Loading...
HomeMy WebLinkAboutPP - 4411 S RYAN WAY - RAISBECK ENGINEERING, INC. - PERMITS AND PLANS4411 S RYAN WAY ASSOCIATED PERMITS M99-0135 97-F-105 D99-0106 08-S-050 D98-0407 99-S-196 M97-0027 98-S-324 D96-0075 97-S-043 • City of Tukwila F! John W. Rants, Mayor Fire Department Fire Department Review Control #M99-0135 (512) Thomas P. Keefe, Fire Chief July 21, 1999 Re: Raisbeck Engineering - 4411 South Ryan Way Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with'the following concerns: 1. H.V.A.C. units rated at greater than 2,000 cfm require auto -shutdown devices. These devices. shall be separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance #1742) H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the air -moving equipment upon detection of smoke in the main supply -air duct served by such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the manufacturer's installation instructions. (UMC 608) Dedicated fire alarm system circuit breaker(s) shall be equipped with a mechanical lockout device. (NFPA 72 (1-5.2.8.2)) Duct smoke detectors shall be capable of being reset from the alarm panel. (City Ordinance #1742) Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #1742) All new fire alarm systems or modifications to Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 57.5-443S7 • City of Tukwila John W. Rants, Mayor Fire Department Thomas P. Keefe, Fire Chief Page number 2 existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #1742) (UFC 1001.3) Call the Tukwila Fire Department at 575-4407 for approval of any system shut down. Have job site address, name and the Tukwila Fire Department Job Number available to confirm shut down approval. (City Ordinance #1742) Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503) (City Ordinance #1742) 2. All electrical work and equipment shall conform strictly to the standards of The National Electrical Code. (NFPA 70) 3. This review limited to speculative tenant space only - special fire permits may be necessary depending on detailed description of intended use. Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. Yours truly, The Tukwila Fire Prevention Bureau cc: TFD file ncd Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439 • City of Tukwila Fire Department John W. Rants, Mayor Thomas P. Keefe, Fire Chief April 13, 1999 Fire Department Review Control #D99-0106 (510) Re: Raisbeck Engineering - 4411 South Ryan Way Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. The total number of fire extinguishers required for your establishment is calculated at one extinguisher for each 3000 sq. ft. of area. The extinguisher(s) should be of the "All Purpose" (2A, 10B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (NFPA 10, 3-1.1) Portable fire extinguishers shall be securely installed on the hanger or in the bracket supplied, placed in cabinets or wall recesses. The hanger or bracket shall be securely and properly anchored to the mounting surface in accordance with the manufacturer's instructions. The extinguisher shall be installed so that the top of the extinguisher is not more than 5 feet above the floor and the clearance between the bottom of the extinguisher and the floor shall not be less than 4 inches. Extinguishers shall be located so as to be in plain view (if at all possible), or if not in plain view, they shall be identified with a sign stating, "Fire Extinguisher", with an arrow pointing to the unit. (NFPA 10, 1-6.3) (UFC Standard 10-1) Clear access to fire extinguishers is required at all times. They may not be hidden or obstructed. (NFPA 10, 1-6.5) Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439 • City of Tukwila John W. Rants, Mayor Fire Department Page number 2 Thomas P. Keefe, Fire Chief Fire extinguishers require monthly and yearly inspections. They must have a tag or label securely attached that indicates the month and year that the inspection was performed and shall identify the company or person performing the service. (NFPA 10, 4-3, 4-4 and 4-4.3) Every six years, dry chemical and halon type fire extinguishers shall be emptied and subjected to the applicable recharge procedures. (NFPA 10, 4-4.1) If the required monthly and yearly inspections of the fire extinguisher(s) are not accomplished or the inspection tag is not completed, a reputable fire extinguisher service company will be required to conduct these required surveys. (NFPA 10, 4-3, 4-4) 2. No point in a sprinklered building may be more than 250 feet from an exit, measured along the path of travel. (UBC 1004.2.5.2.2) Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. Exit doors shall not be locked, chained, bolted, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC 1207.3) Dead bolts are not allowed on auxiliary exit doors unless the dead bolt is automatically retracted when the door handle is engaged from inside the tenant space. (UFC 1207.3) Exit hardware and marking shall meet the requirements of the Uniform Fire Code. (UFC 1207-1212) When two or more exits from a story are required, exit signs