) Time (sec) Time (sec)
2.94 33.4 1.4 61.5
2.94 33.3 1.5 61.4
508 3/4 40 T 2.94 33.3
Total carbon dioxide discharged is 200 lbs
Messages
1.6 61.3
Hydraulic calculation was successful.
Shortest liquid discharge time for Local Application Nozzle is 61.3 sec
Calculation performed on 12/10/2009 2:16:55 PM
Calculation by Suppression Systems, Inc.
Steven Tuck
4417 Pacific Hwy E
Tacoma WA 98424-2611 US
Telephone: 253-926-3300
Fax: 253-926-3306
12/10/2009 Time: 2:17:57 PM
2 End of Printout
62.9
62.9
62.9
GENERAL NOTES:
1. ALL DOORS IN THE CLEAN AGENT HAZARD AREA SHALL HAVE DOOR CLOSURES, DOOR SWEEPS AND DOOR SEALS. (BY OTHERS )
2. THE DISCHARGE TIME OF THE SYSTEM SHALL NOT EXCEED 10 SECOND. THE PROTECTED VOLUME IS TO BE FLOODED AT A 4.2%
CONCENTRATION UNLESS OTHERWISE NOTED ON THE SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS. THE HAZARD AREA
SHALL MAINTAIN A 4.2% CONCENTRATION FOR A MINIMUM OF 10 MIN.
3. THE CLEAN AGENT CONTROL PANEL SHALL HAVE BATTERY BACK-UP TO PROVIDE 24 HOURS OF STANDBY OPERATION WITH 5
MINUTES OF ALARM UNLESS NOTED OTHERWISE ON THE DRAWINGS AND THE BATTERY CALCULATIONS.
4. INTERLOCK WIRING AND CONDUIT TO SHUTDOWN THE HVAC SYSTEM AND/OR DAMPERS (IF REQUIRED) WILL BE WIRED BY
OTHERS. SUPPRESSION SYSTEMS INC. WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CONTROL PANEL.
5. INTERLOCK WIRING AND CONDUIT TO CONNECT TO THE REMOTE FIRE ALARM SYSTEM (IF REQUIRED) SHALL BE PROVIDED BY
OTHERS. SUPPRESSION SYSTEMS INC. WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CONTROL PANEL.
6. INTERLOCK WIRING AND CONDUIT TO SHUTDOWN EQUIPMENT (IF REQUIRED) SHALL BE PROVIDED BY OTHERS. SUPPRESSION
SYSTEMS INC. WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CONTROL PANEL.
7. THE CLEAN AGENT HAZARD AREA SHALL BE SEALED TO PREVENT LEAKAGE OF THE AGENT. (BY OTHERS )
SUPPRESSION SYSTEMS INC. WILL PROVIDE GUIDANCE AND/OR SUPERVISION.
8. THE 120VAC CIRCUIT FOR THE CLEAN AGENT CONTROL PANEL SHALL BEA DEDICATED CIRCUIT WITH A LOCK -OUT DEVICE ON
THE BREAKER SWITCH TO COMPLY WITH NFPA 72 CURRENT ADDITION.
9. ALL TERMINATION'S IN THE CLEAN AGENT CONTROL PANEL SHALL BE PERFORMED BY SUPPRESSION SYSTEMS INC.
CLEAN AGENT PIPING SYSTEM NOTES :
1. REFER TO SYSTEM DRAWINGS AND CALCULATIONS FOR THE LOCATION AND LAYOUT OF THE CLEAN AGENT DISTRIBUTION PIPING
SYSTEM. EXAMINE THE CONFIGURATION OF THE PIPING SYSTEM TO ENSURE THE PIPING AND DISCHARGE NOZZLES DO NOT
INTERFERE WITH ANY ON SITE PHYSICAL OBSTRUCTIONS WITHIN THE CLEAN AGENT HAZARD AREA BEFORE THE PIPING INSTALLATION
BEGINS. SHOULD ANY CONFLICTS OCCUR NOTIFY SUPPRESSION SYSTEMS INC. TO MAKE THE REQUIRED ADJUSTMENTS TO THE
SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS PRIOR TO BEGINNING PIPING INSTALLATION. ANY DEVIATIONS IN THE
ROUTING OF THE PIPE NETWORK SHALL BE VERIFIED AND APPROVED BY SUPPRESSION SYSTEMS INC.
2. CLEAN AGENT SUPPRESSION SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION,
AS WELL AS ALL APPLICABLE LOCAL CODES.
3. PIPING MATERIAL MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001 , CURRENT EDITION.
SCHEDULE 40 OR SCHEDULE 80 PIPE (BLACK OR GALVANIZED) MUST CONFORM TO ASTM A53 OR A106. ORDINARY CAST IRON
PIPE, STEEL PIPE CONFORMING TO ASTM -120, OR NONMETALLIC PIPE SHALL NOT BE PERMITTED TO BE USED.
