Loading...
HomeMy WebLinkAboutPP - 3434 S 152ND ST - KEY BANK OF WA - PERMITS AND PLANS3434 S 152ND ST ASSOCIATED PERMITS 09-F-148 3 Y 34-1 S / S - Global Project Values: LENT Project Name: Key Bank Riverton Heights Standby Hours: 24 itSI1 it KNIGHT Project ID: Alarm Mins: 5 Prepared By: Eric Wise Derating Factor: 1.2 5808 Calculations Date: 9/3/2009 Voltage Drop Waming Version 02.18.09 Threshold % : 10 Panel ID: 5808 Model: 5808 Add. Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: Basement Electrical Room Volts: 24 VDC Max Panel Current: 5.0 Amps Current Draw Ckt.# Circuit Name QtyStandby Alarm Wire AWG Ohms Per Length(ft) Actual Volts @ o & Type 1000 Ft. One-Way Ohms EOL °Drop 5808 5808 CTRL Panel 1 0.206 0.356 SD500-AIM Addr. Input Mod 0 0.000 0.000 SD500-MIM Mini-Input Module 0.000 0.000 SD500-ARM Addr. Relay Module 0.000 0.000 SD500-PS Addr. Pull Station 3 0.002 0.002 SD505-AIS Addr. Ion Smoke Det 0.000 0.000 SD505-AHS Addr. Heat Detector 18 0.010 0.010 SD505-APS Addr. Photo Smoke Det 30 0.017 0.017 SD505-DUCTR Addr. Duct w/Relay 0.000 0.000 SD505-DUCT Addr. Duct 0.000 0.000 SD500-ANM Addr. Notification Module 0.000 0.000 SD500-LED Addr. LED Module 0.000 0.000 SD500-SDM Addr. Smoke Det. Mod. 0.000 0.000 SD505-6RB Addr. Det. Relay Base 0.000 0.000 SD505-6SB Addr. Det. Sounder Base 0.000 0.000 SD505-61B Addr. Det. Isolator Base 0.000 0.000 SD500-LIM Line Isolation Module 0.000 0.000 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial/Parallel Module 0.000 0.000 5496 Power Expander 0.000 0.000 5895XL Power Expander 0.000 0.000 5865-4 LED Annunciator (4G) 0.000 0.000 5865-3 LED Annunciator (3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 5883 Relay Module 0.000 0.000 NAC #1 Main Floor NAC 0.000 2.090 #14 Solid 2.52 185 0.93 18.45 9.55% NAC #2 Basement South NAC 0.000 1.806 #14 Solid 2.52 165 . 0.83 18.90 7.36% NAC #3 Basement North NAC 0.000 1.664 #14 Solid 2.52 160 0.81 19.06 6.58% NAC #4 Notification Appl Circuit 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Total Standby Current (Amps) 0.254 5.969 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 6.097 0.497 Total Alarm AH Required Total Combined AH Required 6.59 Command Shortcuts Multiply By The Derating Factor 1.20 Minimum Battery ArnpHours Required 7.91 Configure Circuits Print Page \ l 3 Y 34-1 S / S �►5 Circuit Configuration Project Information r Project Name: Key Bank Riverton Heights Prepared By: Eric Wise Project ID: 0 Date: 9/3/2009 Ckt. Number: Main Floor NAC Ckt. Name: Main Floor NAC Panel ID: 5808 Use: Notification Appl Circuit v Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 7 Gentex GEC24 Horn/Strobe (110cd) 0.000 0.279 0.000 1.953 1 Gentex GES24 Strobe (60cd) 0.000 0.137 0.000 0.137 Unused Unused 0.000 0.000 0.000 0.000 Unused Unused 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 2.090 Ckt. Number: Basement South NAC Ckt. Name: Basement South NAC Panel ID: 5808 Use: Notification Appl Circuit v. Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 5 Gentex GEC24 Horn/Strobe (110cd) 0.000 0.279 0.000 1.395 3 Gentex GES24 Strobe (60cd) 0.000 0.137 0.000 0.411 Unused Unused 0.000 0.000 0.000 0.000 Unused Unused 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 1.806 Ckt. Number: Basement North NAC Panel ID: Ckt. Name: Basement North NAC Use: 5808 Notification Appl Circuit v Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 4 Gentex GEC24 Horn/Strobe (110cd) 0.000 0.279 0.000 1.116 4 Gentex GES24 Strobe (60cd) 0.000 0.137 0.000 0.548 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 1.664 a R -- r - / (-15r- 3 4(3 ci s. /s Z~� S� SI11\I INA ICI I I Circuit Configuration Project Information Project Name: Key Bank Riverton Heights Prepared By: Eric Wise Project ID: 0 Date: 9/3/2009 Ckt. Number: NAC #4 Panel ID: Ckt. Name: Notification Appl Circuit Use: 5808 Notification Appl Circuit v Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Er 3,./3"/ S. r52'=4 1 F0 2008 BRANCH MODERNIZATION PROGRAM AREA OF WORK in CJ Without Comments As Noted In Red C Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current City stwidards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the odequacy of design rests totally with the designer. Additions, deletions or revisions to these drawings after this d to will void this acceptince and will require a resubrn1ttai of revised drawings for subs`;quent approval. i'irtal.acceptance Is subject to field test and Inspections by The Tukwila Fire Prevention Bureau. Date: 09 By:w Cte.$3 -I-o .!.e rp‘oi 1a 411 defevforS, P1D# 3872 RIVERTON 1-1 E 1 G 1-1 iS-P"t9"R""oe°i-°°.4"`� 3434 SOUTH 152ND ST. SEATTLE, WA 98188 SITE PLAN AREA OF WORK Joy ��� f ( ec"rr C'e; c tilts e. `)- -gzo-7).13 .1;151 y vcq 4.- IA Lake G q w►io „, TUKWItA FIRE DEPARTM PIft Please call: 575•440Z -nd. give this job • • xact address for shut Stain or restoration apnrovol. NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a•Re-inspection Fee and termination of the testing. AERIAL LOCATION 90) cFQ A"3° long: TRUE PLAN NORTH NORTH JACO 250 E. BROAD ST., SUITE 1150, COLUMBUS, OH 43215 (614) 437-4300 FAX (614) 437-4304 Client: KeyBank 2025 ONTARIO ST, 4TH FLOOR CLEVELAND, OHIO 44115 Project: 2008 BRANCH MODERNIZATION PROGRAM PID# 3872 RIVERTON HEIGHTS 3434 SOUTH 152ND ST. SEATTLE, WA 98188 No. Date Issue/Revision B 05-05-09 ISSUE FOR PERMIT / BID A 04-09-09 DESIGN DEVELOPMENT Designed By: PDX Drawn By: KAH Checked By: MKB Project No.: F5W86602 Scale: AS NOTED Sheet Title: Drawing No.: TITLE SHEET ATM ROOM KM . . . VESTIBULE 100 ETR 10-3' TELLER AREA 109 w E C1 Q' iii31 i iti immall •r■M 1■KIMI■N 111111011.1111 MNIOW Imri0! 111111111111111v II MINIIIMNII i■iiM■■ 1■■1111M■ I■11111'®6u. 7 11111164 -gm wpm 111 -�VI■a I■ 1111■■■■ ■■ ■II -■■I ■1 10'-3' -rc, FAC.? er.AcT L.Oc Azt4J Td es r3CTrwkrkm&teo ON S/TP TELLER WORK AREA 108 10'-3 O t9 wen �_„1=IOW L O • ■ 210" O O 4) 00 O 10'-3" STAIRS ST -1 ETR 1 STORAGE 006 O O asp • f WORK STATION 1 WORK STATION 2 teat O AIL 411, ETR ETR ■ ■I O Op O ••_ _•_f>•■1_■ EMU C STOMER AREA 101 0 WHEELCHAIR LIFT 1 OPEN EMERGENCY EXIT 106 ETR 1 WORK STATION n WORK STATION I4 FIRST FLOOR -REFLECTED CEILING PLAN SCALE: 1/8"=1'-0" CONFERENCE ROOM 005 ETR ETR HALL 013 ETR 1 WOMEN'S RESTROOM 1 007 ETR ly PHONE/ ETO ROOM 004 7'-8" f miidI� = .-1_il ��l -1 ■ ■ io Ti ■■■11 STORAGE 003 MEN'S RESTROOM 008 ETR UNISEX RESTROOM 010 ETR ELEC/ MECH ROOM 009 ETR HALL 011 ETR STAIRS • r 0 0 ETR ChAv%rjf4 5v-.0'") 1 CONFERENCE ROOM 102 10'-3" C KIT\L KCAr9 OFFICE 103 10' OFFICE 104 10'-3" SALES WORK ROOM 105 ETR EOL 0 0 Q O O C>3:O C 6111111WIIIIIIWIIIIMII=m111111111=1/4111 , 11 ■11■illi■11■Ii 11 ■11■1111■11■/■ A III �/■■■■�■ ■■.■■■■�■ 1/111111111111111.111 MIllI■__, IIIIi' p i_ .N immurAimi a_iIII,-1 iii1iiiIiUi1MI Al 1111111111■1PRIN __ 117 miiim `Ill NIMII VIIRIEn ■■■■■11111■ ■ 41111111■■ ■■■■■�■I III I71■■■■■� 1111111111111111111111■I relic■■■■■■ ■■•It11■u■■■■111 MAIIIIMIIIIMP111111■•111`! I■■■■■ .. ■■/i���I.:Arilir■r111�> IU!Il1i1flIU • • STAIRS STORAGE 1 014 1 1 ETR WHEELCHAIR LIFT IWL-1 l ADA COU PON ROOM 1 012 1 9'-5" 0021 EMPLOYEE LOUNGE 001 1 1 ETR HALL CUSTOMER SERVICE VAULT 1 015 1171-61 ETR 1 ETR RECORD VAULT 017 I ETR BASEMENT FLOOR -REFLECTED CEILING PLAN SCALE: 1/8"=1'-0" 018 ETR MAIM GLoart_ KE Lj> STItb2E ON L`/ El< ►tbttN STIZO �cr • wewriiF_,R PCtoof \-\S. N\P'NvA4. P\)L.\_. ® ANNUNCt/\ToR. Q P13oTo 514\ng-E • t36 fthVZ KE�'t Dt^T. 19ti' Fr1 &ED \\eA't DET. 114 m, Q► 121,4 U3► NO 6t3 � 120- 1210CH Imo Q�t RCP GENERAL NOTES 1. ALL CEILINGS ARE TO MATCH EXISTING CEILING HEIGHT (U.O.N.). REFER TO REFLECTED CEILING PLANS FOR FURTHER INFORMATION. 