shall be installed at the required exits and where otherwise necessary to clearly indicate the direction of egress. (UBC 1003.2.8.2) Exits shall not pass through kitchens, storerooms, restrooms, closets or spaces used for similar Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439 • City of Tukwila John W. Rants, Mayor Fire Department Page number 3 Thomas P. Keefe, Fire Chief purposes. (UBC 1004.2.2) When two or more exits from a story are required and when two or more exits froma room or an area are required, exit signs shall be illuminated. (UBC 1003.2.8.4) All exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 1 1/2 hours in case of primary power loss, the exit signs shall also be connected to an emergency electrical system provided from storage batteries, unit equipment or an on site generator set, and the system shall be installed in accordance with the electrical code. (UBC 1003.2.8.5) Manually operated edge- or surface -mounted flush bolts and surface bolts are prohibited. When exit doors are used in pairs and approved automatic flush bolts are used, the door leaf having the automatic flush bolts shall have no door knob or surface -mounted hardware. The unlatching of any leaf shall not require more than one operation. (UFC 1207.3) 3. Maintain sprinkler coverage per N.F.P.A. 13. Addition/relocation of walls, closets or partitions may require relocating and/or adding sprinkler heads. Escutcheon plates used with a recessed or flush -type sprinkler shall be part of a listed sprinkler assembly. (NFPA 13-2-2.6.2) All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department review and approval of drawings prior to installation or modification. New sprinkler systems and all modifications to sprinkler systems involving more than 50 heads shall have the written approval of the W.S.R.B., Factory Mutual, Industrial Risk Insurers, Kemper or any other representative designated and/or recognized by The City of Tukwila, prior to submittal Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) .57.5-4439 • City of Tukwila John W. Rants, Mayor Fire Department Page number 4 Thomas P. Keefe, Fire Chief to the Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved drawings. (City Ordinance #1742) Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503) (City Ordinance #1742) Maintain a 3' clear space around the sprinkler riser(s) for emergency access. (NFPA 13 4-1.2) 4. An approved manual fire alarm system is required for this project. The fire alarm system shall meet the requirements of the Americans With Disabilities' Act, chapter 51-20 WAC (Chapter 31 Accessibility), N.F.P.A. 72 and the City of Tukwila Ordinance #1742. Dedicated fire alarm system circuit breaker(s) shall be equipped with a mechanical lockout device. (NFPA 72 (1-5.2.8.2)) All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #1742) (UFC 1001.3) Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503) (City Ordinance #1742) 5. All electrical work and equipment shall conform strictly to the standards of The National Electrical Code. (NFPA 70) An aisle to and working space shall be provided for each electrical panel. An aisle width not less than 24 inches shall provide access to the panel and 30 inches of working space shall be provided directly in front of the panel. (NEC 110-16(a), NEC 110-16(c)) Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439 • City of Tukwila John W. Rants, Mayor Fire Department Page number 5 Thomas P. Keefe, Fire Chief Each circuit breaker shall be legibly marked to indicate it's purpose. (NEC 110-22) 6. Your street address must be conspicuously posted on the building and shall be plainly visible and legible from the street. (UFC 901.4.4) 7. This review limited to speculative tenant space only - special fire permits may be necessary depending on detailed description of intended use. 8. Accumulation of combustible waste material is prohibited during the demolition phase of this project. Remove and properly dispose of all waste material prior to the close of the working day and as often throughout the day as needed. Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. Yours truly, The Tukwila Fire Prevention Bureau cc: TFD file ncd Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439 f Fire Department Fire Department Review Control #D98-0407 (511) • Re: T.I. at Raisbeck Engineering - 4411 South Ryan Way Dear Sir: John W. Rants Mayor Thomas P. Keefe, The Chief The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. The total number of fire extinguishers required for your establishment is calculated at one extinguisher for each 3000 sq. ft. of area. The extinguisher(s) should be of the "All Purpose" (2A, 10B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (NFPA 10, 3-1.1) Extinguishers shall be installed on the hangers or in the brackets supplied, mounted in cabinets, or set on shelves (NFPA 10, 1-6.9), and shall be installed so that the top of the extinguisher is not more than 5 feet above the floor. (NFPA 10; 1-6.9) Extinguishers shall be located so as to be in plain view (if at all possible), or if not in plain view, they shall be identified with a sign stating, "Fire Extinguisher", with an arrow pointing to the unit. (NFPA 10, 1-6.3) (UFC Standard 10-1) Clear access to fire extinguishers is. required at all times. They may not be hidden or obstructed. (NFPA 10, 1-6.5) Fire extinguishers require monthly and yearly inspections. They must have a tag or label securely attached that indicates the month and year that the inspection was performed and shall identify the company or person performing the service. (NFPA 10, 4-3, 4-4 and 4-4.3) Every six years, dry chemical and. Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 5754404 • Fax (206)575443 • City of Tukwila • John W. Rants, Mayo, Fire Department Thomas P. Keefe, Rre Chkek Page number 2 halon type fire extinguishers shall be emptied and subjected to the applicable reb arge procedures. (NFPA 10, 4-4.1) If the required monthly and yearly inspections of the fire extinguisher(s) are not accomplished or the inspection tag is not completed, a reputable fire extinguisher service company will be required to conduct these required surveys. (NFPA 10A-4-4) Maintain fire extinguisher coverage throughout. 2. No point in an unsprinklered building may bemore than 150 feet from an exit, measured along the path of travel. (UBC 1003.4) No point in a sprinklered building may be more than 200 feet from an exit, measured along the path of travel. (UBC 1003.4) Exit doors shall swing in the direction of exit travel when serving any hazardous area or when serving an occupant load of 50 or more. (UBC 1004.2) 3. Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. Exit doors shall not be locked, chained,bolted, barred, latched or otherwise rendered unusable. Alllocking devices shall be of an approved type. (UFC 1207.3) Dead bolts are not allowed on auxiliary exit doors unless the dead bolt is automatically retracted when the door handle is engaged from inside the tenant space. 4. When two or more exits from a story are required, exit signs shall be installed at the required exits and where otherwise necessary to clearly indicate'the direction of egress. (UBC 1013.1) When two or more exits from a story are required and when two or more exits from a room or an area are Noarimwarttrs _Station! 444 Andover Park East • Tukwila, Washington 98188 • Phone(206) 575-4404 • Fax (206) 57544 • . • City of Tukwila John W. Rants, Mayo) Fire Department Thomas P. Keefe, Rre Chle, Page number 3 required by U.B.C. Section 3303, exit signs shall be illuminated. (UBC 1013.3) • Internally illuminated exit signs shall have both bulbs working at all times. (UBC 1013.3) 5. Exits shall be illuminated any time the building is occupied with light having an intensity of not less than 1 foot candle at floor level. Fixtures required for exit illumination shall be supplied from separate sources of power for Group I, Divisions 1.1 and 1.2 occupancies and for all other occupancies where the exiting system serves an occupant load of 100 or more. (UBC 1012.1, 1012.2) The power supply for the exit pathway illumination shall normally be provided by the premise's wiring system. In the event of its failure, illumination shall be automatically provided from an emergency system. Emergency system shall be supplied from storage batteries or an on-site generator set and the system shall be installed in accordance with the requirements of the Electrical Code. (UBC 1012.2) 6. Maintain sprinkler coverage per N.F.P.A. 13. Addition/relocation of walls, closets or partitions may require relocating and/or adding sprinkler heads. Sprinkler protection shall be extended to all areas where required, including all enclosed areas, below obstructions and under overhangs greater than four feet wide. (NFPA 13-4-4.1.3.2.1) .7. Maintain hose station coverage per City Ordinance #1742 and N.F.P.A. 14. Addition/relocation of walls or partitions may require relocating and/or adding hose stations. 8. An approved hose station requires plans review. (Plans must be submitted to the Fire Marshal for approval prior to installation.) (City Ordinance #1742) Headauarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone:1206) 575-4404 .• Fax (206) 57544: • City o, f Tukwila Fire Department Page number 4 John W. Rants, Mayor Thomas P. Keefe, Fine Chief 9. A11 new sprinkler systems and all modifications to existing sprinkler systems shall Have fire department review and approval of drawings prior to installation or modification. New sprinkler systems and all modifications to sprinkler systems involving more than 50 heads shall have the written approval of the W.S.R.B., Factory Mutual, Industrial Risk Insurers, Kemper or anyother representative designated and/or recognized by The City of Tukwila, prior to submittal to the Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved drawings. (City Ordinance #1742) All sprinkler system plans, calculations and the contractors Materials and Test Certificates submitted to The Tukwila Fire Prevention