4. PIPE FITTINGS MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001 , CURRENT EDITION. MALLEABLE
IRON FITTINGS (BLACK OR GALVANIZED) SHALL BE 300 LB. CLASS THAT CONFORM TO ASTM SPECIFICATION A-197. 150 LB. CLASS
FITTINGS AND ORDINARY CAST IRON FITTINGS ARE NOT PERMITTED. ONLY LISTED GROOVED , THREADED , WELDED OR
FLANGED FITTINGS MAY BE USED , PROVIDED THEY CONFORM TO THE ABOVE REQUIREMENTS. HOLE CUT FITTINGS
MAY NOT BE USED.
5. ALL PIPE JOINING METHODS SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION. TEFLON TAPE IS RECOMMENDED
AND SHALL BE USED WITH ALL THREADED PIPING CONNECTIONS. THREADED PIPE AND FITTINGS SHALL BE TAPERED
IN CONFORMANCE WITH ANSI SPECIFICATION B-20.1. ALL GROOVED PIPING CONNECTIONS SHALL BE BE LUBRICATED PER
MANUFACTURERS SPECIFICATIONS.
6. ALL PIPING MUST BE RIGIDLY SUPPORTED BY A COMBINATION OF PIPE HANGERS AND RIGID SUPPORT BRACKETS. PIPE HANGERS
ARE USED TO SUPPORT THE " DEAD LOAD " OF THE PIPING SYSTEM AND SHALL BE SPACED AT INTERVALS NOT EXCEEDING 15
FEET. RIGID SUPPORTS ARE REQUIRED TO SUPPORT THE " LIVE LOAD " OF THE PIPING SYSTEM DURING DISCHARGE. RIGID
BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE - 90° ELBOW, TEE AND NOZZLE. ALL 180° NOZZLES REQUIRE BACK -BRACING
IN THE OPPOSITE DIRECTION OF THE DISCHARGE PATTERN. EARTHQUAKE BRACING SHALL BE USED WHERE REQUIRED BY LOCAL
CODE. REFER TO ANSI 831.1 FOR BRACING REQUIREMENTS.
7. REDUCTIONS IN PIPE SIZE SHALL BE DIRECTLY AFTER A TEE WITH THE TEE BEING THE SAME PIPE SIZE AS THE INLET LINE TO THE
TEE. REDUCTIONS IN PIPE SIZE MAY ALSO BE MADE USING A CONCENTRIC BELL REDUCER AFTER A UNION, PROVIDED THE NEXT
CHANGE IN DIRECTION (TEE) IS LOCATED A MINIMUM OF 10 PIPE DIAMETERS DOWNSTREAM OF THE CONCENTRIC BELL
REDUCER. CONCENTRIC BELL REDUCERS OR CONCENTRIC REDUCING COUPLINGS SHALL BE USED TO MAKE ALL REDUCTIONS
IN PIPE SIZE. REDUCING BUSHINGS, WELD -O -LETS AND HOLE CUT FITTINGS SHALL NOT BE PERMITTED.
8. THE SYSTEM SHALL BE INSTALLED IN A PROFESSIONAL MANNER WITH " GOOD COMMERCIAL PRACTICE ". ALL PIPING AND
FITTINGS MUST BE REAMED , BLOWN CLEAN AND SWABBED WITH A CLEANING SOLVENT TO REMOVE DIRT , RUST
AND OIL.
9. PIPE REDUCTIONS MADE DIRECTLY AFTER A CHANGE IN DIRECTION , WITH THE FITTING BEING THE SAME PIPE SIZE AS THE INLET ,
SHALL BE MADE USING A COMMON CONCENTRIC BELL REDUCER. REDUCING BUSHINGS ARE NOT ACCEPTABLE ( UNLESS
OTHERWISE NOTED ). A MINIMUM OF 10 PIPE DIAMETERS MUST BE MAINTAINED FROM THE CENTER OF THE FITTING TO THE
CENTER OF THE NEXT CHANGE IN DIRECTION.
10. WHEN BRACING THE PIPING CARE SHOULD BE TAKEN TO INSURE THE NOZZLE LOCATIONS ARE WITHIN ONE FOOT OF THE
LOCATIONS SHOWN ON THE SYSTEM PLANS. CORRECT NOZZLES SHALL BE INSTALLED EXACTLY IN ACCORDANCE WITH THE
SYSTEM PLANS AND THE DEFLECTOR SET SCREW SHALL BE IN PLACE DURING A SYSTEM DISCHARGE OR THE AGENT
DISTRIBUTION AND THE SYSTEMS ABILITY TO SUPPRESS A FIRE MAY BE ADVERSELY AFFECTED. NOZZLES SHALL BE INSTALLED
PERPENDICULAR TO THE CEILING FOR PROPER DISTRIBUTION PATTERNS. 180° NOZZLES SHALL BE ALIGNED WITH THE ORIFICE
HOLES ORIENTED PARALLEL TO THE ADJACENT WALLS SO NO DIRECT WALL IMPINGEMENT OF THE AGENT OCCURS.
