MECHANICAL PERMIT
1523049011 Permit Number: M18-0101
14223 TUKWILA INTL BLVD
Project Name: JUBA RESTAURANT & CAFE
Issue Date: 9/4/2018
Permit Expires On: 3/3/2019
Owner:
Name:
Address:
Contact Person:
Name:
SEG 56TH LLC
845 106TH AVE NE SUITE 100 ,
BELLEVUE, WA, 98004
ALEX BURKHART
Address: 727 S KENYON ST , SEATTLE, WA,
98108
Contractor:
Name: EVERGREEN REFRIGERATION LLC
(CONST)
Address: 727 S KENYON ST, SEATTLE, WA,
98108
License No:
Lender:
Name:
Address:
EVERGRL954R2
Phone: (206) 763-1744
Phone: (206) 763-1744
Expiration Date: 1/6/2020
DESCRIPTION OF WORK:
INSTALLATION OF ONE (1) REPLACEMENT ROOFTOP UNIT
Valuation of Work: $15,000.00
Type of Work: REPLACEMENT
Fuel type: GAS
Fees Collected: $397.38
Electrical Service Provided by: SEATTLE CITY LIGHT
Water District: 125
Sewer District: VALLEY VIEW
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fuel Gas Code:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
Permit Center Authorized Signature:/� -i� 1/I w A U' I�
1,
2017
2017
2017
2015
Date:
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
7
Signature: Date: 2-0;
Print Name: C04,eY /
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: Readily accessible access to roof mounted equipment is required.
4: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
5: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
6: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
9: ***MECHANICAL PERMIT CONDITIONS***
10: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
11: Manufacturers installation instructions shall be available on the job site at the time of inspection.
12: The attached set of mechanical plans have been reviewed by The Tukwila Fire Marshals Office and are
acceptable with the following concerns:
13: H.V.A.C. units rated at greater than 2,000 cfm require auto -shutdown devices. These devices shall be
separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance
#2437)
14: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings
shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the
power source of the air -moving equipment upon detection of smoke in the main return -air duct served by
such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall
be installed in accordance with the manufacturer's installation instructions. (IMC 606.1, 606.2.1)
15: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2437)
r �
16: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2437)
17: All new fire alarm systems or modifications to existing systems shall have the written approval of The
Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been
obtained. (City Ordinance #2437) (IFC 901.2)
18: An electrical permit from the City of Tukwila Building Department Permit Center (206-431-3670) is required
for this project.
19: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances
#2436 and #2437)
20: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply
approval of such condition or violation.
21: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention
Bureau at (206)575-4407.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1400 FIRE FINAL
0703 MECH EQUIP EFF
1800 MECHANICAL FINAL
0609 PIPE/DUCT INSULATION
0705 REFRIGERATION EQUIP
0701 ROUGH -IN MECHANICAL
0702 SMOKE DETECTOR TEST
\.
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
/
Mechanical Permit No.
Project No.
Date Application Accepted:
Date Application Expires:
1Y1(13 01 0 (
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
King Co Assessor's Tax No.: 152304901100
Site Address: 14223 Tukwila International Blvd. Suite Number: N/A Floor:
Tenant Name:
Juba Restaurant & Cafe
PROPERTY OWNER
Name: Alex Burkhart
Name: SEG 56th LLC
City: Seattle State: WA Zip: 98108
Address: 845 106th Ave NE, Suite 100
Email: alexb@evergreenhvac.com
City: Bellevue State: WA
Zip: 98168
CONTACT PERSON — person receiving all project
communication
Name: Alex Burkhart
Address: 727 South Kenyon St.
City: Seattle State: WA Zip: 98108
Phone: (206) 763-1744 Fax: (206) 763-2389
Email: alexb@evergreenhvac.com
New Tenant: ❑ Yes ® ..No
MECHANICAL CONTRACTOR INFORMATION
_
Company Name: Evergreen Refrigeration
Address: 727 South Kenyon St.
City: Seattle State: WA Zip: 98108
Phone: (206) 763-1744 Fax: (206) 763-2389
Contr Reg No.: EVERGRL954R2 Exp Date: 01/06/201 8
Tukwila Business License No.: BUS -0992877
Valuation of project (contractor's bid price): $ 15,000
Describe the scope of work in detail:
Installation of one (1) replacement rooftop unit.
Use: Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement m
Fuel Type: Electric ❑ Gas
Other:
H:\Applications\Forms-Applications On Lme\2016 ApphcationstMechanical Permit Application Revised 1-4-16. docx
Revised. January 2016
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Residential, Nighttime
Furnace >100k btu
Industrial
Floor furnace
55 dB(A)
Suspended/wall/floor
mounted heater
57 dB(A)
Appliance vent
Commercial
Repair or addition to
heat/refrig/cooling
system
47 dB(A)
Air handling unit
65 dB(A)
<10.000 cfm
l
Unit Type
Qty
Air handling unit
Residential, Nighttime
>10,000 cfm
Industrial
Evaporator cooler
55 dB(A)
Ventilation fan
connected to single duct
57 dB(A)
Ventilation system
Commercial
Hood and duct
47 dB(A)
Incinerator — domestic
65 dB(A)
Incinerator —
comm/industrial
60 dB(A)
Unit Type
Qty
Fire damper
Residential, Nighttime
Diffuser
Industrial
Thermostat
55 dB(A)
Wood/gas stove
57 dB(A)
Emergency generator
Commercial
Other mechanical
equipment
47 dB(A)
60 dB(A)
65 dB(A)
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 dB(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytime means 7AM-10PM, Monday through Friday and 8AM-1 OPM, Saturday, Sunday and State -recognized holidays.
A few sounds are exempt from the noise code, including:
• Warning devices;
• Construction and property maintenance during the daytime hours (7am-lOpm):
• Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases. a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
1 HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON. AND 1 AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signature:
Date: D ` (to
Print Name: Alex Burkhart Day Telephone: (206) 763-1744
Mailing Address: 727 South Kenyon St. Seattle WA 98108
City State Zip
H \Applications\Forms-Applications On Line\2016 Applications\Mechanmal Permit Application Revised I-4-16.docx
Revised January 2016
bh
Page 2 of 2
DESCRIPTIONS `
PermitTRAK
ACCOUNT
I QUANTITY ,< PAID
$594.02
EL18-0712 Address: 14223 TUKWILA INTL BLVD Apn: 1523049011
$69.62
ELECTRICAL
$66.30
PERMIT FEE MULTI-FAM/COMM
R000.322.101.00.00
0.00
$66.30
TECHNOLOGY FEE
$3.32
TECHNOLOGY FEE
R000.322.900.04.00
0.00
$3.32
EL18-0713 Address: 14223 TUKWILA INTL BLVD Apn: 1523049011
$127.02
ELECTRICAL
$120.97
PERMIT FEE MULTI-FAM/COMM
R000.322.101.00.00
0.00
$120.97
TECHNOLOGY FEE
$6.05
TECHNOLOGY FEE
R000.322.900.04.00
0.00
$6.05
M18-0101 Address: 14223 TUKWILA INTL BLVD Apn: 1523049011
$397.38
MECHANICAL
$382.10
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
PERMIT FEE
R000.322.100.00.00
0.00
$272.53
PLAN CHECK FEE
R000.322.102.00.00
0.00
$76.42
TECHNOLOGY FEE
$15.28
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R15174
R000.322.900.04.00
0.00
$15.28
$594.02
Date Paid: Friday, August 17, 2018
Paid By: EVERGREEN REFRIGERATION & HVAC
Pay Method: CHECK 09562
Printed: Friday, August 17, 2018 9:54 AM 1 of 1
i
4.- . .. SYSTEMS
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
Type of Ins coon:
Address:_
) 27.3i.:4.I
Date Called
qhq
Special Instructions:
Date Wanted:
a.m.
p.m.
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
COMMENTS: Ir.,.
yl47 p14... D c-
/+ ur li
Ff
4f)?rma
Inspector:
Date:
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
Project Summary
PROJ-SUM
2015 WSEC Compliance Forms for Commercial Buildings including R2, R3, & R4 over 3 stories and all R1
Revised Jun 2016
General Info
Project Title: 1 - This title will copy onto other forms
Date 8/16/2018
This PROD SUM
Project Street Address: 14223 Tukwila International Blvd.
For Building Department
'
Use
]
'
form shall be
provided as a cover
Project City, County, Zip: Tukwila, WA 98168
sheet for all
compliance form
Project Owner or Rep: SEG 56th LLC
submittals. Project
Title matches
Jurisdiction: City of Tukwila
project
plans title block.
Project Description
Select all that apply to the
scope of project.
Select Addition + Existing
or Alteration + Existing if
the existing building will be
combined with the addition
or alteration to demonstrate
compliance per Section
C502.1 or C503.1.
New Construction and Additions
❑ New Building ❑ Building A• -' '- - LI-Additie�
Existing
Building
J
❑
❑
Building Retrofit
Alteration ❑ Alteration
Change of Occupancy Historic❑Bu
Elements Scope - Select all that apply
All ❑ Building E
Service Hot Water Systems ❑ Lighting Sy
REVIEWED FOR
CODE COMPLIANCE
ExistingAPPROvEange in '
' ia9 AUG 2 8 2018
•
elopeCity of T fctianicalSystems
tBUILDING qtyistram
xisting
pace Conditioning
stems
Occupancy Type
All Commercial Q Group R - R2, R3, & R4 0
over 3 stories and all R1
Mixed Use - Building is greater than three stories above grade and it has both Commercial and Group
R occupancies.
Mixed Occupancy - Building is three stories or less above grade and it has both Commerical and
Group R2, R3 or R4 occupancies. Select All Commercial to document compliance for the commercial
areas of the building. The residential spaces shall comply with the WSEC Residential Provisions.
Space Conditioning
Categories
Select
❑
all that apply to the scope of project
Fully Conditioned
Low Energy Space Category3
•
Semi-heated2 ❑ Refrigerated Warehouse,
Walk-in Cooler/Freezer,
Refrigerated Display Case'
Eligible Low Energy Spaces
❑ Unconditioned ❑ Low energy heating/cooling capacity
❑ Wireless service ❑ Greenhouse^
equipment shelter
•
Equipment building
Floor Area and
Stories
Floors Above
Grade
Building Gross Conditioned Floor Area
Project Gross Conditioned Floor Area
General Compliance
Path
Q Prescript ve 0 Total Building Performance
Prescriptive Projects complying prescriptively shall demonstrate compliance with all applicable mandatory
and prescriptve requirements of this code. Refer to C401.2, Item 1 for more information. Compliance forms
to include with a Prescriptive submittal: All applicable ENV, LTG, MECH and C406.
Total Building Performance - Projects complying via total building performance (TBP) shall include a
summary of results from a whole building energy model per Section C407 and shall demonstrate compliance
with all applicable mandatory provisions in this Code. Refer to Section C401.2, Item 2 for more information.
Compliance forms to include with a TPB submital: PROJ-SUM, C406 -SUM & C406 -DETAIL, ENV -CHK,
LTG -EXT, LTG -CHK, and all MECH forms (except MECH-ECONO).
VUP,oioi
RnCEDVatu
CM! OC UMVJELA
AUG 17 2018
paRiErAT CENTER
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 ever 3 stories and all R1
ec anical ummary
2015 Washington State Energy Code Compliance
Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Project Title: Juba Restaurant & Cafe
MECH-SUM
Revised January 2017
Date 8/16/2018
Project Information
Applicant Information. Provide contact information for individual who can respond to
inquiries about compliance form information provided.