2. VERTICAL DIMENSIONS ARE ABOVE FINISHED SLAB (A.F.S.) ACOUSTICAL LAY -IN TILES. PATTERN RUNNING IN SAME DIRECTION, EXCEPT THOSE AREAS NOTED OTHERWISE ON REFLECTED CEILING PLANS. 3. CONTRACTOR TO COORDINATE INSTALLATION OF CEILING GRID WITH EXISTING MECHANICAL PLUMBING AND ELECTRICAL PRIOR TO INSTALUNG LIGHT FIXTURES TO ENSURE PROPER CLEARANCES. CONTRACTOR TO NOTIFY ARCHITECT WHEN SUFFICIENT CLEARANCE CANNOT BE MAINTAINED. 4. REPLACE EXISTING ACOUSTICAL TILE TO MATCH EXISTING MFR'S STYLE AND RATING AS REQUIRED BY LOCAL BUILDING CODE OFFICIAL. 5. EXISTING FIRE ALARM SOFTWARE SHALL BE REPROGRAMMED TO INCLUDE ANY NEW DEVICES AND LOCATIONS. 6. FOR LIGHT FIXTURE SCHEDULE SEE ELECTRICAL ENGINEERING DRAWINGS. 7. DIMENSIONED LIGHT FIXTURES ARE FROM FINISH FACE OF PARTITIONS TO CENTER LINE OF FIXTURE AND FROM CENTER LINE OF FIXTURE TO CENTERLINE OF FIXTURE. ALL FIXTURES SHALL BE INSTALLED IN CENTER OF CEILING TILE U.O.N. 10. ALL MULTIPLE SWITCH LOCATIONS ARE TO BE GANGED AND INSTALLED WITH A SINGLE FACE PLATE. 11. ALL V.A.V. BOXES AND ALL ITEMS REQUIRING ACCESS SHALL BE RELOCATED OUT OF GYPSUM BOARD CEILING U.O.N. 12. ANY DISCREPANCIES WITH LIGHT FIXTURES, SWITCHES, THERMOSTATS, DIFFUSERS AS TO LOCATION BETWEEN ARCHITECTURAL AND ENGINEERING DRAWINGS OR BETWEEN THE DRAWINGS AND EXISTING FIELD CONDITIONS SHALL BE CLARIFIED WITH ARCHITECT BEFORE PROCEEDING WITH INSTALLATION. 14. ALL THERMOSTATS TO BE CENTERED ABOVE LIGHT SWITCH U.O.N. AND ARE TO BE MOUNTED 6" ABOVE LIGHT SWITCH, CENTERLINE TO CENTERLINE OF DEVICES UNLESS OTHERWISE NOTED. REFER TO ENGINEERING DRAWINGS FOR REQUIRED QUANTITY. 15. EXISTING CEILING GRID TO REMAIN IN PUBLIC AREAS EXCEPT WHERE INDICATED TO BE DEMOLISHED ON DEMOLITION PLAN. NEW CEILING TILES IN ALL PUBLIC AREAS. SPLICE NEW CEILING CROSS GRID TO EXISTING WHERE REQUIRED TO SUPPORT NEW 2' X 2' LIGHT FIXTURES. PAINT ALL GRID IN PUBLIC AREAS WHITE. 16. ACCESS PANELS SHALL BE INSTALLED AT ANY LOCATION REQUIRING FUTURE ACCESS, PIPING VALVES, VALVE CONTROLS ETC. WHETHER OR NOT INDICATED ON DRAWINGS. ANY ACCESS PANELS REQUIRED IN GYPSUM BOARD CEILING SHALL BE VERIFIED WITH ARCHITECT PRIOR TO INSTALLATION. 17. CONTRACTOR TO VERIFY AND COORDINATE SWITCH AND DIMMER CONTROL LOCATIONS.WITH MILLWORK AND PROVIDE CUT OUT F OR FLUSH MOUNTED SWITCHES IN MILLWORK, 18. REFER TO MECHANICAL ENGINEERING DRAWINGS FOR QUANTITY AND SIZE OF AIR SUPPLY DIFFUSERS, AIR RETURN AND EXHAUST GRILLES. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT PLACEMENT. NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO INSTALLATION. 19. ALL LIGHT FIXTURES, SPRINKLER HEADS AND ANY OTHER CEILING FIXTURES SHALL BE CENTERED IN THE 2.0 X 20 TILES. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION IN ELEVATOR LOBBIES TYP. 20. FINAL EXIT SIGN AND EMERGENCY LIGHT LOCATIONS ARE SUBJECT TO THE APPROVAL OF THE LOCAL AUTHORITY AND FIELD INSPECTOR. 21. ALL SWITCHES LOCATED ON PARTITIONS ADJACENT TO DOOR SWINGING AGAINST PARTITION TO BE POSITIONED CLEAR OF DOOR SWING AND VISIBLE WHEN DOOR IS FULLY OPEN. 22. ALL SWITCHES TO BE BUILDING STANDARD TOGGLE TYPE. 23. SEE LIGHTING PLAN FOR CIRCUITING OF EMERGENCY EXIT SIGN AND 24HR FIXTURE PLACEMENT. 24. FOR SUSPENDED CEILING SYSTEMS AND DETAILS SEE DRAWINGS A-503 & A-504. 25. CONTRACTOR TO REPLACE ALL DAMAGED CEILING TILES IN BACK OF HOUSE WITH CEILING TILES SALVAGED DURING DEMO OF EXISTING CEILING TILES IN PUBLIC AREAS. "NLI b." ATTI L L_ A'1 13‘.&-t" LEGEND • 12"X12" SUSPENDED ACOUSTIC CEILING SYSTEM TO REMAIN NEW 252 SUSPENDED ACOUSTIC CEILING SYSTEM GYPSUM CEILING / SOFFIT 1'x4' RECESSED FLUORESCENT LIGHT FIXTURE 2'x4' RECESSED FLUORESCENT LIGHT FIXTURE 2'x2' RECESSED FLUORESCENT LIGHT FIXTURE O INCANDESCENT LIGHT FIXTURE HVAC DIFFUSSER z E R +a-0" HVAC RETURN DIFFUSSER CONCEALED SPRINKLER HEAD EXIT SIGNS - CEILING MOUNTED CEILING GRID STARTING POINT DENOTES EXISTING ITEM TO REMAIN DENOTES EXISTING ITEM TO BE RELOCATED CEILING OR SOFFIT HEIGHT 0 SHEET KEYNOTES 1. NEW TELLER AREA GYPSUM BOARD SOFFIT TO BE PAINTED PT -2. BACK FACE OF SOFFIT TO ALIGN WITH BACK FACE OF TELLER LINE BELOW 2. LIGHTS NOT PROVIDEt IN THIS AREA TO AVOID GLARE ON VIDEO WALL 3. REPLACE EXISTING CANOPY WITH SIMILAR SYSTEM AS SPECIFIED BY BRILLIANT 4. PATCH EXISTING CEILING AND REPAINT TO MATCH EXISTING AS REQUIRED 5. NEW CEILING GRID AND TILES 6. NEW GYPSUM BOARD CEILING 7. NEW EXPOSED W -BEAM. REFER TO 7/A-504 8. APPROXIMATE LOCATION OF NEW CONDENSATE LINE TO BE INSTALLED ABOVE EXISTING CEILING. REFER TO PLUMBING DRAWINGS. PATCH AND REPAIR CEILING TO MATCH ADJACENT SURFACES 9. NEW GYPSUM BOARD SOFFIT TO BE PAINTED TO MATCH ADJACENT WALLS. SEE 91A-501 E 55 IA A'TGt& E^ T1.1 1-1f3.E Llh Ftcom. 3EL.bv.1 • PLAN NORTH 0 8' 16' 24' JACO 250 E. BROAD ST., SUITE 1150, COLUMBUS, OH 43215 (614) 437-4300 FAX (614) 437-4304 Client: KeyBank 2025 ONTARIO ST, 4TH FLOOR CLEVELAND, OHIO 44115 Project: 2008 BRANCH MODERNIZATION PROGRAM PID# 3872 RIVERTON HEIGHTS 3434 SOUTH 152ND ST. SEATTLE, WA 98188 No. Date Issue/Revision B 05-05-09 ISSUE FOR PERMIT / BID A 04-09-09 DESIGN DEVELOPMENT Designed By: PDX Drawn By: KAH Checked By: MKB Project No.: F5W86602 Scale: AS NOTED Sheet Title: REFLECTED CEILING PLAN Drawing No.: A-104 0 INIENNIWNMENIEWANC