HomeMy WebLinkAboutPP - 9100 EAST MARGINAL WAY SOUTH - AIRFIELD BUSINESS CENTER BLDG A - PERMITS AND PLANS9100 EAST MARGINAL WAY SOUTH ASSOCIATED PERMITS 17-F-111 13-F-080 11-F-143 00-F-047 11-S-149 11-S-032 461g,w44 4itt CITY OF TUKWILA FIRE MARSHAL'S OFFICE 206-575-4407 FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** SITE LOCATION King Co. Assessor's Tax No.: .642.2-(a 0 0 f 50 c/ otE o� 1 Site Address: 1 D D E . ��� 6'G� 1►'i ��I Win (, ,5 Ok ill (,1 1 �5 Suite Number: of l 1 U Floor: � " Qat), 0021, Tenant Name: / t 114'1 .rl d 1 New Tenant? ❑ - Yes sgi; No Property Owner's Name: AfX14' S9-1 ProIii illi h ROO9m,.cul Mailing Address: I4°'LL )114-P.())4I/1.,I1 Avf 6 • Tul%w i`[G{ , WR 9 g 1 �A City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Lt/CLnaC/CTDhf5 Company Name: LCL`?t,Gi.CiL H(C Xi'Tt/ Mailing Address: 1() ?) D X, %46q -" , WA Day Telephone: 2010 255 -la b2 `7 n ,� n City State Zip E-mail Address: L e n- (°�/ U.Sta 610.1 km +L 01'14 Fax Number: 263 -1,9)C.2- 4 gy Contractor's City of Tukwila NICET III number: Business License number: B u5 Ocicl 3 2 Total number of new/relocated devices or sprinkler heads: 121 Valuation of Project (contractor's bid price): $ 37,3S 3 Scope of Work (please provide detailed information): f2 j2 i, 2tit', 6( (5-{7f -9 a c} _" :5 Sa S i454 -c -,-v wifh noo aJcli /nAc7,A, * 4 5 Ra (:t PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR AUTHORIZED AGENT: Signature: {,01/ftn.e Print Name: 0/1/ Date: (9/I/)7 Plan Permit App.doc Day Telephone: Z142-256 /0/9d 1 8/22/14 TFD FP Form 8 443ttlaNt SITE LOCATION Site Address: CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** King Co. Assessor's Tax No.: ct t Do , ,ct,, Tenant Name: M€4/ s%cis Suite Number: / 3 4/ Floor: New Tenant? X- Yes ❑ - No Property Owner's Name: Mailing Address: City State Zip CONTACT PERSON -if there are questions about the submittal. Name: Company Name:e 4 (ca j' Nom_ Mailing Address: O I ©)( 7�5-ci W.e.vt-+ LAA 6 9 so t-{ ., �� (' n 5e�� / City State Zip E-mail Address: �? f• -k. c-�.J %�t�d /1•C . �.t� Fax Number: �j�,.��� 3© ��5� Day Telephone: 2''c-7j7.i8Oe.� Ttcc Valuation of Project (contractor's bid price): $ /7.elf:7 Scope of Work (please provide detailed information): 72 /� n e �fe-Q.1_ 7 e‘,15 -74b 42. rArtee PE ' T APPLICATION NOTES Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING 0 NER OR AUTHORIZED AGENT: Signature: Print Name: e -C 1. 4.J --v Plan Permit App.doc 5/14/10 Date: Day Telephone: ,02.47-7,6 7 S 2' TFD FP Form 8 litt,j44 SITE LOCATION CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East Tukwila, WA 98188 206-575-4407 Date application accepted: FIRE PROTECTION SYSTEMS PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. **PLEASE PRINT** /� �j� ? �'Kiing Co. Assessor's Tax No.: Site Address: "1 i 00 E. /"L 4 l A/ / c7(/ • Suite Numberl 1311 Floor: t Tenant Name: vii/t 1 "vl Sherels New Tenant? - Yes ❑ - No Property Owner's Name: 1+ A. Mailing Address: 70 ..?:;431() 64 V tzgt,itivbW/ City State Zip CONTACT PERSON -if there are questions about the submittal. �y Name: Sl l Day Tel phone: II J1 -.6A0-0 )i10 Company Name: " .�(.FiC l e tM r i� `. t UL (6fe ` • Mailing Address: -Mel Ke ri"/ a3 ort4 ""' E-mail Address: rs ast..rt 0 ax Number: 2� 3 b dOGI Valuation of Project (contractor's bid price): $ C3 140i-•" .- Scope of Work (please provide detailed information): �d 1St //�4' 4q(iffete `vg sivm Ditiv syxt,61I-3/1 PERMIT APPLICATION NOTES Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules. Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILD 1 ` NER OR AUT ZED AGENT: Signature: Date: (I* 1 ( Print Name: errA.Die. Day Telephol e• 11PZ -'78b b $ (0f0 Plan Permit App.doc 5/14/10 TFD FP Form 8 R FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Metal Shorts 9100 East Marginal Way S Permit No.: 11-S-149 Date: July 12, 2011 Reviewer: AI Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1"-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 1/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6ft.(9.2.1.3.3.3). IF . • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a Toss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. INSPECTION RECORD Retain a copy with permit INSPECTION NUMBER /7-f-/// PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 206-575-4407 Project: /4/7/Z eW riA.e% C moi^— Type of I pection: /,/''Z_ /*s 41 Address:! � Suite #: G/%��S Contact Person: Special Instructions: Occupancy Type: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: /tisf.e/� /I/00 rnz (�4,/ 719o) A Okx, i u 7 766F 61/ 94/7 - A bvizy cam• - 444 /L.;/ -jt ia Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: G-,40Date: ///,S// 7 Hrs.: 2 . $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 3/14/14 T.F.D. Form F.P. 113 INSPECTION NUMBER INSPECTION RECO Retain a copy with perm PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: 11-1 r PA P.K Sprinklers: Fire Alarm: Type of Inspection: TA, Address:Cj•/0.0 Suite #: a� nv11_ Permits: Contact Person: Special Instructions: /Uo f/icv,) cPiU SThi../., Phone No.: Approved per applicable codes. corrections required prior to approval. COMMENTS: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: /Uo f/icv,) cPiU SThi../., v q ; Ai: v!/6 V Pco- I \-5 © P1-0 p .17"7 /r o+— (ePo4', Iva stl., V (, p: , %fr o CCS3dP i0 faeg 1 •?4, J - Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector/ �� Date: 6.(46// Hrs.: $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: 1—cA y.., 3^o iv e5 Address: po c./'7 5 - City: City: %{ Company Name: l' CA- 6*d e_ i4 State: l� Zip: <O 41.2. 14-4 Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 i INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: Sprinklers: Type of Inspection: Address: e)(:)Contact Suite #: � � c� `�'' S Person: Special Instructions: Occupancy Type: Phone No.: Approved per applicable codes. Corrections required prior to approval. COMMENTS: T-6 Q Mc [, Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: cd—... Date: j //57j 3 Hrs.: I $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Billing Address Attn: Company Name: Address: City: State: Zip: Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113 Air -{;tick - TUK ILA FIRE MARSHAL'S OFF E Phone: 206-575-4407 • Fax: 206-575-4439 • Email: FireMarshal@tukwilawa.gov 4, CONTRACTORS MATERIAL AND TEST CERTIFICATE FIRE ALARM AND FIRE DETECTION SYSTEMS Fire alarm System is ready for Fire Department acceptance testing. Failure of test will result in termination of the testing and additional fees will be assessed. Contractor is responsible for supplying manpower for Final Acceptance Test with two-way communications. Date/05'h 7 Permit # Property Address 9/e., U ,t, 4 ( �,t� y Suite # City TUKWILA Zip Code °%f /C9J Name of Facility /2, r >C, % f i2.€ St3/c(7, /{ Occupied as /� t (e ( /1 S 01-r-5.5 C'1 1w" /AL, 1 t Owner or Representative Phone # Installing Company Cc(' Cc tie 4/4; 2 Installing Contractor's Address O. ac) x 741SS KY? A IAA 9,0V2.. City kr-i 1 Installer's Name (PRINT) License and/or Certificate General Contractor r !c �/ Phone # ICC - 7C 7— S / ie o * /14Q air LLC Electrical Contractor c.Scct r[' -c /7/4„ g. L.L C FACP Equipment Manufacturer Si ,4.z t l h, y L, Model # s�C> This system has been installed, pre -tested and operates in accordance with the standards listed below and was inspected by (c, sr -/.r %�/c,.