FIRE PROTECTION SYSTEMS PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
**PLEASE PRINT**
King Co. Assessor's Tax No.: 0423049083
Site Address: 10625 East Marginal Way south Suite Number: Floor:
Tenant Name: Tube Art New Tenant? ❑ - Yes [ No
Property Owner's Name: stn Mellon NA Trust RE
Mailing Address: 10625 East Marginal Way South
Tukwila
WA 98168
CONTACT PERSON -if there are questions about the submittal.
Name: Kristopher Conner
Company Name: Froula Alarm Systems, Inc.
Mailing Address: 861 Industry Drive
City State Zip
Day Telephone: 253-753-6660
Tukwila
WA 98188
E-mail Address: kris@froulasolutions.com
Total number of new/relocated devices or sprinkler heads: ,.6
City State Zip
Fax Number: 206-575 8168
Valuation of Project (contractor's bid price): $ 2, 50 o . 0 0
Scope of Work (please provide detailed information): Install fire alarm in small office
PERMIT APPLICATION NOTES
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Fire Marshal to comply with current fee schedules.
Expiration of Plan Review -Every permit issued shall become invalid unless the work on the site authorized by such permit
is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or
abandoned for a period of 180 days after the time the work is commenced. The Fire Marshal is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE
UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OR WASHINGTON, AND I AM AUTHORIZED TO APPLY
FOR THIS PERMIT.
BUILDING OWNER
OR AUTHORIZED AGENT:
Signature: /•••"1----
Print
Print Name: Kristopher Conner
Plan Permit App.doc
Date: _./r /13
Day Telephone: 253-753-6660
1/2/13 TFD FP Form 8
10
lead
r
10
F
15 cd
75 cd
177 cd
10
FIRE ALARM PLAN
SCALE: 1 /8"= 1'-0"
C2) NORTH ELEVATION
SCALE: 1 /8"= 1'-0"
Equipment Legend
Symbol
Quantity
Part Number
Description
Back Box
1
IFP -50
Fire Alarm Control Panel
Included
0 NZ
O3
IDP -Photo
Photoelectric Smoke Detector
4" Square
C)
11
IDP -Heat
Heat Detector
4" Square
4
IDP -Pull -SA
Manual Pull Station
4" Square
F
1
SR
Wall Mount Strobe
4" Square
`�,
1
P2RK
Outdoor Hom Strobe
Included
E3
PC2R
Ceiling Mount Hom Strobe
4" Square
OD
2
SCR
Ceiling Mount Strobe
4" Square
WIRE LEGEND
A- 18 GAUGE 2
B- 14 GAUGE 2
C-18 GAUGE 4
D- 14 GAUGE 4
CONDUCTOR 'FPLP'
CONDUCTOR 'FPLP'
CONDUCTOR 'FPLP'
CONDUCTOR 'FPLP'
LEGENDS
SCALE: NOTES
NOTES:
1) ALL WORK TO CONFORM TO NFPA 72 AND NEC STANDARDS
2) WALL MOUNT HORN STROBES AND STROBES TO BE MOUNTED
80"-96" AFF OR 6" BELOW CEILING WHICHEVER IS LOWER.
3) PULL STATIONS TO BE MOUNTED:
A) 48" - 53" AFF
B) WITHIN 5' OF THE DOOR.
4) FIRE ALARM CONTROL PANEL TO BE ON DEDICATED CIRCUIT
5) WIRING METHOD TO BE OPEN CABLE UNLESS BELOW 7' AND
EXPOSED, THEN IT WILL BE CONTAINED WITHIN CONDUIT.
6) SMOKE DETECTORS TO BE INSTALLED:
A) MORE THAN 36" FROM ANY HVAC DIFFUSER
B) NOT IN CLOSE PROXIMITY TO FLUORESCENT LIGHTING
C) AT LEAST 6" DOWN FROM PEAK IN SLOPED CEILING
7) ALL JUNCTION BOXES, MUD RINGS AND BOX COVERS TO BE
PAINTED RED (INSIDE AND OUT).
8) EXTERIOR HORN STROBES TO BE MOUNTED IN THE TOP 2/3 OF
THE BUILDING STRUCTURE FACING THE ANTICIPATED FIRE
DEPARTMENT ACCESS ROAD.
9) CENTER ROW OF HEAT DETECTORS SPACING DERATED FOR 22'
CEILING HEIGHT.
10) OUTSIDE ROWS OF HEAT DETECTORS SPACING DERATED FOR
12' CEILING HEIGHT.
4
NOTES
PORTABLE
SHOP
SCALE: NOTES
5 RISER
0
SCALE: NOTES
0
0
rf
LS e
Wit oufr'omm ents
As Noted in Red
FwTIe ,;_ : i tea Letter
These plana have .nr , ; e. =' =d by The Tukwila Fire
'--J&tion Bureau tcco:nformance with current City
- ricards. is subject to errors and
.Iiia .OnS whiCi't co no ;. iithoii%e violations of adopted
odards and or,.;'fl: S, The responsibility for the
-:quacy of do 4;r:i; Kotally with the designer.
• ,,ti' nS, deseiir; (,c,; sion5 to these drawings after
arc:: tiVW "^;d .eptarice and will require a
for subsequent approval.
acce.nr.ar,;._ is ::+�0 ct to field test and inspection by
Pi ev :ntion Bureau.
oate:5- 7-15 y: /A-17,</ i
r
Thi 1 ASK def.. kwon l4/Sof -
Y- .L3/456M bre ku-- I1ysdt-e c oi, o- otectile.W PA- La .
UNUSED
SCALE: NOTES
NOTICE
A completed, signed, Tukwila
Fire Department Pre-test
Certificate must be presented
to the Inspector prior to
commencement of Acceptance
Testing of any Fire Alarm
and Detection Systems.
Failure of test will result
in a Re -inspection Fee and
'termination of the testing
TUKWILA FIRE DEPARTMENT'
Please call 206-575-4407 and
give this Fire Permit No.
and exact address for shut-
down or restorut:on app.► ov::+l.
PAID
FEB 22 2013
TUKWILA FIRE
2c Z Z//-
Froula Alarm Systems, Inc.
861 Industry Drive
Tukwila, WA 98188
206-575-1962
DESIGNER OF RECORD
Kristopher Conner
NICET IV
69311
CP 00
>IN (0
Co
Q Q>
LO:52:
�
CD
O F.
L
DATES
SUBMITTAL:
REVISION:
SHEET TITLE
FIRE ALARM
PLAN
SHEET NUMBER
FA -1