MECHANICAL PERMIT
2623049021 Permit Number: M18-0004
16400 SOUTHCENTER PKWY Unit309
Project Name: MANGUBAT
Issue Date: 1/17/2018
Permit Expires On: 7/16/2018
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
RADOVICH PROPERTIES LLC
2835 82ND AVE SE STE S 1, MERCER
ISLAND, WA, 98040
JOHN MERRILL
6426 18TH ST E , FIFE, WA, 98424
MECHANICAL & CONTROL SRVCS INC
(GENERAL)
6426 18TH ST E , FIFE, WA, 98424
MECHACS962BT
Phone: (253) 831-4446
Phone: (253) 926-9777
Expiration Date: 2/26/2018
DESCRIPTION OF WORK:
INSTALL (2) TITUS DESV BOXES. RELOCATE SENSORS, MODIFY DUCTWORK TO ACCOMODATE NEW FL;OOR
LAYOUT
Valuation of Work: $6,500.00
Type of Work: REPLACEMENT
Fuel type: ELECT
Fees Collected: $299.50
Electrical Service Provided by: PUGEST SOUND ENERGY
Water District: TUKWILA
Sewer District: TUKWILA
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
Permit Center Authorized Signature:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2017
2017
2017
2015
Date: (7d(5
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signature:
Print Name:
J0,4, s
Date: p7/4--
This
permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
2: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
3: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
4: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
5: ***MECHANICAL PERMIT CONDITIONS***
6: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
7: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
8: Manufacturers installation instructions shall be available on the job site at the time of inspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd, Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. fi l — 000
Project No.
Date Application Accepted:
Date Application Expires:
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
Site Address:
16400 SOUTHCENTER PARKWAY
King Co Assessor's Tax No.: 2623049021
Suite Number: 3°9 Floor: 3
Tenant Name: MANGUBAT
PROPERTY OWNER
Name: JOHN MERRILL
Name:
RADOVICH PROPERTIES LLC
City: FIFE State: WA
Address:
Zip: 98424
Phone: (253) 831-4446 Fax: (253)
City:
State:
Zip:
CONTACT PERSON — person receiving all project
communication
Name: JOHN MERRILL
Address: 6426 18th ST E
Address: 6426 18TH ST E
City: FIFE State: WA
City: FIFE State: WA
Zip: 98424
Phone: (253) 831-4446 Fax: (253)
926-9222
Email: JOHNM@GROUPMCS.COM
New Tenant: m Yes ❑ ..No
MECHANICAL CONTRACTOR INFORMATION
Company Name: Mechanical & Control Services
Address: 6426 18th ST E
City: FIFE State: WA
Zip: 98424
Phone:(253) 926-9777 Fax: (253)
926-9222
Contr Reg No.: MECHACS962BT Exp Date: 02/26/2018
Tukwila Business License No.: 0997334
Valuation of project (contractor's bid price): $ 6,500
Describe the scope of work in detail:
INSTALL (2) TITUS DESV BOXES. RELOCATE SENSORS. MODIFY DUCTWORK TO ACCOMODATE NEW FLOOR
LAYOUT.
Use: Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement ❑
Fuel Type: Electric ❑ Gas ❑
Other:
H:\Applications\Forms-Applications On Line\2016 Applications\Mechanical Permit Application Revised I-4-16. docx
Revised. January 2016
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Residential, Nighttime
Furnace >100k btu
Industrial
Floor furnace
55 dB(A)
Suspended/wall/floor
mounted heater
57 dB(A)
Appliance vent
Commercial
Repair or addition to
heat/refrig/cooling
system
2
Air handling unit
65 dB(A)
<10,000 cfm
60 dB(A)
Unit Type
Qty
Air handling unit
Residential, Nighttime
>10,000 cfm
Industrial
Evaporator cooler
55 dB(A)
Ventilation fan
connected to single duct
57 dB(A)
Ventilation system
Commercial
Hood and duct
2
Incinerator — domestic
65 dB(A)
Incinerator —
comm/industrial
60 dB(A)
As.
Unit Type
Qty
Fire damper
Residential, Nighttime
Diffuser
Industrial
Thermostat
55 dB(A)
Wood/gas stove
57 dB(A)
Emergency generator
Commercial
Other mechanical
equipment
2
60 dB(A)
65 dB(A)
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 dB(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytime means 7AM-10PM, Monday through Friday and 8AM-10PM, Saturday, Sunday and State -recognized holidays.