For Building Dept. Use
Company Name: Evergreen Refrigeration
Company Address: 727 South Kenyon St. Seattle, WA 98108
Applicant Name: Alex Burkhart
Applicant Phone: 206-763-1744 ext. 247
Project Description
Briefly describe mechanical systems in
the text box provided
❑ Total Bldg Performance (TBP)
This path includes all mandatory
provisions per C401.2 Option 2.
MECH-SUM, MECH-CHK, and C407
Energy Analysis forms required.
ofit ❑ No System Changes
❑ New Building ❑ Building Addition ' Tenant Improvement • System Ret
Installation of one (1) replacment rooftop unit.
Design Load Calculations
❑ Load calculation summary ❑ MECH-LOAD-CALC Form
Provide design load calculations for all mechanical systems and equipment serving the building
ventilating needs. If a load calculation summary is provided with the permit documents that
compliance information then the MECH-LOAD-CALC form is not required.
heating, cooling or
includes all applicable
Mechanical Schedules
forms are not required,
Mechanical Plans ❑ MECH-EQ Forms (TBD)
Indicate location of equipment compliance information. If provided on plans then MECH-EQ
however, include on plans all applicable compliance information listed in MECH-EQ tables.
Dedicated Outdoor Air
System Requirements and
High Efficiency VAV
Alternate
❑ DOAS is required per C403.6 effective July 1, 2017 (office, retail, education, library and
All occupied, conditioned areas shall be served by a DOAS that delivers required ventilation
not require space conditioning fan operation. Space conditioning fans cycled off when no
11Ventilation provided via natural ventilation per 2015 IMC in lieu of DOAS (C403.6,
fire station occupancies)
air in a manner that does
heating or cooling is required.
Exception 1)
of DOAS (C403.6, Exception
library or fire station)
C402.4.1.4 with 100% of
NI Ventilation and space conditioning provided by a HEVAV system per 0403.7 in lieu
)
❑ DOAS included in project, although not required (occupancy not office, retail, education,
• DOAS related allowances included in project:
❑ Prescriptive vertical fenestration maximum area allowance increased tc 40% per
conditioned floor area in building served by DOAS.
• Exception to air economizer per C403.3 Exception 1, include MECH-ECONO form.
Fan Power
Q Project includes HVAC air distribution systems that provide heating and/or cooling
If yes, provide a MECH-FANSYS -SUM form.
❑ For one or more systems, the total fan motor nameplate hp of all fans in HVAC system exceeds 5hp.
If yes, provide a seperate MECH-FANSYS form for each HVAC system exceeding the 5 horsepower threshold.
Refer to Section C403.2.11 and MECH-FANSYS-DOC for requirements and exceptions.
HVAC Hydronic Systems
❑ Hydronic chilled water ❑ Water -loop heat pump D No hydronic systems
❑ Hydronic heating water ❑ Geothermal
C406 Additional
Efficiency Options -
Mechanical
❑ C406.2 More efficient HVAC equipment and fan systems
Requires 90% of heating and cooling capacity to be equipment listed in tables C403.2.3(1)-(9) or air -to -water heat
pumps and heat recovery chillers. All equipment listed in tables C403.2.3(1)-(7) must be 15% more efficient than
minimum requirements. All stand alone supply, return, and exhaust fans over 1hp must have FEQ 2 71 and must be
selected within 10% of maximum total or static pressure.
❑ C406.6 Dedicated outdoor air system (DOAS)
Requires 90% of conditioned floor area to be served by a DOAS per C403.6 that delivers required ventilation air in a
manner that does not require space conditioning fan operation.
❑ C406.7 Reduced energy in service water heating
Requires 90% of floor area be in occupancy types listed in C406.7.1 and that 60% of annual hot water energy use
be provided by heat pump, waste heat recovery or solar water -heating systems.
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1
Mechanical Summary, pg. 2 MECH-SUM
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
Service Water Heating
Systems
Equipment Type (s)
❑ Hot water heating tank(s) ❑ Instantaneous
❑ Dedicated boiler ❑ Heat exchange from space heat boiler or
central hot water/steam
Distribution Type (s)
❑ Circulation System ❑ On -demand
water systems
1 No service
Commissioning
Commissioning is required for:
Q Mechanical systems per C408.2 ❑ Service water heating systems per C408.4
If required, commissioning shall be performed for all applicable systems regardless of individual equipment capacity.
Exceptions to commissioning requirements:
❑ Total output capacity of all mechanical space conditioning systems in the building do not exceed 240,000 Btu/h
cooling or 300,000 Btu/h heating. Mechanical systems commissioning not required.
❑ Capacity of largest service water heating system in building does not exceed 200,000 Btu/h. Service water heating
systems commissioning not required.
Low Energy and Semi -Heated Spaces (Note 6 and 7)
Space
Type
Location in Plan(s)
Space(s) Served
Area Served,
square feet
Heating
Capacity, Btu/h
(Note 4)
Cooling
Capacity, Btu/h
(Note 5)
Peak Space
Conditioning
Capacity,
Btu/h-sf
Compliance
Check
Notes
Note 4 - Provide total installed heating output capacity of systems serving Low Energy or Semi -Heated space(s) in btuh.
Note 5 - Provide total installed cooling capacity of system serving Low Energy space(s) in Btu/h. Not allowed for semi -heated spaces. Enter 0 if no cooling.
Note 6 - Refer to Section C402.1.1 Low Energy Building. Intalled peak space conditioning capacity, heating or cooling, may not exceed 3.4 Btu/h*sf.
Note 7 - Refer to Section C402.1.1.1 and Semi -Heated Space definition in Chapter 2. Total heating output capacity may not exceed 8 Btu/h*sf. Only systems without
electric resistance heating and no cooling are eligible for the wall insulation exception under semi -heated.
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 1 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Revised January 2017
Project Title: Juba Restaurant & Cafe
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
Equipment - Sizing, Performance and Type
N/A
C403.1
Exempt process equipment
Identify equipment to be used in manufacturing, industrial or commercial processes that do not
provide space conditioning; identify provisions applicable to this equipment per C403.1
exception
NA
C403.2.1
Load calculations
Provide load calculations performed per ASHRAE Std 183 or equivalent, using design
parameters per C302 and Appendix C; include load adjustments to account for energy
recovery
NA
C403.2.2
Equipment and system
sizing
Indicate that output capacities of heating and cooling equipment and systems are no greater
than the smallest available equipment size that exceeds the calculated loads; note exceptions
taken
NA
C403.2.3
C403.2.3.2
C403..2.3.2
HVAC equipment
performance requirements
(efficiency)
Provide equipment schedules on plans or complete MECH-EQ forms indicating type, capacity,
rated and WSEC minimum efficiencies for all heating and cooling equipment; include supply
and OSA cfms and operating hours for all air systems; identify heating and cooling equipment
that does not have a corresponding WSEC minimum efficiency (manufacturer rated)
N/A
C405.8
C403.2.14
Electric motor efficiency
List all motors ? 1/12 hp (that are not integral to a rated piece of equipment) in the mechanical
or electrical equipment schedules on plans; indicate hp, rpm, number of poles and rated
efficiency, or exception applied
For fractional hp motors (1/12 - 1 hp), indicate whether they are an electronically commutated
motor, have rated efficiency of at least 70%, or exception taken
N/A
C403.2.11.1
Fan power limitation
For all HVAC fan systems that provide heating and / or cooling, provide system total
nameplate hp in MECH-FANSYS-SUM form
For all applicable HVAC systems with total fan motor hp > 5hp, verify fan system motor hp or
bhp complies with fan power limits per equations in Table C403.2.11.1(1), provide MECH-
FANSYS form for each system
N/A
C403.2.11.2
Motor nameplate hp
For all applicable HVAC systems with total fan motor hp > 5hp, indicate fan motors specified
are the smallest available motor hp size greater than fan bhp, note exceptions taken
N/A
C403.2.11.3
Fan efficiency
For all applicable HVAC systems with total fan motor hp > 5hp, identify in equipment schedule
all fans required to comply with fan efficiency grade and indicate rated FEG is >_ 67, or
exception taken; indicate these fans are sized so total efficiency is within 15% of the fan
maximum total efficiency
N/A
C403.2.11.4
Group R occupancy exhaust
fan efficacy
For all exhaust fans < 400 cfm in Group R occupancies, indicate in equipment schedule the
fan flow rate arid efficacy (cfm/watt), or exception taken; refer to Table C403.2.11.4 (CE -57)
N/A
C403.2.13
Variable flow capacity -
fans
For fan motors >_ 7.5 hp, indicate method of variable flow control (VSD or equivalent method) in
equipment schedule, or exception taken; for equivalent method for an HVAC system refer to
HVAC System Controls for additional requirements
N/A
C403.2.3
Maximum air cooled chiller
capacity
For chilled water plants and buildings with > 500 tons of cooling capacity, indicate air-cooled
chiller capacity is < 100 tons, or exception taken
N/A
C403.4
Large capacity cooling
systems
For buildings with >_ 300 tons of cooling capacity, indicate method of multi -stage or variable
capacity control (VSD, multiple staged compressors, or max capacity of any single unit < 66%
of the total)
N/A
C403.2.3.1
Non-standard water-cooled
centrifugal chillers
For water-cooled centrifugal chillers not designed for operation at standard conditions, provide
calculations documenting maximum full load and part load rated equipment performance
requirements
N/A
C403.2.13.1
C403.4.3.2
Centrifugal fan open -circuit
cooling towers
For open -circuit centrifugal fan cooling towers with >_ 1,100 gpm capacity, indicate cooling
towers comply with efficiency requirements for axial fan open circuit cooling towers
C403.4.2
Large capacity boiler
systems
For single boilers with > 500,000 Btu/h capacity, indicate multi -stage or modulating burner
For boiler
system (sin le or multiple) with > 1,000,000 Btu/h capacity, ty, indicate turndown ratioN/AC403.4.2.5
per Table C403.4.2.5 and method (multiple single input boilers, modulating boilers, or
combination)
N/A
C403.2.13
Variable flow capacity -
pumps
For pump motors >_ 7.5 hp, indicate method of variable flow control (VSD or equivalent method)
in equipment schedule, or exception taken; for equivalent method for a hydronic system refer
to Hydronic System Controls for additional requirements
N/A
C403.2.3
Gas and oil -fired forced air
furnace and unit heaters
For forced air furnaces with capacity >_ 225,000 Btu/h and all unit heaters, indicate in
equipment schedule intermittent ignition or IID, flue or draft damper, and rated jacket loss
N/A
C403.2.4.8
Combustion heating
equipment
For combustion heating equipment with output capacity > 225,000 Btu/h, indicate modulating
or staged combustion control
N/A
C403.2.3.3
Packaged electric heating /
cooling equipment
Verify all packaged electric equipment with > 6,000 Btu/h cooling capacity and any amount of
heating is a heat pump; include in equipment schedules
N/A
C403.2.12
Heating outside a building
Indicate systems providing heating in non -enclosed outdoor occupied spaces are radiant
systems; refer to HVAC System Controls for additional requirements
N/A
C403.2.7.1
Kitchen exhaust hoods
Indicate on plans the type, duty and exhaust air rate of each kitchen hood, refer to HVAC
System Controls for additional requirements
Yes
C403.2.4.3
Outdoor supply air, exhaust
and relief dampers
Indicate locations of OSA intake, and exhaust and relief outlet dampers on plans; indicate
whether dampers are Class 1 motorized, or gravity and exception taken (include leakage
rating, cfm/sf); refer to HVAC System Controls for additional requirements for OSA dampers
