PP - 120 ANDOVER PARK EAST - LUMBER LIQUIDATORS - PERMITS AND PLANS
120 ANDOVER PARK EAST ASSOCIATED PERMITS 12-F-240 11-S-154 FIRE DEPARTMENT SPRINKLER PLAN REVIEW COMMENTS Project Name: Lumber Liquidators 120 Andover Park East Suite 120 Permit No.: 11-S-154 Date: July 15, 2011 Reviewer: Al Metzler Fire Protection Project Coordinator (206) 575-4407 option # 2 (Inspection Requests) (206) 971-8718 (Plan Review Questions) • Lateral sway bracing is required at a maximum spacing of 40' for all mains, cross mains, and branch lines 2.5" and larger. Bracing is provided for the last length of pipe but within 6' of the end of a feed or cross main. Bracing is required unless all the pipe is supported by rods less than 6" or by 30 ° wrap-around U -hooks for any size pipe, 9.3.5.3. • Minimum clearance around pipes: 2 " for 1 "-3.5", 4" for 4" and larger, see 4 exceptions, 9.3.4. • Longitudinal sway bracing is a maximum of 80' for mains and cross mains and within 40 ' of the end of the line, 9.3.5.4. • Provide lateral and longitudinal bracing for changes in pipe direction per section 9.3.5.11.2 for pipe size 2 '/2 inches and larger. • Restrain branch lines at the end sprinkler of each line, restrain against vertical and lateral movement, 9.3.6.3. • Restraints for branch lines shall be at intervals per table 9.3.6.4 and section 9.3.6.4, and restrain sprig ups greater than 4', 9.3.6.6. • Comply with ASCE 7-02, section 9.6.2.6.2 (e). • Ceilings used for flex drop attachments shall comply with ASTM C 635 and ASTM C 636 per section 9.2.1.3.3.2. • Where flexible sprinkler hose fittings exceed 6ft. in length and are supported by a suspended ceiling, a hanger(s) attached to the structure shall be required to ensure that the maximum unsupported length does not exceed 6 ft.(9.2.1.3.3.3). • Provide sprinkler protection beneath all obstructions greater than 4 ft. in width. • Extend sprinkler protection to all combustible concealed spaces. • Comply with NFPA 13 obstruction tables. • Comply with obstructed/non-obstructed construction rules for sprinkler head placement. • Sprinkler heads spaced closer than 6 ft. apart must be baffled. • Modifications involving 20 or more sprinkler heads require hydrostatic test and system isolation if necessary. • For dry pipe and double interlock preaction systems in addition to the standard hydrostatic test, an air pressure leakage test at 40 psi shall be conducted for 24 hours. Any leakage that results in a loss of pressure in excess of 1.5 psi for the 24 hours shall be corrected. • These conditions apply to any sprinkler piping exposed as necessary to accomplish the permitted scope of work. All code references are NFPA 13, 2010 Edition. Al Metzler From: Sent: To: Subject: Attachments: Lagergren, David <dlagergren@tyco.com> Friday, November 09, 2012 8:54 AM Al Metzler,; Correct cut sheets for Lumber Liquidators (Home lectric) l VISTA-128FBP Data Sheet.pdf; GE -2200 -Overhead -Door -Magnetic -Con a .pdf Al — We are proposing the 24 volt version of the panel with addressable modules for all monitored lines (water flow, tamper). The existing panel — an old