Bureau must be stamped with the appropriate level of competency seal. (WAC 212-80) 10. Maintain automatic fire detector coverage per N.F.P.A. 72. Addition/relocation of walls, closets or partitions may require relocating and/or adding automatic fire detectors. Maintain square foot coverage of detectors per manufacturer's specifications in all areas including: closets, elevator shafts, top of stairwells, etc.. (NFPA 72, 5-1.3.4) 11. All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #1742) (UFC 1001.3) 12. All electrical work and equipment shall conform strictly to the standards of The National Electrical Code. (NFPA 70) 13. Required fire resistive construction, including occupancy separations, area separation walls, exterior walls due to location on property, fire resistive lio2fin„artvre V2tinn• 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-443c • City of Tukwila John W Rants, Mayor Fire Department Thomas?. Keefe, Rre Chief Page number 5 requirements based on type of construction, draft stop partitions and roof coverings shall -be -Maintained as specified in the Building Code and Fire Code and shall be properly repaired, restore tedr removeddorhen improperly, altered, breached, penetra installed. (UFC 701). The maximum flame spread class of finish materials used on interior walls and ceilings shall not exceed that set forth in Table No. 8-B of The Uniform Building Code. (UBC 804.1) 14. Your street address must be conspicuously posted on the street. Numbersand ll be shallpcontrastlwithetheirlbackground ible from the street. (UFC 901.4.4) • In order to provide you with the fastest police cease nd fire protection under emergency conditions, post your suite, room or apartment numbbeerrin Numbers a conspicuous place near the main entry d.shall contrast with their background. (UFC 901.4.4) Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503) (City Ordinance #1742) This review limited to speculative tenant space onlynetailed - special fire permits may be necessarydepending description of intended use. Any overlooked hazardous condition and/or violation of f the approval adopted Fire or Building Codes does not imply pP nv of such condition or violation. W chlnotnn OR188 • Phone: (206) 575-4404 • Fax (206) 575 • •City of Tukwila john W. Rants, Mayor Fire Department Thomas P. Keefe, Fire. Chief Page number 6 Yours truly, The Tukwila Fire Prevention Bureau cc: TFD file ncd ► r t • Trikulf12 Wachtncrton 98188 • Phone: (206) 57$4404 • Fax: (206) 57544, City of Tukwila Fire Department February 19, 1997 Fire Department Review Control # M97-0027 Re: H.V.A.C. at Raisbeck Engineering, 4411 S Ryan Wy Dear Sir: John W. Rants, Mayor Thomas P. Keefe, Fire Chief The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. H.V.A.C. units rated at greater than 2,000 cfm require auto -shutdown devices. These devices shall be separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance #1742) H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the air -moving equipment upon detection of smoke in the main supply -air duct served by such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shallbe installed in accordance with the manufacturer's installation instructions. (UMC 608) 2. Duct smoke detectors shall be capable of being reset from the alarm panel. (City Ordinance #1742) Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #1742) 3. In areas that are not continuously occupied, automatic smoke detection shall be provided at each control unit(s) location to provide notification of fire at that location. (NFPA 1-5.6) The installation of wiring and equipment shall be in Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone (206) 575-4404 • Fair (206) 575-4439 i City of Tukwila Fire Department Page number 2 John W. Rants, Mayor Thomas P. Keefe, Fire Chief accordance with N.F.P.A. 70, Article 760, Fire Protective Signaling Systems. (NFPA 72-1-5.5.4) 4. When the control panel is located inside a room, the door to the room shall have a sign with one -inch letters which reads "Fire Alarm" or "Fire Alarm Control". (City Ordinance #1742) Dedicated fire alarm system circuit breaker(s) shall be equipped with a mechanical lockout device. (NFPA 72 (1-5.2.8.2) ) 5. All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #1742) (UFC 1001.3) Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503), (City Ordinance #1742) Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. Yours truly, The Tukwila Fire Prevention Bureau cc: TFD file ncd Xeadauarters Station: 444 Andover Park East • Tukwila_ Washlnvtnn OR1RR • Phnnp• 126A) s71.4efd • Far /2nli) s7s AAWo • City of Tukwila Fire Department Fire Department Review Control #D96-0075 (512) FILE John W. Rants, Mayor Thomas P. Keefe, Rre Chief December 18, 1996 Re: Raisbeck Engineering - 4411 South Ryan Way Dear Sir: The attached set of building plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following concerns: 1. Maintain fire extinguisher coverage throughout. Clear access to fire extinguishers is required at all times. They