11. FINAL INSTALLATION ACCEPTANCE SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION.
ELECTRICAL SYSTEM NOTES
1. THE DETECTION AND CONTROLS PORTION OF THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
WITH NFPA 70, 72 AND STATE AND LOCAL CODES WHERE APPLICABLE.
2. ALL WIRING FOR THE CLEAN AGENT SUPPRESSION SYSTEM SHALL BE INSTALLED IN MINIMUM OF 1/2"
ELECTRICAL METALLIC TUBING (EMT) OR CONDUIT.
3. INITIATING AND RELEASING CIRCUITS SHALL BE INSTALLED N RACEWAYS. ( NFPA 2001 )
4. AC AND DC CURRENT SHALL BE RUN IN SEPARATE CONDUIT AND BOXES.
5. PAINT ALL J -BOXES AND COVERS RED TO IDENTIFY FIRE ALARM SYSTEM.
6. IDENTIFY EACH COVER WITH POWER LIMITED FIRE ALARM CKT.
7. MAINTAIN 1" SEPARATION BETWEEN ALL POWER LIMITED AND NON POWER LIMITED CIRCUITS.
8. CONTROL SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 72 ,
AS WELL AS ALL APPLICABLE LOCAL CODES.
9. SMOKE DETECTORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY OUTLET.
ALL SMOKE DETECTORS SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION TO ALLOW FUTURE
TESTING AND SERVICE.
10. WHEN 17 AMP BATTERIES ARE USED THERE SHALL BE NO PENETRATIONS THROUGH THE BOTTOM
OF THE CONTROL PANEL.
11. AIR HANDLING DAMPERS SHALL SHUT DOWN WHEN CLEAN AGENT SYSTEM IS IN THE PRE -DISCHARGE
CONDITION.
EXCLUSIONS
**WORK LISTED BELOW SHALL BE PROVIDED BY OTHERS OR UNDER OTHER SECTIONS OF THE PROJECT.**
1. 120 VAC POWER SUPPLY TO THE CLEAN AGENT CONTROL PANEL.
2. TELEPHONE LINES FOR REMOTE MONITORING.
3. INTERLOCK WIRING AND CONDUIT FOR SHUTDOWN OF HVAC , DAMPERS AND/OR ELECTRIC POWER
SUPPLIES , RELAYS , SHUNT TRIP BREAKERS OR OTHER DEVICES.
4. CONNECTION TO LOCAL OR REMOTE FIRE ALARM SYSTEMS OR LISTED CENTRAL ALARM STATION.
5. ALL MATERIALS AND LABOR TO ENSUE THE " AIR -TIGHTNESS " OF THE PROTECTED SPACE(S) AND
RESPONSIBILITY FOR THE INTEGRITY OF THE CLEAN AGENT PROTECTED SPACE TO SATISFY THE
REQUIREMENTS FOR THE TEN (10) MINUTE RETENTION TIME. SUPPRESSION SYSTEMS INC. MAY
PROVIDE ASSISTANCE , BY MEANS OF INSPECTION OF THE SPACE AND MAKING RECOMMENDATIONS
ON REMEDIAL ACTIONS THAT MAY BE REQUIRED TO ENSURE ROOM INTEGRITY.
DRAWING INDEX :
FP- 1 - COVER SHEET, NOTES AND FLOOR PLAN
FP- 2 - MACHANICAL DETAILS
FP- 3 - ELECTRICAL DETAILS
PROJECT DATA
APPLICABLE CODES :
NFPA 12 CURRENT EDITION
NFPA 70 CURRENT EDITION
NFPA 72 CURRENT EDITION
SCOPE OF WORK °
PROVIDE ANSUL CO2 CLEAN AGENT FIRE
SUPPRESSION AT QUENCH TANKS #Q1 AND #Q6,
WITH ANSUL DETECTION AND CONTROLS.
JORGENSEN FORGE
8531 EAST MARGINAL WAY SOUTH
SEATTLE, WA 98108
AHJ: FIRE PERMIT
CITY OF TUKWILLA
444 ANDOVER PARK EAST
TUKWILLA, WA 98188
PHONE: 206-575-4404
AHJ: ELECTRICAL PERMIT
6300 SOUTHCENTER BLVD. #100
TUKWILLA, WA 98188
PHONE: 206-4337165
CO2 PIPING
WAREHOUSE
FLOOR I
cJ
TOP OF TANK
FLUID LEVEL
Q1
Zto
N
WAREHOUSE CEILING
TOP OF TANK
\ts
CO2 PIPING
WAREHOUSE FLOOR
BILL OF MATERIALS
ITEM
QTY
PART No.