�,,.,, LL C. On (date) ////7 lac.)/7 and includes the devices listed on back. Circle all that apply: NFPA 72, Chapter 1 2 4 5 6 7 and/or IFC SEC 907 NFPA 70, National Electrical Code, Article 760 Manufacturer's Instructions Manufacturer's Instructions Other (specify) Tukwila City Ordinance Numbers 2050, 2051 UL Central Station Monitor System is monitored by A/l,J/Q I'21 S SIGNED Date //`/S Ac.)/ 7 System Firmware: Installed version K. / Checksum Date Initial program Co.,vp(, �z Installation Date /r /5 2007 Revisions and Reasons /1/9 - Programmed by Yir c. / 4C Q ,., EQUIPMENT INSTALLED AND TESTED: Control Panel J of Manual Station to of _U Smoke. Detectors (- of .2-1. Heat Detectors So of CO Duct Detectors _ of A/V Devices L! 2of LIZ-- Audio Devices k) of 'kJ Visual Devices 11- of 12- Auto 2Auto Door Release of Trouble Indictors j of / Batteries Readings Battery 2C. Generator of HVAC Controls of Fire Alarm Dialer _ of J._ Monitored by /1/G4., 4 5 Make/Model S,i„ f %1'K r s h F/$ 7uu Make/Model ( -, %4n,, /1 f- Sk - A, // Make/Model S', J 1- ,kir/ It f- s/4- h4, , Make/Model < J f 14.(1 4 !- fk - //,-,_,- Make/Model Jt/Af- _.cy &-' o.- S s 4tr-.5-�- •mac --rs�— . . C5 �t�.-► 51.z Jc ✓' Make/Model /v/ Make/Model Si %,. %-7.1 /4 / SG ?c) Make/Model Make/Model Make/Model Full Load Charge .27 (f Make/Model Make/Model Make/Model /9 ES Ru c/.. c' / 77 g r Annunciator _L of J_ Make/Model Si Ara I l i f /S'G U Sprinkler System. (Fire Alarm connections only) Make/Model Make/Model Make/Model Make/Model Water Flow Sw. of Valve Tamper Sw. _ of PIV of Elec. Alarm Bell of Automatic time Delay of Water Flow Alarm A//� seconds. None Installed A//!'•,L Do you meet audible/visible requirements of WAC 51-20, IFC SEC 907., and/or NFPA 72 Chapter 6? Yes ) No Test of alarm System on emergency power, satisfactory? Yes No Test Witnessed by (- i S , . ,' 6 Title 19/4..,_ Date ///,74c.,/ 7 Comments: /rte' Lot_ Ca.1 C s Vlerto : .27 tel_ -2C- 7 ,/7c- 2 23, 9 Jt/.4c 27. /09 c 1/ 3. 25.7 Fire Alarm Certificate.doc Revised: 6/17/14 TFD FP Form #110 PLE From: AES Technical Support <support@aes-intellinet.com> Sent: Monday, October 20, 2014 9:04 AM To: ron_maynard@comcast.net Subject: Battery Calculations 4 attery requirement endceIcula i- ns for 7788E 17744P This attempts to address questions related battery backup requirements and calculations for the UL Listed 7788F and 7744F Subscriber units. Frequently Support is asked if a 10 AH or two 7 AH Batteries can be installed on a 7788F or 7744F to increase back-up capacity. The Technical Specifications on page 7 of the Installation and Operation Manual for the 7744F and 7788F lists: - BACK-UP BATTERY : 12V, 7.5AH (min) (24 Hour standby) - VOLTAGE: 12VDC nominal - CURRENT: 150 mA standby; 1.2A transmit - CURRENT with 7067/7770: 210 mA standby; 1.3A transmit And on page 10: Backup Battery requirement, Commercial Fire • Central Station Fire Signaling (24hr): use a 12V, 7.5 AH battery • Remote Station Fire Signaling (24hr): use a 12V, 7.5 AH battery 7.5 AH as stated in the Technical Specifications is a minimum. If longer back-up capacity is desired, a larger battery may be used. Installing a single 10 AH, two 7 AH, two 7.5 AH or two 10 AH is acceptable. These batteries and combinations have been tested to fully charge within 24 hours. To prepare for the UL Listing evaluation, testing was performed on a 7788F as follows. A fully charged 7788F with a 7.5 AH Battery was put into AC fault and a zone was activated via an auto cycling dry contact every 5 seconds. The "NTR RPT DLY " was reduced to 0 to accommodate the frequent new Packet transmission attempts. The 7788F was operated in this state for 24 hours. The AC was then restored and allowed to charge the 7788F for 48 Hours. Then AC was again removed and operated sending the Alarm and Restore every 5 seconds for another 24 hours. The 7788F and 7744F successfully passed this test on multiple attempts and on multiple units. The intent of describing the test above is to give you confidence that a 7.5 AH battery should operate a 7744F or 7788F in a normal installation where the "NTR RPT DLY " is typically set to 10 and provide sufficient capacity for 24 Hours of operation without AC. In addition the following information was offered by the Director or Operations for AES back on March of 2011. Refer to attached Technical Bulletin 7788battcalc R2.PDF. Information copied from Tech Bulletin below: Subject Standby Battery Calculations Product 7788F and 7744F r12 volt, 7.5 Amp Hour standby battery is required -to meet UL Standard —864 ed ion 9 listing equirements. The 7.5 amp hour battery will provide enough standby power for the 7788 or 7744 subscriber unit to operafe under normal conditions for a minimum of 24 hours_ The normal current load for a 7788F and 7744F, under normal operating conditions is 250ma/hr. 4 hours of operation requires -1 amp 8 hours of operation requires— 2 amps 12 hours of operation requires -3 amps 16 hours of operation requires -4 amps 20 hours of operation requires -5 amps 24 hours of operation requires -6 amps The normal current bad for a 7788F and 7744F with supplemental units 7067 or 7794, under normal operating conditions is 300ma/hr. 4 hours of operation requires— 1.2 amp 8 hours of operation requires— 2.4 amps 12 hours of operation requires -3.6 amps 16 hours of operation requires -4.8 amps 20 hours of operation requires -6 amps 24 hours of operation requires -7.2 amps El 2 advanced ideas advanced solutions Job Name: Airport Business Center Airport Business Center 9100 E. Marginal Way S. Seattle, WA 98068 Circuit Information Panel Name: SNAC1 Circuit Name: NAC1 Starting Voltage: Starting Voltage = 20.4 Prepared By: Leanne Jones Cascade Fire & Security P.O. BOX 7459 KENT, 98042 2067675800 (2) amp circuit Class B @ 14 AWG DC 24 - volt Supply CASCAAL963JT Type and Model Candela Current (Amps) Tone and Volume Dist from last device Dist from source (ft) 12 14 16 18 Horn/Strobe PC2R 75 0.176 Temporal, High 41 41 20.188 20.064 19.864 19.548 Horn/Strobe PC2R 75 0.176 Temporal, High 37 78 20.023 19.802 19.447 18.884 Strobe SCR 30 0.094 44 122 19.858 19.539 19.029 18.220 Strobe SCR 15 0.066 18 140 19.797 19.443 18.876 17.976 Horn/Strobe PC2R 15 0.079 Temporal, High 24 164 19.722 19.324 18.687 17.676 Strobe SCR 15 0.066 24 188 19.655 19.218 18.518 17.406 Strobe SCR 15 0.066 20 208 19.605 19.138 18.390 17.203 Horn/Strobe PC2R 30 0.107 Temporal, High 21 229 19.557 19.062 18.270 17.012 Horn/Strobe PC2R 75 0.176 Temporal, High 21 250 19.519 19.001 18.172 16.857 Strobe SR 15 0.066 26 276 19.489 18.955 18.098 16.739 Horn/Strobe PC2R 30 0.107 Temporal, High 42 318 19.453 18.897 18.007 16.594 Horn/Strobe PC2R 30 0.107 Temporal, High 32 350 19.439 18.876 17.972 16.539 Total current/amps 1.286 Total Dist:350 voltage drop 0.961 1.524 2.428 3.861 6/12/2017 1 Circuit Information Panel Name: SNAC1 Circuit Name: NAC2 Starting Voltage: Starting Voltage = 20.4 (2) amp circuit Class B @ 14 AWG DC 24 - volt Supply Type and Model Candela Current (Amps) Tone and Volume Dist from last device Dist from source (ft) 12 14 16 18 Horn/Strobe PC2R 30 0.107 Temporal, High 99 99 19.978 19.730 19.334 18.704 Horn/Strobe PC2R 75 0.176 Temporal, High 55 154 19.767 19.396 18.801 17.857 Horn/Strobe PC2R 75 0.176 Temporal, High 42 196 19.636 19.188 18.470 17.330 Horn/Strobe P2RK 75 0.176 Temporal, High 39 235 19.542 19.038 18.232 16.951 Horn/Strobe PC2R 15 0.079 Temporal, High 51 286 19.455 18.900 18.011 16.601 Horn/Strobe PC2R 30 0.107 Temporal, High 23 309 19.423 18.849 17.931 16.472 Horn/Strobe PC2R 30 0.107 Temporal, High 27 336 19.397 18.808 17.865 16.368 Strobe SR 15 0.066 36 372 19.378 18.778 17.817 16.291 Strobe SCR 15 0.066 22 394 19.372 18.769 17.802 16.268 Total current/amps 1.060 Total Dist:394 voltage drop 1.028 1.631 2.598 4.132 6/12/2017 2 odvwnoed idea& advanced solutions.