M200
Yes
C403.2.4.3
Return air dampers
Indicate locations of return air dampers that are integral to economizer operation; verify
dampers are motorized; indicate whether dampers are Class 1, or within packaged equipment
eligible for leakage rating exception (include leakage rating, cfm/sf)
M200
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 2 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Revised January 2017
Project Title: Juba Restaurant & Cafe
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
N/A
C403.2.4.3
Stairway and shaft vent
dampers
Indicate location of stairway and shaft vent dampers on plans; verify dampers are Class 1
motorized; refer to HVAC System Controls for additional requirements
N/A
C403.2.4.4
Zone isolation dampers
For systems serving areas > 25,000 sf or spanning more than one floor, that include areas that
are expected to be occupied non -simultaneously; identify isolation zone areas on plans and
locations of associated isolation dampers in HVAC distribution system; refer to HVAC System
Controls for additional requirements
N/A
C403.2.3.4
Humidification
For cooling systems with humidification equipment that are also required to have air
economizer, indicate humidifier is adiabatic (direct evaporative or fog atomization), or
exception taken
Additional Efficiency Package Option, More Efficient HVAC Equipment & Fan Performance -
Must comply with all 3 provisions to be eligible
N/A
C406.2.1
C403.2.3
HVAC system selection
To comply with additional efficiency package option, calculate the percentage of heating and
cooling equipment in the project (based on output capacity) that do not have a corresponding
WSEC listed efficiency; shall be less than 10% to comply
N/A
C406.2.2
C403.2.3
Minimum equipment
efficiency
To comply with additional efficiency package option, indicate that all listed heating and cooling
equipment have a rated efficiency that exceeds WSEC listed efficiency by at least 85%
N/A
C406.2.3
C403.2.11.3
Minimum fan efficiency
To comply with additional efficiency package option, indicate rated FEG of stand alone fans is >_
71; indicate these fans are sized so the fan efficiency at design conditions is within ' 0% of the
maximum total or static efficiency
HVAC System Controls
Yes
C403.2.4.1
Thermostatic controls
(thermostats and
humidistats)
Indicate locations of thermostatic and humidity control devices and the zones they serve on
plans, including perimeter system zones
Where adjacent (neighboring) zones are controlled by separate thermostats (including
perimeter systems used to offset heat gain or loss), and are connected by permanent
openings > 10% of either zone sf area, indicate controls configured to prevent adjacent zones
from operating in conflicting modes (one in heat, other in cool); applies to adjacent perimeter
zones, adjacent nonperimeter zones, and adjacent perimeter and nonperimeter zones
M200
If applying Exception 2 to nonperimeter zones adjacent to perimeter zones, indicate that
setpoints and deadband settings in these zones are coordinated so cooling in a nonperimeter
zone does not occur until the temperature in that zone is 5°F higher than the adjacent
perimeter zone temperature in heating
C403.2.4.1.1
Heat pump supplementary
heat
Indicate staged heating operation with compression as the first stage of heating and
supplemental heating controlled with outdoor lock -out temperature set to 40°F or less
Yes
C403.2.4.1.2
Deadband
Indicate zone thermostatic controls configured with 5°F minimum deadband for systems that
control both heating and cooling
M200
Yes
C403.2.4.1.3
Setpoint overlap restriction
(thermostats)
If separate heating and cooling systems with separate thermostatic control devices are used to
serve a zone, indicate locations of both thermostatic control devices and the zone they serve
on plans
M200
Indicate a limit switch, mechanical stop or DDC control with programming to prevent
simultaneous heating and cooling
Yes
C403.2.4.2
C403.2.4.2.1
C403.2.4.2.2
Automatic setback and
shutdown
Indicate zone thermostatic controls configured with required automatic setback and manual
override functions, setback temperatures, and control method (automatic time clock or
programmable controls); note exceptions taken
M200
Yes
C403.2.4.2.3
Automatic (optimum) start
Indicate system controls that adjust equipment start time required to bring each area served up
to design temperature just prior to scheduled occupancy
M200
Yes
C403.2.4.3
Outdoor supply air dampers
Indicate automatic controls configured to close OSA damper during unoccupied equipment
operation; not including economizer cooling, night flush or IMC required OSA / exhaust
M200
N/A
C403.2.4.3
Stairway and shaft vent
dampers
Indicate method of activation of stairway and shaft vent dampers (fire alarm or interruption of
power)
N/A
C403.2.4.4
Zone isolation controls
For systems serving areas > 25,000 sf or spanning more than one floor, that include areas that
are expected to be occupied non -simultaneously; indicate controls that allow for independent
space conditioning of isolation zones; or exception taken
N/A
C403.2.12
Heating outside a building
Indicate occupancy sensing or timer switch controls configured to automatically shut off
heating system when area served is unoccupied
N/A
C403.2.4.5
Snow melt systems
Indicate automatic controls configured to shut off system when pavement temperature
exceeds 50°F and no precipitation is falling, and when outdoor air temperature exceeds 40°F
N/A
C403.2.4.6
Freeze protection system
controls
Indicate automatic controls to shut off system when outdoor temperature exceeds 40°F, or
conditions protect fluid from freezing
N/A
C403.2.4.9
Group R1 hotel / motel
guest rooms
For hotels and motels with over 50 guest rooms, indicate automatic controls serving guest
rooms that are capable of setback (heating) and set-up (cooling) of temperature setpoint by at
least 5°F; indicate control method - activated by room entry or occupancy sensor
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 3 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Revised January 2017
Project Title: Juba Restaurant & Cafe
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
N/A
C403.2.4.10
C403.2.4.11
Group R2 / R3 dwelling
units, Group R2 sleeping
units
For primary space conditioning system, indicate 5-2 programmable thermostats capable of two
setback periods per day; for all thermostats indicate purpose (heating only, cooling only, or
both), required temperature range and at minimum a 10°F deadband; or exception taken
Yes
C403.2.6
C403.2.11.4
Ventilation
Indicate method of ventilation air delivery (natural or mechanical) for each zone
If mechanically delivered, indicate that systems are configured to provide not more than 150%
of, but at least the minimum required volume of outdoor air to each zone per IMC, ASHRAE
62.1 or other applicable code (WAC, OSHA, etc); or exception taken
M200
If delivered via natural ventilation, identify required elements per IMC including minimum
openable area to the outdoors or qualifying adjoining spaces
N/A
C403.2.6.2
Demand controlled
ventilation
Identify spaces > 500 sf with occupant load > 25 people/1,000 sf per IMC; for each space
indicate whether it is served by an HVAC system with total design OSA > 3,000 cfm, and / or
the system has airside economizer or automatic modulating OSA damper; indicate OSA
controls are configured to provide demand controlled ventilation or provide supporting
documentation for applied exception
N/A
C403.2.6.3
Occupancy sensors
For gyms, classrooms, auditoriums and conference rooms > 500 sf, indicate occupancy -based
OSA control when space is unoccupied and method (closes OSA damper or shuts -off
equipment); or alternate means provided to automatically reduce OSA when space is partially
occupied
N/A
C403.2.6.4
C403.2.6.4.1
Enclosed loading dock
ventilation
For enclosed loading docks, indicate ventilation / exhaust system method of activation (gas
detection system for CO and NO2, or occupancy sensors), and control method (staged or
modulating)
N/A
0403.2.6.4
C403.2.6.4.2
Enclosed parking garage
ventilation
For enclosed parking garages, indicate ventilation / exhaust system activated by gas detection
system for CO and NO2, and control method (staged or modulating); or exception taken
N/A
C403.2.7.1
Kitchen exhaust hoods
Provide calculations that show a balanced accounting of total kitchen exhaust (include all
hoods) with % of: supply air, transfer air from adjacent spaces, and make-up air; if applicable,
indicate that direct make-up air to each hood does not exceed 10% of hood exhaust
For kitchens with total hood exhaust exceeding 2,000 cfm, indicate exhaust air rate per Table
C403.2.7.1 and compliance method (DCV, energy recovery, or transfer air that would
otherwise be exhausted)
WA
0403.2.7.2
Laboratory exhaust systems
Refer to Systems Requiring Energy Recovery for requirements
N/A
C403.2.13
Variable flow capacity -
HVAC system fans
For HVAC fan motors >_ 7.5 hp, indicate method of variable flow control (VSD, or equivalent
control method that reduces design air volume by 50% at 1/3 static design pressure.); note
exception taken
N/A
C403.3.1
DX air handler variable
cooling control
(Under Integrated
Economizer)
For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, indicate number of
cooling stages provided and method (multiple compressors and / or variable speed
compressors); indicate minimum displacement (capacity reduction) as % of full load
Indicate control method (cooling capacity controlled in response to space temperature, space
temperature controlled by modulating supply airflow, or both)
N/A
C403.2.11.5
Fan airflow control
For DX air handling units with cooling capacity >_ 65,000 Btu/h and evaporative and chilled
water air handling units with fan >_ 0.25 hp, indicate whether system is single zone or multiple
zone and related control method (cooling capacity controlled in response to space
temperature, space temperature is controlled by modulating supply airflow, or both)
For mechanical cooling systems (includes DX and chilled water coils) that control cooling
capacity in response to space temperature - Provide a minimum of two stages of fan control;
indicate minimum fan speed is <_ 66% of full speed drawing 5 40% of full speed fan power
during periods of low cooling or ventilation only
For other mechanical cooling systems (includes DX and chilled water coils) that control space
temperature by modulating airflow (in lieu of, or in addition to, controlling capacity in response
to space temperature) - Provide fan controls for modulating supply airflow; indicate minimum
fan speed is <_ 50% of full speed drawing <_ 30% of full speed fan power during periods of low
cooling or ventilation only; or exception taken
N/A
C403.2.4.12
DDC system capabilities
Provide central and zone level DDC controls as required based on system application,
capacity or size thresholds and other qualification per Table C403.2.4.12.1
Identify all DDC system input / output control points; indicate capability for trending and
graphical display
Ducting Systems
Yes
C403.2.8.1
C403.2.8.3
Duct construction
Indicate on plans that all ductwork is constructed and sealed per IMC
M200
For OSA ductwork, also indicate on plans that ductwork meets air leakage requirements per
C402.5 and vapor retarder requirements per the IBC
N/A
0403.2.8.3
Duct pressure classifications
Identify location of low, medium and high pressure ductwork on plans
N/A
C403.2.8.3.3
High pressure duct leakage
test
Indicate high pressure duct leakage testing requirements on plans; provide test results to
jurisdiction when completed
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 4 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial
,. _ _ _ - _ .._ _. _. _ _._..- -...� .-.....