DESCRIPTION
1
6
426613
100 lb. CARBON DIXOIDE CYLINDER W/ HF ACTUATOR AND CV -98 VALVE
2
6
427082
200 BAR FLEXIBLE DISCHARGE BEND
3
4
40309
1/2" HEADER VENT ASSEMBLY
4
1
40094
1/2" HEADER SAFETY
5
1
40076
3/4" HEADER SAFETY
6
2
40860
1/2" CHECK VALVE
7
2
40852
3/4" CHECK VALVE
8
1
428153
1/2" LOCK OUT VALVE
9
1
428154
3/4" LOCK OUT VALVE
10
2
46250
1/4" PRESSURE SWITCH
11
2
42278
ODORIZER
12
6
426100
TYPE "D" NOZZLE W/ STRAINER ORIFICE CODE 3.0
13
2
426102
SEALED NOZZLE W/ STRAINER ORIFICE CODE 2.0
14
2
41942
MAIN NAME PLATE
15
2
41943
RESERVE NAME PLATE
16
2
70449
MAINTENANCE PLATE
17
2
425309
LEAVE AREA WARNING SIGN
18
2
425310
DONT ENTER WARNING SIGN
19
2
425311
CO2 DISCHARGE WARNING SIGN
20
2
433625
LOCK OUT WARNING SIGN
21
1
CUSTOM
CUSTOM BUILT FREE STANDING TWO CYLINDER RACK ASSEMBLY
22
1
CUSTOM
CUSTOM BUILT FREE STANDING FOUR CYLINDER RACK ASSEMBLY
23
1
434957
IQ -318 ADDRESSABLE RELEASE PANEL W/ BATTERIES
24
2
428655
DOUBLE ACTION WEATHER PROOF RELEASE STATION
25
2
076494
ABORT SWITCH
26
2
076498
KEYED LOCKOUT SWITCH
27
14
428098
FMM-1 MINI MONITOR MODULES
28
2
428101
FCM-1 INTELLIGENT CONTROL MODULE •
29
2
431526
HORN STROBE 75CD WEATHERPROOF
30
4
013975
325° ALL WEATHER VERTICAL EP HEAT DETECTOR W/ COLLECTOR
FLUID LEVEL
Q6
N
-sys}c►. - 6� ut_ ce»114.,1 54.44-,o•, Mek.16I,.e peen+ addr+essy5le...
PrOvi L Wt,rv,.,5 S 5 4SL pee MRA ia-, 1 II''
•-•71:".,0041( breaker hgNdt.¢ c1gc,.� 0� 4ek,cw%ut rA c vc✓ii- Lveak v.
fru. 01,er1•. K ,c Y y„t.
fU$►WItA FIRE DEPART ii lE
FREE STANDING CUSTOM RACK please call: 575-440Z
a d give this job
1-005' 0„D a 0a No:IQ' �- -
1-006 -007 and exact address for shut
'ion or restoration approval.
IfilledC #2
-008
1
O Without Comments
As Noted in Red
O Per The Attached Letter
These plans have been reviewed.by The Tukwila Fire
'revention Bureau for conformance with current City
standards. Acce .tfn�.e is subject to errors and
omissions which do not w.it:iorize violations of adopted
standards and orcin aces. The responsibility for the
adequacy of design tests totally with the designer.
Additions, deletions or revisions to these drawings after
this date will void this acceptance and will requirsa
resubmittal of revised drawings for subsequent approvak
Finalacceptance is subject to field test and Inspection b
The Tukwila Fire Prevention Bureau.
