HomeMy WebLinkAboutPP - 16839 SOUTHCENTER PKWY - LAMPS PLUS INC - PERMITS AND PLANS16839 SOUTHCENTER PKWY ASSOCIATED PERMITS 10-F-102 06-S-009 97-S-109 Southcenter Retail II Lamps Plus (tenant) 16831-16875 Southcenter parkway Tukwila, WA 98168 SCOPE OF WORK 1. Connections of two HVAC smoke detectors in the Lamps Plus space to the existing fire control panel. The two new HVAC units will have their own zones for reporting The building is fully sprinlded. Washington Alarm will provide the following: Runner service, annual inspections, maintenance and monitoring Ryan Aal Washington Alarm, Inc. Customer Service Rep. 206-328-3288 206-391-2029 cell raal(a),washingtonalam ,com - IA%) µv? C -D L - E^01. t:4. 1; .t rc.S, 4iv r" FILE PAID JUN - 3 2010 TUKWILA FIRE iA EOL ' CONFIDENTIAL A FIRE ALARM SYSTEMS BATTERY CALCULATION CHART C Form: 1/22/01 - v c r V WAS N TONA ARM DEVICE/ MODULE MODEL NUMBER QUANTITY OF DEVICE/ MODULE STANDBY CURRENT (AMPS) TOTAL STANDBY CURRENT (CXD1 ALARM CURRENT (AMPS) Radionics/Bosch Fire Panel Cell+hnen.er 11/ 1 ..w..... EtI..- T1 1 0.15 CONTROL PANEL AND MODULES 2 0 0 Radionics/Bosch Fire Panel 8112 1 0.15 0.15 0.25 0.25 Supervision module D125 1 0.022 0.022 0.15 0.15 0 0 Battery 12 VOLTS NP7-12 2 0 0 0 0 0 0 0 0 0 0 0 0 INITIATING DEVICES Waterflow 2 0 0 Sprinkler tamper switches 6 0 0 HVAC Smoke detectors 2 0 0 0 0 0 0 0 0 0 0 NOTIFICATION APPLIANCES 0 0 0 0 Sum Column For Standby Load (Amps) Multiply By Required Standby Time (24 or 60 Hours) Total Standby AH 0.172 24 4.128 (G) Sum Column For Alarm Load (Amps) Multiply By Required Alarm Time (5 min = .083) Total Alarm AH 0 0 0 0 0.400 0.083 0.033 TOTAL TOTAL REQUIRED SAFETY TOTAL TOTAL STANDBY ALARM AH AH (G+H) FACTOR SYSTEM SYSTEM AH (G) (H) (Multiply) AMPERE- AMPERE - HOURS HOURS REQUIRED PROVIDED 4.128 0.0332 1 4.161 1.3 5.410 24AH (H) A R A D I 0 N came Package alarm D8112F Fire Control g Data Sheet UL Listings • NFPA 71 Central Station Signaling Systems • NFPA 72A Local Protective Signaling Systems • NFPA 74 Household Fire Warning Equipment Approvals • Factory Mutual • California State Fire Marshal • New York City Board of Standards and Appeals Standard Features • Eight programmable zones • 12 VDC, 2 Amp Alarm Power with three separate outputs •0 VDC, 1 AMP auxiliary power with two separate outputs • Built-in digital communicator with telephone line monitor Dual telephone line operation Real time clock and test timer • Battery charging circuit • Battery voltage supervision • Automatic reset circuit breakers • Dual battery operation • Onboard warning buzzer and diagnostic LEDs • Automatic answer modem • Remote diagnostics and programming • Lightning and RFI protection • Power limited external circuits • 16 ga. metal enclosure .. • Programmable Features • Central Station reporting format • Two telephone numbers • utomatic test reports • dividual zone responses • Custom annunciator text • Programmable bell time • Audible alarm output, steady or pulsed • Automatic silencing I E-8112-024-01 S nOMEGALARM 08112 138112F Package Includes: (1) D8112E1 Control/Communicator (1) D8109 Fire