may not be hidden or obstructed. (NFPA 10, 1-6.5) 2. No point in a sprinklered building may be more than 200 feet from an exit, measured along the path of travel. (UBC 1003.4) Exit doors shall be. openable from the inside without the use of a key or any special knowledge or effort. Exit doors shall not be locked, chained, bolted, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type. (UFC 1207.3) Dead bolts are not allowed on auxiliary exit doors unless the dead bolt is automatically retracted when the door handle is engaged from inside the tenant space. Exit hardware and marking shall meet the requirements of the Uniform Fire Code. (UFC 1207.1-1212.8) 3. When two or more exits from a story are required and when two or more exits from a room or an area are required by U.B.C. Section 3303, exit signs shall be illuminated. _ ... • _ .__ n__1. r__. - 4:.L.JI. tff . Lt....a.... AOf 00 a. D1......,. /')Poli) [7fr1A/L4 • rbv. /9/11.1 C7C.12120 • ofTuxwira John W. RantsMayor Fire Department Thomas P. at" The Page number (UBC 1013.3) Internally illuminated exit signs shall have both bulbs working at all times. (UBC 1013.3) When two or, more exits from a story are required, exit signs shall be installed at the required exits and where otherwise necessary to clearly indicate the direction of egress. (UBC 1013.1) Exits shall be illuminated any time the building is occupied with light having an intensity of not less than 1 foot candle at floor level. Fixtures required for exit illumination shall be supplied from separate sources of power for Group I, Divisions 1.1 and 1.2 occupancies and for all other occupancies where the exiting system serves an occupant load of 100 or more. (UBC 1012.1, 1012.2) The power supply for the exit pathway illumination shall normally be provided by the premise's wiring system. In the event of its failure, illumination shall be automatically provided from an emergency system.Emergency system shall be supplied from storage batteries or an on-site generator set and the system shall be installed in accordance with the requirements of the Electrical Code. (UBC 1012.2) Combustible material shall not be stored in exits or exit enclosures. (UFC 1103.3.2.3) 4. All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department review and approval of drawings prior to installation or modification. New sprinkler' systems and all modifications to sprinkler systems involving more than 50 heads 'shall have the written approval of the W.S.R.B., Factory Mutual, Industrial.Risk Insurers, Kemper or any other. representative designated and/or recognized by The City of Tukwila, prior to submittal to the Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved Headquarters Station: '444Andor`er Palk East • Tukwila, Washington 98188 • Phone (006) .05.44104 • Roc (206) 575.4439 city of Tukwila Ftre Dspamnenf Page number John W. Rants,. Mayor Thom s F aff4 The Chief drawings. (City Ordinance #1742) Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (UFC 10.503) (CityOrdinance #1742) 5. All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. Nowork shall commence until a fire department permit has been obtained. (City Ordinance #1742) (UFC 1001.3) Call the Tukwila Fire Department at 575-4407 for approval of any system shut down. Have job site address, name and the Tukwila Fire Department Job Number available to confirm shut down approval. (City Ordinance #1742) 6. All electrical work and equipment shall conform strictly to the standards of The National Electrical Code. (NFPA 70) 7. Required fire resistive construction, including occupancy separations, area separation walls, exterior walls due to location on property, fire resistive requirements based on type of construction, draft stop partitionsiand roof coverings shall be maintained as specified in the Building Code and Fire Code and shall be properly repaired, restored or replaced when damaged, altered, breached, penetrated, removed or improperly installed. (UFC 701). This review limited to speculative tenant space only special fire permits may be necessary depending, on detailed description of intended use. Any overlooked hazardous condition and/or violation of the adopted fire or Building Codes does not imply approval of such condition or violation. Headquarters Stanton: 444 Andover Park East • Tukwila, Washington 98188 • Phone (206) 575'4404 • f+ix ION?57$4439 Page number Yours truly,' The Tukwila Fire Prevention Bureau cc: TFD file nc d John W Rants, Mayor Thomas P. Kee* Ffre Chief Headquarters Station: 444Ando'.er Pan* Bast • t Washt��48188 • PJB (206)31S,4404 • Fax (206) 5754439 1 INSPECTION NUMBER 7INSPECTION RECORD Retain a copy with permit > R i '1' j FEET 2 9 2008 45--S—os o - PERMIT NUMBERS CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206-575-4407 Project: 476G44 Type of Inspection: SPt w/a/ t— Address: yy// S, gyms, Ws' Suite #: Cont Person; 5 cotT J(t'V77f Special Instructions: Phone No.: VA-1)proved per applicable codes. Corrections required prior to