- Circuit olutionsµ Circuit Information Panel Name: SNAC1 Circuit Name: NAC3 Starting Voltage: Starting Voltage = 20.4 (2) amp circuit Class B @ 14 AWG DC 24 - volt Supply Type and Model Candela Current (Amps) Tone and Volume Dist from last device Dist from source (ft) 12 14 16 18 Horn/Strobe PC2R 75 0.176 Temporal, High 98 98 19.894 19.597 19.122 18.367 Horn/Strobe PC2R 75 0.176 Temporal, High 38 136 19.725 19.329 18.694 17.686 Horn/Strobe PC2R 30 0.107 Temporal, High 29 165 19.616 19.156 18.419 17.249 Horn/Strobe PC2R 30 0.107 Temporal, High 38 203 19.490 18.956 18.101 16.743 Horn/Strobe PC2R 75 0.176 Temporal, High 42 245 19.369 18.764 17.794 16.255 Strobe SR 30 0.094 52 297 19.256 18.584 17.508 Horn/Strobe PC2R 15 0.079 Temporal, High 16 313 19.227 18.538 17.435 Horn/Strobe PC2R 15 0.079 Temporal, High 17 330 19.202 18.498 17.371 Horn/Strobe PC2R 15 0.079 Temporal, High 18 348 19.181 18.465 17.318 Horn/Strobe PC2R 15 0.079 Temporal, High 18 366 19.165 18.441 17.280 Strobe SR 15 0.066 28 394 19.151 18.417 17.242 Strobe SR 15 0.066 10 404 19.148 18.413 17.235 Total current/amps 1.284 Total Dist:404 voltage drop 1.252 1.987 3.165 6/12/2017 3 advanced ideas. advanced sokitions Circuit Information Panel Name: SNAC1 Circuit Name: NAC4 Starting Voltage: Starting Voltage = 20.4 (2) amp circuit Class B @ 14 AWG DC 24 - volt Supply Type and Model Candela Current (Amps) Tone and Volume Dist from last device Dist from source (ft) 12 14 16 18 Strobe SCR 15 0.066 145 145 19.601 19.132 18.380 17.187 Strobe SCR 15 0.066 10 155 19.548 19.048 18.248 16.977 Horn/Strobe PC2R 75 0.176 Temporal, High 34 189 19.379 18.780 17.820 16.296 Horn/Strobe PC2R 75 0.176 Temporal, High 41 230 19.204 18.502 17.377 Horn/Strobe PC2R 75 0.176 Temporal, High 38 268 19.068 18.287 17.034 Horn/Strobe PC2R 75 0.176 Temporal, High 31 299 18.980 18.146 16.810 Strobe SCR 15 0.066 47 346 18.879 17.986 16.555 Horn/Strobe PC2R 15 0.079 Temporal, High 18 364 18.845 17.932 16.469 Horn/Strobe PC2R 30 0.107 Temporal, High 26 390 18.804 17.867 16.366 Horn/Strobe PC2R 75 0.176 Temporal, High 23 413 18.778 17.825 16.300 Horn/Strobe PC2R 30 0.107 Temporal, High 36 449 18.762 17.801 16.261 Total current/amps 1.371 Total Dist:449 voltage drop 1.638 2.599 4.139 6/12/2017 4 Configure Circuits J I Print Page J Global Project Values: SILENT Project Name: Airport Business Center Standby Hours: 24101 KNIGHT Project ID: Alarm Mins: 5 Prepared By: Anton Remington Derating Factor: 1.2 5499 Power Expander Calculations Date: 6/12/2017 Voltage Drop Waming Version 02.18.09 Threshold %' 20 Panel ID: SNAC1 Model: 5499 Power Expander Max NAC Current: 3.0 Amps Location: 19110 Warehouse 1 Volts: 24 VDC Max Panel Current: 9.0 Amps _ Ckt.# Circuit Name Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 5499 5499 Pwr Module 1 1 0.075 0.205 NAC #1 NAC1 0.000 1.286 #14 Solid 2.52 350 1.76 18.13 11.12% NAC #2 NAC2 0.000 1.060 #14 Solid 2.52 394 1.99 18.30 10.32% NAC #3 NAC3 0.000 1.284 #14 Solid 2.52 404 2.04 17.79 12.82% NAC #4 NAC4 0.000 1.371 #14 Solid 2.52 449 2.26 17.30 15.21% Aux 5499 Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Total Standby Current (Amps) 0.075 5.206 Total Alarm Current Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 1.800 0.434 Total Alarm AH Required Total Combined AH Required 2.23 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of the minimal difference between solid and stranded wire no differential was made. Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 2.68 Configure Circuits J I Print Page J SILENT KNICI11' 5808 Calculations Version 10.24 14 Panel ID: Location: 15808 (Suite 9110 Global Project Values: Project Name: Project ID: ; Prepared By: Date: (Airfield Business Center 'Anton Remington 6/12/2017 Standby Hours: Alarm Mins: Derating Factor: Voltage Drop Waming Threshold % : Model: 5808 Add. Fire Alarm Control Panel Volts: 24 VDC 24 5 1 1.2 10 Max NAC Current: 3.0 Amps Max Panel Current: 6.0 Amps Ckt.# 5808 SK SK SK SK SK SK SK SK SK SK SK SK SK SK SK SK SK SK SK B224B1 B200SR B200S B200SR-LF B200S-LF B224RB RTS151 RTS151KEY Circuit Name Qty Current Draw Standby Alarm 5808 CTRL Panel Photo, Photo -T, PhotoR Ion Heat, Heat -HT, ROR Beam, Beam -T Duct Acclimate FIRE -CO Control Control -6 RelayMon-2 Monitor, Minimon Monitor -2 Monitor -10 Pull -SA, Pull -DA Relay Relay -6 Zone Zone -6 Isolator Module Isolator Base Sounder Base Intelligent Sounder Base Low Freq Sounder Base Low Freq Sounder Base Relay Base Magnetic Remote Test Key Activated Test 1 22 50 10 0.170 0.007 0.000 0.015 0.000 0.000 0,000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 0 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.365 0.007 0.000 0 015 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 RA100Z Remote LED 0.000 0.000 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial/Parallel Module 0.000 0.000 5496 Power Expander 0.000 0.000 5895XL Power Expander 0.000 0.000 5865-4 LED Annunciator (4G) 0.000 0.000 5865-3 LED Annunciator (3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 Wire AWG & Type Ohms Per Length(ft) Actual Volts Q '/oDrop 1000 Ft. One -Way Ohms EOL 5883 Relay Module 0 000 0.000 #12 Solid 1.59 0.00 20.40 0.00% NAC #1 SNAC Trigger 0.000 0 000 #12 Solid 1.59 0.00 20.40 0 00% NAC #2 Spare 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% NAC #3 Spare 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% NAC #4 Spare 0.000 0.000 Total Alarm Current (Amps) Total Standby Current (Amps) 0.215 0.415 Alarm Time In Minutes / 60 (5 Mins) Standby Time In Hours 24 0.083 Total Alarm AH Required Total Standby AH Required 5.168 0.035 Total Combined AH Required 5.20 Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 6.24 Command Shortcuts I Configure Circuits ` Print Page July 6, 2011 Fire SpnAle, Consulting LLC PO Box 872528 Vancouver, WA 98687 360-904-2833 phone 360-944-5191 fax firesprinkl 'rcpnsul ip.gf)cc,m(a°,t net Cascade Alarm 27623 Covington Way SE #1 PO Box 7459 Kent, WA 98042 Attn: Reid Saario Re: Metal Shorts Space #9134 Space D Airfield Business Center 9100 East Marginal Way S Tukwila, WA 98108 Reid, The following review and comments are based on drawing FP -1 dated 6-28-11, hydraulic calculations dated 6-28-11 and material data sheets. An extension to the existing wet pipe fire sprinkler system is provided by this submittal. Design is based on ordinary hazard group 2 providing a density of .20 over 1500 sq ft utilizing 155° upright and pendent quick response heads. The above design and material submittal meets the requirements of NFPA 13. Seismic bracing to meet the requirements of NFPA 13 (no seismic calculations submitted for this review). System hydraulic and alarm tests to be performed to meet the requirements of NFPA 13 and the local AH]. A contractor's material and test certificate shall be provided at the completion of the project. If you have any questions or need additional information on the above please