Date: I" By: AV/I
BOTTOM OF TRENCH
QUENCH TANK ELEVATION
SUPPRESSION SYSTEM INC. STANDARD SYMBOL LEGEND ( FOR PART NUMBERS AND QUANTITIES SEE PARTS LIST SHEET FP -1 )(If non standard symbol is used it will be called out on the drawing )
CONTROL PANEL
EZI
AIR SAMPLING PANEL
REMOTE ANNUNCIATOR UNIT
HEAT DETECTOR
Dl
SIREN
ca SUPPRESSION MANUAL RELEASE STATION
EOM
SINGLE HAZARD PANEL
MEI
AIR SAMPLING POWER SUPPLY
EXTENDER PANEL
SOLENOID RELEASING MODULE
SYSTEM CONTROL UNIT
ANALOG LOOP UNIT
IONIZATION DETECTOR
XXX° HEAT DETECTOR
v JUNCTION BOX
MAINTENANCE BYPASS SWITCH .«Ea
SUPPRESSION ABORT STATION
END OF LINE RESISTOR
BRO
MAIN FIRE ALARM CONTROL PANEL
RELAY MODULE
EMI
ADDRESSABLE OUTPUT MODULE (RELAY)
DUCT DETECTOR
FIRE ALARM PULL STATION
AIR SAMPLING DETECTION PORT
MEI
AUTOPULSE PANEL
Gal
SUPERVISED CONTROL MODULE
OM?8
ADDRESSABLE OUTPUT MODULE (SIGNAL)
OD
ELECTRIC ALARM BELL
PRE -ACTION SOLENOID
AIR SAMPLING DROP DETECTION PORT
HIGH LEVEL INTERFACE
AIYI
MINI MONITOR MODULE
AMP
ADDRESSABLE MONITOR MODULE
WEATHER-PROOF STROBE
OT
PRE -ACTION TAMPER SWITCH
S.S.I. SPECIAL ORDER SIGN
IMO
SUPPLEMENTAL POWER SUPPLY
LEM
KEYBOARD DISPLAY UNIT
ADDRESSABLE MONITOR MODULE (DUAL)
STROBE
PRE -ACTION FLOW SWITCH
1-000
COMM. LOOP # AND DEVICE ADDRESS
BATTERY CABINET
EEO
KEYBOARD DISPLAY UNIT (LOCAL)
•
PHOTOELECTRIC DETECTOR
HORN / STROBE
El
PRE -ACTION LOW AIR SWITCH
A1.000
AUDIBLE LOOP # AND DEVICE #
1-022
f
f.1-023
1-001
1-002
U
NAC #1IV75cd
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the. Inspector prior to
commencement of Acceptance
Testing of any Flie Alarm
and Detection Systems.
Failure of test will result
in a Re -Inspection Fee and
termination of the testing.
1-020
.1-021
-003
-004
THE TWO QUENCH TANKS ARE LOCATED IN THE OPEN AREA OF A LARGER
BUILDING APPROXIMATLY 100' APART. SSI SHALL RUN PIPING ALONG THE FLOOR
TO THE NORTH WALL WHERE A CUSTOM FREE STANDING RACK THAT SHALL
HOUSE THE CYLINDERS AND ALL THE ELECTRICAL EQUIPMENT STANDS.
QUENCH TANK FLOOR PLAN
ANSUL.
SUR:C ESSION SYSTEMS, INC.
SPECIAL HAZARD FIRE PROTECTION
4417 PACIFIC HIGHWAY EAST
TACOMA, WA 98424-2611 BUS: 253-926-3300
FAX: 253-926-3306
DEC 2 2 2009
Tukwila Fire
NO.
DATE
REVISION
BY
DATE:
e
n
e
A
A
4
DRAWN:
12/21 /09
NMR
CHECKED:
NMR
APPROVED BY:
SHT
PROJECT NAME:
JORGENSEN FORGE
8531 EAST MARGINAL WAY SO. / SEATTLE, WA 98108
SCALE:
1/4" = 1'-0"
NO.
DATE
REVISION
BY
SHEET TITLE:
FIRE SUPPRESSION AND DETECTION SYSTEMS
COVER SHEET, NOTES AND FLOOR PLANS
JOB NUMBER: 1001
FP -1 �/3
UNISTRUT FITTINGS
ITEM
UNISTRUT NO.
DESCRIPTION
1
P1000T
SLOTTED CHANNEL, 10' AND 20' LENGHTS
2
P1008
NUT, 3/8", 16 THREADS, W/ SPRING
3
HTHR037
STEEL THREADED ROD, 3/8", 16 THREADS
4
P2863
FLAT PLATE, 3/8" BOLT, 7/16" HOLE
5
P1280
CHANNEL END CAPS (TWO PIECES)
6
P1068
90° ANGLE, 2-1/4" X 1-5/8"
7
P2626
90° ANGLE, 2-1/8" X 2-1/8"
8
P1045
Z -SHAPE, 2-1/8" X 1-5/8"
9
P1769
BRACKET, 5-7/8" X 4-3/4", 6300 IN -LB RATING
NOTES:
1. ALL NUTS, BOLTS AND UNISTRUT FITTINGS ARE TO BE SUPPLIED
BY THE INSTALLER, AND CAN NOT BE ORDERED
THROUGH FIKE PROTECTION SYSTEMS.
2. ALL BRACKETING WITH UNISTRUT FITTINGS ARE SHOWN FOR
REFERENCE ONLY, AS ALL INSTALLATIONS WILL VARY WITH LOCATION.
1-1/2" ANGLE IRON OR
P1000 UNISTRUT
iTO MANIFOLD
DISCHARGE BEND
...***.-HF ACTUATOR
-CV-98 VALVE
®1 -CUSTOM RACK
0.25" PRESSURE
PORT
2.309"
2.925'
1.125" - 18 UNEF
PRESSURE OPERATED
ACTUATOR
CV98 ELECTRIC ACTUATOR
1.25"-1
2.5' 0
8 UNEF -
3.025'
1.125"-18UNEF
0.5" CONDUIT
THREADS
J
BOOSTER
ACTUATOR
4.5
2z5
HIX
HF ELECTRIC ACTUATOR
NOTE:
BEND SHOULD NOT BE SEVERE
ENOUGH TO KINK BRAIDED HOSE.