INIEWMEININENDENOV r.aiaiiii�yae_� (WA ,r x ri aesrt _ � ., .,_ 1111,.._.. _== 111���t���lil�tfI11IIIIIIIltl111111 tll�3<�C�■f/�r1 0 SOUTH -ELEVATION SCALE: 1/8":=1'-0" t■ii■■■■■i[ 1•■iiil 0 WIINWIM 111 ■����■��■El R. .1.11. ������■����■�■■/■rte II Ill III II'I I111IT11111ITIIJT[111ITfll j' � NORTH -ELEVATION SCALE: 1 /8"=1'-0° GRACE ICE AND WATER SHIELD -FULL ROLL -TO EXTEND MINIMUM OF 4" OVER GUTTER EDGE EXISTING ROOF SHEATHING b'h .040 ALUMINUM BOX GUTTER VERIFY SIZE IN FIELD, GUTTER TO BE SIZED TO BE SUPPORTED BY GUTTER FORM AND SHALL NOT SAG. FINISH TO BE DARK BRONZE. EXISTING BOX GUTTER FORM, REPLACE AS NECESSARY AND LINE WITH GRACE ICE AND WATERSHIELD PRIOR TO INSTALLATION OF GUTTER J GUTTER DETAIL SCALE: 1"=11-0" CV NEW SHINGLES GRACE ICE AND WATER SHIELD EXTEND FROM GUTTER OVER DRIP EDGE A MINIMUM OF 4" .040 ALUMINUM DRIP EDGE FINISH KYNAR 500 WHITE OUTLINE OF EXISTING FASCIA GUTTER DROP TO EXTEND FULL LENGTH REQUIRED TO BE SINGLE PIECE FROM GUTTER TO DOWN SPOUT WITH MINUMIN OVER LAP AT DOWNSPOUT TO BE 4". DROP TO BE FORMED WITH PITTSBURGH LOCK AND SEALED TO BE WATER TIGHT. /STT i G. !-1 EATS w I T 1+ t �►I 3' nr TYP. ra.rrraaswraras aawaaawwr�risw�srra�r�mwrswec�esaMsr�c. 6.dma l�tlli. Wit_ si�wr.+sa+rr�r----r�w�wn�r=r==rrr_ Ave -- 1 Jy{1"r 1► \■�■�w _- fff�+�►�ill iG'�e— Tr�■ot�■e�r rtr inr Jr ,1 114■■■ �■■■�� 1Ni SS IIIIIIIIIII-4111'�S: C3FTA■■i�Si'�GCf _111,1�� ■Y %r`= " twwr,�r.+r�r�ri�r.�asarisr��r►rr.wrlirr�wrri�ri�iw`rwn�eaa�nrlai+u`r�uwr�iwwa 1111. —_1111_ zimmJjEwikra:wr-o.ranariar i.tit�I�..�s+�m�rrrrar— _— =__ — =_—__ _=___--__ — =J--= _ — _-- _---� LANDS Or HAWLEY ENTERPR SES, INC. PARCEL NO. 0041000493 KING CO. R.O.S. NO. 20000211900001 SURVEYOR'S DESCRIPTION GENERAL NOTES 1. ALL NOTES ARE FOR REFERNCE ONLY UNLESS NOTED OTHERWISE. 2. SIGNS ARE TO BE INSTALLED BY UCENSED SIGN CONTRACTOR UNDER A SEPARATE SIGN PERMIT. Sp 11` ASPHALT S. 152ND STREET (50' PUBLIC RIGHT-OF-WAY) ARCHITECTURAL SITE PLAN SCALE: 1 "=20' 0 SHEET KEYNOTES 1. EXISTING ACCESSIBLE PARKING SPACE. 0 10' 20' 40' SCALE: 1"= 20' 60' NORTH ( 1 ' JACO 250 E. BROAD ST., SUITE 1150, COLUMBUS, OH 43215 (614) 437-4300 FAX (614) 437-4304 Client: KeyBank 2025 ONTARIO ST, 4TH FLOOR CLEVELAND, OHIO 44115 Project: 2008 BRANCH MODERNIZATION PROGRAM PID# 3872 RIVERTON HEIGHTS 3434 SOUTH 152ND ST. SEATTLE, WA 98188 No. Date Issue/Revision B 05-05-09 ISSUE FOR PERMIT/ BID A 04-09-09 DESIGN DEVELOPMENT Designed By: PDX Drawn By: KAH Checked By: MKB Project No.: F5W86602 Scale: AS NOTED Sheet Title: ARCHITECTURAL SITE PLAN Drawing No.: AS -1 00