approval. COMMENTS: Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: _ Occupancy Type: Inspector: 9Gv /51z Date: 2/z( f08 Hrs.: $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. Word/Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113 CCE TE Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. I.! Additions, deletions or revisions to these drawings after t this date will void this acceptance and will require a 11 resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: y-/ b' -17 By: Attl s1/ TUKWILA FIRE DEPARTMENT Please call: 575-4407 and give this job No. 97-F- /or and exact address for shut= down or restoration approval. ra.PI``sB Et-A,Ni '2- 1A ‘DY-- t - «- \ C,c. r4 Aor, L ar rkJS e 0 eA EXt srrr4& f) iL,Ap..m Contr ol. PA, EL D1crt"riAL PAP / 12ssri-r STAT��t�l H ucr sAdvo DErec-ro . (})-4sTALLG0 gik_r -c .$) MNfrNL 1tG DodR- )-40E-DEQ (1JS1LEO 1 C77-1 !2c isit/.!(n t,t1A't"L{L Ft.-0iry �7�r5Tr�(r, 7AAA,p R.. Os t1 ([s4 A ova f C- PcoocTro/J otil' 'fit. -f La FoLLot.,,'1fL ,,SGT S ,t,t o- E b a= L off- M o ,.) I -re ' Z Z. °NE- b to- 1-r/4 IL E ° A-0 Tp F-A-Gt 12•E E ✓A -C DQGT' ET. 3, DA)O &j J E -r( oo 1--toi-D ems/ )26L AsE t�1 t g. t=- l:::, -"o okC... ft R- p ,g r' fC, 5 E -. 0/4 � 1+- b � "t c-- To g.eLC f.)1 T r ,4-r6 o o ` °r �. f c7AA �t /2. f 7. 2-r cot 12 `a /JO,' Akof i r/ -4,4A.1 5. r F12 -0A -t ►? 66le- e.� c�.tt.!,J HE1..04-7` ,13oLiE 000i tom-�iti 4411SRYANWY 97—F-105 Lbs_ TA/Q:. & t t -rr t3 1 E t r4At41 �s 41 /01)4- 2) APR 171997�'- hiAS 14 ,J G-z©A) /-t.-'-g- . 9) .1Z- —22 •(E) (E)• (R) (E) J (E) • (R)0 (R) E 0(R) (E) (E) (R) -11 (R) C^•-•••• (E) (R) (P) (E) (E) (E) 11411111b.i.... (R) jI (R) (E) (E) (F) (E) (E) (R) ,..11/1111111/1i11111 (E) R (E) (R) 2\ D FLOOR (R) (R) (E) rn 0 (E (E)• *(E NOTES (R) = RELOCATED PENDENT (QTY= 20) (P)= PLUG EXISTING 1" OUTLET (QTY= 4) (E)= EXISTING PENDENT \ HANGERS ARE ROD RING & SAMMY SUPER SCRE EAST WING OFFICE REMODEL VIE1,11.1163 • TUKWILA FIRE DEPARTMENT Please call: 575-44.07 and give this job No. ,e52 D•LI and exact address for shuta down or restoration approval, TE Without Comments As Noted In Red Per The Attached Letter Thea plans have been reviewed by The Tukwila Fire .y -au for conformarice wlth current city Acoop'.2nce is subject to errors and nct violations of adopted • Tbo. orthe Or after r.-ZqU'SC:,1 a JfC,ri-LL; subseo,uont approval. 7.1 acceptance is subject to fk-E.!:1 test arid inspection by Tukwila Fire Prevention Bureau. /)•/)-/f9 By: 4-41 ( FE@NEME nFr j'' 1998 H.V.A.C., PIPING, PLUMBING ENERGY MANAGEMENT & FIRE PROTECTION MECHANICAL ENGINEERS AND CONTRACTORS 5005 3RD AVE SOUTH P.O. BOX 24567 SEATTLE,WA. 98134 223-01 #MC-KI-N-372NO (206) 762-3311 PROJECT: McK. PROJECT NUMBER: t.6'0 TITLE: SPRINKLER MODIFICATIONS 4411 S RYAN WY 98-S-324 ° D ,e5r/d N N N / —• N 400.97' N 87?27'9 a W EXIST. FIRE HYDRANT NO PARKING ONI>idbd ON r` EXISTING SYSTEM RISER EXISTING 6" FDC EXISTING 8" SUPPLY—\ I II J N N (4},, 2-1/2" FDC CONNECTIONS \T BACKFLOW PREVENTER EXISTING BUILDING TO CITY MAIN `~ ON S. RYAN WAY EXIST.„, FIRE \ HYDRANT N N 3,991 U.S.F. ADDfl1CN TO MAIN FLOOR I SITE PLAN RAISBECK ENGINEERING SCALE: 1" = 20' 4.997 co GENERAL NOTES 1 SPRINKLER SYSTEM DESIGN PER N.F.P.A. #13 2 ALL MATERIALS SHALL BE NEW AND U.L. LISTED OR F.M. APPROVED 3 FIRE SPRINKLER SYSTEM TO BE INSTALLED, BRACED AND TESTED IN ACCORDANCE WITH N.F.P.A. #13 4 IN LOCALITIES SUBJECT TO FREEZING CONDITIONS IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT THROUGHOUT THE WET PIPE SPRINKLER SYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE , DELUGE AND OTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS 5 FIRE PROTECTION CONTRACTOR SHALL NOT BE RESPONSIBLE FOR THE ABILITY OF THE STRUCTURE TO ADEQUATELY SUPPORT THE FIRE SPRINKLER SYSTEM OR ANY APPURTENANCES THEREOF 6 ALL ELECTRICAL, PAINTING OF PIPE, FURRING, CUTTING OR PATCHING TO BE BY OTHERS 7 SPRINKLER HEADS ARE TO BE LOCATED IN CEILING TILES LINED UP AND SYMMETRICAL. 8 PIPE SIZING PER HYDRAULIC CALCULATIONS, SEE PLAN. 9 EXISTING SPRINKLER SYSTEM HYDRAULICALLY CALCULATED AND DESIGNED TO PROVIDE .15 G.P.N. OVER THE MOST REMOTE 1500 SQ. FT. 10 McKINSTRY SCOPE OF WORK STARTS AT ADDITION TO MAIN FLOOR. ADDED PENDENTS TO MAIN FLOOR FOR NEW ACT TILE CEILING. NEW BRANCH LINES AND UPRIGHTS UNDER ADDITION. 11 1" PIPING TO BE SCHED 40. 1-1/4" AND ABOVE TO BE THIN WALL. 12 NEW SPRINKLER PIPE SIZING TO MATCH EXISTING PIPE SIZING. 13 ALL AREAS TO BE ORDINARY HAZARD 14 SPRINKLER PIPING OUTSIDE AREA OF WORK NOT SHOWN AND ARE TO REMAIN AS IS. GENERAL LEGEND NEW SPRINKLER PIPING EXISTING SPRINKLER PIPING SYSTEM RISER FIRE HYDRANT POST INDICATOR VALVE FIRE DEPT. CONNECTION TUKWITA FIRE DEPARTMEIJ Please call: 575.4407 and give this job No. S and exact address for shuts down or restoration approv, ►;1 A CE TED Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire 1 Prevention Bureau for conformance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions b these drawings after this date will void this acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. (1,11(0 Date: (%1 By: \A"\ --\J S (T FILE ACCEPTED IV ,::,,;•,:i::.,::,'3 tURVEYIIIO Ali I ATiNtl C;%r7I1',..:3 s,'% C1I.E, WAS I6IfIi,Tt mai �s of this BtJ7C8J for C°.3.. -- • 4 g. 3 er addlions as recom'T7eri' n , .. 