BRONZE FEMALE SWIVEL
ADAPTOR THREADED 1-5/16"
12 N-3 (TO CYLINDER VALVE)
CHECK VALVE
IBER GASKET MUST BE IN
PLACE WHEN ATTACHING
TO VALVE
BRONZE MALE COUPLING
1/2" NPT
CUSTOM CYLINDER RACK ASSEMBLY SINGLE ROW DETAIL
SHEET ROCK CEILING
MIN. 1 5/8" STRUT
STRUT CLAMP
CLEAN AGENT PIPE
STRUCTURE
MIN. 1 5/8" STRUT
STRUT CLAMP
CLEAN AGENT PIPE
CLEAN AGENT PIPE
1 -RAISED FLOOR
STRUT CLAMP
MIN. 1 5/8" STRUT
L STRUCTURE
STRUCTURE
PIPE MOUNTING DETAIL
3'-0"
15'-0"
11'-0"
8'-0"
1'-0"
SINGLE 100 LB. VALVE DETAIL
MAIN
w
cc
w
w
ccd
O Q6 HAZARD
ACTUATOR DETAILS
RATE BY VOLUME CALCULATIONS PER NFPA 12 SECTION 6.5 EDITION 2008
TOTAL AGENT = VOLUME X 0.25 FLOW RATE (LB/MIN/CF) X 1.4 (LIQUID FACTOR) X .5 (MIN. DISCHARGE TIME)
HAZARD INFORMATION Q1 - 10' 0 X 3.14 X 4' = 126 CF
126CFX0.25X 1.4X0.5 = 23.0/ 100 = 0.23 = 1 - 100 LB CYLINDER
MINIMUM AGENT 23LBS / 2 NOZZLES = 11.5 LBS PER NOZZLE
SUPPLIED AGENT 100LBS / 2 NOZZLES = 50 LBS PER NOZZLE
MAIN
w
w
MAIN
w
ec
w
w
cc
Q1 HAZARD
20'-0"
RATE BY VOLUME CALCULATIONS PER NFPA 12 SECTION 6.5 EDITION 2008
TOTAL AGENT = VOLUME X 0.25 FLOW RATE (LB/MIN/CF) X 1.4 (LIQUID FACTOR) X .5 (MIN. DISCHARGE TIME)
HAZARD INFORMATION Q1 - 13' X 15' X 4' = 780 CF
780 CF X 0.25 X 1.4 X 0.5 = 136.5/100 = 1.3 =2-100 LB CYLINDERS
MINIMUM AGENT 137LBS / 6 NOZZLES = 22.83 LBS PER NOZZLE
SUPPLIED AGENT 200LBS / 6 NOZZLES = 33.33 LBS PER NOZZLE
2'-9"
5'-0"
2'-9"
5'-0"
501
CODE 3.0 ,
2'-9"
504
( CODE 3.0 )�
2'-9"
502
CODE 3.0
505
CODE 3.0
503
( CODE 3.0
2'-9"
506
( CODE 3.0 T
502
( CODE 2.0
TYPICAL INSTALLATION DISCHARGE BEND DETAILS
1/2" LOCKOUT VALVE
1/4" PRESSURE SWITCH
TO Q6 HAZARD
DORIZER
1/2" HEADER SAFETY
1/2" HEADER VENT ASSEMBLY (TVP. 2)
DISCHARGE HOSE (TYP. 2) ---
CO2 VALVE ASSMEMBLY (TYP. 2
100 LB CO2 CYLINDER (TYP. 2)
V-0" (TYP.) ANGLE INTO HAZARD SEALED NOZZLE
2'-9"
1/2" SHORT NIPPLE (TYP. 5)
- 1/2" CHECK VALVE (TYP. 2)
- 1/2" X 1'-0" (TYP. 2)
1/2" TEE (TYP. 5)
s
MAIN
IJ
w
CC
w
w
cc
Q6 HAZARD MANAFOLD
4'-0" THESE SPECIFICATIONS ARE TO APPLY TO ALL INSTALLATIONS OF CARBON
DIOXIDE FIRE EXTINGUISHER SYSTEMS. NOTE: PIPE SHALL CONFORM TO
ASTM SPECIFICATIONS FOR A53 OR A106 PIPE. A120 SHALL NOT BE USED.
1. ALL PIPE UP TO AND INCLUDING 3/4" SIZE TO BE STANDARD WEIGHT
GALVANIZED STEEL (SCHEDULE 40). EXCEPT THE MANIFOLD SHALL BE
EXTRA HEAVY GALVANIZED STEEL (SCHEDULE 80).