contact the undersigned. Sincere' avid G. Wulbers Fire Sprinkler Consulting LLC Cc: Dan McLuen ._: Ofr.Ota 7/(o( 2©i( HRS SYSTEMS, INC 4792 LAVISTA ROAD TUCKER, GA 30084 HYDRAULIC CALCULATIONS FOR METAL SHORTS SPACE #9134 AIRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY S. TUKWILA, WA 98108 DRAWING NUMBER: FP -1 DATE: JUN 28, 2011 -DESIGN DATA - REMOTE AREA NUMBER: 1 REMOTE AREA LOCATION: SPACE D OCCUPANCY CLASSIFICATION: OHG II DENSITY: .20 gpm/sq. ft. AREA OF APPLICATION: 1500 sq. ft. COVERAGE PER SPRINKLER: 95 sq. ft. TYPE OF SPRINKLERS CALCULATED: 1/2 NUMBER OF SPRINKLERS CALCULATED: 18 *IN -RACK SPRINKLER DEMAND: gpm HOSE -STREAM DEMAND: 250 gpm TOTAL WATER REQUIRED (INCLUDING HOSE):619.5 gpm FLOW AND PRESSURE (AT CITY): 619.6 gpm @ 36.8 psi TYPE OF SYSTEM:WET *VOLUME OF DRY OR PREACTION SYSTEM: *DETAILS: WATER SUPPLY Source: CITY Test Date: 6-28-11 Test By:CITY Location: Static: 130 psi Residual: 20 psi Flow: 10,000 gpm Source Elevation Relative to Finished Flow Level: ft. INSTALLING CONTRACTOR Name: CASCADE ALARM & FIRE PROTECTION Address:P 0 BOX 7459, KENT, WA. 98042 Phone: Certification number:CASCAAL962RW NAME OF DESIGNER: REID AUTHORITY HAVING JURISDICTION: CITY OF TUKWILA NOTES: Calculations performed by HASS granted by HRS SYSTEMS, INC. TUCKER, GA 30084 USA. (Notes continue after pipe calculations results.) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 6/28/2011 C:\DATA\AIRFIELD SPACE D.SDF JOB TITLE: Metal Shorts Space #9134 WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CITY 130.0 20.0 10000.0 129.4 619.6 36.8 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 619.6 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 369.6 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) CITY 0.0 SOURCE 36.8 369.6 1 16.0 K= 5.60 21.4 25.9 2 16.0 K= 5.60 11.7 19.1 3 16.0 K= 5.60 11.9 19.3 4 16.0 K= 5.60 12.8 20.0 5 16.0 K= 5.60 13.6 20.6 6 16.0 K= 5.60 14.9 21.6 7 16.0 K= 5.60 11.9 19.3 8 16.0 K= 5.60 11.9 19.4 9 16.0 K= 5.60 12.3 19.6 10 16.0 K= 5.60 13.1 20.3 11 16.0 K= 5.60 11.9 19.3 12 16.0 K= 5.60 12.0 19.4 13 16.0 K= 5.60 12.4 19.7 14 16.0 K= 5.60 13.1 20.3 15 16.0 K= 5.60 14.1 21.0 16 16.0 K= 5.60 14.2 21.1 17 16.0 K= 5.60 14.6 21.4 18 16.0 K= 5.60 15.5 22.1 A 13.0 23.2 - - - B 13.0 23.2 C 13.0 23.3 D 13.0 23.5 E 13.0 23.6 F 13.0 24.9 G 13.0 25.3 H 13.0 25.9 TOR 13.0 26.0 AV 4.0 29.9 BF1 1.0 31.3 BF2 1.0 36.3 UG 0.5 31.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 6/28/2011 C:\DATA\AIRFIELD SPACE D.SDF JOB TITLE: Metal Shorts Space #9134 PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -25.9 1.682 PL 12.00 PF 0.6 1 16.0 5.6 21.4 25.9 3.7 120 FTG ET PE 1.3 A 13.0 0.0 23.2 0.0 0.021 TL 26.85 PV Pipe: 2 -19.1 1.682 PL 10.00 PF 0.2 2 16.0 5.6 11.7 19.1 2.8 120 FTG 2E PE 0.0 3 16.0 5.6 11.9 19.3 0.012 TL 19.90 PV Pipe: 3 -38.5 1.682 PL 10.00 PF 0.9 3 16.0 5.6 11.9 19.3 5.6 120 FTG 2E PE 0.0 4 16.0 5.6 12.8 20.0 0.044 TL 19.90 PV Pipe: 4 -58.5 1.682 PL 8.17 PF 0.8 4 16.0 5.6 12.8 20.0 8.4 120 FTG ---- PE 0.0 5 16.0 5.6 13.6 20.6 0.095 TL 8.17 PV Pipe: 5 -79.1 1.682 PL 8.17 PF 1.4 5 16.0 5.6 13.6 20.6 11.4 120 FTG ---- PE 0.0 6 16.0 5.6 14.9 21.6 0.166 TL 8.17 PV Pipe: 6 -100.7 1.682 PL 12.17 PF 7.0 6 16.0 5.6 14.9 21.6 14.5 120 FTG ET PE 1.3 B 13.0 0.0 23.2 0.0 0.260 TL 27.02 PV Pipe: 7 -19.3 1.682 PL 8.17 PF 0.1 7 16.0 5.6 11.9 19.3 2.8 120 FTG ---- PE 0.0 8 16.0 5.6 11.9 19.4 0.012 TL 8.17 PV Pipe: 8 -38.6 1.682 PL 8.17 PF 0.4 8 16.0 5.6 11.9 19.4 5.6 120 FTG ---- PE 0.0 9 16.0 5.6 12.3 19.6 0.044 TL 8.17 PV Pipe: 9 -58.3 1.682 PL 8.17 PF 0.8 9 16.0 5.6 12.3 19.6 8.4 120 FTG ---- PE 0.0 10 16.0 5.6 13.1 20.3 0.094 TL 8.17 PV Pipe: 10 -78.5 1.682 PL 29.50 PF 8.9 10 16.0 5.6 13.1 20.3 11.3 120 FTG 3ET PE 1.3 C 13.0 0.0 23.3 0.0 0.164 TL 54.25 PV Pipe: 10A -19.3 1.682 PL 8.17 PF 0.1 11 16.0 5.6 11.9 19.3 2.8 120 FTG ---- PE 0.0 12 16.0 5.6 12.0 19.4 0.012 TL 8.17 PV Pipe: 10B -38.7 1.682 PL 8.17 PF 0.4 12 16.0 5.6 12.0 19.4 5.6 120 FTG ---- PE 0.0 13 16.0 5.6 12.4 19.7 0.044 TL 8.17 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 6/28/2011 C:\DATA\AIRFIELD SPACE D.SDF JOB TITLE: Metal Shorts Space #9134 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 10C -58.4 1.682 PL 8.17 PF 0.8 13 16.0 5.6 12.4 19.7 8.4 120 FTG ---- PE 0.0 14 16.0 5.6 13.1 20.3 0.095 TL 8.17 PV Pipe: 10D -78.7 1.682 PL 25.00 PF 9.0 14 16.0 5.6 13.1 20.3 11.4 120 FTG 2E2T PE 1.3 D 13.0 0.0 23.5 0.0 0.165 TL 54.70 PV Pipe: 11 -21.0 1.682 PL 8.17 PF 0.1 15 16.0 5.6 14.1 21.0 3.0 120 FTG ---- PE 0.0 16 16.0 5.6 14.2 21.1 0.014 TL 8.17 PV Pipe: 12 -42.1 1.682 PL 8.17 PF 0.4 16 16.0 5.6 14.2 21.1 6.1 120 FTG ---- PE 0.0 17 16.0 5.6 14.6 21.4 0.052 TL 8.17 PV Pipe: 13 -63.6 1.682 PL 8.17 PF 0.9 17 16.0 5.6 14.6 21.4 9.2 120 FTG ---- PE 0.0 18 16.0 5.6 15.5 22.1 0.111 TL 8.17 PV Pipe: 14 -85.7 1.682 PL 20.17 PF 6.7 18 16.0 5.6 15.5 22.1 12.4 120 FTG ET PE 1.3 E 13.0 0.0 23.6 0.0 0.192 TL 35.02 PV Pipe: 15 -25.9 4.260 PL 10.00 PF 0.0 A 13.0 0.0 23.2 0.0 0.6 120 FTG ---- PE 0.0 B 13.0 0.0 23.2 0.0 0.000 TL 10.00 PV Pipe: 16 -126.6 4.260 PL 10.52 PF 0.0 B 13.0 0.0 23.2 0.0 2.8 120 FTG ---- PE 0.0 C 13.0 0.0 23.3 0.0 0.004 TL 10.52 PV Pipe: 17 -205.1 4.260 PL 17.50 PF 0.2 C 13.0 0.0 23.3 0.0 4.6 120 FTG ---- PE 0.0 D 13.0 0.0 23.5 0.0 0.010 TL 17.50 PV Pipe: 18 -283.9 4.260 PL 6.83 PF 0.1 D 13.0 0.0 23.5 0.0 6.4 120 FTG ---- PE 0.0 E 13.0 0.0 23.6 0.0 0.019 TL 6.83 PV Pipe: 18A -369.5 4.260 PL 43.00 PF 1.3 E 13.0 0.0 23.6 0.0 8.3 120 FTG ---- PE 0.0 F 13.0 0.0 24.9 0.0 0.031 TL 43.00 PV Pipe: 18B -369.5 6.357 PL 47.00 PF 0.4 F 13.0 0.0 24.9 0.0 3.7 120 FTG T PE 0.0 G 13.0 0.0 25.3 0.0 0.004 TL 84.72 PV Pipe: 18C -369.5 6.357 PL 102.00 PF 0.6 G 13.0 0.0 25.3 0.0 3.7 120 FTG T PE 0.0 H 13.0 0.0 25.9 0.0 0.004 TL 139.72 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 6/28/2011 C:\DATA\AIRFIELD SPACE D.SDF JOB TITLE: Metal Shorts Space #9134 PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 19 -369.5 8.249 PL 6.00 PF 0.1 H 13.0 0.0 25.9 0.0 2.2 120 FTG T PE 0.0 TOR 13.0 0.0 26.0 0.0 0.001 TL 47.11 PV Pipe: 37 -369.5 8.249 PL 11.08 PF 0.0 TOR 13.0 0.0 26.0 0.0 2.2 120 FTG ---- PE 3.9 AV 4.0 0.0 29.9 0.0 0.001 TL 11.08 PV Pipe: 38 -369.5 8.249 PL 3.50 PF 0.0 AV 4.0 0.0 29.9 0.0 2.2 120 FTG B PE 1.5 UG 0.5 0.0 31.4 0.0 0.001 TL 17.59 PV Pipe: 41 -369.5 8.265 PL 25.00 PF 0.1 UG 0.5 0.0 31.4 0.0 2.2 140 FTG TL PE -0.2 BF1 1.0 0.0 31.3 0.0 0.001 TL 96.70 PV Pipe: 42 FIXED PRESSURE LOSS DEVICE BF2 1.0 0.0 36.3 0.0 5.0 psi, 369.5 gpm BF1 1.0 0.0 31.3 0.0 Pipe: 43 -369.6 8.265 PL 10.00 PF 0.1 BF2 1.0 0.0 36.3 0.0 2.2 140 FTG TG PE 0.4 CITY 0.0 SRCE 36.8 (N/A) 0.001 TL 68.30 PV NOTES (HASS): (1) Calculations were performed by the HASS 7.9 computer program under license no. 38011601 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.072 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14.5 ft/sec at pipe 6. DATE: 6/28/2011 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 C:\DATA\AIRFIELD SPACE D.SDF JOB TITLE: Metal Shorts Space #9134 WATER SUPPLY ANALYSIS a O O O O O 3 0 •r{ a O O O N V m .r{ m a O OO0 .63 ,-I J-) O 0 0 W a) E > D b+ • a a O) to 0 0 W to • O1 Sd >r V m •-1 01 .