A few sounds are exempt from the noise code, including:
• Warning devices;
• Construction and property maintenance during the daytime hours (lam -1 Opm);
• Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER ,/ R S RIZED AGEN
Signature:
Print Name: JOHN MERRILL
Mailing Address: 6426 18TH ST E
H:Applications\Forms-Applications On Line\2016 Applications\Mechanical Permit Application Revised 1-4-16. docx
Revised. January 2016
bh
Date: 01/02/2018
Day Telephone: (253) 8314446
FIFE WA 98424
City State Zip
Page 2 of 2
DESCRIPTIONS
PermitTRAK
Cash Register Receipt
City of Tukwila
ACCOUNT
QUANTITY
PAID
M18-0004
Address:
16400 SOUTHCENTER PKWY 310
Apn: 2623049(
21
99.
Credit Card Fee
$8.72
Credit Card Fee
R000.369.908.00.00
0.00
$8.72
MECHANICAL
$279.60
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
PERMIT FEE
R000.322.100.00.00
0.00
$190.53
PLAN CHECK FEE
R000.322.102.00.00
0.00
$55.92
TECHNOLOGY FEE
$11.18
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R13188
R000.322.900.04.00
0.00 $11.18
$299.50
Date Paid: Friday, January 05, 2018
Paid By: JOHN PARKS
Pay Method: CREDIT CARD 215020
Printed: Friday, January 05, 2018 10:02 AM 1 of 1
SYSTEMS
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
/i�`Fi1/GUBAr T
Type of Inspection:
,,2W6t/-,N /y N !CAL
Address:
/o .5507-nerovizn Rod/
Date Called:
Special Instructions:���.T 3� /
Date Wanted:
1-31-18
al
.. .
Requester:
sytwN
Phone No:
20(e--53-1730
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
0/.4 — Rover -f -) N vvvrC(41W Cf4-'-
t� - P/C/4- L ivver/ 404 (71 -
Inspector:
Date:
!3`48
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter BLvd., Suite 100. Call to schedule reinspection.
�litus
Submittal
DESV-1.0 08-01-2017
DESV
Single Duct Terminal Unit
Direct Digital Control, Pressure Independen
W
Control Enclosure
(Optional on Cooling -Only units)
M
G
EVIEVVED F
CODE COMPLIA
APPROVED
JAN 1 0 2018
6 1/2"
Right hand unit shown. All dimensions are in
City of Tukwila 18"
► .-DINO DIV;;;;C)
Slip & Drive
Cleat Connection
Inlet Size
CFM Range
D
F
G
H
L
M
W
4
0-225
3'/8
2 1/8
7 3/8
8
15 1/2
5 3/8
12
5
0-350
4'/8
2 1/8
7 3/8
8
151/2
5 3/8
12
6
0-500
5'/8
2 1/8
7 3/8
8
151/2
3 3/8
12
7
0-650
6'/8
1 1/8
7 3/8
10
151/2
3 3/8
12
8
0-900
7 7/8
1 1/8
7 3/8
10
151/2
3 3/8
12
9
0-1050
8'/8
-
5 3/8
121/2
151/2
3 3/8
14
10
0-1400
9'/8
-
5 3/8
121/2
15'/2
3 3/8
14
12
0-2000
11 7/8
-
5 3/8
15
151/2
3 3/8
16
14
0-3000
13'/8
-
3 3/8
171/2
151/2
3 3/8
20
16
0-4000
15'/8
-
3 3/8
18
151/2
3 3/8
24
24 x 16
0-8000
23'/8 x 15'/8
1 1/8
5 3/8
18
15
3 3/8
38
Accessories (Optional)
Check 21 if provided.
❑ 24 V Control Transformer
❑ Dust Tight Enclosure Seal
❑ Fibre Free Liner
❑ 1/2" EcoShield Liner
❑ '/2" Fibre Free Liner
General Description
RECEIVED
CITY OF TUKWILA
JAN 0 5 2018
PERMIT CENTER
1" Fiberglass Liner
1" EcoShield Liner
1" Fibre Free Liner
Low Leakage
Seal/Test/Certify
SteriLoc Liner
❑ UltraLoc Liner
❑ '/2" EcoShield Liner (Foil Face)
❑ 1" EcoShield Liner (Foil Face)
❑ Disconnect Switch
❑ Hanger Brackets
• Heavy gauge steel housing.
Mechanically sealed and
gasketed, leak resistant
construction. Less than 2% of
nominal cfm at 1.5" sp wg.