2. ALL PIPE OVER 3/4" SIZE TO BE EXTRA HEAVY GALVANIZED STEEL
(SCHEDULE 80)
3. EXTRA HEAVY GALVANIZED MALLEABLE IRON OR DUCTILE IRON FITTINGS
SHOULD BE USED THROUGH 2" SIZE; CLASS 300 Ib. AND GALVANIZED
FORGED STEEL FITTINGS IN ALL LARGER SIZES.
4. PIPE LENGTHS GIVEN ARE FROM CENTER TO CENTER OF FITTINGS.
5. ALL DIMENSIONS ARE TO BE FIELD CHECKED. ANY DEVIATIONS FROM
THE ARRANGEMENT SHOWN WILL REQUIRE
COMPLETE REVIEW OF THE NOZZLE AND LINE PRESSURE
CALCULATIONS BY THE DESIGNER.
6. REAM, CLEAN, AND BLOW OUT ALL PIPE BEFORE INSTALLING.
7. CYLINDERS AND PIPE TO BE SECURELY BRACKETED ESPECIALLY AT
FITTINGS AND NOZZLES.
8. ALL DEAD END PIPE LINES TO BE PROVIDED WITH A 1/2" CAPPED
NIPPLE 2" LONG.
9. DETECTOR CABLE TO BE RUN IN 1/2" THINWALL CONDUIT (E.M.T.)
1'-C' (TYP.) ANGLE INTO HAZARD TYPE "D" NOZZLE
ip
a)
co
to
WEIGH RAIL
WEIGH
SCALE AND
LIFTING
RING. (NOT
SUPPLIED)
100 Ib. CO2
CYLINDER
_ CYLINDER
ro FOUNDATION
CYLINDER WEIGHING
ARRANGEMENT
3/4" LOCKOUT VALVE
1/4" PRESSURE SWITCH
3/4" HEADER SAFETY
3/4" HEADER VENT ASSEMBLY (TYP. 2)
DISCHARGE HOSE (TYP. 4)
CO2 VALVE ASSMEMBLY (TYP. 4)
100 LB CO2 CYLINDER (TYP. 4)
TO Q1 HAZARD
ODORIZER
- 3/4" SHORT NIPPLE (TYP. 7)
- 3/4" CHECK VALVE (TYP. 2)
- 3/4" XV -0" (TYP. 2)
- 3/4" X 3/4" X 1/2" TEE (TYP. 4;
MAIN
w
w
w
c
w
cc
w
w
cc
Q1 HAZARD MANAFOLD
ANSUL.
SUPRZESSION SYSTEMS, INC.
SPECIAL HAZARD RRE PROTECTION
4417 PACIFIC HIGHWAY EAST
TACOMA, WA 984242611 BUS: 253-926-3300
FAX: 253-926-3306
NO.
DATE
REVISION
BY
DATE:
12/21/09
DRAWN:
NMR
CHECKED:
APPROVED BY:
SCALE:
NO.
DATE
NMR
SHT
NOT TO SCALE
REVISION
BY
6
A
PROJECT NAME:
JORGENSEN FORGE
8531 EAST MARGINAL WAY SO. / SEATTLE, WA 98108
SHEET TITLE:
FIRE SUPPRESSION AND DETECTION SYSTEMS
MECHANICAL DETAILS
n
JOB NUMBER: 1001
FP -2 of/3
A-
A+
B-
B+
8 NAC
SECURITY SUPV.
TB9
ZONE CODS
NAC #1
A-
A+
B
B+
TB7 NAC
A-
A+
B-
B+
A
A
B
B
+
TB6 NAC
TB5
9
9
00
9
9
9
m
TB10r" 0B11
®REC IXMII� Acs
EIA -485 I
v¢ TERM.
NZ NW
O �
z
dND FAULT
ENABLE
DISABLE
#2
#3
#4
TB1
3v
C FINEU
NC
NO
C
NC
NO
eeeeee
TX RX REF TX RX REF
TB12
PRINTER
J1
00000
NUP PORT USB A
PC/CRT .onEtk J2
)USBB
'—"J3
®®®®
TB13
SLC 1
ALARM (TROUBLE
999999C NC NO C NC NO
ACTIVE
POWER 0
0
PRE-
DISCHARGE
DISCHARGE 0
ABORT El
ACTIVE
ACKNOWLEDGE
SCROLL DISPLAY
1
Q
i
2
W
A
1
LOWER
CASE
E
S
Z
FIRE
ALARM
f
4
R
D
X
PRE -ALARM SECURITY SUPERVISORY SYSTEM
TROUBLE
SIGNAL
SILENCE
5%1
T
F
6.