Project Title: Juba Restaurant & Cafe
uIcy Iacu 'January cv 11
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code ProvisionInformation
Required - Must be in permit documents
Location in
Documents
Building Department
Notes
Yes
C403.2.8.1
C403.2.8.2
Duct insulation
For supply and return ductwork located in unconditioned space or outdoors, indicate R -value of
insulation on ductwork on plans; identify climate zone; note exceptions taken
For supply ductwork located in conditioned space, identify if design supply temperature is <
55°F or> 105°F and indicate IR -value of insulation on this ductwork on plans; note exception
taken
M200
For OSA ductwork, shafts and plenums, indicate R -value of insulation on these elements on
plans per Table C402.1.3 for steel -framed walls; note exception taken
Piping Systems
N/A
C403.2.9
Pi in insulation
p g
Indicate design temperature range of fluid conveyed in piping and thickness of insulation (in
inches) on hydronic piping plans; or exception taken
N/A
C403.2.9.1
Piping insulation exposed to
weather
Indicate method of protection of pipe insulation from damage / degradation on hydronic piping
plans
Economizers
Yes
C403.3
Air economizer required
Identify in equipment schedules on plans or in MECH-EQ forms all cooling systems requiring
air economizer controls
M200
Provide MECH-ECONO form indicating systems utilizing air economizer exceptions, including
those with water -side economizer in lieu of air economizer; indicate on plans eligible
exception(s) taken and measures to comply with exception(s)
YesC403.3.1
Integrated economizer
operation - air and water
Indicate air and water -side economizers are configured for partial cooling operation even
where additional mechanical cooling is required to meet the load
M200
Yes
C403.3.2
Economizer heating system
impact - air and water
Verify control method of HVAC systems with economizers does not increase building heating
energy usage during normal operation
M200
YesC403.3.3.1
Air economizer capacity
Indicate modulating OSA and return air dampers are configured to provide up to 10D% OSA
for cooling
M200
Yes
C403.3.1
C403.3.3.2
Integrated air economizer
Verify mechanical cooling controls are interlocked with air economizer controls so the outside
air damper remains in 100% open position when mechanical cooling is also required to meet
the cooling load, until the leaving air temperature is <45°F
M200
For systems with cooling capacity >_ 65,000 Btu/h, verify that control of economizer dampers is
not based only on mixed air temperature; or exception taken
Yes
C403.3.3.3
Air economizer high limit
controls
Indicate high limit shut-off control method and required high limit per Table C403.3.3.3
M200
N/A
C403.3.4.1
Water economizer capacity
For eligible systems where water -side economizer may be provided in lieu of air economizer,
indicate system is capable of 100% design cooling capacity at 50°F db / 45°F wb OSA
temperatures
N/A
C403.3.4.2
Water economizer
maximum pressure drop
Indicate pressure drop across precooling coils and heat exchangers in water economizer
system do not exceed pressure drop limit
N/A
C403.3.1
DX air handling equipment
control
For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, refer to HVAC
System Controls for requirements
N/A
C403.2.4.7
DX equipment economizer
fault detection and
diagnostics
For DX air handlers with economizer and cooling capacity >_ 54,000 Btu/h, provide a fault
detection and diagnostics (FDD) system to monitor economizer system operation arid report
faults
Systems Requiring Energy Recovery
N/A
C403.5.1
Energy recovery (ER) -
ventilation / exhaust
systems
For systems with design OSA > 5,000 cfm, or design supply air cfm and % OSA exceeding the
values in Tables C403.5.1(1) or (2), indicate exhaust air ER method; or exception taken with
supporting calculations
For rooms served by multiple systems with aggregate design OSA > 5,000 cfm, or aggregate
design supply air cfm and % OSA exceeding the values in Tables C403.5.1(1) or (2), indicate
exhaust air ER method; or exception taken with supporting calculations
Indicate ER rated effectiveness that increases OSA enthalpy by >_ 50% based on delta
between OSA and return air enthalpies at design conditions
N/A
C403.2.7.2
Laboratory exhaust systems
(energy recovery)
For buildings with total lab exhaust > 5,000 cfm, indicate method of energy recovery used to
pre -condition laboratory make-up air; ER effectiveness (min 25°F); or alternative method per
exception (VAV exhaust, semi -conditioned makeup, or CERM calculation)
N/A
C404.10.4
(under
C404.11)
Pools and permanent spas
exhaust systems
(energy recovery)
For buildings with pools or spas with water surface area > 200 sf, indicate exhaust ar ER
method and use of waste heat (preheat ventilation air, pool water or service hot water); or
exception taken
Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air
temperature at design conditions by >_ 36°F
N/A
C403.5.2
Energy recovery -
For buildings with on-site steam heating systems, indicate condensate water ER
steam condensate systems
For buildings that use off-site generated steam where condensate is not returned to the
source, indicate on-site condensate water ER
2015 Washington State Energy Code Cornpliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 5 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildi
_ _— .__ _.._ .-.....
Project Title: Juba Restaurant & Cafe
nev,aeu OW luaJy cu 1 I
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code ProvisionInformation
Required -Must be in permit documents
Location in
Documents
Building Department
Notes
N/A
C403.5.3
Energy recovery -
For buildings with food service, meat or deli departments that have >_ 500,000 Btu/h of remote
refrigeration capacity for coolers / freezers, indicate condenser ER and use of captured energy
(service water heating, space heating, or dehumidification reheating)
cooler / freezer condensers
For buildings with >_ 40,000 sf conditioned floor area and with >_ 1,000,000 Btu/h of remote
refrigeration capacity for coolers / freezers, indicate condenser ER and use of captured energy
for service water heating and also for space heating, or dehumidification reheating
N/A
0403.5.4
Energy recovery -
condenser systems
For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and
design service hot water load > 250,000 Btu/h, indicate condenser ER to pre -heat service
water; or exception taken. Provide calculations showing the amount of recovered heat that is
utilized (60% of peak heat rejection load or pre -heat service water to 85°F).
Hydronic System Controls
N/A
C403.2.13
0403.4.2.7
Variable flow control -
hydronic system pumps
For hydronic system pump motors >_ 7.5 hp, indicate method of variable flow control (VSD or
equivalent method that requires >_30% design wattage at 50% design fluid flow); note
exception taken
Identify whether hydronic coils have DDC controls and associated manner of pump speed
control (differential pressure, zone hydronic demand, etc)
For boilers that provide building heating, indicate controls that provide heating water
temperature setback based on outdoor temperature
N/A
0403.2.5
0403.4.2.4
Hydronic system setback
and part load controls
For heating and chilled water systems >_ 300,000 Btu/h, indicate systems are configured to
automatically reset supply water temperature based upon demand; or exception taken.
If system pump motor hp >_ 3 hp, also indicate controls automatically reduce flow by? 50%.
For chilled water systems (>_ 300,000 Btu/h, pump motor hp >_ 3 hp) that serve water-cooled
unitary air conditioners, indicate VSD or staged pumps in chilled water system and Beat
rejection loop that reduce pump flow so that one control valve is nearly wide open, or to
maintain a minimum differential pressure; or exception taken
N/A
0403.4.2
Boiler sequencing
Indicate automatic controls that sequence operation of multiple boilers
N/A0403.4.6
Hot gas bypass limitation
For cooling equipment with hot gas bypass, provide either multiple step unloading or
continuous capacity modulation; indicate bypass capacity per Table 0403.4.6
N/A
C403.4.2.2
Two -pipe changeover
systems
Indicate changeover deadband (min 15°F), heating / cooling mode scheduling and changeover
temperature range (limit 30°F)
N/A
0403.4.2.6
Chiller / boiler plant pump
isolation
Indicate controls are configured to automatically reduce overall plant flow and shut-off flow
through individual chillers and boilers when not in use
N/A
0403.2.13.1.1
0403.4.3.1.1
Heat rejection equipment
variable flow control
For cooling towers with fan motors > 7.5 hp, indicate VSD and method to adjust fan speed
(adjusted based on leaving fluid temperature or condenser temperature / pressure of heat
rejection device)
0403.4.3.1,2
For multiple -cell heat rejection equipment with VSD, indicate controls that ramp all fans in
unison
N/A
0403.4.3.3
Heat rejection equipment -
cooling tower flow turndown
Indicate open -circuit cooling towers with multiple pumps or VSD control are designed so all
cells can be ruri in parallel
N/A
0403.4.2.3.1
Water loop heat pump -
deadband
Indicate capability of central equipment to provide minimum 20°F water supply temperature
deadband between heat rejection and heat addition modes; or exception taken
N/A
0403.4.2.3.2.1
Water loop heat pump -—
heat rejection equipment,
Zone 4
Indicate type of cooling tower (open- or closed-circuit) in equipment schedule; indicate method
used to limit system heat loss when heat rejection is not needed
N/A
0403.4.2.3.2.2
Water loop heat pump -
heat rejection equipment,
Zone 5
For open- or closed-circuit cooling towers, provide a heat exchanger that separates the cooling
tower and heat pump loop
N/A
0403.4.2.3.3
Water loop heat pump -
isolation valves
For hydronic heat pump systems with total system power > 10 hp, indicate 2 -way isolation
valves on each heat pump and variable flow system control
Dedicated Outdoor Air Systems (DOAS) - Optional through 6/30/16, Prescriptive 7/1/2016
N/A
C403.6
0403.6.3
Dedicated outdoor air
systems
For buildings with office, retail, education, library and fire station spaces, identify these spaces
on plans; indicate that ventilation air in each occupied space is provided via a DOAS system;
or document compliance with 0403.6.3 Impracticality; or exception taken (buildings complying
with 0402.4.1.4 or C406.6 may not utilize exceptions)
N/A
C403.6.1
Energy recovery ventilation
with DOAS
For all DOAS systems, indicate exhaust air ER method; or exception taken with supporting
calculations. Indicate ER rated effectiveness that increases OSA enthalpy by >_ 50% based on
delta between OSA and return air enthalpies at design conditions.
N/A
0403.6.2
Heating / cooling system
controls with DOAS
Indicate equipment associated with the delivery of zone level heating and cooling (fans,
hydronic pumps, primary air dampers, etc) are configured to shut off, and central equipment is
configured to turn down, when there is no call for heating or cooling in the zone they serve
If applying Exception to heating / cooling fans used for air mixing in the space during deadband
periods, include fan watts per cfm in equipment schedule
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 6 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 &193 over 3 stories and all R1
Revised January 2017
Project Title: Juba Restaurant & Cafe
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
N/A
0402.4.1.4
C403.6
Increased prescriptive
maximum vertical
fenestration area with DOAS
Indicate that all occupied, conditioned spaces are served by a DOAS per C403.6
Additional Efficiency Package Option, Dedicated Outside Air Systems (DOAS)
N/A
0406.6
Building provided with
DOAS
To comply with additional efficiency package option, indicate that 90% or more of al occupied,
conditioned spaces are served by a DOAS per C403.6
Multiple Zone Air Systems
N/A
C403.4.4
Air systems serving multiple
zones
Identify supply air systems serving multiple zones and the zones they serve on plans; indicate
whether system is VAV and method of primary air control; or provide supporting
documentation for applied exception to VAV
N/A
C403.4.4
VAV systems serving
multiple zones
Provide equipment schedules on plans or MECH-EQ form that list all VAV air terminals and
types
For each air terminal include: maximum airflow rates for primary supply air during zone peak
heating and zone peak cooling; maximum airflow during reheating, recooling or mixing;
minimum airflow rate to maintain required ventilation, and the basis for these values if IMC or
ASHRAE 62.1 multiple zone equation is basis for minimum flow rates, provide calculation on
plans
N/A
0403.4.4.1
Single duct VAV terminal
units
Indicate single duct terminal units are configured to reduce primary supply air before reheating
or recooling
N/A
0403.4.4.2
Dual duct systems - terminal
units
For systems with separate warm air and cool air ducts, indicate terminal units are configured to
reduce the flow from one duct to minimum before mixing with air from the other duct
N/A
0403.4.1.1
C403.4.1.2
VAV system static
pressure sensors -
sensors and DDC set points
Indicate locations of duct static pressure sensors on plans; include at least one sensor per
major duct branch; verify controller setpoint pressure at each sensor is 5 1.2 inch wig.