1 i;7npraVCd rtes. pterca apr3+es to ,;. a and occupancy shown thereon. Fw,:s'jetl ;;::;,.,.; t:: - .1 t:.< brat acceptance. b the ti r,{,,,:. -,:.., '•; , r ,t";�lS97t!3 re9atb exCYU.,NC4y�ned u ��+ , `r -� J ,:rLs incutacc© Paten as d©term: .. _ i z: t ctt d:cd with an:1 2pr' c:i . 4411 S RYAN WY 99—S-196 ., 5005 3RD AVE SOUTH SEATTLE,WA. 98134 (206) 762-3311 1419 N.E. LOMBARD PLACE PORTLAND,OR. 97211 (503) 285-6383 RAISBECK ENG. 4411 S. RYAN WAY SEATTLE, WA. 98178 06-02-99 ISSUED FOR PERMIT NO. DATE DESCRIPTION REVISIONS: McKINSTRY DIVISION: FIRE PROTECTION DESIGNED BY: TE DRAWN BY: TE CHECKED BY: PROJECT NUMBER: 4614 DATE: 06-01-99 SCALE: 1"=20' PROJECT TITLE: RAISBECK. ENGINEERING SHEET TITLE:" FIRE SPRINKLER SITE PLAN SHEET NUMBER: 06-02-99 FP1T tiE JUN 14 1999 0--114--0--112--0— nsmomon SYSTEM RISER W „tr I 18� —0— —1112 — —0— v) 2 112 2 — —0— — — - SUPPLY TO SPRINKLERS AT ROOF co 112 --0- 112 —0- - —0 AREA OF WORK 1112 — —0— — 112 — —Q-- — 114 — —0 CUT IN 4" TEE 111 \ K2 O 12-0 12-0 8-0 4-0 Ela r— —� '11 1 1 12-0 j 12-0 i r I s a4 0_16 L 0-6 E>ie \ 112 \ 2 7-6 4-0 12-0 12-0 112 8-0 z 112 ' 12-0 112 \ .11e2 (11 3-6 12-0 112 0-6 4-0 DRAIN 12-0 112 12-0 120 114 12-0 114 0 12-0 114 1 0-6 12-0 4 • jimmies= 0- 114 --0- - 112 — —V- 112 -1/2 — —0— — 112 REPLACE 4" 90 WITH TEE 12-0 12-0 3-5 12-0 12-0 3-5 p1 4 rrir�r 1r�r i J 12-0 12-0 3-5 0-6 12-0 i Ih sI 0-6 12-0 112 12-0 112 1.7 0o 1 Imo, 0-6 t tot 12-0 3-5 AREA OF WORK : I ' i I' i I rr� 'A H ;a i FIRST FLOOR FIRE SPRINKLER PLAN SCALE: 1/8" = 1'-0" Ci' Ch 1 r' iI C; i' JI EXISTING UPRIGHT COVERAGE TO REMAIN THI SPA(E IS FILLEE4WITH INSULTION t 112_ I EXISTING 8" MAIN NEW OFFICE 4" a= L 11 2 1t, NEW REC. PENDENT SPRINKLER TYP. L-1 16" TJI 16" O.C. TYPICAL 4" La 114" EXIST HALL x 1 1 DRIAN SIDEWALL SPRINKLER NEW UPRIGHT COVERAGE • NEW 4" CROSS MAIN STORAGE AREA BUILDING ADDITION SECTION EXISTING 4" MAIN SCALE: 1/4" = 1'-0" i i AREA OF WORK er...: t: ' '� l HEAD LEGEND ACCEPTED BY *, ;1 SURVEYING AND ST TILE, WASIIII ,TO I ,'rarnmts c9 this Bureau for c'assilicc n :::tc'h. _ 1cs or add tions as recornrne; ' d ' I ;ult in improved rates. Acceptance app ies fu p'. ._.r,,rfen and occupancy shown thermal. F1.,1 r d 1; .. • .1 tir?at acceptance. c-t11.ilben1.5 relate exclusively to the re!altio -`'";• •-..:s irlcura^ce rates as determineds:,'cr :-, dj t:.,, n Cad1°::±h and 2, Dr�li: W .:; SYM CNT NAME METAL TEMP K NPT ORIF MFG. MODEL# ESCUT NOTE 0 N/A UPRIGHT BRASS 165 5.60 1/2" 1/2 GEM F-950 EXPOSED EXISTING ® N/A PENDENT CHROME 165 5.60 1/2" 1/2 GEM F-950 RECESSED EXISTING O 36 UPRIGHT BRASS 165 5.60 1/2" 1/2 GEM F-950 EXPOSED NEW 0 PENDENT CHROME 165 5.60 1/2" 1/2 GEM F-950 RECESSED NEW 5005 3RD AVE SOUTH SEATTLE,WA. 98134 (206) 762-3311 1419 N.E. LOMBARD PLACE PORTLAND,OR. 97211 (503) 285-6383 PROEM RAISBECK ENG. 4411 S. RYAN WAY SEATTLE, WA. 98178 06-02-99 ISSUED FOR PERMIT NO. DATE DESCRIPTION REVISIONS: McKINSTRY DIVISION: FIRE PROTECTION DESIGNED BY: TE DRAWN BY: TE CHECKED BY: PROJECT NUMBER: 4614 DATE: 06-01-99 SCALE: 1 /8" _ 1,-0,1 PROJECT TITLE: qW s Xrt RAISBECK ENGINEERING SHEET TITLE: ff - 5-40 FIRST FLOOR FIRE SPRINKLER PLAN SHEET NUMBER: FP1.1 06-02-99 0 01 0 I. 9 01 Rr-7-1 SYSTEM RI L. 111111111110111.1 1•111111111111M1 ji et) to hi •0 1 0 0 6 1_6 • 4 ' M.T. fi =*-I TEEL! ' CUTIN • • I 1-1-7' M.T. rw TEEII rW CU CUT I N I 0 M.T. TEE 8— — B AREA OF • I • RELOCATED ,MEAD 1. • 0 •/- 0 0 01 e4m"' M.T. 3-0 6 - I MT. 0 M.T. 3-0 M.T. -6 3-0 M.T. st— 7-1 CUTIN 1-0 , T. TEE M. M.T. 1-0 L.T M.T. CUT TEE 1-0 M•T• UPRIGHT TO s. EMAIN 04- M.T. M, T I I, I I I CUT IN M. T. 1TEE -.0 wl - M I= I 711 m.T. 1-0 UPRIGHT TO EMAIN V •11 -‘ I 1 :175 a M.T. Th M.T. L `1 - 1-0 AREA. OF .0I< • / 0 0 0 0 SECOND FLOOR FIRE SPRINKLER PLAN SCALE: 1/8" ACCEPTED BY SURVEYING AND NOM SEMI!. WASHiNaix'si • or additions as rcomm.t.ndd,:!! 2;1:1 occupancy shown thereon. Finished • ccrortnts relate exclusively to the relative ef:t in:urance rates as determined under c..r d '.9 hccn Clod v!.'ith and acprmied •.:'' hz.3 HEAD LEGEND SYM CNT NAME METAL TEMP K NPT ORIF MFG. MODEL# ESCUT NOTE 0 N/A UPRIGHT BRASS 165 5.60 1/2" 1/2 GEM F-950 EXPOSED EXISTING 0 N/A PENDENT CHROME 165 5.60 1/2" 1/2 GEM F-950 RECESSED EXISTING 0 0 UPRIGHT BRASS 165 5.60 1/2" 1/2 GEM F-950 EXPOSED NEW 0 43 PENDENT CHROME 165 5.60 1/2" 1/2 GEM F-950 RECESSED NEW •• 5005 3RD ME SOUTH SEAME,WA. 98134 (206) 762-3311 1419 N.E. LOMBARD PLACE PORTLAND,OR. 97211 (503) 285-6383 PROJECT: RAISBECK ENG. 4411 S. RYAN WAY SEATTLE, WA. 98178 06-02-99 ISSUED FOR PERMIT NO. DATE DESCRIPTION REMSIONS: McKINSTRY DIMSION: FIRE PROTECTION DESIGNED BY: TE DRAWN BY: TE CHECKED BY: PROJECT NUMBER: 4614 DATE: 06-01-99 SCALE 1/8" = 1'4" PROJECT TITLE: KA 6(„,,cu)7 RAISBECK ENGINEERING 99- 5—(PQ SHEET TITLE: SECOND FLOOR FIRE SPRINKLER PLAN SHEET NUMBER: • 06-02-99 FP1.2 E 0 i RM, • • 0 • 0 • C/r/C/GC RELOCATE 30,} a". • 8-6 (2A° P� / HANCaIG& "C": 112"siw<rGLIr TU UNDERSIDE L 1- TSI. ser -IA I. WITH CZ)'It:ix I12' LAG SCREW TYPIC.A 4) 0 I II _. r— k1 to C LLT OACI< Ex ISTI NCI HP (I Ids AND KA ISE LINE5 TO x.141140J TYPICAIL ALLLINES 7$' SITE PLAN NTS }7' SCOPE OF WORK SMITH FIRE SYSTEMS WILL EXTEND THE EXISTING SPRINKLER SYSTEM TO COVER BELOW THE NEW MEZZANINE. SFS WILL ALSO RAISE THE EXISTING PIPING ABOVE THE NEW DROP CEILING AND INSTALL NEW PENDENT SPRINKLERS TO COVER THE AREA BELOW THE DROP CEILING. SFS WILL START AT THE EXISTING OVERHEAD PIPING AS SHOWN ON THE PLANS IN DASHED LINES. DESIGN CRITERIA DESIGN PER NFPA *13 - 1994: OFFICES (ABOVE MEZZ.) ORDINARY HAZARD GP II .20 GPM OVER 1,500 SQ. FT. MISC. STORAGE (BELOW MEZZ.) ORDINARY HAZARD GP II .20 GPM OVER 1,500 SQ. FT. CLARIFICATION ALL AREAS PROTECTED BY WET PIPE SPRINKLER EQUIPMENT MUST BE PROTECTED BY OTHERS TO A MINIMUM OF 40° F EXCLUSIONS * PAINTING AND LABELING OF SPRINKLER PIPE AND/OR EQUIPMENT * ELECTRICAL WIRING OF ANY KIND * CENTRAL STATION MONITORING SERVICE, WIRING, AND EQUIPMENT * CENTERING OF PENDENT SPRINKLER HEADS IN THE CEILING TILE (p ao Ps) 8-0 112" II 6—o 112„ 7-71- // --f 7..........., ,..... 6-o -1 /0-0 (o Rov3) u 0 ' I II_.��.I.. //2 Illy �tI I r� / ""— /1. -D "—/1 -'O ORD AO � T 11 4pP yo ELz.S ),(3'-3" c-- /0-0 CDR oPs Yle 1z" CL -a PL -/3/1 S -c 4Z- //4-' i 200 /' 01 .Civ �• /O -0 --"+ .919 D 6, CO3<° PSS f/,' u , -. —O 2i /12- - '2.-- —40-0 -- 10-0 (ORo.'4 ) ', t—/V-0' "ti' (p,zo P43 w? 8oJ �ocnre—? I 11 I) Sr 9. CULT aAci< Irx1 st 1616 Stud- ULPs. DEFLECTOR AT NAA 4,1130_t.zYP(?) 'IL 'S L Exr N/?5 (-7 Gam.. SPS v N 11 2,4 =r (p .f 00 .Q Co N. I ,u !08 43 EL. 06-i NEG✓ /VEZZ N/NE- 12 \ 4e. 0 02R/n/ VA �cLow SCf t E '/:': /:0-• H I, G �v 1. JP's 1 -Io (G4 P / SX/5T/NG 7-i4 /2 AUXILIARY REMOTE AREA # I DESIGN DENSITY: .20 GPM OVER I, SOO SQ. FT. BASE OF RISER DEMAND: 840.9 GPM AT 43.5 PSI (INCLUDES 0 . GPM FOR INSIDE HOSE) G dP /N /Z. s. / , c/'. TL-E"r j=O/Z /LIE- 1,u //E CcS$EZ /i!.) s 4 3--0 EXIST IftG RISER P LAj e 3-0 i 4 SIIKruNEDY 0. .;.4 cam' TO F b.c. Cl_emmYAZ p II c -IN— -, a ?— *—DO ,:s VI K11\1(3 A- hCV( '. > -- 8" KENNkDY 0. S. 1 Y. EXISTI N6 RISER ELEVATION .141.11::21.1 HYDRAULICALLY MOST REMOTE AREA DESIGN DENSITY: . 2 o GPM OVER 1,5'00 SQ. FT. SASE OF RISER DEMAND: 478.9 GPM AT 78.5 PSI (INCLUDES 0 GPM FOR INSIDE HOSE) HANGER LEGEND SPRINKLER LEGEND ABBREVIATIONS SYMBOL LEGEND REVISIONS 1'a" SHURr CLIv/,// its) 'loll x 11211 LAG SCREWS SYM MANUFACTURER TYPE MODEL FINISHIN ESCUTCHEON FINISH ORIFICE SIZE THREAD TEMP SIZE RATING QUANTITY 13 3e" COACH SCREW ROD /A DITIONAL T L'I x!a'Ix I S 1211 H EADI_Ik , US F (4) I(42) NAILS W/ 34' 5IDL BEAM l RACKET, '2"x 2'z" &..)Lr 0 IlELI AI3LE SSP- II( G C.N R CHR 1411 I w/ 12i' NtAT I WASHER RELIABLE �Su L3RZ. (,I I (U'j'-' 2I 38" BEAM CI AMID W/ RETAIWFI` STRAP Ex IsTING SPR INKLER I_X ST 1 IJC IGEN DINT' 1 OCA TtOW RELIA3L E ssa FI 13R 15co TOTAL THIS SHEET 41 AFF BOB BOO BOJ BOP BOT CTS FO IFOW OFOW NAS UNO ABOVE FINISHED FLOOR BOTTOM OF BEAM BOTTOM OF DECK BOTTOM OF JOIST BOTTOM OF PURLIN BOTTOM OF TRUSS CUT OF SUIT FIELD ORDER INSIDE FACE OF WALL OUTSIDE FACE OF WALL NO AUTO SPRINKLERS UNLESS NOTED OTHERWISE CENTERLINE OF PIPE TO REFERENCED STRUCTURE IN INCHES 2 -WAY EARTHQUAKE SWAY BRACE 4 -WAY EARTHQUAKE SWAY BRACE HANGER LOCATION ELEVATION ABOVE REFERENCED POINT IN FEET AND INCHES HYDRAULIC CALCULATION NODE NO. DATE BY REASON FOR REVISION APPROVALS REQUIRED Tt&KWI LA OWNER J IQ° / Q 5k d 5 T,;,s •7—, r'f'I.. z, i2c. Z Z FILE th.ut Comments A doted In Red er The Attached Letter I ave been reviewed _) Ly tl-ih. :..'. Tli.�<wiii:! Mfr: ureaufor cenfer , zc.. Ydiii.1c...1.0i„.... . Acceptance i-, s!.Uoi. ;t •-.:.. CO. .S, and s which do not auth ri.:e ,. c:':;ir...::i1. .:;, rds and ordinarc:s. The ' ' ' I i `ZIgn-.r ts toti../ Jfi%n cne C Iii I'( Additi ns, deletions or revisions to .l e de c ,iier this d to will void this acceptance and vvlii require a resu mittal of revised drawings for subsequent approve Final acceptance is subject to field test and inspection b The T.akwila Fire Prevention Bureau. - Date: .?/ZO( B;.1..) 5(0 FITTER NOTES * PHASE ONE INCLUDES RAISING THE UPSTAIRS PIPE TO 2-1/4” BOD * PHASE TWO INCLUDES THE NEW PIPING BELOW THE MEZZANINE * PHASE THREE INCLUDES THE NEW PENDENT SPRINKLERS BELOW THE NEW DROP CEILING ABOVE THE MEZZANINE. * HANG NEW "BLUE" MAIN AT 12" BOJ, TIGHT TO BOTTOM OF BEAMS * HANG NEW BRANCHLINES AT 6" BOJ. TUKWILA FIRE DEPARTMENT, Please call: 575.4407 and give this job No. 11-1 S 04-� and exact address for shuts down or restoration approval ICONTRACT WITH EDIFICE 300 - 19th AVENUE SEATTLE, WA 98122-5736 PROJECT MANAGER: PHONE: SITE SUPERINTENDENT: 4411 S RYAN WY 97-S-043 la@gwP_Q,N Al FEB 191997 WWWWWWW CHRIS BOWES (206) 328-2700 LOU BODMAN SMITH FIRE SYSTEMS, INC. 1106 54th Ave. E. Tacoma, WA 98424 CONTR. REG. NO. SMITHFS1360T Ph: (206) 926-1880 Fax: (206) 926-2350 PROJECT RAISBECK ENGINEERING 4411 SOUTH RYAN WAY TUKWILA, WASHINGTON DESIGNER DATE SHEET JOB 4G6- cA