Y
G
1
V
7
U
H
B
LISABILW61-11 ACKSILENCE SW5 SW6 SW7
8
J
N
SYSTEM
RESET
9
1
0
K
M
10
9
1
P
L
SPACE
JP2 •
SIGNALS POINT
SILENCED DISABLED
DRILL
HOLD 2 SECONDS
a:
Enter
00000000000000000000
00000000000000000000J
DETECTOR
MODULE
OUTPUT
BATTERY
LEVELS
J
J5O3
O° J6
LAMP
TEST
NEXT
SELECTION
PREVIOUS
SELECTION
RELAAST
ENTRY
INCREMENT
NUMBER
+
(
NFS-320
JP1 O-0
O
RATE COMPENSATED HEAT DETECTOR (Q1)
7- ABORT STATION
MANUAL RELEASE
RATE COMPENSATED HEAT DETECTOR (Q6)
yl,
/- ABORT STATION
_/- MANUAL RELEASE
T I
WEATHERPROOF DIS -CHARGE HORN / STROBE (Q1) n
WEATHERPROOF DIS -CHARGE HORN / STROBE (Q6) n
120VAC BY OTHERS
FIRE SUPPRESSION
RELEASE PANEL
WITH BATTERY
BACKUP
NAC
NAC
CO2 TANKS
100# CYLINDERS
W/ BRACKET SUPPORTS
PER MANUFACTURES
RECOMMENDATIONS
z
z
2
UJ
U.1
W
Q1
w
w
W
6 DISCHARGE NOZZLES (Q1) --� I
2 DISCHARGE NOZZLES (Q6)
z
2
w
w
W
PRESSURE SWITCH (TYP.)
/-CONTROL HEAD/SOLENOID (TYP.)
AUX
POWER
MAIN/RESERVE
SWITCH
UNISTRUT BRACKET
KEY -OPERATED
'O'N _
24VDC
LOCK -OUT SWITCH
ACTUATOR
Ar AV
A�IQ Q
[]1•mr CONDUIT
ADAPTER PLATE --
+
0 N
24VDC
3-0 BOX
LOCK NUT
SENSOR
ACTUATOR
RELEASE CIRCUIT
'O'N
•
'O'N
KEY OPERATED LOCKOUT SWITCH WITH MAIN/RESERVE SWITCH WIRING
DETAIL
THERMAL DETECTOR
SURFACE MOUNTING
DETAIL
DISCHARGE VALVE
CEILING
gl-
ZC21
—I
SOL NOID
Imo
I
FROM
ZC21
L.
,
CONTROL
RELEASE
PANEL
MOUNT ALL DEVCES
ON THE CUSTOM
FRAMING
N.O.
N$
ZC11
UNIT
ZH11
I
I
NCUNISTRUT
NOT TO
720"
EXCEED
130.0'
(ADA)9�'C!�
ae.a
El,.
I MAX
UNIT
_
AC11
AK11
I
L____1
I
KEY OPERATED LOCKOUT SWITCH
WIRING DETAIL
MAIN / RESERVE SWITCH
WIRING DETAIL
GENERAL DEVICE
ELEVATION
HORN/STROBE
3.3K,
1W EOL
,Itimi
i i
HF ACTUATOR
EOL 7
+ +
47K 1/2W
El
19+
It
0
0
I
ti N
1S
�(
7
- -
- +
1
2
IC'
MOMS
FMM-101 ' °
e
I
ORANGE
.
00
4
03
FCM-1
IC
,I
.
+ UTD 144-
3
`o
ABORT STATION
I
m
f
RELEASE STATION
PRESSURE SWITCH
COIL 5
+
' IC
§LC -1IN
VIOLET(+)
I
SLC {+1 IN
,THERMAL
DETECTORS
B+ A+ B- A-
SUPERVISION
'T'
MODULE
SLC IN (-) ,
YELLOW (-) I
sLc( -)our '
-JOS
® S
SLC OUT (+1
SW (+) Our
FMM-101 WIRING DETAIL
NAC WIRING DETAIL
HF ACTUATION WIRING DETAIL
PARKING
PARKING
ENGINEERING
MAIN OFFICE
PARKING
MELT SHOP
MACHINE SHOP
Q1
AREA OF WORK Q6
FORGE SHOP
AREA MAP
ANSUL.
SUPR2ESSI0N SYSTEMS, INC.
SPECIAL HAZARD FIRE PROTECTION
4417 PACIFIC HIGHWAY EAST
TACOMA, WA :: 24.2611 BUS: 253-926-3300
NO.
DATE
REVISION
BY
DATE:
12/21/09
A
DRAWN:
NMR
CHECKED:
NMR
APPROVED BY:
SHT
PROJECT NAME:
JORGENSEN FORGE
8531 EAST MARGINAL WAY SO. / SEATTLE, WA 98108
A
A
SCALE:
NOT TO SCALE
4
NO.
DATE
REVISION
BY
SHEET TITLE:
FIRE SUPPRESSION AND DETECTION SYSTEMS
ELECTRICAL DETAILS
JOB NUMBER: 1001
FP -3 O1 3