For systems with zone level DDC, indicate controls are configured to monitor zone damper
positions and reset static pressure setpoint based on the zone requiring most pressure; include
control logic that automatically detects and generates an alarm if any zone excessively drives
reset logic, and allows building operators to exclude zones from reset logic
N/A
0403.4.4.3
Multiple -zone VAV system
ventilation optimization
controls
For systems with zone level DDC controls, indicate controls are configured to automatically
reduce outdoor airflow in response to changes in system ventilation efficiency; or exception
taken
N/A
Multiple Zone
0403.4.4.4
VAV system supply air reset
Indicate controls automatically reset supply air temperature in response to building loads or
outdoor air temperature; or exception taken
HVAC Systems, High Efficiency VAV - Required for systems utilizing C403.6 DOAS Exception 2, must comply with all 16 provisions
N/A
C403.7,
Item 1
Air economizer
Indicate system is configured for 100% air economizer operation and complies with all related
economizer requirements per C403.3 (without economizer exceptions)
N/A
C403.7,
Item 2
Direct digital controls (DDC)
Provide DDC controls for all components of system; identify all DDC system input / output
control points; indicate capability for trending and graphical display
N/A
C403.7,
Item 3
Outdoor airflow
measurement and reduction
For systems with minimum OSA > 2,500 cfm, indicate outdoor airflow monitoring station that
measures OSA intake under all load conditions; indicate control sequence that increases or
reduces system OSA cfm based on VAV terminal feedback of ventilation efficiency (per
0403.4.4.3 without exceptions) or DCV (per 0403.2.6.2)
N/A
C403.7,
Item 4
'
Supply airflow measurement
For systems with minimum OSA > 2,500 cfm, indicate supply airflow monitoring station capable
of measuring supply IY air delivered to VAV terminals under all load conditions
N/A
0403.7,
Item 5
Zone isolation and
maximum area served
Verify maximum area served by a single HEVAV system is 5_ 50,000 sf, or one entire floor,
whichever is greater; in addition if a system serves > 25,000 sf, that includes areas that are
expected to be occupied non -simultaneously, indicate zone isolation controls per 0403.2.4.4
N/A
C403.7,
Item 6
Interior / exterior zone
design supply air
temperature
Verify that VAV terminals serving interior cooling driven loads are sized per design supply air
temperature that is 5°F higher than VAV terminals serving exterior zones
N/A
0403.7,
Item 7
Maximum air terminal inlet
velocity
Identify air terminals with minimum primary airflow setpoints > 50% of maximum setpoint in
equipment schedule or MECH-EQ form; indicate air terminal inlet velocity does not exceed 900
fpm
N/A
C403.7,
Item 8
Sequence of operation
Indicate DDC system sequences of operation are designed and configured per ASHRAE GPC
36
N/A
C403.7,
Item 9
Maximum allowable system
brake horsepower
Verify fan system bhp is 5 90% of the bhp limit per Option 2 equation in Table 0403.2.11.1(1),
provide MECH-FANSYS form for each system
N/A
C403.7,
Item 10
Fan -powered terminal unit
motor and control
Indicate all series and parallel terminal fans have electronically commutated motors; indicate
DDC control system is configured to vary air terminal fan speed as a function of the bad;
indicate fan speed during periods of low heating, low cooling, or ventilation only is 5 66% of
peak design air flow or provide supporting documentation for applied exception
2015 Washington State Energy Code Cornpliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 7 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all 111
Revised January 2017
Project Title: Juba Restaurant & Cafe
Date 8/16/2018
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no,na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
N/A
C403.7,
Item 11
Application of single duct
and fan -powered terminal
units
Indicate VAV terminal types on plans; verify fan -powered terminal units only serve perimeter
zones with envelope loads; verify all other zones are served by single duct terminal units
N/A
C403.7,
Item 12
Fan -powered terminal unit
primary air reset
Indicate DDC controls are configured to automatically reset the primary supply air dillsetpoint
of all fan -powered terminal units to the minimum required to maintain ventilation during
occupied heating or deadband, based upon the VAV air handling unit OSA ventilation fraction
N/A
C403.7,
Item 13
High occupancy space
controls
For spaces > 150 sf with occupant density >_ 25 people / 1000 sf, indicate space is served by a
dedicated terminal unit with DCV control that resets terminal unit ventilation setpoint; also
indicate occupancy sensor control that automatically reduces minimum ventilation to zero and
sets back room heating and cooling setpoints by 5°F
N/A
C403.7,
Item 14
Dedicated HVAC systems
For server, electronic equipment, telecom or similar spaces with cooling loads > 5 W/sf,
indicate spaces are served by independent HVAC systems that are separate from HPVAV
systems serving rest of building; indicate dedicated HVAC systems have air economizer
controls or energy recovery per C403.3 Exception 9
N/A
C403.7,
Item 15
Central plant efficiency
Indicate whether systems are served by a high efficiency heating water plant, or a high
efficiency chilled water plant
If complying via high efficiency heating water plant: Indicate all VAV terminals have hydronic
heating coils served by heating water system with either gas-fired boiler(s) with thermal
efficiency > 90%, air -to -water heat pumps, or heat recovery chillers
If complying via high efficiency chilled water plant: Indicate all VAV air handlers have cooling
coils served by chillers with rated IPLV efficiency that exceeds WSEC listed IPLV by at least
25% per Table C403.2.3(7) (note water-cooled IPLV is max, all others are min); indicate
smallest chiller or compressor in plant is < 20% of total plant capacity, or provide thermal
storage sized for < 20% of total plant capacity
N/A
C403.7,
Item 16
Fault detection and
diagnostics
Indicate DDC system includes a fault detection and diagnostics (FDD) system configured to
monitor operation and provide fault reporting of required parameters for all VAV air handlers
and VAV air terminal units in the HPVAV system
HVAC Equipment Energy Use Metering
N/A
Documentation
C409.3.1
HVAC equipment energy
use metering
For new buildings > 50,000 sf and building additions > 25,000 sf, verify energy use metering of
all equipment used to provide space heating and cooling, dehumidification and ventilation will
be provided per C409; indicate equipment eligible for exception
and System Specific Requirement To Support Commissioning
Yes
C408.2
Scope of mechanical
systems commissioning
Indicate that all mechanical systems, equipment, and controls for which the WSEC requires
control functions and / or configuration to perform specific functions are required to be
commissioned,:
M200
For buildings with >_ 240,000 Btu/h total output cooling capacity or >_ 300,000 Btu/h total output
heating capacity, indicate that all mechanical systems regardless of individual capacity are
required to be commissioned; or provide building heating / cooling capacity calculation
demonstrating eligibility for exception
C403.2.10
C408.1.1
C408.1.2
C408.1.4.2
C103.6
Commissioning
requirements in construction
documents
Indicate in plans and specifications that Cx per C408 is required for all applicable mechanical
systems;
Yes
Include general summary with at a minimum of Items 1 thru 4 of the Cx plan per C408.1.2
including: narrative description of activities, responsibilities of the Cx team, schedule of
activities including verification of project close out documentation per C103.6, and conflict of
interest plan (if required);
M200
Include in general summary that a Cx project report or Compliance Checklist (Figure
C408.1.4.2) shall be completed by the Certified Cx Professional and provided to the owner
prior to the final mechanical inspection.
Yes
C408.2.2
Air system and hydronic
system balancing
Indicate in plans that air and fluid flow rates shall be tested and balanced within the tolerances
defined in the specifications; indicate systems shall be balanced in a manner to first minimize
throttling losses, then adjusted to meet design flow conditions
M200
Yes
C408.2.2.1
Air system balancing
devices
Indicate devices that provide the capability to balance all supply air outlets, zone terminals and
air handling equipment requiring system balancing
M200
N/A
C408.2.2.2
Hydronic system balancing
devices
Indicate devices that provide the capability to isolate, balance and measure flow across all
hydronic equipment requiring system balancing including heating and cooling coils and pumps
Yes
C408.2.3
Functional performance
testing criteria
Identify in plans and specifications the intended operation of all equipment and controls during
all modes of operation, including interfacing between new and existing -to -remain systems
M200
Project Close Out Documentation
Yes
C103.6
Documentation and project
close out submittal
requirements
Indicate in plans that project close out documentation and training of building operations
personnel is required for all mechanical components, equipment and systems governed by this
code; indicate close out documentation shall include: record documents, O&M manuals,
applicable WSEC compliance forms and calculations
M200
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1
Mechanical Fan System Power Allowance
MECH-FANSYS-SUM
2015 Washington State Energy Code Compliance Forms for Commercial Buildings i
Project Title: Juba Restaurant & Cafe
Date 8/16/2018
For Building Dept. Use
HVAC Air Distribution System Schedule
List all HVAC systems that have the capability to provide heating and/or cooling to the spaces they serve.
System or
Primary Supply
Fan ID
Speed Control
(Note 1)
Description
(Note 2)
System Total
Nameplate HP
(Note 3)
Fan Power
Calculation
Required
(Note 4)
RTU -1
CV
Rooftop packaged heating/cooling unit
2
No
Note 1 - Constant Volume (CV), Variable Air Volume (VAV), or Hospital/Lab CV system that qualifies for VAV budget per C403.2.11.1 Exception 1.
Single zone VAV systems shall comply as CV.
Note 2 - Describe system type and list all fans (or groups of fans) associated with the delivery and removal of conditioned air by the system. Include
all supply, return/relief, exhaust and exhaust hoods (>1 hp), make-up air, dedicated outside air (DOAS), booster fans, and series fan -powered
terminals. VAV parallel fan -powered terminals and economizer relief fans do not need to be included if the fans do not operate at peak
conditions.
Note 3 - Enter the total nameplate hp of all fans associated with the delivery and removal of conditioned air by the system.
Note 4 - This form automatically identifies whether a MECH-FANSYS form is required to demonstrate compliance with the fan power allowance (Yes),
or this information is not required because the system has a combined total nameplate motor hp that is 5 hp or less (No)
MECH-FANSYS Forms
A MECH-FANSYS form shall be provided for each system with total nameplate hp greater than 5 hp. Select (Add Fan
System Form) to generate an additional form. Added forms can be deleted with button in cell E32 of the added form.
•
C T
ENGINEERING
Client:
Design Criteria:
INC
#18147
Structural Construction Documents For:
JUBA CAFE RTU
AT
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512(V)
(206) 285-0618(F)
bmccann@ctengineeri ng. com
14227 Tukwila International Blvd.
Tukwila, WA 98168
08/16/2018
Evergreen Refrigeration & HVAC
727 S. Kenyon St.
Seattle, WA 98108
IBC 2015
Wind: Wind Speed = 85 mph, Kzt = 1.00
Seismic: Sds = .9
Roof Snow Load = 25 psf
REVIEWED FOR
CODE COMPLIANCE
APPROVED
AUG 2 8 2018
City of Tukwila
BUILDING DIVISION
_ RECEIVED
CITY OFI!tiMI SLA
AUG 17 2018
P !RE T 0E6 d ER
MIS-0101
CT
ENGINEERING'
I N C.
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
Aft a8ehtrt
W ¢_ filo -m4
6 Ley
(bio TD.)
z Cir? FI c.E-
Z CSL P Pedke-Avt
ti
Z'CLAP . // /
& &v,
bee..
*5200a ce
?/2"0,C.
ik P9-1211-0 es-m-tz
afr aVir 7.f. 6
(()&mss
e//L6 -Govea"
fes'.