-1 c moo mH am a) m10 a Q Wc Q) a w z a)cnQ • -,i c7 a v .m o w a m ko a m ,-1 M -H O O >i -4 o O co U] m at ('f D N O) kr) P 0 o 0 rn / 0 / O o o • 0 0 0 0 N V. •--I V. l0 CO r1 r-1 CO 10 N c7 4 t7 w w 1:4 43 cn co 04 w — a m -� O O SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 6/28/2011 C:\DATA\AIRFIELD SPACE D.SDF JOB TITLE: Metal Shorts Space #9134 WATER SUPPLY CURVE 132+ 0 \ 1\ 121+ \ 1 \ 1 \ 1 \ 110+ \ I \ I \ I \ 99+ \ 1 \ I \ I \ P 88+ \ R 1 \ E 1 \ S I \ S 77+ \ U 1 \ R I \ E 1 \ 66+ \ ( 1 \ P I \ S I \ I 55+ \ I \ 1 \ I \ 44+ \ 1 \ 1 \ x \ 33+ \ I \ I \ I \ 22+ LEGEND \ " I * <-20.0 psi @ 10000 gpm 1 X = Required Water Supply "Flow Test Point 1 36.80 psi @ 619.6 gpm " 11+ i. 1 0 = Available Water Supply ,, 1 129.36 psi @ 619.6 gpm " I " 0++-+---+----+ + + + + + + 32004800 6400 8000 9600 11200 12800 14400 16000 FLOW (GPM) ScA Le: APPROVED BY: DRAWN BY M4 REVISED SET STROBE CANDELA OUTPUT AS SHOWN ON PLANS. SET HORN SETTINGS TO LOW TEMPORAL IN SMALL OFFICES (POSITION 3 ON SWITCH). SET ALL OTHER HORNS TO MEDIUM TEMPORAL (POSITION 2 ON SWITCH). Without Cornmen= As Noted in Re;° Per The Attach Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards. Acceptance is subject to errors and omissions which do r -at authorize violations of adopted -',:andards and ordinances. -The responsiblilty for the adequacy of design s totally with the designer. Additions, deletions f 1°v,sions to these drawings after this date will void this =acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: (Oer - 17 By: TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire. Permit No. L?—F -!I ( and exact address for shut- down or restoration approval. 1A, TYP. 120VAC DEDICATED CIRCUIT BRKR. BY OWNER SLC IN SLC OUT SLC PROG a 0 H G Style 4 (Class B) N PROG 120VAC R1 T1 R1 T1 R2 T2 R2 T2 TEL PH TEL PH o ALARM O SUPV. o TROUBLE O SILENCED o POWER • • ACK. SILENCE RESET nn cp SILENT KNIGHT 5808 12V-18AH 12V-18AH TROUBLE RELAY -1 RELAY -2 NAC -1 NAC -2 NAC -3 NAC -4 SBUS NC C NC C 0 W O 0 B A NOM BATTERY �1A SK -5808 CONTROL PANEL WIRINGDETNTSAIL 0 SCALE: SPECIFICATIONS: MOUNTING: 8.1 INCH DIAMETER (15.5 CM) 4 INCH SQUARE BOX WITH OR WITHOUT PLASTER RING MIN. DEPTH 1.5 INCHES 4 INCH OCTAGONAL BOX, MIN. DEPTH 1.5 INCHES 3.5 INCH OCTAGONAL BOX, MIN. DEPTH 1.5 INCHES SINGLE GANG BOX, MIN. DEPTH 1.5 INCHES SIGNAL LINE CKT LOOP 1 (-) SIGNAL LINE CKT LOOP 1 (+) HEAT OR SMOKE DETECTOR BASE B210LP BASE MANUAL ALARM STATION, SPRINKLER DEVICE, OR N.O. DRY CONTACT DEVICE. 47K EOL RESISTOR N W REMOTE ANNUN. 5860 SBUS - SBUS + A B -24VDC +24VDC E.— IF RELAYS ARE NOT WIRED IN A N.E. OR FAIL-SAFE CONFIGURATION, THEY MUST BE LOCATED WITHIN 3 FT. OF THE CONTROLLED DEVICE. YEL(-) (+)V10 RED(+) (-)BLK REMOTE ANNUNCIATOR (PROVIDED WITH ENCLOSURE) R -20E �o - JI 8/35VDC L' N/C 11 .1 N/0„ EQUIPMENT N/Ci SHUTDOWN C IN N/O In., SPRINKLER DEVICE, OR N.O. DRY CONTACT DEV1C DIDIDID1Pal a f©IDI©I©1010 to SK—MINIMON ADDRESSABLE MONITOR MODULE 47K EOL RESISTOR 'J 47K EOL RESISTOR DIDI©I©IGiIfO 4.7K OHM 1/2 WATT EOL 4.7K OHM 1/2 WATT EOL 5 5 r°- SK—RELAY SK—MONITOR-2 ADDRESSABLE RELAY MODULE DUAL MONITOR MODULE TYPICAL INITIATION DEVICE CONNESCALE: NCTIONTSS 0 FIRE ALARM CIRCUIT EMERGENCY ALARM CIRCUIT ->(-)TO NEXT DEVICE - ) (+)TO NEXT DEVICE SK—PULL—DA ADDRESSABLE PULL STATION DETAILS SHOWN ARE TYPICAL AND ALL DETAILS MAY NOT APPLY TO ALL JOBS. REF. LAYOUT DRAWINGS & B.O.M. WIRE SCHEDULE CODE DESCRIPTION / FUNCTION A 2C#16 TW. UNSH. JACKETED PAIR, SLC LOOP B 2C#14, UNSH. HORN/STROBE OR NAC TRIGGER CKT.'S C 2C#16, UNSH. POWER OR AUX. CONNECTION D 2C#16, UNSH. MODULE INITIATION ZONE E 2C#16 UNSH. TW PR., SYSTEM BUS F 2#14, THHN - FOR USE IN U.G. CONDUIT & WET LOCATIONS G 2C#16 SH. W/ AUDIO TWIST - FOR SPEAKER CKT. WIRING TO MEET NEC 760 STANDARDS BILL OF MATERIALS (BOM ITEM SYM QTY MODEL NUMBER DESCRIPTION MANUFACTURER GROUND CIRCUIT FAULT / MOUNTING E SMOKE DETECTOR HEAT DETECTOR 1 1 5808 ADDRESSABLE FIRE CONTROL PANEL SILENT KNIGHT PROVIDED WITH PANEL FCP 2 2 PS 1270 BATTERIES, 12VOLT 7 AH POWER SONIC FOR FIIRE CONTROL PANEL 3 1 5499 SNAC PANEL, NAC CIRCUITS SILENT KNIGHT W/ ENCLOSURE SNAC 4 X 2 PS 1270 BATTERIES, 12VOLT 7 AH POWER SONIC FOR SNAC PANELS 5 10 SK—PULL—DA ADDRESSABLE MANUAL PULL STATION SILENT KNIGHT SINGLE BOX IA 6 ® 22 SK—PHOTO ADDRESSABLE SMOKE DETECTOR WITH BASE SILENT KNIGHT 4" OCTAGON OR SQUARE BOX 7 0 5 SCR FIRE ALARM STROBE, RED, CEILING SYSTEM SENSOR SINGLE OR 4" SQUARE BOX 8 ®© 1 P2R FIRE ALARM HORN/STROBE, RED, WALL SYSTEM SENSOR SINGLE OR 4" SQUARE BOX. 9 I-( 7 SR FIRE ALARM STROBE, RED SYSTEM SENSOR SINGLE OR 4" SQUARE BOX 10 ®CI wP 1 P2RK FIRE ALARM HORN/STROBE, RED, W. PROOF SYSTEM SENSOR SELF CONTAINED ENCLOSURE 11 )i 29 PC2R FIRE ALARM HORN/STROBE, RED, W. CEILING SYSTEM SENSOR SELF CONTAINED ENCLOSURE 12 (din 50 SK—HEAT—ROR ADDRESSABLE HEAT DET, 135 ROR SYSTEM SENSOR SINGLE OR 4 INCH OCTAGONAL 13 1 5860/R LCD REMOTE ANNUNICATOR SILENT KNIGHT PROVIDED WITH PANEL ANN 14 15 7788F FIRE SUBSCRIBER WITH INTELLI TAP SILENT KNIGHT PROVIDED WITH PANEL AES 16 1 PS 1280 BATTERIES, 12VOLT 8 AH POWER SONIC FOR AES RADIO 17 i' 18 19 20 21 22 23 24 25 26 27 28 29 30 SET LABEL STROBE EOL CANDELA DEVICES OUTPUT AS SHOWN ON PLANS. > FOR ADDITIONAL MOUNTING OPTIONS SEE DATA SHEETS, PROVIDED. ELECTRICAL NOTES: 1) INSTALLATION SHALL COMPLY WITH NFPA 70, PARTICULARLY ARTICLE 760, AND SHALL ALSO COMPLY WITH NFPA 72, AND ALL LOCAL ELECTRICAL CODES AND LOCAL JURISDICTION REQUIREMENTS. 2) CONDUIT INDICATED ON PRINTS IS DIAGRAMMATIC AND MAY BE REROUTED PER FIELD REQUIREMENTS. 3) AC POWER SHALL NOT OCCUPY THE SAME CONDUIT AS FIRE PROTECTION CIRCUITS (MOST FIRE DETECTION CKT'S ARE NEC CLASS 3) 4) ALL SLC LOOP WIRING SHALL BE 2 CONDUCTOR #16, UNSHIELDED, FIRE ALARM CABLE OF THE PROPER RISER AND / OR PLENUM TYPE.., 5) CONVENTIONAL FIRE DETECTION INITIATING DEVICE CIRCUITS OR' NOTIFICATION APPLIANCE CIRCUITS SHALL NOT BE PARALLEL BRANCHED (TEE TAPPED) TO ENSURE SUPERVISION OF WIRING. ADDRESSABLE CLASS "B" FIRE DETECTION SIGNALING LINE CIRCUITS (SLC) MAY BE PARALLEL BRANCHED (TEE TAPPED) IF SO INDICATED ON THE SYSTEM PLANS. 6) OBSERVE POLARITY OF ALL FIRE DETECTION WIRING. POLARITY SHALL BE MAINTAINED THROUGHOUT ENTIRE SYSTEM; WIRE SHALL BE MARKED AND IDENTIFIED WHERE SPLICED, AND AT ANY JUNCTION BOXES. 7) THE FIRE ALARM PANEL GROUND SHALL BE A SEPARATE CONTINUOUS GROUND WIRE BACK TO THE SOURCE GROUND; CONDUIT GROUND IS NOT ACCEPTABLE PER MANUFACTURER'S SPECIFICATIONS. 8) FIRE ALARM PANEL, AND ANY OTHER FIRE DETECTION EQUIPMENT REQUIRING 120VAC, SHALL BE SUPPLIED BY A DEDICATED CIRCUIT BREAKER OTHER (NON -FIRE DETECTION) EQUIPMENT SHALL NOT SHARE THE FIRE ALARM CIRCUIT(S). THIS BREAKER SHALL BE LOCKED AND CLEARLY MARKED "FIRE ALARM CIRCUIT CONTROL". 120VAC POWER BY OTHERS. 9) POWER SHALL NOT BE APPLIED TO THE FIRE ALARM PANEL UNLESS A REPRESENTATIVE FROM CASCADE. IS PRESENT. DESIGN NOTES: 1) DEVICE LAYOUT PER OWNERS SPECIFICATION. 2) BUILDING TO BE FULL SPRINKLER COVERAGE 3) PROVIDE ONE PULL STATION AND ONE HORN IN VACANT AREA TO MATCH EXISTING CONDITION IN BUILDING BEFORE BUILD OUT. 4) NO HVAC UNITS OVER 2000 CFM SHOWN ON MECHANICAL SCHEDULE. NO DUCT SMOKE DETECTORS PROVIDED. GENERAL NOTES: 1) NOTIFY CASCADE. OF ANY DESIGN QUESTIONS OR CHANGES PRIOR TO INSTALLATION OR FABRICATION. COMPARE DRAWINGS WITH CURRENT CONTRACT DRAWINGS PRIOR TO INSTALLATION. 2) ANY ALTERATIONS OR VARIATIONS FROM DRAWINGS SHOULD BE APPROVED PRIOR TO WORK PROCEEDING AND DOCUMENTED ON THE AS BUILT DRAWINGS. VERIFY DEVICE LOCATIONS PRIOR TO INSTALLATION. 3) REFERENCE FACTORY INSTRUCTION MANUALS DURING INSTALLATION OF FIRE CONTROL EQUIPMENT. 4) DETECTORS SHALL NOT BE MOUNTED IN A DIRECT AIR STREAM. DO NOT INSTALL DETECTORS WITHIN 3'-O" OF AIR SUPPLY DIFFUSERS. 