• Dual density intemal insulation,
treated to resist air erosion.
Meets requirements of NFPA 90A
and UL 181.
• Rectangular discharge opening is
designed for slip and drive cleat
duct connection.
• Multipoint center averaging inlet
velocity sensor.
• Digital control packages can be
factory mounted by Titus.
• Choice of right hand or left hand
control location.
❑ Removable Air Flow Sensor
❑ Bottom Access Door
❑ OSP & IBC Certification
❑ Red List Compliant "Google" Gasketing
MIS- 000'i
Model DESV without coils can be installed
horizontally, vertically, or at any angle.
Operation is not affected by position. For
units with coils, consult technical support.
• Gauge tees for cfm measurement.
• OSHPD Seismic Certification: OSP-0352-
10
Only Titus Alpha digital controls package
approved for seismic installation.
This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are
not to scale. Titus reserves the right to make changes without written notice.
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval
system without permission in writing from Air Distribution Technologies, Inc.
DESV-2.0 08-01-2017
Accessories (Optional)
❑ Hot Water Coil Section
• Aluminum ripple fins, 10 per inch
• Coil pipe connections are male, sweat,
type "L" copper. Connection sizes are %"
OD for 1 row coil unit sizes 04-08. All
other coils have 1/8" OD.
• Coil is installed at discharge of unit.
• On units with attenuators, coil are
installed at the discharge of attenuator.
❑ 1 Row
❑ 2 Row
❑ 3 Row
❑ 4 Row
0
0
L_�
W
❑ Electric Coil Section 0 Optional
Standard Features
• Single side access to low voltage,
high voltage, and electric heater
controls.
• Automatic reset thermal cutouts, one
per element
• Manual reset secondary protection.
• Positive pressure flow switch
• Magnetic contactor for each step.
• Slip and drive cleat discharge duct
connection.
SCR Controlled Electric Heater
Options
❑ Fuse Block
❑ Disconnect switch, door
interlock type
❑ Dust tight construction
0 Mercury contactors
392
•E
368
0 Optional Lynergy Controlled Electric Heater
Supply Voltage
❑ 120V, 1 ph, 60Hz
❑ 208V, 1 ph, 60Hz
❑ 240V, 1 ph, 60Hz
-6 1/4
W
❑ 277V, 1 ph, 60Hz
❑ 208V, 3 ph, 60Hz
❑ 480V, 3 ph, 60Hz (4 wire wye
standard)
12 ri
RH
0 Integral Sound Attenuator
li•
18
392
1
-62
W
12 1/4 -I
Inlet Size
H
W
Water Coil
L (1-2 Row)
L (3-4 Row)
4
8
12
5
7'/4
5
8
12
5
j '/4
thr\
*
1/4
7'
'
#0
2
5
•
7'/4
8
1b
t
2
5
417t/ /4
9
12'/2
14
5
7'/4
10
12'/2
14
5
7'/4
12
15
16
5
7'/4
14
17'/2
20
7'/2
9 3/4
16
18
24
7'/2
9 3/4
24 x 16
18
38
5
7'/4
The total length of the DESV
unit is the summation of the
unit length (with or without
attenuator) and the length of
the optional water coil.
This submittal is meant to demonstrate general dimensions of this product. The drawings are not meant to detail every aspect of the product. Drawings are
not to scale. Titus reserves the right to make changes without written notice.
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, induding photocopying and recording, or by any information storage retrieval
system without permission in writing from Air Distribution Technologies, Inc.
GENERAL HVAC NOTES
1. THE FOLLOWING NOTES APPLY TO ALL MECHANICAL DRAWINGS. ADDITIONAL
MECHANICAL NOTES MAY BE INDICATED ON EACH MECHANICAL DRAWING. SEE
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS WHEN AVAILABLE.
2. INSTALLATION SHALL COMPLY WITH ALL GOVERNING CODES AND REGULATIONS
(LOCAL AND STATE). NOTHING ON THE DRAWINGS OR SPECIFICATIONS SHALL BE
C^ TRUED AS ALLOWING DEVIATION FROM THIS REQUIREMENT. IF A CONFLICT
SOW LD OCCUR BETWEEN DRAWINGS AND REGULATIONS, THE REGULATIONS
SHALL TAKE PRECEDENT AND CONTRACTOR SHALL NOTIFY ENGINEER IN
WRONG OF SUCH CONFLICT PRIOR TO PROCEEDING WITH INSTALLATION.
3. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL
COOSTRUCTION INCLUDING LOUVERS, CONCRETE EQUIPMENT PADS, FLASHING
DETAILS, ETC.
4. REFER TO ARCHITECTURAL DRAWING FOR ROOM ELEVATIONS. LOCATE
MECHANICAL DEVICES SUCH AS TEMPERATURE SENSORS, HUMIDISTAT, PANELS,
ETC. SO THAT THEY DO NOT CONFLICT WITH GENERAL CONSTRUCTION
(WAINSCOT, DOOR HARDWARE, ETC.) NOR WITH THE ELECTRICAL SYSTEM
(LIGHT SWITCHES, SPEAKERS, OUTLETS, ETC.) MOUNT THERMOSTATS 48" AFF
UNO.
5. MECHANICAL DRAWINGS SHOW APPROXIMATE LOCATIONS FOR GRILLES AND
DIFFUSERS. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF
GRILLES, REGISTERS, DIFFUSERS AND OTHER CEILING OR SURFACE MOUNTED
DEVICES. INSTALL EQUIPMENT IN CONFORMANCE WITH ARCHITECTURAL
FEATURES IN THE CENTER OF CEILING TILES, IN THE CENTER OF ROOMS, OR
WHERE INDICATED ON ARCHITECTURAL DRAWINGS. WHERE EQUIPMENT IS NOT
INDICATED ON ARCHITECTURAL DRAWINGS OBTAIN DIRECTION FROM
ARCHITECT PRIOR TO INSTALLATION.
6. SEE ARCH. DRAWINGS FOR EXACT SIZE AND LOCATION OF LOUVERS.
COORDINATE EXACT SIZE OF ATTACHED DUCTWORK/PLENUM AND/OR
MOTORIZED DAMPERS WITH ARCH. DRAWINGS.
7. GENERALLY DUCTWORK PLANNED TO BE TIGHT TO STRUCTURE WITH PIPING
BELOW DUCTWORK AND BETWEEN LIGHT FIXTURES. ADJUST AS NECESSARY.
8. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT AND DUCTWORK TO
PROVIDE CLEARANCES OVER LIGHTING FIXTURES FOR REMOVAL AND SERVICE
ACCESS DUE TO EQUIPMENT MAINTENANCE.
9. ARRANGE HVAC EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY
DRAWINGS, REQUIRED BY CODES AND RECOMMENDED BY MANUFACTURER ARE
PROVIDED. PROVIDE 42" CLEAR AT DISCONNECT SWITCH ON TERMINAL UNITS
WITH ELECTRIC HEATING COIL.
10. GENERAL CONTRACTOR TO PROVIDE ACCESS TO FIRE AND/OR COMBINATION
FIRE/SMOKE DAMPERS THROUGH ACCESS DOORS IN HARD CEILINGS AND
WALLS. WHERE ACCESS DOORS PENETRATE FIRE RATED SYSTEMS THEY SHALL
BE RATED IN ACCORDANCE WITH IBC REQUIREMENTS.
11. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL ELECTRICAL
CHARACTERISTICS OF MECHANICAL EQUIPMENT (VOLTAGES ETC.)
12. DUCTWORK AND PIPING INSTALLED ADJACENT TO ELECTRICAL CABLE TRAYS
SHALL ALLOW MINIMUM ACCESS OF 6" IF RUNNING PARALLEL AND ABOVE CABLE
TRAYS, ALLOW 18" TO THE SIDE OF CABLE TRAYS.
13. ELECTRICAL CHARACTERISTICS OF LISTED EQUIPMENT SHALL BE VERIFIED BY
CONTRACTOR DURING SUBMITTAL PROCESS. ANY ELECTRICAL
CHARACTERISTICS THAT DEVIATE FROM THOSE LISTED SHALL BE IDENTIFIED BY
THE CONTRACTOR, SUBMITTED TO THE ENGINEER FOR APPROVAL AND
COORDINATED WITH THE ELECTRICAL DIVISION PRIOR TO INSTALLATION OF
EQUIPMENT AS REQUIRED TO PROPERLY SERVE EQUIPMENT.
14. DRAWINGS ARE SCHEMATIC IN SOME AREAS AND MAY NOT SHOW OFFSETS
WHICH MAY BE REQUIRED. PROVIDE OFFSETS AS REQUIRED AT NO ADDITIONAL
COST.
15. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES,
ETC. FLOOR PLANS AND SECTIONS INDICATE EQUIPMENT LOCATIONS AND
GENERAL PIPE ROUTING ONLY.
16. DUCTS AND PIPES INDICATED WITHOUT DIMENSIONS SHALL BE SIZED PER
PRECEDING UPSTREAM DUCT AND PIPE SECTIONS.
17. DUCTWORK SIZES SHOWN ARE CLEAR INSIDE DIMENSION.
18. PROVIDE FABRICATED STEEL MEMBER SUPPORTS AS REQUIRED BY
MANUFACTURER'S INSTALLATION INSTRUCTIONS, AS INDICATED ON DRAWINGS
OR IN SPECIFICATIONS FOR INSTALLATION OF EQUIPMENT. REQUIRED
STRUCTURAL MEMBERS, BOLTS AND WELDS SHALL BE IN ACCORDANCE WITH
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) MANUAL.
19. IF REQUIRED FOR INSTALLATION OF PIPES, DUCTS AND EQUIPMENT, PROVIDE
ADDITIONAL STRUCTURAL MEMBERS BETWEEN COLUMNS, JOISTS AND
STRUCTURAL FRAME TO MEET SUPPORT REACTIONS (FORCES, MOMENTS,
DEFLECTIONS). STRUCTURAL MEMBERS SHALL BE DESIGNED BY A REGISTERED
PROFESSIONAL ENGINEER.
20. DO NOT CORE DRILL OR DRILL THROUGH BEAMS, COLUMNS AND SHEAR WALLS,
UNLESS INDICATED ON STRUCTURAL DRAWINGS OR AS APPROVED BY
STRUCTURAL ENGINEER.
21. PROVIDE DUCT LINING FOR THE FOLLOWING DUCTWORK: A. ALL THE AIR
TRANSFER DUCTS AND CEILING RELIEF GRILLES. B. OTHER LOCATIONS WHERE
NOTED ON DRAWINGS OR SPECIFIED.
22. PROVIDE VOLUME DAMPERS FOR EACH SUPPLY BRANCH, RETURN BRANCH
(DUCTED ONLY) AND EXHAUST BRANCH WHERE THREE OR MORE OPENINGS
ARE ASSOCIATED WITH THE BRANCH AND ELSEWHERE AS NOTED ON DRAWINGS
OR IN SPECIFICATIONS.
23. PROVIDE CONICAL SPIN -IN FITTINGS FOR ALL 90 DEGREE ROUND DUCT
BRCHES FROM RECTANGULAR SUPPLY DUCTWORK. DO NOT USE STRAIGHT
TEE -FITTINGS.
24. DUCTWORK STATIC PRESSURE AND SEAL CLASS, BASED UPON SMACNA.
25. REFER TO SEATTLE NREC COMPLIANCE REQUIREMENTS ON DRAWINGS
SCHEDULE SHEETS FOR ADDITIONAL MECHANICAL PROVISIONS.
26. SEA'1 AND LEAK TEST DUCTWORK PER -2015 IMC & 2015 WSEC.
27. BALANCE HVAC SYSTEM PER SEC.
28. COMMISSION HVAC SYSTEM PER SEC.
29. PROVIDE COMPLETION/RECORD DRAWINGS PER SEC.
30. INSULATE DUCTWORK PER SEC.
31. PROVIDE MEANS OF ACCESSING/ADJUSTING BALANCING DAMPERS AT ALL
LOCATIONS WHERE MEANS OF ACCESS HAS NOT BEEN SHOWN ON
ARCHITECTURAL DRAWINGS. PROVIDE UNITED ENERTECH I -SERIES REMOTE
POWER/BALANCE SYSTEM OR APPROVED EQUAL. COORDINATE LOCATION OF
REMOTE JACK WITH ARCHITECT AND RECORD ON AS -BUILT DRAWINGS.
ADDRESS:16400 SOUTHCENTER
PARKWAY, TUKWILA, WA 98188
PARCEL: 2623049021
TENANT: MANGUBAT
SCOPE: INSTALL (2) TITUS DESV
BOXES. MODIFY EXISTING
DUCTWORK WHERE
NECESSARY TO
ACCOMMODATE NEW FLOOR
LAYOUT.
REVISIONS
No chances shall h^ made to the scope
of work with' prior approval of
E!.iildinq Division.