Enclosure (1) D122 Dual Battery Harness (1) D125 Powered Loop Interface (1) D128 Dual Phone Line Switcher (1) D1640 Transformer (2) D161 Phone Cords Description The D8112F Fire Control Package is designed to meet the requirements of the growing Central Station Fire Alarm market, specifically, NFPA 71 applications. This package is well- suited for NFPA 71 applications from simple single -riser systems, to more advanced eight -zone automatic fire alarm systems. The D8112F system can meet the requirements of NFPA 72A Local Protective Signaling Systems by adding the following equipment: D192 Bell Circuit Supervision Module, D1252 Alpha II Command /s 4..r 1:..4...1 • .Jli • Control/Communicator: The D8112 Control/Communicator is an eight zone microprocessor based control panel with an integral digital communicator. Through program- ming and accessory modules, the D8112 offers a degree of flexibility rarely found in other fire alarm control systems. The D8112 is U.L. listed as power limited, therefore (per Article 760 of the National Electrical Code) U.L. listed fire cable can be used for ext- ernal circuits, rather than. expensive conduit. This feature alone can effect substantial installation cost savings. All eight zones are individually programmable and may be used to monitor all types of fire alarm, sprinkler supervision, fixed extin- guishing systems, industrial process supervision, and burglar alarm devices. C O Without Comments IT As Noted in Red O Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformarce with current City standards. Acceptanc;c IS E'. o ect co errors and omissions which do no. r "ir ze v'oLLdons of adopted standards and ordinance., r ,e responsibility for the adequacy of design rest ,oti. ,}y. pith the designer. Additions, deletion3 or ravis°ons to these drawingsafter this date will vold this accepcanc. aid will require °a resubmittal of revised drawint» ler subsequent approval. Final acceptance is subject to field test and Inspection by The Tukwila Fire Prevention Bureau. Date: (p — 7 _/v By: 4-V i NOTICE A completed, signed, Tukwila Fire Department Pre-test Certificate must be presented to the Inspector prior to commencement of Acceptance Testing of any Fire Alarm and Detection Systems. Failure of test will result in a Re -inspection Fee and tArmination of the testing. Rc•,. c. 4:7.0 's r eV/iv-420k Cro r 4.0.1.4, t e• 1-, ►,5 01,4.+ 0t 4e 3rJ tWtwitA FIRE DEPARTi i! Please cath- 075-4440 ana give this Job No. _; j` ` / O �" and enact address for she* down or restoration approve!. 7 (oz \ Se " ANJE, N ,E . *A -los V<.r, tp t-P\oN c , \at "1 & 2• z �No EacaSTr -Z1-97 ✓ .E.�vL1SE_ i<ePr= t172.16.341- vA,Ta a; t1P. z: N E\,4 Vii4No1..1 sE OF -e --le Yhi" N F 151-o" IMPS._ 16;839 1u'ilaC �rt� EiC P�Gv+i`I. 