5) USE ONLY U.L. LISTED DEVICES. 6) DO NOT INSTALL DETECTOR HEADS UNTIL FINAL CLEANING HAS BEEN PERFORMED. 7) FIELD DETERMINE INTERFACE REQUIREMENTS AND LOCATIONS OF EQUIPMENT SUPPLIED BY OTHER TRADES. ( he.. SPRINKLER DEVICES, HVAC UNITS, FIRE DAMPERS, ELEVATOR CONTROLS, & FAN CONTROLS.) FIRE ALARM SYSTEMS SEQUENCE OF OPERATIONS SYSTEM OUTPUT SYSTEM INPUT CIRCUIT FAULT LOW BATTERY AC POWER FAILURE GROUND CIRCUIT FAULT PHONE UNE FAULT E SMOKE DETECTOR HEAT DETECTOR ALARM C FACP X X TROUBLE C FACP X X X X X SUPV. 0 FACP TRANSMIT ALARM TO MONITORING X X X TRANSMIT TROUBLE TO MONITORING X X X X X TRANSMIT SUPV. TO MONITORING ACTIVATE NOTIFICATION DEVICES X X X CONTRACT NI IRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY SOUTH SEATTLE, WA 98108 1 0 06-12-17 RM SUBMIT FOR APPROVAL NO. DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN REVISIONS ;.: Cascade �= ' Fire & Security "First When Seconds Count" 20452 84TH AVE S, KENT, WA 98032 P.O. BOX 7459, KENT, WA 98042 PH: (206) 767-5800 FAX: (253) 630-5851 www.CascadeFire.Rocks CONTRACT WITH: SCALE: NTS DRAWN BY: ANTON REMINGTON CHECKED BY: RON MAYNARD DESCRIPTION: BOM, MATRIX, WIRING DETAILS SYSTEM DESIGN DATA HAZARD CLASSIFICATION: SYSTEM AREA: HYDRAULIC DESIGN DATA - DENSITY: GPM • SQ. FT./PER HD: AREA OF APPLICATION: HOSE ALLOWANCE: GPM TOTAL SYSTEM REQUIREMENTS: WATER SUPPLY INFORMATION: STATIC PRESSURE: PSI DATE 06-12-17 RESIDUAL PRESSURE: PSI FLOWING: GPM TEST TAKEN AT: DATE: DRAWING NO: FA -01 OF 4 PAID JUN 14 2011 TUKWILA FIRE a p3z X5 -34e 18 1 TO WP OFFICE I OFFICE 18 16 L WAREHOUSE 1B TORAGE 18 E.O.L. NAC2 11B 1 ATHIMOM 1 1B TO HIGH CEILING 30.)&1B 15 1B 18 BREAKROOM 1B 1B J TO UPPER AREA NOTIFICATION UPPER DEVICES 0 SCALE: 1/8 BUILDING BEAM 18-36 IN, ROOF PEAK APROX. 24 IN RISE WIRE CAGE WAREHOUSE 18 OFFICE 47(. L ATHROOM LUNCH ROOM TO MEZZANI 118 1D DEAD SPACE ITO MEZZANINE 1B 30 - BATHROOM' 1B L NOTIFICATION LOWER DEVICES 0 SCALE: 1/8 WAREHOUSE Mia 1E MAILROOM B !ATM! TO WAREHOUSE TO SNAC E.O.L. yVr NAC4 30 1BL WORK AREA WAREHOUSE lit_ TO WAREHOUSE/MEZZANINE CONTRACT NI IRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY SOUTH SEATTLE, WA 98108 1 0 06-12-17 RM SUBMIT FOR APPROVAL NO. DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN REVISIONS Cascade Fire & Security "First When Seconds Count" 20452 84TH AVE S, KENT, WA 98032 P.O. BOX 7459, KENT, WA 98042 PH: (206) 767-5800 FAX: (253) 630-5851 www.CascadeFire.Rocks CONTRACT WITH: SCALE: 1/8" =11-0" DRAWN BY: ANTON REMINGTON CHECKED BY: RON MAYNARD DESCRIPTION: FLOOR PLAN NOTIFICATION DEVICES SYSTEM DESIGN DATA HAZARD CLASSIFICATION: SYSTEM AREA: HYDRAULIC DESIGN DATA - DENSITY: GPM SQ. FT./PER HD: AREA OF APPLICATION: HOSE ALLOWANCE: GPM TOTAL SYSTEM REQUIREMENTS: WATER SUPPLY INFORMATION: STATIC PRESSURE: PSI DATE: 06-12-17 RESIDUAL PRESSURE: PSI FLOWING: GPM TEST TAKEN AT: DATE: DRAWING NO: FA -02 OF 4 DEAD SPACE 1B 1B TO OFFICE I 1 k- 1B — WAREHOUSE 16 TO SNAG 1B '475 75 18 1 TO BATHROOM 16 1 fk 16 TO 75 18 SNAC WAREHOUSE 1B �if—� I I TO BATHROOM 1B ---)!E T8 1 � WAREHOUSE 1B WAREHOUSE I Ot TO SNAC / 30 30 30 716 { E.O.L. _ 16 NAC1 1B „30- TO BATHROOM 1 S 7SB 1 TO BATHROOM i TO OFFICE MEZZANINE MEZZANINE 18 1 TO WP OFFICE I OFFICE 18 16 L WAREHOUSE 1B TORAGE 18 E.O.L. NAC2 11B 1 ATHIMOM 1 1B TO HIGH CEILING 30.)&1B 15 1B 18 BREAKROOM 1B 1B J TO UPPER AREA NOTIFICATION UPPER DEVICES 0 SCALE: 1/8 BUILDING BEAM 18-36 IN, ROOF PEAK APROX. 24 IN RISE WIRE CAGE WAREHOUSE 18 OFFICE 47(. L ATHROOM LUNCH ROOM TO MEZZANI 118 1D DEAD SPACE ITO MEZZANINE 1B 30 - BATHROOM' 1B L NOTIFICATION LOWER DEVICES 0 SCALE: 1/8 WAREHOUSE Mia 1E MAILROOM B !ATM! TO WAREHOUSE TO SNAC E.O.L. yVr NAC4 30 1BL WORK AREA WAREHOUSE lit_ TO WAREHOUSE/MEZZANINE CONTRACT NI IRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY SOUTH SEATTLE, WA 98108 1 0 06-12-17 RM SUBMIT FOR APPROVAL NO. DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN REVISIONS Cascade Fire & Security "First When Seconds Count" 20452 84TH AVE S, KENT, WA 98032 P.O. BOX 7459, KENT, WA 98042 PH: (206) 767-5800 FAX: (253) 630-5851 www.CascadeFire.Rocks CONTRACT WITH: SCALE: 1/8" =11-0" DRAWN BY: ANTON REMINGTON CHECKED BY: RON MAYNARD DESCRIPTION: FLOOR PLAN NOTIFICATION DEVICES SYSTEM DESIGN DATA HAZARD CLASSIFICATION: SYSTEM AREA: HYDRAULIC DESIGN DATA - DENSITY: GPM SQ. FT./PER HD: AREA OF APPLICATION: HOSE ALLOWANCE: GPM TOTAL SYSTEM REQUIREMENTS: WATER SUPPLY INFORMATION: STATIC PRESSURE: PSI DATE: 06-12-17 RESIDUAL PRESSURE: PSI FLOWING: GPM TEST TAKEN AT: DATE: DRAWING NO: FA -02 OF 4 1A 1A OFFICE 1A OFFICE '1A RETAIL 1A WAREHOUSE 1A 12 IAESI-_-{FCPI- 18-1SNACI 1A 1A 1A UP TO HEAT BREAKROOM OFFICE WAREHOUSE UPPER ADDRESSABLE DEVICES SCALE: 1/8 BUILDING BEAM 18-36 IN, ROOF PEAK APROX. 24 IN RISE WIRE CAGE LUNCH ROOM 1A 1A Sio4c ei 4 co%_racy -' ' it/FeA- 7)_, 5ec... /7,5%5.1. Ii DEAD SPACE WAREHOUSE 133 u' 1A ORK AREA 1A 1 1A UP TO HEAT WAREHOUSE bATHROONi CO, 1A OFFICE 1A' ®p LOWER ADDRESSABLE DEVICES SCALE: 1/8 MAILROOM 1A 1A ®1A P "n" -=a --0°H 135 CONTRACT NA IRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY SOUTH SEATTLE, WA 98108 SCALE: 1/8"=1"-0 1 0 06-12-17 RM SUBMIT FOR APPROVAL NO. DATE BY REVISIONS — SEE FLAGGED AREA ON PLAN REVISIONS rY�_- Cascade Fire ei Security "First When Seconds Count" 20452 84TH AVE S, KENT, WA 98032 P.O. BOX 7459, KENT, WA 98042 PH: (206) 767-5800 FAX: (253) 630-5851 www. CascadeFi re. Racks CONTRACT WITH: DRAWN BY: ANTON REMINGTON CHECKED BY: RON MAYNARD DESCRIPTION: FLOOR PLAN INITIATIING DEVICES SYSTEM DESIGN DATA HAZARD CLASSIFICATION: SYSTEM AREA: HYDRAULIC DESIGN DATA - DENSITY: GPM SQ. FT./PER HD: AREA OF APPUCATION: HOSE ALLOWANCE: GPM TOTAL SYSTEM REQUIREMENTS: WATER SUPPLY INFORMATION: STATIC PRESSURE: PSI DATE: 06-12-17 RESIDUAL PRESSURE: PSI FLOWING: GPM TEST TAKEN AT: DATE: DRAWING NO: FA -03 OF 4 DOWN TO FAP 1A 1A DEAD SPACE 1A 135 "135 "135 4 (� ®138 0 0 1A 1A 1A 136 ( 1A WAREHOUSE 1A 135 1A 138 135 WAREHOUSE 1A 1AI DOWN TO 0 133 1A 0 138 1A 0135 PULL WAREHOUSE WAREHOUSE —DOWN TO BATHROOM — 1A 1A "135 0 (i)135 4136 Q1 Q 9135 1A 133 1A 1A 1A 1A 136 1A 136 1A 136 1A 135 1A 138 1A 135 1A 4 4 136 "138 ®136 0136 0136 ©136 1A 1A 1A 133 1A 1A ' 136 1A 135 1A 1A 1A DOWN TO BATHROOM 1A 136 t ` 1A 138 1A 1A 1A` 136 0135 MEZZANINE MEZZANINE 1A 1A OFFICE 1A OFFICE '1A RETAIL 1A WAREHOUSE 1A 12 IAESI-_-{FCPI- 18-1SNACI 1A 1A 1A UP TO HEAT BREAKROOM OFFICE WAREHOUSE UPPER ADDRESSABLE DEVICES SCALE: 1/8 BUILDING BEAM 18-36 IN, ROOF PEAK APROX. 