Focus 45 — is failing. The other part of this project is the tamper on the water shut off for the sprinklers. The valve is located in a manhole outside the building. The existing tamper has failed. We are proposing putting a heavy duty magnetic switch on the manhole and connecting that as the tamper— it will activate any time the manhole grate is removed. Please feel free to contact me via phone or email with any other David Lagergren / Commercial Sales Executive / Tyco Integ Cell: (206) 777-5117 / FAX: (253) 620-5992 10029 S Tacoma Way Suite H7 / Lakewood, WA 98499 / USA dlagerdrenatvco.com / www.tvcois.com two Intearatad Security This email (including any attachments) may contain private or business confidential. If you received this please delete it from your system without copying it reply email so that our records can be corrected. informa email in and noti NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acc+ t Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and termination of the testing 1 uestions. ated Securit '"` '' #' E D ❑ Without Comments As Noted in Red ❑ Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau ;fir canformance with current City ,randards. Acry^i_ :: ;. sLbiect to errors and missions which (:;c, rot violations of adopted .::andards and ord'-2,anc -is. The responsibility for the ..clequacy of der: t t=-3iiy with the designer. Additions, deieto: s to these drawings after this date will voce t;+.:.s-_ - p azce and wifi require a resubmittai of revcs .L :::..v;r: s for subsequent approval. on that is itriotal acceptance is s,.tbt ct to fl 'd test and Inspection by '@laic*a Fire ?revenYVorn Bureau. Date: /(-13-1)- By: AAA\ S F►Nk -( !ILL d(Uic4s Ove poi Mt 1. 0 it- ehk,K sr ,kcff dt fi. q Sore FA cc, • Cbs 6441(6611 Livtaa- to W. hN4t CI 01 • 4lv`Ji ob+� itt�, l( Pot DtPt' Kvioy 14.0 TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. l� 1= d,io and exact address for shut- down or restoration approval. 3N11-JNO CI) 23 0 D 11 N) 0 1oiVo1Nnwwo2 Q� D 0 r H j l �! FIRE ALARM SYSTEM ` i, r -- HOME ELECTRIC f +� tel=rnfInd �'R,..,""" ` rt �._i ..� 120 ANDOVER PARK EAST SUITE 10 TUKWILA, WA 98188 PS24 Power Supply O 2003 Honeyw&l Int.rnstgnal Inc. All Rights Resecwi 0 Using PS24 to backup Control Panel Extravagant panel load 624V *averted to 12VDC from 24V hull -wave) Pow Budget Standb /Alarm Durations Battery Standby (hours): Alarm Duration (minutes): Regnhsd Capacity (AH) Use IWO idanlicai boatman w/Ibii AN capacity .m to. 1 059 PS24 POWER SUPPLY MODULE, MAXIMUM CAPACITIES Panel 12V Standby (mA) Panel 12V Alan (mA) Output A Standby (mA) Output A Alan (mA) Output B Standby (mA) Output B (n) PS24 PC Board (mA) Maximum Total Standby Output Maximum Total Alarm Output Max. Battery Capacity r li i/ 4 570 1700 570 1700 40 610 4180 34.4 24V Natificatlon Appliance 01 output A , 0 0�� ���� 0 0 total Standby Total Mann 0 0.0 0.0 0 0 0 0 40 40 40 0 24V Notification Appliance 0 1 0 0 0 Standby Budget Alamo Budgt 0 x fit 5 0 output A_ I:�.. 