•
Gsr4►2
GLI
A
leir6/2"efi (41
Al
1 <464TX4160,_
(_•14. A•71-4 404,016-,e e .6.1*5,0
6-647- 4.4ver6'
CT
ENGINEERING
Client:
Design Criteria:
INC
#18147
Structural Calculations For:
JUBA CAFE RTU
AT
14227 Tukwila International Blvd.
Tukwila, WA 98168
08/16/2018
Evergreen Refrigeration & HVAC
727 S. Kenyon St.
Seattle, WA 98108
IBC 2015
Wind: Wind Speed = 85 mph, Kzt = 1.00
Seismic: Sds = .9
Roof Snow Load = 25 psf
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512(V)
(206) 285-0618(F)
bmccann@ctengineering.com
REVIEWED FOR
CODE COMPLIANCE
APPROVED
AUG 2 8 2018
City of Tukwila
BUILDING DIVISION
RECROVED
CiTY OF i f litt5 LA
AUG 17 2018
P2REFAT CES! a ER
M19-ol0l
CT
ENGINEERING
1 N 0.
GRAVITY LOAD CONSIDERATIONS:
GRAVITY LOADS OK BY INSPECTION. EXISTING UNIT IS ASSUMED SUPPORTED JUST OFF A
PRIMARY SUPPORTING BEAM AND IS EXPECTED TO WEIGH AS MUCH AS THE NEW UNVT PLUS
THE NEW CURB ADAPTER. CT ENGINEERING HAS VISITED THE SITE TO OBSERVE THE EXISTING
FRAMING CONDITIONS NEAR THE RTU.
WIND LOADS - EQUIPMENT (BLDG H < 60')
ASCE 7-10 29.5-1
V 110.0 mph
Kd 0.85 - Table 26.6-1
Kzt 1.0 -
Kz 0.62 - Table 29.3-1- Exp B
qh 16.3 Ib/ft^2
GCrh 1.9 -
GCry 1.5 -
Unit dimensions - weight - horizontal and vertical
RTU
RTU -1
RTU -2
RTU -3
RTU -4
.r.'-cted areas inches. sounds: inches^2
L B he H W -unit W -curb
Af1
Af2
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
Af3 Af4 Ar
101 2/7 60 1/9 28 46 8/9 991 127 4751 2819 2836 1683 6088
CT
ENGINEERING
1 N C.
WIND LOADS - EQUIPMENT (BLDG H < 60')
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
Moments about x -x Axsis El:
Wind forces - Overturning moment (Ib -in) - Resisting Moment (Ib -in) ASCE 10 2.4.1 #7 .6D+.6W - Uplift force (Ib)
RTU Fhl*(0.6) Fv*(0.6) OM RM Uplift - ASD
RTU -1 614 621 33064 17868 253
RTU -2
RTU -3
RTU -4
Moments about y -y Axsis El:
Wind forces - Overturning moment (Ib -in) - Resisting Moment (Ib -in) ASCE 10 2.4.1 #7 .6D+.6W - Uplift force (Ib)
RTU Fh2*(0.6) Fv*(0.6) OM RM Uplift - ASD
RTU -1 364 621 40004 30116 98
RTU -2
RTU -3
RTU -4
Moments about x -x Axsis ( E2:
Wind forces - Overturning moment (Ib -in) - Resisting Moment (Ib -in) ASCE 10 2.4.1 #7 .6D+.6W - Uplift force (Ib)
RTU Fh3*(0.6) Fv*(0.6)
OM RM Uplift - ASD
RTU -1 367 621 55387 20158 586 GOVERNING UPLIFT FORCE. PROVIDE Z CLIPS
RTU -2 AT UNIT TO CURB ADAPTER, #10@ 12" O.C.
CURB ADAPTER TO EXISTING CURB AND LSTA
RTU -3 12 STRAPS AT EXISTING CURB CORNERS TO
RTU -4 EXISTING SUPPORTING FRAMING.
Moments about y -y Axsis Cud E2:
Wind forces - Overturning moment (Ib -in) - Resisting Moment (Ib -in) ASCE 10 2.4.1 #7 .6D+.6W - Uplift force (Ib)
RTU Fh4*(0.6) Fv*(0.6) OM RM Uplift - ASD
RTU -1 217 621 53248 33976 190
RTU -2
RTU -3
RTU -4
Lennox Industries Inc. - Product Submittal
SUBMITTED TO CT ENGINEERING.
Table of Contents
System ID
Qty
Model
Description
7.5T
1
KGA092S4M
PKGGE/7.5 T/13 OKB/230-3
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 1 of 7
Last Changed: DYE, KATE.LYN
Prepared On: 2018-07-27
Phone: 602-281-7186
Lennox Industries Inc. - Product Submittal
System ID: 7.5T
Package Model: KGA092S4M
Description: PKGGE/7.5T/130K13/230-3
HEATING PERFORMANCE
Unit Type
H/E Lowlnput
WE LowOutput
WE Highlnput
H/E HighOutput
System HeatOutput
Packaged Gas
Electric
84500 (Btuh)
67500 (Btuh)
130000 (Btuh)
104000 (Btuh)
104000 (Btuh)
Gas Supply Connection
H/E Heat Rise
AFUE/ ThermalEff
Number of Heating Stages
Gas Supply Pressure
0.75 (in.)
32.1 (°F)
80
2
7 (in.WC)
COOLING PERFORMANCE
Refrigerant
ARI EER
ARI JEER
ARI Total Power
ARI GrossTotalCool
ARI NetTotalCool
Coil GrossTotalCool
Unit NetTotalCool
Coil GrossSensCool
Unit NetSensCool
R -410A
11.0
13.0
7800 (W)
88200 (Btuh)
86000 (Btuh)
92100 (Btuh)
87493 (Btuh)
65852 (Btuh)
61244 (Btuh)
Number Compressors
Number of Cooling Stages
Condensate Drain Size
Cooling OutdoorDB
Cooling OutdoorWB
Cooling CondenserDB
Cooling MixedDB
Cooling MixedWB
Coil DischargeDB
Coil DischargeWB
Unit DischargeDB
Unit DischargeWB
Coil MoistureRemoval
System MoistRemoval
2
2
1.00 (in.)
95.0 (°F)
90.0 (°F)
90.0 (°F)
80.0 (°F)
67.0 (°F)
58.8 (°F)
56.8 (°F)
60.2 (°F)
57.4 (°F)
24.7 (lb/hr)
24.7 (lb/hr)
SUPPLY FAN PERFORMANCE
Supply AirFlow
ExtStaticPress Supply
SupplyFan Req'dPower
SupplyFan NomPower
Supply Fan Type
SupplyDriveReq'd RPM
SupplyDrive Min RPM
SupplyDrive Max RPM
3000 (cfm)
0.80 (in.WC)
1.45 (hp)
2.00 (hp)
MSAV Belt Drive
861 (rpm)
590 (rpm)
890 (rpm)
TotalStaticPress
Wet Coil Static Press
Gas H/E Static Press
Economizer Static Press
Air Filter Qty
Air Filter Length
Air Filter Width
Air Filter Thickness
1.14 (in.WC)
0.10 (in.WC)
0.11 (in.WC)
0.13 (in.WC)
4
20.0 (in.)
25.0 (in.)
2.0 (in.)
ELECTRICAL
Voltage
Frequency
System MCA
System MOCP
Compressors RLA
Cooling FLA Total
Unit Oper Range -Nom Voltage
208V 3Ph
60 (Hz)
38.0 (amp)
50 (amp)
26.2 (amp)
38.5 (amp)
+/- 10%
SupplyFan FLA
CondensingUnit FLA
CondenserFan Power
7.5 (amp)
4.8 (amp)
740 (W)
DIMENSIONS
Cabinet Width
Cabinet Length
Cabinet Height
Total Weight
60.1 (in.)
101.3 (in.)
46.9 (in.)
991 (Ib)
Downflow Supply Length
Downflow Supply Width
Downflow Return Length
Downflow Return Width
20.0 (in.)
28.0 (in.)
24.0 (in.)
27.0 (in.)
SOUND
Outdoor Sound Rating
88 (db)
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 2 of 7
Last Changed: DYE, KATELYN
Prepared On: 2018-07-27
Phone: 602-281-7186
Lennox Industries Inc. - Product Submittal
System ID: 7.5T
Package Model: KGA092S4M
Description: PKGGE/7.5T/130KB/230-3
SYSTEM FEATURES
Durable Outdoor Enamel Paint Finish
Scroll Compressor
High Capacity Driers
Separate Compressor and Controls Compartment
Limited compressor warranty of 5 years
Limited warranty on all other components of 1 year
See Limited Warranty Certificate included with unit for details
AGA -CGA Certified
Redundant Comb. Gas Control Valve
Electronic Flame Sensor
Direct Spark Ignition
Limited warranty on Environ Coil System of 3 years
INCLUDED SYSTEM OPTIONS - FACTORY INSTALLED
MULTI -STAGE AIR VOLUME BELT DRIVE
2 IN MERV4 FILTER
INCLUDED SYSTEM OPTIONS - FIELD INSTALLED
10U58 1 KIECON22B-1 HIGH PERF ECONOMIZER
10Z75 1 C1SNSR6OFF1 SINGLE ENTHALPY KIT
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 3 of 7
Last Changed: DYE, KATELYN
Prepared On: 2018-07-27
Phone: 602-281-7186
Lennox Industries Inc. - Product Submittal
System ID: 7.5T
Package Model: KGA092S4M
Description: PKGGE/7.5T/130KB/230-3
DIMENSIONS - INCHES (MM)
Model
No.
CORNER WEIGHTS
CENTER OF GRAVITY
AA
BB
CC
DD
EE
FF
Base
Max.
Base
Max.
Base
Max.
Base
Max.
Base
Max.
Base
Max.
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
in.
mm
in.
mm
in.
mm
in.
mm
092
248
113
292
133
223
101
255
116
243
110
273
124
276
125
320
145
47
1181
46
1156
24.5
622
25.5
648
102
253
115
297
135
228
103
260
118
248
112
278
126
282
128
326
148
47
1181
46
1156
24.5
622
25.5
648
120
263
119
308
140
237
107
269
122
258
117
288
130
293
133
337
153
47
1181
46
1156
24.5
622
25.5
648
150
286
130
331
150
257
117
289
131
280
127
309
140
318
144
362
164
47
1181
46
1156
24.5
622
25.5
648
Base Unit - The unit with NO OPTIONS
Max. Unit - The unit with ALL OPTIONS Installed. (Economizer, etc.)
58-1/8
(1476)
100
60-1/8
(1527)
o 00]
END VIEW
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 4 of 7
46-7/8
(1191)
43 3/8
(1102)
1
1'3.112
(89)
6-1/8 5-518
(156) (143) BOTTOM SUPPLY
/ AIR OPENING
AA
6-1/8
60-1/8 (1527)
BASE
BOTTOM
POWER ENTRY
5-112 (140)0a.
1(.4;
y7 (178) • (168) t
fDD
-i 7(178)
,._ 34-7/8 ,
(886)
•
24
10-3/4
(610) `I (273)
27
(686)
■ 28
20 (711)
(508)
at)
CENTER OF
GRAVITY
BOTTOM RETURN i
AIR OPENING
EE -+
FF
}
BOTTOM
CONDENSATE
101-1/4
(2572)
TOP VIEW
99-1/4
r.