24 IN RISE WIRE CAGE LUNCH ROOM 1A 1A Sio4c ei 4 co%_racy -' ' it/FeA- 7)_, 5ec... /7,5%5.1. Ii DEAD SPACE WAREHOUSE 133 u' 1A ORK AREA 1A 1 1A UP TO HEAT WAREHOUSE bATHROONi CO, 1A OFFICE 1A' ®p LOWER ADDRESSABLE DEVICES SCALE: 1/8 MAILROOM 1A 1A ®1A P "n" -=a --0°H 135 CONTRACT NA IRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY SOUTH SEATTLE, WA 98108 SCALE: 1/8"=1"-0 1 0 06-12-17 RM SUBMIT FOR APPROVAL NO. DATE BY REVISIONS — SEE FLAGGED AREA ON PLAN REVISIONS rY�_- Cascade Fire ei Security "First When Seconds Count" 20452 84TH AVE S, KENT, WA 98032 P.O. BOX 7459, KENT, WA 98042 PH: (206) 767-5800 FAX: (253) 630-5851 www. CascadeFi re. Racks CONTRACT WITH: DRAWN BY: ANTON REMINGTON CHECKED BY: RON MAYNARD DESCRIPTION: FLOOR PLAN INITIATIING DEVICES SYSTEM DESIGN DATA HAZARD CLASSIFICATION: SYSTEM AREA: HYDRAULIC DESIGN DATA - DENSITY: GPM SQ. FT./PER HD: AREA OF APPUCATION: HOSE ALLOWANCE: GPM TOTAL SYSTEM REQUIREMENTS: WATER SUPPLY INFORMATION: STATIC PRESSURE: PSI DATE: 06-12-17 RESIDUAL PRESSURE: PSI FLOWING: GPM TEST TAKEN AT: DATE: DRAWING NO: FA -03 OF 4 (—)BLK RED(+) o > (—)TO SLC r > (+)TO SLC YEL(—) 47K EOL RESISTOR COM NC NO AES 7788E MAIN CONTROL BOARD 1 Intelli—Tap Module INPUT ZONE TRIGGERS 2 3 g 4 5 g 8 7 EMI ■�I u g 8 12 u ■ 1 /4114,1 l\'JJ r lV u UTIO ■a 11.0.11 n 1 u L—I TO FAP DIALER TO FAP TO FAP TO FAP RELAY 1 14_0/COM RELAY 2 NO/COMM UBLE NSUPV M J (-) 8.0 A/H BATTERY ©136 ©138 ©136 ©136 " 135 1A A 135 " 138 1A135 " 136 " 138 " 138 " 135 " 135 1A IA en ®138 ©135 lA ©136 w138 '136 ®138 EBBSEHHE * ourl oUT2 * ours «UT4 * .41FLT * 8UT *Pc L 1 L—J L—..I 1_1 NAC1-4 NAC1-3 NAC1-2 NAC1-1 3.4 A/H BATTERY 3.4 A/H BATTERY A 135 "136 "133`11 5499 SNAC PANEL WIRING DETAIL SCALE: NTS 135 " 136 135 136 136 " 136 1A 135 138 1A 135 " 138 135 135 e) 138 t" 135 1A 135 135 `' 135 " 135 " 135 " 138 " 136 136 " 136 1A 13 t4 ` 0 - f ` fi FLOOR 1 1A 135 ANN IA,1C 1A FCP 1B IB INSTALL NO CONDUITS IN BOTTOM OF CABINET, TYP. OUT -1 OUT -2 { 4.7K OHM 1/2 WATT 4.7K OHM 1/2 WATT TYPICAL NAC WIRINGDETANTSIL 0 SCALE: 18 18)!( E,O,L. 16' 30 m NAC4 120VAC E.O.L. NAC3 E.O.L. NAC1 4.7K OHM 1/2 WATT 4.7K OHM 1/2 WATT CONTRACT NAF: IRFIELD BUSINESS CENTER 9100 EAST MARGINAL WAY SOUTH SEATTLE, WA 98108 SCALE: 1/8" =1'-0" 1 0 06-12-17 RM SUBMIT FOR APPROVAL NO. DATE BY REVISIONS — SEE FLAGGED AREA ON PLAN REVISIONS rY=Cascade Fire & Security "First When Seconds Count" 20452 84TH AVE S, KENT, WA 98032 P.O. BOX 7459, KENT, WA 98042 PH: (206) 767-5800 FAX: (253) 630-5851 www.CascadeFire. Rocks CONTRACT WITH: DRAWN BY: ANTON REMINGTON CHECKED BY: RON MAYNARD DESCRIPTION: RISER & SNAC WIRING DETAIL SYSTEM DESIGN DATA HAZARD CLASSIFICATION: SYSTEM AREA: HYDRAULIC DESIGN DATA — DENSITY: GPM SO. FT./PER HD: AREA OF APPLICATION: HOSE ALLOWANCE: GPM TOTAL SYSTEM REQUIREMENTS: WATER SUPPLY INFORMATION: STATIC PRESSURE: PSI DATE: 06-12-17 RESIDUAL PRESSURE: PSI FLOWING: GPM TEST TAKEN AT: DATE: DRAWING N0: FA -04 OF 4 RECEPTION .........................0 L •/ 1 .L-_=) 15CD Existing Pull Station Relocated After IDerno r/r�. LP r'r rr� r' CEFI ED„ Existing Smoke Detectors and ,Horn Strobes Relocated After Demo RR Ak ROOM \\ IMew kfc-,) �\ 15CD ,S rro 15cci. o .._.-.• OFFICE -%ew .iz.;....._...�.-__.�T.w.1.1,.--- _tom' 1�---- -- _ NC) CHANGES. NO CHANGES NO CHANGES NO CHANGES r Is IR IE AI..al' ►lR.IVi .L.AA1'y (DILJ'1' ' 'WAREHOUSE NO CHANGES NO CHANGES Dar 2' 4' 8' EIOt1NDARY OF 1JVCRK; NC) CHANGES •BIJILPING SO1PrH OF THIS LINE; 3••-,. • ••• . . .• - • :••• . • 4g, • • ••••••:• • • ..., • c••• . . • • 1.• . • • • • • . „ • •••••14:.: • • • ' •• • ,,,•• •• • , • • . '; ••••• • s.'„••• '** • •• „ . • . , ‘• 4 • ••• .• ••• • . • ." • - ' •• • ' • •• : • '• • • • • • • • . • .• • • . 1 • • • • • . • . • • • • • • .*. 1•1011 6N14044,0 4 4 , 1••""••' • „ HEAT VeiEcratt s tvk ok.N-TEO 7 Ft.,044\ co AcogosA-e .411,64 MoorJr0 u149R, Leptle ;C. 4•04440.18ilta. • ADO' if,•"4.11.1.11,811.4 lot • • •••:. Af•481 • 40.# 41,30t911t. 22* --3 1/2M • --/ 1-kE A1Del-t-c..-t-ae.,- 6P AGAN (-) t-k.a.tc-111-1-S 11,1 pg.. LE 4,) cy?-7mc1 0 a_e- Avra- ID = 9444 61,40aP4 L'o,tc-s CJ azn 014 ft-- 'mlkit NT E Ai \-lazo Novt-nw • • • • • • 4,••48 • ; ONI Po4-51- Dk) -to 641 111\t‘l VA,Act(S \10\101, INA0UffiliNt, ? • • • • • . . • . • • • . ''• •-;• • • ' . • -8 • ", " • ••••:. • •;•:'• • ?:•.::•••• •i• '..."e•••••":. • .:•/:.'"•.1.1..re".? •••. • • Withouf Cornmehts • ' • ..../5akfofeei • Per Tha Attached Letter81• . • • • These plan*S- havo ben ev?wd by Th 'tikw P-reventiort stndards. Acceptance is subject 'teerirots: and,.' Orrilisonsvvhch do nptairihOriie QIctIonof adopted standaeds and Ordlra6,eS The. re1pon3billy,forJhe,7;,:,. adequacyof desnr6sti'latorq wi th doqror Additions, deletions or reVisiOns•t•thet'e ekwThgsaftef • hs date will void thisacceptsnce and will rqquiro 6'. • resubmittal of roViSsed 6raVvIns approyet., , . Final acce.ptande is sift)je.c to,fieldleStand..inspetlofjfi.9 1lie Tukwila rife Preventiom.011reau.• - - 1 ..:...• -, -;:..,,,•y,..,.... Date: .2 - / Liv -.u. ..• . Igv.,• 1,1 1 .,, -,•••\ . .. . . , . ... • . • .. • • TUKWILA. PI RE DPARTNIEpik . . Please cll: • 57.440Z • .'• • .and give this 'job • • • • . • . • . . . . ;:tit4wn .4.0-...40iio?irotiltein *viola • 's I . . • • . ••• • . . • .• 4.. . • • . . • • . . •• . • •• . . . • . . • • • : ; • 1 F C ALARM VA W (E) 8" (E) 8" 00 0 W ❑ Without Comments ❑ As Noted in Red g Per The Attached Letter -se e plans have been rev''.evwed by The Tukwila Fire rtion Bureau for conformance with current City r . - :ards. Acceptance i, ,c.i eject to errors and ,. sions which do not authorize \;ioiationS of adopted ridards arid ordinances. The responsibility for the 4uacy of design reds totally V,iit`-h the designer. drevisions i:hese drawings after deletions or i". \/i ii is *:is date will Fuld trri:: ccr ptance and will require a resubrnittal of revibe" d.,.,:vin ,i= for subsequent approval. Final acceptance is su Ject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: —( By: TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. and exact address for shut- down or u esc oration approval. 0 CON. TO EXISTING 1/ 6" X—MAIN x SPACE C (E) TENANT NO WORK 1,3 w 6 (E) CON. TO EXISTING 6 6" X—MAIN (E) 3-7 O U'- J 6X I 1 41 `:60I A-2 4x2 OGG u) m Ce 1'4x! 4-6GG co c9e7-65 N LLI cnZo ci® Q d N 0 C)2 8-01/2 J QX - /at 40. I J a1 2 c9 C9 m0 0 J X N 5-7 O W r-�► --`nn� 11.x81 `� 5-8/ f" 6-0 P 0 8-0 11.5 TOLCO FIG. 980 UNIVERSAL SWAY BRACE FITTING TDLCO FIG. 4A PIPE CLAMP FOR SWAY BRACING LONGITUDINAL BRACE TDLCO FIG. 980 UNIVERSAL SWAY BRACE FITTING TYP. TOLSTRUT CHANNEL OR 1' PIPE TOLCO FIG. 4A PIPE CLAMP 0 1001 FAST CLAMP SCALE N.T.S 12 N ��I 0 0 c0 co ® 7 tell ALL DRODS -0 1x6 -0 w/48" F EX DROP \ I 1/2x2 I -OGG 11-81/2 $NN co L X \\ ALL: LINES CL=12" BOJ HANG W/#2 SAMMY SCREW, ROD & RING 4 4 co C9 0 0 J X O N N 3-7 B-1 4x21-OGG 4 11-8Y 0 J x N I 0h 0 a. .a5 -101/x, �5-101/ 11— 1 r 0 I 03 0 /O J c9 U' 0 N 0 co 03 0 /O 0 0 C9 O , N XA 0 8-0 0 3- N L4 -E I%xII-3GG N e0 c0 n ACE D 116 EXISTING GLH D x3I!' LAG 801.1 LATERAL BRACE N ao t9 C9 on J X 0 m ' Jcv X ,REMOTE °° AREA # I °° o0 o® N I N N r —101/ 10 Lr) -J B-2 4x2 I -OGG 4 OO 0 O N X 03 C cccc 8 cr w 0 1 5-3 -I- 4x20-OGG 17 i 03 PIPING PLAN CUT PIPE PLAN OHD X 4 16-6 1-0 U' 0 cc) cv co x ce CC 0 U¢ 5-4 GO 5-5 Wxl 1-11G /O N.T.S O U' 1 ¢O fi iX s 10-1 4x10-1 GG 4 10-41 hs -6 9-7 *IL '- G0I ce o % +ti/° 1 LJ GENERAL NOTES I . DESIGN AND INSTALLATION SHALL CONFORM TO NEPA PAMPHLET 13 AND CITY OF TUKWILA REQUIREMENTS. 2. ALL MATERIALS SHALL BE NEW AND U.L. APPROVED. 3. PIPE: ALL PIPE 11/2" AND SMALLER TO BE SCHEDULE 40 BLACK STEEL. ALL PIPE 2" AND LARGER TO BE SCHEDULE 10 BLACK STEEL. 4. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE DUCTILE IRON. 5. PAINTING OF PIPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT IS BY OTHERS. G. ALL ELECTRICAL WIRING AND CONDiUT TO BE PROVIDED AND INSTALLED BY OTHERS. 7. NOT USED 8. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE A5 IT IS SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 9. CASCADE ALARM ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY CASCADE ALARM. 