1 %^C1 :. C) 0 1"00 0 Nt,N7ft 0 0 0 24V NOTIFICATION APPLIANCESlinear Enter Device Names & SpecllicatlOverstayonsOverstayI 0 Weds PS24 output a gr0 Standby Leal (IIIA) Dirvk• (ININ 0 Ratlanpti) Sebum!Manny 0 1 Subtotal Alarm A 0 S yB Standby 0 Subtotal AW Am 0 24V Notification Appliance 24V Notification Appliance 0 i°utput A- � 0 0 \� 0 0 0 0 24V Natificatlon Appliance 01 output A , 0 0�� ���� 0 0 0 0 0 24V Notification Appliance 0 output n 1 0 0\\\\\\ 0 0 0 0 24V Notification Appliance 0 output a l 0 0 0 0 0 0 24V Notification Appliance 0 output A_ I:�.. 0 o \�� 0 0 0 0 24V Notification Appliance 0 °i"P A_. l 0 0\\�\\\ 0 0 0 0 24V Notification Appliance 0 output A i. 0 0 0 0 0 0 24VNotification Appliance 0 Output --n 0 0 0 0 0 0 74V Notification Appliance 0 `output a 1. 0 0 0 0 0 0 24V Notification Appliance 01 Output A 11,_ 0 0 0 0 0 0 24V Notification Appliance 0 Output A L. 0 0, ���' 0 0 0 0 24V Notification Appliance �= Outut 0,PAL` 0 0 ����\ 0 0 0 0 24V Notification Appliance 0 ,output a 0 0\\\\\\ 0 0 0 0 24V Notification Appliance 0 output a �v 0 0 \ 0 0 0 0 24V Notification Appliance 0utput A L,j,i,0 0\ 0 0 0 0 24V BELL CIRCUIT WIRE RUN DATA Units N4a9auUp(Aw) Ohms Par 1000 ft Teat Man current Draw OW Ratlanpti) Atxwl RsNearocaVottage (minass) VItap*AtEDI Drop PS24 Output A Wire Run twin lead P ( ) Feet <Select Wire Gauge> 0 \r\ �� 0 0.00 24.00 0.00 PS24 Output B Wire Run (twin lead) feet w <Select Ware Gauge> 000 ���� 0 0.00 24.00 0.00 POLLING LOOP DEVICES Enter Quantity 4101 SN Single Output Relay Module 4190SN Two Zone SIM 4190WH 4191 SN -WH 4192CP 4192SD Photoelectric Smoke Det. 4192SDT 4193SN Two Zone SIM 4194 Contact 4196 4209U 4275EX Dual PIR ■ LED Adele? 4275EX-SN Dual PIR CI LED Active? 4278EX-SN OLEO Active? DT7500SN CI LED Active? 4293SN 4939SN WH/BR/GY Surf Mt. Cntct. 4944SN Recessed Contact 4945SN-WH LH many powered by itaralby (acr Alan 4207? 0 0 0 0 0 0 0 0 5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4959SN Overhead Door Contact 5192SD Smoke Detector CI LED Active, 5192SDT Smoke w/ Heat d LED Active? 5193SD Smoke Detector t] LED Active, 5193SDT Smoke w/ Heat • LED Active? 998MX PIR • LED Active? IS2500SN PIR ■ LED Active? FG-1625SN Glass Break Detector Quest2260SN • LED Active? 0 0 0 0 0 0 0 0 0 0 0 V.lex-VSI Short Isolator Vistake Addy VPlex (enter gnty & current) Add? Vplex (enter qnry & current) 12V NOTIFICATION DEVICES ON BELL OUTPUT #1 Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current Enter device name, quant., & current 12V NOTIFICATION DEVICES ON BELL OUTPUT #2 (IF USED) Enter Quantity Enter Quantity 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Enter device name, quant., & current Enter device name, quant., & current 0 0 Enter device name, quant., & current 0 Enter device name, quant., & current Enter device name, quant., & current 0 0 0 0 0 0 0 0 0 0 0 0 Marini Arad PAW Loop 7 2 2 0.5 0.4 0.4 0.4 Total Poling Loop 0 0 0 0 0 0 0 Tow Standby CUTIN Taw Enamel retaI Nano *ument Currant Required How many powered Saudi* faux externally? PM" 0 0 0 How many powered latandblr (era \\\\\\\\\\ \\\\\\\\\\\ 0\\\\ 0 0 0 0 112V AUX POWER AND BELL CIRCUIT WIRE RUN DATA Panel Aux Power Wire Run (twin lead) Panel Bell 1 Wire Run (twin lead) Wire oarye(AWM) Alam Current (Aux) Tow TON Polling Standby Polling Loon Loop Currant \\\\\ \\ \ \ \`V o \\\\\�\\\\\\\' \\\\\\ 0 0 0 0 Alarm Current (Aux) Tow Tote/ Soy Standby Polling Loop Loo/ CUMIN 1000 ft \ \\\ \\\\\ \ \\ o \\\ \`\ \\\ 0 0 0 0 Panel Bell 2 Wire Run (twin lead) Feet Feet Feet • • • <Select Wire Gauge> • <Select Wire Gauge> • <Select Wire Gauge> LW 0.00 0.00 0.00 Tool sounder COMM bnte Pahl M e/ 0 0 0 0 0 Total Sounder Current (wawa* 0 0 0 0 0 Tow Soweder Carwt1from Panel rem Sounder DO e2 Conant xtensep 0 0 0 0 0 0 DMA, OW Run L/rytbIndy Ohms perFtlataraxtAlarm Actual I 0 0 0 0.00 0.00 0.00 0 0 0 0 ON,. atop At Mt 1 to 12.00 12.00 12.00 0.00 0.00 0.00 MULTI -POWER DEVICES 4208U [powered by polling loop] 4208U [powered by panel aux power] 4208U [powered externally 4208SN [powered by polling loop] 4208SN 04- -. b nel aux .• -r 4208SN [powered externally] Enter Quantity 0 How many powered externally? 0 0 0 0 0 0 0 0 0 0 0 4208SNF !powered by polling loop] 4208SNF [powered by panel aux power] 0 0 0 0 4208SNF :red extemall 4208SNF (Class B to A Zone Converter) 4209U Grouped Zone Mux. Module 4209U [powered externally] 4297 Polling Loop Extender Addy Device (enter quant. & currents) Add? Device (enter quant. & currents) AUXILIARY POWERED DEVICES 0 0 0 0 0 0 0 How many Enter powered Quantity externally? PS24 24 volt Power Supply Module 4100SM (no more than one per system) 4204: Enter no. of relays used 4204CF Enter no. of relays used 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Starry (ter Poling Loop roar Poli g Loop Total stanmy Cutest Toot Erternal Total Akan Comm Cance RaptYal 0 \ 0 0 0 0� \\� \ \\\ \ • 0 t t 0 0 0 Total Standby (aox Akan Toots Paling Standby pits Current Mull, Polling Loop Loop Current 50 25 40 80 100 0 0 4285 Voice Module 0 0 160 4286 with waming speakers 0 0 220 300 5140DLM Backup Dialer Module 5800RP wireless repeater module 5800TM wireless xmtr module 5881EN receiver 5883 hi -security receiver UVS-QM VA8200 Panel Linking Module VA8201 Alpha Pager Module 0 0 0 0 0 0 0 0 Add? Device (enter quant. & currents) 0 0 0 0 0 0 0 0 0 0 5 100 20 60 80 75 88 165 0 15 110 0 \\\\\\ \\\\ \ X XX X NX XX X XX X \\\\\\\\XX\\\\\\X 0 0 0 0 Total Akan Current 0 0 0 Tem/ External Curets Required 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NX X 0 0 0 0 Add? Device enter • uant. & currents Communicators 7845GSM/7845i-GSM 7845i/7845i-ENT 0 0 0 0 0 0 0 10 10 0 GSMCFI1GSMCF Fire Communicator Vista-GSMNista-GSMCN (Vista -21 iP only) 1 0 0 0 10 10 78471/7847i -E Internet Communicator 0 0 75 Add? Device (enter quant. & currents) 0 0 0 0 Add? Device enter • uant. & currents 0 0 0 0 PIR Motion Detectors (non Vpiex) 15215T 0 LED Active? IS215TCE 152260/1S2260T 0 LED Active? 0 0 0 0 0 0 7 18 4 152460 152500LT 1S2535/IS2535T 152560/1S2560T 152560TC 0 0 0 0 0 0 0 0 9 25 20 20 0 0 25 1S310/1S320 Request to Exit (RTE) 0 0 35 997 Ceiling Mount PIR 0 LED Active? 0 0 12 998 Wall Mount PIR 0 LED Active? 