OPTIONAL DISCONNECT (2521)
(FACTORY INSTALLED)
BASE
BB
CC
`1/
1
Lj
CONDENSATE
DRAIN FRONT)
I ®—t-
GAS SUPPLY
/ INLET FLUE
OUTLET
1
II II
II
II
46
(11
t
5-3`6
(137)
18-1/2 (470)
O
'lull
ELECTRIC
INLETS 34-7/8
t- (886) 39-7/8
(1013)
15-1/2
(394)
FORKLIFT SLOTS
(BOTH SIDES) LIFTING HOLES
(FOR RIGGING)
101-1/4
(2572)
SIDE VIEW
15-1/2
(394)
HORIZONTAL
SUPPLY AIR HORIZONTAL
OPENING RETURN AIR
OPENING
00
6-1/8
(156)
CONDENSATE
DRAIN (BACK)
_3) 30
(8008001 (762)
663/8
(1686
5-318
(137)
SIDE VIEW
(Horizontal Openings)
/8
1)
1-5/8
(41)
30
(762)
12-1/8
O J (308)
Last Changed: DYE, KATELYN
Prepared On: 2018-07-27
Phone: 602-281-7186
Lennox Industries Inc. - Product Submittal
System ID: 7.5T
Package Model: KGA092S4M
Description: PKGGE/7.5T/130KB/230-3
ACCESSORY DIMENSIONS - INCHES (MM)
OUTDOOR AIR HOOD DETAIL
21-3/8
OUTDOOR AIR HOOD
(Fumished with Economizer or
Outdoor Air Damper))
EXHAUST AIR HOOD
(Furnished, Field Installed)
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 5 of 7
(543)
_
0
1l>
II!
100 I 1 I I 001
Last Changed: DYE, KATELYN
Prepared On: 2018-07-27
Phone: 602-281-7186
Lennox Industries Inc. - Product Submittal
System ID: 7.5T
Package Model: KGA092S4M
Description: PKGGE/7.5T/I30KB/230-3
UNIT CLEARANCES - INCHES (MM)
tcr
/OPTIONAL
7,/,,
OUTDOOR
AIR HOOD
AIR
B
"Hf"{'p(O /p ,
lc
\_ -
�I
..*.
4, z
///__...
,x
Unit Clearance
A
B
C
D
Top
Clearance
in.
mm
in.
mm
in.
mm
in.
mm
Service Clearance
60
1524
36
914
36
914
60
1524
Unobstructed
Clearance to Combustibles
36
914
1
25
1
25
1
25
Minimum Operation Clearance
36
914
36
914
36
914
36
914
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
Service Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required for dearance to combustible material.
Minimum Operation Clearance - Required clearance for proper unit operation.
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 6 of 7
Last Changed: DYE, KATELYN
Prepared On: 2018-07-27
Phone: 602-281-7186
Lennox Industries Inc. - Product Submittal
MISCELLANEOUS MATERIALS
83W49 CI ACURB4OB YCD075A,090A,B TO B
Project: 3000804563 Juba Cafe
Quote: 4000946815 Juba Cafe
Page 7 of 7
Last Changed: DYE, KATELYN
Prepared On: 2018-07-27
Phone: 602-281-7186
CDI
CUSTOM CURB ADAPTERS
CDI QUOTE #1166764
Date: 07/27/2018
Distributor: Katelyn Dye (LENNOX)
Job Tag: Juba Cafe
Distributor PO:
CURBS
Crystal Distribution, Inc.
17560 Tyler Street NW
Elk River, MN 55330
Phone: 763.391.7790
Toll Free: 1.888.234.7001
Line
Quantity
CDI Part #
Description
Tag
A
1
1-3005-2085
Curb Adapter
Old Model: YCD090C (OLD UNIT ONLY)
New Model: KGA092
Top Brace; Insulated Condenser Panel (where
required); Fully Insulated (1" Duct Liner R Value 3.85)
Thank you for choosing CDI,
Joshua Eastman
Z
0
APPROVED
O
DESCRIPTION
Q
z
0
z
updated top braces size
NSIONED AND TOLERENCED PE
SUPPLY AIR
C
2
0.
a
0
w
g
5
0
cc
w
w
a
W
2
N
J
w
z
a
a
0
W
r
a
1
z
z
0
1-
a
0
in
w
J
a'
2
0
1-
Q
N
z
U
0
a
U
2
H
w
0
0
re0
a
w
N
1 1/2" ADDED TO EXISTING CURB O.D.
•
N
EXISTING CURB LAYOUT
z
•
E
rc5
72
w'o
VT/K Emergence B Box
CO
00 N
0
M
eat
gCO
2
8
El w �+
0z
~ Z
=w
ce
ow
Ritci
w—w
N0
u)ZO
>a
a
W O W
CO w Z
ILJ—
CLZQ
_
Um
Z ? 0
D Z d
OOP
LLI=w
Z < LL
OUp
0u-0
0HZ
azm
Zncn
N = f
H _
F5§1=1
U U
ZOO
—
O�W
UwOQ
ZQZ
n=O
000
M
N
/%
//>-
28 9/16" -..-I
0)
•
E
rc5
72
w'o
VT/K Emergence B Box
CO
00 N
0
M
eat
gCO
2
8
El w �+
0z
~ Z
=w
ce
ow
Ritci
w—w
N0
u)ZO
>a
a
W O W
CO w Z
ILJ—
CLZQ
_
Um
Z ? 0
D Z d
OOP
LLI=w
Z < LL
OUp
0u-0
0HZ
azm
Zncn
N = f
H _
F5§1=1
U U
ZOO
—
O�W
UwOQ
ZQZ
n=O
000
'PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M18-0101
DATE: 08/17/18
PROJECT NAME: JUBA RESTAURANT & CAFE
SITE ADDRESS: 14223 TUKWILA INTERNATIONAL BLVD
X Original Plan Submittal
Response to Correction Letter #
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
AT /114)(J 0 --)-HO
AM AVG
Building Division si Fire Prevention
Public Works n
Structural
Planning Division
Permit Coordinator
n
•
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
DATE: 08/21/18
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 09/18/18
Approved
Corrections Required
InApproved with Conditions
nDenied
(corrections entered in Reviews) (ie: Zoning Issues)
n
n
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire ❑ Ping 0 PW ❑ Staff Initials:
12/18/2013
EVERGREEN REFRIGERATION r C
Hoene Espanol Contact
Safety & Health Claims & Insurance
4 C Washington State Department of
Labor & Industries
Page 1 of 3
Search L&I
A -Z Index Help My L&J
Workplace Righ€s Trades & Licensing
EVERGREEN REFRIGERATION LLC
Owner or tradesperson
Principals
PATTON, RODGER, PARTNER/MEMBER
PATTON, MATTHEW, PARTNER/MEMBER
Patton, Adam, PARTNER/MEMBER
Patton, Douglas, PARTNER/MEMBER
EVERGREEN REFRIGERATION
LLC, PARTNER/MEMBER
PATTON, DAVID, PARTNER/MEMBER
(End: 01/21/2014)
Doing business as
EVERGREEN REFRIGERATION LLC
WA UBI No.
602 512 953
727 S KENYON ST
SEATTLE, WA 98108
206-763-1744
KING County
Business type
Limited Liability Company
Governing persons
RODGER
PATTON
MATTHEW ALAN PATTON;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor
License specialties
GENERAL
License no.
EVERGRL954R2
Effective — expiration
01/06/2006— 01/06/2020
Bond
Merchants Bonding Co (Mutual)
Bond account no.
WA15097
Active.
Meets current requirements.
$12,000.00
Received by L&I Effective date
12/15/2011 01/01/2012
Expiration date
Until Canceled
Insurance
Nationwide Mutual Ins Co $1,000,000.00
Policy no.
ACP 3037246151
Received by L&I Effective date
07/24/2018 07/31/2018
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602512953&LIC=EVERGRL954R2&SAW= 9/4/2018
EVERGREEN RIEFRIGERATION LLC Page 2 of 3
Expiration date
07/3112019
Nationwide Mutual Ins Co $1,000,000.00
Policy no.
ACP 3018338030 -
Received by L&I Effective date
07/20/2018 07/31/2018
Expiration date
07/31/2019
Insurance history .:
Savings
No savings accour.ts during the previous 6 year period.
Lawsuits against tt,e bond or savings
No lawsuits against the bond or savings accounts during the previous 6 year period.
L&I Tax debts
No L&I tax debts aro recorded for this contractor license during the previous 6 year period, but some debts
may be recorded b'1 other agencies.
License Violations
No license violations during the previous 6 year period.
Workers' comp
Do you know if the business has employees? If so, verify the business is up-to-date on workers' comp premiums.
L&I Account ID Account is current.
422,456-02
Doing business as
EVERGREEN REFF.IGERATION LLC
Estimated workers reported
Quarter 2 of Year 2018 "Greater than 100 Workers"
L&I account contact
T4 / CASSANDRA SMITH (360)902-5632 - Email: SMCA235@Ini.wa.gov
Public Worl s Strikes and Debarments
Verify the contractor -is eligible to perform work on public works projects.
Contractor Strikes
No strikes have bean issued against this contractor.
Contractors not allowed to bid
No debarments ha•e been issued against this contractor.
Workplace s'afety and health
Check for any past safety and health violations found on jobsites this business was responsible for.
Inspection results date
10/24/2014
Inspection no.
317607380
Location
207 SW 156TH St
Burien, WA 9816'
Inspection results date
10/01/2014
Inspection no.
317583862
Location
3411 South 23rd .t
Tacoma, WA 984'5
Violations
No violations
Help us improve
https://secure.lni. ,va.gov/verify/Detail.aspx?UBI=602512953&LIC=EVERGRL954R2&SAW= 9/4/2018
EVERGREEN REFRIGERATION J I ;C
Page 3 of 3
Washington State Dept. of Labor & Industries. Use of this site is subject to the laws of the state of Washington.
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602512953&LIC=EVERGRL954R2&SAW= 9/4/2018
Riv ton Croat Ce rt etcr
St TE1 rT1: a eat hOlic
COMMISSIONING PLAN
GENERAL NOTES
ALL COMMISSIONING OF HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS AS
REQUIRED BY SECTION C408 "SYSTEM COMMISSIONING' OF THE 2015 WASHINGTON STATE
ENERGY CODE (WSEC) SHALL BE PERFORMED BY EVERGREEN REFRIGERATION, LLC. THE
ACTIVITIES TO BE ACCOMPLISHED ARE PER THE SECTIONS LISTED IN THE
"COMMISSIONING COMPLIANCE CHECKLIST" SHOWN BELOW. AT THE COMPLETION OF THE
ACTIVITIES REQUIRED FOR COMMISSIONING AS DEFINED BY SECTION C408 OF WSEC THE
"COMMISSIONING COMPLIANCE CHECKLIST" WILL BE REVIEWED WITH THE BUILDING
OWNER OR THE OWNER'S REPRESENTATIVE AND THIS CERTIFICATION WILL BE SIGNED
AND DATED. THIS WILL SATISFY TO THE CODE OFFICIAL THAT THE REPORT HAS BEEN
ACCEPTED AS REQUIRED BY SECTION C408.1.3 OF WSEC.
C urch, T tlkVvii a •
COMMISSIONING COMPLIANCE CHECKLIST
Project Name:
to ter 1-11(jh School
PROJECT
INFORMATION
Project: Address:
COMMISSIONING
PLAN
(SECTION C408.1.2)
SYSTEMS
BALANCING
(SECTION C408.2.2)
FUNCTIONAL
TESTING
(SECTION C408.2.3)
VICINITY MAP
NOT TO SCALE
Commissioning Authority:
LI Commissioning Plan was used during construction and Induded items below
• A NARRATIVE DESCRIPTION OF ACTIVITIES AND THE PERSONNEL INTENDED TO ACCOMPLISH EACH ONE
• MEASURABLE CRITERIA FOR PERFORMANCE
• FUNCTIONS TO BE TESTED
® Systems Balandng has been completed
• AIR AND HYDRONIC SYSTEMS ARE PROPORTIONATELY BALANCED IN A MANNER TO FIRST MINIMIZE THROTTLING LOSSES
• TEST PORTS ARE PROVIDED ON EACH PUMP FOR MEASURING PRESSURE ACROSS THE PUMP
• HVAC Equipment Functional Testing has been completed (SECTION C408.2.3.1)
HVAC EQUIPMENT HAS BEEN TESTED TO DEMONSTRATE THE INSTALLATION AND OPERATION OF COMPONENTS, SYSTEMS
AND SYSTEM -BY -SYSTEM INTERFACING RELATIONSHIPS IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS
® HVAC Controls Functional Testing has been completed (SECTION C408.2.3.2)
HVAC CONTROLS HAYS BEEN TESTED TO ENSURE THAT CONTROL DEVICES ARE CALIBRATED, ADJUSTED AND OPERATE
PROPERLY.