'r, Tu.v4w11_./4, WA g81SS Zos ‘11-11-5-& '� TUKWILA FIRE DEP aC"Fct, ��ose call: 575.440 and give this job No. f 7 S /b1 and exact address for sf i down or restoration approves C C1171) 1 jlt / Without Comments 0 As Noted to Red 0 Per The Attached Letter y These plans have been reviewed by The Tukwila Fire Prevention Bureau for conformance with current city : standards. Acceptance is subject to errors and omissions which do riot authorize violations of adopted standards and ordinances. The responsibility for the r adequacy of design rests totally with tie designer. Additions, deletions or revisions to these drawings after this date will void this acceptance and will require a V. resubmittal of revised drawings for subsequent approval. ,i Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention % . -au. Date: `i z�q7 By: C:\Lam 1:24 9FT x 13FT CEILIN G CLOUD LIGHT HOUSE Q\Q�G CONCEALED HEAD AT CEILING CLOUD co\ -4 RECESSED SPRI+IKLER AT UGHT HODS_ 1' - LIGHT HOUSE PLAN EXIST. BRA 1/2'=l' -O' 6'-0" North 3'-0" 2"0 PENETRATION (1" CLEARANCE AROUND PIPING) ADD 1" TEE TO 1" EXIST. DROP VIKING FLEXIBLE CONNECTION RECESSED SPRINKLER CONCEALED SPRINKLER 9FT x 13FT CEILING CLOUD 7 LIGHT HOUSE 1 s Plus\FP-1.dwg, 1/13/2006 8:30:04 AM, HP Designiet 700 (E_A0) by HP.pc3, CH LINE ® SQ 1� EXIST. BRANCH LINE ADD NEW UPRIGHT SPRINKLER TO EXIST. 1" OUTLET 0 EXIST. UPRIGHT SPRINKLER ATTIC PLAN 1/2'=1i—oa SPRIG -UPS CHART A 1 X 2-0 w/ 1 X RED COUP 1 North CAS SECTION 0 CCE T Without Comments As Noted In Red Per The Attached Letter These plans have been reviewed by The Tukwila Fire Prevention Bureau for :snfermance with current city standards. Acceptance is subject to errors and omissions which do not authorize violations of adopted standards and ordinances. The responsibility for the adequacy of design rests totally with the designer. Additions, deletions or revisions t'o these drawings after this date will void this,acceptance and will require a resubmittal of revised drawings for subsequent approval. Final acceptance is subject to field test and inspection by The Tukwila Fire Prevention Bureau. Date: /-17 - OSo By: i TUKVVILA FIRE DEPARTMF.[i Please call: 575.4407 end give this job No. O(0,0`069 and exact address for shut. own or restoration approvals NOTE: 1. SCOPE OF WORK: PROVIDE FIRE SPRINKLER COVERAGE TO FOLLOWING AREA (1) FLEX. CONNECTED SPRINKLER TO CEILING CLOUD. (1) RECESSED SPRINKLER TO LIGHT HOUSE. (1) UPRIGHT SPRINKLER IN ATTIC SPACE. 2. DESIGN CRITERIA; NEW SPRINKLERS EXTENDED FROM EXISTING 1" OUTLET. 3. PIPING TO BE SCHEDULE 40 BLACK STEEL PIPE. 4. FITTING TO BE 125# BLACK CAST IRON. REVISIONS SPRINKLER SYMBOL DESCRIPTION Symbol Type Material Make Model Response S.I.N. Temp. K -Factor N.P.T. Orifice Total APPROVING AGENCIES 0 UPRIGHT RECESSED CONCEALED BRASS CHROME CHROME VIKING VIKING VIKING M 131 Fast Fast Fast VK300 VK302 VK404 155,0 155.0 165.0 TOTAL SPRINKLERS SHOWN ON THIS SHEET 5.6 5.6 5.6 TOTAL SPRINKLERS REQUIRED ON THIS CONTRACT 1/2 1/2 1/2 1/2 1/2 1/2 1 1 1 3 0 BOISE SPOKANE LONGVIEW (KIN& FIRE PROTECTION CONTRACTOR'S LICENSE WA. VI—KI—NA—S373 NT AK. AA 1918 MONT. 6476A VIKING AUTOMATIC SPRINKLER COMPANY 3434 FIRST AVENUE SOUTH (206) 622-4656 SEATTLE, WA. 98134 FAX: (206) 622-9319 PORTLAND MEDFORD PROJECT LAMPS PLUS 16839 SOUTHCENTER PARKWAY TUKWILA, WA 98188 JAN 18 2006 Tukwila Fire t2.387 - Date: 01/13/2006 Scale: 1/2" = 1' Job No. WST— Drawn By: LUCIA FUNG Sheet No. FP -1