10. NOT USED I 1. ALL DIMENSIONS ARE TO CENTERLINE OF PIPE. 12. DOTTED LINES DENOTE EXISTING PIPE. 13. SYMBOLS/ABREVIATIONS: [X' -X']- DENOTES CENTER LINE OF SPRINKLER PIPE AFF. X' -X' I- DENOTES CEILING HEIGHT. AFF - CENTERLINE OF PIPE ABOVE FINISHED FLOOR. BDK - CENTERLINE OF PIPE BELOW BOTTOM OF DECK. of - FLEXIBLE GROOVED COUPLING. MT - MECHANICAL TEE FD - FLEXABLE DROP NIPPLE. SEE PLAN FOR LEGNTH. 3-- THREAD END PLUG (A1)- HYDRAULIC REFERENCE NODE. HANGER DETAIL #2 UP TO 4" PIPE WOOD ROOF .DIST SAMMY SUPER SCREW NOBEL HSGST 20 ( 2' LGTH ) 3/8' ALL THREAD ROD ADJUSTABLE RING HANGER SAMMY SCREW SIDEWINDER STEEL ALL THREAD ROD ADJUSTABLE RING HANGER HANGER DETAIL #1 K 1 KEY PLAN NTS ORMAN DINT N/AINS 06-29-11 CONTRACT NAME: Metal Shorts Space #9134 SCALE: 1/8"..r -o" IMPORTANT In Iocolities subject to freezing conditions, it is the owner's responsibility to provide heat throughout wet pipe sprinkler systems areas and in enclosures for dry pipe deluge and other types of valves controlling water supplies to sprinkler systems. This drawing and the information and design application herein contained is the property of Cascade Alarm, and is loaned upon express conditions that the some be returned to Cascade Alarm upon request; all information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be made without written consent of Cascade Alarm. CONTRACT RESPONSIBILITIES SPRINKLERS ITEM CASCADE OTHERS TYPE ORIFICE TEMP. FINISH CANOPY SYMBOL QTY. TY—FRB 1/2" 155 WH 401 WH 2 TY—FRB 1/2" 155 BRASS 79 SYSTEM TYPE WET ® ❑ 0 ❑ Cascade Alarm Airfield Business Center 9100 East Marginal Way S. Tukwila, WA. 98108 DRAWN BY: Reid DESCRIPTION: PIPING PLAN (SPACE D) CHECKED BY: TY- FRB 1/2" 155 WH SEMI RECESSED WH 0 9 NO. OU DATE` BY REVISIONS — SEE FLAGGED AREA ON PLAN ELTA TOTAL THIS SHEET 90 APPROVALS OUT OUT OUT OUT IN IN IN IN FIRE PROTECTION DIVISION Post Office Box 7459, Kent, WA. 206-767-5800, Ext 2 SYSTEM DESIGN DATA DATE: 6/28/11 HAD AStlFFInAllAN. OHG II SYSTEM AREA: HYDRAUUC DENSITY: .20 OEgGN BATA GPM/SQ. FT.: 1500 SQ. FT./HD. AREA OF APPUCA11ON: SQ. FT. 411 OSE ANC S. s.nn GPM TOTAL SYSTEM REQUIRFMFNTC. 610 6 GPM. AT : 36.8 PSI. AT: CITY WATER SUPPLY INFORMATION: STATIC PRESSURE 130 PSI. DRAWING NO. FP 1—CUT PIPE PLAN RESIDUAL PRESSURE : 20 PSI. WITH : 10,000 GPM FLOWING AKEN AT BY : CITY DATE (E) FDC ALARM VA DD (E) 8" W ®(E) 8" 0 N CON.. TO EXISTING 1y� 6' X -MAIN; (E)064 ,, 0 73-7 i m �- -- . - 07.x.. < • I -ccs- 0 I x c0 W J (O W SPACE C (E) TENANT NO WORK CON. TO EXISTING 6 6" X -MAIN I I N <O .O 0 ,� O .;.� ,N..4'/<ti 0 5-8Yi.' C�6-0 : 0 28-0 �..- o M I A-2 Q tit, m ` 4x 14 GGG of v w ' �:0= oN.°8-0/:® O i� Os < V' N - ALL DROSS F -111,2 ::. 00 1x4'-0 0 cs 401 Iv (D; 1 N) ' ®%2-0 - o ® 2/ ,.'\, 9 W/48"::'FLEX DROP:.. .. ........ i -;1 N /�.- \b 0 O • NN o +'\ N I { / ....-415.N N\ to '''/ ...._. ..... _.. .. ........... \ J\ 8-0 V 3-3 1 \,\ - 0 L4 -E \ I — \:\. N \Cti; - t co of' d' C9 l� i r _( N 5-7 N I 4 c N 00 U 0 0 S E .} N \\'`! ALL LINES.CL=12" BOJ HANG W/#1 SAMMY SCREW "ROD 8& RING 0 0 In NI J X (4 0 O m ' Lf) N J X (4 N oo N 11-81/2 5-101/2 5-101/2 11 to N! J X: POJ 3-7 N CO 0 csi Csi W a .. ft,/ U < N J X I co B-1 4x2 1-OGG 4 11-8V2 N -ccv. 0 m0_ Q— N z W (0 N I c0 0Z J 00 CO I O O :- 5-81/2 6-0Y2 ISP 81h B'=2 U 00 0 < ' N I J x a7 00 0-CO1/2/-6 i ACE D 115 0 O N N N 12 M O C N N 11 8-5V2 ....•.1 _C'� Lt ,REMOTE a0 Al EA •._#...I .. r. 0 N N cV 5-101/2 5-101/2 11-:81/2 N I 4 usi N I 4x2 I -OGG 0000 o -° O /O PIPING PLAN N oo N 0p -101 gO) (0. - 61 TOLCO FIG. 980 UNIVERSAL SWAY BRACE FITTING TOLCO FIG. 4A PIPE CLAMP FOR SWAY BRACING LONGITUDINAL BRACE TOLCO FIG. 980 UNIVERSAL SWAY BRACE FITTING TYP. TOLSTRUT CHANNEL OR 1' PIPE TOLCO FIG. 4A PIPE CLAMP 0 1001 FAST CLAMP SCALE: N.T.S O ' N N J X N N M I In • B 3 .._..0..11/2 4x20-OGG a -7/ OHO 4 Qu) J.� 16-6 1-0 N co N II N 10-411 N N 1p B-5 ; :, a 4x 10- I GG i w 0 i 1 0 / ' ' Z y7..................' _- 4 -6 9-7 N CO 1 EXISTING GLB LATERAL BRACE N.T.S GENERAL NOTES I . DESIGN AND INSTALLATION SHALL CONFORM TO NFPA PAMPHLET 13 AND CITY OF TUKWILA REQUIREMENTS. 2. ALL MATERIALS SHALL BE NEW AND U.L. APPROVED. 3. PIPE: ALL PIPE 1 1/4" AND SMALLER TO BE SCHEDULE 40 BLACK STEEL. ALL PIPE I 1/2" AND LARGER TO BE SCHEDULE 10 BLACK STEEL. 4. FITTINGS: ALL FITTINGS (SCREWED AND GROOVED) AND GROOVED COUPLINGS TO BE DUCTILE IRON. 5. PAINTING OF PIPE AND PROTECTION OF SPRINKLER HEADS FROM PAINT 15 BY OTHERS. G. ALL ELECTRICAL WIRING AND CONDIUT TO BE PROVIDED AND INSTALLED BY OTHERS. 7. NOT USED 8. OWNER IS RESPONSIBLE TO ASSURE THAT STRUCTURE A5 IT 5 SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORT ALL FIRE SPRINKLER PIPING LOADS. NO AUXILLIARY DEVICES OR ATTACHMENTS SHALL BE PROVIDED BY COSCO TO SUPPLIMENT THE STRUCTURE TO ACCOMODATE FIRE SPRINKLER PIPING LOADS. 9. CASCADE ALARM ASSUMES NO RESPONSIBILITY, EITHER EXPRESSED OR IMPLIED, FOR THE CONDITION, PERFORMANCE OR CURRENT CODE COMPLIANCE OF THE EXISTING SYSTEM TO BE MODIFIED OR ANY OTHER EXISTING FIRE PROTECTION SYSTEM ON SITE EXCEPT FOR WORK PERFORMED DIRECTLY BY CASCADE ALARM. 10. NOT USED I I. ALL DIMENSIONS ARE TO CENTERLINE OF PIPE. 12. DOTTED LINES DENOTE EXISTING PIPE. 13. SYMBOLS/ABREVIATIONS: [X' -X']- DENOTES CENTER LINE OF SPRINKLER PIPE AFF. 1 X' -X' 1- DENOTES CEILING HEIGHT. AFF - CENTERLINE OF PIPE ABOVE FINISHED FLOOR. BDK - CENTERLINE OF PIPE BELOW BOTTOM OF DECK. of - FLEXIBLE GROOVED COUPLING. MT - MECHANICAL TEE FD - FLEXABLE DROP NIPPLE. SEE PLAN FOR LEGNTH. }- THREAD END PLUG CA -'1)- HYDRAULIC REFERENCE NODE. VSD RODE JOIST SAMMY SUPER SCREW MODEL HSGST 20 ( 2' LGTH ) 3/8' ALL THREAD ROD ADJUSTABLE RING HANGER HANGER DETAIL #2 UP TO 4" PIPE SAMMY SCREW SIDEWINDER WOOD ALL THREAD ROD ADJUSTABLE RING HANGER HANGER DETAIL #1 <EY PLAN NTS FILE COPY CONTRACT NAME: IMPORTANT In localities subject to freezing conditions, it is the owner's responsibility to provide heat throughout wet pipe sprinkler systems areas and in enclosures for dry pipe deluge and other types of valves controlling woter supplies to sprinkler systems. This drawing and the information and design application herein contained is the property of Cascade Alarm, and is loaned upon express conditions thot the same be returned to Cascade Alarm upon request; all information herein contained shall be treated as secret, and confidential; no reproduction of this drawing or any part thereof shall be made without written consent of Cascade Alarm. CONTRACT RESPONSIBILITIES SPRINKLERS ITEM CASCADE OTHERS TYPE ORIFICE TEMP. FINISH CANOPY SYMBOL QTY. TY -FRB 1/2" 155 WH 401 WH 2 TY -FRB 1/2" 155 BRASS 79 TY -FRB 1/2" 155 WH SEMI RECESSED WH 0 9 SYSTEM TYPE WET ® _❑ ❑ ❑ Cascade Alarm PAID JUN 23 ? 23 7111 T C„J'I\VV R_r Metal Shorts Space ##9134 Airfield Business Center 9100 East Marginal Way S. Tukwila, WA. 98108 SCALE: 1 /8"=1'-0" DRAWN BY: Reid DESCRIPTION: PIPING PLAN (SPACE D) CHECKED BY: NO. CDU DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN ELTA TOTAL THIS SHEET 90 APPROVALS OUT OUT OUT OUT IN IN IN IN FIRE PROTECTION DIVISION Post Office Box 7459, Kent, WA. 206-767-5800, Ext 2 SYSTEM DESIGN DATA DATE: 6/28/11 HAZARD CI ASSIFICATION• OHG 11 SYSTEM AREA: HYDRAULIC DENSITY: .20 DFSIC,N DATA: AREA OF APPLICATION: GPM/SO. FT. : 1500 SO. FT./HD. S0. FT. AALLLOWANCE4 250 GPM TOTAL SYSTEM DRAWING NO. RFOI IIRFMENTS• 610 6 GPM. AT : 36.8 PSI. AT: CITY WATER SUPPLY INFORMATION: STATIC PRESSURE 130 PSI. FP 1 RESIDUAL PRESSURE : 20 PSI. WITH : 10,000 GPM FLOWING TEST TAKEN AT BY : CITY DATE