SEQUENCES OF OPERATIONS HAVE BEEN FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN ACCORDANCE WITH
APPROVED PLANS AND SPECIFICATIONS
U Economizers Functional Testing has been completed (SECTION C408.2.3.3)
ECONOMIZERS OPERATE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS
SUPPORTING
DOCUMENTS
(SECTION CI03.6)
COMMISSIONING
RPPrI T
(SECTION C408.1.4.1)
Manuals, record documents and training have been completed or are scheduled
• SYSTEM DOCUMENTATION HAS BEEN PROVIDED TO THE OWNER OR SCHEDULED DATE:
• RECORD DOCUMENTS HAVE BEEN SUBMITTED TO OWNER OR SCHEDULED DATE:
• TRAINING HAS BEEN COMPLETED OR SCHEDULED DATE:
Preliminary Commissioning Report submitted to Owner and indudes items below
• DEFICIENCIES FOUND DURING TESTING REQUIRED BY THIS SECTION WHICH HAVE NOT BEEN CORRECTED AT THE TIME
OF REPORT PREPARATION
• DEFERRED TESTS, WHICH CANNOT BE PERFORMED AT THE TIME OF REPORT PREPARATION DUE TO CLIMATIC
CONDITIONS.
U 1 fEREBY CERTIFY THAT All REQUIREMENTS FOR COMMISSIONING HAVE BEEN COMPLETED IN ACCORDANCE WITH THE
WASHINGTON STATE ENERGY CODE, INCLUDING ALL THE ITEMS ABOVE.
CERTIFICATION
BUILDING OWNER OR OWNER'S REPRESENTATIVE DATE
GAS PACKAGE EQUIPMENT SCHEDULE
MARK
MANF.
MODEL
TONS.
AIRFLOW
SP
MIN. OSA
MOTOR
DRIVE
COOLING
HEATING
ELECTRICAL
WEIGHT
TOTAL
FILTER SIZES
NOTES
CFM
WC
CFM
HP
STYLE
TOTAL
IEER
EER
INPUT
OUTPUT
AFUE
VOLTS
PHASE
M.C.A.
j
RETURN DUCT SECTION
CENTER
'/
BTUH
EXHAUST DUCT SECTION
0
BTUH
BTUH
(%)
(V)
SUPPLY DIFFUSER
(A)
LBS
NO. (LxWxD)
SIDEWALL DIFFUSER
RTU I
LENNOX
KGA092S4M
7.5
3000
0.8
600
2
MSAV BELT
88,200
13.0
11.0
130,000
104,000
80%
208
30
38.0
991
4 (20" x 20" x 2")
1,2,3,4,5
NOTES: I. THE ROOFTOP UNIT COMES COMPLETE WITH AN ECONOMIZER
2. THE ROOFTOP UNIT COMES COMPLETE WITH A SMOKE DETECTOR TO BE PLACED IN THE MAIN RETURN DUCT
3. THIS IS A LIKE FOR LIKE REPLACEMENT, REPLACING MODEL YCD090
4. DOAS NOT REQUIRED PER WSEC C503.4 EXCEPTION, NO COOLING ADDED
5. UNIT WILL SET ON ERL PROVIDED CURB ADAPTER
6. UNIT COMES WITH THERMOSTAT, FIELD VERIFY LOCATION
DUCTWORK
NOT PUBLISHED. AU. RIGHTS RESERVED. THE DRAWING AND SPECIFICATIDNS, IDEAS,
DESIGN AND ARRANGEMENTS REPRESENTED THEREBY APE AND SHAD. REMAIN THE
PROPERTY OF EVERGREEN REFRIGERATION U.C. NO PART THERE OF SHALL BE
DISTRIBUTED TO OTHERS, SOLD, PUBLISHED OR OTHERWISE USED WITHOUT THE
PRIOR WRITTEN CONSENT OF AND APPROPRIATE COMPENSTATIDN TO EVERGREEN
REFRIGERATION LLC. VISUAL CONTACT WITH THE ABOVE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF ACCEPTANCE OF THESE
RESTRICTIONS.
1.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH
DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4" TO EACH DIMENSION IF THE
DUCTWORK IS ON THE INTERIOR OF THE BUILDING.
1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND IS
THE HEIGHT.
1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING LESS
THAN 25 AND A FLAME SMOKE DEVELOPMENT LESS THEN 50, PER IMC 602.2.1.
1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETWEEN
1/2 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT
PRESSURES ABOVE 1/2 WATER COLUMN SHALL BE SEALED IN ACCORDANCE WITH
STANDARD RS -7.
1.5 ALL DUCT GAUGES PER SMACNA, IMC 603-4.
1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603-10.
1.7 ATTACH DIFFUSERS AND GRILLES TO T -BAR PER WA STATE a LOCAL CODES.
1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS.
INSULATION
2.1 INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES.
2.2 INSULATE REFRIGERANT a CONDENSATE PIPING PER STATE & LOCAL ENERGY
CODES.
GENERAL CONTRACTOR
3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP, CEILING,
FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING AND FIRE
PROOF LININGS PER IMC & IBC.
3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS WITH
ERL BEFORE FRAMING OPENINGS.
3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING AS
REQUIRED FOR MECHANICAL WORK.
3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS REQUIRED
FOR MECHANICAL WORK.
3.5 GENERAL CONTRACTOR TO PROVIDE ADEQUATE ENGINEERING AS REQUIRED FOR
MECHANICAL WORK.
3.6 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL
MECHANICAL EQUIPMENT.
3.7 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE
ALL CANT STRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS.
3.8 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OR T -BAR CEILING
AS REQUIRED FOR HVAC INSTALLATION.
3.9 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED
FOR DUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL
BUILDING CODE, WHERE REQUIRED BY SECTION 707 OF IBC.
ELECTRICAL
4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDED
BY ELECTRICAL CONTRACTOR.
4.2 ELECTRICAL CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS,
DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT.
4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS,
WITH ERL MECHANICAL PLAN AND WITH FIELD LOCATIONS.
4.4 ELECTRICAL CONTRACTOR TO INTERLOCK BATHROOM EXHAUST FANS WITH LIGHT
SWITCH.
4.5 ERL TO PROVIDE 7 -DAY NIGHT SETBACK, PROGRAMMABLE TYPE T -STAT WITH
CAPABILITY OF 5°F DEADBAND.
4.6 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER.
4.7 ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL GCFI OUTLET WITHIN 25 FT OF
EACH PIECE OF MECHANICAL EQUIPMENT.
PLUMBING
5.1 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL GAS PIPING FOR
MECHANICAL EQUIPMENT PER CODE.
5.2 PLUMBING CONTRACTOR OFFSETS VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH
AIR INTAKES OR 3' ABOVE HIGHEST POINT OF INTAKE, IMC 401.4.1
5.3 CONDENSATE DRAINS FROM RTU BY ERL TO DRAIN WITHIN 12" OF UNIT. CONDENSATE
DRAINS FOR AIR HANDLERS BY PLUMBER.
ENERGY CODE COMPLIANCE
6.1 THE SUPPLY HEATING AND COOLING ENERGY TO EACH ZONE SHALL BE CONTROLLED
BY INDIVIDUAL THERMOSTATIC CONTROLS CAPABLE OF RESPONDING TO
TEMPERATURE WITHIN THE ZONE. AT MINIMUM, EACH FLOOR SHALL BE CONSIDERED
A ZONE.
6.2 OUTDOOR AIR SUPPLY, EXHAUST OPENINGS AND RELIEF OUTLETS SHALL BE
PROVIDED WITH CLASS IA MOTORIZED DAMPERS WHICH CLOSE AUTOMATICALLY
WHEN THE SYSTEM IS OFF PER WSEC SECTION C403.2.4.3.
MECHANICAL CODE COMPLIANCE
7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS
IN EACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM.
DETECTORS SHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606.
Plan reviewappp `,:�^l r irc.1 CI r.L, n2} to E ^
r v>^ f.N..! A r
Approval of constrt:r(.3i dL..u;i = S dcC3 C.: Ca 1QiiZCi
the violation of any adopt ;d coo or cid nn 03. I accipt
of approved Field Copy and condi:; ..3 i3
By:
Date:
City of Tukwila
BUILDING DIVISION
REVISIONS
No changes shall n-, m=tde to the scope
of work withool p in,. approval of
Tuk'!rila 61_I;ld
NOTE: E: J s on3 w d Ii>CI 11 t) ,� )�'.'"/ pl2n submlttjl
end may inc'ude cdc''"ionaI War) f >r `vi fc
cs
ISE 7,:1i.: FF -''SIT
I i'._..°2 7._. ") FOR:
CJ tit cc:ianical
Ei Etcctrical
121/ iumbing
l Czs Piping
CIiy of Tukwila
pi i4I r-,,,,-.. n,‘,,..,,.,N1
HVAC ROOF PLAN
SCALE: I / I6"=I'
WA2015
SYMBOL LEGEND
NOTE: NOT ALL SYMBOLS SHOWN ON THIS LEGEND MAY
PERTAIN TO THIS PROJECT.
RECTANGULAR DUCT
I0"X20"
CODE
BJILDI
REVIEWED
.
kJ
City
ROUND DUCT
of
VG
10110
FO
0
VISION
-F2-1
2 - '
111111110111111111
FLEXIBLE DUCT
OF
,
SUPPLY DUCT SECTION
LDATE
j
RETURN DUCT SECTION
CENTER
'/
$'
EXHAUST DUCT SECTION
0
e ,
SUPPLY DIFFUSER
1,
RETURN/EXHAUST GRILLE
t
o
SIDEWALL DIFFUSER
7
CEILING MOUNTED
EXHAUST FAN
INLINE FAN
V
d
MANUAL VOLUME DAMPER
C 7
4
ZONE DAMPER
1'
X
d
MOTORIZED DAMPER
M
FIRE SMOKE DAMPER
(120V POWER REQ.)
oaU.
FIRE DAMPER
OTHERMOSTAT
SD
SMOKE DETECTOR
OSENSOR
H;"
EQUIPMENT TAG
v
CD -I
DIFFUSER/GRILLE TAG
250 CFM
DESCRIPTION
CODE
BJILDI
REVIEWED
.
kJ
City
COMPLIANCE
APPROVED
AU282013
of
VG
Tukwila
D
FO
0
VISION
-F2-1
2 - '
CITY
RECEIVED
AUG
OF
TUKWILA
17
2016
LDATE
PERMIT
CENTER
0
PERMIT SET
DATE: 8/8/18
ISSUED FOR
CONSTRUCTION El
AS BUILT
DATE: ----
JUBA RESTAURANT & CAFE
COVER SHEET
DWG BY:
CKD BY:
JOB NO.:
AF
MG/MH
218042