NOTE: levision3 i q i rc :i n..^r.v plan subm!tta-
and may i-' '::d3 ad ';t!onal plan rev cw fees
SEPARATE TE PERA IT
REO{ `IRI D FOR:
Mechanical
lectncal
Iumbing
L`1 Gas Piping
City of Tukwila
Vii!'- `^ f':VISION
0)
0
-.1
1
m
z
m
70
STRANDER BOULEVARD
��IIIIIIIIIIIIIIIIIIIIII�
CIIIIIIIIIIIIOIIIIIIIIq
1111111111211�U 11111111
1
2'
Ciiilll~1321III~I�
IIIIIIIIIIIIIIIIIIIIII�
=1111
del
lor
SITE PLAN
1 ii_1,
128
VAV BOX SCHEDULE
TAG
MANUFACTURER
MODEL
MAX
CFM
MIN
CFM
DESV-1, 2
TITUS
DESV
265-900
145-590
FILE COPY
Permit No. MI ' W°1-1-
Plan
review approval is subject to errors and omissions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Field Copy and conditions is acknowledged:
By: �.
Date: 1//-7/i
City of Tukwila
BUILDING DIVISION
MANGUBAT TI
16400
SOUTHCENTER
PARKWAY
TUKWILA, WA
98188
CCDE COMPUANC`
APPROVED
SAN 1.0 201B
P -J
City of Tukwila
RECEIVED BUI `DING DIVISION
CITY OF TUKWILA
JAN 052018
PERMIT CENTER
MI8OoOti
SCALE
DATE
N/A
1/2/18
COVER PAGE
M-1 .0
MANGUBAT PARTIAL FLOOR PLAN
=1'
MECHANICAL d
CONTROL SERVICES. INC
MANGUBAT TI
16400
SOUTHCENTER
PARKWAY
TUKWILA, WA
98188
SCOPE: MODIFY DUCTWORK &
DIFFUSERS TO
ACCOMMODATE NEW FLOOR
LAYOUT.INSTALL (2) TITUS
DESV BOXES.
REVIEWED FCR
CODE COMPLIANCE
APPROVED
JAN 1 [i 2013
City of Tukwila
I BUILDING DIViS ON
RECEIVED
CITY OF TUKWILA
JAN 0 5 2018
PERMIT CENTER
SCALE
DATE
1/8" = 1'
1/2/18
MECH PLAN
M - 1 .1
9ERMITCOORDCOPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M18-0004
DATE: 01/05/18
PROJECT NAME: MANGUBAT
SITE ADDRESS: 16400 SOUTHCENTER PKWY - SUITE 309
X Original Plan Submittal
Response to Correction Letter #
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
\ \ill
f?[ilding Division
Public Works ❑
Fire
re Pre e on
Structural
Planning Division
❑ Permit Coordinator
1
PRELIMINARY REVIEW:
Not Applicable ❑
(no approval/review required)
DATE: 01/09/18
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE 02/06/18
Approved
Corrections Required
❑ Approved with Conditions
❑ Denied ❑
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping ❑ PW 0 Staff Initials:
12/18/2013
MECHANICAL & CONTROL SRVe3 INC
liinne ESi i iol Contact
Safety & Health Claims & Insurance
Ci) Washington State Department of
Labor & Industries
Search L&I
Page 1 of 2
SEARct
A -Z Index Help My 'MI
Workplace Rights Trades & Licensing
MECHANICAL & CONTROL SRVCS INC
Owner or tradesperson
Hull, Travis Edward
Principals
Hull, Travis Edward, PRESIDENT
Hunt, Ted Lamond, VICE PRESIDENT
HULL, ANGELA DAWN, SECRETARY
GROVER, HAROLD, VICE PRESIDENT
(End: 02/26/2010)
DICKSON, PAUL, TREASURER
(End: 02/26/2010)
WA UBI No.
602 338 440
6426 18th St E
FIFE, WA 98424
253-926-9777
PIERCE County
Business type
Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
MECHACS962BT
Effective — expiration
01/30/2004— 02/26/2018
Bond
American Contractors Indem CO
Bond account no.
100239439
Active.
Meets current requirements.
$12,000.00
Received by L&I Effective date
02/10/2014 02/06/2014
Expiration date
Until Canceled
Bond history
Insurance
Continental Western Ins Co $1,000,000.00
Policy no.
6023856626
Received by L&I Effective date
01/20/2017 01/23/2016
Expiration date
01/23/2018
Insurance history
Savings
Help us improve
https://seeure.lni.wa.gov/verify/Detail.aspx?UBI=602338440&LIC=MECHACS962BT&SAW= 1/17/2018