0 0 13 Motion Detctrs (enter quant. & currents) 0 0 0 0 Motion Detctrs (enter quant. & currents) 0 0 0 0 Motion Detctrs (enter quant. & currents) Motion Detctrs enter • uant. & currents 0 0 0 0 0 0 0 0 Dual Tech Motion Detectors (non Vpiex) DT -515 DT -61 OOSTC 0 0 0 0 20 35 0 0 DT -72357 0 0 20 0 DT-7435/DT-7435C 0 0 30 0 \\\\\\\\NX\X XX NX XX X • 0 0 0 0 0 0 10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0T-7450/DT-7450MIC 0 0 DT -7550 0 0 35 40 0 0 0 0 0 0 0 0 Motion Detctrs (enter quant. & currents) 0 0 0 0 0 0 0 Motion Detctrs (enter quant. & currents) 0 0 0 0 0 0 0 Motion Detctrs (enter quant. & currents) 0 0 0 0 Motion Detctrs (enter quant. & currents) 0 0 0 0 0 0 0 0 0 0 Honeywell Security O 2003 Honeywell International Inc All Rights Reserved 0 Apply UL Power Limb? (Required to rnNMaln (R. Litbg Including UL864) 0 Commercial Hee Imtalfatlon D Comm.fdd Duro Lnsti6tton 1$eiect _Panel _from pul dowttlist_ i Vista- 128F8P (UL864 Edition 9) Battery Standby (hours): Alar Duration (minutes): Recommended Eatery (AH) SELECTED PANEL MAXIMUM OUTPUT RATINGS 24 5 10.2 oruruly Condgency Factor 10% r Posing Loop (ma) v Location: Account It: Model: Engineer: Date: Facility information Enter Standby and Alarm Times HOMES ELECTRIC 10115/2012 Standby — Auxlltary Power (tnA) Alarm Auxiliary Power (m4) Panel Standby (mA) Panel Alarm (mA) Bali 111 Output (mA) Bell a2 Output (tf used; mA) Maximum Panel Standby Output Maximum Panel Alarm Output Max Battery Supported by Panel Calculated Curtant Draw PowerBudgrt 0 Remove Unused Devices From Ust KEYPADS/INTERFACES \\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\ 6139/6139R 128 1000 1700 7.5 55 300 470 150 Catotdatsd Bal Draw BM Power Budget Extemal BMNPower Rogd(mA): 0 6160t6160CR 0 FSA -8 Fire Zone Annunciator FSA -24 Fire Zone Annunciator Add) Keypd (Enter# and Currents) Add'l Keypd (Enter # and Currents) 0 0 0 0 Shy (ax Atom Pall Cesium (Add 1700 1700 0) 0 1300 Total Standby 2800 Totat Alarm 63 Standby Budget 1: Alam Budget Toad Poling Poland Loop Loop \\\\\\\\\\ \ ' \\ 0\\\\\\\\��\\\\\\\,\\\\\\\\� \\\\\\\\�� 0\\\\\\\\\\ 0\\\\\\\\\��.\\\\\\\\.\\\\\\�\\\\\\\�� 0 \\\\\\\\�\\\\\\\\\.' \\\\\\. \\ 0. \\\\\\ \\,\ \\\\\��\\ X\\\\\\X 0 \\\\\\\�\\\\\\\'U 45 X 0 \\\\\\\\ \\\\\\\'\h\\\\\\\\\�' N 0 \\\\\\\N\\\\\\''N\\\\\\\\\\\\\\\\\‘ 0 0.\\\\\\\\\\X NX N 0 0\\\\\\\\X\\\\\\\\\XX\\\\\\XX\\\\\\� 0 0 \\\\\\\ XX \\\\\\\\X\�\\\\\\\�� 0 0 \\\\\\\ \U ,\\\\\\\�\ 0 0\\\\\\\\\�\\\\\\\:\\\\\\\\\ \\\\\\\ 0 0\\\\\\\\\\k:X N\\\\\\\\�� \\\\\\\' 0 \\\\\\\`X\ \X\\\\\\N.\\\\\N 0 0 \\\\\\\\ \ \\\\\\\X\\\\\N 0 0 \\\\\\\\\X‘ X\\\\\\\\ \\\\\\\\ \ 0 0 \\\\\\\\\i \\\ X\\\\\N 0 0 \\\\\\\\\\\\\\\\\\\ 0 \\\\\\\\\\\\\\\\\,x .\\\\\\\\\ 35\\ 0 35 130\\\\\\\\\\XX\\\\\\\ 0 0 0 \\\\\\\\ 0 40 100 0 0 45 150 160 Ext UL Power Reg d (mA): Total Standby Torr Ex$nw Current Total Alarm Current CurrentRapukW O 0 0 O 0 0 O 0 0 O 0 0 O 0 0 0 0 0 O 0 0 O 0 0 O 0 0 O 0 0 45 150 0 0, 0 0 0 0 0 0 0 0 65 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 WIRE & 4 WIRE SMOKE DETECTORS (except Vplex Polling Loop detectors) Enter Ouandry 2 wire smoke detector (zone powered) 2 wire smoke detector (zone powered) 0 2 wire smoke detector (zone powered) 2 wire smoke detector (zone powers • 0 0 12V 4 Wire Smoke (Qnt'y & Currents) 12V 4 wire Smoke (Qnt'y & Currents) 12V 4 wire Smoke (Qnty & Currents) 12V 4 wire Smoke (Qnty & Currents) 0 0 0 0 How many Toast powered 'Standby (a�dt Aare Total Posing Standby Toast Extatnr externally? taw) Cur nt (Azad l Poland Loop' Loop Cement Intel Aam, C nein Current Requitedpowered 0 Two-w,re smoke detector current rs built into the panel budgets hese fields are included to help you create a complete equipment list The line below indicates if number of detectors exceeds panel capacity, or if the selected panel does Trot support 2 -wire smoke detectors 0 0 \ \\ 0 0 \\\\\\ \\\\\\\\\\\\\ \\\ \\ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 34.4 GENERAL NOTES! 1. SYSTEM DESIGNED PER N.F.P.A. #13 STANDARDS. 2. ALL SYSTEM COMPONENTS U.L. LiSTED AND/OR F.M. APPROVED. 3. NEW PIPING SHALL TO BE SCH.40 SPRINKLER PIPE WITH THREADED FITTINGS 4. SCOPE OF WORK IS TO ADD NEW PENDENT HEADS IN NEW DROP CEILING & OFFICE USING MECHANICAL TEES, ADDED THREADED TEES & 1 NEW BRANCH LINE OFF OF 6" CROSS MAIN. NEW HEADS SPACED TO MAXIMUM OF 130 SQ FT. 5. STRUCTURE IS OF WOOD CONSTRUCTION. UPRIGHT PROTECTION TO REMAIN. 6. EXISTING SPRINKLER SYSTEM IS WET WITH SPACING TO ORDINARY HAZARD I. �G -ULAM BEAM EXISTING BRANCH LINES 32'-0 / MECHANICAL TEE TYP - - SHOWROOM -� 101 WAREHOUSE BOD 20-3 4 M 1 t t t 1 1 1 1 1 1,01 11 1 1 1 1 1 1 O'-3 1 1�2 1 O'-4 1 O'-4 w-1 o N 014 y\--37 szt + 1 , O'-4 o ON 1" LINES A THREADED TEE WILL BE INSTALLED TYP T 0 T"' i .t/ 101-0 // 24'-0 MECHANICAL TEE 6 X 1 1/2" AREA OF WORK RCP SCALE: 1l4"= 1'-O" SPRINKLER RISER 102 SIDE SAMMY SCREW Side Sammy Screw Swivel Ring 111018m- All Thread Rod Pipe HANGER DETAIL G LU LAM BEAMS AREA OF WORK SITE PLAN NTS EXISTING BRANCH LINES NEW DROPS WITH FLEXHEADS 7 / / / / / / r-� NEW GWB 9-0 OFFICE 8 / / / / / / / / / / / / / / a F-3 ..4- NEW ACT CEILING @ 10-0 SHOW ROOM NEW FURRED OUT WALL AT FRONT OF SPACE / / / / / / / / / / / Pa EI Without Comments 0 As Noted in Red 0 Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City standards, Acceptance is subjectto errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the &dequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: 7- IS -I(51( �l NEW WALL FOR OFFICE NEW FULL HEIGHT WALL SECTION VIEW A NTS pae C©p TUKWILA FIRE DEPARTMENT Please call 206-575-4407 and give this Fire Permit No. /(-S- U9 and exact address for shut- down or restoration approval, PAID JUL 05 2011 KWILAFIRF Symbol Legend Description Revision No. Revisions Description Symbol Manufacturer Sprinkler Legend Model K Factor Degree Qty. 2 WAY EQ BRACE 4 WAY EQ BRACE RIGID GROOVED COUPLING 0 0 GLOBE EXISTING GL5601 QR CHROME/CHROME PENDENT 5.6 155 13 QR BRASS UPRIGHT 5.6 200 20 FLEXIBLE GROOVED COUPLING NEW SPRINKLER PIPING EXISTING SPRINKLER PIPING HANGER LOCATION CONTRACTOR'S LICENSE: Lic. # RELIAFP 102L1 Job No.: S06251 Date: JUNE 2011 Drawn by: J B Reliance Fire Protection Inc., Tel: (206) 682-6636 PO Box 428 Fax: (206) 64 Preston, WA 98050 e-mail:jim@rerelianciancefire.com Approval: TUKWILA FIRE Scale: AS SHOWN LUMBER LIQUIDATORS 120 ANDOVER PARK EAST ' Loo TUKWILA, WA 98188 FP 1 of 1